Viking TotalPac2 FireFlex Dual / 1230 Systems Inc. Technical Presentation ASPE Cleveland, OH March...

35
Viking TotalPac2 FireFlex Dual / 1230 Systems Inc. www.fireflex. com Technical Presentation ASPE Cleveland, OH March 10th, 2010

Transcript of Viking TotalPac2 FireFlex Dual / 1230 Systems Inc. Technical Presentation ASPE Cleveland, OH March...

Viking TotalPac2FireFlex Dual / 1230Viking TotalPac2FireFlex Dual / 1230

Systems Inc.Systems Inc.

www.fireflex.comwww.fireflex.com

Technical Presentation

ASPE

Cleveland, OH

March 10th, 2010

Technical Presentation

ASPE

Cleveland, OH

March 10th, 2010

History:History:

1990Power

Plants Unit

1990Power

Plants Unit

1991Light & Ordinary

Hazard

1991Light & Ordinary

Hazard

2002Second

Generation

2002Second

Generation

INTEGRATED SPRINKLER SYSTEMSINTEGRATED SPRINKLER SYSTEMS

Expanding the concept:Expanding the concept:

Extended range of configurations:Extended range of configurations:

Skid unitSkid unit Remote controlled unitRemote controlled unit Self-contained unitSelf-contained unit

INTEGRATED SPRINKLER SYSTEMSINTEGRATED SPRINKLER SYSTEMS

Description: Typical System LayoutDescription: Typical System Layout

Integrated CabinetIntegrated Cabinet

Foam TankFoam Tank

Air CylindersAir Cylinders

Distribution NozzlesDistribution Nozzles

Piping Network

ICAF SYSTEMICAF SYSTEM

(water tank also available)(water tank also available)

Description: Compressed Air Foam (CAF)Description: Compressed Air Foam (CAF)

CAF TECHNOLOGYCAF TECHNOLOGY

• Uniform & stable• High momentum• Excellent quality• 10:1 expansion

• Uniform & stable• High momentum• Excellent quality• 10:1 expansion

Integrated Clean Agent SystemsIntegrated Clean Agent Systems

• Clean Agent Integrated Fire Suppression Systems using 3M™ Novec™ 1230 Fire Protection Fluid

• Clean Agent Integrated Fire Suppression Systems using 3M™ Novec™ 1230 Fire Protection Fluid

• Combined Automatic Sprinkler and Clean Agent Integrated Fire Suppression Systems using 3M™ Novec™ 1230 Fire Protection Fluid

• Combined Automatic Sprinkler and Clean Agent Integrated Fire Suppression Systems using 3M™ Novec™ 1230 Fire Protection Fluid

3M Novec 1230:3M Novec 1230:

CLEAN AGENTCLEAN AGENT

Integrated Clean Agent SystemsIntegrated Clean Agent SystemsFireFlex 1230FireFlex 1230

fuelfuel

oxygen

heat

chainreaction

Extinguishing Mechanism

The Fire Tetrahedron Removing one of

the required components for fire

or disrupting the balance between them can cause a fire to extinguish

Novec 1230 Fluid extinguishes primarily

via cooling – removing heat from

the fire

Non-corrosive

Long term testing of compatibility with materials of construction (system hardware)

Compatability with plastics confirmed

30 year shelf life in properly maintained and installed systems

Compatible with fire system materials

3M NOVEC 12303M NOVEC 1230

Environmental Properties

Properties Novec 1230(FK-5-1-12)

Halon 1301 FM-200(HFC-227ea)

ECARO-25(HFC-125)

Ozone Depletion Potential

0 10 0 0

Global Warming Potential

1 6900 3220 3500

Atmospheric Lifetime (years)

0.014 65 29 33

EPA's SNAP Conformance

Yes N/A Yes Yes

3M NOVEC 12303M NOVEC 1230

Physical Properties

Properties Novec 1230(FK-5-1-12)

Halon 1301 FM-200(HFC-227ea)

ECARO-25(HFC-125)

Design % 4-6% 5 % 6.25-8.7 % 8-11.3 %

NOAEL % 10 5 9 7.5

Occupants Safety Margin %

67-150 % Nil 3-44 % Nil

(NOAEL) No Observable Adverse Effects Level for acute toxicity, including cardiac senisitization(NOAEL) No Observable Adverse Effects Level for acute toxicity, including cardiac senisitization

• Site refilling option• Site refilling option

3M NOVEC 12303M NOVEC 1230

3M NOVEC 12303M NOVEC 1230

If Novec 1230 fluid is banned from or restricted in use as a fire protection agent due to ozone depletion potential or global warming potential, 3M will refund the purchase price of the fluid.

