    LaserCOMPACT

    PRODUCT GUIDE

    VLC-500 (Relays Only) Model

    VLC-505 (VESDAnet) Model

    March 2000

    Version 1.0

  • 8/12/2019 VLC Product Manual

    2/31

    Publication historyRelease 1.0 February 2000

    Copyright Information2000 Vision Systems VESDA. All Rights Reserved. VESDA is a registered trademark of Vision

    Products Pty Ltd. VESDA LaserPLUS, LaserSCANNER, LaserCOMPACT, AutoLearn, InfoWORKS,ASPIRE, VSM, VESDAnet and VESDAlink are trademarks of Vision Products Pty Ltd.

    DisclaimerIn accordance with its policy of continuing product and system improvement, Vision Products reserves theright to change designs or specifications without obligation and without further notice.

    Codes and Standards InformationVision Products strongly recommends that this guide is read in conjunction with the appropriate local codesand standards for smoke detection systems and electrical connections. This guide contains genericinformation and some Sections may not comply fully with all local codes and standards. In these cases, thelocal codes and standards must take precedence.

    FCC Compliance Statement

    This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant topart 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmfulinterference in a residential installation. This equipment generates, uses and can radiate radio frequencyenergy and, if not installed and used in accordance with the instruction, may cause harmful interference toradio communications. However, there is no guarantee that interference will not occur in a particularinstallation. If this equipment does cause harmful interference to radio or television reception, the user isencouraged to try and correct the interference by one or more of the following measures:

    Reorientate or relocate the receiving antenna

    Increase the separation between the equipment and receiver

    Connect the equipment to a power outlet which is on a different power circuit from which the receiver isconnected

    Consult the dealer or an experienced radio/television technician for help

    FM 3611 Hazardous Approval WarningExposure of some chemicals may degrade the sealing of relays used on the detector. Relays used on thedetector are marked "TX2-5V" or "G6S-2-5V" or "EC2-5NU".

    UL WarningThe fire alarm threshold (signal) that initiates an evacuation procedure via the Fire Alarm Panel must not beset higher than 0.625%/ft. The COMPACT unit can send this signal either via the Fire Alarm Panel Outputsignal or the Pre-alarm output signal.

    Approvals and StandardsThe product complies with the following standards.AS 1603.8 FCC Class BAS/NZS 3548 AS2211EN50081-1 21 CFR 1010.2EN50130-4 21 CFR 1010.3

    EN 60950

    Safety LabelThe LaserCOMPACT incorporates a Laser device and is classified as a Class 1 Laser product whichcomplies with FDA Regulations 21 CFR 1040.10 and 1040.11. The laser is housed in a sealed Detectorchamber and contains no serviceable parts. This laser emits invisible light and can be hazardous if viewedwith the naked eye. Under no circumstances should this chamber be opened.There is a safety labelonthe chamber as shown below.

    Figure 1 The Laser Warning Label

  • 8/12/2019 VLC Product Manual

    3/31

    Contents

    1. Overview.................................................................................................................... 2

    2. Product Description.................................................................................................. 32.1 Front View of LaserCOMPACT.................................................................................... 32.2 Product Model, Approvals and Standards Label .......................................................... 32.3 Operation.................................................................................................................... 4

    2.3.1 LED and Reset/Isolate Push Button Switch Functions.......................................... 42.4 Factory Default Settings.............................................................................................. 5

    2.4.1 Factory Default User Levels................................................................................. 52.4.2 Factory Default PIN Numbers.............................................................................. 5

    2.5 LaserCOMPACT Detector Models............................................................................... 52.5.1 Relays Only (RO) Model (Part No. VLC 500) ....................................................... 52.5.2 VESDAnet (VN) Model (Part No. VLC 505)......................................................... 5

    2.6 Detector Mounting....................................................................................................... 62.7 Relay Outputs ............................................................................................................. 6

    2.8 Auxiliary Terminals......................................................................................................72.9 Cable Entry Ports........................................................................................................ 72.10 Event Log.................................................................................................................... 7

    3. Assembly Description............................................................................................... 83.1 Assembly Description.................................................................................................. 83.2 Front Cover and LEDs............................................................................................... 113.3 Termination Card ...................................................................................................... 113.4 Cable Entry Ports...................................................................................................... 113.5 Air Inlet Port .............................................................................................................. 113.6 Air Filter Cartridge..................................................................................................... 113.7 Aspirator.................................................................................................................... 133.8 Air Exhaust Port ........................................................................................................ 133.9 Laser Detection Chamber.......................................................................................... 13

    3.10 Processor Card ......................................................................................................... 134. Termination Card Details........................................................................................ 14

    4.1 Wire Terminal Location for RO Model ....................................................................... 144.2 Wire Terminal Location for VN Model........................................................................ 144.3 Power Terminals ....................................................................................................... 154.4 VESDAnet Terminals (VN Model only) ...................................................................... 154.5 Relay Terminals ........................................................................................................ 164.6 Programming Socket................................................................................................. 184.7 Auxiliary Terminals.................................................................................................... 18

    4.7.1 Bias Terminals................................................................................................... 184.7.2 Reset Terminals (General Purpose Input) .......................................................... 194.7.3 Remote LED Terminals ..................................................................................... 19

