VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

download VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

of 19

Transcript of VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    1/19

    A system with the high capacity needed to suit large-sized buildings

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    2/19

    V R VV R VV R VV R V

    VVVVariableariableariableariable RRRRefrigerantefrigerantefrigerantefrigerant VVVVolumeolumeolumeolume

    REGISTERED TRADEMARKREGISTERED TRADEMARKREGISTERED TRADEMARKREGISTERED TRADEMARK

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    3/19

    System Operation

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    4/19

    13A S/S/O 13A S/S/O 13A S/S/O 13A S/S/O

    TPN

    ISOLATOR

    Power Supply Configuration

    Single Phase power supply

    3 ph

    power Supply

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    5/19

    Individual Remote Controller,

    Wired & Wireless Options

    = up to 500 m length

    Controls Configuration

    INDIVIDUAL

    up to 500 m

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    6/19

    4. Intelligent Control System4. Intelligent Control System4. Intelligent Control System4. Intelligent Control SystemLCD REMOTE CONTROLLER(WIRED & WIRELESS)

    LCD screen

    Auto Swing Mechanism Air Flow

    Temperature Setting

    ON/OFF Timer

    Filter Sign

    80 Malfunction CodeDisplay

    Group Control Display

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    7/19

    INV INV INVSTD

    STD

    STD

    1 2 3

    Duty Cycling of Compressors

    Operating period of inverter

    compressor in Unit 1 issignificantly longer thancompressors in units 2 & 3.

    Inverter Compressor inUnit 1 has shorter life.

    Cycle start-upsequence by

    running time.

    Equalises

    compressorrunning time.

    Extended life of

    Inverter comp.

    Conventional SystemAlways startsInverter Compressor

    in unit 1 first. 1 2 3

    3 1 2

    2 3 1

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    8/19

    Dependable and comfortable

    Because the VRV III units are rotated within the

    system at least once every eight hours,averaging out the running time of each outdoor unit.

    This system extends the life of the system as a whole.

    Auto-rotation system

    extends life ofequipment

    With VRV III

    When every unit

    getsa chance to rest,

    none of them getsworn too quickly.

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    9/19

    Back-up Function - Single

    INV

    Compressorbreaks down

    BrokenAlarm isindicated

    STOP

    STOP

    Back-up byfield setting R

    UN

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    10/19

    INV

    INV

    Running

    INV

    Back-up Function - Multiple

    Even though VRV compressor failure rate is extremely low,the back-up function will give further peace of mind.

    Alarm isindicatedon the RC

    Back-up by fieldsetting

    INV

    IN

    V

    INV

    Continue runningStop

    The brokencompressor

    can berepairedwhile theremaining

    units are stilloperating.

    (Only appliesto multiple

    units)

    Compressorbreaks down Broken

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    11/19

    Brief Trouble-shooting

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    12/19

    Self-diagnosis Function- to Quickly Cope with Errors

    Correct display of errors amounting to74 items in the system

    Error code

    display Run lamp

    Unit No.

    Inspection display

    Errors related with indoor unit: 14

    Errors related with outdoor unit: 32

    Errors related with control/wiring: 16

    Central Control4

    HRV8

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    13/19

    Operation lampIndoor Unit No.

    Error CodeInspection

    Display

    Troubleshooting by Remote Controller

    Self-diagnosis by Wired Remote Controller

    Troubleshooting by Remote Controller

    Self-diagnosis by Wired Remote Controller

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    14/19

    Ref: Si38-304; pg174

    Overview of Malfunction CodesOverview of Malfunction Codes

    System still operate during the indication of error code

    Malfunction

    code

    Operation

    Lamp

    Inspection

    Display

    Unit

    No.

    Malfunction Content Page

    Referred

    Indooru

    nit

    A0 Error of external protection device 178

    A1 PCB or E2PROM defect 179

    A3 Malfunction of drain level sys. (33H) 180

    A6 Fan motor(MF) lock, overload 182

    A7 Malfunction of swing flap motor(MA) 183

    A9 Malfunction of EXV (20E) 185

    AF Drain level above limit 187

    AH Malfunction of air filter maintenance -

    AJ Malfunction of capacity setting 188

    C4Malfunction of thermistor (R2T) for heat

    exchanger189

    C5 Malfunction of thermistor (R3T) for gaspipe

    190

    C9Malfunction of thermistor (R1T) for air

    inlet191

    CJ Malfunction of thermostat sensor in RC 192

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    15/19

    Ref: Si38-304; pg174

    System still operate during the indication of error code

    Malfunction

    code

    Operation

    Lamp

    Inspection

    Display

    Unit

    No.

