80 The complete control of technology is one of the pillars of MHI. KXZ models with VRF-T technology are an example: high- performance systems thanks to operating flexibility, high energy efficiency and easy installation. Centralised management makes it possible to reduce electricity costs, thus saving in comparison with traditional systems. KXZ can meet the needs of an increasing number of applications in the commercial and industrial sectors. VRF MULTI SYSTEMS

Transcript of VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new...

Page 1: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

80

The complete control of technology is one of the pillars of MHI. KXZ models with VRF-T technology are an example: high-performance systems thanks to operating flexibility, high energy efficiency and easy installation.

Centralised management makes it possible to reduce electricity costs, thus saving in comparison with traditional systems.

KXZ can meet the needs of an increasing number of applications in the commercial and industrial sectors.

VRF MULTI SYSTEMS

Page 2: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

81

NEW

Line-up outdoor units 82

In heat pump KXZ SYSTEM 86

KXZ MICRO COMPACT series 100

KXE6 MICRO LARGE CONNECTION series 102

KXZP MICRO SMART series 104

KXZ ADVANCED series 106

KXZX Hi-COP series 114

Heat recovery KXZ SYSTEM 118

KXZR 3-PIPE series 124

KXZRX Hi-COP series 130

Line-up indoor units 137

Indoor units 138

Post-treatment modular unit 166

EEV-KIT 168

Water cooled KXZW WATER series 132

VRF Multi systems

Page 3: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

82

KXZ MICRO COMPACT

KXZP MICRO SMART

KXZ ADVANCED

KXZX Hi-COP

KXE6 MICRO LARGE CONNECTION

NEW

OUTDOOR HEAT PUMP UNITS

11.20 kW 14.00 kW 15.50 kW4HP 5HP 6HP

FDC112KXZEN1 FDC140KXZEN1 FDC155KXZEN1FDC112KXZES1 FDC140KXZES1 FDC155KXZES1

22.40 kW 28.00 kW 33.50 kW8HP 10HP 12HP

FDC224KXE6 FDC280KXE6 FDC335KXE6

22.40 kW 28.00 kW8HP 10HP

FDC224KXZPE1 FDC280KXZPE1

28.00 kW 33.50 kW 40.00 kW 45.00 kW 47.50 kW 50.00 kW 56.00 kW10HP 12HP 14HP 16HP 17HP 18HP 20HP

FDC280KXZE1 FDC335KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1

61.50 kW 67.00 kW 73.50 kW 80.00 kW 85.00 kW 90.00 kW 95.00 kW 100.00 kW 106.00 kW 112.00 kW22HP 24HP 26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP

FDC615KXZE1 FDC670KXZE1 FDC735KXZE1 FDC800KXZE1 FDC850KXZE1 FDC900KXZE1 FDC950KXZE1 FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE110+12 12+12 12+14 14+14 14+16 16+16 17+17 18+18 18+20 20+20

FDC280KXZE1FDC335KXZE1

FDC335KXZE1 FDC335KXZE1

FDC335KXZE1 FDC400KXZE1

FDC400KXZE1 FDC400KXZE1

FDC400KXZE1 FDC450KXZE1

FDC450KXZE1 FDC450KXZE1

FDC475KXZE1 FDC475KXZE1

FDC500KXZE1 FDC500KXZE1

FDC500KXZE1 FDC560KXZE1

FDC560KXZE1 FDC560KXZE1

120.00 kW 125.00 kW 130.00 kW 135.00 kW 142.50 kW 145.00 kW 150.00 kW 156.00 kW 162.00 kW 168.00 kW42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP

FDC1200KXZE1 FDC1250KXZE1 FDC1300KXZE1 FDC1350KXZE1 FDC1425KXZE1 FDC1450KXZE1 FDC1500KXZE1 FDC1560KXZE1 FDC1620KXZE1 FDC1680KXZE114+14+14 14+14+16 14+16+16 16+16+16 17+17+17 17+17+18 18+18+18 18+18+20 18+20+20 20+20+20

FDC400KXZE1 FDC400KXZE1 FDC400KXZE1

FDC400KXZE1 FDC400KXZE1 FDC450KXZE1

FDC400KXZE1 FDC450KXZE1 FDC450KXZE1

FDC450KXZE1 FDC450KXZE1 FDC450KXZE1

FDC475KXZE1 FDC475KXZE1 FDC475KXZE1

FDC475KXZE1 FDC475KXZE1 FDC500KXZE1

FDC500KXZE1 FDC500KXZE1 FDC500KXZE1

FDC500KXZE1 FDC500KXZE1 FDC560KXZE1

FDC500KXZE1 FDC560KXZE1 FDC560KXZE1

FDC560KXZE1 FDC560KXZE1 FDC560KXZE1

22.40 kW 28.00 kW 33.50 kW8HP 10HP 12HP

FDC224KXZXE1 FDC280KXZXE1 FDC335KXZXE1

45.00 kW 50.00 kW 56.00 kW 61.50 kW 67.00 kW16HP 18HP 20HP 22HP 24HP

FDC450KXZXE1 FDC500KXZXE1 FDC560KXZXE1 FDC615KXZXE1 FDC670KXZXE18+8 8+10 10+10 10+12 12+12

FDC224KXZXE1FDC224KXZXE1

FDC224KXZXE1FDC280KXZXE1

FDC280KXZXE1FDC280KXZXE1

FDC280KXZXE1FDC335KXZXE1

FDC335KXZXE1FDC335KXZXE1

73.50 kW 80.00 kW 85.00 kW 90.00 kW 95.00 kW 100.00 kW26HP 28HP 30HP 32HP 34HP 36HP

FDC735KXZXE1 FDC800KXZXE1 FDC850KXZXE1 FDC900KXZXE1 FDC950KXZXE1 FDC1000KXZXE18+8+10 8+10+10 10+10+10 10+10+12 10+12+12 12+12+12

FDC224KXZXE1FDC224KXZXE1FDC280KXZXE1

FDC224KXZXE1FDC280KXZXE1FDC280KXZXE1

FDC280KXZXE1FDC280KXZXE1FDC280KXZXE1

FDC280KXZXE1FDC280KXZXE1FDC335KXZXE1

FDC280KXZXE1FDC335KXZXE1FDC335KXZXE1

FDC335KXZXE1FDC335KXZXE1FDC335KXZXE1

VRF Multi systems

Page 4: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

83

KXZRX Hi-COP

KXZR 3-PIPE

KXZW WATER

NEW

NEW

OUTDOOR HEAT RECOVERY UNITS

22.40 kW 28.00 kW 33.50 kW8HP 10HP 12HP

FDC224KXZRE1 FDC280KXZRE1 FDC335KXZRE1

40.00 kW 45.00 kW 47.50 kW 50.00 kW 56.00 kW 61.50 kW 67.00 kW14HP 16HP 17HP 18HP 20HP 22HP 24HP

FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC615KXZRE1 FDC670KXZRE1

73.50 kW 80.00 kW 85.50 kW 90.00 kW 95.00 kW 100.00 kW 106.00 kW 112.00 kW26HP 28HP 30HP 32HP 34HP 36HP 38HP 40HP

FDC735KXZRE1 FDC800KXZRE1 FDC850KXZRE1 FDC900KXZRE1 FDC950KXZRE1 FDC1000KXZRE1 FDC1060KXZRE1 FDC1120KXZRE112+14 14+14 14+16 16+16 17+17 18+18 18+20 20+20

FDC335KXZXRE1FDC400KXZXRE1

FDC400KXZXRE1FDC400KXZXRE1

FDC400KXZXRE1FDC450KXZXRE1

FDC450KXZXRE1FDC450KXZXRE1

FDC475KXZXRE1FDC475KXZXRE1

FDC500KXZXRE1FDC500KXZXRE1

FDC500KXZXRE1FDC560KXZXRE1

FDC560KXZXRE1FDC560KXZXRE1

45.00 kW 50.00 kW 56.00 kW 61.50 kW 67.00 kW16HP 18HP 20HP 22HP 24HP

FDC450KXZRXE1 FDC500KXZRXE1 FDC560KXZRXE1 FDC615KXZRXE1 FDC670KXZRXE18+8 8+10 10+10 10+12 12+12

FDC224KXZRE1FDC224KXZRE1

FDC224KXZRE1FDC280KXZRE1

FDC280KXZRE1FDC280KXZRE1

FDC280KXZRE1FDC335KXZRE1

FDC335KXZRE1FDC335KXZRE1

73.5 kW 80.00 kW 85.00 kW 90.00 kW 95.00 kW 100.00 kW26HP 28HP 30HP 32HP 34HP 36HP

FDC735KXZRXE1 FDC800KXZRXE1 FDC850KXZRXE1 FDC900KXZRXE1 FDC950KXZRXE1 FDC1000KXZRXE18+8+10 8+10+10 10+10+10 10+10+12 10+12+12 12+12+12

FDC224KXZRE1FDC224KXZRE1FDC280KXZRE1

FDC224KXZRE1FDC280KXZRE1FDC280KXZRE1

FDC280KXZRE1FDC280KXZRE1FDC280KXZRE1

FDC280KXZRE1FDC280KXZRE1FDC335KXZRE1

FDC280KXZRE1FDC335KXZRE1FDC335KXZRE1

FDC335KXZRE1FDC335KXZRE1FDC335KXZRE1

22.40 kW 28.00 kW 33.50 kW8HP 10HP 12HP

FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1

45.00 kW 50.00 kW 56.00 kW 61.50 kW 67.00 kW16HP 18HP 20HP 22HP 24HP

FDC450KXZWE1 FDC500KXZWE1 FDC560KXZWE1 FDC615KXZWE1 FDC670KXZWE18+8 8+10 10+10 10+12 12+12

FDC224KXZWE1FDC224KXZWE1

FDC224KXZWE1FDC280KXZWE1

FDC280KXZWE1FDC280KXZWE1

FDC280KXZWE1FDC335KXZWE1

FDC335KXZWE1FDC335KXZWE1

73.00 kW 77.50 kW 85.00 kW 90.00 kW 95.00 kW 100.00 kW26HP 28HP 30HP 32HP 34HP 36HP

FDC730KXZWE1 FDC775KXZWE1 FDC850KXZWE1 FDC900KXZWE1 FDC950KXZWE1 FDC1000KXZWE18+8+10 8+10+10 10+10+10 10+10+12 10+12+12 12+12+12

FDC224KXZWE1FDC224KXZWE1FDC280KXZWE1

FDC224KXZWE1FDC280KXZWE1FDC280KXZWE1

FDC280KXZWE1FDC280KXZWE1FDC280KXZWE1

FDC280KXZWE1FDC280KXZWE1FDC335KXZWE1

FDC280KXZWE1FDC335KXZWE1FDC335KXZWE1

FDC335KXZWE1FDC335KXZWE1FDC335KXZWE1

120.00 kW 125.00 kW 130.00 kW 135.00 kW 142.50 kW 145.00 kW 150.00 kW 156.00 kW 162.00 kW 168.00 kW42HP 44HP 46HP 48HP 50HP 52HP 54HP 56HP 58HP 60HP

FDC1200KXZRE1FDC1250KXZRE1FDC1300KXZRE1FDC1350KXZRE1FDC1425KXZRE1FDC1450KXZRE1FDC1500KXZRE1FDC1560KXZRE1FDC1620KXZRE1FDC1680KXZRE114+14+14 14+14+16 14+16+16 16+16+16 17+17+17 17+17+18 18+18+18 18+18+20 18+20+20 20+20+20

FDC400KXZRE1 FDC400KXZRE1 FDC400KXZRE1

FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1

FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1

FDC450KXZRE1 FDC450KXZRE1 FDC450KXZRE1

FDC475KXZRE1 FDC475KXZRE1 FDC475KXZRE1

FDC475KXZRE1 FDC475KXZRE1 FDC500KXZRE1

FDC500KXZRE1 FDC500KXZRE1 FDC500KXZRE1

FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1

FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1

FDC560KXZRE1 FDC560KXZRE1 FDC560KXZRE1

VRF Multi systems

INDOOR WATER COOLING UNITS

Page 5: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

84

KXZ ADVANCED

KXZ MICRO COMPACT KXZP MICRO SMARTKXE6 MICRO LARGE CONNECTION

KXZX Hi-COP

KXZRX Hi-COP

KXZR 3-PIPE NEW

NEW

NEW

OUTDOOR UNITS - DESIGN FLEXIBILITY

Power can be connected to outdoor units

* When connecting the indoor units in the FDK, FDFL, FDFU or FDFW series, the power of the connectable indoor units cannot exceed 130%.

HP 4 5 6kW 11.2 14.0 15.5EER 4.44 3.54 2.98COP 4.36 3.83 3.62max no. connectable IU 8 10 10power of the connectable IUs (%) 80%~150%

HP 8 10 12kW 22.4 28.0 33.5EER 4.00 3.46 3.41COP 4.15 3.84 3.71max nr. connectable IU 15 19 22power of the connectable IUs (%) 50%~150%*

HP 8 10kW 22.4 28.0EER 4.00 3.56COP 4.67 4.33max nr. connectable IU 8 8power of the connectable IUs (%) 50%~120%

HP 10 12 14 16 17 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60kW 28.0 33.5 40.0 45.0 47.5 50.0 56.0 61.5 67.0 73.5 80.0 85.0 90.0 95.0 100.0 106.0 112.0 120.0 125.0 130.0 135.0 142.5 145.0 150.0 156.0 162.0 168.0EER 3.87 3.74 3.65 3.22 3.40 3.58 3.37 3.80 3.74 3.69 3.65 3.41 3.22 3.40 3.58 3.47 3.37 3.65 3.48 3.34 3.22 3.40 3.46 3.58 3.50 3.43 3.37COP 4.33 4.15 4.21 4.00 4.08 4.15 3.95 4.23 4.15 4.18 4.21 4.10 4.00 4.08 4.15 4.04 3.95 4.21 4.13 4.06 4.00 4.08 4.10 4.15 4.08 4.01 3.95max nr. connectable IU 24 29 34 39 41 43 48 53 58 63 69 73 78 80 80 80 80 80 80 80 80 80 80 80 80 80 80power of the connectable IUs (%) 50~130%

HP 8 10 12 16 18 20 22 24 26 28 30 32 34 36kW 22.4 28.0 33.5 45.0 50.0 56.0 61.5 67.0 73.5 80.0 85.0 90.0 95.0 100.0EER 4.50 4.03 3.86 4.50 4.24 4.03 3.94 3.85 4.30 4.15 4.03 3.96 3.91 3.86COP 4.50 4.61 4.47 4.50 4.55 4.60 4.54 4.46 4.53 4.57 4.61 4.57 4.51 4.46max nr. connectable IU 29 37 44 60 53 59 65 71 78 80 80 80 80 80power of the connectable IUs (%) 80~200% 80~160%

KXZKXZX

Connectable power: 130% (KXZ)Connectable power: 160%~200% (KXZX)

HP 16 18 20 22 24 26 28 30 32 34 36kW 45.0 50.4 56.0 61.5 68.0 73.5 80.0 85.0 90.0 96.0 101.0EER 4.37 3.99 3.79 3.61 3.48 4.16 4.02 3.84 3.69 3.56 3.46COP 4.87 4.63 4.52 4.30 4.13 4.76 4.71 4.58 4.39 4.24 4.11max nr. connectable IU 60 53 59 65 70 78 80 80 80 80 80power of the connectable IUs (%) 80~200% 80~160% 80~130%

HP 8 10 12 14 16 17 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60kW 22.4 28.0 33.5 40.0 45.0 47.5 50.0 56.0 61.5 67.0 73.5 80.0 85.0 90.0 95.0 100.0 106.0 112.0 120.0 125.0 130.0 135.0 142.5 145.0 150.0 156.0 162.0 168.0EER 4.35 3.79 3.47 3.46 3.11 3.20 3.29 3.05 2.88 2.62 3.47 3.46 3.27 3.11 3.21 3.29 3.16 3.06 3.46 3.33 3.21 3.11 3.21 3.23 3.29 3.20 3.13 3.06COP 4.84 4.52 4.12 4.09 3.95 4.10 4.10 3.90 3.80 3.60 4.11 4.10 4.03 3.95 4.09 4.12 4.00 3.90 4.10 4.05 4.00 3.95 4.10 4.10 4.11 4.03 3.97 3.91max nr. connectable IU 29 37 44 53 60 50 53 59 65 71 78 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80 80power of the connectable IUs (%) 50~200% 50~160% 50~130%

VRF Multi systems

Page 6: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

85

KXZW WATER

HP 8 10 12 16 18 20 22 24 26 28 30 32 34 36kW 22.4 28.0 33.5 45.0 50.0 56.0 61.5 67.0 73.0 77.5 85.0 90.0 95.0 100.0EER 5.30 4.87 4.12 5.30 5.09 4.87 4.49 4.11 5.14 5.00 4.86 4.62 4.38 4.12COP 5.90 6.18 5.95 5.90 6.04 6.18 6.05 5.95 5.98 6.08 6.17 6.10 6.02 5.96max nr. connectable IU 22 28 33 44 50 56 61 67 72 78 80 80 80 80power of the connectable IUs (%) 50~150%

OUTDOOR UNITS - DESIGN FLEXIBILITY

Power can be connected to outdoor units

VRF Multi systems

Page 7: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

86

› Refrigerant temperature control

› High efficiency

› High COP values

› 34% energy savings

› Compact design

› Design flexibility

› Fast installation

› Ease of maintenance

› Minimum operating costs

"Innovative technology for evolutionary standards in the air conditioning of industrial and commercial environments"

Functional control and innovative components make this system technology more efficient

VRF Multi systems KXZ seriesHeat pump

COP 4.6 KXZX

Page 8: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

87

WIDE RANGE

THE SYSTEM Mitsubishi Heavy Industries' KXZ heat pump series with VRF-T technology is distinguished by the possibility of controlling the refrigerant temperature in the various stages of operation, improving the performance levels compared to traditional systems. KXZ is a unique system that provides an excellent performance both cooling and heating. Maximum level of design flexibility, reduction of energy consumption and advanced operating functions, centralised management of system and above all Hi-COP (KXZX), complete the profile of the KXZ series, which ensures reliability and efficiency over time.

APPLICATION IN NZEB SOLUTIONKXZ system with VRF-T technology is particularly suitable for applications on buildings constructed according to ZEB logic. In fact, the “zero-energy” buildings, realized according to ZEB logic, have the characteristics of reducing the energy consumption, but also of producing the required energy by renewable energy sources, since their goal is the self-sufficiency. To construct ZEB buildings, it is essential that energy efficiency is put as a priority condition since the construction project, taking into consideration all the components that contribute to the final result: heating, cooling, photovoltaic systems and domestic hot water, until the energy management of the entire structure. To achieve this result, one of the main application solutions is constituted by heat pumps, such as those of KXZ system with VRF-T technology.

WHY CHOOSE THE KXZ – VRF-T SYSTEM? HERE ARE 4 GOOD REASONS.

1. ENERGY SAVINGS UP TO 34%With VRF-T technology, refrigerant temperature control during the condensation and evaporation phases in the refrigerant system ensures energy savings up to 34% in cooling mode during the partial loads, compared to the traditional VRF models.

Traditional system cooling operation

Room temperature

Set temperature

Energy savings: Max 34%Room temperature

Set temperature

Compressor

Low pressure target

Control of the temperature difference

Compressor

Low pressure target

Constant level

In a traditional system, the refrigerant target pressure to be maintained is constant. As soon as room temperature reaches the temperature set by the user, the compressor is forced to decrease and increase the rpm by on-off cycles that affect the overall efficiency and performance.

KXZ system cooling operation with activation of VRF-T mod

With the new VRF-T, the refrigerant target pressure to be maintained is not constant, but adjusts proportionally to the difference between the room temperature and the desired temperature. This allows the Inverter compressors to modulate the rpm without ever stopping, thus expressing the maximum efficiency for a global energy saving operation.

Indoor units.16 types of units for a total of 91 models.The variety of types and capacities ensures an offer capable of meeting all the design and installation requirements.

Outdoor units.Up to 80 connectable indoor units. 5 product lines from 8 to 60HP (22.4~168.0 kW): Micro Compact, Micro Smart, Advanced, HiCOP and Water. Mitsubishi air conditioners with VRF-T technology all have double vertical fan and three-phase power supply. They can be installed also in twin combination, with only one refrigerant circuit. The total splitting distance reaches 1000 m.

VRF Multi systems KXZ series

Page 9: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

88

2. COMPACT DESIGN, FOR EASY INSTALLATION

10~60HP (KXZ)

DC Inverter fan motor

Tetrahedral structure of heat exchanger

High efficiency heat exchanger with anti-corrosion Blue Fin

Dual condensate drain

New Scroll Multi-Port compressors, all Inverter. No On/Off

New vector Inverter control

3. NEW ELECTRICAL WINDING FOR THE COMPRESSOR, FOR HIGH PERFORMANCE AND EFFICENCY

The new compacted design of the motor winding significantly improves the electrical performance, which results in increased efficiency, especially in partial loads with a consequent increase in seasonal efficiency.

4. DC INVERTER COMPRESSOR, FOR HIGH SCOP

The multi-port discharge system of the compressor guarantees better volumetric performance. Optimisation of the pressure control, in particular to the medium compressor operation frequencies, with consequent improvement to seasonal efficiency performance.All KXZP/KXZ/KXZX outdoor units use DC Inverter compressors only, and no on/off compressor.

Discharge port

In the case of KXZP (8/10HP); KXZ (10/12/18/20HP) and KXZX (8HP)

Multi-port discharge

Adjustment of compression phase with multi-port discharge that ensures a greater efficiency

Total efficiency

* Used for KXZP SMART power 8/10HP; KXZ ADVANCED power 10/12/17/18/20HP and KXZX Hi-COP power 8HP and KXZR both standard and Hi-COP.

Supp

lied p

ower

New concentrated windings*

Windings distributedin standard mode

Increasein seasonal average

efficiencyCompressor speed

Heat pumpVRF Multi systems KXZ series

Page 10: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

89

KXZ

manifold distributor

EXCHANGER EXCHANGER

NEW REFRIGERANT DISTRIBUTORThe new configuration composed of distributor and capillary has optimized the diffusion of refrigerant in the new heat exchanger, with a further increase in the total efficiency of system and a decrease in the possibility of icing on heat exchanger, with consequent reduction in defrost time.

Oil balance pipe

OIL LEVEL CONTROLMitsubishi oil level adjustment technology for the combination of two or three outdoor units allows operation with constant balancing, maintaining the units' performance and guaranteeing a long system life.

POWER OUTPUT CONTROLThe power output can be controlled and selected by the function of power cut through RC-EX3, remote control, to obtain a greater energy saving. The 5-step power control (100-80-60-40-0%) is available, that can be programmed in hour intervals, every week.

INVERTER CONTROL (VECTOR)The use of a new vector inverter control, allows the user to:• Increasetheresponsespeedofcompressorsatlowandhigh

speed.•Re-createexactlythesinusoidalwaveformofthevoltage

applied.• Increasetheefficiencyofcompressorsatlowspeedandpartial

loads.

Powe

r sup

ply

Operation time

NEW FAN DESIGN

New fan blades with serrated edges that treat a greater air volume, offering low resistance to air and reducing energy consumption.

Serrated edges

DC FAN MOTOR

The use of DC fan motors can help achieve excellent efficiency, with an increase higher than 60% compared to the previous models.

Rotor (squirrel cage ofconductor material)

Stator (coil)

Rotor (permanent magnet)

Stator (coil)

VRF Multi systems KXZ series

previous

Page 11: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

90

ADVANTAGES FOR DESIGNERS

The system design phase requires flexible and advanced solutions, able to respond to each manufacturing solution.Below is a list of all the points that make KXZ - VRF-T a system equipped with all the advantages that meet new design standards.

1. HIGH SPLITTING LENGTH, FLEXIBLE DESIGN 1000 m [10~60HP

(KXZ series)]

The splitting height difference between indoor units has been increased up to 18 m, permitting the placement of indoor units on three additional storeys. The farthest indoor unit (160 m) or the total length (1000 m) contribute to the flexible design of the system.

Total length: 1000 m

max. 10 m

To the first branch: max 130 m

From the first branch pipe to the furthest IU: 90 m*

max. 5 m

Outdoor unit max. 0.4 m

Splitting height difference 50 m (outdoor unit higher) -> 70 m**40 m (outdoor unit lower)

Max height difference between IUs 18 m

Furthest indoor unit

160 m

Indoor unit

Indoor unit

Indoor unit

Thanks to the significant reduction in the weight and overall plan dimensions, the KXZ and KXE6 (Lc) MICRO outdoor units can be easily transported in a lift capable of containing 6 people (if permitted by the condominium regulations), with a consequent reduction in costs, time and working procedures.The outdoor units in the KXZ and KXZX series have a functional base, which makes it easier to lift and transport them to the place of installation. They are also characterised by the same overall plan dimensions, which facilitates the installation of the machines in series as well as optimising times and procedures for maintenance and replacement of each unit.

Lift

2. EASY TRANSPORT & INSTALLATION

H 1675 x L 1080 x D 480

Heat pumpVRF Multi systems KXZ series

Page 12: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

91

1080 mm

970 mm

KXE6 Micro (Lc) KXZP SMART

480 mm

1505 mm

1675 mm

KXE6 Micro (Lc) KXZP SMART

221 kg

165 kg

-20° C

-15° C

+15.5° C

+50° C

-20° C

-15° C

+15.5° C

+46° C

3. WIDE OPERATING RANGE, FLEXIBLE DESIGN

The KXZP series enables operation in heating mode with an outdoor temperature limit of -20°C and a cooling range up to 50°C.This series allows for a more flexible system design, considering a heating range at low temperature conditions down to -20°C, and a cooling range up to 46°C.

