View PDF - Royal BC Museum
Transcript of View PDF - Royal BC Museum
Continuous Optimization for Commercial Buildings Program
Retrocommissioning Final
Report
Jan 31 2013
Prepared for:
The Royal BC Museum Corp
Victoria, BC
COP10-322
Prepared by:
Avalon Energy Management
300-1245 Esquimalt Rd
Victoria, BC
HOTO OF BUILDING]
BC Hydro Final Report Template Page 2 of 46
© Copyright 2008 PECI
TABLE OF CONTENTS
INTRODUCTION ....................................................................................................................................................... 5
1.0 PROJECT OVERVIEW ................................................................................................................................. 6
2.0 PROJECT RESULTS ..................................................................................................................................... 7
3.0 IMPLEMENTED MEASURES ...................................................................................................................... 8
3.1 MEASURE 1: ARCHIVES CHILLER PUMP ON ONLY IF CHILLER ...................................................................... 8 Overview ........................................................................................................................................................... 8 Measure ............................................................................................................................................................. 8 Measure Maintenance .................................................................................................................................. 8
3.2 MEASURE 2: BETTER CONTROL ARCHIVES REHEAT .................................................................................. 9 Overview ........................................................................................................................................................... 9 Measure ............................................................................................................................................................. 9 Measure Maintenance ................................................................................................................................ 10
3.3 MEASURE 3: REDUCE AHU RUN HOURS ............................................................................................... 10 Overview ......................................................................................................................................................... 10 Measure ........................................................................................................................................................... 10 Measure Maintenance ................................................................................................................................ 11
3.4 MEASURE 4: REDUCE EXHIBITS & FANNIN PUMP RUN HOURS ................................................................ 12 Overview ......................................................................................................................................................... 12 Measure ........................................................................................................................................................... 12 Measure Maintenance ................................................................................................................................ 13
3.5 MEASURE 5: REDUCE SECURITY 5 KW RESISTANCE WARM-UP ................................................................. 13 Overview ......................................................................................................................................................... 13 Measure ........................................................................................................................................................... 13 Measure Maintenance ................................................................................................................................ 14
3.6 MEASURE 6: F10 W CORRIDOR MAT DECOUPLED FROM 3N RA ........................................................... 15 Overview ......................................................................................................................................................... 15 Measure ........................................................................................................................................................... 15 Measure Maintenance ................................................................................................................................ 16
3.7 MEASURE 7: REPAIR AH2 OCCUPANCY SENSOR ...................................................................................... 16 Overview ......................................................................................................................................................... 16 Measure ........................................................................................................................................................... 16 Measure Maintenance ................................................................................................................................ 16
3.8 MEASURE 8 : REDUCE INTEGRAL ON SF4 (7CON17) ............................................................................... 17 Overview ......................................................................................................................................................... 17 Measure ........................................................................................................................................................... 17 Measure Maintenance ................................................................................................................................ 17
3.9 MEASURE 9: DDC CONTROL AH5 ......................................................................................................... 18 Overview ......................................................................................................................................................... 18 Measure ........................................................................................................................................................... 19 Measure Maintenance ................................................................................................................................ 19
3.10 MEASURE 10: RAISE 2N & 3N GALLERY RT-SP FROM 20 TO 21C ................................................... 20 Overview ......................................................................................................................................................... 20 Measure ........................................................................................................................................................... 20 Measure Maintenance ................................................................................................................................ 21
3.11 MEASURE 11: PUT COOL ‘STAT ON 2ND EAST ELECTRIC RM FAN ....................................................... 21 Overview ......................................................................................................................................................... 21
BC Hydro Final Report Template Page 3 of 46
© Copyright 2008 PECI
Measure ........................................................................................................................................................... 21 Measure Maintenance ................................................................................................................................ 21
3.12 MEASURE 12: TUNE GIFT HCV & MAD CONTROLLER ....................................................................... 22 Overview ......................................................................................................................................................... 22 Measure ........................................................................................................................................................... 22 Measure Maintenance ................................................................................................................................ 23
3.13 MEASURE 13: BETTER CONTROL EXHIBITS REHEAT .............................................................................. 23 Overview ......................................................................................................................................................... 23 Measure ........................................................................................................................................................... 23 Measure Maintenance ................................................................................................................................ 24
3.14 MEASURE 14: USE SF-8 & 11 HUMIDIFIERS ......................................................................................... 24 Overview ......................................................................................................................................................... 24 Measure ........................................................................................................................................................... 25 Measure Maintenance ................................................................................................................................ 25
3.15 MEASURE 15: RETROFITS 15,16,17 – ............................................................................................... 25 REDUCTIONS ON EXISTING SPEED DRIVES ........................................................................................................... 25
Overview ......................................................................................................................................................... 25 Measure ........................................................................................................................................................... 25 Measure Maintenance ................................................................................................................................ 26
3.16 MEASURE 16: RETROFIT 18 - E+ BOILER HSWT-SP ........................................................................ 27 Overview ......................................................................................................................................................... 27 Measure ........................................................................................................................................................... 27 Measure Maintenance ................................................................................................................................ 27
3.17 MEASURE 17: RETROFIT 19, 20, 21 – NEW SPEED DRIVES ............................................................... 28 Overview ......................................................................................................................................................... 28 Measure ........................................................................................................................................................... 28 Measure Maintenance ................................................................................................................................ 28
3.18 MEASURE 18: RETROFIT 22 - NEW AC UNIT FOR AV RM .................................................................. 29 Overview ......................................................................................................................................................... 29 Measure ........................................................................................................................................................... 29 Measure Maintenance ................................................................................................................................ 30
3.19 MEASURE 19: RETROFIT 23 -ALLOW SF8 MAD TO OPEN PAST 50% .................................................. 30 Overview ......................................................................................................................................................... 30 Measure ........................................................................................................................................................... 30 Measure Maintenance ................................................................................................................................ 30
3.20 MEASURE 20: RETROFIT 24 - ALLOW CH-12 ON AT LOWER OAT ....................................................... 31 Overview ......................................................................................................................................................... 31 Measure ........................................................................................................................................................... 31 Measure Maintenance ................................................................................................................................ 31
3.21 MEASURE 21: RETROFIT 25 - SUMMER PURGE FOR AH1-5 ................................................................. 32 Overview ......................................................................................................................................................... 32 Measure ........................................................................................................................................................... 32 Measure Maintenance ................................................................................................................................ 32
3.22 MEASURE 22: RETROFIT 26 -REDUCE FANNIN WR EF9 RUN HOURS ................................................... 33 Overview ......................................................................................................................................................... 33 Measure ........................................................................................................................................................... 33 Measure Maintenance ................................................................................................................................ 33
3.23 MEASURE 23: RETROFIT 27 - GENERAL MAINTENANCE ..................................................................... 34 Overview & Recommendations ............................................................................................................... 34 Measure Maintenance ................................................................................................................................ 35
4.0 UPDATED BUILDING DOCUMENTATION ......................................................................................... 36
BC Hydro Final Report Template Page 4 of 46
© Copyright 2008 PECI
ATTACHMENT A: IMPLEMENTATION SUMMARY TABLE ........................................................................ 38
ATTACHMENT B: TRAINING OUTLINE ........................................................................................................... 43
ATTACHMENT C: TRAINING COMPLETION FORM .................................................................................... 44
© Copyright 2008 by Portland Energy Conservation, Inc. (PECI). This material may not be distributed or reproduced without the express written permission of PECI.
