WSEC 2015 - Acuity Brands | Lighting, Controls, and ... · The Washington State Energy Code (WSEC)...
Transcript of WSEC 2015 - Acuity Brands | Lighting, Controls, and ... · The Washington State Energy Code (WSEC)...
nLight® Applications Guide
www.acuitycontrols.com
WSEC 2015
2 1Intro
www.acuitycontrols.com • 800-535-2465
ACUITY CONTROLS
It’s not just smarter. It’s easier.
Acuity Controls is advanced lighting controls
technology, service and support from a single
expert source. We offer one of the industry’s
most extensive product portfolios for indoor and
outdoor applications; single rooms to campuses
to municipalities. Our product solutions include
occupancy and photosensors, centralized and
distributed systems, panels, fixture-integrated,
wired and wireless controls that simply work.
2 1
WSEC: nLight Applications Guide
Table of Contents
Code Requirements for Common Building Spaces
How to Use This Guide
Private Office Solutions
Open Office Solutions
Conference Room Solutions
Classroom Solutions
Stairwell Solutions
Public Restroom Solutions
Corridor Solutions
Gymnasium Solutions
Warehouse Solutions
Network Control
Appendix A – nLight Enabled Fixtures
Appendix B – Requirements Overview
04
05
06
10
12
14
18
20
22
24
26
28
29
30
TABLE OF CONTENTS
2 3Title 24 Lighting Control
www.acuitycontrols.com • 800-535-2465
2 3
WSEC: nLight Applications Guide
About
About WSECThe Washington State Energy Code (WSEC) 2015 is
a residential and commercial building energy code
based on the IECC which has been adopted by many
states and municipalities. The intention of this code
is to reduce energy consumption by outlining design
and construction requirements which include specific
constraints for lighting controls. The use of lighting
controls to synchronize light levels with daylight,
occupancy, and multi-level control demand response
capability are required in order to be compliant.
About This Guide
Acuity Controls offers the nLight® WSEC Applications
Guide as a reference of typical nLight layouts that
help make code compliance quicker and easier. The
Acuity Controls Design Services Team is also available
to support engineers and contractors with detailed
design, submittal, and installation. For additional
information, please contact your Acuity Brands
Sales Representative.
About nLightThe nLight networked digital lighting control system
is easy-to-use, easy-to-install and saves energy. Using
only standard CAT-5e cable, nLight networks together
occupancy sensors, wall stations, and digital LED
luminaires to create a digital lighting system with
unmatched flexibility! nLight easily scales from one
room to an entire campus, creating a lighting control
solution that’s perfect for your space and need.
nLight may be used to meet the Enhanced Digital
Lighting Controls option found in Section C406, when
employing nLight enabled fixtures.
ABOUT
4 5
www.acuitycontrols.com • 800-535-2465
Code Requirements for Common Building Spaces
* Note: This summary is for general information purposes only and is provided without any warranty as to accuracy, completeness, or otherwise. The user should read the applicable code sections for more complete and detailed descriptions of code requirements and exceptions and should consult with a professional engineering or other competent advisor before making any decision or taking any action based on this summary.
The chart below is an overview of the Code Requirements for Common Building Spaces. Please use this information as a guide. For specific code requirements please refer to the IECC code.
Control Requirement*
Code Provision
Code Summary*
Space Type
Private Office
Open Office
Conference, Meeting,
Multipurpose Room
Classroom, Lecture Hall,
Training Room
Lobby Corridor Restroom Stairwell Warehouse
Manual-Onor AutoOn
≤ 50%C405.2.1.1.2
Automatically controlled spaces must be controlled to automatically turn the
lighting on to not more than 50% power.
Full Automatic-On C405.2.1.1.2
Automatically controlled spaces are allowed to turn
on to full.
Full Auto-Off via Occupancy
SensorC405.2.1.1.1
Fixtures must automatically turn off within 30 minutes of all occupants leaving the
space.
Time Switch Controls
(with backbone networked installed)
C405.2.2.1
Each area of the building not provided with occupant
sensor controls shall be provided with time switch controls. These areas must
also be provided with a manual override switch.
Light Reduction Control C405.2.2.2
Spaces shall have a manual control that allows the occupant to reduce the connected lighting load
uniformly by at least 50%.
Manual Control(Local Switch) C405.2.3
Areas shall incorporate a manual control to allow
occupants to turn fixtures off.
Daylight-Responsive
ControlsC405.2.4
Daylight-responsive controls shall be provided within
each space with more than two general lighting fixtures within sidelight and toplight
daylight zones.
