X-RAY GENERATOR HF1 G/26 - starunited.com.cn · Technical data sheet HF1 G/26 IMD Generators Srl...
Transcript of X-RAY GENERATOR HF1 G/26 - starunited.com.cn · Technical data sheet HF1 G/26 IMD Generators Srl...
Technical data sheet
HF1 G/26
Doc.008984 Data 11/11/2014
Pagina 1 di 14
HV MAX VOLTAGE OUTPUT: 49 kV
HV RIPPLE FREQUENCY: 40 kHz
POWER OUTPUT: 8 kW
X-RAY GENERATOR HF1 G/26
MODEL: HF1 G/26 CLASS: I B (IEC60601-1)
CODE: XRG.14.C19.001 S/N:
Viale Matteotti, 28/A 24050 Grassobbio BERGAMO ITALY
+39 035-52.63.44 FAX +39 035-52.60.86
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 2 di 14
Index of contents
1 General description .......................................................................................... 3 2 Classification ................................................................................................... 3 3 Technical characteristics ................................................................................... 4
3.1 High voltage output connectors ..................................................................... 4 3.2 Generator electric characteristics ................................................................... 4 3.3 H.V. transformer power supply ...................................................................... 4 3.4 Filament power supply .................................................................................. 4 3.5 Output signals ............................................................................................. 5 3.6 Thermal characteristics ................................................................................. 5 3.7 Mechanical characteristics ............................................................................. 5 3.8 Conditions of use ......................................................................................... 6 3.9 Electromagnetic compatibility (EMC) .............................................................. 6 3.10 Electric diagrams .................................................................................. 7 3.11 PSM06/2M Interface board ..................................................................... 8
4 Labelling ......................................................................................................... 9 5 Symbols ....................................................................................................... 10 6 Installation ................................................................................................... 10
6.1 Unpacking ................................................................................................. 10 6.2 Mechanical interface ................................................................................... 10 6.3 Housing .................................................................................................... 10 6.4 Electrical installation .................................................................................. 11
6.4.1 Power connection ............................................................................... 11 6.4.2 Connection for filaments power supply .................................................. 11 6.4.3 Protective earth connection ................................................................. 11
7 Maintenance ................................................................................................. 12 7.1 Checks and inspections ............................................................................... 12 7.2 Cleaning and disinfection ............................................................................ 12
8 Risks ............................................................................................................ 13 8.1 Generator hazards ..................................................................................... 13
9 Disposal of the device .................................................................................... 13 10 Declaration of responsibility ............................................................................ 14
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 3 di 14
1 General description
The HF1 G/26 generator is a medical device which has been developed to power supply X-
ray tubes for radiography and fluoroscopy application, designed and manufactured with the
aim of achieving a major quality in radiation field.
The 40kHz H.V. output rectified frequency guarantees a very low ripple and improves the
H.V. rise time applied to radiogenic insert.
In order to power supply the X-ray tube this generator has to be properly connected to a
high frequency inverter. In this document suitable inverter models are mentioned.
The original release of this manual is in Italian language. For further information, please
refer to Italian version.
WARNING: No modification of this equipment is allowed.
2 Classification
CLASSIFICATION EN 60601-1
Type of protection against short circuits Class I
Operational mode Continuous operation with
intermittent loading
Unit not to be used in the presence of an inflammable anaesthetic mixture with air
or nitrous oxide
CLASSIFICATION 93/42/EEC DIRECTIVE
In accordance with Annex IX of 93/42/EEC
directive Class II b
The HF1 G/26 generator is classified as a Class IIb medical device, as determined by
93/42/EEC Annex IX Rule 10:
“Active devices intended to emit ionizing radiation and intended for diagnostic
and therapeutic interventional radiology including devices which
control or monitor such devices, or which directly influence their
performance, are in Class IIb.”
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 4 di 14
3 Technical characteristics
3.1 High voltage output connector
Compatible to Claymount CA-3 type receptacle (complying to NEMA XR-7).
