    DEPARTMENT OF THE NAVY NAVAL FACILITIES ENGINEERING COMMAND, HAWAII

    400 MARSHALL ROADJBPHH, HAWAII 96860-3139

    REQUEST FOR PROPOSAL (RFP)25 January 2012

    FOR WORK REQUEST # 091050 REPLACE UPS SYSTEM B1322, JOINT BASEPEARL HARBOR HICKAM, HAWAII

    HUBZONE MACC Contractors:ENVIRONET INC. N62478-10-D-4020PIONEER CONTRACTING CO., LTD N62478-10-D-4021RAASS BROTHERS INC. N62478-10-D-4022SAN JUAN CONSTRUCTION, INC. N62478-10-D-4023TOMCO CORP. N62478-10-D-4024

    Encl: (1) PDF of NAVFAC Hawaii Drawing Nos. 19027413 through19027419

    (2) UFGS Specifications(3) Price Proposal Schedule dated 25 January 2012

    A. A site visit will be held on:

    Date: Thursday, 2 February 2012Time: 10:00 a.m.Place: Meet at project site

    For contractor personnel that need a one-day base pass for thesite visit, please provide a list of names and their respective

    companies to Richard Griffin ([email protected]) nolater than 12:00 p.m. on 27 January 2012 .

    B. Request you submit a task order proposal in accordance withthe following:

    1. Scope of Work: The Government is soliciting to award atask order to Replace UPS System, Bldg 1322 in accordance withDrawings and Specifications (PDF) enclosures (1 & 2).

    2. Performance Period: The task order completion date will

    be established at 180 calendar days from award. The contractorshall commence work in accordance with FAR 52.211-10,Commencement, Prosecution and Completion of Work (Apr 1984).

    3 . Proposal Format: a. Complete the Price Proposal Schedule dated

    25 January 2012 , enclosure (3), and submit with your proposal.b. Provide a narrative of the methodology to perform

    and complete the work.

    4. Davis-Bacon Act: Comply with the Davis-Bacon Act

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    2/43

    General Decision (minimum wage rates and fringe benefits)included with the contract award of the Contractors currentoption period. It is valid throughout the option period of thecontract.

    5. Liquidated Damages: In accordance with FAR clause52.211-12, Liquidated DamagesConstruction (Sep 2000), if theContractor fails to complete the work within the time specifiedin the task order, the Contractor shall pay liquidated damagesas stated in clause for each calendar day of delay until thework is completed and the Government obtains beneficialoccupancy.

    6. Bonds: Bid Bonds are required; within 15 calendar daysafter the task order is awarded, the Contractor is required tosubmit Performance and Payment Bonds, each equal to the amountof the task order.

    7. Invoicing: In accordance with DFARS 252.232-7003,Electronic Submission of Payment Requests, this task order

    requires the use of the DoD Wide Area Workflow (WAWF) system forthe submission of invoices in accordance with NFAS 5252.232-9301, Invoicing Procedures Electronic (Nov 2009).

    8. Requests for Information (RFIs): Contractor shall emailtheir RFIs to Richard Griffin ([email protected]) nolater than 12:00 p.m. on 13 February 2012 .

    9. Proposal Due Date: Contractor shall email their proposalto Richard Griffin ([email protected]) no later than2:00 p.m. on 27 February 2012 .

    If you have any questions or comments regarding the RFP, pleasecontact Richard Griffin ([email protected]) ortelephone 474-3220 ext 298

    Enclosure (3)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    3/43

    ENCLOSURE (1

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    4/43

    ENCLOSURE (1

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    5/43

    ENCLOSURE (1

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    6/43

    ENCLOSURE (1

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    7/43

    ENCLOSURE (1

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    8/43

    ENCLOSURE (1

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    9/43

    ENCLOSURE (1

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    10/43

    SECTION TABLE OF CONTENTS

    DIVISION 26 - ELECTRICAL

    SECTION 26 33 53.00 20

    UNINTERRUPTIBLE POWER SUPPLY (UPS)

    04/08PART 1 GENERAL

    1.1 REFERENCES1.2 RELATED REQUIREMENTS1.3 DEFINITIONS1.4 SUBMITTALS1.5 PERFORMANCE REQUIREMENTS

    1.5.1 Normal Operation1.5.2 Emergency Operation (Loss or deviation of AC Input Power)1.5.3 Return of AC Input Power Source1.5.4 Failure of AC Input Power to Return1.5.5 Transfer to Bypass AC Power Source1.5.6 Retransfer to Inverter1.5.7 UPS Bypass Maintenance1.5.8 Battery Maintenance

    1.6 QUALITY ASSURANCE1.6.1 UPS Drawings1.6.2 UPS Installation1.6.3 Work Plan1.6.4 Factory Test Plan1.6.5 Performance Test Plan1.6.6 Factory Tests Report1.6.7 Performance Tests Report1.6.8 Regulatory Requirements1.6.8.1 Reference Standard Compliance1.6.8.2 Independent Testing Organization Certificate1.6.9 Standard Products1.6.9.1 Alternative Qualifications1.6.9.2 Material and Equipment Manufacturing Date

    1.7 DELIVERY AND STORAGE1.8 PROJECT/SITE CONDITIONS

    1.8.1 Environmental Conditions1.8.2 Sound Pressure Levels1.8.3 Verification of Dimensions

    1.9 SPECIAL TOOLS1.10 OPERATION AND MAINTENANCE MANUALS

    1.10.1 Additions to UPS Operation and Maintenance Manuals1.10.2 Spare Parts

    1.11 WARRANTY

    PART 2 PRODUCTS

    2.1 UPS SYSTEM DESCRIPTION2.1.1 Semiconductor Fusing2.1.2 Control Power2.1.3 EMI/RFI Protection2.1.4 Internal Wiring2.1.5 Internal Assembly2.1.6 Cabinets

    2.1.6.1 Cabinet Finish2.1.6.2 Live Parts (300 Volts and Above)2.1.6.3 Drawout Assemblies

    2.1.7 Safety

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    11/43

    2.1.8 UPS System Load Profile2.2 UPS SYSTEM RATINGS

    2.2.1 System Capacity2.2.2 Battery Capacity2.2.3 Static Switch2.2.4 Module Bus Bracing2.2.5 AC Input

    2.2.6 AC Output2.2.7 Transient Response2.2.7.1 Voltage Transients2.2.7.2 Frequency

    2.2.8 Efficiency2.3 UPS MODULE

    2.3.1 General Description2.3.1.1 Interchangeability

    2.3.2 Rectifier/Charger Unit2.3.2.1 Input Protective Device2.3.2.2 Surge Protection2.3.2.3 Input Isolation Transformer2.3.2.4 Power Walk-In2.3.2.5 Sizing2.3.2.6 Battery Charging Current

    2.3.2.7 DC Ripple2.3.2.8 DC Voltage Adjustment2.3.2.9 Battery Isolation Protective Device

    2.3.3 Inverter Unit2.3.3.1 Output Overload2.3.3.2 Output Frequency Control2.3.3.3 Output Protective Device2.3.3.4 Output Transformer

    2.3.4 External Protection2.3.5 Internal Protection

    2.4 STATIC BYPASS TRANSFER CIRCUIT2.4.1 Uninterrupted Transfer2.4.2 Interrupted Transfer2.4.3 Manual Transfer2.4.4 Automatic Uninterrupted Forward Transfer2.4.5 Forced Transfer2.4.6 Overload Ratings2.4.7 Static Switch Disconnect

    2.5 MAINTENANCE BYPASS SWITCH2.5.1 General2.5.2 Load Transfer2.5.3 Load Bank Protection Device

    2.6 MODULE CONTROL PANEL2.6.1 Module Meters

    2.6.1.1 Monitored Functions2.6.1.2 Meter Construction

    2.6.2 Module Controls2.6.3 Module Alarm Indicators2.6.4 Module Emergency OFF Button

    2.7 SELF-DIAGNOSTIC CIRCUITS2.8 REMOTE MONITORING PANEL2.8.1 Indicators2.8.2 Audible Alarm

    2.9 COMMUNICATIONS AND DATA ACQUISITION2.9.1 Emergency Control Contacts2.10 TEMPERATURE CONTROL

    2.10.1 General2.10.2 Blower Power Source2.10.3 Temperature Sensors

    2.11 BATTERY SYSTEM

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    12/43

    2.11.1 General2.11.2 Battery Ratings2.11.3 Battery Construction2.11.4 Battery Cabinet2.11.5 Battery Rack2.11.6 Cell-Terminal Covers2.11.7 Battery Disconnect2.11.8 Seismic Requirements2.11.9 Battery Monitor

