® VT VOLTAGE TRANSFORMER 11kV / 22kV / 33kV PRODUCT GUIDE

Transcript of VT - NOJA Power Voltage... · 2019. 11. 6. · NOJA Power Switchgear applies a policy of ongoing...

  • ®

    VTVOLTAGE TRANSFORMER 11kV / 22kV / 33kV

    PRODUCT GUIDE

  • Introduction

    Voltage Transformer VT11/220-04

    Voltage Transformer VT22/220-03

    Voltage Transformer VT33/220-03

    1. Product Guide Voltage Transformer 11kV 22kV 33kV

  • Introduction 1.2.

    VT Mounting Diagram:

    Product Guide Voltage Transformer 11kV 22kV 33kV

    Model/Type reference VT11/220-04 VT22/220-03 VT33/220-03

    Temperature Rise Test: Allowed Temerature rise: 60K

    Primary rated voltage: 13.2kV (1.2)Secondary winding rated burden 100VATemperature rise of each windings:(AB: 6.6K) : (ab:16:4K) - 29.5°C

    Primary rated voltage: 11kVSecondary winding rated burden 250VA(AB: 15.5K) : (ab:26:3K) - 30.1°C

    Allowed Temerature rise: 75K

    Primary rated voltage: 28.6kV (1.3)Secondary winding rated burden 200VATemperature rise of each windings:(AB: 6.8K) : (ab3:7.4K) - 30.2°C

    Primary rated voltage: 33kV (1.5) (8hrs from 28.6kV)Secondary winding rated burden 200VA(AB: 14.7K) : (ab3:15:3K) - 31.6°C

    Primary rated voltage: 11kVSecondary winding rated burden 500VA(AB: 11.8K) : (ab3:12.0K) - 30.8°C

    Allowed Temerature rise: 65K

    Primary rated voltage: 36.3kV (1.1)Secondary winding rated burden 240VA(AB:15K) : (ab:15K) - 20.1°Cmetal structure (12K)

    Short Circuit withstand capability test : ab:255.1V, current 28.66A, duration:0.979s,

    ab3: 239.4V, current 26.87A,duration O,954 s,

    33kV, duration: 1s

    Lightning Impulse Test: 75kV/1.2/50usImpulse 15 positive, 15 negative

    125kV/1.2/50usImpulse 15 positive, 15 negative

    200kV/1.2/50usImpulse 15 positive, 15 negative

    Determination of errors Accuracy class: 5M, Rated Burden 100VA, Power factor: 0.8

    Accuracy class: 5M, Rated Burden 200VA, Power factor: 0.8

    Accuracy class: 5M, Rated Burden 200VA, Power factor: 0.8

    Artificial pollution test: 62700Cm20.13mg/cm21,O mg/Cm2NaC1, kieselguhr, Distilled water, Dextrin29~30 °C, 2.8X4.2X2.8m3, 22kV, 15min, 3times

    62700Cm20.13mg/cm21,O mg/Cm2NaC1, kieselguhr, Distilled water, Dextrin29 °C, 2.8 X 4.2 X 2.8m3, 22kV, 15min, 3times

    _

    PD Test: 24.0kV, A:1.5pC, B:1.5pC 28.0kV, A:5.9pC, B:6.2pC 55.8kV, A:50pC, B:50pC

    OSM Control Cable

    VT Output Cable

    OSM Control Cable

    Unbroken OSM Earth to Ground Conductor

    RC Controller

    Bond VT to OSM Earth

    Bond Controller OSM Earth

    VT (Phase to Phase)

    Supply Load

    OSM Control Cable

    VT Output Cable

    OSM Control Cable

    Unbroken OSM Earth to Ground Conductor

    RC Controller

    Bond VT to OSM Earth

    Bond Controller OSM Earth

    VT (Phase to Phase)

    Supply Load

    Type Test Summary:(IEC 60044-2 Instrument transformers - Inductive voltage transformers)

  • ®

    Specification:

    Mode|/Type reference VT11/220-04 VT22/220-03 VT33/220-03

    Rated voltage 11kV 22kV 33kV

    Rated frequency: 50/60 Hz 50/60 Hz 50/60 Hz

    Insulation level 12/42/75kV 24/50/125kV 36/70/170kV

    Limit output 250VA 500VA 500VA

    Secondary voltage 220V 220V 220V

    Ratio - 100:1 150:1

    Class 5M 5M 5M

    Burden 100VA 200VA 200VA

    Burden power factor COSΦ =0.8 (lagging) COSΦ =0.8 (lagging) COSΦ =0.8 (lagging)

    Short circuit withstand capability test 11kV 1s 22kV 1s 33kV 1s

    Phase to phase 11kV/220V and 11kV/110V

    22kV/220V and 22kV/110V 33kV/220V and 33kV/110V

    Power frequency withstand voltage

    Primary to Secondary & Ground 42kV 60s 50kV 60s 70kV 60s

    Secondary to Ground 3kV 60s 3kV 60s 2.5kV 60s

    Environment temp -20°C to 55°C -20°C to +55°C -20°C to +55°C

    Distributor

    NOJA POWER EUROPE SALES OFFICE

    NOJA Power Switchgear Pty Ltd

    Sebastianstrasse 38, 53115

    Poppesldorf, Bonn, Germany

    Phone: +49 (0) 228 8236 9408

    Email: [email protected]

    Web: www.nojapower.eu

    NOJA POWER AUSTRALIACORPORATE OFFICE & FACTORY

    NOJA Power Switchgear Pty Ltd

    16 Archimedes Place, Murarrie

    Brisbane Qld 4172

    Australia

    Phone: +61 (7) 3907 8777

    Fax: +61 (7) 3399 6777

    Email: [email protected]

    Web: www.nojapower.com.au

    NOJA POWER UKSALES OFFICE

    NOJA Power Limited

    Hyde Park House, Cartwright Street

    Hyde, Cheshire SK14 4EH

    United Kingdom

    Phone: +44 (0) 7805 352 502

    Email: [email protected]

    Web: www.nojapower.co.uk

    NOJA POWER BRAZILOFFICE & FACTORY

    NOJA Power do Brasil Ltda

    Avenida Pierre Simon de Laplace,

    965A Techno Park – Campinas – SP

    Brasil

    Phone: +55 (19) 3283 0041

    Fax: +55 (19) 3283 0041

    Email: [email protected]

    Web: www.nojapower.com.br

    NOJA POWER USASALES OFFICE

    NOJA Power, LLC

    Office: 333 SE 2nd Ave.

    Suite 2053, Miami, FL 33131

    United States of America

    Phone: +1.484-515-4880

    Email: [email protected]

    Web: www.nojapower.com

    NOJA Power® and OSM® are registered trademarks of NOJA Power Switchgear Pty Ltd. This document is copyright and is intended for users and distributors of NOJA Power Switchgear product. It contains information that is the intellectual property of NOJA Power Switchgear and the document, or any part thereof, should not be copied or reproduced in any form without written permission from NOJA Power Switchgear. NOJA Power® and OSM® are registered trademarks of NOJA Power Switchgear and should not be reproduced or used in any way without written authorization.NOJA Power Switchgear applies a policy of ongoing development and reserves the right to change product without notice. NOJA Power Switchgear does not accept any responsibility for loss or damage incurred as a result of acting or refraining from action based on information in this User Manual.

    NOJA-5004-02

    Scan to view NOJA Power website