3.2 Generator electric characteristics
H.V. output rectified ripple frequency
40 kHz
Nominal power
8 kW
(40 kV 200mA)
0,1 sec
Maximum voltage to X-ray tube 49 kVDC
Anode to Ground 49 kVDC
Maximum current in X-ray tube (radiography) Please refer to the X-ray tube load charts
200 mA
Voltage ripple at maximum power < 1 %
Rise time at the maximum power < 1 ms
Type of power supply See chap. 3.3
3.3 H.V. transformer power supply
Supply the H.V. transformer in compliance with the reported characteristics, by using IMD
Generators HF1 CAN M8/39, HF1 M8 CMF or IMD Generators equivalent one.
Screw
terminals Input characteristics Radiography / Fluoroscopy
A, B
Type of power supply ~ Single phase
Operating frequency 20 kHz
Max input voltage 350 Vpk
Max input current 200 Apk
3.4 Filament power supply
Filament power supply is not included in this HF1 G/26 generator.
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 5 di 14
3.5 Output signals
For Output signals please see chapt. 3.11
3.6 Thermal characteristics
Thermal safety
Cut-off temperature 60°C ± 5 °C
Type of contact Normally closed
Rubber bellow expansion volume 0.12 dm3
3.7 Mechanical characteristics
Aluminum case structure
Dimensions (see figure)
Weight (approx.): 10.5 kg
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 6 di 14
3.8 Conditions of use
Transport and storage conditions
Range of temperature 0° – 50° C
Relative humidity 20 – 90 %
Atmospheric pressure 700 – 1060 hPa
Working conditions
Range of temperature 10° – 40° C
Relative humidity 30 – 75 %
Atmospheric pressure 700 – 1060 hPa
3.9 Electromagnetic compatibility (EMC)
This apparatus is in compliance with the standard IEC 60601-1-2 that defines the max.
allowed emission levels from electronic devices and required immunity from interference
caused by externally generated electromagnetic fields.
It is not, however, possible to exclude radio signals coming from transmitters such as
mobile phones or similar mobile radio devices. These and other transmitting devices,
including those in compliance with EMC standards, may influence the proper functioning of
medical apparatus when used in proximity and with a relatively high transmitting power.
Therefore, the use of radio equipment in proximity to electronically controlled system must
be avoided in order to eliminate any interference risk.
Any transmissions by mobile radio equipment must be avoided.
Mobile phones must be switched off in zones close to the unit.
These rules must be applied when the unit is switched on (that
means connected to the mains and ready to use).
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 7 di 14
3.10 Electric diagrams
Here below it is possible to see how to connect the HF1 G/26 generator to the HF1CAN M8/39 inverter through
the PSM06/2M interface board:
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 8 di 14
3.11 PSM06/2M Interface board
Interface board layout
Signal Pinout Characteristics
kV+ CP1: 1 Scale factor 1V = 10 kV
Analog signal 0 ÷ 4.9 VDC
mA+, mA- CP1: 5, 4 Current signal
Analog mA Type of signal
THERMIC
SWITCH CP2: 1, 2
Thermal safety switch Normally closed switch
Logic signal
GND CP1: 2 Signal GND
A / B / GND Screws Power connectors
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 9 di 14
4 Labelling
PICTURE 1: Label placed on the generator
PICTURE 2: Label position on the generator
Label position
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 10 di 14
5 Symbols
The symbols that have been used are illustrated below:
Symbol Meaning Position
Caution: see the attached documentation Unit label
Equipment that requires a correct disposal
(2002/96/EC) Unit label
Manufacturer Unit label
Protective earth Unit
~ Alternate current Technical data sheet
6 Installation
To install the device in a radiological system, look over the information reported below.
ATTENTION –Everybody who uses or connects the equipment to a X-ray
tube configures a medical system, and is therefore responsible that the
system complies with the requirements of the system standard IEC
60601-1-3 and IEC 60601-2-54.
Be sure to proper connect and manage the thermal safety switch of the generator
in order to avoid dangerous overheating and/or mechanical damages to the case
structure.
6.1 Unpacking
ATTENTION – Unpack with caution to avoid mechanical damages of the
chassis and the electronic board.
6.2 Mechanical interface
Install the generator through the six anchorages Ø5.5mm visible in the drawing at the
chapter 3.7.
