VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING SYSTEM
FOR CAST-IN-PLACE CONCRETE APPLICATIONS
PRODUCT MANUAL
www.cetco.com
PRODUCT MANUAL
- 2 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
CONTENTS
WHAT IS SODIUM BENTONITE?PRODUCT DESCRIPTIONASSOCIATED SYSTEM PRODUCTSACCESSORIESLIMITATIONS
INSTALLATION GUIDELINESSECTION 1: UNDERSLAB INSTALLATION 1.1 Substrate Preparation
1.2 Installation
1.3 Pile Caps & Grade Beams
1.4 Slab Penetrations
1.5 Elevator Pits
1.6EdgeofSlab,BackilledWalls 1.7EdgeofSlab,PropertyLineWalls SECTION 2: PROPERTY LINE CONSTRUCTION 2.1 Property Line Installation Guidelines
2.2 Soldier Pile & Lagging
2.3MetalSheetPilingRetainingWall 2.4 Earth Formed Shotcrete Retention
2.5AugerCastCaissonRetentionWall SECTION 3: BACKFILLED WALLS 3.1 Surface Preparation
3.2 Installation
3.3BackilledWallPenetrations 3.4 Terminations
3.5MasonryBlockWalls SECTION 4: SPECIAL CONDITIONS 4.1 Precast Concrete Construction
4.2 Contaminated Conditions
THIS MANUAL CONTAINS THE INSTALLATION GUIDE-
LINES FOR THE VOLTEX AND VOLTEX DS WATER-
PROOFING SYSTEM FOR CAST-IN-PLACE CONCRETE
APPLICATIONS, INCLUDING UNDERSLAB, PROPERTY
LINE WALLS, AND BACKFILLED WALLS. THIS MANUAL
DOES NOT COVER SHOTCRETE, MASONRY BLOCK,
OR PRECAST CONCRETE APPLICATIONS. FOR APPLI-
CATIONS NOT COVERED IN THIS MANUAL, CONTACT
CETCO FOR SPECIFIC INSTALLATION GUIDELINES.
BEFORE INSTALLATION, READ THIS MANUAL TO GAIN
FAMILIARITY WITH SPECIFIC PROCEDURES AND AP-
PLICATIONS. IN THIS MANUAL THE PRODUCT NAME
“VOLTEX” IS USED GENERICALLY FOR ALL VOLTEX
PRODUCT TYPES.
WHAT IS SODIUM BENTONITE?Sodium bentonite is a non-toxic mineral of volcanic origin found exten-
sively in the Black Hills region of North America. Bentonite is specially
processed by CETCO to achieve the highest possible performance for
allofourwaterprooingproducts.CETCOalsomanufacturersacontami-nant resistant bentonite to assure optimum performance in moderate
saline or contaminated water.
Bentonite prevents water intrusion by forming a dense monolithic mem-
brane upon contact with water. The specially processed bentonite ex-
pandsunderconinement,forminganimperviousmembranethatwillbe maintained for the life of the structure.
PRODUCT DESCRIPTIONVOLTEX is a highly effective waterprooing composite comprised of twopolypropylene geotextiles and sodium bentonite. The two geotextiles are in-
terlocked by a patented needlepunching process which encapsulates and
coninesthebentonite.VOLTEXDS® integrates a polymer liner bonded to
the outside surface of the nonwoven geotextile. The polymer liner provides
extremely low permeabilities for water vapor transmission.
Figure1–CrosssectionillustrationofVOLTEXwaterprooingmembranemechanicallybondedtoconcrete
Concrete
Needlepunched geotextileibers
Granular sodium bentonite
Nonwoven geotextile
VOLTEX forms a continuous mechanical bond to concrete. This bond is created when VOLTEX’s strong geotextileibersareencapsulated by poured concrete as shown in the illustration
Wovengeotextile
www.cetco.com
Installation of VOLTEX is fast and easy. Simply position the product into
place and fasten. VOLTEX can be installed on green concrete, in virtu-
ally any weather, without the need for primers or adhesives. VOLTEX
can be easily cut on site to form around corners and penetrations. The
result is always a consistent self-sealing membrane.
DURABILITYThe VOLCLAY® sodium bentonite in VOLTEX is uniformly encapsulated
between two high-strength woven and non-woven geotextiles. CETCO’s
state-of-the-art needlepunching process interlocks the geotextiles,
preventing the displacement of bentonite prior to, during, and after in-
stallation. The geotextiles provide superior protection from inclement
weather and construction-related damage, without requiring to use a
protection course.
SUPERIOR ADHESIONWhenconcreteispouredagainstVOLTEX,atenaciousmechanicalbondis created with VOLTEX’s high strength geotextile. Independent labora-
torytestingconductedinaccordancewithASTMD903(mod.)(PeelAd-
hesiontoConcrete),yieldsanaverageadhesionvalueof2.6kN/m(15lbs/in).ThemechanicalbondwillholdVOLTEXinintimatecontactwiththe concrete should any ground settlement occur, thereby preventing
watermigrationbetweenthewaterprooingandtheconcrete.
COST EFFECTIVE AND TIME EFFICIENTVOLTEX is designed to be installed on a properly prepared subgrade,
withouttheneedtopouraworkingslab.Theproduct’sinherentlexibil-ity allows for easy installation on irregular surfaces and rough property
line forming. VOLTEX can be installed as soon as the forms are stripped;
there is no waiting for the concrete to cure.
ASSOCIATED SYSTEM PRODUCTSWATERSTOP-RX® – expanding concrete joint waterstop used around
penetrations and applicable concrete joints. Swells upon hydration.
AQUADRAIN® – foundation drainage composite consisting of a molded
proilecoreandailterfabric.Includessheetdrainageandbasedraincollection.
ACCESSORIESBENTOSEAL® – trowel grade mastic used to detail around penetrations,
corner transitions and terminations.
CETSEAL – single-component polyether general sealant and adhesive. HYDROBAR TUBES®–watersolubleilmtubingilledwithactivegranu-
lar material.
WATERSTOPPAGE® – active granular material used at detail areas that
require additional protection.
SEAMTAPE® – premium tape used to seal overlapped membrane edges
ofVOLTEXDS.AKWASWELL® – caulk grade hydrophilic waterstop.
TERMINATION BAR–Min.25mm(1”)widealuminumorstainlesssteelbarwithpre-punchedholeson300mm(12”)centeringforfastening.
CEMENTITIOUS BOARD – 12 mm (1/2”) thick cementitious wallboardforprotectionofwaterprooingduringtheremovalofsteelsoldierpile cap and top lagging boards.
ENVIROSHEET – self-adheringlashingmembraneusedforgradeandthru-walllashing.
TB-BOOT – pre-formed, single piece cover for tie-back heads and soil
nails.Threesizesavailable:TB-6SN,TB-8&TB-10.
LIMITATIONS
VOLTEX should only be installed after substrate preparation has
been properly completed and is suitable to receive the waterproof-
ing system. Concrete work should use conventional cast-in-place
formsthatproduceasmoothsurface.Donotusestay-in-placecon-
crete forming; use removeable forming products only.