BC Hydro Final Report Template Page 5 of 46
© Copyright 2008 PECI
Introduction
Through the BC Hydro Continuous Optimization for Commercial Building Program, 27 measures were
implemented at The Royal BC Museum, resulting in an estimated annual energy savings of $31,434. To
ensure that these savings persist over time, it is vital that the facilities staff and service contractors,
current and future, are aware of the implemented measures and the actions that need to be taken in order
to support and maintain each measure.
This document is a complete record of the work performed at this facility, including the in-depth
investigation of the building systems and the implementation of selected measures to optimize building
performance.
Avalon provided the professional services for this project and any questions related to this document can
be directed to:
C.Op Provider Firm Name: Avalon Mechanical Consultants
C.Op Provider Main Contact: Bob Landell
Address: 300-1245 Esquimalt Rd
City, Province, Postal Code: Victoria, BC V9A 3P2
Phone Number: 250 384 4128 x103
Email: [email protected]
BC Hydro Final Report Template Page 6 of 46
© Copyright 2008 PECI
1.0 Project Overview
Project Information Project/Building Name Royal BC Museum
Building Owner RBCM Corp
Building Location 675 Belleville Street, Victoria, BC V8W 9W2
Project Start Date 12/15/2011
Project Completion Date 7/31/2012
Contact List C.Op Provider Bob Landell
C.Op Firm Avalon Energy Management
email [email protected]
phone (250) 384-4128
Building Owner Representative Pam Lowings
email [email protected]
phone 250 387-3361
Building Engineer Tanya Duce
email [email protected]
phone (250) 387 3007
BC Hydro Program Representative Graham Henderson
email [email protected]
phone (604) 453-6471
BC Hydro Final Report Template Page 7 of 46
© Copyright 2008 PECI
2.0 Project Results
The primary objective of the project at this facility was to identify deficiencies in the operation of a
facility’s mechanical equipment, lighting, and related controls, and determine opportunities for corrective
action and other operational and maintenance improvements that reduce energy consumption and
demand.
To perform the investigation, Avalon assessed the facility’s equipment and operations. Functional
performance testing was used to verify the intended operation of individual components and systems
under various conditions and modes of operation, and analysis of system data occurred either through
trends from the building automation system or by the use of portable data logging equipment.
A complete list of findings was provided after the investigation at the meeting between the Owner,
Avalon, and the BC Hydro Program Representative to select measures for implementation. Over Nov,
2011 through Jan 2013, 27 opportunities were identified at The RBCM.
Once the RCx investigation was complete, 27 measures were selected for implementation, listed below:
1 Arch ChP on only if Chiller
2 Better Control Archives Reheat
3 Reduce AHU Run Hours
4 Reduce Pump Run Hours
5 Reduce Security 5 kW resistance warm-up
6 F10 W Corridor MAT Decoupled from 3N RA
7 Repair AH2 Occ sensor
8 Reduce Integral on SF4 7con17
9 DDC Control AH5
10 Raise 2N & 3N Gallery RT-SP from 20 to 21C
11 Put Cool Stat on 2nd E Elect Rm TF
12 Tune Gift HCV & MAD Controller
13 Better Control Exhibits Reheat
14 Use SF-8 & 11 Humidifiers
15 Reduce RF12b Speed
16 Reduce ASD speed on AH4
17 SF-8 & SF-11 VFD Reductions
18 E Boiler HSWT-SP
19 Put ASD on AH Totem
20 Put ASD on EF WR
21 Put ASD on SF Ent
22 New AC unit for AV Rm
23 Allow SF8 MAD to open past 50%
24 Allow Ch-12 to come on at lower OAT
25 Summer Purge for Worst 2 Zones AH1-5
26 Reduce Fannin WR EF9 Run Hours
27 General Maintenance
BC Hydro Final Report Template Page 8 of 46
© Copyright 2008 PECI
3.0 Implemented Measures
The following section provides information about the implementation of these measures and documents
the actions that need to be taken in order to maintain each measure.
3.1 Measure 1: Archives Chiller Pump On Only if Chiller
Overview
The 1 hp chilled water pump that serves the cooling coil in the Archives AHU was found to be operating
needlessly while the chiller was off.
Measure
Reprogram so that pump cannot operate unless the “chilled water available” variable is in effect.
Create trend log of PP-Arch status and “chilled water available” variable and alarm if pump running
unnecessarily.
Please see the following separate graphs and charts that illustrate evidence of how measure was verified:
The implementation information for this measure is summarized in the table below:
Completion date Jan 15 2013
Implementation cost $90
Projected energy and cost savings 161 kWh and 0 kW, or $12
XXXX therms, or $XXXX
Non-energy impacts maintenance reductions
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
Upon project completion, the recommended method for verifying that this measure is implemented
properly is periodic review of runtime logs.
BC Hydro Final Report Template Page 9 of 46
© Copyright 2008 PECI
3.2 Measure 2: Better Control Archives Reheat
Overview
Most Archives perimeter radiation systems and reheat coils are not under the control of the building DDC
system.
Simultaneous pneumatic heating and AHU chiller or free cooling can occur.
SAT set point set according to RTavg, can cause unnecessary cooling during heating season.
Night setback can be prevented.
Measure
Provide DDC control of the 9 largest zone reheat coil HCVs and 1 Room Temp Sensor per zone. Note
that this is less than half the number of existing reheat coils (24).
Convert stacks (6 coils), and Coil 18, 2 coils in public area = 9 HCV EPTs and 9 RTS.
Control existing actuators with EPTs.
Create trend logs for AHU runtime, SAT_SP, RT, RT_SP, and reheat HCV%.
Please see the following separate graphs and charts that illustrate evidence of how measure was verified:
Completion date Dec 15, 2012
Implementation cost $10565
Projected energy and cost savings 16800 kWh and 0 kW, or $538
XXXX therms, or $XXXX
Non-energy impacts Improved comfort, artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
BC Hydro Final Report Template Page 10 of 46
© Copyright 2008 PECI
Measure Maintenance
Upon project completion, the recommended method for verifying that this measure is implemented
properly is to site verify HCVs stroking and full closure at 0%, and review trend logs for good control
and operation as per design intent.