KXZP

KXZ/KXZX

HEATING

Cooling

HEATING

Cooling

4. BLUE FIN FUNCTION, AGAINST CORROSION OF THE HEAT EXCHANGERS

The particular coating of the heat exchanger louvers guarantees perfect resistance to corrosion and deterioration caused by atmospheric agents.

5. COMPACT DESIGN

10% less23% less

10% less

25% less

6. EXTERNAL STATIC PRESSURE UP TO 35 PA

9. ADDITIONAL FUNCTIONS:

• POWER DEMAND FUNCTION The outdoor unit's rated power can be decreased.•SEASONAL OPTION A summer/winter season function change can be set.• OUTPUT SIGNAL OPTION Indicates start-up signal or error signal.

7. FUNCTION OF OUTDOOR FAN MOTORS

Function with pressure head useful for ducting.

8. AUTOMATIC FUNCTION FOR REDUCED WEAR

The outdoor units with multiple compressors are subject to wear. This automatic function balances the automatic operation of compressors, depending on the hours of operation.

VRF Multi systems KXZ series

Page 13: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

92

8~60HP

Inverter

KXZ KXZP SMART

1. MONITORING FUNCTION

Thanks to a simple navigation menu, the displays on the outdoor unit boards are able to show all the vital parameters of the unit and any error messages for prompt intervention.

Connect a PC to the RS 232C port, available on the board, to monitor and save all the historical data of system for assistance and control activities. Our Mente PC software must be installed on the PC.

2. BACK UP FUNCTION, OPERATION RESTORED

The unit uses Inverter compressors only.In the event that one of them malfunctions, the unit can however operate at reduced capacity.

In multiple combinations of high capacity of two or three outdoor units, unit malfunction does not affect total operation of the system, which will continue to operate in a partial manner.

3. EASY ACCESS TO THE ELECTRICAL BOX FOR EASY MAINTENANCE

Inverter service and maintenance are now easier thanks to the new control box with a structure of 3 levels (KXZ) and 2 levels (KXZP SMART) with a hinged connection.

Running Compressor failure

KXZ: 18 and 20HP

Unit failure

Combination of two or three outdoor units

ADVANTAGES FOR INSTALLERS

Installing KXZ units in a system means having an installation able to satisfy the most varied requirements, thanks to useful functions and important features which make the life of the system easier to manage, during both installation and maintenance.

Heat pumpVRF Multi systems KXZ series

Page 14: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

93

4. IMPROVED PRACTICALITY

Position of pipes:1) From the front2) To the right3) Below4) From the back

New holes for thread insertion, to prevent falls

Service panel maintenance

Clear rain cover

Unit installation and maintenance of unit are easier thanks to the reduced number of fixing screws on the service panel (from 5 to 2).

5. GAS TESTING FUNCTION

This function provides for a procedure capable of verifying whether the amount of refrigerant gas contained inside the system is correct. The positive side to this is evident, as it optimises the use of gases that are harmful to the environment, as required by current legislation.

6. AUTO-ADDRESSING FUNCTION

Simply power the unit and this automatic function will facilitate intelligent connection between multiple units.

7. ADDITIONAL FUNCTIONS

•Simplifiedtestprocedure

•Simplifiedfunctionforwiring

•Easyfunctionforrefrigerantinstallationandmaintenance

•Theunit'sdistinguishingfeatureisthatofbeingEasy Service, as it permits easy maintenance, easy electronic check and feedback by the protection system in case of malfunctions

VRF Multi systems KXZ series

Page 15: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

94

1. REDUCED COSTS

Cost reduction is an advantage that relates to several aspects: - Savings in management costs- Savings in maintenance costs- Savings on annual consumption thanks to high energy

efficiency

2. COMPLETE SOLUTION

The only system for heating, cooling and management control that can fit any solution.

3. MAXIMUM RELIABILITY

- Well-tested systems in every condition- After-sales service and service network always available- Prompt availability of spare parts

4. INTEGRATION & BUILDING AUTOMATION

The KXZ- VRF-T system boasts integration with home automation systems or Building Automation for easier and more uniform management.

5. BEST ENERGY CLASS

Being in heat pump, the use of KXZ- VRF-T improves building energy classifications with higher scores, thus increasing building value.

A complete system in terms of comfort and smart control, that can be customised to meet the needs of all types of buildings, stores or housing solutions.KXZ with VRF-T technology, designed with integration in mind, is an ideal system because it allows end users to achieve maximum energy efficiency as well as manage several systems, with ease of use guaranteed by leading control standards.

Heat pumpVRF Multi systems KXZ series

ADVANTAGES FOR USERS

Page 16: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

95

HEAD8-371-2/1B

REFRIGERANT CONNECTIONS

VRF-T systems are manufactured to the highest standards of quality and reliability and it is therefore essential for the installation procedures and materials to have the same qualitative features, to ensure trouble-free long-term operation. It is advisable to use high quality copper refrigerant piping, in coils or in straight, semi-rigid lengths. The copper piping should be chosen considering the higher operating pressure of R410A refrigerant gas and the increased pressure circulating in the system produced by reverse cycle operation. All materials used must comply with European standards (EN 12735). The branch pipe kits supplied must be used to connect the indoor units and the manifold kits must be used to connect the outdoor units (if necessary). It is forbidden to use standard accessories (elbow pipes, T-joints etc.). The branch pipes must be installed according to manufacturer guidelines and must allow a continuous flow of refrigerant in accordance with European standard E378:2017.All connecting welds must be made under slight nitrogen pressure to prevent the oxidation of the inner surface of the copper pipes. During installation, no accidental entry of condensate, dust or any other contaminant must be permitted. Once installation is complete, a leak test must be carried out to check for refrigerant leaks with pressurised nitrogen. The ends of the pipe must be bent and welded and an appropriate service valve affixed.

Additional refrigerant chargeOnly R410A refrigerant gas must be used, and this must be added by weight using an electronic meter. The amount of additional refrigerant must be carefully calculated according to the manufacturer’s guidelines, defined by the length and diameter of each section of the system piping.

Single outdoor unit

Refrigerant piping system with manifold kit Refrigerant piping system with branch pipe kit

KXZ ADVANCED - KXZX HiCOP

KXZ ADVANCED - KXZX HiCOP

Combined outdoor units

Refrigerant piping system with branch pipe kit

Refrigerant oil compensation pipe

Set of outdoor unit branch pipesOutdoor unit Set of branch pipes

2 units (for 615 ~ 1120) DOS-2A-3(B)3 units (for 1200 ~ 1680) DOS-3A-3

VRF Multi systems KXZ series

DOS-2A-3(B)

Page 17: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

96

DIS-22-1G(1B)/DIS-180-1G(1B) HEAD6-180-1G(1B)

DIS-371-1G(1B)/DIS-540-3 DOS-2A-3(B)/DOS-3A-3

Combined outdoor units

HP 10 12 14 16 17 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60Liquid side Furthest IU

=<90 mø 9.52 ø 12.7 ø 15.88 ø 19.05

Gas side ø 22.22 ø 28.58 ø 34.92Liquid side Furthest IU

=> 90 mø 12.7 ø 15.88 ø 19.05 ø 22.22

Gas side ø 22.22 ø 28.58 ø 34.92

Liquid sideGas side

YES

NO

NO

vertical

horizontal

floor

floor

floor

floor

First branch pipe of the indoor unitTotal capacity of indoor units

Set of branch pipes

Set of manifoldsModel Branch pipes

~179 DIS-22-1G(1B) HEAD4-22-1G(1B) Max. 4 units180~370 DIS-180-1G(1B) HEAD6-180-1G(1B) Max. 6 units371~539 DIS-371-1G(1B) HEAD8-371-2(1B) Max. 8 units540~ DIS-540-3 HEAD8-540-3 Max. 8 units

Branch pipes Manifolds

YES

KXZ ADVANCED - KXZX HiCOP

REFRIGERANT CONNECTIONS

Refrigerant oil compensation pipe

Refrigerant piping system with manifold kit

HEAD8-540-3

DOS-2A-3(B)

Heat pumpVRF Multi systems KXZ series

Page 18: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

97

ELECTRICAL CONNECTIONSVRF MHI systems require highly simplified electrical connections to the indoor units, thanks to a control circuit that uses 2 non-polarised conductors. The supply system has wiring that can be connected on the front, right, left or rear of the outdoor unit. For three-phase outdoor units and single phase indoor units, a separate power supply must be used. The interaction between the outdoor unit and indoor unit takes place via the control device only.

Outdoor unit power supply: three-phase, 4 wires, 380~415V Separated power supply system

Outd

oor u

nitEarth leakagebreaker

Circuitbreaker Ground

A Main power supply cable (4 wires)B Signal lines - Superlink (2 wires)C Indoor units power cable (2 wires)D Cables for the wired remote control (2 wires)

Earth leakagebreaker

Circuitbreaker

Indoor unit

wired remote control

Indoor unit power supply: single phase 220~240V

CAUTION: if the RCD is dedicated solely to protecting against leakage to earth, it will be necessary to install a circuit breaker.

The maximum number of indoor units that can be connected to a signal line is 128, and it is possible to create groups of outdoor and/or indoor units connected to the same outdoor unit or to separate outdoor units, as long as they are connected to the same signal line. The signal line can also be connected by adopting the method described below (multiple connectors).

0.75 mm2 1.25 mm2~1000 mm YES YES

1000~1500 mm YES NO

Signal line

IMPORTANT: A loop connection of the signal lines is NOT ALLOWED

A loop cannot be formed with the signal, therefore the section of the connection indicated with ........is not permitted

Length (m) Type of cables100~200 0.5 mm2 x 2 wires

~300 0.75 mm2 x 2 wires~400 1.25 mm2 x 2 wires~600 2.0 mm2 x 2 wires

Single outdoor unit

Combined outdoor units

OU signal terminal board

IU signal terminal board

The signal lines have no polarity therefore the connections listed below are permitted

Network connectors

Signal lines

Refrigerant lines

The signal line is 5 VDC and uses 2 non-polarised conductors marked A1 and B1. AB connects the outdoor unit to the indoor unit and vice versa. For the signal line with 2 conductors, use shielded cables measuring 0.75 or 1.25 mm2. Earth the shield on all the indoor and outdoor units.

If using combined outdoor units, connect:• Thesignallinebetweenindoorand

outdoor units, and the signal line between outdoor units that belong to the same

refrigerant line, to A1 and B1;• Thesignallinebetweenoutdoor

units belonging to a different refrigerant line to A2 and B2.

The specifications for the connection between the wired remote control and the indoor units (XY connection) are 0.3 mm2 x 2 wires. The maximum permitted length is 600 m. If the length exceeds 100 m, refer to the table.

Wired remote control

OU

IU

OUOUOU

IUIUIU

OU

IU

OU OU

IU IU

IU IU IU

OU OU OU OU

IU

IU

IU

IU

VRF Multi systems KXZ series

Page 19: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

98

4545

5656

7171

2828

5656

total314

total198

It is possible to fix the operation mode of the system (cooling or heating) using a switch (SW3-7) on the outdoor unit PC board: this enables the user to decide the operation of the system inside the building (e.g. cooling only in summer/heating only in winter), to avoid unnecessary energy waste. It is also possible to wire the control switch to a remote location (inside the building), in a control room, or even linked to an ambient thermostat.

FIXED COOLING MODE/FIXED HEATING MODE (SUMMER/WINTER SWITCH)

Priority operating mode selection You can select the following priority operation modes (for the whole

system).

1. The first unit's operating mode commands the operating mode (default setting).

The system operates according to the mode selected by the majority of units in operation, taking into consideration the greater capacity between the sum of units in cooling mode and those in heating mode. The minority operating mode is set to fan mode automatically.

“Majority” operating mode

In “Master” function, if you select the cooling mode, the units set in heating mode switch to fan mode automatically.

“Master” operating mode

Operating modecooling capacity

45+45+56+56+56+56

Cooling mode

Fan mode

Operating modeheating capacity71+71+28+28

Fan mode

Heating mode

Cooling mode Heating mode "Master" mode: cooling

"Master" mode: cooling

OPERATING MODE

2. The last unit's operating mode determines the operating mode for whole system.

3. “Majority” operating mode4. “Master” operating mode

Heat pumpVRF Multi systems KXZ series

Page 20: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

99

VRF Multi systems KXZ series

Page 21: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

100

Connects up to 10 indoor units/150% capacity

FDC 112 KXZEN1/ZES1 11.2 kW single phase/three-phaseFDC 140 KXZEN1/ZES1 14.0 kW single phase/three-phaseFDC 155 KXZEN1/ZES1 15.5 kW single phase/three-phase

› Maximum energy efficiency: COP 4,36 (4HP)› Scroll DC Inverter compressor on all units› DC Inverter fan motors › 4 sound levels in Silent mode› New PCB cooling system: A refrigerant pipe branch passes to

the base of the PCB to prevent overheating

Diagrams and measurements

Max height difference between IUs 15 m

Indoor unit

Indoor unit

Outdoor unit

* The total length of piping, liquid side ø9.52 mm (3/8") should be 50 m or less.

Total length 100 m

Height difference:30 m top OU15 m bottom OU

Furthest IU: 70 m*

Operating range

terminal board

intake

intake

outlet(Service space)

All measurements are in mm.

A Service valve (gas side) ø 15.88 (5/8”) (flare fitting)

B Service valve (liquid side) ø 9.52 (3/8”) (flare fitting)

C Piping outputD Condensate drain ø 20 x 3 holesE Fixing bolt holes M10 x 4 holesF Cable output ø 30 x 3 holes

DimensionsExample of installation

1 2 3L1 open open 500L2 300 5 openL3 150 300 150L4 5 5 5

Notes:(1) The unit should not be surrounded by walls on

any side(2) Secure the unit using anchor bolts(3) In case of exposure to strong wind, direct the unit so

that the air expulsion grille is at 90° in relation to the prevailing wind direction

(4) Allow at least 1 m clearance above the unit(5) If there are obstacles in front of the air expulsion

grille, the height must not exceed the height of the unit

(6) The label with the installation data is positioned in the bottom right corner of the front panelMinimum installation space

HP 4 5 6Liquid side

Furthest IU =<70 mø 15.88 (5/8")

Gas side ø 9.52 (3/8")

Refrigerant connections

Branch pipes Manifolds

Outdoor unit

› Can connect 1.5 kW indoor units› New system for managing indoor unit priorities› "Pump down" safety function: to identify any gas leaks inside

the room (third-party sensor) and start up the refrigerant recall procedure by the outdoor unit, present inside the system

VRF Multi systems KXZ MICRO COMPACT seriesHeat pump

VRF-T TECHNOLOGYenergy savings up to 34% in cooling

HEAD4-22-1G(1B) HEAD6-180-1G(1B)

DIS-22-1G(1B)DIS-180-1G(1B)

NEW

Page 22: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

101

1. EU Delegated Regulation No.626/2011 on the labelling indicating the energy consumption of air conditioners.2. EU Regulation No.206/2012 - N.2281/2016 - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a

refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.

VRF Multi systems KXZ MICRO COMPACT series

KXE6 NEW KXZ4HP 6 units → 8 units5HP 8 units → 10 units15H6 8 units → 10 units2

Increased number of connectable IU

1. max capacity <=100% with 9 or 10 connected units2. max capacity <=100% with 9 or 10 connected units

* With limitations on maximum connectivity.

Models FDC112KXZEN1 FDC140KXZEN1 FDC155KXZEN1 FDC112KXZES1 FDC140KXZES1 FDC155KXZES1Nominal Cool. capacity (T=35°C) kW 11.20 14.00 15.50 11.20 14.00 15.50Cool. power consumption (T=35°C) kW 2.52 3.96 5.20 2.52 3.96 5.20Annual energy consumption in Cool. kWh/a - - - - - -Seasonal energy efficiency class in Cool. 626/20111 A+ - - A+ - -Seasonal energy efficiency index in Cool. SEER2 5.94 7.73 7.21 5.94 7.73 7.21Rated energy efficiency coefficient in Cool. EER3 4.44 3.54 2.98 4.44 3.54 2.98Nominal Heat. capacity (T=7°C) kW 11.20 14.00 15.50 11.20 14.00 15.50Heat. power consumption (T=7°C) kW 2.57 3.66 4.28 2.57 3.66 4.28Annual energy consumption in Heat. kWh/a - - - - - -Seasonal energy efficiency class in Heat. 626/20111 A+ - - A+ - -Seasonal energy efficiency index in Heat. SCOP2 4.17 4.59 4.55 4.17 4.59 4.55Rated energy efficiency coefficient in Heat. COP3 4.36 3.83 3.62 4.36 3.83 3.62Power Single phase 220~240V 50Hz Three-phase 380~415V 50HzRated current in Cool. A 12.2 19.6 25.7 4.1 6.5 8.6Rated current in Heat. A 12.6 18.3 21.4 4.2 6.1 7.1Sound pressure level dB(A) 52 53 54 52 53 54Sound power level dB(A) 69 71 71 69 71 71External dimensions (HxLxD) mm 845x970x370 845x970x370 845x970x370 845x970x370 845x970x370 845x970x370Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 85 85 85 87 87 87Refrigerant circuit/Compressor type and qty. RMT5126MDE21x1 RMT5126MDE21x1 RMT5126MDE21x1 RMT5126MDE31x1 RMT5126MDE31x1 RMT5126MDE31x1Motor kW 1.9 2.9 3.2 1.9 2.9 3.2Starting method In line, direct

Indoor System Units Number of connectable IU from 1 to 8 from 1 to 10* from 1 to 10* from 1 to 8 from 1 to 10* from 1 to 10*Total connectable capacity 90 ~ 168 112 ~ 210 124 ~ 233 90 ~ 168 112 ~ 210 124 ~ 233

Crankcase heater W 20 20 20 20 20 20Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A R410A R410A R410A R410A R410AQuantity kg 5.00 5.00 5.00 5.00 5.00 5.00Tons of CO2 equivalent 10.44 10.44 10.44 10.44 10.44 10.44Refrigerant oil l 1.0 (M-MA68) 1.0 (M-MA68) 1.0 (M-MA68) 1.0 (M-MA68) 1.0 (M-MA68) 1.0 (M-MA68)Defrost control Microcomputer controlledAir treatment/Fan type and quantity Axial fan x 1Motor W 86x1 86x1 86x1 86x1 86x1 86x1Starting method Direct Direct Direct Direct Direct DirectAir flow (Standard) m3h 4500 4500 4500 4500 4500 4500Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection, overcurrent protection, power transistor overheating protection, abnormal high pressure protection

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52)Gas side ø 5/8” (15.88)

Joining method by flare fittingsCondensate drain Hole for drain ø 20x3Piping insulation Necessary (on both sides, liquid and gas)Accessories - - - - - -

NEW

4-6HP (11.2~15.5 kW)

Page 23: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

102

Up to the first branch pipe:max 130 m

From the first branch pipe to the furthest IU: 90 m* Furthest IU 160 m

Max height difference between IUs 18 m

Indoor unit

Indoor unit

Indoor unit

Outdoor unit

* With length difference between the furthest indoor unit and the nearest one from the first branch pipe < 40 m.

Total length 510 m

Height difference:50 m top OU40 m bottom OU

FDC224KXE6 FDC280KXE6 FDC335KXE6A Service valve (gas side) ø 19.05 (3/4”) (flare fitting) ø 19.05 (3/4”) (flare fitting) ø 19.05 (3/4”) (flare fitting)B Service valve (liquid side) ø 9.52 (3/8”) (flare fitting) ø 9.52 (3/8”) (flare fitting) ø 12.7 (1/2”) (flare fitting)C Piping output 4 holes 4 holes 4 holesD Hole for condensate drain ø 20 x 4 holes ø 20 x 4 holes ø 20 x 4 holesE Fixing bolt holes M10 x 4 holes M10 x 4 holes M10 x 4 holes

F Electrical connection outletø 30 x 2 holes (front)

ø 45 (side)ø 30 x 2 holes (rear)

ø 30 x 2 holes (front)ø 45 (side)

ø 30 x 2 holes (rear)

ø 30 x 2 holes (front)ø 45 (side)

ø 30 x 2 holes (rear)

G Connecting position of the local pipe (gas side) ø 19.05 (3/4”) (brazing) ø 22.22 (7/8”) (brazing) ø 25,4 (1”) (brazing)

Dimensions Example of installation1 2 3

L1 open open 1500(500)*1

L2 300 5 openL3 300 300 300L4 250(5)*2 250(5)*2 250(5)*2

Notes:(1) The unit should not be surrounded by walls on any side(2) Secure the unit using anchor bolts The anchor bolt must not

protrude more than 15 mm.(3) In case of exposure to strong wind, direct the unit so that the

air expulsion grille is at 90° in relation to the prevailing wind direction

(4) Allow at least 1 m clearance above the unit(5) If there are obstacles in front of the air expulsion grille, the height

must not exceed the height of the unit(6) The label with the installation data is positioned in the bottom

right corner of the front panel(7) Connect the service valve with the local pipe using the

connection pipe (gas side only)(8) The mark shows the position for the local pipe connection (gas

side only)

terminal board

intakeintake

outlet(Service space)

Minimum installation space

*1 The Figure in () shows the applicable value when the flexible flow adapter is installed.

*2 On condition of setting as it is specified in (), it is necessary to ensure 250 mm for L4 dimension when the compressor is replaced (i.e. if unit is moved).

Connect up to 22 indoor units/150% capacity

FDC 224 KXE6 22.4 kW three-phaseFDC 280 KXE6 28.0 kW three-phaseFDC 335 KXE6 33.5 kW three-phase

› 1 DC Inverter compressor (8 ~ 10 HP), 1 3D Scroll compressor (12 HP)

› High split: up to 510 m in total and with a maximum distance between the OU and the furthest IU of 160 m

Operating range

Diagrams and measurements

All measurements are in mm.

Outdoor unit

VRF Multi systems KXE6 MICRO LARGE CONNECTION seriesHeat pump

Page 24: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

103

HP 8 10 12Liquid side Furthest IU

=<90 mø 9.52 ø 12.7

Gas side ø 19.05 ø 22.22 ø 28.58Liquid side Furthest IU =>

90 mø 12.7

Gas side ø 22.22 ø 28.58

Refrigerant connections Branch pipes Manifolds

2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a

refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.

VRF Multi systems KXE6 MICRO LARGE CONNECTION series

Models FDC224KXE6 FDC280KXE6 FDC335KXE6Nominal Cool. capacity (T=35°C) kW 22.40 28.00 33.50Cool. power consumption (T=35°C) kW 5.60 8.09 9.82Annual energy consumption in Cool. kWh/aSeasonal energy efficiency index in Cool. SEER2 6.55 6.03 5.77Rated energy efficiency coefficient in Cool. EER3 4.00 3.46 3.41Nominal Heat. capacity (T=7°C) kW 25.00 31.50 37.50Heat. power consumption (T=7°C) kW 6.03 8.21 10.12Annual energy consumption in Heat. kWh/aSeasonal energy efficiency index in Heat. SCOP2 4.55 4.54 4.49Rated energy efficiency coefficient in Heat. COP3 4.15 3.84 3.71Power Three-phase 380~415V 50HzRated current in Cool. A 9.25 13.22 15.87Rated current in Heat. A 9.85 13.41 16.36Sound pressure level dB(A) 59 60 61Sound power level dB(A) - - -External dimensions (hxlxd) mm 1675x1080x480Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.1) equivalentNet weight kg 221 221 224Refrigerant circuit/Compressor type and qty. GTC5150NH40K×1 GTC5150NH40K×1 GTD5160NH40K×1Motor kW 3.81 5.22 7.25Starting method In line, direct

Indoor System Units Number of connectable IU from 1 to 15 from 1 to 19 from 1 to 22Total connectable capacity 112 ~ 336 140 ~ 420 167 ~ 502

Crankcase heater W 33 33 33Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088 R410A/2088 R410A/2088Quantity kg 11.50 11.50 11.50Tons of CO2 equivalent 24.01 24.01 24.01Refrigerant oil l 1.7 (M-MA32R) 1.7 (M-MA32R) 1.7 (M-MA32R)Defrost control Microcomputer controlledAir treatment/Fan type and quantity Axial fan x 2Motor W 144x2Starting method DirectAir flow (Standard) m3h 12000Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection, overcurrent protection, power transistor overheating protection, abnormal high pressure protection

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52) Liquid side ø 3/8” (9.52) Liquid side ø 1/4” (12.7)Gas side ø 3/4” (19.05) Gas side ø 7/8” (22.22) Gas side ø 1” (25.4)

Joining method Liquid line flare/Gas line brazingCondensate drain Holes for drain ø20x4Piping insulation Necessary (on both sides, liquid and gas)Accessories - - -

DIS-22-1G/1BDIS-180-1G/1B

DIS-371-1G/1B HEAD4-22-1G/1B HEAD6-180-1G/1BHEAD8-371-2/1B

8~12 HP (22.4~33.5 kW)

Page 25: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

104

Up to the first branch pipe: max 90 m

From the first branch pipe to the furthest IU: 40 m

Furthest IU 120 m

Max height difference between IUs 18 m

Indoor unit

Indoor unit

Indoor unit

Outdoor unit

Total length 150 m

Height difference:30 m top OU30 m bottom OU

intake

intake

outlet (Service space)

Minimum installation space

terminal board

Piping accessory(only for model FDC 280 KXZPE1)

Dimensions Example of installation1 2 3

L1 open open 500L2 300 5 openL3 150 300 150L4 250(5)* 250(5)* 250(5)*

* It is necessary to ensure 250 mm for L4 dimension when the compressor is replaced.