Plug Load/Controlled
ReceptaclesC405.10
50% of all receptacles shall be controlled by the occ
sensor or time switch
On-O
f Co
ntro
lDa
yligh
t Con
trol
(or)
(or) (or) (or) (or)
4 5
WSEC: nLight Applications Guide
How to Use This Guide
6 7
www.acuitycontrols.com • 800-535-2465
PRIVATE OFFICE: No Windows, nLight Enabled Fixtures
CAT-5e Cable
Line Voltage Wires
Line Power Feed
nPP20 PL nWSX PDT LV DX
Bill of Materials
Symbol Qty Product # Description
4 Various; see Appendix A nLight Enabled Fixture
1 nWSX PDT LV DX On/Off and Raise/Lower, Occupancy WallPod
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
Surface or recessed mount sensors also available
Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1) and qualify for enhanced digital lighting controls C406.4
For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
SEQUENCE OF OPERATIONS: ADDITIONAL OPTIONS:
Fixtures:
All fi xtures are dimmable
All fi xtures are controlled together or independently
Adjustable High/Low Trim
Optional automatic lumen compensation
Occupancy Control:
Fixtures must be turned on manually (or optionally can be confi gured to come on automatically to 50%)
Fixtures and receptacles automatically turn off when room becomes vacant
Daylight Control:
Not required for offi ces without windows or with 2 or less luminaires
Manual Control:
On/off & raise/lower control of fi xtures
Supports the Following Requirements:
Full Auto-Off via Occupancy Sensor (C405.2.1.1)
Manual Control (local switch) (C405.2.2.3)
Lighting Reduction (C405.2.2.2)
Enhanced Digital Lighting Controls (C406.4) (with backbone networked installed)
Controlled Receptacles/Plug Load (C405.10)
Operational details describe the functionality provided by the equipment specified in the solution
Room description Room layout with devices & locations
Room layout diagram with control, fixture,and wiring type detail
Required list ofdevices in order to implement room layout design above
Additional options that add control capacity beyond code requirements
Quick summary of applicable code sections
6 7
www.acuitycontrols.com • 800-535-2465
PRIVATE OFFICE: No Windows, nLight Enabled Fixtures
CAT-5e Cable
Line Voltage Wires
Line Power Feed
nPP20 PL nWSX PDT LV DX
Bill of Materials
Symbol Qty Product # Description
4 Various; see Appendix A nLight Enabled Fixture
1 nWSX PDT LV DX On/Off and Raise/Lower, Occupancy WallPod
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
¡ Surface or recessed mount sensors also available
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1) and qualify for enhanced digital lighting controls C406.4
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
SEQUENCE OF OPERATIONS: ADDITIONAL OPTIONS:
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently
¡ Adjustable High/Low Trim
¡ Optional automatic lumen compensation
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures and receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Not required for offices without windows or with 2 or less luminaires
Manual Control:
¡ On/off & raise/lower control of fixtures
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1)
¡ Manual Control (local switch) (C405.2.2.3)
¡ Lighting Reduction (C405.2.2.2)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone networked installed)
¡ Controlled Receptacles/Plug Load (C405.10)
6 7
WSEC: nLight Applications Guide
PRIVATE OFFICE: No Windows, 0-10V Dimming Fixtures
Bill of Materials
Symbol Qty Product # Description
1 nPP16 D Relay Module with 0-10V Dimming Output
1 nWSX PDT LV DX On/Off and Raise/Lower, Occupancy WallPod
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
CAT-5e Cable
Line Voltage Wires
Line Power Feed
0-10V Wires
nPP20 PL nWSX PDT LV DX
nPP16 D
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Manual Control (Local Switch)(C405.2.3)
¡ Lighting Reduction (C405.2.2.2)
¡ Controlled Receptacles/Plug Load (C405.10)
¡ Surface or recessed mount sensors also available
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
SEQUENCE OF OPERATION: ADDITIONAL OPTIONS:
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures and receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Not required for offices without windows or with two or less luminaires
Manual Control:
¡ On/off & raise/lower control of fixtures
8 9
www.acuitycontrols.com • 800-535-2465
nPP20 PL
DZ 2
DZ 1
nCM ADCX DZ
nWSX PDT LV DX
PRIVATE OFFICE: Windows, nLight Enabled Fixtures
CAT-5e Cable
Line Voltage Wires
Line Power Feed
SEQUENCE OF OPERATIONS: ADDITIONAL OPTIONS:
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently
¡ Optional automatic lumen compensation
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max. number zones = number of fixtures)
¡ Not required for offices without windows or with two or less luminaires
Manual Control:
¡ On/off & raise/lower control of fixtures
¡ Surface or recessed mount sensors also available
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1) and qualify for enhanced digital Lighting Controls (C406.4)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Sidelight Daylight Zones (C405.2.4.2)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone network installed)
¡ Controlled Receptacles/Plug Load (C405.10)
Bill of Materials
Symbol Qty Product # Description
4 Various; see Appendix A nLight Enabled Fixture
1 nWSX PDT LV DX On/Off & Raise/Lower WallPod
1 ADCX DZ Dual Zone Automatic Dimming Photocell
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
8 9
WSEC: nLight Applications Guide
nPP20 PL
nPP16 D
DZ 2
DZ 1
nCM ADCX DZ
nWSX PDT LV DX
nPP16 D
CAT-5e Cable
Line Voltage Wires
Line Power Feed
0-10V Wires
PRIVATE OFFICE: Windows, 0-10V Dimming Fixtures
ADDITIONAL OPTIONS:
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Not required for offices without windows or with two or less luminaires
Manual Control:
¡ On/off & raise/lower control of fixtures
¡ Surface or recessed mount sensors also available
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For emergency lighting control add an nPP16 D ER pack
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Bill of Materials
Symbol Qty Product # Description
2 nPP16 D Relay Module with 0-10V Dimming Output
1 nWSX PDT LV DX On/Off and Raise/Lower, occupancy WallPod
1 ADCX DZ Dual Zone Automatic Dimming Photocell
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Lighting Reduction (C405.2.2.2)
¡ Sidelight Daylight Zones (C405.2.4.2)
¡ Controlled Receptacles/Plug Load (C405.10)
SEQUENCE OF OPERATIONS:
10 11
www.acuitycontrols.com • 800-535-2465
OPEN OFFICE with nLight Enabled Fixtures
DZ 2
DZ 1
nCM ADCX DZ
nCM PDT 9
nCM PDT 9
nCM PDT 9
nCM PDT 9
nPP20 PL
EMG 1EMG
nPODM DX
nPODM DX
CAT-5e Cable
Line Voltage Wires
Line Power Feed
EM Power Feed
0-10V Wires
Note: Not all emergency nLight enabled fixtures require a normal monitoring feed. Refer to data sheet for additional information.