6.3 Housing
CAUTION – It is recommended to install the generator totally housed in a
protection case, avoiding mechanical damages and preventing the direct
contact by the user/patient otherwise customer must guarantee that
temperature of the parts that are likely to be touched doesn’t exceed the
maximum temperature allowable by the table 23 of the IEC 60601-1 third
edition.
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 11 di 14
6.4 Electrical installation
6.4.1 Power connection
For general characteristics check chap. 3.3. The connection through a shielded cable is
suggested as follows:
Connection terminals A / B
Cable 4 x 2,5mm2 shielded
Consisting of single isolated conductors with a
formation of 2 x 2,5mm2 per phase
Maximum length 5,5 m
Nominal insulation 600 VDC
6.4.2 Connection for filaments power supply
Not applicable
6.4.3 Protective earth connection
The connection through an electrical cable is suggested as the follows:
Connection terminal Nominal cross section 1 x 6 mm2
Maximum length 5.5 m
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 12 di 14
7 Maintenance
Generators requires regular checks and maintenance.
Regular inspections and maintenance are aimed to maintain good operation and service
safety serve and to protect the patient and operator from hazards due to any eventual
breakage of mechanical parts.
The maintenance program reported below includes checks to be observed by the
manufacturer of the equipment where generator is installed and must be carried out by
expressly authorised personnel.
CAUTION - IN THE CASE OF REPLACEMENT OF ANY COMPONENT, USE ORIGINAL SPARE
PARTS ONLY.
THIS GENERATOR HAS BEEN DEVELOPED TO POWER SUPPLY X-RAY TUBES. SINCE HIGH
VOLTAGE DISCHARGES IN THE X-RAY TUBES CAN BE FREQUENTLY OBSERVED, IMD
GENERATORS RECOMMENDS TO PROPERLY PERFORM SEASONING OF THE TUBE WHEN IT
IS NEEDED IN ORDER TO AVOID DAMAGES THAT COULD BE CAUSED TO THE GENERATOR
DURING RELEVANT HV DISCHARGES IN THE X-RAY TUBE. (PLEASE OBSERVE X-RAY TUBE
MANUFACTURER SEASONING RECOMMENDATIONS).
7.1 Checks and inspections
Please carry out the periodical checks listed in the following table.
These checks must only be carried out by qualified personnel.
VERIFICA / CHECK
Integrity of the warning and danger labels.
Absence of cracks, clefts, oil spills, corrosions and deformations.
Absence of unusual noise in the generator during X-ray
emission.
Generator mechanical fixing and general state.
Electronic board fixing and general state.
7.2 Cleaning and disinfection
This generator doesn’t need particular operations of cleaning and disinfection; in case of
cleaning of its surfaces or other parts of the equipment in which it is installed, cleaning
products have not to be used if produce explosive, gaseous mixtures. If they are used
make sure that gases are dispersed before switching on the generator.
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 13 di 14
8 Risks
Proper use and safe operating practices with respect to generators are responsibility of
equipment users.
The manufacturer provides information on its products and associated hazards, but it
assumes no responsibility for after-sale operating and safety practices.
Appropriate safe operating practices should be employed.
All persons who work with X-ray tube head or equipment which utilizes such devices must
take precautions to protect themselves against radiation exposure and possible serious
bodily injury.
Do not operate this generator except in accordance with information included in: this
Technical Data Sheet, these precautions and any additional information provided by the X-
ray tube manufacturer and/or competent safety authorities.
8.1 Generator hazards
HIGH VOLTAGE
All generators for X-Ray tubes operate at voltages high enough to kill through electrical
shock. Equipment designed should prevent personnel contact with high voltages. When
direct access to the generator or X-ray tube is required, the primary circuits should be
disconnected.
HOT OIL
Relevant heat occurs in the generators after prolonged operation. This heat is exchanged
through the dielectric oil to the external generator surfaces and then radiated to the air.
Misuse of the generator can result in a damage of the housing causing hot oil to escape,
potentially resulting in scalds or burns. Take precautions to avoid such damages. Be sure to
be in compliance with the use specifications of the manufacturer and to comply the
installation recommendations.