    5. Specifications.......................................................................................................... 206. Factory Default Settings......................................................................................... 217. Alarm Threshold Settings....................................................................................... 228. Physical Dimensions .............................................................................................. 239. Parts Replacement .................................................................................................. 25

    9.1 Opening the Detector ................................................................................................ 269.2 Closing the Detector.................................................................................................. 269.3 Replacing the Air Filter Cartridge............................................................................... 269.4 Replacing the Aspirator ............................................................................................. 27

  • 8/12/2019 VLC Product Manual

    4/31

    LaserCOMPACT Product Guide

    1. Overview

    The LaserCOMPACT is an aspirating smoke detector that provides all the benefits of aspiratingsmoke detection, including very early warning, for small areas. The LaserCOMPACT has beendesigned to protect areas up to 500sq.m (5,000sq.ft).

    The detector operates by drawing air from a protected area via a pipe network. A sample ofthe air is filtered to remove dust and dirt before it is passed through the laser detectionchamber. Smoke present in the detection chamber creates light scattering, which viasophisticated electronics produces a signal representing the absolute level of smoke present.

    The LaserCOMPACT can be programmed to have 2 or 3 alarm thresholds, which can be setacross its wide sensitivity range to provide both very early warning of a potential fire situationand allow the initiation of further control procedures should the smoke level increase.

    All pipe network designs for the LaserCOMPACT should be supported by the ASPIRE PipeModelling program results.

    VESDA products are only distributed through trained and accredited channels.

    It is understood that personnel installing this equipment are familiar with the VESDA technologyand have a good understanding of local codes and standards regarding electrical cabling.Installation engineers should be certified where appropriate.

    For details of your nearest Accredited Distributors please contact Vision Systems VESDA.Contact details are at the back of this document.

  • 8/12/2019 VLC Product Manual

    5/31

    LaserCOMPACT Product Guide

    2. Product Description

    2.1 Front View of LaserCOMPACT

    Figure 1 Front View of LaserCOMPACT Model

    2.2 Product Model, Approvals and Standards Label

    A label similar to that shown in Figure 2 is located at the bottom of the LaserCOMPACTenclosure and displays the detector model, approvals and standards.

    Figure 2 Label Details

  • 8/12/2019 VLC Product Manual

    6/31

    LaserCOMPACT Product Guide

    2.3 Operation

    2.3.1 LED and Reset/Isolate Push Button Switch Functions

    Refer to Figure 5 for the location of the LED indicators. The functions of the LED indicators onthe front panel from top to bottom and the push button Reset/Isolate switch are:-

    Fire This RED LEDlights up when the Fire alarm threshold is initiated.

    Pre-Alarm This RED LEDlights up when the Pre-Alarm threshold is initiated.

    This LED flashes when the Alert alarm threshold is initiated and*Alert Overlay in ON.

    *The option to have an Alert warning is set in the programming asAlert Overlay. When this condition is ON the LED will flash and thefault relay changes states in an Alert condition.

    Fault This YELLOW LED lights when a fault condition occurs.It is also lit during airflow normalisation.

    OK This Green LEDstays lit during normal operation; showing the unit ishealthy.

    This LED flashes twice repeatedly during air flow normalisationand/or three times repeatedly during AutoLearn.

    Reset/Isolate This Yellow LEDis lit when the unit is Isolated. During this condition

    the Pre-Alarm and/or Fire relay is de-energised (unlatched) if therelays have previously been energised (latched).

    (The default setting for the Fault relay is the energised (latched) stateunless altered during programming).

    Reset/IsolatePush ButtonSwitch

    To Reset the unit, press this switch once.To Isolate the unit, press and hold the switch for 2 seconds.To De-isolate the unit, press and hold the switch again for 2 seconds.While the detector is Isolated, any faults may be cleared by pressingthis switch once.

    If a remote Reset switch has been fitted to the Reset terminals and isset to the Isolate position

    ORIf the Reset/Isolate button has been locked out in the programming,this switchwill not operate. Refer to Section 2.8 and 4.7.

  • 8/12/2019 VLC Product Manual

    7/31

    LaserCOMPACT Product Guide

    2.4 Factory Default Settings

    The LaserCOMPACT is shipped from the factory with the default settings as per the table inSection 6.0. Only authorised personnel at the Administrative (ADM) or Distributor (DST) levelmay alter these values.

    2.4.1 Factory Default User Access Levels

    The factory set default access levels are 1 User (USR), 1 Administrator (ADM) and 1 Distributor(DST). Each level requires a four-digit PIN number to be entered before gaining access to thedetector. The user may add, alter, delete or modify user names and PINs after having gainedaccess into the system. Up to 10 Users and 4 Administrators may be added.

    2.4.2 Factory Default PIN Numbers

    The factory default Personal Identification Numbers (PIN) are distributed to authorisedpersonnel attending accredited VESDA training courses and may be altered after gainingaccess into the system.

    2.5 LaserCOMPACT Detector Models

    The LaserCOMPACT comes in two models and are as follows:-

    2.5.1 Relays Only (RO) Model (Part No. VLC 500)

    This model is used as a single stand-alone smoke detector and is not connected intoVESDAnet. The model is identified by the part number (VLC-500) which is located on a label

    at the bottom of the enclosure (See Figure 2)

    Programming this detector is by connecting a PC with a RS232 communication cable to the 9pin programming socket on the termination card located inside the detector. Run the VConfigPro or VConfig Basic program from the PC to program.

