Vertical Water Source Heat Pumps

44
Catalog C: 1160-9 Vertical Water Source Heat Pumps Unit Sizes 1 /2 to 5 Tons (2.1 to 15.0 kW) ® R M A N U F A C T U R E R C E R TIFIE D TO A R I A S C O M P L Y I N G W I T H I S O S T A N D A R D 1 3 2 5 6 -1 H E A T P U M P S W A T E R T O A IR B R IN E T O A I R

Transcript of Vertical Water Source Heat Pumps

Page 1: Vertical Water Source Heat Pumps

Catalog C: 1160-9

Vertical Water Source Heat PumpsUnit Sizes 1⁄2 to 5 Tons(2.1 to 15.0 kW)

®

R

MA

NU

FAC

TURE

R

CERTIFIED TO ARI AS COMPLYIN

GW

ITH

ISOSTANDARD 13256-1

HEAT PUMPS

WA

TE

RTO

AIR BRINETO

AIR

Page 2: Vertical Water Source Heat Pumps

Page 2 / Catalog 1160

Vertical water source heat pump units

Features:m High efficiency. EERs from 10.4 to 12.0

COPs from 3.8 to 4.0.m Performance rated with ISO Standard 13256-1.m Safety agency listed with CETL.m Multiple panels for easy accessibility to

compressor and fan sections.m Removable fan motor/wheel assembly.m Two return air configurations.m High and low side refrigerant service valves.

(7/00)

. . . and featuring the Mark IV/AC control system with:m Built-in night setback, load shed, shutdown,

and 2-hour override operation.m Compressor short cycle protection.m Random start.m Silent reversing valve operation.

m LED readout.m Condensate overflow protection.m Automatic defrost cycle.m Optional boilerless system control.m Optional pump restart.

m Multi-space fan motor with terminal strip.m High cfm/ton performance.m High sensible cooling performance.m Low unit height.m Circuit board control system for “clean”

wiring.m Freezestat protected water circuit.m Optional extended range heating operation.m Fully rated 50 cycle units.

“AAF,” “McQuay” and “MicroTech” are registered trademarks of AAF-McQuay Incorporated.©AAF-McQuay Incorporated 2000. All rights reserved throughout the world.

The information in this catalog supersedes and replaces previous (catalogues)(bulletins) with regards to AAF-McQuay TerminalAir Conditioning products. Illustrations cover the general appearance of AAF-McQuay products at the time of publication and

AAF-McQuay reserves the right to make changes in design and construction at anytime without notice.

. . . and even more control options and accessory itemsfor a complete water source heat pump installation.

Unit Sizes007, 009 & 012

Unit Sizes015 & 019

Unit Sizes024 & 030

Unit Sizes036 & 042

Unit Sizes048 & 060

Page 3: Vertical Water Source Heat Pumps

Catalog 1160 / Page 3

ContentsModel nomenclature ...................................................... 3ISO performance data ................................................... 4Design features .............................................................. 5Control features ............................................................. 7Airflow correction factors ............................................ 1250 cycle correction factors .......................................... 12Operating limits ............................................................ 13Capacity data ............................................................... 14

Physical data ............................................................... 36Fan performance data ................................................. 36Electrical data .............................................................. 37Dimensional data ......................................................... 38Typical Mark IV unit wiring diagrams .......................... 39Typical Microtech unit wiring diagrams ...................... 40Thermostat connection diagrams ............................... 41Engineering guide specifications ................................ 42

NOTE: For illustration purposes only. Not all options available with all models.Please consult AAF-McQuay Sales Representative for specific availability.

AAF-McQuay WSHP Product Nomenclature

W FMS 1 009 E Z

Product CategoryW = WSHP

Product IdentifierSee box below

Design Series1 = A Design2 = B Design3 = C Design4 = D Design5 = E Design

Nominal Capacity007 = 7,000009 = 9,000012 = 12,000015 = 15,000019 = 19,000etc....

Coil Options(None)

VoltageE = 208/230-60-1F = 208/230-60-3J = 265-60-1K = 460-60-3L = 575-60-3M = 230-50-1N = 380-50-3

FDD = Floor mtd/DDC Controls/Ext. Range/Less BoardFDE = Floor mtd/DDC Controls/Ext. RangeFDL = Floor mtd/DDC Controls/Std. Range/Less BoardFDS = Floor mtd/DDC Controls/Std. RangeFME = Floor mtd/Mark IV/Ext. RangeFMS = Floor mtd/Mark IV/Std. Range

Product Identifier

Model nomenclature

Page 4: Vertical Water Source Heat Pumps

Page 4 / Catalog 1160

ISO performance dataRated in Accordance With ISO Standard 13256-1

UNIT SIZE AIRFLOW VOLTAGECFM L/S

WATERFLOWGPM L/S

HEATINGCOP

COOLINGEER COPBTU/HR BTU/HR

Notes:EER = Energy Efficiency Ratio COP = Coefficient of Performance L/s = liters per secondCooling capacity is based on 80˚F (27˚C) db, 67˚F (19˚C) wb entering air temperature and 85˚F (29˚C) entering, 95˚F (35˚C) leaving water termperature.Heating capacity is based on 70˚F (21˚C) db entering air temperature and 70˚F (21˚C) entering water temperature.

230 109 1.8 0.11 208-230/60/1 6800 1984 10.4 3.0 9800 2859 3.8007 265/60/1

1.6 0.10 230/50/1 6000 1750 10.6 3.1 8600 2509 3.8300 142 2.3 0.15 208-230/60/1 8800 2567 10.7 3.1 12000 3500 3.9

009 265/60/12.0 0.13 230/50/1 8100 2363 10.8 3.1 10500 3063 3.8

400 189 3.2 0.20 208-230/60/1 11600 3384 11.2 3.2 14000 4084 3.8012 265/60/1

3.0 0.19 230/50/1 10202 2975 11.4 3.3 12200 3559 3.9

3.5 0.22208-230/60/1

13100 3821 12.3 3.6 17200 5017 4.1015 500 236 265/60/1

3.2 0.20 230/50/1 11500 3355 12.6 3.7 15100 4405 4.2

5.1 0.32208-230/60/1

19000 5542 11.6 3.4 23500 6855 3.8019 630 297 265/60/1

4.6 0.29 230/50/1 16700 4871 11.9 3.5 20700 6038 3.9208-230/60/1

6.4 0.40 265/60/1 24400 7117 12.0 3.5 32000 9334 4.0024 800 378 208-23 6

460/60/35.8 0.37 230/50/1 21505 6272 12.4 3.6 28000 8168 4.1

208-230/60/1

7.9 0.50 265/60/1 29600 8634 11.9 3.5 39000 11376 3.9030 1000 472 208-230/60/3

460/60/37.1 0.45 380/50/3 26000 7584 12.3 3.6 34300 10005 4.0

208-230/60/1

9.3 0.59 265/60/1 35200 10268 11.9 3.5 45000 13127 4.0036 1200 566 208-230/60/3

460/60/38.4 0.53 380/50/3 31000 9043 12.3 3.6 39500 11522 4.1

208-230/60/1042 1400 661 11.0 0.69 208-230/60/3 41800 12193 12.0 3.5 53000 15460 4.0

460/60/39.9 0.62 380/50/3 37500 10939 12.4 3.6 46500 13564 4.1

208-230/60/1

12.1 0.76 208-230/60/3 46000 13470 120.9 3.5 56000 16400 4.3048 1600 755 460/60/3

575/60/312.0 0.76 380/50/3 41000 12440 12.5 3.8 49000 14760 4.4

208-230/60/1

15.8 1.00 208-230/60/3 58000 17000 12.0 3.2 78000 22860 3.9060 2200 1038 460/60/3

575/60/315.8 1.00 380/50/3 52000 15490 11.2 3.4 68000 20350 4.0

WATTS WATTS

Page 5: Vertical Water Source Heat Pumps

Catalog 1160 / Page 5

Design features

Each water source heat pump is factory assembled andtested to insure reliability. Servicing is done easily throughlarge removable access panels to internal components. Afull height access panel on the back side allows access tothe compressor and fan section. An upper front panel allowsaccess to the fan motor. Two lower panels allow access tothe compressor/control box section. Each unit is shippedon a wooden skid to facilitate moving with a forklift andcovered with corrugated material for maximum protection.

Five unique cabinet sizes make up our 1/2 through 5 ton(2.1 through 15.0 kW) vertical heat pump product line. Theresult is a consistent cabinet shape with the lowest possibleprofile. The consistent shape makes layout simple; the water,condensate and duct connection locations are the same forall units.

For maximum flexibility, each unit is available in either aleft-hand or right-hand return air arrangement to provide theoptimum piping location and service access.

The cabinet is constructed of unpainted, G-60 galvanizedsteel. Large panels are provided for access to the fan/motorcompartment and the compressor/control compartment. Theinteriors of the top and side panels and the bottom of theunit are covered with 1⁄2" thick (13 mm), 11⁄2 lb. (681 g) densitycoated glass fiber. The 1" (25 mm) thick filter is supportedby factory mounted brackets which allow for face, side orbottom removal.

The water and condensate connections protrude throughthe outside of the cabinet for maximum accessibility. The

water connections are FPT type for easy connection toflexible hoses. The large 7/8" (22 mm) O.D. condensateconnection assures trouble-free condensate removal.

The electrical components are located in the compressorsection of the unit. Holes provided on the side of the cabinetto facilitate main power and low voltage control wiringthrough separate holes. All wiring connections are madeinternal to the cabinet for maximum safety. Each unit is ratedto accept time delay fuses or HACR circuit breakers forbranch circuit overcurrent protection.

The control box is accessible through a panel and canbe moved without access to the side of the unit to allow foreasier compressor removal. The control box houses themajor operating electrical controls including the controlcircuit board, transformer, compressor relay and fan relay.Each component is accessible for service or replacement.

Two unique control systems are offered: Mark IV/AC orMicroTech®, each utilizing a printed circuit board. The printedcircuit board approach allows for direct quick-connect wiringto the controlled components making for “clean” wiring. Eachcontrol board receives power from a large capacity 50 VAtransformer. The control board has a built-in terminal stripfor low voltage control wiring connections. The Mark IV/ACcontrol board provides the basic control functions along withthe numerous advanced features. MicroTech is an advanceddirect digital control system. See the “Controls” section formore detailed information.

Page 6: Vertical Water Source Heat Pumps

Page 6 / Catalog 1160

Refrigeration systemThe refrigeration system includes a hermetic compresser,reversing valve, water-to-refrigerant coaxial heat exchanger,capillary tube expansion device, airside coil, safety controls,and both high and low refrigerant service valves. Two panelsallow for access to the compressor, reversing valve andsafety controls.

The compressor is isolated from the bottom panel withrubber isolators. The compressor junction box is alwayslocated toward the front access panel.

The reversing valve is located so as not to interfere withcompressor removal through the access panel. The valve isenergized in the heating mode and will “fail-safe” to thecooling mode which is the predominate mode of operation.

The two heat exchanger components incorporate themost recent transfer technologies. The coaxial heatexchanger has a copper inner tube and a steel outer tubeand is designed for a maximum heat transfer at normal andlow water flow rates with minimum pressure drop. The largeface area coil has copper tubes and aluminum fins. The finsare lanced and the tubes have finned edges on the inside toenhance heat transfer capabilities.

Safety controls include low suction temperature(freezestat) and high pressure switches to lock outcompressor operation at extreme conditions. The low suctiontemperature switch provides the most reliable protectionagainst freezeup of the coaxial heat exchanger without thenuisance trips associated with low pressure switches whichonly protect against low refrigerant charge. The safetycontrols can only be reset from the main disconnect switchand not from the wall thermostat which preventsunauthorized reset of the unit, which may permanentlydamage a major component.

Fan sectionThe fan section includes the fan housing, fan wheel, fanmotor and drain pan. The fan section is separated from thecompressor section with an insulated drain pan and dividerpanel for maximum sound attenuation. The upper panelprovide service access to the fan motor. The separate frontfan and compressor section access panels allow for fanoperation and compressor operation checkout without airbypass around the coil.

The drain pan is of ample height to allow for self-primingof the condensate trap. All of this assures trouble-freecondensate removal.

The fan motor is a multispeed, PSC type with integralmounting brackets and thermal overload protection. Themotor is isolated from the fan housing for minimum vibrationtransmission. Unit sizes 015 and larger have a terminal stripon the motor for simple motor speed change without goingback to the control box. All the fan/motor assemblies havea removable orifice ring on the housing to accommodatemotor and fan wheel removal without disconnecting theductwork. The fan housing protrudes through the cabinetallowing adequate material for connection of a flexible duct.

Optional factory installed featuresExtended range units are available for applicationsrequiring heating operation at reduce entering conditions.The extended range unit will operate at 40°F (5°C) minimumentering water temperature and 40°F (5°C) minimum enteringair temperature. The unit is modified with a suction line

accumulator, insulated coaxial heat exchanger, insulatedrefrigerant tubing, compressor crankcase heater and a lowersetting on the freezestat safety switch.

The extended range system has advantages in closedloop applications. The ability to operate at reduced waterconditions allows the loop water temperature to fall to 40°F(5°C) before supplemental (boiler) heat has to be added tothe loop, thus taking full advantage of the heat available inthe water loop obtained from internal heat gains. The resultis reduced boiler operation which means reduced energyconsumption.

Left-handreturn

Right-handreturn

Page 7: Vertical Water Source Heat Pumps

Catalog 1160 / Page 7

Mark IV/AC control systemThe Mark IV/AC control system is specifically designed forour water source heat pump units and provides control ofthe entire unit as well as outputs for unit status and “fault”detection. The built-in safety and operating features of theMark IV/AC control system assure safe operation of the unitwhich extends the equipment life.

The Mark IV/AC control system is a microprocessor-basedcontrol board conveniently located in the unit control sectionfor accessibility. The Mark IV/AC control board has quick-connect terminals for simple connection of controlcomponents. A 14-pin low voltage terminal strip providesall the necessary terminals for control connections. LEDsare located in front for quick inspection. The board is 24 voltAC at the thermostat.

The Mark IV/AC control system requires standard typeheating and cooling mercury bulb wall thermostats; there isno need for special “heat pump” thermostats.

The Mark IV/AC control system has the following operatingfeatures:

• Start-up. The unit will not operate until all the inputs andsafety controls are checked for normal conditions.

• Cooling Mode. On a call for cooling, the compressor andfan will start 0 to 32 seconds later. When satisfied, thecompressor and fan shut off immediately.

• Heating Mode. On a call for heating, the reversing valveis energized after 60 seconds and the compressor andfan start immediately. When satisfied, the compressor andfan shut off immediately, the reversing valve isde-energized 60 seconds later to eliminate “swish” noiseand to insure that the compressor always starts up atequalized pressure.

• Short Cycle Protection and Random Start. Each timethe compressor stops, a new random compressor startdelay time between 180 and 212 seconds is generatedeach time power is applied to the unit. This preventscompressor short cycling and assures units will not startat the same time after coming back from an unoccupied cycle.

• Unoccupied Mode. A simple “grounded” signal, no powersource required, puts the unit into the unoccupied modefor night setback operation. The fan shuts off and the unitis put under control from the setback bulb of thethermostat; the day heating thermostat control and coolingis locked out. Not connecting the setback temperatureterminal of the wall thermostat accomplishes a simple“shutdown” mode. A unique LED status is generated forindication of the unoccupied mode. On a call for heating,the fan and the compressor will start after 0 to 32 seconds.

• Override Mode. A switch on the deluxe thermostat canbe activated during the unoccupied mode to put the unitback into the occupied mode for two hours for after-hoursheating or cooling.

• Pump Restart. A signal from the Mark IV/AC board to ourLoop Water Control Panel will restart the water circulatingloop pump when the compressor is energized.

• Load Shed. Again, a simple grounded signal puts the unitinto the load shed mode. The compressor shuts off andthe fan will start on a call for heating or cooling.Compressor power consumption is eliminated and the fanoperation will mask the fact that heating and cooling

Control Features

operation has been temporarily suspended. A unique LEDstatus is generated for indication of the load shed mode.

• Brownout Protection. The Mark IV/AC board measuresthe input voltage and will suspend compressor and fanoperation if the voltage falls below 80% of the nominalline voltage. A unique LED status is generated and anoutput signal is made available for connection to a “fault”LED at the thermostat.

• Unit Shutdown. Again, a simple grounded signal puts theunit into the shutdown mode. Compressor and fanoperations are suspended. A unique LED status isgenerated and an output signal is made available forconnection to a “fault” LED at the thermostat.

• Condensate Overflow Protection. The Mark IV/AC boardincorporates a liquid sensor at the top of the drain pan.Sensing water, cooling operation is suspended. A uniqueLED status is generated and an output signal is madeavailable for connection to a “fault” LED at the thermostat.Heating operation is not suspended in this mode.

• Safety Control. The Mark IV/AC board receives separateinput signals from the refrigerant high pressure switch andthe low suction temperature (freezestat) switch. In a highpressure situation, compressor operation is suspended.In a low temperature situation, the unit goes into a defrostcycle where the unit is put into cooling operation for 60seconds which will assure that the coaxial heat exchangeris free of ice. Each switch generates its own unique LEDstatus and an output signal is made available forconnection to a “fault” LED at the thermostat if eithersituation exists.

• Testing. The Mark IV/AC board allows service personnelto eliminate the fan, reversing valve and compressor timedelays for faster diagnostics. The output terminals andexposed quick-connect terminals allow troubleshootingwith a voltmeter.

Mark IV/AC and fault outputs

IndicationLEDs Fault

Yellow Green Red OutputNormal Mode Off On Off OffHigh Pressure Fault Off Off Flash OnLow Temperature Fault Flash Off Off OnCondensate Overflow On Dim Off OnBrownout Off Flash Off OnLoad Shed Off Off On OffUnoccupied Mode On On Off OffUnit Shutdown Off Flash Off On

Page 8: Vertical Water Source Heat Pumps

Page 8 / Catalog 1160

GroundTime Clock

inOccupied Mode

Unit1

Unit2

Unit3

ToAdditional

Units

The Mark IV/AC control system allows for the followingoptional field installed controls and accessories:

• Boilerless System Kit. Eliminates the need for a boiler inthe system water loop. The boilerless system control boardsenses the entering water temperature to the unit andlocks out compressor heating operation if the watertemperature falls below the adjustable setpoint. Contactsare provided to energize a field supplied electric heaterdownstream of the unit on a call for heating.

• Auxiliary Relay. Available to control other devices whenthe fan operates. The relay can also be factory mounted.

• Multiple Unit Control Panels. Allow a single thermostatto control up to three units in parallel.

• Motorized Valve. Used for variable pumping applications.The valve is wired in the compressor circuit and is pipedin return water line from the unit. The valve opens whenthe compressor is on and closes when the compressor isoff. Valve is rated for 300 psig (2070 kPa).

To activate the unoccupied mode for units on the same clockschedule, a single wire can be “daisy chained” between unitsand simply grounded through the time clock contacts. Thesame system can also be done to activate the load shed andemergency shutdown modes by running additional wiresbetween units to ground.

Field wiring to activate unoccupied mode

Page 9: Vertical Water Source Heat Pumps

Catalog 1160 / Page 9

Loop Water Controller (LWC)

The Loop Water Controller (LWC) is a stand-alone,preprogrammed, pre-tested, microprocessor-basedcontroller providing control of the heat rejection, heat additionstages and the water circulating pumps for control of a watersource heat pump system through solid-state output relays. The controller has a keypad/display to view all statusconditions, temperatures, setpoints and monitor/alarmconditions. The display is two lines by sixteen columns in asupertwist LCD format. The LWC can be applied to control a traditional single loopsystem; closed circuit evaporative cooler, boiler, primarypump and standby pump; or a two-loop system with theheat pump loop having a boiler, primary pump and standbypump separated by a water-to-water heat exchanger to acondenser water loop with an open cooling tower, primary(stage 1) pump and a standby (stage 2) pump. The pumpscan be operated as “auto” or “manual” lead-lag. Pumpsequencing allows the standby pump to automatically comeon upon failure of the lead pump as indicated by a flowswitch. The LWC controls heating and cooling stages from the heatpump loop supply temperature and from the outdoor airtemperature for reset of the heat addition setpoint, if desired.Other locations can be temperature monitored: heat pumploop return temperature, entering and leaving towertemperatures, entering and leaving boiler temperatures, andstorage tank temperature. Clock schedule outputs are built-in to (1) time control theheat pump circulating pump for shutdown at night (can berestarted if outdoor air temperature falls) and (2) provideprogrammable time schedules for heat pump unit occupied/unoccupied operation. A maximum of six time clock scheduleoutputs are available. Two LWC models are available. LWC-16 and LWC-24provide 9 and 17 configurable outputs, respectively, choosingbetween heat rejection (cooling) stages, heat addition(heating) stages and time clock schedules. Each heating andcooling output has individual on and off (differential) setpointadjustment capability. Modulating heating and cooling outputsignals are available to control tower bypass valve and two-way or three-way boiler heat addition valves.