DON’T USE THE GENERATOR IF H.V.+ IS NOT PROPERLY CONNECTED TO
THE X-RAY TUBE.
9 Disposal of the device
Once the product is at the end of its use it must be disposed following the enforced rules
concerning the separate collection of waste and it cannot be treated as a simple urban
waste.
The symbol means that the product has the requirements requested by new directives
introduced for the environmental protection (2002/95/EC, 2002/96/EC,
2003/108/EC) and it must be disposed properly once its life cycle is ended.
When the device has reached the end of its life it must be disposed at the proper
centres for the separate collection of electrical and electrical wastes, or it must
be returned to the reseller or to the manufacturer in case you want to replace
the product with another equivalent new one.
The proper separate collection helps to avoid possible negative effect on the environment
and on health and it facilitates the second use and the re-cycle of materials of which the
device is composed of. Ask for further information to the local authorities about the areas
dedicated to the wastes disposal.
Who does not dispose the product following here above mentioned, will be responsible in
front of the enforced rules.
Technical data sheet
HF1 G/26
IMD Generators Srl Doc.008984 Data 11/11/2014
Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 14 di 14
10 Declaration of responsibility
IMD Generators is only responsible for the safety of its products when their repair
and/or modification has been carried out by IMD Generators or by personnel
expressly authorised by IMD Generators itself.
IMD Generators shall not be held responsible in any way for malfunction, damage
and/or danger due to incorrect use of the system or to disregard of the maintenance
Regulations.
The manufacturer of the equipment where the device is installed should take care of
proper device use by trained and qualified operators.
All the technical in formations and those relevant for the compliance may be required to
the manufacturer (93/42/EEC directive and following amendments):
Viale Matteotti, 28/A 24050 Grassobbio BERGAMO ITALY
+39 035-52.63.44 FAX +39 035-52.60.86
Technical data sheet
Control unit HF1 Mammo 8kW LC
Doc.010575 Data 13/03/2017
Pagina 1 di 19
CONTROL UNIT HF1 Mammo 8kW LC
CODE: IRI.37.208.001 S/N:
Viale Matteotti, 28/A � 24050 Grassobbio � BERGAMO � ITALY
� +39 035-52.63.44 � FAX +39 035-52.60.86
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 2 di 19
Index of contents
1 General description .................................................................................... 3
2 Classification ............................................................................................. 3
3 Technical characteristics ............................................................................. 4
3.1 Electric characteristics and I/O (power) ..................................................... 4
3.2 Input / Output (signals) ............................................................................ 5
3.2.1 Digital protocol of communication and interfacing ................................ 6
3.3 Performances of the control unit .................................................................... 7
3.3.1 Inverter .......................................................................................... 7
3.3.2 Filament ......................................................................................... 7
3.3.3 Stator driver ................................................................................... 7
3.4 S219/M Logic board ................................................................................. 8
3.5 Mechanical characteristics ........................................................................ 11
4 Labelling .................................................................................................. 13
5 Conditions of storage and usage ................................................................. 14
6 Electromagnetic compatibility (EMC) ........................................................... 14
7 Symbols .................................................................................................. 14
8 Installation .............................................................................................. 15
8.1 Unpacking ............................................................................................. 15
8.2 Mechanical installation ............................................................................. 15
8.3 Electrical installation ............................................................................... 16
9 Maintenance ............................................................................................ 17
9.1 Checks and inspections to be carried out by the user .................................. 17
9.2 Cleaning and disinfection ......................................................................... 17
10 Risks ....................................................................................................... 18
10.1 Control unit hazards ............................................................................. 18
11 Disposal of the device .............................................................................. 18
12 Declaration of responsibility ....................................................................... 19
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 3 di 19
1 General description
This HF1 Mammo 8kW control unit is a sophisticated device which features in just one single
product many functions of a mammographic unit such as power inverter, filament board and
rotating board. In order to complete the presentation of this unit it is important to mention
the integrated digital interface standard buses (CAN-BUS and/or RS232 Option) which allow
the final system manufacturer to reduce the integration efforts to implement X-ray
equipment, as a matter of fact, the integrator needs just to communicate to one single logic
board (S219) which is in charge to distribute all the commands to all the power stadiums of
the unit. A simple and easy power interface connectors solution completes the introduction
of this product.
