Volt Reg Apps10

download Volt Reg Apps10

of 53

Transcript of Volt Reg Apps10

  • 7/29/2019 Volt Reg Apps10

    1/53

    This document is the exclusive property of Alstom Grid and shall not betransmitted by any means, copied, reproduced or modified without the prior

    written consent of Alstom Grid Technical Institute. All rights reserved.

    GRID

    Technical Institute

    On/Under Load Tap ChangingTransformer

    Voltage Regulating Control

  • 7/29/2019 Volt Reg Apps10

    2/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control2

    Contents

    On Load Tap Changing Transformers

    Voltage Regulation

    Time Delays

    Grading Between Voltage Levels

    Line Drop Compensation

    Parallel Operation

    Distributed Generation

    Supplementary Control Functions

  • 7/29/2019 Volt Reg Apps10

    3/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control3

    Voltage RegulationPurpose

    Electrical plant is designed to operate within finite

    voltage limits

    To control the system voltage transformers with tap

    changers are commonly usedOff Load manually changed

    On Load automatically adjusted

    Tap changers physically alter the transformer ratio and

    hence the voltage

    Automatic voltage regulating relay is used to control the

    tap changer

  • 7/29/2019 Volt Reg Apps10

    4/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control4

    Voltage RegulationPerformance Criteria

    Two Mutually Exclusive Parameters

    voltage quality

    number of tap changes

    Voltage Quality

    customer focused quality measurement

    percentage of time outside deadband or statuary limits

    length of voltage disturbance

    Number of Tap Changes

    supplier focused quality measurement

    directly relates to cost of ownership of the tap changer

  • 7/29/2019 Volt Reg Apps10

    5/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control5

    On Load Tap Changing Transformers

  • 7/29/2019 Volt Reg Apps10

    6/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control6

    On Load Tap Changing TransformersTypical Supply Network

  • 7/29/2019 Volt Reg Apps10

    7/53On/Under Load Tap Changing Transformer Voltage Regulating Control7

    On Load Tap Changing TransformersTap-Outs and Windings

    Tap-outs are normally on the HV winding

    Tap-outs can be at the Line End or Neutral End

    Causes variations in the impedance of the transformer

    Transformer impedance calculated at the centre tap position

  • 7/29/2019 Volt Reg Apps10

    8/53On/Under Load Tap Changing Transformer Voltage Regulating Control8

    On Load Tap Changing TransformersDevelopment of the Tap Changer

    Developed in the late 1920s

    Two primary considerations

    The load current must not be interrupted

    No windings should be short-circuited during transitions

    Early tap changers were reactors, could be continuously

    rated useful when mechanisms were unreliable

    Resistor transition tap changers now used, reliable

    stored energy drive mechanisms

    Typical Operation ~75ms

  • 7/29/2019 Volt Reg Apps10

    9/53On/Under Load Tap Changing Transformer Voltage Regulating Control9

    On Load Tap Changing TransformersDouble Resistor Flag Sequence

    1

    2

    3

    4

    5

    6

    7

    8+

    R R

    Selector Compartment

    No load switching takes place here.

    'In Tank' double compartment tapchangers, have selectors immersed

    in the main transformer tank.

    'External' double compartment tap

    changers, have selectors external to

    the main transformer tank andseparate from diverters, but can

    share oil with the main transformer

    tank.

    Diverter Compartment

    Oil contamination takes place here.Oil kept separate from selectors

    and main transformer tank.

    All load switching takes place here.

    Double Compartment Tap Changer Single Compartment Tap Changer

    Oil is shared between selectors and

    diverters.

    Oil is not shared between the

    single compartment and the maintransformer tank.

    The diverter may be a vacuum

    switch to prevent oil contamination.

    Double compartment tap changersare usually found on large

    distribution and transmissiontransformers.

    Single compartment tap changers

    are usually found on distribution

    transformers.

    All switching takes place in the same

    compartment.