    Malfunction Content Page

    Referred

    Outdooru

    nit

    E1 PCB defect 193

    E3 Actuation of HP switch 194

    E4 Actuation of LP switch 195

    E5 Compressor motor lock 196

    E6 STD compressor lock or over current 197

    E7 Malfunction of outdoor unit fan motor 198

    E9 Malfunction of EXV (Y1E ~ 3E) 200

    F3 Abnormal discharge pipe temp. 202

    F6 Refrigerant overcharge 203

    H3 Malfunction of HP switch -

    H4 Actuation of LP switch -

    H7 Abnormal outdoor fan motor signal 204

    H9Malfunction of outdoor air thermistor

    (R1T)205

    Overview of Malfunction CodesOverview of Malfunction Codes

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    16/19

    Ref: Si38-304; pg174

    System still operate during the indication of error code

    Malfunction

    code

    Operation

    Lamp

    Inspection

    Display

    Unit

    No.

    Malfunction Content Page

    Referred

    Outd

    oorunit

    J2 Current sensor malfunction 206

    J3Malfunction of discharge pipe thermistor

    (R31 ~ 33T)207

    J5Malfunction of suction pipe thermistor

    (R2T)208

    J6Malfunction of heat exchanger thermistor

    (R4T)209

    J7 Malfunction of header thermistor -

    J8Malfunction of oil equalizing pipe

    thermistor (R7T)-

    J9Malfunction of receiver gas pipe

    thermistor (R5T)210

    JA Malfunction of discharge pipe pressuresensor

    211

    JCMalfunction of suction pipe pressure

    sensor212

    Overview of Malfunction CodesOverview of Malfunction Codes

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    17/19

    Ref: Si38-304; pg174 & 17

    System still operate during the indication of error code

    Malfunction

    code

    Operation

    Lamp

    Inspection

    Display

    Unit

    No.

    Malfunction Content Page

    Referred

    Inverterunit

    L0 Inverter system error -

    L4 Malfunction of INV radiating fin temp rise 213

    L5 INV comp motor grounding / short circuit 214

    L6 Comp motor coil grounding / short circuit -

    L8 INV current abnormal 215

    L9 INV startup error 216

    LA Malfunction of power unit -

    LCMalfunction of transmission btw INV &

    control PCB217

    P1 INV over-ripple protection 219

    P4Malfunction of INV radiating fin temp rise

    sensor220

    Overview of Malfunction CodesOverview of Malfunction Codes

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    18/19

    Ref: Si38-304; pg17

    System still operate during the indication of error code

    Malfunction

    code

    Operation

    Lamp

    Inspection

    Display

    Unit

    No.

    Malfunction Content Page

    Referred

    Sy

    stem

    U0LP drop due to refrigerant shortage or

    EXV failure221

    U1 Reverse phase / open phase 222

    U2Power supply insufficient or

    instantaneous failure223

    U3 Check operation not conducted 225

    U4Malfunction of transmission btw indoor &

    outdoor unit226

    U5Malfunction of transmission btw RC &

    indoor unit228

    U5Failure of RC PCB or setting during

    control by RC228

    U7Malfunction of transmission btw outdoor

    unit229

    U8Malfunction of transmission btw master &

    slave RC

    231

    U9Malfunction of transmission btw indoor &

    outdoor unit in the same sys.232

    UA Excessive no. of indoor units 234

    Overview of Malfunction CodesOverview of Malfunction Codes

  • 8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting

    19/19

    Ref: Si38-304; pg17

    System still operate during the indication of error code

    Malfunction

    code

    Operation

    Lamp

    Inspection

    Display

    Unit

    No.

    Malfunction Content Page

    Referred

    S

    ystem

    UC Address duplication of CRC 235

    UEMalfunction of transmission btw CRC &

    indoor unit

    236, 240,

    246

    UFRefrigerant system not set, incompatible

    wiring / piping238

    UHMalfunction of system ,refrigerant system

    address undefined

    239

    CRC&

    Sched

    uleTimer

    M1 Or PCB defect 241, 248

    M8 OrMalfunction of transmission btw optional

    controllers for centralize control242, 249

    MA OrImproper combination of optionalcontrollers for centralized control

    243, 250

    MC Or Address duplication, improper setting 245, 252

    Overview of Malfunction CodesOverview of Malfunction Codes