Transcript of Weidmuller SAI PI
SAI-Active UniversalProduct Information
Contents
3
SAI-Active Universal
Overview 4
Applications 8
PROFIBUS-DP 10
DeviceNet™ 12
CANopen 14
PROFINET 16
EtherNet/IP 17
Modbus TCP 18
Accessories 20
Sensor cables 24
Valve connector 27
Appendix 28
Sensor-Actuator-Interface-Active
Overview
4
SAI-Active Universal
I/O LEDs for status, input and output
as well as individual channel diagnosis
Status LEDs for voltage,
fieldbus and
group diagnosis
2 x Multicard markers or
1 x 40-mm long strip
for printing IP addresses
2-hole mounting and functional earth connection
Transparent strips of markers:
• A marker for each I/O point
• Illuminated print
• Printjet compatible
M12 or M8 circular connectors
with threaded ring made of metal
Illuminated configuration area
for fieldbus address and
plug-in jumpers for voltages
2 x M12 circular connectors for fieldbusses
2 x M12 circular connectors for power supply
Just 54 mm wide
The SAI-Active Universal range is the result of years of
experience that Weidmüller has made with distributors for
industry. The fieldbus systems supported are PROFIBUS-DP,
DeviceNet™ and CANopen.
The housing has been tailor made to meet the demands of
industry. That is why it is resistant to aggressive cleaning
agents, vibration, shocks and temperature as well as being
sealed against the ingress of water and dust.
One module – three Ethernet dialects
The new SAI Active Universal modules for Industrial Ethernet
have three Ethernet dialects integrated. The module selects
PROFINET IO, EtherNet/IP or Modbus TCP by means of
automatic port recognition functionality.
5
Overview
Connection technology
The concept behind the new distributors champions rapid and
simple installation in harsh environments. Commercially avail-
able, standardised M8 and M12 connectors form the back-
bone of the connection technology. Robust threaded rings
made of metal as well as standard assignments ensure safety
and fewer mistakes during the wiring process.
Two M12 connections are available respectively for the field-
bus. Thus, there is no need for an external T-piece – and the
modules can easily be connected up to one another. As the
standards specify, B-coding is used for PROFIBUS-DP and
A-coding for DeviceNet™ und CANopen. Industrial Ethernet is
wired point-to-point from a switch. The modules are equipped
with a D-coded M12 connector.
User-friendly connection of the functional earth is achieved by
means of a metal clip in the mounting hole. A secure contact is
created automatically when screwed to an earthed base made
of metal. Otherwise, the screw point offers sufficient space for
a round cable lug, via which a cable can be connected for
dissipation purposes.
Two central mounting holes ensure simple and reliable
mounting.
Status indication
I/O statuses are indicated by means of elegant light guides
in the form of arrowheads. These point in the direction of
the markings and connectors.
The light also illuminates the corresponding marker, which
allows it to be quickly and clearly read under working
conditions.
In addition, the power supplies, group diagnostic messages
and fieldbus statuses are indicated via seven status
indicators.
Overview
6
SAI-Active Universal
The electronics
Diagnosis
Each I/O channel is constantly scanned for errors. If an error is
detected, the colour of the LED changes from yellow to red
and a message is transmitted via the fieldbus. As well as
individual channel diagnostics, a module diagnosis is also
available for overvoltages, short-circuits and the fieldbus.
Outputs
The outputs are short-circuit proof as well as being protected
against polarity reversal. Two outputs are available for high-
performance actuators that can be operated with max. output
power of 2 A. As well as offering freedom of choice between
16DI through to 8DI/8DO, the 16DI/8DO allows the user to
customise the configuration to suit the application.
Analogue modules
The analogue combi-module is uniquely versatile. The configu-
ration between current and voltage is selected via the configu-
ration software of the master. JACKPAC® offers further inter-
face options. These modules are simply installed between the
distributors and the sensors where they condition signals.
The module offers 4 additional digital inputs.
Power supply
The modules can be supplied with max. 4 different voltages.
In addition to the module voltage, which is also used for the
inputs, three supply terminals are available for the outputs.
The outputs can also be individually switched off in accordance
with application needs. Two jumpers provide the option of
bridging the electrical power supply. Thus enabling 3 output
circuits to be operated separately.
Illuminated configuration area
The configuration area for the module is situated below the
transparent cover. Two rotary switches are available to set the
fieldbus addresses. Thus allowing up to a max. 126 addres-
ses to be set for PROFIBUS-DP. Two jumpers have also been
included on the right-hand side to bridge the electrical power
supplies. Illuminating the configuration area is to date a unique
feature that signalises the module is switched on and
functioning. Moreover, it also allows the rotary switches to be
more easily recognised.
Overview
7
Transparent markers
A marker is available for each I/O channel as well as two
markers for the module as a whole. The markers do not have
to be fitted individually on the I/O side. Marker strips offer the
added advantage of rapid installation. An additional 40-mm
wide marker has been specially adapted to suit the module.
This allows longer texts such as markings with up to
40 characters to be fitted and clearly read without hindrance.
Supplementary products
A Multicard strip is included in the range of supply for marking
the module. In conjunction with Weidmüller’s PrintJet, these
markers are remarkably user-friendly to print.
The new M12 sealing plugs can now be more easily fitted
manually and to the correct torque using our Screwty® tool.
Two additionally integrated slots allow the plug to be fitted with
either a small or large flat bladed screwdriver.
Cables and accessories provide a perfect finish to our
programme of distributors.
Applications
8
SAI products in action
If it is true that Weidmüller belongs to the world-wide leaders
in the field of distributors, then this has a particularly good
reason. In developing SAI distributors Weidmüller’s design
engineers have concentrated on achieving economically
favourable installation concepts. This has led, quite often in
close co-operation with renowned users, to the introduction of
sophisticated products onto the market that lead the way with
regard to functionality and set standards in quality – all over
the world.
Today, modern installation concepts have to be drawn up so
that they save materials, money, time, space and weight from
the very beginning. For that reason, products that make such
concepts possible are of crucial significance.
And it is exactly in this regard that you can trust Weidmüller's
quality, experience and innovative force.
Applications
9
‘Mounted directly’, Weidmüller’s SAI distributors are integrated
into the machine or system. They bring together signals from
the sensors and actuators on the spot. At this point, installa-
tion and service costs can be reduced by utilising pre-
assembled cables and commercially available M8/M12 circular
connectors. Fieldbus interfaces on the other side of the
distributor provide the connection to the controls.
In order to supply the customer with optimum products for
their applications, the new SAI-Active Universal series has
turned to innovative ideas and remained true to proven
standards. Our SAI-Active distributors are at home in factory
automation - in the field. Exactly where the process is in action
– where the sensors and actuators are fitted. These versatile
products support all conventional fieldbus systems as well as
being able to process both analogue and digital signals.
10
System description PROFIBUS-DP
PROFIBUS
Principle
PROFIBUS-DP is a master–slave system consisting of one
master (usually implemented in the PLC) and up to 31 slaves
per segment. During operation, the master constantly interrog-
ates the slave stations. Several masters can also be integrated
within one network to relay the transmission authorisation
(token passing).
PROFIBUS-DP uses a physical layer based on the RS 485
standard which has performed excellently in industrial applica-
tions.
The system uses a shielded, twisted 2-wire cable and is
extremely resistant to electrical interference. PROFIBUS-DP
is suitable for connecting a large number of I/O points. Up
to 126 addressable subscribers enable the connection of
thousands of analogue and digital I/O points within a network.
Every PROFIBUS-DP module has a so-called GSD file which
contains detailed information about the module (I/O data
volume, possible transmission rates, update status, etc.).
