MATERIAL TESTING AGENCY FOR THE CONSTRUCTION
INDUSTRY
INSTITUTE FÜR BAUSTOFFE, MASSIVBAU UND BRANDSCHUTZ
[Institute for Building Materials, Massive Structures and Fire Protection]
General Building Inspection Test Certificate
Test Certificate Number:
Object: Ceilings according to DIN 4102-4, Sections 3.4 to 3.8 and
3.11 as well as load bearing and non-load bearing, space-
enclosing walls made of reinforced concrete or brickwork
according to DIN 4102-4, Sections 4.2 and 4.5 with "resilient
joint sealing tape F 120" joint sealing tapes of fire resistance
class F 30 or F 120 according to DIN 4102-2
Applicant: Adolf Würth GmbH & Co. KG
Reinhold-Würth-Straße 12-16
D-74653 Künzelsau
Date issued: September 30, 2000
[Repeated stamp:]
[MATERIAL TESTING
AGENCY FOR THE
CONSTRUCTION
INDUSTRY]
Valid until: September 30, 2005
On the basis of this building inspection test certificate, the above-mentioned object can be
used in the sense of the State Construction Ordinance of the respective State.
This general building inspection test certificate comprises 8 sheets and 6 appendixes.
MATERIAL TESTING AGENCY FOR THE
CONSTRUCTION INDUSTRY
Technical University Braunschweig
Beethovenstraße 52
D-38106 Braunschweig
Telephone +49-(0)531-391-5431
Fax +49-(0)531-391-4573
E-Mail mpa@tu-bs de
http://www.mpa.tu-bs de
Norddeutsche Landesbank Hannover
Account 106 020 050 (BLZ 250 500 00)
Swift Code NOLADE 2H
VAT No. MPA-DE 183500654
[German Accreditation
Council]
DAP∙P-02 204-04-94-00 ∙ DAP∙P-02.204-02-94-00 ∙ DAP∙P-02.204-01-92-00 ∙ DAP∙P-02.204-03-94-00 ∙ DAP∙P-02.204-05-94-00 ∙ DAP∙P-02.204-06-94-00 DKD∙K∙22501
Test laboratories accredited according to DIN EN 45001. The accreditations apply to the test methods set out in the documents
MPA Braunschweig
Sheet 2 of the general building inspection test certificate No. P-3568/2560-MPA BS of September 30, 2000
1 Object and scope of application
1.1 Object
1.1.1 The general building inspection test certificate applies to the manufacture and use
of ceilings exposed from below or above to fire, according to Sections 3.4 to 3.8 and 3.11 of DIN
4102-4: 1994-03 1) as well as to load bearing or non-load bearing, space-enclosing walls made of
reinforced concrete or brickwork according to Sections 4.2 and 4.5 of DIN 4102-4: 1994-05 with
"resilient joint sealing tape F 120" joint sealing tapes, which belong to fire resistance class F 30
or F 120, designation (short designation) F 30-AB or F 120-AB according to DIN 4102-2: 1977-
09.
1.1.2 The ceilings with joint sealing tapes must be made from ceiling constructions
according to Sections 3.4 to 3.8 and 3.11 and the "resilient joint sealing tape F 120" joint sealing
tapes according to Section 2. The space-enclosing walls (one-sided fire exposure) with joint
sealing tapes must consist of wall constructions made of reinforced concrete or brickwork,
Sections 4.2 and 4.5 of DIN 4102-4: 1994-03 with "resilient joint sealing tape F 120" joint
sealing tapes according to Section 2.
1) This general building inspection test certificate contains dated and undated references to and specifications
from other standards or guidelines. These references are cited in the respective passages in the text and the standards are listed on sheet 7. For dated references, subsequent amendments to or revisions of these standards must be taken into consideration in this general building inspection test certificate. For undated references, the last version of the referenced standard or guideline is applicable.
1.2 Scope of application
1.2.1 The ceiling and walls with joint sealing tapes must, in the case of fire resistance
class F 30, have a thickness d ≥ 100 mm and, in the case of fire resistance class F 120, a
thickness d ≥ 150 mm, and for the rest they have to satisfy the conditions of Sections 3.4 to 3.8
and 3.11 as well as 4.2 and 4.5 of DIN 4102-4.
The minimum component thickness d in the case of chamfered edges must be based on
the end points of the chamfering (see Figure 1).
