VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard- Pressure, Standard-Temperature Butterfly Valves Product Bulletin 1 VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves are designed specifically for a wide range of Heating, Ventilating, and Air Conditioning (HVAC) applications including two-position and modulating control of hot, chilled, or condenser water, and 50/50 glycol solutions. These valves are also bidirectional, allowing positive shutoff with the flow in either direction. Two-way configurations are available in sizes from 2 through 6 in. for M9000 Electrically Actuated, and 2 through 10 in. for D-3000 Pneumatically Actuated assemblies. Three-way assemblies have two valves that are linked together and mounted on a flanged, cast-iron tee. Three-way configurations are available in sizes from 2 through 6 in. for M9000 Electrically Actuated and 2 through 8 in. for D-3000 Pneumatically Actuated assemblies. M9000 Electrically Actuated models are available with or without a rugged, factory-installed weather shield. M9000 Electrically Actuated non-spring return, non-weather shield models feature an integral handle for manual positioning of the valve, independent of a power supply. Figure 1: VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Table 1: Features and Benefits Features Benefits Low Seating/Unseating Torques Reduce actuator torque and size requirements, particularly with lower pressure rated valves. Bubble-Tight Shutoff Provides positive closure when needed. PreAssembled Actuators Reduce assembly costs. Compatible with All Types of ANSI 125/150 Slip-On and Weld-Neck Flanges Allows configuration in the field, with readily available standard fittings. M9000 Electric Actuators Available with or without a Rugged, Factory-Installed Weather Shield Provide protection from the elements in outside applications. M9000 Electric Actuators Available with or without End Switches Provide adjustable switch points for positive indication or operation of auxiliary equipment. D-3000 Pneumatic Actuators Available with or without a Pneumatic Positioner Provide precise valve positioning. VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin Code No. LIT-977202 Issued May 7, 2007 Supersedes January 26, 2005

Transcript of VF Series M9000 Electrically and D-3000 Pneumatically … · 2013-08-06 · VF Series M9000...

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesProduct Bulletin Code No. LIT-977202

Issued May 7, 2007Supersedes January 26, 2005

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves are designed specifically for a wide range of Heating, Ventilating, and Air Conditioning (HVAC) applications including two-position and modulating control of hot, chilled, or condenser water, and 50/50 glycol solutions. These valves are also bidirectional, allowing positive shutoff with the flow in either direction.

Two-way configurations are available in sizes from 2 through 6 in. for M9000 Electrically Actuated, and 2 through 10 in. for D-3000 Pneumatically Actuated assemblies. Three-way assemblies have two valves that are linked together and mounted on a flanged, cast-iron tee. Three-way configurations are available in sizes from 2 through 6 in. for M9000 Electrically Actuated and 2 through 8 in. for D-3000 Pneumatically Actuated assemblies.

M9000 Electrically Actuated models are available with or without a rugged, factory-installed weather shield. M9000 Electrically Actuated non-spring return, non-weather shield models feature an integral handle for manual positioning of the valve, independent of a power supply.

Figure 1: VF Series M9000 Electrically and D-3000 Pneumatically Actuated

Standard-Pressure, Standard-Temperature Butterfly Valves

Table 1: Features and BenefitsFeatures BenefitsLow Seating/Unseating Torques Reduce actuator torque and size requirements, particularly with lower

pressure rated valves.

Bubble-Tight Shutoff Provides positive closure when needed.

PreAssembled Actuators Reduce assembly costs.

Compatible with All Types of ANSI 125/150 Slip-On and Weld-Neck Flanges

Allows configuration in the field, with readily available standard fittings.

M9000 Electric Actuators Available with or without a Rugged, Factory-Installed Weather Shield

Provide protection from the elements in outside applications.

M9000 Electric Actuators Available with or without End Switches

Provide adjustable switch points for positive indication or operation of auxiliary equipment.

D-3000 Pneumatic Actuators Available with or without a Pneumatic Positioner

Provide precise valve positioning.

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

1

Application OverviewAll VF Series Standard-Pressure, Standard-Temperature Valves are available with a factory-assembled M9000 Series Electric Actuator or D-3000 Series Pneumatic Actuator, to provide years of trouble-free operation. The valve and actuator can be provided in Normally Open (N.O.) or Normally Closed (N.C.) combinations for two-way operation. Three-way valves are available in four mounting styles to meet all possible piping layouts. These butterfly valves have an inherent modified equal percentage relationship between disk rotation and flow at a constant pressure drop (as illustrated in Figure 2).

The valve body is cast iron and meets the temperature and pressure requirements for ANSI Class 125 B16.1 Class B pipe flanges. The valve neck is extended to allow for 2 in. (51 mm) of insulation as well as easy access to the actuator. All valve sizes are fully lugged.

The resilient seat of VF Series M9000 Electrically Actuated or D-3000 Series Pneumatically Actuated Standard-Pressure, Standard-Temperature Valves is molded from Ethylene Propylene Diene Monomer (EPDM). The disk is constructed of aluminum bronze, and the stem is 416 stainless steel.

The flow characteristics of VF Series M9000 Electrically Actuated or D-3000 Series Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves are illustrated in Figure 2. Inherent flow characteristics are modified equal percentage.

Figure 2: Modified Equal Percentage Valve Flow Characteristics

100

90

80

70

60

50

40

30

20

10

00 10 20 30 40 50 60 70 80 90 100

Percent of Valve Opening

Per

cent

of F

low

Actual Flow Curve(Modified Equal

Percentage)

EqualPercentageFlow Curve

FIG

:MEP

VFC

Table 2: Valve Flow Coefficients, Cv (kv)Valve Size, in.

Disk Position, Degrees Open1

90° Maximum Stroke for Valves with M9000 Electric Actuators

80° 70°Maximum Stroke for Valves with D-3000 Pneumatic Actuators

60° 50° 40° 30° 20°

2 159 135 105 70.6 44.5 26.3 14.2 4.06

2-1/2 266 215 156 140 65.3 38.6 20.9 6.17

3 457 342 240 156 98.0 57.9 31.4 13.6

4 860 625 423 274 173 102 55.1 23.9

5 1,320 970 656 426 268 158 85.6 37.2

6 2,020 1,420 941 610 384 227 123 53.3

8 3,540 2,500 1,660 1,080 679 401 217 94.3

10 5,580 3,830 2,560 1,660 1,040 617 334 145

1. Recommended disk rotation is between 30° and 70° open for proportional control; preferred disk rotation for control valve sizing is 50° to 70° open.

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

2

Product GuidelinesPlease be sure to read the following information carefully before installing a VF Series M9000 Electrically Actuated or D-3000 Series Pneumatically-Actuated Standard-Pressure, Standard-Temperature Butterfly Valve Assembly.

• Be sure that the pipeline and flange faces are clean. Pipe scale, metal chips, weld slag, and weld rods can obstruct disk movement and damage the disk and seat.

• The resilient seat of the valve is equipped with molded O-rings on the face of the seat; do not use gaskets.

• The valves should be handled by the extended valve neck only. Heavier valves may require a nylon sling to be used as a hoist around the valve neck and/or cast-iron tee (on three-way assemblies). Never pick up a valve by the actuator, mounting bracket, or interconnecting linkage.

• Most VF Series M9000 Electrically Actuated or D-3000 Series Pneumatically-Actuated Standard-Pressure, Standard-Temperature Butterfly Valve Assemblies are shipped with the disk in the near-closed position (approximately 10 degrees open).

For proper actuator wiring and commissioning, refer to the following documents:

• M9108, M9116, M9124, and M9132 Series Electric Non-Spring Return Actuators Installation Instructions (Part No. 34-636-399)

• M9220-AGx-3 Floating Electric Spring Return Actuators Installation Instructions (Part No. 34-636-1689)

• M9220-Bxx-3 On/Off Electric Spring Return Actuators Installation Instructions (Part No. 34-636-1239)

• M9220-GGx-3 Proportional Electric Spring Return Actuators Installation Instructions (Part No. 34-636-1697)

Table 3: Cv Correction Factor - Two-Way and Three-Way – 90° Fully OpenValve Size, in.

Pipe Size, in.2 2-1/2 3 4 5 6 8 10 12 14

2 159 140 123 --- --- --- --- --- --- ---

2-1/2 --- 266 231 --- --- --- --- --- --- ---

3 --- --- 457 336 --- --- --- --- --- ---

4 --- --- --- 860 679 551 --- --- --- ---

5 --- --- --- --- 1,320 1086 776 --- --- ---

6 --- --- --- --- --- 2,020 1,484 1,202 --- ---

8 --- --- --- --- --- --- 3,540 2,811 2,287 ---

10 --- --- --- --- --- --- --- 5,580 4,612 3,768

Table 4: Cv Correction Factor - Two-Way and Three-Way – 70° (Modulating Applications)Valve Size, in.

Pipe Size, in.2 2-1/2 3 4 5 6 8 10 12 14

2 105 100 95 --- --- --- --- --- --- ---

2-1/2 --- 156 148 --- --- --- --- --- --- ---

3 --- --- 240 212 --- --- --- --- --- ---

4 --- --- --- 423 385 345 --- --- --- ---

5 --- --- --- --- 656 611 518 --- --- ---

6 --- --- --- --- --- 941 838 754 --- ---

8 --- --- --- --- --- --- 1,660 1,525 1,384 ---

10 --- --- --- --- --- --- --- 2,560 2,401 2,202

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

3

• D-3153 Pneumatic Actuator Product Bulletin (LIT-2681054P)

• D-3240 Series Pneumatic Piston Actuators Product Bulletin (LIT-2681055P)

SelectionUse Table 5 and Table 6 as a quick-reference for ordering a butterfly valve assembly and factory-mounted actuator. For more detailed information on standard valve and actuator assemblies (including flow coefficients), see Table 7 through Table 30.