VOLTEX is designed for below-grade waterprooing applicationswheretheproductisproperlyconined.VOLTEXproductsshouldnotbe installed in standing water or over ice. If ground water contains
strongacids,alkalies,orisofaconductivityof2,500μmhos/cmorgreater, water samples should be submitted to the manufacturer
for compatibility testing. Ultraseal may be required if contaminated
ground water or saltwater conditions exist.
VOLTEX isdesigned foruseunder reinforcedconcrete slabs100mm (4”) thick or greater on a compacted earth/gravel substrate.VOLTEXrequiresaminimum150mm(6”)thickreinforcedconcreteslab if installed over a mud slab. VOLTEX is not designed for split-
slab plaza deck construction.
VOLTEX is not designed to waterproof expansion joints. Do not use VOLTEX on masonry block foundation walls. Con-sult CETCO for special installation guidelines that apply to shotcrete and precast concrete construction.
In this manual, the product name “VOLTEX” is used generi-cally in the installation and application guidelines for the applicable products: VOLTEX, VOLTEX CR, VOLTEX DS and VOLTEX DSCR. Refer to the table on the back page for prod-uct descriptions and roll sizes. Illustrations are not shown to scale.
PRODUCT MANUAL
- 4 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
INSTALLATION GUIDELINESBefore installing VOLTEX read this installation manual to gain familiarity
withspeciicproceduresandapplications.Forapplicationsnotcoveredinthismanual,contactCETCOforspeciicinstallationguidelines.
VOLTEXisengineeredforuseunderreinforcedconcreteslabs100mm(4”) thickorgreateronacompactedearth/gravel substrate.VOLTEXrequiresaminimum150mm(6”)thickreinforcedconcreteslabifin-
stalledoveramudslab.VOLTEXCRorVOLTEXDSCRisusedincontami-nated conditions as determined by a CETCO water sample test.
For hydrostatic conditions, VOLTEX should be installed under foot-
ings and grade beams as shown in Figures 1.6, 1.7 and 1.8. For non-
hydrostatic conditions, VOLTEX should be installed around footings and
gradebeamsasshowninFigures1.9,1.10and1.11.
Prior to installing VOLTEX the substrate must be properly prepared.
Complete all required elevator pit, sump pit, grade beam and piling
work prior to installing VOLTEX under main slab area. These areas must
becorrectlytiedintotheunderslabwaterprooingtoformamonolithicseal.
1.1 SUBSTRATE PREPARATIONSubstrate may be concrete, earth, sand, or crushed stone. Earth and
sand substrates should be compacted to a minimum 85% ModiiedProctordensity.Crushedstoneshouldbenolargerthan19mm(3/4”)insize.Substrateshouldbesmoothandwithoutsharpdelectionsorpockets.
1.2 INSTALLATIONInstallVOLTEXorVOLTEXDSovertheproperlypreparedsubstratewiththedarkgray(woven)geotextilesideup.Overlapalladjoiningedgesaminimumof100mm(4”)andstaggersheetendsaminimumof300mm(12”)(Figure1.1).Nailorstapleedgestogetherasrequiredtopre-
ventanydisplacementbeforeandduringconcreteplacement(Figure1.2).
Whentheslabispouredinsections,VOLTEXshouldextendaminimum300mm(12”)beyondtheslabedge(Figure1.3).ThisenablesVOLTEXto be properly overlapped for subsequent slab section pours. WATER-
STOP-RX should be installed in all applicable slab construction joints
(Figure1.3).
SECTION 1
UNDERSLAB INSTALLATION
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
Overlap 100mm(4")min.
Figure 1.2 – Secure overlaps together with fasteners
Figure 1.3 – Extend VOLTEX a minimum 300mm(12”) beyond slab edge. Install
WATERSTOP-RX in joint
Figure 1.1 – Overlap edges 100mm(4”)withseamsstaggered300mm(12”)
VOLTEX
Overlap 100mm (4")Min.
Stagger300mm(12”)
Reinforced concrete slab
300mm(12”)min VOLTEX
WATERSTOP-RX min.75mm(3”)coverage
www.cetco.com
WATERSTOP-RX 75mm(3”)min.coverage
Reinforced concrete slab a minimum100mm(4”)thick
VOLTEX
Compacted Substrate
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
Figure1.4–VOLTEXinstalleddirectlyovercompactedearth/gravelsubstraterequiresaminimum100mm(4”)slab
Reinforced concrete slab a minimum150mm(6”)thick
VOLTEX
Compacted Substrate
Concrete mud slab
Figure1.5–VOLTEXinstalledoveramudslabrequiresaminimum150mm(6”)thickreinforcedslab
WATERSTOP-RX 75mm(3")min.coverage
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
PRODUCT MANUAL
- 6 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
HYDROSTATIC CONDITIONS NON-HYDROSTATIC CONDITIONS
VOLTEX
VOLTEX
Hydrobar Tube
Figure1.6–Slabonfootingdetail(hydrostatic)
VOLTEX
BENTOSEAL
Hydrobar Tube
VOLTEX
Mud slab
Figure1.7–Raisedslabdetailwithmudslab(hydrostatic)
VOLTEX
VOLTEX
Figure1.8–Flushslabdetailpropertylinewall(hydrostatic)
VOLTEX
Hydrobar Tube
Figure1.9–Slabonfootingdetail(non-hydrostatic)
VOLTEX
BENTOSEAL
VOLTEX
Mud slab
Figure1.10–Raisedslabdetailwithmudslab(non-hydrostatic)
VOLTEX
Term Bar & BENTOSEAL
300mm (12”)
Figure1.11–Flushslabdetailbackilledwall(non-hydrostatic)
WATERSTOP-RX 75mm(3")min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
WATERSTOP-RX 75mm(3”)min.coverage WATERSTOP-RX
75mm(3”)min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
Term bar and BENTOSEAL
www.cetco.com
1.3 PILE CAPS AND GRADE BEAMSVOLTEX is typically not installed over pile caps but cut to it tightlyaroundpilecaps.Thenapplyaminimum19mm(3/4”) thickilletofBENTOSEALatintersectionofVOLTEXandthepiling(Figure1.12)withWaterstoppageunderVOLTEXat thepilingedge.BENTOSEAL should
extendontoVOLTEXandpilingaminimumof50mm(2”)at19mm(3/4”)thickness.WATERSTOP-RX should be installed on top surface of
pilecaparoundreinforcingsteel(Figure1.12).
Detail gradebeams thesameaspilecaps (Figure1.14)withanon-hydrostatic condition. For hydrostatic conditions, VOLTEX should be in-
stalledundertheentiregradebeam(Figure1.15).Linethegradebeamformwork with VOLTEX prior to placement of reinforcing steel. Leave a
minimum300mm(12”)ofVOLTEXat the topof the formto tie intobelowslabwaterprooing.