Safety alarms include visual and audible notification of alow water temperature, high water temperature, or no flowcondition. Upon activation of any alarm, the LWC hascontacts to send out an emergency shutdown signal. Aremote alarm panel is available for alarm notification at aremote location. The LWC interfaces with Mark IV/AC controlled heat pumpunits for a low cost control system. The Mark IV/AC boardcan receive occupied/unoccupied time clock scheduleoutputs and an emergency shutdown signal (pump restart)from the Mark IV/AC board to energize and override the maincirculating pump, if it is scheduled off, whenever acompressor operates from a call for night setback heat orfrom a call for heating or cooling during the two-hour overridecycle. Simple “daisy chain” wiring is required between MarkIV/AC board terminals. Optional Microtech MonitorTM for Windows Software allowsthe operator to monitor and control setpoints of the LWC atan IBM PC by direct connecting or through a phone line.Includes system graphics.

Additional features include built-in test mode to simulateall control modes, pre-cool cycle to start heat rejection earlierfor undersized boilers, pre-heat cycle to start heat additionearlier for undersized towers, keypad password protection,and holiday schedules.

Mark IV/AC Interface

Mark IV/AC Board TerminalsP = Pump RestartC = CommonU = UnoccupiedE = Unit ShutdownL = Load ShedF = Fault Relay

ThermostatO = 2-Hour OverrideW2 = Night Setback HeatingG = FanW1 = Day HeatingY1 = CoolingR = Power — AC VoltsA = Altitude Fault Signal to LED

O W2 G W1 Y1 R A

F P C U E L F P C U E L

O W2 G W1 Y1 R A

Mark IV/ACBoard

Deluxe AutoChangeover

Wallstat

Deluxe AutoChangeover

Wallstat

PumpRestart

Unocc.Sched.

UnitShut-down

Loop WaterController

PumpRestart

Relay

OptionalPersonalComputer

Heat Pump Supply Loop Temp.

Heat Pump Loop Flow SwitchOutside Air Temp.

Optional Temperature Sensors

Optional Condenser Loop Flow Switch

Optional Condenser Loop Temp.

Heat Pump Loop Pumps

Condenser Loop PumpsHeat Rejection Stages

Modulating Heat Rejection

Heat Addition Stages

Modulating Heat Addition

Additional UnoccupiedSchedules — 6 Total

Pump Restart}Unoccupied

Optional Load Shed Input

Unit Shutdown

INPUTS OUTPUTS

Mark IV/ACBoard

Page 10: Vertical Water Source Heat Pumps

Page 10 / Catalog 1160

MicroTech 2000 water sourceheat pump controller

Each vertical heat pump unit is available with a newMicroTech water source heat pump unit controller. The newcontroller is a microprocessor-based control systempreprogrammed with the software required to monitor andcontrol the unit. The controller enables the mode ofoperation, monitors the water and air temperatures, andcommunicates fault conditions.The controller includespassword protection to protect against unauthorized oraccidental setpoint or parameter changes.

The new MicroTech control system includes unit-mountedreturn air, discharge air and leaving water temperaturesensors; optional tenant setpoint adjustment knob andtenant override button; and the capability of replacing thereturn air sensor with a wall-mounted roorn sensor.

The PC has the ability to communicate with each heatpump unit and the entire system through two dedicatedtwisted conductors. Each controller utilizes LonWorkstechnology, retaining programmable setpoint parametersand control logic. Each controller may operate stand-alone,independent of the network communications and will:

● control heating and cooling from a room sensor● provide fan and compressor operation● monitor all safety controls● monitor discharge air temperature● monitor leaving water temperature● provide status of all vital unit functions● provide optional control outputs

The IBM-compatible MonitorTM software package allowsthe operator to interface with each unit controller into aMicroTech network by using a MicroTech gateway panel.Parameters within each controller are factory set but can bechanged from the PC. All control sequencing, stop/start andsafety monitoring is displayed on the PC screen with thefollowing unique values and parameters for each unit:

● return air and discharge air temperatures● compressor, fan and reversing valve status● high pressure, low temperature, brownout and drain pan

status● occupied and unoccupied heat and cool setpoints● auto/manual and occupied/unoccupied fan control● mode, fault, system, schedule and setpoint operation● compressor starts and fan run hours● load shed level and tenant override

In addition, the following unique operation andmaintenance parameters can be displayed for each unit:

● leaving water temperature● return air temperature setpoint adjustment● adaptive optimal start● occupied/unoccupied (on/cycle) fan mode● room temperature warning● filter changes from fan hours● compressor management: on/off differential, minimum

off time, maximum cycle

An amber, on-board status LED aids ln diagnostics byindicating the water source heat pump operating mode andalarm conditions. If there are no current alarm conditions,the LED will indicate the unit operating mode as shown inthe table below. If there are one or more alarm conditionspresent, the LED will flash in a specific sequence to indicatea particular alamn condition.

New MicroTech WSHP unit controlier LED indication

Status LED State Mode

On continually Occupied, Occupied Load ShedOn 1/2 sec, off 51/2 sec. UnoccupiedOn 51/2 sec., off 1/2 sec. Tenant Override, Overide Load ShedFlashing Alarm Condition

Time schedules can be graphically displayed to showstart/stop times for each day of the week and holidays. Upto 16 holiday dates and duration cycles can be set for atotal of 240 possible holiday dates. Each heat pump can beassigned to a different time schedule and any number ofheat pumps can be assigned to the same time schedule.

Group summary screens are available to display variousparameters for 12 units. Screens are grouped to cover majorgroups such as temperatures, setpoints, and status.

Control and monitoring of the entire water source heatpump system through the MicroTech network includes theMicroTech Loop Water Controller and Application SpecificControllers complete with graphic displays.

Wall-mounted roorn sensors are available to control theheating and cooling operation of each new MicroTech watersource heat pump unit controller. These include a basic roomsensor with LED status, tenant override and optional tenantsetpoint adjustment.

For remote access, a Modem Access Unit allows a remotePC to call the MicroTech network through phone lines aswell as allowing the MicroTech network to dial out topredefined phone numbers.

Page 11: Vertical Water Source Heat Pumps

Catalog 1160 / Page 11

Field installed accessories

Wall mounted thermostats are available for automatic ormanual changeover. All include a fan switch for constant“on” operation or “automatic” for cycle operation with thecompressor. All thermostats are 24 volt type and have dualFahrenheit and Celsius temperature setpoint scales.Thermostat accessories include universal guard, lockingcover and adapter plate to convert from horizontal to verticaljunction box mounting. Individual thermostats include:

• Standard Manual Changeover. Single point lever for one-stage heating and cooling. System “heat-off-cool” switchand fan “on-off” switch.

• Standard Manual and Automatic Changeover. Dualsetpoint levers for one-stage cooling operation. System“off-auto” switch and fan “on-auto” switch. Includes LEDfor “fault.”

• Deluxe Automatic Changeover. Dual setpoint levers forone-stage heating, one-stage cooling, one-stage nightsetback operation. Night setback temperature setpoint is12˚F (-6.6˚C) below daytime heating setting. System “off-auto” switch and fan “on-auto” switch. Includes LED for“fault.”

• Programmable Microelectronic Changeover. Two stageheating, two stage cooling, night setback, night setup andday/night time clock operation. Features include 7-dayprogrammability, four settings per day, keyboard lockcode, time delay and adjustable dead band. System“heat-auto-cool-off” and fan “on-auto” switches.

Supply and return water hoses are available as fire-ratedconstruction in 2 or 3 foot (0.6 or 0.9 m) lengths. Fire-ratedhoses have a synthetic polymer core with an outer ratedcovering of steel. Fittings are steel. Assembly is “fire-rated”and tested according to ASTM-84 81a not to exceed flamespread 25, fuel contribution 25 and smoke density 50.

Each hose has MPT connections. Fire-rated hoses havea swivel connection at one end. Hoses are available in 1/2"(13 mm), 3/4" (19 mm), or 1" (25 mm) to match the FPT fittingson the unit.

Condensate hose is available as a 30" (762 mm) long, clearplastic hose with the necessary clamps and a MPT hosefitting for connection to the FPT field piping.

ManualChangeoverThermostat

AutomaticChangeoverThermostat

ProgrammableThermostat

Combination balancing and shutoff (ball) valves areconstructed of brass and rated at 400 psig (2758 kPa)maximum working pressure. Valves have built-in adjustablememory stop to eliminate rebalancing. Valves have FPTconnections on both ends for connection to the water hoseand to the field piping.

A return air duct collar kit provides a 1" (25 mm) deepcollar for connection of return air ductwork. The kit alsoallows for a 1" (25 mm) or 2" (51 mm) thick filter. The kitconsists of four sheet metal brackets and fasteners. Thebrackets replace the ones shipped with the unit and can befastened to allow for side or bottom filter removal.

Page 12: Vertical Water Source Heat Pumps

Page 12 / Catalog 1160

Airflow correction factors

115PERCENT OF NOMINAL AIRFLOW

95 10085 105

TOTAL COOLING CAPACITY 0.972 0.982 0.994 1.00 1.007 1.010 1.013SENSIBLE COOLING CAPACITY 0.926 0.948 0.974 1.00 1.027 1.055 1.066kW - COOLING 0.977 0.984 0.993 1.00 1.011 1.018 1.028TOTAL HEAT OF REJECTION 0.975 0.983 0.991 1.00 1.008 1.015 1.018TOTAL HEATING CAPACITY 0.967 0.978 0.990 1.00 1.009 1.017 1.024kW - HEATING 1.009 1.006 1.003 1.00 0.997 0.995 0.993TOTAL HEAT OF ABSORPTION 0.967 0.976 0.989 1.00 1.010 1.019 1.025

90 110

50 cycle correction factorsHEATING

TOTAL

0.901 0.941 0.849 0.887 0.899 0.850 0.916

COOLING

SENSIBLE kW HEAT OFREJECTION

TOTAL

To determine unit performance at varying airflow rates, apply the above factors to the tables shown in the catalog supplement.

kW HEAT OFABSORPTION

Page 13: Vertical Water Source Heat Pumps

Catalog 1160 / Page 13

Operating limits

STANDARD EXTENDED RANGEUNITS UNITS

Cooling Heating Cooling Heating Min Ambient Air 50°F 40°F 40°F 40°F Normal Ambient Air 80°F 70°F 80°F 70°F Max Ambient Air 100°F 85°F 100°F 85°F Min Entering Air ➀ ➁ 50°F 50°F 50°F 40°F Normal Ent Air DB/WB 80/67°F 70°F 80/67°F 70°F Max Ent Air DB/WB ➀ ➁ 100/83°F 80°F 100/83°F 80°F

Air limits — °F (English units) EnvironmentThis equipment is designed for indoor installation only.Sheltered locations such as attics, garages, etc., generallywill not provide sufficient protection against extremes intemperature and/or humidity, and equipment performance,reliability, and service life may be adversely affected.

Power supplyA voltage variation of ±10% of nameplate utilization voltageis acceptable. Three-phase system unbalance shall notexceed 2%.

Additional information (initial start-up only)1. Standard units:

Standard conditions are guaranteed to start and operatein an ambient temperature of 40°F (5°C), with entering airat 40°F (5°C), with entering water at 70°F (21°C), with bothair and water at the flow rates used in the ARI Standard320-86 rating test, for initial start-up in winter. Note: Thisis not a normal or continuous operating condition. It isassumed that such a start-up is for the purpose of bringingthe building space up to occupancy temperature.

2. Extended range units:All extended range heat pump conditioners are guaranteedto start and operate in an ambient temperature of 40°F(5°C), with entering air at 40°F (5°C), with entering waterat 70°F (21°C), with both air and water at the flow ratesused in the ARI Standard 320-86 rating test, for initialstart-up in winter.

Operating voltages115/60/1 . . . . . . . . . . . . . . . .104 volt min.; 127 volts max.208-230/60/1 . . . . . . . . . . . .197 volt min.; 253 volts max.265/60/1 . . . . . . . . . . . . . . . .238 volt min.; 292 volts max.230/50/1 . . . . . . . . . . . . . . . .197 volt min.; 253 volts max.460/60/3 . . . . . . . . . . . . . . . .414 volt min.; 506 volts max.380/50/3 . . . . . . . . . . . . . . . .342 volt min.; 418 volts max.575/60/3 . . . . . . . . . . . . . . . .515 volt min.; 632 volts max.

Note: Voltages listed are to show voltage range. However,units operating with overvoltage and undervoltage forextended periods of time will experience prematurecompontent failure.

Water enthalpy — °F (English units)

Notes:➀ At ARI flow rate➁ Maximum and minimum values may not be combined. If one value

is at maximum or minimum, the other two conditions may not exceedthe normal condition for standard units. Extended range units maycombine any two maximum or minimum conditions, but not morethan two, with all other conditions being normal conditions.

STANDARD EXTENDED RANGEUNITS UNITS

Cooling Heating Cooling Heating Min Ambient Air 10°C 10°C 5°C 5°C Normal Ambient Air 27°C 21°C 27°C 21°C Max Ambient Air 38°C 29°C 38°C 29°C Min Entering Air ➀ ➁ 20°C 10°C 10°C 5°C Normal Ent Air DB/WB 27/19°C 21°C 21°C 21°C Max Ent Air DB/WB ➀ ➁ 38/28°C 27°C 27°C 27°C

Air limits — °C (SI units)

Cooling Heating Cooling Heating Min Ent Water ➀ ➁ 55°F 55°F 40°F 40°F Normal Ent Water 85°F 70°F 85°F 70°F Max Ent Water ➀ ➁ 110°F 90°F 110°F 90°F

Water enthalpy — °C (SI units)

Cooling Heating Cooling Heating Min Ent Water ➀ ➁ 13°C 13°C 5°C 5°C Normal Ent Water 29°C 21°C 29°C 21°C Max Ent Water ➀ ➁ 43°C 32°C 43°C 32°C

Page 14: Vertical Water Source Heat Pumps

40

50

60

70

80

85

90

100

110

Page 14 / Catalog 1160

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Capacity data — 60 HertzUnit size 007 at 230 cfm 60 Hz — English units

75/63 54 7900 5500 0.550 9800 60 6589 0.552 470980/67 55 8599 5700 0.540 10500 70 6929 0.600 488985/71 56 9400 5900 0.532 11199 80 7370 0.673 507075/63 51 8000 5500 0.551 9900 60 6650 0.553 475980/67 52 8699 5700 0.540 10599 70 7000 0.603 494085/71 53 9500 5900 0.530 11300 80 7429 0.677 512075/63 71 7299 5200 0.557 9199 60 7339 0.575 537980/67 72 8000 5400 0.558 9900 70 7730 0.637 555985/71 74 8699 5700 0.561 10599 80 8220 0.724 574075/63 63 7500 5299 0.551 9400 60 7440 0.578 545980/67 64 8199 5500 0.549 10099 70 7830 0.642 563985/71 66 8900 5799 0.548 10800 80 8320 0.731 583075/63 61 7599 5400 0.550 9500 60 7509 0.581 551980/67 61 8300 5599 0.546 10099 70 7900 0.645 570085/71 62 9000 5799 0.543 10900 80 8400 0.736 588975/63 80 6900 5000 0.577 8800 60 8199 0.608 612080/67 81 7500 5299 0.585 9500 70 8640 0.684 629985/71 83 8300 5500 0.593 10300 80 9189 0.791 649075/63 73 7099 5099 0.565 9000 60 8310 0.613 620980/67 74 7799 5400 0.570 9699 70 8750 0.690 638985/71 75 8500 5599 0.575 10500 80 9310 0.800 658075/63 70 7200 5200 0.561 9099 60 8380 0.616 628080/67 71 7799 5400 0.564 9800 70 8839 0.695 645985/71 72 8599 5599 0.568 10500 80 9410 0.807 665075/63 89 6400 4900 0.609 8500 60 9070 0.647 686080/67 91 7099 5099 0.620 9199 70 9570 0.741 704085/71 92 7799 5400 0.635 10000 80 10189 0.868 723075/63 82 6599 5000 0.591 8699 60 9189 0.653 695980/67 83 7299 5200 0.601 9400 70 9699 0.749 713985/71 85 8099 5400 0.612 10099 80 10339 0.880 733075/63 80 6700 5000 0.585 8699 60 9279 0.657 704080/67 81 7400 5200 0.594 9400 70 9800 0.756 721985/71 81 8199 5500 0.603 10199 80 10439 0.889 741075/63 98 6000 4700 0.648 8199 60 9970 0.695 759980/67 100 6700 4900 0.665 8900 70 10539 0.808 778085/71 102 7400 5200 0.687 9699 80 11230 0.957 796975/63 92 6200 4799 0.627 8400 60 10109 0.703 770980/67 93 6900 5000 0.641 9099 70 10689 0.819 788985/71 94 7599 5299 0.659 9900 80 11400 0.971 808075/63 89 6299 4799 0.619 8400 60 10210 0.709 779080/67 90 7000 5099 0.631 9099 70 10800 0.828 796985/71 91 7700 5299 0.648 9900 80 11519 0.982 816975/63 103 5799 4599 0.671 8099 60 10429 0.722 796980/67 105 6400 4900 0.692 8800 70 11029 0.845 815085/71 106 7200 5099 0.717 9599 80 11769 1.005 833975/63 97 6000 4700 0.647 8199 60 10580 0.731 808080/67 98 6700 5000 0.665 8900 70 11189 0.858 825985/71 99 7400 5200 0.687 9699 80 11939 1.021 846075/63 94 6099 4700 0.638 8300 60 10679 0.738 816080/67 95 6799 5000 0.654 9000 70 11310 0.867 834985/71 96 7500 5200 0.674 9800 80 12070 1.033 853975/63 108 5599 4500 0.696 7900 60 10900 0.752 833080/67 109 6200 4799 0.720 8699 70 11539 0.886 850985/71 111 6900 5099 0.750 9500 80 12310 1.056 869975/63 102 5799 4599 0.670 8099 60 11050 0.762 844980/67 103 6400 4900 0.691 8800 70 11710 0.899 864085/71 104 7200 5099 0.717 9599 80 12490 1.074 883075/63 99 5900 4599 0.660 8099 60 11169 0.770 853980/67 100 6500 4900 0.679 8900 70 11830 0.910 873085/71 101 7299 5200 0.703 9699 80 12630 1.087 891975/63 117 5099 4299 0.752 770080/67 119 5799 4599 0.784 840085/71 121 6500 4900 0.821 930075/63 111 5299 4400 0.722 779980/67 112 6000 4700 0.750 859985/71 113 6700 5000 0.783 940075/63 109 5400 4500 0.710 790080/67 110 6099 4700 0.736 859985/71 111 6799 5000 0.768 940075/63 119 5000 4299 0.769 759980/67 119 5599 4599 0.802 840085/71 120 6400 4900 0.842 9199

1.4 0.8

1.8 1.7

0.9 0.2

1.4 0.8

1.8 1.7

0.9 0.2

1.4 0.8

1.8 1.7

0.9 0.2

1.4 0.8

1.8 1.7

0.9 0.2

1.4 0.8

1.8 1.7

0.9 0.2

1.4 0.8

1.8 1.7

0.9 0.2

1.4 0.8

1.8 1.7

0.9 0.2

1.4 0.8

1.8 1.7

1.8 1.7

Page 15: Vertical Water Source Heat Pumps

Catalog 1160 / Page 15

40

50

60

70

80

85

90

100

110

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 009 at 300 cfm 60 Hz — English units