The station GSD file is required in order to configure a station
within the PROFIBUS-DP system.
The GSD files are available on the Weidmüller website at
www.weidmueller.com.
Network structure
The network is constructed as a line structure with an active
bus termination at both ends.
When utilising SAI-Active Universal modules a bus terminator
plug (Order No.: 1784770000) is plugged into the BUS-Out
socket. Ideally, no spur lines should be created; to that end,
the Weidmüller modules have been designed with two
connections for connecting the fieldbus.
Max. 126 nodes can be addressed at all transmission
rates. The maximum extension with 7 repeaters is 9.6 km
(8 x 1.2 km).
Bus extension
Transmission Length of bus line Stub cable length No. of repeaters
rate Total segment (max.)
9.6 kbps 1200 m 6.6 m 7
19.2 kbps 1200 m 6.6 m 7
93.75 kbps 1200 m 6.6 m 7
187.5 kbps 1200 m 6.6 m 7
500 kbps 400 m 6.6 m 7
1.5 Mbps 200 m 6.6 m 4
12 Mbps 100 m preferably none 4
Maximum system extension
PROFIBUS-DP can accommodate max. 32 devices per
segment. One segment corresponds to a subsection between
two repeaters. If no repeaters are used, the complete network
corresponds to one segment. The following table indicates
the maximum extension options.
Addressing
The address setting for the corresponding station is set
manually by means of two coded rotary switches.
Transmission rate
The transmission rate must be identical throughout the
whole network, and is defined by the master. The baud rate
is compared automatically upon switching on. No adjustments
need to be made at the module.
At 12 Mbps the typical response time is < 1 ms per
1000 I/O points.
The baud rate cannot be changed during operation!
11
PROFIBUS
PROFIBUS-DP Universal
Ordering dataPlug-on type
16 digital inputs
16 digital inputs / 8 digital outputs
4 analogue inputs / 2 analogue outputs / 4 digital inputs
Information
Technical data bus system
Bus sharing unit Slave
Transmission rate Max. 12 Mbps
Diagnostic display red
Fieldbus interface RS 485
Potential isolation yes
Station address rotary switch 1–125
bps rate automatic
Information
Technical dataGeneral data
Insulation material of housing PBT
Flammability class UL 94 V-0
Operation temperature 0 °C ... 55 °C
Storage temperature –25 °C ... 70 °C
Ingress protection class IP 67
Electrical data electronics-module
Operating voltage 24 V DC (20,4 … 28.8 V)
Max. current carrying capacity per output signal 0.5 A; 2.0 A
Output levels Short-circuit-protected
Total current. max. 8 A
Digital inputs TYPE 1 to EN 61131-2
Analogue outputs –10 … +10 V; 0 … +10 V; 0 … 20 mA; 4 … 20 mA
Analogue inputs –10 … +10 V; 0 … +10 V; 0 … 20 mA; 4 … 20 mA
Resolution 12 Bit
Accuracy < 0.2 %
UL certification in preparation UL certification in preparation
Type Qty. Order No.
SAI-AU M8 PB 16DI 1 1906550000
SAI-AU M8 PB 16DI/8DO 1 1906640000
Type Qty. Order No.
SAI-AU M12 PB 16DI 1 1890020000
SAI-AU M12 PB 16DI/8DO 1 1890010000
SAI-AU M12 PB AI/AO/DI 1 1890000000
AccessoriesPlug Type Qty. Order No.
Terminating plug PB in M12 plug SAIEND PB M12 5P B-COD 1 1784770000
Metal plug, pin M12, 5-pole, b-coded SAISM 5/8S M12 5P B-COD 1 1784790000
Metal plug, socket M12, 5-pole, b-coded SAIBM 5/8S M12 5P B-COD 1 1784780000
Accessories
Protective cap, M12, black SAI-SK-M12-UNI 20 2330260000
Marker, transparent ESG 8/13.5/43.3 SAI AU 5 1912130000
SAI-AU SAI-AU
M8 M12
12
DeviceNetTM
DeviceNetTM
Principle
DeviceNetTM is a fieldbus system from the USA that is being
increasingly employed in Europe and Asia. In terms of the
physical layers 1 and 2 of the ISO 7-layer model, DeviceNetTM
is based on CAN (Controller Area Network).
The ISO application layer (layer 7) in DeviceNetTM makes use
of the so-called “Common Industrial Protocol” (CIP). This is
an open standard which is also used for ControlNetTM and
EtherNet/IP. In the future this will enable permanent communi-
cation between the field level and the Internet.
DeviceNetTM is a multi-master system and its protocol pri-
oritises the data traffic in such a way that I/O signals have
a higher priority than configuration data.
Every DeviceNetTM module has a so-called EDS file (Electronic
Data Sheet), containing an exact description of the module.
All information about I/O and status data required by a master,
e.g. a PLC or IPC, are saved in this file and can be used to
integrate the module step by step into the control program.
The EDS files are available for downloading on the Weidmüller
website at www.weidmueller.com.
Network structure
ISO 11898 prescribes a line structure for the DeviceNetTM
network.
A line structure has a terminating resistor of 120 Ω at each
end. A bus terminator connector (order No. 1784760000) can
be plugged into the “Bus OUT” output socket of the
Weidmüller DeviceNetTM SAI distributors.
Ideally, there should be no stub cables; Weidmüller modules
have two special connections for the fieldbus. The number of
subscribers is limited to 63.
Addressing
Any address from 1 to 63 is possible. The address setting of
the station can be set manually at the device or via the master.
Two coded rotary switches are located underneath the cap,
with separate adjustment of tens and units.
Bus line length, transmission rate
The maximum length of the bus line depends on the transmis-
sion rate (baud rate). The following table serves as a guide for
an optimum bus design:
Max. bus expansion in m Data rate in kbps
500 125
250 250
100 500
DeviceNet™
Pin Plug (x71) Socket (x72)
1 shield
2 Vplus
3 CAN-GND
4 CAN-H
5 CAN-L
Housing shield
13
DeviceNetTM
DeviceNetTM Universal
Ordering dataPlug-on type
16 digital inputs
16 digital inputs / 8 digital outputs
4 analogue inputs / 2 analogue outputs / 4 digital inputs
Information
Technical data bus system
Bus sharing unit Slave
Transmission rate Max. 500 kbps
Diagnostic display red
Fieldbus interface RS 485
Potential isolation yes
Station address rotary switch 1–63
bps rate automatic
Information
Technical dataGeneral data
Insulation material of housing PBT
Flammability class UL 94 V-0
Operation temperature 0 °C ... 55 °C
Storage temperature –25 °C ... 70 °C
Ingress protection class IP 67
Electrical data electronics-module
Operating voltage 24 V DC (20.4 … 28.8 V)
Max. current carrying capacity per output signal 0.5 A; 2.0 A
Output levels Short-circuit-protected
Total current. max. 8 A
Digital inputs TYPE 1 to EN 61131-2
Analogue outputs –10 … +10 V; 0 … +10 V; 0 … 20 mA; 4 … 20 mA
Analogue inputs –10 … +10 V; 0 … +10 V; 0 … 20 mA; 4 … 20 mA
Resolution 12 Bit
Accuracy < 0.2 %
UL certification in preparation UL certification in preparation
Type Qty. Order No.
SAI-AU M8 DN 16DI 1 1906730000
SAI-AU M8 DN 16DI/8DO 1 1906740000
Type Qty. Order No.
SAI-AU M12 DN 16DI 1 1906700000
SAI-AU M12 DN 16DI/8DO 1 1906710000
SAI-AU M12 DN AI/AO/DI 1 1906720000
AccessoriesPlug Type Qty. Order No.