    2.5.2 VESDAnet (VN) Model (Part No. VLC 505)

    This model is used when the detector is to be connected into VESDAnet. The model isidentified by the part number (VLC-505) which is located on a label at the bottom of theenclosure (See Figure 2)

    Communication to this detector is performed by one of the following methods:-

    Connect a LCD Programmer to the 15 pin programming socket on the termination card

    OR

    Connect a PC to the 15 pin programming socket via a PC-Link HLI device and running theVConfig Pro of VConfig Basic program from the PC

    OR To a VESDAnetsocketfrom a remote Programmer or PC.

    This detector can be used as a stand-alone device and not connected into VESDAnet. In thisconfiguration, the VESDAnet terminals must be linked. Refer to Section 4.4.

  • 8/12/2019 VLC Product Manual

    8/31

    LaserCOMPACT Product Guide

    2.6 Detector Mounting

    The LaserCOMPACT comes with a separate metal mounting bracket that is attached onto the

    mounting location. The detector can only be mounted with the supplied mounting bracket. Theback of the detector is slotted over the four tabs on the mounting bracket and is locked in placewith an anti-tamper screw located inside the enclosure. Refer to Figure 3 for mounting andFigure 6 for the anti tamper screw location.

    Figure 3 Mounting the Detector onto the Mounting Bracket

    2.7 Relay Outputs

    There are three relays (Fire, Pre-Alarmand Fault) for interfacing to external devices or to theFire Alarm Panel. The relays are programmable to the energised (latched) or de-energised(non-latched) states via a PC or LCD Programmer. Refer to the table below for the conditionsfor these relays to change states.

    Note:The Fault relay is set to the energised (latched) state on power up and is de-energised(unlatched) when a fault or Alert condition is present. Connection is made between theNO and C terminals when the relay is energised.

    RELAY CONDITIONS FOR RELAYS TO CHANGE STATES

    Fire Fire alarm smoke threshold level is initiated. (Relay is energised)

    Pre-Alarm Pre-Alarm smoke threshold level is initiated. (Relay is energised)

    Fault Fault found on detector or on VESDAnet loop.Air flow Normalisation is initiated.System Isolation is initiated.(Relay is de-energised for all three conditions above)

    When the Overlay Alertfunction has been selected and when theAlertsmoke threshold level has been initiated or when a fault ispresent. (Relay is de-energised)

    Note: The above relay states are not applicable when the relay states are reprogrammed bythe user.

    Back of the box

    Mounting bracket

    Bracket tab X 4

    Rectangular Slots X 4

  • 8/12/2019 VLC Product Manual

    9/31

    LaserCOMPACT Product Guide

    2.8 Auxiliary Terminals

    The auxiliary terminals on the termination card are Bias, Resetand LED. Refer to Section 4.7

    for wire connection details. These terminals have the following functions:-

    Bias terminals These output terminals provide 10VDC supply to power the Reset inputterminals via a remote ON/OFF switch.

    LED terminals These output terminals provide a 5V, 15mA DC supply via a 220 ohm resistorto drive an LED located in another part of the building.

    Reset terminals These terminals are also known as the General Purpose Input (GPI) and is(GPI Input) used for one of these three functions; Reset, Mains OK or Standby. The

    Reset terminals can be programmed to one of the functions if required andrequires 5V to 33VDC to operate. Any input into this terminal overrides theReset switch on the front panel. These functions operate as follows:-

    Reset/Isolate

    The detector Isolates when 5 VDC is applied to this terminal andReset when the voltage drops 2 VDC.

    MainsOK

    The detector monitors the state of the external power supply andresponds to the following conditions.

    Mains OK 5 VDC is at this terminal

    Mains Fail 2 VDC is at this terminal

    Standby The detector Isolates and the aspirator turns OFF when 5 VDC is atthis terminal.

    Note:The input states are not defined for any voltages > 2 to < 5 VDC.

    2.9 Cable Entry Ports

    There are four 25 mm (1in) cable entry ports on the top right hand side of the detector. Anyof the ports can be used to run the cables into the detector. Refer to Figure 4, 6 and Section 3.4for more details.

    2.10 Event Log

    The detector stores and logs up to a maximum of 12,000 events on a first in first out basis. By

    regulation, detectors are normally required to be powered from a battery backed DC powersupply. This ensures that the log is held indefinitely. If it is required to totally remove the DCpower source and it is considered the log may hold useful then the user should download thelog into a PC using VConfig Pro software program before disconnecting the DC power.