1.8 4.4

2.3 7.2

1.2 2

1.8 4.4

2.3 7.2

1.2 2

1.8 4.4

2.3 7.2

1.2 2

1.8 4.4

2.3 7.2

1.2 2

1.8 4.4

2.3 7.2

1.2 2

1.8 4.4

2.3 7.2

1.2 2

1.8 4.4

2.3 7.2

1.2 2

1.8 4.4

2.3 7.2

2.3 7.2

75/63 55 10699 7299 0.831 13500 60 7799 0.761 520080/67 56 11199 7400 0.818 14000 70 8189 0.772 555985/71 56 11900 7500 0.803 14599 80 8759 0.825 594075/63 52 10900 7400 0.852 13800 60 7879 0.761 528080/67 52 11400 7500 0.840 14300 70 8279 0.773 563985/71 53 12099 7599 0.825 14900 80 8849 0.830 601975/63 71 9699 6900 0.769 12300 60 8820 0.761 621980/67 71 10199 7000 0.762 12800 70 9289 0.796 657085/71 73 10900 7200 0.757 13500 80 9939 0.880 694075/63 64 10099 7000 0.783 12699 60 8949 0.762 634980/67 65 10599 7200 0.775 13300 70 9429 0.801 670085/71 66 11400 7299 0.764 14000 80 10089 0.887 707075/63 61 10199 7099 0.794 13000 60 9039 0.763 644080/67 62 10800 7299 0.785 13500 70 9529 0.804 679085/71 62 11500 7400 0.774 14199 80 10199 0.892 716075/63 80 9099 6599 0.766 11699 60 9900 0.774 725980/67 81 9699 6799 0.767 12300 70 10470 0.839 759985/71 82 10400 7000 0.770 13000 80 11179 0.942 795975/63 73 9500 6799 0.765 12099 60 10050 0.776 740080/67 74 10099 6900 0.761 12699 70 10630 0.845 774085/71 75 10800 7200 0.758 13400 80 11349 0.952 809975/63 71 9599 6799 0.767 12300 60 10220 0.780 755980/67 71 10199 7000 0.762 12800 70 10810 0.852 790085/71 72 11000 7200 0.757 13599 80 11480 0.960 819975/63 89 8500 6400 0.785 11199 60 11070 0.802 833080/67 90 9099 6599 0.794 11800 70 11689 0.887 866085/71 91 9900 6799 0.807 12599 80 12519 1.028 900975/63 83 8900 6500 0.772 11500 60 11240 0.808 848080/67 84 9500 6700 0.774 12099 70 11869 0.895 881085/71 84 10199 7000 0.780 12900 80 12720 1.042 916975/63 80 9000 6599 0.768 11599 60 11359 0.812 858980/67 81 9599 6799 0.768 12300 70 12000 0.902 891985/71 81 10400 7000 0.770 13000 80 12880 1.053 927975/63 98 7900 6099 0.821 10800 60 12240 0.839 936980/67 99 8599 6400 0.838 11400 70 12880 0.948 964085/71 100 9300 6599 0.856 12199 80 13849 1.129 999075/63 92 8300 6200 0.800 11000 60 12419 0.845 952980/67 93 8900 6500 0.810 11699 70 13080 0.960 980085/71 94 9699 6799 0.822 12500 80 14080 1.148 1016075/63 90 8400 6299 0.791 11099 60 12550 0.850 965080/67 90 9099 6599 0.799 11800 70 13230 0.969 992985/71 91 9800 6799 0.809 12599 80 14250 1.163 1027975/63 103 7700 6000 0.845 10500 60 12789 0.858 985980/67 104 8300 6299 0.862 11199 70 13490 0.985 1013085/71 105 9000 6599 0.887 12099 80 14529 1.187 1047075/63 97 8000 6099 0.820 10800 60 12980 0.866 1001980/67 98 8599 6400 0.834 11500 70 13699 0.999 1028985/71 99 9400 6700 0.848 12300 80 14769 1.209 1065075/63 94 8099 6200 0.810 10900 60 13130 0.872 1015080/67 95 8800 6400 0.822 11599 70 13939 1.014 1048085/71 96 9599 6700 0.833 12400 80 14960 1.226 1076975/63 107 7400 5900 0.870 10300 60 13349 0.882 1033980/67 108 8000 6200 0.891 11000 70 14179 1.031 1066085/71 110 8800 6500 0.923 11900 80 15220 1.251 1094975/63 102 7700 6000 0.845 10500 60 13550 0.891 1050980/67 103 8300 6299 0.859 11199 70 14410 1.047 1083985/71 104 9099 6599 0.879 12099 80 15490 1.276 1113075/63 99 7799 6000 0.834 10599 60 13710 0.899 1064080/67 100 8500 6299 0.846 11300 70 14580 1.060 1097085/71 101 9300 6599 0.861 12199 80 15679 1.295 1125975/63 117 6799 5700 0.924 990080/67 118 7400 5900 0.957 1069985/71 119 8199 6299 1.005 1159975/63 111 7000 5799 0.897 1009980/67 112 7700 6099 0.921 1090085/71 113 8500 6400 0.954 1180075/63 109 7200 5799 0.886 1019980/67 110 7900 6099 0.905 1090085/71 110 8699 6400 0.932 1190075/63 119 6599 5599 0.946 980080/67 119 7299 5900 0.977 1059985/71 120 8099 6200 1.019 11599

Page 16: Vertical Water Source Heat Pumps

40

50

60

70

80

85

90

100

110

Page 16 / Catalog 1160

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 012 at 400 cfm 60 Hz — English units

2.6 10.1

3.4 16.7

1.7 4.6

2.6 10.1

3.4 16.7

1.7 4.6

2.6 10.1

3.4 16.7

1.7 4.6

2.6 10.1

3.4 16.7

1.7 4.6

2.6 10.1

3.4 16.7

1.7 4.6

2.6 10.1

3.4 16.7

1.7 4.6

2.6 10.1

3.4 16.7

1.7 4.6

2.6 10.1

3.4 16.7

3.4 16.7

75/63 53 13599 9699 0.789 16300 60 8689 0.809 592980/67 53 14400 10000 0.787 17100 70 9289 0.857 636085/71 54 15500 10300 0.786 18199 80 10060 0.948 682075/63 50 13699 9800 0.793 16399 60 8820 0.811 605980/67 50 14599 10000 0.790 17300 70 9429 0.861 649085/71 51 15699 10400 0.786 18399 80 10220 0.956 695075/63 68 12599 9300 0.815 15300 60 9919 0.830 708980/67 69 13400 9599 0.830 16199 70 10580 0.902 750085/71 71 14500 10000 0.855 17399 80 11439 1.026 794075/63 62 12900 9500 0.794 15599 60 10130 0.834 728080/67 63 13800 9699 0.800 16500 70 10810 0.912 769085/71 64 15000 10099 0.811 17699 80 11689 1.041 813075/63 59 13099 9500 0.790 15800 60 10279 0.838 741980/67 60 13900 9800 0.793 16699 70 10970 0.919 783985/71 61 15099 10099 0.800 17800 80 11880 1.053 827975/63 77 11800 9000 0.867 14800 60 11310 0.866 835980/67 79 12699 9400 0.895 15800 70 12070 0.971 875085/71 80 13900 9699 0.939 17100 80 13019 1.127 916975/63 72 12199 9199 0.831 15099 60 11550 0.874 856080/67 72 13099 9500 0.847 16000 70 12320 0.985 896085/71 73 14300 9900 0.872 17300 80 13279 1.142 939075/63 69 12400 9300 0.819 15199 60 11720 0.880 872080/67 70 13300 9599 0.831 16100 70 12519 0.995 911985/71 70 14500 9900 0.851 17399 80 13480 1.154 953975/63 87 11099 8699 0.439 14300 60 12699 0.917 957080/67 88 12000 9099 0.982 15400 70 13570 1.058 996085/71 90 13199 9500 1.026 16699 80 14509 1.218 1035975/63 81 11500 8900 0.893 14599 60 12970 0.929 980080/67 82 12500 9300 0.922 15599 70 13849 1.073 1018985/71 83 13599 9599 0.960 16899 80 14810 1.238 1058975/63 79 11699 9000 0.875 14699 60 13169 0.937 997080/67 79 12599 9300 0.900 15699 70 14050 1.083 1034985/71 80 13800 9699 0.936 17000 80 15039 1.253 1075975/63 96 10400 8400 1.026 13900 60 14109 0.984 1075080/67 98 11400 8800 1.067 15000 70 14980 1.132 1111985/71 99 12500 9300 1.126 16399 80 16019 1.323 1150975/63 91 10800 8599 0.974 14099 60 14410 1.000 1099080/67 92 11800 9000 1.011 15199 70 15289 1.150 1135985/71 93 13000 9400 1.052 16600 80 16359 1.349 1175975/63 88 11000 8699 0.954 14199 60 14630 1.012 1117980/67 89 11900 9099 0.989 15300 70 15519 1.163 1155085/71 90 13199 9500 1.026 16699 80 16609 1.368 1193975/63 101 10000 8300 1.065 13699 60 14820 1.023 1133080/67 102 11000 8699 1.113 14800 70 15689 1.174 1168985/71 104 12199 9199 1.181 16199 80 16789 1.382 1207075/63 96 10500 8400 1.021 13900 60 15109 1.036 1158080/67 97 11400 8800 1.054 15000 70 16010 1.193 1193985/71 98 12699 9300 1.105 16399 80 17140 1.410 1233075/63 93 10599 8500 0.998 14000 60 15339 1.046 1176980/67 94 11599 8900 1.033 15099 70 16250 1.209 1213085/71 95 12800 9400 1.075 16500 80 17410 1.432 1251975/63 106 9699 8099 1.108 13500 60 15490 1.053 1190080/67 107 10599 8599 1.162 14599 70 16410 1.218 1225085/71 109 11900 9000 1.242 16100 80 17559 1.444 1263075/63 101 10099 8300 1.061 13699 60 15800 1.068 1215080/67 101 11000 8699 1.101 14800 70 16750 1.240 1250985/71 103 12300 9199 1.160 16300 80 17929 1.476 1290075/63 98 10199 8400 1.042 13800 60 16030 1.079 1234980/67 99 11199 8800 1.078 14900 70 17000 1.257 1271085/71 100 12500 9300 1.130 16300 80 18219 1.500 1309975/63 115 8900 7799 1.193 1300080/67 117 9900 8300 1.266 1419985/71 119 11099 8800 1.365 1580075/63 110 9300 8000 1.148 1319980/67 111 10300 8500 1.202 1440085/71 112 11599 9000 1.281 1600075/63 108 9400 8099 1.127 1330080/67 109 10500 8599 1.178 1450085/71 109 11800 9000 1.247 1600075/63 118 8699 7799 1.217 1280080/67 118 9699 8300 1.283 1409985/71 119 11099 8800 1.376 15800

Page 17: Vertical Water Source Heat Pumps

Catalog 1160 / Page 17

40

50

60

70

80

85

90

100

110

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 015 at 500 cfm 60 Hz — English units

2.7 8.8

3.6 14.5

1.8 4.3

2.7 8.8

3.6 14.5

1.8 4.3

2.7 8.8

3.6 14.5

1.8 4.3

2.7 8.8

3.6 14.5

1.8 4.3

2.7 8.8

3.6 14.5

1.8 4.3

2.7 8.8

3.6 14.5

1.8 4.3

2.7 8.8

3.6 14.5

1.8 4.3

2.7 8.8

3.6 14.5

3.6 14.5

75/63 52 13900 10000 0.652 16100 60 11070 0.872 809980/67 53 14900 10400 0.673 17100 70 11599 0.978 825985/71 54 16300 10800 0.704 18699 80 12130 1.088 841975/63 49 14000 10099 0,620 16100 60 11330 0.881 832080/67 50 15000 10400 0.639 17199 70 11849 0.988 848085/71 50 16399 10900 0.666 18600 80 12400 1.100 864075/63 68 13199 9800 0.794 15900 60 12439 0.924 928980/67 69 14199 10099 0.822 17000 70 12960 1.034 942985/71 71 15599 10500 0.863 18500 80 13509 1.150 958075/63 62 13400 9900 0.741 16000 60 12789 0.937 958980/67 63 14500 10199 0.765 17100 70 13320 1.049 973085/71 64 15800 10599 0.799 18600 80 13859 1.166 988075/63 59 13599 9900 0.709 16000 60 13070 0.949 983980/67 60 14599 10300 0.731 17100 70 13609 1.062 998085/71 60 16000 10699 0.761 18600 80 14160 1.180 1013075/63 78 12699 9599 0.884 15699 60 14080 0.990 1069980/67 79 13699 9900 0.916 16899 70 14619 1.106 1083985/71 81 15099 10400 0.961 18399 80 15169 1.228 1098075/63 72 13000 9699 0.832 15800 60 14470 1.006 1102980/67 73 14000 10000 0.859 16899 70 15009 1.124 1117985/71 74 15400 10500 0.897 18500 80 15570 1.247 1131075/63 69 13099 9699 0.800 15900 60 14789 1.019 1131080/67 69 14199 10099 0.824 17000 70 15339 1.139 1144985/71 70 15599 10599 0.858 18500 80 15900 1.264 1158975/63 87 12300 9400 0.976 15599 60 15699 1.058 1208980/67 89 13300 9800 1.011 16800 70 16250 1.181 1222085/71 90 14800 10300 1.061 18399 80 16820 1.308 1234975/63 82 12500 9500 0.923 15699 60 16129 1.077 1244980/67 82 13599 9900 0.954 16800 70 16679 1.201 1258085/71 84 15000 10400 0.995 18399 80 17250 1.330 1272075/63 79 12699 9599 0.891 15699 60 16480 1.093 1275080/67 79 13699 9900 0.919 16899 70 17039 1.218 1288085/71 80 15199 10400 0.957 18399 80 17609 1.348 1301975/63 97 11800 9199 1.068 15400 60 17300 1.129 1344980/67 99 12900 9699 1.109 16699 70 17859 1.257 1357085/71 100 14300 10199 1.162 18300 80 18440 1.389 1368975/63 92 12099 9300 1.015 15500 60 17769 1.150 1383980/67 92 13099 9699 1.049 16699 70 18329 1.280 1396085/71 94 14599 10300 1.097 18399 80 18910 1.414 1408975/63 89 12199 9400 0.983 15599 60 18149 1.168 1416080/67 89 13300 9800 1.014 16800 70 18719 1.299 1428985/71 90 14699 10300 1.056 18300 80 19309 1.435 1441075/63 102 11599 9099 1.114 15400 60 18100 1.165 1411980/67 104 12699 9599 1.157 16600 70 18660 1.296 1424085/71 105 14099 10099 1.212 18300 80 19239 1.431 1435975/63 96 11800 9199 1.062 15400 60 18579 1.188 1451980/67 97 12900 9699 1.097 16699 70 19149 1.320 1465085/71 99 14400 10199 1.147 18300 80 19739 1.457 1476975/63 94 12000 9300 1.030 15500 60 18980 1.207 1485980/67 94 13099 9699 1.062 16699 70 19559 1.340 1498085/71 95 14500 10199 1.107 18300 80 20149 1.479 1509975/63 107 11400 9000 1.163 15300 60 18890 1.202 1477980/67 108 12500 9500 1.205 16600 70 19460 1.335 1490085/71 110 13900 10000 1.263 18199 80 20050 1.473 1501975/63 101 11599 9099 1.108 15400 60 19390 1.226 1519980/67 102 12699 9599 1.147 16699 70 19969 1.361 1532085/71 104 14199 10099 1.198 18300 80 20559 1.501 1543975/63 99 11800 9199 1.076 15400 60 19809 1.246 1555080/67 99 12900 9599 1.111 16600 70 20390 1.382 1566985/71 100 14300 10199 1.159 18300 80 20989 1.525 1578975/63 117 10900 8900 1.256 1519980/67 118 12000 9400 1.302 1650085/71 120 13500 9900 1.365 1810075/63 111 11199 9000 1.203 1530080/67 112 12300 9500 1.244 1650085/71 114 13800 9900 1.300 1819976/63 109 11300 9000 1.171 1530080/67 109 12500 9500 1.209 1660085/71 110 13900 10000 1.260 1819975/63 118 10900 8900 1.265 1519980/67 119 12000 9400 1.307 1650085/71 120 13500 9900 1.362 18100

Page 18: Vertical Water Source Heat Pumps

40

50

60

70

80

85

90

100

110

Page 18 / Catalog 1160

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 019 at 830 cfm 60 Hz — English units

3.8 13.7

5.1 23.1

2.5 6.4

3.8 13.7

5.1 23.1

2.5 6.4

3.8 13.7

5.1 23.1

2.5 6.4

3.8 13.7

5.1 23.1

2.5 6.4

3.8 13.7

5.1 23.1

2.5 6.4

3.8 13.7

5.1 23.1

2.5 6.4

3.8 13.7

5.1 23.1

2.5 6.4

3.8 13.7

5.1 23.1

5.1 23.1

75/63 53 20199 14400 1.330 24699 60 17469 1.486 1240080/67 54 21800 14900 1.314 26300 70 17690 1.550 1240085/71 55 23699 15500 1.303 28100 80 18000 1.644 1239075/63 50 20399 14500 1.321 24899 60 17739 1.491 1265080/67 50 22000 15000 1.300 26500 70 17969 1.560 1265085/71 51 23899 15500 1.284 28300 80 18300 1.657 1265075/63 69 19100 13900 1.403 23899 60 18710 1.514 1353980/67 70 20699 14500 1.413 25600 70 18989 1.597 1353985/71 72 22500 15000 1.431 27399 80 19379 1.710 1353975/63 63 19500 14099 1.371 24199 60 19129 1.525 1391980/67 64 21199 14699 1.369 25899 70 19429 1.614 1391985/71 65 23000 15300 1.374 27699 80 19839 1.734 1391975/63 60 19699 14199 1.358 24300 60 19440 1.534 1421080/67 60 21300 14699 1.351 26000 70 19760 1.628 1419985/71 61 23199 15300 1.350 27800 80 20179 1.752 1419975/63 79 18399 13599 1.465 23399 60 20359 1.562 1502980/67 80 20000 14199 1.490 25100 70 20730 1.670 1502985/71 82 21800 14800 1.523 27000 80 21199 1.810 1502975/63 73 18899 13800 1.425 23699 60 20839 1.579 1544980/67 73 20500 14400 1.438 25399 70 21230 1.694 1544985/71 74 22300 15000 1.459 27300 80 21730 1.841 1544975/63 69 19000 13900 1.408 23899 60 21199 1.592 1576980/67 70 20699 14500 1.416 25500 70 21609 1.712 1575985/71 71 22500 15000 1.431 27399 80 22129 1.865 1575975/63 88 17800 13400 1.540 23000 60 22059 1.625 1651080/67 90 19399 14000 1.581 24800 70 22510 1.758 1651085/71 91 21100 14599 1.624 26699 80 23070 1.922 1651075/63 82 18199 13599 1.493 23300 60 22600 1.648 1698080/67 83 19800 14199 1.520 25000 70 23079 1.789 1698085/71 84 21600 14699 1.553 26899 80 23660 1.959 1698075/63 79 18399 13599 1.472 23399 60 23010 1.665 1732080/67 80 20000 14199 1.495 25100 70 23510 1.812 1732085/71 81 21800 14800 1.524 27000 80 24100 1.988 1732075/63 98 17100 13099 1.628 22600 60 23809 1.702 1800080/67 100 18699 13699 1.684 24399 70 24329 1.856 1800085/71 101 20399 14300 1.741 26399 80 24980 2.047 1800075/63 92 17500 13300 1.573 22899 60 24420 1.732 1850080/67 93 19100 13900 1.617 24600 70 24960 1.891 1850085/71 94 20899 14500 1.660 26600 80 25649 2.094 1850075/63 89 17699 13400 1.549 23000 60 24869 1.751 1887980/67 90 19300 14000 1.587 24699 70 25429 1.919 1887985/71 90 21100 14599 1.626 26699 80 26149 2.130 1887975/63 103 16699 12900 1.677 22399 60 24690 1.744 1873980/67 104 18300 13500 1.738 24199 70 25250 1.909 1873985/71 106 20100 14199 1.806 26199 80 25960 2.117 1873975/63 97 17100 13099 1.619 22699 60 25320 1.772 1926980/67 98 18800 13800 1.670 24500 70 25920 1.949 1926985/71 99 20600 14400 1.719 26399 80 26670 2.169 1926075/63 94 17300 13199 1.593 22800 60 25789 1.795 1966080/67 95 19000 13800 1.638 24600 70 26420 1.980 1966085/71 95 20800 14400 1.683 26500 80 27199 2.210 1966075/63 108 16399 12800 1.729 22300 60 25579 1.785 1948980/67 109 18000 13500 1.796 24100 70 26190 1.966 1948085/71 111 19699 14099 1.875 26100 80 26960 2.192 1948075/63 102 16800 12900 1.667 22500 60 26239 1.818 2003080/67 103 18399 13599 1.724 24300 70 26890 2.011 2003085/71 104 20199 14199 1.783 26300 80 27710 2.250 2003075/63 99 17000 13099 1.640 22600 60 26730 1.844 2044080/67 100 18600 13699 1.692 24399 70 27420 2.046 2044085/71 100 20399 14300 1.744 26399 80 28269 2.296 2042975/63 118 15699 12500 1.842 2200080/67 119 17300 13199 1.924 2380085/71 121 19000 13800 2.026 2589975/63 112 16100 12699 1.773 2219980/67 113 17699 13300 1.842 2400085/71 114 19500 14000 1.924 2610075/63 109 16300 12800 1.743 2219980/67 109 17899 13400 1.806 2410085/71 110 19699 14099 1.880 2610075/63 119 15599 12500 1.858 2189980/67 119 17199 13099 1.936 2380085/71 120 19000 13800 2.032 25899

Page 19: Vertical Water Source Heat Pumps

Catalog 1160 / Page 19

40

50

60

70

80

85

90

100

110

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 024 at 800 cfm 60 Hz — English units