3.3 Measure 3: Reduce AHU Run Hours
Overview
Conversation with Facilities staff indicated that certain AHU weekly schedules were longer than
necessary. These 8 units were identified:
- EH AHU1 - EH AHU5 - RF Add'n
- SF Add'n - E Coor HP - Rm 23 EF2 &3 (10op4 &5)
- EF WR - Fannin EF8 Janitor
Run time logs should be maintained.
If the other recommendations of the report concerning DDC upgrade of SF-5, and the reheat in Archives
and Exhibits are implemented, then there may be non-public areas where occupancy follows regular work
hours, and room temp setbacks could be instituted.
Measure
Place all weekly and annual BACnet schedules on a central graphic for quick and easy adjustment.
BACnet schedules can be pre-programmed for many years. The following is a list of holidays to be pre-
programmed for non-public areas:
Days Holiday
1 Labour day
1 Thanksgiving
1 Remembrance Day
3 Xmas (3 days)
1 Good Friday
1 Easter Monday
1 Victoria Day
1 BC Day
1 Canada Day
11 per year
Some weekly schedules have been reduced already in an effort to reduce the amount of dry air being
brought into the building. This dry air was causing difficulties in maintaining mandated relative humidity
in critical the ASHRAE AA galleries. The possibility exists of having RBCM staff adjust schedules
every Friday –based on information from Event Planning- but this has not been assumed in the
calculations.
BC Hydro Final Report Template Page 11 of 46
© Copyright 2008 PECI
Please see the following separate graphs and charts that illustrate evidence of how measure was verified:
Completion date Sept 20, 2012
Implementation cost $365
Projected energy and cost savings 88161 kWh and 0 kW, or $6636
XXXX therms, or $XXXX
Non-energy impacts maintenance reductions
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
Upon project completion, the recommended method for verifying that this measure is implemented
properly is :
the Annual and Weekly schedules should be checked in the DDC system;
after a statutory holiday, runtime logs for unit commands and fan status (usually amps) should
both be compared to the intended schedules.
On a regular basis going forward, a Building Operator should review the unit status run times to ensure
that fans are not on too long.
BC Hydro Final Report Template Page 12 of 46
© Copyright 2008 PECI
3.4 Measure 4: Reduce Exhibits & Fannin Pump Run Hours
Overview
Conversation with Facilities staff indicated that certain pumps with weekly schedules were on longer than
necessary. Seven units were identified. Run time logs should be maintained.
Measure
Program to be off unless required:
- PP2 (EH ChW): Reprogram so that pump cannot operate unless the “chilled water available”
variable is in effect.
- PP4 (EH Bsmt Pre-heat): Disable if no call for unoccupied heating in zones served by the 3
AHU’s.
- P-lag lobby (EH Heat): Disable this back-up pump unless lead pump fails.
- P4 Add (EH Heat): Disable this 3-way valve pump if HCV<5%.
- DHW P (EH): Schedule to be off from midnight until 6:00am
- DHW St P (EH DHW): Schedule to be off from midnight until 5:30am
- Pond Pumps: Duty cycle (on 3 hours, off one hour) if OAT > 3C.
Please see the following separate graphs and charts that illustrate evidence of how measure was verified:
Completion date Feb 8 2012
Implementation cost $725
Projected energy and cost savings 8448 kWh and 0 kW, or $636
XXXX therms, or $XXXX
Non-energy impacts maintenance reductions
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
BC Hydro Final Report Template Page 13 of 46
© Copyright 2008 PECI
Measure Maintenance
Upon project completion, the recommended method for verifying that this measure is implemented
properly is :
the Annual and Weekly schedules should be checked in the DDC system;
after a statutory holiday, runtime logs for pump commands should be compared to the intended
schedules.
On a regular basis going forward, a Building Operator should review the unit status run times to ensure
that pump is not on too long.
3.5 Measure 5: Reduce Security 5 kW Resistance Warm-up
Overview
Measure
Reprogram such that heating mode is reset at start-up. Ensure that trend log and electric heat runtime log
remain active.
BC Hydro Final Report Template Page 14 of 46
© Copyright 2008 PECI
Please see the following separate graphs and charts that illustrate evidence of how measure was verified:
Completion date Oct 15 2012
Implementation cost $275
Projected energy and cost savings 760 kWh and 0 kW, or $57
XXXX therms, or $XXXX
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is code review and
review of DDC log 10TL24, and review of backup heat runtime log during cool weather.
BC Hydro Final Report Template Page 15 of 46
© Copyright 2008 PECI
3.6 Measure 6: F10 W Corridor MAT Decoupled from 3N RA
Overview
The west corridor AHU was found to control to an RTS not located within its zone. On Dec 13, 2011, we
put the exterior corridor's SAT on OAT reset as a stopgap measure.
The trend indicates an average OA temperature of 3.8C
Average MAT before 16.5
Average MAT after 20
Measure
The permanent solution involves the installation of the DDC RT sensor within the corridors.
Site review illustrated how measure was verified:
Completion date Dec 13 2011
Implementation cost $150
Projected energy and cost savings 22583 kWh and 0 kW, or $723
XXXX therms, or $XXXX
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
BC Hydro Final Report Template Page 16 of 46
© Copyright 2008 PECI
Measure Maintenance
Periodic review of trend logs of OAT, MAT, MAD, HCV and RT.
3.7 Measure 7: Repair AH2 Occupancy Sensor
Overview
Occupancy sensors were found to be sensing occupancy continuously. Digital inputs were incorrectly
"inverted" to normally closed. This defeated the pre-existing strategy that called for VFD to slow to 50%
when no one is present.
Measure
Inputs 10in 27 and 10in28 were corrected on Dec. 14, 2011 to reduce the amount of dry air being
admitted to the building Cold weather. This was done to reduce instances of ASHRAE AA alarms.
Program and trend review illustrated that the measure was verified:
Completion date Nov 16 2011
Implementation cost $90
Projected energy and cost savings 608 kWh and 0 kW, or $46
XXXX therms, or $XXXX
Non-energy impacts maintenance reductions
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is by periodic review
of trend log 7tl29 to ensure that the fan speed drops to 50% on a regular basis.
BC Hydro Final Report Template Page 17 of 46
© Copyright 2008 PECI
3.8 Measure 8 : Reduce Integral on SF4 (7con17)
Overview
Review of trend log 7tl24 revealed that the cooling demand controller had integral windup (and over-
reaction once fan started in the morning) causing low SAT at startup and over-cooling (which had to be
heated later).
Measure
The software controller was tuned in November 2011 to reduce the amount of dry economizer air, and
instances of ASHRAE AA alarms.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Nov 16 2012
Implementation cost $50
Projected energy and cost savings 3000 kWh and 0 kW, or $96
XXXX therms, or $XXXX
Non-energy impacts Improved comfort, artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
Periodic review of trend log 7tl24 to verify that AHU4 MAD is not opening in cool weather start-up,
only to cause heating later in the morning.
BC Hydro Final Report Template Page 18 of 46
© Copyright 2008 PECI
3.9 Measure 9: DDC Control AH5
Overview
All of the heat delivery associated with this unit is pneumatically controlled outside of the DDC system.