Table 5: Ordering Data1

V F Butterfly

1 2 Valve

4 Disk Type/ 4 = Standard Disk Without Weather Shield

3 Actuator 5 = Standard Disk With Weather Shield

Enclosure 6 = Undercut Disk without Weather Shield

2 Body Type 2 = Two-Way, Normally Open (N.O.)

4 4 = Two-Way, Normally Closed (N.C.)

8 = Three-Way

3 Flange 3 = ANSI Class 125/150, Fully Lugged

5

1 Flow Characteristics

1 = Modified Equal Percentage

6

C Valve Size A = 2 in. (With Four Mounting Lugs)

7 B = 2-1/2 in. (With Four Mounting Lugs)

C = 3 in. (With Four Mounting Lugs)

D = 4 in. (With Eight Mounting Lugs)

E = 5 in. (With Eight Mounting Lugs)

F = 6 in. (With Eight Mounting Lugs)

G = 8 in. (With Eight Mounting Lugs)

H = 10 in. (With Twelve Mounting Lugs)

A Valve Style A = Two-Way

8 D = Three-Way, Style D2

E = Three-Way, Style E2

F = Three-Way, Style F2

G = Three-Way, Style G2

+ + = Factory-Mounted Actuator

9

Example: Two-way 3 in. ANSI Class 125/150 Valve1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 = Field

V F 4 2 3 1 C A +

Butterfly Valve Assembly

1. For a replacement valve body, configure the appropriate code number from the first eight fields in Table 5; the existing actuator-to-valve linkage will need to be reused.

2. See Figure 6 for three-way valve body styles.

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

4

Table 6: Ordering Data – Adding a Factory Mounted Actuator1

V F 4 2 3 1 C A + + = Factory-Mounted Actuator

1 2 3 4 5 6 7 8 9 2 = Tandem Actuators

9 1 6 Factory Mounted Electric Actuator

916 = M9116 Non-Spring Return

10 11 12 924 = M9124 Non-Spring Return

92N = M9220 Spring Return Open

94N = M9220 Spring Return Closed

G Control A = Floating

13 B = On/Off

G = Proportional with 0-10 VDC Feedback

G Voltage G = 24 VAC

14

C Auxiliary Switches

A = None

15 C = Two Auxiliary Switches

3 1 5 3 Factory Mounted Pneumatic Actuator

3153 = D-3153

10 11 12 13 3244 = D-3244

3246 = D-3246

P Accessories P= D-9502 Pneumatic Positioner

14 Blank = None

Example: Two-way normally open valve without weather shield, 3 in., with proportional, non-spring return electric actuator, 0 to 10 VDC feedback and two auxiliary switches

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 = Field

V F 4 2 3 1 C A + 9 1 6 G G C

Butterfly Valve Assembly

1. For a replacement valve body, configure the appropriate code number from the first eight fields in Table 5; the existing actuator-to-valve linkage will need to be reused. Refer to the appropriate actuator product bulletin for additional actuator details.

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

5

Two-Way Valve with M9000 Series Electric Actuator (Less Weather Shield)

Table 7: On/Off (Floating) Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (Less Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.

M91xx-AGA-2 without End Switches

M91xx-AGC-2 with Two End Switches

2 159 105 200 VF4231AA+916AGA VF4231AA+916AGC

2-1/2 266 156 200 VF4231BA+916AGA VF4231BA+916AGC

3 457 240 200 VF4231CA+916AGA VF4231CA+916AGC

4 860 423 200 VF4231DA+924AGA VF4231DA+924AGC

5 1320 656 50 VF4231EA+924AGA VF4231EA+924AGC

5 1320 656 200 VF4231EA2924AGA2

2. Valve assemblies have two actuators mounted in tandem.

VF4231EA2924AGC2

6 2020 941 100 VF4231FA2924AGA2 VF4231FA2924AGC2

Figure 3: Two-Way Valve with M9000 Series Non-Spring Return Electric Actuator

(Less Weather Shield)

Figure 4: Two-Way Valve with M9000 Series Spring Return Electric Actuator

(Less Weather Shield)

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

6

Table 8: 0 to 10 VDC Proportional Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (Less Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M91xx-GGA-2 without End Switches

M91xx-GGC-2 with Two End Switches

2 159 105 200 VF4231AA+916GGA VF4231AA+916GGC

2-1/2 266 156 200 VF4231BA+916GGA VF4231BA+916GGC

3 457 240 200 VF4231CA+916GGA VF4231CA+916GGC

4 860 423 200 VF4231DA+924GGA VF4231DA+924GGC

5 1320 656 50 VF4231EA+924GGA VF4231EA+924GGC

5 1320 656 200 VF4231EA2924GGA2 VF4231EA2924GGC2

6 2020 941 100 VF4231FA2924GGA2 VF4231FA2924GGC2

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

Table 9: Floating Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (Less Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M9220-AGA-3 without End Switches

M9220-AGC-3 with Two End Switches

Spring Open Spring Closed Spring Open Spring Closed2 159 105 200 VF4231AA+92NAGA VF4431AA+94NAGA VF4231AA+92NAGC VF4431AA+94NAGC

2-1/2 266 156 200 VF4231BA+92NAGA VF4431BA+94NAGA VF4231BA+92NAGC VF4431BA+94NAGC

3 457 240 200 VF4231CA+92NAGA VF4431CA+94NAGA VF4231CA+92NAGC VF4431CA+94NAGC

4 860 423 50 VF4231DA+92NAGA VF4431DA+94NAGA VF4231DA+92NAGC VF4431DA+94NAGC

4 860 423 200 VF4231DA292NAGA2 VF4431DA294NAGA2 VF4231DA292NAGC2 VF4431DA294NAGC2

5 1320 650 100 VF4231EA292NAGA2 VF4431EA294NAGA2 VF4231EA292NAGC2 VF4431EA294NAGC2

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

Table 10: On/Off Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (Less Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M9220-BGA-3 without End Switches

M9220-BGC-3 with Two End Switches

Spring Open Spring Closed Spring Open Spring Closed2 159 105 200 VF4231AA+92NBGA VF4431AA+94NBGA VF4231AA+92NBGC VF4431AA+94NBGC

2-1/2 266 156 200 VF4231BA+92NBGA VF4431BA+94NBGA VF4231BA+92NBGC VF4431BA+94NBGC

3 457 240 200 VF4231CA+92NBGA VF4431CA+94NBGA VF4231CA+92NBGC VF4431CA+94NBGC

4 860 423 50 VF4231DA+92NBGA VF4431DA+94NBGA VF4231DA+92NBGC VF4431DA+94NBGC

4 860 423 200 VF4231DA292NBGA2 VF4431DA294NBGA2 VF4231DA292NBGC2 VF4431DA294NBGC2

5 1320 656 100 VF4231EA292NBGA2 VF4431EA294NBGA2 VF4231EA292NBGC2 VF4431EA294NBGC2

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

7

Table 11: 0 to 10 VDC Proportional Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (Less Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M9220-GGA-3 without End Switches

M9220-GGC-3 with Two End Switches

Spring Open Spring Closed Spring Open Spring Closed2 159 105 200 VF4231AA+92NGGA VF4431AA+94NGGA VF4231AA+92NGGC VF4431AA+94NGGC

2-1/2 266 156 200 VF4231BA+92NGGA VF4431BA+94NGGA VF4231BA+92NGGC VF4431BA+94NGGC

3 457 240 200 VF4231CA+92NGGA VF4431CA+94NGGA VF4231CA+92NGGC VF4431CA+94NGGC

4 860 423 50 VF4231DA+92NGGA VF4431DA+94NGGA VF4231DA+92NGGC VF4431DA+94NGGC

4 860 423 200 VF4231DA292NGGA2 VF4431DA294NGGA2 VF4231DA292NGGC2 VF4431DA294NGGC2

5 1320 656 100 VF4231EA292NGGA2 VF4431EA294NGGA2 VF4231EA292NGGC2 VF4431EA294NGGC2

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

8

Three-Way Valves with M9000 Series Electric Actuators (Less Weather Shield)

Table 12: On/Off (Floating) Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (Less Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

1. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

M91xx-AGA-2 without End Switches

M91xx-AGC-2 with Two End Switches

2 159 105 200 VF4831AD+916AGA VF4831AD+916AGC

2-1/2 266 156 200 VF4831BD+916AGA VF4831BD+916AGC

3 457 240 200 VF4831CD+916AGA VF4831CD+916AGC

4 860 423 50 VF4831DD+924AGA VF4831DD+924AGC

5 1320 656 100 VF4831ED2924AGA2

2. Valve assemblies have two actuators mounted in tandem.

VF4831ED2924AGC2

6 2020 941 100 VF4831FD2924AGA2 VF4831FD2924AGC2

Table 13: 0 to 10 VDC Proportional Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (Less Weather Shield) (Part 1 of 2)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M91xx-GGA-2 without End Switches

M91xx-GGC-2 with Two End Switches

2 159 105 200 VF4831AD+916GGA VF4831AD+916GGC

2-1/2 266 156 200 VF4831BD+916GGA VF4831BD+916GGC

3 457 240 200 VF4831CD+916GGA VF4831CD+916GGC

4 860 423 50 VF4831DD+924GGA VF4831DD+924GGC

Figure 5: Three-Way Valve with M9000 Series Electric Actuator (Less Weather Shield)

N.O.

Style F

N.O.

N.C.

Style G

N.C. FIG

:3w

ay_v

bs

N.C.

Style D

N.O.

Style E

N.C.

N.O.

Figure 6: Three-Way Valve Body Styles

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

9

5 1320 656 100 VF4831ED2924GGA2 VF4831ED2924GGC2

6 2020 941 100 VF4831FD2924GGA2 VF4831FD2924GGC2

1. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

2. Valve assemblies have two actuators mounted in tandem.

Table 14: On/Off Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (Less Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)2

M9220-BGA-3 without End Switches

M9220-BGC-3 with Two End Switches

2 159 105 200 VF4831AD+92NBGA VF4831AD+92NBGC

2-1/2 266 156 200 VF4831BD+92NBGA VF4831BD+92NBGC

3 457 240 150 VF4831CD+92NBGA VF4831CD+92NBGC

4 860 423 175 VF4831DD292NBGA3 VF4831DD292NBGC3

1. Code numbers listed are three-way valves in Style D. See Figure 6. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.