¡ Surface or recessed mount sensors also available
¡ Add Graphic WallPod (model nPOD GFX) for individual row and up to 16 scene control
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1) and qualify for enhanced digital Lighting Controls (C406.4)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently
¡ Optional automatic lumen compensation
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max. number zones = number of fixtures)
¡ Not required for offices without windows or with two or less luminaires
Manual Control:
¡ Master on/off & raise/lower control of fixtures
¡ Optional individual row control (add nPODM 4P DX)
ADDITIONAL OPTIONS:
Bill of Materials
Symbol Qty Product # Description
14Various; see Appendix A
nLight Enabled Fixture
2Various; see Appendix A
nLight Enabled Fixture with EMG Option
2 nPODM DX On/Off & Raise/Lower WallPod
4 nCM PDT 9 Dual Technology Occupancy Sensor
1 nCM ADCX DZ Dual Zone Automatic Dimming Control Photocell
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Manual Control (Local Switch) (C405.2.2.3)
¡ Sidelight Daylight Zone (C405.2.4.2)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone network installed)
¡ Controlled Receptacles/Plug Load (C405.10)
SEQUENCE OF OPERATIONS:
10 11
WSEC: nLight Applications Guide
nPP16 D
nPP16 D
nPP16 D
nCM ADCX DZ
nCM PDT 9
nCM PDT 9
nCM PDT 9
nCM PDT 9
nPP16 D
nPP20 PL nPODM DX
nPODM DX
nPP16 D ER
DZ 2
DZ 1
OPEN OFFICE with 0-10V Dimming Fixtures
CAT-5e Cable
Line Voltage Wires
Line Power Feed
EM Power Feed
0-10V Wires
¡ Surface or recessed mount sensors also available
¡ Add Graphic WallPod (model nPOD GFX) for individual row and up to 16 scene control
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ Each row controlled independently
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to come on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Daylight zones defined by rows
¡ Not required for offices without windows or with two or less luminaires
Manual Control:
¡ Master on/off & raise/lower control of fixtures
¡ Optional individual row control (add nPODM 4P DX)
ADDITIONAL OPTIONS:
Bill of Materials
Symbol Qty Product # Description
4 nPP16 D Relay Module with 0-10V Dimming Output
1 nPP16 D ER Emergency Relay Module with 0-10V Dimming Output
2 nPODM DX On/Off & Raise/Lower WallPod
4 nCM PDT 9 Dual Technology Occupancy Sensor
1 nCM ADCX DZ Dual Zone Automatic Dimming Control Photocell
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Sidelight Daylight Zone (C405.2.4.2)
¡ Controlled Receptacles/Plug Load (C405.10)
nPP16 D ER
SEQUENCE OF OPERATIONS:
12 13
www.acuitycontrols.com • 800-535-2465
CONFERENCE ROOM with nLight Enabled Fixtures
nCM PDT 9
nCM ADCX DZ
nPP20 PL
DZ 2
DZ 1
nPODM 4S DX
A/V
A/V
CAT-5e Cable Line Voltage Wires Line Power Feed
¡ Surface or recessed mount sensors also available
¡ Add nPOD GFX for touch screen control
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1) and qualify for enhanced digital lighting controls (C406.4)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ Each row/fixture controlled independently
¡ Optional automatic lumen compensation
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to some on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)
¡ Not required for areas without windows or with two or less luminaires
Manual Control:
¡ On/off & raise/lower control of two groups of fixtures
ADDITIONAL OPTIONS:
Bill of Materials
Symbol Qty Product # Description
1 Various; see Appendix A nLight Enabled Linear Fixture
6 Various; see Appendix A nLight Enabled Downlight Fixture
1 nPODM 4S DX Dual On/Off & Raise/Lower WallPod
1 nCM PDT 9 Dual Technology Occupancy Sensor
1 nCM ADCX DZ Automatic Dimming Control Photocell
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Manual Control (Local Switch) (C405.2.2.3)
¡ Sidelight Daylight Zone (C405.2.4.2)
¡ Enhanced Digital Lighting Controls (C406.4)
¡ Controlled Receptacles/Plug Load (C405.10)
SEQUENCE OF OPERATIONS:
12 13
WSEC: nLight Applications Guide
CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires
nPP16 D
nPP16 D
nCM PDT 9
nCM ADCX DZ
nPP20 PL
DZ 2
DZ 1
nPP16 D
nPODM 4S DX
nPP16 D
nPP16 D
A/V
A/V
CONFERENCE ROOM with 0-10V Dimming Fixtures
Bill of Materials
Symbol Qty Product # Description
5 nPP16 D Relay Module with 0-10V Dimming Output
1 nPODM 4S DX Dual On/Off & Raise/Lower WallPod
1 nCM PDT 9 Dual Technology Occupancy Sensor
1 nCM ADCX DZ Automatic Dimming Control Photocell Dual Zone
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
¡ Surface or recessed mount sensors also available
¡ Add nPOD GFX for touch screen control
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ Each row controlled independently
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to some on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Daylight zones defined by rows
¡ Not required for areas without windows or with two or less luminaires
Manual Control:
¡ On/off & raise/lower control of each row
ADDITIONAL OPTIONS:
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Sidelight Daylight Zone (C405.2.4.2)
¡ Controlled Receptacles/Plug Load (C405.10)
SEQUENCE OF OPERATIONS:
14 15
www.acuitycontrols.com • 800-535-2465
CAT-5e Cable
Line Voltage Wires
Line Power Feed
0-10V Wires
Bill of Materials
Symbol Qty Product # Description
9 Various; see Appendix A nLight Enabled Fixture
1 nPODM DX On/Off & Raise/Lower WallPod
1 nPODM 4S DXTeacher Station — 4 Scene Control Master On/Off & Raise/Lower