If any of the pneumatic zone reheat sensors or valves are either set too high, or an HCV has failed open,
the Space average temperature and RAT will affect the system control.
Simultaneous pneumatic heating and AHU chiller or free cooling can occur.
SAT set point set according to RTavg, can cause unnecessary cooling during heating season.
Night setback can be prevented.
SF-5 (AHU5) has DDC control of the fan and MAD. There is no heating coil on AHU5, only 6 zone
reheat coils:
1. Cafe
2. Shop
3. Clifford Carl Hall (in hallway by main wash rooms)
4. Pam’s office
5. Conference room next to Pam's office (this stat also controls the temperature for Tanya's space so
she is either too hot or too cold depending on how busy the conference room is).
6. John's cubicle.
There are three zone DDC temperature sensors:
MUS SF5-TEA-ROOM 7in59. Is in behind drinks fridge in cafeteria. This RT should be moved
to. Pillar inside cafeteria.
MUS-SF5-GIFT-SHOP-RT 7in27. Is next to entrance of gift shop off of Cliff Carl Hall.
MUS-SF5-ORIENT-RT 7in36 is next to security booth entrance inside Cliff Carl Hall. All points
where verified correct input points.
Cold weather review revealed that AHU5 was at 100% outside air and cooling coil was 100% open (there
was no chilled water at the time) - the system was trying to cool the SAT while the pneumatic terminals
were heating. The Property Management and Operations manager's office is fed from a 7" x 15 re-heat
coil in Boiler room. The Reheat coil was unable to meet the demand of the space due to the low SAT
(unnecessary cooling).
Control for AHU5 SAT had been in manual but was released to auto and based on both space temperature
and OAT.
If any of the RT's, MAT, RAT, SAT, OAT and C02 are out of calibration, the SAT will be inappropriate,
affecting the comfort in the spaces and the ability for the zone reheat's to heat the SA .
BC Hydro Final Report Template Page 19 of 46
© Copyright 2008 PECI
Measure
DDC control of heat delivery in areas served by SF5. The following is suggested:
1. Relocate café room temp sensor for better sensing
2. Install new riser conduit from Panel 16 enclosure to mezzanine admin area
3. Install new room temp sensors in 3 offices (Pam, John and Tanya)
4. Install room temp sensor with override pushbutton in mezzanine conference room
5. Install CO2 sensor in conference room for demand controlled ventilation
6. Take DDC control of 6 existing heating coil control valves using electronic to pneumatic
transducers
7. Install supply air temp sensors downstream of heating coils
8. System programming and Graphics updates
9. Create trend logs of all RT’s, HCV’s, MAD, CCV, modes, etc.
10. Commissioning and testing of new points and software.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Aug 20 2012
Implementation cost $3500
Projected energy and cost savings 68282 kWh and 0 kW, or $2350
XXXX therms, or $XXXX
Non-energy impacts maintenance reductions
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is periodic trend
review to verify that
simultaneous heating and cooling are minimized
unoccupied setbacks are being achieved.
BC Hydro Final Report Template Page 20 of 46
© Copyright 2008 PECI
3.10 Measure 10: Raise 2N & 3N Gallery RT-SP from 20 to 21C
Overview
Half of the Exhibit Hall gallery area is humidified, dehumidified, reheated and controlled to ASHRAE
AA environmental standards (50% RH +/- 5%).
The RT set point had been 20C. This resulted in high cooling and dehumidifying loads throughout the
year for these low heat loss zones, and a great deal of poorly conditioned air was proven to infiltrate these
ASHRAE AA galleries.
Lobby RH sensor Calibration Dec 1 2011:
3rd
floor by elevator
39.6 RH hand held
39.0 RH DDC
1st floor by NG shop and escalator
38.8 RH Hand held
39.5 RH DDC
Measure
A change to the RTSP for 2N and 3N was made Dec 2011 (20 to 21C), which reduces need for cooling
At the same time, the setpoints for the entrance lobby, 2nd
floor and 3rd
floors only, were changed to 21.0
°C. Most of them had been set to 21.5 or 22 °C.
This should reduce the gallery air handlers having to both humidify and cool simultaneously during times
of dry air infiltration.
It should also reduce the need for electric heat in the lobby.
ZONE WAS AFTER DEC 6 11
2S 21.5 21
2N 20 21
3S 22 21
3N 20 21
2 GIFT 20 21
LOBBY 22 21
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Dec 7 2011
Implementation cost $50
Projected energy and cost savings 3679 kWh and 0 kW, or $277
Non-energy impacts maintenance reductions
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
BC Hydro Final Report Template Page 21 of 46
© Copyright 2008 PECI
Measure Maintenance
The recommended method for verifying that this measure is persisting is review of RT trend logs, and
discussion with Property Management and Operations.
3.11 Measure 11: Put Cool ‘Stat on 2nd East Electric Rm Fan
Overview
The transfer fan that cools the east electrical room on the 2nd
floor was sending well-conditioned (near
50% RH) air into the east corridor continuously. This aggravated the serious problem of condensation on
the large expanses of single pane glass, while adding to the load on AHU9 (2N).
Measure
A cooling t’stat was added in March 2012 to cycle the fan only when needed.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Mar 15 2012
Implementation cost $150
Projected energy and cost savings 1089 kWh and 0 kW, or $76
XXXX therms, or $XXXX
Non-energy impacts maintenance reductions
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
Periodic site review of t’stat function and set point.
BC Hydro Final Report Template Page 22 of 46
© Copyright 2008 PECI
3.12 Measure 12: Tune Gift HCV & MAD Controller
Overview
The Gift shop AHU has both supply and return fans totaling 8 HP. The unit was programmed such that
free cooling and heating frequently occurred at the same time (see below).
Measure
Reprogram these predominantly exterior zones:
SAT_SP = (18-(0.25*OAT))+( RTSP - HotZoneAVG·RT ) * 2.25
Limit: 13C to 30C
MAT-SP = (SAT-SP – 1).
Use one simple controller to eliminate simultaneous heating and cooling. Controller 0 to 49= HVC at min
OAD; 50 to 100= economizer, then mechanical cooling (if it exists).
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
BC Hydro Final Report Template Page 23 of 46
© Copyright 2008 PECI
Completion date Oct 15 2012
Implementation cost $180
Projected energy and cost savings 23923 kWh and 0 kW, or $766
XXXX therms, or $XXXX
Non-energy impacts Improved comfort, artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
Periodic review of trend logs for Opt Start input, SAT_SP, HCV and damper positions, and verify
operation is in accordance with sequence intent.
3.13 Measure 13: Better Control Exhibits Reheat
Overview
Most Exhibit Hall perimeter radiation systems and reheat coils are not under the control of the building
DDC system. This applies to 23 HCVs.
Simultaneous pneumatic heating and AHU chiller or free cooling can occur.