    2.12 FACTORY TESTING2.12.1 Transient Tests2.12.2 Efficiency Tests

    2.13 CABLE LUGS AND TERMINATIONS2.13.1 Cable Lugs2.13.2 Terminations

    2.14 INSPECTION2.15 FIELD FABRICATED NAMEPLATES2.16 MANUFACTURER'S NAMEPLATES2.17 FACTORY APPLIED FINISH

    PART 3 EXECUTION

    3.1 INSTALLATION3.1.1 Control Cable3.1.2 Grounding Conductor3.1.3 UPS Output Conductors3.1.4 DC Power Conductors3.1.5 Seismic Protection3.1.6 Conduit Entries3.1.7 Battery Rack Assembly3.1.8 Battery Cabinet Assembly3.1.9 Battery Installation

    3.2 FIELD QUALITY CONTROL3.2.1 Installation Preparation3.2.2 Initial Inspection and Tests3.2.3 Performance Tests

    3.2.3.1 UPS Unit Performance Tests3.2.3.2 Emergency Generator Operation3.2.3.3 Battery Performance Test (Constant KW)

    3.3 DEMONSTRATION3.3.1 Instructing Government Personnel

    3.4 FINAL ADJUSTMENTS3.5 NAMEPLATE MOUNTING3.6 FIELD APPLIED PAINTING3.7 DISPOSAL

    -- End of Section Table of Contents -

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    13/43

    SECTION 26 33 53.00 20

    UNINTERRUPTIBLE POWER SUPPLY (UPS) 04/08

    PART 1 GENERAL

    1.1 REFERENCES

    The publications listed below form a part of this specification to the extentreferenced. The publications are referred to within the text by the basicdesignation only.

    ACOUSTICAL SOCIETY OF AMERICA (ASA)

    ASA S1.4 (1983; Amendment 1985; R 2006) Specificationfor Sound Level Meters (ASA 47)

    ASTM INTERNATIONAL (ASTM)

    ASTM B 173 (2001a; R 2007e1) Standard Specificationfor Rope-Lay-Stranded Copper ConductorsHaving Concentric-Stranded Members, forElectrical Conductors

    ASTM D 709 (2001; R 2007) Laminated ThermosettingMaterials

    INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS (IEEE)

    IEEE 100 (2000; Archived) The AuthoritativeDictionary of IEEE Standards Terms

    IEEE 450 (2002; R 2003; INT1 2005) RecommendedPractice for Maintenance, Testing, andReplacement of Vented Lead-Acid Batteriesfor Stationary Applications

    IEEE C2 (2007; TIA 2007-1; TIA 2007-2; TIA 2007-3;TIA 2007-4; TIA 2007-5; Errata 2006-1; Errata2007-2; Errata 2009-3 ) National ElectricalSafety Code

    IEEE C57.110 (1998; Errata 2002; R 2004; R 2008)Recommended Practice for EstablishingLiquid-Filled and Dry-Type Power andDistribution Transformer Capability When

    Supplying Non-sinusoidal Load CurrentsIEEE C62.41.1 (2002; R 2008) Guide on the Surges

    Environment in Low-Voltage (1000 V andLess) AC Power Circuits

    IEEE C62.41.2 (2002) Recommended Practice onCharacterization of Surges in Low-Voltage(1000 V and Less) AC Power Circuits

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    14/43

    INTERNATIONAL ELECTRICAL TESTING ASSOCIATION (NETA)

    NETA ATS (2009) Standard for Acceptance TestingSpecifications for Electrical PowerEquipment and Systems

    INTERNATIONAL ORGANIZATION FOR STANDARDIZATION (ISO)

    ISO 9001 (2000; R 2008; Corr 1 2009) QualityManagement Systems- Requirements

    NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION (NEMA)

    NEMA 250 (2008) Enclosures for Electrical Equipment(1000 Volts Maximum)

    NEMA PE 1 (2003) Uninterruptible Power Systems (UPS)Specification and Performance Verification

    NATIONAL FIRE PROTECTION ASSOCIATION (NFPA)

    NFPA 70 (2008; TIA 08-1) National Electrical Code

    UNDERWRITERS LABORATORIES (UL)

    UL 1449 (2006; R thru 2009) Surge Protective Devices

    UL 1778 (2005; R 2006) Uninterruptible Power Systems

    1.2 RELATED REQUIREMENTS

    Section 26 08 00 APPARATUS INSPECTION AND TESTING applies to this section,with the additions and modifications specified herein.

    1.3 DEFINITIONS

    Unless otherwise specified or indicated, electrical and electronics termsused in these specifications, and on the drawings, shall be as defined inIEEE 100.

    1.4 SUBMITTALS

    Government approval is required for submittals with a "G" designation;submittals not having a "G" designation are for Contractor Quality Controlapproval. The following shall be submitted in accordance with Section 01 3300 SUBMITTAL PROCEDURES:

    SD-02 Shop Drawings

    UPS Drawings; G

    UPS Installation; G

    SD-03 Product Data

    UPS Module; G

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    15/43

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    16/43

    same time, an alarm shall sound to alert operating personnel and a troublesignal shall be sent over the communication network, allowing startup of asecondary power source or orderly shutdown of the critical load.

    1.5.3 Return of AC Input Power Source

    When stable ac input power source returns the rectifier/charger shall resumeoperation and shall simultaneously supply the inverter with dc power andrecharge the battery. This shall be an automatic function and shall cause nodisturbance to the critical load.

    1.5.4 Failure of AC Input Power to Return

    Should the ac input power fail to return before the battery voltage reachesthe discharge limit, the UPS system shall disconnect from the critical loadto safeguard the battery.

    1.5.5 Transfer to Bypass AC Power Source

    When the UPS controller senses an overload or degradation of the inverter

    output, the bypass switch shall automatically transfer the critical loadfrom the inverter output to the bypass ac power source without aninterruption of power. If the bypass ac power source is outside ofspecified tolerance limits, the UPS and the critical load shall shut down.

    1.5.6 Retransfer to Inverter

    The static bypass switch shall be capable of automatically retransferringthe load back to the inverter output after the inverter output has returnedto normal conditions. Retransfer shall only occur if the two sources aresynchronized.

    1.5.7 UPS Bypass Maintenance

    Manual closure of the maintenance bypass switch shall transfer the criticalload from the inverter output to the bypass ac power source withoutdisturbing the critical load bus. UPS module shall be capable of manualreturn to normal operation after completion of maintenance.

    1.5.8 Battery Maintenance

    The battery protective device shall provide the means of disconnecting thebattery from the rectifier/charger and inverter for maintenance. The UPSmodule shall continue to function and meet the performance criteriaspecified except for the battery back-up time function.

    1.6 QUALITY ASSURANCE

    The manufacturer shall have a documented quality assurance programincluding:

    a. Inspections of incoming parts, modular assemblies and final product.

    b. Final test procedure for the product including proof of performancespecifications.

    c. On-site test procedure shall include an inspection of controls andindicators after installation of the equipment.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    17/43

    d. ISO 9001 quality certification.

    1.6.1 UPS Drawings

    Detail drawings consisting of a complete list of equipment and materials,manufacturer's descriptive and technical literature, battery sizingcalculations per IEEE 485, installation instructions, single-line diagrams,ladder-type schematic diagrams, elevations, layout drawings, and detailsrequired to demonstrate that the system has been coordinated and willfunction properly as a unit.

    1.6.2 UPS Installation

    Include wiring diagrams and installation details of equipment indicatingproposed location, layout and arrangement, control panels, accessories,piping, ductwork, and other items that must be shown to ensure acoordinated installation. Wiring diagrams shall identify circuit terminalsand indicate the internal wiring for each item of equipment and theinterconnection between each item of equipment. Drawings shall indicateadequate clearance for operation, maintenance, and replacement of operating

    equipment devices. Submittals shall include the nameplate data, size, andcapacity. Submittals shall also include applicable federal, military,industry, and technical society publication references.

    1.6.3 Work Plan

    Submit 6 copies of schedules of dates for factory tests, installation,field tests, and operator training for the UPS system. Furnish a list ofinstrumentation equipment for factory and field test reports.

    1.6.4 Factory Test Plan

    Submit 6 copies of factory test plans and procedures at least 21 calendardays prior to the tests being conducted. Provide detailed description oftest procedures, including test equipment and setups, to be used to ensurethe UPS meets the performance specification and explain the test methods tobe used. As a minimum, the test procedures shall include the test requiredunder the paragraph entitled "Factory Testing."

    1.6.5 Performance Test Plan

    Submit 6 copies of test plans and procedures at least 15 calendar daysprior to the start of field tests. Provide detailed description and datesand times scheduled for performance of tests, and detailed description oftest procedures, including test equipment (list make and model and providefunctional description of the test instruments and accessories) and setupsof the tests to be conducted to ensure the UPS meets the performance

    specification. Explain the test methods to be used. As a minimum, the testprocedures shall include the tests required under the paragraph entitled"Performance Tests."

