VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf ·...

21
AN ISO 9001 & 14001 COMPANY TENDER DOCUMENT TENDER No: DLI/CON/729/560 FOR “External & Internal Electrical works including Supply, Installation, Testing & Commissioning of Transformers, Electrical HT/LT Panels, Air-conditioning & Fire Fighting works for 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No.04- 3333, Action Area – 1D, New Town, Kolkata”. VOLUME – III PRICE BID/ BILL OF QUANTITY

Transcript of VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf ·...

Page 1: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

AN ISO 9001 & 14001 COMPANY

TENDER DOCUMENT

TENDER No: DLI/CON/729/560

FOR

“External & Internal Electrical works including Supply, Installation, Testing & Commissioning of Transformers, Electrical HT/LT Panels, Air-conditioning & Fire Fighting works for 1st Phase (B+G+IV) of Administrative Building of New

Town Kolkata Development Authority at Plot No. DG/13, Premises No.04-3333, Action Area – 1D, New Town, Kolkata”.

VOLUME – III

PRICE BID/ BILL OF QUANTITY

 

Page 2: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Engineering Projects (India) Ltd. (A Govt. Of India Enterprise) 

 Abstract Sheet

Tender No: DLI/CON/729/560

Tender for “External & Internal Electrical works including Supply, Installation, Testing & Commissioning of Transformers, Electrical HT/LT Panels, Air-conditioning & Fire Fighting works for 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No.04-3333, Action Area – 1D, New Town Kolkata”.

Total Estimated Value: Rupees .Seven Cores thirteen lakh twenty thousand two hundred sixty only. 

Note : The above prices are including of all taxes and duties etc.. 

Sl. No. Item Description Value (in Rs.)1 HT Sub-Station 10997060.422 Generator & AMF panel 9619588.293 Air condition system with VRF 24635119.004 Compound Lighting 5470262.295 Fire 14812025.25

Total 65510055.25Add Tender Premium -1 @ 8.44% 5529048.66

Total 71039103.91Add Tender Premium -2 @ 0.40% 284156.41

Total= 71323260.32Say= 7,13,23,260.00

Page 3: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1 ELECTRICAL SECTION ‐I ( Sub Station)Transformer & AccessoriesSupply, installation, testing and commissioning of 750KVA, 11/0.433KV, 3 Phase, 4 wire, 50 Hz, ONAN transformer for indoorduty with a ‐20% to +5% Off‐load tap changer in the step of 1.25%, cable box at primary and secondary end with double floatbuchholz relay protection, high winding & oil temparature sensors ‐ Alarm & Trip, and at neutral earthing conductor withcontrol cabling from transformer to HT Breaker (to trip primary breaker) complete with all fittings, interconnection of controlcables and accessories , first filling of oil as per detailed technical specifications and as required.(Voltamp / ABB / Areva / Tesla)

2 Set       14,99,432.87  29,98,865.74                     

HT PanelSupply, delivery, erection, testing and commissioning of Three (3) panel, 630 Amps, 11KV, 3‐Phase, 50HZ, metal clad, dead front, 350MVA rupturing capacity Vacuam Circuit Breaker as per the detailed specifications and drawings including connections, etc. complete with following incommers and outgoings as required.(Siemens / ABB / Areva)Incommer:1 No. VCB Pannel having the following.1 No. 630A, 11KV, 3 Phase, 50HZ, metal clad, dead front, 350 MVA rupturing capacity, Fully drawout type , Vacuum Circuit Breaker(Breaker Breaking capacity ‐25KA).1 No. 11KV/110V resin cast Potential Transformer with HRC fuses.having accuracy class‐1 for metering1 set of Phase indicating lamp with HRC fuses.                                                                                                                1 No. 0‐15KV voltmeter with selector switch1 set of indicating lamps to indicate ON,OFF,TRIP ,Spring Charge & TRIP CIRCUIT HEALTHY.)2 No. Push Buttom for CLOSE and TRIP.1 no.Trip /Neutral/Close Switch1 no.Local/Remote Switch1 No. 100/5‐5A Current Transformer for metering and protection(accuracy class‐‐0.5 for metering & 5P10 for protection) 1 No 0‐100 Amps ammeter with selector switch.1 set of CDG 61(2 No.O/C, 1 No. E/R relay (electromagnetic/electrostatic) 1 set of Undervoltage relay and Overvoltage relay.(Electromagnetic)1 no 30V DC shunt trip coil & 1 no.30V DC closing coil.1 No. Master Trip relay.(Electromagnetic)1 No. Power factor meter.

1 no.Trivectormeter 1 no.Frequency MeterBusbar: 11 KV, 350 MVA, 800 Amps Three Phase busbars of Cu.for Incomer & Outgoing2 nos.Outgoings:1 No. VCB Pannel having the following1 No. 630A, 11KV, 3 Phase, 50HZ, metal clad, dead front, 350 MVA rupturing capacity, Fully drawout type , Vacuum Circuit Breaker(VCB breaking capacity ‐25KA)1 set indicating lamps to indicate ON, OFF, TRIP, SPRING CHARGED, TRIP CIRCUIT HEALTHY.2 No. Push Buttom for CLOSE and TRIP.1 no.Trip/Neutral/Close Switch1 no.Local/Remote Switch1 No. 50/5‐5A Current Transformer for metering and protection.1 No 0‐50 Amps ammeter with selector switch.1 set of CDG 61(2 No.O/C, 1 No. E/R relay (Electromagnetic/electrostatic).1 No Master Trip Relay(Electromagnetic).2 Set ofAuxiliary relay  Buchholz,Oil & winding temp  Protaction with alarm and trip signals.(Electromagnetic)1 no.buzar with Push Buttor for common to the SwitchboardH.T. Panel as mentioed aboveElectrical Interlocking between HT,LT & Generator set will be done accordingly as per scheme.Necessary scheme will be intimated at the time of drawing approval.

3 Battery Chager: Supply, delivery, erection, testing and commissioning of the battery charger panel complete with battery control cabling, etc. as required. Rate shall also include provision of minimum 200 AH 30/24 volt SMF.VRLA Battery including Float cum Boost Thyrister/IGBT controlled.battery charger with one no. as Hot standby suitable for operation at240 volt AC 50 Hz supply,1 No. AC Voltmeter (0 ‐ 500 Volt).1 No. DC Voltmeter.1 No. DC Ammeter.1 set of AC and DC indicating lamps.1 No. DC Battery charging position indicator.DCDB with 63A DP MCB as incomer and 16 nos SP MCB as outgoing complete as per specifications and suitable to above.Control cabling between DC Distribution panel to the HT panel of the Substation with cable size 4C X 2.5 Sqmm. Copper cable.Battery Charger Panel as mentioned above

1 set          2,23,948.31  2,23,948.31                       

4 Safety EquipmentsSupply and laying of 12 KV grade, 12mm, 1 metre wide anti skid chequered type rubber mat. 100 sqmm 869.61                   86,961.00                           

5 Supply and laying of 1.1 KV grade 12mm, 1 metre wide anti skid chequered type rubber mat. 500 sqmm 417.13                   2,08,565.00                       6 Supply and installation of Fire Buckets 13 litre capacity 4 Nos. duly filled with sand and GI pipe support stand for these buckets

including painting, etc. complete as required. 4 Set 1,457.43               5,829.72                             

7 Supply and fixing shock treatment chart in English, Hindi and local language mounted on 5mm. Thick plywood and 3mm. Thickplain glass front complete as required.

4 Set 325.22                   1,300.88                             

8 Supply and fixing of ISI marked 6.5 kg Co2 type portable fire extinguisher with necessary clamps, supports and trolley in Panelroom approved by ISI complete as required. 6 Set 7,374.01               44,244.06                           

9 Supply, storing, handling and fixing in position First Aid Medical Box and an 'Artificial Respirator' complete as per technicalspecifications as required.

5 Each 522.17                   2,610.85                             

10 Supply and testing of 11KV ISI marked hand gloves 2 Each 517.12                   1,034.24                             

ENGINEERING PROJECTS (INDIA) LIMITED( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No. 04‐3333, Action Area ‐ 1D, New Town 

Tender No: DLI/CON/729/560                                                             Dated 08.12.2016

BILL OF QUANTITIES

1 set       17,16,938.39  17,16,938.39                     

2

Page 4: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)11 Supply, installation, testing and commissioning of self contained emergency light unit consisting of 1X20 watt fluorescent tube

and dry type SMF battery for 1 hour backup complete as required.2 Each 2,012.93               4,025.86                             

12 H.T. Cables Supply, laying, testing and commissioning of following sizes of 11KV grade multicore aluminium conductor XLPE armoured power cable directly in duct/hume pipe as per IS : 7098(contractor to measure exact required quantity before supply as per installation position) (Nicco / Polycab)

12.1  3C X 240 Sq.mm. 200 M 2,421.98               4,84,396.00                       12.2  3C X 120 Sq.mm. 69 M 1,498.84               1,03,419.96                       13 H.T. Cable Terminations.

Supplying and making end termination with heat shrinkable jointing kit(outdoor type) with Raychem kits complete with allaccessories including lugs suitable for following size 3 core, XLPE aluminium conductor cable of 11KV grade as required.