The integrated power inverter converts the direct input current into an alternating current,
in particular this product transforms the DC input into a 20kHz AC output with variable
amplitude depending on the input set values and feedback signals which comes from its
load. The typical load of this apparatus is a high voltage transformer with cascade rectifying
circuitry which power supplies a X-ray tube. Due to this a 40kHz ripple frequency is overlaid
on the high voltage output into the load. The logic board of the unit is in charge to control
in a closed loop the final X-ray tube voltage according to input and feedback signals. It is
also possible to control different X-ray output power and exposure timing.
The integrated filament board is in charge to fire up the filament of the insert in order to
modulate the desired anodic current in the load supervised by the electronic control board
while the stator driver board is involved in the stator power supply to control the speed
rotation of the X—ray insert.
WARNING: Written authorization to IMD Generator S.r.l. is mandatory prior to any
modification for the unit use with function other than the ones foreseen.
2 Classification
CLASSIFICATION EN 60601-1
Type of protection against short circuits Class I
Degree of protection against direct and
indirect contacts Not applicable
Operational mode Continuous operation with
intermittent loading
Unit not to be used in the presence of an inflammable anaesthetic mixture with air
or nitrous oxide
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 4 di 19
3 Technical characteristics
3.1 Electric characteristics and I/O (power)
All the control unit interface connectors are from Molex (except power GND).
In order to connect the unit, following headers are needed:
CP1 = 2ways Minifit SR 42816 series connector
CP2 = 3ways Minifit SR 42816 series connector
CP3 = 8ways (4x2) Minifit Jr 5557 series connector
CP4 = 3ways Microfit 43645 series connector
CP5 = 4ways (2x2) Microfit 43645 series connector
CP6 = 6ways (3x2) Microfit 43020 series connector
GND = M5 brass nut
Terminals Input / Output characteristics
CP1-1,2
Input power supply (Inverter + Filament + Stator power supply)
Single phase
230Vac 50/60Hz
Rated input max power
11kVApk
(max 32Apk) Depending on the exposure
parameters
Max input current protection breakers 32A 400Vac aM 20kA
Recommended thermo-magnetic circuit
breaker
Un = 230Vac 50/60Hz
In = 32A
Number of poles = 2
Protection class = C
as per IEC-EN 60898
GND Screw
GND Connected to the
Control unit chassis
Control unit interface connectors layout
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 5 di 19
Terminals Input / Output characteristics
CP2-1,2 Power output
Single phase
20kHz
(Max 210Vacrms )
CP3,1: (LF)
CP3,2: (SF)
CP3,3: (CM)
CP3,4: GND
Filament power board output:
(LF) = Large Focus
(SF) = Small focus
(CM) = Common
Single phase
16kHz
(Max 5.0Arms)
CP3,5: (P)
CP3,6: (S)
CP3,7: (C)
CP3,8: GND
Stator driver power board output:
(P) = Main phase
(S) = Shifted
(C) = Common
Single phase +
shifted phase
50Hz
(Max 230Vacrms / 7Apk)
3.2 Input / Output (signals)
For connectors positioning and description please observe picture at chapter 3.1
Terminals Signal Block diagram
CP4-1,3
(CP4-2: GND)
INPUT
CAN BUS
CP5-1,2
INPUT
Digital*
Command
X-Ray
CP5-3,4
OUTPUT
Digital*
HV > 85%
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 6 di 19
Terminals Signal Block diagram
CP6-4,5
INPUT
Digital
Thermal
safety switch
This input manages the normally closed contact which
comes from the safety switch in the load.
CP6-1 mA+
CP6-2 mA-
INPUT
Analog
Feedback
Anodic mA
These inputs have to be connected to the load as
indicated in the chapter 8.3
CP6-3
(CP6-6=GND)
INPUT
Analog
Feedback
kV+
These inputs have to be connected to the load as
indicated in the chapter 8.3
*For digital inputs a 12 ÷ 24Vdc is recommended
3.2.1 Digital protocol of communication and interfacing
All the inputs and outputs commands / feedbacks are available by digital I/O communication
(CAN-BUS). For digital communication protocol please refer to the IMD Generators document
number 007078 and/or eventual subsequent modifications and additions (please ask to IMD
Generators for updated documents).