5.0 5.9

6.2 8.9

4.0 3.9

5.0 5.9

6.2 8.9

4.0 3.9

5.0 5.9

6.2 8.9

4.0 3.9

5.0 5.9

6.2 8.9

4.0 3.9

5.0 5.9

6.2 8.9

4.0 3.9

5.0 5.9

6.2 8.9

4.0 3.9

5.0 5.9

6.2 8.9

4.0 3.9

5.0 5.9

6.2 8.9

6.2 8.9

75/63 53 27199 19000 1.699 33000 60 20329 1.983 1356080/67 54 28699 19500 1.693 34500 70 20850 2.026 1392985/71 55 30699 20000 1.689 36399 80 21480 2.104 1430075/63 51 27300 19100 1.694 33100 60 20649 1.985 1386980/67 51 28899 19500 1.686 34700 70 21179 2.031 1425085/71 52 30800 20100 1.679 36600 80 21820 2.113 1460975/63 66 25899 18500 1.744 31899 60 23309 2.007 1646080/67 67 27500 19000 1.748 33500 70 23899 2.083 1678985/71 68 29500 19600 1.755 35500 80 24629 2.200 1712075/63 63 26100 18600 1.737 32000 60 23750 2.012 1687980/67 63 27699 19100 1.740 33600 70 24359 2.094 1721085/71 64 29699 19600 1.747 35700 80 25100 2.216 1753975/63 60 26300 18699 1.727 32200 60 24129 2.017 1723980/67 61 27899 19199 1.728 33799 70 24760 2.103 1757985/71 62 29899 19699 1.732 35799 80 25510 2.231 1789975/63 76 24899 18100 1.806 31100 60 26640 2.057 1962080/67 76 26500 18600 1.820 32700 70 27339 2.175 1992085/71 77 28600 19300 1.841 34799 80 28190 2.338 2021075/63 72 25100 18199 1.795 31199 60 27149 2.067 2008980/67 73 26699 18699 1.808 32799 70 27870 2.191 2039085/71 74 28699 19300 1.830 35000 80 28739 2.362 2067975/63 70 25300 18300 1.781 31399 60 27589 2.076 2050080/67 71 26899 18800 1.792 33000 70 28329 2.206 2080085/71 71 28899 19399 1.810 35100 80 29219 2.384 2107975/63 85 23800 17699 1.885 30300 60 29980 2.134 2269980/67 86 25500 18300 1.911 32000 70 30800 2.296 2296985/71 87 27600 18899 1.949 34200 80 31769 2.505 2321975/63 82 24000 17699 1.871 30399 60 36559 2.150 2323080/67 83 25699 18300 1.897 32100 70 31410 2.320 2348985/71 84 27699 18899 1.934 34299 80 32390 2.535 2373975/63 80 24199 17800 1.853 30500 60 31070 2.164 2367980/67 80 25899 18399 1.877 32299 70 31929 2.342 2394085/71 81 27899 19000 1.910 34399 80 32929 2.561 2419075/63 95 22699 17199 1.979 29500 60 33350 2.237 2571080/67 96 24500 17899 2.021 31399 70 34259 2.436 2594085/71 97 26600 18600 2.075 33700 80 35340 2.688 2616075/63 92 22899 17300 1.962 29600 60 34000 2.260 2628980/67 93 24600 17899 2.003 31500 70 34929 2.464 2651985/71 94 26699 18600 2.059 33700 80 36049 2.729 2673075/63 90 23100 17399 1.942 29800 60 34570 2.281 2678080/67 90 24899 18000 1.980 31600 70 35509 2.489 2701985/71 91 26899 18699 2.031 33899 80 36670 2.765 2723075/63 100 22199 17000 2.032 29100 60 35030 2.295 2719080/67 101 23899 17699 2.081 31000 70 35979 2.510 2741085/71 102 26100 18399 2.140 33399 80 37149 2.794 2760975/63 97 22399 17100 2.014 29300 60 35700 2.316 2780080/67 97 24100 17699 2.062 31100 70 36689 2.544 2801085/71 98 26199 18399 2.124 33500 80 37899 2.841 2821075/63 95 22600 17100 1.992 29399 60 36289 2.336 2832080/67 95 24300 17800 2.037 31300 70 37320 2.574 2853085/71 96 26399 18500 2.095 33600 80 38560 2.883 2871975/63 104 21600 16800 2.087 28800 60 36689 2.350 2867080/67 105 23399 17500 2.144 30699 70 37719 2.594 2887085/71 107 25600 18300 2.212 33100 80 38969 2.909 2905075/63 102 21899 16899 2.067 28899 60 37399 2.376 2928980/67 102 23600 17600 2.125 30899 70 38479 2.633 2948985/71 103 25699 18300 2.193 33200 80 39780 2.963 2967075/63 99 22100 17000 2.045 29100 60 38030 2.400 2983980/67 100 23800 17699 2.097 31000 70 39140 2.668 3003085/71 101 25899 18300 2.163 33299 80 40479 3.011 3019975/63 114 20600 16399 2.206 2810080/67 115 22399 17100 2.279 3010085/71 116 24500 17899 2.366 3260075/63 111 20800 16500 2.183 2819980/67 112 22500 17100 2.257 3019985/71 113 24699 17899 2.343 3270075/63 109 21000 16500 2.159 2839980/67 110 22800 17199 2.229 3039985/71 111 24899 18000 2.310 3279975/63 119 19899 16100 2.281 2769980/67 120 21699 16899 2.368 2980085/71 120 23899 17600 2.475 32399

Page 20: Vertical Water Source Heat Pumps

40

50

60

70

80

85

90

100

110

Page 20 / Catalog 1160

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 030 at 1000 cfm 60 Hz — English units

5.7 7.5

7.7 16.8

3.8 2.5

5.7 7.5

7.7 16.8

3.8 2.5

5.7 7.5

7.7 16.8

3.8 2.5

5.7 7.5

7.7 16.8

3.8 2.5

5.7 7.5

7.7 16.8

3.8 2.5

5.7 7.5

7.7 16.8

3.8 2.5

5.7 7.5

7.7 16.8

3.8 2.5

5.7 7.5

7.7 16.8

7.7 16.8

75/63 54 32399 22800 2.014 39200 60 24910 2.319 1703980/67 55 34899 23600 2.016 41799 70 25160 2.400 1701985/71 56 38000 24600 2.026 44899 80 25510 2.512 1698975/63 50 32899 23000 1.992 39700 60 25550 2.328 1766080/67 51 35399 23899 1.987 42200 70 25829 2.417 1762985/71 52 38600 24699 1.988 45399 80 26199 2.537 1758975/63 70 29899 21800 2.154 37299 60 27140 2.356 1914980/67 71 32399 22699 2.194 39899 70 27469 2.462 1912085/71 73 35600 23600 2.259 43299 80 27899 2.602 1907975/63 63 31000 22300 2.084 38100 60 28829 2.392 2071980/67 64 33600 23100 2.101 40799 70 29219 2.516 2067985/71 65 36799 24000 2.133 44100 80 29719 2.678 2062975/63 60 31500 22500 2.055 38600 60 29629 2.411 2146080/67 61 34100 23300 2.064 41200 70 30050 2.545 2142085/71 62 37299 24300 2.085 44399 80 30589 2.717 2137075/63 79 28600 21300 2.253 36299 60 30829 2.442 2253980/67 81 31199 22199 2.314 39100 70 31289 2.590 2250085/71 82 34299 23199 2.405 42500 80 31879 2.778 2244075/63 73 29699 21699 2.172 37100 60 32869 2.502 2437980/67 74 32299 22699 2.207 39799 70 33409 2.676 2432985/71 75 35500 23600 2.262 43200 80 34079 2.891 2426075/63 70 30199 22000 2.137 37500 60 33840 2.534 2525080/67 70 32799 22899 2.163 40200 70 34420 2.720 2519085/71 71 36100 23800 2.205 43600 80 35140 2.949 2512075/63 89 27300 20800 2.367 35399 60 34619 2.561 2592980/67 90 29899 21699 2.450 38299 70 35229 2.757 2587085/71 92 33100 22899 2.565 41799 80 35979 2.997 2580075/63 83 28300 21199 2.277 36100 60 37030 2.652 2803080/67 84 31000 22100 2.332 39000 70 37740 2.880 2796085/71 85 34299 23199 2.411 42500 80 38600 3.154 2787975/63 79 28800 21399 2.237 36500 60 38189 2.701 2901980/67 80 31500 22300 2.281 39299 70 38939 2.941 2894985/71 81 34799 23399 2.348 42799 80 39850 3.235 2885975/63 98 26000 20199 2.493 34500 60 38520 2.715 2930980/67 100 28600 21300 2.601 37500 70 39280 2.960 2923085/71 102 31800 22399 2.747 41200 80 40219 3.259 2914975/63 92 27000 20699 2.397 35200 60 41310 2.840 3167080/67 93 29699 21699 2.473 38100 70 42200 3.126 3157985/71 95 33000 22699 2.575 41799 80 43299 3.476 3148075/63 89 27500 20899 2.352 35500 60 42649 2.905 3278080/67 90 30199 21800 2.417 38399 70 43609 3.213 3268985/71 91 33500 23000 2.505 42100 80 44780 3.589 3257975/63 103 25300 20000 2.560 34100 60 40509 2.804 3098980/67 105 28000 21100 2.681 37100 70 41359 3.075 3091085/71 107 31199 22199 2.845 40899 80 42399 3.411 3080975/63 97 26300 20300 2.461 34700 60 43500 2.948 3349080/67 98 29000 21399 2.549 37700 70 44500 3.271 3339085/71 100 32399 22500 2.666 41500 80 45719 3.663 3327075/63 94 26800 20600 2.415 35100 60 44939 3.026 3465980/67 95 29500 21600 2.491 38000 70 46020 3.374 3456085/71 96 32899 22699 2.592 41700 80 47329 3.794 3442975/63 108 24699 19699 2.630 33700 60 42520 2.898 3267080/67 109 27300 20800 2.763 36700 70 43469 3.204 3257985/71 111 30600 22000 2.948 40600 80 44630 3.578 3246975/63 102 25699 20100 2.529 34299 60 45719 3.070 3529980/67 103 28399 21199 2.629 37399 70 46850 3.432 3518985/71 104 31699 22300 2.761 41200 80 48210 3.868 3506075/63 99 26100 20300 2.480 34600 60 47280 3.162 3653080/67 100 28899 21399 2.569 37600 70 48490 3.551 3642085/71 101 32200 22500 2.684 41399 80 49939 4.018 3628075/63 117 23399 19199 2.776 3279980/67 119 26000 20300 2.938 3600085/71 121 29300 21600 3.167 4010075/63 112 24300 19600 2.671 3339980/67 113 27100 20699 2.797 3660085/71 114 30399 21899 2.968 4060075/63 109 24800 19800 2.620 3370080/67 110 27500 20800 2.733 3689985/71 111 31000 22100 2.883 4079975/63 119 23399 19300 2.770 3289980/67 119 26199 20399 2.910 3610085/71 120 29699 21699 3.101 40200

Page 21: Vertical Water Source Heat Pumps

Catalog 1160 / Page 21

40

50

60

70

80

85

90

100

110

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 036 at 1200 cfm 60 Hz — English units

7.0 8.3

9.0 11.9

4.7 4.7

7.0 8.3

9.0 11.9

4.7 4.7

7.0 8.3

9.0 11.9

4.7 4.7

7.0 8.3

9.0 11.9

4.7 4.7

7.0 8.3

9.0 11.9

4.7 4.7

7.0 8.3

9.0 11.9

4.7 4.7

7.0 8.3

9.0 11.9

4.7 4.7

7.0 8.3

9.0 11.9

9.0 11.9

75/63 53 38899 27199 2.433 47200 60 32799 2.676 2373980/67 54 41299 27899 2.420 49500 70 33280 2.799 2380085/71 55 44100 28699 2.410 52399 80 33990 2.971 2392075/63 51 39399 27500 2.416 47600 60 33149 2.683 2405980/67 51 41700 28100 2.400 49899 70 33710 2.813 2417085/71 52 44600 28800 2.384 52700 80 34369 2.988 2423975/63 69 36500 26199 2.555 45200 60 35439 2.738 2617080/67 70 39000 27000 2.567 47700 70 36049 2.896 2623085/71 72 41899 27899 2.587 50700 80 36890 3.107 2635975163 63 37399 26600 2.503 45899 60 36210 2.759 2685980/67 64 39799 27300 2.505 48299 70 36909 2.930 2698085/71 65 42700 28199 2.513 51299 80 37740 3.150 2705075/63 60 37899 26800 2.476 46299 60 36609 2.770 2721980/67 61 40299 27600 2.474 48700 70 37329 2.947 2733985/71 61 43200 28300 2.476 51600 80 38179 3.173 2742075/63 79 35000 25699 2.669 44100 60 38840 2.841 2921080/67 80 37500 26500 2.699 46700 70 39619 3.046 2928985/71 81 40399 27399 2.741 49799 80 40649 3.310 2942075/63 73 35899 25899 2.601 44700 60 39719 2.871 2998980/67 74 38299 26800 2.621 47299 70 40590 3.092 3010985/71 74 41299 27600 2.650 50299 80 41609 3.367 3019075/63 70 36299 26199 2.566 45100 60 40179 2.888 3039080/67 71 38799 27000 2.579 47600 70 41079 3.115 3051985/71 71 41700 27899 2.602 50600 80 42130 3.397 3060075/63 88 33500 25000 2.807 43100 60 42350 2.973 3227080/67 89 36000 25899 2.857 45799 70 43299 3.228 3235085/71 91 39000 26899 2.925 49000 80 44409 3.529 3242975/63 82 34299 25399 2.726 43600 60 43340 3.015 3311980/67 83 36799 26300 2.764 46299 70 44340 3.285 3320085/71 84 39799 27100 2.817 49399 80 45539 3.596 3332975/63 80 34799 25500 2.682 44000 60 43859 3.038 3356080/67 80 37299 26399 2.714 46600 70 44939 3.315 3368985/71 81 40299 27399 2.759 49700 80 46100 3.631 3378075/63 98 32000 24300 2.967 42100 60 45960 3.136 3532980/67 99 34500 25300 3.039 44899 70 47020 3.422 3540985/71 101 37600 26300 3.121 48200 80 48299 3.772 3550075/63 92 32799 24699 2.873 42600 60 47060 3.186 3625080/67 93 35399 25699 2.933 45399 70 48159 3.485 3632985/71 94 38399 26699 3.007 48600 80 49509 3.853 3642075/63 90 33299 24899 2.822 43000 60 47630 3.211 3674080/67 90 35899 25899 2.875 45700 70 48759 3.519 3682085/71 91 38899 26899 2.945 48899 80 50210 3.902 3696075/63 103 31199 24100 3.053 41600 60 47740 3.216 3682980/67 104 33799 25100 3.138 44500 70 48880 3.526 3690985/71 105 36799 26199 3.228 47799 80 50329 3.910 3706075/63 97 32100 24300 2.955 42200 60 48939 3.271 3784080/67 98 34600 25300 3.026 44899 70 50149 3.600 3792985/71 99 37600 26500 3.107 48299 80 51609 4.001 3802075/63 94 32600 24600 2.901 42500 60 49539 3.301 3835080/67 95 35100 25600 2.964 45200 70 50789 3.639 3843985/71 96 38100 26600 3.040 48500 80 52289 4.051 3853075/63 108 30399 23699 3.145 41200 60 49590 3.303 3838080/67 109 33000 24800 3.241 44100 70 50829 3.642 3846985/71 110 36100 25899 3.341 47500 80 52340 4.054 3857075/63 102 31300 24100 3.041 41700 60 50789 3.363 3938080/67 103 33899 25100 3.124 44500 70 52109 3.721 3946985/71 104 36899 26199 3.213 47899 80 53689 4.156 3957075/63 99 31800 24300 2.984 42000 60 51429 3.396 3990980/67 100 34399 25300 3.059 44799 70 52780 3.765 4000085/71 101 37399 26300 3.142 48100 80 54399 4.211 4010075/63 117 28899 23199 3.339 4029980/67 118 31500 24300 3.451 4329985/71 120 34600 25399 3.583 4689975/63 112 29800 23399 3.227 4079980/67 113 32399 24600 3.329 4370085/71 114 35500 25699 3.442 4720075/63 109 30300 23699 3.164 4110080/67 110 32899 24699 3.262 4400085/71 111 35899 25800 3.364 4739975/63 119 28800 23000 3.359 4020080/67 120 31399 24199 3.473 4320085/71 120 34500 25300 3.609 46799

Page 22: Vertical Water Source Heat Pumps

40

50

60

70

80

85

90

100

110

Page 22 / Catalog 1160

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 042 at 1400 cfm 60 Hz — English units

7.7 6.4

10.6 14.2

5.2 2.4

7.7 6.4

10.6 14.2

5.2 2.4

7.7 6.4

10.6 14.2

5.2 2.4

7.7 6.4

10.6 14.2

5.2 2.4

7.7 6.4

10.6 14.2

5.2 2.4

7.7 6.4

10.6 14.2

5.2 2.4

7.7 6.4

10.6 14.2

5.2 2.4

7.7 6.4

10.6 14.2

10.6 14.2

75/63 54 44700 31899 2.768 54200 60 34359 3.007 2410080/67 55 47899 32899 2.752 57299 70 35729 3.152 2496985/71 56 51899 34100 2.739 61200 80 37219 3.359 2575075/63 50 45299 32200 2.737 54600 60 35039 3.016 2473980/67 51 48500 33200 2.713 57700 70 36390 3.171 2557085/71 52 52399 34200 2.690 61600 80 37969 3.390 2639975/63 70 42500 31000 2.932 52600 60 38520 3,089 2798080/67 71 45799 32200 2.946 55799 70 39979 3.289 2876085/71 73 49799 33299 2.973 59899 80 41700 3.561 2955075/63 64 43200 31300 2.875 53000 60 39560 3.114 2892980/67 65 46399 32299 2.879 56200 70 41070 3.329 2971085/71 66 50399 33500 2.893 60299 80 42850 3.619 3050075/63 60 43799 31600 2.830 53399 60 40280 3.133 2957980/67 61 47000 32600 2.824 56700 70 41829 3.359 3037085/71 61 51000 33799 2.825 60600 80 43659 3.661 3117075/63 80 41000 30399 3.088 51500 60 43549 3.231 3252080/67 81 44299 31600 3.127 54899 70 45219 3.503 3325985/71 83 48299 32899 3.171 59200 80 47179 3.855 3402075/63 73 41600 30699 3.017 51899 60 44789 3.273 3361980/67 74 44899 31899 3.044 55299 70 46469 3.562 3431085/71 75 48899 33000 3.084 59500 80 48460 3.924 3507075/63 70 42200 30800 2.959 52299 60 45609 3.302 3434080/67 71 45500 32000 2.976 55700 70 47399 3.607 3509085/71 71 49500 33299 3.005 59799 80 49359 3.974 3579975/63 89 39399 29800 3.275 50600 60 48689 3.423 3700080/67 91 42700 31000 3.341 54100 70 50479 3.755 3765985/71 93 46899 32299 3.402 58500 80 52609 4.167 3838075/63 83 40000 29899 3.190 50899 60 50020 3.481 3814080/67 84 43399 31300 3.245 54500 70 51920 3.827 3885985/71 85 47500 32600 3.297 58799 80 54070 4.260 3953075/63 80 40700 30199 3.122 51299 60 50950 3.521 3892980/67 80 44000 31399 3.163 54799 70 52880 3.876 3964985/71 81 48100 32700 3.207 59000 80 55100 4.328 4032075/63 99 37799 29000 3.487 49700 60 53750 3.636 4134080/67 101 41200 30399 3.568 53399 70 55740 4.034 4196985/71 102 45399 31800 3.669 57899 80 58149 4.541 4265975/63 93 38500 29300 3.392 50100 60 55200 3.701 4257080/67 94 41899 30699 3.466 53700 70 67350 4.129 4325085/71 95 46100 32000 3.549 58200 80 59810 4.662 4389075/63 90 39100 29600 3.314 50399 60 56219 3.749 4342080/67 90 42500 30800 3.381 54000 70 58429 4.196 4410985/71 91 46600 32299 3.444 58399 80 60960 4.750 4475075/63 104 37000 28699 3.601 49299 60 56250 3.751 4345080/67 105 40500 30100 3.693 53100 70 58439 4.196 4411985/71 107 44600 31500 3.814 57600 80 60939 4.748 4474075/63 98 37700 29000 3.502 49600 60 57850 3.830 4478080/67 99 41100 30399 3.585 53399 70 60070 4.301 4539085/71 100 45299 31800 3.687 57899 80 62759 4.891 4607075/63 94 38299 29300 3.420 50000 60 58920 3.886 4565980/67 95 41700 30699 3.494 53600 70 61219 4.377 4628085/71 96 45899 32000 3.577 58100 80 63990 4.990 4696075/63 109 36200 28399 3.720 48899 60 58840 3.882 4559080/67 110 39700 29899 3.824 52700 70 61100 4.369 4618985/71 112 43899 31399 3.969 57500 80 63840 4.978 4685075/63 103 36899 28699 3.618 49299 60 60460 3.970 4690980/67 104 40399 30100 3.710 53000 70 62899 4.492 4757085/71 105 44500 31500 3.834 57600 80 65689 5.131 4817975/63 99 37500 29000 3.532 49500 60 61600 4.034 4782980/67 100 41000 30399 3.615 53299 70 64109 4.578 4847985/71 101 45100 31699 3.718 57799 80 66989 5.242 4909075/63 119 34600 27800 3.962 4810080/67 120 38100 29300 4.105 5210085/71 122 42399 30800 4.301 5710075/63 113 35299 28100 3.854 4839980/67 114 38799 29500 3.981 5239985/71 115 43000 31100 4.152 5720075/63 109 35899 28300 3.767 4870080/67 110 39399 29800 3.875 5260085/71 111 43600 31300 4.024 5739975/63 119 34299 27699 4.014 4800080/67 120 37799 29199 4.161 5200085/71 121 42200 30800 4.361 57000