1 nWV PDT 16 Dual Technology Wide View Occupancy Sensor
1 nCM ADCX DZ Dual Zone Automatic Dimming Control Photocell
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
CLASSROOM with nLight Enabled Fixtures (Recessed)
¡ Surface or recessed mount sensors also available
¡ Add graphic wallpod (model nPOD GFX) for individual row and up to 16 scene control
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1) and qualify for enhanced digital lighting controls (C406.4)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ Each row/fixture controlled independently
¡ Optional automatic lumen compensation
¡ Adjustable High/Low Trim
¡ a = A/V Zone
¡ b = General Zone
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to some on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)
¡ Not required for areas without windows or with two or less luminaires
Manual Control:
¡ Master on/off & raise/lower control of entire room
¡ Master 4 scene control
¡ a = A/V Zone
¡ b = General Zone
ADDITIONAL OPTIONS:
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Sidelight Daylight Zone (C405.2.4.2)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone network installed)
¡ Controlled Receptacles/Plug Load (C405.10)
SEQUENCE OF OPERATIONS:
nWV PDT 16
nCM ADCX
nPODM 4S DX
nPP16
DZ 1A DZ 1B
DZ 2A DZ 2B
DZ 1B
DZ 2B
A B B
nPODM 4S DXnWV PDT 16
14 15
WSEC: nLight Applications Guide
CLASSROOM with 0-10V Dimming Fixtures (Distributed Relays; Recessed)
CAT-5e Cable
Line Voltage Wires
Line Power Feed
0-10V Wires
¡ Surface or recessed mount sensors also available
¡ Add graphic wallpod (model nPOD GFX) for individual row and up to 16 scene control
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ Each row controlled independently
¡ Adjustable High/Low Trim
¡ a = A/V Zone
¡ b = General Zone
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to some on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)
¡ Not required for areas without windows or with two or less luminaries
Manual Control:
¡ Master on/off & raise/lower control of entire room
¡ Master 4 scene control
¡ a = A/V Zone
¡ b = General Zone
ADDITIONAL OPTIONS:
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Sidelight Daylight Zone (C405.2.4.2)
¡ Controlled Receptacles/Plug Load (C405.10)
Bill of Materials
Symbol Qty Product # Description
6 nPP16 D Relay Module with 0-10V Dimming Output
1 nPODM DX On/Off & Raise/Lower WallPod
1 nPODM 4S DXTeacher Station — 4 Scene Control Master On/Off & Raise/Lower
1 nWV PDT 16 Dual Technology Wide View Occupancy Sensor
1 nCM ADCX DZ Automatic Dimming Control Photocell
1 nPP20 PL Plug Load (Receptacle) PowerPack 20 Amp
SEQUENCE OF OPERATIONS:
nWV PDT 16
nPP16 D
nPP16 D
nPP16 D
nPODM 4S DX
nCM ADCXnPP16
DZ 1
DZ 2
16 17
www.acuitycontrols.com • 800-535-2465
CLASSROOM with nLight Enabled Fixtures (Linear)
CAT-5e Cable
Line Voltage Wires
Line Power Feed
0-10V Wires
nCM ADCX DZ
DZ 1 a DZ 1 b
DZ 2 a DZ 2 b
DZ 1 b
DZ 2 b
a b b
nWV PDT 16
DZ 1
DZ 2
nPODM 4S DX
nWV PDT 16
EM
EM
nPP20 PL
¡ Surface or recessed mount sensors also available
¡ Add graphic wallpod (model nPOD GFX) for individual row and up to 16 scene control
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1) and qualify for enhanced digital lighting controls (C406.4)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ Each row/fixture controlled independently
¡ Optional automatic lumen compensation
¡ Adjustable High/Low Trim
¡ a = A/V Zone
¡ b = General Zone
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to some on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)
¡ Not required for areas without windows or with two or less luminaires
Manual Control:
¡ Master on/off & raise/lower control of entire room
¡ Master 4 scene control
¡ a = A/V Zone
¡ b = General Zone
ADDITIONAL OPTIONS:
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Sidelight Daylight Zone (C405.2.4.2)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone network installed)
¡ Controlled Receptacles/Plug Load (C405.10)
SEQUENCE OF OPERATIONS:
Bill of Materials
Symbol Qty Product # Description
9 Various; see Appendix A 20’, 3 Circuit, nLight Enabled, Emergency
2 nWV PDT 16 nLight Dual-Technology Occupancy Sensor
1 nCM ADCX DZ nLight Photocell Dual Zone
1 nPODM 4S DX nLight Preset Wallpod, Master Station
2 nPODM nLight Wallpod On/Off
1 nPP20 PL nLight Plug Load Controller, 20A
16 17
WSEC: nLight Applications Guide
CLASSROOM with 0-10V Dimming Fixtures (Distributed Relays; Linear)
CAT-5e Cable
Line Voltage Wires
Line Power Feed
0-10V Wires
nWV PDT 16
nPP16 D
nPP16 D
nPP16 D
nPODM 4S DXnCM ADCX DZ DZ 1
DZ 2
DZ 1 a DZ 1 b
DZ 2 a DZ 2 b
DZ 1 b
DZ 2 b
a b b
nPP16 D
nPP16 D
nPP16 D
nWV PDT 16
EM
EM
nPP16 D ER
nPP16 D ER
nPP20 PL
¡ Surface or recessed mount sensors also available
¡ Add graphic wallpod (model nPOD GFX) for individual row and up to 16 scene control
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ Each row controlled independently
¡ Adjustable High/Low Trim
¡ a = A/V Zone
¡ b = General Zone
Occupancy Control:
¡ Fixtures must be turned on manually (or optionally can be configured to some on automatically to 50%)
¡ Fixtures and Receptacles automatically turn off when room becomes vacant
Daylight Control:
¡ Smooth continuous dimming
¡ Custom grouping of fixtures into separate daylight zones (max number zones = number of fixtures)
¡ Not required for areas without windows or with two or less luminaries
Manual Control:
¡ Master on/off & raise/lower control of entire room
