What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source...

53
PUBLIC Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 1 What’s new in Logix? 1 Studio 5000 V28 and High Performance Hardware

Transcript of What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source...

Page 1: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

PUBLIC

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 1

What’s new in Logix?

1

Studio 5000 V28 and High Performance Hardware

Page 2: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 2PUBLIC

Logix V24 Enhancements

Program Parameters

Logical Organizer

Partial Import Online Enhancements

Module Encapsulation in AOI

Multiple course updates Rate for Motion

Safe and Standard Connections

Factory Talk Alarm and Events

Support for 1000 Programs / Task

Tools: Compare and Merge Tool

Operating systems Supported Microsoft® Windows® 7 Professional (64-bit) with Service

Pack 1 Microsoft Windows 7 Home Premium (32-bit) with Service

Pack 1 Microsoft Windows Server 2008 R2 Standard Edition with

Service Pack 1 Microsoft Windows 8 Professional (64-bit) Microsoft Windows 8.1 Professional (64-bit) Microsoft Windows Server 2012 Standard Edition (server

version of Windows 8)

2

Page 3: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 3PUBLIC

Logix Designer V26.01 License-Based Source

Protection This release of the Logix Designer

application supports Licensed-Based Source Protection. License-Based Source Protection controls permissions on the following license protected components

When a component is license protected, a CmStick containing the corresponding license must be plugged into a USB port on the computer to open the project containing the component.

License protection uses licenses that you create and administer through a license portal. You can access the CodeMeter® WebAdmin portal through the CodeMeter icon placed in your Windows taskbar after you install Logix Designer application.

Motion Hardware Profile Extensions Kinetix 5700

Operating systems Supported Microsoft® Windows® 7 Professional

(64-bit) with Service Pack 1 Microsoft Windows 7 Home Premium

(32-bit) with Service Pack 1 Microsoft Windows Server 2008 R2

Standard Edition with Service Pack 1 Microsoft Windows 8 Professional (64-

bit) Microsoft Windows 8.1 Professional

(64-bit) Microsoft Windows Server 2012

Standard Edition (server version of Windows 8)

3

Page 4: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 4PUBLIC

Architect Logix Designer View Designer

Studio 5000 V27

Application Code Manager

Introducing three new major components

Page 5: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

PUBLIC

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 5

Studio 5000V28 Highlights

5

Simplifying your design journey

Page 6: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 6PUBLIC

Studio 5000 – Logix DesignerV28

Page 7: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 7PUBLIC

Channel Level Data Structure

Digital

Analog

All information associated with a channel is contained within the channel structure

Data structures have been “future proofed” by allocating reserved bits for new features

The addition of the “Health” status provides for a single check to determine the validity of the data

Each “Health” status is a 2 bit field providing 3 data states

Good Uncertain Faulted

A transition of the “Health” status will rollup and trigger the diagnostic counter to increment

V28

Page 8: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 8PUBLIC8

General EditorDetermination of a “Lonely Routine” During Project Verification

No JSR for “fbd” routine

Warning MessageDuring Verify

During project verify locate routines with no corresponding JSR (Jump to Subroutine)

V28

Page 9: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 9PUBLIC9

Logical OrganizerLocating Routines/Programs Easier Between Organizers

Launches Logical Organizer

Navigates to theContext you

Searched from

Bi-directional

Find

V28

Page 10: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 10PUBLIC

Include Header on Create

1

Structured Text EditorCustomized Comment Header

Customizable Header for Consistent Structured Text Routine Documentation

Customized Header

Auto-Create

V28

Page 11: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 11PUBLIC

FactoryTalk Temporary Users

1

Use FactoryTalk Temporary Users to temporarily give someone access to privileges of a different user group

V28

Page 12: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 12PUBLIC1

Secure a project file with a Permission Set to use the same policies for many controllers

Permission Sets for Securing ProjectsV28

Page 13: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 13PUBLIC1

Apply Permission Sets to Routines, AOIs and Tags to have different policies for different components

Permission Sets for Securing Routines, AOIs and Tags

V28

Page 14: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 14PUBLIC

Guest User Access

1

With Guest Users, grant limited permissions to users who aren’t members of your FactoryTalkDirectory

