Winding Temperature Simulation System - Smart Grid Solutions - Siemens

download Winding Temperature Simulation System - Smart Grid Solutions - Siemens

of 8

Transcript of Winding Temperature Simulation System - Smart Grid Solutions - Siemens

  • 7/24/2019 Winding Temperature Simulation System - Smart Grid Solutions - Siemens

    1/8

    You are here:

    Winding Temperature Simulation System

    September 2011

    By Mike Miller

    One item often overlooked during the testing & commissioning of a transformer is the verification of the oil-winding temperature gradient within the winding temperature simulation

    ystem.

    Unless the transformer came with some type of fiber optic temperature probes mounted directly to the windings youre going to have to rely on a system designed to simulate the

    ctual temperature of the windings and not just the temperature of the insulating oil that surrounds and cools those windings.

    efore conducting the simulation, you will need to locate and/or verify the following:

    1. Top oil temperature indication for a referenc e or star ting point

    2. Some type of transformer load reference

    3. A device to fine tune that load reference

    4. A way of applying a temperature bias based on the transformers load

    5. The actual gradient value which comes from the manufacturer s heat run or temperature rise tes t at a known load point.

    . Top oil temperature

    Using another oil temperature indicator, have the face plate read HV, LV or TV Winding Temperature. These are normally referred to in the ANSI/IEEE standard device classifications a 26 device. In this case were using it as a transformer thermal relay so its true designation will be a 49 device as described by IEEE standards below:

    EEE Std C37.2- 2008 IEEE Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations are as follows:

    .1.26 Device number 26apparatus thermal device A device that functions when the temperature of the protected apparatus (other than the load-carrying windings of machines

    nd transformers as covered by device function number 49), or that of a liquid or other medium, exceeds a predetermined value or when the temperature of the protected apparatus

    r that of a liquid or other medium, exceeds a predetermined value or decreases below a predetermined value.

    .1.49 Device number 49machine or transformer thermal relay A device that functions when the temperature of a machine armature winding or other load-carrying winding or

    lement of a machine or power transformer exceeds a predetermined value.

    . Load Reference

    oad reference is done by the use of a current transformer (CT). This (Hot-Spot) CT will be a single ratio CT and that ratio is specified by the transformer manufacturer to somewhat

    match the current of the phase or leg its monitoring.

    . Device for fine-tuning the load reference

    he load reference will be in the form of the secondary current from the above CT. Though this secondary current will remain proportional to the loading of the transformer its not of

    much use at this point. You will need to adjust the secondary current to give the exact temperature bias needed by using some type of calibration unit - either an adjustable resistor or

    small multi-tap auto transformer. This device will serve as the calibrating mechanism for the whole system.

    . Applying the temperature bias

    he easiest way to affect the reading of a temperature probe is to heat it, using the heater coil inside the wells of thermal plates on the transformer tank walls or tank cover.

    You can tell this well is for the winding temperature if it has some form of conduit running to it. Inside the conduit are the conductors that will carry the now calibrated CT secondary

    urrent to the heater coil.

    n the case of the Qualitrol thermal plates, the winding temperature probe wells are marked with a (WT) for winding temperature and an (LT) for liquid temperature. Be certain not to

    onfuse them when checking the calibration of the indicators, themselves.

    . Actual Temp

    he temperature gradient is found in the factory test reports and should already be applied by the setting of the calibration unit.

    he table below is from a temperature rise test of a 55 MVA transformer during the FAT (factory acceptance tests).

    . Terminals X2-X0 tell us which numbers to reference.

    . Average winding temp at shutdown, subtracted by, Average oil temperature at shutdown, plus the factories 3C constant equals a Gradient of 14.85C This is saying that this

    winding is running 14.85 C hotter than the top oil temperature when the transformer is at full load. This unit is a 55 MVA / 15 MVA, 19.1 kV / 4.16 kV, Dyn1 Aux unit.

    Winding Temperature Simulation System

    > Siemens USA > Smart Grid Solutions > Newsletters > Archive > Winding Temperature Simulation System

    http://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Winding-Temperature-Simulation-System-.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/MV-Breaker-Replacement.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/Pages/TD-Guardian-Newsletter.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/Pages/smart-grid.aspxhttp://usa.siemens.com/http://w3.usa.siemens.com/smartgrid/us
  • 7/24/2019 Winding Temperature Simulation System - Smart Grid Solutions - Siemens

    2/8

    Now you are ready to check the system and make sure everything is working properly.