Terminating resistor in M12 plug SAIEND CAN-M12 5P A-COD 1 1784760000
Metal plug, pin M12, 5-pole, A-coded shield SAIS-M-5/8S M12 5P A-COD 1 1784740000
Metal plug, socket M12, 5-pole, A-coded shield SAIB-M-5/8S M12 5P A-COD 1 1784750000
Accessories
Protective cap, M12, black SAI-SK-M12-UNI 20 2330260000
Marker, transparent ESG 8/13.5/43.3 SAI AU 5 1912130000
SAI-AU SAI-AU
M8 M12
Bus line length, transmission rate
The maximum length of the bus line
depends on the transmission rate (baud
rate). The following table serves as a
guide for an optimum bus design:
14
The CANopen system
CANopen
CANopen (M12 A-coded)
Pin Plug (x71) Socket (x72)
1 shield
2 not used
3 CAN-GND
4 CAN-H
5 CAN-L
Housing shield
Active
A CAN network is based on a server–
client principle with a serial bus connec-
ting network subscribers having equal
access status. The electrical connection
consists of a 2-wire line with or without
shielding depending on the application.
CANopen was defined as a uniform
protocol for networking the different
CANopen subscribers. The protocol
stipulates the significance of the data
for the corresponding device type (e.g.
I/O modules, drives, shaft encoders,
controls).
This means it is now easy for application
programmers to use all types of
CANopen-compatible components
irrespective of manufacturer.
CANopen subscribers in the same devi-
ce series organise their data in the same
way. The characteristics of these device
classes are summarised in “device
profiles”.
An object directory is defined in
CANopen nodes and describes all devi-
ce parameters. This is used not only for
device description but also as a data
access interface by other CANopen
devices.
Larger, non-time-critical data quantities
are transmitted using “service data
objects” (SDO). In addition, at least
two “process data objects” (PDO) are
available for transmitting process data.
Manufacturer-specific objects and other
functions are described in the manual.
Every CANopen module has a so-called
EDS file (Electronic Data Sheet) contai-
ning an exact description of the module.
All information about I/O and status data
required by a master, e.g. a PLC or IPC,
Bus expansion
Max. bus expansion Data rate in kbps
7000 m 10
3500 m 20
600 m 125
300 m 250
90 m 500
40 m 1000
are saved in this file and can be used
to integrate the module step by step into
the control program.
The EDS files are available for down-
loading on the Weidmüller website at
www.weidmueller.com.
Network structure
ISO 11898 prescribes a line structure for
the CANopen network. A line structure
has a terminating resistor of 120 at each
end.
The cable gland version of the
Weidmüller CANopen SAI distributors
have an internal switch for activating the
terminating resistor.
When utilising SAI-Active Universal
modules a bus terminator plug (Order
No.: 1784760000) is plugged into the
BUS-Out socket. Ideally, no spur lines
should be created; to that end, the
Weidmüller modules have been designed
with two connections for connecting the
fieldbus.
Addressing
Any address from 1 to 126 is possible
with CANopen. The address is set by
means of two coded rotary switches in
the module.
15
CANopen
CANopen Universal
Ordering dataPlug-on type
16 digital inputs
16 digital inputs / 8 digital outputs
4 analogue inputs / 2 analogue outputs / 4 digital inputs
Information
Technical data bus system
Bus sharing unit Slave
Transmission rate Max. 1 Mbps
Diagnostic display red
Fieldbus interface RS 485
Potential isolation yes
Station address rotary switch 1–125
bps rate automatic
Information
Technical dataGeneral data
Insulation material of housing PBT
Flammability class UL 94 V-0
Operation temperature 0 °C ... 55 °C
Storage temperature –25 °C ... 70 °C
Ingress protection class IP 67
Electrical data electronics-module
Operating voltage 24 V DC (20.4 … 28.8 V)
Max. current carrying capacity per output signal 0.5 A; 2.0 A
Output levels Short-circuit-protected
Total current. max. 8 A
Digital inputs TYPE 1 to EN 61131-2
Analogue outputs –10 … +10 V; 0 … +10 V; 0 … 20 mA; 4 … 20 mA
Analogue inputs –10 … +10 V; 0 … +10 V; 0 … 20 mA; 4 … 20 mA
Resolution 12 Bit
Accuracy < 0.2 %
UL certification in preparation UL certification in preparation
Type Qty. Order No.
SAI-AU M8 CAN 16DI 1 1906680000
SAI-AU M8 CAN 16DI/8DO 1 1906690000
Type Qty. Order No.
SAI-AU M12 CAN 16DI 1 1906650000
SAI-AU M12 CAN 16DI/8DO 1 1906660000
SAI-AU M12 CAN AI/AO/DI 1 1906670000
AccessoriesPlug Type Qty. Order No.
Terminating resistor in M12 plug SAIEND CAN-M12 5P A-COD 1 1784760000
Metal plug, pin M12, 5-pole, A-coded shield SAIS-M-5/8S M12 5P A-COD 1 1784740000
Metal plug, socket M12, 5-pole, A-coded shield SAIB-M-5/8S M12 5P A-COD 1 1784750000
Accessories
Protective cap, M12, black SAI-SK-M12-UNI 20 2330260000
Marker, transparent ESG 8/13.5/43.3 SAI AU 5 1912130000
SAI-AU SAI-AU
M8 M12
16
PROFINET
PROFINET
Principle
PROFINET is the open automation standard of the PROFIBUS
Users Organisation. The aim is to realise a consistent auto-
mation concept based on Industrial Ethernet that is indepen-
dent of manufacturers.
The PROFINET specification distinguishes between three dif-
ferent forms:
• PROFINET CBA (component-based automation) a superim-
posed networking of installation elements
• PROFINET IO for real-time communication with field devices
• PROFINET IRT for isochronous real-time communication,
e.g. with drives
The Weidmüller SAI modules comply with the PROFINET IO
standard and are approved by the PROFIBUS Users
Organisation. The customary IO view familiar to PROFIBUS-DP
users is employed, with cyclic transmission of the IO data of
field devices to the process image of the PLC.
PROFINET IO describes a device model that is based on the
key features of PROFIBUS-DP and comprises slots and chan-
nels. The characteristics of the field devices are described by
a GSD (General Station Description) on an XML basis.
Network structure
PROFINET installations are based on the specific requirements
for Ethernet networks in an industrial environment. They pro-
vide the device manufacturer with clear specifications for
device interfaces and the cabling required.
Like Standard Ethernet, PROFINET installations are also wired
with a star structure. The star structure is characterised by a
central signal distributor (switch) with individual connections
to all the network’s terminals. A line or tree structure can be
set up with the help of a 3-port switch in the device or in the
proximity of each device.
Weidmüller can supply products for the network infrastructure
– please refer to our Industrial Ethernet catalogue.
Addressing
Address assignment supports two standards:
Discovery and Basic Configuration protocol (DCP) and
Dynamic Host Configuration Protocol (DHCP).
• DCP enables assignment of IP parameters with manufac-
turer-specific configuration/programming tools or in pan-
system engineering.
• DHCP specifies the Ethernet standard for dynamic assign-
ment and management of IP addresses from a predefined
range.
Transmission rate
The transmission rate is 10 or 100 Mbps.
Weidmüller modules detect the transmission rate automatically
and set themselves accordingly.
PROFINET distinguishes between three categories for the
transmission of data:
• TCP, UDC and IP for non-time-critical data such as par-
ameter assignment and configuration; response time 100 ms
• Soft Real Time (SRT) for time-critical process data used in
factory automation; response time 10 ms
• Isochronous Real Time (IRT) for particularly demanding
applications, e.g. motion control; response time < 1 ms
category.