SAT set point set according to RTavg, can cause unnecessary cooling during heating season.
Night setback can be prevented.
Measure
DDC conversion of
SF3 coils (6 largest coils out 8),
SF1 coils (7),
perim rad HCV (2)
= 15 HCV EPTs and 10 RTS
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Nov 20 2012
Implementation cost $29225
Projected energy and cost savings 84000 kWh and 0 kW, or $2688
Non-energy impacts Improved comfort, artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
BC Hydro Final Report Template Page 24 of 46
© Copyright 2008 PECI
Measure Maintenance
Upon project completion, the recommended method for verifying that this measure is implemented
properly is to site verify HCVs stroking and full closure at 0%, and review trend logs for good control
and operation as per design intent.
3.14 Measure 14: Use SF-8 & 11 Humidifiers
Overview
The trend graph below indicates that the new electric steam humidifiers in 3N (111 kW) are
unintentionally maintaining excellent conditions in 3S. 2N humidity is also well maintained.
It has been determined that over-pressure in the old south galleries adds humidification loads to the new
galleries.
The old galleries have passive (wetted media) humidifiers that have been decommissioned, and which
could take some of the unintended load of the electric humidifiers.
BC Hydro Final Report Template Page 25 of 46
© Copyright 2008 PECI
Measure
Re-Cx SF8 and 11 wetted media humidifiers.
Use pulse control of city water control valve to cycle full open for 20 seconds and off for 180 seconds on
a call for humidity.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Nov 29 2012
Implementation cost $180
Projected energy and cost savings 10642 kWh and 1 kW, or $1033
XXXX therms, or $XXXX
Non-energy impacts Improved comfort, artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is periodic review of
the 2N and 3N relative humidity trends, and site review of the old wetted media humidifiers operation.
3.15 Measure 15: Retrofits 15,16,17 –
Reductions on Existing Speed Drives
Overview
AHUs 4,8,11 and 12B had pre-existing adjustable speed drives (ASDs). It was determined that average
speeds could be marginally reduced.
Measure
AHUs
4 : Reduce from 77% to 72%
8 : Reduce from 82% to 75%
11: Reduce from 60% to 55%
12B (RF only): Reduced from 75% to 60%.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
BC Hydro Final Report Template Page 26 of 46
© Copyright 2008 PECI
Completion date Nov 11 2011
Implementation cost $680
Projected energy and cost savings 18221 kWh and 0 kW, or $1140
XXXX therms, or $XXXX
Non-energy impacts Improved artefact preservation &
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is periodic review of
the fan speed trend logs.
BC Hydro Final Report Template Page 27 of 46
© Copyright 2008 PECI
3.16 Measure 16: Retrofit 18 - E+ Boiler HSWT-SP
Overview
The current SWT setpoint is reset based on OAT as follows:
OAT Setpoint
0 82
20 25
BUT this limited to a minimum value of 50°C (the remark in the code indicates that this was added due to
AHU-9’s reheat requirements). As such, there are potential savings in dropping this limiting factor or
dynamically changing it based on AHU-9’s HCV position (or others).
50C = 122F min HSWT
GPM is very high with this system, and TD is low.
Reduced water temperatures should result in reduced parasitic heat loss throughout all 3 buildings.
Measure
Reduce 82C to 76C; Pole HCV's and add demand influence to the OA reset strategy. Pay special
attention to AH9 reheat in summer.
If OAT>16, and AHU9 reheat = 0, then boiler & pumps off.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Sep 15, 2012
Implementation cost $725
Projected energy and cost savings 44800 kWh and 0 kW, or $1542
XXXX therms, or $XXXX
Non-energy impacts Improved comfort, artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is periodic review of
HSWT trends and boiler Pulse meter.
BC Hydro Final Report Template Page 28 of 46
© Copyright 2008 PECI
3.17 Measure 17: Retrofit 19, 20, 21 – New Speed Drives
Overview
AHUs 4,8,11 and 12B had pre-existing adjustable speed drives (ASDs). It was determined that average
speeds could be marginally reduced.
Measure
AHUs
3 : Reduce from 100% to 80%
7 : Reduce from 100% to 85%
EF-WR: Reduce from 100% to 60%
SF Entrance: Reduced from 100% to 83%.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Oct 15, 2012 (increased Jan 2013)
Implementation cost $14200
Projected energy and cost savings 91888 kWh and 0 kW, or $11273
XXXX therms, or $XXXX
Non-energy impacts Improved artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is periodic review of
the fan speed trend logs.
BC Hydro Final Report Template Page 29 of 46
© Copyright 2008 PECI
3.18 Measure 18: Retrofit 22 - New AC Unit for AV Rm
Overview
The AV Area is a small portion of the basement that served by AHU-1 in Rm 026. Average RT is always
high due to A/V internal load
The Wood Shop is also on AH1, but is always cold – due to the AH free cooling required for the AV area.
Measure
Provide a new 2 ton split cassette heat pump.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Sep 15 2012
Implementation cost $8500
Projected energy and cost savings 14900 kWh and -2 kW, or $20
XXXX therms, or $XXXX
Non-energy impacts Improved comfort, artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
BC Hydro Final Report Template Page 30 of 46
© Copyright 2008 PECI
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is periodic review of
the SF2 runtime log.
3.19 Measure 19: Retrofit 23 -Allow SF8 MAD to Open Past 50%
Overview
SF8 OAD has been limited to 50% opening since the removal of SF-9. Plant chiller (not on RBCM meter)
likely has to provide more cooling as a result.
Measure
Reprogram OAD to allow full opening in free cooling.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Nov 15 2012
Implementation cost $90
Projected energy and cost savings 0 kWh and 0 kW, or $0
XXXX therms, or $XXXX
Non-energy impacts Improved comfort, artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is periodic review of
the SF8 MAD and MAT trends during mild weather.
BC Hydro Final Report Template Page 31 of 46
© Copyright 2008 PECI
3.20 Measure 20: Retrofit 24 - Allow Ch-12 on at Lower OAT
Overview
When Ch12 was locked out in cool (dry) weather, the economizer brought in dry air and caused
humidifier to work at max. With chiller enabled during a test, the control system chose humid RA for net
energy savings.
Measure
Allow the chiller to run down to design winter conditions. This measure was implemented Nov 16, 2011
in support of the gallery’s ASHRAE AA environmental requirements.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Nov 15 2011
Implementation cost $50
Projected energy and cost savings 1808 kWh and 0 kW, or $136
XXXX therms, or $XXXX
Non-energy impacts Improved artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is periodic review of
the chiller and OAD trends during cold weather and 3TL40/41.
BC Hydro Final Report Template Page 32 of 46
© Copyright 2008 PECI
3.21 Measure 21: Retrofit 25 - Summer Purge for AH1-5
Overview
Use free cooling form cool outdoor air on warm summer nights. Central plant chiller savings will not
appear on the RBCM Hydro meters.