13.1  3C X 240 Sq.mm. 1 Each 19,311.20             19,311.20                           13.2  3C X 120 Sq.mm. 1 Each 19,311.20             19,311.20                           14 Supplying and making end termination with heat shrinkable jointing kit(indoor type) with Raychem kits complete with all

accessories including lugs suitable for following size 3 core, XLPE aluminium conductor cable of 11KV grade as required.

14.1  3C X 240 Sq.mm. 3 Each 12,401.79             37,205.37                           14.2  3C X 120 Sq.mm. 4 Each 11,852.35             47,409.40                           15 Supply and laying of following sizes non pressure NP2 class(light duty) RCC pipe(300mm) with collar joint with stiff mixture of

cement (1‐cement : 2‐fine sand) including testing the joints, etc. as per specification and required. 15 Metre 792.85                   11,892.75                           

15.1 Cable TraySupply and Erecting of perforated type Hot dip G.I. cable tray of 14G of specific dimensions. The cable tray shall be hung fromceiling/ fixed to wall with necessary ceiling suspensors, tee, nots, nuts etc, together with tees, bends etc. All necessaryrequired hard ware for mounting cable tray along with fabricated supports as per site condition shall be included in cable trayrate. The tray shall be continuously earthed with included in cable tray rate. The tray shall be continuously earthed with 25 x 6mm GI Flat. The cost of GI Flat shall be included along with cable tray rates complete as per specification.(Rattan Eng.)

15.2  150 x 75 mm 200 Meter 909.00                   1,81,800.00                       15.3 300 x 75 mm 150 Meter 1,616.00               2,42,400.00                       16 LT CABLES 

Supply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cable supports provided, includeunloading, shifting upto site. The scope includes clamping of cables by ready made G.I. spacers, saddles or clamps fabricatedout of GI strip 3 mm thick.                    (NICCO /POLYCAB /SKYTONE / NATIONAL / GLOSTER/ECKO)

16.1  4C X 16Sq.mm. ‐ Al stranded for Substation & lighting panel 350 Metre 197.96                   69,286.00                           16.2  3.5C X 300Sq.mm. ‐ Al for FIRE PNL & Rising Main 160 Metre 1,356.43               2,17,028.80                       16.3 3.5C X 400Sq.mm. ‐ Al for trf, capacitor pnl, VRF & DG Set 550 Metre 1,732.15               9,52,682.50                       17 LT Cable Terminations: Supplying & fixing of double compression type Brass glands & making joint with necessary AL. / CU.

crimping socket of long neck type connecting the same to various equipment like section pillar, switch, starter, motor etc. forthe following sizes:(COMET/ CONNECT WEL/ DOWELS)

17.1  4C X 16Sq.mm. ‐ Al  4 End 104.54                   418.16                                17.2 3.5C X 300Sq.mm. ‐ Al 8 End 631.76                   5,054.08                             17.3 3.5C X 400Sq.mm. ‐ Al 32 End 631.76                   20,216.32                           18 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type connecting the same to various

equipment like section pillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

18.1 4C X 16Sq.mm. ‐ Al  4 Set 99.99                     399.96                                18.2 3.5C X 300Sq.mm. ‐ Al 8 Set 1,422.59               11,380.72                           18.3 3.5C X 400Sq.mm. ‐ Al 32 Set 2,111.91               67,581.12                           

DISTRIBUTION PANELMain L.T panel complete as per Technical Specifications/ data sheets/ SLD and applicable standards.Supply, delivery, erection, testing and commissioning of LT Panel, cubicle type, totally enclosed, free standing type, dust,damp and vermin proof panel made up of 14 SWG CRCA sheet, complete with copper busbars, danger notice plate,interconnections with suitable capacity copper leads / solid copper strips/rods, necessary interlocking, power coat painted andhaving incoming and outgoing switchgears as mentioned below and complete as per technical specifications and as required.1. All ACBs shall have 5 NO + 5 NC contacts2. All relays to operate at 240Volts, Single phase, 50Hz, AC supply through UPSIncommer:2 Nos. ACB Panels each having following.1 No. 1250A, 415/500V, Rated service short circuit rupturing capacity (Ics) 50 KA, Motorised, Fully Drawout type(EDO), FourPole, Air Circuit Breaker with microprocessor based overload, short circuit & earth fault trip including under voltage releaseand lockable trip push button. ACB should have Icw=50KA for 1 sec.(L&T / ABB )Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACBPush button to CLOSE the ACB.R, Y, & B Phase indicating lamps with 2A control SP MCBs1000/5A CTs with CT shorting links for power factor inprovement panel suitable for giving signal to APFCR at less than 10% ofsecondary ratio current.All Incoming ACBs shall have multi function meter ‐ parameters ‐ digital multifunction meter EM6400 or equivalent shallindicating A / V / KWH / PF / FREQ / DM / VAR with RS‐485 port with suitable CTs, CT shorting links.Busbar:

19

Page 5: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)2000 AMP,50KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length ‐ Current ratio shall be 1 sq mm = 0.8 A.Buscoupler:1 Nos. ACB Panels each having following.1 No. 1250A, 415/500V, Rated service short circuit rupturing capacity (Ics) 50 KA, Motorised, Fully Drawout type(EDO), FourPole, Air Circuit Breaker with microprocessor based overload, short circuit, Instanteneous & earth fault trip including undervoltage release and lockable trip push button. The ACB should have Icw=35KA for 1 sec.(L&T / ABB ).1 set of indicating lamps to indicate OPEN, CLOSE, TRIPPush button to CLOSE the ACB1 set of meter with ASS and CTsOUTGOINGS:5 No. MCCB as per following details / specifications:630 Amps, 415V, 50KA(Ics) FP MCCB with variable current settings of 0.4 to 1.0 In and having microprocessor based O/L, S/C &E/F protection release.(Legrand / L&T /ABB/Havells)Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should havespreader links & phase barriersIndicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB..R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs3 No. MCCB as per following details / specifications:500 Amps, 415V, 35KA(Ics) FP MCCB with variable current settings of 0.4 to 1.0 In and having microprocessor based O/L, S/C &E/F protection release.(Legrand / L&T /ABB/Havells)

Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should havespreader links & phase barriersIndicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB R,Y & B phase indicating lamps(LED type)with 2A control SP MCBs.2 No. MCCB as per following details / specifications:250 Amps, 415V, 25KA(Ics) FP MCCB with thermal magnetic release having variable current settings of 0.4 to 1.0 In.(Legrand /L&T /ABB/Havells)Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should havespreader links & phase barriers.Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB.R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs. 2 No. MCCB as per following details / specifications:150 Amps, 415V, 25KA(Ics) FP MCCB with thermal magnetic release having variable current settings of 0.4 to 1.0 In.(Legrand /L&T /ABB/Havells)Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should havespreader links & phase barriers.Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB.R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs.2 No. MCCB as per following details / specifications:100 Amps, 415V, 25KA(Ics) FP MCCB with thermal magnetic release having variable current settings of 0.4 to 1.0 In.(Legrand /L&T /ABB/Havells)Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should havespreader links & phase barriers.Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB.R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs.4 No. MCCB as per following details / specifications:63 Amps, 415V, 25KA(Ics) FP MCCB with thermal magnetic release having variable current settings of 0.4 to 1.0 In.(Legrand /L&T /ABB/Havells)Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should havespreader links & phase barriers.Indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for MCCB.R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs.All Outgoing MCCBs shall have multi function meter ‐ parameters ‐ digital multifunction meter shall indicating A / V / KWHwith RS‐485 port with suitable CTs, CT shorting links.ASS/VSS : Make ‐ KAYCEE/ L&T.Main LT Panel as mentioned above (T/N/C switch should be provided all the Incomer/Outgoing/Buscoupler panel)Electrical Interlocking between HT,LT & Generator set will be done accordingly as per scheme.Necessary scheme will beintimated at the time of drawing approval.

19.3 Capacitor Panel (250 KVAR)Supply, installation, testing, and commissioning of M.V. cubicle type, 14 SWG CRCA Sheet, totally enclosed free standing type,dust, damp and vermin proof capacitor panel complete with busbars, M.V. danger notice plate, ammeter, ammeter selectorswitch, indicating lamps, CT's , Extra heavy duty capacitors suitable for non linear loads upto 20% (L&T model MD‐XL orequivalent), contactors suitable for capacitor switching(current limiting contactor circuit to supress switching inrush current)interconnections with suitable capacity aluminium leads / solid aluminium strips, rods, connection of incoming and outgoingcables with thimbles, stove enamelled painted and having following incoming and outgoing switchgears complete asrequired.Incommer:1No. 500A, 415/500V , 35KA rupturing capacity, FP Moulded Case Circuit Breaker with thermal magneticx release havingvarible current setting of 0.8 to 1.0 In.Extended rotary operating mechanism with door interlock with defeat feature and padlock facility. MCCB should havespreader links & phase barriers.1 set of phase indicating lamps with HRC fuses.Incoming MCCB shall have multi functionmeter ‐ parameters ‐ digital multifunctionmeter shall indicating A / V / PF / VAR withRS‐485 port with suitable CTs, CT shorting links.Busbar:630 AMP,35KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length ‐ Current ratio shall be 1 sq mm = 0.8 AOutgoings:1 No. 100 KVAR capacitor bank each with 250 Amps TPN MCCB, 250A TP contractor suitable for capacitor switching with pushbuttons and indicators.(Legrand / L&T /Havells)