The maximum length of the bus cable is the same for both
transmission rates.
The following table can serve as a guide for bus installations
complying with the standard:
Max. bus extension (m) Data rate (Mbps)
100 10
100 100
17
EtherNet/IP
EtherNet/IP
Principle
EtherNet/IP (Ethernet Industrial Protocol) is an open standard
that was developed by Rockwell Automation and the Open
DeviceNet Vendor Association (ODVA) for industrial networks.
EtherNet/IP is based on the Ethernet TCP/IP standards and
the Common Industrial Protocol (CIP).
CIP an open standard that is implemented in ISO layer 7, and
is also used for ControlNet™ and DeviceNet™ installations.
This enables continuous communications between the field
level and the Internet. The protocol includes a control compo-
nent for cyclic, real-time-compatible I/O signal transmission
(implicit messaging) and an information component for the
configuration, diagnosis and management messages (explicit
messaging).
The I/O data uses the User Datagram Protocol/Internet
Protocol (UDP/IP) and the information data uses TCP/IP
protocols.
The IEEE802.3 standard is incremented on layers 1 and 2
(physical media and data link respectively).
Addressing
The Dynamic Host Configuration Protocol (DHCP) is used to
assign addresses to modules in EtherNet/IP networks.
Network structure
Like Standard Ethernet, EtherNet/IP installations are also wired
with a star structure. The star structure is characterised by a
central signal distributor (switch) with individual connections to
all the network’s terminals. A line or tree structure can be set
up with the help of a 3-port switch in the device or in the
proximity of each device.
Weidmüller can supply products for the network infrastructure
– please refer to our Industrial Ethernet catalogue.
Transmission rate
The transmission rate is 10 or 100 Mbps.
Weidmüller modules detect the transmission rate automatically
and set themselves accordingly.
The maximum length of the bus cable is the same for both
transmission rates.
The following table can serve as a guide for bus installations
complying with the standard:
Max. bus extension (m) Data rate (Mbps)
100 10
100 100
18
Modbus TCP
MODBUS TCP
Principle
Modbus TCP is a fieldbus system for automation technology
based on EtherNet TCP/IP. It has been accepted by the
Internet Engineering Task Force (IETF) as a draft RFC standard
and has been made available for all to use by Schneider
Automation. Modbus TCP is based on Modbus, a well-
established industrial application protocol. The Modbus object
models remain unchanged.
A connection is set up via TCP/IP by the server (e.g. I/O
device) being addressed via port number 502. Commands are
initiated by the client (Master) and executed by the server
(slave). The length of a Modbus telegram is max. 256 bytes.
Network structure
Like Standard Ethernet, Modbus TCP installations are also
wired with a star structure. The star structure is characterized
by a central signal distributor (switch) with individual connec-
tions to all the network’s terminals. A line or tree structure can
be set up with the help of a 3-port switch in the device or in
the proximity of each device.
Weidmüller can supply products for the network infrastructure
– please refer to our Industrial Ethernet catalogue.
Addressing
The addressing is carried out via a BOOTP (Internet Bootstrap
Protocol) inquiry via the client, using the Dynamic Host
Configuration Protocol (DHCP), or the user can set the IP
address with a software tool.
Bus extension/transmission rate
The transmission rate is 10 or 100 Mbps.
Weidmüller modules detect the transmission rate automatically
and set themselves accordingly.
The maximum length of the bus cable is the same for both
transmission rates.
The following table can serve as a guide for bus installations
complying with the standard:
Max. bus extension (m) Data rate (Mbps)
100 10
100 100
19
Active Universal
Active Universal
Ordering dataPlug-on type
16 digital inputs
16 digital inputs / 8 digital outputs
4 analogue inputs / 2 analogue outputs / 4 digital inputs
Information
Technical data bus system
Bus sharing unit Server
Transmission rate 10 / 100 Mbps
Diagnostic display red
Fieldbus interface IEEE 802.3
Potential isolation yes
Station address rotary switch 1-125
bps rate automatic
Information
Technical dataGeneral data
Insulation material of housing PBT
Flammability class UL 94 V-0
Operation temperature 0 °C ... 55 °C
Storage temperature -25 °C ... 70 °C
Ingress protection class IP 67
Electrical data electronics-module
Operating voltage 24 V DC (20,4…28.8 V)
Max. current carrying capacity per output signal 0.5 A;2.0 A
Output levels Short-circuit-protected
Total current. max. 8 A
Digital inputs TYPE 1 to EN 61131-2
Analogue outputs -10…+10 V;0…+10 V;0…20 mA;4…20 mA
Analogue inputs -10…+10 V;0…+10 V;0…20 mA;4…20 mA
Resolution 12 Bit
Accuracy < 0.2 %
Information UL certification in preparation
Voltage supply with standard M12 plug-in connectors (see chap. D)
Type Qty. Order No.
SAI-AU M8 IE 16DI 1 1906880000
SAI-AU M8 IE 16DI/8DO 1 1906890000
Type Qty. Order No.
SAI-AU M12 IE 16DI 1 1906850000
SAI-AU M12 IE 16DI/8DO 1 1906860000
SAI-AU M12 IE AI/AO/DI 1 1906870000
AccessoriesPlug Type Qty. Order No.
Metal plug Ethernet, socket M12, D-coded, straight SAISM-4/8S-M12-4P D-COD 1 1892120000
Metal plug Ethernet, pin M12, D-coded, straight SAIBM-4/8S-M12-4P D-COD 1 1892130000
Accessories
Protective cap, M12, black SAI-SK-M12-UNI 20 2330260000
Marker, transparent ESG 8/13.5/43.3 SAI AU 5 1912130000
SAI-AU SAI-AU
M8 M12
20
Accessories
Profibus cables with moulded plugs
Dimensions
L L
M12
M12
M12
M12
The following cables are available:
Pre-assembled cables with a connector at one end only require
suitable plugs and sockets to complete the cable assembly.
Ordering dataMoulded plugs and sockets
one end only
straight plug 1.5 m
3.0 m
5.0 m
10.0 m
straight socket 1.5 m
3.0 m
5.0 m
10.0 m
Connecting cables
straight plug to straight socket 0.3 m
1.5 m
3.0 m
5.0 m
10.0 m
Note
Technical dataCable
Conductor cross-section mm2
Strands mm2
Insulation
Filler strand mm2
Individual shielding (wire)
Total shielding (cable)
Wire colour
Sheathing
Mechanical properties
Permissible temperature °C
Storage temperature °C
Operating temperature °C
Electrical properties
Impedance Ohm
Note
2 x 0.33
42 x 0.1
PE; 2.6 – 0.2 dia
0.34 stranded wire
aluminium foil
C-shielding made from tinned 0.1 mm wires,
coverage approx. 85 %
red, green
PUR, violet (RAL 4008)
–25 ... 80
–5 ... 80
135 – 165 at f = 3 – 20 MHz
L in the drawing is the cable length
Type (Qty = 1) Order No.
SAIL-M12G-PB-1.5U 1873300150
SAIL-M12G-PB-3.0U 1873300300
SAIL-M12G-PB-5.0U 1873300500
SAIL-M12G-PB-10U 1873301000
SAIL-M12BG-PB-1.5U 1873320150
SAIL-M12BG-PB-3.0U 1873320300
SAIL-M12BG-PB-5.0U 1873320500
SAIL-M12BG-PB-10U 1873321000
SAIL-M12G-M12G-PB-0.3U 1873310030
SAIL-M12G-M12G-PB-1.5U 1873310150
SAIL-M12G-M12G-PB-3.0U 1873310300
SAIL-M12G-M12G-PB-5.0U 1873310500
SAIL-M12G-M12G-PB-10U 1873311000
Other versions on request
Wall bushing
Ordering data
Type Length Qty Order No.