  • 8/12/2019 VLC Product Manual

    10/31

    LaserCOMPACT Product Guide

    3. Assembly Description

    3.1 Assembly DescriptionThe components of the LaserCOMPACT are housed inside a grey plastic enclosure with adecal fascia on the front cover and a metal back panel. The front cover is removable and issecured to the enclosure with two screws located on the left and right hand side of the cover.The plastic tie attaches the cover to the enclosure, is removable and is used to prevent strainon the cable loom. The detector contains two parts:-

    a) The Front Cover

    The front cover (Refer to Figure 5 and Section 3.2) houses the following components:-

    5 LEDs to indicate Fire, Pre-Alarm, Fault, OK and Reset/Isolate states

    Reset/Isolate Push Button Switch

    b) The Main Enclosure

    The main enclosure (Refer to Figure 4 and 6) houses the following components:-

    Termination Card (Refer to Section 3.3)

    Cable Entry Ports (Refer to Section 3.4)

    Air Inlet Port (Refer to Section 3.5)

    Air Filter Cartridge(Refer to Section 3.6)

    Aspirator (Refer to Section 3.7) Air Exhaust Port (Refer to Section 3.8)

    Laser Detection Chamber (Rear of enclosure, refer to Section 3.9)

    Central Processing Card (Rear of enclosure, refer to Section 3.10)

    Figure 4 View of LaserCOMPACT with Front Cover and Enclosure joined

    Air Inlet Port Cable Entry Ports(One port on rear)

    LEDIndicators

    Main Enclosure

    Front Cover

    DecalFascia

    Air Exhaust Port(Bottom of Enclosure)

    Screws

  • 8/12/2019 VLC Product Manual

    11/31

    LaserCOMPACT Product Guide

    Figure 5 Front View of LaserCOMPACT

    Anti Tamper Screw

    TerminationCard

    Programming Socket15 pin for VNmodel9 pin for ROmodel

    Air FilterCartridge

    Air Inlet Port Cable Entry Ports

    Aspirator

    Fuse 1.5A

    Air Exhaust PortFilter Screw

    Wire TerminalStrips

    VESDAnetnumber

    Reset/IsolatePush ButtonSwitch

    LED Indicators

  • 8/12/2019 VLC Product Manual

    12/31

    LaserCOMPACT Product Guide

    Figure 6 Location of Components in the Main Enclosure (Front Cover Removed)

  • 8/12/2019 VLC Product Manual

    13/31

    LaserCOMPACT Product Guide

    3.2 Front Cover and LEDs

    The front cover has a self adhesive printed decal attached next to the LED display. On the rearof the cover is a card with LEDs and a Reset switch. This card connects to the termination card

    with a wire loom labelled LED CARD. The front cover hangs down from the enclosure by aplastic tie when the cover is in the open position and ensures the cable loom is not stressed.

    3.3 Termination Card

    This card is attached to the detector enclosure with four screws. This is an interface card thatallows power, VESDAnet, relay and auxiliary wires to be connected to the detector. There aretwo wire terminal strips on the card to terminate the wires. The maximum wire size that can fitinto the terminal is 2.5sq mm (12AWG).

    The power protection fuse (1.5A) is removable and protects the detector electrical systemagainst short circuit or overload. The DC power converters on this card steps down the

    incoming DC power to lower voltages.

    There are three programmable relays with contacts rated at 2A @ 30VDC and forms aninterface to the fire alarm control panel or to other devices. The default relay settings are thede-energised (unlatched) states except the Fault relay, which is energised (latched), on powerup. These relays may be programmed to any states.

    The 9 pin or 15 pin, programming socket on the card allows interface with a PC or a LCDProgrammer. Refer to Sections 4.6 to determine which programming device is to be used foreach model type.

    3.4 Cable Entry Ports

    There are four cable entry ports, two on the right hand side, one on the top right hand side andone on the rear of the enclosure. The size of the cable entry port is 25 mm (1in) and haspush out hole plugs covering these ports. Any of these cable entry ports may be used to run thecables into the enclosure. To remove the hole plugs use your thumb to push out the plugs frominside the enclosure.

    3.5 Air Inlet Port

    There is one air inlet port located on the top of the enclosure that allows the sampled air toenter into the detector for analysis. An arrow pointing towards the port identifies the air inletand has a plug that must be removed during installation. The size of the air inlet port is 25mm(1in) and is able to fit a pipe up to this size. The air inlet port tapers towards the inside and

    allows the pipe to be inserted as far as it will go. This pipe connection must NOT be glued.

    3.6 Air Filter Cartridge

    The air filter cartridge is located at the bottom left hand side of the enclosure and is held inplace by a single recessed screw. The filter elements are housed inside a disposable cartridgeand cannot be cleaned for reuse. To remove the air filter cartridge, undo the screw and lift outthe air filter cartridge.

    The sampled air from the environment passes through two stages of air filters within the airfilter cartridge. The first stage removes the large particles of dirt and allows the smaller smokeparticles to pass into the detection chamber for analysis. The second stage removes thesmaller particles of dirt and passes very clean air into the detection chamber to keep the optical

    surfaces clean.

  • 8/12/2019 VLC Product Manual

    14/31

    LaserCOMPACT Product Guide

    The expected filter operating life is 5 years in a normal office environment. In dustyenvironments, the life expectancy of the filter is reduced. The detector monitors the air filter lifeand efficiency and the user is prompted when it is time to change the filter.