    You will need a way of simulating the secondary current of an energized CT. There are many choices including a top-of-the-line, Doble F-2253 all the way down to a poor man's

    pecial (light bulbs, clamp-on amp meter and a dimmer switch).

    Regardless of what current source you use, youll need to know the correct amount of current to apply to the winding simulation system and its heat source.

    o find this out, you need to know a few things about the transformer:

    1. The Hot-Spot CTs location (Figure 5)

    2. The Hot-Spot CTs ratio (Figure 5)

    3. The current at a known load on that CT (Figure 6)

    Now well calculate the actual secondary current that the Hot Spot CT will produce taking these items into consideration.

    1. Current on LV(X) at 15 MVA is shown to be 2,081.8 amps

    2. Hot Spot CT ratio is 2090:5 amps

    Here is how you calculate the secondary current:

    Take the known current multiplied by CT secondary (2081.8 * 5)

    Then divide the product by the CT primary (10,409 / 2090 )

    The answer = 4.98 amps

    Now, you know that when the LV(X) is at 15 MVA, the secondary current of the Hot Spot CT will be 4.98 amps. Your current source has to be able to supply the 4.98 amps to the

    erminals where the Hot Spot CTs S1 & S2 leads land. You also know that according to the manufacturer's temperature rise test, the temperature gradient on the LV winding is 14.85

    C.

    Now it is time to calculate how much current you will need to actually apply to the winding temperature simulations systems heat source by adjusting the calibration unit.

    irst, look at the devices shown in figure 1 and figure 2 and how theyre adjusted to get the current we need.

    or the adjustable resistor:you will use the formula:

    R = ( 4.9*Ih ) / ( Ict Ih )

    R = Resistance value to set the adjustable resistor.

    4.9 = Constant.

    Ict = Hot Spot CT secondary current at known load.

    Ih = Heater current required

    Now fill in the formula with our known values:

    R = (4.9 * 0.730) / (4.98 - 0.730)

    R = (3.577) / (4.25)

    R = 0.841

    he adjustable resistor should set to a resistance value of 0.841 Ohms.

    or the multi-t ap auto t ransformer:

    he connection diagram with input and output ratios will help you understand the multi-tap auto transformer.

    Current from the Hot-Spot CT is injected into the X1 and X2 terminals (normally) and the adjusted current is picked up on any two tap combinations based on the output current

    eeded.

    xample:

    X1 (tap1) to X2 (tap 5) have 75.5 turns.

    ap 2 to tap 7 has a total of (14+13+31.5+3+3=) 64.5 turns.

    hats a ratio of 1.171:1

    .98 amps feeding into X1 & X2 = 4.252 amps on taps 2 & 7.

    .98 amps feeding into X1 & X2 = 4.45 amps on taps 2 & 8.

    Caution, be sure your injecting current into the correct side of the transformer.)

  • 7/24/2019 Winding Temperature Simulation System - Smart Grid Solutions - Siemens

    3/8

    Heres why:

    .98 amps into taps 4 & 5 = 13.36 amps on taps 1 & 8!

    Now that Now that you know how to adjust your current output up or down, you will need to find the correct current to apply to the heater coil. First, you will need to look at the heater

    oil and see which heater you have and what its resistance is. Each of the Qualitrol heaters will have their own characteristic curve.

    Once you match up your heater to one of the three charts below youll then need to find the temperature rise or gradient in the Y axis of the chart and trace it across to the solid

    urved line and then trace straight down to the bottom or X axis for the desired current to be injected into the heater.

    Keeping with your current gradient of 14.85 C - In the transformer you see a 609-1 heater element. Refering to figure 10, follow the 14.85 C across, then trace down you will see a

    eater coil current of 4.4 amps. The dashed lines show the possible error or deviation from the chart. There will be some trial and error when setting this for the first time.

  • 7/24/2019 Winding Temperature Simulation System - Smart Grid Solutions - Siemens

    4/8

  • 7/24/2019 Winding Temperature Simulation System - Smart Grid Solutions - Siemens

    5/8

    ased on this information, if you are injecting 4.8 amps into taps 1 and 5, you will get 4.45 amps out of taps 2 and 8. Using this information, you can adjust the current up or down

    epending on what the gauge reads.