¡ Master 4 scene control
¡ a = A/V Zone
¡ b = General Zone
ADDITIONAL OPTIONS:
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Sidelight Daylight Zone (C405.2.4.2)
¡ Controlled Receptacles/Plug Load (C405.10)
SEQUENCE OF OPERATIONS:
Bill of Materials
Symbol Qty Product # Description
9 Various; see Appendix A 20’ 3 Circuit, Emergency
1 nWV PDT 16 Dual Technology Wide View Occupancy Sensor
1 nCM ADCX DZ Dual Zone Automatic Dimming Control Photocell
6 nPP16D nLight Power Pack with 0-10VDC Dimming
2 nPP16 D ER nLight Power Pack with 0-10VDC Dimming
1 nPODM 4S DX nLight Preset Wallpod, Master Station
2 nPODM nLight Wallpod On/Off
1 nPP20 PL nLight Plug Load Controller, 20A
18 19
www.acuitycontrols.com • 800-535-2465
STAIRWELL with nLight Enabled Fixtures
CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires
¡ Surface or recessed mount sensors also available
¡ Stairwell can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For sidelight/toplight daylight zones with three or more fixtures add ADCX option for daylight control (C405.2.4)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
ADDITIONAL OPTIONS:
Bill of Materials
Symbol Qty Product # Description
2 FixtureVarious; see appendix A, nLight Enabled Fixture w/embedded occupancy sensor
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone network installed)
SEQUENCE OF OPERATIONS:
18 19
WSEC: nLight Applications Guide
STAIRWELL with 0-10V Dimming Fixtures
nPP16
nCM 10 nCM 10
CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires
¡ Surface or recessed mount sensors also available
¡ Stairwell can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For sidelight/toplight daylight zones with three or more fixtures add ADCX option for daylight control. May require additional nPP16D Relay/ Dimming modules
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Fixtures:
¡ All fixtures are dimmable
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
ADDITIONAL OPTIONS:
Bill of Materials
Symbol Qty Product # Description
1 nPP16 D Relay Module with 0-10V Dimming Output
2 nCM PDT 10 PIR Extended Range Occupancy Sensor
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1)
SEQUENCE OF OPERATIONS:
20 21
www.acuitycontrols.com • 800-535-2465
PUBLIC RESTROOM with nLight Enabled Fixtures
nCM PDT 9 nCM PDT 9
nWSX PDT LV nWSX PDT LV
EMG EMG
CAT-5e Cable Line Voltage Wires Line Power Feed EM Power Feed
Bill of Materials (Each Restroom)
Symbol Qty Product # Description
2 Various; see Appendix A nLight Enabled Fixture
2 Various; see Appendix A nLight Enabled Emergency Fixture
1 nWSX PDT LV On/Off, Occupancy WallPod
1 nCM PDT 9 Dual Technology Occupancy Sensor
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently (per room)
¡ Optional automatic lumen compensation
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off when room becomes vacant
Manual Control:
¡ On/off control of fixtures (per room)
ADDITIONAL OPTIONS:
¡ Surface or recessed mount sensors also available
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1) and qualify for enhanced digital lighting controls (C406.4).
¡ For emergency lighting control order fixtures with -n80EMG or -n100EMG option
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone network installed)
SEQUENCE OF OPERATIONS:
EMG
20 21
WSEC: nLight Applications Guide
nCM PDT 9 nCM PDT 9
nPP16 DnPP16 D
nWSX PDT LV nWSX PDT LV
EM EM
nPP16 D ERnPP16 D ER
CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires EM Power Feed
PUBLIC RESTROOM with 0-10V Dimming Fixtures
Bill of Materials (Each Restroom)
Symbol Qty Product # Description
1 nPP16 D Relay Module with 0-10V Dimming Output
1 nPP16 D EREmergency Relay Module (UL924) with 0-10V Dimming Output
1 nWSX PDT LV On/Off & Occupancy WallPod
1 nCM PDT 9 Dual Technology Occupancy Sensor
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together (per room)
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off when room becomes vacant
Manual Control:
¡ On/off control of fixtures (per room)
ADDITIONAL OPTIONS:
¡ Surface or recessed mount sensors also available
¡ Room can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ Emergency nPP16 D ER pack only required when using a generator or inverter. Not required when using battery packs.
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Manual Control (Local Switch) (C405.2.2.3)
SEQUENCE OF OPERATIONS:
22 23
www.acuitycontrols.com • 800-535-2465
CORRIDOR with nLight Enabled Fixtures
nCM 10 nCM 10
nCM 10
nCM 10
EMG
EM
GCAT-5e Cable
Line Voltage Wires
Line Power Feed
EM Power Feed
Bill of Materials
Symbol Qty Product # Description
6 Various; see Appendix A nLight Enabled Fixture
3 (EFM) Various; see Appendix A nLight Enabled Emergency Fixture
4 nCM 10 Extended Range PIR Occupancy Sensor
Optional:
3 nPODM On/Off Wallpod
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently
¡ Optional automatic lumen compensation
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
ADDITIONAL OPTIONS:
¡ Surface or recessed mount sensors also available
¡ Space/zone can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1) and qualify for enhanced digital lighting controls (C406.4)
¡ For emergency lighting control order fixtures with -n80EMG or -n100EMG option
¡ For sidelight/toplight daylight zones with more than two luminaires, add nCM ADCX for daylight control (C405.2.4)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Enhanced Digital Lighting Controls (C406.4) (with network backbone installed)