  • 8/12/2019 VLC Product Manual

    15/31

    LaserCOMPACT Product Guide

    3.7 Aspirator

    The aspirator is a proprietary high efficiency suction air pump that draws in air through anetwork of sampling air pipes and passes a small sample of the filtered air into the laser

    detection chamber. The rest of the air is forced out through the exhaust pipe located at thebottom of the enclosure. The aspirator runs continuously at a constantly regulated speed. Theairflow through the aspirator is monitored continuously by the airflow sensor located inside theair inlet port and the user is prompted when there is a reduction or an increase in the airflow.

    3.8 Air Exhaust Port

    This port allows the sampled air to be expelled into the environment. There is one air exhaustport and is located at the bottom right hand side of the enclosure. The size of the air exhaust

    port is 25mm (1in) and is able to fit a pipe up to this size. A plug covers the air exhaust portand must be removed during installation. The air from this port can be piped back to the firezone via pipes connected to this outlet if required. Any pipe connection made to the exhaust

    port must NOT be glued.

    3.9 Laser Detection Chamber

    The Laser detection chamber is located in the rear of the enclosure behind the metal backpanel.

    Note: This component is inaccessible, not serviceable and is not to be opened byanypersonnel.The metal back panel is not to be opened by any personnel.

    In this chamber, a small portion of the smoky air passes through a laser beam causing lightscattering. The scattered light is analysed by the central processor card to determine the smokedensity or obscuration.

    3.10 Processor Card

    The central processor card is located in the rear of the enclosure behind the metal back panel.

    Note: This component is inaccessible, not serviceable and is not to be opened byany personnel.The metal back panel is not to be opened by any personnel.

  • 8/12/2019 VLC Product Manual

    16/31

    LaserCOMPACT Product Guide

    4. Termination Card Details

    4.1 Wire Terminal Location for RO Model

    NC = Normally Close NO = Normally Open C = Common

    Figure 7 Wire Terminal Location for RO Model

    4.2 Wire Terminal Location for VN Model

    Figure 8 Wire Terminal Location for VN Model

    Terminal A Terminal B1 Bias (-) (GND) 1 Shield

    2 Reset (-) 2 VESDAnet A (-)

    3 Reset (+) 3 VESDAnet A (+)

    4 Bias (+) 4 Shield

    5 LED (-) (GND) 5 VESDAnet B (-)

    6 LED (+) 6 VESDAnet B (+)

    7 FIRE (NO) 7 Power (-)

    8 FIRE (C) 8 Power (+)

    9 PRE-ALARM (NO) 9 Power (-)

    10 PRE-ALARM (C) 10 Power (+)

    11 FAULT (NO)

    12 FAULT (C)

    13 FAULT (NC)

    AB

    Pin 1

    Pin 1

    Terminal A Terminal B1 FIRE (NO) 1 Bias (-) (GND)

    2 FIRE (C) 2 Reset (-)

    3 PRE-ALARM (NO) 3 Reset (+)

    4 PRE-ALARM (C) 4 Bias (+)

    5 FAULT (NO) 5 LED (-) (GND)

    6 FAULT (C) 6 LED (+)

    7 FAULT (NC) 7 Power (-)

    8 Power (+)

    9 Power (-)

    10 Power (+)

    Pin 1Pin 1

    A B

  • 8/12/2019 VLC Product Manual

    17/31

    LaserCOMPACT Product Guide

    4.3 Power Terminals

    There are four power terminals designated Power (+)and Power (-) on Terminal B for 24VDCpower connection. The Power (+) terminal is for positive 24VDC supply and the Power (-)terminal is for DC Ground. The four power terminals enable power to be brought into thedetector via a single wire pair and looped out to another device via another wire pair. Thedetector has reverse polarity protection to minimise the risk of a reverse power connection tothe detector.

    Note: The LaserCOMPACT will not operate when the supply is reversed.Do not operate when the DC supply voltage is outside the device operatingvoltage range of 18VDC to 30VDC. Damage may occur if more than 30VDC isapplied.

    Figure 9 Wire Connection Details for Power Terminals

    4.4 VESDAnet Terminals (VN Model only)

    These terminals are located on the termination card in the VN model only. There are sixVESDAnet terminals on Terminal Bdesignated VESDAnet A (+), VESDAnetA (-), VESDAnetB (+),VESDAnetB (-)and Shield (Qty 2).The terminals enable the VESDAnetwires to bebrought into the detector and looped out to another device.

    Data communication between detectors is bidirectional and the Aor Bchannel set of terminalsmay be used to terminate the incoming or outgoing wires. Refer to Figure 10 for cabling details.The polarity of the data wires must be maintained throughout the network and all Shieldwiresmust be terminated at all wire ends.

    When the detector is to be used as a stand-alone device and is not connected into VESDAnetthe VESDAnet A and B channels must be looped as shown in Figure 11.

    VESDAnet was designed to function at its optimum in a Closed Loopnetwork (Refer to Figure10 for closed loop wiring) and this configuration is highly recommended to achieve a faulttolerant loop. The detectors must be programmed to the Closed Loopconfiguration (systemdefault setting).

    An Opened Loop configuration is possible by not linking the VESDAnet terminals betweendetectors 1 and 5 (Refer to Figure 10). Detector 1 and detector 5 must be programmed to theOpened Loop configuration otherwise the system will generate a fault.