    Note: For oil bulb type temperature indicators, you will need to let it cook for at least 30 minutes to get a good gradient reading. Qualitrol recommends a full three hours to allow the

    auge to settle out. In the first half hour you will know if you are close. Figure 13 below illustrates a time constant curve showing how fast the gauge will respond to the heat generated

    y the heater coil.

    n summary

    or analog type temperature gauges: Series 104

    1. Check y our transformer to s ee what devices it is using for its winding temperature simulation system.

    2. Calculate the secondary cur rent of the hot spot CT.

    3. Locate or calculate your transformers temperature gradient.

    4. Verify the settings to the matching unit, resistor or tr ansformer.

    5. With the transformer de-energized, lift the hot spot CT secondary wires and related ground wires and shorting scr ews.

    6. Land your current sourc e wires in their place.

    7. Record your top oil and winding temperature before injecting current.

    8. Inject the calculated hot spot secondary current.

  • 7/24/2019 Winding Temperature Simulation System - Smart Grid Solutions - Siemens

    6/8

    9. In 30 minutes check y our winding temperature. If its close, proceed. If not, k ill the power and readjust the matching unit. Give the bulb time to cool off before starting the test

    again.

    10. Once y ou have re-adjusted the matching unit and the bulb has c ooled back down, inject the same c urrent again into the simulation sys tem.

    11. At the 30 minute mark, if its close, k eep going and in three hours record y our heated winding temperature.

    12. Now subtract y our un-heated temperature from your heated temperature and this will be your measured gradient.

    ooking at the test unit again:

    he unheated winding temperature indicator read 23C.

    he same gauge heated for three hours now reads 38C.

    38C 23C = 15C

    The gradient was 14.85C

    That is a deviation of 0.15C. Generally a deviation of +/- 2.5C is acceptable.

    or the electronic temperature monitors:09, TTC1000, Weschler Advantage, etc.

    1. Refer to steps 2, 3 and 5 above.

    2. Verify the gradient, hot spot CT ratio and transformer load current are corr ectly entered into the controllers software.

    3. Inject current as described above, but you will pass curr ent through the window of the split core CT of the electronic temperature monitor (ETM). A wire is usually looped from S1

    to S2 for this.

    4. The electronic monitors do not need the 3 hour cook time. In the software you c an change the time constant to zero ( 0) for tes ting but change it back when y ou are done.

    5. The gradient is displayed instantly.

    DANGER / HAZARDOUS VOLTAGE: Always use extreme caution when working with electricity or electrical equipment. Always properly de-energize and ground the

    quipment before maintenance. Maintenance work should only be performed by qualified and properly trained personnel. The use of unauthorized parts in the repair

    r maintenance of the equipment or tampering by unqualified personnel will result in dangerous conditions which could result in death, severe injury or equipment

    amage.

    he information contained herein is general in nature and the instructions contained herein do not purport to cover all details or variations in equipment. The

    nstructions are not intended to provide every possible contingency which may be encountered during installation, operation or maintenance. Users should always

    se sound practices in application, installation, operation and maintenance of the equipment. Should further information be desired or should particular problemsrise that are not covered sufficiently for the user's purposes, additional information should be requested from your local Siemens representative. Siemens reserves

    he right to make changes in the information shown herein or to make improvements at any time without notice or obligations.