  • 7/29/2019 Volt Reg Apps10

    10/53On/Under Load Tap Changing Transformer Voltage Regulating Control10

    Voltage Regulation

  • 7/29/2019 Volt Reg Apps10

    11/53On/Under Load Tap Changing Transformer Voltage Regulating Control11

    Voltage RegulationBasic Operation

    Controller monitors secondary voltage

    voltage setting - nominal voltage level

    voltage deadband - permissible range

    Initial Time delay used to filtertransient voltage fluctuations

    definite time

    inversely proportional to the

    deviation from the voltage

    setting

  • 7/29/2019 Volt Reg Apps10

    12/53On/Under Load Tap Changing Transformer Voltage Regulating Control12

    Control a voltage

    regulating

    transformer (on-load

    tap changer)

    Maintain system

    voltage within set

    limits

    Issue tap up/down

    commands

    Time

    Voltage

    Vs

    + dVs

    - dVs

    Basic Regulating Requirements

  • 7/29/2019 Volt Reg Apps10

    13/53On/Under Load Tap Changing Transformer Voltage Regulating Control13

    Voltage RegulationExample Operation

    + Voltage

    Deadband

    - Voltage

    Deadband

    Voltage

    Setting

    Time Delay

    t

    V

    Voltage out

    of deadband

    Voltage restored

    to within deadband

  • 7/29/2019 Volt Reg Apps10

    14/53On/Under Load Tap Changing Transformer Voltage Regulating Control14

    Voltage RegulationAlgorithms

    There are different voltage regulation algorithms

    Basic On/Off Controller

    Simple time delayed with immediate reset

    Hysteresis on the Voltage Limits

    Using different pick-up and drop-off quantities

    Proportional Resetting Initial Delay Timers

    The timer resets proportionally

    Complex

    Standard deviation measures

    Performance criteria functions

  • 7/29/2019 Volt Reg Apps10

    15/53On/Under Load Tap Changing Transformer Voltage Regulating Control15

    Time Delays

  • 7/29/2019 Volt Reg Apps10

    16/53On/Under Load Tap Changing Transformer Voltage Regulating Control16

    DeadbandVoltageV

  • 7/29/2019 Volt Reg Apps10

    17/53On/Under Load Tap Changing Transformer Voltage Regulating Control17

    Initial DelayInter-tap Delay

    Time

    Tap pulse duration - 0 to 5s (MVGC fixed at 1s)

    Multiple Tap Change SequenceInter-Tap Delay - Definite Time

    VoltageDeviation

    Vs

    dVs

    The timer is reset after each operation to invoke initial timer

  • 7/29/2019 Volt Reg Apps10

    18/53On/Under Load Tap Changing Transformer Voltage Regulating Control18

    VoltageDeviation

    Vs

    dVs

    Initial Delay (Inverse Time)

    Multiple Tap Change SequenceInter-Tap Delay - Inverse Time

    Time

    The timer is reset after each operation to invoke initial timer

  • 7/29/2019 Volt Reg Apps10

    19/53On/Under Load Tap Changing Transformer Voltage Regulating Control19

    Initial Time DelaysTypical Setting Ranges

    Initial Time Delay Setting Ranges

    0 to 300s

    Inter-tap Delay Setting Ranges

    0 to 120s (typically 5 10s)

    Initial Time Delays also ensure time grading between

    voltage levels

  • 7/29/2019 Volt Reg Apps10

    20/53On/Under Load Tap Changing Transformer Voltage Regulating Control20

    Grading Between Voltage Levels

  • 7/29/2019 Volt Reg Apps10

    21/53On/Under Load Tap Changing Transformer Voltage Regulating Control21

    Grading Between Voltage LevelsCauses of Voltage Deviations

    Grid Supply

    Load

    Load

    A

    CB

    Line

    T3T2

    T1

    Load

    Voltage deviations occur for three reasons

    Change in downstream load

    Change in upstream supply voltage

    Embedded generation

    di l l

  • 7/29/2019 Volt Reg Apps10

    22/53On/Under Load Tap Changing Transformer Voltage Regulating Control22

    Grading Between Voltage LevelsTime Grading

    Grid Supply

    Load

    Load

    A

    C

    BT3

    T2

    T1

    Load

    Discrimination to allow higher voltage to operate first

    T1 time delay < T2 time delay < T3 time delay (initial)

