Whole thesis 1 - National University of Singapore Text.pdf · through a building envelope and, ......
Transcript of Whole thesis 1 - National University of Singapore Text.pdf · through a building envelope and, ......
1
1 Introduction
1.1 Background
Insulation is one of the techniques that will always be around. It is a passive
product, once installed it works efficiently, quietly and continually, usually out of sight
enclosed within a structure, a casing or under cladding. Its purpose is to reduce or prevent
the transmission of heat or sound or electricity.
Insulation comes to the fore when the new design of buildings, plant, equipment
or production processes is being considered. It is at this stage that the right specification
must be made, any shortfall in the thickness, or error in the type and application details
will prove costly to rectify at a later date. There are many reasons why professional
engineers, architects and indeed laymen use insulation. They include having to comply
with mandatory legislation i.e. Building Regulations or Standards, to reduce heat
loss/heat gain, to reduce running costs, to control process temperatures, to control surface
temperatures, to reduce the risk of freezing, to provide condensation control, or to reduce
heating plant capacity.
Thermally insulating materials have thus been vital to mankind throughout history.
Their applications are not limited to providing protection of man against extreme
temperatures in their habitats, but they have already been widely used for commercial and
industrial purposes since the industrial revolution in late nineteenth century. For example,
thermal insulators have been employed in cryogenic services to prevent heat gain, such as
2
for storage of liquefied natural gas (LNG) at cryogenic temperature of -162.2 oC (see
Figure 1.1) and refrigeration of foodstuffs and storage of liquid hydrogen for aerospace
endeavors. (Cunningham and Roni, 1978)
Figure 1.1: A typical LNG storage tank under construction
They are also needed to prevent heat loss, such as in hot water storage tanks. For
underwater pipes which carry very high temperature crude oil from offshore oil rig to the
processing plants on land, they need to be insulated to prevent seawater from cooling the
oil in these pipes, causing them to become too viscous to flow and as a result not being
able to be transported.
Over the past decades, there has also been an increasing need to develop cost-
effective insulating materials to provide thermal comfort for the inhabitants in buildings.
Due to rising oil prices, measures have been taken to conserve energy used by buildings
to provide thermal comfort. Hence, in many parts of the world, the focus is on energy
efficiency in the design of buildings through more cost-effective thermal insulation
systems. Energy efficiency also addresses the environment concern of green-house gas
emissions that cause global warming.
3
In Singapore, the Building and Construction Authority (BCA) has played an
active role throughout the years to help to enhance energy efficiency in buildings by
ensuring that minimum standards in energy efficiency are met. Recently, due to
improvement of technology and better building materials, BCA has replaced the Overall
Thermal Transfer Value (OTTV) with a new standard called the Envelope Thermal
Transfer Value (ETTV). ETTV gives a more accurate correlation with the total heat gain
through a building envelope and, hence, is a more reliable indicator for energy efficiency.
It would replace the current OTTV formulation for envelope. Similarly, the OTTV
formulation for roof would also be replaced with the new Roof Thermal Transfer Value
(RTTV) formulation.
The new ETTV of the building and RTTV of roof with skylights, as determined in
accordance with the formula set out in the “Guidelines on Envelope Thermal Transfer
Value for Buildings” issued by the Commissioner of Building Control, shall not exceed
50 W/m2. However, for roofs without skylights, the U-value cannot exceed the limit
prescribed in Table 1.1 for buildings of the corresponding weight group obtained from
BCA Approved document (October 2004)1. The system analysis approach allows for
flexibility in design without compromising energy efficiency while the requirement on
energy efficient equipment is introduced to ensure that only energy efficient equipment
are used. When compared to the old standards, it is estimated that the new standards on
OTTV, maximum lighting power budget and the efficiency of air-conditioning equipment
could reduce electricity consumption by as much as 24%.
4
Table 1.1: Maximum thermal transmittance for roof of air-conditioned building
1.2 Motivation of research
The search for economical and high insulating materials that suit the different
kinds of application mentioned above is still continuing. One prime candidate of a cost-
effective thermal insulation is aerated concrete. Aerated concrete is produced by
introducing air bubbles during the casting process of concrete. There are two main types
of aerated concrete, namely Autoclaved Aerated Concrete (AAC) and foamed concrete.
Autoclaved aerated concrete (AAC) is produced by introducing gas (hydrogen) bubbles
into cement paste or mortar usually made with Portland cement of suitable consistence
using aluminum powder (0.2 % by mass of cement) which reacts with Ca(OH)2 and
alkalis released into solution. The gas bubbles expand the mixture to the required density
after which the concrete is cured either in steam at atmospheric pressure or in steam at
180oC under high pressure in an autoclave.
The air in foamed concrete can be introduced into a mortar or concrete mix using
two methods. The first method is by mixing a pre-formed foam from a foam generator
can be mixed with other constituents in a normal mixer or ready mixed concrete truck.
Second, a synthetic- or protein-based foam-producing admixture can be mixed with the
other mix constituents in a high-shear mixer. The resulting bubbles in the hardened
concrete should be discrete, usually within the size of 0.1 mm to 1 mm.
5
AAC has to be factory-made and is used where financial means and other
conditions favor mass production of high-quality products. However, foamed concrete
can be produced at a much lower cost as its main ingredients are readily available and it
can be manufactured on a small scale at construction site, thus saving on transportation
cost of components to the site. Compared to AAC, foamed concrete offers environmental
benefits as it does not require so much fuel energy for high temperature autoclaving.
Foamed concrete uses relatively lower water cement ratio than AAC, so the compressive
strength of foamed concrete can sometimes be higher than AAC. There are also no waste
products and the ingredients are non-hazardous.
Foamed concrete has good mechanical strength, is lightweight and has low
thermal conductivity. It can be produced in a wide range of densities and properties
which can vary to suit particular requirements. Like ordinary concrete, it can easily be
molded to any desired shape or sizes. Foamed concrete can offer a versatile and cost-
effective alternative to other insulation materials. Results from NUS in-house data
showed that energy savings per unit area by using foamed concrete wall (S.G. = 0.8,
thermal conductivity of 0.26 W/m.K) as compared to using convectional concrete wall
(S.G. = 2.4, thermal conductivity of 2.5 W/m.K) is more than 70 %. Thus, it is showed
that foamed concrete can be an effective insulation material to help in energy-saving in
buildings.
Roofing is probably the most widespread application of foamed concrete. (See
Figure 1.2) It is used to provide graded insulation on roof projects beneath waterproofing
membranes. Foamed concrete has two benefits when it is used for roofing. The first
benefit is that it provides a high degree of thermal insulation. The second benefit is that it
6
can be used to lay a flat roof to falls, i.e. to provide a slope for drainage. In countries
where roofs are flat and where roof surfaces are used as part of everyday life, foamed
concrete is strong enough to support foot or even vehicular traffic on the roof. Foamed
concrete is also much lighter than slopes made from mortar screeds. This means that a
roof with a slope made of foamed concrete imposes a lower loading on the structure of
the building.
Figure 1.2: Casting foamed concrete as insulating roof deck
Due to the tremendous market for foamed concrete as an insulating material to
meet the rising needs in the building industry and other industries due to its versatility
and economy, continual development and research to understand more about foamed
concrete is required. It would thus be very useful if more information can be known about
how different factors in the mix design of foamed concrete affect its thermal and strength
properties to offer an economical and effective insulation for various applications.
One major concern for the use of an insulating material is its ability to maintain
its low thermal conductivity in the environment it is used. High-porosity materials like
foamed concrete tend to absorb water which will increase its thermal conductivity, thus
7
causing the insulating material to lose its effectiveness. One suggestion is to incorporate
polymer into foamed concrete to resist water ingress so as to maintain the effectiveness of
the insulating material during field application. The thermal conductivity of polymer (k ≈
0.19- 0.3 W/m.K) (Weber, 2001) is also much lower than cement paste (k ≈ 0.66 -1.2
W/m.K) (Matiasovsky and Koronthalyova, 2002). Thus, it can be added to foamed
concrete to replace some of the cement content in order to decrease the effective or
resultant thermal conductivity of the resultant material. So far, no record of studies on
properties of polymer-modified foamed concrete could be found in the literature.
However, from several studies that showed improved properties of polymer-modified
normal weight or lightweight concrete, there is reason to believe that adding polymer
might improve the performance of foamed concrete. Thus, it will be interesting to study
the mechanical properties and also thermal conductivity of polymer-modified foamed
concrete in this research study and to discover how this improved material can be
extended to other applications.
Though there is currently some available literature on factors affecting thermal
conductivity of aerated concrete, the majority of the research is focused on AAC. Studies
of thermal conductivity (k) of foamed concrete seem to be fewer in comparison. There
seems to be a lack of comprehensive study on the topic of thermal conductivity for
foamed concrete. Moreover, there are some useful information that are lacking as well in
the literature like the effect of air bubble size (keeping total air content constant) on
thermal conductivity. Thus, in this research study, areas where further studies is
necessary to understand more about this material which is becoming more popular and
widely used will be investigated.
8
Hence, this study is undertaken to measure and analyze the thermal conductivity
and some mechanical and thermal properties of foamed concrete in greater detail and also
to find reliable theoretical or numerical models for its prediction. Thermal performance
of foamed concrete which is governed by its thermal conductivity will be studied with
regards to its sensitivity to various factors such as w/c ratio of foamed concrete mix, foam
content and polymer content. The information will provide greater insight to design a
cost-effective foamed concrete mix that is able to achieve its intended purpose with
maximum saving in materials and cost.
Foamed concrete can be applied locally as an insulating material for roofing
systems over the roofs of HDB flats and other flat roof. Lately, secondary roofing slabs
made from ferrocement has been used over the flat roofs of most HDB apartments as part
of the heat insulation system (see Figure 1.3).
However, this secondary roofing system has some disadvantages. For example,
the ferrocement slabs are just mounted on the concrete stumps and thus this system
cannot be applied to apartments in areas where there are strong winds as the slabs can be
blown off easily thus posing a danger to the residents and passer-by. Heat can also be
transferred through these concrete stumps, to give rise to the temperature of the main roof
below. Thus, the effectiveness of the insulation system using ferrocement and air gap for
the roof will be reduced.
Another disadvantage is that after years of deterioration, the strength of the
ferrocement slab will decrease such that it will easily break when someone steps on it.
This again, poses a danger to people who have to go up to the roof due to the nature of
their work. (See Figure 1.4)
9
The layer of trapped air between the main and secondary roofs is supposed to
prevent heat transmission to the dwellings below. However, once the ferrocement
secondary roof slab is broken, the insulation provided by the air layer will be ineffective
since heat will be directly transferred to the main roof at the broken portions. Moreover,
the air layer is not strictly adiabatic at the boundaries due to the many openings at the
sides. This may cause heat to be transferred to the main roof through the sides as well.
Hence, the thermal insulation performance of the secondary roofing system may not be as
effective as expected.
These precast ferrocement roof slabs are dense and impermeable to water due to
the high grade of mortar used in their manufacture. Thus, waterproof membranes are
eliminated. However, if there are any holes caused by deterioration of the slabs, or gaps
caused by imperfect workmanship when laying the roof slabs, water may seep through
the building envelope into the building, causing leaking problems to the inhabitants.
Thus, there is a need to come up with more effective roofing systems that suit the
local environmental requirement to replace it. In this research, the feasibility of foamed
concrete as the insulation material for two alternative systems to provide thermal
insulation to the main roof slab will be studied (see Figure 1.5 and Figure 1.6).
Figure 1.3: Sketch of HDB Secondary Roof System
Roofing Slabs
Concrete Stumps
Air Gap Air Gap
Main Roof Level
10
Figure 1.4: Picture showing deteriorated roof slab
Figure 1.5: Sketch of the secondary roofing system proposed using low grade foamed concrete
(Alternative A)
Figure 1.6: Sketch of the new roofing system proposed using higher grade foamed concrete
(Alternative B)
Foamed Concrete secondary roofing Slab
Main Roof Level (normal weight concrete)
Foamed Concrete roofing System
11
1.3 Objectives and Scope
1.3.1 Objectives
1) To study and understand how various key factors (namely foam content, water-
cement ratio and air void size) affect the thermal conductivity and strength for
different mix designs of foamed concrete.
2) To propose a simplified and user-friendly equation using numerical model (via
FLUENT software) for predicting thermal conductivity of foamed concrete to aid
in the design of foamed concrete mixes for structural and non-structural insulation
purposes, verifying it with current and other researchers’ experimental results and
other analytical models.
3) To investigate the effect of incorporating acrylic polymer into foamed concrete on
its thermal conductivity, mechanical properties and water-resistance property.
4) To investigate the suitability of foamed concrete as an insulation material for
roofing system of buildings to suit local requirements and to propose suitable
design mix of foamed concrete to be used.
1.3.2 Scope of Work
1. To measure the thermal conductivity and some mechanical properties (3-,7-,
28-day compressive strength, flexural strength, splitting tensile strength and
12
elastic modulus) of foamed concrete and polymer-modified foamed concrete
with varying foam content, water-cement ratio and polymer content.
2. To investigate the effect of different air bubble size on thermal conductivity of
foamed concrete via numerical models using FLUENT software.
3. To find out the effect of varying foam content and polymer content on the air
bubble sizes using automatic imaging microscopy.
4. To analyze and explain the effect of varying foam content, water-cement ratio
and polymer content in foamed concrete on its thermal conductivity and
mechanical properties.
5. To determine which existing theoretical models can predict the thermal
conductivity of foamed concrete realistically.
6. To investigate the effectiveness of the proposed foamed concrete roofing
systems using (Alternative A and B) suitable mix proportions of foamed
concrete for use on roofs of local buildings.
13
2 Literature Review
This chapter describes various topics that are related to the objectives of this
research project. It starts off with the theory of thermal conductivity to understand more
about how heat is conducted in foamed concrete and in polymers. Since polymer-
modified foamed concrete would also be investigated for this research, it would be good
to have a basic background on how heat is transferred in polymers. Thermal resistance of
building insulations will be discussed in order to have a clear understanding of how
insulation works.
The heat flow meter is used to measure the thermal conductivity values of the
concrete specimens and a more detailed description of the apparatus is available in this
chapter as well. Reasons for choosing this apparatus over other equipment will be offered.
A comparison between foamed concrete and other commercially available insulation
material is also presented in this chapter.
There are a few sections devoted to literature review of research works done on
the mechanical and thermal properties of foamed concrete. Information regarding this
material that is still lacking from the literature review is identified. A literature review of
the various theoretical models available to predict thermal conductivity of foamed
concrete is also provided. This section covers a few of the available mathematical
relations for correlating the effective thermal conductivity of a mixture with the thermal
conductivities of the individual components.
Currently, there is no literature available about polymer-modified foamed
concrete. However, there are many studies done for polymer-modified concrete. Thus,
14
studying the properties of polymer-modified concrete may give some insights on the
possible effects of incorporating polymer to foamed concrete. The last section of this
chapter will provide more details on flat roofing system used in HDB rooftops. It will
provide some information on its disadvantages and the need to look for alternative
insulation material.
2.1 Thermal conductivity Theory
Thermal conductivity is a material property that plays a key role in all heat
transfer calculations. Heat transfer occurs through three mechanisms, namely conduction,
convection and radiation. Heat is mainly transferred via conduction in solids. Heat
conduction refers to the transport of energy in a medium due to a temperature gradient.
Fourier’s law is given by:
q= -k (dT/dt) (2.1)
where
q = heat flux (W)
k = thermal conductivity (W/m.K)
dT = temperature gradient (K)
dt = thickness of the material (m)
Fourier’s law shows that heat transfer through conduction depends on thermal
conductivity and a temperature gradient. This thermal conductivity is assumed to be
constant. However, it varies with temperature and also moisture content in the material.
The thermal conductivity of a homogeneous material is defined by the Fourier’s law. The
same definition is extended to a heterogeneous material, with the temperature gradient
15
being the average value of the temperature gradient over a region large in comparison
with the size of inhomogeneities.
Heat is transported in solid mainly by electron transport and phonon transport.
Electron transport is the dominant transport mechanism in pure metals. Phonons are
defined as the quanta frequency of atomic vibrations. They transfer heat energy through
interactions with themselves and subatomic particles. In metal alloys, both electron and
phonon transport of the heat energy play a significant part. However, in dielectric
materials like polymers and concrete, the dominant way in which heat is conducted is by
phonons.
Bhattacharjee et. al (2004) studied on permeable porosity and thermal
conductivity of construction material. It was reported that most of the ceramics
construction materials such as bricks, blocks and concrete (chemically combined) are
porous in nature. Heat transfer through these materials is a complex process and involves
many components. The most important of these components are: (1) Heat conduction in
solid materials, (2) heat conduction through pore fluid (air or water), (3) convection heat
transfer through pore fluid, (4) radiation from solid surfaces of pores, and (5) evaporation
and condensation in the pores, when they are partially saturated with water. Hence, the
measured thermal conductivity is the amount of heat flow under the unit temperature
gradient for a unit area that encompasses some or all of the above mode of heat transfer
and is effective or equivalent thermal conductivity. These components of heat transfer are
additive but in general not independent.
For a pore diameter smaller than 3 mm, the effect of radiation and convection in
pores can be neglected in comparison with other modes of heat transfer at atmospheric
16
pressure and temperature (Luikov, 1980). Thus, at normal ambient condition, the
conduction heat transfer through the solid skeleton and through fluid in the pores are
likely to be the most dominant mechanisms of heat transfer influencing the effective
thermal conductivity of the porous construction materials, when the pores are either
completely dry or fully saturated with water. When the pores are partially saturated,
evaporation condensation of moisture within the pores would also contribute to effective
conductivity significantly.
For a material with reasonably small cells or pores, such as foamed concrete
which contains air voids typically in the range 0.1 to 1 mm, heat transfer due to radiation
and convection within the pores is small and can be neglected or lumped in with the true
conduction component at atmospheric pressure and temperature.
In the case of foamed concrete, air bubbles are incorporated with cement paste to
bring down the thermal conductivity of the final product since air has a low thermal
conductivity. The thermal conductivity of foamed concrete depends on the thermal
conductivity of the solid material (cement paste), as well as the volumetric fraction of the
air or void space. The solid mass/ total volume or the bulk density is a special parameter
of the insulation system. Increasing the bulk density will also increase the thermal
conductivity of foamed concrete.
For materials like polymers, which are extremely long chained molecules that
have repeating units, their thermal conductivities are low as they do not have free
electrons or a regular atomic grid for effective heat transfer through atomic vibration.
Polymers are mostly amorphous (non-crystalline) and it is significantly less crystalline
than other crystalline materials like metals or low-molecular-weight compounds. Thermal
17
conductivity has been experimentally shown to increase with increasing crystallinity or
orientation of polymer chains. This can be extrapolated to show that amorphous polymer
will be less conductive than semi-crystalline polymers.
2.2 Thermal resistance of building insulation
2.2.1 Resistance Concept
The rate at which heat flows through a slab of homogenous material under steady-
state conditions is given by:
where:
Q = the resultant heat flow (Watts)
A = the surface area through which the heat flows (m²)
∆T = the temperature difference between the warm and cold sides of the material (K), and
R = the thermal resistance per unit area of the piece of material (m²K/W).
Resistance is usually given as an "R" value which is the resistance of one square
metre of the material subject to a one degree temperature difference. Thus an R value of
a typical fibreglass may be given as R = 2.4, with the implication that it has the units
m²K/Watt. This means that if one takes the area of insulation in square metres
multiplied by the temperature difference in degrees Kelvin and divided by 2.4, one gets
Q = A. ∆Τ
R (2.2)
18
the heat flow in Watts. For example, 100 square metres of R2.4 insulation, exposed to a
20°K difference, will pass about 833 Watts.
2.2.2 The U-value
The U-Value is an important concept in building design. It represents the air-to-
air transmittance of an element. This refers to how well an element conducts heat from
one side to the other, which makes it the reciprocal of its thermal resistance. U-value
can be obtained by inverting thermal resistance value of an element.