    1.6.6 Factory Tests Report

    Submit 6 copies of factory test report within 45 calendar days aftercompletion of tests. Receive approval of test prior to shipping unit.Factory test reports shall be signed by an official authorized to certifyon behalf of the UPS manufacturer of that the system meets specified

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    18/43

    requirements in accordance with the requirements set forth in paragraphentitled "Factory Testing". Test reports in shall be in booklet formtabulating factory tests and measurements performed, upon completion andtesting of the installed system. Reports shall state the Contractor's nameand address, the name of the project and location, and list the specificrequirements which are being certified.

    1.6.7 Performance Tests Report

    Submit report of test results as specified by paragraph entitled"Performance Tests" within 15 calendar days after completion oftests. Field test reports shall be signed by an official authorized tocertify on behalf of the UPS manufacturer that the system meets specifiedrequirements in accordance with the requirements set forth in paragraphentitled "Performance Tests". Test reports in shall be in booklet formtabulating factory tests and measurements performed, upon completion andtesting of the installed system. Reports shall state the Contractor's nameand address, the name of the project and location, and list the specificrequirements which are being certified.

    1.6.8 Regulatory Requirements

    In each of the publications referred to herein, consider the advisoryprovisions to be mandatory, as though the word, "shall" had beensubstituted for "should" wherever it appears. Interpret references inthese publications to the "authority having jurisdiction," or words ofsimilar meaning, to mean the Contracting Officer. Equipment, materials,installation, and workmanship shall be in accordance with the mandatoryand advisory provisions of NFPA 70 unless more stringent requirements arespecified or indicated.

    1.6.8.1 Reference Standard Compliance

    Where equipment or materials are specified to conform to industry andtechnical society reference standards of the organizations such as

    American National Standards Institute (ANSI), American Society for Testingand Materials (ASTM), National Electrical Manufacturers Association(NEMA), Underwriters Laboratories (UL), and Association of EdisonIlluminating Companies (AEIC), submit proof of such compliance. The labelor listing by the specified organization will be acceptable evidence ofcompliance.

    1.6.8.2 Independent Testing Organization Certificate

    In lieu of the label or listing, submit a certificate from an independenttesting organization, competent to perform testing, and approved by theContracting Officer. The certificate shall state that the item has been

    tested in accordance with the specified organization's test methods andthat the item complies with the specified organization's referencestandard.

    1.6.9 Standard Products

    Provide materials and equipment that are products of manufacturersregularly engaged in the production of such products which are of equalmaterial, design and workmanship. Products shall have been in satisfactorycommercial or industrial use for 2 years prior to bid opening. The 2-year

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    19/43

    period shall include applications of equipment and materials under similarcircumstances and of similar size. The product shall have been on sale onthe commercial market through advertisements, manufacturers' catalogs, orbrochures during the 2-year period. Where two or more items of the sameclass of equipment are required, these items shall be products of a singlemanufacturer; however, the component parts of the item need not be theproducts of the same manufacturer unless stated in this section. Equipmentshall be supported by a service organization that is, in the opinion ofthe Contracting Officer, reasonably convenient to the site.

    1.6.9.1 Alternative Qualifications

    Products having less than a 2-year field service record will be acceptableif a certified record of satisfactory field operation for not less than6000 hours, exclusive of the manufacturers' factory or laboratory tests,is furnished.

    1.6.9.2 Material and Equipment Manufacturing Date

    Products manufactured more than 2 years prior to date of delivery to site

    shall not be used, unless specified otherwise.

    1.7 DELIVERY AND STORAGE

    Equipment placed in storage shall be protected from humidity andtemperature variations, moisture, water intrusion, dirt, dust, or othercontaminants. In harsh environments where temperatures exceed non-operational parameters established within this specification, the equipmentstorage facility shall be environmentally controlled to ensure temperatureparameters are within equipment specification. Documentation of same shallbe provided to the Government when storage is implemented.

    1.8 PROJECT/SITE CONDITIONS

    1.8.1 Environmental Conditions

    The UPS and battery system shall be capable of withstanding any combinationof the following external environmental conditions without mechanical orelectrical damage or degradation of operating characteristics.

    a. Operating altitude: Sea level to 1,000 meters 3,300 ft. (Systemsapplied at higher altitudes shall be derated in accordance with themanufacturer's instructions).

    b. Non-operating altitude: Sea level to 11,000 meters 36,000 ft.

    c. Operating ambient temperature range: 0 to 40 degrees C 32 to 104degrees F. Range for batteries is 10 to 30 degrees C 50 to 86degrees F.

    d. Non-operating and storage ambient temperature range: Minus 20 toplus 50 degrees C Minus 4 to plus 122 degrees F.

    e. Operating relative humidity: 0 to 95 percent, withoutcondensation.

    1.8.2 Sound Pressure Levels

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    20/43

    Sound pressure levels produced by the UPS, when operating under full ratedload, at a distance of 1 meter 39 inches in any direction from the perimeterof the unit, shall not exceed 65 dB as measured on the A scale of a Type 1sound level meter at slow response conforming to ASA S1.4.

    1.8.3 Verification of Dimensions

    The Contractor shall become familiar with details of the work, verifydimensions in the field, and shall advise the Contracting Officer of anydiscrepancy before performing the work.

    1.9 SPECIAL TOOLS

    Provide one set of special tools, calibration devices, and instrumentsrequired for operation, calibration, and maintenance of the equipment.

    1.10 OPERATION AND MAINTENANCE MANUALS

    1.10.1 Additions to UPS Operation and Maintenance Manuals

    In addition to requirements of Data Package 5, include the followings onthe actual UPS system provided:

    a. An outline drawing, front, top, and side views.

    b. Prices for spare parts and supply list.

    c. Routine and field acceptance test reports.

    d. Date of Purchase.

    e. Corrective maintenance procedures.

    f. Test measurement levels with specific test points.

    1.10.2 Spare Parts

    Furnish the following spare parts, of the same material and workmanship,meeting the same requirements, and interchangeable with the correspondingoriginal parts.

    a. Fuses: Two of each type and rating.

    b. Circuit boards: One circuit board for each critical circuit.

    c. Air Filters: One set of filters.

    All items on the spare parts list shall be stocked on island and madeavailable for 24 hour purchase.

    1.11 WARRANTY

    The equipment items shall be supported by service organizations which arereasonably convenient to the equipment installation in order to rendersatisfactory service to the equipment on a regular and emergency basisduring the warranty period of the contract.

    PART 2 PRODUCTS

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    21/43

    2.1 UPS SYSTEM DESCRIPTION

    The UPS system shall conform to UL 1778 and shall consist of UPS module,battery system, battery protective device, static bypass transfer switch,controls and monitoring. Input ac power shall be connected to the normalsource ac input of the UPS module. Alternate power source shall beconnected to bypass/maintenance bypass. The battery shall be connected tothe dc input of the UPS module through the battery protective device. Theac output of the UPS system shall be connected to the critical loads.

    2.1.1 Semiconductor Fusing

    Power semiconductors shall be fused with fast-acting fuses to preventcascaded or sequential semiconductor failures. Indicator lamp or displaypanel denoting blown fuse conditions shall be readily observable by theoperator without removing panels or opening cabinet doors.

    2.1.2 Control Power

    Provide dual control power supplies. [Control power shall be derived fromtwo sources, input and output, with automatic selective control. ] Thecontrol power circuit shall have suitable protection, appropriately markedand located in the immediate vicinity of the input protective device.

    2.1.3 EMI/RFI Protection

    The components and the system shall be designed to minimize the emission ofelectromagnetic waves that may cause interference with other equipment.

    2.1.4 Internal Wiring

    Wiring practices, materials, and coding shall be in accordance with therequirements of NFPA 70, OSHA, and other applicable standards. Wire runsshall be protected in a manner which separates power and control wiring.Control wiring shall be minimum No. 16 AWG extra-flexible stranded copper.Logic-circuit wiring may be smaller. Ribbon cables shall be minimum No. 22

    AWG. Control wiring shall have permanently attached wire numbers.

    Busbar and wiring shall be tinned copper. Seal all bare copper openings.

    2.1.5 Internal AssemblyThe printed circuit board (PCB) subassemblies shall be mounted in pull-outand/or swing-out trays where feasible. Cable connections to the trays shallbe sufficiently long to allow easy access to all components. Where notfeasible to mount PCB subassemblies in pull-out or swing-out trays, theyshall be firmly mounted inside the enclosure. Every PCB subassembly shall bemonitored. Self-test and diagnostic circuitry shall be included in the logiccircuits such that a fault can be isolated down to the PCB subassemblylevel.