2. All valves are rated for dead-end service. Valves rated at for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

3. Valve assemblies have two actuators mounted in tandem.

Table 15: Proportional Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (Less Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)2

M9220-GGA-3 without End Switches

M9220-GGC-3 with Two End Switches

2 159 105 200 VF4831AD+92NGGA VF4831AD+92NGGC

2-1/2 266 156 200 VF4831BD+92NGGA VF4831BD+92NGGC

3 457 240 150 VF4831CD+92NGGA VF4831CD+92NGGC

4 860 423 175 VF4831DD292NGGA3 VF4831DD292NGGC3

1. Code numbers listed are three-way valves in Style D. See Figure 6. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.

2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

3. Valve assemblies have two actuators mounted in tandem.

Table 13: 0 to 10 VDC Proportional Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (Less Weather Shield) (Part 2 of 2)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M91xx-GGA-2 without End Switches

M91xx-GGC-2 with Two End Switches

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

10

Two-Way Valves with M9000 Series Spring Return and Non-Spring Return Electric Actuator (With Weather Shield)

Table 16: Floating Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (Less Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)2

M9220-AGA-3 without End Switches

M9220-AGC-3 with Two End Switches

2 159 105 200 VF4831AD+92NAGA VF4831AD+92NAGC

2-1/2 266 156 200 VF4831BD+92NAGA VF4831BD+92NAGC

3 457 240 150 VF4831CD+92NAGA VF4831CD+92NAGC

4 860 423 175 VF4831DD292NAGA3 VF4831DD292NAGC3

1. Code numbers listed are three-way valves in Style D. See Figure 6. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.

2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

3. Valve assemblies have two actuators mounted in tandem.

Table 17: On/Off (Floating) Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (With Weather Shield) (Part 1 of 2)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M91xx-AGA-2 without End Switches

M91xx-AGC-2 with Two End Switches

2 159 105 200 VF5231AA+916AGA VF5231AA+916AGC

2-1/2 266 156 200 VF5231BA+916AGA VF5231BA+916AGC

3 457 240 200 VF5231CA+916AGA VF5231CA+916AGC

4 860 423 200 VF5231DA+924AGA VF5231DA+924AGC

Figure 7: Two-Way Valve with M9000 Series Electric Actuator (With Weather Shield)

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

11

5 1320 656 50 VF5231EA+924AGA VF5231EA+924AGC

5 1320 656 200 VF5231EA2924AGA2 VF5231EA2924AGC2

6 2020 941 100 VF5231FA2924AGA2 VF5231FA2924AGC2

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

Table 18: 0 to 10 VDC Proportional Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (With Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M91xx-GGA-2 without End Switches

M91xx-GGC-2 with Two End Switches

2 159 105 200 VF5231AA+916GGA VF5231AA+916GGC

2-1/2 266 156 200 VF5231BA+916GGA VF5231BA+916GGC

3 457 240 200 VF5231CA+916GGA VF5231CA+916GGC

4 860 423 200 VF5231DA+924GGA VF5231DA+924GGC

5 1320 656 50 VF5231EA+924GGA VF5231EA+924GGC

5 1320 656 200 VF5231EA2924GGA2 VF5231EA2924GGC2

6 2020 941 100 VF5231FA2924GGA2 VF5231FA2924GGC2

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

Table 19: Floating Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (With Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M9220-AGA-3 without End Switches M9220-AGC-3 with Two End SwitchesSpring Open Spring Closed Spring Open Spring Closed

2 159 105 200 VF5231AA+92NAGA VF5431AA+94NAGA VF5231AA+92NAGC VF5431AA+94NAGC

2-1/2 266 156 200 VF5231BA+92NAGA VF5431BA+94NAGA VF5231BA+92NAGC VF5431BA+94NAGC

3 457 240 200 VF5231CA+92NAGA VF5431CA+94NAGA VF5231CA+92NAGC VF5431CA+94NAGC

4 860 423 50 VF5231DA+92NAGA VF5431DA+94NAGA VF5231DA+92NAGC VF5431DA+94NAGC

4 860 423 200 VF5231DA292NAGA2 VF5431DA294NAGA2 VF5231DA292NAGC2 VF5431DA294NAGC2

5 1320 656 100 VF5231EA292NAGA2 VF5431EA294NAGA2 VF5231EA292NAGC2 VF5431EA294NAGC2

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

Table 17: On/Off (Floating) Control Two-Way Valves with M9000 Series Non-Spring Return Electric Actuators (With Weather Shield) (Part 2 of 2)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M91xx-AGA-2 without End Switches

M91xx-AGC-2 with Two End Switches

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

12

Table 20: On/Off Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (With Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M9220-BGA-3 without End Switches M9220-BGC-3 with Two End SwitchesSpring Open Spring Closed Spring Open Spring Closed

2 159 105 200 VF5231AA+92NBGA

VF5431AA+94NBGA

VF5231AA+92NBGC

VF5431AA+94NBGC

2-1/2 266 156 200 VF5231BA+92NBGA

VF5431BA+94NBGA

VF5231BA+92NBGC

VF5431BA+94NBGC

3 457 240 200 VF5231CA+92NBGA

VF5431CA+94NBGA

VF5231CA+92NBGC

VF5431CA+94NBGC

4 860 423 50 VF5231DA+92NBGA

VF5431DA+946BGA

VF5231DA+92NBGC

VF5431DA+94NBGC

4 860 423 200 VF5231DA292NBGA2

VF5431DA294NBGA2

VF5231DA292NBGC2

VF5431DA294NBGC2

5 1320

656 100 VF5231EA292NBGA2

VF5431EA294NBGA2

VF5231EA292NBGC2

VF5431EA294NBGC2

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

Table 21: 0 to 10 VDC Proportional Control Two-Way Valves with M9000 Series Spring Return Electric Actuator (With Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

M9220-GGA-3 without End Switches M9220-GGC-3 with Two End Switches

Spring Open Spring Closed Spring Open Spring Closed

2 159 105 200 VF5231AA+92NGGA VF5431AA+94NGGA VF5231AA+92NGGC VF5431AA+94NGGC

2-1/2 266 156 200 VF5231BA+92NGGA VF5431BA+94NGGA VF5231BA+92NGGC VF5431BA+94NGGC

3 457 240 200 VF5231CA+92NGGA VF5431CA+94NGGA VF5231CA+92NGGC VF5431CA+94NGGC

4 860 423 50 VF5231DA+92NGGA VF5431DA+94NGGA VF5231DA+92NGGC VF5431DA+94NGGC

4 860 423 200 VF5231DA292NGGA2 VF5431DA294NGGA2 VF5231DA292NGGC2 VF5431DA294NGGC2

5 1320 656 100 VF5231EA292NGGA2 VF5431EA294NGGA2 VF5231EA292NGGC2 VF5431EA294NGGC2

1. All valves are rated for dead-end service. Valves rated at 200 psig closeoff have 150 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

13

Three-Way Valve with M9000 Series Spring Return and Non-Spring Return Electric Actuator (With Weather Shield)

Table 22: On/Off (Floating) Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (With Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

1. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

M91xx-AGA-2 without End Switches

M91xx-AGC-2 with Two End Switches

2 159 105 200 VF5831AD+916AGA VF5831AD+916AGC

2-1/2 266 156 200 VF5831BD+916AGA VF5831BD+916AGC

3 457 240 150 VF5831CD+916AGA VF5831CD+916AGC

4 860 423 100 VF5831DD+924AGA VF5831DD+924AGC

5 1320 656 100 VF5831ED2924AGA2

2. Valve assemblies have two actuators mounted in tandem.

VF5831ED2924AGC2

6 2020 941 100 VF5831FD2924AGA2 VF5831FD2924AGC2

Figure 8: Three-Way Valve with M9000 Series Spring Return and Non-Spring Return

Electric Actuator (With Weather Shield)

N.O.

Style F

N.O.

N.C.

Style G

N.C. FIG

:3w

ay_v

bs

N.C.

Style D

N.O.

Style E

N.C.

N.O.

Figure 9: Three-Way Valve Body Styles

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

14

Table 23: 0 to 10 VDC Proportional Control Three-Way Valves with M9000 Series Non-Spring Return Electric Actuator (With Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)1

1. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

M91xx-GGA-2 without End Switches

M91xx-GGC-2 with Two End Switches

2 159 105 200 VF5831AD+916GGA VF5831AD+916GGC

2-1/2 266 156 200 VF5831BD+916GGA VF5831BD+916GGC

3 457 240 150 VF5831CD+916GGA VF5831CD+916GGC

4 860 423 100 VF5831DD+924GGA VF5831DD+924GGC

5 1320 656 100 VF5831ED2924GGA2

2. Valve assemblies have two actuators mounted in tandem.

VF5831ED2924GGC2

6 2020 941 100 VF5831FD2924GGA2 VF5831FD2924GGC2

Table 24: Floating Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (With Weather Shield)

1. Code numbers listed are three-way valves in Style D. See Figure 9. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)2

2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

M9220-AGA-3 without End Switches

M9220-AGC-3 with Two End Switches

2 159 105 200 VF5831AD+92NAGA VF5831AD+92NAGC

2-1/2 266 156 200 VF5831BD+92NAGA VF5831BD+92NAGC

3 457 240 150 VF5831CD+92NAGA VF5831CD+92NAGC

4 860 423 175 VF5831DD292NAGA3

3. Valve assemblies have two actuators mounted in tandem.

VF5831DD292NAGC3

Table 25: On/Off Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (With Weather Shield)

1. Code numbers listed are three-way valves in Style D. See Figure 9. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)2

2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

M9220-BGA-3 without End Switches

M9220-BGC-3 with Two End Switches

2 159 105 200 VF5831AD+92NBGA VF5831AD+92NBGC

2-1/2 266 156 200 VF5831BD+92NBGA VF5831BD+92NBGC

3 457 240 150 VF5831CD+92NBGA VF5831CD+92NBGC

4 860 423 175 VF5831DD292NBGA3

3. Valve assemblies have two actuators mounted in tandem.

VF5831DD292NBGC3

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

15

Two-Way Valves with D-3000 Series Spring Return Pneumatic Actuators

Table 26: Proportional Control Three-Way Valves1 with M9000 Series Spring Return Electric Actuators (With Weather Shield)

Size, in.