SEQUENCE OF OPERATIONS:
EMG
22 23
WSEC: nLight Applications Guide
nCM 10 nCM 10
nCM 10
nPP16 D
nCM 10
nPP16 D ER
EM
EM
nPP16 D ER
CORRIDOR with 0-10V Dimming Fixtures
CAT-5e Cable
Line Voltage Wires
Line Power Feed
0-10V Wires
Bill of Materials
Symbol Qty Product # Description
1 nPP16D Relay Module with 0-10V Dimming Output
1 nPP16 D EREmergency Relay Module (UL924) with 0-10V Dimming Output
4 nCM 10 Extended Range PIR Occupancy Sensor
Optional:
3 nPODM On/Off Wallpod
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off or optionally can be configured to drop to low dim setting when space becomes vacant
ADDITIONAL OPTIONS:
¡ Surface or recessed mount sensors also available
¡ Space/zone can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ Emergency nPP16 DER only required when using a Gen/Invester. Not required when using battery packs
¡ For sidelight/toplight daylight zones with more than two luminaires add nCM ADCX for daylight control (C405.2.3.1/2) (may require additional nPP16 D Relay and Dimming modules)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
SEQUENCE OF OPERATIONS:
24 25
www.acuitycontrols.com • 800-535-2465
GYMNASIUM with XPoint™ Wireless
CAT-5e Cable Line Voltage Wires Line Power Feed
XPA CMRB6 XPA CMRB6 EM XPA CMRB6 XPA CMRB6 EM XPA CMRB6
XPA CMRB6 XPA CMRB6 XPA CMRB6 XPA CMRB6 XPA CMRB6
XPA CMRB6 XPA CMRB6 XPA CMRB6 XPA CMRB6 XPA CMRB6
XPA CMRB6 XPA CMRB6 XPA CMRB6 XPA CMRB6 XPA CMRB6
XPA CMRB6 XPA CMRB6 EM XPA CMRB6 XPA CMRB6 EM XPA CMRB6
RS CCS BWH
SIAC2L2
RS CCS BWH
SIAC2L2
TO BACKBONE ETHERNETSWITCH
XPABRG POE
WIRELESS BRIDGE
Bill of Materials
Symbol Qty Product # Description
25 Fixtures Generic with 0-10VDC dimming
21 XPA CMRB6 High Bay Occupancy Sensor with Photocell
4 XPW CMRB6 EM High Bay Occupancy Sensor with Photocell w/UL924
1 XPW BRG POE XPW Wireless Bridge
2 SIAC2L2 XPW Wirless Contact Closure Input
2 RS CCS BWH Contact Closure, On/Off/Dim Wall Switch
Fixtures:
¡ All fixtures are dimmable
¡ All fixtures are controlled together or independently
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off when the space becomes vacant or optionally can be configured to a low dim setting
Manual Control:
¡ On/off & raise/lower control of fixtures
ADDITIONAL OPTIONS:
¡ Space can be connected to the nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Full Auto-On via Occupancy Sensor (C405.2.1.1.2)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone network installed)
¡ Sidelight or Toplight Daylight Zones (C405.2.4)
SEQUENCE OF OPERATIONS:
EM
24 25
WSEC: nLight Applications Guide
GYMNASIUM with 0-10V Dimming Fixtures
CAT-5e Cable Line Voltage Wires Line Power Feed
nCM
6nC
M 6
nCM
6nC
M 6
nCM
6nC
M 6
nPP
16 D
nPP
16 D
nPP
16 D
nPP
16 D
nPP
16 D
nCM
AD
CX
nCM
AD
CX
nPO
DM
nPP
16 D
nPP
16 D
Bill of Materials
Symbol Qty Product # Description
25 Fixtures Generic with 0-10VDC dimming
6 nCM6 High Bay Occupancy Sensor
2 nCM ADCX nLight Photocell
5 nPP16 D nLight Power Pack w/0-10VDC
2 nPP16 D ER nLight Power Pack w/0-10VDC Emergency UL924
1 nGFX nLight LCD Touchscreen
1 nPODM nLight Wallpod On/Off operation
Fixtures:
¡ All fixtures are dimmable
¡ Each row controlled independently
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied
¡ Fixtures automatically turn off when the space becomes vacant or optionally can be configured to a low dim setting
Manual Control:
¡ On/off & raise/lower control of fixtures
¡ Graphic Wallpod (nPOD GFX) allows for individual row and up to 16 scene control
ADDITIONAL OPTIONS:
¡ Space can be connected to the nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For local integration with HVAC, add an nAR40 Auxiliary Relay Pack
SEQUENCE OF OPERATIONS:
Supports the Following Requirements:
¡ Full Auto-Off via Occupancy Sensor (C405.2.1.1.1)
¡ Full Auto-On via Occupancy Sensor (C405.2.1.1.2)
¡ Manual Control (Local Switch) (C405.2.3)
¡ Sidelight or Toplight Daylight Zones (C405.2.4)
26 27
www.acuitycontrols.com • 800-535-2465
XPA CMRB6 EMXPA CMRB6 EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
EM
EM
EM
EM
EM
XPA CMRB6 EMXPA CMRB6 EM
XPA CMRB6 EMXPA CMRB6 EM
XPA CMRB6 EMXPA CMRB6 EM
XPA CMRB6 EMXPA CMRB6 EM
XPA CMRB6 EM
XPA CMRB6 EM
XPA CMRB6 EM
XPA CMRB6 EM
XPA CMRB6 EM
RS CCS BWH
SIAC2L2
RS CCS BWH
SIAC2L2
RS CCS BWH
SIAC2L2
XPABRG POE
WIRELESS BRIDGE TO BACKBONE ETHERNETSWITCH
CAT-5e Cable Line Voltage Wires Line Power Feed
Fixtures:
¡ All fixtures are dimmable
¡ Optional automatic lumen compensation
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied or optionally can be configured to a low dim setting
¡ Fixtures automatically turn off when space becomes vacant
Manual Control:
¡ On/off & raise/lower control of fixtures
ADDITIONAL OPTIONS:
¡ Surface or recessed mount sensors also available
¡ Space can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Bill of Materials
Symbol Qty Product # Description
35 Fixture Generic with 0-10VDC dimming
20 XPA CMRB6 High Bay Occupancy Sensor with Photocell
15 XPW CMRB6 EM High Bay Occupancy Sensor with Photocell w/UL924
1 XPW BRG POE XPW Wireless Bridge
3 SIAC2L2 XPW Warless Contact Closure Input
3 RS CCS BWH Contact Closure, On/Off/Dim Wall Switch
Supports the Following Requirements:
¡ Occupancy Sensor Control Function in Warehouse (C405.2.1.2)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone network installed)
SEQUENCE OF OPERATIONS:
WAREHOUSE with XPoint™ Wireless
EM
26 27
WSEC: nLight Applications Guide
