Wet-seal CPD Solutions...
Transcript of Wet-seal CPD Solutions...
CPD Solutions 2016
References from AS 3740 2010 Amended 2012and AS 4654.2 2012
Presentation by Robert Rath
We t - s e a l
New Parliament House Construction 1983
Robert Rath was supervisor over road construction and waterproofingfor 5 ½ years
Internal Waterproofing to AS:3740 2010 Amended 2012
Design Consideration
Type of Substrate Concrete Screed Structural Flooring (Particle board) Plywood Compressed Fibre Cement Scyon Hebel Others (e.g. Screed Super, Strand board, Modak board
Eternit system floor)
Basic overview 70% water based
15% resin (petroleum base)
15% other-bitumen, polyurethanes, epoxies
Names given; Ardex, Davco, Mapei, Bostik,
Crommelin (Termidry)
Main Domestic Products used in AustralianWaterproofing
ProductsWaterbasedresin
other
AS 3740 2010 amdt 2012
Actual floor waterproofed by a waterproofing contractor Non–compliant to the NCC
AS 3740 2010 amdt 2012
Bond breaker required on structural floor substrates and all floor to wall junctions
AS 3740 2010 amdt 2012
In general water based membranes require a minimum of 48 hours prior to tiling (there are exceptions)
AS 3740 2010 amdt 2012
Requirements for baths that have showers over them
For baths that do not have an integral edge detail to allow for a vertical termination of thewaterproofing, there shall be full waterproofing at the walls and floor area and waterproofingunder the bath. The enclosed space under the bath shall be ventilated.
NOTE: Ventilation is required to allow evaporation of water leaking around the edge of thebath into the enclosed airspace under the bath.
AS 3740 2010 amdt 2012
HUMDINGER KITS WASTE CONNECTORS - OVERFLOW • Cut 40mm DWV pipe to desired length and
push into Humdinger elbow. • All rubber ring joints, no gluing required. • Drill out nipple to connect overflow. • Overflow connection can be drilled out to
accommodate overflow.
AS 3740 2010 amdt 2012
Water stop angle required at door entry or 1500mm from rose outlet (NOTE a minimum of 15mm)
AS 3740 2010 amdt 2012
Hobless shower - water stop angle required(NOTE a minimum of 5mm above final finish)
AS 3740 2010 amdt 2012
Enclosed shower screen placement (NOTE SHALL be installed flush with inside edge of hob)
AS 3740 2010 amdt 2012
Hob shower - water stop angle required(NOTE a minimum of 5mm above final finish)
Testing shower area for leaks
Shower screen installed on the external side of hob Non-compliant with NCC (will fail over time)
Testing shower area for leaks
Test under way (water leaking from behind tile and through grout) (less than 2 minutes)
Testing shower area for leaks
Test under way (water leaking from behind tile and through grout (less than 2 minutes)
Waterproofing Failures
Incorrect application of waterproofing, lack of knowledge on National Construction Code requirements, Hobs, Penetrations, Incorrect positioning of shower screen, not waterproofing full floors on unenclosed shower areas, laying membranes on high moisture concrete or screed, not having the Waterstop angle installed correctly (e.g. allowing tiler to install incorrectly).
Tradespersons carrying out works on or above unprotected membrane and damaging membrane.
Builders applying pressure to have tiles laid before the manufactures recommended cure time. (Legal requirement, complying to manufacturers specifications data, Newcastle Builder and Telecom case NSW). Tiler screeds above the flashing.
Tilers cutting out water stop angles and re-positioning without complying to the Code.
Grout hard up against membrane (cuts through membrane). Screed hard up against membrane (movement abrasive to the membrane).
Causes
Suitable Substrates
• Comply with AS: 3600• Type of finish prior to membrane application (e.g. Wood float finish) • Minimum 1:100 Fall• Drip line
Concrete
• Comply with AS 1684 (all parts)• Minimum 1:100 Fall• AS/NZS 2269 (Staggered sheets required)
Timberplywood
• AS/NZS 2908.2 • or ISO 8336• Minimum 1:100 fall
Cellulose – cement products
Waterproofing of Decks and Balconies to AS:4654 Requirements
Design Consideration
Type of Substrate Concrete Plywood Compressed Fibre Cement Scyon Hebel Others (e.g. Screed Super, Strand board, Modak board,
Eternit system floor) Note: Particle Board or Tile and Slate Underlay is not
acceptable.