2 Set 4,30,027.70          8,60,055.40                       

1 Set 23,27,487.43       23,27,487.43                     

Page 6: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)1 No. 50 KVAR capacitor bank each with 125 Amps TPN MCCB, 100A TP contractor suitable for capacitor switching with pushbuttons and indicators.(Legrand / L&T /Havells) suitable for capacitor switching with push buttons and indicators.(Legrand /L&T /Havells)1no.40KVAR capacitor bank each with 100Amps TPN MCCB,100A TP contractor suitable for capacitor switching with pushbutton and indicators (Legrand/L&T/Havells)1 No. 30 KVAR capacitor bank each with 63 Amps TPN MCCB, 63A TP contractor suitable for capacitor switching with pushbuttons and indicators.(Legrand / L&T /Havells)1 No. 20 KVAR capacitor bank each with 63 Amps TPN MCCB, 63A TP contractor suitable for capacitor switching with pushbuttons and indicators.(Legrand / L&T /Havells)1 No. 10 KVAR capacitor bank each with 32 Amps TPN MCCB, 32A TP contractor suitable for capacitor switching with push buttons and indicators.(Legrand / L&T /Havells)1 No. Electronic type, microprocessor based, Automatic power factor correction relay in 8 steps

1,09,73,060.42                 

Page 7: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1 Electrical Section II (Generator & AMF Panel )LT cables Supply ,Laying of cables on cable trays/Hume pipes/structural supports/undergrounds and cablesupports provided ,include unloading ,shifting upto site.The scope includes clamping of cables byready made G.I spacers,saddles or clamps fabricated out of GI strip 3 mmthick.(Polycab/Havells/KEI)3.5CX400sq.mm ‐for DG set

650 Metre 1,732.51                  11,26,131.50           

2 LT Cable TerminationsSupplying & fixing of double compression type Brass glands & making joint with necessary AL. /CU. crimping socket of long neck type connecting the same to various equipment like sectionpillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS).3.5C X 400Sq.mm. ‐ Al

32 End 631.76                     20,216.32                 

3 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck typeconnecting the same to various equipment like section pillar, switch, starter, motor etc. for thefollowing sizes:(COMET/ CONNECT WEL/ DOWELS).3.5C X 400Sq.mm. ‐ Al

32 End 2,111.91                  67,581.12                 

DG Set & accessoriesSupply, installation, testing and commissioning of sound proof 750 KVA Diesel Generator setcomprising of water cooled radiator type, Diesel Engine with rated capacity of suitable BHP at1500 rpm, direct injection type, 4 stroke, with suitable no. cylinders coupled to 750 KVAbrushless type 415 Volts, 50HZ, self exciting Alternator with suitable size of flexible coupling andfollowing main components, complete with all accessores conforming to technical specificationsand as required. Make :Kirloskar.Cooling System : water cooled radiator type.Exhaust System : Pipe, Chimney, silencer and supports (as approved by Pollution Control Board /Local Authorities ).Fuel system : Day tank (990 litres‐2 nos.) and their interconnecting piping system.Lube oil system.Air system.Electronic Governer.Starting System.Coupling arrangement.safety controls.Instrument panel for engine.Control panel with metering, interlocks and annunciations complete as per specifications.Batteries, Boost and trickle battery charger.Provision of Busduct connection from alternator terminals to AMF Panel, control cable, neutraland equipment earthing complete as required.Spring loaded cushy pads, foundation bolts, etcMaking cement concrete foundation with 1:2:4(1 cement ,2 course sand,4 graded 

stone aggregate 40mm nominal size)suitable for DG set as perr recommendation ofmanufacturer .Sound proof canopy with openable doors,fresh air fans,control panel,as per requirement ofPollution Control BoardAll other minor civil,mechanical works including material supply and electrical works completeas required..This includes protection relays, meters etc complete. control cabling from AMF DG set mentioned as above panel.panel to DG set & LT panels is deemed to be included in this item.AMF ‐ PANEL (FOR 750 KVA ABOVE DG SET)Supply, installation, testing and commissioning of M.V. cubicle type totally enclosed freestanding type, dust, damp, and vermin proof capacitor panel complete with busbars, M.V.damper notice plate, ammeter, ammeter selector switch, voltmeter, voltmeter selector switch,PF meter indicating lamps, CTs,interconnections, interlocking between two feeders and bus coupler, with suitable capacityaluminium leads / solid alumionium strips / rods, connection of incoming & outgoing cables withthimbles, stove enamelled painted and having following incoming and outgoing switchgears andas per technical bapecifications & as required.

ENGINEERING PROJECTS (INDIA) LIMITED( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No. 04‐3333, Action Area ‐ 1D, New Town Kolkata

Tender No: DLI/CON/729/560                                                             Dated 08.12.2016

BILL OF QUANTITIES

1 Set 84,05,659.35          84,05,659.35           

4

Page 8: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

1 No. ACB  Panels each having following.1 No. 1250A, 415/500V, rated service short circuit rupturing capacity (Ics) 50 KA, mororised, fullydrawout type(EDO), four pole, Air Circuit Breaker with microprocessor based overload, shortcircuit & earth fault trip including under voltage release and lockable trip push button ACBshould have Icw=50KA for 1 sec.1 set of indicating lamps with 2A protection MCBs to indicate OPEN, CLOSE, TRIP for ACB.Push button to CLOSE the ACB.R, Y & B Phase indicating lamps (LED type) with 2A control SP MCBs.Incoming ACB shall have multi function meter ‐ parameters ‐ digital multifunction meter shallindicating A / V / KWH with RS‐485 port with suitable CTs, CT shorting links.

AMF Cubicle1 No. frequency meter (45‐55 HZ.)1 set under voltage relay.1set over voltage relay.1 set under frequency relay.1 set of Master trip / supervisory relay.1 set of battery charger (with tricle and boost charger.).1 set of DC voltmeter and ammeter.1 set of Reverse power and Reactive power relay.1 set R, Y, B, Breaker ON/OFF & other fault indication lamps. 1 set 8 window Alarm annunciator with separate hooter, accept, reset and rest push button. 1 No. Hooter.1 No. Engine Cranking Relay.1 set of Main supply voltage monitor, alternate voltmeter monitor and Engine starting relays.1 set of Auxiliary relays, timer, push button and control fuses.ENCLOSUREFabrication, PVC sleeving, control/ power wiring and necessary hardware for complete AMF PanelTotal of DG Set & AMF Panel.Electrical Interlocking between HT,LT & Generator set will be done accordingly as per scheme.Necessary scheme will be intimated at the time of drawing approval.

96,19,588.29           

Page 9: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1.0 Electrical Section III ( AIR‐CONDITIONING SYSTEM)Supply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cablesupports provided, include unloading, shifting upto site. The scope includes clamping of cables byready made G.I. spacers, saddles or clamps fabricated out of GI strip 3 mm thick. (KEI/POLYCAB/Havells)

0.00

1.1 3.5C X 95Sq.mm. ‐ Al  basement ventilation PNL 120 Metre 532.27 63,872.401.2 3.5C X 400Sq.mm. ‐ Al for  VRF PNL  550 Metre 1,732.51 9,52,880.502.0 LT Cable Terminations

Supplying & fixing of double compression type Brass glands & making joint with necessary AL. /CU. crimping socket of long neck type connecting the same to various equipment like sectionpillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

2.1 3.5C X 95Sq.mm. ‐ Al 6 End 324.21 1,945.262.2 3.5C X 400Sq.mm. ‐ Al 32 End 631.76 20,216.323.0 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type

connecting the same to various equipment like section pillar, switch, starter, motor etc. for thefollowing sizes:(COMET/ CONNECT WEL/ DOWELS)

3.1 3.5C X 95Sq.mm. ‐ Al 6 End 349.97 2,099.823.2 3.5C X 400Sq.mm. ‐ Al 32 End 2,111.91 67,581.12

VRF Main PanelSupply, installation, testing and commissioning of following outdoor type with sloping canopy onthe top, double door, M.V cubicle type totally enclosed, 14 SWG CRCA Sheet, IP‐54 protected,free standing type, dust, damp and vermin proof, Distribution Board/Panel complete withbusbars, M.V. danger notice plate, interconnections with suitable capacity aluminium leads/solidaluminium strips/rods, connection of incomming and outgoing cables with thimbles, powder coatpainted and having following incoming and outgoing switchgears complete as required. Incommer:630 Amps, 415V, 50KA(Isc), FP MCCB with thermal magnetic release having variable currentsetting of 0.8 to 1.0 In.Extended rotary operating mechanism with door interlock with defeat feature and padlockfacility. MCCB should have spreader links & phase barriers.1 set of phase indicating lamps with 2A SP control MCB.Incoming MCCB shall have multi function meter ‐ parameters ‐ digital multifunction meter shallindicating A / V with RS‐485 port with suitable CTs, CT shorting links.Busbar:

1000 AMP,50KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length ‐ Current ratio shall be1 sq mm = 0.8 AOutgoings:4 sets of the following:150 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable currentsetting of 0.8 to 1.0 In.1 set of phase indicating lamps with 2A SP control MCB.1 No. 0‐200 Amps ammeter with selector switch and CT's 200/5A.3 sets of the following:100 Amps, 415V, 10KA(Isc), FP MCCB with phase indicating lamps.1 set of phase indicating lamps with 2A SP control MCB.1 No. 0‐100 Amps ammeter with selector switch and CT's 100/5A.2 sets of the following:63 Amps, 415V, 10KA(Isc), FP MCB with phase indicating lamps.1 set of phase indicating lamps with 2A SP control MCB.1 No. 0‐100 Amps ammeter with selector switch and CT's 100/5A.All MCBs are C‐series type.