Connect up to 8 indoor units/120% capacity

FDC 224 KXZPE1 22.4 kW three-phaseFDC 280 KXZPE1 28.0 kW three-phase

› Maximum energy efficiency: COP 4.67 (8 HP)

› Only DC Inverter compressors

› High split: up to 150 m in total and with a maximum distance between the OU and the furthest IU of 120 m

› Compressor speed control

Operating range

Diagrams and measurementsAll measurements are in mm.

Ref. ItemA Gas side pipe fitting ø 19.05 (3/4”) (flare)B Liquid side pipe fitting ø 9.52 (3/8”) (flare)C Hole for draw-out cable (front - side) ø 30 x 2 holesD Hole for draw-out cable (front - side) ø 45 x 2 holesE Hole for draw-out cable (rear) ø 50F Pipe / cable draw-out port 4 holesG Condensate drain ø 20 x 3 holesH Fixing bolt hole M10 x 4 holes

Notes:(1) The unit should not be surrounded by walls on any side(2) Secure the unit using anchor bolts The anchor bolt must not

protrude more than 15 mm.(3) In case of exposure to strong wind, direct the unit so that

the air expulsion grille is at 90° in relation to the prevailing wind direction

(4) Allow at least 1 m clearance above the unit(5) If there are obstacles in front of the air expulsion grille, the

height must not exceed the height of the unit(6) The label with the installation data is positioned in the

bottom right corner of the front panel(7) Connect the service valve with the local pipe using the

connection pipe (gas side only) (The accessory pipe is used for FDC280KXZPE1 only)(8) Concerning the fixing of the accessory pipe, please refer to

the attached installation manual

VRF Multi systems KXZP MICRO SMART series

Outdoor unit

Heat pump

Page 26: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

105

HEAD4-22-1G/1B HEAD6-180-1G/1B

DIS-22-1G/1BDIS-180-1G/1B

Branch pipes ManifoldsRefrigerant connections

HP 8 10Liquid side Furthest IU

=<90 mø 9.52

Gas side ø 19.05 ø 22.22Liquid side Furthest IU =>

90 mø 12.7

Gas side ø 22.22 ø 28.58

VRF Multi systems KXZP MICRO SMART series

2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a

refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.

Models FDC224KXZPE1 FDC280KXZPE1Nominal Cool. capacity kW 22.40 28.00Cool. power consumption kW 5.60 7.87Seasonal energy efficiency index in Cool. SEER2 6.65 6.68Rated energy efficiency coefficient in Cool. EER3 4.00 3.56Nominal Heat. capacity kW 22.40 28.00Heat. power consumption kW 4.80 6.47Seasonal energy efficiency index in Heat. SCOP2 4.34 4.50Rated energy efficiency coefficient in Heat. COP3 4.67 4.33Power Three-phase- 380-415V 50HzRated current in Cool. A 9.2 12.9Rated current in Heat. A 7.9 10.6Sound level dB(A) 60 63External dimensions (hxlxd) mm 1505×970×370 1505×970×370Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalent Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 165 165Refrigerant circuit/Compressor type and qty. GTC5150NC40FK×1 GTC5150NC40FK×1Starting method Direct, in line Direct, in line

Indoor System Units Number of connectable IU from 1 to 8 from 1 to 8Total connectable capacity 112 ~ 268 140 ~ 336

Crankcase heater W 33*1 33*1Refrigerant circuit/Heat exchanger Pipes finned with Blue fin treatment and grooved internally Pipes finned with Blue fin treatment and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088Quantity kg 8.9 8.9Tons of CO2 equivalent 18.58 18.58Refrigerant oil l 1.45 (M-MA32R) 1.45 (M-MA32R)Defrost control Micro -computerised Micro -computerisedAir treatment/Fan type and quantity Axial fan x 2 Axial fan x 2Motor W 86×2 86×2Starting method Direct DirectAir flow (Standard) m3h 7800 8700Available static pressure Pa Max 35Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52)Gas side: ø19.05 (3/4”) (ø22.22 (7/8”) Gas side: ø22.22 (7/8”) (ø25.4 (1”) (ø28.58 (1 1/8”)

Joining method Gas side: brazing / Liquid side: flareCondensate drain Drain holes: ø20 × 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - -

8~10HP (22.4~28.0 kW)

Page 27: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

106

Connect up to 29 indoor units/130% capacity

FDC 280 KXZE1 28.0 kWFDC 335 KXZE1 33.5 kW

› Maximum energy efficiency: COP 4.33 (10HP)

› Only DC Inverter compressors

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%.

VRF Multi system KXZ ADVANCED seriesHeat pumpModular outdoor units

2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a

refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.

Models FDC280KXZE1 FDC335KXZE1Nominal Cool. capacity kW 28.00 33.50Cool. power consumption kW 7.24 8.96Seasonal energy efficiency index in Cool. SEER2 7.25 7.38Rated energy efficiency coefficient in Cool. EER3 3.87 3.74Nominal Heat. capacity kW 31.50 37.50Heat. power consumption kW 7.28 9.04Seasonal energy efficiency index in Heat. SCOP2 4.89 4.85Rated energy efficiency coefficient in Heat. COP3 4.33 4.15Power Three-phase- 380-415V 50HzRated current in Cool. A 11.9 14.6Rated current in Heat. A 12 14.8Sound level dB(A) 57 61Outdoor(?) dimensions (hxlxd) mm 1690×1350×720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 272 272Refrigerant circuit/Compressor type and qty. GTC5150NC47LF×1Motor kW 4.76*1 5.94*1Starting method Direct, in line

Indoor System Units Number of connectable IU from 1 to 24 from 1 to 29Total connectable capacity* 140 ~ 364 168 ~ 435

Crankcase heater W 33*1 33*1Refrigerant circuit/Heat exchanger Pipes finned with Blue fin treatment and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088Quantity kg 11.00 11.00Tons of CO2 equivalent 22.97 22.97Refrigerant oil l 2.25 (M-MA32R)Defrost control Micro -computerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386×2Starting method DirectAir flow (Standard) m3h 13200 16800Available static pressure Pa Max 50Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52) Liquid side φ12.7 (1/2”)Gas side ø 7/8” (22.22) Gas side: ø25.4 (1”) (ø22.22 (7/8”))

Joining method Gas side: brazing / Liquid side: flareCondensate drain Drain holes: ø20 × 10pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - -

10~12HP (28.0~33.5 kW)

Page 28: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

107

Operating rangeTotal length: 1000 m

Outdoor unit

Up to the first branch pipe: max 130 m

Indoor unit

Indoor unit

Indoor unitFrom the first branch pipe to the furthest IU: 90 m*

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)** Comply with installation conditions. For details, refer to the Technical Manual.

Furthest IU 160 m

Max height difference between IUs 18 m

Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)

Diagrams and measurementsAll measurements are in mm.

rearView of refrigerant connections

References for the dimensions of the holes of the fixing boltsIncoming air

D (bottom)

C (front)C (right)

D (right)

C (rear)

D (front)

Label with instructions

Box for power cable wiring

Box for signal cable wiring

7-segment displayinspection hole

D (left)

Drain pipe

Notes:(1) Secure the unit using anchor bolts(2) Allow at least 2 m clearance above the unit(3) The adhesive label with the installation data should be positioned under the front panel (right side)(4) The inlet openings for the electrical and refrigerant connections are pre-cut (open using a cutter)(5) For the piping inlet, use the ø 88 hole(6) Use the fixing holes (M10) indicated with “L” and “J” when replacing an outdoor unit belonging to the old series(7) Connect the refrigerant oil compensation pipe (“K”) when using in combination with the outdoor unit

Ref. Item FDC280KXZE1 FDC335KXZE1A Gas side pipe fitting ø 22.22 (7/8”) (brazing) ø 25.4 (1”) (brazing)B Liquid side pipe fitting ø 9.52 (3/8”) (flare) ø 12.7 (1/2”) (flare)C Refrigerant pipe outlet ø88 (or ø100)D Power cable inlet ø 50 (right - left - front), slot 40 x 80 (at bottom)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) flareL Opening for movement 230 x 60

Example of installationDimensions 1 2

L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open

Installation spaces

H3

H4H1Intake

Intake

H2

Intake

VRF Multi system KXZ ADVANCED series

Page 29: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

108

Connect up to 48 indoor units/130% capacity

FDC 400 KXZE1 40.0 kWFDC 450 KXZE1 45.0 kWFDC 475 KXZE1 47.5 kW

› Maximum energy efficiency: COP 4.21 (14 HP)

› Only DC Inverter compressors

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

FDC 500 KXZE1 50.0 kWFDC 560 KXZE1 56.0 kW

Modular outdoor units

Heat pumpVRF Multi system KXZ ADVANCED series

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a

refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.

Models FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1Nominal Cool. capacity kW 40.00 45.00 47.50 50.00 56.00Cool. power consumption kW 10.96 13.98 13.98 13.97 16.62Seasonal energy efficiency index in Cool. SEER2 6.66 6.36 6.84 7.29 6.45Rated energy efficiency coefficient in Cool. EER3 3.65 3.22 3.40 3.58 3.37Nominal Heat. capacity kW 45.00 50.00 53.00 56.00 63.00Heat. power consumption kW 10.69 12.50 13.00 13.49 15.59Seasonal energy efficiency index in Heat. SCOP2 4.23 4.36 4.31 4.58 4.30Rated energy efficiency coefficient in Heat. COP3 4.21 4.00 4.08 4.15 4.04Power Three-phase- 380-415V 50HzRated current in Cool. A 17.5 22.4 22.6 22.6 26.9Rated current in Heat. A 17.5 20.4 21 21.8 25.8Sound level dB(A) 62 61 61 62 66External dimensions (hxlxd) mm 2048x1350x720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 317 317 370 370 370Refrigerant circuit/Compressor type and qty. GUC5185ND47Vx1 GTC5150NC47LFx2Motor kW 7.32*1 9.32*1 4.64*2 4.91*2 5.36*2Starting method Direct, in line

Indoor System Units Number of connectable IU from 1 to 34 from 1 to 39 from 1 to 41 from 1 to 43 from 1 to 48Total connectable capacity* 200 ~ 520 225 ~ 585 238 ~ 617 250 ~ 650 280 ~ 728

Crankcase heater W 40*1 40*1 33*2 33*2 33*2Refrigerant circuit/Heat exchanger Pipes finned with Blue fin treatment and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088Quantity kg 11.50 11.50 11.50 11.50 11.50Tons of CO2 equivalent 24.01 24.01 24.01 24.01 24.01Refrigerant oil l 2.9 (M-MA32R) 4.2 (M-MA32R)Defrost control Micro -computerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386×2Starting method DirectAir flow (Standard) m3h 16800 16800 16800 16800 18600Available static pressure Pa Max 50Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection

Diameter cooling/refrigerant pipes mm (inch) Liquid side φ12.7 (1/2”)Gas side: ø25.4 (1”) (ø28.58 (11/8”)) Gas side: φ28.58 (11/8”)

Joining method Gas side: brazing / Liquid side: flareCondensate drain Drain holes: ø20 × 10pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - - - - -

14~20HP (40.0~56.0 kW)

Page 30: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

109

Operating rangeTotal length: 1000 m

Outdoor unit

Up to the first branch pipe: max 130 m

Indoor unit

Indoor unit

Indoor unitFrom the first branch pipe to the furthest IU: 90 m*

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)

** Comply with installation conditions. For details, refer to the Technical Manual.

Furthest IU 160 m

Max height difference between IUs 18 m

Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)

rear

View of refrigerant connections

References for the dimensions of the holes of the fixing boltsIncoming air

D (bottom)

C (front) C (right)

D (right)

C (rear)

D (front)

Label with instructions

Box for power cable wiring

Box for signal cable wiring

7-segment displayinspection hole

D (left)

Drain pipe

C (bottom)

Installation spaces

Intake

Intake

Notes:(1) Secure the unit using anchor bolts(2) Allow at least 2 m clearance above the unit(3) The adhesive label with the installation data should be positioned under the front panel (right side)(4) The inlet openings for the electrical and refrigerant connections are pre-cut (open using a cutter)(5) For the piping inlet, use the ø 88 hole(6) Use the fixing holes (M10) indicated with “L” and “J” when replacing an outdoor unit belonging to the old series(7) Connect the refrigerant oil compensation pipe (“K”) when using in combination with the outdoor unit

Ref. Item FDC400KXZE1 FDC450~560KXZE1A Gas side pipe fitting ø 25.4 (1”) (brazing) ø 28.58 (11/8”) (brazing)B Liquid side pipe fitting ø 12.7 (1/2”) (flare)C Refrigerant pipe outlet ø 88 (or ø 100)D Power cable inlet ø 50 (right - left - front), slot 40 x 80 (at bottom)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) flareL Opening for movement 230 x 60

Example of installationDimensions 1 2

L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open

Intake

H2H4

H1

H3

VRF Multi system KXZ ADVANCED series

Diagrams and measurementsAll measurements are in mm.

Page 31: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

110

Total length: 1000 m

max. 10 m (equalisation pipe oil)

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)

** Comply with installation conditions. For details, refer to the Technical Manual.

max. 0.4 m

Max height difference between IUs 18 m

Outdoor unit

max. 5 m

Indoor unit

Indoor unit

Indoor unit

Up to the first branch pipe: max 130 m

Furthest IU 160 m

From the first branch pipe to the furthest IU: 90 m*

Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)

Connect up to 58 indoor units/130% capacity

FDC 615 KXZE1 (FDC280+FDC335) 61.5 kWFDC 670 KXZE1 (FDC335+FDC335) 67.0 kW

› Maximum energy efficiency: COP 4.23 (22HP)

› Only DC Inverter compressors

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

Operating range

Combinations

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 3. Value measured according to harmonised standard EN14511.

Modular outdoor units

Heat pumpVRF Multi system KXZ ADVANCED series

Models FDC615KXZE1 FDC670KXZE1

CombinationsFDC280KXZE1 FDC335KXZE1FDC335KXZE1 FDC335KXZE1

- -Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 61.50 67.00Cool. power consumption kW 16.2 17.92Rated energy efficiency coefficient in Cool. EER3 3.80 3.74Nominal Heat. capacity kW 69.00 75.00Heat. power consumption kW 16.32 18.08Rated energy efficiency coefficient in Heat. COP3 4.23 4.15Rated current in Cool. A 26.50 29.20Rated current in Heat. A 26.80 29.60

Indoor System Units Number of connectable IU from 2 to 53 from 2 to 58Total connectable capacity* 308 ~ 799 335 ~ 871

Net weight kg 544 544

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 1/2” (12.7)mm (inch) Gas side: ø28.58 (1.1/8”)

Oil equalisation mm (inch) ø 3/8” (9.52)

22~24HP (61.5~67.0 kW)

Page 32: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

111

Connect up to 80 indoor units/130% capacity

FDC 735 KXZE1 (FDC335+FDC400) 73.5 kWFDC 800 KXZE1 (FDC400+FDC400) 80.0 kWFDC 850 KXZE1 (FDC400+FDC450) 85.0 kWFDC 900 KXZE1 (FDC450+FDC450) 90.0 kW

› Maximum energy efficiency: COP 4.21 (28HP)

› Only DC Inverter compressors

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

FDC 950 KXZE1 (FDC475+FDC475) 95.0 kWFDC 1000 KXZE1 (FDC500+FDC500) 100.0 kWFDC 1060 KXZE1 (FDC500+FDC560) 106.0 kWFDC 1120 KXZE1 (FDC560+FDC560) 112.0 kW

Total length: 1000 m

max. 10 m (equalisation pipe oil)

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)

** Comply with installation conditions. For details, refer to the Technical Manual.

max. 0.4 m

Max height difference between IUs 18 m

Outdoor unit

max. 5 m

Indoor unit

Indoor unit

Indoor unit

Up to the first branch pipe: max 130 m

Furthest IU 160 m

From the first branch pipe to the furthest IU: 90 m*

Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)

Operating range

Combinations

Modular outdoor units

Heat pumpVRF Multi system KXZ ADVANCED series

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 3. Value measured according to harmonised standard EN14511.

Models FDC735KXZE1 FDC800KXZE1 FDC850KXZE1 FDC900KXZE1 FDC950KXZE1 FDC1000KXZE1 FDC1060KXZE1 FDC1120KXZE1

CombinationsFDC335KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1

- - - - - - - -Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 73.50 80.00 85.00 90.00 95.00 100.00 106.00 112.00Cool. power consumption kW 19.92 21.92 24.94 27.96 27.96 27.94 30.59 33.24Rated energy efficiency coefficient in Cool. EER3 3.69 3.65 3.41 3.22 3.40 3.58 3.47 3.37Nominal Heat. capacity kW 82.50 90.00 95.00 100.00 106.00 112.00 119.00 126.00Heat. power consumption kW 19.73 21.38 23.19 25 26 26.98 29.44 31.9Rated energy efficiency coefficient in Heat. COP3 4.18 4.21 4.10 4.00 4.08 4.15 4.04 3.95Rated current in Cool. A 32.10 35.00 39.90 44.80 45.20 45.20 49.50 53.80Rated current in Heat. A 32.30 35.00 37.90 40.80 42.00 43.60 47.60 51.60

Indoor System Units Number of connectable IU from 2 to 63 from 2 to 69 from 2 to 73 from 2 to 78 from 2 to 80 from 2 to 80 from 2 to 80 from 2 to 80Total connectable capacity* 368 ~ 955 400 ~ 1040 425 ~ 1105 450 ~ 1170 475 ~ 1235 500 ~ 1300 530 ~ 1378 560 ~ 1456

Net weight kg 589 634 634 634 740 740 740 740

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 5/8” (15.88) Liquid side: ø19.05 (3/4”)mm (inch) Gas side: ø31.75 (1.1/4”) (ø34.92 (1.3/8”) Gas side: ø38.1 (1.1/2”) (ø34.92 (1.3/8”)

Oil equalisation mm (inch) ø 3/8” (9.52)

26~40HP (73.5~112.0 kW)

Page 33: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

112

Connect up to 80 indoor units/130% capacity

FDC 1200 KXZE1 (FDC400+FDC400+FDC400) 120.0 kWFDC 1250 KXZE1 (FDC400+FDC400+FDC450) 125.0 kWFDC 1300 KXZE1 (FDC400+FDC450+FDC450) 130.0 kWFDC 1350 KXZE1 (FDC450+FDC450+FDC450) 135.0 kWFDC 1425 KXZE1 (FDC475+FDC475+FDC475) 142.5 kW

› Maximum energy efficiency: COP 4.21 (42HP)

› Only DC Inverter compressors

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

FDC 1450 KXZE1 (FDC475+FDC475+FDC500) 145.0 kWFDC 1500 KXZE1 (FDC500+FDC500+FDC500) 150.0 kWFDC 1560 KXZE1 (FDC500+FDC500+FDC560) 156.0 kWFDC 1620 KXZE1 (FDC500+FDC560+FDC560) 162.0 kWFDC 1680 KXZE1 (FDC560+FDC560+FDC560) 168.0 kW

Total length: 1000 m

max. 10 m (equalisation pipe oil)

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)** Comply with installation conditions. For details, refer to the Technical Manual.

max. 0.4 m

Max height difference between IUs 18 m

Outdoor unit

max. 5 m

Indoor unit

Indoor unit

Indoor unit

Up to the first branch pipe: max 130 m

Furthest IU 160 m

From the first branch pipe to the furthest IU: 90 m*

Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)

Operating range

Combinations

Modular outdoor units

Heat pumpVRF Multi system KXZ ADVANCED series

Models FDC1200KXZE1 FDC1250KXZE1 FDC1300KXZE1 FDC1350KXZE1 FDC1425KXZE1 FDC1450KXZE1 FDC1500KXZE1 FDC1560KXZE1 FDC1620KXZE1 FDC1680KXZE1

CombinationsFDC400KXZE1 FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC475KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1FDC400KXZE1 FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1FDC400KXZE1 FDC450KXZE1 FDC450KXZE1 FDC450KXZE1 FDC475KXZE1 FDC500KXZE1 FDC500KXZE1 FDC560KXZE1 FDC560KXZE1 FDC560KXZE1

Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 120.00 125.00 130.00 135.00 142.5 145.00 150.00 156.00 162.00 168.00Cool. power consumption kW 32.88 35.9 38.92 41.94 41.94 41.93 41.91 44.56 47.21 49.86Rated energy efficiency coefficient in Cool. EER3 3.65 3.48 3.34 3.22 3.40 3.46 3.58 3.50 3.43 3.37Nominal Heat. capacity kW 135.00 140.00 145.00 150.00 159.00 162.00 168.00 175.00 182.00 189.00Heat. power consumption kW 32.07 33.88 35.69 37.5 39 39.49 40.47 42.93 45.39 47.85Rated energy efficiency coefficient in Heat. COP3 4.21 4.13 4.06 4.00 4.08 4.10 4.15 4.08 4.01 3.95Rated current in Cool. A 52.50 57.40 62.30 67.20 67.80 67.80 67.80 72.10 76.40 80.70Rated current in Heat. A 52.50 55.40 58.30 61.20 63.00 63.80 65.40 69.40 73.40 77.40

Indoor System Units Number of connectable IU from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80Total connectable capacity* 600 ~ 1560 625 ~ 1625 650 ~ 1690 675 ~ 1755 713 ~ 1852 725 ~ 1885 750 ~ 1950 780 ~ 2080 810 ~ 2106 840 ~ 2184

Net weight kg 951 951 951 951 1110 1110 1110 1110 1110 1110

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø19.05 (3/4”)mm (inch) Gas side: ø38.1 (1.1/2”) (ø34.92 (1.3/8”)

Oil equalisation mm (inch) ø 3/8” (9.52)

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 3. Value measured according to harmonised standard EN14511.

42~60HP (120.0~168.0 kW)

Page 34: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

113

Page 35: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

114

FDC 224 KXZXE1 22.4 kWFDC 280 KXZXE1 28.0 kWFDC 335 KXZXE1 33.5 kW

› Maximum energy efficiency: COP 4.61 (10HP)

› Only DC Inverter compressors

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

Connect up to 44 indoor units/200% capacity Connects up to 80 indoor units/160% (FDC 450 KXZE1 200%) capacity

Combinations 16~36HP (45.0~67.0 kW)

FDC 450 KXZXE1 (FDC224+FDC224)FDC 500 KXZXE1 (FDC224+FDC280)FDC 560 KXZXE1 (FDC280+FDC280)FDC 615 KXZXE1 (FDC280+FDC335)FDC 670 KXZXE1 (FDC335+FDC335)FDC 735 KXZXE1 (FDC224+FDC224+FDC280)FDC 800 KXZXE1 (FDC224+FDC280+FDC280)FDC 850 KXZXE1 (FDC280+FDC280+FDC280)FDC 900 KXZXE1 (FDC280+FDC280+FDC335)FDC 950 KXZXE1 (FDC280+FDC335+FDC335)FDC 1000 KXZXE1 (FDC335+FDC335+FDC335)

45.0 kW50.0 kW56.0 kW61.5 kW67.0 kW73.5 kW80.0 kW85.0 kW90.0 kW95.0 kW100.0 kW

Total length: 1000 m

max. 10 m (equalisation pipe oil)

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m (MAX 85 m)

** Comply with installation conditions. For details, refer to the Technical Manual.

max. 0.4 m

Max height difference between IUs 18 m

Outdoor unit

max. 5 m

Indoor unit

Indoor unit

Indoor unit

Up to the first branch pipe: max 130 m

Furthest IU 160 m

From the first branch pipe to the furthest IU: 90 m*

Splitting height difference50 m (outdoor unit higher) –> 70 m**40 m (outdoor unit lower)

Operating range

CHARACTERISTICS Hi-COP

› High efficiency

› Low consumption

› High energy savings

VRF Multi system KXZX Hi-COP series

Modular outdoor units

Heat pump

FDC 224 KXZXE1 FDC 280~335 KXZXE1

8~12 HP (22.4~33.5 kW)

Page 36: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

115

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%.