V28

Page 15: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 15PUBLIC

Secondary Security Authority

1

Guest Users can further limit access to a project file with a Secondary Security Authority

V28

Page 16: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 16PUBLIC

UX Improvements in the FactoryTalkAdministration Console

1

System Tray Utility shows FactoryTalk Login Status Connected / Cached / Cache

Expires Soon / Cached Expired

Provides warnings Logical Names shown in

FactoryTalk Hierarchy Security Settings dialog is resizable,

and action selection persists when switching user selection

V28

Page 17: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

PUBLIC

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 17

Controls for High Performance Automation ControlLogix 5580, CompactLogix 5380 Compact 5069 IO & Stratix 5400 Overview

Page 18: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 18PUBLIC

Agenda

ControlLogix 5580 (L8xE) Controllers

Next Generation Compact IO 5069 Platform

Stratix 5400 Managed Industrial Switch and Architectures

CompactLogix 5380 Controllers

Page 19: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 19PUBLIC

LeverageStratix

5400 with Gig port

Single slot - Quad Core CPU providing• 5x-20x overall scan time improvement vs 5570• Separation of controller functionalities across CPU cores• Controllers scaled by number of supported Ethernet nodes• 25% Increase in memory when compared to L7x processors

1GB Ethernet/IP embedded port• EtherNet/IP I/O (ie; Class 0/1) = 128,000 pps >5x then the 1756-EN2T• 256 total motion axis support @ maximum ~32axis/ms• Support high speed IO with sub millisecond screw to screw response

Ideal processor for • High performance & High axes motion on Ethernet/IP applications

Safety, Phase manager FTAE & high availability will be supported in future release

ControlLogix 5580 Overview

High Performance Controller

Catalog Description 1756-L83E ControlLogix 10MB Controller with 100 EtherNet/IP nodes 1756-L85E ControlLogix 40MB Controller with 300 EtherNet/IP nodes

SupportedIn V28

Page 20: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 20PUBLIC

ControlLogix 5580 Runtime Memory Usage

Previously, design recommendations instructed users to reserve no less than 20% of available memory for future firmware updates and for runtime memory consumers. Memory consumers include : MSG instructions, HMI Trends, Alarms, RSLinx®, Online Edits The 5580 controller runtime memory consumers now separated from application memory freeing up application memory In addition, the onboard memory is now increased

ControlLogix 5580 controllers have 25% or more memory!

5570 Controller Memory Size (MB)5571 25572 45573 85574 165575 32

5580 Controller

Memory Size (MB)

% IncreasedMemory Size

5583E 10 25%5585E 40 25%

Page 21: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 21PUBLIC

Performance & Feature ComparisonsFeatures 5570 5580

Overall performance 1x 5x-20xMemory 2-32 MB 3-40 MBAxis per controller 100 256Axis per ms (50% CPU loading) 6 32Number of I/O (Class 0&1) connections

512*Number of message (Class 3) connectionsNumber of unconnected buffers 40 256Cached Message Buffers 32 256Simultaneous Messages 16 256Embedded Ethernet port No* 1 GbEthernet I/O (Class 0/1) Packets/Sec N/A 128,000Ethernet Messaging (Class 3) MSG/Sec N/A 2000×

Integrated Motion on EtherNet/IP Yes YesSERCOS motion Yes NoLogix Designer V20+ V28+

*Requires 1 or more 1756-ENxT modules for connection to EtherNet/IP nodes× Data size = 32-bits / 1-DINT

Catalog Description 1756-L83E ControlLogix 10MB Controller with 100 EtherNet/IP nodes 1756-L85E ControlLogix 40MB Controller with 300 EtherNet/IP nodes

Page 22: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 22PUBLIC

L7x to L8xE Program Migration Guide

Replacement Guidelines: ControlLogix 5560/5570 to ControlLogix 5580Publication 1756-RM100B-EN-P - November 2015