Measure
Run the AHUs in warm areas
Pre-cool or Purge mode is provided on normally occupied days during early morning (typically 3:00 –
6:00 AM) when space temperature exceeds 23°C and outdoor air temperature is < 19°C. Pre-cool is also
limited to operation only from May 1 to Oct 1. Warm-up mode is disabled whenever purge mode is
executed. Pre-cool fan is cycled off if RTavg < 22C.
Pre-cool for fans with VFDs to be at 55% speed to benefit from fan law savings
EF's to also be enabled at low speed.
Create runtime log for purge mode.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Cancelled due to cost
Implementation cost $XXXX
Projected energy and cost savings
Non-energy impacts
Contact information for
Implementer/Contractor
Measure Maintenance
The recommended method for verifying that this measure is periodic review of AHU and mode runtime
logs during hot summer. Ensure that mode does not run in cool weather.
BC Hydro Final Report Template Page 33 of 46
© Copyright 2008 PECI
3.22 Measure 22: Retrofit 26 -Reduce Fannin WR EF9 Run Hours
Overview
The Fannin fan unit that presently has DDC enable is EF8 (0.33hp) which is erroneously labeled
“washrooms”. The fan that actually serves the washrooms is EF-9 which is substantially larger (3 hp).
This unit should be connected through the DDC to go off overnight on a weekly schedule.
Measure
Provide a DDC relay and current transformer.
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
Completion date Nov 15 2011
Implementation cost $2200
Projected energy and cost savings 11000 kWh and 0 kW, or $828
XXXX therms, or $XXXX
Non-energy impacts Improved artefact preservation
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is periodic review of
the EF9 runtime log.
BC Hydro Final Report Template Page 34 of 46
© Copyright 2008 PECI
3.23 Measure 23: Retrofit 27 - General Maintenance
Overview & Recommendations
UNIT LOCATION RECOMMENDATION
AH1 EH026 Dampers require cleaning & lubrication
MAT single point sensors reloation/replacement recommended
AH2 EH026 Dampers require cleaning & lubrication
MAT single point sensors reloation/replacement recommended
Heating & cooling coils need cleaning
AH3 EH026 Dampers require cleaning & lubrication
MAT single point sensors reloation/replacement recommended
AH4 EH026 Dampers require cleaning & lubrication
MAT single point sensors reloation/replacement recommended
AH5 EH026 Dampers require cleaning & lubrication
EH026 MAT single point sensors reloation/replacement recommended
AH7 EH Bsmt Dampers require cleaning & lubrication
SF8 M200 Dampers require cleaning & lubrication
Intake cleaning recommended
SF11 M300 Dampers require cleaning & lubrication
Intake cleaning recommended
Fannin Bsmt Dampers require cleaning & lubrication
Adjust damper linkage
Reheat coil requires cleaning
Intake cleaning recommended
Archives Roof Dampers require cleaning & lubrication
Intake cleaning recommended
Please see separate PDF files of graphs and charts that illustrate evidence of how measure was verified.
BC Hydro Final Report Template Page 35 of 46
© Copyright 2008 PECI
Completion date July 20 2012
Implementation cost $7500
Projected energy and cost savings 16321 kWh and 0 kW, or $562
XXXX therms, or $XXXX
Non-energy impacts Improved artefact preservation,
maintenance
Contact information for
Implementer/Contractor
Houle Controls , Joe LeRoy, 250 388
5665 ([email protected]) Victoria
Measure Maintenance
The recommended method for verifying that this measure is implemented properly is site and trend log
review.
BC Hydro Final Report Template Page 36 of 46
© Copyright 2008 PECI
4.0 Updated Building Documentation
Building documentation in which updates were made based upon the optimization activities include, but
arenot limited to:
Facility drawings: Avalon provided as-built record drawings for Exhibit Hall reheat coils, AHU zoning,
and for Fannin system schematics. These were used to produce the DDC Graphics that are now in place
for the complex:
• Heating and chilled water hydronics
• AHU5
• Lobby AH1
• AH8
• AH9
• AH 12a & b
• Gift Shop
• Cor HP1 & 2
• Wet Lab
No changes were made to the O&M manuals.
Sequences of operation were provided to the Facilities Dept.and reflect changes or additions to control
strategies and sequences of operation.
Lists of remaining issues were compiled and presented to the RBCM at the Training Session.
BC Hydro Final Report Template Page 37 of 46
© Copyright 2008 PECI
BC Hydro Final Report Template Page 38 of 46
© Copyright 2008 PECI
ATTACHMENT A: Implementation Summary Table
[See Finding Workbook’s “Implementation Summary Table” tab. Select and paste table below and modify as needed.]
# Measure
Estimated Annual Electric Usage
Savings (kWh)
Estimated Annual Electric Usage
Savings ($)
Estimated
Annual Electric Deman
d Saving
s ($)
Estimated Annual
Gas Savings
(GJ)
Estimated Annual
Gas Savings
($)
Estimated Annual
Total Savings
($)
Estimate Implementation
Cost ($)
Simple Payback (years)
Measure life
(years) NPV ($)
IRR (%)
Description of Finding
Implementer
Recommendations for
Implementation
Recommended Evidence of
Implementation Method
Implement without
incentives as part of <2 year simple
payback bundle? (Y or N)
1 Add line of code requiring chiller status to allow pump to run
161 $12 $0 0 $0 $12 $50 4.1 5.0 $ 6
24% Archives Bldg ChW pumps was sometimes on when chiller was off.
DDC contractor
define scope; obtain quote; approve implementation; review
review of code and run time log
Y
2 Convert larger pneu zones to DDC: stacks (6 coils), and Coil 18, 2 coils in public area = 9 HCV EPTs and 9 RTS
16,800 $538 $0 0 $0 $538 $9,550 17.8 5.0 $ (7,088) 6% Most perimeter radiation systems and reheat coils are not under the control of the building DDC system.Simultaneous pnuematic heating and AHU chiller or free cooling can occur. SAT set point set according to ~ RTavg, can cause unnecessary cooling during heating season
DDC contractor
define scope; obtain quote; approve implementation; review
review of new points, code and trend logs
Y
3 Reduce weekly and annual schedules where possible
88,161 $6,636 $0 0 $0 $6,636 $700 0.1 5.0 $ 29,692 948% Units listed in doc file are running for longer periods that required.
DDC contractor
define scope; obtain quote; approve implementation; review
Review of code and run time logs
Y
4 Reduce weekly and annual schedules where possible
8,448 $636 $0 0 $0 $636 $100 0.2 5.0 $ 2,812
636% Units listed in doc file are running for longer periods that required.