    9/01/2011

    Archived Topics from Previous Newsletters

    Power Transformer Topics

    Load Tap Changer Topics

    Medium-Voltage Topics

    Share this Page:> > > > >

    > Dissolved Gas Analysis

    > Field Drying of Transformer Insulation

    > GAS Guard 8

    > Insulating Oil

    > Legacy Transformer

    > Oil Filled and Air Core Shunt Reactors

    > Pressure Relief Devices for Transformers

    > Processing Transformer Insulation

    > SITRAM DRY

    > Transformer Bushing Replacement

    > Transformer Contingency Planning

    > Transformer Condition Ranking

    > Transformer Dew Point Measurements

    > Transformer Dew Point Measurement Part 2

    > Transformer Receiving Inspection

    > Welding on an oil-filled Transformer

    > Winding Temperature Simulation System

    > Ferranti Packard On load Tap Changer Upgrades

    > TLF and TLS Tap Changer Upgrades

    > 3AF 3AH Operators Maintenance

    > Air Magnetic Breakers

    > Allis Chalmers AIS Switchgear

    > Allis Chalmers D and F Switchgear

    > Anatomy of a Short Circuit

    > Arc Flash Hazard Analysis

    > Arc Flash Hazard Labels

    > Arc Furnace Switching Applications

    > Capacitor Trip Devices

    > Circuit Breakers or Contactors

    > Circuit Breaker Standards

    > Closed Door Racking systems

    > GMI Breakers Go to College

    > Ground Sensor Current Transformer Cable Routing

    > Heat Generation Estimation for Historic Switchgear

    > Interrupter Switch Technology Comparison

    http://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Interrupter-Switch-Technology-Comparison.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Heat-Generation-Estimation-for-Historic-Switchgear.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Ground-Sensor-Current-Transformer-Cable-Routing.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/GMI-Breakers-Go-to-College.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/Pages/Siemens-Closed-Door-Racking-(CDR)-systems-for-Westinghouse-DHP-and-DH-Breakers.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Circuit-Breaker-Standards.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Circuit-Breakers-or-Contactors.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Capacitor-Trip.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Arc-Furnace-Switching-Applications.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Arc-Flash-Hazard-Labels.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Arc-Flash-Hazard-Analysis.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Anatomy-of-a-Short-Circuit.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Allis-Chalmers-D-and-F-Switchgear.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Allis-Chalmers-AIS-Switchgear.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Air-Magnetic-Breakers.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/3AF-3AH-Operators-Maintenance.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/Pages/TLF--TLS-Tap-Changer-Upgrades.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Ferranti-Packard-On-load-Tap-Changer-Upgrades.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Winding-Temperature-Simulation-System-.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Welding-on-an-oil-filled-Transformer.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Transformer-Receiving-Inspection.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Transformer-Dew-Point-Measurements-2.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Transformer-Dew-Point-Measurements.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/transformer_condition_ranking.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Transformer-Contingency-Planning.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Transformer-Bushing-Replacement.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/SITRAM%C2%AE-DRY.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Processing-Transformer-Insulation.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Pressure-Relief-Devices.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Oil-Filled-and-Air-Core-Shunt-Reactors.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Legacy-Transformer.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Insulating-Oil.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/GAS-Guard-8.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Field-Drying-of-Transformer-Insulation.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Dissolved-Gas-Analysis-Monitoring.aspxhttps://www.xing.com/app/user?op=share;url=http://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Winding-Temperature-Simulation-System-.aspxhttp://www.facebook.com/sharer.php?u=http://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Winding-Temperature-Simulation-System-.aspx&t=Winding%20Temperature%20Simulation%20System%20-%20Smart%20Grid%20Solutions%20-%20Siemenshttp://twitter.com/home/?status=http://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Winding-Temperature-Simulation-System-.aspxmailto:?subject=Winding%20Temperature%20Simulation%20System%20-%20Smart%20Grid%20Solutions%20-%20Siemens&body=The%20following%20page%20from%20the%20Siemens%20Global%20Website%20has%20been%20recommended%20to%20you:%20http://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Winding-Temperature-Simulation-System-.aspx
  • 7/24/2019 Winding Temperature Simulation System - Smart Grid Solutions - Siemens