(2.3)
where RT = total thermal resistance
where Ro = air film resistance of external surface (m2K/W); Ri = air film resistance of
internal surface (m2K/W); K 1, K 2, K n = thermal conductivity of basic material (m2K/W);
b 1, b 2, b n = thickness of basic material (m); Ra = thermal resistance of air space. Table
2.1 shows Ri, Ro and Ra for different scenarios.
The U-Value is a property of a material. Its units are Watts per metre squared
Kelvin (W/m² K). This means that, if a wall material had a U-Value of 1 W/m² K, for
every degree of temperature difference between the inside and outside surface, 1 Watt
of heat energy would flow through each metre squared of its surface.
19
Table 2.1: a) Surface film resistance of walls and roofs; b) Air space resistance of walls and roofs (for
air space greater than 100 mm, the Ra for 100 mm should be used)
2.2.3 Thermal resistance of Air Spaces
Heat is transferred across an air space by a combination of conduction,
convection and radiation. Heat transfer by conduction is inversely proportional to depth
of the air space. Convection is mainly dependant on the height of the air space and its
depth. Heat transfer by radiation is relatively independent of both thickness and height,
but is greatly dependent on the reflectivity of the internal surfaces. All three
mechanisms are dependent on surface temperatures. When all three heat transfer
processes occur at the same time, the overall thermal resistance of air spaces, both
reflective and non-reflective, becomes virtually independent of gap depth when it is
greater than around 25mm. (Shirtliffe, 1972)
a b
20
2.2.4 Structure of thermal insulators
Commercial insulations generally have two basic structures: a continuous body of
gas that contains a dispersion of solid particles or fibres; and a continuous matrix of solid
material with a random dispersion of gas-filled cavities. For ordinary air spaces with no
heat reflective system, heat is transferred primarily through radiation and convection and
contribution through conduction decreases as the thickness of air spaces increases. With
reflective surface, heat transfer through radiation is greatly reduced. When a small
amount of opaque solid material is distributed throughout an air space, it inhibits heat
transfer by convection and radiation while contributing little to conduction, thereby
raising the value of the thermal resistance of the space as shown in Figure 2.1. Solids
such as glass, rock and plastic that provide little resistance to heat flow can be used in this
way to produce good insulation.
Figure 2.1: Variation of heat transfer across air spaces with thickness, orientation, surface
reflectivity and fibre fill showing size contribution by radiation, conduction and pure convection
21
Figure 2.2: Resistance versus thickness for air spaces and wood
The limiting value for a low density, open pore type of insulation is given by the
uppermost curve in Figure 2.2, which represents an ideal situation of heat transfer
through air by conduction only. When thickness of air spaces increases, the resistance
increases. The lowest curve represents the other extreme, which includes the full effect of
radiation and convection. Low density, open pore insulations have resistance versus
thickness curves that lie somewhere between these extremes. (Shirtliffe, 1972)
2.2.5 Effect of Density on Thermal Resistance
The resistance of all types of insulation is strongly dependent on the amount of solid
material present, especially at the low densities that are of practical interest. Figure 2.3
shows how the resistance of 1-inch-thick layers of different materials, measured under a
set of standardized test conditions, varies with density. At very low densities there is so
22
little solid material that there is an appreciable amount of heat transfer through the sample
by radiation and some by convection as well. As the proportion of solid material is
increased, these components of heat transfer become quite small until at some point the
increased conduction due to increased amount of solid just matches the reduction due to
decreased convection and radiation. This is the density for maximum resistance. Beyond
this point, resistance decreases slowly as the amount of solid increases. (Shirtliffe, 1972)
Reflective surfaces facing and in contact with insulation can be used to increase
the resistance of low density insulations. If the bounding surfaces of an insulation have a
low emissivity, there will be less heat transfer by radiation and over-all resistance will be
less dependent on density. The dotted curves in Figure 2.3 are examples of the results for
samples with aluminum foil at the surface.
The cost of insulation is dependent on density. Manufacturers tend to market
insulations at densities lower than those that give maximum R per unit thickness because
lower densities give a lower cost per unit of resistance. The range in which most
commercial fibrous insulations are produced is shown in Figure 2.3.
23
Figure 2.3: Resistance of 1-inch specimens versus density.
2.3 Steady-state heat conductivity measurements
Thermal conductivity (k) defines a material's ability to transmit heat and is measured in watts per square metre of surface area for a temperature gradient of one Kelvin (K) per unit thickness of one metre, W/m.K. Most thermal conductivity measurements are made under steady-state conditions, which typically take some hours to achieve.
Figure 2.4 shows a schematic diagram of a heat flow meter (HFM) according to ASTM C
518. It establishes steady state unidirectional heat flux through a test specimen between
two parallel plates of constant but different temperatures. It consists of a multi-junction
thermopile formed with the junctions on either side of the specimen to be tested. The heat
flowing through the specimen is measured with calibrated heat flux transducers that are
24
in contact with the sample at the plate interface. The thermal conductivity is determined
by the following equation:
where k is a constant known as thermal conductivity of the material; T1 and T2 are the
temperature of the hot and cold plate respectively, T1 > T2; x is the thickness of the
specimen; E is the voltage output of the heat flux sensor and S is the calibration factor of
sensor.
Heat Flux transducer (to data logger)
Figure 2.4: Diagram of a Heat flow meter apparatus
Another widely-used apparatus for measuring thermal conductivity is called the
guarded hot-plate (GHP) according to ASTM C177 as shown in Figure 2.5. It employs a
very similar operating principle as the heat flow meter. It has a guarded heating unit, two
auxiliary heating plates, two cooling units, secondary guarding in the form of edge
k = T1 – T2
xSE (2.4)
Cold Plate
Specimen (with 2-inch thick
Styrofoam insulation)
Hot plate
Heater
Cooling bath
25
insulation and a temperature controlled secondary guard. The heat source is positioned in
the center between two samples of the same material. Two samples are used to guarantee
symmetrical heat flow upward and downward, as well as complete absorption of the
heater’s energy by the test samples.
A well-defined power is put into the hot plate during the test. The measurement
temperatures and temperature gradient are adjusted between the heat source and the
auxiliary plates by adjusting the power input into the auxiliary heaters. The guard heater(s)
around the hot plate and the sample set-up guarantee a linear, one-dimensional heat flow
from the hot plate to the auxiliary heaters. The auxiliary heaters are in contact with a heat
sink to ensure heat removal and improved control. By measuring the power input into the
hot plate, the temperature gradient and the thickness of the two samples, the thermal
conductivity can be determined according to the Fourier equation.
Figure 2.5: Diagram of a guarded-hot-plate apparatus
HFM can be easily handled by one person and can give rapid results within a few
hours, and it is applicable to a wide range of test specimen. The set-up can be calibrated
with an NIST standard material with known k-value, thus it can give accurate test results.
26
Guarded hot plate has a broader temperature range (-180 to 650 oC) and is an absolute
measurement method which means that no calibration of the unit is necessary. Thus, it
can offer better accuracy. The GHP set-up is however quite cumbersome and would need
at least two people preferably to set up the test.
The results using HFM can be considered as reproducible as those of GHP, albeit
accuracies may be slightly lower than GHP due to heat losses at the edge of the
equipment.
2.4 Insulation Materials
Table 2.2: Thermal conductivity of some common insulation materials
Material
k-value
(W/m.K)
ρd, dry
density
(kg/m3)
Polyurethane foam 0.02 32
Polystyrene 0.037 30
Glass Wool 0.041 65 ~ 160
Polyethylene 0.0348 32 ~ 38
Rock Wool 0.04 40 ~ 130
0.065 300
0.08 400
0.095 500 Foamed concrete
0.115 600
0.194 870 Perlite Concrete 0.28 1315
Vermiculite Concrete 0.1 400
Normal weight concrete with granite 2.6-2.7 2400
Table 2.2 shows the comparison of thermal conductivity between foamed
concrete and other insulation materials and their dry density. Foamed concrete has a wide
range of thermal conductivity depending on its density. For low-density foamed concrete,
their thermal conductivity or k-value are quite low compared to the normal weight and
27
heavy weight concrete. Their values are in the same order as some of the commonly-used
thermal insulator in the market. Thus, the potential of using foamed concrete as thermal
insulators is high.
2.5 Properties of foamed concrete
Aerated concrete is relatively homogeneous when compared to normal weight
concrete, as it does not contain coarse aggregate phase. The properties depend mainly on
its microstructure (void-paste system) and composition, which are affected by the type of
binder used, and curing. Aerated concrete is normally envisaged as a good insulation
material; however it can also be utilized for structural usage. Typical mixes are given in
Table 2.3 (Cox and van Dijk, 2002). Typical properties of foamed concrete are shown in
Table 2.4. (Aldridge, 2002)
Further relevant information on the mechanical properties of foamed concrete and
factors affecting its thermal conductivity will be discussed in this section.
Table 2.3: Typical foamed concrete mixes
28
Table 2.4: Typical properties of foamed concrete
2.5.1 Mechanical Properties
2.5.1.1 Compressive strength
Aerated concrete has a lower strength as compared to normal weight concrete due
to the higher amount of voids in the former. The specimen size and shape, method of
pore-formation, direction of loading, age, water content, characteristics of ingredients
used and method of curing are reported to influence the strength of aerated concrete.
Compressive strength can be significantly influenced by the pore structure of the air
pores and the mechanical condition of pore shells. When density is reduced, larger
macropores are formed which leads to a significant drop in compressive strength.
(Narayanan and Ramamurthy, 2000)
Wee et al. (2005) studied on the air void system of foamed concrete and its effect
on mechanical properties. Wee et al. reported that compressive strength of concrete is
controlled by water to cement ratio, because it determines the porosity of cement paste
(Neville, 1997). Compressive strength is also controlled by the size of the existing voids
in the cement paste (Odler and Robler, 1985; Kearsley and Visagie, 1999; Toshio et al.,
29
1991). The result stated in the paper is only applicable for foamed concrete with w/c ratio
of 0.3.
The relationship between strength or modulus to density ratios and spacing factor
as presented in Figure 2.6c indicates that spacing factor also controls the mechanical
properties of foamed concrete produced with the same w/c ratio. When the spacing factor
increases up to 0.04 mm, the corresponding increase in the strength and modulus ratio
was significant. Likewise, as shown in Figure 2.6d, when the spacing factor increases up
to 0.04 mm, the average air void size reduces significantly which thereby contributes to
the significant increase in the strength and modulus ratio. As the spacing factor increases
further from 0.04 to 0.14 mm, the strength and modulus ratio did not increase
significantly. This could be due to the small change in the average air-void size when the
spacing factor increases from 0.04 to 0.14 mm as shown in Figure 2.6c. It is evident that
air void size in combination with the spacing factor significantly governs the mechanical
properties of the foamed concrete. A small air void size in combination with a larger
spacing factor would lead to better mechanical properties and the optimal values of these
factors would result in optimal strength to weight ratio. Figure 2.6d shows the optimal
spacing factor to be 0.04 mm above which, the strength or modulus to density ratios did
not increase significantly. This optimal value was at the transitional air content of 42%
which demarcated the trends of air-void size (Figure 2.6a) and air-void frequency (Figure
2.6b).
Concrete with higher air content tends to result in larger air-voids because of the
proximity of the air-voids, which lead to higher incidence of void coalescing and forming
30
larger air-voids. This observation is more pronounced in concrete with air content of
more than 42%. It is apparent that when the paste content is less than 58%, the average
air-void size increases because there is less cement paste to prevent the air-voids from
coalescing.
Powers (1967) and Mielenz et al. (1958) reported that the coalescence of air-voids
in air entrained concrete may be due to the difference of surface tensions in different size
of bubbles creating difference of pressure. If the water surrounding a small bubble
should become saturated with respect to the pressure in the small bubble, it will become
supersaturated with respect to the water surrounding a large bubble and subsequently one
should expect air to diffuse through the water from a smaller to the larger bubble,
diminishing the smaller and enlarging the larger. This diffusion seems to be more
dominant in lower density mixes which contains lower paste content.
According to Hoff’s (1972) and Kearsley and Wainwright (2001) observations,
the strength of cellular concrete varied with porosity which is directly proportional to the
density. The relationship between dry density versus compressive strength and spacing
factor of the foamed concrete are shown in Figure 2.6d. The compressive strength
increasing with increase in density is well aligned with the trend reported for foamed
concrete by many researchers [ACI Committee 523.3 R-75; McCormick, 1967; Tam et
al., 1981; Fujiwara et al., 1995; Kearsley, 1999; Kearsley and Wainwright, 2001). Figure
2.6e also shows that the spacing factor increases correspondingly as the compressive
strength with an increase in the density. It can also be seen that the rate at which the
compressive strength and the spacing factor increase with density are congruous
31
suggesting that the spacing factor governs the compressive strength for the foamed
concrete made with same w/c ratio. There is a general trend of compressive strength
increasing proportionally with the increasing wet densities for a given w/c ratio, strength
results also depend very much on the test conditions such as the sizes and shapes of
specimens, the moisture content, curing methods and the direction of loading. (Wee, 1997)
Compressive strength of aerated concrete varies inversely with moisture content.
On drying to equilibrium with normal atmosphere, there is an increase in strength and an
even larger increase on complete drying out. Thus, it was recommended that strength
tests be done on materials that have attained equilibrium with the surroundings.
Compressive strength to density ratio of foamed concrete was found to be increased by
using fly ash as a partial/complete replacement for the filler. (Durack and Weiqing, 1998;
Sengupta, 1992; De Rose and Morris, 1999; Giannakou, 2002 )
There are several strength prediction relations that have been proposed to assess
the compressive strength of aerated concrete. For instance, in the case of foamed
concrete, the Feret’s equation (Tam et. al, 1987) relating the strength (S), water–cement
(w/c) and air–cement (a/c) ratios, is given as
S=K[1/(1+(w/c)+(a/c))]n (2.5)
where, K and n are empirical constants. This equation provides a good prediction of
strength. Results showed that the strength of foamed concrete depends on both the water-
cement ratio and the air-cement ratio. The relationship is improved when another term
32
which is the degree of hydration is introduced through Power’s gel/ space ratio concept
into a modified form of Feret’s formula.
Figure 2.6: a) Relationship between air content and air-void size; b) Relationship between air
content and frequency; c) Relationship between average air-void size and spacing factor; d)
Variation of compressive strength or modulus of elasticity density ratio with spacing factor; e)
Relationship between dry density versus compressive strength and spacing factor
0.08
0.10
0.12
0.14
0.16
0.18
0.20
0.22
0.24
0.26
Ave
rag
e a
ir-v
oid
siz
e (
mm
)
0 10 20 30 40 50 60 70 80
Air content (%)
0 10 20 30 40 50 60 70 80
Air content (%)
1.0
1.5
2.0
2.5
3.0
3.5
4.0
4.5
Air-v
oid
fre
que
ncy
(1/m
m)
AVS - 0.230
AVS - average air-void size
0.1790.157
0.120
0.112
0.101
0.00 0.02 0.04 0.06 0.08 0.10 0.12 0.14 0.16
Spacing factor (mm)
0
5
10
15
20
25
30
35
Str
en
gth
or
mo
du
lus t
o d
en
sity
ra
tio Strength - spacing factor
Modulus - spacing factor
a
e
c d
b
0.075 0.100 0.125 0.150 0.175 0.200 0.225 0.250
Average air-void size (mm)
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
Sp
acin
g f
acto
r (m
m)
AC - 11%
26%
41%56%
62%71%
( - 0.6)(0.8)(1.0)
(1.3)
(1.6)
(1.9)AC - air content
( - density)
200 400 600 800 1000 1200 1400 1600 1800 2000
Dry density (kg/m )
0
10
20
30
40
50
60
70
Co
mp
ressiv
e s
tre
ng
th (
MP
a)
0.00
0.02
0.04
0.06
0.08
0.10
0.12
0.14
0.16
Spa
cin
g fa
cto
r (m
m)
3
Strength - density
Spacing factor - density
33
2.5.1.1 Splitting tensile and Flexural strength
Lim (1984) reported that splitting tensile strength for foamed concrete to be at 7
to 12 % of compressive strength and flexural strength lies in the range of 15 to 33 % of
compressive strength. Preliminary Studies were carried out by Wee (1997) on the
properties of foamed concrete with w/c of 0.5, 0.6 and 0.65 and densities varying from
1300, 1600 and 1900 kg/m3 was done. Result shows that flexural and splitting tensile
strength ranged from 0.8 and 2.5 N/mm2 and 0.3-1.2 N/mm2 on the 28th day respectively.
These values were low compared to normal weight concrete. Thus, reinforcing materials
would be needed to increase its flexural capacity in order to ensure easy handling of
foamed concrete on site, especially for thin and long slabs. Splitting tensile strength
according to Wee (1997) was found to be 10 to 13 % of compressive strength and
flexural tensile strength was found to be from 20 to 35 % of compressive strength. The
values reported by Wee (1997) were slightly higher than Lim (1984).
2.5.1.2 Drying Shrinkage
Foamed concrete possesses high drying shrinkage due to the absence of aggregates.
Drying shrinkage increases for decreasing density of foamed concrete. Some of the
typical values of drying shrinkage of foamed concrete can be found in Table 2.3.
Autoclaved aerated concrete has a much lower shrinkage compared to air-cured aerated
concrete. The average drying shrinkage of typical autoclaved aerated concrete is
approximately 0.02 per cent. Shrinkage changes in response to changes in moisture
conditions develop tensile stresses and ultimately lead to cracking in the restrained
product. Rudolph and Valore (1954) commented that the linear drying shrinkage of
34
foamed concrete ranges from 0.3 to 0.6 % as compared to a range of 0.01 to 0.1 % for
AAC.
2.5.2 Thermal conductivity
Foamed concrete has a lower thermal conductivity than conventional concrete.
This is due to the inclusion of air bubbles which have very low thermal conductivity. The
thermal conductivity of foamed concrete is generally accepted as being dependent
primarily on the density. Other factors which affect the thermal conductivity include
moisture content, temperature level, raw materials, pore structure, etc. and will be
discussed further in the later sections. The test method and the apparatus used may have
an influence on the thermal conductivity values. Thus, comparisons between test results
obtained with different methods and equipment should only be made if their influence is
known.
2.5.2.1 Effect of density
The effect of density on thermal performance of aerated concrete was studied
extensively by De Rose and Morris (1999), Loudon (1983), Weigler and Karl (1979) and
Shrivastava (1977). It was found that the higher the density, higher the thermal
conductivity. This is because a denser solid material would propagate heat by conduction
faster as the particles of the solid are more closely packed. Thus at a higher rate of atomic
vibration, collision of the particles (or the transfer of heat energy) takes place faster.
Narayanan and Ramamurthy (2000) commented that thermal conductivity of
aerated concrete is largely a function of density. It does not matter whether the product is
moist cured or autoclaved as far as thermal conductivity is concerned. Rudolph and
35
Valore (1954) also reported similarly that thermal conductivity data from various sources
are in good agreement and are a function of density from 10 to 70 lb per cu ft (160 to
1121 kg/m3), regardless of composition, cell-forming process, or curing and possibly
different types of specimens and test conditions as shown in Figure 2.7.
Figure 2.7: Relationship of thermal conductivity to density for moist-cured and autoclaved cellular
concretes of various compositions and made by various processes. (Data from 17 different sources
and NBS test)
Weigler and Karl (1980) investigated on the properties of structural lightweight
aggregate concrete with reduced density by adding foamed into the concrete mix –
Lighweight aggregate foamed concrete (LAF-concrete). Their intention was to reduce the
density of concrete for load bearing and stiffening structural members and to improve the
thermal insulation properties and thus extend the scope of application of structural
lightweight concrete.
Figure 2.8 shows the thermal conductivity values of LAF-concrete together with
lightweight concretes including foamed concrete. For 20 % of entrained air, the
concrete’s density is reduced by 20 % and the thermal conductivity by 25 %. Compared
36
to other kinds of lightweight concrete of the same compressive strength, LAF-concrete
has a lower thermal conductivity. For a dry density between 700 to 1000 kg/m3, the
highest strength of 5 to 14 MPa were obtained using lightweight aggregates (expanded
clay and expanded shale) with a particle density between 0.6 and 0.9 kg/m3.