    2.1.6 Cabinets

    UPS system shall be installed in cabinets of heavy-duty structure meetingthe NEMA PE 1 standards for floor mounting. UPS module cabinet shall bestructurally adequate for forklift handling or lifting. Removable liftingeyes shall be provided on top of each cabinet. UPS module cabinet shallhave hinged and lockable doors on the front only, with assemblies andcomponents accessible from the front. Doors shall be key lockable.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    22/43

    Operating controls shall be located outside the locked doors. Input,output, and battery cables shall be installed through the top or bottom ofthe cabinet.

    2.1.6.1 Cabinet Finish

    Equipment cabinet shall be cleaned, primed and painted in the manufacturer'sstandard colors, in accordance with accepted industry standards. Cabinetsshall be labeled in accordance with NFPA 70 for arc flash hazard withwarning sign reading: "Warning-Potential Arc Flash Hazard. Appropriate PPEand Tools Required when working on this equipment" or similar wording.

    2.1.6.2 Live Parts (300 Volts and Above)

    Live parts (300 volts and above) that are exposed when front access doorsare open shall be adequately protected or covered to minimize the chance ofaccidental contact.

    2.1.7 Safety

    UPS shall be equipped with instruction plates including warnings andcautions, suitably located, and describing any special or importantprocedures to be followed in operating and servicing the equipment. Thecontrol panel display shall also provide warning messages prior toperforming a critical function.

    2.1.8 UPS System Load Profile

    The UPS system shall be compatible with the load characteristics defined inthe LOAD PROFILE below and load configuration. Compensation for UPS/loadinteraction problems resulting from nonlinear loads or transformer and motorinrush shall be provided.

    LOAD PROFILE

    Type of load: Computer and Electronic losds.

    Size of load: 100 kVA .

    Switching pattern: unswitched.

    Transient characteristics: inrush current magnitude of [_____] timessteady state rms current for duration of [___] cycle; range of powerfactor variation of [_____] to [_____] [lagging][leading]; voltage dipof [_____]%.

    Steady-state characteristics: [0.8 lagging][0.9 lagging][1.0][_____]power factor.

    Special factors: [harmonic characteristics - Total Harmonic Distortion[___]%][high elevation][nonstandard input and output voltages][_____].

    2.2 UPS SYSTEM RATINGS

    Unless stated otherwise, the parameters listed are under full output loadat 0.9 power factor, with batteries fully charged and floating on the dcbus and with nominal input voltage.

    2.2.1 System Capacity

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    23/43

    100 kVA.

    2.2.2 Battery Capacity

    Discharge time to end voltage: 30 minutes, at 25 degrees C 77 degrees F.End voltage at full discharge shall be 1.67 volts per cell. Battery shallbe capable of delivering 150 percent of full rated UPS load at initialstart-up.

    Provide two strings of batteries for each UPS, in two separate cabinets,wired in a parallel redundant setup. The system shall have the capabilityof temporarily disconnecting one battery cabinet and still provide (limited)UPS power.

    2.2.3 Static Switch

    22,000 amperes symmetrical interrupting capacity.

    2.2.4 Module Bus Bracing

    Braced for 22,000 amperes symmetrical interrupting capacity.

    2.2.5 AC Input

    a. Voltage 208Y/120 volts.

    b. Number of phases: 3-phase, 4-wire, plus ground.

    c. Voltage Range: Plus 10 percent, minus 20 percent, without affectingbattery float voltage or output voltage.

    d. Frequency: 60 Hz, plus or minus 5 percent.

    e. Power walk-in: 20 percent to 100 percent over 10 to 20 seconds.

    f. Total harmonic current distortion (THD) reflected into the primary line:5 percent maximum.

    g. Transformer sub-cycle inrush: 4 to 8 times full load rating.

    h. Input surge protection: per IEEE C62.41.1 and IEEE C62.41.2.

    i. Input power factor: Lagging from 1-100 percent load.

    2.2.6 AC Output

    a. Voltage 208Y/120 volts.

    b. Number of phases: 3-phase, 4-wire, plus ground.

    c. Voltage regulation:

    (1) Balanced load: Plus or minus 1.0 percent.

    (2) 50 percent load imbalance, phase-to-phase: Plus or minus 2 percent.

    (3) No-load voltage modulation: Plus or minus 1 percent.

    (4) Voltage drift: Plus or minus 1 percent over any 30 day interval (orlength of test) at stated ambient conditions.

    d. Voltage adjustment: Plus or minus 5 percent manually.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    24/43

    e. Frequency: 60 Hz.

    f. Frequency regulation: Plus or minus 0.1 percent.

    g. Frequency drift: Plus or minus 0.1 percent over any 24 hour interval (orlength of test) at stated ambient conditions when on internaloscillator.

    h. Harmonic content (RMS voltage): Voltage THD shall be a maximum of 2percent with 100 percent linear load and 5 percent with 100 percentnonlinear load and a crest factor of less than 3 to 1.

    i. Load power factor operating range: 1.0 to 0.8 lagging.

    j. Phase displacement:

    (1) Balanced load: Plus or minus 1 degree of bypass input.

    (2) 50 percent load imbalance phase-to-phase: Plus or minus 3 degrees ofbypass input.

    k. Wave-form deviation factor: 5 percent at no load.

    l. Overload capability (at full voltage) (excluding battery):

    (1) 125 percent load for 10 minutes.

    (2) 150 percent load for 60 seconds.

    (3) 300 percent load for one cycle after which it shall be currentlimited to 150 percent until fault is cleared or UPS goes to bypass.

    2.2.7 Transient Response

    2.2.7.1 Voltage Transients

    a. 100 percent load step: Plus or minus 5 percent.

    b. Loss or return of ac input: Plus or minus 1 percent.

    c. Automatic transfer of load from UPS to bypass: Plus or minus 4 percent.

    d. Manual retransfer of load from bypass to UPS: Plus or minus 4 percent.

    e. Response time: Recovery to 99 percent steady-state condition within 20milliseconds after any of the above transients.

    2.2.7.2 Frequency

    a. Transients: Plus or minus 0.6 Hz maximum.

    b. Slew Rate: 1.0 Hz maximum per second.

    2.2.8 Efficiency

    a. Minimum Efficiency: 99 percent over the range of 10% to 100% load.The UPS shall continuously monitor the voltage and frequency of the bypasssource. When the source parameters are within acceptable limits, the UPSwill utilize a minimal/optimal combination of its internal subsystem toensure acceptable power is always delivered to the critical load, at asystem efficiency of 99% or greater, over the range of 10% to 100% load.The energy saver system shall be enabled by the user, and shall be

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    25/43

    adjustable. It shall incorporate a High Alert mode to automatically(without user intervention)provide maximum power conditioning any timebypass source variation levels exceed preset, adjustable limits. Whenenergy saver system is utilized, the UPS must attenuate ANSI C62.41-typeline transients to within IEC and ITIC limits. The energy saver systemshall be able to distinguish between upstream (utility) faults anddownstream (load) faults, and react appropriately to protect and supportthe critical load, without interruption.

    2.3 UPS MODULE

    2.3.1 General Description

    UPS module shall consist of a rectifier/charger unit and a 3-phase inverterunit with their associated transformers, synchronizing equipment, protectivedevices, surge suppression, and accessories as required for operation.

    2.3.1.1 Interchangeability

    The subassemblies in one UPS module shall be interchangeable with thecorresponding modules within the same UPS, and from one UPS system toanother of identical systems.

    2.3.2 Rectifier/Charger Unit

    Rectifier/charger unit shall be solid state and shall provide regulateddirect current to the dc bus, supplying power to the inverter and chargingthe battery plant.

    2.3.2.1 Input Protective Device

    Rectifier/charger unit shall be provided with an input protective device.The protective device shall be sized to accept simultaneously the full-rated load and the battery recharge current. The protective device shallbe capable of shunt tripping and shall have 22,000 amperes symmetricalinterrupting rating. The protective device shall have provision forlocking in the "off" position.

    2.3.2.2 Surge Protection

    A surge suppression device shall be installed at the UPS input to protectagainst lightning and switching surges. Internal components shall beprotected from surges that enter at each ac input connection including maininput, static bypass transfer switch, and maintenance bypass/isolationswitch. Surge suppressors shall protect internal components according toIEEE C62.41.1 and IEEE C62.41.2, Category B. Surge suppressors shall be UL1449 approved to fail in "safe" mode.

    2.3.2.4 Power Walk-InRectifier/charger unit shall be protected by a power walk-in feature suchthat when ac power is returned to the ac input bus, the total initial powerrequirement will not exceed 20 percent of the rated full load current. Thisdemand shall increase gradually to 100 percent of the rated full loadcurrent plus the battery charging current over the specified time interval.