If Novec 1230 fluid is banned from or restricted in use as a fire protection agent due to ozone depletion potential or global warming potential, 3M will refund the purchase price of the fluid.

3M Novec 1230:3M Novec 1230:

Pre-Engineered Discharge Nozzles:

• Available: 1", 1½" & 2" dia.

• 180° or 360° discharge pattern

• 32' x 32' spacing – 16'-4" max. height

• No piping below 8,500 cu.ft. !

Pre-Engineered Discharge Nozzles:

• Available: 1", 1½" & 2" dia.

• 180° or 360° discharge pattern

• 32' x 32' spacing – 16'-4" max. height

• No piping below 8,500 cu.ft. !

CLEAN AGENTCLEAN AGENT

FIREFLEX 1230FIREFLEX 1230

Engineered Systems:

• Larger or multiple room hazards or volumes

• Need some calculations/software required

• Re-use existing Halon 1301 piping at 500psi

Engineered Systems:

• Larger or multiple room hazards or volumes

• Need some calculations/software required

• Re-use existing Halon 1301 piping at 500psi

3M Novec 1230:3M Novec 1230:

Engineered Discharge Nozzles:

• Available: ½", 1", 1½", 2" & 2½" dia.

• 180° or 360° discharge pattern

• 32' x 32' spacing – 16'-4" max. height

• Re-use existing Halon 1301 piping at 500psi

Engineered Discharge Nozzles:

• Available: ½", 1", 1½", 2" & 2½" dia.

• 180° or 360° discharge pattern

• 32' x 32' spacing – 16'-4" max. height

• Re-use existing Halon 1301 piping at 500psi

CLEAN AGENTCLEAN AGENT

Product Description:Product Description:

• Fully Integrated

• Clean Agent System Only

• Factory Built & Tested

• Fully Integrated

• Clean Agent System Only

• Factory Built & Tested

FIREFLEX 1230FIREFLEX 1230

Product Description:Product Description:

• Sturdy Cabinet with Lock

• Competitively Priced

• Eliminates Site Coordination Issues

• Sturdy Cabinet with Lock

• Competitively Priced

• Eliminates Site Coordination Issues

FIREFLEX 1230FIREFLEX 1230

Product Description:Product Description:Integrated Potter PFC-4410 RC Releasing panel

Integrated Potter PFC-4410 RC Releasing panel

Clean Agent Cylinder from 40 to 601 lbs cap.

Clean Agent Cylinder from 40 to 601 lbs cap.

Sturdy CabinetSturdy Cabinet

Detailed Instructions & Unit Serial NumberDetailed Instructions & Unit Serial Number

FIREFLEX 1230FIREFLEX 1230

Available Configurations:Available Configurations:

• Clean Agent Only – No Sprinklers

• Self-contained or Remote Controlled (no panel)

• Master-Salve Cylinders Available

• Main-Reserve Arrangement Available

• Pre-Engineered or Engineered Piping System

• Clean Agent Only – No Sprinklers

• Self-contained or Remote Controlled (no panel)

• Master-Salve Cylinders Available

• Main-Reserve Arrangement Available

• Pre-Engineered or Engineered Piping System

FIREFLEX 1230FIREFLEX 1230

FIREFLEX 1230FIREFLEX 1230System dimensions and Capacity Table:System dimensions and Capacity Table:

FireFlex® 1230 Cabinets Capacity (# of cylinders) & dimensions

Cylinder Size (lbs) Dimensions

Cabinet Size 40 76 164 322 601 A B C

24" 1 1 1 1 -- 23" 25" 77⅛"

36" 2 2 2 -- 1 35¾" 25" 77⅛"

48" -- -- -- 2 2 46" 25" 77⅛"

Integrated Clean Agent SystemsIntegrated Clean Agent SystemsFireFlex DUALFireFlex DUAL

FIREFLEX DUALFIREFLEX DUALProduct Description:Product Description:

• Fully Integrated System

• Combines Preaction & Clean Agent

• Factory Built & Tested

•Serialized

• Fully Integrated System

• Combines Preaction & Clean Agent

• Factory Built & Tested

•Serialized

Product Description:Product Description:

• Sturdy Cabinet with Lock

• Competitively Priced

• Eliminates Site Coordination Issues

• Sturdy Cabinet with Lock

• Competitively Priced

• Eliminates Site Coordination Issues

FIREFLEX DUALFIREFLEX DUAL

Product Description:Product Description:

Air CompressorAir Compressor

Optional Common Integrated Potter PFC 4410RC Releasing Panel

Optional Common Integrated Potter PFC 4410RC Releasing Panel

Viking Preaction 2” & 3” Viking Preaction 2” & 3”