    Terminal B

    Power (+)

    Power +

    Power (-)

    Power (-)GND

    8

    9

    10

    7

    +24V

    GNDFrom 24VPowerSupply

    +24V24V Power toNext Device

  • 8/12/2019 VLC Product Manual

    18/31

    LaserCOMPACT Product Guide

    Figure 10 Wire Connection Details (Closed Loop) for VESDAnetTerminals

    Figure 11 Wire Connection Details for VESDAnet Loop

    4.5 Relay Terminals

    There are three alarm relays designated Fault, Pre-Alarm and Fire. Refer to Figure 12. Therelays can be used to connect power or data to the fire alarm control panel or to activateexternal devices. The relay terminals are located at the following terminals on the terminationcard:-

    RO model --- Terminal strip A, pins 1 to 7VN model --- Terminal strip A, pins 7 to 13

    There are three terminals for the Fault relay (Fault NO, Fault NC, Fault C)and two terminalseach for the Pre-Alarm (Pre-Alarm NO, Pre-Alarm C)and Fire (Fire NO, Fire C)relays.

    The default relay states are non-energised (non-latched) except the Fault relay, which is set to

    the energised (latched) state on power up. The relays can be programmed to any state.

    Note: NC = Normally CloseNO = Normally Open

    B+6

    5

    4

    2

    3

    1Shield

    A-

    A+

    Shield

    B-

    Terminal B

    Detector 3

    Terminal B

    1

    2

    3

    4

    5

    6

    1

    2

    3

    4

    5

    6

    1

    2

    3

    4

    5

    6

    1

    2

    3

    4

    5

    6

    1

    2

    3

    4

    5

    6

    Shield

    A-

    A+

    Shield

    B-

    B+

    Detector 1

    Terminal B

    Detector 2

    Terminal B

    Detector 4

    Terminal B

    Shield

    B+

    B-

    Shield

    A-

    A+

    Shield

    A-A+

    B-

    ShieldShield

    B-

    B+

    Shield

    Shield

    A-

    A+

    B-

    B+

    Detector 5

    Terminal B

    B+

    Shield

    A-

    A+

  • 8/12/2019 VLC Product Manual

    19/31

    LaserCOMPACT Product Guide

    C = Common

  • 8/12/2019 VLC Product Manual

    20/31

    LaserCOMPACT Product Guide

    Figure 12 Wire Connection Details for Relay Terminals

    4.6 Programming Socket

    The 9 pin or 15 pin programming socket on the termination card provides the communicationinterface between the detector and a PC or LCD Programmer. Use the information listed belowto determine the type of programming device required to program the VN or the RO detector.

    ROmodel The programming socket on the termination card has 9 pins.Use a PC and connect the RS232 data cable directly to the 9 pin VESDAlinkprogramming socket.

    VNmodel The programming socket on the termination card has 15 pins.Use a LCD Programmer and connect the programmer cable to the 15 pin

    VESDAnet programming socket.ORUse a PC with a VESDA PC-Link HLI device and the appropriate data cablesto connect to the 15 pin VESDAnet programming socket.

    4.7 Auxiliary Terminals

    There are three pairs of auxiliary terminals on both models designated as:-

    a) Biasb) Resetc) LED

    4.7.1 Bias TerminalsThe Bias (+) output terminal provides a 10V supply via a 1K resistor to power the Resetterminals via a Reset/Isolate switch located in another part of the building. The Bias ()terminal is the Bias ground. Refer to Figure 13 for a suggested circuit.

    Bias -

    Bias +

    Switch

    6

    5

    4

    3

    LED -

    Reset +

    LED +

    Reset -2

    1

    LED

    SwitchIsolate -- Close PositionResetOpen Position

    Terminal ATerminal A

    13

    12

    11

    10

    9

    C

    C

    NC

    NO

    NO

    8

    7

    C

    NO

    Fire}

    Pre-Alarm}

    Fault}7

    6

    5

    4

    3

    C

    C

    NC

    NO

    NO

    2

    1

    C

    NO

    Fire}

    Pre-Alarm}

    Fault}Terminal pin location for RO Terminal pin location for VN

  • 8/12/2019 VLC Product Manual

    21/31

    LaserCOMPACT Product Guide

    Figure 13 Wire Connection Details for Auxiliary Terminals

    4.7.2 Reset Terminals (General Purpose Input)

    This input terminal pair could be used for one of the three functions listed below.

    Reset/Isolate Switch Mains OK

    Standby

    This input terminal requires a voltage supply between 5V to 33V DC to operate. Connect theRESET (+)to the positive output and theRESET (-) to the ground output of the external deviceor use the Bias outputs and wire up as per Figure 13. The detector must be programmed toone of the above function which is located under the Miscellaneousmenu in the programmingdevice. The voltage input to this terminal is isolated from the system by an opto-couplerdevice.

    4.7.3 Remote LED Terminals

    This output terminal pair provides a 5V, 15mA DC supply via a 220ohm resistor to power up aremote LED indicator. Connect the LED (+) to the positive terminal and the LED (-) to thenegative terminal of the remote LED indicator as per Figure 13.