    7/8

    Protective Relay Topics

    High-Voltage Topics

    Voltage Regulator Topics

    Asset Management Topics

    Low-Voltage Topics

    About Our Authors

    Contact us

    > Medium Voltage Power Systems

    > MV Breaker Replacement

    > Outdoor Switchgear

    > SARRACS

    > SDV Free Standing Vacuum Breakers

    > Siemens Closed Door Racking Solutions

    > Survey Air Magnetic Breakers

    > Tech Topics

    > TVA Sequioa Replaces ITE HK Breakers

    > Type SP SF6 Power Circuit Breakers

    > Vacuum Loss

    > Detecting Fast Power Swing Frequencies

    > New Protection Method for Automated Distribution Feeders

    > SIPROTEC-7SJ62

    > Substation Simulator

    > Stator Ground Fault Protection

    > 3AT Maintenance

    > AC BZO oil circuit breaker

    > BZO 63kA Uprate

    > BZO Maintenance

    > Digital Radiography

    > Essentials of SF6 Monitoring

    > kA Rated Circuit Breakers and Switchgear

    > Maintenance and Adjustment Tips on BZO 242-3 Contact Rod

    > Power Factor Testing of High Voltage SF6 Breakers

    > Replacement Current Transformers on SP--SPS--SPS2--SF6 Power Circuit Breakers

    > SF6 Breaker Maintenance

    > SF6 Gas in Medium Voltage Switchgear

    > TCP HV SF6 Power Circuit Breaker

    > Insulating Oil in Siemens Voltage Regulators

    > Understanding Voltage Regulators

    > Voltage Regulator Control Panel MJ4A

    > Voltage Regulators Drive Springs

    > Allis Chalmers/Load Tap Changer (LTC) Training Programs

    > ARMA Services

    > Cabinet Heaters

    > Electrical Equipment Lifespan

    > Kenett Power Unit

    > Labor Resource Planning

    > Maintenance Training

    > Power Circuit Breaker Training

    > Refurbishment and Upgrade Solution for TD Equipment

    > Transformer Condition Ranking

    > Transformer Contingency Planning

    > Voltage Regulator Training

    > Static Micro-ohm Resistance Readings

    > Andre Smit

    > Doug Edwards

    > Jeff Phelan

    > Jim McIver

    > Juan Acosta

    > Keith Flowers

    > Larry Kirchner

    > Rodney Fickler

    > Stephen Bosak

    > Ted Olsen

    > Todd Rittenhouse

    > Tom Melle

    > [email protected]

    > Customer Support

    http://w3.usa.siemens.com/smartgrid/us/Documents/AS%20Key%20Contacts%20flyer%20for%20website.pdfmailto:[email protected]://w3.usa.siemens.com/smartgrid/us/en/newsletters/Pages/Tom-Melle-Bio.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Todd-Rittenhouse.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Ted-Olsen.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Steve-Bosak.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Rodney-Fickler.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Larry-Kirchner.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Keith-Flowers.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Juan-Acosta.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/Pages/Jim-McIver-Bio.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Jeff-Phelan.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Doug-Edwards.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Andre-Smit.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Static-Micro-ohm-Resistance-Readings0828-3126.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Voltage-Regulator-Training.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Transformer-Contingency-Planning.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/transformer_condition_ranking.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/Pages/Refurbishment-and-Upgrade-Solutions-for-TD-Equipment.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Power-Circuit-Breaker-Training.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Maintenance-Training.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Labor-Resource-Planning.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Kenett-Power-Unit.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Electrical-Equipment-Lifespan.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Understanding-Cabinet-Heaters.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/ARMA-Services.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Allis-ChalmersLoad-Tap-Changer-(LTC)-Training-Programs.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Voltage-Regulators-Drive-Springs.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Voltage-Regulator-Control-Panel-MJ4A.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Understanding-Voltage-Regulators.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Insulating-Oil-in-Siemens-Voltage-Regulators.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/TCP-HV-SF6-Power-Circuit-Breaker.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/SF6-Gas-in-Medium-Voltage-Switchgear.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/SF6-Breaker-Maintenance.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Replacement%20Current%20Transformers%20on%20SP--SPS--SPS2--SF6-Power-Circuit-Breakers.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Power-Factor-Testing-of-High-Voltage-SF6-Breakers-.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Maintenance-and-Adjustment-Tips-on-BZO-242-3-Contact-Rod-.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/kA-Rated-Circuit-Breakers-and-Switchgear.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Essentials-of-SF6-Monitoring.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Digital-Radiography.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/BZO-Maintenance.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/Pages/BZO-63kA-Uprate.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/AC-BZO-oil-circuit-breaker.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/3AT-Maintenance.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Stator-Ground-Fault-Protection.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Substation-Simulator.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/SIPROTEC-7SJ62.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/New-Protection-Method-for-Automated-Distribution-Feeders.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Detecting-Fast-Power-Swing-Frequencies.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Vacuum-Loss.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Type-SP-SF6-Power-Circuit-Breakers.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/TVA-Sequioa-Replaces-ITE-HK-Breakers.aspxhttp://w3.usa.siemens.com/powerdistribution/us/en/resources/Pages/Tech-Topics-Application-Notes.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Survey-Air-Magnetic-Breakers.aspxhttp://www.youtube.com/watch?v=v1rLEXFE-Hc&feature=player_embeddedhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/SDV-Free-Standing-Vacuum-Breakers.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/SARRACS.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/Pages/Switchgear-Outdoor-Enclosure-Type---Why-isn't-it-NEMA-3.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/MV-Breaker-Replacement.aspxhttp://w3.usa.siemens.com/smartgrid/us/en/newsletters/archive/Pages/Medium-Voltage-Power-Systems.aspx
  • 7/24/2019 Winding Temperature Simulation System - Smart Grid Solutions - Siemens

    8/8

    1996-2015