Voltage distribution (400 kV) – scenario 1
Scenario 1.a (2011): Voltages within limits
Scenario 1.b (2015): Severe voltage drop in
western region Additional measures
necessary, Redispatch actions
Scenario 1.c (2020): Severe voltage drop in
Western and Southern region Additional measures
necessary, 3 Gvar operational equipment
![Page 2: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/2.jpg)
Stationary simulations
2
• Voltages within the transmission grid depend on line utilization
• Severe voltage drops within scenario 2020
• Grid calculation with optimized operation of HVDC lines
• Voltage increase by decraesing the load within the AC-grid
Realer Lastfall 2011 Szenario 2020Szenario 2020 mit HGÜScenario 2020 with HVDC
Vol
tage
in k
V
![Page 3: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/3.jpg)
Line
Util
izat
ion
in %
Scenario 2040
3
![Page 4: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/4.jpg)
4
Overview
European power system
VGB research project
Stationary aspects
Dynamic aspects
Outlook
Conclusions
![Page 5: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/5.jpg)
5
Dynamic simulations
Excitation of the system by a major power imbalance
Simulation of the transient grid dynamics
![Page 6: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/6.jpg)
6
Comparison of transient frequency behavior –scenario 1
Scenario 1.a Scenario 1.b
![Page 7: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/7.jpg)
7
Transient frequency behavior – scenario 1excitation within Germany
![Page 8: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/8.jpg)
8
Transient voltage behavior – Scenario 1excitation of 500 Mvar
Significant impact of increasing intermittent generation on transient voltage behavior
Scenario 1.a
Scenario 1.b
![Page 9: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/9.jpg)
9
Inertial response in future
Increasing frequency drop with decreasing inertia
![Page 10: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/10.jpg)
10
Conclusions
Stationary aspects Transmission limits violated on a few lines Severe voltage drops in different regions due to increasing power flows Additional measures necessary, especially for voltage control HVDC lines contribute to system stability
Transient system dynamics Transient frequency behavior shows no significant changes concerning the
whole system by 2020 (joint-action) Local frequency deviations are increasing Significant impact on transient voltage behavior can be seen Possible impact on synchronous generators of power plants
![Page 11: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/11.jpg)
11
Overview
European power system
VGB research project
Stationary aspects
Dynamic aspects
Outlook
Conclusions
![Page 12: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/12.jpg)
Bottleneck of DPGS-integration
110 kV
20 kV400 V20 kV
Voltage
Allowed voltage range
Peak load, w/o DPGS
Legend
DPGS: Decentralised power generation systems
nom 10%U
transU
nom 10%U
loadU
reserveUload flow
12
Distance to feed-in point
![Page 13: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/13.jpg)
transU
nom 10%U
load genU Uload flow
Bottleneck of DPGS-integration
110 kV
20 kV400 V20 kV
Voltage
Allowed voltage range
Off-peak load, with DPGS
Distance to feed-in point
10%nomU
13
Legend
![Page 14: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/14.jpg)
Bottleneck of DPGS-integration
genloadU U
loadU
~ ~
110 kV
20 kV400 V20 kV
Spannung
nom 10%U
transU
10%nomU
Allowed voltage range
Peak load, w/o DPGS
Off-peak load, with DPGS
Legend
load flow
load flow
14
Distance to feed-in point
![Page 15: Voltage distribution (400 kV) scenario 1€¦ · Voltage distribution (400 kV) –scenario 1 Scenario 1.a (2011): Voltages within limits Scenario 1.b (2015): Severe voltage drop in](https://reader034.fdocuments.us/reader034/viewer/2022043009/5f39ea931b805f03777f2e7d/html5/thumbnails/15.jpg)
Dipl.-Ing. Florian GutekunstPhone: +49 711 / 685 65580
University of StuttgartInstitute of Combustion and Power Plant TechnologyDepartment Power Generation and Automatic ControlPfaffenwaldring 23 70569 StuttgartGermany