  • 8/12/2019 VLC Product Manual

    22/31

    LaserCOMPACT Product Guide

    5. Specifications

    Supply Voltage 18 to 30VDC

    Power Consumption 4.0W quiescent, 4.5W with alarm

    Current Consumption 170mA at 24VDC quiescent, 190mA with alarm

    Fuse Rating 1.5A

    Dimensions (WHD) 225mm x 225mm x 85mm (8 7/8in x 8 7/8in x 3 3/8in)

    Weight 1.9kg (4.2lbs)

    Operating Temperature Detector Ambient -10to 39C (14F to 103F)

    Sampled Air: -20to 60C (-4to 140F)

    Humidity: 10-95% RH, non-condensing

    Sampling Pipe Network Maximum area of coverage 500sq m(5000sq.ft)Computer Design Tool: ASPIRE

    Pipe Size ID: 15-21mm (9/16in7/8in)

    OD: 25mm (1in)

    Relays 3 Relays, contacts rated 2A @ 30VDC

    Programmable to latched or non-latched states

    Relays DefaultConfiguration

    Fire

    Pre-Alarm

    Alert/Fault (Maintenance and Isolate)

    Programmable 060 sec time delay for each relay

    IP Rating IP30Cable Access 4 x 25mm (1in) cable entries

    Cable Termination Screw terminal blocks (0.2-2.5sq mm, 30-12 AWG)

    Sensitivity Range 0.005 to 20.00% obs/m

    (0.0015 to 6.25% obs/ft)

    Threshold Setting Range Alert: 0.0051.990% obs/m (0.0015 - 0.6218% obs/ft)

    Pre-Alarm: 0.0101.995% obs/m (0.0031 - 0.6234% obs/ft)

    Fire: 0.01520.00% obs/m (0.00466.25% obs/ft) **

    ** Limited to 12% obs/m (4% obs/ft) in UL mode (Default)

    Key Software Features Event log: Up to 12,000 events stored on FIFO basis.

    Smoke level, alarms and faults with time and date stamp

    AutoLearn: Minimum 15 minutes, maximum 15 days. Recommended minimum period 14 days. During AutoLearn thresholds are NOT changed from pre-set values.

    UL Mode: Factory Default = ON (Fire set to 4% obs/ft (12% obs/m) to comply with UL268)

    Factory Default = OFF (Fire Threshold can be set up to 6.25%/ft (20% obs/m))

  • 8/12/2019 VLC Product Manual

    23/31

    LaserCOMPACT Product Guide

    6. Factory Default Settings

    Parameter Default Value Minimum

    Access Level

    Action Threshold 0.14% obs/m (0.044% obs/ft) Adm

    AirflowHigh Urgent 130% Adm

    AirflowHigh Minor 120% Adm

    AirflowLow Minor 80% Adm

    AirflowLow Urgent 70% Adm

    Alarm DelaysPre-Alarm 10 seconds Adm

    Alarm DelaysAlert 10 seconds Adm

    Alarm DelaysFire 10 seconds Adm

    Alarms Latched Latched Adm

    Alert Threshold 0.08% obs/m (0.025% obs/ft) Adm

    AutoLearn 14 days0 Hours

    0 Minutes

    AdmAdm

    Adm

    Button LockoutButtons Enabled Adm

    Communications Open-ended loopPreferred PortNetwork DelayHealth Check

    NoneA15 seconds45 seconds

    AdmDstDstDst

    Delay Times Simultaneous/Cumulative Adm

    Device ID Name/Location Adm

    Event Log to View Smoke LevelAlarmsFaultsUser Action

    AdmAdmAdmAdm

    Faults Latched Latched Adm

    Filter Service Interval 1825 days (5 years) Adm

    Fire Threshold 0.2% obs/m (0.062% obs/ft) Adm

    Full Scale 2.000% obs/m (0.61% obs/ft) Adm

    Instantaneous - Fire Disabled Adm

    Loop Number (VN Version only) 0 Adm

  • 8/12/2019 VLC Product Manual

    24/31

    LaserCOMPACT Product Guide

    Parameter Default Value Minimum

    Access Level

    Overlay Alert Not Selected Adm

    Power Supply Zone Number 0 Adm

    Reference DetectorDelay 2 minutes Adm

    Reference DetectorDetector 255 = No Reference Adm

    Reference DetectorDilution 100% Adm

    Smoke ChangeChange By 0.02% obs/m (0.0062% obs/ft) Adm

    Smoke ChangeMin Interval 2 seconds Dst

    UL Flag restricting maximum Threshold Set Adm

    Units SI Adm

    Zone Name/Location Blank Adm

    Zone Number 0 Adm

    7. Alarm Threshold Settings

    Alarm Threshold

    Settings (Default)

    UL Alarm Threshold

    Settings

    % obs/m % obs/ft % obs/m % obs/ft

    Alert (min) 0.005 0.0015 0.005 0.0015

    Alert (max) 1.990 0.6218 1.990 0.6218

    Pre-Alarm (min) 0.010 0.0031 0.010 0.0031

    Pre-Alarm (max) 1.995 0.6234 1.995 0.6234

    Fire (min) 0.015 0.0046 0.015 0.0046

    Fire (max) 20.0 6.25 12.8 4.0

    UL Specs: To meet UL specifications, Any alarm thresholds (signal) that initiates anevacuation procedure via the Fire Alarm Panel must not be set higher than0.625%/ft.