ENGINEERING PROJECTS (INDIA) LIMITED( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No. 04‐3333, 

Tender No: DLI/CON/729/560                                                             Dated 08.12.2016

BILL OF QUANTITIES

1 Set 2,66,640.00 2,66,640.00

4.0

Page 10: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Basement Ventilation Panel:Supply, installation, testing and commissioning of following M.V cubicle type totally enclosed, 14SWG CRCA Sheet, IP‐54 protected, free standing type, dust, damp and vermin proof, DistributionBoard/Panel complete with busbars, M.V. danger notice plate, interconnections with suitablecapacity aluminium leads/solid aluminium strips/rods, connection of incomming and outgoingcables with thimbles, powder coat painted and having following incoming and outgoingswitchgears complete as required. Incommer:150 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable currentsetting of 0.8 to 1.0 In.Extended rotary operating mechanism with door interlock with defeat feature and padlockfacility. MCCB should have spreader links & phase barriers.1 set of phase indicating lamps with HRC fuses.Incoming MCCB shall have multi function meter ‐ parameters ‐ digital multifunction meter shallindicating A / V with RS‐485 port with suitable CTs, CT shorting links.Busbar:

200 AMP,25KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length ‐ Current ratio shall be 1 sq mm = 0.8 A.Outgoings:3 set of the following (Axial flow exhaust fan).32 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current settingof 0.8 to 1.0 In.Extended rotary operating mechanism with door interlock with defeat feature and padlockfacility. MCCB should have spreader links & phase barriers.1 No. 3 Phase, DOL Starter for 7.5KW, pump motor with TP contactors, thermal overload relay,Timer, Local Push Push Buttons and Auto‐manual selector switch.Single Phase preventer.1 set of phase indicating lamp bwith 2A SP control MCBs.Indicating  Lamps for ON / OFF / TRIP indication with 2A SP control MCBs.1 No. 0‐100 Amps ammeter with selector switch and CT's 100/5A.

4.4 7 set of the following (Jet Fan)32 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current settingof 0.8 to 1.0 In.Extended rotary operating mechanism with door interlock with defeat feature and padlockfacility. MCCB should have spreader links & phase barriers.1 No. 3 Phase, DOL Starter for 3.7KW, pump motor with TP contactors, thermal overload relay,Timer, Local Push Push Buttons and Auto‐manual selector switch.Single Phase preventer.1 set of phase indicating lamp with 2A SP control MCBs.Indicating  Lamps for ON / OFF / TRIP indication with 2A SP control MCBs.1 No. 0‐100 Amps ammeter with selector switch and CT's 100/5A.All Outgoing MCCBs shall have multi function meter ‐ parameters ‐ digital multifunction metershall indicating A / V with RS‐485 port with suitable CTs, CT shorting links.

1 Set 5,71,188.33 5,71,188.33

5.0 Supply of Aircooled Digital Scroll VRF SYSTEM Unit with R 410a Refrigerant, Aircooled Condenseralong with inbuilt microprocessor panel.OUTDOOR UNIT (Mitsubishi,Carrier midea,Blue Ster)

5.1  63 HP ‐ GROUND FLOOR 1 Each 14,05,420.05 14,05,420.055.2  12 HP ‐ GROUND FLOOR 1 Each 3,59,455.97 3,59,455.975.3  63 HP ‐ FIRST FLOOR 1 Each 14,05,420.05 14,05,420.055.4  57 HP ‐ SECOND FLOOR 1 Each 13,32,695.00 13,32,695.005.5  54 HP ‐ THIRD FLOOR 1 Each 1,30,949.53 1,30,949.535.6  50 HP ‐ FOURTH FLOOR 1 Each 12,82,650.51 12,82,650.516.0 VRF INDOOR UNITS6.1  COMPACT CASSETTE UNIT 0.6 TR 8 Each 33,979.43 2,71,835.446.2  COMPACT CASSETTE UNIT 0.6 TR 16 Each 34,277.38 5,48,438.086.3  LARGE CASSETTE UNIT 2.8 TR 4 Each 48,876.93 1,95,507.726.4  LARGE CASSETTE UNIT 2.3 TR 3 Each 42,089.73 1,26,269.196.5  LARGE CASSETTE UNIT 1.5 TR 1 Each 41,098.92 41,098.926.6  WALL MOUNTED UNIT 1.0 TR 6 Each 20,999.92 1,25,999.526.7  WALL MOUNTED UNIT 0.8 TR 4 Each 20,909.02 83,636.086.8  DUCTED UNIT 8.0 TR 10 Each 63,753.22 6,37,532.206.9  DUCTED UNIT 6.0 TR 6 Each 60,122.27 3,60,733.626.1  DUCTED UNIT 5.0 TR 6 Each 57,703.32 3,46,219.926.1  DUCTED UNIT 4.0 TR 11 Each 43,272.44 4,75,996.84

Page 11: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

6.1  DUCTED UNIT 3.0 TR 6 Each 34,540.99 2,07,245.946.1  5.5 TR TREATED FRESH AIR UNIT 2 Each 47,614.43 95,228.866.1  3.5 TR TREATED FRESH AIR UNIT 2 Each 41,843.29 83,686.586.2  SUPPLY OF  IMPORTED REFNET JOINTS 79 Each 7,434.61 5,87,334.196.2  CORDLESS CONTROLLER 42 Each 915.06 38,432.526.2  CORDED CONTROLLER 39 Each 3,139.08 1,22,424.126.2  2.0 TR (3 STAR) NON VRF STAND ALONE SPLIT UNIT FOR SERVER ROOM 3 Each 45,450.00 1,36,350.007.0 Price for  Supply Installation & Commissioning of Ancillary Items for VRF7.1  Installation & Commissioning of  Digital Scroll VRF Units , with outdoor mounting, pressure 

testing, nitrogen flushing etc16 Each 23,583.50 3,77,336.00

7.2  REF ( R ‐ 410 ) VRF 130 Kg 1,959.40 2,54,722.007.3  V I Pads‐ VRF 16 Set 686.80 10,988.807.4  Installation of  VRF Indoor Units 85 Each 1,767.50 1,50,237.507.5  Installation of stand alone split unit including  copper pipe, control cable between indoor & 

outdoor units, refrigerant gas etc.3 Each 4,913.65 14,740.95

7.6  Installation of Axial Fan units 10 Each 3,928.90 39,289.007.7  Installation of jet fan units 12 Each 2,060.40 24,724.807.8  installation of co sensor 4 Each 1,572.57 6,290.287.9  Supply and Installation of imported  REFNET JOINTS 1 LOT 38,814.30 38,814.307.1  Refrigerant Piping with insulation 

Suction/ Liquid line with Nitrile rubber insulation(Nippon/Nissan/Rajco//Totaline)

7.1  1 3/8" OD 140 Rmt 1,920.01 2,68,801.407.1  15/8" OD 145 Rmt 2,232.10 3,23,654.507.1  11/8" OD 200 Rmt 1,395.82 2,79,164.007.1  7/8" OD 285 Rmt 1,094.84 3,12,029.407.2  5/8" OD 180 Rmt 805.98 1,45,076.407.2  3/4" OD 320 Rmt 968.59 3,09,948.807.2  3/8" OD 160 Rmt 507.02 81,123.207.2  1/2" OD 485 Rmt 604.99 2,93,420.157.2  1/4" OD 240 Rmt 369.66 88,718.408.0 HDPE Drain piping  with insulation8.1  40 mm. 100 Rmt 298.96 29,896.008.2  32 mm 200 Rmt 259.57 51,914.008.3  25 mm 400 Rmt 219.17 87,668.009.0 Electricals/Cables

Control Cable 2C x 1.5 sqmmfor VRF unit1400 Rmt 158.57 2,21,998.00

10.0 GSS Ducting 24G with hangers, supports etc.10.1    24 G 1050 Sqmtr 785.78 8,25,069.0010.2   22 G 300 Sqmtr 914.05 2,74,215.0010.3 DUCT THERMAL INSULATION WITH13 MM AL. FOIL FACED GLASS WOOL (TAIL END) 750 Sqmtr 874.66 6,55,995.0010.4 Duct Acoustic Insulation with 12 mm thick FGP (48Kg/cum) RP Tissue + 36g Aluminium Perforated 

Sheet200 Sqmtr 661.55 1,32,310.00

10.5   Air distribution Discrete Grilles / Diffusers10.6  GI Duct Dampers 10 Smt 4,484.40 44,844.0010.7  Supply air grilles/diffusers air grille with VCD and air box 20 Smt 9,039.50 1,80,790.0010.8  Return air grilles/diffusers air grille with VCD 28 Smt 8,682.97 2,43,123.1610.9  Fresh air packaged with BIRD SCREEN/COWL/DAMPER 18 Each 4,129.89 74,338.0210.10  Flexible fire retardent canvass connection 43 Each 2,161.40 92,940.2011.0 BASEMENT VENTILLATION SYSTEM

Axial fan 800mm Dia Tube axial Type Fan is suitable for 3~, 400 V, 50 Hz power supply and for 300°C & 2 hrs operation.