    Otherwise hunting can occur between voltage levels

    Can be compromised by embedded/distributed generation

  • 7/29/2019 Volt Reg Apps10

    23/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control23

    Line Drop Compensation

    Li D C ti

  • 7/29/2019 Volt Reg Apps10

    24/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control24

    Line Drop CompensationRegulating the Voltage at a Remote Point

    Tap Changer

    Time Delay

    VoltageDeadband

    Voltage SettingAVC Relay

    Supply

    Load

    VT

    CT

    +-

    Bus

    X R

    Feeder

    Voltage Drop

    Line Drop Compensation

    )(FEEDERFEEDERLOADSLOAD

    jXRIVV

    )( AVCAVCAVCSBUS jXRIVV

    Simulates voltage drop of the line

    Artificially boosts transformer voltage at times of high loading

    Li D C ti

  • 7/29/2019 Volt Reg Apps10

    25/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control25

    Line Drop CompensationRelay Implementation

    Vr Vxl

    Remote

    Voltage

    VREM

    Load

    IL

    Bus Voltage VBUS = VREM + Vr + Vxl

    Calculate the Voltage Drop at nominal load

    Bus

    Voltage

    VB

    Li D C ti

  • 7/29/2019 Volt Reg Apps10

    26/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control26

    Line Drop CompensationPhasor Diagram

    IL

    VBUS

    -ILX

    -ILR

    VREM Voltage Setting

    The relay calculates and

    regulates the VREM magnitude

    ILX required for power factor

    The measured

    bus voltage

  • 7/29/2019 Volt Reg Apps10

    27/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control28

    Parallel Operation

    P ll l O ti

  • 7/29/2019 Volt Reg Apps10

    28/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control29

    Parallel OperationTransformer Operating in Parallel

    Transformers in parallel can cause Circulating Currents

    Circulating Current affects LDC causing tap changer

    runaway

    Circulating Current are damaging to Transformer

    Therefore special control techniques are required

    Paralleling using Master-Follower Control

    Paralleling using Circulating Current Control

    Paralleling using Negative Reactance Control

    P ll l O ti

  • 7/29/2019 Volt Reg Apps10

    29/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control30

    Parallel OperationMaster - Follower

    One controller designated the master

    All other controllers (followers) follow the master

    Requires that

    Identical transformers / tap changers

    Locality of equipment

    Security of communications is critical

    Circulating current should be monitored

    Parallel Operation

  • 7/29/2019 Volt Reg Apps10

    30/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control31

    Parallel OperationCirculating Currents due to Tap Disparity

    2IL

    T1

    T2

    Ic

    IL-Ic

    IL+Ic

    If T1 is on a higher

    tap than T2

    Current seen by

    #1 is IL + IC

    Current seen by

    #2 is IL - IC

    #2

    #1

    Parallel Operation

  • 7/29/2019 Volt Reg Apps10

    31/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control32

    Parallel OperationCirculating Current Effect on LDC

    2IL

    T1

    T2

    Ic

    Vxl Vr

    IL-Ic

    IL+Ic

    IC is measured in LDC circuit but

    is not present in the feeder

    #2

    #1

    Parallel Operation

  • 7/29/2019 Volt Reg Apps10

    32/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control33

    Parallel OperationLDC on T1

    IL

    VBUS

    -ILX

    -ILR

    VREM

    ICIL + IC (Volts High)

    VREG

    -IcR

    -IcX

    The regulated voltage VREG

    contains a -VC component

    VREG will be regulated up to VREM,

    therefore increasing the over

    voltage even further

    Voltage Setting

    The regulatedvoltage

    The measured

    bus voltage

    Parallel Operation

  • 7/29/2019 Volt Reg Apps10

    33/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control34

    Parallel OperationLDC on T2

    IL

    VBUS

    -ILX

    -ILR

    VREM

    IC

    IL - IC (Volts

    Low)