Figure 2.8: Thermal conductivity of lightweight-aggregate foamed concrete and various other types
of lightweight concrete at a moisture content of 5 % by volume as a function of the dry density of the
concrete.
2.5.2.2 Effect of moisture
Since moisture will always be present in concretes exposed to the environment
and that moisture would increase the thermal conductivity of concretes, normally a
moisture correction factor is employed to adjust the thermal conductivity obtained from a
particular oven dry density. There are two aspects of moisture correction. Firstly, the
practical moisture content has to be decided and secondly, measured thermal
conductivities have to be multiplied by an appropriate moisture factor to obtain the
thermal conductivity of the practical moisture content.
37
There are a number of moisture correction curve available. The one used in UK is
commonly known as the ‘Jakob’ moisture curve, since it appeared in Jakob’s 1949 book
on Heat transfer. Figure 2.9 compares results on AAC by Jespersen with the Jakob
moisture curve. It was shown that agreement with the Jakob curve is fairly good at
moisture contents above 2 % by volume, below 2 %, agreement is poor. The moisture
correction curve in France is the same as in UK. For the German moisture correction as
described in DIN 52612, it represents a 6 % change in thermal conductivity for each 1 %
change in moisture content by volume. This slope is lesser than that of the Jakob moisture
curve which is about 11 % change in thermal conductivity for 1 % moisture content by
volume in the range of 1 to 5 %. In USA, a different moisture correction curve which is
based on moisture content by weight rather than by volume. Valore, 1980 proposed a
change of 4 to 6 % in thermal conductivity for 1 % change in moisture content by weight.
Figure 2.9: a) The ‘Jakob’ moisture correction; b) Jespersen’s data on thermal conductivity versus
moisture content of AAC at different densities
a b
38
Loudon (1983) did experiments on concrete material of different densities to
investigate whether the moisture correction should be related to moisture content by
volume or by weight. Experimental details are described in Loudon (1983). Loudon
found that Jakob moisture factor over-calculated the thermal conductivity values.
Experimentally-determined moisture factors for AAC correlate better with moisture
content by weight than moisture content by volume. For AAC, a moisture correction of 4
% increase in k value for 1 % increase in moisture content in AAC by weight seemed
appropriate (Figure 2.10).
Lippe (1992) and Laurent and Guerre-Chaley (1995) also found an increasing
trend of k value of AAC as moisture content increases. Kudriashev (1949) who studied
on thermal conductivity values for lime-silica autoclaved cellular concretes (density from
497 to 993 kg/m3) containing different percentages of free moisture and reported a 4 %
increase in thermal conductivity for each percent increase in density due to free moisture.
Whereas, Graf (1949) reported a slightly higher value of 6 % increase in thermal
conductivity value for various cellular concretes for each percent increase in density due
to free moisture. The rationale behind is that some of the air gaps in the solid matrix is
replaced with water and since water has a conductivity of about 25 times that of air, the
thermal conductivity of the concrete increases. Additional heat can also be transferred
across air spaces by an evaporation-condensation process.
39
Figure 2.10: Moisture factor λ / λdry vs moisture content by weight (Loudon, 1983)
2.5.2.3 Effect of mineral Admixture
The addition of fly ash has the effect of decreasing thermal conductivity of
foamed concrete. A 30 % replacement of cement by fly ash was found to decrease k by
12 to 38 % as found by Giannakou and Jones (2002). This was attributed to the lower
density and cenospheric particle morphology of fly ash, which increases the heat flow
path.
De Rose and Morris (1999) studied on the effect of lime and fly ash on the
thermal conductivity of foamed concrete with fixed w/c ratio and fixed density. They
reported that lime and fly ash both had an influence on thermal conductivity. Adding lime
as an additive to the mix increased the k –value. A 10 % addition of fly ash which was
used as a replacement for the cement reduces k –value, following the trend of the results
by Giannakou and Jones (2002) as shown in Figure 2.11.
40
Figure 2.11: Thermal conductivity at fixed w/c ratio and fixed density
2.5.2.4 Effect of pore structure
The pore structure of a material often plays a dominant role in controlling their
useful physical and functional properties including thermal conductivity, and thus is of
importance in the evaluation of performance of the material. Thus, it is important to know
the relations between the pore properties for example the scale, the extent, connectivity of
the pore network in porous materials and other physical and functional properties of the
material. However, the effect of pore structure, size of pores, the shape, the arrangement
of combination of different pore sizes on thermal conductivity of foamed concrete seems
to be lacking.
There are many studies on the factors affecting the effective thermal conductivity
of two-component materials. For example, Meredith and Tobias (1962) who investigated
on analytical models to predict thermal conductivity of a two-component material,
commented that neither the size distribution of the discrete particles in a two-component
material nor the manner in which they are deployed are of consequence if the
concentration of the discrete phase is sufficiently dilute. However, these factors must be
considered if their concentration is increased. This suggests that the effects of discrete
41
particles properties like size distribution and arrangement on effective thermal
conductivity of the two-component material are dependent upon its volume fraction.
Zhang and Liang (1995) who also studied the effective thermal conductivity of
mixed solids materials using numerical analysis found that the effective thermal
conductivity of 2 materials mixed together (one being the discrete phase and the other
being the continuous phase) is dependent upon the volume fraction of the discrete phase,
rather than its size or dimension.
2.5.2.5 Effect of temperature
When the temperature at the hot and cold side of the heat flux meter is increased,
the heat energy being transferred to the particles inside the foamed concrete is increased,
causing more vigorous vibration of the particles and also increases the rate of collision
between particles. Thus, the rate at which heat is conducted through conduction is
increased, resulting in a higher thermal conductivity in specimens which are tested at
higher temperature. The effect of increasing temperature of aerated concrete is to increase
thermal conductivity as observed by Marmoret (1999) and Laurent and Guerre-Chaley
(1995).
2.5.2.6 Effect of age
There is limited literature on the effect of age on the thermal conductivity of
foamed concrete. However, Khan (2002) and Kook et al. (2003) studied the effect of age
on thermal conductivity of a series of specimens (normal weight concrete, cement paste
with gravel, cement mortar and cement paste) which was moist-cured at 20 oC and tested
42
at 3, 7, 14 and 28 days. Their results showed that age hardly affects thermal conductivity
values except at very early age when the cement paste is still hydrating.
2.6 Analytical models to predict thermal conductivity of foamed concrete
In order to ‘design’ an ideal foamed concrete with a suitable thermal conductivity
for its intended purpose, it is essential to know the relation of the effective thermal
conductivity. A great number of analytical models can be used to predict the effective
thermal conductivity of a heterogeneous material exist in the literature. Most theoretical
models are based on certain hypotheses to attempt to depict the physical reality using
simple models with varying accuracy.
Several important factors affect the thermal conductivity of a material. These
include the thermal conductivity of its constituents (discrete and continuous phase), size
and shape, volume fraction, dispersion (degree of mixing) of the discrete phase. Since air
bubbles in foamed concrete are typically spherical and thus isotropic, so their orientation
is not significant. The geometrical structure of the system is important. The following
section will cover the available mathematical formulas in the literature which are used to
correlate the effective thermal conductivity of a mixture with the thermal conductivities
and volume fractions of the individual components. They mainly differ in the
assumptions of their geometrical structures. These available formulas together with their
assumptions and geometrical structures will be compared and their critiques discussed
further here.
43
2.6.1 Series slab and parallel tube model
The most basis model for purposes of analysis of thermal conductivity is that in
which the two components in a mixture are arrayed in alternative parallel layers as shown
in Figure 2.12. If the heat flow is parallel to the layers, the effective thermal conductivity
is given by
(2.6)
where f1 and f2 are the volume fractions of the components having thermal conductivities
λ1 and λ2. If the heat flow is perpendicular to the component layers, the expression of
effective thermal conductivity is given by
(2.7)
These two expressions represent the extreme limits of the true effective thermal
conductivity of a two-component mixture. These limits are shown in Figure 2.13 for the
case of λ1 = 10λ2. Although both of them predict thermal conductivity values
intermediate between the conductivities of the individual components, the conductivity
obtained is very different for the two cases. Thus these limits are of relatively little use
except for laminated materials or unidirectional composite with continuous fibers and are
not suitable for the prediction of thermal conductivity for foamed concrete.
However, from these two simplest models, it is possible to obtain tighter limits for
the thermal conductivity of a two-component mixture by calculating the apparent
effective conductivity.
44
Figure 2.12: Two-phase material with phases distributed as parallel slabs.
Figure 2.13: Effective thermal conductivity of a laminated material with heat flow parallel or
perpendicular to laminations.
Several investigators have represented a disperse second component by a different
geometrical structure, in a cubic array of cubes as shown in Figure 2.14 instead of the
slabs and tubes in Figure 2.12.
Series slabs
As shown in Figure 2.14, the mixture is divided into slabs (A) containing no disperse
second component and into slabs (B) containing both continuous and disperse
45
components. The effective conductivity of the B-slabs is computed, by assuming the
disperse and continuous components act as conductors in parallel. The effective
conductivity of the mixture is computed by taking the A-slabs and the B-slabs in series.
Figure 2.14: Cross-section of the model in which a disperse second phase is considered to be a cubic
array of cubes.
The expression to predict the effective thermal conductivity, λ of a two-component
mixture is given by:
(2.4)
whereby Pa is the fraction of the total area which contains the disperse component of
conductivity λd and (1- Pa) is the fraction of the area which contains the continuous
component of conductivity λc. Pl is the fraction of the total length containing the disperse
46
component. The geometrical assumption of the series slab and parallel tube can be
applied to the dispersions of, for example, fibers or platelets oriented parallel or
perpendicular to the flow of heat.
For a disperse component in the form of cubes or in which cubes may be used to
approximate an isometric discrete component, Equations 2.6 and 2.7 may be recast in
terms of the volumetric fraction of disperse component, which is designated as f. For the
model used, it is easily seen that Pa = f 1/3 and P l = f 2/3; with these substitutions, the forms
usually seen are obtained:
Series Slabs:
(2.8)
Parallel Tubes:
(2.9)
These expressions may look complicated, but the model reduces to the two simple
electrical networks as shown in Figure 2.14. The series-slabs model, always
overestimates the effective thermal conductivity since the continuous component has an
infinite thermal conductivity normal to the principal flow of heat. On the other hand, the
parallel-tubes model effectively assumes that the continuous component has zero thermal
conductivity normal to the principal flow of heat, thus this approach always
underestimates the effective thermal conductivity. Thus, these two methods may not be
47
able to predict the effective thermal conductivity of foamed concrete accurately based on
its models assumed.
2.6.2 Geometric mean model
When a series distribution of the phases and their resistance to heat flow is
assumed, a lower bound effective thermal conductivity of a heterogenous mixture is
obtained. On the other hand, when a parallel distribution is assumed, an upper bound is
obtained. The weighted geometric mean of the constituents’ thermal conductivity
sgsgeff
εελλλ = (2.10)
has been proposed by Woodside and Messmer (1961) as a suitable intermediate between
these two extrema to find a better prediction of the thermal conductivity value. λeff
represents the effective thermal conductivity of the two-component mixture, λg and λs
represent the thermal conductivity and εg and εs represent the volume fractions of the
discrete and continuous phase respectively.
2.6.3 Assad Model
Assad proposes an empirical relationship that is very similar to the geometric
mean equation: the ‘Assad’ equation is
(2.11)
where m = cε and c 1. When c= 1, this equation is identical to the geometric mean
equation. By choice of the average value of m = 0.868ε for clayey aerated concrete (CAC)
and clayey wood concrete (CWC) and m = 0.810ε for autoclaved aerated concrete (AAC),
this model was used to predict the mean effective thermal conductivity within an error of
48
less than ±5 % for CAC and CWC against a higher error of ±20 % for AAC. This model
allows some flexibility to choose an appropriate value for the parameter, m to model the
effective thermal conductivity of a two-phase material. (Goual et al., 1999)
2.6.4 Maxwell model
Maxwell derived an expression for the conductivity of a two-component
dispersion of spherical particles (instead of cubic discrete phase) of conductivity, λd
imbedded in a medium of conductivity λc. λ is the effective thermal conductivity of the
two-component material. Maxwell’s relation can be written in the form:
(2.12)
This expression is rigorously valid for dilute dispersions where the average distance
between dispersed particles is much larger than the particle size and should be accurate
for volume fraction of discrete phase, f ≤ 0.1. Thus, this expression should be suitable for
foamed concrete with volume fraction of the discrete air particles smaller or equal to 0.1.
However, for foamed concrete, the volume fraction of air particles can be significantly
higher than 0.1, thus this expression may not be accurate for concrete with higher foam
content.
2.6.5 Meredith and Tobias Model
For higher concentration of dispersed components, with volume fraction higher
than 0.1, Lord Rayleigh treated the case of uniform spheres arrayed in a cubic lattice
49
distribution. Meredith and Tobias (1962) extended Rayleigh’s derivation by an additional
term and obtained:
(2.13)
Equation 2.13 should be more accurate than Equation 2.12 for values of f from 0.1 up to
π/6 = 0.524, which is the maximum possible value for a cubic array of spheres. For
dispersions which are sufficiently dilute for Equation 2.12 to be valid, neither the size
distribution of the disperse particles nor the manner in which they are deployed are of
consequence. However, these factors must be considered if the concentration of the
dispersed component is increased.
2.6.6 The self-consistent model
Figure 2.15 shows the geometrical model for generalized self consistent scheme
assumed by Kerner (1956). The geometric model consists of a typical inclusion of
spherical shape being imbedded in a concentric spherical matrix shell. The composite
sphere thus obtained was then embedded in a homogeneous and isotropic medium of the
effective thermal conductivity of the composite model. This model is quite different
from the rest of the other models which are either a cubic array of cubes or of spheres.
Concentric model does not restrict the volume fraction of spherical discrete phase
like in the case of Meredith and Tobias model which only allow a maximum volume
fraction of greater than π/6 = 0.524 (which is the maximum possible value for a cubic
array of spheres) to be modeled. Thus, this could be useful to predict the effective
50
thermal conductivity of foamed concrete with very high air content. Moreover, the
spherical geometry assumed by the self-consistent model is consistent with the actual
shape of the air inclusion into foamed concrete. Equation 2.14 shows the formula of the
effective thermal conductivity with respect to the porosity and the thermal conductivity of
the continuous solid medium which is the cement matrix. (Hashin, 1968)
Figure 2.15: Geometrical Model for Generalized Self Consistent Scheme
(2.14)
where is the effective thermal conductivity of the composite material. A typical
spherical particle of arbitrary radius a, consists of material of conductivity k2. The particle
is embedding a concentric matrix shell of unspecified radius ρ, the matrix conductivity
being k1.
Boutin (1996) used the self-consistent method to determine the thermal
conductivity of autoclaved aerated concrete (AAC). He showed that this method is
efficient for autoclaved aerated concrete as its microstructure contains very different-
51
sized pores. His studies showed that the predicted thermal conductivity obtained using
the self-consistent method was reported to be in excellent agreement with the
experimental data.
2.7 Polymer-Modified concrete (PMC)
2.7.1 Background knowledge
Polymer-modified concrete (PMC) is defined as Portland cement and aggregate
combined at the time of mixing with organic polymers that are dispersed or redispersed in
water. This dispersion is called latex, and the organic polymer is a substance composed of
thousands of simple molecules combined into large molecules. These simple molecules
are known as monomers and they go through a reaction called polymerization whereby
they are combined.
A polymer generally contains about 50 % polymer by weight of spherical and
very small (0.01 to 1 microm in diameter) polymer particles held in suspension in water
by surface-active agents. The presence of surface-active particles agents in the latex tends
to incorporate large amounts of entrained air in concrete; therefore, air entraining agents
are usually added to commercial polymer. The spherical polymer molecules and the
entrained air associated with the polymer usually provide excellent workability. Typically,
water/cement ratios are in the range 0.40 to 0.45, and cement contents are of the order
390 to 420 kg/m3. (Kumar M. P. and P.J.M. Monteiro, 1997)
Two processes occur in latex modification of Portland cement mortar and
concrete, namely cement hydration and latex coalescence. Cement hydration generally
occurs first and as the cement particles hydrate and the mixture sets and hardens, the latex
52
particles become concentrated in the void spaces. As water is continuously removed by
cement hydration, evaporation, or both, the latex particles coalesce into a polymer which
is interwoven in the hydrated cement giving a comatrix that coats the aggregate particles
and lines the interstitial voids.
The hardened cement paste is predominantly made up of an agglomerated
structure of calcium silicates, aluminates, and hydroxide bound together by relatively
weak Van der Waal’s forces. The latex being incorporated into the cement paste helps to
reduce rate and extent of moisture movement by blocking the passages whereby
microcracks are formed caused by stresses during drying shrinkage. The latex polymer
film also bridges the microcracks formed and prevents propagation. Thus, tensile strength
and fracture toughness of the polymer-modified concrete is increased. Moreover, the
ingress of fluids like water or soluble salts is hindered due to the passage way of
microcracks being blocked. This naturally increases both the chemical and frost
resistance of concrete.
The optimum degree of polymer modification is usually obtained at about 10 to
20 percent dry latex solids by weight of cement of the mixture. Too low a percent of latex
will not have a significant contribution to the overall properties and not able to harness
the water-reducing effects of the latex, and thus, require more water in the mix for
equivalent workability. This effect of less polymer and more water will degrade the
hardened properties of the mortar and concrete. If too much latex is used, it is not
economical and it can cause excessive air entrainment, and can cause the mixture to act
as a polymer filled with aggregates and cement. (ACI Committee 548)
53
Latexes which are commonly used with hydraulic cements are synthetic
elastomeric polymers like styrene-butadiene rubber (SBR), polychloroprene and
Thermoplastic polymers like polyacrylic ester, styrene-acrylic, vinyl acetate copolymers
and also polyvinyl acetate. There are some improvements in the properties of concrete
being modified by polymer. The final product will have improved bond strength to
concrete substrates, increased flexibility and impact resistance, improved resistance to
ingress of water and dissolved salt and also improved resistance to frost action.
Polymer composition has a significant effect on the properties of the cured
concrete. The effect of various volume fraction of polymer in cement paste and also
formed concrete on thermal conductivity of the materials and the strength and durability
properties will be investigated. Thus, by adding polymer into foamed concrete,
composites which are lightweight, high strength, insulating and weather-resistant can be
produced. Some field applications may include external insulation on concrete block or
cast-in-place roof insulation.
Acrylic latexes have been used for modifying hydraulic cement mixtures for more
than 30 years to improve properties like adhesion, abrasion adhesion, impact strength,
flexural strength, and resistance to permeability. In order to obtain maximum physical
properties, acrylic latex-modified cement mortars should be cured in air. This is because
when latex is allowed to coalesce and form a film through the removal of water, the full
potential of increasing the properties of the mortar is achieved.
2.7.2 Properties of PMC
A review of the literature shows that there has already been much work done to
investigate the properties of polymer-modified mortars and normal weight concrete
54
(Ohama, 1987, Ray et. al, 1994, Afridi et. al, 1994, Mindress et. al, 2003). These studies
show that polymers are added to concrete to improve its workability, drying shrinkage,
strength and durability. There are also reports of properties of polymer-modified
lightweight aggregate concrete (Fontana et al. 1987). However, there are only a few
studies about the use of polymer on lightweight aggregate concrete (LWACs). Reports of
mechanical and thermal properties of foamed concrete with polymer corporated are
almost non-existent. Thus, since information on how polymer will affect the total air
content in foamed concrete which in turn affects the properties of polymer-modified
foamed concrete is lacking, more research in this area is needed.
The compressive strength of LMC is often higher than that of an unmodified
concrete under dry curing conditions because strength continues to develop beyond 28
days. This is attributed not only to the development of the polymer film, but also to the
fact that the polymer inhibits loss of water from latex-modified concrete, LMC. Hence,
the cement can hydrate more completely under these conditions. However, relative
improvements in strength are greater under flexural and tensile loading seen from Table
2.5. Also, LMC has a higher micro strain at failure in tensile loading as shown in Figure
2.20. The greater linearity of the stress-strain curve indicates that more microcracking
occurs prior to failure. It is believed that the polymer films inhibit the propagation of
microcracks because of their high tensile strength. Furthermore, the ability of the film to
form fibrils on rupture provides stress transfer behind the crack tip, thereby reducing
stress concentrations and keeping cracks closed.