SAI-WDF-5P M12 60 mm 60 mm 1 1819450000
SAI-WDF-5PB M12 60 mm 60 mm 1 1820690000
SAI-WDF-4PB M12 60 mm 60 mm 1 1820700000
SAI-WDF-4P M12 60 mm 60 mm 1 1820710000
21
Accessories
PROFIBUS-DP M12 plug-in connectors
Ordering dataPlug
4-pole, PG 7
4-pole, PG 9
5-pole, PG 9
5-pole, PG 9
8-pole, PG 9
Socket
4-pole, PG 7
4-pole, PG 9
5-pole, PG 9
5-pole, PG 9
8-pole, PG 9
Notes
Technical data
No. of Poles
Type of connection
Housing material
Connection thread
Cable connection diameter mm
Connection cross-section mm2
Rated current A
Rated voltage V
Temperature range °C
Class of protection
Contact surface
Notes
Plug / socket
5-pole straight
Type Qty Order No.
SAISM-5/8S M12 5P B-COD 1 1784790000
SAIBM-5/8S M12 5P B-COD 1 1784780000
Other versions on request
5
screw
CuZn
M12
6 ... 8
0.25 ... 0.75
4
125
–40 ... 85
IP67
CuSnZn
Dimensions
appr
ox. 6
2
M12x1
Ø 19.6
Ø 6–8 mmCable bushing
Ø 6–8 mmCable bushing
M12x1
Ø 19.6
appr
ox. 5
7
Plug / socket
4-pole straight
Type Qty Order No.
SAIS-4-IDC-M12 (PB) 1 1864730000
SAIB-4-IDC-M12 (PB) 1 1864740000
Other versions on request
4
IDC
CuZn
M12
7 ... 8.8
0.25 ... 0.75
4
32
–25 ... 85
IP67
tinned
Dimensions
M12x1
app
rox.
48.
8
O20.5
app
rox.
52.
2
M12x1
O20.5
22
Accessories
Protective caps for various distributors
Ordering data
Type Qty Order No.
SAI-SK-M8 50 1802760000
Protective cap M8 socket Dust cap for M12 plug
Ordering data
Type Qty Order No.
Dust cap for M12 plug (yellow) 50 1781520000
Protective cap M12 Universal socket
Ordering data
Type Qty Order No.
SAI-SK-M12-UNI 20 2330260000
Ordering data
Type Colour Order No.
TM sleeve TM 203/18 VO 1798480000
TM-I 18 NEUTRAL WS white 1718431044
TM-I 18 NEUTRAL GS yellow 1718431687
Ordering data
Type Colour Order No.
for SAI-Active Universal
ESG 8/13,5/43,3 SAI AU transparent 1912130000
HARAX® is a registered trademark of Harting KGaA.
The marker tags can be labelled quickly and reliably using Weidmüller’s PrintJet
marking system.
TM-I
Marking systemfor sensor cables
Markers in MultiCard format
Screwty® compatible, can also be operated by hand.
23
Screwty® for M8 / M12
Accessories
The perfect tool for all situations
Screwty® is the ideal, universal tool for tightening and releasing cable
glands on all common sensor and actuator cables. The Screwty® can
also reach those round plug connectors normally considered inaccessible!
No great force is required – simply turn the tool to tighten or release the
plug connector as required.
The Screwty® also fits the majority (more than 90%) of the line and
plug connectors of other suppliers and is therefore a unique tool useful
throughout the world. The Screwty® consists of a handle with a conven-
tional 1/4" fitting. This means it can be used for all sizes: for M12 and M8
round plug connectors, and the M12F and M8F types, also for plugs
and sockets on custom cables.
The Screwty® is suitable for the following round plug connectors:
Size M8 M8F M12 M12F
10 ±0.3 mm 11.9 ±0.3 mm 14.5 ±0.3 mm 19.8 ±0.3 mm
Thread M8x1 M8x1 M12x1 M12x1
An adjustable torque fitting is also available for the Screwty® – for
guaranteeing extra reliability during installation.
The torque can be infinitely adjusted between 0.5 and 1.7 Nm. This
accurate setting enables all round plug connectors to be tightened
precisely with a certain torque.
Weidmüller specifies the following torques for its round plug connectors:
Size M8 M8F M12 M12F
Torque 0.5 – 0.6 Nm 0.5 – 0.6 Nm 0.8 – 1.0 Nm 0.8 – 1.0 Nm
Thread M8x1 M8x1 M12x1 M12x1
The Screwty® an also be fitted with other blades to create a torque screw-
driver. You can find these blades in the “Tools” section of the main
catalogue.
The following Screwty® models are available:
Ordering data
Type Use Qty Order No.
Screwty® M12 moulded M12 lines 1 1900000000
Screwty® M8 moulded M8 lines 1 1900010000
Screwty® M12 F M12 plugs for custom assembly 1 1900020000
Screwty® M8 F M8 plugs for custom assembly 1 1900030000
Screwty® M12 KO or SD 1 1900100000
Screwty® M8 KO or SD 1 1900110000
Screwty® M12F KO or SD 1 1900120000
Screwty® M8F KO or SD 1 1900130000
WK-1/4" (Screwty®) 1 1862200000
1/4"-Handhold 1 4294820000
Screwty®-M12-DM* moulded M12 lines with torque requirement 1 1900001000
Screwty®-M8-DM* moulded M8 lines with torque requirement 1 1900011000
Screwty®-M12 F-DM* M12 plugs, custom assembly w. torque requirement 1 1900021000
Screwty®-M8 F-DM* M8 plugs, custom assembly with torque requirement1 1900031000
Screwty®-Set* 1 1910000000
Screwty®-Set-DM* 1 1920000000
Other sizes in preparation
*) Fittings
Type Contents
Screwty®-M12-DM 1 interchangeable blade, 1 torque handle, 1 setting aid fo Screwty®
torque, 1 Screwty® M12 fitting
Screwty®-M8-DM 1 interchangeable blade, 1 torque handle, 1 setting aid fo Screwty®
torque, 1 Screwty® M18 fitting
Screwty®-M12 F-DM 1 interchangeable blade, 1 torque handle, 1 setting aid fo Screwty®
torque, 1 Screwty® M12 F fitting
Screwty®-M8 F-DM 1 interchangeable blade, 1 torque handle, 1 setting aid fo Screwty®
torque, 1 Screwty® M18 F fitting
Screwty® Set 1 Screwty® standard handle and one M12, M8, M12 F, M8 F fittings
Screwty® Set-DM 1 interchangeable blade, 1 torque handle, 1 setting aid for Screwty®
torque, 1 each of Screwty® M12, M8, M12 F, M8 F fittings
Simply turn the ratchet to tighten
or loosen the cable gland.
Legend:
F for custom assemblies
DM torque
KO or SD ratchet only (attachment)
Screwty® screwdriver, 4 ratchets
Screwty® DM torque screwdriver, 4 ratchets, interchangeable blade
WK interchangeable blade
24
Sensor cables
Are you already a Weidmüller customer?
Why not buy your M12 or M8 cables from us as well?
Weidmüller has a wide range of M12 and M8 cables on offer.
And, as you would expect, Weidmüller quality also applies to
these articles.
Why take any risks?
In response to numerous customer requests, we have exten-
ded our portfolio to include:
• PVC cables
• PUR/PVC cables
• PUR halogen-free cables
… all that on top of fast delivery times and reasonable
conditions. Contact us and we will make you an offer. It costs
nothing to ask.