    VREG

    -ICR

    -ICX

    The regulated voltage VREG

    contains a +VC component

    VREG will be regulated down to VREM,

    therefore reducing the under

    voltage even further

    The measured

    bus voltage

    Voltage Setting

    The regulated

    voltage

    Parallel Operation

  • 7/29/2019 Volt Reg Apps10

    34/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control35

    Parallel OperationCirculating Current Control

    Pilot Method (when tap changers are matched)

    Extract the circulating current

    Apply to a compensation circuit, derive a proportional

    voltage magnitude

    Feed this derived VC back into the measuring circuit to

    compensate for the circulating current effect

    Circulating Current Control

  • 7/29/2019 Volt Reg Apps10

    35/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control36

    Circulating Current ControlPilot Method

    T1

    T2

    VC

    VC

    T1>T2

    Ic

    jXt

    jXt

    IL+IC

    IL-IC

    IC

    -IC

    IL

    IL

    V1C = ICXt

    V2C = -ICXt

    2IL

    Circulating Current Control

  • 7/29/2019 Volt Reg Apps10

    36/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control37

    Circulating Current ControlCirculating Current Compensation on T1

    IL

    VBUS

    -ILX

    -ILR

    VREM

    ICIL + IC (Volts High)

    VREG

    Voltage Setting

    VC

    The voltage VREG is compensated

    by VC

    VREG will be regulated correctly

    reducing the over voltage

    The measured

    bus voltage

    The regulated

    voltage

    -IcR

    -IcX

    VREG

    Circulating Current Control

  • 7/29/2019 Volt Reg Apps10

    37/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control38

    Circulating Current ControlCirculating Current Compensation on T2

    The voltage VREM is compensated

    by VC

    VREG will be regulated correctly

    increasing the under voltage

    IL

    VBUS

    -ILX

    -ILR

    IC

    IL - IC (Volts

    Low)

    VREGVoltage Setting

    VC

    VREM

    The measured

    bus voltage

    The regulated

    voltage

    VREG

    -ICX

    -ICR

    Alternative Connections for

  • 7/29/2019 Volt Reg Apps10

    38/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control39

    Ic

    IL+Ic IL-Ic

    Ic

    IL IL

    IcRs Rs

    IL

    +Ic -Ic

    2IL

    Requires the use of swamping resistors (Rs)

    Alternative Connections forLDC Circuits (Parallel)

    Alternative Connections for

  • 7/29/2019 Volt Reg Apps10

    39/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control40

    Ic

    IL+Ic

    IL-Ic2IL 2IL

    IL

    +Ic -Ic

    IL+Ic IL+Ic

    ICTICT

    2IL

    Requires the possible use of interposing CTs (ICTs)

    Alternative Connections forLDC Circuits (Series)

    Parallel Operation

  • 7/29/2019 Volt Reg Apps10

    40/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control41

    Parallel OperationNegative Reactance Control

    Reverse Reactance Control (non matched tap changers

    or different sources)

    Utilises the reactance compensation of the Line Drop

    Compensation circuit

    Reverses reactance and feeds back into compensation

    circuit

    Lack of specific feeder reactance in LDC results in

    susceptibility to power factor

    Negative Reactance Control

  • 7/29/2019 Volt Reg Apps10

    41/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control42

    Negative Reactance ControlCompensation on T1

    IL

    VBUS

    VREM

    ICIL + IC (Volts High)

    VREG

    Voltage Setting

    ILXt

    -ILR-ICRICXt

    The measured

    bus voltage

    The regulated

    voltage

    VREM

    VREG

    -ILX

    -ILR-IcR

    -IcX

    The reactance of LDC is reversed

    VREG will be regulated correctly

    reducing the over voltage

    Negative Reactance Control

  • 7/29/2019 Volt Reg Apps10

    42/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control43

    Negative Reactance ControlCompensation on T2

    IL

    VBUS

    -ILX

    -ILR

    VREM

    IC

    VREG

    -ICR

    -ICX

    Voltage Setting

    ILXt

    -ILR-ICR

    ICXt

    The reactance of LDC is reversed

    VREG will be regulated correctly

    increasing the under voltageIL - IC (Volts

    Low)