11.1 30000 CMH 10 Each 1,26,250.00 12,62,500.0011.2 315mm dia Jet Fan is suitable for 3~, 400 V, 50 Hz power supply and for 300°C & Hrs operation. 

CFD analysis price is Included in our offer.12 Each 60,600.00 7,27,200.00

11.3 CO SENSOR 8 Each 25,250.00 2,02,000.0012.0 Supply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cable

supports provided, include unloading, shifting upto site. The scope includes clamping of cables byready made G.I. spacers, saddles or clamps fabricated out of GI strip 3 mm thick. (Havells/POLYCAB /KEI)

12.1  3.5C X 16Sq.mm. ‐ PVC/Cu ARM, stranded,  from VRF Panel to unit. 120 Metre 1,300.88 1,56,105.6012.2    3.5C X 25Sq.mm. ‐ PVC/Cu ARM, stranded,  from VRF Panel to unit. 250 Metre 1,761.44 4,40,360.0012.3   3.5C X 120Sq.mm. ‐ PVC, Al, stranded as incommer from Rising Main 320 Metre 1,037.27 3,31,926.4012.4    3.5C X 150Sq.mm. ‐ PVC, Al, stranded as incommer from Rising Main 80 Metre 1,203.92 96,313.60

Page 12: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

13.0 Supplying & fixing of double compression type Brass glands & making joint with necessary AL. /CU. crimping socket of long neck type connecting the same to various equipment like sectionpillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

13.1   4C X 16Sq.mm. ‐ Cu  8 End 104.54 836.3213.2     3.5C X 25Sq.mm. ‐ Cu  24 End 160.59 3,854.1613.3    3.5C X 120Sq.mm. ‐ Al  8 End 324.21 2,593.6813.4    3.5C X 150Sq.mm. ‐ Al  2 End 324.21 648.4214.0 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type

connecting the same to various equipment like section pillar, switch, starter, motor etc. for thefollowing sizes:(COMET/ CONNECT WEL/ DOWELS)

14.1  4C X 16Sq.mm. ‐ Cu  8 End 99.99 799.9214.2   3.5C X 25Sq.mm. ‐ Cu  24 End 125.75 3,018.0014.3  3.5C X 120Sq.mm. ‐ Al  8 End 452.99 3,623.9214.4   3.5C X 150Sq.mm. ‐ Al  2 End 477.23 954.4615.0 VRF Panel (Type ‐ 1)

Supply, installation, testing and commissioning of following outdoor type Distribution Board withsloping canopy on the top, IP‐65 protected, double door, M.V. cuble type totally enclosed, 14SWG CRCA Sheet, free standing type, dust, damp and vermin proof, MV Panel complete withbusbars, M.V. danger notice plate, interconnections witrh suitable capacity aluminium leads/solidaluminium strips/rods, connection of incomming and outgoing cables with thimbles, stoveenamelled painted and having following incomming and outgoing switchgears complete asrequired for VRF Panel.Incommer:125 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable currentsetting of 0.8 to 1.0 In.Extended rotary operating mechanism with door interlock with defeat feature and padlockfacility. MCCB should have spreader links & phase barriers.1 set of phase indicating lamps with HRC fuses.Incoming MCCB shall have multi function meter ‐ parameters ‐ digital multifunction meter shallindicating A / V with RS‐485 port with suitable CTs, CT shorting links.Busbar:200 AMP,25KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length ‐ Current ratio shall be1 sq mm = 0.8 AOutgoings:4 Nos. 50 Amps 415V, FP MCB, 10KA with phase indicating lamps.1 No. 0‐100 Amps ammeter with selector switch and CT's 100/5A with each feeder.All MCBs are C‐series type.VRF Panel (Type ‐ 1) as above.

6 set 2,02,000.00 12,12,000.00

VRF Panel (Type ‐ 2)Supply, installation, testing and commissioning of following outdoor type Distribution Board withsloping canopy on the top, IP‐65 protected, double door, M.V. cuble type totally enclosed, 14SWG CRCA Sheet, free standing type, dust, damp and vermin proof, MV Panel complete withbusbars, M.V. danger notice plate, interconnections witrh suitable capacity aluminium leads/solidaluminium strips/rods, connection of incomming and outgoing cables with thimbles, stoveenamelled painted and having following incomming and outgoing switchgears complete asrequired for VRF Panel.Incommer:160 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable currentsetting of 0.8 to 1.0 In.Extended rotary operating mechanism with door interlock with defeat feature and padlockfacility. MCCB should have spreader links & phase barriers.1 set of phase indicating lamps with HRC fusesIncoming MCCB shall have multi function meter ‐ parameters ‐ digital multifunction meter shallindicating A / V with RS‐485 port with suitable CTs, CT shorting links.Busbar:250 AMP,25KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length ‐ Current ratio shall be1 sq mm = 0.8 A.Outgoings:5 Nos. 50 Amps 415V, FP MCB, 10KA with phase indicating lamps.1 No. 0‐100 Amps ammeter with selector switch and CT's 100/5A with each feeder.All MCBs are C‐series type.VRF Panel (Type ‐ 1) as above

17.0 OTHER FITTING17.1  32A FP SFU ISOLATOR (for 12HP outdoor unit at Gnd Fl. ) Make : Laygrad 1 No. 2,020.00 2,020.0017.2   Supply and fixing 250 Volt , 6‐10A per way, (2+6) way SPN MCBDB with SS enclosure double door 

with IP 42/43 protrction with 1 no 40 A DP isolator as a incomer and 5 nos SPMCBs (C curve 10KA) as outgoing concelled in wall after cutting the wall and mending good damages to originalfinish including interconnection with suitable size of copper wire and neutral link & protrction forearthing attachment . Make : Legrand.

1 No. 3,354.21 3,354.21

18.0 Electrical Rising main & Tap off boxes for VRF

1 set 2,27,250.00 2,27,250.00

16.0

Page 13: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

18.1 Supply, erection, testing and commissioning of 1000 Amps, FP internally earthed Al. Rising MainSystem, IP54, 50KA breaking capacity along with all necessary fabrication of supports and otheraccessories works complete as per specification, through the shaft/ceiling/wall of different flooras required including end feed units with MCCB & tap off boxes of rating as follows at every floor .All joints / tees bends / phase change over boxes etc are deemed to be included in the supply.Arrangement for future extention arrangement upto eight floor has to included and complete asrequired of make MDS‐Legrand/C&S or approved equivalent.

35 Mtr. 25,425.74 8,89,900.90

18.2   End Feed Unit, 1000A, ACB, 50KA 1 Each 1,45,736.94 1,45,736.9418.3  Tap Off boxes, 160A, 25KA for Gnd Floor 1 Each 43,680.48 43,680.4818.4    Tap Off boxes, 125A, 25KA for 1st Fl, 2nd Fl, 3rd Fl & 4th Fl. 4 Each 41,072.66 1,64,290.6419.0 BASEMENT VENTILATION SYSTEM

LT CABLESSupply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cable supports provided, include unloading, shifting upto site. The scope includes clamping of cables by ready made G.I. spacers, saddles or clamps fabricated out of GI strip 3 mm thick. (Havells /POLYCAB /KEI)

19.1   3C X 2.5 Sq.mm. ‐ PVC/Cu ARM, stranded,  for Jet Fan. 300 Metre 341.38 1,02,414.0019.2  3C X 10 Sq.mm. ‐ PVC, Al, stranded, for Axial Fan 250 Metre 310.07 77,517.5019.3  3.5C X 150 Sq.mm. ‐ PVC, Al, stranded, as incommer. 70 Metre 1,203.92 84,274.4020.0 Cutting channel of 40mm X 40mm size on masonry wall incl. S&F heavy gauge 19 mm dia 3 mm 

thick polythene pipe by means of iron hooks and supplying and drawing 18 SWG GI Wire fish wire incl. mending good damages to building works

1400 RM 74.49 1,04,286.00

21.0 Supplying and Drawing 1.1 KV, 2 x 22/0.3 (1.5 sqmm), single core, stranded, 'FR' PVC insulated&unsheathedsingle core stranded copper wire (approved make) of the following sizes in the prelaid19mm dia 3mm thick polythene pipe and by the prelaid 18 SWG GI Wire fish wire and makingnecy. connection as required for VRF unit/ CO Sensor.