Page 23: Vertical Water Source Heat Pumps

Catalog 1160 / Page 23

40

50

60

70

80

85

90

100

110

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 048 at 1600 cfm 60 Hz — English units

9.0 10.6

12.0 17.8

6.0 5.1

9.0 10.6

12.0 17.8

6.0 5.1

9.0 10.6

12.0 17.8

6.0 5.1

9.0 10.6

12.0 17.8

6.0 5.1

9.0 10.6

12.0 17.8

6.0 5.1

9.0 10.6

12.0 17.8

6.0 5.1

9.0 10.6

12.0 17.8

6.0 5.1

9.0 10.6

12.0 17.8

12.0 17.8

75/63 53 49100 35399 2.925 59100 60 38079 3.111 2746080/67 54 52500 36399 2.936 62500 70 39250 3.271 2808985/71 55 56500 37700 2.959 66599 80 40590 3.472 2873975/63 50 49899 35700 2.849 59600 60 38689 3.121 2803980/67 51 53299 36700 2.849 63000 70 39890 3.286 2867985/71 51 57299 37899 2.857 67099 80 41250 3.494 2932975/63 69 46500 34100 3.210 57399 60 42189 3.185 3132080/67 70 49899 35500 3.254 61000 70 43469 3.380 3194085/71 72 54000 36799 3.315 65299 80 44929 3.620 3257075/63 63 47500 34700 3.098 58100 60 43149 3.205 3221080/67 64 50899 35799 3.129 61500 70 44469 3.409 3282985/71 65 54899 37000 3.175 65799 80 45960 3.659 3347975/63 60 48299 35000 3.012 58600 60 43859 3.220 3286980/67 60 51600 36200 3.030 62000 70 45210 3.431 3350085/71 61 55700 37299 3.061 66200 80 46740 3.688 3414975/63 79 44899 33600 3.416 56500 60 47159 3.299 3589980/67 80 48299 34799 3.481 60200 70 48590 3.539 3650985/71 82 52399 36100 3.565 64599 80 50210 3.828 3714075/63 73 45799 34000 3.292 57100 60 48250 3.327 3689980/67 73 49200 35100 3.343 60600 70 49719 3.578 3750985/71 74 53299 36500 3.417 65000 80 51390 3.878 3814975/63 70 46600 34299 3.197 57500 60 49060 3.349 3763080/67 70 50100 35500 3.235 61100 70 50570 3.607 3825085/71 71 54100 36799 3.290 65400 80 52259 3.917 3889975/63 89 43200 32899 3.640 55600 60 52170 3.439 4042980/67 90 46700 34299 3.729 59399 70 53750 3.726 4103085/71 91 50799 35600 3.834 63899 80 55539 4.067 4164975/63 82 44200 33299 3.505 56100 60 53390 3.478 4152080/67 83 47700 34600 3.580 59899 70 55020 3.777 4213085/71 84 51799 36000 3.671 64299 80 56859 4.129 4277075/63 79 44899 33600 3.401 56600 60 54299 3.507 4232980/67 80 48399 34799 3.462 60200 70 55969 3.816 4295085/71 81 52500 36299 3.539 64599 80 57840 4.175 4359075/63 98 41500 32200 3.880 54799 60 57210 3.607 4489980/67 100 45000 33600 3.993 58600 70 58950 3.941 4550085/71 101 49200 35100 4.126 63299 80 60869 4.323 4611975/63 92 42500 32600 3.735 55299 60 58570 3.657 4609080/67 93 46000 33899 3.836 59100 70 60350 4.000 4670085/71 94 50200 35399 3.950 63600 80 62340 4.398 4732975/63 89 43299 32899 3.624 55600 60 59590 3.695 4696980/67 90 46799 34299 3.709 59399 70 61390 4.045 4759085/71 91 50899 35600 3.806 63899 80 63429 4.456 4821975/63 103 40700 31899 4.005 54299 60 59750 3.701 4711980/67 104 44200 33200 4.129 58299 70 61539 4.051 4771085/71 106 48399 34700 4.279 63000 80 63560 4.463 4832975/63 97 41700 32200 3.857 54899 60 61170 3.754 4835980/67 98 45200 33700 3.968 58700 70 63009 4.117 4896085/71 99 49399 35100 4.098 63399 80 65109 4.546 4959075/63 94 42500 32600 3.743 55200 60 62219 3.793 4928080/67 95 45899 33899 3.839 59000 70 64109 4.168 4989085/71 96 50200 35399 3.949 63600 80 66260 4.610 5052075/63 108 39899 31500 4.134 54000 60 62270 3.795 4932080/67 109 43399 33000 4.269 58000 70 64150 4.169 4992085/71 111 47600 34600 4.438 62799 80 66280 4.611 5053975/63 102 40799 31899 3.981 54399 60 63759 3.851 5060980/67 103 44399 33399 4.104 58399 70 65700 4.243 5121985/71 104 48600 34899 4.250 63100 80 67900 4.704 5185075/63 99 41600 32200 3.864 54799 60 64859 3.895 5157080/67 100 45100 33600 3.973 58700 70 66849 4.300 5217985/71 101 49299 35100 4.096 63299 80 69109 4.774 5282075/63 118 38100 30800 4.399 5320080/67 119 41700 32299 4.562 5729985/71 121 46000 34000 4.768 6220075/63 112 39200 31199 4.240 5360080/67 113 42700 32700 4.385 5770085/71 114 47000 34399 4.571 6260075/63 109 39899 31500 4.117 5400080/67 110 43500 33000 4.248 5800085/71 110 47700 34600 4.407 6279975/63 119 38200 30800 4.384 5320080/67 120 41899 32299 4.541 5739985/71 120 46100 34000 4.738 62299

Page 24: Vertical Water Source Heat Pumps

40

50

60

70

80

85

90

100

110

Page 24 / Catalog 1160

Extended Range Units Only

List of Abbreviations in Capacity Data TablesEWT = Entering water temperature, ˚FGPM = Water flow, gallons per minuteWPD = Water pressure drop, ft. of waterEA = Entering air temperature, ˚F (db/wb)LWT = Leaving water temperature, ˚FTOT = Total net cooling and heating capacity, Btu/hrSEN = Sensible cooling capacity, Btu/hrkW = Total unit power input, kWTHR = Total heat of rejection, Btu/hrTHA = Total heat of absorption, Btu/hrLWT = THR 3 (500 2 gpm) + EWTTHA = TOT – (kW 2 3413)

COOLING HEATINGEWT GPM WPD EA LWT TOT SEN kW THR EA TOT kW THA

Unit size 060 at 2000 cfm 60 Hz — English units

12.0 11.3

15.4 18.4

8.0 5.1

12.0 11.3

15.4 18.4

8.0 5.1

12.0 11.3

15.4 18.4

8.0 5.1

12.0 11.3

15.4 18.4

8.0 5.1

12.0 11.3

15.4 18.4

8.0 5.1

12.0 11.3

15.4 18.4

8.0 5.1

12.0 11.3

15.4 18.4

8.0 5.1

12.0 11.3

15.4 18.4

15.4 18.4

75/63 53 66299 47000 4.106 80299 60 50750 4.568 3504980/67 54 69000 47600 4.133 83099 70 52109 4.805 3560985/71 54 72700 48500 4.177 86900 80 53670 5.100 3615975/63 51 67700 47399 3.990 81299 60 52090 4.594 3629980/67 51 70400 48100 4.004 84099 70 53500 4.844 3685985/71 51 74099 49200 4.028 87900 80 55119 5.154 3742075/63 69 61399 44799 4.560 77000 60 57149 4.708 4097980/67 70 64200 45700 4.623 80000 70 58689 5.006 4150085/71 71 67900 46799 4.718 84000 80 60450 5.369 4202075/63 63 63500 45700 4.357 78400 60 58189 4.734 4192980/67 64 66299 46600 4.401 81299 70 59780 5.043 4246085/71 64 70000 47700 4.470 85299 80 61579 5.418 4299075/63 60 64799 46299 4.234 79299 60 59780 4.776 4336980/67 61 67599 47000 4.264 82200 70 61420 5.102 4390985/71 61 71400 48100 4.311 86099 80 63299 5.495 4443975/63 79 58600 43700 4.840 75099 60 64510 4.915 4763080/67 80 61399 44600 4.925 78299 70 66280 5.289 4813085/71 81 65200 45899 5.045 82500 80 68299 5.735 4863075/63 73 60700 44600 4.627 76500 60 65719 4.954 4871080/67 73 63500 45500 4.691 79500 70 67540 5.341 4921085/71 74 67299 46799 4.786 83700 80 69620 5.801 4971075/63 70 62000 45000 4.500 77299 60 67560 5.016 5034080/67 70 64799 45899 4.548 80400 70 69459 5.423 5085085/71 71 68700 47200 4.619 84500 80 71609 5.905 5135075/63 88 55799 42500 5.132 73299 60 71959 5.175 5420080/67 89 58700 43799 5.242 76599 70 73989 5.630 5467085/71 90 62500 45100 5.385 80900 80 76260 6.158 5514975/63 82 57899 43299 4.913 74599 60 73349 5.229 5539980/67 83 60799 44399 4.999 77799 70 75430 5.699 5588085/71 84 64700 45700 5.118 82099 80 77750 6.240 5635075/63 80 59100 44000 4.783 75400 60 75459 5.314 5721980/67 80 62100 45100 4.851 78599 70 77620 5.808 5770085/71 81 66000 46100 4.950 82900 80 80010 6.368 5817975/63 98 53000 41399 5.437 71500 60 79530 5.490 6068980/67 99 55899 42700 5.569 74900 70 81760 6.012 6114085/71 100 59899 44200 5.743 79500 80 84299 6.624 6159075/63 92 55000 42200 5.211 72799 60 81079 5.557 6200980/67 93 58000 43500 5.321 76200 70 83379 6.096 6246985/71 93 61899 44899 5.464 80599 80 85989 6.730 6292075/63 90 56299 42700 5.081 73599 60 83430 5.659 6401080/67 90 59299 44000 5.171 76900 70 85829 6.228 6446985/71 91 63299 45299 5.291 81299 80 88560 6.895 6492075/63 103 51500 40899 5.591 70599 60 83310 5.654 6390980/67 104 54600 42200 5.739 74200 70 85680 6.220 6434985/71 105 58500 43799 5.927 78700 80 88379 6.884 6478075/63 97 53600 41600 5.365 71900 60 84950 5.728 6529080/67 98 56600 42899 5.487 75400 70 87390 6.316 6573085/71 98 60600 44399 5.645 79900 80 90180 7.003 6617075/63 94 54799 42200 5.234 72700 60 87430 5.845 6737980/67 95 57799 43299 5.336 76099 70 89989 6.466 6781985/71 95 61899 44899 5.469 80599 80 92900 7.189 6826075/63 107 50100 40299 5.749 69799 60 87109 5.830 6710980/67 108 53200 41600 5.908 73299 70 89640 6.445 6754085/71 110 57200 43299 6.116 78000 80 92510 7.162 6795975/63 102 52200 41200 5.520 71000 60 88849 5.915 6856080/67 102 55200 42500 5.654 74500 70 91450 6.553 6898985/71 103 59200 44000 5.828 79099 80 94409 7.295 6940975/63 99 53299 41600 5.390 71700 60 91480 6.049 7073080/67 100 56500 42899 5.505 75299 70 94209 6.722 7115985/71 100 60500 44399 5.650 79799 80 97299 7.502 7159075/63 117 47299 39200 6.064 6800080/67 118 50399 40700 6.251 7179985/71 119 54399 42299 6.498 7659975/63 112 49399 39899 5.836 6929980/67 112 52500 41399 5.997 7290085/71 113 56500 43100 6.207 7770075/63 109 50500 40500 5.708 6990080/67 110 53700 41799 5.850 7359985/71 110 57799 43299 6.026 7829975/63 119 47600 39200 6.031 6820080/67 119 50799 40700 6.197 7200085/71 120 55000 42500 6.415 76900

Page 25: Vertical Water Source Heat Pumps

Catalog 1160 / Page 25

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

Extended Range Units Only

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 007 at 109 L/s 50 Hz — SI units

0.09 2.5

0.11 4.5

0.06 0.8

0.09 2.5

0.11 4.5

0.06 0.8

0.09 2.5

0.11 4.5

0.06 0.8

0.09 2.5

0.11 4.5

0.06 0.8

0.09 2.5

0.11 4.5

0.06 0.8

0.09 2.5

0.11 4.5

0.06 0.8

0.09 2.5

0.11 4.5

0.06 0.8

0.09 2.5

0.11 4.5

0.11 4.5

24/17 11 2000 1500 0.503 2500 16 1729 0.526 119927/19 11 2200 1600 0.494 2700 21 1800 0.552 123930/21 12 2399 1699 0.486 2899 27 1919 0.617 130024/17 10 2100 1500 0.505 2600 16 1739 0.526 120927/19 10 2200 1600 0.496 2700 21 1810 0.554 125030/21 10 2399 1699 0.487 2899 27 1929 0.619 131024/17 20 1899 1399 0.496 2399 16 1929 0.540 138927/19 20 2000 1500 0.495 2500 21 2020 0.582 143930/21 21 2200 1600 0.494 2700 27 2149 0.657 148924/17 17 1899 1399 0.496 2399 16 1949 0.542 140927/19 17 2100 1600 0.492 2600 21 2040 0.585 145930/21 17 2200 1699 0.489 2700 27 2169 0.662 151024/17 15 1899 1399 0.496 2399 16 1969 0.543 141927/19 16 2100 1600 0.491 2600 21 2060 0.588 146930/21 16 2299 1699 0.487 2799 21 2189 0.664 152024/17 25 1699 1399 0.507 2200 16 2169 0.565 160027/19 26 1899 1500 0.510 2399 21 2270 0.619 163930/21 26 2100 1600 0.516 2600 27 2410 0.709 169924/17 22 1800 1399 0.501 2299 16 2189 0.568 162027/19 23 2000 1500 0.502 2500 21 2290 0.623 166930/21 23 2100 1600 0.505 2600 27 2439 0.716 171924/17 21 1800 1399 0.499 2299 16 2209 0.570 163927/19 21 2000 1500 0.499 2500 21 2310 0.626 167930/21 22 2100 1600 0.501 2600 27 2459 0.720 173924/17 30 1600 1300 0.525 2200 16 2370 0.591 177027/19 30 1800 1399 0.533 2299 21 2470 0.654 182030/21 31 2000 1600 0.542 2500 27 2640 0.761 187924/17 27 1699 1300 0.515 2200 16 2390 0.595 180027/19 27 1800 1500 0.520 2399 21 2500 0.659 184030/21 28 2000 1600 0.528 2500 27 2669 0.769 189924/17 26 1699 1300 0.511 2200 16 2410 0.597 181027/19 26 1899 1500 0.516 2399 21 2520 0.663 186030/21 27 2000 1600 0.523 2600 27 2689 0.774 191924/17 35 1500 1300 0.558 2100 16 2609 0.626 197927/19 36 1699 1399 0.569 2200 21 2729 0.704 202930/21 37 1800 1500 0.581 2399 27 2919 0.831 208924/17 33 1600 1300 0.542 2100 16 2640 0.631 200927/19 33 1699 1399 0.553 2299 21 2770 0.711 204930/21 34 1899 1500 0.563 2399 27 2950 0.841 210924/17 32 1600 1300 0.537 2100 16 2660 0.634 202927/19 32 1699 1399 0.547 2299 21 2790 0.716 206930/21 32 1899 1500 0.557 2500 27 2979 0.847 212924/17 37 1500 1300 0.571 2000 16 2689 0.640 204927/19 38 1600 1399 0.583 2200 21 2819 0.723 210030/21 39 1800 1500 0.597 2399 27 3009 0.856 214924/17 35 1500 1300 0.554 2100 16 2720 0.645 208027/19 35 1699 1399 0.565 2200 21 2859 0.730 212030/21 36 1800 1500 0.577 2399 27 3049 0.867 218024/17 34 1500 1300 0.548 2100 16 2740 0.649 210027/19 34 1699 1399 0.559 2299 21 2879 0.735 214030/21 34 1899 1500 0.570 2399 27 3080 0.874 220024/17 40 1399 1199 0.591 2000 16 2819 0.661 214927/19 41 1600 1399 0.605 2200 21 2950 0.752 220030/21 42 1699 1500 0.622 2299 27 3149 0.896 225924/17 38 1500 1199 0.573 2000 16 2850 0.668 218027/19 38 1600 1399 0.585 2200 21 2990 0.761 222930/21 38 1800 1500 0.600 2399 27 3200 0.908 229024/17 37 1500 1300 0.567 2000 16 2870 0.672 220027/19 37 1600 1399 0.578 2200 21 3020 0.767 225030/21 37 1800 1500 0.592 2399 27 3220 0.916 231024/17 46 1300 1199 0.638 189927/19 46 1399 1300 0.657 210030/21 47 1600 1399 0.680 229924/17 43 1300 1199 0.616 200027/19 44 1500 1300 0.633 210030/21 44 1600 1500 0.653 229924/17 42 1399 1199 0.608 200027/19 43 1500 1300 0.625 210030/21 43 1699 1500 0.644 229924/17 47 1199 1199 0.650 189927/19 48 1399 1300 0.671 210030/21 48 1600 1399 0.694 2299

Capacity data — 50 Hertz

Page 26: Vertical Water Source Heat Pumps

Extended Range Units Only

Page 26 / Catalog 1160

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 009 at 142 L/s 50 Hz — SI units

0.11 12.4

0.15 22.9

0.08 6.6

0.11 12.4

0.15 22.9

0.08 6.6

0.11 12.4

0.15 22.9

0.08 6.6

0.11 12.4

0.15 22.9

0.08 6.6

0.11 12.4

0.15 22.9

0.08 6.6

0.11 12.4

0.15 22.9

0.08 6.6

0.11 12.4

0.15 22.9

0.08 6.6

0.11 12.4

0.15 22.9

0.15 22.9

24/17 12 2899 2100 0.776 3700 16 2009 0.738 127027/19 12 3000 2200 0.768 3799 21 2089 0.730 136030/21 13 3200 2299 0.758 3899 27 2250 0.758 148924/17 10 3000 2100 0.801 3799 16 2029 0.737 130027/19 10 3100 2200 0.793 3899 21 2120 0.730 138930/21 10 3200 2299 0.784 4000 27 2279 0.761 152024/17 20 2700 2000 0.715 3399 16 2299 0.730 157027/19 21 2799 2100 0.709 3500 21 2399 0.740 165930/21 21 2899 2200 0.703 3600 27 2569 0.795 177024/17 18 2700 2000 0.727 3500 16 2330 0.729 160027/19 18 2899 2100 0.721 3600 21 2430 0.741 168930/21 18 3000 2200 0.713 3700 27 2600 0.799 180024/17 16 2799 2000 0.739 3500 16 2359 0.729 162927/19 16 2899 2100 0.733 3700 21 2459 0.743 171930/21 16 3100 2299 0.725 3799 27 2640 0.805 183024/17 26 2500 1899 0.705 3200 16 2620 0.732 188927/19 26 2600 2000 0.704 3299 21 2740 0.765 197930/21 26 2799 2200 0.704 3500 27 2939 0.851 208924/17 23 2600 1899 0.706 3299 16 2649 0.733 191927/19 23 2700 2000 0.703 3399 21 2770 0.768 200930/21 24 2799 2200 0.700 3500 27 2970 0.856 212024/17 21 2600 2000 0.709 3299 16 2680 0.734 194927/19 22 2700 2100 0.706 3399 21 2810 0.772 204030/21 22 2899 2200 0.701 3600 27 3009 0.862 214924/17 30 2299 1800 0.714 3000 16 2870 0.743 212927/19 31 2500 2000 0.717 3200 21 3009 0.796 222030/21 31 2600 2100 0.722 3299 27 3229 0.898 233024/17 28 2399 1899 0.708 3100 16 2899 0.745 216027/19 28 2500 2000 0.709 3200 21 3049 0.800 225030/21 28 2700 2100 0.711 3399 27 3259 0.905 235924/17 26 2500 1899 0.706 3200 16 2939 0.747 220027/19 26 2600 2000 0.705 3299 21 3089 0.806 229030/21 27 2700 2100 0.704 3399 27 3310 0.914 239924/17 36 2100 1800 0.742 2899 16 3200 0.769 243027/19 36 2299 1899 0.751 3000 21 3359 0.839 252030/21 37 2399 2000 0.764 3200 27 3580 0.970 260924/17 33 2200 1800 0.730 2899 16 3240 0.773 245927/19 34 2299 1899 0.736 3100 21 3390 0.844 254930/21 34 2500 2100 0.745 3299 27 3649 0.985 266024/17 32 2299 1800 0.723 3000 16 3279 0.778 250027/19 32 2399 1899 0.726 3100 21 3439 0.851 258930/21 32 2600 2100 0.732 3299 27 3700 0.997 270024/17 38 2100 1699 0.754 2799 16 3299 0.780 252027/19 38 2200 1899 0.766 3000 21 3459 0.854 260930/21 39 2399 2000 0.780 3200 27 3720 1.002 272024/17 35 2100 1800 0.741 2899 16 3339 0.785 256027/19 36 2299 1899 0.749 3000 21 3509 0.861 264030/21 36 2500 2000 0.761 3200 27 3770 1.014 275924/17 34 2200 1800 0.733 2899 16 3390 0.789 260027/19 34 2299 1899 0.738 3100 21 3560 0.868 268930/21 34 2500 2100 0.747 3299 27 3830 1.028 279924/17 40 2000 1699 0.776 2799 16 3459 0.795 266027/19 41 2100 1800 0.791 2899 21 3629 0.881 275030/21 41 2299 2000 0.806 3100 27 3910 1.048 285924/17 38 2100 1699 0.761 2799 16 3500 0.799 270027/19 39 2200 1899 0.773 3000 21 3669 0.888 279030/21 39 2399 2000 0.785 3100 27 3959 1.061 289924/17 37 2100 1699 0.751 2899 16 3549 0.804 274027/19 37 2200 1899 0.760 3000 21 3729 0.897 283030/21 37 2399 2000 0.771 3200 27 4019 1.077 293924/17 46 1800 1600 0.825 260027/19 46 2000 1800 0.844 279930/21 47 2100 1899 0.869 300024/17 44 1899 1600 0.811 270027/19 44 2000 1800 0.825 279930/21 45 2200 2000 0.844 300024/17 42 1899 1699 0.799 270027/19 43 2100 1800 0.811 289930/21 43 2200 2000 0.826 310024/17 47 1699 1600 0.843 260027/19 47 1899 1800 0.860 279930/21 48 2100 1899 0.884 3000

