Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

54
CM 321 - Mechanical Lessons Learned Top Mistakes to Avoid when Improving your Building’s Water Efficiency Troy Aichele Aichele and Associates, LLC October 7, 2010

description

 

Transcript of Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

Page 1: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Lessons Learned Top Mistakes to Avoid when Improving your

Building’s Water Efficiency

Troy Aichele

Aichele and Associates, LLC

October 7, 2010

Page 2: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Aichele

+ IKE

LEE

Page 3: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 4: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 5: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Plunging into Plumbing – Specialty Systems Instructors: Troy Aichele

Page 6: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 7: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 8: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Objectives

1. Audits

2. Installation

3. The Human

Factor

Page 9: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Troy’s Toilet Trivia

In the United States, when is the toilet flushed

more often than any other time of the year?

Page 10: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Objectives

1. Audits

2. Installation

3. The Human

Factor

Page 11: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Assemble Data

Historical Use

Cost Data /

Utility Rates

Building Use and

Occupancy

Page 12: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Compare Benchmarks Water Use / SF / Year Comparisons

0

20

40

60

80

100

120

0 500,000 1,000,000 1,500,000 2,000,000

Gallo

ns

Hospital Size (Square Feet)

Page 13: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 14: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 15: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Sensor Activated Water Closets

Page 16: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Waterless

Urinals

Page 17: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

74

Find Existing Leaks

Page 18: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Be thorough

Page 19: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 20: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 21: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 22: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Actual Fixture Counts not matching

Audit Count

Page 23: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 24: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Troy’s Toilet Trivia

Which toilet cubicle in a public restroom is

usually the cleanest?

Page 25: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Over or Under Estimating Use Rates

Water Closet – 3 / Day (Women)

– 1 / Day (Men)*

Urinal – 2 / Day (Men)

Faucets – 1 Minute / Person / Day

Shower Use – 8 Minutes / Day

*3 / Day if no urinals

Page 26: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Over or Under Estimating Use Rates

Page 27: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Measuring with Bucket and

Stopwatch

Measure twice

and average

Measure 10%

of similar

devices

throughout

facility

Page 28: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Objectives

1. Audits

2. Installation

3. The Human

Factor

Page 29: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Lowering GPF without changing bowl

Page 30: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Fixture Footprints

are not all the same

Page 31: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

System Shut-downs vs. Freezing

Page 32: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Beta-Testing

Page 33: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Problematic Existing Conditions

Page 34: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Aerators vs. Flow Control

Page 35: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 36: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Objectives

1. Audits

2. Installation

3. The Human

Factor

Page 37: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Straying from Water Audit

Recommendations

Page 38: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Low Water Flow Concerns:

Maintenance Problems

Page 39: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Low Water Flow

Concerns:

User Negative

Feedback

Page 40: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Putting Water Efficiency

Ahead of User or Building needs

Page 41: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Troy’s Toilet Trivia

What percentage of Americans feel better

about themselves after flushing the toilet?

Page 42: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Waiting for the perfect time

Page 43: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Irrigation (Xeriscaping)

Page 44: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Think you’re not eligible

for rebates ?

Page 45: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Utility Rate Trends

$-

$1.00

$2.00

$3.00

$4.00

$5.00

$6.00

$7.00

$8.00

$9.00

2002 2003 2004 2005 2006 2007 2008 2009

Year

PeakWater$/CCFSewer$/CCF

10% 10 %

Utility Rate Trends…

Waste

Water

Page 46: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 47: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Follow-up Audits /

Stop looking for new products

Page 48: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Boiler Stack Economizer

Condensate Recovery

Cost: $1,090

Water / Sewer Savings: 720 GPD

Return on Investment: 5 Months

77

Page 49: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Prioritize Work via ROI Durations

Page 50: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

1. Audits

2. Installation

3. The Human

Factor

Objectives

Page 51: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 52: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

Page 53: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical

BONUS ROUND !!!

What day is World Plumbing Day?

Page 54: Watersmart innovations 2010 top mistakes to avoid when improving your building's water efficiency

CM 321 - Mechanical