A system with the high capacity needed to suit large-sized buildings
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
2/19
V R VV R VV R VV R V
VVVVariableariableariableariable RRRRefrigerantefrigerantefrigerantefrigerant VVVVolumeolumeolumeolume
REGISTERED TRADEMARKREGISTERED TRADEMARKREGISTERED TRADEMARKREGISTERED TRADEMARK
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
3/19
System Operation
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
4/19
13A S/S/O 13A S/S/O 13A S/S/O 13A S/S/O
TPN
ISOLATOR
Power Supply Configuration
Single Phase power supply
3 ph
power Supply
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
5/19
Individual Remote Controller,
Wired & Wireless Options
= up to 500 m length
Controls Configuration
INDIVIDUAL
up to 500 m
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
6/19
4. Intelligent Control System4. Intelligent Control System4. Intelligent Control System4. Intelligent Control SystemLCD REMOTE CONTROLLER(WIRED & WIRELESS)
LCD screen
Auto Swing Mechanism Air Flow
Temperature Setting
ON/OFF Timer
Filter Sign
80 Malfunction CodeDisplay
Group Control Display
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
7/19
INV INV INVSTD
STD
STD
1 2 3
Duty Cycling of Compressors
Operating period of inverter
compressor in Unit 1 issignificantly longer thancompressors in units 2 & 3.
Inverter Compressor inUnit 1 has shorter life.
Cycle start-upsequence by
running time.
Equalises
compressorrunning time.
Extended life of
Inverter comp.
Conventional SystemAlways startsInverter Compressor
in unit 1 first. 1 2 3
3 1 2
2 3 1
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
8/19
Dependable and comfortable
Because the VRV III units are rotated within the
system at least once every eight hours,averaging out the running time of each outdoor unit.
This system extends the life of the system as a whole.
Auto-rotation system
extends life ofequipment
With VRV III
When every unit
getsa chance to rest,
none of them getsworn too quickly.
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
9/19
Back-up Function - Single
INV
Compressorbreaks down
BrokenAlarm isindicated
STOP
STOP
Back-up byfield setting R
UN
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
10/19
INV
INV
Running
INV
Back-up Function - Multiple
Even though VRV compressor failure rate is extremely low,the back-up function will give further peace of mind.
Alarm isindicatedon the RC
Back-up by fieldsetting
INV
IN
V
INV
Continue runningStop
The brokencompressor
can berepairedwhile theremaining
units are stilloperating.
(Only appliesto multiple
units)
Compressorbreaks down Broken
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
11/19
Brief Trouble-shooting
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
12/19
Self-diagnosis Function- to Quickly Cope with Errors
Correct display of errors amounting to74 items in the system
Error code
display Run lamp
Unit No.
Inspection display
Errors related with indoor unit: 14
Errors related with outdoor unit: 32
Errors related with control/wiring: 16
Central Control4
HRV8
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
13/19
Operation lampIndoor Unit No.
Error CodeInspection
Display
Troubleshooting by Remote Controller
Self-diagnosis by Wired Remote Controller
Troubleshooting by Remote Controller
Self-diagnosis by Wired Remote Controller
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
14/19
Ref: Si38-304; pg174
Overview of Malfunction CodesOverview of Malfunction Codes
System still operate during the indication of error code
Malfunction
code
Operation
Lamp
Inspection
Display
Unit
No.
Malfunction Content Page
Referred
Indooru
nit
A0 Error of external protection device 178
A1 PCB or E2PROM defect 179
A3 Malfunction of drain level sys. (33H) 180
A6 Fan motor(MF) lock, overload 182
A7 Malfunction of swing flap motor(MA) 183
A9 Malfunction of EXV (20E) 185
AF Drain level above limit 187
AH Malfunction of air filter maintenance -
AJ Malfunction of capacity setting 188
C4Malfunction of thermistor (R2T) for heat
exchanger189
C5 Malfunction of thermistor (R3T) for gaspipe
190
C9Malfunction of thermistor (R1T) for air
inlet191
CJ Malfunction of thermostat sensor in RC 192
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
15/19
Ref: Si38-304; pg174
System still operate during the indication of error code
Malfunction
code
Operation
Lamp
Inspection
Display
Unit
No.