2.7.2.1 Mechanical Properties
55
Table 2.5: Mechanical Properties of Latex-modified concrete
Figure 2.16: Tensile stress vs microstrains of polymer-modified concrete with different percentages
of polymer
56
The increased durability of LMC relative to plain concrete can be attributed to
three factors. Firstly, the polymer film lining capillary pore surfaces impedes water
absorption and permeability and prevents the entry of aggressive agents. Secondly, the
improved resistance to tensile cracking reduces the formation of a network of
microcracks that can assist in water transport. When cracks do form, filaments of
polymer, which bridge the cracks, keep them closed. Thirdly, the lower w/c ratio
provides generally improved durability. The air entraining properties of the latex will
naturally provide frost resistance. (Mindress et. al, 2003)
Rossignolo and Agnesini (2002) also studied the mechanical properties of
styrene-butadiene rubber (SBR) modified lightweight aggregate concrete (LWACs). The
main objective of their study is to provide some basic information on the properties of
high performance LWACs using Brazilian LWAs, natural sand, superplasticizer, silica
fume and SBR latex. Properties in the fresh state, compressive strength, splitting tensile
strength, flexural strength, and water absorption of the LWACs were tested. The
inclusion of SBR latex in LWACs decreases the water-(cement and ground granulated
blast furnace slag) [N/(C+S)] ratio.
The compressive strength of SBR-modified LWACs is slightly lower than that of
unmodified LWACs. A decrease in the 7-day compressive strength is, on average, 3.0 %
and 4.4 % at a polymer-cement ratio (P/C, as solid polymer content by mass of cement)
of 5 % and 10 % respectively. This is attributed to an increase in the air content of SBR-
modified LWACs caused by air entrainment.
57
The tensile strength increase is, on average 10 % at a P/C of 5 % and 18 % at a
P/C of 10 %. The flexural strength increase is, on average 16 % at P/C at 5 % and 26 % at
a P/C of 10 %. Such superior properties are attributed mainly to an overall improvement
in cement hydrate-aggregate bond because of a decrease in W/(C+S) and the high tensile
strength of SBR films present in SBR-modified LWACs.
ACI Committee Report 548 reported the strength properties of acrylic-modified
concrete. It was reported that the flexural and tensile strength properties of acrylic-
modified mortar of air-dried specimens are significantly higher than wet-cured specimens
(1 day at 95 % relative humidity plus 6 days immersion in water). Figure 2.17 shows the
flexural modulus (ASTM D 790) of latex-modified mortars as a function of the polymer-
cement ratio by mass. Modification of cement mixtures with acrylic, results in increased
flexibility of the hardened mortar and concrete.
Figure 2.17: Flexural modulus versus acrylic polymer-cement ratio of Portland cement mortar
58
2.7.2.2 Thermal conductivity
There is a major concern of whether concrete, especially lightweight ones have
the ability to maintain its low thermal conductivity in the environment it is used. (Fontana
et al. 1987) Aerated concrete or lightweight concrete is susceptible to water absorption
due to its high porosity. The increase in moisture content within the material has an effect
of increasing the thermal conductivity quite significantly.
There are some recent papers by Ohama (1998) and Fowler (1999) which
reviewed the recent developments and uses of polymer-modified concrete. Polymer was
used to reduce the amount of water absorption in lightweight aggregate concrete so that
their thermal conductivity will not increase due to the intrusion of rain water during its
application. Fontana et al. (1987) have developed lightweight polymer concrete
composites with excellent insulating properties. Lightweight aggregates used are
expanded perlites, glass nodules or hollow alumina silicate microspheres bound together
with unsaturated polyester or epoxy resins.
Expanded perlites are still being used in thermal insulation applications. For
example in India, Keltech Energies Ltd., a leading manufacturer of expanded perlite has
been involved in the manufacture & installation of large perlite concrete blocks for LNG
tanks. Perlite is a natural lightweight siliceous aggregate which is capable of expanding
up to 25 times its original volume upon heating to around 860oC. The large amount of air
voids that are produced in the expansion process is responsible for expanded perlite
excellent insulation property. Glass nodules are also being used currently as loose fill
insulation.
59
These insulating polymer concrete (IPC) with densities of 480 to 960 kg/m3 has
thermal conductivity values ranging from 0.1557 to 0.3287 W/m.K. They have excellent
durability to freezing and thawing due to their low water absorption rate and low
permeability. The compressive strength of the IPC allows it to be used for structural
purposes.
2.7.2.3 Durability
Studies by Rossignolo and Agnesini (2002) show a significant decrease in water
absorption with the inclusion of SBR-latex in unmodified LWACs. The water absorption
of SBR-modified LWACs is, on the average 3.7 % at a P/C of 5 % and 2.3 % at a P/C of
10 %, compared with that of 6.5 % on average for unmodified LWACs.
The decrease in water absorption of SBR-modified LWACs is due to a reduction
in permeability, caused by a reduction in W/(C+S). Such W/(C+S) reduction affects the
gel-space ratio and causes a reduction in the capillary porosity of the system. Polymer
films present in SBR-modified LWAC surfaces also contribute to a reduction in the water
absorption.
ACI Committee Report 548 also reported the durability property of acrylic-
modified concrete. Figure 2.18 shows the results of chloride ion penetration of
unmodified and acrylic latex-modified Portland cement concretes. Adding acrylic to
mortars and concrete can help to reduce permeability of the amount of chloride ion.
60
Figure 2.18: Chloride ion penetration of unmodified and acrylic latex-modified Portland cement
concretes
Studies done by Lim (2005) on water absorption of polymer-modified foamed
concrete is slightly reduced as compared to unmodified ones as shown in Figure 2.19.
The specimens’ densities are the range of 1000 kg/m3, with 50 % foamed content but
polymer content varying from 5- 15 % of cementitious material used. The reduction is
about 4 % for an increase in 5 % polymer content. A decrease in the water absorption of
polymer-modified foamed concrete is attributed mainly to a reduction in permeability,
caused by a reduction in w/c ratio. Such w/c reduction ultimately affects the gel-space
ratio and causes a reduction in the capillary porosity of the system. The water-resistant
performance of foamed concrete modified by acrylic is not as beneficial as expected.
Other additives can be added to foamed concrete reduce the water absorption further.
61
Graph of water absorption vs polymer content
37.7
36.9
34.9
33.5
30
31
32
33
34
35
36
37
38
39
40
0 5 10 15 20
Polymer content (% of cementitious material)
Wa
ter
ab
so
rpti
on
(k
g/m
^3
)
50 % foamedconcrete withpolymer
Figure 2.19: Graph of water absorption of polymer-modified foamed concrete vs polymer content
2.8 Flat roofing systems
A new ferrocement roofing system for HDB blocks has been used to replace the
old practice which consisted of a roofing system consisting of grade 40 reinforced
concrete slab laid at a gradient of 1:50, a layer of waterproof membrane and an elevated
secondary roofing slab. A layer of trapped air between the main and secondary roofs
prevents heat transmission to the dwellings below.
The precast ferrocement roofing slab is made of high grade mortar reinforced with
layers of galvanised fine wire meshes. It is 600 mm x 900 mm and 20 mm thick. It has
good thermal and shrinkage cracking resistance and is also impervious to water
penetration. This material is a thinner and lighter building cladding element with a greater
strength than normal concrete. It is applied in the form of thin secondary roof slabs which
serve to insulate the main roof from intense heat and to drain away rain water (See Figure
2.20).
62
This new roofing system simplifies the overall roof construction process as they
can be installed easily on site. It helps to reduce tedious work of applying a waterproof
membrane on the main roof slabs and also maintenance costs by eliminating the need for
waterproofing membranes. Ferrocement is used as attractive façade features in many of
HDB’s upgrading projects. Its use has also been extended to cladding of service ducts.
Figure 2.20: a) Stools are placed on the main roof to support the secondary roof; b) Trial installation
of ferrocement secondary roof in Sembawang (Singapore)
Numerical studies were done by Chew (2005) using FLUENT software to provide
information on the effectiveness of using different thickness or air gap to provide thermal
insulation for HDB’s secondary roofing system. Chew’s studies showed that air gap may
not necessarily be an effective thermal insulation material for roofing application despite
its low thermal conductivity value. Thicker air gap would lead to the formation of
convection currents. This would in turn bring about the transfer of heat through the bulk
movement of the air particles.
The onset of the convection currents for thicker air gaps could be seen clearly
from the pictures of the streamlines for different air gap thickness in Figures 2.21-2.24.
However, if the air gap layer is too small, though heat transfer by conduction dominates,
the overall amount of heat transferred which is a function of the thickness will still be too
63
high to provide effective thermal insulation. His results have shown that the optimum
thickness of air gap which minimizes the heat transfer is about 160 mm as shown in
Figure 2.25.
The airspace resistance to heat is dependent on not only conduction, but also
convection and radiation in and across the air space. The influencing factors include: a)
thickness of the airspace, b) flow of air in the air space, c) surface properties (emissivity)
and d) direction of heat flow (horizontally or vertically).
For unventilated cavities, thermal resistance increases with increase in cavity
thickness up to a width of 25 m. For larger gaps, convection becomes important and
thermal resistance does not increase.
Figure 2.21: Streamline picture (air gap thickness 10 cm)
Figure 2.22: Streamline picture (air gap thickness 25 cm)
64
Figure 2.23: Streamline picture (air gap thickness 40 cm)
Figure 2.24: Streamline picture (air gap thickness 100 cm)
Besides air, Chew (2005) also analyzed other insulation materials with FLUENT
to find out the heat flux transferred by each material. It was reported that LECA 500
loose fill and foamed concrete with 75 % foam will give the best thermal insulation. For
an insulation thickness of about 25 cm, LECA 500 lightweight concrete can be twice as
effective as air in providing thermal insulation.
Foamed concrete is several times better than air or normal weight concrete in
terms of thermal insulation performance. However, it is important to note that though
foamed concrete with high foam content exhibit excellent thermal insulation property, it
has very low structural strength which makes it only suitable for non-structural
application. For structural usage, the amount of foam in foamed concrete has to be lower.
In Singapore, it is stated that all structural concrete has to be at least grade 30 in CP 65.
65
0
10
20
30
40
50
60
70
80
0 5 10 15 20 25 30
Thickness of insulation (cm)
He
at F
lux (
W/m
2)
Air (Experimental)
Air (Simulation)
Figure 2.25: Relationship between heat flux and air thickness (using results obtained experimentally
and by simulation using FLUENT)
66
3 Experimental Details
This chapter will focus on giving more information on how the various
experiments were done in the midst of this research project. Information on the
preparation, mix design and designation of the concrete specimens and the properties of
the various constituents of the concrete specimens will be available. The experiments for
this research project are mainly measurement of thermal conductivity, compressive
strength, other mechanical properties of foamed concrete and polymer-modified foamed
concrete and also microscopy study. Thus, details on the thermal conductivity testing
procedures using heat flow meter to investigate the effects of foam content, water-cement
ratio, temperature and polymer content will be described. Experimental procedures like
compressive strength, modulus of elasticity, modulus of rupture, splitting tensile and
microscopy study are also stated in the following sections.
3.1 Materials, casting and curing
Equal portions of Ordinary Portland Cement (OPC) and Ground Granulated Blast
Furnace Slag (GGBFS) were used to form the paste of the foamed concrete. The
chemical composition and physical properties of OPC and GGBFS are given in Table 3.1.
The superplasticiser used for improving workability was Super 20, a ready-to-use
aqueous solution of a modified naphthalene sulfonate and selected highly purified
organic compounds. Super 20 is a low viscosity liquid that contains no chloride and has
been formulated to comply with BS 5075: Part 3: 1985.
67
The polymer used is 100 % acrylic emulsion, which contains 47 % solids by mass.
Its appearance is a milky emulsion and it is non-ionic. Its density at 25oC is 1.06 kg/litre.
Protein-based foaming agent with a specific gravity of 1.1 was used to produce
preformed foam using a foam generator. It cost slightly more than S$3 per litre.
The casting of foamed concrete was done according to ASTM C 796-97. The
ambient temperature during mixing and casting was 27 ± 3o. Immediately after casting
and finishing, the specimens were covered with plastic sheets to avoid direct exposure to
wind and hence minimize evaporation. The covered specimens were kept at the same
temperature until demoulding. After 24 hours, the specimens were demoulded and stored
in the fog room for curing. Concretes were moist-cured in a fog room at 30±2oC and
100% RH for 28 days before using for macrostructure study.
The casting of polymer-modified foamed concrete was done in a similar way as
that of foamed concrete except that acrylic polymer was added to the mixing water of the
mix. OPC and GGBFS were first added to the mixer, followed by mixing water with
acrylic polymer incorporated and lastly, foam and superplasticiser were added in and
mixed well. After casting and finishing, the specimens were also covered with plastic
sheets to avoid rapid hydration during the first 24 hours to avoid surface cracking. The
covered specimens were kept at the same temperature until demoulding. After 24 hours,
the specimens were demoulded.
To obtain maximum physical properties, acrylic latex-modified cement mortars
were cured in air. This procedure is in contrast to unmodified mortar for which optimum
strength properties are achieved by continuous wet-curing. The reason for this difference
is that in order for the latex to beneficially modify the properties of the mixture, it must
68
be allowed to coalesce and form a film. The removal of water is crucial in this film-
forming process. Thus, acrylic latex-modified foamed concrete specimens for this study
were air-cured at room-temperature condition for 28 days before using for macrostructure
study.
Table 3.1: Physical properties and chemical compositions of ordinary Portland cement and ground
granulated blast furnace slag
Composition Specific
gravity
Fineness
(cm2/g),
Blaine
SiO2 Al2O3 Fe2O3 CaO MgO SO3 K2O Na2O
OPC 3.15 3130 20.57 5 3.23 64.3 2.35 2.57 0.7 0.07
GGBS 2.90 4480 32.50 13.80 0.2 42.9 5.8 2 - -
3.2 Mix design and designation
The mix design of the concrete specimens prepared is tabulated in Table 3.2 and
Table 3.3. Mixes are designated according to their types. Five foamed concrete
specimens were represented by Series ‘F’ (F1 to F5), with foam content ranging from 25
% to 70 % and water-cement ratio (w/c) ranging from 0.35 to 0.55. For cement paste,
three specimens of different w/c 0.35, 0.45 and 0.55 were cast, and they are represented
by Series ‘C’ (C1-C3).
Polymer-modified foamed concrete are represented by Series ‘PF’ (PF1-PF6).
Four of them (PF1-PF4) have the same amount of foam content of 50 %, but have
varying contents of polymer, ranging from 5 % to 20 %. P5 and P6, on the other hand,
have the same amount of polymer content of 10 %, but having different foam content of
20 % and 80 % respectively. The series ‘CP’ (CP1-CP4) are cement paste with varying
amount of polymer from 5 % to 20 %.
69
Table 3.2: Mix Design of foamed concrete and cement paste specimens
Mix Designation
Foam content
(%) w/c ratio
Fresh Density (kg/m3)
Cement (kg/m3)
GGBS (kg/m3)
Water (kg/m3)
Foam (kg/m3)
F1 50 0.45 1000 335 335 302 27.6
F2 70 0.45 550 193 193 173 40.6
F3 25 0.45 1440 477 477 429 14.8
F4 50 0.35 1070 385 385 270 27.6
F5 50 0.55 900 297 297 327 27.6
C1 0 0.45 1860 640 640 576 0
C2 0 0.35 1980 734 734 514 0
C3 0 0.55 1760 567 567 624 0
Table 3.3: Mix Design of polymer-modified foamed concrete and cement paste with polymer
specimens
Mix Designation
Foam content
(%) w/c ratio
Fresh Density (kg/m3)
Cement (kg/m3)
GGBS (kg/m3)
Water (kg/m3)
Polymer (kg/m3)
Foam (kg/m3)
PF1 50 0.35 1020 354.4 354.4 230.1 35.4 33.5
PF2 50 0.35 960 342 342 205.2 68.4 33.5
PF3 50 0.35 1000 331 331 182 99.3 33.5
PF4 50 0.35 960 320.5 320.5 160.3 128.2 33.5
PF5 20 0.35 1580 547.5 547.5 328.5 109.5 13.4
PF6 80 0.35 478 137 137 82.2 27.4 53.6
CP1 0 0.35 1940 708.5 708.5 460.5 70.9 0
CP2 0 0.35 1920 684.5 684.5 410.7 136.9 0
CP3 0 0.35 1900 662 662 364.1 198.6 0
CP4 0 0.35 1880 641 641 320.5 256.4 0
3.3 Experimental Procedures
3.3.1 Thermal conductivity
Before the concrete specimens are tested for their thermal conductivity value by
means of the heat flow meter, they are oven dried at a temperature of 105 oC for 24 hours
and cooled for 4-5 hours to let the temperature gradually drops to about room temperature.
Foamed concrete specimens were tested for their thermal conductivity values at age 7
days and 28 days, whereas polymer-modified foamed concrete specimens were tested
70
only at age of 28 days. A picture of the test specimens (300 x 300 x 50 mm) for
measuring thermal conductivity is shown in Figure 3.1.
Figure 3.1: Foamed concrete test specimens for measuring thermal conductivity (300 x 300 x 50 mm)
Due to the many advantages of HFM as mentioned in Chapter 2, this apparatus
will be used for measuring the thermal conductivity values of the specimens in this study.
The heat flow meter apparatus as shown in Figure 3.2 is the main apparatus used in the
determination of thermal conductivity of foamed concrete. It was designed according to
ASTM guideline as described by Wijeysundera et al. (1989). It consists of two metal
plates. The plate having a higher temperature is called the hot plate and the one having a
lower temperature is called the cold plate. The hot plate consists of a brass plate with
heater and the cold plate has a fin-tube heat exchanger built with thick brass plate. The
temperature of the hot plate was maintained by using a water bath with an accuracy of
±0.01 oC.
71
Both heat flux meters on the hot and cold side of the heat flow meter have a
dimension of 100 mm by 100 mm with a thickness of 20 mm. They are used to measure
the heat flux at the surface of the specimen on the top and bottom. The heat flux meters
are positioned in the center of two rubber pads respectively. This is to prevent the
existence of an air gap between the specimen and the plates and also to prevent latent
heat losses from the heat flow meter.
The thermocouples and thermopiles used to measure the temperatures at the top
and bottom surfaces of the specimen are calibrated using master thermometer which is
accurate to ±0.1 oC. A thermopile is an array of thermocouples connected in parallel and
therefore it has higher sensitivity than a single thermocouple. In this study, a 10-junction
thermopile will be used. Calibration data of thermocouple and thermopile is available in
Appendix A. Figure 3.2 shows the schematic drawing of the heat flow meter apparatus
with the cold plate and the hot plate sandwiching the concrete specimens.
The error analysis of the heat flow meter is carried out to estimate how the
various measurements of heat flux, thickness of concrete slab and temperature contribute
to the overall uncertainty in the measurements. The heat flow meter apparatus has an
uncertainty of about ±6 % for the measurement of dry thermal conductivity.
(Wijeysundera et al., 1982) Note that calculation of error analysis of the apparatus is
presented in Appendix A.
72
Figure 3.2: Heat flow meter apparatus with two heat flux transducers and one specimen in between
The information of thermal conductivity of the standard material glasswool is
available for different temperature range and thus the heat flux transducers are calibrated
accordingly to obtain the conversion factor. In this case, there are two heat flux meters,
one on the top and the other at the bottom of the specimen. Assuming that these are
physically identical and have similar outputs, the outputs of the two transducers are
summed and then calibrated as a single transducer apparatus, thus having one common
conversion factor as shown in Table 3.4.