Figure1.12–PileCapDetail(Hydrostaticcondition)
Figure1.13–PileCapDetail(Non-hydrostaticcondition)
Figure1.14–GradeBeam(Non-hydrostaticcondition) Figure1.15–GradeBeam(Hydrostaticcondition)
WATERSTOP-RX
Concrete pile
BENTOSEAL
VOLTEX
Waterstoppage
WATERSTOP-RX
Metal I-beam
VOLTEX
WATERSTOP-RX
50mm(2”)thickilletofBENTOSEAL
GranularWaterstoppage
WATERSTOP-RX
Waterstoppage
VOLTEX
BENTOSEAL
Pile cap
BENTOSEAL
Pile
WATERSTOP-RX Reinforcing steel BENTOSEAL
VOLTEX
Grade beam
50mm(2”)thick illetof Waterstoppage
Grade beam
Reinforcing steelWATERSTOP-RX
VOLTEX
PRODUCT MANUAL
- 8 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
1.4 SLAB PENETRATIONSCutVOLTEX tocloselyitaroundpenetrations (Figure1.16).Trowelaminimum19mm(3/4”)thickilletofBENTOSEAL around the penetra-
tiontocompletelyillanyvoidareabetweenVOLTEXandthepenetra-
tion(Figure1.17).TheBENTOSEAL should extend up the penetration
about38mm(1–1/2”)andextendontoVOLTEX.Inareaswheremulti-ple penetrations are close together, it may be impractical to cut VOLTEX
toitaroundeachpenetration.PourWaterstoppage,granularbenton-
ite,aminimum6mm(1/4”)thickaroundthepenetrationscoveringtheentiresubstratearea.Withgravelsubstrate,installminimum200mm(8”) collar of VOLTEX around penetration prior to placing waterstop-
page. Then apply a thick layer of BENTOSEAL around each penetration
asdetailed(Figure1.19).
Figure 1.17 – BENTOSEAL troweled around penetrations Figure 1.18 – Slab penetration cross section detail
Figure1.19–Multiplepipepenetrations.TrowelBENTOSEAL around pipes and covering area between the pipes
VOLTEX
Pipe
BENTOSEAL
DARK GRAY (WOVEN) GEOTEXTILE SIDE UP
VOLTEX
Waterstoppage
BENTOSEAL
WATERSTOP-RX 75mm(3")min.coverage Pipe
Mud Slab Substrate Compacted Earth or Gravel Substrate
Mud slab
WATERSTOP-RX
BENTOSEAL
Continue VOLTEX between pipes
VOLTEX
WaterstoppageMud slab substrate
Continue VOLTEX between pipes
WATERSTOP-RX
BENTOSEAL
Gravel substrate
VOLTEX collar Waterstoppage
www.cetco.com
1.5 ELEVATOR PITSVOLTEX should be placed on vertical surfaces and on the substrate be-
lowtheslabtoformacontinuousenvelopearoundtheelevatorpit(Fig-
ure1.20).Iftheverticalsoilcutissmoothandstable,VOLTEXmaybe
installed directly against the soil. Contain unstable soils with a retaining
wall. InstallVOLTEXdirectlyagainsttheretainingwall.Duetovariouselevatorpistonplungerdesigns,consultCETCOforspeciicinstallationand detailing for piston plungers that penetrate the pit slab.
Figure1.20–VOLTEXunderelevatorpitslabandonexcavationcutwalls
1.6 EDGE OF SLAB, BACKFILLED WALLSWhen the installation reaches the outer edge of the slab, continueVOLTEXuptothetopedgeoftheformsinsidesurface(Figure1.21)orextendtheVOLTEXsheetoutthetopoftheformaminimumof300mm(12”)(Figure1.22).Attheslabcorner,VOLTEXshouldremainincontactwith the substrate and the inside surface of the concrete form.
When the slab edge form is removed, any undamaged portion ofVOLTEX extended outside the form should be positioned and secured
tothetopoftheconcretefooting.Damagedmaterialoutsidetheformshould be cut off and disposed of. Overlap the secured VOLTEX edge
ontopofthefootingaminimum150mm(6”)withthesucceedingwallwaterprooing.InstallHydrobarTubesatwall-to-footingcornerpriortoinstallingoverlappingwallwaterprooing.
WATERSTOP-RXshouldbeinstalledintheperimeterwall/slabintersec-
tion joint as illustrated in Figure 1.23.
Figure 1.21 – VOLTEX turned up and secured at top of concrete form Figure 1.22 – Extra tail of VOLTEX extended out of form and later cut off after concrete pour
300mm(12”) min
VOLTEX
Compacted substrate
VOLTEX VOLTEX secured to top of form before concrete pour
Slab edge form
Compacted substrate
VOLTEX
Extra tail of VOLTEX extended out of form. Cut off damaged areas before installing VOLTEX overlap
Slab edge form
Compacted substrate
WATERSTOP-RX 75mmmin.(3”)coverage
PRODUCT MANUAL
- 10 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
1.7 EDGE OF SLAB, PROPERTY LINE CONSTRUCTIONWherepropertylineretainingwalls,suchassoldierpileandlagging,areused as the outside form, continue the underslab VOLTEX installation
uptheretainingwallaminimum300mm(12”)abovethetopedgeoftheslaborfooting(Figure1.23).Theextra300mm(12”)sheetexten-
sion is very important since there is no access to the outer edge of the
footing after it is poured.
Slab to Wall Corner Transition:InstallVOLTEXorVOLTEXDSsheethorizontallyoriented(darkgraywovengeotextilefacinginstaller)withaminimum300mm(12”)ofthesheetextendingoutontothehorizontalsubstrate.Thetopedgeofthesheetmustextendaminimum300mm(12”)abovetheinishedslabsurface.SecureVOLTEXsheettolaggingwall with washer-head fastener maximum 600 mm (24”) on center.OverlapedgesofadjacentVOLTEXsheetsaminimum100mm(4”).
Iftheslabthicknessisgreaterthan600mm(24”),installasecondfullsheetorcutstripofVOLTEX,horizontallyoriented,tomeetthe300mm(12”)requirementabovetheslab.Overlaptopedgeofprevioussheetandedgesofadjacentsheetsaminimum100mm(4”).
Base Wall Course: InstallirstVOLTEXsheetcourseontheshoringwallhorizontallyoriented (darkgreywovengeotextile facing installer)over the corner transition sheet, with the bottom edge extending down
to the wall/slab transition corner as shown in Figure 1.23. SecureVOLTEX sheet to lagging wall with washer-head fasteners maximum
600mm(24”)oncenter.OverlapedgesofadjacentVOLTEXsheetsaminimum100mm(4”).
Install underslab VOLTEX membrane extending to corner transition,
overlappingthe300mm(12”)sheettailofthecornertransitionsheetinstalledatthewallbase.Securecorneredgewithfasteners300mm(12”)oncenter.
Formetalsheetpilingshoringwalls,irstinstalltheVOLTEXcornertran-
sition sheet horizontally oriented with the bottom edge extending mini-
mum300mm(12”)outontothesubstrate.Cutthebottomedgeofthecorner transition sheet at piling transition angles to allow the bottom
edgetolaylatontothesubstrate.Pour38mm(11/2")continuouscantof Waterstoppage along base of shoring wall. Then install underslabVOLTEXsheetcuttoitcontoursofmetalsheetpiling.Finally,installthebaseshoringwallVOLTEXsheet(horizontallyoriented)overlappingthecorner transition sheet.