    The measured

    bus voltage

    The regulatedvoltage

    VREM

    VREG

    Negative Reactance Control

  • 7/29/2019 Volt Reg Apps10

    43/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control44

    Negative Reactance ControlUnity Power Factor

    IL

    Error

    VBUSVREG

    ILXt

    VX = ILXt

    VR = 0

    Small error present at

    unity power factor

    Negative Reactance Control

  • 7/29/2019 Volt Reg Apps10

    44/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control45

    Negative Reactance ControlNon - Unity Power Factor

    IL

    VBUSVREG

    ILXt

    VX = ILXt

    VR = IL(Xt.tan) Error enlarges with a lower

    power factor, unless R is

    specified

    ILXt.tan

    Negative Reactance Control

  • 7/29/2019 Volt Reg Apps10

    45/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control46

    Negative Reactance ControlLDC and Low Power Factor

    ZA2390

    IL

    VBUS

    ILXt

    -ILR

    VREM

    -ILX

    -ILR

    VREG

    IL(Xt+X).tan

    Error

    VX = ILXt

    VR = -ILR + IL(X+Xt).tan Addition of LDC results in

    greater error

    Negative Reactance Control

  • 7/29/2019 Volt Reg Apps10

    46/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control47

    Negative Reactance ControlLDC and Low Power Factor Correction

    IL

    VBUS

    ILXt

    -ILR

    VREM

    -ILX

    -ILR

    VREG

    IL(Xt+X).tan

    VX = ILXt

    VR = -ILRcos - IL(Xt+X).sin Corrects for low power

    factor

    VR

    ILR

    IL(Xt+X).tanVR

    (IL(Xt+X).tan).cos = IL(X+Xt).sin

    VREG

  • 7/29/2019 Volt Reg Apps10

    47/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control48

    Distributed Generation

    Distributed Generation

  • 7/29/2019 Volt Reg Apps10

    48/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control49

    Distributed Generationand LDC circuits

    Distributed generation can cause reverse power flow

    through transformer bus Effects LDC circuit and hence voltage regulation

    Bus

    Voltage

    VB

    Load A

    Load B

    Load C

    G

    When:

    G < Load A no significant problem (if design practice followed)

    G > Load A potential for low voltage levels due to reduced observed load

    G > Load A, B and C LDC scheme will not operate correctly due to reverse power

    Distributed Generation

  • 7/29/2019 Volt Reg Apps10

    49/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control50

    Distributed Generationand Cancellation CT

    Cancellation CT can be used to maintain direction load

    seen by control relayMaintains voltage during high load periods

    VB Load A

    Load B

    Load C

    G

    Now When:

    G < Load A no significant problem (if design practice followed)

    G > Load A IG summed into IB therefore control relay sees all load current

    G > Load A, B and C LDC scheme will not operate correctly due to reverse power

    IB

    IG

    Distributed Generation

  • 7/29/2019 Volt Reg Apps10

    50/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control51

    Distributed Generationand Negative Reactance Schemes

    Distributed generation can cause a change in power factor

    This will effect Negative/Reverse Reactance paralleling

    schemes which require a constant and specified power

    factor

    Circulating current minimisation schemes are preferential

  • 7/29/2019 Volt Reg Apps10

    51/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control52

    Supplementary Control Functions

    Supplementary Control Functions

  • 7/29/2019 Volt Reg Apps10

    52/53

    On/Under Load Tap Changing Transformer Voltage Regulating Control53

    pp y

    Load Shedding

    voltage setting override ( 10%) Over Current / Under Voltage Supervision

    inhibit control during fault conditions

    Excessive Circulating Current

    protects against parallel control failure

    Under Current Inhibit

    stops operations when low forward or reverse power

    Reverse Current Operation

    Auto/Manual/Remote Operations

    Measurements

    Supplementary Control Functions

  • 7/29/2019 Volt Reg Apps10

    53/53

    pp yTap Changer Supervision

    Tap Changer Monitoring

    tap changer confirmation response (time limited)

    voltage monitoring

    voltage change occurs

    in the correct direction

    of sufficient magnitude

    operations with no initiating signal

    Tap Change Operations Counter

    alarms at settable threshold

    frequency alarms

    excessive operations per time period

    (day / month / maintenance period)