What is a resistance grounding.docx

6

Click here to load reader

Transcript of What is a resistance grounding.docx

Page 1: What is a resistance grounding.docx

What is a resistance grounding?

Resistance grounding in an electrical system is defined as the use of a resistor as a

grounding path between the neutral point of transformer or generator and the earth

ground. There are two methods to accomplish this system of grounding, namely the low

resistance grounding and high resistance grounding.

IEEE Standard 142-1991 states that the reasons for limiting the current by resistance

grounding may be one or more of the following:

1. To reduce the burning and melting effects in faulted electrical equipment such as switch gears, transformers, cables and rotating machines.

2. To reduce the mechanical stress in circuits and apparatus carrying fault currents.

3. To reduce electrical shock hazards to personnel caused by stray ground fault currents in the ground return path.

4. To reduce arc blast or flash hazard to personnel who may have accidentally caused or who happen to be close proximity to the ground fault.

5. To reduce the momentary line voltage dip occasioned by the occurrence and clearing of a ground fault.

6. To secure control of the transient over voltages while the same time avoiding the shutdown of a facility circuit on the occurrence of the first ground fault (high resistance grounding).

Low Resistance Grounding

Low resistance grounding limits the ground fault current to a minimum value of 50

amperes. The reason for having this value is to quickly clear the fault (usually within a

few seconds).

Purpose:

Limit the damage to the equipment

Prevent additional faults from occurring

Provides safety to personnel

Localizes the fault

Characteristics:

Limits phase to ground currents to 50 ampere to 400 ampere.

Page 2: What is a resistance grounding.docx

Reduces  arcing current and eliminates arc flash hazards associated with phase to ground arcing current conditions.

Limit the mechanical damage and thermal damage to shorted transformer and rotating machinery windings.

Does not prevent operation of over current devices.

Does not require a ground fault detection system.

Conductor insulation and surge arresters must be rated based on the line-to-line voltage. Phase to neutral loads must be served through an isolation transformer.  

High Resistance Grounding

IEEE Standard 142-1991 defines High Resistance Grounded System as follows:

 A grounded system with a purposely inserted resistance that limits ground fault current can

flow for an extended period without exacerbating damage. This level of current is commonly

thought to be a 10 A or less. High resistance grounded systems are designed to meet the

criteria R0 < = Xco to limit the transient over-current voltages due to arcing ground faults. Ro

is the per phase zero sequence resistance of the system and Xco is the distributed per phase

capacitive reactance-to-ground of the system.

Purpose:

High resistance grounding solves the problem of transient over-voltages, thereby

reducing equipment damage. This is to industrial plants where the connected loads are

very sensitive.

Characteristics:

Limit phase to ground currents to 5-10 ampere . Reduces  arcing current and eliminates arc flash hazards associated with phase to ground arcing current conditions.

Eliminate  the mechanical damage and may limit thermal damage to shorted transformer and rotating machinery windings.

Prevents operation and over current devices until the fault can be located.

Requires a ground fault detection system to notify the facility engineer that a ground fault condition has occurred.

Conductor insulation and surge arresters must be rated based on the line-to-line voltage. Phase to neutral loads must be served through an isolation transformer.   

Page 3: What is a resistance grounding.docx

Sizing the grounding resistor

Ohms law (R = V / I) state that if we know the phase to ground voltage  and the desired

current we can directly compute for the grounding resistance. But in case of grounding

resistance we need to consider the line to ground capacitance that the system has. This

capacitance determines the magnitude of zero sequence charging current. Therefore

we need to know first the charging current of the capacitance developed between phase

to ground and we will determine the resistor calculation thereafter.

Determining the   capacitive charging current

Schematic and Phasor Diagram of Capacitance Charging Current

As describe in the above diagram, while there is no physical capacitance present in the

circuit however there is a large value of current that is being expected during the fault

condition, that is why we will not disregard the same. For convenience we will use the

typical charging current table, viz:

Page 4: What is a resistance grounding.docx

Typical Charging Current

With the resistance set for the maximum, the current should be limited to the half the

estimated charging current.

Three Phase Formula: Rmax =  2VL / [ sqrt(3) x 3 Ico]

Example:

An electrical system with installed capacity of 5 MVA has a system voltage of 13, 800

Volts. Determine the maximum value of grounding resistor?

Solution:

Referring to the table above @ 13,800 Volts and 5 MVA (5,000 KVA), 3 Ico = 50 Amps

Therefore:

Rmax =  2VL / [ sqrt(3) x 3 Ico]

R max = 2 x (13,800) / (1.73 x 50)

R max = 319 ohms

Page 5: What is a resistance grounding.docx

Summary:

1.  Resistance Grounding Systems have many advantages over solidly grounded systems including arc-flash hazard reduction, limiting mechanical and thermal damage associated with faults, and controlling transient over voltages.

2. High resistance grounding systems may also be employed to maintain service continuity and assist with locating the source of a fault.

3. When designing a system with resistors, the design/consulting engineer must consider the specific requirements for conductor insulation ratings, surge arrestor ratings, breaker single-pole duty ratings, and method of serving phase-to-neutral loads.