    2.3.2.5 Sizing

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    26/43

    Rectifier/charger unit shall be sized for the following two simultaneousoperating conditions:

    a. Supplying the full rated load current to the inverter.

    b. Recharging a fully-discharged battery to 95 percent of rated ampere-hourcapacity within ten times the discharge time after normal ac power is

    restored.2.3.2.6 Battery Charging Current

    a. Primary current limiting: Battery-charging current shall be voltageregulated and current limited. The battery-charging current limit shallbe separately adjustable from 2 percent to 25 percent of the maximumdischarge current. After the battery is recharged, the rectifier/chargerunit shall maintain the battery at full float charge until the nextoperation under input power failure. Battery charger shall be capable ofproviding equalizing charge to the battery.

    2.3.2.7 DC Ripple

    Rectifier/charger unit shall minimize ripple current and voltage suppliedto the battery; the ripple current into the battery shall not exceed 3percent RMS of the inverter input rated current; the ripple voltage intothe battery shall not exceed 2 percent RMS of the float voltage.

    2.3.2.8 DC Voltage AdjustmentRectifier/charger unit shall have manual means for adjusting dc voltage forbattery equalization, to provide voltage within plus 10 percent of nominalfloat voltage.

    2.3.2.9 Battery Isolation Protective Device

    Module shall have a dc protective device to isolate the module from thebattery system. The protective device size and interrupting rating shall beas required by system capacity and shall incorporate a shunt trip asrequired by circuit design. The protective device shall have provision forlocking in the "off" position.

    2.3.3 Inverter Unit

    Inverter unit shall be a solid-state device deriving its power from the dcbus (rectifier or battery source) and providing ac power within specifiedlimits to the critical load. Inverter shall utilize microprocessorcontrolled solid state Pulse Width Modulation (PWM) controlled IGBT powertransistor technology to shape the ac output.

    2.3.3.1 Output Overload

    The inverter shall be able to sustain an overload as specified across itsoutput terminals. The inverter shall not shut off, but shall continue tooperate within rated parameters, with inverse-time overload shutdownprotection. If the overload condition persists beyond the rated parametersof the inverter, the inverter shall current limit, load shall be transferredto the bypass source, and the inverter shall disconnect automatically fromthe critical load bus.

    If the bypass source is not available and the overload/fault condition

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    27/43

    continues, the inverter shall current limit for a limited time asdetermined by the manufacturer and shall shut down to protect the internalcomponents.

    2.3.3.2 Output Frequency Control

    The inverter shall normally operate in phase-lock and synchronism with thebypass source. When the bypass source frequency deviates by more than 0.5Hz, the internal frequency oscillator shall automatically take control andbecome the new frequency reference. Upon restoration of the bypass sourcewithin the required tolerance, the inverter shall synchronize back with thatsource at a slew rate not exceeding the specified rate. The oscillator shallbe temperature compensated and shall be manually adjustable.

    2.3.3.3 Output Protective Device

    The output protective device shall be capable of shunt tripping or openingon an applied control signal and shall have the proper frame size and triprating to supply overload current as specified. External output protectivedevice shall have provision for locking in the "off" position. The inverteroutput protective device shall work in conjunction with the bypassprotective device for both manual and automatic load transfers to and frombypass power.

    2.3.4 External Protection

    UPS module shall have built-in self-protection against undervoltage,overvoltage, overcurrent and surges introduced on the ac input sourceand/or the bypass source. The UPS shall also have built-in self-protectionagainst overvoltage and voltage surges introduced at the output terminalsby paralleled sources, load switching, or circuit breaker operation in thecritical load distribution system.

    2.3.5 Internal Protection

    UPS module shall be self-protected against overcurrent, sudden changes inoutput load and short circuits at the output terminals. UPS module shall beprovided with output reverse power detection which shall cause the module tobe disconnected from the critical load bus when output reverse power ispresent. UPS module shall have built-in protection against permanent damageto itself and the connected load for predictable types of failure withinitself and the connected load. At the end of battery discharge limit, themodule shall shut down without damage to internal components.

    2.4 STATIC BYPASS TRANSFER CIRCUIT

    A static bypass transfer circuit shall be provided as an integral part ofthe UPS and shall consist of a static switch, made up of two reverse-paralleled SCRs (silicon-controlled rectifiers) per phase conductor, and abypass protective device or bypass switch, made up of a contactor or motoroperated circuit breaker. The bypass protective device shall be in parallelwith the static switch. The inverter output protective device shalldisconnect and isolate the inverter from the bypass transfer circuit.

    The control logic shall contain an automatic transfer circuit that sensesthe status of the inverter logic signals and alarm conditions and providesan uninterrupted transfer of the load to the bypass ac power source, withoutexceeding the transient limits specified herein, when a malfunction occursin the UPS or when an external overload condition occurs. The power sectionof the static bypass transfer circuit shall be provided as a plug-in type

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    28/43

    assembly to facilitate maintenance. The static bypass transfer circuit shallbe used to connect the input bypass ac power source to the critical loadwhen required, and shall have the following features:

    2.4.1 Uninterrupted Transfer

    The static bypass transfer switch shall automatically cause the bypass ac

    power source to assume the critical load without interruption when thebypass control logic senses one of the following conditions and the UPSinverter output is synchronized to the bypass ac power source:

    a. Inverter overload exceeds unit's rating.

    b. Battery protection period is expired and bypass is available.

    c. System failure.

    d. Inverter output undervoltage or overvoltage.

    2.4.2 Interrupted Transfer

    If an overload occurs and the UPS inverter output is not synchronized to thebypass ac power source, the UPS inverter output shall current-limit for 200milliseconds minimum. The inverter shall then turn off and an interruptedtransfer to the bypass ac power source shall be made.

    If the bypass ac power source is beyond the conditions stated below, aninterrupted transfer shall be made upon detection of a fault condition:

    a. Bypass voltage greater than plus or minus 10 percent from the UPS ratedoutput voltage.

    b. Bypass frequency greater than plus or minus 0.5 Hz from the UPS ratedoutput frequency.

    c. Phase differential of ac bypass voltage to UPS output voltage greaterthan plus or minus 3 degrees.

    2.4.3 Manual Transfer

    It shall be possible to make a manually-initiated static transfer from thesystem status and control panel. The transfer shall be make-before-breakutilizing the bypass switch.

    2.4.4 Automatic Uninterrupted Forward Transfer

    The static bypass transfer switch shall automatically forward transfer,without interruption after the UPS inverter is turned "on", or after aninstantaneous overload-induced reverse transfer has occurred and the loadcurrent has returned to less than the unit's 100 percent rating.

    2.4.5 Forced Transfer

    The control logic circuitry shall provide the means of making a forced orreverse transfer of the static bypass transfer circuit on an interruptedbasis. Minimum interruption shall be 200 milliseconds when the UPS inverteris not synchronized to the bypass ac power source.

    2.4.6 Overload Ratings

    The static bypass transfer switch shall withstand the following overload

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    29/43

    conditions:

    a. 1000 percent of UPS output rating for one cycle.

    b. 150 percent of UPS output rating for 30 seconds.

    c. 125 percent of UPS output rating for 10 minutes.

    2.4.7 Static Switch Disconnect

    A static switch disconnect shall be incorporated to isolate the staticbypass transfer switch assembly so it can be removed for servicing. Theswitch shall be equipped with auxiliary contacts.

    2.5 MAINTENANCE BYPASS SWITCH

    2.5.1 General

    A maintenance bypass switch shall be provided in a matching, free-standingfloor-mounted enclosure. The maintenance bypass switch shall provide thecapability to continuously support the critical load from the bypass AC

    power source while the UPS is isolated for maintenance. The maintenancebypass switch shall be housed in a separate cabinet or enclosure in such away that service personnel will not be exposed to electrically live partswhile maintaining the equipment. Switch shall contain a maintenance bypassprotective device and a module isolation protective device.

    2.5.2 Load Transfer

    The maintenance bypass switch shall provide the capability of transferringthe critical load from the UPS static bypass transfer switch to maintenancebypass and then back to the UPS static bypass transfer switch with nointerruption to the critical load.

    2.5.3 Load Bank Protection Device

    A load bank protective device shall be provided to allow the UPS system tobe tested using a portable load bank. The load bank protective device shallbe connected on the line side of the maintenance bypass switch isolationprotective device.

    2.6 MODULE CONTROL PANEL

    The UPS module shall be provided with a control/indicator display panel.The display panel shall be on the front of the UPS module. Controls,meters, alarms and indicators for operation of the UPS module shall be onthis panel. The display panel shall be menu driven for browsing all thescreens.