After the thermocouples and thermopiles were carefully placed on the top and
bottom faces of the concrete specimen, the concrete specimen was placed between the
two hot and cold plates. The cold plate was set at 20 oC and the hot was set at 10 oC
higher, which is 30 oC. The experiment was left to run for at least five to six hours to
allow the experimental apparatus to reach steady state. After that, the temperature
difference was obtained from voltage generated by thermopile and the average heat flux
was calculated using the voltages from the cold and hot plates. With known temperature
Specimen
Hot-side Heat flux Transducer Cold-side Heat flux Transducer
Heat flow meter
73
difference, heat flux and thickness of the concrete specimens, the thermal conductivity of
the material can be calculated using the heat transfer equation. The experiment was
repeated by changing the cold plate to 30 oC, 40 oC and 50 oC and the hot side being 10
oC higher than the cold side.
Table 3.4: Calibration of heat flux meters at different temperature ranges
102 (TC cold)
103 (TC hot)
104 (thermo-pile mV)
105 (Flux- cold)-
microV
106 (Flux-hot)-
microV
∆T (thermo-couple)
(103-102)
∆T (thermo-
pile) (deg C)
k from Standard
Data (W/m.K)
Q (W/m2)
Common conversion
factor
20.2 29.4 1.84 472 412 9.2 8.9376 0.03425 12.7547 14.4284
30.2 39.4 1.88 485 434 9.2 9.1285 0.0355 13.5026 14.6927
40.2 49.4 1.91 497 450 9.2 9.2717 0.0366 14.1393 14.9306
50.3 59.5 1.95 509 479 9.2 9.4626 0.0379 14.9430 15.1245
3.3.2 Compressive strength
Compressive strength test was carried out on 100 mm cubes according to BS 1881:
Part 116 (1983). A loading rate of 200 kN per minute was adopted. Three cube specimens
were tested and the average of the three compressive strength values was presented. The
tests were carried out using an Avery-Denison compression machine of 2000 kN capacity
which met the specification stipulated in BS 1881: Part 116 (1983).
The compressive test was conducted on the pure cement paste and foamed
concrete at age 7 and 28 days. As for polymer-modified foamed concrete, the test was
done when the specimens are at the age of 3-days, 7-days and 28-days.
74
3.3.3 Modulus of Elasticity
Modulus of elasticity test was conducted on the standard cylinder of 100 by 200
mm according to BS 1881: Part 121 (1983). The compressive strain was measured with
four transducers. The transducers were mounted in the middle section of the cylinder.
Three specimens were tested and the presented value of modulus of elasticity was
obtained by taking the average. The tests were carried out using the Instron Model 8500
Dynamic Materials Testing System.
3.3.4 Modulus of Rupture
Flexural tests were performed using third point loading test in accordance with BS
1881: Part 118 (1983). The size of the specimens was 100x100x 400 mm3. Three
specimens were tested and the presented value of flexural strength was obtained by
taking the average. The tests were carried out using the Instron Testing System.
3.3.5 Splitting tensile strength
Splitting tensile tests were performed on the standard cylinder of 100 by 200 mm
according to BS 1881: Part 117 (1983). Three specimens were tested and the presented
value of splitting tensile strength was obtained by taking the average.
3.3.6 Microscopy
The samples for microscopy are cuboids of size 70mm by 70mm by 30mm thick
which were cut from a 100 mm cube. The top surface of the cuboids was polished to
attain a smooth surface. In order to get a better contrast for automatic imaging processing,
75
the polished surface was colored by permanent black ink in two perpendicular directions
to ensure that the entire surface was covered with the ink. After the ink dried, white
cement powder was used to fill up the voids on foamed concrete polished surface.
Figure 3.4a shows a sample that was prepared for automatic image analysis to
find out its microscopic properties. The prepared surface was then scanned with a
2400dpi (dots per inch) scanner. This image was analyzed fully automatically by
employing computer software to attain the bubble size distribution in a 60 x 60mm area.
The software is able to identify all circular-shaped air pores from the image and measure
the size of each individual air pores identified. The results can then be collated and the
pore size distribution of the concrete sample can be obtained fairly efficiently.
Air bubbles incorporated into foamed concrete typically have diameter in the
range of 0.1-1 mm. The resolution of the scanner used is 2400dpi. Thus the diameter of
the smallest bubble is represented by 9.45 pixels (> 4 pixels) which can sufficiently
represent the bubble. Particle size analysis of white cement powder shows that the mean
particle size of white cement is 27 µm (sufficiently smaller than the size of air bubbles).
Thus, it is small enough to fill up the air void fully.
To ensure that surface treatment using black marker and white cement will not
distort the air voids on the surface and hence result in inaccurate results, some
verification of the method used was done to provide sufficient confidence for the
obtained results. In one of the tests, two images of the same area were prepared as shown
in Figure 3.3a and c. Figure 3.3a was taken after it was polished and Figure 3.3c was
taken after it was painted black, with the air voids on the polished surface being filled
with white cement. The two images were compared to check whether the voids remained
76
intact after the surface preparation. When the processed image from Figure 3.3d is
superimposed on to the uncoated specimen in Figure 3.3a, it was verified upon
comparison that nearly all the voids remained intact. Thus, the surface treatment process
to get a better contrast can be considered feasible and it will not distort the results
significantly.
Figure 3.3: a) uncoated specimen; b) processed image superposed on to the uncoated specimen as
shown in (a) ; c) coated specimen image with better contrast and d) processed image of (c) using
software
Another verification test was to check whether different types and extent of post-
processing of the same image will significantly affect the results of the pore sizes of the
foamed concrete. Figure 3.4a-c shows the different images being analyzed. These three
images originated from the same image; Figure 3.4a is the original image, Figure 3.4b
has undergone sharpening to get a better contrast in Adobe Photoshop software and
a
c d
b
77
Figure 3.4c has undergone sharpening as well as additional edge processing to the
circular bubbles. By observation, Figure 3.4c shows a reduction in the number of bubbles
after the edge processing as compared to Figure 3.4a and b.
Results from Figure 3.5 show that the results from cutout 1 and cutout 2 are very
similar. This means that increasing the contrast of the original image to cutout 2 will not
affect the results. However, post-processing the original image to cutout 3 will cause the
results of the pore size distribution to deviate from original result. Thus, the other images
to be analyzed will only be sharpened to get a better contrast.
Figure 3.4:a) Cutout (original scanned image), b) Cutout 2, c) Cutout 3
Pore size distribution
-50
0
50
100
150
200
250
0 10 20 30 40 50
Size of air pores
Fre
qu
en
cy
cutout 2
cutout 3
cutout
Figure 3.5: Pore distribution of images which underwent different post-processing
a)
c)
b)
c)
78
The last verification test was to extract a snapshot of the air void selection process
to see whether the software can capture the available air voids. The shaded portions in
Figure 3.6 represent the locations of air voids on one surface of the foamed concrete
specimen. From the snapshot in Figure 3.6, it can be shown that software was able to
select almost all the air voids using circles. Thus, there is much confidence to trust in the
reliability of the method to process the image automatically to count the number of air
bubbles in the area and also to measure the size of the air bubbles.
Figure 3.6: Counting process of image in Figure 3.5d
79
4 Numerical Analysis 4.1 Introduction
In order to come up with an optimized design of foamed concrete with a suitable
thermal conductivity to suit its intended purpose, it is important to know the effect of
thermal conductivity, shape, volume etc. of each component on the effective thermal
conductivity of the mixed system of air bubbles in cement matrix. Appropriate theoretical
models can be a fast way to predict the effective thermal conductivity of mixed solid
materials without having to do the experiments.
Zhang and Liang (1995) did a study on numerical analysis of effective thermal
conductivity of mixed solid materials. They reported that numerical analysis has high
accuracy. It eliminates the need for any hypotheses and it allows effective thermal
conductivity of mixed solid materials with discrete phases of different shapes. They also
reported that the effective thermal conductivity of mixed solid materials is influenced by
the weight (or volume) fraction and the thermal conductivity of individual components in
the materials rather than by the size or dimension of the discrete phase.
The present study aims to verify whether besides thermal conductivity of cement
matrix, the arrangement or space location of air pores, different combinations of pores of
different sizes, shape and size affect the effective thermal conductivity of foamed
concrete. The reason for the study is because the strength of foamed concrete can be
increased by having smaller air bubbles. However, there has been some concern as to
whether by having smaller bubbles will affect the thermal conductivity of foamed
concrete if the amount of air in the foamed concrete is constant.
80
Thus, in this study, the effect of air bubble size (given the same volume fraction
of air bubbles) will be investigated via numerical modeling whereby the geometry and
size of the air bubble can be taken into consideration. Analytical model like self-
consistent model is able predict thermal conductivity of foamed concrete fairly accurately,
however its computation does not include the size of air bubble and also geometry of air
bubble. Thus, numerical method using FLUENT software is selected to carry out the
investigation.
The feasibility of using foamed concrete as an alternative roofing system for HDB
flat roofs will also be investigated by using GAMBIT and FLUENT software. The
relationship of heat flux versus thickness of foamed concrete as an insulator is studied.
4.2 FLUENT
The software used in this study is FLUENT 6.0. It is an unstructured finite
volume CFD (Computational Fluid Dynamics) code which utilizes fundamental mass,
momentum and energy balances to predict fluid flow, heat transfer and other physical
phenomena over a specified domain. CFD enables the user to analyze the impact of
changes to geometry. It complements physical modeling and is thus more cost effective.
Its benefits also include allowing for the investigation of more design options for 2D &
3D arbitrary geometry in less time. It can also provide comprehensive data which is not
easily obtainable from experimental tests. Other than the effect of changes in geometry or
other properties of materials, the cause can be highlighted as well.
“Pre-processing” is the first stage of the CFD investigation and it involves
creating a geometry and internal grid. The grid “discretises” the domain to solve the
81
energy equation. The values of the variables found in the energy equation are calculated
within each cell and thus the accuracy and robustness of the flow solution is dependent
upon how the domain is divided. Smaller elements within the domain can give more
accurate solutions. The boundary type and zone assignment is done at the GAMBIT and
after which the final grid is exported to FLUENT to be solved and post-processed.
FLUENT is a state-of-the-art computer program for modeling fluid flow and heat
transfer in complex geometries. . The pre-processor of FLUENT used is GAMBIT.
FLUENT provides complete mesh flexibility, solving your flow problems with
unstructured meshes that can be generated about complex geometries with relative ease.
Supported mesh types include 2D triangular/quadrilateral, 3D
tetrahedral/hexahedral/pyramid/wedge, and mixed (hybrid) meshes. FLUENT also
allows you to refine or coarsen your grid based on the flow solution. It uses unstructured
Finite Volume method CFD codes and it is an integrated interface for CFD Solver and
Post-processing. All functions required to compute a solution and display the results are
accessible in FLUENT through an interactive, menu-driven interface.
The flow of thermal energy from matter occupying one region in space to matter
occupying a different region in space is known as heat transfer. Heat transfer can occur
by three main methods: conduction, convection, and radiation. Physical models involving
only conduction and/or convection are the simplest, while buoyancy-driven flow, or
natural convection, and radiation models are more complex. Depending on the problem,
FLUENT will solve a variation of the energy equation that takes into account the heat
transfer methods specified. FLUENT is also able to predict heat transfer in periodically
82
repeating geometries, thus greatly reducing the required computational effort in certain
cases.
FLUENT solves the energy equation in the following form:
(4.1)
Where keff is the effective conductivity (k + kt, where kt is the turbulent thermal
conductivity, defined according to the turbulence model being used), and Jj is the
diffusion flux of species j. The first three terms on the right-hand side of Eqn. 4.1
represent energy transfer due to conduction, species diffusion, and viscous dissipation,
respectively. Sh includes the heat of chemical reaction, and any other volumetric heat
sources defined.
In Eqn. 4.1,
(4.2)
where sensible enthalpy is defined for ideal gases as
(4.3)
and for incompressible flows as
83
(4.4)
In Eqn. 4.3 and Eqn. 4.4, Yj is the mass fraction of species j and
(4.5)
where Tref is 298.15 K.
4.3 Thermal conductivity studies
4.3.1 Description of the problem
The effect of size of air bubbles on thermal conductivity of foamed concrete is
investigated by means of the FLUENT software mentioned in Section 4.2. It can be done
by simulating the problem using a cubic model with a spherical shaped air bubble inside.
For this part of the study, the amount of air used is constant at 25 %.
This is a one-dimensional heat flow problem with heat flowing in one direction
from the top to the bottom of the geometry. The sides are at adiabatic condition assuming
that heat does not flow laterally in this case. Assuming the air bubbles are equally spaced
in the cube in an example as shown in Figure 4.1a, we can take advantage of symmetry in
the problem and simplify it by having a smaller domain to reduce computational efforts.
For example in Figure 4.1a, there are 64 air bubbles inside the 3 D cube, it can be divided
into 64 smaller elements with one spherical air bubble inside the cube and only one of
these smaller cubes needs to be solved.
84
Moreover, when air is incorporated into cementitious material during the casting
of foamed concrete and mixed well, from the point of statistics, the material is considered
to be uniform. Thus, the effective thermal conductivity of foamed concrete material is
equal to that of each cubic volume element in Figure 4.1b. The same geometry is scaled
proportionally for different sizes of air bubble to simulate the difference in air bubble size.
Note that the amount of air volume inside the cube remains unchanged. The grid quality
is kept constant for the different cases to make sure that the solutions are not affected by
it.
After the model is set up, numerical analysis is done to find out the effective
thermal conductivity of the model. The effective thermal conductivity of an element is
evaluated by Eqn. 4.6.
)(
.
12 TT
Lqkeff
−= (4.6)
The steady-state heat conduction equation and the respective boundary conditions for the
element are as follow:
(4.7)
85
a) b)
Figure 4.1: a) 3-D geometry of models with 64 bubbles in the cube and b) a cubic volume element for
analysis
4.3.2 Pre-processing
The basic steps in pre-processing is
1) Building up the geometry of the model
2) Generating the mesh
3) Defining boundary type and material type
A geometry to represent foamed concrete structure with air void introduced in
cement matrix is created first and a mesh is generated for the geometry in the GAMBIT
software. The amount of air fraction is 25 %. The mesh generated is then exported to
FLUENT solver. A domain is first defined by specifying a geometry in which the heat
flow is to be solved. In order to solve the heat flow equations in FLUENT to simulate
experimental conditions when determining thermal conductivity, the domain must be
divided into small “control volumes” or “cells”. The values of the heat flow variables are
calculated within each cell. The accuracy and robustness of the heat flow solution is
86
dependent upon how the domain is divided or the grid quality. In order to get accurate
solutions, small variations should occur between cells of the heat flow variable values.
The final step in pre-processing was to define the boundary type and material type.
All the boundaries are assumed to be walls. As for the material type, it was either defined
as a fluid or solid depending on whether air or concrete was used in the analysis.
4.3.3 Post-processing
The data file from GAMBIT was first imported to FLUENT. The first step would
then be to check whether the scale of the model was correct (see Figure 4.2).
Figure 4.2: Checking of model scale
The next step would then be to activate the energy equation and the gravity
function (see Figure 4.3). Before initialization, the boundary conditions (see Figure 4.4)
87
of the walls were set and the material properties defined. The top wall was maintained at
340K while the bottom wall was maintained at 300K. The side walls were assumed to be
adiabatic. Then initialization and iterations were carried out. After the solution converged,
the flux report, temperature and flux contour (see Figure 4.5) could then be generated.
Figure 4.3: Setting the gravity function
88
Figure 4.4: Defining boundary conditions
Figure 4.5: Obtaining the heat flux report
4.3.4 Calibration of the model
Convergence test for different grid quality was done to find out which is the
largest mesh size that can be used without compromising on the accuracy of the solution.
89
Figure 4.6a-d shows the grids for geometry created with decreasing mesh size meaning
that the number of cells is more. At a mesh size of 0.005, there is a convergence of the
solution obtained as shown in Figure 4.7. Thus, this mesh size corresponding to this
geometry size was used in the subsequent models.
a) b)
c) d)
Figure 4.6a-d: FLUENT models with mesh size = 0.01, 0.008, 0.005 and 0.003 respectively
90
Convergence Test of model
0.3815
0.3816
0.3817
0.3818
0.3819
0.382
0.3821
0.3822
0.3823
0.3824
0.3825
0 0.001 0.002 0.003 0.004 0.005 0.006 0.007 0.008 0.009 0.01 0.011
Mesh interval size
Th
erm
al c
on
du
cti
vit
y (
W/m
.K)
Figure 4.7: Mesh convergence Test
4.4 Simulation of HDB roofing system using foamed concrete
It is proposed that foamed concrete is used as a material for the roofing system on
the flat roof of HDB flats. Thus, it is necessary to first find out the potential of using
foamed concrete as thermal insulator as compared to using air gap. The performance of
foamed concrete as an insulating roofing system will be investigated in this study via
numerical methods (FLUENT). This problem was considered as a one-dimensional heat
flow problem with heat flowing in one direction from the top to the bottom of the
geometry and the sides are at adiabatic condition assuming that heat does not flow
laterally in this case.
Field measurements were conducted on a rooftop of a local commercial building
by a research done by the building department in National University of Singapore (“A
91
study of Rooftop Gardens in Singapore”, 2002)2. The surface temperatures of a concrete
rooftop at varying local (Singapore) time which are adapted from the field study can be
found in Figure 4.8. The highest surface roof temperature was observed to be 60 oC.
Surface temperature of the roof is affected by amount of solar radiation, air
temperature, humidity and wind. The resultant amount of solar radiation absorbed and
emitted by the roof to raise the temperature of the roof surface is related to the nature of
the surface of the roof. Thus, the design surface temperature of rooftop is dependent on
many factors. The right climatic condition and material properties have to be taken into
account to come out with a realistic design value.
In this study, the worst scenario was considered where the top surface is at 60 oC
and the bottom surface of the roof insulation will be taken to be at a fixed temperature of
20 oC (design temperature of the interior of an air-con room). The properties of Mix F3
(keff = 0.3707, density = 1440 kg/m3) were used to model the roof insulator made of
foamed concrete. The thickness of the two-dimensional rectangular model was varied
from range 7.5 cm to 30 cm. Heat flux produced due to the temperature differential
versus change in thickness of insulation was calculated using the results obtained from
the FLUENT simulation.
92
Graph of surface temperature of rooftop vs local (Singapore) time
0
10
20
30
40
50
60
70
0000-0900 0900-1200 1200-1800 1800-2100 2100-2400
Local (Singapore) time (hrs)
Su
rfa
ce
te
mp
era
ture
of
roo
fto
p (
0C
)
Figure 4.8: Design surface temperature of a typical rooftop at different local (Singapore) time
(adapted from “A study of Rooftop Gardens in Singapore”, 2002)2
93
5 Results and Discussion
In recent years, there is an increasing demand for insulating building materials
like foamed concrete due to the need to cut down on energy wastage. There is a
tremendous market for foamed concrete as an insulating material to meet the rising needs
in the building industry and other industries due to its versatility and economy. Currently,
there is a lack of comprehensive information in the literature for foamed concrete. Thus,
it would be very useful if there is a deeper understanding of what the key factors affecting
its thermal properties and strength properties are. This will aid the end-user to better
design foamed concrete mixes for various applications cost-effectively.
In this chapter, results on effects of key factors like foam content, water-cement
ratio, air void size and polymer content on both the thermal conductivity and strength for
different mix design of foamed concrete and polymer-modified foamed concrete will be
presented. In this study, foam content refers to the amount of foam content designed.
Note that for modeling, keff denotes effective thermal conductivity and it represents the
resultant thermal conductivity of the foamed concrete as a function of thermal
conductivity of cement paste matrix and air bubbles. The results obtained will be
discussed to provide a deeper understanding of these factors in order to fulfill the first
and second objectives of this research project as stated in the introduction in Chapter 1.
The third objective was to propose a model using numerical method (FLUENT
software) for predicting the thermal conductivity of foamed concrete to aid in the design
of cost-effective and innovative mixes for structural and non-structural insulation
purposes. Results from the FLUENT modeling will be presented here. The results from
94
current research and other researchers’ experiments will be used to verify the numerical
results obtained by the proposed model. Analytical models were also used to predict
thermal conductivity of foamed concrete. Results from the various models were used to
compare with the model proposed for this model.