Page 23: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 23PUBLIC23

Publication: IASIMP-QR026E-EN-E

ControlLogix 5580Popular Reference Drawings

Page 24: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 24PUBLIC

Agenda

ControlLogix 5580 (L8xE) Controllers

Stratix 5400 Managed Industrial Switch and Architectures

Next Generation Compact IO 5069 Platform

CompactLogix 5380 Controllers

Page 25: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 25PUBLIC

Onboard Display Immediate status of comms,

module health and I/O activity without opening Logix Designer

USB Port Provides easy programming,

troubleshooting and firmware updates

Ports Dual Configurable IP port supports DLR/Linear

topologies or Multiple IP addresses for network separation between the machine level and the enterprise level

Enhanced Security Features digitally-signed controller

firmware, controller-based change detection and logging and role-based access control

Three-position mode switch adds a physical layer of security

Embedded Power Supply Built-in System and Field power, reduce physical

field power termination to I/O modules

5069 I/O Supports up to 31 local I/O modules

Analog, digital, HSC, universal analog input, sourcing digital input, address reserve, field power distribution, relay output, sinking digital input

CompactLogix 5380Hardware Features

Page 26: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 26PUBLIC

1 GB Ethernet port High-speed communication, I/O and Motion

Decreased scan times for runtime performance Core programming languages execute with the same performance

Increased application capacity Supports increased number of motion axes

Reduces the need for multiple controllers in complex applications

Supports increased number of EtherNet/IP nodes

CompactLogix 5380High Performance and Increased Capacity

Page 27: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 27PUBLIC

Diagnostic display and status indicators Immediate status of communications, module health and

I/O module activity

Embedded Power Supply Built-in System and Field power, reduce physical

field power termination to I/O modules.

USB Port Programing/Troubleshooting/Flashing Allows local programming support

5380 CompactLogix™ Controller Multi-core CPU enables high-

speed performance

Embedded Energy Storage module Memory backup without a battery

Dual 1-GB Ethernet Port Enables high-performance I/O and motion controlHigh speed backplane

Packet transfer rate of 4.4µs (511 byte packet)

CompactLogix 5380High Performance Control

Page 28: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 28PUBLIC

CompactLogix 5380 HighlightsThe CompactLogix™ 5380 controller is being introduced to enable faster system performance.

• The dual 1-Gb embedded EtherNet/IP port enables The Connected Enterprise by helping customers connect information from across the plant floor to the rest of the enterprise

• Customers with the following challenges have found the CompactLogix 5380 exceeds expectations:

Applications 5380 5370General Purpose

Complex

High Performance

Safety Future

PhaseManager™ Future

Integrated Motion on the EtherNet/IP network

Code execution time limitations• Structured Text = ladder performance

High axis count applications• 20 axes per controller supported

High performance applications• Both local and distributed I/O performance increased

with 5069 Compact I/O™

Page 29: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 29PUBLIC

Controller Communications

29

Communications now separated from control User control and motion tasks are no longer interrupted by communications Previously 20% of the controller scan was used for CPU communications Provides reduced complexity for user programming and task balancing System Overhead Time Slice removed - Users no longer need to adjust

Page 30: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 30PUBLIC

Programming Language Execution and Task Switching EnhancementsController Language Scan Times Five LD routines with 1000 rungs each Five STX routines with 1000 lines each

1000 ADD / SUB / MUL / DIV / MOD instructions

15,000 different program scoped tags, ie: Worst caseL30ER– Ladder Diagram L340ERM – Ladder Diagram

11x Increase!

L30ER – Structured Text L340ERM – Structured Text

20x Increase!

Structured Text Scan Time = Ladder Diagram Scan Time

Controller Task Switching Times

Controller Task execution scan time

Task Switch Time

L3x 168 ms 165 µsCMX 5370 45 ms 42 - 45 µsCMX 5380 09 ms 09 - 10 µs

Page 31: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 31PUBLIC

Enhanced Diagnostics

31

CompactLogix™ 5380 Controller Task Monitor now part of product embedded web page

Page 32: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 32PUBLIC

Performance & Feature ComparisonsFeatures 5370 L3 5380 L3

Overall performance 1x 5x-20xMemory 1-3 MB 0.6-4 MBAxis per controller 16 20Axis per ms (50% CPU loading) 2 32Number of I/O (Class 0&1) connections