Page 27: Vertical Water Source Heat Pumps

Catalog 1160 / Page 27

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

Extended Range Units Only

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 012 at 189 L/s 50 Hz — SI units

0.16 28.9

0.22 52.4

0.11 14.3

0.16 28.9

0.22 52.4

0.11 14.3

0.16 28.9

0.22 52.4

0.11 14.3

0.16 28.9

0.22 52.4

0.11 14.3

0.16 28.9

0.22 52.4

0.11 14.3

0.16 28.9

0.22 52.4

0.11 14.3

0.16 28.9

0.22 52.4

0.11 14.3

0.16 28.9

0.22 52.4

0.22 52.4

24/17 11 3600 2600 0.721 4299 16 2200 0.749 144927/19 11 3799 2700 0.719 4500 21 2339 0.772 156030/21 11 3899 2799 0.717 4700 27 2540 0.832 170924/17 9 3600 2600 0.729 4400 16 2240 0.750 148927/19 9 3799 2700 0.726 4500 21 2379 0.774 161030/21 9 4000 2899 0.723 4700 27 2589 0.838 175024/17 19 3299 2500 0.727 4099 16 2560 0.761 180027/19 19 3500 2600 0.731 4200 21 2709 0.801 190930/21 20 3700 2700 0.739 4400 27 2939 0.890 204924/17 16 3399 2500 0.717 4099 16 2609 0.763 185027/19 16 3600 2600 0.719 4299 21 2759 0.806 195930/21 17 3799 2799 0.722 4500 27 3000 0.899 210024/17 15 3500 2500 0.715 4200 16 2660 0.765 188927/19 15 3600 2600 0.716 4299 21 2810 0.811 200030/21 15 3799 2799 0.717 4500 27 3049 0.908 214024/17 25 3100 2399 0.763 3899 16 2959 0.784 216927/19 25 3299 2500 0.775 4000 21 3120 0.846 227930/21 25 3500 2700 0.791 4299 27 3379 0.970 241024/17 22 3200 2399 0.744 4000 16 3009 0.788 222027/19 22 3399 2600 0.750 4099 21 3180 0.854 233030/21 23 3600 2700 0.760 4299 27 3450 0.983 247024/17 20 3200 2399 0.734 4000 16 3060 0.792 227027/19 21 3399 2600 0.739 4099 21 3240 0.862 237930/21 21 3600 2700 0.746 4400 27 3509 0.997 252024/17 29 2899 2299 0.809 3700 16 3279 0.812 247027/19 30 3100 2500 0.827 3899 21 3470 0.895 256930/21 30 3299 2600 0.852 4099 27 3750 1.047 270924/17 27 3000 2299 0.783 3799 16 3339 0.818 252027/19 27 3200 2500 0.796 4000 21 3529 0.905 262030/21 27 3399 2700 0.813 4200 27 3819 1.058 275924/17 25 3100 2299 0.770 3799 16 3399 0.824 256927/19 25 3200 2500 0.780 4000 21 3589 0.916 268030/21 26 3399 2700 0.793 4200 27 3890 1.070 281924/17 35 2700 2200 0.877 3600 16 3669 0.857 281027/19 35 2899 2399 0.906 3799 21 3879 0.968 291030/21 36 3100 2500 0.936 4000 27 4169 1.125 304024/17 33 2799 2200 0.848 3600 16 3729 0.866 287027/19 33 3000 2399 0.868 3799 21 3950 0.982 297030/21 33 3200 2600 0.896 4099 27 4240 1.140 310024/17 31 2799 2299 0.831 3700 16 3799 0.875 291927/19 31 3000 2399 0.848 3899 21 4030 0.995 302930/21 32 3200 2600 0.873 4099 27 4320 1.156 316024/17 37 2600 2200 0.904 3500 16 3799 0.875 291927/19 37 2799 2299 0.934 3700 21 4019 0.994 302930/21 38 3000 2500 0.963 4000 27 4309 1.154 314924/17 34 2700 2200 0.872 3600 16 3870 0.884 297927/19 35 2899 2399 0.895 3799 21 4089 1.005 308030/21 35 3100 2600 0.925 4000 27 4389 1.171 320924/17 33 2799 2200 0.854 3600 16 3930 0.895 304027/19 33 2899 2399 0.875 3799 21 4160 1.016 314030/21 33 3200 2600 0.903 4099 27 4459 1.188 327924/17 40 2500 2100 0.942 3399 16 3990 0.904 308927/19 40 2700 2299 0.972 3700 21 4219 1.025 318930/21 41 2899 2500 1.007 3899 27 4519 1.200 331924/17 37 2600 2200 0.910 3500 16 4070 0.916 314927/19 38 2799 2299 0.940 3700 21 4290 1.037 325030/21 38 3000 2500 0.966 4000 27 4599 1.219 337924/17 36 2600 2200 0.893 3500 16 4139 0.928 320927/19 36 2799 2399 0.917 3700 21 4360 1.050 331030/21 36 3100 2500 0.945 4000 27 4679 1.238 343924/17 45 2299 2000 1.019 329927/19 46 2500 2200 1.052 350030/21 46 2700 2399 1.096 379924/17 43 2399 2100 0.991 329927/19 43 2600 2299 1.019 360030/21 44 2799 2399 1.055 379924/17 42 2399 2100 0.974 339927/19 42 2600 2299 0.999 360030/21 42 2799 2500 1.033 389924/17 47 2200 2000 1.037 320027/19 47 2399 2200 1.069 350030/21 47 2600 2599 1.111 3799

Page 28: Vertical Water Source Heat Pumps

Extended Range Units Only

Page 28 / Catalog 1160

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 015 at 227 L/s 50 Hz — SI units

0.17 26.1

0.23 44.4

0.11 12.2

0.17 26.1

0.23 44.4

0.11 12.2

0.17 26.1

0.23 44.4

0.11 12.2

0.17 26.1

0.23 44.4

0.11 12.2

0.17 26.1

0.23 44.4

0.11 12.2

0.17 26.1

0.23 44.4

0.11 12.2

0.17 26.1

0.23 44.4

0.11 12.2

0.17 26.1

0.23 44.4

0.23 44.4

24/17 10 3600 2700 0.546 4099 16 2919 0.771 214927/19 10 3799 2799 0.560 4299 21 3040 0.854 218930/21 11 4099 3000 0.578 4700 27 3189 0.958 222924/17 8 3600 2700 0.521 4099 16 2990 0.779 220927/19 9 3799 2899 0.532 4400 21 3109 0.863 225030/21 9 4099 3000 0.548 4700 27 3259 0.967 229924/17 19 3399 2600 0.672 4000 16 3310 0.816 249027/19 19 3600 2799 0.690 4299 21 3430 0.903 252930/21 20 3899 3000 0.717 4599 27 3580 1.011 256924/17 16 3399 2600 0.628 4099 16 3399 0.828 258027/19 16 3700 2799 0.643 4299 21 3529 0.916 260930/21 17 4000 3000 0.664 4599 27 3680 1.025 264924/17 14 3500 2600 0.602 4099 16 3479 0.837 264927/19 15 3700 2799 0.616 4299 21 3609 0.926 268030/21 15 4000 3000 0.634 4599 27 3759 1.037 272024/17 25 3200 2500 0.756 4000 16 3770 0.873 289927/19 25 3500 2700 0.777 4299 21 3890 0.965 293030/21 26 3799 2899 0.807 4599 27 4049 1.079 297024/17 22 3299 2600 0.711 4000 16 3879 0.887 299027/19 22 3500 2700 0.730 4299 21 4009 0.980 302930/21 23 3799 3000 0.754 4599 27 4160 1.096 306924/17 20 3299 2600 0.685 4000 16 3970 0.899 306927/19 20 3600 2799 0.701 4299 21 4089 0.992 310030/21 21 3899 3000 0.723 4599 27 4250 1.110 314024/17 30 3100 2500 0.827 4000 16 4150 0.923 322927/19 30 3399 2700 0.850 4200 21 4280 1.018 325930/21 31 3700 2899 0.882 4599 27 4429 1.137 329924/17 27 3200 2500 0.782 4000 16 4269 0.938 333027/19 27 3399 2700 0.802 4200 21 4400 1.035 335930/21 28 3700 2899 0.830 4599 27 4559 1.156 339924/17 25 3200 2500 0.756 4000 16 4370 0.952 341027/19 25 3500 2700 0.774 4299 21 4490 1.050 343930/21 26 3799 2899 0.799 4599 27 4660 1.171 347924/17 36 3000 2399 0.912 3899 16 4599 0.984 362027/19 36 3200 2600 0.938 4200 21 4730 1.084 364930/21 37 3600 2899 0.974 4500 27 4889 1.208 368024/17 33 3100 2500 0.867 3899 16 4730 1.003 372927/19 33 3299 2700 0.890 4200 21 4860 1.104 375930/21 33 3600 2899 0.921 4500 27 5019 1.229 379024/17 31 3100 2500 0.841 4000 16 4839 1.018 381927/19 31 3399 2700 0.861 4200 21 4969 1.120 385030/21 32 3700 2899 0.890 4599 27 5129 1.247 387924/17 38 3000 2399 0.940 3899 16 4750 1.006 374027/19 38 3200 2600 0.968 4200 21 4879 1.107 377030/21 39 3500 2899 1.004 4500 27 5040 1.232 381024/17 35 3000 2399 0.896 3899 16 4879 1.025 385927/19 35 3299 2600 0.920 4200 21 5019 1.127 389030/21 35 3600 2899 0.951 4500 27 5179 1.254 391924/17 33 3100 2500 0.869 3899 16 4990 1.041 395027/19 33 3299 2700 0.891 4200 21 5129 1.144 397930/21 34 3600 2899 0.920 4500 27 5290 1.272 401924/17 41 2899 2399 0.983 3899 16 4969 1.038 393027/19 41 3100 2600 1.012 4200 21 5110 1.141 395930/21 42 3500 2799 1.050 4500 27 5269 1.269 400024/17 38 3000 2399 0.939 3899 16 5110 1.058 404927/19 38 3200 2600 0.964 4200 21 5250 1.163 408030/21 38 3500 2899 0.997 4500 27 5410 1.292 412024/17 36 3000 2399 0.912 3899 16 5230 1.075 415027/19 36 3299 2600 0.935 4200 21 5360 1.181 417930/21 37 3600 2899 0.966 4500 27 5530 1.312 421924/17 46 2799 2299 1.069 379927/19 47 3000 2600 1.101 409930/21 48 3299 2799 1.143 450024/17 43 2799 2399 1.025 389927/19 44 3100 2600 1.053 409930/21 44 3399 2799 1.090 450024/17 42 2899 2399 0.999 389927/19 42 3100 2600 1.024 409930/21 43 3399 2799 1.058 450024/17 47 2799 2299 1.071 379927/19 47 3000 2600 1.099 409930/21 48 3299 2799 1.136 4500

Page 29: Vertical Water Source Heat Pumps

Catalog 1160 / Page 29

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

Extended Range Units Only

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 019 at 275 L/s 50 Hz — SI units

0.24 40.9

0.32 68.5

0.16 19.8

0.24 40.9

0.32 68.5

0.16 19.8

0.24 40.9

0.32 68.5

0.16 19.8

0.24 40.9

0.32 68.5

0.16 19.8

0.24 40.9

0.32 68.5

0.16 19.8

0.24 40.9

0.32 68.5

0.16 19.8

0.24 40.9

0.32 68.5

0.16 19.8

0.24 40.9

0.32 68.5

0.32 68.5

24/17 10 5299 4000 1.129 6400 16 4580 1.293 329027/19 11 5700 4299 1.111 6799 21 4629 1.341 329030/21 11 6099 4599 1.096 7200 27 4709 1.424 329024/17 9 5299 4000 1.122 6400 16 4650 1.297 335927/19 9 5700 4299 1.100 6799 21 4700 1.348 335930/21 9 6200 4599 1.080 7299 27 4790 1.434 335024/17 19 5000 3899 1.196 6200 16 4950 1.317 364027/19 20 5400 4200 1.198 6599 21 5009 1.380 362930/21 21 5799 4500 1.205 7000 27 5110 1.482 362924/17 16 5099 3899 1.170 6299 16 5059 1.325 374027/19 17 5500 4200 1.164 6700 21 5129 1.393 372930/21 17 5900 4500 1.161 7099 27 5230 1.501 372924/17 15 5200 3899 1.159 6299 16 5139 1.332 381027/19 15 5599 4299 1.149 6700 21 5209 1.403 381030/21 15 6000 4599 1.143 7099 27 5320 1.516 381024/17 25 4799 3799 1.257 6099 16 5429 1.358 407027/19 26 5200 4099 1.271 6500 21 5509 1.441 407030/21 26 5599 4400 1.279 6900 27 5629 1.570 405924/17 22 4900 3799 1.224 6099 16 5549 1.370 417927/19 23 5299 4200 1.231 6500 21 5639 1.459 417930/21 23 5700 4500 1.236 7000 27 5769 1.595 416924/17 21 5000 3899 1.210 6200 16 5639 1.380 425927/19 21 5400 4200 1.212 6599 21 5740 1.473 425930/21 21 5799 4500 1.219 7000 27 5870 1.615 425924/17 30 4700 3700 1.317 6000 16 5830 1.402 442927/19 31 5000 4099 1.342 6400 21 5929 1.503 442930/21 31 5500 4400 1.356 6799 27 6080 1.658 441924/17 27 4799 3799 1.280 6000 16 5969 1.419 454927/19 27 5099 4099 1.296 6400 21 6070 1.524 454930/21 28 5599 4400 1.303 6900 27 6240 1.692 454024/17 26 4799 3799 1.263 6099 16 6070 1.432 463927/19 26 5200 4099 1.275 6500 21 6179 1.541 463930/21 26 5599 4400 1.280 6900 27 6349 1.718 462924/17 36 4500 3700 1.401 5900 16 6330 1.464 486027/19 36 4900 4000 1.434 6299 21 6450 1.586 486030/21 37 5299 4299 1.471 6700 27 6639 1.788 484924/17 33 4599 3700 1.358 5900 16 6480 1.483 500027/19 33 5000 4000 1.385 6299 21 6610 1.617 499030/21 34 5400 4400 1.405 6799 27 6820 1.833 499024/17 31 4599 3700 1.338 5900 16 6589 1.498 509927/19 32 5000 4000 1.363 6400 21 6730 1.641 508930/21 32 5400 4400 1.377 6799 27 6950 1.869 508024/17 38 4400 3600 1.431 5799 16 6490 1.484 500927/19 38 4799 4000 1.469 6299 21 6620 1.619 500030/21 39 5200 4299 1.515 6700 27 6839 1.837 500024/17 35 4500 3700 1.386 5900 16 6650 1.506 513927/19 35 4900 4000 1.416 6299 21 6790 1.653 513930/21 36 5299 4299 1.445 6799 27 7019 1.887 512924/17 33 4500 3700 1.365 5900 16 6769 1.524 525027/19 34 4900 4000 1.393 6299 21 6919 1.680 524030/21 34 5400 4299 1.414 6799 27 7160 1.925 523024/17 41 4299 3600 1.480 5799 16 6740 1.520 521927/19 41 4700 3899 1.526 6200 21 6889 1.674 521930/21 42 5099 4299 1.585 6700 27 7129 1.917 520924/17 38 4400 3600 1.432 5799 16 6910 1.547 537027/19 38 4799 4000 1.467 6299 21 7070 1.713 536030/21 39 5200 4299 1.509 6700 27 7330 1.973 534924/17 36 4400 3700 1.410 5900 16 7040 1.568 546927/19 37 4799 4000 1.441 6299 21 7209 1.745 546930/21 37 5299 4299 1.475 6700 27 7480 2.017 545924/17 47 4099 3500 1.587 570027/19 47 4500 3899 1.658 620030/21 48 4900 4200 1.746 670024/17 44 4200 3600 1.533 570027/19 44 4599 3899 1.586 620030/21 45 5000 4200 1.655 670024/17 42 4299 3600 1.508 579927/19 43 4599 3899 1.555 620030/21 43 5099 4200 1.615 670024/17 47 4099 3500 1.600 570027/19 48 4500 3899 1.667 609930/21 48 4900 4200 1.750 6700

Page 30: Vertical Water Source Heat Pumps

Extended Range Units Only

Page 30 / Catalog 1160

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 024 at 354 L/s 50 Hz — SI units