Figure 1
Joint sealing tape
MPA Braunschweig
Sheet 3 of the general building inspection test certificate No. P-3568/2560-MPA BS of September 30, 2000
1.2.2 The joint sealing tapes may be arranged between individual ceiling portions,
between the walls specified below or between ceiling portions and
- load bearing and non-load bearing, space-enclosing walls made of brickwork according
to DIN 1053-1 to 4,
- load bearing and non-load bearing, space-enclosing walls made of concrete or
reinforced concrete according to DIN 1045 or
- walls made of aerated concrete slabs and panels according to DIN 4166.
The wall constructions must be of the same fire resistance class as the ceilings with joint sealing
tapes. For the fire resistance class of the above-mentioned wall constructions, a proof of usability
in terms of fire protection (for example, DIN 4102-4 or a general building inspection test
certificate) must provided.
1.2.3 The joint sealing tapes between individual ceiling portions or between ceiling
portions and the above-mentioned wall constructions or between the above-mentioned wall
constructions must be closed in accordance with Section 2.1.
1.2.4 To the extent that there are requirements in terms of noise protection, further
supporting documents must be provided.
1.2.5 According to the explanation of the applicant, no products are used in the
construction that are subject to the Regulation on Hazardous Substances, the Ordinance for
Prohibition of Chemicals or the FCKW [chlorofluorocarbon] Ordinance for Prohibition of
Halogenated Hydrocarbons, or the conditions imposed by the above-mentioned ordinances (in
particular the marking obligation) are complied with.
Moreover, the applicant declares that — to the extent that, for commerce and placing on
the market or for use, measures must be taken with a view to hygiene, health protection or
environmental protection — these measures are instituted or publicized in the required manner
by the applicant.
Therefore, there was no reason to test the effects of the building products in the installed
state for compliance with the health and environmental protection requirements.
MPA Braunschweig
Sheet 4 of the general building inspection test certificate No. P-3568/2560-MPA BS of September 30, 2000
2 Specifications for the ceilings or walls with "resilient joint sealing tape F 120" joint
sealing tapes
2.1 Specification for the implementation
Joint sealing tapes between individual ceiling portions, between ceiling portions and wall
constructions as well as between individual wall portions according to Section 1.2.2
The joint sealing tapes having a maximum width of 40 mm must consist of an at least 50
mm high (fire resistance class F 30) or an at least 80 mm or 100 mm high (fire resistance class F
120) "resilient joint sealing tape F 120" joint sealing tape according to the general building
inspection test certificate No. P – NDS04 – 121 of the Hannover Material Testing Agency for the
Construction Industry. In the case of the installation of joint sealing tapes between individual
ceiling portions, between ceiling portions and wall constructions as well as between individual
wall portions according to Section 1.2.2 of the fire resistance class F 120, it is possible to arrange,
instead of an at least 80 mm high or an at least 100 mm high "resilient joint sealing tape F 120"
joint sealing tape, in each case two at least 40 mm or at least 50 mm high "resilient joint sealing
tape F 120" joint sealing tapes according to Appendixes 1.3 to 1.6. In the case of the installation
of 21-40 mm wide joint sealing tapes between individual ceiling portions, between ceiling
portions and wall constructions as well as between individual wall portions according to Section
1.2.2 of the fire resistance class F 30, 5 mm thick skim made of silicone (minimum construction
material class B2 according to DIN 4102-1: 1998-05) must be applied additionally to the joint
sealing tapes.
Further details regarding the setup of the ceilings or walls with "resilient joint sealing
tape F 120" joint sealing tapes can be obtained from Appendixes 1.1 to 1.6 of this general
building inspection test certificate.
2.2 Properties and composition of the building products used
The indications in terms of the marking, the material characteristic values, the
classification and the proof of usability compiled in Table 1 apply to the building products to be
used.
Table 1, see sheet 5
MPA Braunschweig
Sheet 5 of the general building inspection test certificate No. P-3568/2560-MPA BS of September 30, 2000
Table 1: Compilation of the characteristic values of the building products
Building material
designation
Thickness
[mm]
Weight per unit
area
[kg/m2]
Bulk density
[kg/m3]
Construction
material
classification
Proof of usability
"Resilient joint
sealing tape F 120"
joint sealing tape
40.0
50.0
80.0
100.0
≥ 6.8
≥ 8.5
≥ 13.6
≥ 17.0
-
≥ 170.0
-
B1
-
ABP 1) No. P –
NDS04 - 219
Silicone ≥ 5.0 - - at least B2 According to
DIN 4102-1:
1998-05
1) ABP � General Building Inspection Test Certificate
2.3 Proof of compliance
The construction type indicated in this general building inspection test certificate requires
proof of compliance (compliance proof) according to the specifications of the Building Rules
List A (BRL A) Part 3. According to BRL A Part 3, serial No. 1, a compliance declaration of the
manufacturer (entrepreneur) must occur.