Cv at 90°

Cv at 70°

Closeoff Pressure (psig)2

M9220-GGA-3 without End Switches

M9220-GGC-3 with Two End Switches

2 159 105 200 VF5831AD+92NGGA VF5831AD+92NGGC

2-1/2 266 156 200 VF5831BD+92NGGA VF5831BD+92NGGC

3 457 240 150 VF5831CD+92NGGA VF5831CD+92NGGC

4 860 423 175 VF5831DD292NGGA3 VF5831DD292NGGC3

1. Code numbers listed are three-way valves in Style D. See Figure 9. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.

2. All valves are rated for dead-end service. Valves rated for 150 to 200 psig closeoff have 150 psig maximum dead-end service rating.

3. Valve assemblies have two actuators mounted in tandem.

Table 27: Two-Way Butterfly Valve Assemblies with 175 psig Closeoff PressureSize, in.

Cv at 70°

Closeoff Pressure (psig)1

1. All valves are rated for dead-end service. Valves rated at 175 psig closeoff have 150 psig maximum dead-end service rating.

On/Off (Proportional Control) Proportional Control (With Postioner)Spring Open Spring Closed Spring Open Spring Closed

2 105 175 VF4231AA+3153 VF4431AA+3153 VF4231AA+3153P VF4431AA+3153P

2-1/2 156 175 VF4231BA+3153 VF4431BA+3153 VF4231BA+3153P VF4431BA+3153P

3 240 175 VF4231CA+3153 VF4431CA+3153 VF4231CA+3153P VF4431CA+3153P

4 423 175 VF4231DA+3244 VF4431DA+3244 VF4231DA+3244P VF4431DA+3244P

5 656 175 VF4231EA+3246 VF4431EA+3246 VF4231EA+3246P VF4431EA+3246P

6 941 175 VF4231FA+3246 VF4431FA+3246 VF4231FA+3246P VF4431FA+3246P

8 1,660 175 VF4231GA232462

2. Valve assemblies have two actuators mounted in tandem.

VF4431GA232462 VF4231GA23246P2 VF4431GA23246P2

Figure 10: Two-Way Valves with D-3000 Series Spring Return Pneumatic Actuators

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

16

Three-Way Valves with D-3000 Series Spring Return Pneumatic Actuators

Table 28: Two-Way Butterfly Valve Assemblies with 50 psig Closeoff PressureSize, in.

Cv at 70°

Closeoff Pressure (psig)1

On/Off (Proportional Control) Proportional Control (With Postioner)Spring Open Spring Closed Spring Open Spring Closed

4 423 50 VF6231DA+3153 VF6431DA+3153 VF6231DA+3153P VF6431DA+3153P

5 656 50 VF6231EA+3244 VF6431EA+3244 VF6231EA+3244P VF6431EA+3244P

6 941 50 VF6231FA+3246 VF6431FA+3246 VF6231FA+3246P VF6431FA+3246P

8 1,660 50 VF6231GA+3246 VF6431GA+3246 VF6231GA+3246P VF6431GA+3246P

10 2560 50 VF6231HA232462 VF6431HA232462 VF6231HA23246P2 VF6431HA23246P2

1. All valves are rated for dead-end service. Valves rated at 50 psig closeoff have 50 psig maximum dead-end service rating.2. Valve assemblies have two actuators mounted in tandem.

Table 29: Three-Way Butterfly Valve Assemblies with 175 psig Closeoff PressureSize, in.

Cv at 70°

Closeoff Pressure (psig)1

1. All valves are rated for dead-end service. Valves rated at 175 psig closeoff have 150 psig maximum dead-end service rating.

On/Off Control2

2. Code numbers listed are three-way valves in Style D. See Figure 12. For Styles E, F, or G, change the D in the eighth digit of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.

Proportional Control (With Postioner)2

2 105 175 VF4831AD+3153 VF4831AD+3153P

2-1/2 156 175 VF4831BD+3244 VF4831BD+3244P

3 240 175 VF4831CD+3244 VF4831CD+3244P

4 423 175 VF4831DD+3246 VF4831DD+3246P

5 656 175 VF4831ED+3246 VF4831ED+3246P

6 941 175 VF4831FD232463

3. Valve assemblies have two actuators mounted in tandem.

VF4831FD23246P3

Figure 11: Three-Way Valves with D-3000 Series Spring Return Pneumatic Actuators

N.O.

Style F

N.O.

N.C.

Style G

N.C. FIG

:3w

ay_v

bs

N.C.

Style D

N.O.

Style E

N.C.

N.O.

Figure 12: Three-Way Valve Body Styles

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

17

DimensionsTwo-Way VF Series M9000 Electrically Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesValve sizes 2 through 3 in. feature four mounting lugs with a different orientation than what is illustrated in Figure 13 and Figure 14. Valve sizes 4 through 6 in. feature eight mounting lugs with an orientation similar to what is illustrated in Figure 13 and Figure 14. Always bolt the side of valve marked INLET first to the pipe flange.

For dead-end service, the side of the valve marked INLET should be installed facing pressure when downstream piping will be removed. Placement of a downstream flange is recommended when the valve will be dead-ended for extended periods, in the presence of elevated temperatures, dangerous or expansive fluids, or any combination thereof.

Table 30: Three-Way Butterfly Valve Assemblies with 50 psig Closeoff PressureSize, in.

Cv at 70°

Closeoff Pressure (psig)1

On/Off (Proportional Control)2 Proportional Control (With Postioner)2

4 423 50 VF6831DD+3244 VF6831DD+3244P

5 656 50 VF6831ED+3246 VF6831ED+3246P

6 941 50 VF6831FD+3246 VF6831FD+3246P

8 1,660 50 VF6831GD232463 VF6831GD23246P3

1. All valves are rated for dead-end service. Valves rated at 50 psig closeoff have 50 psig maximum dead-end service rating.2. Code numbers listed are three-way valves in Style D. See Figure 12. For Styles E, F, or G, change the D in the eighth digit

of the code number to the desired style. Example VFxxxxxE+xxxxx, VFxxxxxF+xxxxx, VFxxxxxG+xxxxx.3. Valve assemblies have two actuators mounted in tandem.

Figure 13: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116, M9124 Non-Spring Return and M9220 Spring Return Electric Actuators (Less Weather Shield)

EH

F

C D

A Sleeve

SingleDesign

G

EH

C D

B Chord

TandemDesign

FIG

:2w

ay_e

lec_

ns

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

18

ce d for r l

for

Table 31: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116 and M9124 Series Non-Spring Return Electric Actuators (Less Weather Shield) Dimensions, in. (mm)

Valve Size, in.

A B C D E F G H J Lug Data ClearanRequireActuatoRemova

Bolt Circle

No. of Holes

Threads UNC-2B

2 1.81 (46)

1.49 (38)

13.1 (333)

16.2 (411)

5.75 (146)

12-1/2 (318)

4.5 (114)

7.14 (181)

4(102)

4.75 (121)

4 5/8–11 5(127)

2-1/2 1.94 (49)

2.01 (51)

13.6 (345)

17 (432)

5.75 (146)

12-1/2 (318)

4.5 (114)

7.14 (181)

4(102)

5.5 (140)

4 5/8–11 5(127)

3 2.19 (56)

2.64 (67)

13.8 (351)

17.6 (447)

5.75 (146)

12-1/2 (318)

4.5 (114)

7.14 (181)

4(102)

6(152)

4 5/8–11 5(127)

4 2.19 (56)

3.67 (93)

14.6 (371)

18.9 (480)

5.75 (146)

12-1/2 (318)

4.5 (114)

7.14 (181)

4(102)

7.5(191)

8 5/8–11 5(127)

5 2.31 (59)

4.71 (120)

15.1 (384)

20.0 (508)

5.75 (146)

12-1/2 (318)

4.5 (114)

7.14 (181)

4(102)

8.5(216)

8 3/4–10 5(127)

61 2.31 (59)

5.66 (144)

18.9 (480)

24.3 (617)

8.31 (211)

15(381)

8.75 (222)

9.7 (246)

4(102)

9.5(241)

8 3/4–10 5(127)

1. Valve assemblies have two actuators mounted in tandem.

Table 32: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9220 Series Spring Return Electric Actuators (Less Weather Shield) Dimensions, in. (mm)

Valve Size, in.

A B C D E F G H J Lug Data ClearanceRequired Actuator Removal

Bolt Circle

No. of Holes

Threads UNC-2B

2 1.81 (46)

1.49 (38)

13.1 (333)

16.2 (411)

7.81 (198)

--- 4.5 (114)

10 (254)

4.91 (125)

4.75 (121)

4 5/8–11 6(152)

2-1/2 1.94 (49)

2.01 (51)

13.6 (345)

17.0 (432)

7.81 (198)

--- 4.5 (114)

10 (254)

4.91 (125)

5.5(140)

4 5/8–11 6(152)

3 2.19 (56)

2.64 (67)

13.8 (351)

17.6 (447)

7.81 (198)

--- 4.5 (114)

10 (254)

4.91 (125)

6(152)

4 5/8–11 6(152)

4 2.19 (56)

3.67 (93)

14.6 (371)

18.9 (480)

7.81 (198)

--- 4.5 (114)

10 (254)

4.91 (125)

7.5(191)

8 5/8–11 6(152)

51 2.31 (59)

4.71 (120)

19.2 (488)

24.1 (612)

8.31 (211)

--- 8.75 (222)

10.44 (265)

4.91 (125)

8.5(216)

8 3/4–10 6(152)

1. Valve assemblies have two actuators mounted in tandem.

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

19

Table 33: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116 and M9124 Series Non-Spring Return, and M9220 Series Spring Return Electric Actuators with Weather Shield Dimensions, in. (mm)

Valve Size, in.