DDC contractor
define scope; obtain quote; approve implementation; review
Review of code and run time logs
Y
5 reset heating mode at start-up (keep resist ht off)
760 $57 $0 0 $0 $57 $300 5.2 5.0 $ (38)
19% HP being off at night causes resistance heat to come on each morning
DDC contractor
define scope; obtain quote; approve implementation; review
Review of code and run time logs
Y
6 put a RTS in the west corridor, and control heating valve accordingly
22,583 $723 $0 0 $0 $723 $0 0.0 5.0 The west corridor AHU was found to control to an RTS not located withing its zone
DDC contractor
define scope; obtain quote; approve implementation; review
Site review & trend review
Y
BC Hydro Final Report Template Page 39 of 46
© Copyright 2008 PECI
# Measure
Estimated Annual Electric Usage
Savings (kWh)
Estimated Annual Electric Usage
Savings ($)
Estimated
Annual Electric Deman
d Saving
s ($)
Estimated Annual
Gas Savings
(GJ)
Estimated Annual
Gas Savings
($)
Estimated Annual
Total Savings
($)
Estimate Implementation
Cost ($)
Simple Payback (years)
Measure life
(years) NPV ($)
IRR (%)
Description of Finding
Implementer
Recommendations for
Implementation
Recommended Evidence of
Implementation Method
Implement without
incentives as part of <2 year simple
payback bundle? (Y or N)
7 Set sensor switches properly
608 $46 $0 0 $0 $46 $0 0.0 5.0 Occ sensor intended to reduce fan speed was not hardware configured properly
DDC contractor
define scope; obtain quote; approve implementation; review
VFD trend review
Y
8 Tune controller (done Nov 2011)
3,000 $96 $0 0 $0 $96 $50 0.5 5.0 $ 390
192% Integral windup while AHU off at night was causing low SAT at startup and over-cooling
DDC contractor
define scope; obtain quote; approve implementation; review
MAD and SAT trend review
Y
9 Take control of non-DDC heating
68,282 $2,350 $0 0 $0 $2,350 $3,500 1.5 5.0 $ 7,261
67% SAT-SP found to be in manual - 15 in warm weather; 17 on Dec 1st; When released on Dec 7th, SAT varied between 14 and 19 C
DDC contractor
define scope; obtain quote; approve implementation; review
review of new points, code and trend logs
Y
10 Raise RT set point (done)
3,679 $277 $0 0 $0 $277 $50 0.2 5.0 $ 1,218
554% Two large high cooling galleries had Rm Temp set points of 20C
DDC contractor
define scope; obtain quote; approve implementation; review
Review of RT-SP
Y
11 Put cooling stat on Transfer Fan
1,089 $76 $0 0 $0 $76 $150 2.0 5.0 $ 199
51% Elect room transfer fan was on 24/7 (increasing condensation on east hall windows)
DDC contractor
define scope; obtain quote; approve implementation; review
Site observation Y
12 Use one simple controller to eliminate simultaneous heating and cooling. Controller 0 to 49= HVC at min OAD; 50 to 100= economizer, then mechanical cooling (if it exists).
23,923 $766 $0 0 $0 $766 $2,000 2.6 5.0 $ 1,506
38% AHU was found to heat and cool at the same time
DDC contractor
define scope; obtain quote; approve implementation; review
trend review Y
13 Convert SF5 coils (6), SF1 coils (7), preim rad HCV (2) = 15 HCV EPTs and 10 RTS
84,000 $2,688 $0 0 $0 $2,688 $16,800
6.3 5.0 $ (4,490)
16% Most perimeter radiation systems and reheat coils are not under the control of the building DDC system.Simultaneous pnuematic heating and AHU chiller or free cooling can occur. SAT set point set according to ~ RTavg, can cause unnecessary cooling during heating season
DDC contractor
define scope; obtain quote; approve implementation; review
review of new points, code and trend logs
Y
BC Hydro Final Report Template Page 40 of 46
© Copyright 2008 PECI
# Measure
Estimated Annual Electric Usage
Savings (kWh)
Estimated Annual Electric Usage
Savings ($)
Estimated
Annual Electric Deman
d Saving
s ($)
Estimated Annual
Gas Savings
(GJ)
Estimated Annual
Gas Savings
($)
Estimated Annual
Total Savings
($)
Estimate Implementation
Cost ($)
Simple Payback (years)
Measure life
(years) NPV ($)
IRR (%)
Description of Finding
Implementer
Recommendations for
Implementation
Recommended Evidence of
Implementation Method
Implement without
incentives as part of <2 year simple
payback bundle? (Y or N)
14 Re-Cx 2 passive humidifiers in AHUs
10,642 $917 $116 0 $0 $1,033 $100 0.1 5.0 $ 4,632 1033%
Passive drip humidifiers had been decommissioned, causing increased load on electric humidifiers
DDC contractor
define scope; obtain quote; approve implementation; review
Site review Y
15 Reduce RF speed (done)
2,919 $220 $0 0 $0 $220 $50 0.2 5.0 $ 956
439% High RF speed was increasing the short circuiting of highly conditioned S/A into return air grill (before it could impact the space)
DDC contractor
define scope; obtain quote; approve implementation; review
VFD trend review
Y
16 Reduce AH4 speed by avg 5%
2,923 $220 $0 0 $0 $220 $100 0.5 5.0 $ 908
220% CFM per sq ft is high. DDC contractor
define scope; obtain quote; approve implementation; review
VFD trend review
Y
17 Reduce AH speeds by avg 5%
12,379 $700 $0 0 $0 $700 $400 0.6 5.0 $ 2,806 175% Highly variable load in zone with somewhat arbitrary min speed s (80 and 60%).