WAREHOUSE with 0-10V Dimming Fixtures
nCM 6 nCM 6
nCM 6
nCM 6
nCM 6nCM 6
nCM 6
nCM 6
nCM 6 nCM 6
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
EM
nCM 6
nCM 6
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
STORAGE RACKS
nPP16 D ERnPP16 D
nPP16 D ER
nPP16 D
nPP16 D ER
nPP16 D
nPP16 D ER
nPP16 D
nPP16 D ER
nPP16 D
nPP16 D ER
nPP16 D
CAT-5e Cable Line Voltage Wires Line Power Feed
WAREHOUSE with XPoint™ Wireless
Fixtures:
¡ All fixtures are dimmable
¡ Optional automatic lumen compensation
¡ Adjustable High/Low Trim
Occupancy Control:
¡ Fixtures automatically go to full bright when occupied or optionally can be configured to a low dim setting
¡ Fixtures automatically turn off when space becomes vacant
Manual Control:
¡ On/off & raise/lower control of fixtures
ADDITIONAL OPTIONS:
¡ Surface or recessed mount sensors also available
¡ Space can be connected to nLight backbone to enable network control or time schedules (C405.2.2.1)
¡ For local integration with HVAC, add an nAR 40 Auxiliary Relay Pack
Bill of Materials
Symbol Qty Product # Description
35 Fixture Generic 0-10VDC Dimming
12 nCM6 High Bay Occupancy Sensor
6 nPP16 D nLight Power Pack w/0-10VDC
6 nPP16 D ER nLight Power Pack w/0-10VDC Emergency UL924
1 nGFX nLight LCD Touchscreen
2 nPODM nLight Wallpod On/Off operation
SEQUENCE OF OPERATIONS:
Supports the Following Requirements:
¡ Occupancy Sensor Control Function in Warehouse (C405.2.1.2)
¡ Enhanced Digital Lighting Controls (C406.4) (with backbone network installed)
28 29
www.acuitycontrols.com • 800-535-2465
nLight Networked Lighting Control: Programmable Time Switch
Bridge
nLightECLYPSE™ECLYPSE™ECLYPSE™ ECLYPSE™
nPODM DX
nCM PDT 9
nCM ADCX nCM ADCX
nCM PDT 9 nPODM DX
CAT-5e Cable Line Voltage Wires Line Power Feed 0-10V Wires
Programmable Time Switch Control:Although not pictured within each of
the individual room design guides,
each nLight Control Zone can be
connected via an nLight backbone
to create a networked nLight lighting
control system capable of meeting
the requirements of the WSEC
programmable timeclock provision
(Section C405.2.2.1). A networked
system also enables astronomical
time clock control.
Additionally, the nLight network
backbone is required to meet the
Enhanced Digital Lighting Controls
additional efficiency package option
(C406.4).
For additional information regarding
building management integration
or demand response features,
please contact your Acuity Brands
Sales Representative.Bill of Materials
Symbol Qty Product # Description
1 nBRG 8 KIT 8-Port Backbone Bridge
1 nECY Lighting and HVAC ControllerECLYPSE™ECLYPSE™ ECLYPSE™
28 29
WSEC: nLight Applications Guide
APPENDIX A: nLight Enabled Fixtures
Product Family Fixture Series Notes
Lithonia Lighting LDN Downlight
Lithonia Lighting DOM Downlight
Gotham EVO LED Downlight
Gotham Incito LED Downlight
Lithonia Lighting IBL / IBH LED Highbay
Lithonia Lighting PTN LED Highbay - Proteon
Mark Architectural Lighting
Slot 2 LED Pendant, Recessed, Wall, Surface
Mark Architectural Lighting
Slot 4 LED Pendant, Recessed, Wall, Surface
Mark Architectural Lighting
SPR LED Perimeter
Lithonia Lighting AC Series LED Recessed
Lithonia Lighting AL SeriesLED High Performance Architectural Recessed
Lithonia Lighting AVLED Avante® LED Recessed - Direct/Indirect
Lithonia Lighting BLT Series LED Recessed
Lithonia Lighting BZL Series LED Recessed Indirect
Lithonia Lighting FSL Series LED Recessed
Lithonia Lighting RT Series LED Recessed Volumetric
Lithonia Lighting T Series LED Recessed Troffer
Lithonia Lighting VT Series LED Recessed Volumetric
Lithonia Lighting GT Series General Recessed Troffer
Lithonia Lighting SBS Series LED Shadow Box Square
Lithonia Lighting RTLX LED Surface Volumetric
Lithonia Lighting ST LED LED Surface Volumetric
ReLight RTLR LED Relight Volumetric Recessed Mount
ReLight RTLEDRT Relight Volumetric for Lensed Troffers
ReLight SBS LX LED Relight Shadow Box Square
ReLight VTL RT LED LED Relight Lensed Troffers
ReLight VTLR LED LED Relight Parabolic Lensed
Product Family Fixture Series Notes
Mark Architectural Lighting Fin LED Recessed
Mark Architectural Lighting Veil LED Recessed
Mark Architectural Lighting Whisper LED Recessed
Mark Architectural Lighting Nol LED Recessed
Peerless Mino LED Recessed
Peerless Vellum LED Recessed, Suspended
ReLight ACLX AC Series Surface Mount
ReLight T LX LED Relight Surface Mount
Lithonia Lighting ALLS LED Surface Mount
ReLight VTLXLED Relight Volumetric Surface Mount
Peerless Lightline, Indirect Suspended
Peerless Lightedge Suspended
Peerless Icetray Suspended
Peerless Cerra Suspended
Peerless Open Suspended
Peerless Prima Suspended
Peerless Naro Suspended
Peerless Tulip Suspended
Peerless Envision Suspended
Peerless Aero Suspended
Peerless Enzo Suspended
Peerless Round 2/4 LED Suspended, Wall
Peerless Square LED Suspended, Wall
Peerless Origami LED Suspended, Wall
Peerless Bruno LED Suspended, Wall
Peerless Staple Suspended, Wall
Lithonia Lighting WL Series LED Wall Bracket Surface
Note: New nLight enabled fixtures are added regularly. Please reference fixture spec sheets for nLight enabled options.
nLight Networked Lighting Control: Programmable Time Switch
30 31
www.acuitycontrols.com • 800-535-2465
APPENDIX B: Requirements Overview
Control Requirement
CodeProvision Code Summary* Recommendations for
Compliance nLight Solution Details
Manual Control(Local Switch) C405.2.3.2
Areas shall incorporate a manual control to allow occupants to turn fixtures off.