A B C D E F G H J Lug Data Clearance Required for Actuator Removal

Bolt Circle

No. of Holes

Threads UNC-2B

2 1.81 (46)

1.49 (38)

17.8 (452)

20.9 (531)

11.9 (302)

--- 9 (229)

15.5 (394)

8.25 (210)

4.75(121)

4 5/8–11 6(152)

2-1/2 1.94 (49)

2.01 (51)

18.3 (465)

21.5 (546)

11.9 (302)

--- 9 (229)

15.5 (394)

8.25 (210)

5.5(140)

4 5/8–11 6(152)

3 1.94 (49)

2.64 (67)

18.5 (470)

22.3 (566)

11.9 (302)

--- 9 (229)

15.5 (394)

8.25 (210)

6(152)

4 5/8–11 6(152)

4 2.19 (56)

3.67 (93)

19.3 (490)

23.5 (597)

11.9 (302)

--- 9 (229)

15.5 (394)

8.25 (210)

7.5(191)

8 5/8–11 6(152)

5 2.31 (59)

4.71 (120)

19.8 (503)

24.5 (622)

11.9 (302)

--- 9 (229)

15.5 (394)

8.25 (210)

8.5(216)

8 3/4–10 6(152)

61

1. Valve assemblies have two actuators mounted in tandem.

2.31 (59)

5.66 (144)

20.3 (516)

25.5 (648)

11.9 (302)

--- 9 (229)

15.5 (394)

8.25 (210)

9.5(241)

8 3/4–10 6(152)

Figure 14: Two-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116, M9124 Non-Spring Return and M9220 Spring Return Electric Actuators (With Weather Shield)

FE

H

CD

G

FIG

:2w

ay_e

lec_

ws

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

20

Three-Way VF Series M9000 Electrically Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesValve sizes 2 through 3 in. feature four mounting lugs with a different orientation than what is illustrated in Figure 15 and Figure 16. Valve sizes 4 through 6 in. feature eight mounting lugs with an orientation similar to what is illustrated in Figure 15 and Figure 16.

Three-way valve assemblies are supplied with the INLET side of the valves bolted to the pipe tee. If it is necessary to make changes, always bolt the side of valve marked INLET first to the pipe flange.

For dead-end service, the side of the valve marked INLET should be installed facing pressure when downstream piping will be removed. Placement of a downstream flange is recommended when the valve will be dead-ended for extended periods, in the presence of elevated temperatures, dangerous or expansive fluids, or any combination thereof.

Table 34: Three-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116 and M9124 Series Non-Spring Return Electric Actuators (Less Weather Shield) Dimensions, in. (mm)

Valve Size, in.

A B C D E F G H J K L Lug Data Clearance Required forActuator Removal

Bolt Circle

No. of Holes

Threads UNC-2B

2 1.75 (44.5)

1.5 (38)

13.1 (333)

16.2 (411)

5.75 (146)

12.5 (318)

4.5 (114)

7.14 (181)

4.5 (114)

6.25 (159)

--- 4.75 (121)

4 5/8–11 5(127)

2-1/2 1.88 (47.8)

2.01 (51)

13.6 (345)

17.3 (439)

5.75 (146)

12.5 (318)

4.5 (114)

7.14 (181)

5 (127)

6.88 (175)

--- 5.5 (140)

4 5/8–11 5(127)

3 1.88 (47.8)

2.64 (67)

13.8 (351)

17.6 (447)

5.75 (146)

12.5 (318)

4.5 (114)

7.14 (181)

5.5 (140)

7.39 (188)

--- 6(152)

4 5/8–11 5(127)

4 2.13 (54.0)

3.67 (93)

14.6 (371)

19.2 (488)

5.75 (146)

12.5 (318)

4.5 (114)

7.14 (181)

6.5 (165)

8.63 (219)

--- 7.5 (191)

8 5/8–11 5(127)

5 2.25 (57.2)

4.71 (120)

15.1 (383)

20.3 (516)

5.75 (146)

12.5 (318)

4.5 (114)

7.14 (181)

7.5 (191)

9.75 (248)

--- 8.5 (216)

8 3/4-10 5(127)

6 2.25 (57.2)

5.66 (144)

18.9 (480)

24.6 (625)

8.31 (211)

--- 8.75 (222)

9.7 (246)

8 (203)

10.25 (260)

--- 9.5 (241)

8 3/4-10 5(127)

Figure 15: Three-Way Assemblies: M9116, M9124 Non-Spring Return and M9220 Spring Return Electric Actuators (Less Weather Shield)

JKEH

EH

F

A

G

BChord

SingleDesign

TandemDesign

FIG

:3w

ay_e

lec_

ns

GC D

C D

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

21

Table 35: Three-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9220 Series Spring Return Electric Actuators (Less Weather Shield) Dimensions, in. (mm)

Valve Size, in.

A B C D E F G H J K L Lug Data Clearance Required for Actuator Removal

Bolt Circle

No. of Holes

Threads UNC-2B

2 1.75 (44.5)

1.5 (38)

13.1 (333)

16.2 (411)

7.81 (198)

---

4.5 (114)

10 (254)

4.5 (114)

6.25 (159)

--- 4.75 (121)

4 5/8–11 6(152)

2-1/2 1.88 (47.8)

2.01 (51)

13.6 (345)

17.3 (439)

7.81 (198)

---

4.5 (114)

10 (254)

5 (127)

6.88 (175)

--- 5.5 (140)

4 5/8–11 6(152)

3 1.88 (47.8)

2.64 (67)

13.8 (351)

17.6 (447)

7.81 (198)

---

4.5 (114)

10 (254)

5.5 (140)

7.39 (188)

--- 6(152)

4 5/8–11 6(152)

4 2.13 (54.0)

3.67 (93)

14.6 (371)

19.2 (488)

7.81 (198)

---

4.5 (114)

10 (254)

6.5 (165)

8.63 (219)

--- 7.5 (191)

8 5/8–11 6(152)

5 2.25 (57.2)

4.71 (120)

15.1 (383)

24.3 (617)

8.31 (211)

---

8.75 (222)

10.44 (265)

7.5 (191)

9.75 (248)

--- 8.5 (216)

8 3/4-10 6(152)

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

22

Table 36: Three-Way VF Series Standard-Pressure, Standard-Temperature Butterfly Valves with M9116 and M9124 Series Non-Spring Return, and M9220 Series Spring Return Electric Actuators with Weather Shield Dimensions, in. (mm)

Valve Size, in.

A B C D E F G H J K L Lug Data Clearance Required for Actuator Removal

Bolt Circle

No. of Holes

Threads UNC-2B

2 1.75 (44.5)

1.5 (38)

17.8 (452)

20.9 (531)

11.9 (302)

--- 9(229)

15.5 (394)

--- 6.25 (159)

8.25 (210)

4.75 (121)

4 5/8–11 6(152)

2-1/2 1.88 (47.8)

2.01 (51)

18.3 (465)

21.8 (554)

11.9 (302)

--- 9(229)

15.5 (394)

--- 6.88 (175)

8.25 (210)

5.5 (140)

4 5/8–11 6(152)

3 1.88 (47.8)

2.64 (67)

18.5 (470)

22.3 (566)

11.9 (302)

--- 9(229)

15.5 (394)

--- 7.39 (188)

8.25 (210)

6(152)

4 5/8–11 6(152)

4 2.13 (54.0)

3.67 (93)

19.3 (490)

23.8 (605)

11.9 (302)

--- 9(229)

15.5 (394)

--- 8.63 (219)

8.25 (210)

7.5 (191)

8 5/8–11 6(152)

5 2.25 (57.2)

4.71 (120)

19.8 (503)

24.8 (630)

11.9 (302)

--- 9(229)

15.5 (394)

--- 9.75 (248)

8.25 (210)

8.5 (216)

8 3/4-10 6(152)

6 2.25 (57.2)

5.66 (144)

20.3 (516)

25.8 (655)

11.9 (302)

--- 9(229)

15.5 (394)

--- 10.25 (260)

8.25 (210)

9.5 (241)

8 3/4-10 6(152)

Figure 16: Three-Way Assemblies: M9116, M9124 Non-Spring Return and M9220 Spring Return Electric Actuators (With Weather Shield)

LE

H

CD

G

FIG

:3w

ay_e

lec

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

23

Two-Way Pneumatically-Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesValve sizes 2 through 3 in. feature four mounting lugs. Valve sizes 4 through 8 in. feature eight mounting lugs. Valves 10 in. in size have 12 mounting lugs. Always bolt the side of valve marked INLET first to the pipe flange.

For dead-end service, the side of the valve marked INLET should be installed facing pressure when downstream piping will be removed. Placement of a downstream flange is recommended when the valve will be dead-ended for extended periods, in the presence of elevated temperatures, dangerous or expansive fluids, or any combination thereof.

Figure 17: Single Pneumatic Piston Actuator Assembled on a Two-Way Butterfly Valve

(See Table 37.)

C

D

FIG

:sing

_pne

u_2w

ay

ASleeve

F

H G

BChord

Figure 18: Dual Tandem Pneumatic Piston Actuators Assembled on a Two-Way Butterfly

Valve (See Table 37.)

ASleeve

FIG

:dua

l_Pn

eu_2

way

D

C

F Typical

H

G Typical

BChord

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

24

Table 37: Overall Dimensions of D-3153, D-3244, and D-3246 Series Pneumatic Piston Actuators Assembled on Two-Way VF4000 and VF6000 Series Butterfly Valves, in. (mm)

Valve Size, in.