Combinations

VRF Multi system KXZX Hi-COP series

Models FDC224KXZXE1 FDC280KXZXE1 FDC335KXZXE1Nominal Cool. capacity kW 22.40 28.00 33.50Cool. power consumption kW 4.98 6.95 8.68Seasonal energy efficiency index in Cool. SEER2 7.58 7.27 7.41Rated energy efficiency coefficient in Cool. EER3 4.50 4.03 3.86Nominal Heat. capacity kW 25.00 31.50 37.50Heat. power consumption kW 5.56 6.83 8.39Seasonal energy efficiency index in Heat. SCOP2 4.86 4.91 4.86Rated energy efficiency coefficient in Heat. COP3 4.50 4.61 4.47Power Three-phase- 380-415V 50HzRated current in Cool. A 8.7 11.7 14.7Rated current in Heat. A 9.6 11.7 14.3Sound level dB(A) 56 56 62External dimensions (hxlxd) mm 1690×1350×720 2048×1350×720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 280 325 325Refrigerant circuit/Compressor type and qty. GTC5150NC47LF×1 GUC5185ND47V×1Motor kW 3.23*1 4.60*1 5.72*1Starting method Direct, in line

Indoor System Units Number of connectable IU from 1 to 29 from 1 to 37 from 1 to 44Total connectable capacity* 180 ~ 448 224 ~ 560 268 ~ 670

Crankcase heater W 33*1 40*1 40*1Refrigerant circuit/Heat exchanger Pipes finned with Blue fin treatment and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP4 R410A/2088Quantity kg 11 11.5 11.5Tons of CO2 equivalent 22.97 24.01 24.01Refrigerant oil l 2.25 (M-MA32R) 2.9 (M-MA32R)Defrost control Micro -computerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386×2Starting method DirectAir flow (Standard) m3h 13200 13200 16800Available static pressure Pa Max 50Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 3/8” (9.52) Liquid side ø 3/8” (9.52) Liquid side φ12.7 (1/2”)Gas side: ø19.05 (3/4”) Gas side ø 7/8” (22.22) Gas side: ø25.4 (1”) (ø22.22 (7/8”))

Joining method Gas side: brazing / Liquid side: flareCondensate drain Drain holes: ø20 × 10pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - - -

2. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.3. Value measured according to harmonised standard EN14511.4. Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a

refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%.3. Value measured according to harmonised standard EN14511.

Models FDC450KXZXE1 FDC500KXZXE1 FDC560KXZXE1 FDC615KXZXE1 FDC670KXZXE1 FDC735KXZXE1

CombinationsFDC224KXZXE1 FDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC224KXZXE1FDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC335KXZXE1 FDC224KXZXE1

- - - - - FDC280KXZXE1Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 45.00 50.00 56.00 61.50 67.00 73.50Cool. power consumption kW 10 11.8 13.9 15.6 17.4 17.1Rated energy efficiency coefficient in Cool. EER3 4.50 4.24 4.03 3.94 3.85 4.30Nominal Heat. capacity kW 50.00 56.0 63.0 69.00 75.00 82.50Heat. power consumption kW 11.1 12.3 13.7 15.2 16.8 18.2Rated energy efficiency coefficient in Heat. COP3 4.50 4.55 4.60 4.54 4.46 4.53Rated current in Cool. A 17.50 20.00 23.50 26.40 29.30 29.40Rated current in Heat. A 19.20 21.20 23.30 26.00 28.60 31.40

Indoor System Units Number of connectable IU from 2 to 60 from 2 to 53 from 2 to 59 from 2 to 65 from 2 to 71 from 3 to 78Total connectable capacity* 360 ~ 900 400 ~ 800 448 ~ 896 492 ~ 984 536 ~ 1072 588 ~ 1176

Net weight kg 560 605 650 650 650 885

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 1/2” (12.7) Liquid side ø 5/8” (15.88) Liquid side ø 1/2” (12.7) Liquid side ø 5/8” (15.88)mm (inch) Gas side: ø28.58 (1.1/8”) Gas side: ø31.75 (1.1/4”) (ø34.92 (1.3/8”)

Oil equalisation mm (inch) ø 3/8” (9.52)

Models FDC800KXZXE1 FDC850KXZXE1 FDC900KXZXE1 FDC950KXZXE1 FDC1000KXZXE1

CombinationsFDC224KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1FDC280KXZXE1 FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC335KXZXE1FDC280KXZXE1 FDC280KXZXE1 FDC335KXZXE1 FDC335KXZXE1 FDC335KXZXE1

Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 80 85.0 90 95.0 100.0Cool. power consumption kW 19.3 21.1 22.7 24.3 25.9Rated energy efficiency coefficient in Cool. EER3 4.15 4.03 3.96 3.91 3.86Nominal Heat. capacity kW 90.0 95.0 100 106.0 112.0Heat. power consumption kW 19.7 20.6 21.9 23.5 25.1Rated energy efficiency coefficient in Heat. COP3 4.57 4.61 4.57 4.51 4.46Rated current in Cool. A 32.90 35.60 38.40 41.00 43.70Rated current in Heat. A 33.50 35.20 37.40 40.10 42.80

Indoor System Units Number of connectable IU from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80 from 3 to 80Total connectable capacity* 640 ~ 1280 680 ~ 1360 720 ~ 1440 760 ~ 1520 800 ~ 1600

Net weight kg 930 975 975 975 975

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø 5/8” (15.88)mm (inch) Gas side: ø31.75 (1.1/4”) (ø34.92 (1.3/8”) Gas side: ø38.1 (1.1/2”)

Oil equalisation mm (inch) ø 3/8” (9.52)

Page 37: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

116

Diagrams and measurementsAll measurements are in mm.

rear

View of refrigerant connections

References for the dimensions of the holes of the fixing bolts

Incoming air

D (bottom)

C (front) C (right)

D (right)

C (rear)

D (front)

Label with instructions

Box for power cable wiring

Box for signal cable wiring

7-segment displayinspection hole

D (left)

C (bottom)

Drain pipe

Installation spaces

H3

H4H1Intake

Intake

Intak

e

H2

Intake

Notes:(1) Secure the unit using anchor bolts(2) Allow at least 2 m clearance above the unit(3) The adhesive label with the installation data should be positioned under the front panel (right side)(4) The inlet openings for the electrical and refrigerant connections are pre-cut (open using a cutter)(5) For the piping inlet, use the ø 88 hole(6) Use the fixing holes (M10) indicated with “L” and “J” when replacing an outdoor unit belonging to the old series(7) Connect the refrigerant oil compensation pipe (“K”) when using in combination with the outdoor unit

Ref. Item FDC224KXZXE1A Gas side pipe fitting ø 19.05 (3/4”) (brazing)B Liquid side pipe fitting ø 9.52 (3/8”) (flare)C Refrigerant pipe outlet ø 88 (or ø 100)D Power cable inlet ø 50 (right - left - front), slot 40 x 80 (at bottom)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 4 5 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) flareL Opening for movement 230 x 60

Example of installationDimensions 1 2

L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open

Modular outdoor units

Heat pumpVRF Multi system KXZX Hi-COP series

FDC 224 KXZXE1

Page 38: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

117

Diagrams and measurementsAll measurements are in mm.

rearView of refrigerant connections

References for the dimensions of the holes of the fixing boltsIncoming air

D (bottom)

C (front) C (right)

D (right)

C (rear)

D (front)

Label with instructions

Box for power cable wiring

Box for signal cable wiring

7-segment displayinspection hole

D (left)

C (bottom)

Drain pipe

Installation spaces

H3

H4H1Intake

Intake Intak

e

H2

Intake

Notes:(1) Secure the unit using anchor bolts(2) Allow at least 2 m clearance above the unit(3) The adhesive label with the installation data should be positioned under the front panel (right side)(4) The inlet openings for the electrical and refrigerant connections are pre-cut (open using a cutter)(5) For the piping inlet, use the ø 88 hole(6) Use the fixing holes (M10) indicated with “L” and “J” when replacing an outdoor unit belonging to the old series(7) Connect the refrigerant oil compensation pipe (“K”) when using in combination with the outdoor unit

Ref. Item FDC280KXZXE1 FDC335KXZXE1A Gas side pipe fitting ø 22.22 (7/8”) (brazing) ø 25.4 (1”) (brazing)B Liquid side pipe fitting ø 9.52 (3/8”) (flare) ø 12.7 (1/2”) (flare)C Refrigerant pipe outlet ø 88 (or ø 100)D Power cable inlet ø 50 (right - left - front), slot 40 x 80 (at bottom)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) flareL Opening for movement 230 x 60

Example of installationDimensions 1 2

L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open

VRF Multi system KXZX Hi-COP series

FDC 280~335 KXZXE1

Page 39: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

118

VRF Multi system KXZR 3-PIPE seriesHeat recovery

Simultaneous heating and coolingThese heat recovery systems work with 3 interconnecting pipes and therefore are commonly referred to as "3-pipe" systems. These systems offer both heating and cooling in a single indoor unit, based on the room conditions/requirements. The systems incorporate a highly sophisticated air conditioning control for multiple indoor areas, regardless of the cooling or heating needs, for applications where the building orientation (N, S, E, W) may result in a heat increase/loss on different sides of the same building.The range starts from a cooling capacity of 22.4 kW and goes up to 20HP with a cooling capacity of 56.0 kW. The outdoor units can also be combined in "pairs" or in "triple combination", reaching 60 HP/168.0 kW on a single system.

During defrost or during automatic compressor protection, activated every hour during heating, the heating operation stops and restarts temporarily after a specific time interval. The series is equipped with the same automatic compressor protection even in cooling mode. During this protection period, only the air flow is active and the cooling operation restarts at the end of a specific time interval.

DESIGN FLEXIBILITYTotal power of the indoor units

HP KXZR8~16 200%

17~34 160%36~60 130%

HP KXZRX16 200%

18~34 160%36 130%

• Where total power is higher than 130%, an additional refrigerant charge is required on site.

* With 8-34HP systems, if one or more of the FDK, FDFL, FDFU and/or FDFW series are connected to the system, the total power of the indoor units cannot exceed 130%.

Connectable indoor unitsIt is possible to connect up to 80 indoor units to the outdoor unit of greater power size. 16 different types of indoor units are available, visible or recessed, in different sizes, for a total of 91 overall possibilities.

Heat recovery systems

The KXZR series has an an extensible system design, considering a heating range at low temperature conditions down to -20°C, and a cooling range up to 46°C (previous model: 43°C).

HEATING

Cooling

The interconnection piping system has a unique arrangement with two of the interconnecting pipes passing through an PFD distribution controller and the third tube connected directly to each indoor unit from the main pipe path. This reduces installation times and the number of braze-welded connections on the site. The PFD distribution controllers are available for single connection or as a 4-way combined PFD connection, with each connected unit characterised by independent cooling or heating.

Outdoor unit

Wide operating range

CompressorAccumulator

Balanced cooling and heating operationReceiver

High pressure gas

Low pressure gas

Indoor unit Indoor unit Indoor unit Indoor unit

Flow divider

This model is not suitable for the use of annual cooling operations, for example for the server room, especially in areas where the outdoor air temperature falls below 5°C. In case of mixed operation in cooling and heating with outdoor air temperature lower than 5°C, the cooling power can decrease with respect to the operating power in cooling mode only.

NEW

Page 40: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

119

VRF Multi system KXZR 3-PIPE seriesHeat recovery

Continuous control of the heating power reduces compressor frequency by modulating it at the minimum speed for a longer period of time. The total number of defrost cycles is considerably reduced, increasing the total power delivered and ensuring high comfort.

Improved cooling capacity at low outdoor temperatureThe small partitions of the exchanger and the internal pressure control allow the outdoor unit to operate in cooling mode even in low ambient temperature conditions, for greater capacity in very low environmental conditions (-5°C) compared to the previous model.

2-partition heat plate exchanger

KXZRE1

Exchanger resizing allows for better control of the pressure at low load regimes.

In the previous model, in the presence of a strong heating demands and simultaneous low cooling demands in low ambient temperature conditions, the pressure control is adjusted to maintain a greater heating power compared to a sufficient cooling power.The new heat exchanger and pressure control adopted in the KXZR series has simultaneously improved its capacity for both heating and cooling power *. * The cooling system has priority for the required heating mode compared to a very low cooling demand, where most of the indoor units are used in heating mode.

previous model

KXZRE1

Time

During simultaneous cooling and heating at an outside temperature of -5°C.

Continuous heating up to 5 hours without outside temperature constraints

CONTINUOUS HEATING POWER CONTROL

Delivery air temperature in the cooled room

Output temperature from indoor units °C

defrost defrost defrost

Traditional control

Output temperature from indoor units °C

defrost defrost

Continuous control of heating power and overall increase of supplied power

Output temperature from indoor units °C

Imperceptible temperature oscillation

300 minutes

Previous mode

The 4-partition heat exchanger reduces dimensions.

Page 41: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

120

DIS-22-1-RG(RB)DIS-180-1-RG(RB)

DOS-2A-3-R

Single outdoor unit

YES

vertical

horizontal

floor

floor

floor

floor

NO

NO

YESBranch pipes Manifolds

HP 8 10 12 14 16 17 18 20 22 24 26 28 30 32 34 36 38 40 42 44 46 48 50 52 54 56 58 60Liquid side

Furthest IU =<90 m

ø 9.52 ø 12.7 ø 15.88 ø 19.05Intake gas ø 19.05 ø 22.22 ø 28.58 ø 34.92Delivery gas ø 15.88 ø 19.05 ø 22.22 ø 28.58Liquid side

Furthest IU => 90 m

ø 12.7 ø 15.88 ø 19.05 ø 22.22Intake gas ø 22.22 ø 28.58 ø 34.92Delivery gas ø 15.88 ø 19.05 ø 22.22 ø 28.58

If the longest distance (measured between the outdoor unit and the furthest indoor unit) is 90 m or more (actual length), change the size of the main pipe according to the following table.

Even if the longest distance exceeds 90 m (actual length), it is not necessary to change the size of the exhaust gas pipes.

Heat recoveryVRF Multi system KXZR 3-PIPE series

REFRIGERANT CONNECTIONSVRF-T systems are manufactured to the highest standards of quality and reliability and it is therefore essential for the installation procedures and materials to have the same qualitative features, to ensure trouble-free long-term operation. It is advisable to use high quality copper refrigerant piping, in coils or in straight, semi-rigid lengths. The copper piping should be chosen considering the higher operating pressure of R410A refrigerant gas and the increased pressure circulating in the system produced by reverse cycle operation. All materials used must comply with European standards (EN 12735). The branch pipe kits supplied must be used to connect the indoor units and the manifold kits must be used to connect the outdoor units (if necessary). It is forbidden to use standard accessories (elbow pipes, T-joints etc.). The branch pipes must be installed according to manufacturer guidelines and must allow a continuous flow of refrigerant in accordance with European standard E378:2017.All connecting welds must be made under slight nitrogen pressure to prevent the oxidation of the inner surface of the copper pipes. During installation, no accidental entry of condensate, dust or any other contaminant must be permitted. Once installation is complete, a leak test must be carried out to check for refrigerant leaks with pressurised nitrogen. The ends of the pipe must be bent and welded and an appropriate service valve affixed.

Additional refrigerant chargeOnly R410A refrigerant gas must be used, and this must be added by weight using an electronic meter. The amount of additional refrigerant must be carefully calculated according to the manufacturer’s guidelines, defined by the length and diameter of each section of the system piping.

NEW

Page 42: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

121

DOS-2A-3-R DOS-2A-3-R

Combined outdoor units

First branch pipe of the indoor unitTotal capacity of indoor units

Set of branch pipes

~179 DIS-22-1-RG(RB)180~370 DIS-180-1-RG(RB)371~539 DIS-371-2-RG(RB)540~ DIS-540-2-RG

Set of outdoor unit branch pipesOutdoor unit Set of branch pipes2 units (for 735 ~ 1120) DOS-2A-3-R3 units (for 1200 ~ 1680) DOS-3A-3-R

Downstream of the PFDTotal capacity of indoor units

Set of branch pipes

~179 DIS-22-1-G(B)180~370 DIS-180-1-G(B)371~539 DIS-371-1-G(B)540~ DIS-540-3

Refrigerant oil compensation pipe Refrigerant oil compensation

pipe

ELECTRICAL CONNECTIONSVRF MHI systems require highly simplified electrical connections to the indoor units, thanks to a control circuit that uses 2 non-polarised conductors. The supply system has wiring that can be connected on the front, right, left or rear of the outdoor unit. For three-phase outdoor units and single phase indoor units, a separate power supply must be used. The interaction between the outdoor unit and indoor unit takes place via the control device only.

Outdoor unit power supply: three-phase, 4 wires, 380~415V Separate power system

Outd

oor u

nitEarth leakagebreaker

Circuitbreaker Ground

A Main power supply cable (4 wires)B Signal lines - Superlink (2 wires)C Indoor units power cable (2 wires)D Cables for the wired remote control (2 wires)

Earth leakagebreaker

Circuitbreaker

Indoor unit

wired remote control

Indoor unit power supply: single phase 220~240V

IMPORTANT: if the RCD is dedicated solely to protecting against leakage to earth, it will be necessary to install a circuit breaker.

VRF Multi system KXZR 3-PIPE seriesHeat recovery

REFRIGERANT CONNECTIONS

Page 43: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

122

PFD 1124-E, PFD 1804-E, PFD 2804-E, PFD 1124X4-E

Designed and manufactured at Mitsubishi Heavy Industries specialist research laboratories, the PFD flow divider now enables all indoor units to be integrated into an air conditioning network, to switch from cooling mode to heating mode, or vice versa, while the whole system remains operational, thus preventing costly power on and power off cycles. In case of conversion from cooling mode to heating mode and vice versa, by simply combining the indoor unit and the PFD box, the sound level is reduced, thanks to the shutdown of the compressor which, however, does not lead to any reduction in capacity. The risk of refrigerant leaks is reduced by changing the welding method between the refrigerant piping and the PFD box. By using the optional extension cable for the PFD box, equipped with a connector, it is possible to further separate the PFD box from the indoor unit. This enables a reduction in sound level caused by the PDF box and the flow of refrigerant.

Relay kit4-outlet PFD

FLOW DIVIDER

Heat recoveryVRF Multi system KXZR 3-PIPE series

ELECTRICAL CONNECTIONS

The maximum number of indoor units that can be connected to a signal line is 128, and it is possible to create groups of outdoor and/or indoor units connected to the same outdoor unit or to separate outdoor units, as long as they are connected to the same signal line. The signal line can also be connected by adopting the method described below (multiple connectors).

0.75 mm2 1.25 mm2~1000 mm YES YES

1000~1500 mm YES NO

Signal lineSingle outdoor unit

Combined outdoor units

OU signal terminal board

IU signal terminal board

The signal lines have no polarity therefore the connections listed below are permitted

Signal lines

The signal line is 5 VDC and uses 2 non-polarised conductors marked A1 and B1. AB connects the outdoor unit to the indoor unit and vice versa. For the signal line with 2 conductors, use shielded cables measuring 0.75 or 1.25 mm2. Earth the shield on all the indoor

and outdoor units.If using combined outdoor units, connect:• Thesignallinebetweenindoorand

outdoor units, and the signal line between outdoor units that belong to the same

refrigerant line, to A1 and B1;• Thesignallinebetweenoutdoor

units belonging to a different refrigerant line to A2 and B2.

OU OU OU

IU

IU

IU

IU

IMPORTANT: A loop connection of the signal lines is NOT ALLOWED

A loop cannot be formed with the signal, therefore the section of the connection indicated with ........is not permitted

OU

IU

OUOUOU

IUIUIU

OU

IU

OU OU

IU IU

IU IU IU

Length (m) Type of cables100~200 0.5 mm2 x 2 wires

~300 0.75 mm2 x 2 wires~400 1.25 mm2 x 2 wires~600 2.0 mm2 x 2 wires

The specifications for the connection between the wired remote control and the indoor units (XY connection) are 0.3 mm2 x 2 wires. The maximum permitted length is 600 m. If the length exceeds 100 m, refer to the table.

Wired remote control

NEW

Page 44: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

123

PFD 1124-E, PFD 1804-E, PFD 2804-E, PFD 1124X4-E

PFD

240V AC

kit

220/240V AC 12V DC

SC-SL1N/2NA/4-AE

FLOW DIVIDER

The remote control settings (such as power on/off of single indoor units, temperature setting, as well as controlling the heating/cooling procedures) are possible via a remote control connected to each indoor unit. At the same time, together with the individual remote control, the SC-SL1N/2NA/4-AE centralised control panels can also be used. For more details, refer to the Installation Manual.

Selection and control from centralised panel

Ease of installationThe design PFD flow divider makes it possible to connect the liquid line of the indoor unit directly from the liquid piping coming from the outdoor unit, therefore bypassing the PFD. This reduces the number of connections per indoor unit and, consequently, installation times and costs. Groups of indoor units up to a total capacity of 44.8 kW (11.2 kW x 4) can be connected to a single PFD by means of branch pipes, therefore the units in this group will all operate in the same mode,cooling or heating. The PFD1124X4-E 4-pipe control device, able to connect up to 4 indoor units with individual operation - simultaneous cooling or heating - is also available. The PFD flow divider is connected to the indoor unit with a 3-wire signal cable via a relay kit (supplied) to be installed within a maximum distance of 2 metres. The indoor unit, on the other hand, can be installed up to a distance of 40 m. The PFD electric power supply may derive directly from the indoor unit or from other sources.

IU

up to 2 m

the maximum distance between the PFD and the IU cannot exceed 40 m

PFD Relay

OU

IU

Delivery gas side

Intake gas side

Gas side

Liquid side

Flow divider Total IU power downstream Indoor units that can be connected*PFD1124-E less than 11.2 kW 1-5PFD1804-E less than 18.0 kW 1-8PFD2804-E less than 28.0 kW 1-10

PFD1124X4-E less than 44.8 kW (11.2 kW x 4) up to 20

VRF Multi system KXZR 3-PIPE seriesHeat recovery

* Refer to the technical manuals for specifications.

Page 45: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

124

Connects up to 44 indoor units/200% capacity

FDC 224 KXZRE1 22.4 kWFDC 280 KXZRE1 28.0 kWFDC 335 KXZRE1 33.5 kW

› Maximum energy efficiency: COP 4.84

› The units use a Multi-port DC Inverter compressor with concentrated electric winding

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

Heat recoveryModular outdoor units

VRF Multi system KXZR 3-PIPE series

Models FDC224KXZRE1 FDC280KXZRE1 FDC335KXZRE1Nominal Cool. capacity kW 22.40 28.00 33.50Cool. power consumption kW 5.15 8.08 9.98Seasonal energy efficiency index in Cool. SEER1 6.27 6.11 7.00Rated energy efficiency coefficient in Cool. EER2 4.35 3.47 3.36Nominal Heat. capacity kW 22.40 31.50 37.50Heat. power consumption kW 4.62 8.11 9.55Seasonal energy efficiency index in Heat. SCOP1 4.06 4.02 4.84Rated energy efficiency coefficient in Heat. COP2 4.85 3.88 3.93Power Three-phase- 380-415V 50HzRated current in Cool. A 9.00 12.90 15.90Rated current in Heat. A 8.00 12.80 15.50Sound pressure level dB(A) 55 55 61Sound power level dB(A) 73 74 81External dimensions (HxLxD) mm 1690x1350x720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.1) equivalentNet weight kg 289 289 289Refrigerant circuit/Compressor type and qty. GTC5150NC47LFMotor kW 3.41x1 4.80x1 6.54x1Starting method Direct, in line

Indoor System Units Number of connectable IU from 1 to 29 from 1 to 37 from 1 to 44Total connectable capacity 112 - 448 140 - 560 167 - 670

Crankcase heater W 33x1Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP3 R410A/2088Quantity kg 11.50 11.50 11.50Tons of CO2 equivalent 24.01 24.01 24.01Refrigerant oil l 2.35 (M-MA32R)Defrost control ComputerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386x2Starting method DirectAir flow (Standard) m3h 13200 16800Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protectionDiameter cooling/refrigerant pipesLiquid side mm (inch) ø9.52 (3/8”) ø12.7 (1/2”)Delivery gas line mm (inch) ø19.05 (3/4”) ø22.22 (7/8”) ø25.4 (1”) (ø22.22 7/8”)Intake gas line mm (inch) ø15.88 (5/8”) ø19.05 (3/4”)Joining method Gas side brazing / Liquid side flareCondensate drain Drain holes ø20 x 6pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - - -

1. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.2. Value measured according to harmonised standard EN14511.3.Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a

refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.

NEW

8~12HP (22.4~33.5 kW)

Page 46: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

125

Operating rangeTotal length: 1000 m

Outdoor unit

Up to the first branch pipe: max 130 m

Indoor unit

Indoor unit

Indoor unitFrom the first branch pipe to the furthest IU: 90 m*

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.

Furthest IU 160 m

Max height difference between IUs 18 m

Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)

Diagrams and measurementsAll measurements are in mm.

(left)

(front)

(front)(right)

(right)

(right)

Label

7-segment display

bottomback - view of refrigerant connections

Box for signal cable wiring

Box for power cable wiring

Intak

e

IntakeInt

ake

Service spaces

Incoming air

Drain pipe

H1

H3

H4H2

Example of installation

Dimensions 1 2L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open

Ref. Item 224 280 335A Intake gas piping connection ø 19.05 (3/4")(brazing) ø 22.22 (7/8")(brazing) ø 25.4 (1”) (brazing)B Liquid side pipe fitting ø 9.52 (flare) ø 12.7 (flare)C Delivery gas piping connection ø 15.88 (3/8")(brazing) ø 19.05 (3/4")(brazing)D Power cable inlet ø 50 (right-left-front), 40x80 (lower side)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) (flare)L Opening for movement 230 x 60N Refrigerant pipe outlet ø 88 (or ø 100)

VRF Multi system KXZR 3-PIPE seriesNEW

Page 47: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

126

Connects up to 71indoor units and up to 160% capacity (200% for FDC 400~450)

› Maximum energy efficiency: COP 4.10

> The units use a Multi-port DC Inverter compressor with concentrated electric winding

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

FDC 400 KXZRE1 40.0 kWFDC 450 KXZRE1 45.0 kWFDC 475 KXZRE1 47.5 kW

FDC 500 KXZRE1 50.0 kWFDC 560 KXZRE1 56.0 kWFDC 615 KXZRE1 61.5 kW

FDC 670 KXZRE1 67.0 kW

Heat recoveryModular outdoor units

VRF Multi system KXZR 3-PIPE series

1. EU Regulation No.2281/2016 - - Value measured according to harmonised standard EN14825.2. Value measured according to harmonised standard EN14511.3.Refrigerant leakage contributes to climate change. When released into the atmosphere, refrigerants with a lower global warming potential (GWP) contribute less to global warming than those with a higher GWP. This appliance contains a

refrigerant with a GWP of 2088. If 1 kg of this refrigerant fluid were released into the atmosphere, therefore, the impact on global warming would be 2088 times higher than 1 kg of CO2, over a period of 100 years. Under no circumstances should the user try to intervene on the refrigerant circuit or disassemble the product. Always contact qualified personnel if necessary.