Figure1.23–SLAB-TO-WALLTRANSITION–VOLTEXcornertransitionsheetshouldextendpasttheheightofthetopoftheinishedslablevelaminimum300mm(12”)andextendundertheslab300mm(12”)
Figure 1.24 – AQUADRAIN100BDDISCHARGEPIPE–ConnectAQUAD-
RAIN100BDtowaterdischargepipesusing100BDaccessorycon-
nections
VOLTEX under slabVOLTEX transition sheet at corner in-stalled horizontally oriented
Cast-in-place concrete wall
VOLTEX base course installed horizontally oriented
Woodlagging
300mm (12”)min
VOLTEX base course installed horizontally oriented
AQUADRAIN SheetDrain
Woodlagging
300mm (12”)min
AQUADRAIN100BDbasedrainconnected to discharge pipes
VOLTEX transition sheet at corner installed horizontally oriented
VOLTEX
DischargePipe
WATERSTOP-RX 75mm(3")min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
300mm(12”)BENTOSEAL
www.cetco.com
The use of construction techniques described in this section allow the
exterior building dimensions to coincide with the property line, thereby
maximizinguseofavailablelandforbuilding.VOLTEX/VOLTEXDShasbeen proven to be one of the most effective and widely used means
forwaterprooingpropertylineconstruction.Cast-in-placepropertylineconstruction methods include soldier pile & lagging, metal sheet piling,
earth formed shotcrete retention walls, and auger cast caisson walls.
For all property line construction methods, VOLTEX is installed to the shoring wall prior to concrete placement.Install VOLTEX or VOLTEX DS with the dark grey (woven) geotextile inward, facing the installer, away from the shoring wall. Refer to each applicable construction method in Section 2 for speciic sub-strate preparation and detailing installation guidelines.
AQUADRAINsheetand100BDbasedraincompositesystemshouldbeconnectedtoanoperativewaterdischargesystem(sumppumporgrav-
itytodaylightdischarge).
Protectbentonitewaterprooingproductsfromhydratingbeforemate-
rialiscontainedwithconcreteorbackill.Afteranyprecipitation,stand-
ingwatershouldbepumpedoffwaterprooingassoonaspossible.
Shoring Wall: Excavation work should provide shoring wall in good
condition to receive waterprooing system. Wood lagging shoringshouldextendtothelowestlevelofthewaterprooinginstallationwithanyvoidsorcavitiesexteriorofthelaggingilledwithcompactedsoilorcementitiousgrout.Voidsorcavitiesattie-backsshouldbeilledwithgrout or compacted soil prior to VOLTEX installation. Interior surface of
lagging timbers should be monolithic and tight together with gaps less
than25mm(1”).Gapsinexcessof25mm(1”)shouldbecompletelyilledwithcementitiousgroutorothersolidmaterial.
Cut rock excavations and concrete auger cast caisson retaining walls
must be suficiently planar. Typically a shotcrete or grout layer is re-
quired to provide acceptable surface to install VOLTEX.
Employconstructionmethodstostopwaterlowingthroughshoringwallpriortowaterprooinginstallation.Ifonlywaterseepage,installpolyeth-
ylene sheeting over the seepage area prior to installing VOLTEX. Poly-
ethylene sheeting should extend from seepage elevation to base of wall
toprotectentirewaterprooinginstallationatthatarea.
SECTION 2
PROPERTY LINE CONSTRUCTION
Figure1.25–RAISEDSLABCONDITION–ConnectAQUADRAIN100BDtowaterdischargepipesusing100BDaccessoryconnectors
Figure 1.26 – Metal sheet piling to slab transition detail
Cast-in-place concrete wall
AQUADRAIN
VOLTEXWood lagging
Hydrobar tube
VOLTEX
Dischargepipe
AQUADRAIN100BDbasedrainconnectedtodischarge pipes
VOLTEX underslab
300mm(12”)min.
Waterstoppagecantin corner over VOLTEX corner transition sheet
Metal sheetpiling
VOLTEX base layer horizontally oriented
WATERSTOP-RX 75mm(3”)min.coverage
WATERSTOP-RX 75mm(3”)min.coverage
BENTOSEAL
Retained earth
VOLTEX corner transition sheet horizontally oriented(installirst)
VOLTEX corner transition sheet horizontally oriented(slicedto contour sheet piling)
VOLTEX cut to itcontoursofsheet piles
Mud slab
INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
PRODUCT MANUAL
- 12 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
2.1 PROPERTY LINE WALL INSTALLATION
GUIDELINESAfter the slab-to-wall corner transition sheet and bottom wall sheet
coursehavebeen installedperSection1.7Page10,VOLTEXsheetscan be installed either vertically or horizontally oriented. Fasten the
VOLTEX intopositionwithwasher-head fastenersmaximum600mm(24”)oncenteraroundthesheetedge.InstallsucceedingVOLTEXsheetoverlappingtheprevioussheetedge100mm(4”). (Note:Shingle lapseams so that the bottom edge of the upper sheet is over the lower
sheetstopedge).
Continueinstallationupwalluntilgradedetail,orasspeciied,stagger-ingallsheetendsofadjacentrollsaminimum300mm(12”).Donotallow sheet overlap joints to occur at same elevation as concrete cold
joints. Plan by chalk lining the location of construction joints.
Penetrations: Install a cut collar of VOLTEX tightly around the penetra-
tion;extendingaminimum300mm(12”)radius.ApplyBENTOSEAL over
VOLTEX collar around penetration; extending BENTOSEAL a minimum
75mm(3”)radiusat6mm(1/4”)thickness.TheninstallmaincourseofVOLTEX membrane tightly around the penetration. Finally, detail around
penetrationwith19mm(3/4”)thickcantofBENTOSEAL.Withsleevedpipes,theconcreteworkshouldincludeillingthegapbetweenthepipeand the sleeve with non-shrink cementitious grout, mechanical seal by
others and install WATERSTOP-RX to outside of sleeve.
Tie-Back Covers:SelectappropriatesizeTB-Boottoitovertie-backplate and allow proper cast-in-place concrete coverage per project re-
quirements. TB-Boot should it over entire tie-back head without thetie-back plate or cables in direct contact with the TB-Boot. Prior to TB-
Bootinstallation,illvoidsinretentionwallsubstrateandtie-backheadassemblywithspray foam (min20psi)ornon-shrinkgrout.Fornon-hydrostatic conditions, install and secure AQUADRAIN drainage com-
posite course per manufacturer’s guidelines to soil retention wall prior
to installing TB-Boot. For hydrostatic conditions, install TB-Boot prior
toVOLTEXmembrane.Withsoldierpiles,strippileswithwaterprooingmembrane prior to TB-Boot placement.