25
Sensor cables
Connecting lines
Many applications with sensors require suitable connecting
cables. The connecting cables are available in different designs.
The M12/M8 plug-in connectors are available in straight and
90° versions and also with LEDs.
• When plugged in, the M12 connecting cables comply with
class of protection IP68.
• The cable sheathing is black and made of polyurethane
(PUR or PVC).
• The connecting cables are supplied with two marking
sleeves.
Corresponding tags TM-I 18 for the marking sleeves can be
found in this chapter.
Sensor cables
Weidmüller can supply various cable lengths as indicated in the
following table:
Typical cable lengths are:
Order No. code
Practical solutions based on practical experience
The coded order number represents an easy way of ordering
the cables you want from this wide range of products. The
cable length required is added to the 6-digit number specified
by Weidmüller (see example). The order numbers on the
following pages show the extensive range of cable lengths
available.
Example:
Ordering data for a cable
SAIL-M12G M12G-5-x.xU = 945734xxxx.
The placeholder “x” is replaced by the cable length.
The following example is for a line 1.2 m long.
SAIL-M12G M12G-5-1.2U = 9457340120.
In the case of connecting cables with two plug-in connectors,
the male end is always specified first and the socket end
second.
• 1.5 m • 3.0 m • 5.0 m • 10.0 m
M12/M12
M12/M8
Example of designation
S A I L - M 1 2 G M 8 W S - 2 / 4 S 1 . 5 U M12
M8
G = straightW = 90°
for M8
S = ScrewR = Clipfor M12 not specified
3 poli
4 poli
5 poli
2/4
bridged
Cable length
1.5 m 3.0 m 5.0 m 10 m X m
Cable
Q = PUR-PURV = PVC-PVCU = PUR-PVC
- = no optionsL = LED (for W only, not 2/4)S = shielded
M12
M8
G = straightW = 90°
Pin Socket
M8/M8
26
Sensor cables with plug at one end only
Sensor/actuator cable pre-assembled with M8/M12
plug-in connector at one end
Machine designers frequently require individual line lengths.
Sensor cables with a connector fitted at one end only can
be easily adapted to the corresponding situation.
The cables are available in many different versions: straight,
90° and with all common pole numbers (3, 4 and 5). Plugs
and sockets can be assembled to suit individual customer
requirements for connecting cables.
The cable sheathing is of PUR (polyurethane) and is suitable for
use with cable carrier systems.
Plugs and cables are in neutral black.
Sensor cables
Weidmüller can supply various cable lengths as indicated in
the following table:
Typical cable lengths are:
Order No. code
Ordering data for a cable
SAIL-M12G M12G-5-x.xU = 945734xxxx.
The placeholder “x” is replaced by the cable length. The
following example is for a line 1.2 m long.
SAIL-M12G M12G-5-1.2U = 9457340120.
In the case of connecting cables with two plug-in connectors,
the male end is always specified first and the socket end
second.
Example of designation
• 1.5 m • 3.0 m • 5.0 m • 10.0 mM12 with plug or socket
at one end
M8 with plug or socket
at one end
M8 or M12 with LEDs
at one end
M8 or M12 shielded
at one end
S A I L - M 8 B G S - 2 / 4 S 1 . 5 U M12
M8
not specified = PinB = socket
G = straightW = 90°
for M8
S = ScrewR = Clipfor M12 not specified
3-poli
4-poli
5-poli
8-poli
12-poli
2/4
bridged
Cable length
1.5 m 3.0 m 5.0 m 10 m X m
Cable
Q = PUR-PURV = PVC-PVCU = PUR-PVC
- = no optionsL = LEDS = shielded
connector at one end only
Sensor cables
27
Valve connector
Valve connector with integral seal
This range of valve connectors are fitted with a transparent
housing, which provides the added advantage of allowing the
operating status indicators to be seen from all sides. An additio-
nal seal is not needed in this case as it is already integrated in
the housing. In addition, a lug has been included in the con-
struction to ensure that the protective hose fits securely. All
variants are equipped with supprossor circuitry.
Weidmüller’s delivery programme includes valve connectors of
the types A, B and C to DIN and industrial standards.
Protection to IP67 is fulfilled when plugged. Socket or pin
connectors with various cable exits and a variety of pole
numbers can also be obtained from Weidmüller.
Type A
Type C with protective sleeve
Valve plugtype A
Valve plugtype B
Contact gab 18 mm
Type VSA
Contact gab 11 mm
works standard
Type VSB
Contact gab 10 mm
DIN 43650 (ISO 6952)
Type VSBD
Contact gab 9.4 mm
works standard
Type VSC
Contact gab 8 mm
DIN 43650 (ISO 6952)
Type VSCD
1 2
18
1 211
1210
129.
4
128
Valve plugtype C
1
2
brown
LEDyellow
blue
PE
PE
green/yellow
28
Appendix
UAEUnited Arab EmiratesWeidmüller Middle-EastP.O. Box 62448DubaiPhone +971 4 3522215, 3523043Fax +971 4 [email protected]
ArgentinaCPI SABauness 26601431 Buenos AiresPhone +54 11 45238008Fax +54 11 [email protected]
AustriaWeidmüller Ges.m.b.H.Industriezentrum Nö SüdStraße 2, Objekt M22355 Wiener NeudorfPhone +43 2236 6708-0Fax +43 2236 [email protected]
AustraliaWeidmüller Pty. Ltd.43 Huntingwood DriveHuntingwood,NSW, 2148P.O.Box 6944BlacktownNSW, 2148Phone +61 2 9671-9999Fax +61 2 [email protected]
AzerbaijanWest Industries Ltd. Caspian Plaza, 5-th Floor 44 J. Jabbarly Str., Baku, Azerbaijan Phone +99412 499 15 15 Fax +99412 499 14 93 [email protected]
Bosnia-HerzegovinaBH ES Elektrosistem d.o.o.ul. J. Veselinovica 1878000 Banja LukaBosnaPhone +387 51 317500Fax +387 51 [email protected]
BelgiumWeidmüller Benelux B.V.Ambachtenlaan 11 A3001 HeverleePhone +32 16 395990 Fax +32 16 [email protected]
BulgariaWeid-Bul eOOdul. Nezabravka 33 A, bl. 315/3/101113 SofiaPhone +359 2 9632560Fax +359 2 [email protected]
BahrainKhayber Trading CompanyP.O. Box 1976 Manama, BahrainPhone +973 17720747 Fax +973 17720331 [email protected]
BrazilConexel Conexoes Elétricas Ltda.Rua Garcia Lorca, 176- V. Paulicéia, 09695-900, Sao Bernado do Campo - SP, BrasilPhone +55 11 43669600Fax +55 11 [email protected]
BelarusTECHNIKON Ltd.Oktyabrskaya Str. 16/5 Apt. 704 220030 Minsk Belarus Phone +375 17 2104626Fax +375 17 [email protected]