512*Number of message (Class 3) connectionsNumber of unconnected buffers 40 256Cached Message Buffers 32 256Simultaneous Messages 16 256Embedded Ethernet port 10/100Mb 10/100/1000MbEthernet I/O (Class 0/1) Packets/Sec 10,000 128,000Ethernet Messaging (Class 3) MSG/Sec 400 2000×

Integrated Motion on EtherNet/IP Yes YesAnalog motion No FutureIntegrated safety (SIL2 PLd / SIL3 PLe) Yes FutureLogix Designer V20+ V28+

× Data size = 32-bits / 1-DINT

Memory Size Total # of Controller EtherNet/IP node

5069-L306ER/ERM(July 2016)

0.6 MB 16

5069-L310ER/ERM (July 2016)

1 MB 24

5069-L320ER5069-L320ERM(July2016)

2 MB 40

5069-L330ER/ERM(July 2016)

3 MB 50

5069-L340ER(July 2016)5069-L340ERM

4 MB 55

Page 33: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 33PUBLIC

CompactLogix 5380 General Specifications

33

Operating Temperature 0°C to + 60°C (32°F to +140°F)

Storage Temperature -25°C to + 85°C (-40°F to +185°F)

Relative Humidity 5% to 95% non-condensing

Maximum Altitude 2000 meters (6561 feet)

Vibration Operating: 5 g, 10 to 500 Hz, 0.030 in.

maximum peak-to-peak Shock

Operating: 30 g DIN rail mounted Non-Operating: 50 g DIN rail mounted

Certification (At Release)

Certification(Post release)

Page 34: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 34PUBLIC

Agenda

ControlLogix 5580 (L8xE) Controllers

Next Generation Compact IO 5069 Platform

Stratix 5400 Managed Industrial Switch and Architectures

CompactLogix 5380 Controllers

Page 35: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 35PUBLIC

Compact 5069 IO Overview

35

5069-AEN2TR Supports 31 local I/O modules Supports DLR (Device Level Ring) configuration Supports 1-GB embedded switch technology for

Device Level Ring, Linear and Star topologies

Phase 1 Release Limited I/O modules Connects to 5580 and 5380 processors ONLY Provides screw to screw time of 500 micro seconds.

High Speed

IO

Page 36: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 36PUBLIC

5069 IO Modules

36

Output - 24Vdc

Input – Analog/Temperature

Output – Analog

Output – Relay Isolated

EtherNet/IP Adapter

Field Power Distribution

ARM

IB16F

OB16F

IY4

OF4

OW4I

AEN2TR

FPD

OF8

Address Reserve

IF8

IB6F-3W

OX4I

High Speed Counter HSC2xOB4

IB16

OB16

Input - 24Vdc

Operating Temperature:0°C to + 60°C (32°F to +140°F)Storage Temperature: -25°C to + 85°C (-40°F to +185°F)