Foamed concrete was proposed for use as a thermal insulating material on flat
roofs of HDB flats or other buildings due to its good insulating property. As discussed in
Chapter 1, there are various disadvantages of the current ferrocement roofing system
using an air layer as a thermal insulator. It was proposed that the insulation system may
be rectified and improved by using an alternative insulating material like foamed concrete
on the flat roofs of HDB flats and other buildings to suit the local requirement. There
would be two mix designs of foamed concrete proposed for foamed concrete insulation
roofing system. This will meet the last objective of this research project as stated in
Chapter One.
5.1 Thermal conductivity
5.1.1 Experimental results for foamed concrete
Thermal conductivity results for the various foamed concrete (w/c ratio varying
from 0.35-0.55 and foam content ranges from 25 to 70 %) and cement paste mixes
measured after 7 and 28 days curing are tabulated in Table 5.1 and Table 5.2 respectively.
The tables show the thermal conductivity results at temperatures ranging from 25- 55 oC.
The description of the sample designation number and the mix design can be found in
Table 3.2. The experimental thermal conductivity data were obtained using heat flow
95
meter using concrete specimens which were oven-dried for 24 hours before testing to
remove the moisture inside.
Table 5.1: Measured thermal conductivity of concrete specimens using heat flow meter after 7 days
Sample W/C ratio
Actual Wet
Specific Gravity
k (W/m.K)
Mean temp: 25
oC
k (W/m.K)
Mean temp: 35 oC
k (W/m.K)
Mean temp: 45 oC
k (W/m.K)
Mean temp: 55 oC
Foam Content
(%)
F4 0.35 1.07 0.2217 0.2265 0.2291 0.2323 50
F1 0.45 1 0.1902 0.1934 0.1964 0.1987 50 Varying w/c ratio
F5 0.55 0.9 0.1832 0.1868 0.1862 0.1911 50
F2 0.45 0.55 0.1228 0.1272 0.1319 0.1348 70
F1 0.45 1 0.1902 0.1934 0.1964 0.1987 50 Varying
foam content F3 0.45 1.44 0.3378 0.3491 0.3533 0.3593 25
C1 0.45 1.86 0.4948 0.5018 0.5104 0.53 0
C2 0.35 1.98 0.5571 0.5689 0.5836 0.599 0
Cement paste
(varying w/c
ratio) C3 0.55 1.76 0.4587 0.4637 0.4776 0.4888 0
Table 5.2: Measured thermal conductivity of concrete specimens using heat flow meter after 28 days
Sample W/C ratio
Actual Wet
Specific Gravity
k (W/m.K)
Mean temp: 25 oC
k (W/m.K)
Mean temp: 35 oC
k (W/m.K)
Mean temp: 45 oC
k (W/m.K)
Mean temp: 55 oC
Increase of k at 25 oC from 7 days to 28 days
% In-crease of k at 25 oC from 7 days to 28 days
Foam Cont-ent (%)
F4 0.35 1.07 0.2509 0.2554 0.2613 0.2653 0.0292 11.65 50
F1 0.45 1 0.2241 0.2246 0.2258 0.2281 0.0339 15.14 50 Varying w/c ratio
F5 0.55 0.9 0.1934 0.1967 0.199 0.2024 0.0102 5.27 50
F2 0.45 0.55 0.1576 0.1637 0.1616 0.1637 0.0348 22.09 70
F1 0.45 1 0.2241 0.2246 0.2258 0.2281 0.0339 15.14 50 Varying
foam content F3 0.45 1.44 0.3707 0.3764 0.39 0.3986 0.0329 8.86 25
C1 0.45 1.86 0.5345 0.5504 0.5633 0.5714 0.0398 7.44 0
C2 0.35 1.98 0.5768 0.5809 0.5894 0.5975 0.0197 3.41 0
Cement paste
(varyiing w/c
ratio) C3 0.55 1.76 0.4845 0.4914 0.5015 0.515 0.0257 5.31 0
Results show that thermal conductivity of cement pastes ranges from 0.4914-
0.5809 W/m.K. Due to the inclusion of air bubbles into cement paste, foamed concrete
96
possesses lower thermal conductivity ranging from 0.1576 to 0.3764 W/m.K. The lowest
thermal conductivity of foamed concrete obtained for this research project is 0.1576
W/m.K at foam content of 70 %. Thermal conductivity of foamed concrete is observed to
be significantly dependent on its density and foam content and less significantly on w/c,
temperature and age. Their effects will be discussed in greater details in subsequent
sections.
5.1.1.1 Effect of density and age
Figure 5.1 shows how thermal conductivity of foamed concrete changes with its
specific gravity. The trend shows that thermal conductivity of concrete is largely
dependent upon the density of the concrete. When density increases, thermal conductivity
increases as well. At higher densities, the amount of solid material present is higher and
the solid particles are more closely packed together. Thus, the rate of collision between
particles (rate of heat transfer) is increased. When the density is lower, there are less solid
particles due to the inclusion of air particles which are spaced much further apart, thus
impeding the rate of conduction which is the dominant heat transfer mechanism. Other
heat transfer mechanism like heat radiation and convection are hindered as well since the
air pores are small, so contributions by them are considered as negligible.
Different density of foamed concrete is used for different applications. Lower
density foamed concrete has lower thermal conductivity and strength properties, and
hence is suitable for insulation purposes. On the other hand, foamed concrete with higher
density can be used for structural purposes due to its higher strength values. However, its
insulation application will be limited since its thermal conductivity is higher.
97
For example, foamed concrete (generally without sand) with density lower than
600 kg/m3 will be suited to be used in roof and floor as insulation against heat and sound
and is applied on rigid floors (i.e. in itself it is not a structural material). It can also used
for tennis courts and interspace filling between brickwork leaves in underground walls,
insulation in hollow blocks and any other filling situation where high insulating
properties are required. For higher density from about 600 to 900 kg/m3, foamed concrete
(normally sand is added) is used for the manufacture of precast blocks and panels for
curtain and partition walls, slabs for false ceilings, thermal insulation and soundproofing
screeds in multi-level residential and commercial buildings.
For more heavy weight foamed concrete with density from 900 to 1200 kg/m3, it
is used in concrete blocks and panels for outer leaves of buildings, architectural
ornamentation as well as partition walls, concrete slabs for roofing and floor screeds.
Foamed concrete with structural strength which is obtained at 1200 to 1600 kg/m3 is used
in precast panels of any dimension for commercial and industrial use, in-situ casting of
walls, garden ornaments and other uses where structural concrete of light weight is an
advantage.
Increasing age of foamed concrete has an increasing effect on its thermal
conductivity as can be observed from Figure 5.1. At a later age, foamed concrete would
have undergone a higher degree of hydration, resulting in denser concrete thus the
thermal conductivity of the material will increases slightly. The percentage increase in
thermal conductivity due to aging seems to be higher for foamed concrete mixes with
higher foam content as shown in table 5.2. Mix F2 which has a high foam content of 70
% showed about 22 % percentage increase in k at 25 oC from 7 to 28 days. This value is
98
relatively higher than for other mixes (C1, F3 and F1) which has the same w/c ratio of
0.45 but with lower foam content.
Comparison of the effects of Specific Gravity on Thermal Conductivity of Foamed
concrete at 7 and 28 days
0.1228
0.1902
0.3378
0.4948
0.1576
0.3707
0.53
0.2241
0.0000
0.0500
0.1000
0.1500
0.2000
0.2500
0.3000
0.3500
0.4000
0.4500
0.5000
0.5500
0.6000
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 1.1 1.2 1.3 1.4 1.5 1.6 1.7 1.8 1.9 2
Specific Gravity of Fresh Concrete
Th
erm
alC
on
du
cti
vit
y (
W/m
.K)
25 Deg C (7 days)
25 deg C (28 days)
Figure 5.1: Graph of Thermal conductivity against specific gravity of foamed concrete with w/c= 0.45
at both 7 days and 28 days
5.1.1.2 Effect of foam content or porosity
As foam content in foamed concrete increases, thermal conductivity decreases
quite drastically. This is why foamed concrete can be a good insulator with the addition
of pre-formed foam since air is a poor conductor of heat and thus can help to impede heat
transfer. The addition of 70 % of foam is able to reduce the thermal conductivity by about
70 %, which is quite substantial. The effect on thermal conductivity of foamed concrete
due to foam content can be observed from Figure 5.2. Thermal conductivity of foamed
concrete falls within a band due to an uncertainty of about ±6 % for the heat flow meter
99
apparatus (Wijeysundera et al., 1982), thus the observed parallel trend for results
measured on 28 days may not exist.
In this research, a mix of foamed concrete with 80 % foam content, w/c ratio of
0.35 was attempted to be cast. However, it experienced serious foam collapse and thus
was unable to be cast successfully. Since when a very large amount of foam is added, it
results in an insufficient amount of cement paste to surround the air voids. Coalesce of air
bubbles thus take place. When the air bubbles get bigger after the coalescence, the
tendency for the enlarged bubble to burst during mixing and handling of the mix of
foamed concrete is higher.
Comparison of the effects of foam content on Thermal Conductivity of Foamed concrete
at 7 and 28 days
0.122781233
0.190176337
0.337822347
0.494758305
0.1576
0.2241
0.3707
0.53
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0.5
0.55
0.6
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75
Foam content (%)
Th
erm
al
Co
nd
uc
tiv
ity
(W
/m.K
)
25 Deg C (7 days)
25 deg C (28 days)
Figure 5.2: Graph of Thermal conductivity against foam content at both 7 days and 28 days (w/c =
0.45)
Mix C1
Mix F3
Mix F1
Mix F2
100
5.1.1.3 Effect of w/c ratio
The effect of water-cement ratio (w/c) was also investigated and it was found that
higher w/c ratio results in a lower thermal conductivity of the foamed concrete as seen in
Figure 5.3. The amount of foam content is kept at 50 %, however results of thermal
conductivity of cement matrix (C1, C2 and C3) decreases with increasing w/c ratio as
seen from Table 5.2. Thus, thermal conductivity of foamed concrete is not only
dependent on air void fraction, but also on the thermal conductivity of the cement paste.
Thus, these two parameters, air void ratio and thermal conductivity of cement paste,
would be used to predict thermal conductivity of foamed concrete in analytical models in
later sections.
Cement content decreases with higher w/c ratio. The amount of cement hydration
products will thus be reduced, resulting in less dense material or lesser amount of solid
which are more sparsely-spaced, with interstitial voids as shown in Figure 5.4.
Propagation of heat by conduction decreases as a result of lower rate of particle collision
and thus, transfer heat energy is slowed down.
The trend is very similar to that reported by Kook et al. (2003) who also
investigated the effect of w/c ratio on cement paste. They found that with the addition of
more cement content which means a lower w/c ratio, the thermal conductivity of cement
paste increases. The reason is that cement has a higher thermal conductivity value than
water. The results show that changing w/c ratio of foamed concrete does not have as great
a significant effect on the thermal property as compared to varying foam content.
101
Effects of w/c on Thermal Conductivity of Foamed concrete (50% foam content)
0.2509
0.2241
0.1934
0.2217
0.1902
0.1832
0.17
0.19
0.21
0.23
0.25
0.27
0.3 0.35 0.4 0.45 0.5 0.55 0.6
w/c
Th
erm
al C
on
du
cti
vit
y (
W/m
.K)
28 days
7 days
Figure 5.3: Graph of Thermal conductivity against w/c at 28 days
Figure 5.4: Schematic diagram of cement hydration with different w/c ratio
Mix F4
Mix F1
Mix F5
High thermal conductivity Low thermal conductivity
102
5.1.1.4 Effect of temperature
Figure 5.5 shows the plot of thermal conductivity of the various mixes of foamed
concrete and cement paste (at oven-dried condition) against the mean temperature of
material. The temperature range is from 25 oC to 55 oC. A very slight increasing trend can
be observed from Figure 5.5. However, the increase was not very significant within the
short temperature range which the materials were tested.
When the temperature of the hot side and cold side of the heat flux meter is
increased, the heat energy being transferred to the particles inside the foamed concrete is
increased, causing more vigorous vibration of the particles and also increases the rate of
collision between particles. Thus, the rate at which heat is conducted through conduction
is increased, resulting in a higher thermal conductivity in specimens which are tested at
higher temperature. This increasing trend is consistent with the works of other
researchers like Marmoret (1999) and De Rose and Morris (1999).
Thus, thermal conductivity of foamed concrete may change when it is applied at
different countries. For example, in the desert where the ambient temperature is typically
higher at 45 oC, thermal conductivity of foamed concrete is slightly higher than that of
the same mix of concrete would differ at places with milder temperature of say 25 oC.
This should be taken into consideration when designing foamed concrete as an insulation
material. The increase of thermal conductivity value due to 10 oC increase in temperature
is typically 1-3 % and is seldom higher than 4 %.
103
Comparison of the effects of Temperature on Thermal Conductivity of Foam concrete at
28 days
0.1000
0.2000
0.3000
0.4000
0.5000
0.6000
10 15 20 25 30 35 40 45 50 55 60
Mean Temperature (degree Celcius)
Th
erm
al
Co
nd
uc
tivit
y (
W/m
.K)
Mix F1
Mix F2
Mix F3
Mix F4
Mix C1
Mix C2
Mix C3
Figure 5.5: Graph of Thermal conductivity against temperature
5.1.2 Experimental results for foamed concrete with polymer
The results of thermal conductivity for various polymer-modified foamed
concrete and cement paste mixes are tabulated in Table 5.3 measured after 28 days curing.
The description of the sample designation number and the mix design can be found in
Table 3.3 in Chapter 3. Effects of polymer content, foam content and density on thermal
conductivity of polymer-modified foamed concrete will be discussed.
104
Table 5.3: Measured thermal conductivity of polymer-modified concrete specimens using heat flow
meter after 28 days
Mix Designation
Polymer Content
(%)
Foam content
(%) w/c ratio
Fresh Density (kg/m3)
Thermal conductivity, k (W/m.K)
Control 0 50 0.35 1000 0.237
PF1 5 50 0.35 1020 0.232
PF2 10 50 0.35 960 0.226
PF3 15 50 0.35 1000 0.215
PF4 20 50 0.35 960 0.191
PF5 10 20 0.35 1580 0.3909
PF6 10 80 0.35 478 0.1046
CP1 5 0 0.35 1940 0.55
CP2 10 0 0.35 1920 0.535
CP3 15 0 0.35 1900 0.509
CP4 20 0 0.35 1880 0.481
5.1.3 Effect of varying polymer content
Figure 5.6 shows the effect of polymer content on thermal conductivity of
polymer-modified foamed concrete and cement paste. As shown in Figure 5.6, increasing
the amount of polymer will reduce the thermal conductivity of the material slightly. The
effect of polymer to reduce the thermal conductivity of cement paste with no foam added
was observed to be higher than for foamed concrete with 50 % foam content as can be
seen by the gradients of the two equations on Figure 5.6.
105
Graph of thermal conductivity vs polymer content
0.481
0.237 0.2320.226 0.215
0.191
0.577
0.550 0.535
0.509y = -0.0047x + 0.577
y = -0.0022x + 0.2422
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0 5 10 15 20
polymer content (% by weight of cementitious material content)
th
erm
al
co
nd
ucti
vit
y (
W/m
.K)
50 % foamed concrete
0 % foamed concrete
Mix C2
Mix PF3Mix PF2Mix PF1
Mix Control
Mix CP4
Mix CP3Mix CP2
Mix CP1
Mix PF4
Figure 5.6: Graph of thermal conductivity of foamed concrete against polymer content
Polymer which is added to replace some of the cementitious material in foamed
concrete has a lower thermal conductivity (k ≈ 0.19- 0.3 W/m.K) than cement paste (k ≈
0.66 -1.2 W/m.K). The reduced thermal conductivity could also be due to the additional
air bubbles caused by air entrainment when acrylic polymer is added into the mix. Thus,
adding polymer to foamed concrete helps to lower the overall thermal conductivity of the
polymer-modified foamed concrete.
There is a limit to the amount of foam added into foamed concrete. The higher the
amount of foam, the lesser the amount of cement paste to surround the air voids which
could result in air void coalescence as discussed in Section 5.1.1.2. It was found that a
mix of 80 % foam content, w/c 0.35 and 10 % polymer by weight of cement is cast
106
successfully. Addition of a small amount of polymer can improve the problem of foam
collapse. Initially, however, when a mix of 80 % foam content and w/c ratio of 0.35 was
cast without polymer, it experienced foam collapse. Thus, one benefit of adding acrylic
polymer into foamed concrete is that it allows a greater amount of foam to be added into
foamed concrete. This enables further reduction of its thermal conductivity when a
maximum amount of foam content allowed in foamed concrete is reached. The
effectiveness of foamed concrete as an insulation material can be improved as a much
lower thermal conductivity can be reached by adding a small amount of polymer.
The rationale could be because polymer has smaller particle size than unhydrated
cement particles or hydrated cement products. Polymer consists of long chains of
molecules made up by physical aggregates of smaller molecules united by vague "partial
valences," not true giant molecules held together by chemical bonds. In fact, X-ray
crystallography of polymer fibers revealed unit cells no bigger than those of ordinary
molecules like carbon dioxide or water. Thus, the smaller polymer molecules are able to
maneuver more easily among the air voids and to surround them as compared to cement
particles or hydrated cement products. Thus, the polymer could possibly allow a much
smaller spacing factor of air bubbles to be sustained in foamed concrete of very high
foam content without air void coalescence.
5.1.4 Effect of foam content
Foam content in polymer-modified foamed concrete was varied from 20 to 80 %,
while keeping polymer content constant at 10 %. As the foam content in polymer-
modified foamed concrete increases, thermal conductivity decreases quite drastically as
107
shown in Figure 5.7. The trend is similar to that of foamed concrete. Due to the addition
of 10 % of polymer content (by weight of cement), a material of a high foam content of
80 % resulting in a very low thermal conductivity of 0.1046 W/m.K. measured at 25 oC
can be obtained.
Graph of effective thermal conductivity vs foam content in polymer-modified foamed concrete
0.1046
0.2263
0.5350
0.3909
0
0.1
0.2
0.3
0.4
0.5
0.6
0 10 20 30 40 50 60 70 80 90
foam content (% in polymer-modified foamed cocnrete)
Eff
ec
tive
th
erm
al
co
nd
uc
tiv
ity
(W
/m.K
)
10 % polymer content
Figure 5.7: Graph of thermal conductivity of polymer-modified foamed concrete against foam
content
5.2 Simulation Results for effect of air bubble size on thermal conductivity of foamed concrete
Theoretically, the effect of air bubbles size on keff is negligible when it is assumed
that there are only single-sized air bubbles in foamed concrete. Nevertheless, the effect of
air bubble size was investigated using numerical method by means of FLUENT software.
The method of modeling is discussed earlier in Section 4.3 in Chapter 4. The air content
Mix CP2
Mix PF6
Mix PF4
Mix PF5
108
for four types of foamed concrete with differing air bubble size was kept constant at 25 %.
It can be observed from Figure 5.8 that the air bubble diameter has no effect on keff of
material modeled with an air content of 25 % using single-sized air bubbles.
The conclusion that air bubble size does not affect thermal conductivity of foamed
concrete (if air content is kept constant) should only be applicable to air bubbles which
are reasonably small. In other words, the effect of air void size on thermal conductivity of
foamed concrete may be significant for air voids of much larger magnitude than the
typical air bubbles found in foamed concrete due to the additional effect of convection
and radiation. The air bubbles in foamed concrete are usually quite small, in the size of
the range 0.1 to 1 mm. According to Luikov (1980), for a pore diameter smaller than 3
mm in porous material, the effect of radiation and convection in pores can be neglected in
comparison with other modes of heat transfer at atmospheric pressure and temperature.
Heat transfer through radiation and convection within the pores is small and can be
neglected or lumped in with the true conduction component at atmospheric pressure and
temperature. Chew (2005) found that within an air gap of 10 cm thickness (see Figure
2.21), heat transfer through conduction still governs. Heat transfer through an air gap
below the size of 10 cm should be by conduction. Thus, heat transfer due convection and
radiation can be neglected through air bubbles in foamed concrete which are of typically
in the size range of 0.1 to 1 mm.