The entrepreneur who manufactures the ceiling or the wall with joint sealing tapes must
prepare for the applicant a written compliance declaration (form, see sheet 8) by means of which
he certifies that the ceiling or wall with joint sealing tapes produced by him meets the provisions
of this general building inspection test certificate.
3 Legal basis
This general building inspection test certificate is issued under §§ 24 ff of the Lower
Saxony Building Ordinance (NBauO) in the version of July 13, 1995 (Nds. GVBl. [Lower
Saxony Law and Ordinance Gazette], p. 199), amended by Article II of the law of May 28, 1996
(Nds. GVBl. p. 252) and by the 8th law of October 6, 1997 (Nds. GVBl., p. 422) in connection
with the Building Rules List A. The Federal States’ building ordinances of the remaining federal
States contain corresponding legal bases.
MPA Braunschweig
Sheet 6 of the general building inspection test certificate No. P-3568/2560-MPA BS of September 30, 2000
4 General information
4.1 The general building inspection test certificate does not replace the authorizations,
approvals and certifications legally prescribed for executing building projects.
4.2 The general building inspection test certificate is granted without prejudice to the
rights of third parties in particular private proprietary rights.
4.3 The manufacturers or distributors of the construction must, notwithstanding the
regulations in the "special provisions," make available copies of the general building inspection
test certificate to the user of the construction.
4.4 The general building inspection test certificate may be duplicated only in its
entirety. Publication of excerpts requires the approval of the Braunschweig Material Testing
Agency for the Construction Industry. The texts and drawings of advertising materials must not
be in contradiction with the general building inspection test certificate. Translations of the
general building inspection test certificate must contain the information "from the Braunschweig
Material Testing Agency for the Construction Industry, unverified translation of the German
original."
4.5 The general building inspection test certificate is granted in a manner that allows it to be
retracted. The general building inspection test certificate can subsequently be added to and
amended, in particular when new technical findings require this.
Braunschweig, September 30, 2000
For a list of further applicable standards and guidelines, see the following sheet
The Director On behalf of
The Case Officer Processor
ORR Dr.-Ing. Rohling
Dipl.-Ing. Rabbe
Sheet 7 of the general building inspection test certificate No. P-3568/2560-MPA BS of September 30, 2000
List of further applicable standards and guidelines
DIN 4102-4: Fire behavior of construction materials and construction components;
composition and use of classified construction materials, construction
components and special construction components (Version March 1994)
DIN 4102-2: Fire behavior of construction materials and construction components;
construction components, terms, requirements and tests (Version
September 1977)
DIN 1053-1: Brickwork; prefabricated brickwork; calculation and execution
DIN 1053-2: Brickwork; brickwork strength classes based on suitability tests;
calculation and execution
DIN 1053-3: Brickwork; reinforced brickwork; calculation and execution
DIN 1053-4: Brickwork; structures made of prefabricated brick construction
components
DIN 1045: Concrete and reinforced concrete; dimensioning and execution
DIN 4166: Aerated concrete slabs and panels and aerated concrete design slabs and
panels
DIN 4102-1: Fire behavior of construction materials and construction components; Part
1: Construction materials, terms, requirements and tests (Version May
1998)
Building Rules List A Part 3 (in the respective valid version); published in
DIBt - Mitteilungen
MPA Braunschweig
Sheet 8 of the general building inspection test certificate No. P-3568/2560-MPA BS of September 30, 2000
Form for
Compliance Declaration
- Name and address of the company that manufactured the ceiling/wall with joint sealing
tapes
- Construction site or building:
- Date of manufacture:
- Fire resistance class F ...
It is confirmed hereby that the ceiling/wall with joint sealing tapes of fire resistance class
F 30 or F 120 was manufactured and installed in a professionally correct manner with regard to
all the details and in compliance with all the provisions of the general building inspection test
certificate No. P-3568/2560-MPA BS of the Braunschweig Material Testing Agency for the
Construction Industry of September 30, 2000.