Page 37: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 37PUBLIC

5069 Digital Input Modules5069-IB16, 5069-IB16F, 5069-IB6F-3W

37

Catalog Indicator

Power Status Indicator

I/O Status Indicator

I/O removable terminal

Product Type

Note: I/O removable terminals are sold separately

Page 38: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 38PUBLIC

5069 Digital Input Modules5069-IB16, 5069-IB16F, 5069-IB6F-3W

Page 39: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 39PUBLIC

5069 Digital Output Modules5069-OB16 and 5069-OB16F

393939

Catalog Indicator

Power LED Status

I/O Status Indicator

I/O removable terminal

External Field Power input

Product Type

Note: I/O removable terminals are sold separately

Page 40: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 40PUBLIC

5069 Digital Output Modules5069-OB16 and 5069-OB16F

Page 41: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 41PUBLIC

5069 Analog Input Modules5069-IY4 and 5069-IF8

41

I/O Status Indicator

I/O removable terminal

Catalog Indicator

Power LED Status

Product Type IF8 IY4

Note: I/O removable terminals are sold separately

Page 42: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 42PUBLIC

5069 Analog Input Modules5069-IY4 and 5069-IF8

42Scan Time: 0.625 ms per channel 2.5 ms per group

Page 43: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 43PUBLIC

5069 Analog Output Modules5069-OF4 and 5069-OF8

43

I/O Status Indicator

I/O removable terminal

Catalog Indicator

Power LED Status

Product Type OF4 OF8

Note: I/O removable terminals are sold separately

Page 44: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 44PUBLIC

5069 High Speed Counter Module5069-HSC2XOB4

44

I/O Status Indicator

I/O removable terminal

Catalog Indicator

Power LED Status

Product Type

Note: I/O removable terminals are sold separately

Page 45: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 45PUBLIC

5069 High Speed Counter Module5069-HSC2XOB4

45

Page 46: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 46PUBLIC

5069 Field Power Distribution Module

464646

Power removable terminal

Catalog Indicator

Power LED Status

Product Type

Note: I/O removable terminals are sold separately

Page 47: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 47PUBLIC

5069 Address Reserve Module Anatomy

474747

Catalog Indicator

Power LED Status

Product Type Purpose

Slot reservation for future expansion

Page 48: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 48PUBLIC

5069 Compact I/O General Specifications Operating Temperature

0°C to + 60°C (32°F to +140°F) Storage Temperature

-25°C to + 85°C (-40°F to +185°F) Relative Humidity

5% to 95% non-condensing Maximum Altitude

2000 meters (6561 feet) Vibration

Operating: 4.6 g, 10 to 500 Hz, 0.030 in. maximum peak-to-peak

Shock Operating: 30 g DIN rail mounted Non-Operating: 50 g DIN rail mounted

Certification (At Release)

Certificatio(Post release)

Page 49: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 49PUBLIC

Agenda

ControlLogix 5580 (L8xE) Controllers

Next Generation Compact IO 5069 Platform

Stratix 5400 Managed Switch and Architectures

CompactLogix 5380 Controllers

Page 50: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 50PUBLIC

Stratix 5400 Managed Switches

50

Optimized Integration Embedded Cisco technology provides

integration with enterprise network FactoryTalk® View faceplates for status

monitoring and alarming Predefined Logix 5000® tags for

monitoring and alarming Studio 5000® Add-on Profiles (AOPs)

for configuration and monitoring

Stratix 5400™ Enhanced Switching & Routing All gig port options for high performance

resilient network requirements Layer 3 routing capability for segmented

network and plant to enterprise integration

Advanced Networking Features Power over Ethernet (PoE) for

simplified end device wiring Network Address Translation (NAT)

reduces commissioning time Enhanced security options

Simplified Setup and Maintenance Common configuration and support tools Default automation configurations Optimized “Smartport “ configurations DHCP per port device IP addressing SD card for easy device replacement

Product Profile ENET-PP012-EN-P

Page 51: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 51PUBLIC

ControlLogix 5580 High Performance Architecture #1

Leverage built-in high performance

EtherNet/IP port on L8 with gig

connection to handle network

traffic

Leverage Stratix 5400 with all Gig ports for high speed communication with L8xE & 5069 IO

Leverage 5069 IO using gig

connection for high screw to

screw response

PanelView Plus 7 with Embedded

Switch technology to join the DLR

network

Kinetix 5500 servo system for single to multi-axis

applications with single cable VPL

motors

Page 52: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 52PUBLIC

Leverage Stratix 5400 with all Gig ports for high speed

communication with 5069 IOStratix 5400 also allows for

system to join the network via REP and segment the traffic via

VLAN/NAT

Leverage built-in high performance EtherNet/IP port on L8 with gig connection to handle 5069 IO &

CIP Motion

Leverage EN2T for all other IO and HMI communication.

ControlLogix 5580 High performance Architecture #2

Page 53: What’s new in Logix? - TRCAutomation.Solutions€¦ · Logix Designer V26.01 License-Based Source Protection This release of the Logix Designer application supports Licensed- Based

PUBLIC

www.rockwellautomation.com

Copyright © 2016 Rockwell Automation, Inc. All Rights Reserved. 53

Thank You!!