Fill pre-formed shape of TB-Boot with 2-part urethane spray foam
(min20PSI)andplaceovertie-backheadbeforefoamsetsup.Se-
cure TB-Boot to soil retention system using washer head fasteners
alongtheoutsideedgeofthelatbase.Apply6mm(1/4”)thickbyminimum75mm(3”)widecontinuousringofBENTOSEAL onto the
latbasejustoutsideofthe12mm(1/2”)raisedcollar.Install4-ftby4-ftpieceofVOLTEX(withprecutholeincentertoittightaroundthe12mm(1/2”)raisedcollar)overtheentirelatbasewithoutsideedges fastened to the retaining wall. Secure inside VOLTEX edge
around raised collar with washer-head fasteners that pass through
the BENTOSEALring;typicalfastenerspacing150mm(6”).Donotinstall fasteners or puncture TB-Boot inside of the 12 mm (1/2”)raised collar. Apply counter lashing of BENTOSEAL along VOLTEX
sheet edge around raised collar. Then install VOLTEX ield sheetoverlappingoutermembraneedgeminimum100mm(4”).
Figure 2.1 – WALL PENETRATION – Cut and secure VOLTEX tightlyaround penetrations and then apply BENTOSEAL 19 mm (3/4”) ringaroundpenetrationandextendovermembraneaminimum75mm(3”)radiusatminimum6mm(1/4”)thickness
Figure2.2–SLEEVEDWALLPENETRATION–Cut and secure VOLTEX tightly around penetrations and then apply BENTOSEAL19mm(3/4”)ringaroundpenetrationandextendovermembraneamin.75mm(3”)
300mm (12”)min
Woodlagging
300mm(12")VOLTEXcol-lar around pipe penetration
19mm(3/4")BENTOSEAL cant
WATERSTOP-RX
Pipe
Cast-in-place concrete wall
VOLTEX
AQUADRAINSheetDrain
300mm (12”)min
Woodlagging
300mm(12")VOLTEXcol-lar around pipe penetration
19mm(3/4")BENTOSEAL cant
WATERSTOP-RX
Pipe
VOLTEX
AQUADRAIN Sheet Drain
Pipesleeve,illedwithnon-shrink grout
Cast-in-place concrete wall
BENTOSEAL ring 6mmx75mm(1/4”x3")min
BENTOSEAL ring 1/4"x3"min
Mechanical seal by others
www.cetco.com
Soldier Pile Stripping: Install a strip of VOLTEX over all soldier piles
with raised lagging hanger bolts, form tie rods, or other irregular sur-
face.VOLTEXstripshouldextendaminimum150mm(6”)tobothsidesof the piling. Apply BENTOSEAL6mmx50mm(1/4”x2”)toVOLTEXstripsurfacealongbothedgesofeachsoldierpile(Figure2.9).
Cementitious Board: Prior to installing VOLTEX/VOLTEX DS to in-
ishedgrade, install12mm(1/2”)thickcementitiouswallboardcen-
teredoversteelsoldierpilefrominishedgradeelevationtospeciieddepth that the top of steel soldier pile and wood lagging will be removed
(Figure2.13).
Grade Termination:TerminateVOLTEXmembrane300mm(12”)be-
lowinishedgradeelevationwithwasher-headfastenersmaximum300mm(12”)oncenter.InstallENVIROSHEETlashingtoprimedconcretesubstrate with bottom edge overlapping top edge of VOLTEX membrane
minimum100mm(4”).Overlapallrollendsaminimum100mm(4”)toformacontinuouslashing.Heightoflashingshallbeperprojectde-
tailsandspeciications.Installarigidterminationbaralongtopedgeof
ENVIROSHEET;fastenedmaximum300mm(12”)oncenter.Completegrade termination detail with tooled bead of CETSEAL along the top
edge,atallpenetrationsthroughthelashing,andallexposedoverlapseams.
Where lagging timbers and the top end of steel soldier piles are re-
moved, repair any waterprooing damaged by the excavation and re-
moval of the retention wall system. Secure all excavated VOLTEX over-
lap seams with washer-head fasteners maximum 600 mm (24”) oncenter;withVOLTEXDSalsoapplySeamtapecenteredalongoverlapseams.Backillshallbeplacedandcompactedtominimum85%Modi-iedProctordensitypromptlyafterwaterprooing installation.Backillshouldconsistofcompactablesoilorangularaggregate19mm(3/4”)or less) freeofdebris,sharpobjects,andstones larger than19mm(3/4”).Seeterminationdetailsigures3.11and3.12,page22.
Figure2.3:TIE-BACKDETAIL–InstallTB-Bootcenteredovertie-backthen install main course of VOLTEX with BENTOSEALdetailing.Donotfasten boot inside of raised collar around center formed area
Shoring wall
VOLTEX
AQUADRAIN sheet drain
2-part urethane expanding spray foam (min.20PSI)
Soldier pile
Fastener
Use spray foamtoillall voids behind tie-back
Donotfasten boot inside of raised collar
Tie-back head with cables
CETCO pre-formed TB-Boot
BENTOSEAL 6 mm X 75 mm (1/4”x3”)min VOLTEX
Field Sheet
Concrete wall
Fastener
Raised collar
Figure2.3a:TIE-BACKDETAIL–InstallTB-Bootcenteredovertie-backthen install VOLTEX with BENTOSEALdetailing.Donotfastenbootin-
side of raised collar around center formed area
Shoring wall
Soldier pile
Fastener
VOLTEX pile strip
VOLTEX
Raised collar
TB-Boot
Fastener
Soldier pile
VOLTEXieldsheet
Use spray foamtoillall voids behind tie-back
Donotfasten boot inside of raised collar
VOLTEX pile strip
VOLTEX pile strip
Tie-back head with cables
CETCO pre-formed TB-Boot
2-part urethane expanding spray foam (min.20PSI)
VOLTEXieldsheet
BENTOSEAL 6 mm X 75 mm (1/4”x3”)min
NON-HYDROSTATIC CONDITIONS HYDROSTATIC CONDITIONS
BENTOSEAL
Soldier pile
AQUADRAIN
BENTOSEAL
BENTOSEAL
BENTOSEAL
PRODUCT MANUAL
- 14 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
2.2 SOLDIER PILE & LAGGING RETAINING WALLVerify the following substrate preparation work has been completed.
Then install VOLTEX following the property line installation guidelines in
Section 2.1 on page 12 and 13.
Preparation: Gaps between the wood lagging must be no wider than
25mm(1”).Ifthegapsbetweenlaggingareinexcessof25mm(1”),thegapsshouldbecompletelyilledwithcementitiousgrout,wood,ex-
trudedpolystyrene(40psimin.)orcompactedsoil(Figure2.7).Ifwaterislowingthroughthelagging,athinpolyethylenesheetingcanbein-
stalled over the area before VOLTEX is installed.
In areas with large gaps (up to 63 mm [2–1/2”]) between lagging,AQUADRAIN sheet drainage composite can be installed over the lagging
toprovideauniformsurface tomountVOLTEX (Figure2.8).Securelyfasten AQUADRAIN to the lagging surface with washerhead nails be-
foreinstallingVOLTEX.Gapslargerthan63mm(2–1/2”)betweenlag-
gingshouldbecompletelyilledwithgrout,wood,extrudedpolystyrene(40psimin.)orcompactedsoilevenifAQUADRAIN is installed prior to
VOLTEX.Donotuseplywoodorothersurfacetreatmentoverlargelag-
ginggapsthatleavesthecavityvoid.Details2.10through2.12onpage15 illustrate the installation of VOLTEX over the different wood lagging
positions relative to the soldier piling.