Actuator A B C D E F G H

2 D-3153 1.81(46)

1.49(38)

3.14 (79.8)

12.84 (326.0)

10.33 (262.4)

14.06 (357)

5.68 (144)

9.06 (230)

2-1/2 1.94(49)

2.01(51)

3.40 (86.4)

13.34 (339)

10.83 (275.0)

14.06 (357)

5.68 (144)

9.06 (230)

3 1.94(49)

2.64(67)

3.77 (95.6)

13.59 (345.0)

11.08 (281)

14.06 (357)

5.68 (144)

9.06 (230)

4 2.19 (55.6)

3.67(93)

4.26 (108.2)

14.37 (364)

11.83 (300)

14.06 (357)

5.68 (144)

9.06 (230)

D-3244 2.19 (55.6)

3.67(93)

4.26 (108.2)

15.41 (391)

12.88 (327)

17.75 (451)

6.70 (170)

11.20 (285)

5 2.31 (58.6)

4.71 (119.6)

4.89 (124.2)

15.91 (404)

13.38 (340)

17.75 (451)

6.70 (170)

11.20 (285)

D-3246 2.31 (58.6)

4.71(119.6)

4.89 (124.2)

15.72 (399)

13.56 (344.5)

22.80 (579)

8.22 (209)

13.67 (347)

6 2.31 (58.6)

5.66 (143.7)

5.41 (137.4)

16.22 (410)

14.06 (357)

22.80 (579)

8.22 (209)

13.67 (347)

8 2.53 (64.3)

7.72 (196)

6.54 (166.0)

16.72 (425)

14.56 (370)

22.80 (579)

8.22 (209)

13.67 (347)

Tandem D-3246

2.53 (64.3)

7.72 (196)

6.54 (166.0)

17.60 (447)

15.44 (392)

22.80 (579)

8.22 (209)

16.44 (418)

10 2.85 (72.4)

9.70 (246.2)

7.83 (198.9)

18.78 (477)

16.62 (422)

22.80 (579)

8.22 (209)

16.44 (418)

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

25

Three-Way Pneumatically-Actuated Standard-Pressure, Standard-Temperature Butterfly ValvesValve sizes 2 through 3 in. feature four mounting lugs. Valve sizes 4 through 8 in. feature eight mounting lugs. Valves 10 in. in size have 12 mounting lugs. Always bolt the side of valve marked INLET first to the pipe flange.

Three-way valve assemblies are supplied with the INLET side of the valves bolted to the pipe tee. If it is necessary to make changes, always bolt the side of valve marked INLET first to the pipe flange.

For dead-end service, the side of the valve marked INLET should be installed facing pressure when downstream piping will be removed. Placement of a downstream flange is recommended when the valve will be dead-ended for extended periods, in the presence of elevated temperatures, dangerous or expansive fluids, or any combination thereof.

Figure 19: Single Pneumatic Piston Actuator Assembled on a Three-Way Butterfly Valve

D

CChord

A

B FIG

:sing

_pne

u_3w

ay

J

H

G

Figure 20: Dual Tandem Pneumatic Piston Actuators Assembled on a Three-Way Butterfly

ValveFI

G:d

ual_

pneu

_3w

ay

FE

D

A

B

CChord

J

H

G Typical

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

26

Table 38: Overall Dimensions of D-3153, D-3244, and D-3246 Series Pneumatic Piston Actuators Assembled on Three-Way VF4000 and VF6000 Series Butterfly Valves, in. (mm)

Valve Size, in.

Actuator A B C D E F G H J

2 D-3153 6.25 (159)

10.75 (273)

1.49 (38) 3.00 (76) 12.84 (326)

10.33 (262)

14.06 (357)

5.68 (144)

11.93 (303)

2-1/2 D-3244 6.88 (175)

11.88 (302)

2.01 (51) 3.50 (89) 14.41 (366)

11.88 (302)

17.75 (451)

6.70 (170)

13.58 (345)

3 7.38 (185)

12.88 (327)

2.64 (67) 3.75 (950

14.66 (372)

12.13 (308)

17.75 (451)

6.70 (170)

14.08 (358)

4 8.36 (219)

15.13 (384)

3.67 (93) 4.50 (114)

15.41 (391)

12.88 (327)

17.75 (451)

6.70 (170)

15.33 (389)

D-3246 8.36 (219)

15.13 (384)

3.67 (93) 4.50 (114)

15.22 (386)

13.06 (332)

22.80 (579)

8.22 (209)

16.58 (421)

5 9.75 (248)

17.25 (438)

4.71 (119.6)

5.00 (127)

15.72 (399)

13.56 (344)

22.80 (579)

8.22 (209)

17.97 (456)

6 10.25 (261)

18.25 (463)

5.66 (143.7)

5.50 (140)

16.22 (410)

14.06 (357)

22.80 (579)

8.22 (209)

18.47 (496)

Tandem D-3246

10.25 (261)

18.25 (463)

5.66 (143.7)

5.50 (140)

16.22 (412)

14.06 (357)

22.80 (579)

8.22 (209)

18.47 (469)

8 11.44 (291)

20.44 (519)

7.72 (196.2)

6.75 (171)

17.60 (447)

15.44 (392)

22.80 (579)

8.22 (209)

19.66 (499)

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

27

Shipping Weights Table 39: Representative Maximum Shipping Weights for VF4000, VF5000, and VF6000 Series Two-Way

Butterfly Valve and Actuator Assemblies1

Valve Size, in.

M9000 Electrically Actuated

Shipping Weight, lb (kg) D-3000 Pneumatically Actuated

Shipping Weight,lb (kg)Without

Weather Shield

With Weather Shield

2 M9116-GGx-2 (+916GGx) 22 (10) 26 (11.8) One D-3153 (+3153) 26 (11.8)

M9220-GGx-3 (+92NGGx)2 24 (10.9) 31 (14.1)

2-1/2 M9116-GGx-2 (+916GGx) 23.5 (10.7) 27.5 (12.5) One D-3153 (+3153) 27 (12.2)

M9220-GGx-3 (+92NGGx)2 25.5 (9.1) 32.5 (14.7)

3 M9116-GGx-2 (+916GGx) 24.5 (11.1) 28.5 (12.9) One D-3153 (+3153) 30 (13.6)

M9220-GGx-3 (+92NGGx)2 26.5 (12) 33.5 (15.2)

4 M9124-GGA-2 (+924GGA) 30 (13.6) 35 (15.9) One D-3244 (+3244) 54 (24.5)

M9220-GGx-3 (+92NGGx)2 35 (15.9) 39 (17.7) One D-3153 (+3153) 44 (20)

Two M9220-GGx-3 (+92NGGx)2 44 (20) 48 (21.8) --- ---

5 M9124-GGA-2 (+924GGA) 34 (15.4) 56 (25.4) One D-3246 (+3246) 89 (40.4)

Two M9124-GGA-2 (2924GGA) 40 (18.1) 60 (27.2) One D-3244 (+3244) 77 (34.9)

Two M9220-GGx-32 (+92NGGx) 48 (21.8) 66 (29.9) --- ---

6 Two M9124-GGA-2 (2924GGA) 46 (20.9) 62 (28.1) One D-3246 (+3246) 129 (58.5)

8 --- --- --- Two D-3246s (23246) 206 (93.4)

One D-3246 (+3246) 138 (62.6)

10 --- --- --- Two D-3246s (23246) 227 (103)

1. The above shipping weights are only approximate, and are based on the heaviest valve, actuator, and accessory combination available for each size.

2. The weights given for M9220 actuated assemblies are for M9220-AGx and M9220-GGx models. For Assemblies with M9220-Bxx On/Off actuators, add 1.2 lbs. (0.55 kg) for single actuator assemblies and 2.4 lbs. (1.1 kg) for tandem actuated assemblies to the weights listed.

Table 40: Representative Maximum Shipping Weights for VF4000, VF5000, and VF6000 Series Three-Way Butterfly Valve and Actuator Assemblies1 (Part 1 of 2)

Valve Size, in.

M9000 Electrically Actuated

Shipping Weight, lb (kg) D-3000 Pneumatically Actuated

Shipping Weight,lb (kg)Without

Weather Shield

With Weather Shield

2 M9116-GGA-2 (+916GGA) 60 (27.2) 63 (28.6) One D-3153 (+3153) 62 (28.1)

M9220-GGx-3 (+92NGGx)2 63 (28.6) 70 (31.8)

2-1/2 M9116-GGA-2 (+916GGA) 69 (31.3) 73 (33.1) One D-3244 (+3244) 82 (37.2)

M9220-GGx-3 (+92NGGx)2 73 (33.1) 80 (36.3)

3 M9116-GGA-2 (+916GGA) 80 (36.3) 84 (38.1) One D-3244 (+3244) 92 (41.7)

M9220-GGx-3 (+92NGGx)2 84 (38.1) 91 (41.3)

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

28

Repair Information .

4 M9124-GGA-2 (+924GGA) 120 (54.4) 124 (56.2) One D-3246 (+3246) 151 (68.5)

Two M9220-GGx-3 (+92NGGx)2 132 (59.9) 136 (61.7) One D-3244 (+3244) 142 (64.4)

5 Two M9124-GGA-2 (2924GGA) 148 (67.1) 151 (68.5) One D-3246 (+3246) 186 (84.3)

6 Two M9124-GGA-2 (2924GGA) 183 (83) 186 (84.4) Two D-3246s (23246) 370 (168)

One D-3246 (+3246) 311 (141)

8 --- --- --- Two D-3246s (23246) 397 (180)

1. The above shipping weights are only approximate, and are based on the heaviest valve, actuator, and accessory combination available for each size.

2. The weights given for M9220 actuated assemblies are for M9220-AGx and M9220-GGx models. For Assemblies with M9220-Bxx On/Off actuators, add 1.2 lbs. (0.55 kg) for single actuator assemblies and 2.4 lbs. (1.1 kg) for tandem actuated assemblies to the weights listed.