109
Effect of air bubble size on thermal conductivity of foamed concrete
0.3816
0.3816
0.3816
0.3816
0.3816
0.38140
0.38145
0.38150
0.38155
0.38160
0.38165
0.38170
0.38175
0.38180
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55
Air bubble diameter size (mm)
Eff
ec
tiv
e t
he
rma
l c
on
du
cti
vit
y o
f fo
am
ed
co
nc
rete
(W
/m.K
)
Figure 5.8: Plot of air bubble diameter against thermal conductivity result from FLUENT
The effect of having different air bubble sizes in foamed concrete on keff was
investigated using FLUENT software as well. Models with mixed-sized spherical air
bubbles of different arrangements are shown in Figure 5.9. The total air content in the
two models was 25 %. The value of thermal conductivity of cement paste used in both
the models was 0.73 W/m.K. Analysis using FLUENT software obtained keff of 0.5205
W/m.K and 0.5325 W/m.K for models shown in Figure 5.9 (b) and (c) respectively.
These two values are very close to the keff of 0.5214 W/m.K obtained from a model with
a single-sized air bubble shown in Figure 5.9 (a). These thermal conductivity values are
tabulated in Table 5.4. The percentage differences between results obtained for the
various models are also tabulated in Table 5.4 and it can be shown that the results do not
110
differ very much. Thus, it shows that that the effect of size and arrangement of air
bubbles in foamed concrete on effective thermal conductivity is not very significant.
a) b) c)
Figure 5.9: FLUENT models with 25 % air content –a) single-sized air bubble; b) mixed-size
spherical air bubbles; c) mixed-size spherical air bubbles with different size combination of air
bubbles.
Table 5.4: Effective thermal conductivity for different types of model obtained by FLUENT analysis
Type of Model Effective Thermal
conductivity, W/m.K.
% difference
from spherical air
bubble
Spherical air bubble model 0.5214 -
Mixed-sized air bubbles model 1
0.5325 2.09
Mixed-sized air bubbles model 2
0.5205 -0.17
keff is observed to be heavily dependent on the volume fraction of air bubbles
(discrete phase) rather than on their sizes for low air content of 25 %. Thus, this implies
that the insulating property of foamed concrete is not compromised even by having
smaller size air bubbles (with same air content) which helps in increasing the strength of
the material. However, this finding might not be able to be extrapolated to foamed
concrete with higher foam content since only a porosity of 25 % was investigated in this
111
study. Modeling of spherical air void of higher air content in a cube was not done due to
geometrical constraint.
Attempts had been made to back up the findings of numerical method with
experimental data by using different-sized bubbles with the same porosity. The method of
varying the average size of air bubbles was suggested to be varied using different foam
density. However, it was found to be hard to control the density of foamed concrete in
that way and moreover, the specimens obtained were of different density. Thus, the
thermal conductivity results obtained would not only be due to the effect of varying the
bubble size, but it would also be interfered by the effect of density. Hence, these attempts
did not work out well.
Other suggestions to vary the size of air bubbles in foamed concrete of the same
porosity would be to use different-sized polystyrene beads. However, due to
unavailability of the materials and lack of time, the tests could not be carried out.
5.3 Models to predict effective thermal conductivity, keff
5.3.1 Multi-variable regression method
A multi-variable regression model is useful for a quick estimation of thermal
conductivity of other design mix of foamed concrete that are within the range of
the experimental results. The statistical model to estimate the thermal
conductivity, k (W/m.K) for foamed concrete, with specific gravity ranging from
0.5 to 2.0, is given by:
112
k28 days = 0.544 – 0.005076x1 – 0.300x2 + 0.000259 x3 (5.1)
where x1 = w/c ratio of the foamed concrete sample
x2 = foamed content of the foamed concrete sample (%)
x3 = temperature of foamed concrete sample (K)
This equation is an empirical model to approximate the thermal performance of
foamed concrete when its w/c ratio, foam content and operating temperature are known.
The predicted values from this empirical model have a percentage root mean square error
of 6.98 %. Figure 5.10 is a scatter plot which compares the experimental thermal
conductivity value with the predicted one using Equation 5.1. The graph shows that the
predicted values provide a reasonable estimate for the corresponding experimental k
values as the correlation coefficient (R-squared value) is 0.9442 which is quite close to 1.
However, it can be observed from Figure 5.10 that Equation 5.1 underestimate thermal
conductivity value of foamed concrete with too low or too high foam content.
113
R2 = 0.9442
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0.45
0.0000 0.0500 0.1000 0.1500 0.2000 0.2500 0.3000 0.3500 0.4000 0.4500
Experimental thermal conductivity, k (W/K.m)
Pre
dic
ted
l th
erm
al co
nd
uc
tivit
y, k (
W/K
.m)
Line of Equality
Figure 5.10: Scatter plot illustrating the relationship between the predicted k value using multi-
variable regression method and experimental k value
5.3.2 Analytical models
Analytical models can offer fast results of keff of foamed concrete with varying
foam content and mix proportions by solving equations derived from fundamentals with
certain realistic assumptions. Due to the reasons given in Chapter 2, three models were
chosen to be used for prediction of thermal conductivity of foamed concrete. They are
namely: 1) geometric model, 2) Assad model, and 3) Self-consistent model. However, it
is important to verify the predicted values from these three analytical models chosen with
known experimental values to test which are the ones that can offer close results.
The three analytical models to be tested are calculated by inputting the porosity of
the foamed concrete and also the thermal conductivities of the solid matrix and air. The
114
thermal conductivities of the solid matrix of different water-cement ratio to be used in the
different analytical models are obtained from the experimental results of thermal
conductivity of the pure cement paste, namely Mixes C1, C2 and C3. Thermal
conductivity of air at a temperature of 25 oC is taken to be 0.028 W/m.K.
Table 5.5 shows the calculated results from the analytical models and also the
experimental values of the respective samples at a mean temperature of 25 oC. Figure
5.11 shows the comparison of predicted values of the three different analytical models
with experimental results. Estimation of thermal conductivity values using geometric
model shown in Equation 2.10 was not able to predict thermal conductivity values of
foamed concrete as obtained from the experiments as can be observed from the high
percentage error in Table 5.5.
Table 5.5: Comparison between predictions from analytical models and experimental results
Geometric Model Assad Model Self-consistent
Model
Experimental values (25
Deg C) Sample
air (%)
w/c
k value (W/m.K)
% error
k value (W/m.K)
% error
k value (W/m.K)
% error k value (W/m.K)
Mix F3 25 0.45 0.2494 32.71 0.3373 9.01 0.3647 1.61 0.3707
Mix F1 50 0.45 0.1174 47.62 0.2146 4.23 0.2305 -2.87 0.2241
Mix F2 70 0.45 0.0642 59.24 0.1495 5.13 0.1401 11.08 0.1576
Mix F4 50 0.35 0.1278 49.06 0.2335 6.92 0.2509 0.00 0.2509
Mix F5 50 0.55 0.1171 39.43 0.2067 -6.88 0.2140 -10.64 0.1934
115
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0 0.05 0.1 0.15 0.2 0.25 0.3 0.35 0.4
Experimental thermal conductivity, k (W/K.m)
Pre
dic
ted
l th
erm
al co
nd
uc
tivit
y, k (
W/K
.m)
Geometric Model
Assad Model
Self-consistent Model
Line of Equality
Figure 5.11: Comparison of prediction from different analytical models with experimental results
On the other hand, the Assad model (Goual et al., 1999), which is an empirical
relationship that is very similar to the geometric mean equation, was able to obtain
predicted values of thermal conductivity much closer to experimental values. Assad also
found that the results obtained using geometric model was unable to give good
predictions and hence he proposed the Assad model which is given by the relationship as
shown in Equation 2.11. By choice of the average value of m = 0.60ε where c= 0.55 for
foamed concrete, this model was used to predict the mean effective thermal conductivity
within an error of less than ± 9%. This model allows some flexibility to choose an
appropriate value for the parameter, m (= cε) to model the effective thermal conductivity
of a two-phase material. Assad model states that c 1, however in this case, c was taken
to be much lower than 1.
116
The third model used which is the self-consistent model from Equation 2.14 was
also able to predict closely the thermal conductivity of the foamed concrete of different
w/c ratio and also porosity. The errors between the results obtained from self-consistent
model and experimental values are within 11%. The reason that self-consistent model
was a fairly good prediction model could be because it assumes a concentric model that
does not restrict the volume fraction of spherical air bubbles, thus enabling thermal
conductivity with high air content to be predicted closely as well.
Boutin (1996) also used the self-consistent method to determine the thermal
conductivity of autoclaved aerated concrete (AAC). Boutin showed that this method is
efficient for autoclaved aerated concrete as its microstructure contains very different-
sized pores. The predicted thermal conductivity obtained using the self-consistent method
was reported to be in excellent agreement with the experimental data as mentioned in
Section 2.6.6 in Chapter 2. Thus, it showed that self –consistent method can be used to
predict effective thermal conductivity fairly accurately for aerated concrete with macro-
pores like auto-claved aerated concrete and foamed concrete.
5.3.3 Numerical method using FLUENT
Using numerical method allows a different geometry of air bubbles to be
modeled fairly readily to study the shape effect. For example, air bubbles can be modeled
as spheres or cubes in GAMBIT which is the pre-processor of FLUENT. More complex
geometries like effect of having different-sized air bubbles in a model or having air
bubbles arranged in various ways on keff can be analyzed by first modeling in GAMBIT
117
and then analyzing in FLUENT. These more complex geometries may be much harder to
achieve in analytical methods where simpler models are used.
a) b)
c) d)
Figure 5.12: FLUENT models with varying air contents (spherical air bubble) a) 10 %, b) 25 %, c) 35
% and d) 45 %
In Figure 5.12, different volumes of air inside a cement matrix are modeled
using spheres to investigate the effectiveness of using FLUENT to predict thermal
conductivity of foamed concrete with different foam content. However the disadvantage
of modeling air bubbles in a cube as spheres is that there is a maximum amount of air
void allowed due to the limitation of the size of a spherical air bubble inside a cube. Thus,
the maximum foam content used is 45 %. The dimension and properties of the cement
matrix modeled were constant throughout.
Figure 5.13 shows the plot of keff of foamed concrete at different air volume
against thermal conductivity of cement matrix. The keff of foamed concrete cannot be
lower than thermal conductivity of air which was taken as 0.028 W/m.K, which means
that any value of keff which is lower than 0.028 is not meaningful. Thus, the straight lines
118
on the graph in Figure 5.13 have their lowest point imposed at 0.028. The ratios of keff /
thermal conductivity of cement matrix for various air contents were obtained from the
gradients of the functions in Figure 5.13.
When air bubbles are modeled as cubes, higher air contents can be modeled.
Figure 5.14 shows the models of foamed concrete with different air content up to 70 %
being used. For a particular air content used, the thermal conductivity of the cement
matrix used is also varied and analyzed in FLUENT to find out its effect. The result is
plotted in Figure 5.15. To test the effect of modeling different-sized air bubbles in
different geometrical position, analysis is done for the models shown in Figure 5.16.
Effect of thermal conductivity of cement matrix on the effective thermal conductivity of
foamed concrete
y = 0.9039x + 0.0036
y = 0.5773x + 0.0128
y = 0.4573x + 0.0162
y = 0.7019x + 0.0094
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Thermal conductivity of matrix (W/m.K)
Eff
ecti
ve t
herm
al co
nd
ucti
vit
y (W
/m.K
)
35% Foam content
(Spherical air bubble)
0% Foam
content
10% Foam content (Spherical
air bubble)
45% Foam content
(Spherical air bubble)
25% Foam content
(Spherical air bubble)
Figure 5.13: Plot of thermal conductivity of foamed concrete at different air content against thermal
conductivity of cement matrix (where air is modeled as a sphere)
119
a) b)
c) d)
Figure 5.14: FLUENT models with varying air contents (cubic air bubble) a) 10 %, b) 25 %, c) 45 %
and d) 70 %
Effect of thermal conductivity of cement matrix on the effective thermal conductivity of
foamed concrete
y = 0.223x + 0.0218
y = 0.8923x + 0.0042
y = 0.6846x + 0.0102
y = 0.4594x + 0.0161
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
Thermal conductivity of matrix (W/m.K)
Eff
ecti
ve t
herm
al co
nd
ucti
vit
y (W
/m.K
)
25% Foam content (cubic
air bubble)
0% Foam
content
10% Foam content (cubic air
bubble)
45% Foam content (cubic
air bubble)
70% Foam content (cubic
air bubble)
Figure 5.15: Plot of thermal conductivity of foamed concrete at different foam content against
thermal conductivity of cement matrix (air is modeled as a cube)
120
a) b) c)
Figure 5.16: FLUENT models with a) 25 % air content using mixed-size spherical air bubbles; b) 25
% air content using mixed-size spherical air bubbles with of different size combination of air
bubbles.c) 35 % air content using mixed-size spherical air bubbles (with the same arrangement of air
bubbles as (a));
The FLUENT analysis results show a decrease of thermal conductivity with an
increase in air content in the cement matrix as plotted in Figure 5.13 and Figure 5.15. It
can be observed that the keff of foamed concrete is linearly related to the thermal
conductivity of cement paste. Thus, the ratio of effective thermal conductivity/ thermal
conductivity of cement matrix for a particular air content will be a constant. The ratio of
effective thermal conductivity of foamed concrete/ thermal conductivity of cement matrix
has been calculated as a function of volume fraction as shown in Figure 5.17. This figure
shows that numerical method employing FLUENT software can be used to predict the keff
of foamed concrete with different foam content quite accurately, especially for foamed
concrete with lower foam content.
For air content of up to 45 %, it was found that both keff obtained using FLUENT
software are very similar for air bubbles modeled as spheres and cubes. Beyond 45 %,
the comparison cannot be made because of the limitation of the volume of spherical air
bubble in a cube. Prediction of thermal conductivity of foamed concrete with air bubbles
modeled as cubes and containing high air contents of 70 % was shown to be slightly
121
lower than the experimental result as shown in Figure 5.17. This could show that when
the volume fraction of the discrete phase of air voids is low (below 45 %), the shape
assumed for the disperse particles is not of consequence.
For the range of air content of up to 35 % investigated, keff of the foamed concrete
models using spherical air bubbles or cubic air bubbles or mixed-sized spherical air
bubbles with different arrangements are very similar as shown in Figure 5.16. The
arrangement or space location of air pores, different combinations of pores of different
sizes; and shape, size and thickness of interporous partition did not appear to affect the
keff of foamed concrete significantly for the range of air content investigated. This implies
that keff is influenced mainly by the volume fraction of the air bubbles instead of by the
arrangement of different combinations of air voids of varying sizes and shape of the air
bubbles.
The curve in Figure 5.17 is the model proposed to correlate effective thermal
conductivity (keff), thermal conductivity of the cement matrix (kmatrix) and percentage
volume of air. It is obtained by using results derived from FLUENT numerical analysis in
this research project. It normalizes effective thermal conductivity by thermal conductivity
of the cement matrix on the y-axis.
Experimental results found in the current research on foamed concrete and
polymer-modified foamed concrete were used to verify the model proposed.
Experimental values were found to fall closely to this curve. Experimental results from
NUS in-house data done on foamed concrete without sand using Guarded Hot Plate
apparatus was also plotted on the same axis. They were also shown to fall reasonably
122
close to the curve. Results from thermal conductivity of litebuilt® foam3 were found to fit
the model proposed.
Analytical models proposed by other researcher to predict keff were also plotted on
the figure. Figure 5.17 shows that results obtained from self-consistent model (Hashin,
1968) and Assad model (Goual et al., 1999) fall closely to the curve that represent the
model proposed. However, results found using the geometric model (Woodside and
Messmer, 1961) fall quite far below the curve, showing that this method underestimated
keff quite significantly.
When volume of percentage of air, ε (%) is near to 100, the value of k/kmatrix
approaches zero since the composite would be mainly air which has the thermal
conductivity value of air of 0.028 W/m.K. that is close to zero. Thermal conductivity
results predicted by analytical models like self-consistent model gave higher values at
very high foam content. However, the proposed model is able to predict thermal
conductivity of foamed concrete more accurately, especially at very high foam content.
Thus, the proposed model which is well-verified by analytical models as well as
experimental data from current and other researches provides a simplified and user-
friendly equation as shown in Figure 5.17. This equation is useful to predict thermal
conductivity of foamed concrete when thermal conductivity of cement matrix and volume
fraction of air is known.
123
k/kmatrix (25 deg C) vs Volume percentage of air
-0.1
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
1.1
0 10 20 30 40 50 60 70 80 90 100
Volume percentage of air, ε (%)
k/k
matr
ix
Experimental results (foamed concrete without polymer)
Experimental results (foamed concrete with polymer)
Experimental (foamed concrete: NUS in-house results)
Experimental value (litebuilt foam)
FLUENT results (spherical air)
FLUENT results (cubic_air)
FLUENT results (mixed air bubble sizes)
Self-consistent method (Analytical: Hashin, 1968)
Geometric model (Analytical:Woodside and Messmer,1961)
Assad Model (Analytical Model)
Proposed Model
Poly. (Proposed Model)
Figure 5.17: Ratio effective thermal conductivity of foamed concrete/ thermal conductivity of matrix
versus volume fraction of air.
It can also be used in designing work as well. For a certain design k value of
foamed concrete, the designer can decide on a percentage of air to be used and from the
equation, thermal conductivity of the matrix can be obtained. Since relationship of
thermal conductivity of cement matrix and w/c ratio is known from Figure 5.3, w/c ratio
of the design mix can be obtained as well. Thus, design mix of foamed concrete can be
obtained easily to cater for different applications.
5.4 Compressive Strength
Compressive strength results for the various foamed concrete and cement paste
mixes measured after 7 and 28 days curing are tabulated in Table 5.6. The sample
designation number and the mix design can be found in Table 3.2.
124
Table 5.6: 7- and 28- day compressive strength of foamed concrete and cement paste
Mix Designation
Fresh Density (kg/m3)
Compressive strength -7 days (MPa)
Compressive strength -28 days (MPa)
F1 1000 6.59 9.57
F2 550 0.96 1.43
F3 1440 19 29.36
F4 1070 8.43 11.87
F5 9000 4.07 6.14
C1 1860 40.63 57.31
C2 1980 58.08 82.97
C3 1760 33.96 43.59
5.4.1 Effect of density and age
Figure 5.18 shows how compressive strength of foamed concrete changes with its
specific gravity. The trend shows that compressive strength of concrete is highly affected
upon the density of the concrete. When density decreases, compressive strength decreases
as well. This is because compressive strength can be significantly influenced by the pore
structure of the air pores and the mechanical condition of pore shells. When density is
reduced, larger macropores are formed which led to a significant drop in compressive
strength. The increase in compressive strength of foamed concrete from 7 days to 28 days
is about 30 %.
125
Comparison of the effects of Specific Gravity on Compressive Strength of Foamed
concrete at 7 and 28 days
6.59
19.00
40.63
0.96
57.31
29.36
9.57
1.43
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
0 0.5 1 1.5 2
Specific Gravity of Fresh Concrete
Co
mp
res
siv
e S
tre
ng
th (
MP
a)
(7 days)
(28 days)
Figure 5.18: Graph of Compressive strength of foamed concrete vs specific gravity of fresh concrete
5.4.2 Effect of foam content
From Figure 5.19 and Figure 5.20, it can be shown that compressive strength of
foamed concrete and polymer-modified foamed concrete decreases with increasing foam
content. Compressive strength of concrete is also highly dependent upon the foam
content of the concrete. When the amount of foam increases, compressive strength
decreases quite drastically. There is less cement paste to surround the air voids thus
causing the air voids to coalesce and the average air void size to increase. Thus, foamed
concrete with high air content would experience higher tendency of coalesce of air-voids,
leading to larger macro pores and a significant drop in compressive strength.