This is also confirmed for the building products or individual parts (for example, silicone)
that are not manufactured by the undersigned himself/herself, on the basis of
- the provided marking of the parts in accordance with the provisions of the general
building inspection test certificate*)
- first-hand verifications *)
*) Strike out any text that is not applicable
- corresponding written confirmations of the manufacturer of the building products or
parts, which the undersigned included in his records. *)
______________________________________________________________________________
Place, Date Stamp and signature
(This certification must be handed over to the builder to be forwarded to the competent building
inspection authority.)
Overview list: resilient joint sealing tape F 120
All the installation variants are applicable to a wall/wall, ceiling/ceiling and wall
connection
F class Ceiling -
wall thickness
Joint width Minimum
installation
depth
Silicone covering (B2)
(layer thickness ≥ 5 mm)
F 30 ≥ 100 mm up to 20 mm ≥ 50 mm not necessary
F 30 ≥ 100 mm from 21 to 40 mm ≥ 50 mm necessary
F 120 ≥ 150 mm up to 20 mm
up to 20 mm
≥ 80 mm
≥ 2 x 40 mm
not necessary
not necessary
F 120 ≥ 150 mm from 21 to 40 mm
from 21 to 40 mm
≥ 100 mm
≥ 2 x 50 mm
not necessary
not necessary
Measurements in mm
Construction design of the test body*
Overview list Appendix 1.1 of
ABP No.
P-3568/2560 - MPA BS
of September 30, 2000
Material Testing Agency for the Construction Industry
Institute for Building Materials, Massive Construction and Fire Protection
of the Technical University Braunschweig
Measurements in mm
Construction design of the test body
Joints made of "resilient joint sealing tape F 120" joint sealing tapes of fire
resistance class F 30
(wall/wall, ceiling/ceiling and wall/ceiling connection)
Appendix 1.2 of
ABP No.
P-3568/2560 - MPA BS
of September 30, 2000
Material Testing Agency for the Construction Industry
Institute for Building Materials, Massive Construction and Fire Protection
of the Technical University Braunschweig
F 30 for W/W and C/C
Joint width up to 20 mm Joint width up to 20 mm Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width up to 20 mm Joint width up to 20 mm Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
F 30 for W/C
Measurements in mm
Construction design of the test body
Joints made of "resilient joint sealing tape F 120" joint sealing tapes of fire
resistance class F 120
Joint width up to 20 mm (wall/wall and ceiling/ceiling connection)
Appendix 1.3 of
ABP No.
P-3568/2560 - MPA BS
of September 30, 2000
Material Testing Agency for the Construction Industry
Institute for Building Materials, Massive Construction and Fire Protection
of the Technical University Braunschweig
F 120 for W/W and C/C
F 120 for W/W and C/C
Joint width up to 20 mm Joint width up to 20 mm Joint width up to 20 mm Joint width up to 20 mm
Joint width up to 20 mm Joint width up to 20 mm Joint width up to 20 mm Joint width up to 20 mm
Measurements in mm
Construction design of the test body
Joints made of "resilient joint sealing tape F 120" joint sealing tapes of fire
resistance class F 120
Joint width up to 20 mm (wall/ceiling connection)
Appendix 1.4 of
ABP No.
P-3568/2560 - MPA BS
of September 30, 2000
Material Testing Agency for the Construction Industry
Institute for Building Materials, Massive Construction and Fire Protection
of the Technical University Braunschweig
F 120 for W/C
F 120 for W/C
Joint width up to 20 mm Joint width up to 20 mm Joint width up to 20 mm
Joint width up to 20 mm Joint width up to 20 mm Joint width up to 20 mm
Measurements in mm
Construction design of the test body
Joints made of "resilient joint sealing tape F 120" joint sealing tapes of fire
resistance class F 120
Joint width from 21 mm to 40 mm (wall/wall and ceiling/ceiling connection)
Appendix 1.5 of
ABP No.
P-3568/2560 - MPA BS
of September 30, 2000
Material Testing Agency for the Construction Industry
Institute for Building Materials, Massive Construction and Fire Protection
of the Technical University Braunschweig
F 120 for W/W and C/C
F 120 for W/W and C/C
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Measurements in mm
Construction design of the test body
Joints made of "resilient joint sealing tape F 120" joint sealing tapes of fire
resistance class F 120
Joint width from 21 mm to 40 mm (wall/ceiling connection)
Appendix 1.6 of
ABP No.
P-3568/2560 - MPA BS
of September 30, 2000
Material Testing Agency for the Construction Industry
Institute for Building Materials, Massive Construction and Fire Protection
of the Technical University Braunschweig
F 120 for W/C
F 120 for W/C
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm
Joint width from 21 mm to 40 mm