Figure 2.8 – AQUADRAIN used
to cover gaps in lagging less
than 63 mm (2.5”). (Cast-in-placeconcretewall)
Woodlagging
VOLTEX
Grout caps larger than25mm(1”)
WATERSTOP-RX
Woodlagging
VOLTEX
AQUADRAIN
WATERSTOP-RX
Figure2.9–InstallVOLTEXontosoldierpileandwoodlaggingretainingwallpriortocast-in-placeconcretewall
BENTOSEAL troweled over surface of VOLTEX strip at both edges of the soldier pile
VOLTEX strip centered over soldier pile BENTOSEAL
TB-Boot over tie-back plate
VOLTEX corner transition sheet installed horizontally oriented
VOLTEX base wall course installed horizontally oriented
Wood lagging
Tie-back head
Soldier pile
VOLTEX section
100mm (4”)
INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
Figure 2.7 – VOLTEX installed di-
rectly to wood lagging with gaps
illed. (Cast-in-place concretewall)
www.cetco.com
Wood lagging
Steel piling
VOLTEX main course
VOLTEX strip over pile prior to main course
WATERSTOP-RX (75mm(3”)min coverage)
BENTOSEAL
Cast-in-place concrete wall
Woodlagging
Steel piling
Retained earth
VOLTEX main course
BENTOSEAL between sheets of VOLTEX
VOLTEX strip over pile prior to main course
Fill gap with solid material
Cast-in-place concrete wall
Plate & bolts secure lagging
WATERSTOP-RX (75mm(3")min coverage)
Figure 2.11 – Lagging secured to inside surface of front pile lange.Install VOLTEX strip to cover mounting plates and bolts prior to main
course(PlanView)
Figure2.10–Laggingsecuredtooutsidesurfaceof frontpilelangeprovidingsmoothsurface(PlanView)
Figure2.12–Lagging secured to insidesurfaceofbackpile lange.Install BENTOSEAL and VOLTEX strip prior to main VOLTEX course and
inward BENTOSEALcant.(PlanView)
Steel piling
Woodlagging
VOLTEX main course
BENTOSEAL, apply two cants – one before VOLTEX strip and one after main course
WATERSTOP-RX to exterior of cut rebar hole in steel piling
VOLTEX strip over pile prior to main VOLTEX course
WATERSTOP-RX (75mm(3”)min coverage)
Figure2.13–WALLEXCAVATIONATGRADE–Cementitiousboardpro-
tectswaterprooingduringexcavationandremovalofsteelpiletopandwood lagging
VOLTEX Cementitious board
Woodlagging
Steel H-pile, top removed with excavation work
AQUADRAIN sheet drainCast-in-place concrete wall
PRODUCT MANUAL
- 16 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
Figure 2.14 – Sheet pile interlock detail
Figure 2.15 – Install VOLTEX onto metal sheet piling retaining wall with powder-actuated fasteners
2.3 METAL SHEET PILING RETAINING WALLVerify the following substrate preparation work has been completed.
Then install VOLTEX following the property line installation guidelines in
Section 2.1 on page 12 and 13. Special knurled powder-actuated fas-
teners are recommended to secure VOLTEX to the metal sheet piling.
Preparation:Trowela12mm(1/2”)thicklayerofBENTOSEAL along
all sheet piling knuckles. Fill voids or cavities at tieback plates with ce-
mentitious grout or compacted soils. If excessive water is penetrating
the sheet piling knuckles, Bentogrout can be injected to the outside of
theknuckletostopwaterlow(Figure2.14).ConsultCETCOforBentogrout applications and installation guidelines.
Alternate Plywood MethodAlternatively,12mm(1/2”)plywoodmaybefastenedtothesheetpilingtocreatealatsurfaceuponwhichVOLTEXisfastened.Allvoidspacesbetweentheplywoodandsheetpilingmustbeilledwithcompactedearth or concrete. Apply VOLTEX to plywood following “Property Line
Construction”GuidelinesinSection2,Page11.
BENTOGROUT injected to exterior sideofsheetpileinterlock(perprojectrequirements)
Retained earth
Sheet piling
VOLTEXBENTOSEALSheet pile interlock
Cast-in-place concrete wall
VOLTEX vertical seams should not occur at interlocking of sheet piling
VOLTEX
WATERSTOP-RX (75mm(3”)mincoverage)
Retained earth
Metal sheet piling
Completelyillareabehind plywood with compacted soil or concrete
Optional technique: plywood fastened to sheet piling to form latsurfacetomountVOLTEX
INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
www.cetco.com
2.4 EARTH FORMED SHOTCRETE
RETAINING WALLVerify the following substrate preparation work has been completed.
Then install VOLTEX following the property line installation guidelines in
Section 2.1 on page 12 and 13.
Preparation: The surface of the earth formed diaphragm wall must
besuficientlyplanartoprovideanadequatelysmoothsurfacetoapplyVOLTEX. VOLTEX can be applied over large, relatively shallow indenta-
tions. The surface should not contain voids or sharp protrusions in ex-
cessof25mm(1”).FillallvoidswithcementitiousgroutandremoveprotrusionspriortoinstallingVOLTEX(Figure2.18).
Figure 2.17 – Earth formed concrete retention wall with concrete cais-
sonsupports.(PlanView)
Figure 2.18 – VOLTEX installation over an earth formed shotcrete retention wall prior to cast-in-place concrete wall
Figure 2.16 – Grout void area and remove protrusions to provide
smooth surface for VOLTEX
WATERSTOP-RX 75mm(3")min-coverage)
Grout irregular areas
VOLTEX
Cast-in-place concrete wall
Shotcrete retaining wall (non-structural)
Shotcrete retaining wall (non-structural)
VOLTEX
WATERSTOP-RX
Cast-in-place concrete wall
Retained earth Concrete caisson
Retained earth
Shotcrete retaining wall (non-structural)
VOLTEX
VOLTEX corner transition sheet horizontally oriented
Grouted depressions and irregular surfaces
100mm(4”)
100mm(4”)INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
PRODUCT MANUAL
- 18 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
Figure2.19–CutRockexcavationwithshotcreteappliedtoprovideasmoothsurfaceforwaterprooinginstallation
Figure2.20–Fillinrecessesbetweencastcaissonswithgrouttopro-
videsmoothsurface(PlanView).
2.5 AUGER CAST CAISSON WALLSVerify the following substrate preparation work has been completed.
Then install VOLTEX following the property line installation guidelines in
Section 2.1 on page 12 and 13.