1400 RM 40.40 56,560.00

22.0 Supplying & fixing of double compression type Brass glands & making joint with necessary AL. /CU. crimping socket of long neck type connecting the same to various equipment like sectionpillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

22.1 3C X 2.5Sq.mm. ‐ PVC/Cu ARM, stranded,  for Jet Fan. 24 End 59.09 1,418.1622.2 3C X 10Sq.mm. ‐ PVC, Al, stranded, for Axial Fan 20 End 104.54 2,090.8022.3 3.5C X 150Sq.mm. ‐ PVC, Al, stranded, as incommer. 2 End 324.21 648.4223.0 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type

connecting the same to various equipment like section pillar, switch, starter, motor etc. for thefollowing sizes:(COMET/ CONNECT WEL/ DOWELS)

23.1 3C X 2.5Sq.mm. ‐ PVC/Cu ARM, stranded,  for Jet Fan. 24 set 52.52 1,260.4823.2 3C X 10Sq.mm. ‐ PVC, Al, stranded, for Axial Fan 20 set 72.72 1,454.4023.3 3.5C X 150Sq.mm. ‐ PVC, Al, stranded, as incommer. 2 set 531.26 1,062.52

2,46,35,119.19

Page 14: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1 Electrical Section IV ( COMPOUND LIGHTING )Supply, Laying of cables on cable trays/Hume pipes/structural supports/underground and cablesupports provided, include unloading, shifting upto site. The scope includes clamping of cables byready made G.I. spacers, saddles or clamps fabricated out of GI strip 3 mm thick. (Havells/POLYCAB /KEI)

1.1  3C X 2.5Sq.mm. ‐ PVC/Cu ARM, stranded,  for Campus Lighting pnl outdoor lighting 500 Metre 127.26                  63,630.00                1.2  4C X 10Sq.mm. ‐ Al stranded for Campus Lighting pnl outgoing 500 Metre 105.04                  52,520.00                1.3  4C X 16Sq.mm. ‐ Al stranded for Substation & lighting pnl 350 Metre 139.38                  48,783.00                2 Supplying & fixing of double compression type Brass glands & making joint with necessary AL. /

CU. crimping socket of long neck type connecting the same to various equipment like sectionpillar, switch, starter, motor etc. for the following sizes:(COMET/ CONNECT WEL/ DOWELS)

2.1   4C X 10Sq.mm. ‐ Al,  20 End 69.69                    1,393.80                  2.2  4C X 16Sq.mm. ‐ Al  4 End 69.69                    278.76                       3 Supplying & finishing cable ends with necessary AL. / CU. crimping socket of long neck type

connecting the same to various equipment like section pillar, switch, starter, motor etc. for thefollowing sizes:(COMET/ CONNECT WEL/ DOWELS)

3.1  4C X 10Sq.mm. ‐ Al,  20 End 48.48                    969.60                       3.2  4C X 16Sq.mm. ‐ Al  4 End 66.66                    266.64                       4 Campus / Outdoor Lighting Panel

Supply, installation, testing and commissioning of following outdoor type Lighting DistributionBoard with Synchronous Timer / Timer Circuit for automatic controlling, sloping canopy on thetop, IP‐65 protected, double door, M.V. cuble type totally enclosed, 14 SWG CRCA Sheet, freestanding type, dust, damp and vermin proof, MV Panel complete with busbars, M.V. dangernotice plate, interconnections witrh suitable capacity aluminium leads/solid aluminiumstrips/rods, connection of incomming and outgoing cables with thimbles, stove enamelledpainted and having following incomming and outgoing switchgears complete as required forcampus / outdoor lighting.Incommer:40 Amps, 415V, 25KA(Isc), FP MCCB with thermal magnetic release having variable current settingof 0.8 to 1.0 In.1 set of phase indicating lamp with HRC fuses.TimerAll incoming with 40A DIGITAL, 365 DAYS, 24 HRS. PROGRAMMABLE TIMER with suitablecontactor.Busbar:100 AMP,25KA, 650 Volts, 3 phase 50 Hz FP Al. bus bars of suitable length ‐ Current ratio shall be1 sq mm = 0.8 AOutgoings:4 Nos. 20 Amps 415V, FP MCB phase indicating lamps.9 Nos. 10 Amps 415V, DP MCB phase indicating lamps.All MCBs are C‐series type.

3 set 51,533.54            1,54,600.62             

5 Campus / Outdoor Lighting Panel as aboveSupply, Installation, testing & commissioning of standard light fittings and lighting accessoriesincluding lamp and other accessories as required.The scope shall include, providing of allhardware such as downrod, nuts,anchor fastners, bolts, screws, cleats, clamps, Lugs, PVCinsulated wires / cables (CROMPTON GREAVES / BAJAJ / PHILIPS)

5.1 Excavation in all sorts of soils including hard rock/ murrum for required depth and back filling.Contractor's scope of work under this item shall include disposal of surplus earth and shoring,shuttering and dewatering if required. Excavation shall be done as per directions of Engineer‐in‐charge.

600 Rmt 190.89                  1,14,534.00             

5.2 Supplying and spreading fine sand for a thickness of 100 mm. and providing and laying bricks forcable protection. on all the three sides. 600 Rmt 124.23                  74,538.00                

5.3 Supply & fixing of 25mm. external dia rigid PVC conduit laid in floor/wall etc for laying ofcable/GI wire by cutting & making good for damages , inclusive of all tees, bends, elbows,reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipehooks etc. complete as per the direction of EIC. 

600 M                    46.46  27,876.00                

ENGINEERING PROJECTS (INDIA) LIMITED( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development Authority at Plot No. DG/13, Premises No. 04‐3333, 

Tender No: DLI/CON/729/560                                                             Dated 08.12.2016

BILL OF QUANTITIES

Page 15: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

6 Supply, installation, testing and commissioning of 5.6 mtr above ground, seamless conicaltapering GI poles with single seamless conical tapering suitable length of GI bracket of approvedshape & suitable for mounting with 28W LED fixture & Solar Panel of approved make. The ratesshall be inclusive of necessary foundation (min. 450 x 450 x 750 mm, M:15) with anchor boltscoping with baseplate, etc. complete. The pole shall have concealed type (flush door with properstrengthening to the cutout of the door opening) junction box with loop in loop out connector(bakelite connector of 15A) and MCB for fixture.a) 40 mm diameter GI pipe with long bend for each cable entry .b) Wiring up to the light fixture from the junction box using 3nos x 2.5 sq.mm. flexible copperwires of specified make.c) Excavation & back filling for erection of poles. Debris to be removed from the site to suitablelocation instruction of the engineer incharge.d) Earthing with GI earth spike, size 1822 length X 20 mm. dia directly driven in soil below groundlevel & interconnection of spike with poles / looping box with 6 SWG GI wire (2 runs). GIprotection for earthing lead of suitable length (Av. 3 mtr. approx.) for pole earthing & looping boxearthing.

40 set 1,06,050.00         42,42,000.00           

7 Supply, installation, testing and commissioning of BOLLARD, GARDINA 2, 1x26W CFL(TU),HAVELLS CAT NO. LHLC02126099 or approved equivalent, complete with base & logbolts,terminal box etc. for garden & wiring through 3CX2.5 sqmm. copper armoured cable.a) 25 mm diameter GI pipe with long bend for each cable entry .b) Providing necessary foundation with 300mmX300mmX300mm. Deep 1:3:6 ratio cementconcrete complete as required.c) Excavation & back filling for erection . Debris to be removed from the site to suitable locationinstruction of the engineer incharge.

30 set 8,561.42               2,56,842.60             

8 Supply, installation, testing and commissioning of JETA 6, 1X400W MH Set, HAVELLS CAT NO.LHFY40140C99 with lamp or approved make, outdoor fittings as integral architectural floodlightings, terminal box, etc. of building complete with all accessoies and necessary electricalwiring through 3CX2.5 sqmm. copper armoured cable.a) 25 mm diameter GI pipe for each cable entry .b) Providing necessary foundation with 300mmX300mmX300mm. Deep 1:3:6 ratio cementconcrete complete as required.c) Excavation & back filling for erection. Debris to be removed from the site to suitable locationinstruction of the engineer incharge.

15 set 13,171.41            1,97,571.15             

9 Supply, installation, testing and commissioning of Impact popular arrylic IP 65, 1X 70W SON,Havells Cat No. LHRY28170D99, street light fixture, outdoor fitting, with 70 Watts Sodium Vapourlamp complete with control gear, acrylic cover, terminal box, etc. and its wiring with 2CX2.5sq.mm. PVC insulated copper wire and 1.5 sq.mm. PVC insulated copper earth wire from controlbox complete as required to be connected with Substation DB.(wiring for the same shall be paidin rmt)

4 Each 5,400.28               21,601.12                

10 Garden spike and mini flood luminaires, 1 X 50W E‐27 for garden use (Make : Bajaj) 20 Each 2,594.77               51,895.40                11 Supply, installation, testing and commissioning of Water body light philips cat no. EW Graze

power Wee narrow 2700K or equivalent model from approved makes as required.The above installations shall be completed as per specifications and as required.

20 Each               7,836.99  1,56,739.80             

12 SITC of IP66 Water Tight Junction Box 139mm x 115mm x 70mm With necessary clamp formounting of the J.B. (All the cable / wire connections to the DB shall be with the Water tight IP 66Polyamide Glands, open Holes should be sealed with the IP65 Grommets only ) J. B. Should beprovided with cable connectors to connect 1 nos. of 4.0 sq. mm. x 2 core cables + Earth wire & 6nos. of 2.5 sq. mm x 2 core wires + Earthing wires.(Make of Hensel make cat.no. KD5065 +Connectors + IP65 Glands + IP65 Grommets or equivalent) (wiring for the same shall be paid inrmt) ‐ fountain, ramp light, etc. from Campus lighting Panel (wiring for the same shall be paid inrmt).