Include manual control device(s) in all room control system designs with the possible exception of public spaces where a manualswitch might hinder safety or security.
nLight WallPod devices provide a user with local control of lighting within an nLight controlled space (i.e.: nLight zone). WallPods are available in multiple styles — each with varying features and user experience.
Push-Button WallPod Graphic WallPod
Traditional tactile buttons and LED user feedback.
Full-color touch screen provides a sophisticated look and feel.
Programmable Time Switch Controls
C405.2.2.1
Each area of the building not provided with occupant sensor controls shall be provided with time switch controls. These areas must also be provided with a manual override switch.
Utilizing controls capable of being networked across an entire building enables simple compliance via a single central programmable time switch.
Individual nLight Control Zones (ie rooms) can be easily networked together across an entire building simply by connecting them into a “backbone” made up of one or more nLight Bridge devices and an nLight Gateway. The Gateway provides programmable time switch functionality for an nLight network as well as interfaces to the SensorView Suite of web-based software applications (via an Ethernet LAN / WAN connection).
Network Gateway
Additional benefits of installing an nLight backbone include remote status monitoring, iOS smartphone app control, and BMS interface capability
Full Auto-Off via Occupancy Sensor
C405.2.1.1.1Fixtures must automatically turn off within 30 minutes of all occupants leaving the space.
Always include occupancy sensors in all control system designs regardless of lighting type.
nLight occupancy sensors utilize 100% digital passive infrared (PIR) detection, come in several mounting styles, and offer multiple coverage pattern options. Additionally, nLight sensors are available with patented MicrophonicsTM dual technology detection for rooms with obstructions. Configuring for full off vs. low dimming control is done with system programming.
Manual-On, Auto On ≤ 50%, Full Automatic On
C405.2.1.1.2
Automatically controlled spaces must be controlled to either turn the lighting on to not more than 50%, or in certain spaces, to full on.
Always include occupancy sensors in all control system designs.
Reducing the level of dimmable fixtures to 50% is easiest method of compliance, however turning off 50% of lighting via circuit switching is also an option.
360° Occupancy Sensor 120° WideView Corner Sensor
Surface or recessed mounts to ceiling tiles or sheetrock/plaster.
Directly mounts in corner or to ceiling via repositionable ceiling bracket.
Shut
-Off
Cont
rol
* Note: This summary is for general information purposes only and is provided without any warranty as to accuracy, completeness, or otherwise. The user should read the applicable code sections for more complete and detailed descriptions of code requirements and exceptions and should consult with a professional engineering or other competent advisor before making any decision or taking any action based on this summary.
30 31
WSEC: nLight Applications Guide
APPENDIX B: Requirements Overview
Control Requirement
Code Provision Code Summary* Recommendation for
Compliance nLight Solution Details
Manual Lighting Reduction
C405.2.2.2
Spaces shall have a manual control that allows the occupant to reduce the connected lighting load uniformly by at least 50%.
Continuously dimmable LED (or fluorescent) fixtures and manual dimming controls are the easiest method of compliance.
nLight provides multiple options for controlling continuous dimming luminaires. This allows spaces with several lighting types and technologies to be controlled together and with a common user experience.
nLight enabled Acuity Brands Fixtures Dimming Relay Packs / Panels
Acuity offers a wide variety of LED fixtures with factory installed integrated nLight controls that provide smooth continuous dimming, and optional automatic lumen maintenance or manual task tuning.
nLight dimming relay packs / panels enable control of any 0-10VDC dimmable LED (or fluorescent) luminaire. Manual task tuning control can also be used.
Daylight-Responsive Controls
C405.2.4
Daylight-responsive controls shall be provided within each space with sidelight and toplight daylight zones.
Automatic daylight harvesting photocells that continuously adjust the level of dimming fixtures according to daylight levels provide the most effective and least distracting control.
nLight offers standalone daylight harvesting sensors as well as occupancy sensors with integrated daylight harvesting. Sensors are available in four different housings and provide continuous dimming control of any/all networked nLight enabled fixtures or dimming relay packs, each capable of being its own daylight zone.
Ceiling Mount Dimming Photocell Recessed Mount Dimming Photocell
Light
Leve
l Con
trol
* Note: This summary is for general information purposes only and is provided without any warranty as to accuracy, completeness, or otherwise. The user should read the applicable code sections for more complete and detailed descriptions of code requirements and exceptions and should consult with a professional engineering or other competent advisor before making any decision or taking any action based on this summary.
One Lithonia Way | Conyers, Georgia 30012 | Phone: 800.535.2465©2015 Acuity Brands Lighting, Inc. All rights reserved. | 04/15 | SSI_1832One Lithonia Way | Conyers, Georgia 30012 | Phone: 800.535.2465©2016 Acuity Brands Lighting, Inc. All rights reserved. | NL_5309_0816
Additional Resources:
Acuity Controls Typical Layout Drawingswww.acuitybrands.com/typicals
Use the Following Sections of the WSEC 2015 Code as Reference:Section C405.2.1.1.1 – Full Auto-Off via Occupancy Sensor
Section C405.2.1.1.2 – Manual-On or Partial-On
Section C405.2.1.1.2 – Full Automatic On
Section C405.2.2.1 – Time Switch Controls
Section C405.2.2.2 – Manual Lighting Reduction
Section C405.2.4 – Daylight-Responsive Controls
Section C406.4 – Enhanced Digital Lighting Controls
Section C405.2.1 – Occupancy Sensor Controls
Section C405.10 – Controlled Receptacles