Waterproofing of Decks and Balconies to AS:4654 requirements
Class of Membrane
Class 1 membrane: Normally strong and rigid, elongation at break less than 60%. Class 2 membrane: More flexible with elongation at break less than 300%. Class 3 membrane: Highly flexible, elongation at break greater than 300%.
Waterproofing of Decks and Balconies to AS:4654 requirements
Service Conditions
Ultra violet light can damage some membranes and protection is required (e.g. Tiles over the membrane or roof garden over the membrane).
Local environment conditions can effect membranes and the range of temperatures vary from -150C to +850C.
Low temperatures may reduce elongation and high temperature can cause softening of the membrane.
Water immersion for long periods may result in degradation of the membrane (what is the water absorption in membrane?).
Chemicals may effect some membranes (e.g. fertilizers, orange/citrus).
Waterproofing of Decks and Balconies to AS:4654 Amended 2012
AS:4654 Membrane for above ground usage AS:4654.1 Materials AS:4654 .2 Design and installation
Waterproofing of Decks and Balconies to AS:4654 requirements
Types of Membrane Systems
A membrane system that is weighted down by ballast or other finishes (ballasted membranes).
Liquid membranes or systems with full bonding to the substrate (fully bonded membranes).
Membrane system that uses ballast insulation over them (IRMA) (e.g. Australia’s New Parliament House roof area).
Membranes that are fastened to the substrate (mechanically fixed) (e.g. high wind roofs).
Membranes that are only partly bonded to the substrate (partially bonded) (e.g. may be used in areas where extra movement is required).
Considerations
Applicator competent. Knowledge of the Australian Standard and NCC. The Builders knowledge of substrate requirements. The Builders knowledge of weather conditions and the effects on membranes. The cost of getting it wrong (e.g. if a deck cost $1200 to waterproof, then you can expect a minimum of
$9,500 as a starting point, and if a person lost their life due to a catastrophic failure that was instigated by the membrane failing, then no cost can replace the persons life).
Builder reputation!!! The disturbance to your clients home and lifestyle. Scaffolding. Work hours lost by all parties.
Type of Membrane?
Wet-seal Enviro-coat DS 411 Liquid Applied Completely reinforced with fabric
throughout the entire system
Thermoplastic Example: Sarnafil Hot Weld
Wet-seal Enviro-coat DS 411 Membrane turn up and under door
frame sill detailing All movement joints detailed
Level entry and Preparation
Level Entry Detail referenced from AS 4654.2
Post Penetration Correct detailing is a MUST
Protection Correct planning to limit damage
to membrane
Waterproofing Failures
Bituminous Membrane Reason: Workmanship Incorrect detailing
Sheet Membrane Reason: Workmanship Incorrect detailing
Torch on Membrane Reason: incorrect acceptance of
substrate Incorrect levels (ponding water)
and poor workmanship
Waterproofing Failures
Water Migration from Door Sill
Reported as Membrane Failure Incorrect report
Internal Flooring Timber not affected
Supervisor Brain Failure
Advised contractor job ready to have membrane applied Advised contractor job
ready to have membrane applied
Common Issues that Lead to Waterproofing Failures
Penetrations, post, railings and service units fitted after the membrane has been laid without notifying the installer!
Tradespersons carrying out works on or above unprotected membrane.
Builders applying pressure to have the job done when adverse weather conditions will or are likely to be present.
Capillary (e.g. drip angle hard up against the external fascia (min. of 6mm offset required), wall sheeting down into screed bed).
Tiler screeds above the flashing.
Tiler installs tiles without movement joints or expansion joints (interferes with floor to wall membrane movement details).
Grout hard up against membrane (cuts through membrane).
Screed hard up against membrane (movement abrasive to the membrane).
Causes
Good Design To Accommodate Aesthetics
Membrane flashed up over 120mm behind cedar cladding. Powder coated 50mm angle on internal side of external doors.With waterproofing to top of angle, weep hole/drainage at base of door sill.
Good Design and Project Management
Be aware of new products and testing of compatibility
Protection Scyon Code
Australian Standard
Internal or External
Testing
Scyon is becoming one of the main movers