The CAN-BUS is available on the connectors CP4. For hardware interfacing and connectors
pinout please refer to the chapter 3.2 and 8.3 (Electrical installation).
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 7 di 19
3.3 Performances of the control unit All the mentioned performances are related to Imd Generators Mammographic generator HF1 series.
3.3.1 Inverter
Pulsed load output power 8 kW
(200mA @ 40 kV 0,1 sec)
kV Range 22 ÷ 49 kVDC
Max RAD mode load output 200mA @ 40 kV
(0,1 sec)
Max FLUORO pulsed mode load output 200mA @ 40 kV
(25 fps)
Max frame per second rate 30 fps
3.3.2 Filament
Max load output power 65VA
(5A @ 13V)
3.3.3 Stator driver
Steady state nominal power 280 VA
Maximum surge power (launch max 1sec) 1600 VA
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 8 di 19
3.4 S219/1 M Logic board
(the board is completely enclosed into the control unit chassis)
S219/1 logic board layout
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 9 di 19
S219 LED description: Led from DL1 till DL14 are visible through the glass available on the chassis, for its positioning
please see at chapter 3.5
GREEN LED
• DL1 = ON (+24Vdc) when the Control unit is supplied and fuse F1 is OK.
• DL3 = ON (Control unit ready) when the Control unit is ready to receive commands
and no errors are there.
• DL11 = ON (Watch dog OK) when the internal microprocessor is running and the
inverter is ON.
• DL21= ON (Filament ready) when the filament current in the primary side of the
transformer is within factory set limits.
YELLOW LED
• DL8 = ON (X-ray command HW) when the safety hardware command is received
from the logic board.
• DL9 = ON (HV>85%) when the HV output in the load overtakes 85% of set kV that
means exposure has started.
• DL10 = ON (X-ray command SW) when the safety hardware command X-Ray is
received AND the internal firmware enables the X-Ray emission.
• DL12 = ON (PWM Command 1) when PWM command1 is sent to the driver board.
• DL13 = ON (PWM Command 2) when PWM command2 is sent to the driver board.
• DL14 = ON (PWM enable) when the firmware enables the PWM commands to driver
board.
• DL15 = ON (Stator driver run) when the firmware enables the stator driver to run.
• DL16 = ON (Stator driver ready) when the stator driver is ready (stator OK).
• DL17 = ON Not Used
• DL18 = ON Not Used
• DL19 = ON Not Used
• DL22= ON (Filament small focus) when the filament small focus is selected.
• DL23= ON (Hi mA Scale) when the high scale of mA reading is selected.
RED LED
• ALL = ON (Undervoltage Fault) when the S219 logic board power supply is lower
than 18Vdc.
• ALL = Blink (Not Calibrated Board) when the S219 logic board has to be calibrated
(factory procedure).
• DL2= ON (Communication error) when an error in the communication protocol is
detected.
• DL4= ON Not Used
• DL5= ON (kV overvoltage error ) when the kV feedback raises over the 110% of
the kV max value. It preserves load overvoltage condition.
• DL6= ON (kV start error) when the kV feedback doesn’t raise over 30kV within 4ms
from X-ray command ON. It shows a missing of feedback from the high
voltage stadium.
• DL6= Blink (kV discharge error) when the kV signal fall before the end of exposure, it
shows a kV discharge behavior
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 10 di 19
• DL6 & DL7= ON (Thermal safety switch intervention) when the thermal safety switch of
the load has intervened.
• DL7= ON (over mA max error) when the anodic current exceed the max factory set
value.
• DL20= ON (Filament current Error) when the filament current exceed the max limit.
• DL20= Blink (Filament current Error) when the filament current is lower than min limit.