BY
BR
BH
BG
BE
BA
AZ
AU
AT
AR
AE CanadaW Interconnections Canada Inc.10 Spy Court, Markham, Ontario L3 R5 H6Phone +1 905 475-1507Fax +1 905 [email protected] www.weidmuller.ca
SwitzerlandWeidmüller Schweiz AGRundbuckstrasse 28212 Neuhausen am RheinfallPhone +41 52 6740707Fax +41 52 [email protected]
ChileFelipe Bahamondes S.A./ATS AGROServicios AgroindustrialesMaria Luisa Santander 0475ProvidenciaCasilla 3425SantiagoPhone +56 2 341-1271Fax +56 2 [email protected]
ChinaWeidmüller Interface InternationalTrading (Shanghai) Co., Ltd.12 F, Century Ba-Shi Building,No. 398 Huaihai Road (M)Shanghai 200020P.R. China Phone +86 21 63868188Fax +86 21 63867177www.cnweidmuller.com
ColombiaAutomatizacion Avanzada S. A.Carrera 97 No. 42 A-23 B3, Santafe de Bogotá Colombia.Phone +57 1 4132048 Fax +57 1 [email protected]
Costa RicaELVATRON S.A.400 Norte Banco Costa Rica, la Uruca, San José, Costa RicaPhone +506 2 961060 Fax +506 2 960328 [email protected]
Serbia and MontenegroES-YU ElektrosistemPariske komune 4111070 Novi Beograd SerbiaPhone +381 11 697212 Fax +381 11 693608 [email protected]
Czech RepublicWeidmüller s. r. o.Videnska ul. 34025242 Vestec u PrahyPhone +420 2 44001400Fax +420 2 [email protected]
GermanyWeidmüller GmbH & Co. KGOhmstraße 932758 DetmoldPhone +49 5231 1428-0Fax +49 5231 [email protected]
DenmarkKnud Wexøe A/SSkaettekaeret 11P.O. Box 1522840 HoltePhone +45 45465800Fax +45 45465801 [email protected]
EstoniaAlter Electric OÜTüri 6, 11313 Tallinn, EstoniaPhone +372 65 19 666Fax +372 65 [email protected]
EE
DK
DE
CZ
CS
CR
CO
CN
CL
CH
CA EgyptStandard Electric87, Mohamed Farid Street Heliopolis, Cairo, EgyptPhone +20 6 42 29 77/ 6 42 29 88Fax +20 6 42 29 [email protected]
SpainWeidmüller S. A.Narcis Monturiol 11-13Pol.Ind. Sudoeste08960 Sant Just DesvernBarcelonaPhone +34 93 4803386Fax +34 93 [email protected] www.weidmuller.es
FinlandJUHA-ELEKTRO OYKylvöpolku 6, P. O. Box 5700681 HelsinkiPhone +358 9 478411Fax +358 9 47841311
FranceWeidmüller EURL12, Chaussée Jules CésarB.P. 263 Osny95523 CERGY PONTOISE CedexPhone +33 1 34245500Fax +33 1 [email protected]
United KingdomWeidmuller Ltd.1 Abbey Wood RoadKings Hill, West MallingKent ME19 4YTPhone +44 1732 877000Fax +44 1732 [email protected]
GreeceElectrorama S.A.1 An. Martali Str.41335 LarissaPhone +30 2410 552533 Fax +30 2410 283463 [email protected]
Hong KongUnited Equity LimitedSuite B, 11/F International IndustrialCentre2-8 Kwei Tei Street, Fotan, ShatinHong KongPhone +852 26876739Fax +852 [email protected]
CroatiaElektro Partner d.o.o.Radnicka cesta 2210000 ZagrebPhone +385 1 6184793Fax +385 1 [email protected]
HungaryWeidmüller Kereskedelmi KftDombóvári út 13 1117 BudapestP. O. Box 221507 BudapestPhone +36 1 464-7888Fax +36 1 [email protected]
IndonesiaP. T. Nego ElectrindoKomplek Sentra Kramat, Blok A18Jl. Kramat Raya No. 7-9Jakarta 10450 IndonesiaPhone +62 21 3156218Fax +62 21 [email protected]
IrelandA.P. Haslam Ltd.14 Sunshine Ind. EstateCrumlin RoadDublin 12Phone +353 1 453-2522 Fax +353 1 [email protected]
IE
ID
HU
HR
HK
GR
GB
FR
FI
ES
EG IsraelA.U. Shay Ltd.Embar Street 23/25P.O.Box 10049Petach-Tikva 49222Phone +972 3 9233601Fax +972 3 [email protected]
IndiaWeidmüller Representative officeVijay Dattani# 156-4th cross, Prashant ExtensionWhitefieldBangalore - 560 066Phone +91 80 [email protected]
IranTAF Co.72, Iranshahr Av.Unit 5, 15816 TeheranPhone +98 21 8831-7851Fax +98 21 [email protected]
IcelandSamey Automation CenterLyngas 13, 210 Garoabaer,IcelandPhone +354 510 5200Fax +354 510 [email protected]
ItalyWeidmüller S.r.l.Via Albert Einstein 420092 Cinisello BalsamoMilanoPhone +39 02 660681Fax +39 02 [email protected]
JordanHorizons Engineering P.O. Box 330607 ZC 11133 Amman Phone +962 64882114 Fax +962 4882115 [email protected]
JapanNihon Weidmüller Co. Ltd. Asahi Seimei Bldg. 11F1-14-1 Fuchucho Fuchu-shiTokyo 183-0055 JapanPhone +81 42 330-7891 Fax +81 42 330-7895www.weidmuller.co.jp
South KoreaWeidmüller Co., Ltd.2 floor Wooam B/D 46-27Samsung2-Dong, Kangnam-KuSeoul Korea, Zip: 135-868Phone +82 2 5160003 Fax +82 2 [email protected]
KuwaitNOURI Industrial Establishment Co.P.O.Box 2829, Safat 13029 KuwaitPhone +965 4333355Fax +965 [email protected]
KazakhstanSEA STAR58-A, Office 609, Abilay Khan Aven.Almaty, 50004KazakhstanPhone +7 3272 733307Fax +7 3272 [email protected]
KazakhstanElectric Light LLP84, Auezov StreetOffice 310480057 AlmatyKazakhstanPhone +7 3272 421709Fax +7 3272 [email protected]
KZ
KZ
KW
KR
JP
JO
IT
IS
IR
IN
IL
Worldwide activities
29
Appendix
LebanonProgress Engineering & TradingEnterprisesP.O. Box 11-1111Pharaon Bldg., Opp Electr. du LibanChafaca Str., Al NahrBeirut - LebanonPhone +961 1 444664Fax +961 1 [email protected]
LithuaniaELEKTROS IRANGATinklu g.29a, 5319 Panevezys,LithuaniaPhone +370 45582828Fax +370 [email protected]
LuxembourgPlease contact Weidmüller Belgium, Heverlee
LatviaElektrosistemas SIAK. Ulmana gatve 140LV-1029 RigaLatviaPhone +371 7870557Fax +371 [email protected] www.profs.lv
MacedoniaES MK Elektrosistem d.o.o.Ul. Bulevar III makedonske brigade bb91000 SkopljeMacedoniaPhone +389 91 460295Fax +389 91 [email protected]
MexicoW Interconnections, S.A. de C.VAv. Ingenieros Civiles No. 204-B, Conjunto Industrial Chachapa72990 Chachapa, Puebla MexicoPhone +52 222 2866247/48/49Fax +52 222 [email protected]
MalaysiaConnect Plus Technology Sdn Bhd9, Jalan PJS 11/24,Bandar Sunway,46150 Petaling Jaya,Selangor Darul Ehsan,MalaysiaPhone +60 3 5633 7363Fax +60 3 5633 [email protected]
NetherlandsWeidmüller Benelux B.V.Franciscusweg 2211216 SE HilversumPostbus 15051200 BM HilversumPhone +31 35 6261261Fax +31 35 [email protected]
NorwaySiv. Ing. J. F. Knudtzen A/SBillingstadsletta 971396 Billingstad, P.O. Box 1601378 NesbruPhone +47 66 983350Fax +47 66 [email protected]
New ZealandCuthbert S. Steward Limited27 Te Puni StreetPOB 38496 PetonePetone, WellingtonPhone +64 4 5686156Fax +64 4 5686056