    2.6.1 Module Meters

    2.6.1.1 Monitored Functions

    The following functions shall be monitored and displayed:

    a. Input voltage, phase-to-phase (all three phases).

    b. Input current, all three phases.

    c. Input frequency.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    30/43

    d. Battery voltage.

    e. Battery current (charge/discharge).

    f. Output voltage, phase-to-phase and phase-to-neutral (all threephases).

    g. Output current, all three phases.

    h. Output frequency.

    i. Output kilowatts.

    j. Elapsed time meter to indicate hours of operation, 6 digits.

    k. Bypass voltage, phase-to-phase and phase-to-neutral (all threephases).

    l. Output kilovars.

    m.

    Output kilowatt hours, with 15-minute demand attachment.n. Battery temperature.

    o. Output Percentage load.

    p. Remaining battery time.

    2.6.1.2 Meter Construction

    The display panel shall display alphanumeric parameters based on true RMSmetering with 1 percent accuracy (minimum 4 significant digits).

    2.6.2 Modules

    Modules shall have the following controls:

    a. Lamp test/reset pushbutton.

    b. Alarm test/reset pushbutton.

    c. Module input protective device trip pushbutton, with guard.

    d. Module output protective device trip pushbutton, with guard.

    e. Battery protective device trip pushbutton, with guard.

    f. Emergency off pushbutton, with guard.

    g. DC voltage adjustment potentiometer, with locking guard.

    h. Control power off switch.

    i. UPS/bypass transfer selector switch.

    j. Static bypass transfer switch enable/disable selector switch.

    2.6.3 Module Alarm Indicators

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    31/43

    Module shall have indicators for the following alarm items. Any one of theseconditions shall turn on an audible alarm and the appropriate summaryindicator. Each new alarm shall register without affecting any previousalarm.

    a. Input ac power source failure.

    b. Input protective device open.

    c. Input power out of tolerance.

    d. Overload.

    e. Overload shutdown.

    f. DC overvoltage/shutdown.

    g. DC ground fault.

    h. Low battery.

    i. Battery discharged.

    j. Battery protective device open.

    k. Blower fan failure.

    l. Low battery shutdown.

    m. UPS on battery.

    n. Equipment overtemperature.

    o. Fuse blown (with indication where).

    p. Control power failure.

    q. Charger off/problem.r. Inverter fault/off.

    s. Emergency power off.

    t. External shutdown (remote EPO activated).

    u. Critical load on static bypass.

    v. Static bypass transfer switch disabled/failure.

    w. Inverter output overvoltage.

    x. Inverter output undervoltage.

    y. Inverter output overfrequency.

    z. Inverter output underfrequency.

    aa. Bypass source voltage outside limits.

    bb. Bypass frequency out of range.

    cc. Bypass source to inverter out of synchronization.

    dd. Overtemperature shutdown.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    32/43

    ee. Hardware shutdown.

    2.6.4 Module Emergency OFF Button

    Pressing the emergency off button shall cause the module to be disconnectedfrom the system, via its input protective device, output protective device,and battery protective device. The button shall include a protective coverto prevent unintentional activation.

    2.7 SELF-DIAGNOSTIC CIRCUITS

    The control logic shall include status indicators for trouble-shooting thecontrol circuits. These indicators shall be mounted on the circuit card edgeor face such that they will be visible without repositioning the card, andshall be labeled with the function name.

    2.8.1 Indicators

    Minimum display shall include the following indicators:

    a. Load on UPS.

    b. Load on battery.

    c. Load on bypass.

    d. Low battery.

    e. Summary alarm.

    f. New alarm (to alert the operator that a second summary alarmcondition has occurred).

    2.8.2 Audible Alarm

    Any single indicator shall also turn on the audible alarm. An audible alarmtest/reset button and lamp test/reset button shall be included. This resetbutton shall not affect nor reset the alarm on the module.

    2.9 COMMUNICATIONS AND DATA ACQUISITION

    A communication port shall be provided for use with

    the following:

    a. A set of four Form C remote alarm contacts rated at 120V, 0.5A, shall beprovided for remote alarm monitoring.

    b. Auto-dial modem communication shall be provided to communicate with aremote modem in case an alarm function is active.

    c. A SNMP (Simple Network Management Protocol) adapter shall be provided tocommunicate UPS monitoring via a network or direct connection to a PC.

    d. A standard Web Browser adapter shall be provided to remotely view andmonitor UPS functions over the Internet.

    All the communication ports and contacts shall be capable of simultaneouscommunication.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    33/43

    2.9.1 Emergency Control Contacts

    Provide normally open contacts to signal when power is supplied to the UPSfrom emergency engine generators or alternate source.

    2.10 TEMPERATURE CONTROL

    2.10.1 General

    Cabinet and enclosure ventilation shall be adequate to ensure thatcomponents are operated within their ratings. Forced-air cooled rectifier,inverter, and control unit will be acceptable. The cooling fans shallcontinue operation if UPS input power is lost. Redundancy shall be providedso that failure of one fan or associated circuit breaker will not cause anoverheat condition. Cooling air shall enter the lower front of the cabinetsand exhaust at the top. Blower power failure shall be indicated as a visualand audible alarm on the control panel. Air inlets shall have replaceablefilters that may be located on the inside of the cabinet doors and shall beeasily accessible for replacement.

    2.10.2 Blower Power Source

    Blower power source shall be internally derived from the output side of UPSmodule, with automatic transfer arrangement.

    2.10.3 Temperature Sensors

    Temperature sensors shall be provided to monitor the air temperature.Separate sensors shall monitor the temperature of rectifier and inverterheat sinks. Separate sensors shall also monitor the transformertemperature. Critical equipment over-temperature indication shall start atimer that shall shut down the UPS system if the temperature does notreturn below the setpoint level recommended by the UPS manufacturer.

    2.11 BATTERY SYSTEM

    2.11.1 General

    Battery system shall contain the battery cells, racks, battery disconnect,battery monitor and cabinet, if required. A storage battery with sufficientampere-hour rating to maintain UPS output at full capacity for thespecified duration shall be provided for each UPS module. The battery shallbe of heavy-duty, industrial design suitable for UPS service. The cellsshall be provided with flame arrestor vents, intercell connectors andcables, cell-lifting straps, cell-numbering sets, and terminal grease.Intercell connectors shall be sized to maintain terminal voltage withinvoltage window limits when supplying full load under power failureconditions. Cell and connector hardware shall be stainless steel of a typecapable of resisting corrosion from the electrolyte used.

    2.11.2 Battery Ratings

    a. Type: VRLA AGM Lead Acid.

    b. Specific gravity when fully charged: [1.215][_____].

    c. End voltage [1.67][_____] volts per cell.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    34/43

    d. Float voltage: 2.25 volts per cell.

    e. Equalizing voltage: 2.38 volts per cell.

    2.11.3 Battery Construction

    The battery shall be of the valve-regulated, sealed, non-gassing,recombinant type.

    2.11.4 Battery Cabinet

    The battery pack assembly shall be furnished in a battery cabinet matchingthe UPS cabinet. The battery cabinet shall be designed to allow for checkingthe torque on the connections in the battery system and to provide adequateaccess for annual housekeeping chores. External wiring interface shall bethrough the bottom or top of the assembly. A smoke and high temperaturealarm shall annunciate detection of either smoke or high temperature withinthe battery cabinet.

    2.11.5 Battery Rack

    The battery shall be provided with a suitable number of [two-tier][three-tier] racks to fit the room layout shown. Battery rack shall be steel andshall be protected with electrolyte-resistant paint. Battery rack shall beshipped unassembled and shall include hardware necessary for assembly. Eachrack shall be complete with bus bars to accommodate cables from UPS module.Bus bar connectors for battery-to-battery connections and high-flex multi-stranded copper cable ( ASTM B 173 stranding class H) with proper cablesupports for connecting top row of batteries to bottom row of batteries atrack ends shall be provided. End sections shall be cut to length to preventwasting floor space.

    ]2.11.6 Cell-Terminal Covers

    Acid-resistant transparent cell-terminal covers not exceeding 1.83 meters6 feet in length and with vent holes drilled on top where needed shall beprovided.

    2.11.7 Battery Disconnect

    Each battery pack assembly shall have a fused disconnect switch provided ina NEMA 1 enclosure, finished with acid-resistant paint and located in linewith the assembly. Switch shall be complete with line side and load side busbars for connection to battery cells. Switch shall be rated 480 V dc,[_____] amperes, 3-pole with interrupting rating as required by systemcapacity, and shall have an external operator that is lockable in the "off"position.

    2.11.8 Battery Monitor

    A battery monitor shall be provided for each battery pack assembly. At aminimum, this device shall monitor the following parameters:

    a. Total system voltage.

    b. Ambient room temperature.

    c. Total battery discharge cycles with a duration of [30 seconds orless][greater than 30 seconds but less than 5 minutes][greater than 5minutes].