S219 POTENTIOMETERS description:
• P1 Filament working frequency adjust (factory set)
• P2 Inverter working frequency adjust (factory set)
S219 TEST POINTS description:
• Tp1 +5Vdc
• Tp2 GND
• Tp3 Filament working frequency
• Tp4 kV+ feedback (1V=10kV in the load)
• Tp5 kVTOT feedback (-1V=15kV in the load)
• Tp6 N.C.
• Tp7 Set kV (1V=15kV in the load)
• Tp8 Anodic mA in the load (1V=100mA)
• Tp10 Inverter working frequency
• Tp12 PWM output command1
• Tp13 PWM output command2
• Tp14 Filament current feedback 1V=1000mA
S219 signals directly available through the chassis:
At the chapter 3.2 it is possible to see the signals which are available at the connectors fixed
on the chassis, in particular:
• Can bus terminals.
• Hardware X-ray command input which guarantees the safety control of exposure starting.
• The output signal HV>85% that is available to detect the effective starting of exposure.
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 11 di 19
3.5 Mechanical characteristics
Dimensions (see figures)
Unit: mm
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 12 di 19
Weight (approx.) 14kg
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 13 di 19
4 Labelling
Labels placed on the control unit
Labels position on the control unit
Label position
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 14 di 19
5 Conditions of storage and usage
Transport and storage conditions
Range of temperature 0° – 50° C
Relative humidity (non condensing) 20 – 90 %
Atmospheric pressure 700 – 1060 hPa
Working conditions
Range of temperature 10° – 40° C
Relative humidity (non condensing) 30 – 75 %
Atmospheric pressure 700 – 1060 hPa
6 Electromagnetic compatibility (EMC)
It is not possible to exclude radio signals coming from transmitters such as mobile phones or
similar mobile radio devices, including those in compliance with EMC standards, may influence
the proper functioning of the apparatus when used in proximity and with a relatively high
transmitting power.
Therefore, the use of radio equipment in proximity to electronically controlled system must be
avoided in order to eliminate any interference risk.
Any transmissions by mobile radio equipment must be avoided.
Mobile phones must be switched off in zones close to the unit.
These rules must be applied when the unit is switched on (that
means connected to the mains and ready to use).
7 Symbols
The symbols that have been used are illustrated below:
Symbol Meaning Position
Caution: see the attached documentation
Unit /
Technical data sheet /
Unit label
Equipment that requires a correct disposal
(2002/96/EC) Unit label
Manufacturer Unit label
Protective earth Unit
~ Alternate current Technical data sheet /
Unit label
Dangerous voltage Unit
Warning: dangerous voltage Unit
Small focus Technical data sheet /
Unit
Large focus Technical data sheet /
Unit
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 15 di 19
8 Installation To install the device in a radiological system, look over all the information reported in this
document. Furthermore IMD Generators suggests also to protect:
• 230Vac main power input with a couple of 32A 400Vac aM 20kA fuses as indicated
in the chapter 8.3.
ATTENTION – Accessory equipment connected to the control unit analog and
digital interfaces must be in compliance with the nationally harmonized IEC
standards. Furthermore all configurations shall comply with the system
standard IEC60601-1-1. Everybody who uses or connects the equipment
configures a medical system, and is therefore responsible that the system
complies with the requirements of the system standard IEC 60601-1-3 and
IEC 60601-2-54.
8.1 Unpacking
ATTENTION – Unpack the control unit with caution to avoid mechanical
damages of the chassis and interface connectors.
8.2 Mechanical installation
Install the control unit through the four M5 threaded holes fitted on its mechanical structure
(please refer to chapter 3.5).
CAUTION – It is recommended to install the control unit in a sheltered position, to
protect it from mechanical damages and prevent the direct contact by the
user/patient.
Please note that the components inside the control unit, during its working, could accumulate
a significant amount of heat. The control unit chassis was projected keeping in mind this and
a fan/blower inside helps to let the heat flowing outside the chassis. It is recommended to
choose a properly position that could let the control unit “breathe” in a well-ventilated area of
the final equipment.
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 16 di 19
8.3 Electrical installation
Here below it is possible to see how to connect the HF1 Control unit Mammo 8kW to a HF1
G/26 generator equipped with the PSM26/2M interface board (Drawing number 009025):
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 17 di 19
9 Maintenance The control unit requires regular checks. Regular inspections are aimed to maintain good
operation and service safety and to protect the patient and operator from electrical hazards.