Oman DAN INTERNATIONAL LLC. PO.BOX 2901 111 Seeb Oman Phone +968 503 677 Fax +968 503 755 [email protected]
OM
NZ
NO
NL
MY
MX
MK
LV
LU
LT
LB PeruTECNOLOGÍA ELÉCTRICAY SOLUCIONES S.A.C.Calle Huandoy 501, Lima 32 – PerúPhone +51 1 5620004Fax +51 1 [email protected]
PhilippinesEl Criscent CorporationB-41 L-10, Villa Palao,Banlic, Calamba City Laguna 4027,PhilippinesPhone +63 49 3456329Fax +63 49 [email protected]
PhilippinesEnclosure Systems Specialists IncG/F, GE Building2291 Don Chino Roces Ava ExtMakati City 1231,PhilippinesPhone +63 2 813 8580Fax +63 2 813 [email protected]
PolandWeidmüller Sp. z o.o.ul. Goledzinowska 1003-302 WarszawaPolandPhone +48 22 5100940Fax +48 22 [email protected]
PortugalWeidmüller - Sistemas de Interface, S. A.Estrada Outeiro Polima, Lote B, N° B2, Escritório 2 - Abóboda2785-518 Sao Domingos de RanaLisboaPhone +351 21 4459190Fax +351 21 [email protected] www.weidmuller.pt
ParaguayRewo Paraguay S.A.Sucre 2590 esq Emeterio MirandaAsunciónParaguayPhone +595 21 60 60 13Fax +595 21 60 60 [email protected]
QatarDoha Motors (Technical Division) Post Box No. 145 Al Wakrath Road Doha-Qatar Phone +974 465 1441 Fax +974 465 4579 [email protected]
Romania Rominterface Impex SRL Str. Gh. Dem Teodorescu 30A 030916 Bukarest - sector 3 Phone +40 21 3220230Fax +40 21 [email protected]
RussiaWeidmüller Representative Office Shabolovka street 2119049 Russia, MoskauPhone +7 495 771-6940Fax +7 495 [email protected]
Saudi ArabiaAl Abdulkarim Trading P.O. Box 5777, Dammam 31432 Saudi ArabiaPhone +966 3 833-7110Fax +966 3 [email protected]
SA
RU
RO
QA
PY
PT
PL
PH
PH
PE Saudi ArabiaSaudi Electric Supply Co.P.O. Box 3298, Al Khobar 31952 Saudi ArabiaPhone +966 3 882-9546227Fax +966 3 [email protected]
SwedenWeidmüller ABStockholm, Arenavägen 39, 12177 JohanneshovP.O. Box 1012012128 Stockholm-GlobenPhone +46 771 43 00 44Fax +46 8 [email protected]
SingaporeWeidmüller Pte. Ltd.629 Aljunied Road, #05-05Cititech Industrial BuildingSingapore 389838Phone +65 6841 5311Fax +65 6841 [email protected]
SloveniaELEKTROSPOJI d.o.o.Stegne 251000 LjubljanaPhone +38 6 15113810 Fax +38 6 [email protected]
SlovakiaElektris s.r.o.Racianska 188SK 83153 Bratislava, Slovakia Phone +421 2 49200113Fax +421 2 [email protected]
Syria Hovaguimian Bros. P.O. Box 5093 Damascus Syria Phone +963 11-221 84 05 Fax +96311-224 48 69 [email protected]
ThailandPisanu Engineering Co., Ltd 800/2 Asoke Dindaeng Road, Dindaeng, Bangkok 10400ThailandPhone +66 2 2459113 Fax +66 2 [email protected]
TurkeyWeidmüller Elektronik Ticaret Ltd. Sti.Kavacik Mah. Mihrabad Cad. 143/134810 Beykoz –
.Istanbul / Turkey
Phone +90 216 5371070 (Pbx)Fax +90 216 [email protected]
TaiwanFittatek Co., Ltd.12 F No. 185 Fu-Kuo Road, Tso Ying Dist, Kaohsiung, TaiwanPhone +886 7556-0858 Fax +886 [email protected]
TaiwanEucan Enterprise Ltd.No. 145 He Ping 2nd RdKaohsiung, TaiwanPhone +886 7 715 6610Fax +886 7 715 [email protected]
UkraineTEKO InterfacePer.Industrialny 203056 - KievPhone +380 04463 57760Fax +380 04463 [email protected]
UA
TW
TW
TR
TH
SY
SK
SI
SG
SE
SA USAW-Interconnections, Inc.821 Southlake Boulevard,Richmond, VA 23236Phone +1 804 7942877Fax +1 804 [email protected]
Uruguay Rewo Uruguay S.A. AV. Bolivia 2001 Esq Rocafuerte Carrasco Montevideo Phone +598 260 4 8439 Fax +598 260 4 8439 [email protected]
VenezuelaSomerinca C. A.Edificio Esteban Piso 2Calle Vargas Bolleita Notre Caracas 1070 AVenezuelaPhone +58 212 2352748Fax +58 212 [email protected]
VietnamNew Sky Co., Ltd 206 Nguyen Thai Binh Str., Ward 12., Tan Binh Dist.,Ho Chin Minh CityVietnam Phone +848 811 6768Fax +848 811 [email protected]
YemenPlease contact Weidmüller Middle-East United Arab Emirates
South AfricaRAD Interface Pty. Ltd.5 Bundo RoadSebenza ExtensionEdenvale 1609P.O.Box 193Edenvale 1610Phone +27 11 452-1930Fax +27 11 [email protected]
Other countriesWeidmüller Interface GmbH & Co. KGP.O. Box 303032720 DetmoldKlingenbergstraße 1632758 DetmoldPhone +49 5231 14-0Fax +49 5231 14-20 [email protected]
DE
ZA
YE
VN
VE
UY
US
DE Group companies
DE Agency abroad
DE Without own Agency
30
Appendix
We cannot guarantee that there are no mistakes in thepublications or software provided by us to the customer for thepurpose of making orders. We try our best to quickly correcterrors in our printed media. For this purpose we list corrections,which have been identified after publishing printed media, on ourweb site at www.weidmueller.com. For convenience we list thesecorrections against product catalogue number and/or pagenumber. This Internet-database is part of our catalogue.
All orders are based on our general terms of delivery, which canbe reviewed on the websites of our group companies where youplace your order. On demand we can also send the general termsof delivery to you.
Order number:
5654350000/04/2006/DMMD
www.weidmueller.com
ArgentinaAustraliaAustriaAzerbaijan BahrainBelarusBelgiumBosnia-HerzegovinaBrazilBulgariaCanadaChileChinaColombiaCosta RicaCroatiaCzech RepublicDenmarkEgyptEstoniaFinlandFranceGermanyGreeceHong KongHungaryIcelandIndiaIndonesiaIran
IrelandIsraelItalyJapanJordanKazakhstanKuwaitLatviaLebanonLithuaniaLuxembourgMacedoniaMalaysiaMexicoNetherlandsNew ZealandNorwayOmanParaguayPeruPhilippinesPolandPortugalQatarRomaniaRussiaSaudi ArabiaSerbia/MontenegroSingaporeSlovakia
SloveniaSouth AfricaSouth KoreaSpainSwedenSwitzerlandSyriaTaiwanThailandTurkeyUAEUkraineUnited KingdomUruguay USAVenezuelaVietnamYemen
Weidmüller is the leading manufacturer of componentsfor electrical connection technology. The Weidmüller product portfolio ranges from terminal blocks, PCB connectors and terminals, protected components, Industrial Ethernet components and relay sockets to power supply and overvoltage protection modules suitable for all applications. Electrical installation andmarking material, basic I/O components and a variety oftools round off the range. As an OEM supplier, the company sets global standards in the field of electricalconnection technology.