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    35/43

    The monitor shall also record the total accumulated discharge minutes andaccumulated battery system discharge kW hours.

    2.12 FACTORY TESTING

    The UPS system shall be factory tested to meet the requirements specifiedusing a test battery (not the battery to be supplied with the system). UPSmodule shall be factory load tested as an independent assembly with 3-phaseac input power and with battery power for a minimum of 8 hours, with meterreadings taken every 30 minutes. Load shall be balanced at rated kVA andrated power factor. Factory tests for the UPS module shall be run under fullload, and will be witnessed by the Government. Should a malfunction occur,the problem shall be corrected and the test shall be repeated. As a minimum,the factory tests shall include the parameters described in paragraphs acInput, ac Output, Transient Response and Efficiency. The tests shallencompass all aspects of operation, such as module failure, static bypassoperation, battery failure, input power failure and overload ratings. TheContracting Officer shall be notified in writing at least 2 weeks beforetesting. Factory-test time shall not be used for system debugging and/orcheckout. Such work shall be done prior to notifying the Government that thesystem is ready for testing. Factory tests shall be performed during normalbusiness hours. The system shall be interconnected and tested for anadditional 8 hours to ensure proper wiring and performance.

    2.12.1 Transient Tests

    Transient tests shall be conducted using high-speed oscillograph typerecorders to demonstrate the operation of the components to thesatisfaction of the Government. These tests shall include 50 percent to 100percent load changes, manual transfer, manual retransfer, low dc businitiated transfer and low ac output bus transfer. A recording instrumentequipped with an event marker shall be used.

    2.12.2 Efficiency Tests

    Testing for efficiency shall be performed at zero output up to 100 percentof stated kVA output in 25 percent steps, .9 power factor, with batteryfully charged and floating on the dc bus, with nominal input voltage, andwith module connected to represent actual operating conditions.

    2.13 CABLE LUGS AND TERMINATIONS

    2.13.1 Cable Lugs

    Provide appropriate compression type lugs on all ac and dc power connectionsto the UPS system and battery as required. Aluminum or bare copper cablelugs are not suitable.

    2.13.2 Terminations

    Terminals shall be supplied for making power and control connections.Terminal blocks shall be provided for field wiring terminals. Terminalblocks shall be heavy-duty, strap-screw type. Terminal blocks for fieldwiring shall be located in one place in each module. Control wiring shallbe extended to the terminal block location. No more than two wires shallland on any terminal point. Where control wiring is attached to the samepoint as power wiring, a separate terminal shall be provided. If bus ductis used, bus stubs shall be provided where bus duct enters cabinets.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    36/43

    2.14 INSPECTION

    Inspection before shipment is required. The manufacturer shall notify theGovernment at least 2 weeks before shipping date so that an inspection canbe made.

    2.15 FIELD FABRICATED NAMEPLATES ASTM D 709. Provide laminated plastic nameplates for each equipment

    enclosure, relay, switch, and device; as specified or as indicated on thedrawings. Each nameplate inscription shall identify the function and, whenapplicable, the position. Nameplates shall be melamine plastic, 3 mm 0.125inch thick, white with black center core. Surface shall be matte finish.Corners shall be square. Accurately align lettering and engrave into thecore. Minimum size of nameplates shall be 25 by 65 mm 1.0 by 2.5 inches.Lettering shall be a minimum of 6.35 mm 0.25 inch high normal block style.

    2.16 MANUFACTURER'S NAMEPLATES

    Each item of equipment shall have a nameplate bearing the manufacturer'sname, address, model number, and serial number securely affixed in aconspicuous place; the nameplate of the distributing agent will not beacceptable.

    2.17 FACTORY APPLIED FINISH

    Electrical equipment shall have factory-applied painting systems whichshall, as a minimum, meet the requirements of NEMA 250 corrosion-resistancetest.

    PART 3 EXECUTION

    3.1 INSTALLATION

    Electrical installations shall conform to IEEE C2, NFPA 70, and torequirements specified herein. Provide new equipment and materials unlessindicated or specified otherwise.

    Field Engineering Support: The UPS manufacturer shall directly employ anationwide field service department staffed by factory-trained fieldservice engineers dedicated to startup, maintenance, and repair of UPSequipment. The organization shall consist of local offices managed from acentral location. Field engineers shall be available locally to provideon-site emergency response within 24 hours. Third-party maintenance willnot be accepted.

    3.1.1 Control Cable

    UPS control wiring shall be installed in individual separate rigid steelconduits, unless connections are made between side by side matchingcabinets of UPS. Tag control wires with numeric identification tagscorresponding to the terminal strip location to where the wires areconnected. In addition to manufacturer's requirements, provide fouradditional spare conductors between UPS module and remote alarm panel insame conduit. When routing control cables inside UPS module, maintain aminimum 155 mm 6 inches separation from power cables.

    3.1.2 Grounding Conductor

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    37/43

    Provide an insulated equipment grounding conductor in feeder and branchcircuits. Conductor shall be separate from the electrical system neutralconductor. Ground battery racks and battery breaker cabinets with aseparate equipment grounding conductor to the UPS cabinet.

    3.1.3 UPS Output Conductors

    Isolate the UPS output conductors from the UPS cabinet to the critical loadpanels and from other conductors by installing in separate conduit.Isolation shall prevent inductive coupling from other conductors.

    3.1.4 DC Power Conductors

    When installed in conduits, place dc power conductors from the UPS cabinetto the battery circuit breaker such that each conduit contains an equalnumber of positive and negative conductors, for example, two positive andtwo negative conductors in each conduit.

    3.1.5 Conduit Entries

    Conduit entries shall use the available conduit areas shown onmanufacturer's installation drawings. Conduit entries shall not be madethrough the front, side or rear panels of the UPS or Maintenance BypassCabinet.

    3.1.6 Battery Cabinet Assembly

    Battery cabinets are typically factory assembled for up to 100 KVA UPSsystems. Battery cabinets for larger units typically require assembly at thesite. Installation of battery cabinets shall conform to the manufacturer'sinstructions.

    3.1.9 Battery Installation

    Installation of batteries shall conform to the manufacturer's instructions.]3.2 FIELD QUALITY CONTROL

    Contractor shall notify Contracting Officer in writing at least 45 calendardays prior to completion of the UPS system installation. At this time theContractor, will schedule the UPS manufacturer's technical representative toinspect the completed installation. The UPS technical representative shallprovide instruction for activity personnel as specified in paragraph titled"DEMONSTRATION".

    3.2.1 Installation Preparation

    The following items shall be completely installed by the Contractor and be

    operational prior to the arrival of the UPS representative for inspection,unit start-up and testing:

    a. Ventilation equipment in the UPS and battery rooms.

    b. Battery cabinets and cells. This is not applicable for maintenance-free battery.

    c. Battery connections including cell-to-cell, tier-to-tier, and rack-to-rack connections, with correct polarity;

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    38/43

    d. DC power and control connections between UPS and battery circuitbreaker, with correct polarity;

    e. DC power connection between battery circuit breaker and battery,with correct polarity;

    f. Clockwise phase rotation of ac power connections;

    g. AC power to rectifier input bus;

    h. AC power to UPS bypass input bus;

    i. AC power to UPS maintenance bypass circuit breaker;

    j. AC power from UPS output to UPS maintenance bypass output circuitbreaker;

    k. Remote monitors and control wiring;

    l. UPS system and battery system properly grounded;

    m.

    Emergency shower and eye wash;n. Control connections between UPS and emergency engine generator

    signal contacts;

    o. Control connections between UPS module and UPS maintenance bypasscabinet;

    p. Clean and vacuum UPS and battery room floors, battery cells, and UPSequipment, both inside and outside.

    q. Ensure that shipping members have been removed.

    r. Provide IEEE 450 battery installation certification.

    3.2.2 Initial Inspection and TestsThe UPS technical representative and the Contracting Officer, in thepresence of the Contractor, will inspect the completed installation. TheContractor shall correct construction or installation deficiencies asdirected. Perform acceptance checks in accordance with the manufacturer'srecommendations and include the following visual and mechanicalinspections, performed in accordance with NETA ATS.

    a. Visual and mechanical inspection

    (1) Compare equipment nameplate data with drawings, specifications andapproved shop drawings.

    (2) Inspect physical and mechanical condition. Inspect doors, panels,and sections for paint, dents, scratches, fit, and missing hardware.Inspect the displays for scratches, dark pixels or uneven brightness.

    (3) Inspect anchorage, alignment, grounding, and required clearances.

    (4) Verify that fuse sizes and types correspond to drawings.