This chapter reports the checks that have to be observed by the manufacturer of the
equipment where the control unit is installed and must be carried out by expressly authorized
and properly trained personnel.
CAUTION - In the case replacement of any component use only original
spare parts. NOTE: Against risks of fire hazards replace following fuses with ones
having the same rating:
Control unit fuses:
(Main power DC on the PSM03 board) F1 = 80A 660Vac gRB 200kA(BS88-FE / 77x17.1)
(Driver board PSM44 input AC) F1 = 1,5AT (ferrule 5x20)
(Filament power board S223 main input AC) F2 = 2AT (ferrule 5x20)
(Filament power board S223 DC) F1 = 1AT (ferrule 5x20)
(Stator driver board PSM20/1 Main AC input) F1 = F2 = 10AT (ferrule 5x20)
9.1 Checks and inspections to be carried out by the user
CHECKS
• Integrity of the warning and danger labels.
• Control unit mechanical fixing and general state.
• Integrity of wirings and connections
• Cleanness of inlet and outlet air masks
9.2 Cleaning and disinfection
The control unit doesn’t need particularly operations of cleaning and disinfection; in case of
cleaning of parts of the equipment in which it is installed, cleaning products have not to be
used if produce explosive, gaseous mixtures. If they are used, make sure that gases are
dispersed before switching on the control unit.
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 18 di 19
10 Risks
The manufacturer provides information on its products and associated hazards, but it assumes
no responsibility for after-sale operating and safety practices.
Appropriate safe operating practices should be employed.
Do not operate this control unit except in accordance with information included in this
technical data sheet, these precautions, and any additional information provided by the
control unit Manufacturer and/or competent safety authorities.
Being the control unit installed together with an X-ray tube, see the X-ray tube technical data
sheet for hazards related to X-ray emission and for the precautions to be adopted during the
X-ray exposure.
10.1 Control unit hazards
VOLTAGE
The control unit is fed by dangerous mains voltage, so equipment designed should prevent
personnel contact with this apparatus.
When direct access to the control unit is required, the primary circuits should be disabled
waiting a minimum time of 5 minutes to allow a correct discharge of the inner control unit
capacitors.
11 Disposal of the device
Once the product is at the end of its use it must be disposed following the enforced rules
concerning the separate collection of waste and it cannot be treated as a simple urban waste.
The symbol here beside means that the product has the requirements requested
by new directives introduced for the environmental protection (2002/95/EC,
2002/96/EC, 2003/108/EC) and it must be disposed properly once its life cycle is
ended.
When the device has reached the end of its life it must be disposed at the proper
centres for the separate collection of electrical and electrical wastes, or it must be
returned to the reseller or to the manufacturer in case you want to replace the
product with another equivalent new one.
The proper separate collection helps to avoid possible negative effect on the environment and
on health and it facilitates the second use and the re-cycle of materials of which the device is
composed of. Ask for further information to the local authorities about the areas dedicated to
the wastes disposal.
Who does not dispose the product following here above mentioned, will be responsible in front
of the enforced rules.
Technical data sheet
Control unit HF1 Mammo 8kW LC
IMD Generators Srl Doc.010575 Data 13/03/2017 Viale G. Matteotti 28/A – 24050 – Grassobbio (Bergamo) – Italy Pagina 19 di 19
12 Declaration of responsibility
➠ IMD Generators is only responsible for the safety of its products when their repair
and/or modification has been carried out by IMD Generators or by personnel expressly
authorised by IMD Generators itself.
➠ IMD Generators shall not be held responsible in any way for malfunction, damage
and/or danger due to incorrect use of the system or to disregard of the maintenance
regulations.
➠ The manufacturer of the equipment where the device is installed should take care of
proper device use by trained and qualified operators.
All the technical information and those relevant for the compliance may be required to the
manufacturer (93/42/EEC directive and following amendments):
Viale Matteotti, 28/A � 24050 Grassobbio � BERGAMO � ITALY
� +39 035-52.63.44 � FAX +39 035-52.60.86