Models FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC615KXZRE1 FDC670KXZRE1Nominal Cool. capacity kW 40.00 45.00 47.50 50.00 56.00 61.50 67.00Cool. power consumption kW 11.55 14.45 14.82 15.19 18.31 21.35 25.51Seasonal energy efficiency index in Cool. SEER1 6.34 6.04 6.60 7.01 6.25 5.79 5.78Rated energy efficiency coefficient in Cool. EER2 3.46 3.11 3.21 3.29 3.06 2.88 2.63Nominal Heat. capacity kW 40.00 45.00 47.50 50.00 56.00 61.50 63.00Heat. power consumption kW 9.76 11.38 11.58 12.17 14.33 16.15 17.47Seasonal energy efficiency index in Heat. SCOP1 4.22 4.33 4.27 4.54 4.29 4.34 4.66Rated energy efficiency coefficient in Heat. COP2 4.10 3.95 4.10 4.11 3.91 3.81 3.61Power Three-phase- 380-415V 50HzRated current in Cool. A 18.50 23.20 24.00 24.60 29.60 34.60 41.30Rated current in Heat. A 16.00 18.60 18.80 19.70 23.20 26.20 28.30Sound pressure level dB(A) 60 62 61 61 64 65 65Sound power level dB(A) 81 82 81 81 84 84 84External dimensions (HxLxD) mm 2048x1350x720Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.1) equivalentNet weight kg 357 410Refrigerant circuit/Compressor type and qty. GUC5185ND47V GTC5150NC47LF×2Motor kW 7.92×1 9.73×1 4.53×2 4.84×2 5.79×2 7.05×2 9.87×2Starting method Direct, in line

Indoor System Units Number of connectable IU from 1 to 53 from 1 to 60 from 1 to 50 from 1 to 53 from 1 to 59 from 1 to 65 from 1 to 71Total connectable capacity 200 - 800 225 - 900 240 - 760 250 - 800 280 - 896 308 - 984 335 - 1172

Crankcase heater W 40 33×2Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveRefrigerant/GWP3 R410A/2088Quantity kg 11.50Tons of CO2 equivalent 24.01Refrigerant oil l 3.3 (M-MA32R) 4.4 (M-MA32R)Defrost control ComputerisedAir treatment/Fan type and quantity Axial fan x 2Motor W 386x2Starting method DirectAir flow (Standard) m3h 16800 18600Shock and vibration absorption Rubber vibration absorber (for compressor)Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protectionDiameter cooling/refrigerant pipesLiquid side mm (inch) ø12.7 (1/2”)Delivery gas line mm (inch) ø25.4 (1”) (ø28.58 1-1/8”) ø28.58 (1 - 1/8”)Intake gas line mm (inch) ø22.22 (7/8”) ø25.4 (1”) (ø22.22 7/8”)Joining method Gas side brazing / Liquid side flareCondensate drain Drain holes ø20 x 6pcs., ø45 x 3pcs.Piping insulation Necessary (on both sides, liquid and gas)Accessories - - - - - - -

NEW

14~24HP (40.0~67.0 kW)

Page 48: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

127

Operating rangeTotal length: 1000 m

Outdoor unit

Up to the first branch pipe: max 130 m

Indoor unit

Indoor unit

Indoor unitFrom the first branch pipe to the furthest IU: 90 m*

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.

Furthest IU 160 m

Max height difference between IUs 18 m

Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)

Diagrams and measurementsAll measurements are in mm.

rear

View of refrigerant connections

References for the dimensions of the holes of the fixing boltsIncoming air

D (bottom)

C (front) C (right)

D (right)

C (rear)

D (front)

Label with instructions

Box for power cable wiring

Box for signal cable wiring

7-segment displayinspection hole

D (left)

C (bottom)

Drain pipe

Installation spaces

H3

H4H1Intake

Intak

e

H2

Intake

Intake

Example of installation

Dimensions 1 2L1 500 openL2 10(30) 10(30)L3 100 100L4 10(30) openH1 1500 openH2 unlimited unlimitedH3 1000 unlimitedH4 unlimited open

Ref. Item 400 450 475 500 560 615 670A Intake gas piping connection ø 25.4 (1”) (brazing) ø 28.58 (1 - 1/8") (brazing)B Liquid side pipe fitting ø 12.7 (flare)C Delivery gas piping connection ø 22.22 (7/8")(brazing) ø 25.4 (1”) (brazing)D Power cable inlet ø 50 (right-left-front), 40x80 (lower side)F Fixing bolt hole M10 x 4 holesG Condensate drain pipe connection ø 45 x 3 holesH Condensate drain ø 20 x 10 holesK Refrigerant oil compensation pipe connection ø 9.52 (3/8”) (flare)L Opening for movement 230 x 60N Refrigerant pipe outlet ø 88 (or ø 100)

VRF Multi system KXZR 3-PIPE seriesNEW

Page 49: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

128

Operating rangeTotal length: 1000 m

Outdoor unit

Up to the first branch pipe: max 130 m

Indoor unit

Indoor unit

Indoor unitFrom the first branch pipe to the furthest IU: 90 m*

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.

Furthest IU 160 m

Max height difference between IUs 18 m

Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)

Connects up to 80 indoor units and up to 160% capacity (FDC 735~950) and up to 130% capacity (FDC 1000~1120)

› Maximum energy efficiency: COP 4.12› The units use a Multi-port DC Inverter compressor with concentrated electric winding

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

FDC 735 KXZRE1 (FDC335+FDC400) 73.5 kWFDC 800 KXZRE1 (FDC400+FDC400) 80.0 kWFDC 850 KXZRE1 (FDC400+FDC450) 85.0 kWFDC 900 KXZRE1 (FDC450+FDC450) 90.0 kW

FDC 950 KXZRE1 (FDC475+FDC750) 95.0 kWFDC 1000 KXZRE1 (FDC500+FDC500) 100.0 kWFDC 1060 KXZRE1 (FDC500+FDC560) 106.0 kWFDC 1120 KXZRE1 (FDC560+FDC560) 112.0 kW

Heat recoveryModular outdoor units

VRF Multi system KXZR 3-PIPE series

Combinations

1. Value measured according to harmonised standard EN14511.

Models FDC735KXZRE1 FDC800KXZRE1 FDC850KXZRE1 FDC900KXZRE1 FDC950KXZRE1 FDC1000KXZRE1 FDC1060KXZRE1 FDC1120KXZRE1

Combined units FDC335KXZRE1 FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1

Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 73.50 80.00 85.0 90.0 95.0 100.0 106.0 112.0Cool. power consumption kW 21.20 23.10 26.00 28.90 29.60 30.40 33.50 36.60Rated energy efficiency coefficient in Cool. EER1 3.47 3.46 3.27 3.11 3.21 3.29 3.16 3.06Nominal Heat. capacity kW 73.5 80.0 85 90.0 95.0 100.0 106.0 112.0Heat. power consumption kW 17.90 19.50 21.1 22.8 23.2 24.3 26.5 28.7Rated energy efficiency coefficient in Heat. COP1 4.11 4.10 4.03 3.95 4.09 4.12 4.00 3.90Rated current in Cool. A 34.30 37.00 41.70 46.40 48.00 49.20 54.20 59.20Rated current in Heat. A 29.30 32.00 34.60 37.20 37.60 39.40 49.20 46.40Net weight kg 646 714 714 714 820 820 820 820Diameter cooling/refrigerant pipesLiquid side mm (inch) ø15.88 (5/8”)Delivery gas line mm (inch) ø31.75 (1-1/4”) ø34.92 (1-3/8”) ø38.1 (1-1/2”) ø34.92 (1-3/8”)Intake gas line mm (inch) ø25.4 (1”) ø28.58 (1-1/8”) ø28.58 (1-1/8”) ø31.75 (1-1/4”) ø28.58 (1-1/8”)Oil equalisation mm (inch) ø9.52 (3/8”)Accessories -

NEW

26~40HP (73.5~112.0 kW)

Page 50: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

129

Operating rangeTotal length: 1000 m

Outdoor unit

Up to the first branch pipe: max 130 m

Indoor unit

Indoor unit

Indoor unitFrom the first branch pipe to the furthest IU: 90 m*

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.

Furthest IU 160 m

Max height difference between IUs 18 m

Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)

Connects up to 80 indoor units/130% capacity

› Maximum energy efficiency: COP 4.11

› The units use a Multi-port DC Inverter compressor with concentrated winding

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

FDC 1200 KXZRE1 (FDC400+FDC400+FDC400) 120.0 kWFDC 1250 KXZRE1 (FDC400+FDC400+FDC450) 125.0 kWFDC 1300 KXZRE1 (FDC400+FDC450+FDC450) 130.0 kWFDC 1350 KXZRE1 (FDC450+FDC450+FDC450) 135.0 kWFDC 1425 KXZRE1 (FDC475+FDC475+FDC475) 142.5 kW

FDC 1450 KXZRE1 (FDC475+FDC475+FDC500) 145.0 kWFDC 1500 KXZRE1 (FDC500+FDC500+FDC500) 150.0 kWFDC 1560 KXZRE1 (FDC500+FDC500+FDC560) 156.0 kWFDC 1620 KXZRE1 (FDC500+FDC560+FDC560) 162.0 kWFDC 1680 KXZRE1 (FDC560+FDC560+FDC560) 168.0 kW

Heat recoveryModular outdoor units

VRF Multi system KXZR 3-PIPE series

Models FDC1200KXZRE1 FDC1250KXZRE1 FDC1300KXZRE1 FDC1350KXZRE1 FDC1425KXZRE1 FDC1450KXZRE1 FDC1500KXZRE1 FDC1560KXZRE1 FDC1620KXZRE1 FDC1680KXZRE1

Combined unitsFDC400KXZRE1 FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1FDC400KXZRE1 FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1FDC400KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC450KXZRE1 FDC475KXZRE1 FDC500KXZRE1 FDC500KXZRE1 FDC560KXZRE1 FDC560KXZRE1 FDC560KXZRE1

Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 120.00 125.00 130.00 135.00 142.50 145.00 150.00 156.00 162.00 168.00Cool. power consumption kW 34.65 37.55 40.45 43.55 44.46 44.83 45.57 48.69 51.81 54.93Rated energy efficiency coefficient in Cool. EER1 3.46 3.33 3.21 3.10 3.21 3.23 3.29 3.20 3.13 3.06Nominal Heat. capacity kW 120.00 125.00 130.00 135.00 142.50 145.00 150.00 156.00 162.00 168.00Heat. power consumption kW 29.28 30.9 32.52 34.14 34.74 35.33 36.51 38.67 40.83 42.99Rated energy efficiency coefficient in Heat. COP1 4.10 4.05 4.00 3.95 4.10 4.10 4.11 4.03 3.97 3.91Rated current in Cool. A 55.50 60.20 64.90 69.60 72.00 72.60 73.80 78.80 83.80 88.80Rated current in Heat. A 48.00 50.60 53.20 55.80 56.40 57.30 59.10 62.60 66.10 69.60Net weight kg 1071 1071 1071 1071 1230 1230 1230 1230 1230 1230Diameter cooling/refrigerant pipesLiquid side mm (inch) ø19.05 (3/4”)Delivery gas line mm (inch) ø38.1 (1-1/2”) ø34.92 (1-3/8”)Intake gas line mm (inch) ø31.75 (1-1/4”) ø28.58 (1-1/8”)Oil equalisation mm (inch) ø9.52 (3/8”)Accessories - - - - - - - - - -

Combinations

1. Value measured according to harmonised standard EN14511.

NEW

42~60HP (120.0~168.0 kW)

Page 51: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

130

FDC 450 KXZRXE1 (FDC224+FDC224) 45.0 kWFDC 500 KXZRXE1 (FDC224+FDC280) 50.0 kWFDC 560 KXZRXE1 (FDC280+FDC280) 56.0 kW

FDC 615 KXZRXE1 (FDC280+FDC335) 61.5 kWFDC 670 KXZRXE1 (FDC335+FDC335) 67.0 kW

Connects up to 70 indoor units and up to 160% capacity (FDC 500~670) and up to 200% capacity (FDC 450)

› Maximum energy efficiency: COP 4.87

› The units use a Multi-port DC Inverter compressor with concentrated electric winding

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

Operating rangeTotal length: 1000 m

Outdoor unit

Up to the first branch pipe: max 130 m

Indoor unit

Indoor unit

Indoor unitFrom the first branch pipe to the furthest IU: 90 m*

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.

Furthest IU 160 m

Max height difference between IUs 18 m

Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)

VRF Multi system KXZRX Hi-COP seriesHeat recoveryModular outdoor units

Combinations

1. Value measured according to harmonised standard EN14511.

Models FDC450KXZRXE1 FDC500KXZRXE1 FDC560KXZRXE1 FDC615KXZRXE1 FDC670KXZRXE1

Combined units FDC224KXZRE1 FDC224KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1FDC224KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1 FDC335KXZRE1

Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 45.00 50.00 56.00 61.5 67.00Cool. power consumption kW 10.29 12.53 14.76 17.02 19.28Rated energy efficiency coefficient in Cool. EER1 4.37 3.99 3.79 3.61 3.48Nominal Heat. capacity kW 45.00 50.00 56.00 61.5 67.00Heat. power consumption kW 9.24 10.81 12.38 14.31 16.24Rated energy efficiency coefficient in Heat. COP1 4.87 4.63 4.52 4.30 4.13Rated current in Cool. A 18.00 21.20 24.40 28.00 31.60Rated current in Heat. A 16.00 18.30 20.60 23.60 26.60Net weight kg 578 578 578 578 578Diameter cooling/refrigerant pipesLiquid side mm (inch) ø12.7 (1/2”)Delivery gas line mm (inch) ø28.58 (1-1/8”)Intake gas line mm (inch) ø22.22 (7/8”) ø25.4 (1”) ø22.22 (7/8”)Oil equalisation mm (inch) ø9.52 (3/8”)Accessories -

NEW

16~24HP (45.0~67.0 kW)

Page 52: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

131

Operating rangeTotal length: 1000 m

Outdoor unit

Up to the first branch pipe: max 130 m

Indoor unit

Indoor unit

Indoor unitFrom the first branch pipe to the furthest IU: 90 m*

* With difference of length between the farthest indoor unit and the nearest one from the first branch pipe < 40 m.

Furthest IU 160 m

Max height difference between IUs 18 m

Splitting height difference50 m (outdoor unit higher) 40 m (outdoor unit lower)

Connects up to 80 indoor units and up to 160% capacity (FDC 735~950) and up to 130% capacity (FDC 1000)

› Maximum energy efficiency: COP 4.76› The units use a Multi-port DC Inverter compressor with concentrated winding

› High split: up to 1000 m in total and with a maximum distance between the OU and the furthest IU of 160 m

FDC 735 KXZRXE1 (FDC224+FDC224+FDC280) 73.5 kWFDC 800 KXZRXE1 (FDC224+FDC280+FDC280) 80.0 kWFDC 850 KXZRXE1 (FDC280+FDC280+FDC280) 85.0 kW

FDC 900 KXZRXE1 (FDC280+FDC280+FDC335) 90.0 kWFDC 950 KXZRXE1 (FDC280+FDC335+FDC335) 95.0 kWFDC 1000 KXZRXE1 (FDC335+FDC335+FDC335) 100.0 kW

Heat recoveryModular outdoor units

VRF Multi system KXZRX Hi-COP series

Combinations

1. Value measured according to harmonised standard EN14511.

Models FDC735KXZRXE1 FDC800KXZRXE1 FDC850KXZRXE1 FDC900KXZRXE1 FDC950KXZRXE1 FDC1000KXZRXE1

Combined unitsFDC224KXZRE1 FDC224KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1FDC224KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1 FDC335KXZRE1FDC280KXZRE1 FDC280KXZRE1 FDC280KXZRE1 FDC335KXZRE1 FDC335KXZRE1 FDC335KXZRE1

Power supply Three-phase- 380-415V 50HzNominal Cool. capacity kW 73.50 80.00 85.00 90.00 95.00 100.00Cool. power consumption kW 17.67 19.91 22.14 24.90 26.66 28.92Rated energy efficiency coefficient in Cool. EER1 4.16 4.02 3.84 3.61 3.56 3.46Nominal Heat. capacity kW 73.50 80.00 85.00 90.00 95.00 100.00Heat. power consumption kW 15.43 17 18.57 20.5 22.43 24.36Rated energy efficiency coefficient in Heat. COP1 4.76 4.71 4.58 4.39 4.24 4.11Rated current in Cool. A 30.20 33.40 36.60 40.20 43.80 47.40Rated current in Heat. A 26.30 28.60 30.90 33.90 36.90 39.90Net weight kg 867 867 867 867 867 867Diameter cooling/refrigerant pipesLiquid side mm (inch) ø15.88 (5/8”)Delivery gas line mm (inch) ø31.75 (1-1/4”) ø34.92 (1-3/8”) ø38.1 (1-1/2”) ø34.92 (1-3/8”)Intake gas line mm (inch) ø25.4 (1”) ø28.58 (1-1/8”) ø28.58 (1-1/8”)Oil equalisation mm (inch) ø9.52 (3/8”)Accessories - - - - - -

NEW

26~36HP (73.5~100.0 kW)

Page 53: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

132

FDC 224 KXZWE1 22.4 kWFDC 280 KXZWE1 28.0 kWFDC 335 KXZWE1 33.5 kW

Connect up to 33 indoor units/150% capacity

1) ENERGY SAVING Reduced operating costs

2) FLEXIBLE DESIGN• Compactdesign• Easytransportandinstallation

3) BMS (BUILDING MANAGEMENT SYSTEM) The same system for controlling the air-cooled system (KXZ)

4) SERVICE AND MAINTENANCE• Easyfrontaccesstothemainparts(compressor,control,

plate heat exchanger, etc.) • Widerangeofcontrolsoftwareandmaintenance

instruments (Mente PC, SL-Checker, etc.)

APPLICABLE ON:

• Skyscrapers 100 metres or higher• Glass façades; outside of

buildings Possibility to hide the

motocondensing unit

Outdoor engine room units (renovation projects)

Total length: 510 m

Engine room

Furthest IU 160 m

Cooling towerWater pipes

Up to the first branch pipe: max 130 m

From the first branch pipe to the furthest IU: 90 m

Max height difference between IUs 15 m

Height difference:40 m OU low

Height difference: 50 m

Outdoor units on every floor (new construction projects)

Total length: 510 m

Outdoor unit

Indoor unit

Furthest IU 160 m

Cooling tower

Refrigerant pipes

Water pipes

Water cooledOutdoor unit

VRF Multi system KXZW WATER series

FDC224~335KXZWE1

8~12 HP (22.4~33.5 kW)

Page 54: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

133

Ref. ItemA High/low gas side piping

Please see OU specifications for refrigerant pipes.

B Gas side inletC Liquid side pipingD Parallel oilF Incoming water R1 1/4”G Outgoing water R1 1/4”H Condensate drain outlet Rp 1/2”, 2 holesJ Electrical absorption ø 35K Signal cable absorption ø 35L Fixing bolt hole ø 18 x 4 holes

DimensionsFDC-KXZWE1

224, 280 335C1 142 139C2 322 316

DimensionsExample of installation

1L1 600 or moreL2 20 or moreL3 500 or moreL4 20 or moreL5 300 or more

Model FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1 Connection typeHigh/low gas side piping ø 19.05 (3/4”) ø 22.22 (7/8”) ø 25.4 (1”) BrazingGas side inlet ø 9.52 (3/8”) ø 9.52 (3/8”) ø 12.7 (1/2”)

FlangeLiquid side piping ø 9.52 (3/8”) ø 9.52 (3/8”) ø 9.52 (3/8”)

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 1. Value measured according to harmonised standard EN14511.

Models FDC224KXZWE1 FDC280KXZWE1 FDC335KXZWE1Nominal Cool. capacity* kW 22.40 28.00 33.50Cool. power consumption kW 4.23 5.75 8.13Rated energy efficiency coefficient in Cool. EER1 5.30 4.87 4.12Nominal Heat. capacity kW 25.00 31.50 37.50Heat. power consumption kW 4.24 5.10 6.30Rated energy efficiency coefficient in Heat. COP1 5.90 6.18 5.95Power Three-phase- 380-415V 50HzRated cool. current in A 7.14 9.64 13.40Rated heat. current in A 7.13 8.59 10.50Sound level dB(A) 48 50 52External dimensions (HxLxD) mm 1100 x 780 x 550 1100 x 780 x 550 1100 x 780 x 550Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 185

Indoor System Units Number of connectable IU from 1 to 22 from 1 to 28 from 1 to 33Total connectable capacity* 112 ~ 336 140 ~ 420 167 ~ 503

Crankcase heater W 33 x 1 33 x 1 33 x 1Refrigerant circuit/Heat exchanger Heat plate exchangerRefrigerant control Electronic expansion valveRefrigerant R410AQuantity kg 9.9Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 9.52 (3/8”) Liquid side: ø 12.7 (1/2”)Gas side: ø 19.05 (3/4”) Gas side: ø 22.22 (7/8”) Gas side: ø 25.4 (1”) [ø 22.22 (7/8”)]

Oil equalisation - - -Joining method Gas side: flange / Liquid side: flare

Water pipe diameterWater inlet R1 1/4”

Water outlet R1 1/4”Condensate outlet Rp 1/2” (internal threading)

wall

Pipes

(rear)

(front)

Label with instructions

Box for power cable wiring

Box for signal cable wiring

7-segment displayinspection hole

VIEW A

(Service space)

Installation space

wall

wallwall

Dimensions after pipe connection

Diagrams and measurementsAll measurements are in mm.

VRF Multi system KXZW WATER series

Page 55: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

134

Connect up to 80 indoor units/150% capacity

45.0 kW50.0 kW56.0 kW61.5 kW67.0 kW73.0 kW

FDC 775 KXZWE1 (FDC224+FDC280x2) FDC 850 KXZWE1 (FDC280x3)FDC 900 KXZWE1 (FDC280x2+FDC335)FDC 950 KXZWE1 (FDC280+FDC335x2)FDC 1000 KXZWE1 (FDC335x3)

FDC 450 KXZWE1 (FDC224x2)FDC 500 KXZWE1 (FDC224+FDC280)FDC 560 KXZWE1 (FDC280x2)FDC 615 KXZWE1 (FDC280+FDC335)FDC 670 KXZWE1 (FDC335x2)FDC 730 KXZWE1 (FDC224x2+FDC280)

77.5 kW 85.0 kW90.0 kW95.0 kW100.0 kW

1) ENERGY SAVING Reduced operating costs

2) FLEXIBLE DESIGN• Compactdesign• Easytransportandinstallation

3) BMS (BUILDING MANAGEMENT SYSTEM) The same system for controlling the air-cooled system (KXZ)4) SERVICE AND MAINTENANCE• Easyfrontaccesstothemainparts(compressor,control,

plate heat exchanger, etc.) • Widerangeofcontrolsoftwareandmaintenance

instruments (Mente PC, SL-Checker, etc.)