Clean Agent CylinderClean Agent Cylinder

Detailed Instructions & Unit Serial NumberDetailed Instructions & Unit Serial Number

FIREFLEX DUALFIREFLEX DUAL

Available Configurations:Available Configurations:

• Preaction Single or Double Interlock

• 2" or 3" dia. Sprinkler Valve

• Self-contained or Remote Controlled (no panel)

• Pre-engineered or Engineered Piping System

• Preaction Single or Double Interlock

• 2" or 3" dia. Sprinkler Valve

• Self-contained or Remote Controlled (no panel)

• Pre-engineered or Engineered Piping System

FIREFLEX DUALFIREFLEX DUAL

FIREFLEX DUALFIREFLEX DUAL

FireFlex® DUAL Cabinets Capacity (# of cylinders) & dimensions

Cylinder Size (lbs) Dimensions

Cabinet Size 40 76 164 322 601 A B C

36" 1 1 -- -- -- 35¾" 25" 77⅛"

48" -- -- 1 1 1 46" 25" 77⅛"

System dimensions and Capacity Table:System dimensions and Capacity Table:

NFPA 2001 Standard on Clean Agent Fire Protection Systems

ISO 14520 Standard on Gaseous Media Fire Extinguishing Systems

UL Listed FM Approved

VdS Approved LPCB Approved

IMO Recognized

Lloyds Approved

Standards, Approvals and Listings for Novec 1230 Fluid

U.S EPA SNAP approved as alternative to halon in occupied spaces

DNV Approved

Bureau Veritas Approved

CNPP Approved

LISTINGS & APPROVALSLISTINGS & APPROVALSClean Agent(Sevo Equipment):Clean Agent(Sevo Equipment):

UL & ULC Listed:

• 360 psi Pre-engineered Systems

• Engineered Systems by Mid-2010

FM Approved:

• 500 psi Pre-Engineered Systems

• Engineered Systems early 2010

UL & ULC Listed:

• 360 psi Pre-engineered Systems

• Engineered Systems by Mid-2010

FM Approved:

• 500 psi Pre-Engineered Systems

• Engineered Systems early 2010

Potter Releasing Panel & Viking Preaction System:Potter Releasing Panel & Viking Preaction System:

• UL & ULC Listed

• FM Approved

• CSFM Approved

• NYC Accepted

• UL & ULC Listed

• FM Approved

• CSFM Approved

• NYC Accepted

LISTINGS & APPROVALSLISTINGS & APPROVALS

FIREFLEX DUAL & 1230

(Assembled Units):

FIREFLEX DUAL & 1230

(Assembled Units):

• Pre-engineered System: c-UL-us (early 2010)

• FM Approved 500 psi

• Engineered System: c-UL-us & FM (early 2010)

• CSFM & NYC (early 2010)

• Pre-engineered System: c-UL-us (early 2010)

• FM Approved 500 psi

• Engineered System: c-UL-us & FM (early 2010)

• CSFM & NYC (early 2010)

LISTINGS & APPROVALSLISTINGS & APPROVALS

• Cable racks

• Clean Rooms

• Clinical / Diagnostic equipment

• Control Rooms

• Data Centers

• Electric Utility facilities

• Generator & turbine enclosures

• Cable racks

• Clean Rooms

• Clinical / Diagnostic equipment

• Control Rooms

• Data Centers

• Electric Utility facilities

• Generator & turbine enclosures

APPLICATIONSAPPLICATIONS

• IT Systems

• Mix rooms

• Pump Stations

• Switch Rooms & UPS

• Telecommunications

• Testing / Imaging equipment

• Transformer Vaults

• Etc…

• IT Systems

• Mix rooms

• Pump Stations

• Switch Rooms & UPS

• Telecommunications

• Testing / Imaging equipment

• Transformer Vaults

• Etc…

Information required for designInformation required for design• Obtain specifications

• Approvals required, AHJ

• Determine if a reserve is required

• Identify hazard normal ambient temperature

• Obtain location altitude

• Obtain drawings, sketches of dimensions

• Qualify room size when quoting a job

• Obtain hazard areas, length, width, ceiling height

• Determine system location

• Obtain specifications

• Approvals required, AHJ

• Determine if a reserve is required

• Identify hazard normal ambient temperature

• Obtain location altitude

• Obtain drawings, sketches of dimensions

• Qualify room size when quoting a job

• Obtain hazard areas, length, width, ceiling height

• Determine system location

Thank you !Thank you !

www.fireflex.comwww.fireflex.com

FIREFLEX DUAL&

FIREFLEX 1230

by the same people who first brought you integrated fire

protection systems

FIREFLEX DUAL&

FIREFLEX 1230

by the same people who first brought you integrated fire

protection systems

Systems Inc.Systems Inc.