126
Effects of foam content on Compressive strength of Foam concrete (7 and 28 days)
0.96
40.63
9.57
29.36
57.31
6.59
19.00
1.43
0.00
10.00
20.00
30.00
40.00
50.00
60.00
70.00
0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75
Foam content (%)
Co
mp
res
siv
e S
tre
ng
th (
MP
a)
7 days
28 days
Figure 5.19: Graph of Compressive strength of foamed concrete vs foam content of foamed concrete
Graph of Compressive strength vs foam content
23.99
5.69
1.060
5
10
15
20
25
30
0 10 20 30 40 50 60 70 80 90
Foam content (%)
Co
mp
res
siv
e s
tre
ng
th (
MP
a)
Foamed concrete with polymercontent of 10 % of cementitiousmaterial
Figure 5.20: Graph of Compressive strength of polymer-modified foamed concrete vs foam content
of foamed concrete
Figure 5.21 shows that air void size increases with foam content in foamed
concrete. It can be observed that the foamed concrete with polymer content of 10 % by
127
weight of cementitious materials has higher air void size than the unmodified foamed
concrete. This explains the trend of lower compressive strength in foamed concrete with
polymer added.
Effect of foam content on average air bubble size
0
0.05
0.1
0.15
0.2
0.25
0.3
0.35
0.4
0 20 40 60 80 100
foam content (%)
Avera
ge a
ir v
oid
siz
e (
mm
) No polymer added,
w/c=0.35
Additional polymer
content = 10 % of
cementitious materials,
w/c=0.35
Figure 5.21: Effect of foamed concrete on average air bubble size of foamed concrete
5.4.3 Effect of water-cement ratio
The effect of water-cement ratio on compressive strength was investigated. Figure
5.22 shows that higher w/c ratio brings about a lower compressive strength of the foamed
concrete due to less cement hydration products with lower amount of cement used.
128
Effects of w/c on Compressive strength of Foam concrete (7 and 28 days)
0.00
2.00
4.00
6.00
8.00
10.00
12.00
14.00
0.2 0.25 0.3 0.35 0.4 0.45 0.5 0.55 0.6
w/c ratio
Co
mp
res
siv
e S
tre
ng
th (
MP
a)
7 days
28 days
Figure 5.22: Graph of Compressive strength of foamed concrete vs water-cement ratio of foamed
concrete (50 % foam content used)
5.4.4 Effect of volume fraction of polymer
There is also a slight decreasing trend in compressive strength as the amount of
polymer incorporated into foamed concrete is increased as shown in Figure 5.23. This
could be due to an increase in air void size due to the effect of increasing polymer content
as shown in Figure 5.24. The air void results were obtained by using the microscopy
method as described in Section 3.3.6 in Chapter 3.The compressive strength of acrylic-
modified foamed concrete is slightly lower than that of unmodified foamed concrete. A
decrease in the 28-day compressive strength is, on average, 15.0 % and 20 – 35 % at a
polymer-cement ratio (P/C, as solid polymer content by mass of cement) of 5 % and 10-
20 %.
129
0
1
2
3
4
5
6
7
8
9
10
0 5 10 15 20 25
Polymer content (% of cementitious material)
Co
mp
res
siv
e s
tre
ng
th (
MP
a)
Figure 5.23: Graph of Compressive strength of polymer-modified foamed concrete vs polymer
content (50 % foam content used)
Effect of polymer content on average air void size
0.174
0.2210.235
0
0.05
0.1
0.15
0.2
0.25
0 5 10 15 20
Polymer Content (% of cementitious materials)
Av
era
ge
air
vo
id s
ize
(mm
)
Figure 5.24: Effect of polymer content on average air void size of foamed concrete
5.5 Modulus, Flexural tensile strength, Splitting tensile strength
Inclusion of polymer into foamed concrete has the effect of increasing the
splitting tensile strength and flexural tensile strength. However, Modulus of Elasticity is
130
reduced due to polymer being added. Results are tabulated in Table 5.7 and plotted in
Figures 5.25- 5.29.
Splitting tensile strength was found to be 10 to 18 % of compressive strength and
flexural tensile strength was found to be from 27 to 60 % of compressive strength for
different amount of polymer added. Increase in splitting tensile strength and flexural
strength of foamed concrete caused by adding polymer are attributed mainly to an overall
improvement in cement hydrate bond because of a decrease in w/c ratio and the high
tensile strength of polymer films present in material. Thus, modification of foamed
concrete mixtures with acrylic, results in increased flexibility of the hardened mortar and
concrete. The increase in flexibility of foamed concrete with polymer added can also by
observed by the decrease in modulus of elasticity with increasing amounts of polymer
added.
Table 5.7: Mechanical properties of polymer-modified concrete
Mix Designation
Foam content
(%) w/c ratio
Fresh Density (kg/m3)
Dry Density (kg/m3)
Splitting Tensile Strength (MPa)
Flexural Tensile(MPa)
Modulus of
Elasticity Polymer (kg/m3)
Foam (kg/m3)
PF1 50 0.35 1020 902.10 0.7894 2.0280 5.4600 35.4 33.5
PF2 50 0.35 960 868.41 0.9295 2.9175 3.3400 68.4 33.5
PF3 50 0.35 1000 896.32 0.8902 3.0090 3.1300 99.3 33.5
PF4 50 0.35 960 819.20 1.1533 3.7901 2.4267 128.2 33.5
PF5 20 0.35 1580 1293.51 2.4202 9.2130 2.1567 109.5 13.4
PF6 80 0.35 478 456.64 0.2260 0.5556
Can't be done (too
low) 27.4 53.6
131
2.4202
0.8902
0.2260
0
0.5
1
1.5
2
2.5
3
0 20 40 60 80 100
Foam content (%)
Sp
litt
ing
te
ns
ile
str
en
gth
(MP
a)
Foamed concrete with polymercontent of 10 % of cementitiousmaterial
Figure 5.25: Graph of splitting tensile strength of polymer-modified foamed concrete vs foam content
1.1533
0.9295
0.8902
0.7894
0
0.2
0.4
0.6
0.8
1
1.2
1.4
0 5 10 15 20 25
Polymer content (% of cementitious material)
Sp
litt
ing
te
ns
ile
str
en
gth
(M
Pa
)
50 % foamedconcrete withpolymer
Figure 5.26: Graph of splitting tensile strength of polymer-modified foamed concrete vs polymer
content
132
9.213
2.9175
0.55560
1
2
3
4
5
6
7
8
9
10
0 20 40 60 80 100
Foam content (%)
Fle
xu
ral
ten
sil
e s
tre
ng
th (
MP
a)
50 % foamed concrete with polymer
Figure 5.27: Graph of flexural tensile strength of polymer-modified foamed concrete vs foam content
0
0.5
1
1.5
2
2.5
3
3.5
4
0 5 10 15 20 25
Polymer content (% of cementitious material)
Fle
xu
ral
ten
sil
e s
tre
ng
th (
MP
a)
Figure 5.28: Graph of flexural tensile strength of polymer-modified foamed concrete vs polymer
content (50 % foam content used)
133
5.4600
2.1567
3.34003.1300
2.4267
0
1
2
3
4
5
6
0 5 10 15 20 25
Polymer content (% of cementitious material)
Mo
du
lus o
f E
lasti
cit
y (
MP
a)
50 % foamcontent
Figure 5.29: Graph of modulus of elasticity of polymer-modified foamed concrete vs polymer content
5.6 Proposed alternative roofing systems to provide insulation for the flat roofs of HDB flats
5.6.1 Potential of foamed concrete as a roof insulator
As discussed in Chapter 2, using air gap as a thermal insulator for roofing
application may not be as effective as expected even though air has a very low thermal
conductivity of 0.028 W/m.K. Figure 5.30 shows the sketch of the HDB Secondary
Roofing system. The relationship between heat flux and thickness of foamed concrete (F3)
is found via FLUENT simulation as described in Section 4.4. It is superimposed on the
results of heat flux vs thickness of air gap (derived by FLUENT simulation and
experiments using heat flow meter) obtained by Chew (2005) as shown in Figure 5.31.
As can be seen from Figure 5.31, there exists an optimum thickness of air gap which
minimizes heat transfer. On the other hand, heat flux can be reduced further when the
thickness of foamed concrete gets larger and there is no limit like the case of air. Thus, it
134
shows that foamed concrete can be a more potential roof insulator as compared to air gap.
The U-values (thermal transmittance) of the two alternative roofing systems to provide
insulation for the flat roofs of HDB flats or other buildings would be presented in the
following sections.
Figure 5.30: Sketch of HDB Secondary Roofing System
0
20
40
60
80
100
120
0 5 10 15 20 25 30 35
Thickness of insulation (cm)
He
at
Flu
x (
W/m
2)
Air (Experimental)
Air (Simulation)
Foamed concrete (Simulation)
Figure 5.31: Graph of heat flux vs thickiness of insulation
Ferrocement Roofing Slabs
Air Gap Air Gap
Main Roof Level 120mm Reinforced concrete
Concrete Stump
135
5.6.2 Proposed designs of roofing systems
The proposed designs of the two different alternative roofing systems are
described here. Figure 5.34 shows the results of U-value of each different roofing system
for varying thickness of insulation used. U-value is calculated using the formula given in
Equation 2.3 found in Chapter 2. The data calculated are shown in Appendix B. Two
different alternative roofing systems were investigated. Alternative A (shown in Figure
5.32) consists of a layer of foamed concrete (F3) with k = 0.37 W/m.K., foam content of
25 %, w/c of 0.45 and S.G of 2.5. This grade was chosen in order to comply with the
minimum grade of 30 MPa for structural concrete. The minimum thickness of foamed
concrete need to abide to the U-value of 1.2 W/m2K (value obtained from Table 1.1) is
24.5 cm. It serves as the main roof; there is no normal grade reinforced concrete beneath
it.
Alternative B (shown in Figure 5.33) consists of a layer of foamed concrete
overlaying a 120 mm thick reinforced concrete main roof. The minimum required
strength of foamed concrete used as insulation on roof system is 1.5 kN/m2 (or 1.5 MPa).
Taking into account some factor of safety, the minimum strength can be taken as 3 MPa.
The required strength is quite low because roof tops are generally only subjected to pure
compression and there is no bending. This mix of foamed concrete (with k = 0.19 W/m.K.
and an expected compressive strength of 5 MPa) which consists of 60 % foam content,
w/c of 0.45, S.G of about 0.8 is proposed for Alternative B. The minimum thickness of
foamed concrete for Alternative B roofing system needed to abide to the U-value of 1.2
W/m2K is 10 cm.
136
As shown in Figure 5.34, there is a certain limit to which how low the U-value of
the roofing system using air gap (Figure 5.31) can reach and its U-value exceeded the
required limit of U-value which is set at 1.2 W/m2K. Its U-value can only reach to
minimum of 2.155 W/m2K for roofing system using air gap as an insulator. On the
contrary, U-value can be further reduced for the few proposed alternative roofing systems
using foamed concrete when a larger thickness of foamed concrete is used. Thus, using
air gap as an insulator in roofing systems is not as effective.
Figure 5.32: Sketch of the new roofing system proposed using higher grade foamed concrete
(Alternative A)
Figure 5.33: Sketch of the secondary roofing system proposed using low grade foamed concrete
(Alternative B)
Foamed Concrete secondary roofing Slab
Main Roof Level (normal weight concrete)
B: k = 0.19W/m.K; strength ≈ 5 MPa; S.G.= 0.8
Main Roof Level (foamed concrete)
Foamed Concrete roofing System A: k = 0.37 W/m.K, Strength≈ 30 MPa S.G. = 1.44
137
0.00
0.20
0.40
0.60
0.80
1.00
1.20
1.40
1.60
1.80
2.00
2.20
2.40
2.60
2.80
3.00
3.20
3.40
3.60
3.80
4.00
4.20
4.40
4.60
4.80
0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54
Thickness of insulation (cm)
U-v
alu
e (
W/m
2K
)HDB's current: Air gap in between ferrocement slab on top and RC slab below
Proposed Alternative A: Foamed concrete with k= 0.37 W/m.K.
Proposed Alternative B: Foamed concrete with k= 0.19 W/m.K on top of 120mm RC slab
Lightweight aggregate concrete mix with k = 0.8 W/m.K.
B: 11 cm
50 cmA: 24.5 cm
Figure 5.34: Graph of U-values of different roofing systems of an air-conditioned building against
thickness of insulation
The air space resistance, Ra, for air space beyond 100 mm is still 0.174 m2K/W
(Table 2.1b) as stipulated in the guidelines on ETTV of buildings by BCA (extrapolation
is not permitted), thus its thermal resistance did not increase even though a larger
thickness of air gap is used. According to Chew (2005), thermal resistance decreases
when air gap is too large. This is because airspace resistance to heat is dependent on not
only conduction, but also convection and radiation in and across the air space. Thus,
thermal resistance which is the measure of the resistance to heat transferred offered by a
certain component is increased when thickness of air gap is increased. Heat transfer
through conduction governs in the system until the optimum thickness is reached.
When the air gap is larger than the optimum thickness, its effectiveness as an
insulator will be diminished. This is due to the onset of convection currents when the
138
thickness of air gap gets too large as shown in Figures 2.21 to 2.24. The result shown is
derived assuming that there is no movement of air laterally through the air gap. However,
in reality, there can be additional movement of air due to wind through the openings at
the sides or holes caused by deterioration and this could further increase the heat transfer
from the exterior to the interior of the air-conditioned building.
When lightweight aggregate concrete using LECA with k = 0.8 W/ m.K. and S.G.
1.56 (Chew, 2005) was used as the insulation material, the minimum thickness of foamed
concrete needed to abide to the U-value of 1.2 W/m2K is 50 cm. This thickness is twice
the thickness of foamed concrete proposed in Alternative A. Moreover, the S.G of the
lightweight aggregate is much higher than foamed concrete, thus, the dead weight of the
roof would be very high. Using foamed concrete as the insulating material seemed to be a
more viable option on comparison.
Foamed concrete has much strength as an insulating material. The designer using
this material can make use of its good mechanical strength, lightweight property and low
thermal conductivity property to produce a wide range of densities and properties which
can vary to suit particular requirements. It is also a relatively cheaper option as compared
to many other thermal insulators. From the results, it seems that using foamed concrete as
a roofing insulation is feasible and its performance can be even better than using air as an
insulator.
5.6.3 Effect of moisture on design of roofing system
The result in Figure 5.34 is based on oven-dry foamed concrete. However, in
practice, the foamed concrete that will be cast on site will contain a certain percentage of
139
moisture. The thermal conductivity of foamed concrete will increase when it is wet. Since
moisture correction value for thermal conductivity of foamed concrete is not available,
thermal conductivity of each proposed mix is altered based on assumption that the
finding by Loudon (1983) that for every 1 % of moisture content, a moisture correction of
4 % in the keff of autoclaved aerated concrete would apply to foamed concrete.
32
16
29.5
24.5
11
15
0.00
5.00
10.00
15.00
20.00
25.00
30.00
35.00
0 2 4 6 8 10 12
Thickness of insulation (cm)
U-v
alu
e (
W/m
2K
)
Proposed Alternative A: Foamed concrete with k= 0.37 W/m.K.
Proposed Alternative B1: Foamed concrete with k= 0.19 W/m.K on top of 120mm RC slab
Figure 5.35: Effect of moisture content on the minimum required thickness of foamed concrete as
insulation
Thus, Figure 5.35 shows the thickness of insulation required to abide to the U-
value of 1.2 W/m2K that BCA has regulated versus moisture content in foamed concrete.
Since the thickness of foamed concrete needed as insulation is within reasonable limits,
Alternatives A and B can be considered as viable options to overcome the problems of
the roofing system used by HDB lately.
140
6 Conclusion and Recommendations
6.1 Conclusion
In this project, thermal conductivity values and the corresponding compressive
strength values of foamed concrete and also polymer-modified foamed concrete were
determined. The effect of various key factors like foam content, w/c ratio, polymer-
content on these two properties were investigated. This information will be useful to
engineers who need to design suitable structural or non-structural elements such as the
roofing system for which heat insulation is an important consideration. The minimum
thickness of the roof slabs that is required to comply with U-value limits set by BCA was
found. With the mix proportion and dimension of the elements known, the cost can be
well estimated.
Based on the findings for this research study, the following conclusions can be drawn:
1) Increasing the foam content in foamed concrete causes a decrease in the 28-day
compressive strength and also the thermal conductivity.
2) Increasing the water-cement ratio in foamed concrete reduces the 28-day
compressive strength and also the thermal conductivity.
3) Changing the air void size of foamed concrete while keeping the total amount of
air void constant at 25 % does not change its thermal conductivity value based on
numerical study using FLUENT software. Thermal conductivity of foamed
concrete is influenced mainly by the volume fraction of the air bubbles instead of
141
( ) 0098.10135.010425 +−×= − εε
matrixk
k
by the arrangement of different combinations of pores with varying sizes, shape
and size of the air bubbles when the volume fraction is sufficiently low.
4) Insulating property of polymer-modified foamed concrete was improved quite
significantly by almost 20 % when 20 % by weight of cementitious materials was
incorporated in the foamed concrete mix (denoted by PF4) as compared to
unmodified foamed concrete with the same foam content and w/c ratio.
Mechanical properties like splitting tensile strength, flexural strength of polymer-
modified foamed concrete were found to increase quite significantly. Its elastic
modulus decreased, thus allowing more elongation of the material. However,
water resistance was not too significantly increased and compressive strength was
found to be reduced by about 20 %.
5) Adding polymer to foamed concrete which has high foam content can increase the
stability of the air bubbles (or prevent air bubbles from collapsing) and it enables
foamed concrete of very low density to be produced.
6) A simplified and user-friendly equation,
(where k, kmatrix denotes thermal conductivity of foamed concrete and cement
matrix respectively and ε denotes volume percentage of air, %) was derived from
results using numerical analysis (via FLUENT software). It is useful to predict
thermal conductivity of foamed concrete. It was verified by experimental values
obtained in current research and also in other research, as well as values predicted
from two analytical models, namely self-consistent model and Assad model.
7) Foamed concrete is a more viable choice compared to air gap or lightweight
aggregate concrete as an insulation material on roofing systems. Two suitable mix
142
designs and thickness of foamed concrete as alternative roofing systems on top of
HDB or other buildings to replace the ferrocement secondary roofing system
while complying to the U-value of 1.2 W/m2K set by BCA have been investigated
and found feasible as follows:
a) Alternative A which consists of a single 29.5 cm thick layer of high
grade foamed concrete (F3: 25 % foam content, w/c of 0.45, S.G. of 1.44)
with thermal conductivity of 0.44 W/m.K. (assuming moisture content of
5 %) and compressive strength of about 30 MPa.
b) Alternative B which consists of a 15 cm thick layer of lower grade foamed
concrete (60 % foam content, w/c of 0.45, S.G of 0.8) with thermal
conductivity of 0.228 W/m.K. (assuming moisture content of 5 %) and
compressive strength of about 5 MPa on top of a 12 cm thick reinforced
concrete slab.
6.2 Recommendations for Future Research
In this project, the effect of air void size while keeping air void fraction constant
is studied using numerical method only. Experiments can be done to find out the effect to
verify the numerical results found using FLUENT modeling. It can be done by
introducing polystyrene beads of singular size into cement paste to simulate “foamed
concrete with single-sized air bubbles” and testing the thermal conductivity of using
different sizes of polystyrene beads for different concrete specimens.
As moisture will affect the thermal insulation performance of any concrete greatly
during its application, the water resistance performance of the polymer-modified foamed
143
concrete is still not good enough for water-proofing membrane to be eliminated.
However, a higher percentage of polymer of about 30 % or 40 % (weight of cementitious
materials) could be added to foamed concrete to further reduce its water absorption
instead of a maximum of 20 % used in this study. A roofing system which is devoid of
water-proofing membrane can be proposed with a suitable grade of foamed concrete that
has sufficiently high water-resistant capability.
This study deals only with thermal conductivity of foamed concrete and polymer-
modified foamed concrete. Lightweight aggregates like LECA, perlite and vermiculite
could be added into foamed concrete in further research to improve the compressive
strength level and yet not compromise on the thermal conductivity of the lightweight
aggregate foamed concrete.