Table 40: Representative Maximum Shipping Weights for VF4000, VF5000, and VF6000 Series Three-Way Butterfly Valve and Actuator Assemblies1 (Part 2 of 2)

Valve Size, in.

M9000 Electrically Actuated

Shipping Weight, lb (kg) D-3000 Pneumatically Actuated

Shipping Weight,lb (kg)Without

Weather Shield

With Weather Shield

Table 41: Replacement Electric Spring and Non-Spring Return ActuatorsCode Number DescriptionM9116-AGA-2 Electric Motor Actuator, Non-Spring Return, 140 lb⋅in, Floating Control, 24 VAC/VDC Input, No End

Switches (Cannot be Used in Tandem Configurations)

M9116-AGC-2 Electric Motor Actuator, Non-Spring Return, 140 lb⋅in, Floating Control, 24 VAC/VDC Input, Two End Switches (Cannot be Used in Tandem Configurations)

M9116-GGA-2 Electric Motor Actuator, Non-Spring Return, 140 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, No End Switches

M9116-GGC-2 Electric Motor Actuator, Non-Spring Return, 140 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, Two End Switches

M9124-AGA-2 Electric Motor Actuator, Non-Spring Return, 210 lb⋅in, Floating Control, 24 VAC/VDC Input, No End Switches

M9124-AGC-2 Electric Motor Actuator, Non-Spring Return, 210 lb⋅in, Floating Control, 24 VAC/VDC Input, Two End Switches

M9124-GGA-2 Electric Motor Actuator, Non-Spring Return, 210 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, No End Switches

M9124-GGC-2 Electric Motor Actuator, Non-Spring Return, 210 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, Two End Switches

M9220-AGA-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, Floating Control, 24 VAC/VDC Input, No End Switches

M9220-AGC-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, Floating Control, 24 VAC/VDC Input, Two End Switches

M9220-BGA-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, On/Off Control, 24 VAC/VDC Input, No End Switches

M9220-BGC-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, On/Off Control, 24 VAC/VDC Input, Two End Switches

M9220-GGA-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, No End Switches

M9220-GGC-3 Electric Motor Actuator, Spring Return, 177 lb⋅in, Proportional Control, 0 (2) to 10 VDC or 0 (4) to 20 mA Input, 0 (2) to 10 VDC Feedback, Two End Switches

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

29

Table 42: Replacement Pneumatic Spring Return ActuatorsCode Number DescriptionD-3153-5120 Pneumatic Piston Actuator with Positioner, for Use with 2, 2-1/2, or 3 in. 175 or 150 psig Valves or

4 in. 50 psig Valves

D-3153-5130 Pneumatic Piston Actuator without Positioner, for Use with 2, 2-1/2, or 3 in. 175 or 150 psig Valves or 4 in. 50 psig Valves

D-3244-5100 Pneumatic Piston Actuator with Positioner, for Use with 4 in. 175 or 150 psig Valves or 5 in. 50 psig Valves

D-3244-5110 Pneumatic Piston Actuator without Positioner, for Use with 4 in. 175 or 150 psig Valves or 5 in. 50 psig Valves

D-3246-5100 Pneumatic Piston Actuator with Positioner, for Use with 5 or 6 in. 175 or 150 psig Valves or 6, 8, or 10 in. 50 psig Valves

D-3246-5110 Pneumatic Piston Actuator without Positioner, for Use with 5 or 6 in. 175 or 150 psig Valves or 6, 8, or 10 in. (Requires Two Actuators) 50 psig Valves

Table 43: Mounting Kits 1 for Field Mounting D-3000 Series, Pneumatic Piston Actuators on Two-Way VF4000 and VF6000 Series Butterfly Valves

Code Number DescriptionVF4-D3000-201 D-3153-51x0 Actuator Mounting Kit for 2, 2-1/2, or 3 in. 175 psig Valves

VF4-D3000-202 D-3513-51x0 Actuator Mounting Kit for 4 in. 50 psig Valves

VF4-D3000-203 D-3244-51x0 Actuator Mounting Kit for 4 in. 175 psig and 5 in. 50 psig Valves

VF4-D3000-204 D-3246-51x0 Actuator Mounting Kit for 5 in. for 175 psig Valves

VF4-D3000-205 D-3246-51x0 Actuator Mounting Kit for 6 in. 50 or 175 psig Valves

VF4-D3000-206 D-3246-51x0 Actuator Mounting Kit for 8 in. 50 psig Valves

VF4-D3000-207 D-3246-51x0 Actuator Mounting Kit for 8 in. 175 psig Valves (Includes Parts for Mounting Two Actuators)

VF4-D3000-208 D-3246-51x0 Actuator Mounting Kit for 10 in. 50 psig Valves (Includes Parts for Mounting Two Actuators)

1. The mounting kits contain a mounting bracket, crankarm, sleeve adaptor, a clevis kit, and all necessary hardware for completing actuator field mounting D-3000 Series Actuator to bare stem VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).

Table 44: Conversion Kits for Changing the Configuration of VF4000 and VF6000 Series Three-Way Valve Assemblies with D-3000 Series Pneumatic Piston Actuators (Part 1 of 4)

Valve Size Existing Assembly Desired Assembly Conversion Kit1

2 in. VF4831AD VF4831AE or VF4831AF VF4-D3000-301

VF4831AG VF4-D3000-302

VF4831AE VF4831AD VF4-D3000-303

VF4831AF 2

VF4831AG VF4-D3000-304

VF4831AF VF4831AD VF4-D3000-303

VF4831AE 2

VF4831AG VF4-D3000-304

VF4831AG VF4831AD VF4-D3000-305

VF4831AE or VF4831AF VF4-D3000-301

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

30

2-1/2 in. VF4831BD VF4831BE or VF4831BF VF4-D3000-301

VF4831BG VF4-D3000-302

VF4831BE VF4831BD VF4-D3000-303

VF4831BF 2

VF4831BG VF4-D3000-304

VF4831BF VF4831BD VF4-D3000-303

VF4831BE 2

VF4831BG VF4-D3000-304

VF4831BG VF4831BD VF4-D3000-305

VF4831BE or VF4831BF VF4-D3000-301

3 in. VF4831CD VF4831CE or VF4831CF VF4-D3000-306

VF4831CG VF4-D3000-307

VF4831CE VF4831CD VF4-D3000-308

VF4831CF 2

VF4831CG VF4-D3000-309

VF4831CF VF4831CD VF4-D3000-308

VF4831CE 2

VF4831CG VF4-D3000-309

VF4831CG VF4831CD VF4-D3000-310

VF4831CE or VF4831CF VF4-D3000-306

Table 44: Conversion Kits for Changing the Configuration of VF4000 and VF6000 Series Three-Way Valve Assemblies with D-3000 Series Pneumatic Piston Actuators (Part 2 of 4)

Valve Size Existing Assembly Desired Assembly Conversion Kit1

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

31

4 in. VF4831DD VF4831DE or VF4831DF VF4-D3000-306

VF4831DG VF4-D3000-307

VF4831DE VF4831DD VF4-D3000-308

VF4831DF 2

VF4831DG VF4-D3000-309

VF4831DF VF4831DD VF4-D3000-308

VF4831DE 2

VF4831DG VF4-D3000-309

VF4831DG VF4831DD VF4-D3000-310

VF4831DE or VF4831DF VF4-D3000-306

VF6831DD VF6831DE or VF6831DF VF4-D3000-306

VF6831DG VF4-D3000-307

VF6831DE VF6831DD VF4-D3000-308

VF6831DF 2

VF6831DG VF4-D3000-309

VF6831DF VF6831DD VF4-D3000-308

VF6831DE See Note

VF6831DG VF4-D3000-309

VF6831DG VF6831DD VF4-D3000-310

VF6831DE or VF6831DF VF4-D3000-306

5 in. VF4831ED VF4831EE or VF4831EF VF4-D3000-311

VF4831EG VF4-D3000-312

VF4831EE VF4831ED VF4-D3000-313

VF4831EF 2

VF4831EG VF4-D3000-314

VF4831EF VF4831ED VF4-D3000-313

VF4831EE 2

VF4831EG VF4-D3000-314

VF4831EG VF4831ED VF4-D3000-315

VF4831EE or VF4831EF VF4-D3000-311

VF6831ED VF6831EE or VF6831EF VF4-D3000-311

VF6831EG VF4-D3000-312

VF6831EE VF6831ED VF4-D3000-313

VF6831EF 2

VF6831EG VF4-D3000-314

VF6831EF VF6831ED VF4-D3000-313

VF6831EE 2

VF6831EG VF4-D3000-314

VF6831EG VF6831ED VF4-D3000-315

VF6831EE or VF6831EF VF4-D3000-311

Table 44: Conversion Kits for Changing the Configuration of VF4000 and VF6000 Series Three-Way Valve Assemblies with D-3000 Series Pneumatic Piston Actuators (Part 3 of 4)

Valve Size Existing Assembly Desired Assembly Conversion Kit1

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

32

6 in. VF4831FD VF4831FE or VF4831FF VF4-D3000-311

VF4831FG VF4-D3000-312

VF4831FE VF4831FD VF4-D3000-313

VF4831FF 2

VF4831FG VF4-D3000-314

VF4831FF VF4831FD VF4-D3000-313

VF4831FE 2

VF4831FG VF4-D3000-314

VF4831FG VF4831FD VF4-D3000-315

VF4831FE or VF4831FF VF4-D3000-311

VF6831FD VF6831FE or VF6831FF VF4-D3000-311

VF6831FG VF4-D3000-312

VF6831FE VF6831FD VF4-D3000-313

VF6831FF 2

VF6831FG VF4-D3000-314

VF6831FF VF6831FD VF4-D3000-313

VF6831FE 2

VF6831FG VF4-D3000-314

VF6831FG VF6831FD VF4-D3000-315

VF6831FE or VF6831FF VF4-D3000-311

8 in. VF6831GD VF6831GE or VF6831GF VF4-D3000-316

VF6831GG VF4-D3000-317

VF6831GE VF6831GD VF4-D3000-318

VF6831GF 2

VF6831GG VF4-D3000-319

VF6831GF VF6831GD VF4-D3000-318

VF6831GE 2

VF6831GG VF4-D3000-319

VF6831GG VF6831GD VF4-D3000-320

VF6831GE or VF6831GF VF4-D3000-316

1. The conversion kit includes the necessary levers and threaded rod. These kits are designed for VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).