DDC contractor
define scope; obtain quote; approve implementation; review
VFD trend review
Y
18 Lower reset schedule; allow cooler summer SWT; turn boiler & pumps off if OAT high and AH9 does not need reheat
44,800 $1,542 $0 0 $0 $1,542 $200 0.1 5.0 $ 6,860 771% Very high flow with low TD. HSWT high, and reset schedule limited to 50C in summer
DDC contractor
define scope; obtain quote; approve implementation; review
Review of code and trends
Y
19 Install VFD 18,326 $1,379 $0 0 $0 $1,379 $5,750 4.2 5.0 $ 568
24% Simple unoccupied single zone system with high perimeter loads runs at constant speed
DDC contractor
define scope; obtain quote; approve implementation; review
review of new points, code and trend logs
Y
20 Install VFD (done) 18,821 $1,417 $0 0 $0 $1,417 $1,750 1.2 5.0 $ 4,738 81% Very high volume EF brings extra unconditioned air that adds heat, cool, dehum and humidification loads - particularly to ASHRAE areas
DDC contractor
define scope; obtain quote; approve implementation; review
review of new points, code and trend logs
Y
21 Install VFD (done) 54,741 $8,477 $0 0 $0 $8,477 $11,000
1.3 5.0 $ 27,822 77% AHU SF was much higher than design and RF volume. It was pressurizing lobby and adding heat, cool, dehum and humidification loads - particularly to ASHRAE areas
DDC contractor
define scope; obtain quote; approve implementation; review
review of new points, code and trend logs
Y
BC Hydro Final Report Template Page 41 of 46
© Copyright 2008 PECI
# Measure
Estimated Annual Electric Usage
Savings (kWh)
Estimated Annual Electric Usage
Savings ($)
Estimated
Annual Electric Deman
d Saving
s ($)
Estimated Annual
Gas Savings
(GJ)
Estimated Annual
Gas Savings
($)
Estimated Annual
Total Savings
($)
Estimate Implementation
Cost ($)
Simple Payback (years)
Measure life
(years) NPV ($)
IRR (%)
Description of Finding
Implementer
Recommendations for
Implementation
Recommended Evidence of
Implementation Method
Implement without
incentives as part of <2 year simple
payback bundle? (Y or N)
22 Install smal AC unit to allow warmer AHU MATs
14,090 $253 -$232 0 $0 $20 $7,500 369.2 10.0 $ (7,327)
0% Small AV room causes large AHU to cool when the rest of the basement does not require it
DDC contractor
define scope; obtain quote; approve implementation; review
Review install, AHU code and trends
Y
23 Release OAD to open fully
0 $0 $0 0 $0 $0 $200 5.0 $ (200)
Free cooling capacity if AHU is limited (as result of half served area being removed)
DDC contractor
define scope; obtain quote; approve implementation; review
trend review Y
24 Re-program: If OA dew point < 3C, Close OAD and cool with chiller when building occupied (9:45 to 17:15)
1,808 $136 $0 0 $0 $136 $50 0.4 5.0 $ 573
272% When Ch12 locked out in cool weather, econo brought in dry air and caused humidifier to work at max.
DDC contractor
define scope; obtain quote; approve implementation; review
Trend & runtime review
Y
25 free cool during nite during hot weather
0 $0 $0 0 $0 $0 0 0 )
26 add DDC relay and weekly schedule
11,000 $828 $0 0 $0 $828 $700 0.8 5.0 $ 3,092 118% Fan found to run 24/7 DDC contractor
define scope; obtain quote; approve implementation; review
review of new points, code and trend logs
Y
27 refurbish, clean and lube
16,321 $562 $0 0 $0 $562 $7,450 13.3 2.0 $ (6,375)
8% Dirty coils, stuck dampers, bad seals, lonkages not set
Mech contractor
define scope; obtain quote; approve implementation; review
Site review and trend review
Y
530,264 $ 31,550 $ (116) 0 $ -
$ 31,434
$ 68,500 2.2
BC Hydro Final Report Template Page 42 of 46
© Copyright 2008 PECI
BC Hydro Final Report Template Page 43 of 46
© Copyright 2008 PECI
ATTACHMENT B: Training Outline
Training Outline
The Commissioning Provider (C.Op Provider) is responsible for customizing the outline for the training
and developing the training materials. Before preparing the training outline and materials, the C.Op
Provider should assess the related level of knowledge of the building operators, to set up the training
accordingly. For reference, the Program provides the following sample outline for the training:
Background on the energy use of this particular building
o Present Energy Utilization Index
o Describe Operating Schedules and Owner’s operating requirements
RCx investigation process used in this building
o Describe the methods used to identify problems and deficiencies
o Review the Master List of Findings Summary
Implementation process in this building
o Describe the measures that were implemented and by whom
o Walk around the building to look at any physical changes or step through the new control
sequences at the operator workstation
o Provide as many details about implementation as necessary to describe what was done
o Describe improved performance that these measures will create (show trends if available)
O&M requirements
o Describe the O&M requirements needed to keep these improvements working
o Describe how the staff can be aware of energy efficiency opportunities and begin looking
for additional savings potential
The C.Op Provider should follow the outline to prepare materials, as necessary, to hand out at the training
session.
BC Hydro Final Report Template Page 44 of 46
© Copyright 2008 PECI
ATTACHMENT C: Training Completion Form
Program Use Only Project ID
Facility Information
Company
Name
THE ROYAL BC
MUSEUM
CORPORATION
Building Name(s)
Exhibit Hall
Fannin Curatorial Tower
Archives
Facility
Address 675 BELLEVILLE
STREET City VICTORIA Province BC
Postal
Code V8W 9W2
Mailing
Address City Province
Postal
Code
Training Details
Location RBCM Date Jan 31 2013
Commissioning
Provider/Trainer Bob Landell
Materials Attached
Agenda
Materials used for training
List of individuals who attended
COMMISSIONING PROVIDER SIGNATURE
By signing this Training Completion Form, I verify that this training took place with the listed attendees.
Commissioning Provider (print name): Bob Landell
Signature: Date: Jan 31 2013
FACSIMILE/SCANNED SIGNATURES: Facsimile transmission of any signed original document, and the retransmission of
any signed facsimile transmission, shall be the same as delivery of the original signed document. Scanned original documents
transmitted to BC Hydro as an attachment via electronic mail shall be the same as delivery of the original signed document. At
the request of BC Hydro, C.Op Provider shall confirm documents with a facsimile transmitted signature or a scanned signature
by providing an original document.
BC Hydro Final Report Template Page 45 of 46
© Copyright 2008 PECI
Targeted Documentation
O & M Manual
O & M Manual updated Describe updates below and attach copies of new or
amended portions
O & M Manual not updated Province reasons below
Building has no O & M Manual
Building Plans (“as-builts”)
Building Plans updated Describe below
Wiring diagrams updated Describe below
No plans or diagrams updated Describe below
The DDC system had very limited graphics prior to the recent DDC upgrades. Graphics are now in place for the
complex heating and chilled water hydronics, AHU5, lobby AH1, AH8, AH9, AH 12a & b, Gift Shop, Cor HP1 &
2, Wet Lab. This is a highly valuable upgrade for RBCM operations.
EMS Programming
New sequences of operation on file Specify location of file and attach copy
Printed screenshots on file Specify location of file and attach copy
Optional cost is pending approval for update of complicated ASHRAE AA temp, dew point and RH programming.
General C.Op Sequences and verification trends have been submitted to RBCM (RBCM Con Op DDC Software Seq
Op.docx). Tanya Duce maintains the records.
Equipment Manuals
Manuals for new equipment are on file Describe below (attach copy if applicable)
N/A
BC Hydro Final Report Template Page 46 of 46
© Copyright 2008 PECI
Checklist of subjects discussed at training
Explain investigation process and how measures were identified
Describe implemented measures, and how they are reducing energy usage
Building walkthrough to show implemented measures
Describe methods for monitoring and maintaining optimum system performance related to implemented
measures
Describe scenarios where system setting changes would be required, and how to maintain optimum
energy efficiency, e.g., seasonal-based manual adjustments to setpoints.
List of Individuals Who Attended
Name Title Building (address or name) Contact information (e-mail
and/or phone number)
Tanya Duce Facilities Operator RBCM 250 387 3007
Cameron Holt Maint Personnel RBCM 250 893 1261
Steve Brame Maint Personnel RBCM 250 893 2192