Preparation: The surface of auger cast caisson and cut rock excava-
tionwallsmustbesuficientlyplanartoprovideanadequatelysmoothsurface to apply VOLTEX. VOLTEX can be applied over large, relative-
ly shallow indentations where VOLTEX can conform tight against the
surface. The surface should not contain voids or sharp protrusions in
excessof25mm(1”).Fillalllargerecessesbetweencaissonswithce-
mentitiousgroutpriortoinstallingVOLTEX(Figure2.20).Cutrockexca-
vations typically require shotcrete or grout work to provide acceptable
surfacetoinstallVOLTEX(Figure2.19).
Figure 2.21 – VOLTEX installation over an auger cast concrete retention wall prior to cast-in-place concrete wall
Retained earth side Concrete caisson
VOLTEX Grout recesses
Retained earth
VOLTEX
100mm(4”)
VOLTEX corner transi-tion sheet horizontally oriented
Shotcrete retaining wall (non-structural)
Grouted depressions and irregular surfaces
Cut rock formation from excavation
Shotcrete applied to cut rock surface(non-structural)
VOLTEX TB-6SN
VOLTEX
WATERSTOP-RX
BENTOSEAL detailing
DARK GRAY (WOVEN) GEOTEXTILE SIDE FACING INSTALLER
www.cetco.com
InstallVOLTEXorVOLTEXDSwiththedarkgray(woven)geotextilesideagainst the concrete wall on cast-inplace concrete foundation walls
priortobackilling.VOLTEXmaybeappliedassoonastheformsareremoved. It is not necessary to wait for the concrete to completely cure.
Use VOLTEX with concrete cast with conventional forms that produce
smooth surface.
3.1 SURFACE PREPARATIONFooting should be swept clean of silt, rocks and debris to provide VOLTEX
with direct contact to the concrete in the application area. The wall sur-
face must be properly prepared before VOLTEX is installed. Areas of
surfacehoneycombingorvoidsshouldbeilledwithcementitiousgroutor BENTOSEAL.Protrusionsofover6mm(1/4”)shouldbeknockedoffsmooth with the concrete surface. Concrete work should include com-
pletelyillingtaper-tieholeswithnon-shrinkcementitiousgroutandapiece of WATERSTOP-RXcenteredinthewall(Figure3.1).ApplyBEN-
TOSEALoverexteriorgroutedsurfaceofallformtieholes(Figure3.1).
3.2 INSTALLATIONBefore installing theirstcourseofVOLTEX,placeHydrobarTubesatthewall/footinginsidecorner(Figure3.2).“Butt”theendsofHydrobarTubes together to form a continuous line.
Beginning at the bottom corner of the wall, install VOLTEX horizontal-
lyorientedwith1.5m(5’)ononewallandtheremainderaroundthecornerontheotherwallsurface(Figure3.2).CutthebottomedgeofVOLTEXatthecorneraminimumof150mm(6”)sothatVOLTEXcanbe extended onto the footing. Fasten VOLTEX into position with washer
headfastenersmaximum600mm(24”)oncenter.Thencutandinstalla VOLTEX section over the uncovered footing corner area. Apply BEN-
TOSEALattheVOLTEXsectiontoVOLTEXoverlaps.(Figure3.2).
Install adjacent VOLTEX rolls of the bottom course horizontally oriented.
Eachrollshouldoverlaptheprecedingrollaminimum100mm(4”)andshould extend onto the footing a minimum 150 mm (6”). At verticalinsidecornersapplyacontinuous19mm(3/4”)illetofBENTOSEAL
directlyinthecornerpriortoinstallingVOLTEX(Figure3.3).Staggerallverticaloverlapjointsaminimumof300mm(12”)(Figure3.4).Whenhydrostatic conditions exist, the vertical wall VOLTEX should cover the
entirefootingandoverlaptheunderslabwaterprooingaminimum150mm(6”)(Figure3.6).TapeallVOLTEXDSmembraneoverlapseamswithCETCO Seamtape.
SECTION 3
BACKFILLED WALLS
Figure 3.2 – Start VOLTEX at the corner horizontally. Place cut section
at corner and apply BENTOSEAL at overlaps
Figure 3.1 – Concrete form tie details
Figure3.3–ApplyilletofBENTOSEAL to inside corner
Snap-Tie Taper-Tie
Non-shrink grout
Concrete Tile BENTOSEAL exterior face of form tie
Non-shrink grout
VOLTEX
Install VOLTEX around corner
Hydrobar Tube under VOLTEX
VOLTEX
BENTOSEAL
InstallVOLTEXtoitcorner
Install VOLTEX toitcorner
19mm(3/4”)illetofBENTOSEAL
Inside corner of cast-in-place concrete wall
WATERSTOP-RX
PRODUCT MANUAL
- 20 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
Figure3.4–VOLTEXinstalledoncast-in-placebackilledwall,overlapedges100mm(4”)andstaggerverticalendlaps
Backill: The excavated area should be backilled and compactedpromptlyafterVOLTEXisinstalled.UseplacedbackillasaplatforminapplyingsucceedingVOLTEXcourses.Thebackillmustbecompactedtoaminimum85%ModiiedProctordensity.Backillshouldconsistofcompactible soilsorangularaggerate (19 mm (3/4") or less) freeofdebris,sharpobjects,andstonelargerthan19mm(3/4”).Whenback-
illcannotbeplacedimmediatelyprotectmembranefromprecipitationand debris by sealing edges to concrete substrate with CETCO SEAM-
TAPE or tooled bead of CETSEAL. This temporary temination can be left
in place covered by subsequent membrane overlap. Figure3.5–MinimumVOLTEXoverlapdetail;tapeVOLTEXDSseams
Figure3.6–Stepbystepdetailofoutsidewallbasecornerinstallation(hydrostaticcondition)
Trowel BENTOSEAL over grouted form-tie holes
VOLTEX
Hydrobar Tubes placed under VOLTEX at transition at footing
Stagger end seams a minimum 300mm(12”)
Mechanically fasten VOLTEX maximum 600 mm (24”) on center
Install CETCO Seamtape atVOLTEXDSmembraneoverlaps
100mm(4”)overlap
WATERSTOP-RX(min75mm(3”))coverage)
150mm(6”)
Min. 100mm (4”)
Cast-in-place concrete wall
Washer-headmechanicalfastener
VOLTEXDS
CETCO Seamtape
Step 1. Step 2.
Step 3. Step 4.
VOLTEX turned up from underslab
Trowel BENTOSEAL at corner
CutandfoldirstVOLTEX section
Cut and fold second VOLTEX section
Place third VOLTEX piece over the previous two sections
INSTALL VOLTEX OR VOLTEX DS WITH DARK GRAY (WOVEN) GEOTEXTILE SIDE AGAINST THE CONCRETE WALL
Term bar and BENTOSEAL
www.cetco.com
3.3 BACKFILLED WALL PENETRATIONSCutVOLTEXtocloselyitaroundpenetrations.AfterinstallingVOLTEX,trowelaminimum19mm(3/4”)thickilletofBENTOSEAL around the
penetrationtocompletelyillanyspacebetweenthepenetrationandthe VOLTEX edge. The BENTOSEAL should extend onto the penetration
38mm(1–1/2”)andcoverVOLTEX’sedge(Figure3.7).Inareaswheremultiple penetrations are close together, it may be impractical to cut
VOLTEXtoitaroundbaseofeachpenetration.Therefore,applya19mm (3/4”) thick illet of BENTOSEAL around each penetration and
covertheentiresurfacebetweenthepenetrations(Figure3.8).ExtendBENTOSEAL38mm(1–1/2”)ontothepenetrations.