    (5) Verify the unit is clean inside and out.

    (6) Test all electrical and mechanical interlock systems for correctoperation and sequencing.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    39/43

    (7) Inspect bolted electrical connections for high resistance using oneof the following methods:

    (a) Use a low-resistance ohmmeter.

    (b) Verify tightness of accessible bolted electrical connections bycalibrated torque-wrench method.

    (c) Perform thermographic survey.

    (8) Verify operation of forced ventilation.

    (9) Verify that vents are clear and new clean filters are installed.

    3.2.3 Performance Tests

    Provide equipment, test instruments, power, load bank, materials and laborrequired for tests. Contracting Officer will witness all tests and thetests shall be subject to his approval. Perform tests in accordance withthe manufacturer's recommendations and include the following electricaltests.

    3.2.3.1 UPS Unit Performance Tests

    Upon completion of battery activation procedures, Contractor shall connectload bank to UPS output. Load bank required shall be determined by thefollowing:

    UPS KVA RATING X 0.8 = KW of LOAD BANK

    Performance test is to be run under the supervision of the UPS technicalrepresentative. UPS unit shall be operated under full load for a minimum ofone hour. Contractor shall be required to operate feeder and bypass powerfeeder breakers during testing of the UPS.

    a. Electrical Tests(1) Perform resistance measurements through bolted connections with a

    low-resistance ohmmeter.

    (2) Test static transfer from inverter to bypass and back. Use normalload, if possible.

    (3) Set free running frequency of oscillator.

    (4) Test dc undervoltage trip level on inverter input breaker. Setaccording to manufacturer's published data.

    (5) Test alarm circuits.

    (6) Verify synchronizing indicators for static switch and bypassswitches.

    (7) Perform electrical tests for UPS system breakers.

    (8) Perform electrical tests for UPS system batteries.

    b. Test Values

    (1) Compare bolted connection resistances to values of similarconnections.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    40/43

    (2) Verify bolt-torque levels.

    (3) Micro-ohm or millivolt drop values shall not exceed the high levelsof the normal range as indicated in the manufacturer's publisheddata. If manufacturer's data is not available, investigate any valueswhich deviate from similar connections by more than 50 percent of thelowest value.

    c. Load Test

    The installed system shall be load tested for a continuous 24 hour periodby means of resistive load banks. The system shall be continuously testedat 1/2 load for 8 hours, 3/4 load for 8 hours and full load for 8 hours.Provide resistive load banks of total kW load of equipment to facilitatestartup under load conditions, and to conduct load tests described above.Instrument readings shall be recorded every half hour for the following:

    (1) Input voltage (all three phases).

    (2) Input current (all three phases).

    (3) Input frequency.

    (4) Battery voltage.

    (5) Output voltage (all three phases).

    (6) Output current (all three phases).

    (7) Output kilowatts.

    (8) Output frequency.

    d. Full Load Burn In Test

    The installed system shall undergo an additional full load burn-in period of24 continuous hours. If a failure occurs during the burn-in period, the testsshall be repeated. Instrument readings shall be recorded every half hour asabove. During the burn-in period, the following tests shall be performed:

    (1) With the UPS carrying maximum continuous design load and suppliedfrom the normal source, switch [100 percent load][50 percent load] onand off a minimum of five times within [the burn-in period] [_____].

    (2) With the UPS carrying maximum continuous design load and suppliedfrom the emergency source, repeat the switching operations describedin step a. Also, verify that the UPS module rectifier charger unit(s)go into the second-step current limit mode.

    (2) With the UPS carrying maximum continuous design load and operating onbattery power, repeat the switching operations described in step aabove.

    (4) Continue operation on battery power for 1 minute, then restorenormal power.

    The Contractor shall furnish a high-speed dual trace oscillograph to monitorten or more cycles of the above tests at the ON and OFF transitions and twotypical steady-state periods, one shortly after the load is energized (at 30to 60 seconds) and one after operation has stabilized (at 8 to 10 minutes).Four copies of the traces shall be delivered to the Contracting Officer.

    e. Battery Discharge Test

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    41/43

    With the battery fully charged, the system shall undergo a complete batterydischarge test to full depletion and a recharge to nominal conditions.Instrument readings shall be recorded every minute during discharge for thefollowing:

    (1) Battery voltage.

    (2) Battery current.

    (3) Output voltage (all three phases).

    (4) Output current (all three phases).

    (5) Output kilowatts.

    (6) Output frequency.

    3.2.3.2 Emergency Generator Operation

    Test UPS to observe operation with emergency generator service. UPS technicalrepresentative shall verify UPS battery current limiting feature functionsproperly.

    3.3 DEMONSTRATION

    3.3.1 Instructing Government Personnel

    Furnish the services of competent instructors to give full instruction todesignated Government personnel in the adjustment, operation, and

    maintenance of the specified systems and equipment, including pertinentsafety requirements as required. Instructors shall be thoroughly familiar

    with all parts of the installation and shall be trained in operating theoryas well as practical operation and maintenance work. Provide training at thefactory, and on-site.

    On-site training shall include 16 hours of instruction, divided into 4 modules, over a 2 day period for 12 personnel.

    Lesson plans should cover: UPS overview, UPS Operation and alarms, UPSSystem Checks, and UPS Maintenance.

    Use approximately half of the time for classroom instruction. Additionaltraining with the equipment prior to actual energization is desirable.

    Provide lesson plans, handouts, and training manuals to be studied one weekprior to the training. Provide a simple 10 question quiz for each session,consisting of basic homework questions such as multiple choice, true/falseand/or fill in the blank type questions.

    UPS software, programs and associated files shall be provided to personnel.

    When significant changes or modifications in the equipment or system are made under the terms of the contract, provide additional instructions to

    acquaint the operating personnel with the changes or modifications.

    Provide factory training for two personnel. Factory training shall consistof a minimum of one week at the factory plant. Transportation, and room andboard,will be paid by the government.

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    42/43

    3.4 FINAL ADJUSTMENTS

    a. Remove load bank and reconnect system for normal operation.

    b. Equalize battery at 480 volts for a period of 72 hours.

    c. Resume charging battery at normal float voltage of [411][_____] voltsdc.

    d. Check battery connections are properly torqued to manufacturer'sspecifications. Take and record, for cell-to-cell and terminalconnections, detailed micro-ohm resistance readings. Remake connectionshaving a resistance of more than 10 percent above the average.

    e. All manufacturer's data and operation manuals, which are an integral partof, and shipped with UPS, shall be delivered to Contracting Officer.

    3.5 NAMEPLATE MOUNTING

    Provide number, location, and letter designation of nameplates as indicated.Fasten nameplates to the device with a minimum of two sheet-metal screws ortwo rivets.

    3.6 FIELD APPLIED PAINTING

    Paint electrical equipment as required to match finish of adjacent surfacesor to meet the indicated or specified safety criteria. Painting shall be asspecified in Section 09 90 00 PAINTS AND COATINGS.

    3.7 DISPOSAL

    Upon completion of UPS installation and testing, Contractor shall removeand dispose of empty, partially full and excess acid drums, includingshipping containers, obsolete batteries, and obsolete UPS modules. Removalshall be accomplished off-base and in conformance with local laws andregulations regarding disposal of hazardous material.

    -- End of Section -

    ENCLOSURE (2)

  • 8/3/2019 Wr 091050 Rfp Replace Ups System b1322

    43/43

    PRICE PROPOSAL SCHEDULE 25 January 2012

    WORK REQUEST # 091050 REPLACE UPS SYSTEM B1322, JOINT BASEPEARL HARBOR HICKAM, HAWAII

    BID ITEM 0001:PRICE TO PERFORM ENTIRE WORK COMPLETE AND IN ACCORDANCE WITH NAVFACDRAWING, Drawing Nos. 19027413 through 19027419

    UNDER REPLACE UPS SYSTEM B1322, JOINT BASE PEARL HARBOR HICKAM,HAWAII

    LUMP SUM = $_______________

    ACKNOWLEDGEMENTS

    1. This proposal acknowledges receipt of Amendments and Responses toRFIs to the proposed Task Order:

    Amendment No. DatedAmendment No. Dated

    Amendment No. DatedResponse to RFI Dated ____________________________Response to RFI Dated ____________________________Response to RFI Dated ____________________________

    2. Name of Contractor:Phone No._______________________________________________E-mail Address: _________________________________________

    3. Proposal Acceptance Period: Offers shall remain valid for sixtydays

    4. A narrative of the methodology to conduct and complete the work isattached.

    Signature of Person Authorized to Sign Proposal:

    _______________________________________________

    Printed Name of Person Authorized to Sign Proposal:

    ________________________________________________

    Date: ____________________________________

    ENCLOSURE (3)