Worldwide PollutionControl Association
Michigan Coal to Gas SeminarJune 5-6, 2012
Visit our website at www.wpca.info
All presentations posted on this website are copyrighted by the Worldwide Pollution Control Association (WPCA). Any unauthorized downloading, attempts to modify or to incorporate into other presentations, link to other websites, or to obtain copies for any other purposes than the training of attendees to WPCA Conferences is expressly prohibited, unless approved in writing by the WPCA or the original presenter. The WPCA does not assume any liability for the accuracy or contents of any materials contained in this library which were presented and/or created by persons who were not employees of the WPCA.
![Page 2: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/2.jpg)
.1
Gas Conversion ProjectsBurner Management Considerations
Pensacola, Florida – May 30, 2012Detroit, Michigan – June 5, 2012
John E. BollingerManager – IC & E Engineering
![Page 3: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/3.jpg)
.2
Key Topics
1. NFPA 2. Main Gas Supply3. Igniter Gas Header4. Main Gas Header5. Venting6. Flame Scanning 7. Combustion Control
![Page 4: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/4.jpg)
.3
National Fire Protection AssociationWithin the Boiler House – NFPA 85
![Page 5: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/5.jpg)
.4
NFPA – Balance of Plant
1. Natural Gas Supply – NFPA 54 National Fuel Gas Code
2. Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage, and Handling of Liquefied Natural Gas. (LNG) Potential use as a replacement for oil as an igniter fuel.
![Page 6: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/6.jpg)
.5
Main Gas Supply
GasSupply
Main Gas shut offvalve PSLPSH Gas Header
IgniterHeader
PressureRegulator
OverpressureRelief Valve
![Page 7: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/7.jpg)
.6
Igniter Gas Header
PressureRegulator
PSL
PSH
Igniter
OtherIgniters
Igniter Shutoff Valves
Igniter HeaderShutoff Valve
Igniter HeaderVent Valve
Igniter Vent Valve
![Page 8: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/8.jpg)
.7
Leak Testing
• Chapter 6 of NFPA 85 describes the requirements for leak testing the gas supply system within the boiler house.
• These requirements include permanent provisions within the gas piping system for performing leak tests.
• Newer Burner Management systems include a leak test function within the start-up routines.
![Page 9: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/9.jpg)
.8
Burner Gas Header
PressureRegulator
PSH
MainBurner
OtherBurners
Burner Shutoff Valves
Burner HeaderCharging Valve
Burner HeaderVent Valve
Burner Vent Valve
PSL
FT
FlowTransmitte
r
Gas FlowControl Valve
Burner HeaderShutoff Valve
![Page 10: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/10.jpg)
.9
Venting
Igniter Vents Burner VentsPressure Relief Vent Header Vent
Vented to Safe location above
Boiler
![Page 11: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/11.jpg)
.10
BMS RequirementsNo single component failure shall prevent a mandatory Master Fuel Trip (MFT)
BMS logic system independent from any other logic system
Logic protected from unauthorized changes
Logic not to be changed on-line
Proper operator intervention not to be prevented
Trips require operator intervention to reset
Signals from boiler control system permitted, but they must be hardwired if part of MFT
![Page 12: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/12.jpg)
.11
Master Fuel Trip (MFT)Stop All fuel flow to furnace.
Close all burner header safety shutoff valvesClose igniter header safety shutoff valvesClose individual igniter safety shutoff valvesDe-energize igniter sparksDe-energize precipitators and other ignition sources
![Page 13: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/13.jpg)
.12
Flame Scanning - Gas
Scanner types – Ultraviolet and Ionization
Sighting to insure flame discrimination
Gas Recirculation considerations
![Page 14: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/14.jpg)
.13
Flame Scanners – Gas Applications
Ultraviolet (UV) Scanner Head
Ionization Detector
![Page 15: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/15.jpg)
.14
Gas Conversion Architecture
![Page 16: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/16.jpg)
.15
Burner Management System Graphics
![Page 17: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/17.jpg)
.16
Typical Main Gas Valve Rack Assembly
![Page 18: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/18.jpg)
.17
Combustion Control
1. Existing control strategy is usually sufficient
2. Increase number of burners in service as load increases
3. When co-firing with coal burners, gas is fired through burners that are not firing coal. Separation of fuels via pulverizer groups
4. Maintain burner pressure within specified range
![Page 19: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/19.jpg)
.18
Combustion Control
5. Air flow should always lead fuel flow
6. Fuel to Air curves should be based on BTU values for Gas.
7. Cross limiting of fuel to air
8. Boiler outlet Oxygen used for air trim control
![Page 20: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/20.jpg)
.19
Area Classifications
• A gas conversion can be cause to review the Area Classification.
• NFPA 85 section 4.1.5 and A4.1.5 (Annex) references Hazardous Area Classifications.
• Addition of a Gas Supply to the boiler house does not automatically change the Area Classification to Hazardous.
![Page 21: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/21.jpg)
.20
Take Away Points
1. Main Gas Supply Pressure control and protection
2. Safety shut off valves to insure adequate isolation
3. Venting to a safe location
4. Maintain safe Air/fuel ratios
![Page 22: Worldwide Pollution Control Associationwpca.info/pdf/presentations/Detroit2012/Boiler Control Issues-John...Liquefied Natural Gas – NFPA 59A - Standard for the Production, Storage,](https://reader038.fdocuments.us/reader038/viewer/2022110300/5b0a70a07f8b9a0b0f8baf47/html5/thumbnails/22.jpg)
.21
Questions ?