0.32 18.3

0.39 26.6

0.25 11.4

0.32 18.3

0.39 26.6

0.25 11.4

0.32 18.3

0.39 26.6

0.25 11.4

0.32 18.3

0.39 26.6

0.25 11.4

0.32 18.3

0.39 26.6

0.25 11.4

0.32 18.3

0.39 26.6

0.25 11.4

0.32 18.3

0.39 26.6

0.25 11.4

0.32 18.3

0.39 26.6

0.39 26.6

24/17 10 7000 5099 1.436 8400 16 5330 1.670 366027/19 11 7400 5500 1.426 8800 21 5440 1.705 374030/21 11 7900 5799 1.415 9300 27 5599 1.779 381924/17 9 7000 5200 1.433 8400 16 5410 1.671 372927/19 9 7400 5500 1.421 8800 21 5519 1.709 381030/21 10 7900 5799 1.409 9300 27 5690 1.786 389924/17 18 6599 5000 1.476 8099 16 6160 1.689 446927/19 18 7099 5299 1.475 8500 21 6290 1.751 453030/21 19 7599 5700 1,477 9000 27 6469 1.862 461024/17 16 6700 5000 1.467 8099 16 6280 1.694 458927/19 16 7099 5400 1.465 8599 21 6419 1.760 466030/21 17 7599 5700 1.466 9099 27 6610 1.876 473024/17 15 6700 5000 1.460 8199 16 6379 1.697 467927/19 15 7200 5400 1.456 8599 21 6509 1.766 474030/21 16 7700 5700 1.455 9099 27 6709 1.888 482024/17 24 6299 4900 1.535 7900 16 7089 1.731 534927/19 24 6799 5200 1.544 8300 21 7240 1.826 541030/21 25 7299 5599 1.558 8900 27 7459 1.981 548024/17 22 6400 4900 1.521 7900 16 7230 1.740 549027/19 22 6799 5299 1.529 8400 21 7389 1.840 554930/21 23 7400 5599 1.543 8900 27 7620 2.002 562024/17 21 6400 4900 1.510 8000 16 7339 1.747 558927/19 21 6900 5299 1.517 8400 21 7500 1.850 565030/21 22 7400 5599 1.527 8900 27 7730 2.017 571924/17 28 6099 4799 1.599 7700 16 7860 1.783 608027/19 29 6599 5200 1.618 8199 21 8029 1.907 612930/21 29 7099 5500 1.644 8699 27 8269 2.086 619024/17 27 6200 4799 1.581 7799 16 8029 1.796 623027/19 27 6599 5200 1.599 8199 21 8199 1.925 628030/21 28 7099 5500 1.625 8800 27 8449 2.111 633924/17 26 6200 4799 1.568 7799 16 8150 1.806 633927/19 26 6700 5200 1.584 8199 21 8330 1.936 638930/21 26 7200 5599 1.607 8800 27 8580 2.129 645024/17 34 5799 4700 1.692 7500 16 8789 1.860 692927/19 35 6299 5099 1.725 8000 21 8980 2.004 696930/21 35 6799 5400 1.756 8599 27 9259 2.235 701924/17 33 5900 4700 1.670 7599 16 8970 1.874 709927/19 33 6299 5099 1.702 8000 21 9169 2.027 713930/21 33 6900 5500 1.734 8599 27 9460 2.269 719024/17 32 5900 4700 1.654 7599 16 9099 1.885 721927/19 32 6400 5099 1.683 8099 21 9310 2.044 725930/21 32 6900 5500 1.714 8599 27 9599 2.294 730924/17 36 5700 4599 1.727 7500 16 9089 1.884 720927/19 37 6200 5000 1.763 8000 21 9289 2.042 725030/21 37 6700 5400 1.800 8500 27 9589 2.291 729024/17 35 5799 4700 1.704 7500 16 9279 1.900 737927/19 35 6200 5000 1.740 8000 21 9490 2.068 741930/21 35 6799 5400 1.776 8599 27 9800 2.329 746924/17 34 5799 4700 1.687 7500 16 9419 1.913 750927/19 34 6299 5099 1.720 8000 21 9640 2.087 754930/21 34 6799 5400 1.753 8599 27 9949 2.357 758924/17 39 5599 4599 1.781 7400 16 9550 1.925 762927/19 40 6099 5000 1.823 7900 21 9769 2.105 766030/21 40 6599 5400 1.868 8500 27 10089 2.383 770024/17 38 5700 4599 1.756 7400 16 9759 1.946 780927/19 38 6099 5000 1.798 7900 21 9980 2.135 783930/21 38 6700 5400 1.842 8500 27 10310 2.427 787924/17 37 5700 4599 1.738 7400 16 9900 1.961 794027/19 37 6200 5000 1.778 7900 21 10140 2.158 798030/21 37 6700 5400 1.819 8500 27 10470 2.459 800924/17 45 5299 4500 1.900 720027/19 45 5799 4900 1.952 770030/21 46 6299 5299 2.020 840024/17 43 5400 4500 1.872 729927/19 44 5799 4900 1.924 779930/21 44 6400 5299 1.990 840024/17 42 5400 4500 1.852 729927/19 43 5900 4900 1.901 779930/21 43 6400 5299 1.963 840024/17 47 5200 4400 1.953 709927/19 48 5599 4799 2.015 770030/21 48 6200 5200 2.099 8300

Page 31: Vertical Water Source Heat Pumps

Catalog 1160 / Page 31

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

Extended Range Units Only

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 030 at 448 L/s 50 Hz — SI units

0.36 22.4

0.49 51.3

0.24 7.5

0.36 22.4

0.49 51.3

0.24 7.5

0.36 22.4

0.49 51.3

0.24 7.5

0.36 22.4

0.49 51.3

0.24 7.5

0.36 22.4

0.49 51.3

0.24 7.5

0.36 22.4

0.49 51.3

0.24 7.5

0.36 22.4

0.49 51.3

0.24 7.5

0.36 22.4

0.49 51.3

0.49 51.3

24/17 11 8300 6200 1.711 10000 16 6469 2.043 444027/19 11 8900 6599 1.705 10599 21 6530 2.105 444030/21 12 9699 7099 1.702 11400 27 6620 2.207 442924/17 9 8500 6200 1.696 10099 16 6639 2.050 461027/19 9 9099 6700 1.685 10699 21 6700 2.117 459930/21 10 9800 7099 1.677 11500 27 6799 2.227 458924/17 20 7700 6000 1.817 9500 16 7150 2.075 508927/19 20 8300 6400 1.838 10199 21 7219 2.158 508030/21 21 9099 6900 1.872 10900 27 7339 2.289 505924/17 16 8000 6099 1.769 9699 16 7589 2.103 550927/19 17 8599 6500 1.776 10400 21 7679 2.200 549030/21 17 9300 7000 1.789 11099 27 7809 2.350 548024/17 15 8099 6099 1.748 9800 16 7809 2.118 570927/19 15 8699 6500 1.749 10500 21 7900 2.222 570030/21 15 9500 7000 1.755 11199 27 8039 2.382 567924/17 25 7400 5799 1.905 9300 16 8199 2.148 607027/19 26 8000 6299 1.941 9900 21 8310 2.265 604930/21 27 8699 6799 1.997 10699 27 8460 2.443 603024/17 22 7599 5900 1.848 9400 16 8740 2.196 655927/19 23 8199 6400 1.868 10099 21 8869 2.332 654930/21 23 9000 6799 1.900 10900 27 9050 2.535 651924/17 21 7700 6000 1.820 9500 16 9009 2.222 679927/19 21 8300 6400 1.835 10199 21 9140 2.368 678030/21 21 9099 6900 1.858 11000 27 9330 2.582 675924/17 30 7099 5700 1.990 9099 16 9099 2.231 687927/19 31 7700 6200 2.041 9699 21 9230 2.380 686030/21 32 8400 6700 2.111 10599 27 9429 2.598 683924/17 27 7299 5799 1.926 9199 16 9730 2.301 744027/19 28 7900 6299 1.960 9900 21 9880 2.472 741930/21 28 8699 6799 2.009 10699 27 10099 2.719 738924/17 26 7400 5799 1.895 9300 16 10029 2.338 770927/19 26 8000 6299 1.922 10000 21 10189 2.517 769030/21 26 8800 6799 1.961 10800 27 10429 2.782 766024/17 36 6700 5500 2.104 8800 16 10199 2.360 786027/19 37 7299 6000 2.176 9500 21 10359 2.543 783930/21 37 8099 6599 2.267 10400 27 10609 2.819 779924/17 33 6900 5599 2.035 9000 16 10929 2.451 849027/19 33 7599 6099 2.087 9699 21 11119 2.668 847030/21 34 8400 6599 2.152 10500 27 11410 2.990 842924/17 31 7000 5700 2.000 9000 16 11279 2.501 880027/19 32 7700 6200 2.043 9699 21 11490 2.736 876930/21 32 8500 6700 2.100 10599 27 11800 3.080 873024/17 38 6599 5500 2.145 8699 16 10570 2.404 817927/19 38 7200 6000 2.224 9400 21 10750 2.605 816030/21 39 8000 6500 2.324 10300 27 11009 2.903 813024/17 35 6799 5599 2.075 8900 16 11339 2.508 883927/19 35 7400 6099 2.132 9599 21 11550 2.746 881030/21 36 8199 6599 2.204 10400 27 11849 3.093 876924/17 33 6900 5599 2.038 8900 16 11710 2.565 916027/19 34 7599 6099 2.088 9699 21 11939 2.821 913030/21 34 8400 6599 2.150 10500 27 12269 3.193 908924/17 41 6400 5400 2.209 8599 16 11130 2.479 866927/19 41 7000 5900 2.297 9300 21 11330 2.706 864030/21 42 7799 6400 2.413 10199 27 11630 3.041 859924/17 38 6599 5500 2.136 8699 16 11960 2.605 935927/19 38 7299 6000 2.204 9500 21 12189 2.873 933930/21 39 8099 6500 2.288 10400 27 12539 3.262 928924/17 36 6700 5500 2.098 8800 16 12359 2.674 969927/19 37 7400 6000 2.157 9500 21 12609 2.962 966930/21 37 8199 6599 2.230 10400 27 12980 3.378 961924/17 46 6000 5299 2.343 840027/19 47 6700 5799 2.454 909930/21 48 7500 6299 2.606 1009924/17 44 6200 5400 2.268 850027/19 44 6900 5900 2.355 930030/21 45 7700 6400 2.470 1019924/17 42 6400 5400 2.227 859927/19 43 7000 5900 2.305 930030/21 43 7799 6500 2.406 1019924/17 47 6000 5299 2.342 840027/19 47 6700 5799 2.439 919930/21 48 7500 6299 2.567 10099

Page 32: Vertical Water Source Heat Pumps

Extended Range Units Only

Page 32 / Catalog 1160

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 036 at 472 L/s 50 Hz — SI units

0.44 24.7

0.57 35.7

0.30 14.4

0.44 24.7

0.57 35.7

0.30 14.4

0.44 24.7

0.57 35.7

0.30 14.4

0.44 24.7

0.57 35.7

0.30 14.4

0.44 24.7

0.57 35.7

0.30 14.4

0.44 24.7

0.57 35.7

0.30 14.4

0.44 24.7

0.57 35.7

0.30 14.4

0.44 24.7

0.57 35.7

0.57 35.7

24/17 11 10300 8000 2.035 12300 16 8330 2.222 612027/19 11 10900 8500 2.019 12900 21 8439 2.308 616030/21 11 11699 9099 2.003 13699 27 8599 2.449 616924/17 9 10400 8099 2.021 12400 16 8419 2.227 620927/19 9 11099 8599 2.000 13099 21 8539 2.316 624030/21 10 11800 9099 1.979 13800 27 8699 2.461 625924/17 19 9699 7799 2.152 11800 16 9080 2.267 683027/19 20 10300 8300 2.158 12500 21 9210 2.378 684930/21 21 11099 8900 2.169 13300 27 9419 2.556 687924/17 17 9900 7799 2.105 12000 16 9269 2.280 700027/19 17 10500 8400 2.102 12599 21 9400 2.398 701930/21 17 11300 9000 2.104 13400 27 9619 2.585 705924/17 15 10000 7900 2.080 12099 16 9369 2.288 709927/19 15 10699 8400 2.072 12699 21 9529 2.412 713930/21 16 11400 9000 2.068 13500 27 9740 2.602 716024/17 25 9300 7599 2.268 11500 16 10009 2.342 769027/19 26 9900 8199 2.291 12199 21 10179 2.488 770930/21 26 10699 8699 2.316 13000 27 10419 2.709 773024/17 22 9500 7700 2.206 11699 16 10230 2.362 788927/19 23 10099 8199 2.220 12400 21 10400 2.516 791030/21 23 10900 8800 2.241 13199 27 10669 2.747 794024/17 21 9599 7700 2.171 11800 16 10349 2.374 800027/19 21 10300 8300 2.179 12400 21 10529 2.532 801930/21 22 11000 8800 2.194 13199 27 10800 2.766 805024/17 30 8900 7500 2.385 11300 16 10810 2.422 841027/19 31 9599 8000 2.424 12000 21 11009 2.599 842930/21 31 10400 8599 2.456 12900 27 11269 2.839 844924/17 27 9099 7500 2.312 11400 16 11060 2.449 863027/19 28 9800 8099 2.341 12099 21 11259 2.630 864030/21 28 10599 8699 2.368 13000 27 11529 2.881 866924/17 26 9300 7599 2.270 11500 16 11189 2.465 874027/19 26 9900 8199 2.293 12199 21 11390 2.647 875930/21 26 10699 8699 2.318 13000 27 11669 2.905 877924/17 36 8500 7299 2.548 11099 16 11789 2.534 926927/19 36 9199 7900 2.595 11800 21 12009 2.729 930030/21 37 10000 8500 2.651 12699 27 12320 3.019 932024/17 33 8699 7299 2.462 11199 16 12050 2.563 950927/19 33 9400 7900 2.505 11900 21 12279 2.769 952930/21 34 10199 8599 2.548 12800 27 12599 3.072 955024/17 32 8800 7400 2.413 11300 16 12199 2.580 964027/19 32 9500 8000 2.453 12000 21 12429 2.792 966030/21 32 10300 8599 2.488 12800 27 12769 3.103 967924/17 38 8400 7200 2.607 11000 16 12109 2.569 956027/19 38 9099 7799 2.657 11699 21 12339 2.777 958030/21 39 9900 8500 2.723 12599 27 12669 3.084 959924/17 35 8599 7299 2.518 11099 16 12380 2.601 980027/19 35 9300 7900 2.563 11800 21 12619 2.820 982030/21 36 10099 8500 2.615 12699 27 12960 3.142 983924/17 34 8699 7299 2.466 11199 16 12529 2.620 992927/19 34 9400 7900 2.508 11900 21 12779 2.846 994930/21 34 10199 8500 2.552 12800 27 13130 3.176 998024/17 41 8199 7200 2.694 10900 16 12589 2.627 998027/19 41 8900 7799 2.756 11599 21 12839 2.855 1000030/21 42 9699 8400 2.836 12500 27 13189 3.188 1002924/17 38 8400 7200 2.605 11000 16 12880 2.664 1023027/19 38 9099 7799 2.656 11699 21 13140 2.904 1025030/21 39 9900 8500 2.721 12599 27 13509 3.254 1027924/17 37 8500 7299 2.550 11000 16 13060 2.687 1039027/19 37 9199 7900 2.597 11800 21 13310 2.933 1039030/21 37 10000 8500 2.654 12699 27 13689 3.291 1041924/17 47 7700 7000 2.882 1059927/19 47 8500 7599 2.969 1140030/21 48 9300 8199 3.080 1240024/17 44 8000 7099 2.785 1069927/19 44 8699 7700 2.858 1150030/21 45 9500 8300 2.953 1240024/17 43 8099 7099 2.727 1080027/19 43 8800 7700 2.792 1159930/21 43 9599 8400 2.878 1250024/17 47 7700 7000 2.885 1059927/19 48 8400 7599 2.972 1140030/21 48 9300 8199 3.083 12400

Page 33: Vertical Water Source Heat Pumps

Catalog 1160 / Page 33

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

Extended Range Units Only

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 042 at 566 L/s 50 Hz — SI units

0.49 19.4

0.67 42.8

0.33 7.2

0.49 19.4

0.67 42.8

0.33 7.2

0.49 19.4

0.67 42.8

0.33 7.2

0.49 19.4

0.67 42.8

0.33 7.2

0.49 19.4

0.67 42.8

0.33 7.2

0.49 19.4

0.67 42.8

0.33 7.2

0.49 19.4

0.67 42.8

0.33 7.2

0.49 19.4

0.67 42.8

0.67 42.8

24/17 11 11800 9000 2.394 14099 16 9269 2.626 663927/19 11 12500 9599 2.376 14900 21 9539 2.728 680930/21 12 13400 10199 2.358 15800 27 9919 2.904 700924/17 9 11900 9099 2.374 14300 16 9419 2.633 679027/19 9 12599 9699 2.351 15000 21 9699 2.740 695030/21 10 13500 10300 2.326 15900 27 10089 2.924 716024/17 20 11099 8800 2.528 13699 16 10400 2.688 770927/19 20 11900 9400 2.531 14400 21 10699 2.830 787030/21 21 12800 10099 2.541 15400 27 11130 3.060 807024/17 17 11300 8900 2.482 13800 16 10669 2.706 795927/19 17 12099 9500 2.478 14599 21 10980 2.858 811930/21 18 13000 10099 2.479 15500 27 11419 3.102 832024/17 15 11500 8900 2.449 13900 16 10849 2.719 813027/19 15 12199 9500 2.440 14599 21 11169 2.878 828930/21 16 13099 10199 2.432 15599 27 11619 3.131 849024/17 26 10699 8599 2.665 13400 16 11769 2.796 897027/19 26 11500 9199 2.687 14199 21 12109 2.989 911930/21 27 12400 9900 2.718 15099 27 12599 3.286 931024/17 23 10900 8699 2.605 13500 16 12070 2.824 924027/19 23 11699 9300 2.620 14300 21 12429 3.030 940030/21 23 12599 10000 2.643 15199 27 12919 3.335 958924/17 21 11000 8699 2.562 13599 16 12269 2.845 942927/19 21 11800 9400 2.569 14400 21 12640 3.059 958030/21 21 12699 10000 2.582 15300 27 13150 3.370 976924/17 31 10300 8500 2.802 13099 16 12910 2.914 999027/19 31 11099 9099 2.843 14000 21 13289 3.147 1014030/21 32 12099 9800 2.880 14900 27 13800 3.479 1032024/17 27 10500 8500 2.733 13199 16 13240 2.953 1028927/19 28 11300 9199 2.765 14099 21 13630 3.191 1043930/21 28 12199 9800 2.798 15000 27 14169 3.543 1061924/17 26 10599 8599 2.681 13300 16 13470 2.981 1049027/19 26 11400 9199 2.704 14099 21 13859 3.222 1064030/21 26 12400 9900 2.733 15099 27 14410 3.588 1082024/17 36 9900 8300 2.992 12900 16 14269 3.070 1119927/19 37 10699 9000 3.047 13699 21 14679 3.342 1133930/21 38 11599 9599 3.107 14699 27 15269 3.754 1151924/17 33 10099 8300 2.912 13000 16 14630 3.114 1151927/19 34 10900 9000 2.964 13800 21 15070 3.403 1166030/21 34 11800 9699 3.011 14800 27 15679 3.838 1183924/17 32 10199 8400 2.852 13099 16 14880 3.145 1174027/19 32 11000 9000 2.897 13900 21 15330 3.446 1188030/21 32 12000 9800 2.935 14900 27 15960 3.897 1206024/17 38 9699 8199 3.060 12800 16 14720 3.124 1158927/19 39 10500 8900 3.120 13599 21 15150 3.417 1173030/21 40 11500 9599 3.192 14699 27 15769 3.856 1191024/17 35 9900 8300 2.978 12900 16 15099 3.173 1191927/19 36 10699 9000 3.032 13699 21 15550 3.484 1207030/21 36 11699 9599 3.090 14800 27 16190 3.947 1224024/17 34 10000 8300 2.915 13060 16 15359 3.208 1215027/19 34 10900 9000 2.965 13800 21 15820 3.531 1228930/21 34 11800 9699 3.010 14800 27 16480 4.011 1247024/17 41 9500 8099 3.167 12699 16 15400 3.214 1217927/19 42 10300 8800 3.235 13500 21 15859 3.538 1232030/21 43 11300 9500 3.323 14599 27 16510 4.019 1249024/17 38 9699 8199 3.080 12800 16 15800 3.271 1251927/19 39 10500 8900 3.141 13599 21 16280 3.615 1266930/21 39 11500 9599 3.216 14699 27 16960 4.122 1283924/17 37 9800 8199 3.015 12800 16 16070 3.312 1275927/19 37 10599 8900 3.069 13699 21 16570 3.669 1290030/21 37 11599 9599 3.130 14699 27 17269 4.195 1307024/17 47 9000 7900 3.386 1240027/19 48 9900 8599 3.483 1340030/21 49 10900 9400 3.609 1450024/17 44 9199 8000 3.296 1250027/19 45 10000 8699 3.379 1340030/21 45 11000 9400 3.490 1450024/17 43 9400 8099 3.228 1259927/19 43 10199 8800 3.300 1350030/21 43 11199 9500 3.394 1459924/17 47 9000 7900 3.412 1240027/19 48 9800 8599 3.511 1330030/21 48 10800 9400 3.637 14500

Page 34: Vertical Water Source Heat Pumps

Extended Range Units Only

Page 34 / Catalog 1160

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 048 at 661 L/s 50 Hz — SI units