VRF Multi system KXZW WATER seriesWater cooledModular outdoor units

APPLICABLE ON:

• Skyscrapers 100 metres or higher• Glass façades; outside of buildings Possibility to hide the motocondensing unit

FDC224~670KXZWE1

FDC730~1000KXZWE1

16~36HP (45.0~100.0 kW)

Page 56: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

135

Models FDC450KXZWE1 FDC500KXZWE1 FDC560KXZWE1 FDC615KXZWE1 FDC670KXZWE1

Combined unitsFDC224KXZWE1 FDC224KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1FDC224KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1 FDC335KXZWE1

- - - - -Nominal Cool. capacity kW 45.00 50.00 56.00 61.50 67.00Cool. power consumption kW 8.49 9.83 11.50 13.70 16.30Rated energy efficiency coefficient in Cool. EER1 5.30 5.09 4.87 4.49 4.11Nominal Heat. capacity kW 50.00 56.00 63.00 69.00 75.00Heat. power consumption kW 8.47 9.27 10.20 11.40 12.60Rated energy efficiency coefficient in Heat. COP1 5.90 6.04 6.18 6.05 5.95Power Three-phase- 380-415V 50HzRated cool. current in A 14.30 16.50 19.30 22.70 26.80Rated heat. current in A 14.30 15.60 17.20 19.10 21.00Sound level dB(A) 51 52 53 54 55External dimensions (HxLxD) mm 1100 x 780 x 550 x 2Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 185 x 2

Indoor System Units Number of connectable IU from 1 to 44 from 1 to 50 from 1 to 56 from 2 to 61 from 2 to 67Total connectable capacity* 224 ~ 672 252 ~ 756 280 ~ 840 307 ~ 923 335 ~ 1005

Crankcase heater W 33 x 2Refrigerant circuit/Heat exchanger Heat plate exchangerRefrigerant control Electronic expansion valveRefrigerant R410AQuantity kg 9.9 x 2Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 12.7 (1/2”)Gas side: ø 28.58 (1, 1/8”)

Oil equalisation ø 9.52 (3/8”)Joining method Gas side: flange / Liquid side: flare

Water pipe diameterWater inlet R1 1/4”

Water outlet R1 1/4”Condensate outlet Rp 1/2” (internal threading)

Models FDC730KXZWE1 FDC775KXZWE1 FDC850KXZWE1 FDC900KXZWE1 FDC950KXZWE1 FDC1000KXZWE1

Combined unitsFDC224KXZWE1 FDC224KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1FDC224KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1 FDC335KXZWE1FDC280KXZWE1 FDC280KXZWE1 FDC280KXZWE1 FDC335KXZWE1 FDC335KXZWE1 FDC335KXZWE1

Nominal Cool. capacity kW 73.00 77.50 85.00 90.00 95.00 100.00Cool. power consumption kW 14.20 15.50 17.50 19.50 21.70 24.30Rated energy efficiency coefficient in Cool. EER1 5.14 5.00 4.86 4.62 4.38 4.12Nominal Heat. capacity kW 82.50 90.00 95.00 100.00 106.00 112.00Heat. power consumption kW 13.80 14.80 15.40 16.40 17.60 18.80Rated energy efficiency coefficient in Heat. COP1 5.98 6.08 6.17 6.10 6.02 5.96Power Three-phase- 380-415V 50HzRated cool. current in A 23.80 26.00 29.30 32.50 36.00 40.00Rated heat. current in A 23.20 24.90 25.90 27.50 29.40 31.40Sound level dB(A) 54 54 55 56 56 57External dimensions (HxLxD) mm 1100 x 780 x 550 x 3Exterior appearance (Munsell colour) Stucco white (4.2Y7.5 / 1.16) equivalentNet weight kg 185 x 3

Indoor System Units Number of connectable IU from 2 to 72 from 2 to 78 from 2 to 80 from 2 to 80 from 2 to 80 from 2 to 80Total connectable capacity* 364 ~ 1092 392 ~ 1176 420 ~ 1275 447 ~ 1343 475 ~ 1425 502 ~ 1508

Crankcase heater W 33 x 3Refrigerant circuit/Heat exchanger Heat plate exchangerRefrigerant control Electronic expansion valveRefrigerant R410AQuantity kg 9.9 x 3Safety devices Compressor overheating protection/overcurrent/power transistor overheating protection/abnormal high pressure protection

Diameter cooling/refrigerant pipes mm (inch)Liquid side: ø 15.88 (5/8”)

Gas side: ø 31.75 (1 1/4”) [ø 34.92 (1 3/8”)] Gas side: ø 38.1 (1 1/2”) [ø 34.92 (1 3/8”)]

Oil equalisation ø 9.52 (3/8”)Joining method Gas side: flange / Liquid side: flare

Water pipe diameterWater inlet R1 1/4”

Water outlet R1 1/4”Condensate outlet Rp 1/2” (internal threading)

Combinations

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 1. Value measured according to harmonised standard EN14511.

* When connecting the indoor units in the following series: FDK, FDFL, FDFU or FDFW, the power of the connectable indoor units cannot exceed 130%. 1. Value measured according to harmonised standard EN14511.

VRF Multi system KXZW WATER series

Combinations

Page 57: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

136

Page 58: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

137

HP 0.5 0.8 1 1.25 1.6 2 2.5 3.2 4 6 6 8 10kW 1.5 2.2 2.8 3.6 4.5 5.6 7.1 9.0 11.2 14.0 16.0 22.4 28.0

m3/h 250 350 500 800 1000

INDOOR UNITS

Cass

ette

uni

ts

84x84

60x60

2-way

1-way

ducted 1-way

compact

Duc

ted

with high adjustable

head

with low and medium

adjustable head

all-outside air

with low adjustable

head

design

Wall

Ceiling

Floo

r

recessed

console

Post-treatment modu-lar unit

VRF Multi systems

FDT

SAF DXSAF DXSAF DXSAF DXSAF DX

NEW

NEW

FDTC

FDTW

FDTS

FDTQ

FDU

FDUM

FDU F

FDUT

FDUH

FDK

FDE

FDFW

FDFU

• • • • • • • • •• • • • • •

• • • • • • •• •

• • •• • • • • • • • •

• • • • • • • • • •• • • •

•• • • • • •• • •

• • • • • • • •• • • • • •

• • •• • • •

Page 59: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

138

› 9 power levels (2.80 ~ 16.00 kW)› Ideal for commercial applications: the cassette becomes invisible because it is

completely built into the false ceiling › Removable caps on the 4 corners for easy installation› Easy condensate drain pan control› Anti-draft panel: flexible flap control for FDT (optional)› Condensate drain pump as standard: raises condensation up to 850 mm from

the flush panel

Cassette 84x84

Standard panel

Anti-draft panel

VRF Multi systemsIndoor units

ANTI-DRAFT PANEL page 34Maximum comfort without direct drafts:new flap control for increased flexibility.

Model FDT28KXZE1 FDT36KXZE1 FDT45KXZE1 FDT56KXZE1 FDT71KXZE1 FDT90KXZE1 FDT112KXZE1 FDT140KXZE1 FDT160KXZE1Standard panel T-PSA-5AW-EAnti-draft panel T-PSAE-5AW-ENominal Cool. capacity kw 2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00 16.00Nominal Heat. capacity kw 3.20 4.00 5.00 6.30 8.00 10.00 12.50 16.00 18.00Power 220-240V~ 50HzCool. power consumption kw 0.02 - 0.02 0.03 - 0.03 0.03 - 0.03 0.04 - 0.04 0.08 - 0.08 0.13 - 0.13 0.14 - 0.14 0.14 - 0.14 0.14 - 0.14Heat. power consumption kw 0.02 - 0.02 0.03 - 0.03 0.03 - 0.03 0.04 - 0.04 0.08 - 0.08 0.13 - 0.13 0.14 - 0.14 0.14 - 0.14 0.14 - 0.14Rated current in Cool. A 0.2 - 0.19 0.3 - 0.28 0.3 - 0.28 0.36 - 0.33 0.70 - 0.64 1.04 - 0.95 1.12 - 1.02 1.12 - 1.02 1.12 - 1.02Rated current in Heat. A 0.2 - 0.19 0.3 - 0.28 0.3 - 0.28 0.36 - 0.33 0.70 - 0.64 1.04 - 0.95 1.12 - 1.02 1.12 - 1.02 1.12 - 1.02Sound pressure level dB(A) P-Hi 33 Hi 31 Me 29 Lo 27 P-Hi 34 Hi 31 Me 29 Lo 27 P-Hi 35 Hi 33 Me 31 Lo 27 P-Hi 38 Hi 33 Me 31 Lo 27 P-Hi 47 Hi 35 Me 32 Lo 28 P-Hi 49 Hi 38 Me 36 Lo 31 P-Hi 49 Hi 39 Me 37 Lo 31 P-Hi 49 Hi 42 Me 39 Lo 32 P-Hi 49 Hi 42 Me 39 Lo 33Sound power level dB(A) 49 49 50 55 62 65 66 66 66

External dimensions (HxLxD) mm Unit 236 × 840 × 840 Unit 298 × 840 × 840Panel 35 × 950 × 950

Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2) similarNet weight kg Unit 20 Panel 5 Unit 21.5 Panel 5 Unit 25 Panel 5Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Turbo fan × 1Motor W 58 58 58 58 58 120 120 120 120Starting method Direct, in lineAir flow (standard) m3h PHi 900 Hi 840 Me 720 Lo 600 PHi 960 Hi 840 Me 720 Lo 600 PHi 1020 Hi 900 Me 780 Lo 600 PHi 1200 Hi 960 Me 780 Lo 660 PHi 1680 Hi 1020 Me 840 Lo 720 PHi 2220 Hi 1500 Me 1320 Lo 900 PHi 2280 Hi 1560 Me 1380 Lo 1020 PHi 2280 Hi 1680 Me 1500 Lo 1080 PHi 2280 Hi 1740 Me 1560 Lo 1140Static pressure Pa 0Renewal air inlet PossibleAir filter and quantity Plastic mesh filter x 1 (washable)Shock and vibration absorption Rubber vibration absorber (for fan motor)Thermal and acoustic insulation Polyurethane foam

Optional control devices Wired remote control: RC-EX3, RC-E5, RCH-E3Remote control kit: RCN-T-5AW-E2

Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø6.35 (1/4”)Gas side: ø9.52 (3/8”)

Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25 Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories included Assembly kit, Condensate pipe

FDT 28~160KXZE1

T-PSAE-5AW-E

T-PSA-5AW-E

NEW

Page 60: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

139

All measurements are in mm.

Hole dimension

Suspension rod spacing

Susp

ensio

n rod

spac

ing: P

2 (7

70)

Electrical box

Condensate pipe(accessory)On-site connection

Extraction grilleAir delivery

Decorative panel

Space for installation and service

or mo

re

or moreobstacle

When installing more than one unit, it is necessary to keep a distance of 5 m or more between one machine and the next.

Installation plate for suspension rod

50 or

more

Electrical box

Fixing

Holes for self-tapping screws

Fixing

Holes for self-tapping screws

850

or les

sMa

x. ris

e

Diagrams and measurements

Anti-draft function(*1)

Holes for self-tapping screws

860~910 Hole dimension

Suspension rod spacing: P1 (770)

Susp

ensio

n rod

spac

ing: P

2 (7

70) Electrical

box

Condensate pipe(accessory)On-site connection

Extraction grilleAir delivery

Decorative panel

Space for installation and service

or mo

re

or moreobstacle

When installing more than one unit, it is necessary to keep a distance of 5 m or more between one machine and the next.

Installation plate for suspension rod

50 or

more

Electrical box

Fixing

Holes for self-tapping screws

Fixing

Holes for self-tapping screws

850

or les

sMa

x. ris

e

Anti-draft function(*1)

Holes for self-tapping screws

Note:1. The label with the model code is applied inside the extraction grille.3. Section 1 (* 1) is only available on panel T-PSA-5AW.

Ref. ItemModel FDT28KXZE1 FDT36~56KXZE1 FDT71KXZE1

A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC Condensate drain VP25 (O.D. 32)D Hole for electrical cables

F Suspension rods M10 or M8G External air intake ø 125 pre-cutH Outlet air intake ø 200 pre-cut

Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC Condensate drain VP25 (O.D. 32)D Hole for electrical cables

F Suspension rods M10 or M8G External air intake ø 125 pre-cutH Outlet air intake ø 200 pre-cut

FDT 28~71KXZE1

FDT 90~160KXZE1

Page 61: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

140

300 m

m

TC-OAS-ETC-OAD-E

075 mm

› 6 power levels (1.50 ~ 5.60 kW)› Ideal for insertion into modular ceilings › Maximum compactness: only 24.8 cm in height.› RCN-TC-24W-E2 corner kit with remote control (optional)› Removable caps on the 4 corners for easy installation› Condensate drain pump as standard› Panel: TC-PSA-25W-E

Cassette 60X60

AIR RENEWAL AIR FLOW

The shape and angle of the deflector lead air away from the ceiling to prevent stains.

Optional accessories for outdoor air intake, TC-OAD-E, TC-OAS-E

outdoor airfalse ceiling

panel

Values for 1 channel(?)Air flow: 1.3m3/min (78m3/h)(10% approx. of the max air flow)Press. Static: 12 Pa (at max air flow)

Notes:1 channel = about 10% of total unit air flow;2 channel = about 20% of total FDTC air flow;

Model FDTC15KXE6F* FDTC22KXE6F FDTC28KXE6F FDTC36KXE6F FDTC45KXE6F FDTC56KXE6FPanel (optional) TC-PSA-25W-ENominal Cool. capacity kW 1.50 2.20 2.80 3.60 4.50 5.60Nominal Heat. capacity kW 1.70 2.50 3.20 4.00 5.00 6.30Power 220-240V~ 50HzCool. power consumption kW 0.02 - 0.02 0.03 - 0.03 0.03 - 0.03 0.03 - 0.03 0.05 - 0.05 0.05 - 0.05Heat. power consumption kW 0.02 - 0.02 0.03 - 0.03 0.03 - 0.03 0.03 - 0.03 0.05 - 0.05 0.05 - 0.05Rated cool. current in A 0.06 - 0.05 0.15 - 0.14 0.15 - 0.14 0.15 - 0.14 0.25 - 0.23 0.25 - 0.23Rated heat. current in A 0.06 - 0.05 0.15 - 0.14 0.15 - 0.14 0.15 - 0.14 0.25 - 0.23 0.25 - 0.23Sound pressure level dB(A) Hi 32 Me 28 Lo 25 Hi 35 Me 33 Lo 30 Hi 38 Me 36 Lo 31 Hi 40 Me 37 Lo 31 Hi 45 Me 39 Lo 31Sound power level dB(A) 56 58 60

External dimensions (HxLxD) mm Unit 248 x 570 x 570Panel 35 x 700 x 700

Exterior appearance Chalk whiteMunsell colour ( 6.8Y8.9 / 0.2) similarNet weight kg Unit 14 Panel 3.5 Unit 15 Panel 3.5Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Turbo fan x 1Motor W 33Starting method Direct, in lineAir flow (standard) m3/h Hi 420 Med 330 Lo 270 Hi 570 Me 510 Lo 420 Hi 600 Me 540 Lo 420 Hi 780 Me 600 Lo 420Static pressure Pa 0Renewal air inlet Possible with accessoriesAir filter and quantity Plastic mesh filter x 1 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-TC-24W-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2")

Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit, TC-OAS-E (Optional), TC-OAD-E (Optional)

* Unit can only be connected with OU KXE6 from 8HP to 12HP and all KXZ OU.

Indoor units

VRF Multi systems

FDTC 15~56KXE6F

Page 62: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

141

All measurements are in mm.Diagrams and measurements

Ref. ItemModel FDTC15~28KXE6F FDTC36~56KXE6F

A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain VP25 (note 2)D Hole for electrical cables ø 25F Suspension rods M10 or M8G External air intake Pre-cut

Space for installation and service

or mo

re

or moreobstacle

When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.

Suspension rod spacing

Susp

ensio

n rod

spac

ing

Electrical box

Condensate pipe(accessory)On-site connection

Extraction grille

Air delivery

Decorative panel

Holes for self-tapping screws

or les

sMa

x. ris

e

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.3. This unit has been designed to be inserted into an inspectable ceiling. In case of installation in an inspectable ceiling, provide for an inspection opening on the side of the electrical box.

or mo

re

Installation plate for suspension rod

or les

sMa

x. ris

e

Ultra-thin design, only 248 mm over the ceiling Standard condensate drain pump

FDTC 15~56KXE6F

Page 63: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

142

› 7 power levels (2.80 ~ 14.00 kW)› Can be fully built in to the false ceiling, enabling uniform air distribution in

environments with a rectangular perimeter› Panels: TW-PSA-26W-E (models FDTW 28/45/56/71 KXE6F); TW-PSA-46W-E

(models FDTW 90/112/140 KXE6F)

2-way cassette

INDIVIDUAL CONTROL OF AIR OUTLET LOUVERS CONDENSATE DRAIN PUMP

The new design of the louvers ensures uniform, wide-ranging air distribution throughout the area to be conditioned. The enlargement of the delivery vents has significantly reduced the load on the fan motor, resulting in increased energy efficiency.

750 o

r less

Maxim

um ris

e

Model FDTW28KXE6F FDTW45KXE6F FDTW56KXE6F FDTW71KXE6F FDTW90KXE6F FDTW112KXE6F FDTW140KXE6FPanel (optional) TW-PSA-26W-E TW-PSA-46W-ENominal Cool. capacity kW 2.80 4.50 5.60 7.10 9.00 11.20 14.00Nominal Heat. capacity kW 3.20 5.00 6.30 8.00 10.00 12.50 16.00Power 220-240V~ 50HzCool. power consumption kW 0.09 - 0.09 0.10 - 0.10 0.10 - 0.10 0.14 - 0.14 0.19 - 0.19 0.19 - 0.19 0.19 - 0.19Heat. power consumption kW 0.09 - 0.09 0.10 - 0.10 0.10 - 0.10 0.14 - 0.14 0.19 - 0.19 0.19 - 0.19 0.19 - 0.19Rated cool. current in A 0.45 - 0.45 0.55 - 0.55 0.55 - 0.55 0.75 - 0.75 1.00 - 1.00 1.00 - 1.00 1.00 - 1.00Rated heat. current in A 0.45 - 0.45 0.55 - 0.55 0.55 - 0.55 0.75 - 0.75 1.00 - 1.00 1.00 - 1.00 1.00 - 1.00Sound pressure level dB(A) Hi 38 Me 34 Lo 31 Hi 45 Me 41 Lo 37Sound power level dB(A) 58 65 -

External dimensions (HxLxD) mm Unit 325 x 820 x 620 Unit 325 x 1535 x 620Panel 20 x 1120 x 680 Panel 20 x 1835 x 680

Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2) similarNet weight kg Unit 20 Panel 8.5 Unit 21 Panel 8.5 Unit 23 Panel 8.5 Unit 35 Panel 13Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Turbo fan x 1Motor W 30 35 40 35 x 2Starting method Direct, in lineAir flow (standard) m3/h Hi 720 Me 600 Lo 540 Hi 1620 Me 1380 Lo 1200Static pressure Pa 0Renewal air inlet PossibleAir filter and quantity Plastic mesh filter x 1 (washable) Plastic mesh filter x 2 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-TW-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch.)

Liquid side: ø 6.35 (1/4") Liquid side: ø 9.52 (3/8")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2") Gas side: ø 15.88 (5/8")

Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit

Indoor units

VRF Multi systems

FDTW 28~140KXE6F

Page 64: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

143

All measurements are in mm.Diagrams and measurements

Space for installation and service

or more

obstacle

When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.

Ceiling hole dimension

Ceilin

g hole

dime

nsion

Electrical box

Condensate pipe(accessory)On-site connection

Decorative panel

Suspension rod spacing

Suspen

sion ro

d spac

ing

or les

sMa

x. ris

e

Air delivery Extraction grille

Slot for suspension rod

or moreor more or more

Panel centre

Electrical box

Ceiling hole dimension

Ceilin

g hole

dime

nsion

Electrical box

Condensate pipe(accessory)On-site connection

Suspension rod spacing

or les

sMa

x. ris

e

Slot for suspension rod

Panel centre

Electrical box

Suspen

sion ro

d spac

ing

Space for installation and service

or more

obstacle

When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.

Decorative panel

Air delivery

Extraction grille

or moreor more or more

Ref. ItemModel FDTW28KXE6F FDTW45~56KXE6F FDTW71KXE6F FDTW90~140KXE6F

A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC Condensate drain VP25 (note 2)D Hole for electrical cablesF Suspension rods M10G External air intake Pre-cutH Outlet air intake Pre-cut

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.

FDTW 28~140KXE6F

FDTW 90~140KXE6F

Page 65: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

144

1-way cassette

› 2 power levels (4.50 and 7.10 kW)› Can be mounted on the ceiling with a suspended unit or built into the false

ceiling› Maximum compactness: only 22 cm high, ideal for installations in

environments with low false ceilings› Wide air flow, ideal for environments with very high ceilings› Possibility to connect air renewal ducts› Panel: TS-PSA-3AW-E

Ultra-compact design: its height of only 22 cm and weight of 27/28 kg guarantee easy and quick installation.

INDIVIDUAL CONTROL OF AIR OUTLET LOUVERSULTRA-COMPACT MODEL

The new design of the louvers ensures uniform, wide-ranging air distribution throughout the area to be conditioned. The enlargement of the delivery vents has significantly reduced the load on the fan motor, resulting in increased energy efficiency.

Model FDTS45KXE6F FDTS71KXE6FPanel (optional) TS-PSA-3AW-ENominal Cool. capacity kW 4.50 7.10Nominal Heat. capacity kW 5.00 8.00Power 220-240V~ 50HzCool. power consumption kW 0.04 - 0.04 0.09 - 0.09Heat. power consumption kW 0.04 - 0.04 0.09 - 0.09Rated cool. current in A 0.27 - 0.25 0.60 - 0.55Rated heat. current in A 0.27 - 0.25 0.60 - 0.55Sound pressure level dB(A) Hi 40 Me 38 Lo 35 Hi 44 Me 41 Lo 36Sound power level dB(A) 60 61

External dimensions (HxLxD) mm Unit 220 x 1150 x 565Panel 35 x 1250 x 650

Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2) similarNet weight kg Unit 27 Panel 5 Unit 28 Panel 5Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 4Motor W 35 70Starting method Direct, in lineAir flow (standard) m3h Hi 720 Me 660 Lo 570 Hi 900 Me 720 Lo 600Static pressure Pa 0Renewal air inlet PossibleAir filter and quantity Plastic mesh filter x 2 (washable) Plastic mesh filter x 3 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-TS-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4") Liquid side: ø 9.52 (3/8")Gas side: ø 12.7 (1/2") Gas side: ø 15.88 (5/8")

Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit

Indoor units

VRF Multi systems

FDTS 45-71KXE6F

Page 66: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

145

FDTS 45-71KXE6F

All measurements are in mm.Diagrams and measurements

Ref. ItemModel FDTS45KXE6F FDTS71KXE6F

A Gas side ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC Condensate drain VP25 (note 2)D Hole for electrical cablesF Suspension rods M10G External air intake Pre-cutH Condensate drain (dr. nat.) VP25

Ceiling hole dimension

Ceilin

g hole

dime

nsion

Condensate pipe(accessory)On-site connection

or les

sMa

x. ris

e

Panel centre

Electrical box

Space for installation and service

or mo

re

obstacle

When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.

Decorative panel

Air delivery

Extraction grille

or more

Air delivery

Extraction grille

or moreor more

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.