4 Each 1,055.45               4,221.80                  

54,70,262.29           

Page 16: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

1 Electrical Section ‐V ( Fire)INSIDE PUMP HOUSEProviding & fixing, testing and commissioningof electrically driven high pressure centrifugalfire hydrant and sprinkler pump, suitable forautomatic operation consisting of thefollowing:Horizontal, end suction centrifugal pump,suitable for operation on 415 volts ± 6%, 3phase, 50 HZ A.C supply. The installationshall be complete with flexible coupling andcoupling guard as required. Fire pump shallhave C.I. casing, CS diffusers, bronze impeller(hard finished and dynamically balanced) andS.S. (304) Shaft with mechanical seal, capablefor delivering head to ensure a minimumpressure of 3.5 Kg/Sqcm at the farthest ortopmost hydrant / sprinkler. The installationshall be complete with necessary pressuregauge with gun metal shut off cock on deliveryside. Squirrel cage induction motor, TEFC typesuitable for operation on 415 volts, 3 phase 50HZ A.C supply, for the above pump withsynchronous speed of 2900 RPM, conformingto IP 55 protection & class F insulation. The

2 Sets 2,35,000.00 4,70,000.00

2 Providing & fixing, testing and commissioningof Diesel Engine driven fire pump suitablefor automatic operation comprising of thefollowing and conforming to BS 649/IS 10002all amended upto date.Horizontal, split casing centrifugal pump,suitable for operation on 415 volts ± 6%, 3phase, 50 HZ A.C supply. The installationshall be complete with flexible coupling andcoupling guard as required. Fire pump shallhave C.I. casing, CS diffusers, bronze impeller(hard finished and dynamicallybalanced) and SS (304) shaft withmechanical seal, capable for delivering head toensure a minimum pressure of 3.5 Kg/Sqcm atthe farthest or topmost hydrant / sprinkler.The installation shall be complete withnecessary pressure gauge with gun metal shutoff cock on delivery side.Heat exchanger cooled (secondary cooling)diesel engine of speed 1500 RPM suitable forthe above pump with automatic startingmechanism and other accessories including fueltank (fabricated from 3mm MS sheet, paintedwith two coats of synthetic enamel paint over acoat of primer) of capacity adequate to sustainpump operation for 8 hours continuous

k h k h ll b f d h

1 Set 7,27,200.00 7,27,200.00

ENGINEERING PROJECTS (INDIA) LIMITED( A GOVT OF INDIA ENTERPRISE )

Name of the Work : Construction of 1st Phase (B+G+IV) of Administrative Building of New Town Kolkata Development 

Tender No: DLI/CON/729/560                                                             Dated 08.12.2016

BILL OF QUANTITIES

Page 17: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

3 bolts.Capacity  :  2850LPM.Head        :  80 MSupply, installation, testing and commissioningof Jockey pump (pressurisation pump) of thefollowing duty:Horizontal end suction Centrifugal pump,suitable for operation on 415 volts ± 6%, 3phase, 50 HZ A.C supply. The installation shallbe complete with Flexible coupling andcoupling guard, complete as required. Jockeypump shall be of stainless steel construction.Horizontal, end suction centrifugal pump,suitable for operation on 415 volts ± 6%, 3phase, 50 HZ A.C supply. The installationshall be complete with flexible coupling andcoupling guard as required. Fire pump shallhave C.I. casing, CS diffusers, bronze impeller(hard finished and dynamically balanced) andS.S. (304) Shaft with mechanical seal, capablefor delivering head to ensure a minimumpressure of 3.5 Kg/Sqcm at the farthest ortopmost hydrant / sprinkler. The installationshall be complete with necessary pressuregauge with gun metal shut off cock on deliveryside. (The pump should be tested for benchmark at factory and shall be gotten approvedb h l fi h i )

1 Set 95,950.00 95,950.00

4 Providing & fixing MS Class ‘C’ diesel engineexhaust pipe (including all fittings, clamps, steelsupport) of suitable dia for the engine. The pipeshall be provided with 12 mm thick superceraceramic fibre rope.150 mm dia

36 RM 1,818.00 65,448.00

5 Providing & fixing dial type (150 mm) pressuregauge suitable for working pressure of 250 PSI.  5 Each 1,111.00 5,555.00

6 Providing & fixing testing and commissioning of adjustable pressure switches for jockey pump/ electric pump along with control wiring up to main panel as required 

8 Each 2,222.00 17,776.00

Control Panel for Fire Pumps.Fabricating & supply, installing, testing and commissioning of compartmentalised common control Panel for Electrical Motor driven pumps.and diesel engine driven pump.INCOMING.1 nos.630 A TPN MCCB (25KA)PVC Sleeves.1 set RYB indicating lamps with individual HRC Control fuses.1 No. 96 sq.mm 0‐600 Amps. Ammeter with selector switch and suitable rated.current transformers.1 No.  0‐500V 96 sqmm Voltmeter with selector Switch.1 Nos 600 A, 4 POLE ATS (ASCO 300 Series) OVER LAPPING NEUTRAL.OUTGOINGFeeder for Main Fire Pump ‐ 2 Nos.1 Nos 250 A TP MCCB.DOL starter with TP Contractors and indicating lamps ON/OFF/TRIP push.Buttons

7

Page 18: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

DIESEL ENGINE PUMP (STAND BY OPERATION) ‐1 No.20 Amps DPMCB ‐ 2 NosBattery charger with transformers with rectifierresistence DC ammeter, DCvoltmeter, Trickle/Booster/Off selector switch ‐2 nos1 set of indicating lamps for the following :Phase indicationBattery charger onDC supply onControl switch onEngine fails to startPump onLow oil pressure.High water temperature.Auto manual selector switch.1 sets of push button stations for the following :Engine start.Engine stopEngine hooter ACK.Engine Fault reset.Selector switches (Engine control, modeAll the components shall be housed in acommon cubical made of 16 SWG MS Sheetwith required stiffners (if required) The Panelshall be powder coated of approved color bothinside & outside. The Panel shall be powdercoated of approved colour both inside &outside. The Panel shall have both bottom &

8 1100 V GRADE POWER / CONTROL CABLESSupply, laying, testing & commissioning of FRLS, PVC outer sheathed, steel armoured,aluminium/copper condoctor,1100 V gradepower cables with glands etc. The cables shallbe laid in tray/hume pipe/in trenches/onwalls/floor etc.as required. For cables laid

td th t h ll i l d E th ti8.1 3.5 C x 70 sq mm YFY for Main Pumps 35 Meter 757.50 26,512.508.2  4 C x 10 sq mm YFY for Jockey Pumps 20 Meter 242.40 4,848.008.3  12 C x 2.5 sq mm for Diesel Engines 20 Meter 459.55 9,191.008.4  2 C x 2.5 sqmm for instrumentation 55 Meter 191.90 10,554.509 G.I Earthing strips of 50 mm x 6 mm thick strip 

shall be run on floor/ceiling/walls etc from Fire Pumps to MCC Panel

30 Meter 85.85 2,575.50

10 Supply,installation,testing & commissioning of MS Pipes IS : 1239/3589 with painting, one coat of primer with two coats of synthetic enamel paint of approved color/shade.(Above Ground Piping)

10.1 200 mm Nb (6.35 mm thick. IS‐3589) 36 RM 2,020.00 72,720.0010.2  150 mm Nb 24 RM 1,717.00 41,208.0010.3  100 mm Nb 6 RM 1,111.00 6,666.0010.4 50 mm Nb 18 RM 454.50 8,181.0010.5 25 mm Nb 6 RM 277.75 1,666.5011

Supply,installation,testing & commissioning ofCI Gate Valve as per IS : 14846 (PN 10) and nonrising spindle type with flanges, bolts, nuts, washers, gaskets, etc.

11.1 150 mm Nb 3 Each 11,110.00 33,330.0011.2  100 mm Nb 1 Each 6,060.00 6,060.0011.3 c) 50 mm Nb 2 Each 3,535.00 7,070.0012

Supply, installation, testing & commissioning ofCI Non Return Valve as per IS : 5312 (PN 16)swing check type with required  flanges, nuts, bolts, gaskets etc.

12.1 150 mm Nb 4 Each 10,100.00 40,400.0012.2 50 mm Nb 1 Each 3,535.00 3,535.0012.3 40 mm Nb 4 Each 3,030.00 12,120.00

1 set 1,86,850.00 1,86,850.00

Page 19: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

13Supplying, Installation, testing & commissioning of Aluminium Di‐ Cast Butterfly valves (PN 16) standard lever operated type with flanges,nuts & bolts, gaskets etc.40 mm Nb

4 Each 2,828.00 11,312.00

14Supplying, Installation, testing & commissioning Gun Metal screw type Ball Valve.25 mm Nb

14 Each 1,010.00 14,140.00

15Supply,installation,testing & commissioning ofCI Foot valve wuth suction strainer withcompanion flanges,gaskts,nuts,bolts etc 

15.1  200 mm Nb 3 Each 12,120.00 36,360.0015.2  80 mm Nb 1 Each 5,050.00 5,050.0016

Hydrant SystemSupply,installation,testing & commissioning ofMS Pipes IS : 1239 (medium grade) withpainting, one coat of primer with two coats ofsynthetic enamel paint of approvedcolor/shade.( Above Ground Piping )

16.1 150 mm Nb 448 RM 1,717.00 7,69,216.0016.2 100 mm Nb 55 RM 1,111.00 61,105.0016.3 80 mm Nb 100 RM 858.50 85,850.0017

Supply,installation,testing & commissioning of MS Pipes IS : 1239 (medium grade) being laid in trenches/hume pipe support complete with necessary fitiings e.g bends,flanges etc and insulated with Anticorrosive bitumen primer and wrapped with 3 mm thick Polymer corrosion resistant tape.150 mm Nb

20 RM 2,020.00 40,400.00

18Supply,installation,testing & commissioning of Hume pipe with jointing collars NP2 for laying of under ground pipe.300 mm dia

24 RM 2,424.00 58,176.00

19Supplying, Installation, testing & commissioning of Aluminium Di‐ Cast Butterfly valves (PN 16) standard lever operated type with flanges,nuts & bolts, gaskets etc.150 mm Nb

4 Each 2,828.00 11,312.00

20 Supply,installation,testing & commissioning of CI Non Return Valve as per IS dual plate wafer type with required  flanges, nuts, bolts, gaskets etc.150 mm Nb.