Malfunction Content Page
Referred
Outdooru
nit
E1 PCB defect 193
E3 Actuation of HP switch 194
E4 Actuation of LP switch 195
E5 Compressor motor lock 196
E6 STD compressor lock or over current 197
E7 Malfunction of outdoor unit fan motor 198
E9 Malfunction of EXV (Y1E ~ 3E) 200
F3 Abnormal discharge pipe temp. 202
F6 Refrigerant overcharge 203
H3 Malfunction of HP switch -
H4 Actuation of LP switch -
H7 Abnormal outdoor fan motor signal 204
H9Malfunction of outdoor air thermistor
(R1T)205
Overview of Malfunction CodesOverview of Malfunction Codes
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
16/19
Ref: Si38-304; pg174
System still operate during the indication of error code
Malfunction
code
Operation
Lamp
Inspection
Display
Unit
No.
Malfunction Content Page
Referred
Outd
oorunit
J2 Current sensor malfunction 206
J3Malfunction of discharge pipe thermistor
(R31 ~ 33T)207
J5Malfunction of suction pipe thermistor
(R2T)208
J6Malfunction of heat exchanger thermistor
(R4T)209
J7 Malfunction of header thermistor -
J8Malfunction of oil equalizing pipe
thermistor (R7T)-
J9Malfunction of receiver gas pipe
thermistor (R5T)210
JA Malfunction of discharge pipe pressuresensor
211
JCMalfunction of suction pipe pressure
sensor212
Overview of Malfunction CodesOverview of Malfunction Codes
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
17/19
Ref: Si38-304; pg174 & 17
System still operate during the indication of error code
Malfunction
code
Operation
Lamp
Inspection
Display
Unit
No.
Malfunction Content Page
Referred
Inverterunit
L0 Inverter system error -
L4 Malfunction of INV radiating fin temp rise 213
L5 INV comp motor grounding / short circuit 214
L6 Comp motor coil grounding / short circuit -
L8 INV current abnormal 215
L9 INV startup error 216
LA Malfunction of power unit -
LCMalfunction of transmission btw INV &
control PCB217
P1 INV over-ripple protection 219
P4Malfunction of INV radiating fin temp rise
sensor220
Overview of Malfunction CodesOverview of Malfunction Codes
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
18/19
Ref: Si38-304; pg17
System still operate during the indication of error code
Malfunction
code
Operation
Lamp
Inspection
Display
Unit
No.
Malfunction Content Page
Referred
Sy
stem
U0LP drop due to refrigerant shortage or
EXV failure221
U1 Reverse phase / open phase 222
U2Power supply insufficient or
instantaneous failure223
U3 Check operation not conducted 225
U4Malfunction of transmission btw indoor &
outdoor unit226
U5Malfunction of transmission btw RC &
indoor unit228
U5Failure of RC PCB or setting during
control by RC228
U7Malfunction of transmission btw outdoor
unit229
U8Malfunction of transmission btw master &
slave RC
231
U9Malfunction of transmission btw indoor &
outdoor unit in the same sys.232
UA Excessive no. of indoor units 234
Overview of Malfunction CodesOverview of Malfunction Codes
-
8/10/2019 VRV-III System Operation-Tr VRV-III System Operation-Trouble Shootingouble Shooting
19/19
Ref: Si38-304; pg17
System still operate during the indication of error code
Malfunction
code
Operation
Lamp
Inspection
Display
Unit
No.
Malfunction Content Page
Referred
S
ystem
UC Address duplication of CRC 235
UEMalfunction of transmission btw CRC &
indoor unit
236, 240,
246
UFRefrigerant system not set, incompatible
wiring / piping238
UHMalfunction of system ,refrigerant system
address undefined
239
CRC&
Sched
uleTimer
M1 Or PCB defect 241, 248
M8 OrMalfunction of transmission btw optional
controllers for centralize control242, 249
MA OrImproper combination of optionalcontrollers for centralized control
243, 250
MC Or Address duplication, improper setting 245, 252
Overview of Malfunction CodesOverview of Malfunction Codes