Page 67: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

146

1-way compact ducted cassette

› 3 power levels (2.20 ~ 3.60 kW)› Ideal for smaller environments, with a fan speed of only 300 m3/h› Panel with direct delivery› Panel equipped with motorised louver for comfortable air flow distribution› Condensate drain pump as standard h 60 cm

PANELULTRA-COMPACT MODEL

TQ-PSA-15W-E

Air delivery

Extraction grille

Model a b c d

TQ-PSA-15W-E 625 514 650 580Holes for self-tapping screws

External air intake (pre-cut)

Model FDTQ22KXE6F FDTQ28KXE6F FDTQ36KXE6FPanel (optional) Direct delivery

TQ-PSA-15W-ENominal Cool. capacity kW 2.20 2.80 3.60Nominal Heat. capacity kW 2.50 3.20 4.00Power 220-240V~ 50HzCool. power consumption kW 0.05 - 0.07 0.05 - 0.07 0.05 - 0.07Heat. power consumption kW 0.05 - 0.07 0.05 - 0.07 0.05 - 0.07Nominal Cool. current A 0.25 - 0.32 0.25 - 0.32 0.25 - 0.32Nominal Heat. current A 0.25 - 0.32 0.25 - 0.32 0.25 - 0.32Sound pressure level dB(A) Hi 41 Me 38 Lo 33Sound power level dB(A) 60

External dimensions (HxLxD) mm Unit 250 x 570 x 570Panel 35 x 625 x 650

Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2) similarNet weight kg Unit 23 Panel 2.5Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 1Motor W 30Starting method Direct, in lineAir flow (standard) m3/h Hi 420 Me 360 Lo 300Static pressure Pa 0Renewal air inlet PossibleAir filter and quantity Plastic mesh filter x 1 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2")

Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit

Indoor units

VRF Multi systems

FDTQ 22~36KXE6F

Page 68: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

147

All measurements are in mm.Diagrams and measurements

Direct delivery (TQ-PSA-15W-E)

Ref. ItemModel FDTQ22~28KXE6F FDTQ36KXE6F

A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain VP25 (note 2)D Hole for electrical cables ø 30E Suspension rods M10F1.2 External air intake Pre-cut

Space for installation and service

or mo

re

obstacle

When installing more than one unit, it is necessary to keep a distance of 3 m or more between one machine and the next.

or more

Condensate pipe(accessory)On-site connection

Suspension rod spacing

or mo

re

Condensate pipe(accessory)On-site connection

Installation plate for suspension rod

Suspension rod spacingHole dimension

Centre of panel

Electrical box

Installation plate for suspension rod

Centre of panel

Electrical box Su

spen

sion r

od sp

acing

Hole

dimen

sion

Susp

ensio

n rod

spac

ing

Holes for self-tapping screws

Holes for self-tapping screws

or les

sMa

x. ris

e

or moreor more

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.3. This unit has been designed to be inserted into an inspectable ceiling.

or more

FDTQ 22~36KXE6F

Page 69: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

148

High adjustable head ducted

› 9 power levels (4.50 ~ 28.00 kW)› Units with rear recovery› Adjustable 100~200 Pa head for models from 4.50 to 16.00 kW and only 200

Pa for models from 22.40 to 28.00 kW› Maximum compactness: only 28 cm (models from 4.50 to

16.00 kW) and 37.9 cm high (22.40 and 28.00 kW models)› Integrated condensate drain pump for models from 4.50 to 16.00 kW

COMPACT SIZE

Models from 4.50 to 16.00 kW Models from 22.40 to 28.00 kW

Indoor units

VRF Multi systems

Model FDU45KXE6F FDU56KXE6F FDU71KXE6F FDU90KXE6F FDU112KXE6F FDU140KXE6F FDU160KXE6F FDU 224KXZE1 FDU 280KXZE1Nominal Cool. capacity kW 4.50 5.60 7.10 9.00 11.20 14.00 16.00 22.40 28.00Nominal Heat. capacity kW 5.00 6.30 8.00 10.00 12.50 16.00 18.00 25.00 31.50Power 220-240V~ 50HzCool. power consumption kW 0.10 - 0.10 0.10 - 0.10 0.24 - 0.25 0.24 - 0.25 0.31 - 0.32 0.35 - 0.36 0.42 - 0.43 1.16 - 1.20 1.16 - 1.20Heat. power consumption kW 0.10 - 0.10 0.10 - 0.10 0.24 - 0.25 0.24 - 0.25 0.31 - 0.32 0.35 - 0.36 0.42 - 0.43 1.16 - 1.20 1.16 - 1.20Rated cool. current in A 0.63 - 0.58 0.63 - 0.58 1.80 - 1.70 1.80 - 1.70 2.00 - 2.00 2.30 - 2.20 2.70 - 2.50 6.8 - 6.5 6.8 - 6.5Rated heat. current in A 0.63 - 0.58 0.63 - 0.58 1.80 - 1.70 1.80 - 1.70 2.00 - 2.00 2.30 - 2.20 2.70 - 2.50 6.8 - 6.5 6.8 - 6.5Sound pressure level dB(A) Hi 32 Med 29 Lo 26 Hi 32 Med 29 Lo 26 Hi 33 Med 29 Lo 25 Hi 33 Med 29 Lo 25 Hi 38 Med 36 Lo 30 Hi 40 Med 34 Lo 29 Hi 40 Med 35 Lo 30 P-Hi 52 Hi 50 Med 47 Lo 35Sound power level dB(A) 60 60 65 65 75 75External dimensions (hxlxd) mm 280 ×750 × 635 280 ×750 × 635 280 ×950 × 635 280 ×950 × 635 280 ×1.370 × 740 280 ×1.370 × 740 280 ×1.370 × 740 379 × 1.600 × 893 379 × 1.600 × 893Net weight kg 29 29 34 34 54 54 54 89 89Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 1 Centrifugal fan x 2 Centrifugal fan x 3Motor W 100 100 130 130 100 + 130 100 + 200 100 + 200 130 + 350 130 + 350Starting method Direct, in lineAir flow (standard) m3h Hi 600 Med 540 Lo 480 Hi 1140 Med 900 Lo 600 Hi 1680 Med 1500 Lo 1140 Hi 1920 Med 1560 Lo 1200 Hi 2100 Med 1680 Lo 1320 P-Hi 4800 Hi 4320 Med 3840 Lo 3360Static pressure Pa Standard 100 Max 200 Max 200 Max 200Renewal air inlet PossibleAir filter and quantity To be found locallyShock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (in) Liquid side: ø6.35 (1/4”) Liquid side ø9.52 (3/8”)Gas side: ø12.7 (1/2”) Gas side ø15.88 (5/8”) Gas side ø19.05 (3/4”) Gas side ø22.2 (7/8”)

Joining method by flare fittings by blazingRefrigerant R410ADrain pump Built-in -Condensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories -

FDU 45~160KXE6F

FDU 224~280KXZE1

Page 70: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

149

Diagrams and measurements

Ref. ItemA Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Inspection hole 450 x 450G External air intake Pre-cutH Outlet air intake Pre-cut

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.

Space for installation and service

or mo

re

Condensate pipe(accessory)On-site connection

Suspension rod spacingInstallation plate for suspension rod

Electrical box

Susp

ensio

n rod

spac

ing

Holes for self-tapping screws

Hole

VIEW M

Holes for self-tapping screws

Dimen

sions

of

ducti

ng

Air delivery

Dimensions of ducting

or les

sMa

x. rise

Dimen

sions

of

ducti

ng Dimensions of ducting

Inletduct

Inspectionhole or

more

Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Inspection hole 450 x 450G External air intake Pre-cutH Outlet air intake Pre-cut

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.

Space for installation and service

or mo

re

Condensate pipe(accessory)On-site connection

Suspension rod spacingInstallation plate for suspension rod

Electrical box

Susp

ensio

n rod

spac

ing

Holes for self-tapping screws

VIEW M

Holes for self-tapping screws

Dimen

sions

of

ducti

ng Air delivery

Dimensions of ducting

or les

sMa

x. rise

Dimen

sions

of

ducti

ng Dimensions of ducting

Inletduct

Inspectionhole

or mo

re

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.

Space for installation and service

or mo

re

Condensate pipe(accessory)On-site connection

Suspension rod spacingInstallation plate for suspension rod

Electrical box

Susp

ensio

n rod

spac

ing

Holes for self-tapping screws

VIEW M

Holes for self-tapping screws

Dimen

sions

of

ducti

ng

Air delivery

Dimensions of ducting

or les

sMa

x. rise Dimensions

of ducting

Inletduct

Inspectionhole

or mo

re

Hole

Hole

Dimen

sions

of

ducti

ng

Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Inspection hole 450 x 450G External air intake Pre-cutH Outlet air intake Pre-cut

Ref. ItemModel FDU 224KXZE1 FDU 280KXZE1

A Gas side ø 19.05 (3/4") flare

ø 22.22 (7/8") flare

B Liquid side ø 9.52 (3/8") flareC Condensate drain VP25 (note 2)D Hole for electrical cables

E Suspension rods M10F Inspection hole 450 x 450

Dimensions of ducting

Dimen

sions

of

ducti

ng

Dimen

sions

of

ducti

ng

Air delivery

Dimensions of ducting

Susp

ensio

n rod

spac

ing

Space for installation and service

or mo

re

Installation plate for suspension rod

All measurements are in mm.

FDU 45~56KXE6F

FDU 112~140KXE6F

FDU 71~90KXE6F

FDU 224~280KXZE1

Page 71: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

150

Ducted with adjustable medium and low head

› 10 power levels (2.20 ~ 16.00 kW)› Ultra-compact design: only 28 cm in height.› Optional UM-FL1EF (FDUM 22~56KXE6F), UM-FL2EF (FDUM 71~90KXE6F),

UM-FL3EF (FDUM 112~160KXE6F)› ESP function: automatic maintenance of the air flow rate as flow resistance

varies

Model FDUM22KXE6F FDUM28KXE6F FDUM36KXE6F FDUM45KXE6F FDUM56KXE6F FDUM71KXE6F FDUM90KXE6F FDUM112KXE6F FDUM140KXE6F FDUM160KXE6FNominal Cool. capacity kW 2.20 2.80 3.60 4.50 5.60 7.10 9.00 11.20 14.00 16.00Nominal Heat. capacity kW 2.50 3.20 4.00 5.00 6.30 8.00 10.00 12.50 16.00 18.00Power 220-240V~ 50HzCool. power consumption kW 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.20 - 0.20 0.20 - 0.20 0.29 - 0.29 0.33 - 0.33 0.33 - 0.33Heat. power consumption kW 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.10 - 0.10 0.20 - 0.20 0.20 - 0.20 0.29 - 0.29 0.33 - 0.33 0.33 - 0.33Rated cool. current in A 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.91 - 0.83 0.91 - 0.83 1.32 - 1.21 1.50 - 1.38 1.50 - 1.38Rated heat. current in A 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.46 - 0.42 0.91 - 0.83 0.91 - 0.83 1.32 - 1.21 1.50 - 1.38 1.50 - 1.38Sound pressure level dB(A) Hi 32 Me 29 Lo 26 Hi 33 Me 29 Lo 25 Hi 38 Me 36 Lo 30 Hi 40 Me 34 Lo 29 Hi 40 Me 34 Lo 29Sound power level dB(A) 60 64 -External dimensions (HxLxD) mm 280 x 750 x 635 280 x 950 x 635 280 x 950 x 635 280 x 1370 x 740Net weight kg 29 34 54Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2Motor W 100 130 100 + 130 100 + 200Starting method Direct, in lineAir flow (standard) m3/h Hi 600 Me 540 Lo 480 Hi 1140 Me 900 Lo 600 Hi 1680 Me 1500 Lo 1140 Hi 1920 Me 1560 Lo 1200Static pressure Pa Max 100Renewal air inlet PossibleAir filter and quantity OptionalShock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4") Liquid side: ø 9.52 (3/8")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2") Gas side: ø 15.88 (5/8")

Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP20 or VP25 Piping insulation Necessary (on both sides, liquid and gas)Accessories UM-FL1EF (Optional) UM-FL2EF (Optional) UM-FL3EF(Optional)

Indoor units

VRF Multi systems

FDUM 22~160KXE6F

Page 72: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

151

Diagrams and measurements

Ref. ItemModel FDUM22~28KXE6F FDUM36~56KXE6F FDUM71~90KXE6F FDUM112~160KXE6F

A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F External air intake Pre-cutG Outlet air intake Pre-cutH Inspection hole 450 x 450

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.

Space for installation and service

or mo

re

Suspension rod spacingInstallation plate for suspension rod

Electrical box

Susp

ensio

n rod

spac

ing

Holes for self-tapping screws

Hole

Holes for self-tapping screws

Inspectionhole

or mo

re

VIEW M

VIEW M

Space for installation and service

or mo

re

Suspension rod spacingInstallation plate for suspension rod

Electrical box

Susp

ensio

n rod

spac

ing

Holes for self-tapping screws

Holes for self-tapping screws

Inspectionhole

or mo

re

Space for installation and service

or mo

re

Suspension rod spacingInstallation plate for suspension rod

Electrical box

Suspe

nsion

rod s

pacin

g

Holes for self-tapping screws

Holes for self-tapping screws

Inspectionhole

or mo

re

Hole

Hole

VIEW M

Condensate pipe(accessory)On-site connection

Dimen

sions

of du

cting

Air delivery

Dimensions of ducting

or les

sMa

x. rise

Dimensions of ducting

Inletduct

Dimen

sions

of

ducti

ng

Holes for self-tapping screws

Condensate pipe(accessory)On-site connection

Dimen

sions

of du

cting

Air delivery

Dimensions of ducting

or les

sMa

x. rise

Dimensions of ducting

Inletduct

Dimen

sions

of

ducti

ng

Holes for self-tapping screws

Condensate pipe(accessory)

On-site connection

Dimen

sions

of du

cting

Air delivery

Dimensions of ducting

or les

sMa

x. rise

Dimensions of ducting

InletductHoles for

self-tapping screws

Dimen

sions

of du

cting

All measurements are in mm.

FDUM 71~90KXE6F

FDUM 112~160KXE6F

FDUM 22~56KXE6F

Page 73: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

152

All-outside air ducted

› 4 power levels (9.00 ~ 28.00 kW)› Maximum compactness: only 28 cm (9.00~14.00 kW) and only 37.9 cm (22.40~28.00 kW)› Max pressure head of fans: 200 Pa.› Automatic function “all-outside air“ to save energy when the outdoor

temperature drops below the set temperature.› Can be connected to 8~60HP outdoor units except Micro Compact KXZ

(4~6HP) and KXZ Smart

AIR CONDITIONING AND OUTDOOR AIR INTAKE

The diagram below illustrates the integration of the FDU-F unit inside a KXZ system

NoteCheck the possible connections and limits of use on the technical documentation.

FDU-FIU IU

KXZ OU

Air conditioning Outsiderenewal air co

rrido

r

rooms

Outgoing air

Renew

al air

Outside air

Outside airRen

ewal a

ir

The compact design, the fan head of 200 Pa and the lowest noise level on the market make the unit suitable for installation in environments designed to ensure comfort and relaxation

Indoor units

VRF Multi systems

Model FDU650FKXZE1 FDU1100FKXZE1 FDU1800FKXZE1 FDU2400FKXZE1Nominal Cool. capacity kW 9.00 14.00 22.40 28.00Nominal Heat. capacity kW 6.50 10.50 16.00 21.50Power 220-240V~ 50HzCool. power consumption kW 0.24 - 0.25 0.35 - 0.36 1.16 - 1.20 1.16 - 1.20Heat. power consumption kW 0.24 - 0.25 0.35 - 0.36 1.16 - 1.20 1.16 - 1.20Rated current in Cool. A 1.80 - 1.70 2.30 - 2.20 6.80 - 6.50 6.80 - 6.50Rated current in Heat. A 1.80 - 1.70 2.30 - 2.20 6.80 - 6.50 6.80 - 6.50Sound power level dB(A) 55 62 68 70Sound pressure level dB(A) Hi 31 Hi 37 Hi 42 Hi 45External dimensions (HxLxD) mm 280 × 950 × 635 280 × 1370 × 740 379 × 1600 × 893 379 × 1600 × 893Net weight kg 34 54 89 89Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2 Centrifugal fan x 3Motor W 130 100 + 200 130 + 350 130 + 350Starting method Direct, in lineAir flow (standard) m3h Hi 660 Hi 1080 Hi 1800 Hi 2400Static pressure Pa Max: 200 Max: 200 Max: 200 Max: 200Air filter and quantity To be found locallyShock and vibration absorption Rubber vibration absorber (for fan motor)Thermal and acoustic insulation Polyurethane foam

Control devices Wired remote control: RC-EX3, RC-E5, RCH-E3Remote control kit: RCN-KIT4-E2

Ambient temperature control Electronic thermostat

Safety devices Thermal protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø9.52 (3/8”)Gas side ø15.88 (5/8”) Gas side ø19.05 (3/4”) Gas side ø22.22 (7/8”)

Joining method by flare fittings by blazingRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories included Condensate drain pipe

FDU 650~2400FKXZE1

Page 74: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

153

Diagrams and measurements

Ref. Item FDU650FKXZE1A Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Outside air openingG Air outlet openingH Inspection hole 450 x 450

Ref. Item FDU1800FKXZE1 FDU2400FKXZE1

A Gas side ø 19.05 (3/4") flare

ø 22.22 (7/8") flare

B Liquid side ø 9.52 (3/8") flareC Condensate drain VP25 (note 2)D Hole for electrical cables

E Suspension rods M10F Inspection hole 450 x 450

Ref. Item FDU1100FKXZE1A Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1 Condensate drain VP25 (note 2)C2 Condensate drain (dr. nat.) VP20D Hole for electrical cablesE Suspension rods M10F Outside air openingG Air outlet openingH Inspection hole 450 x 450

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.

Space for installation and service

or mo

re

Condensate pipe(accessory)On-site connection

Suspension rod spacingInstallation plate for suspension rod

Electrical box

Susp

ensio

n rod

spac

ing

Holes for self-tapping screws

VIEW M

Holes for self-tapping screws

Dimen

sions

of

ducti

ng Air delivery

Dimensions of ducting

or les

sMa

x. rise

Dimensions of ducting

Inlet duct

Inspection hole

or mo

re

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP25 condensate drain on site.

Space for installation and service

or mo

re

Suspension rod spacingInstallation plate for suspension rod

Electrical box

Susp

ensio

n rod

spac

ing

Holes for self-tapping screws

Holes for self-tapping screws

Dimen

sions

of

ducti

ng

Air delivery

Dimensions of ducting

or les

sMa

x. rise

Dimensions of ducting

Inlet duct

Inspection hole

or mo

re

Hole

Hole

Dimen

sions

of du

cting

Dimensions of ducting

Dimen

sions

of du

cting

Air delivery

Inlet duct

Susp

ensio

n rod

spac

ing

Notes: 1. The label with the model code is applied inside the extraction grille.

Space for installation and service

or mo

re

Inspectionhole or

more

Installation plate for suspension rod

Electrical box

Suspension rod spacing

Dimensions of ducting

Dimen

sions

of du

cting

VIEW M

Dimen

sions

of du

cting

All measurements are in mm.

FDU 650FKXZE1

FDU 1100FKXZE1

FDU 1800~2400FKXZE1

Page 75: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

154

Ducted with low adjustable head

› 7 power levels (1.50 ~ 7.10 kW)› Ideal for applications in hotels, hospitals and small offices› Optional filter kit: UT-FL1EF (FDUT 15~36); UT-FL2EF (FDUT 45~56); UT-FL3EF (FDUT 71)› Ducting flange: UT-SAT1EF (FDUT 15~36); UT-SAT2EF (FDUT 45~56); UT-SAT3EF (FDUT 71)

COMPACT SIZE

Extremely quiet: only 22 dB(A) for models from 1.50 - 2.80 kW.

models FDUT 15, 22, 28, 36 KXE6F models FDUT 45, 56 KXE6F

VERY QUIET OPERATION

Unit

Model FDUT15KXE6F-E FDUT22KXE6F-E FDUT28KXE6F-E FDUT36KXE6F-E FDUT45KXE6F-E FDUT56KXE6F-E FDUT71KXE6F-ERear recovery

Nominal Cool. capacity kW 1.50 2.20 2.80 3.60 4.50 5.60 7.10Nominal Heat. capacity kW 1.70 2.50 3.20 4.00 5.00 6.00 8.00Power 220-240V~ 50HzCool. power consumption kW 0.06 - 0.06 0.07 - 0.07 0.07 - 0.07 0.07 - 0.07 0.08 - 0.08 0.08 - 0.08 0.08 - 0.08Heat. power consumption kW 0.06 - 0.06 0.07 - 0.07 0.07 - 0.07 0.07 - 0.07 0.08 - 0.08 0.08 - 0.08 0.07 - 0.07Rated cool. current in A 0.27 - 0.27 0.28 - 0.25 0.28 - 0.25 0.32 - 0.29 0.36 - 0.33 0.38 - 0.35 0.42 - 0.42Rated heat. current in A 0.27 - 0.27 0.29 - 0.25 0.29 - 0.25 0.33 - 0.28 0.34 - 0.32 0.35 - 0.33 0.46 - 0.46Sound pressure level dB(A) Hi 28 Me 26 Lo 22 Hi 33 Me 30 Lo 26 Hi 34 Me 32 lo 28 Hi 35 Me 33 Lo 30 Hi 35 Me 31 Lo 28Sound power level dB(A) 52 57 58 59 59External dimensions (HxLxD) mm 200 x 750 x 500 200 x 950 x 500 220 x 1150 x 565Net weight kg 21 22 25 31Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2 Centrifugal fan x 3 Centrifugal fan x 4Motor W 14 38 100Starting method Direct, in lineAir flow (standard) m3/h Hi 360 Me 300 Lo 240 Hi 450 Me 360 Lo 300 Hi 510 Me 420 Lo 330 Hi 690 Me 540 Lo 420 Hi 750 Me 540 Lo 432 Hi 960 Me 780 Lo 570Static pressure Pa St, 10 Max 35 St, 10 Max 50Renewal air inlet Not possibleAir filter and quantity UT-FL1EF (Optional) UT-FL2EF (Optional) UT-FL3EF (Optional)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Thermal protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4”) Liquid side: ø 9.52 (3/8”)Gas side: ø 9.52 (3/8”) Gas side: ø 12.7 (1/2”) Gas side: ø 15.88 (5/8")

Joining method by flare fittingsRefrigerant R410ADrain pump Built-inCondensate drain Connectable with VP25Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit, UT-SAT1EF (Flange) Assembly kit, UT-SAT2EF (Flange) Assembly kit, UT-SAT3EF (Flange)

Indoor units

VRF Multi systems

FDUT 15~71KXE6F-E

Page 76: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

155

Diagrams and measurements

Ref. ItemModel FDUT15~28KXE6F-E

A Gas side ø 9.52 (3/8") flareB Liquid side ø 6.35 (1/4") flare

C1 Condensate drain VP25 (used with connected connector)

C2 Condensate drain (dr. nat.) VP25 (used with connected connector)

D Hole for electrical cables ø 25 x 2E Suspension rods M10F Inspection hole 450 x 450; 270 x 770

Ref. ItemModel FDUT45~56KXE6F-E

A Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flare

C1 Condensate drain VP25 (used with connected connector)

C2 Condensate drain (dr. nat.) VP25 (used with connected connector)

D Hole for electrical cables ø 25 x 2E Suspension rods M10F Inspection hole 450 x 450; 270 x 770

Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flare

C1 Condensate drain VP25 (used with connected connector)

C2 Condensate drain (dr. nat.) VP25 (used with connected connector)

D Hole for electrical cables ø 25 x 2E Suspension rods M10F Inspection hole 450 x 450; 270 x 770

Dimensions of ducting

Inlet duct

Dimen

sions

of du

cting

Dimensions of ducting

Dimen

sions

of du

cting

Dimensions of ducting

Dimen

sions

of du

cting

Suspension rod spacing

Installation plate for suspension rod

Electrical box

Condensate pipe(accessory)On-site connection

Inlet duct

Inlet duct

Susp

ensio

n rod

spac

ing

Suspension rod spacing

Installation plate for suspension rod

Electrical box

Condensate pipe(accessory)On-site connection

Susp

ensio

n rod

spac

ing

Suspension rod spacing

Installation plate for suspension rod

Electrical box

Condensate pipe(accessory)On-site connection

Susp

ensio

n rod

spac

ingDim

ensio

ns of

ducti

ng

Air delivery

or les

sMa

x. rise

Dimensions of ducting

Dimen

sions

of du

cting

Air delivery

or les

sMa

x. rise

Dimensions of ducting

Dimen

sions

of du

cting

Air delivery

or les

sMa

x. rise

Dimensions of ducting

Space for installation and service

obstacleor more

obstacleView from lower side

of unitInlet from rear with duct Inlet from rear or more

or more obstacle

or mo

re

or more obstacle

or mo

reor

more

or mo

re

Space for installation and service

obstacleor more

obstacleView from lower side

of unitInlet from rear with duct Inlet from rear or

more

or more obstacle

or mo

re

or more obstacle

or mo

reor

more

or mo

re

Space for installation and service

obstacleor more

obstacleView from lower side

of unit

Inlet from rear with duct Inlet from rear

or more

obstacle or mo

re or mo

re

or more

obstacle or mo

re or mo

re

Ref. ItemModel FDUT36KXE6F-E

A Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flare

C1 Condensate drain VP25 (used with connected connector)

C2 Condensate drain (dr. nat.) VP25 (used with connected connector)

D Hole for electrical cables ø 25 x 2E Suspension rods M10F Inspection hole 450 x 450; 270 x 770

All measurements are in mm.

FDUT 45~56KXE6F-E

FDUT 71KXE6F-E

FDUT 15~36KXE6F-E

Page 77: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

156

Ducted compact

› 3 power levels (2.20 ~ 3.60 kW)› Maximum compactness: only 25.7 cm in height.› Maximum installation flexibility› Rear air intake from back› Extremely quiet: only 27 dB(A)› UH-DU-E condensate drain kit (optional)› UH-FL-1E filter kit (optional)

The electrical box and the condensate drain pump can be installed on both sides of the unit, while the incoming air penetrates through the bottom or the back.The lowest noise impact on the market makes the unit suitable for installation in rooms designed to ensure comfort and relaxation. Compact and lightweight, FDUH is ideal for installation in hotels, hospitals and small offices.Furthermore, the application of the RCH-E3 remote control (optional) enables the user to take advantage of a simplified device to prepare and make the environment to be air conditions as comfortable as possible.

Electrical box

Condensate drain fall

ELECTRICAL BOX

Model FDUH22KXE6F FDUH28KXE6F FDUH36KXE6FNominal Cool. capacity kw 2.20 2.80 3.60Nominal Heat. capacity kw 2.50 3.20 4.00Power 220-240V~ 50HzCool. power consumption kw 0.05 - 0.07 0.05 - 0.07 0.05 - 0.07Heat. power consumption kw 0.05 - 0.07 0.05 - 0.07 0.05 - 0.07Rated cool. current in A 0.25 - 0.32 0.25 - 0.32 0.25 - 0.32Rated heat. current in A 0.25 - 0.32 0.25 - 0.32 0.25 - 0.32Sound pressure level dB(A) Hi 33 Me 30 Lo 27Sound power level dB(A) 60External dimensions (HxLxD) mm Unit 257 x 570 x 530Net weight kg 22Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 1Motor W 30Starting method Direct, in lineAir flow (standard) m3/h Hi 420 Me 390 Lo 360Static pressure Pa 30Renewal air inlet Not possibleAir filter and quantity OptionalShock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2")

Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories UH-FL1E (filter); UH-DU-E (condensate drain pump)

Indoor units

VRF Multi systems

FDUH 22~36KXE6F

Page 78: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

157

Diagrams and measurements

Ref. ItemModel FDUH22~28KXE6F FDUH36KXE6F

A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC1,2 Condensate drain VP20 (note 2)D Hole for electrical cables ø 30E Suspension rods M10F Inspection hole 635 x 890 (note 3)

Notes: 1. The label with the model code is applied inside the extraction grille.2. Prepare the connection for the VP20 condensate drain on site (for drain pipes you can choose C1 or C2).3. When the electrical box is found on the rear, the installation space must be modified for this new position.4. The electrical box and condensate drain pipe can be moved to the rear.

Space for installation and serviceSuspension rod spacing

Electrical box

Holes for self-tapping screws

Condensate pipe(accessory)On-site connection (note 4)

Air delivery

Dimensions of ducting

Dimen

sions

of du

cting

air ou

tlet

Note 4Su

spen

sion r

od sp

acing

Holes for self-tapping screws

VIEW G

VIEW G

Lower plate(Can be located on the rear side)

(Can be located on the rear side)

Holes for self-tapping screws

In case of bottom air intake

All measurements are in mm.