2. A conversion kit is not required when converting between Styles E and F; simply switch the valve with the actuator and bracket to the opposite flange, and adjust the valves to the desired normally open and normally closed positions

Table 44: Conversion Kits for Changing the Configuration of VF4000 and VF6000 Series Three-Way Valve Assemblies with D-3000 Series Pneumatic Piston Actuators (Part 4 of 4)

Valve Size Existing Assembly Desired Assembly Conversion Kit1

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

33

Table 45: D-3000 Replacement BracketsPneumatic Actuator

Bracket Kit1

D-3153 VF4-D3000-601

D-3244 VF4-D3000-602

D-3246 VF4-D3000-603

Two D-3246 VF4-D3000-604

1. For VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).

Table 46: D-3000 Replacement CrankarmsPneumatic Actuator Crankarm

Kit1

Master Lever, Three-Way, Styles D and G and Normally Open Two-Way with Tandem D-3246

VF4-D3000-610

Master Lever, Three-Way, Styles E and F and Normally Closed Two-Way with Tandem D-3246

VF4-D3000-611

Slave Lever, Three-Way Style D VF4-D3000-612

Slave Lever, Three-Way Style E and F

VF4-D3000-613

Slave Lever, Three-Way Style G VF4-D3000-614

Two-Way with One D-3000 Series Actuator

VF4-D3000-615

1. For VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).

Table 47: D-3000 Replacement Sleeve AdaptorsValve Size Sleeve Adaptor

Kit1

2, 2-1/2, and 3 in. VF4-D3000-620

4 and 5 in. VF4-D3000-621

6 in. VF4-D3000-622

8 in. VF4-D3000-623

1. For VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).

Table 48: Clevis Kits for Field Repair of D-3153, D-3244, and D-3246 Series Pneumatic Actuators

Pneumatic Actuator Clevis Kit1

D-3153 VF4-D3000-630

D-3244 VF4-D3000-631

D-3246 VF4-D3000-632

Three-Way Tandem Actuators VF4-D3000-633

1. Clevis kit includes clevis, clevis pin, and clevis hair pin. These kits are designed for VF4000 and VF6000 Series Valves date coded 0501 or later (manufactured 2005 or later).

Table 49: Mounting Kits for Field Mounting M9000 Series Electric Actuators on Two-Way VF4000 Series Butterfly Valves

Mounting Kit Code Number1

Valve Size Actuator

VF4-M9000-120 2, 2-1/2, and 3 in. M9116

VF4-M9000-121 4 and 5 in. M9124

VF4-M9000-122 6 in. Tandem M9124

VF4-M9000-123 2, 2-1/2, and 3 in. M9220

VF4-M9000-124 4 in. M9220

VF4-M9000-125 5 in. Tandem M9220

1. Mounting kit includes all brackets and hardware to mount M9000 Series Actuators to a bare stem VF4000 Series Valve date coded 0501 or later (manufactured 2005 or later).

Table 50: Mounting Kits for Field Mounting M9000 Series Electric Actuators on Three-Way VF4000 Series Butterfly Valves

Mounting Kit Code Number1

Valve Size Actuator

VF4-M9000-130 2, 2-1/2 and 3 in. M9116

VF4-M9000-131 4 in. M9124

VF4-M9000-132 5 in. Tandem M9124

VF4-M9000-133 6 in. Tandem M9124

VF4-M9000-134 2, 2-1/2, and 3 in. M9220

VF4-M9000-135 4 in. Tandem M9220

1. Mounting kit includes all brackets and hardware to mount M9000 Series Actuators to a bare stem VF4000 Series Valve date coded 0501 or later (manufactured 2005 or later).

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

34

Table 51: Weather Shield Kits for Field Installation on Two-Way VF4000 Series Valves with M9000 Series Electric Actuators

Mounting Kit Code Number1

1. Weather shield kit includes weather shield and all necessary hardware for installation on an existing VF4000 Series Valve and M9000 Series Actuator assembly date coded 0501 or later (manufactured 2005 or later).

Valve Size Actuator

VF4-M9000-140 2, 2-1/2, and 3 in. M9116

VF4-M9000-141 4 and 5 in. M9124

VF4-M9000-142 6 in Tandem M9124

VF4-M9000-143 2, 2-1/2, and 3 in. M9220

VF4-M9000-144 4 in. M9220

VF4-M9000-145 5 in. Tandem M9220

Table 52: Weather Shield Kits for Field Installation on Three-Way VF4000 Series Valves with M9000 Series Electric Actuators

Mounting Kit Code Number1

1. Weather shield kit includes weather shield and all necessary hardware for installation on an existing VF4000 Series Valve and M9000 Series Actuator assembly date coded 0501 or later (manufactured 2005 or later).

Valve Size Actuator

VF4-M9000-150 2, 2-1/2, and 3 in. M9116

VF4-M9000-151 4 in. M9124

VF4-M9000-152 5 in. Tandem M9124

VF4-M9000-153 6 in. Tandem M9124

VF4-M9000-154 2, 2-1/2, and 3 in. M9220

VF4-M9000-155 4 in. Tandem M9220

Table 53: M9000 Replacement BracketsActuator Code Number1

M9116 or M9124 VF4-M9000-640

Tandem M9124 (Also Requires VF4-M9000-640)

VF4-M9000-641

M9220 VF4-M9000-642

Tandem M9220 (Also Requires VF4-M9000-642)

VF4-M9000-643

M9116 or M9124 with Weather Shield

VF4-M9000-644

M9220 with Weather Shield VF4-M9000-645

1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).

Table 54: Replacement Levers for Three-Way Valve Assemblies with M9000 Series Actuators

Valve Size Code Number1

2, 2-1/2, and 3 in. VF4-M9000-650

4 and 5 in. VF4-M9000-651

6 in. VF4-M9000-652

1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).

Table 55: Replacement Couplers for Two-Way Valve Assemblies with M9000 Series Actuators

Valve Size

Actuator Code Number1

2, 2-1/2, and 3 in.

M9116 or M9220 VF4-M9000-660

4 and 5 in. M9124 VF4-M9000-661

4 in. M9220

6 in. Tandem M9124 VF4-M9000-662

5 in. Tandem M9220 VF4-M9000-663

1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

35

Technical Specifications

Table 56: Replacement Couplers for Three-Way Valve Assemblies with M9000 Series Actuators

Valve Size

Actuator Code Number1

2, 2-1/2, and 3 in.

M9116 or M9220 VF4-M9000-670

4 in. M9124 VF4-M9000-671

5 in. Tandem M9124 VF4-M9000-672

4 in. Tandem M9220

6 in. Tandem M9124 VF4-M9000-673

1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).

Table 57: Rod End Kit for Three-Way Valve Assemblies with M9000 Series Actuators

Valve Size Code Number1

Three-Way, All Sizes VF4-M9000-680

1. For VF4000 and VF5000 Series Valves date coded 0501 or later (manufactured 2005 or later).

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves1 (Part 1 of 2)Service Hot, Chilled, or Condenser Water, and 50/50 Glycol Solutions

(Not Designed for Use in Steam Applications)

Models and Ordering Data See Table 5 through Table 30.

Body Styles and Sizes Two-Way and Three-Way, 2 through 10 in., Fully Lugged

Fluid Temperature Limits -30 to 250°F (-34 to 121°C)

Maximum Closeoff Pressure

See Table 9 through Table 30. (All Valves are Rated for Dead-End Service; Maximum Dead-End Pressure Rating is 150 psig)

Maximum Fluid Velocity 30 ft/Second (9 m/Second)

Rangeability 80:1 Minimum

Leakage Bubble Tight, Bidirectional Shutoff Rated for Dead-End Service (Uni-Directional); Inlet Must Face Pressure

Flow Characteristics Modified Equal Percentage (See Figure 2.)

Flow Coefficients (Cv) See Table 2 through Table 4.

Materials Body Cast Iron, ASTM A126 CL B

Tee (Three-Way Valves Only)

Cast Iron

Disk Aluminum Bronze, ASTM B148

Seal and Liner Ethylene Propylene Diene Monomer (EPDM)

Stem 416 Stainless Steel

Bearings Reinforced Polytetrafluoroethylene (RPTFE)

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

36

Ambient Temperature Limits

Storage -20 to 150°F (-29 to 66°C); Preferably 40 to 85°F (4 to 29°C)

Operating Spring Return Actuator (M9220 Series): -40 to 131°F (-40 to 55°C)

Non-Spring Return Actuator (M91xx Series): -4 to 122°F (-20 to 50°C)

Weather Shield Rating NEMA 4

Valve and Actuator Assembly Shipping Weights

See Table 39 and Table 40.

Repair Parts Valve None available; for a Replacement Valve Body, configure the appropriate code number from the first eight fields in Table 5.

Actuators and Brackets

See Table 41 through Table 57.

1. Refer to the appropriate actuator product bulletin for actuator specifications. All information included in this product bulletin is for valves date coded 0501 or later (manufactured 2005 or later).

The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult the local Johnson Controls office. Johnson Controls, Inc. shall not be liable for damages resulting from misapplication or misuse of its products.

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves1 (Part 2 of 2)

Published in U.S.A. www.johnsoncontrols.com

VF Series M9000 Electrically and D-3000 Pneumatically Actuated Standard-Pressure, Standard-Temperature Butterfly Valves Product Bulletin

37

Controls Group507 E. Michigan StreetMilwaukee, WI 53202

Metasys® is a registered trademark of Johnson Controls, Inc.All other marks herein are the marks of their respective owners.

© 2007 Johnson Controls, Inc.