Figure 3.7 – Single penetration cast-in-place wall detail
Figure3.10–InstallVOLTEXbetweenpenetrationswithaccessibility.Trowel BENTOSEAL around penetrations
Figure3.8–CutVOLTEXtoitaroundpenetrations
Figure3.9–Closemultiplepenetrations.TrowelBENTOSEAL around
and between penetrations
VOLTEX
Cast-in-place concrete wall
BENTOSEAL troweled around penetration
Pipe
WATERSTOP-RX (min.75mm(3”)coverage)
VOLTEX Apply BENTOSEAL to cut out area
VOLTEX cut out around multiple penetrations
WATERSTOP-RX
VOLTEX
BENTOSEAL
Pipe
BENTOSEAL
Pipe
VOLTEX
WATERSTOP-RX
WATERSTOP-RX
VOLTEX
BENTOSEAL
Pipe
BENTOSEAL
VOLTEX
BENTOSEAL
Pipe
VOLTEX
WATERSTOP-RX
PRODUCT MANUAL
- 22 -North America: +1 847.851.1800 | +1 800.527.9948 | www.cetco.com
VOLTEX® & VOLTEX® DSBENTONITE GEOTEXTILE WATERPROOFING FOR CAST-IN-PLACE CONCRETE APPLICATIONS
3.4 GRADE TERMINATIONSTerminateVOLTEXmembrane300mm(12”)belowinishedgradeel-evationwithwasher-headfastenersmaximum300mm(12”)oncen-
ter. Install ENVIROSHEET lashing to primed concrete substrate withbottom edge overlapping top edge of VOLTEX membrane minimum
100mm(4”).Overlapallrollendsaminimum100mm(4”)toformacontinuouslashing.Heightoflashingshallbeperprojectdetailsandspeciications.InstallarigidterminationbaralongtopedgeofENVIRO-
SHEET;fastenedmaximum300mm(12”)oncenter.Completegradetermination detail with tooled bead of CETSEAL along the top edge, at
allpenetrationsthroughthelashing,andallexposedoverlapseams.Grade terminations are illustrated in Figures 3.11 and 3.12.
3.5 MASONRY BLOCK WALLSVOLTEX is not recommended for waterprooing masonry block walls.Consult with CETCO regarding recommended products and installation
guidelines for masonry block walls.
4.1 PRECAST CONCRETE CONSTRUCTIONConsult CETCO regarding products and special installation guidelines
for precast concrete plank decks, precast earth covered roofs, and pre-
cast wall construction.
4.2 CONTAMINATED CONDITIONSUseVOLTEXCR(ContaminantResistant)inconditionswheretheground-
water contains high concentrations of chemicals or saline. These condi-
tions are typically encountered at industrial sites and coastal regions. If
groundwater contains strong acids, alkalies, or has a
conductivityof2,500μmhos/cmorgreater (highsaltconcentration),water samples should be submitted to CETCO for compatibility testing.
Forcompatibility testing,provide two (2) litersofsitegroundwater ina clean, unbreakable container. Ship water sample to: CETCO, 2870ForbsAve,HoffmanEstates,IL60192,ATTN:BMGFieldServices.Uponanalysis, CETCO will provide a written report evaluating the water’s
compatibilitywithVOLTEXandrecommendanyspecialproductand/orinstallation requirements
Figure3.11–Terminationatinishedgrade
Figure 3.12 – Termination at grade with brick veneer
SECTION 4
SPECIAL CONDITIONS
IMPORTANT NOTICE
FOR SHOTCRETE, PRECAST CONCRETE, EXPANSION JOINTS AND OTHER APPLICATIONS NOT COVERED IN THIS MANUAL, CONTACT CETCO FOR TECHNICAL ASSISTANCE AND INSTALLATION GUIDELINES.
Brick veneer
Weephole
CETSEAL
Finished grade
ENVIROSHEET grade lashing
VOLTEX
ENVIROSHEET grade lashing
VOLTEX
100mm(4”)min
Finished grade
Tooled bead of CETSEAL
Terminationbarfastened300mm(12”)maximumoncenter
Tooled bead of CETSEAL
Terminationbarfastened300mm(12”)maximumoncenter
www.cetco.com
The information and data contained herein is believed to be accurate and
reliable.Speciicationsandotherinformationcontainedhereinsupersedeallpreviously printed material and are subject to change without notice.
Manufacturer’s warranty of installed system is available. Contact seller for
terms and sample documents including all limitations.
All goods sold by seller are warranted to be free from defects in material and
workmanship.
The foregoing warranty is in lieu of and excludes all other warranties not ex-
pressly set forth herein, whether expressed or implied by operation of law or
otherwise including but not limited to any implied warranties of merchant-
abilityoritness. Seller shall not be liable for incidental or consequential losses, damages or
expenses, directly or indirectly arising from the sale, handling or use of the
goods, or from any other cause relating thereto, and seller’s liability hereun-
derinanycaseisexpresslylimitedtothereplacement(intheformoriginally
shipped)ofgoodsnotcomplyingwiththisagreementoratseller’selection,tothe repayment of, or crediting buyer with, an amount equal to the purchase
price of such goods, whether such claims are for breach of warranty or neg-
ligence.
Any claim by buyer with reference to the goods sold hereunder for any cause
shall be deemed waived by buyer unless submitted to seller in writing within
thirty(30)daysfromthedatebuyerdiscoveredorshouldofdiscovered,anyclaimed breach.
Materials should be inspected and tested by purchaser prior to their use if
productqualityissubjecttoveriicationaftershipment.Performanceguaran-
tees are normally supplied by the applicator.
Note:VOLTEXwaterprooingsystemisnotanexpansionjointmaterial.
LIMITED WARRANTY
PRODUCT TABLE
PRODUCT DESCRIPTION
VOLTEX Bentonitegeotextilewaterprooingmembranewithstandardsodiumbentonite
VOLTEX CR Bentonitegeotextilewaterprooingmembranewithcontaminantresistantsodiumbentonite
VOLTEXDS Bentonitegeotextilewaterprooingmembranewithstandardsodiumbentoniteandapolyethylenelinercomponent
VOLTEXDSCR Bentonitegeotextilewaterprooingmembranewithcontaminantresistantsodiumbentoniteandapolyethylenelinercomponent
IMPORTANT NOTICE
Contact CETCO for veriication of speciication and instal-lation requirements to comply for eligibility of HydroShield Warranty.
www.cetco.com
©2015CETCO.IMPORTANT:Theinformationcontainedhereinsupersedesallpreviousprintedversions,andisbelieved to be accurate and reliable. For the most up-to-date information, please visit www.CETCO.com. CETCO accepts no responsibility for the results obtained through application of this product. CETCO reserves the right to update information without notice.