4 Each 1,313.00 5,252.00

21Supply,installation,testing & commissioning of 25 mm Nb GM Air Release Valve on Hydrant and Sprinkler riser 

21.1Providing & fixing dial type (150 mm) pressuregauge suitable for working pressure of 250 PSIon top of Hydrant Riser

2 Each 1,111.00 2,222.00

22 Supply,installation,testing & commissioning of Fire Hydrant eqiupments as follows: 

22.1  SS Single head Hydrant Valve as per Is 5290 with 63 mm dia instantaneous couplings & 80mm dia flanged inlet,Blank caps,chain.For External/Yard Hydrant System

6 Each 5,454.00 32,724.00

22.2 SS Single head Landing Valve as per Is 5290 with 63 mm dia instantaneous couplings & 80mm dia flanged inlet,Blank caps,chain.For Internal Hydrant System

15 Each 5,454.00 81,810.00

22.3 One length of 15 m long,63 mm dia RRL Hose with SS instantaneous couplings and copper binding for internal Hydrant.

15 Each 4,545.00 68,175.00

Page 20: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

22.4 Two length of 15 m long,63 mm dia CP Hose  with SS instantaneous couplings and copper binding for external Hydrant.

12 Each 4,040.00 48,480.00

22.5 SS short Branch Pipe with 16 mm nozzle. 21 Each 1,818.00 38,178.0022.6  CRCA Hose cabinet accompanied 1 no RRL 

Hose,Branch Pipe for Internal Hydrant.15 Each 2,020.00 30,300.00

22.7  CRCA Hose cabinet accompanied 2 nos. CP Hose,Branch Pipe for External Hydrant.

6 Each 1,616.00 9,696.00

22.8  Fire First Aid Hose Reel drum with 20mm Nb Thermo Plast Hose of 30 mtr in lenghth and dual type (jet+spray) nozzle complete.

15 Each 5,858.00 87,870.00

22.9 4 way Fire Brigade Inlet connection, 63 mm dia in built dia SS non return valve

1 Each 5,050.00 5,050.00

22.10 4 way Fire Water Reservoir Inlet connection, 63  1 Each 5,050.00 5,050.0023 Fire Water Sprinkler System

Supply, installation, testing &commissioning of MS Pipes IS : 1239/3589 withpainting, one coat of primer with two coats of

h l f d23.1 150 mm Nb 160 RM 1,717.00 2,74,720.0023.2 100 mm Nb 119 RM 1,111.00 1,32,209.0023.3 80 mm Nb 398 RM 858.50 3,41,683.0023.4 65 mm Nb 195 RM 505.00 98,475.0023.5 50 mm Nb 91 RM 454.50 41,359.5023.6 40 mm Nb 391 RM 479.75 1,87,582.2523.7 32 mm Nb 484 RM 404.00 1,95,536.0023.8 25 mm Nb 2100 RM 277.75 5,83,275.0024 Supplying, Installation, testing & commissioning 

of Aluminium Di‐ Cast Butterfly valves (PN 16) standard lever operated type with flanges,nuts & bolts, gaskets etc.100 mm Nb

10 Each 3,636.00 36,360.00

25 Supply, installation, testing & commissioning ofCI Non Return Valve as per IS dual plate wafertype with required flanges, nuts, bolts, gasketsetc.100 mm Nb

10 Each 5,353.00 53,530.00

26 Supplying, Installation, testing & commissioning Gun Metal screw type Ball Valve.25 mm Nb

40 Each 1,010.00 40,400.00

27Supplying, Installation, testing & commissioning Standard response quartzoid bulb type sprinkler with 15 mm screwed end connection of 68 deg. C temparature rating and Sprinkler shall must be UL listed.

27.1 Upright Sprinkler 442 Each 202.00 89,284.0027.2 Pendent Sprinkler 631 Each 202.00 1,27,462.0027.3 Sidewall sprinker for Ramp area 225 Each 222.20 49,995.0028

Supplying, Installation, testing & commissioning Stainless steel corrogated flexible pipe (hose) for dropping sprinklers belowfalse ceiling,pipe shall be UL listed

214 Each 1,313.00 2,80,982.00

29Supplying, Installation, testing & commissioning of Sprinkler control valve  ( ICV ) with motor gong bell and trims as required.150 mm Nb

3 Each 45,450.00 1,36,350.00

30 Supplying, Installation, testing & commissioning of Water Flow switch.

11 Each 2,474.50 27,219.50

31Providing & fixing dial type (150 mm) pressure gauge suitable for working pressure of 250 PSI on top of Sprinkler Riser

2 Each 1,111.00 2,222.00

32 Steel structure & supports 1 Lot 35,350.00 35,350.00Fire Extinguishers and Fire Check Door   Supply, installaing and commissioning of Portable Fire Extinguishers of following type & capacity

33 Carbon Di‐oxide type Fire Extinguishers33.1 2.0kg capacity 15 Each 3,333.00 49,995.0033.2 4.5 kg capacity 20 Each 5,050.00 1,01,000.00

Page 21: VOLUME – III - Engineering Projectsengineeringprojects.com/Tender/UploadFiles/3180_Vol-III.pdf · Town Kolkata Development Authority at Plot No. DG/13 ... pnl, VRF & DG Set 550

Sl.  Item Description Qnty Unit Rate (Rs.) Amount (Rs.)

34 Dry chemical type Fire Extinguishers34.1 5.0 Kg capacity 70 Each 1,313.00 91,910.0034.2 10.0 kg capacity 10 Each 1,616.00 16,160.0035 WCO2 type Fire Extinguishers35.1 9.0 ltrs capacity 40 Each 1,414.00 56,560.0035.2 Mechanical Foam 35.3 9.0 ltrs capacity 8 Each 1,616.00 12,928.0035.4 Fire Buckets round bottom type enamel painted 

white inside, red outside with lid and mounting Bracket.

8 Each 454.50 3,636.00

35.5 2 hours Rated Wooden Fire Check Door (Frame & Shutter) with paint finish.( Frame & Shutter ) with paint finish. ( Two nos )

200.00 sqm 6,767.00 13,53,400.00

35.6 Moduler type Clean Agent Fire Extinguishers,  Capacity 4.0 Kg capacity 

39.00 Each 17,170.00 6,69,630.00

35.7 Moduler type ABC Fire Extinguishers, Capacity 5.0 Kg capacity

5.00 Each 7,070.00 35,350.00

36 SIGNAGES36.1 Photoluminescence signages " FIRE EXIT " 40 Each 378.75 15,150.0036.2 Floor identification signages 20 Each 151.50 3,030.0036.3 Electronic signages with emergency battery 

back up for 12 hours16 Each 2,020.00 32,320.00

36.4 Fire Notice 8 Each 505.00 4,040.0037 Fire Alarm and Detection System      

Providing & Fixing, testing & commissioning ofAddressable Pull type Manual Call point with allnecessary fittings and consumables

56 Each 3,181.50 1,78,164.00

38 Providing & Fixing, testing & commissioning ofAddressable Hooter cum Strobe/ Flasher withall necessary fittings and consumables

40 Each 3,333.00 1,33,320.00

39 Providing & Fixing, testing & commissioning ofAddressable Photo Electric Smoke Detectorwith all necessary fittings and consumables

449 Each 2,979.50 13,37,795.50

40 Providing & Fixing, testing & commissioning ofAddressable Heat Detector with all necessaryfittings and consumables

12 Each 2,929.00 35,148.00

41 Providing & Fixing, testing & commissioning ofAddressable Fault Isolator Modules with allnecessary fittings and consumables

19 Each 2,525.00 47,975.00

42 Providing & Fixing, testing & commissioning ofAddressable Monitor Modules with allnecessary fittings and consumables

10 Each 2,828.00 28,280.00

43 Providing & Fixing, testing & commissioning of Addressable Duct Sensor Detector with all necessary fittings and consumables

425 Each 6,565.00 27,90,125.00

44 Providing & Fixing, testing & commissioning of Addressable Control  Modules with all necessary fittings and consumables

225 Each 3,333.00 7,49,925.00

45 Providing & Fixing, testing & commissioning of Response Indicator

170 Each 85.85 14,594.50

46 Providing & Fixing, testing & commissioning of  300 Each 707.00 2,12,100.0047 Providing & Fixing, testing & commissioning of 

250 watt RMS output solid state Amplifier with Microphone

1 Set 25,250.00 25,250.00

48 Providing & Fixing, testing & commissioning of Microprocessor based Intelligent Fire Alarm Panel With battery and battery chargers,The FACP shall have provision of Loop expansion and shall be networkable type. Provision for interfacing with other systems such as SCADA / IBMS with all required hardware and software.

1 Set 2,77,750.00 2,77,750.00

49 Providing & Fixing, laying and termination of Power and Control cable .  3000 RM  146.45 4,39,350.00

1,48,12,025.25