  • 8/12/2019 VLC Product Manual

    25/31

    LaserCOMPACT Product Guide

    8. Physical Dimensions

    Figure 14 Dimensions in mm (inches) for LaserCOMPACT with mounting Bracket (Rear View)

    E=Cable Entry Point on Rear of Enclosure

    E

    112.5(4.43)

    MountingBracket

    2058.07

    225(8.86)

    225(8.86)

    112.5(4.43)

    95(3.74)

  • 8/12/2019 VLC Product Manual

    26/31

    LaserCOMPACT Product Guide

    Figure 15 Dimensions in mm (inches) for LaserCOMPACT

    70.5(2.78)

    85(3.35)

    225(8.86)

    225(8.86)

    60 (2.36)

    33(1.30)

    Right Hand Side View

    Bottom View

    31 (1.22)

    45 (1.77)

    28(1.10)

    Air Inlet Port

    17.8(0.68)

    26 (1.02)

    Air Exhaust

    Cable Entry

    E

    E= Cable Entry Point

    E

  • 8/12/2019 VLC Product Manual

    27/31

    LaserCOMPACT Product Guide

    9. Parts Replacement

    A) Air Filter Cartridge

    B) Termination Card Screws (4)C) Termination CardD) Main EnclosureE) AspiratorF) Sample Air HoseG) Front CoverH) Aspirator Cable LoomJ) Manifold Outlet Flange

    A

    C

    D

    E

    F

    G

    B

    H

    J

  • 8/12/2019 VLC Product Manual

    28/31

    LaserCOMPACT Product Guide

    Front Cover (B)Screws (A)

    9.1 Opening the Detector

    1. Undo two Philips head screws

    on front cover (A).2. Open front cover (B) and allowcover to hang by the attachedplastic strap.

    9.2 Closing the Detector

    1. Replace the front cover over detectorenclosure ensuring the plastic strap andcable loom is not wedged betweencover and enclosure.

    2. Tighten the two screws (A)

    9.3 Replacing the Air Filter Cartridge

    Disassembly

    1. Locate the air filter cartridge (A) inside thedetector compartment.

    2. Undo the recessed Philips head filterscrew (B).

    3. Lift out the air filter cartridge.

    Assembly

    1. Insert a new air filter cartridge (A).2. Tighten filter screw (B).3. Reset the filter counter by connecting a LCD

    programmer or a PC with VConfig Pro or VConfigBasic software to the programming socket.

    4. Using a LCD programmer (VN version only):

    a) Enter your user level and PIN numberto Log ON to the detector.

    b) Initiate the New Filter command locatedunder the Filter menu.

    5. Using a PC only (Applicable to RO version) orUsing a PC with a PC-Link HLI (Applicable toVN version only):

    a) Enter your user level and PIN number toLog ON to the detector.

    b) Initiate Reset Filter Settings commandlocated under the Device menu.

    6. Close up the detector.

    Air FilterCartridge (A)

    Filter Screw (B)Air Filter Cartridge (A)

  • 8/12/2019 VLC Product Manual

    29/31

    LaserCOMPACT Product Guide

    9.4 Replacing the Aspirator

    Disassembly

    1. Remove the four screws (A) securing thetermination card.

    2. Disconnect the aspirator cable loom fromthe connector on the aspirator.

    3. Gently pull out termination card (B) frominterface card (connected behind).

    4. Be careful not to dislodge any wiresconnected to the termination card.

    5. Leave the termination card suspended byits wires.

    6. Pull off the air hose from aspirator pipe (D).7. Undo three Philips head screws securing aspirator (E). Screws are captive and do not

    come off the aspirator.8. Turn aspirator anti-clockwise (F) using the exhaust port as the pivot point.

    9. Push aspirator upward (G) and remove.

    Assembly

    1. Check the new aspirator has a gasket on the inlet flange and three attached screws.2. Wipe manifold outlet flange surface (J) if dirty. See Figure 16.3. Do the reverse of disassembly.4. Secure aspirator with three screws (E).5. Connect removed air hoseto pipe on aspirator. Ensure a tight fit over the pipe.6. Insert Termination Card (B) into interface card (C).7. Secure the termination card with four screws (A).8. Connect aspirator cable connector to socket on aspirator. Connector is polarised and can

    only be inserted one way.

    9. Check all wires are secured to its connectors or terminals.10. Power ON the detector and check the aspirator is running.11. Close up the detector.

    (D)

    Screws (E)

    (F)

    (G)

    Air Hose

    Interface CardConnector (C)

    Screw (A) TerminationCard (B)

  • 8/12/2019 VLC Product Manual

    30/31

    LaserCOMPACT Product Guide

  • 8/12/2019 VLC Product Manual

    31/31

    Australia and Asia The Americas Europe and the Middle East www.vesda.com

    Vision SystemsVESDAPrivate Bag 215

    495 Blackburn RoadMount Waverley, VIC, 3149AustraliaPh +61 3 9211 7200

    Vision SystemsVESDA35 Pond Park Road

    Hingham, MA 02043, USAPh +781 740 2223Toll Free 800 229 4434Fax +781 740 4433

    Vision SystemsVESDAVision House, Focus 31 Mark Road

    Hemel HempsteadHerts, HP2 7BW UKPh +44 1442 242 330Fax +441442 249 327