FDUH 22~36KXE6F

Page 79: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

158

› 8 power levels (1.50 ~ 9.00 kW)› Simple, modern design for seamless integration into any environment (1.50~5.60 kW)› Maximum compactness: only 23 cm in depth (1.50~5.60 kW models)› Simplified maintenance and cleaning thanks to the easily

removable front panel

Wall

Indoor units

VRF Multi systems

Model FDK15KXZE1 FDK22KXZE1 FDK28KXZE1 FDK36KXZE1 FDK45KXZE1 FDK56KXZE1 FDK71KXZE1 FDK90KXZE1Nominal Cool. capacity kW 1.50 2.20 2.80 3.60 4.50 5.60 7.10 9.00Nominal Heat. capacity kW 1.70 2.50 3.20 4.00 5.00 6.30 8.00 10.00Power 220-240V~ 50HzCool. power consumption kW 0.02 0.02 0.02 0.03 0.03 0.03 0.04 0.05Heat. power consumption kW 0.02 0.02 0.02 0.03 0.03 0.03 0.04 0.05Rated current in Cool. A 0.18 - 0.16 0.18 - 0.16 0.18 - 0.16 0.27 - 0.25 0.27 - 0.25 0.27 - 0.25 0.34 - 0.31 0.42 - 0.39Rated current in Heat. A 0.18 - 0.16 0.18 - 0.16 0.18 - 0.16 0.27 - 0.25 0.27 - 0.25 0.27 - 0.25 0.34 - 0.31 0.42 - 0.39Sound pressure level in Cool. dB(A) PHi 38 Hi 34 Me 31 Lo 28 PHi 38 Hi 36 Me 32 Lo 28 PHi 38 Hi 36 Me 32 Lo 28 PHi 40 Hi 38 Me 33 Lo 28 PHi 43 Hi 41 Me 36 Lo 33 PHi 43 Hi 41 Me 36 Lo 33 PHi 42 Hi 40 Me 37 Lo 35 PHi 44 Hi 42 Me 39 Lo 35Sound pressure level in Heat. PHi 38 Hi 34 Me 31 Lo 28 PHi 38 Hi 36 Me 32 Lo 28 PHi 38 Hi 36 Me 32 Lo 28 PHi 40 Hi 38 Me 33 Lo 28 PHi 43 Hi 41 Me 36 Lo 33 PHi 44 Hi 42 Me 37 Lo 33 PHi 42 Hi 40 Me 37 Lo 35 PHi 44 Hi 42 Me 39 Lo 35Sound power level in Cool. dB(A) 54 55 55 58 58 58 59 61Sound power level in Heat. 54 55 55 58 58 61 59 61External dimensions (HxLxD) mm 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 290 × 870 × 230 339 × 1197 × 262 339 × 1197 × 262Exterior appearance Snow whiteMunsell colour (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similar (8.0Y9.3/0.1) similarNet weight kg 11.5 11 11 12 11.5 11.5 17 17Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Tangential × 1Motor W 42 42 42 42 42 42 56 56Starting method Direct, in lineAir flow in Cool. m3h PHi 342 Hi 300 Me 270 Lo 216 PHi 510 Hi 480 Me 360 Lo 300 PHi 510 Hi 480 Me 360 Lo 300 PHi 660 Hi 600 Me 480 Lo 420 PHi 720 Hi 660 Me 540 Lo 480 PHi 720 Hi 660 Me 540 Lo 480 PHi 1260 Hi 1140 Me 960 Lo 840 PHi 1380 Hi 1260 Me 1140 Lo 960Air flow in Heat. PHi 342 Hi 300 Me 270 Lo 216 PHi 510 Hi 480 Me 360 Lo 300 PHi 510 Hi 480 Me 360 Lo 300 PHi 660 Hi 600 Me 480 Lo 420 PHi 720 Hi 660 Me 540 Lo 480 PHi 780 Hi 720 Me 600 Lo 480 PHi 1260 Hi 1140 Me 960 Lo 840 PHi 1380 Hi 1260 Me 1140 Lo 960Static pressure Pa 0Renewal air inlet Not availableAir filter and quantity Propylene mesh filter x 2 (washable)Shock and vibration absorption Rubber vibration absorber (for fan motor)Thermal and acoustic insulation Polyurethane foam

Control devices Wired remote control: RC-EX3, RC-E5, RCH-E3Remote control kit: RCN-K-E2 Remote control kit: RCN-K71-E2

Ambient temperature control Electronically-controlled thermostat

Safety devices Thermal protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø6.35 (1/4”) Liquid side ø9.52 (3/8”)Gas side: ø9.52 (3/8”) Gas side ø12.7 (1/2”) Gas side ø15.88 (5/8”)

Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP16Piping insulation Necessary (on both sides, liquid and gas)Accessories included Assembly kit

FDK 15~90KXZE1

FDK 15~56KXZE1

NEW

FDK 71~90KXZE1

Page 80: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

159

Diagrams and measurementsAll measurements are in mm.

Ref. ItemModel FDK22~28KXZE1 FDK36~56KXZE1

A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Hole for right rear pip. ø 65D Hole for left rear pip. ø 65E Condensate drain pipe VP16F Electrical cable outletG Pipe output (both sides)

Pipe output from bottom(see image above)

(Service space)

Installation plate Unit

Space for installation and maintenance front view

Ref. ItemModel FDK 71~90KXZE1

A Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC Hole for right rear pip. ø 65D Hole for left rear pip. ø 65E Condensate drain pipe VP16F Electrical cable outletG Pipe output (both sides)

(Service space)

(Serv

ice sp

ace)

(Serv

ice sp

ace)

Electrical box

Pipe output from bottom(see image above)

(Service space)Installation plate Unit

Space for installation and maintenance front view

(Service space)

(Serv

ice

spac

e)

Electrical box

(Serv

ice

spac

e)

FDK 71~90KXZE1

FDK 15~56KXZE1

Page 81: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

160

Ceiling

› 6 power levels (3.60 ~ 14.0 kW)› Ideal for very large environments, thanks to the particularly wide air flow› Maximum compactness: only 21 cm high (3.60 to 7.00 kW models)› Quick and easy installation, thanks to a net weight of only 28 kg (3.60 to 5.60

kW models)› Reception kit for RCN-E-E2 infrared remote control (optional)

FLEXIBLE PIPE ORIENTATION

Maximum flexibility: the refrigerant piping can be attached in 3 different positions (rear, top, right), as can that of the condensate drain (left, right).

Top

Rear

Right

Indoor units

VRF Multi systems

Model FDE36KXZE1 FDE45KXZE1 FDE56KXZE1 FDE71KXZE1 FDE112KXZE1 FDE140KXZE1Nominal Cool. capacity kW 3.60 4.50 5.60 7.00 11.20 14.00Nominal Heat. capacity kW 4.00 5.00 6.30 8.00 12.50 16.00Power 220-240V~ 50HzCool. power consumption kW 0.05 - 0.06 0.05 - 0.06 0.05 - 0.06 0.10 - 0.11 0.14 - 0.16 0.16 - 0.18Heat. power consumption kW 0.05 - 0.06 0.05 - 0.06 0.05 - 0.06 0.09 - 0.10 0.13 - 0.15 0.15 - 0.17Rated current in Cool. A 0.25 - 0.26 0.25 - 0.26 0.25 - 0.26 0.46 - 0.48 0.65 - 0.67 0.77 - 0.78Rated current in Heat. A 0.23 - 0.25 0.23 - 0.25 0.23 - 0.25 0.42 - 0.44 0.59 - 0.63 0.70 - 0.72Sound pressure level dB(A) Hi 39 Me 38 Lo 36 Hi 39 Me 38 Lo 36 Hi 39 Me 38 Lo 36 Hi 41 Me 39 Lo 37 Hi 44 Me 41 Lo 39 Hi 46 Me 44 Lo 43Sound power level dB(A) 60 60 60 62External dimensions (hxlxd) mm 210 × 1.070 × 690 210 × 1.070 × 690 210 × 1.070 × 690 210 × 1.320 × 690 250 × 1.620 × 690 250 × 1.620 × 690Exterior appearance Chalk whiteMunsell colour (6.8Y8.9 / 0.2 ) similarNet weight kg 28 28 28 37 49 49Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2 Centrifugal fan x 4Motor W 25 25 25 20 × 2 30 × 2 40 × 2Starting method Direct, in lineAir flow (standard) m3h Hi 600 Me 540 Lo 420 Hi 600 Me 540 Lo 420 Hi 600 Me 540 Lo 420 Hi 960 Me 840 Lo 720 Hi 1560 Me 1380 Lo 1260 Hi 1740 Me 1560 Lo 1380Static pressure Pa 0Renewal air inlet Not possibleAir filter and quantity Plastic mesh filter x 2 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-E-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side ø6.35 (1/4”) Liquid side ø9.52 (3/8”)Gas side ø12.7 (1/2”) Gas side ø15.88 (5/8”)

Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit

FDE 36~140KXZE1

Page 82: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

161

Diagrams and measurements

Space for installation and service

obstacle

When installing more than one unit, it is necessary to keep a distance of 4 m or more between one machine and the next.

or more

Condensate pipe (accessory)On-site connection

Suspension rod spacing

or mo

re

Air delivery

Extraction grille

Suspension rod spacing

The slope of the condensate drain pipe inside the unit must be 10 mm.

Ref. ItemA Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC1,2 Condensate drain VP20D Hole for suspension cables M10 or M8E Rear pre-cut PE coverF Top pre-cut Cover plateG Hole for condensate drain Pre-cut

or more

or more

Position for bottom and top pre-cut

Hole for condensate drain pipe (left output)

Piping can be connected in 3 different directions. Remove the pre-cut part, using a cutter of a similar instrument.

Notes: 1. The label with the model code is applied inside the extraction grille.

Space for installation and service

obstacle

When installing more than one unit, it is necessary to keep a distance of 4.5 m or more between one machine and the next.

or more

Condensate pipe (accessory)On-site connection

Suspension rod spacing

or mo

re

Air delivery

Extraction grille

Suspension rod spacing The slope of the condensate drain pipe inside the unit must be 10 mm.

Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1,2 Condensate drain VP20D Hole for suspension cables M10 or M8E Rear pre-cut PE coverF Top pre-cut Cover plateG Hole for condensate drain Pre-cut

or moreor more

Position for bottom and top pre-cut

Hole for condensate drain pipe (left output)

Piping can be connected in 3 different directions. Remove the pre-cut part, using a cutter of a similar instrument.

Notes: 1. The label with the model code is applied inside the extraction grille.

Right pre-cut

Right pre-cut

Space for installation and service

obstacle

When installing more than one unit, it is necessary to keep a distance of 5 m or more between one machine and the next.

or more

Condensate pipe (accessory)On-site connection

Suspension rod spacing

or mo

re

Air delivery

Extraction grille

Suspension rod spacing

The slope of the condensate drain pipe inside the unit must be 10 mm.

Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC1,2 Condensate drain VP20D Hole for susp. cables M10 or M8E Rear pre-cut PE coverF Top pre-cut Cover plateG Hole for condensate drain Pre-cut

or more

or more

Position for bottom and top pre-cut

Hole for condensate drain pipe (left output)

Piping can be connected in 3 different directions. Remove the pre-cut part, using a cutter of a similar instrument.

Notes: 1. The label with the model code is applied inside the extraction grille.

Right pre-cut

All measurements are in mm.

FDE 71KXZE1

FDE 112~140KXZE1

FDE 36~56KXZE1

Page 83: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

162

Console

› 3 power levels (2.80 ~ 5.60 kW)› Particularly wide, uniform air flow› Maximum compactness: only 23.8 cm in depth› Quick and easy installation, thanks to a net weight of only 19 kg (2.80 kW model)› Reception kit for RCN-FW-E2 infrared remote control (optional)

Simultaneous louver selection - top and bottom - can be selected at the same time using the special button. Control all other functions on the unit with the special remote control.

With infrared remote control use

UNIFORM AIR DISTRIBUTION

Model FDFW28KXE6F FDFW45KXE6F FDFW56KXE6FNominal Cool. capacity kW 2.80 4.50 5.60Nominal Heat. capacity kW 3.20 5.00 6.30Power 220-240V~ 50HzCool. power consumption kW 0.02 - 0.02 0.02 - 0.02 0.03 - 0.03Heat. power consumption kW 0.02 - 0.02 0.02 - 0.02 0.03 - 0.03Rated cool. current in A 0.10 - 0.09 0.10 - 0.09 0.15 - 0.14Rated heat. current in A 0.10 - 0.09 0.10 - 0.09 0.15 - 0.14Sound pressure level dB(A) Hi 36 Me 34 Lo 30 Hi 38 Me 36 Lo 33 Hi 44 Me 37 Lo 33Sound power level dB(A) 55 57 60External dimensions (HxLxD) mm 600 x 860 x 238Exterior appearance Fine snowMunsell colour ( 8.0Y9.3 / 0.1 ) similarNet weight kg 19 20Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Turbo fan x 1Motor W 40Starting method Direct, in lineAir flow (standard) m3/h Hi 540 Me 480 Lo 420 Hi 660 Me 540 Lo 480Static pressure Pa 0Renewal air inlet Not possibleAir filter and quantity Propylene mesh filter x 1 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional ; RCN-FW-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4")Gas side: ø 9.52 (3/8") Gas side: ø 12.7 (1/2")

Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP16 (I,D, 16.0)Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit

Indoor units

VRF Multi systems

FDFW 28~56KXE6F

Page 84: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

163

Diagrams and measurements

Unit

Service space

Space for installation and maintenance front view

Pipe output from bottom(see image above)

Notes: 1. The label with the model code is applied inside the extraction grille.2. When installing on walls, leave the unit at least 150 mm from the ground.

Service space

Assembly plate

Ref. ItemModel FDFW28KXE6F FDFW45~56KXE6F

A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Hole for right rear pip. ø 65D Hole for left rear pip. ø 65E Condensate drain pipe VP16F Screw for fixing the indoor unit ø 5G Pipe output (both sides)

All measurements are in mm.

FDFW 28~56KXE6F

Page 85: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

164

Flush floor

› 4 power levels (2.80 ~ 7.10 kW)› Maximum compactness: only 63 cm high and 22.5 cm deep

Model FDFU28KXE6F FDFU45KXE6F FDFU56KXE6F FDFU71KXE6FNominal Cool. capacity kW 2.80 4.50 5.60 7.10Nominal Heat. capacity kW 3.20 5.00 6.30 8.00Power 220-240V~ 50HzCool. power consumption kW 0.09 - 0.10 0.09 - 0.10 0.09 - 0.10 0.09 - 0.10Heat. power consumption kW 0.09 - 0.10 0.09 - 0.10 0.09 - 0.10 0.09 - 0.10Rated cool. current in A 0.41 - 0.42 0.41 - 0.42 0.41 - 0.42 0.41 - 0.42Rated heat. current in A 0.41 - 0.42 0.41 - 0.42 0.41 - 0.42 0.41 - 0.42Sound pressure level dB(A) Hi 41 Me 38 Lo 36 Hi 43 Me 41 Lo 40Sound power level dB(A) 58 60External dimensions (HxLxD) mm 630 x 1077 x 225 630 x 1362 x 225Net weight kg 25 32Refrigerant circuit/Heat exchanger Pipes finned and grooved internallyRefrigerant control Electronic expansion valveAir treatment/fan type and quantity Centrifugal fan x 2Motor W 30 40Starting method Direct, in lineAir flow (standard) m3/h Hi 720 Me 660 Lo 600 Hi 840 Me 720 Lo 600 Hi 1080 Me 900 Lo 720Static pressure Pa 0Renewal air inlet Not possibleAir filter and quantity Propylene mesh filter x 1 (washable)Shock and vibration absorption Rubber sleeve (for fan motor)Thermal and acoustic insulation Polyurethane foamControl devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT4-E2, optional RC-EX3Ambient temperature control Electronically-controlled thermostat

Safety devices Overvoltage protection for the fan motorAnti-frost protection thermostat

Diameter cooling/refrigerant pipes mm (inch) Liquid side: ø 6.35 (1/4") Liquid side: ø 9.52 (3/8")Gas side:ø 9.52 (3/8") Gas side: ø 12.7 (1/2") Gas side: ø 15.88 (5/8")

Joining method by flare fittingsRefrigerant R410ACondensate drain Connectable with VP20Piping insulation Necessary (on both sides, liquid and gas)Accessories Assembly kit

Indoor units

VRF Multi systems

FDFU 28~71KXE6F

Page 86: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

165

Diagrams and measurements

DIMENSIONS

Model a b c d e

FDFU 28~56KXE6F 786 810 722 750 806FDFU 71KXE6F 1071 1095 1007 1035 1091

Notes: 1. The label with the model code is applied inside the extraction grille.

Ref. ItemModel FDFU28KXE6F FDFU45~56KXE6F FDFU71KXE6F

A Gas side ø 9.52 (3/8") flare ø 12.7 (1/2") flare ø 15.88 (5/8") flareB Liquid side ø 6.35 (1/4") flare ø 9.52 (3/8") flareC Condensate drain Lead screw PT20A, 360 mmD Slot M10E Metal arms for floor fixing M8

Slot

Air filter

Electrical box

Level adjustment screw

Slot

Hose

Electronic expansion valve box

Space for installation and service

lining lining

All measurements are in mm.

FDFU 28~71KXE6F

Page 87: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

166

The simple and flexible solution for increasing comfort in buildings, with high energy performance

DXA-DU-E: condensate drain kit up to 60 cm (optional)

The SAF DX units, available in 5 power ratings, is a device designed to increase the comfort capacity of KXZ systems located in buildings, with their high quality profile in terms of energy.Extremely flexible in that it operates independently from the regenerator, it is able to optimise temperature of the primary air taken in by the SAF regenerators or by similar systems installed in the building. Its compact size and installation separate from the fan unit, solve numerous installation problems; the lack of moving parts makes it possible to install the unit in a wider range of locations and reduces noise to a minimum.

•CanbecombinedwithallindoorandoutdoorunitsintheKXZrange*.

•CanbeconnectedtotheSuperlinknetworkandalltheavailablecentralised controls.

•ItispossibletousealltheKXZserieslocalcontrols(tointegrateinto the system seamlessly and easily).

•Thecondensatedrainpumpisavailableasanoptional.•Theextractiontemperatureordeliverytemperaturecanbe

controlled alternately**.

Note* If using the SAF DX, the load index available for the outdoor unit is reduced to 100% of

the rated capacity.** The available options vary depending on configurations.

The SAF DX post-treatment is not intended to replace an indoor unit.

SAF DX

Indoor air

Air expelled

Outside air

Heatexchanger

Inlet air

Renewal air delivery T. sensorT Sensor. air renewal

Direct expansion coil for heating or cooling

Unit model SAF DX250E6 SAF DX350E6 SAF DX500E6 SAF DX800E6 SAF DX1000E6Nominal Cool. capacity* kW 2.00 2.80 3.60 5.60 6.30Nominal Heat. capacity* kW 1.80 2.20 2.80 4.50 5.60Power Single phase 220-240V~ 50HzCool. power consumption W 7.20Heat. power consumption W 7.20Rated cool. current in A 0.05Rated heat. current in A 0.05External dimensions (HxLxD) mm 315 x 452 x 422 315 x 537 x 422 315 x 682 x 422 315 x 822 x 422Net weight kg 12.3 13.6 16.1 18.4Air flow (standard) m3/h 250 350 500 800 1000Static pressure Pa 38 66Control devices Optional wired remote control RC-E5, optional RCH-E3, optional RCN-KIT-3-E

Diameter cooling/refrigerant pipes mm (in) Liquid side: ø 6.35 (1/4”) Liquid side: ø 6.35 (1/4”) Liquid side: ø 9.52 (3/8”)Gas side: ø 9.52 (3/8”) Gas side: ø 12.7 (1/2”) Gas side: ø 15.88 (5/8”)

* Measured under the conditions specified in the table.

Inlet air temperature/ventilation Outdoor temperature StandardMode DB WB DB WBCooling * 27° C 19° C 35° C 24° C ISO- T1Heating** 20° C 7° C 6° C

** ISO-T1-compliant test.

Post-treatment modular unit SAF DX

SAF DX250E6SAF DX350E6SAF DX500E6SAF DX800E6SAF DX1000E6

SAF DX250~1000E6

Page 88: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

167

Diagrams and measurements

Space for installation and service Space for installation and service

Dimensions of ducting

Electrical box

Indoor air

Outside airDim

ensio

ns of

ducti

ng

Inspection holeInspection hole

Dimensions of ducting

Electrical box

Indoor air

Outside air

Dimen

sions

of du

cting

Label with model code

Label with model code

Ref. ItemA Gas side ø 9.52 (3/8") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain R1D Hole for power supply lineE Wiring holeF Suspension rods M10

Ref. ItemA Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain R1D Hole for power supply lineE Wiring holeF Suspension rods M10

Space for installation and serviceSpace for installation and service

Dimensions of ducting

Electrical box

Indoor air

Outside air

Dimen

sions

of du

cting

Inspection holeInspection hole

Dimensions of ducting

Electrical box

Indoor air

Outside air

Dimen

sions

of du

cting

Label with model code

Label with model code

Ref. ItemA Gas side ø 12.7 (1/2") flareB Liquid side ø 6.35 (1/4") flareC Condensate drain R1D Hole for power supply lineE Wiring holeF Suspension rods M10

Ref. ItemA Gas side ø 15.88 (5/8") flareB Liquid side ø 9.52 (3/8") flareC Condensate drain R1D Hole for power supply lineE Wiring holeF Suspension rods M10

All measurements are in mm.

Post-treatment modular unit SAF DX

SAF DX500E6SAF DX250E6, SAF DX350E6

SAF DX1000E6SAF DX800E6

Page 89: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

168

EEV-KIT is a control kit for any type of AHU and/or fan coil with direct expansion coil that can be found on the market, which permits connection with KXZ OU.EEV-KIT consists of an electronic control system and an electronic expansion valve for refrigerant flow control.

(Air handling unit*) OU

* Can be found by different manufacturers on the market

Type of systemEEV-KIT

EEVKIT6-E-M EEVKIT6-E-CSingle - 1 or more boxes in parallel*

Multiple 1 box (Master) Multiple boxes (Slave)

Applications

Model EEV6-71-E EEV6-160-E EEV6-280-ESize (kW) 2.20~7.10 9.00~16.00 22.40~28.00

* Can connect to a single cooling system. In the case of more than one cooling system, make sure to use EEV-KIT control ASSY for multiple systems.

EEV-Control Assy EEV-Set

EEV-Set

FanFan

System configuration

• Inthecaseofasinglecoolingsystem,youmustuseoneEEVKIT6-E-C control for each expansion valve up to a maximum of 32.

• Inthecaseofamultiplecoolingsystem,youmustuseoneEEVKIT6-E-M 1 master control + no. EEVKIT6-E-C controls up to a maximum of 32.

• TheEEVKIT6-E-Ccontroliscommonuseforsingleandmultiplesystems.

Single cooling systemAsystem composed of several outdoor units with a single cooling circuit (see the two examples below). In the figure to the left, system A uses one single EEV-KIT. In the figure to the right, system B uses more than one EEV-KIT.

System A System B

This system only has an EEV-KIT installed on an internal coil consisting of a single exchanger. This type of system can be applied to internal coils with maximum power 10HP (28 kW).

It is a system that has more than one EEV-KIT installed in an internal coil consisting of multiple exchangers in a single cooling circuit. This system can reach a maximum power of 60HP (KXZ), 48HP (KXE6).

AHU

Control

valve 1

valve 2

control 1

control 2

AHU control system EEV-KIT

Page 90: VRF MULTI SYSTEMS - Mitsubishi Heavy Industries€¦ · 83 kxzrx hi-cop kxzr 3-pipe kxzw water new new outdoor heat recovery units 22.40 kw 28.00 kw 33.50 kw 8hp 10hp 12hp fdc224kxzre1

169

RC-E5

SC-SL4-AE/BE

SC-SL4-AE/BE

RC-E5

Advantages

• Possibilityofexpandingthesystemwithrespecttothesinglesystemuptoapowerof896kW (indoor unit: composed of 32 circuits, 28 kW).• Possibilityofremotecontrolthroughaspecialconnector.•Possibilityofcontrollingsteps.

SUPERLINK II CONNECTION

AHU

Fan

Master control

This system is composed of an air handling unit with the following characteristics:1. Multiple cooling circuits2. Presence of a Master control system that controls the whole system.

Multiple cooling system

Parts to be added to the single cooling system

•AMastercontrolsystem.• TheSlavecontrolsystemandtheexpansionvalvearethesamethatareusedforthesingle

cooling system.

EEV Master control

2 sensors

Air intake Delivery air

EEV Slave control

3 sensors1 EEV-KIT

filters filters

Heat exchanger temperature sensors (Thi-R1, R2, R3)

EEV Slave control

3 sensors1 EEV-KIT

filters filters

Heat exchanger temperature sensors (Thi-R1, R2, R3)

Single cooling system

System A

System B

Control line from remote

Superlink adapter

Multiple system

Multiple cooling system

Superlink adapter

Control line from remote

System A

DX-FCU: Direct expansion fan coilDX-AHU: Direct expansion air handling unit

Control system for UTA EEV-KIT