0.57 31.9

0.76 53.6

0.38 15.4

0.57 31.9

0.76 53.6

0.38 15.4

0.57 31.9

0.76 53.6

0.38 15.4

0.57 31.9

0.76 53.6

0.38 15.4

0.57 31.9

0.76 53.6

0.38 15.4

0.57 31.9

0.76 53.6

0.38 15.4

0.57 31.9

0.76 53.6

0.38 15.4

0.57 31.9

0.76 53.6

0.76 53.6

24/17 10 12900 10000 2.463 15400 16 10060 2.670 738927/19 11 13800 10800 2.461 16300 21 10320 2.794 751930/21 11 14900 11599 2.467 17399 27 10660 2.980 767924/17 9 13099 10099 2.399 15500 16 10220 2.677 754927/19 9 14000 10900 2.388 16399 21 10480 2.805 767930/21 10 15099 11599 2.381 17500 27 10839 2.997 783924/17 19 12199 9800 2.735 15000 16 11240 2.732 850927/19 20 13199 10500 2.764 15900 21 11519 2.885 864030/21 21 14300 11300 2.790 17000 27 11900 3.108 878924/17 16 12500 9900 2.631 15099 16 11490 2.747 874027/19 17 13400 10599 2.649 16000 21 11779 2.907 886930/21 17 14500 11400 2.668 17199 27 12169 3.139 902924/17 15 12699 9900 2.558 15199 16 11679 2.759 891927/19 15 13599 10699 2.565 16100 21 11980 2.924 905030/21 15 14699 11400 2.576 17300 27 12380 3.163 921024/17 25 11800 9599 2.940 14699 16 12640 2.827 981027/19 26 12699 10400 2.985 15699 21 12949 3.016 993930/21 27 13800 11099 3.035 16899 27 13380 3.287 1008924/17 22 12000 9699 2.824 14900 16 12929 2.849 1008027/19 23 13000 10500 2.861 15800 21 13250 3.046 1019930/21 23 14099 11199 2.897 17000 27 13689 3.327 1035924/17 21 12199 9699 2.741 15000 16 13140 2.867 1026927/19 21 13099 10500 2.768 15900 21 13470 3.070 1040030/21 21 14300 11300 2.791 17000 27 13919 3.357 1056024/17 30 11400 9400 3.126 14500 16 13810 2.924 1088027/19 31 12400 10199 3.184 15599 21 14150 3.145 1100930/21 32 13500 11000 3.259 16699 27 14599 3.446 1116024/17 27 11699 9500 3.001 14699 16 14130 2.954 1116927/19 28 12599 10300 3.050 15699 21 14480 3.181 1130030/21 28 13699 11099 3.108 16800 27 14939 3.492 1144924/17 26 11900 9599 2.911 14800 16 14369 2.977 1139027/19 26 12800 10400 2.951 15699 21 14720 3.207 1150930/21 26 13900 11199 2.994 16899 27 15199 3.528 1166924/17 36 11000 9300 3.362 14300 16 15210 3.058 1215027/19 37 11900 10000 3.443 15400 21 15580 3.306 1226930/21 37 13000 10900 3.552 16600 27 16079 3.658 1241924/17 33 11199 9400 3.231 14500 16 15560 3.091 1247027/19 34 12199 10099 3.297 15500 21 15939 3.351 1258930/21 34 13300 10900 3.387 16699 27 16460 3.717 1274024/17 32 11400 9400 3.134 14500 16 15830 3.118 1271027/19 32 12300 10199 3.189 15500 21 16219 3.385 1283030/21 32 13500 11000 3.262 16699 27 16750 3.762 1298024/17 38 10800 9199 3.444 14300 16 15679 3.103 1257027/19 39 11800 10000 3.535 15300 21 16059 3.365 1268930/21 39 12900 10800 3.654 16500 27 16579 3.735 1283924/17 35 11099 9300 3.309 14400 16 16039 3.140 1290027/19 35 12000 10099 3.384 15400 21 16440 3.414 1301930/21 36 13099 10900 3.486 16600 27 16969 3.799 1316924/17 34 11199 9400 3.212 14500 16 16309 3.169 1314027/19 34 12199 10099 3.274 15500 21 16719 3.451 1326930/21 34 13300 11000 3.356 16699 27 17269 3.848 1341924/17 41 10599 9099 3.571 14199 16 16379 3.176 1319927/19 42 11500 9900 3.675 15199 21 16780 3.460 1332030/21 42 12699 10699 3.814 16500 27 17329 3.858 1347024/17 38 10800 9199 3.430 14300 16 16760 3.218 1353927/19 38 11800 10000 3.520 15300 21 17179 3.514 1366030/21 39 12900 10800 3.638 16600 27 17739 3.928 1381024/17 37 11000 9300 3.331 14400 16 17050 3.251 1380027/19 37 12000 10000 3.405 15400 21 17469 3.556 1391930/21 37 13099 10900 3.505 16600 27 18050 3.983 1407024/17 47 10099 8900 3.835 1400027/19 48 11099 9699 3.971 1509930/21 48 12199 10599 4.145 1639924/17 44 10400 9000 3.686 1409927/19 44 11400 9800 3.806 1519930/21 45 12500 10699 3.960 1639924/17 42 10599 9099 3.581 1419927/19 43 11500 9900 3.683 1519930/21 43 12699 10699 3.816 1650024/17 47 10199 8900 3.800 1400027/19 48 11199 9800 3.930 1509930/21 48 12300 10699 4.093 16399

Page 35: Vertical Water Source Heat Pumps

Catalog 1160 / Page 35

4

10

16

21

27

29

32

38

43

COOLING HEATINGEWT L/s WPD EA LWT TOT SEN kW THR EA TOT kW THA

Extended Range Units Only

List of Abbreviations in Capacity Data TablesL/s = Airflow, liters per secondEWT = Entering water temperature, ˚CL/s = Water flow, liters per secondWPD = Water pressure drop, kilo Pascal (kPa)EA = Entering air temperature, ˚C (db/wb)LWT = Leaving water temperature, ˚CTOT = Total net cooling and heating capacity, WattsSEN = Sensible cooling capacity, WattskW = Total unit power input, kWTHR = Total heat of rejection, WattsTHA = Total heat of absorption, WattsLWT = THR 3 (4180 2 L/s) + EWTTHA = TOT – (kW 2 1000)

Unit size 060 at 850 L/s 50 Hz — SI units

0.76 34.0

0.97 54.8

0.50 15.0

0.76 34.0

0.97 54.8

0.50 15.0

0.76 34.0

0.97 54.8

0.50 15.0

0.76 34.0

0.97 54.8

0.50 15.0

0.76 34.0

0.97 54.8

0.50 15.0

0.76 34.0

0.97 54.8

0.50 15.0

0.76 34.0

0.97 54.8

0.50 15.0

0.76 34.0

0.97 54.8

0.97 54.8

24/17 11 17000 13099 4.263 21199 16 11890 2.447 941027/19 11 17899 13900 4.801 22699 21 12630 3.111 949030/21 12 19100 14800 5.338 24399 27 13429 3.797 959924/17 9 17300 13199 4.072 21300 16 12390 2.636 972027/19 10 18199 14000 4.624 22800 21 13119 3.280 981030/21 10 19399 14900 5.348 24699 27 13880 3.934 991924/17 20 15800 12599 4.729 20500 16 14480 3.391 1106027/19 20 16699 13500 5.174 21899 21 15099 3.932 1114030/21 21 17899 14400 4.574 22500 27 15710 4.426 1125024/17 17 16300 12800 4.578 20899 16 14869 3.528 1131027/19 17 17199 13699 5.070 22300 21 15480 4.047 1140030/21 17 18399 14599 4.826 23199 27 16050 4.507 1150924/17 15 16600 12900 4.455 21000 16 15429 3.718 1167927/19 16 17500 13800 4.966 22399 21 16000 4.205 1176930/21 16 18699 14699 5.026 23699 27 16530 4.614 1189024/17 26 15099 12300 4.842 19899 16 17239 4.308 1290027/19 26 16000 13199 4.848 20899 21 17690 4.672 1299030/21 26 17199 14199 4.380 21600 27 18030 4.891 1309924/17 22 15599 12500 4.771 20399 16 17660 4.440 1318927/19 23 16500 13400 5.068 21600 21 18089 4.772 1327930/21 23 17699 14300 4.500 22199 27 18379 4.942 1340024/17 21 15900 12599 4.711 20600 16 18260 4.621 1360927/19 21 16800 13500 5.167 22000 21 18640 4.906 1369930/21 22 18000 14400 4.617 22600 27 18809 4.953 1383024/17 30 14500 12099 4.863 19399 16 19399 4.948 1441927/19 31 15400 13000 4.680 20100 21 19640 5.101 1450930/21 31 16600 14000 4.351 21000 27 19620 4.953 1463024/17 27 15000 12300 4.850 19800 16 19839 5.070 1474027/19 28 15900 13199 4.816 20699 21 19899 5.035 1483930/21 28 17199 14199 4.369 21500 27 19969 4.974 1496024/17 26 15300 12400 4.820 20100 16 20469 5.236 1519927/19 26 16199 13300 4.919 21100 21 20289 4.958 1530030/21 26 17399 14199 4.421 21899 27 20480 5.023 1542924/17 36 13800 11800 4.752 18600 16 21199 4.935 1623027/19 36 14699 12699 4.589 19300 21 21210 4.850 1632930/21 37 15900 13699 4.447 20399 27 21699 5.218 1644924/17 33 14300 12000 4.853 19100 16 21469 4.845 1658927/19 33 15199 12900 4.640 19899 21 21550 4.833 1669030/21 34 16500 13900 4.362 20800 27 22160 5.316 1680924/17 32 14500 12099 4.859 19399 16 21859 4.732 1710027/19 32 15500 13000 4.689 20199 21 22059 4.829 1719930/21 32 16699 14000 4.349 21100 27 22839 5.482 1732924/17 38 13599 11699 4.698 18300 16 21649 4.789 1682927/19 38 14500 12599 4.583 19100 21 21789 4.828 1692930/21 39 15699 13599 4.509 20199 27 22469 5.388 1705024/17 35 14000 11900 4.819 18899 16 21940 4.712 1719927/19 35 15000 12800 4.607 19600 21 22160 4.831 1730030/21 35 16199 13800 4.394 20600 27 22969 5.516 1742024/17 34 14300 12000 4.854 19100 16 22379 4.617 1773027/19 34 15199 12900 4.644 19899 21 22719 4.855 1782930/21 34 16500 13900 4.362 20800 27 23710 5.726 1794924/17 41 13199 11599 4.633 17800 16 22379 4.618 1773027/19 41 14099 12500 4.594 18699 21 22710 4.855 1782030/21 42 15400 13500 4.629 20000 27 23699 5.722 1794924/17 38 13699 11800 4.724 18399 16 22710 4.560 1812027/19 38 14599 12699 4.585 19199 21 23129 4.888 1821030/21 38 15800 13699 4.471 20300 27 24269 5.897 1833924/17 37 13900 11800 4.785 18699 16 23199 4.497 1867027/19 37 14900 12800 4.600 19500 21 23760 4.960 1876930/21 37 16100 13800 4.410 20500 27 25109 6.180 1889024/17 46 12500 11300 4.549 1700027/19 47 13400 12300 4.678 1810030/21 47 14599 13300 4.956 1960024/17 44 13000 11500 4.598 1760027/19 44 13900 12400 4.613 1850030/21 44 15099 13500 4.718 1980024/17 42 13199 11500 4.630 1780027/19 43 14099 12500 4.593 1869930/21 43 15400 13500 4.614 2000024/17 47 12599 11300 4.556 1710027/19 47 13500 12300 4.660 1819930/21 48 14800 13300 4.877 19600

Page 36: Vertical Water Source Heat Pumps

Page 36 / Catalog 1160

Fan performance data

Physical data60 cycle (English units)

UNIT SIZE 007 009 012 015 019 024 030 036 042 048 060

Fan Wheel - 0 x W (in) 6 x 6 6 x 6 6 x 8 8 x 7 8 x 7 10 x 7 10 x 7 10 x 7 11 x 10 11 x 10 12 x 7

Fan Motor Power (hp) 1/20 1/20 1/8 1/8 1/8 1/5 1/3 1/2 1/3 3/4 3/4

Coil Face Area (sq. ft.) 0.7 1.2 1.2 1.5 1.9 2.1 2.6 3.1 3.6 4.7 5.8

Coil Rows 3 3 3 3 3 3 3 3 3 3 3

Refrigerant Charge (oz.) 10.5 17 23.5 23 28.5 34.5 45.5 47.5 53.5 67 83

Filter - (Qty) Size (in.) (1) 20 x 12 (1) 20 x 16 (1) 25 x 20 (1) 30 x 24 (2) 27 x 19

Water Connections - FPT 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4

Condensate Conn. - O.D. (in.) 7/8 7/8 7/8 7/8 7/8 7/8 7/8 7/8 78 7/8 7/8

Weight - Operating (lbs.) 107 112 121 120 155 180 191 243 262 280 323

Weight - Shipping (lbs.) 119 124 133 135 168 195 206 259 278 300 343

UNIT SIZE 007 009 012 015 019 024 030 036 042 048 060

Fan Wheel - D x W (mm) 152 x 152152 x 152 152 x 203 203 x 178 203 x 178 254 x 178 254 x 178 254 x 178 279 x 254 279 x 254 305 x 178

Fan Motor Power (Watts) 37.3 37.3 93.3 93.3 93.3 149.2 248.7 373.0 248.7 559.5 559.5

Coil Face Area (sq. m) 0.065 0.111 0.111 0.139 0.177 0.195 0.242 0.288 0.334 0.437 0.539

Coil Rows 3 3 3 3 3 3 3 3 3 3 3

Refrigerant Charge (g) 298 482 666 652 808 978 1290 1347 1517 1899 2353

Filter - (Qty) Size (mm) (1) 508 x 305 (1) 508 x 406 (1) 635 x 508 (1) 762 x 610 (2) 686 x 483

Water Connections - FPT 1/2 1/2 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4

Condensate Conn - O.D. (mm) 22 22 22 22 22 22 22 22 22 22 22

Weight - Operating (kg) 48.5 50.8 54.9 54.4 70.3 81.6 86.6 110.2 7.0 56.2 60.3

Weight - Shipping (kg) 54.0 56.2 60.3 61.2 76.2 88.5 93.4 117.5 126.1 136.1 155.6

50 cycle (SI units)

*Factory wiredFor wet coil, calculate face velocity (cfm / coil face area, sq ft). Add the following static to the external static pressure for the corresponding face velocity:300 fpm = .05"; 400 fpm = .08"; 450 fpm = .10"; 500 fpm = .12"; 550 fpm = .14". Re-enter table at the increased external static pressure to determine final cfm.

*Factory wiredFor wet coil, calculate face velocity (L/s / coil face area, sq m). Add the following static to the external static pressure for the corresponding face velocity:1.52 m/s = 12.5 Pa; 2.03 m/s = 19.9 Pa; 2.29 m/s = 24.9 Pa; 2.54 m/s = 29.9 Pa; 2.79 m/s = 34.9 Pa. Re-enter table at the increased external static pressureto determine final airflow.

60 cycle, 208 volts, single phase (includes allowance for dry coil and filter)UNIT FAN EXTERNAL STATIC PRESSURE (INCHES OF WATERI MIN.SIZE SPEED 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.50 0.60 0.75 0.90 CFM007 HI 315 295 274 253 227 197 170 — — — — 170009 HI 327 314 300 286 272 257 242 — — — — 220012 Hl* 490 1 460 446 425 403 381 358 302 — — — 300015 LOW* 570 553 534 515 495 476 454 410 — — — 375019 Hl* 692 678 560 625 600 584 550 495 — — — 475024 LOW* 852 835 814 790 762 732 696 618 — — — 600030 Hl* 1235 1225 1210 1190 1175 1150 1125 1065 985 845 — 750036 LOW* 1343 1335 1313 1295 1275 1250 1227 1165 1100 — — 900042 Hl* 1522 1518 1514 1510 1504 1490 1480 1442 1385 1255 — 1100048 LOW* 1730 1723 1710 1700 1676 1653 1627 1560 1470 1330 — 1200060 HI* 2175 2150 2120 2088 2060 2035 2000 1940 1880 1785 1695 1500

50 cycle, 230 volts, single phase (includes allowance for dry coil and filter)UNIT FAN EXTERNAL STATIC PRESSURE (Pa) MIN.SIZE SPEED 24.9 37.6 49.8 62.3 74.7 87.2 99.6 124.5 149.4 186.8 224.1 L/s007 HI 149 139 129 119 107 93 80 — — — — 80009 HI 154 148 142 135 128 121 114 — — — — 104012 Hl* 231 217 210 201 190 180 169 143 — — — 142015 LOW* 269 261 252 243 234 225 214 193 — — — 177019 Hl* 327 320 264 295 283 276 260 234 — — — 224024 LOW* 402 394 384 373 360 345 328 292 — — — 283030 Hl* 583 578 571 562 554 543 531 503 465 399 — 354036 LOW* 634 630 620 611 602 590 579 550 519 — — 425042 Hl* 718 716 714 713 710 703 698 680 654 592 — 519048 LOW* 816 813 807 802 791 780 768 736 694 628 — 566060 HI* 1026 1015 1000 985 972 960 944 915 887 842 800 708

Page 37: Vertical Water Source Heat Pumps

Catalog 1160 / Page 37

Electrical dataUnits without Boilerless System electric heat

UNIT SIZEPOWER COMPRESSOR FAN MOTOR TOTAL UNIT MIN. MIN. CIRCUIT MAX. FUSE

VOLTAGE ➀ Hz PHASE RLA LRA FLA FLA VOLTS AMPACITY SIZE ➁208-230 60 1 2.9 1 5.9 0.46 3.3 197 4.0 15

007 265 60 1 2.6 12.3 0.38 3.0 240 3.6 15230 50 1 2.6 12.3 0.46 3.6 197 3.7 15

208-230 60 1 3.5 20.0 0.46 4.0 197 4.8 15009 265 60 1 3.1 16.0 0.38 3.5 240 4.3 15

230 50 1 3.1 16.0 0.46 4.7 197 4.3 15208-230 60 1 6.6 31.2 0.83 7.5 197 9.1 15

012 265 60 1 4.2 27.0 0.65 4.9 240 5.9 15230 50 1 4.2 27.0 0.81 6.3 197 6.1 15

208-230 60 1 5.9 29.0 0.90 6.8 197 8.3 15015 265 60 1 5.5 27.0 0.80 6.3 240 7.7 15

230 50 1 5.5 27.0 1.30 10.0 197 8.2 15208-230 60 1 9.7 54.0 0.90 10.6 197 13.0 20

019 265 60 1 8.7 42.0 0.80 9.5 240 11.7 20230 50 1 8.7 42.0 1.30 11.6 197 12.2 20

208-230 60 1 10.9 56.0 1.30 12.2 197 14.9 25265 60 1 9.9 55.0 1.20 11.1 240 13.6 20

024 208-230 60 3 7.5 51.0 1.30 8.8 187 10.7 15460 60 3 3.9 25.0 0.70 4.5 416 5.6 15230 50 1 9.9 55.0 1.50 14.7 197 13.9 20

208-230 60 1 15.3 75.0 1.70 17.0 197 20.8 35265 60 1 13.9 73.0 1.70 15.5 240 19.1 30

030 208-230 60 3 10.0 68.0 1.70 11.7 187 14.2 20460 60 3 4.8 34.0 1.00 5.8 416 7.0 15380 50 3 4.8 34.0 1.90 7.12 342 7.9 15

208-230 60 1 16.1 82.0 3.50 19.6 197 23.6 35265 60 1 15.0 83.0 2.80 17.8 240 21.6 35

036 208-230 60 3 10.0 70.0 3.50 13.5 187 16.0 25460 60 3 5.1 33.0 1.60 6.7 416 8.0 15380 50 3 5.1 33.0 4.50 10.6 342 10.9 15

208-230 60 1 19.0 105.0 3.00 22.0 197 26.8 45

042208-230 60 3 11.9 85.0 3.00 14.9 187 17.9 25

460 60 3 5.9 42.0 1.70 7.6 416 9.1 15380 50 3 5.9 45.0 2.50 10.9 342 9.9 15

208-230 60 1 21.8 105.0 5.20 25.2 197 38.5 60208-230 60 3 14.1 130.0 5.20 17.1 187 28.9 40

048 460 60 3 7.1 64.0 2.80 8.9 416 14.5 20575 60 3 5.8 52.0 2.20 7.4 520 12.2 15380 50 3 5.7 64.0 7.30 17.0 342 17.7 20

208-230 60 1 28.2 135.0 5.20 27.2 197 40.5 60208-230 60 3 16.7 150.0 5.20 21.9 187 26.0 40

060 460 60 3 9.6 73.0 2.80 9.9 416 14.8 20575 60 3 8.3 59.0 2.20 8.0 520 12.6 20380 50 3 7.2 73.0 7.30 17.6 342 16.3 20

➀ 208-230 volt units are shipped for 208 volt operation. For 230 volt operation, the tap on the 24 volt control transformer must be changed from the208 volt tap to the 230 volt tap.

➁ Maximum time delay (Class RK5) fuse or HACR circuit breaker; value is amps.

Page 38: Vertical Water Source Heat Pumps

Page 38 / Catalog 1160

DIMENSIONS WATERUNIT SIZE A B C D E F CONNS.

in. mm in. mm in. mm in. mm in. mm in. mm (FPT)007 & 009 21 533 21 533 24 610 4.89 124 7.55 192 1.50 38 1/2

012 21 533 21 533 24 610 4.89 124 9.42 239 1.50 38 1/2

015 21 533 21 533 30 762 8.81 224 9.18 233 1.50 38 1/2

024 & 030 21 533 21 533 37 940 9.00 229 11.00 279 1.50 38 3/4

036 25 635 25 635 37 940 9.00 229 12.00 305 1.50 38 3/4

042 25 635 25 635 37 940 9.00 229 15.00 381 1.50 38 3/4

048 28 711 28 711 46 1168 9.00 229 15.00 381 1.50 38 3/4

060 28 711 28 711 46 1168 9.00 229 15.00 381 1.50 38 3/4

Dimensional data

Left-hand return air Right-hand return air

UNIT SIZE A B C Din. mm in. mm in. mm in. mm

007, 009, 012 20.00 508 11.20 284 1.67 42 1.03 26015 & 019 20.00 508 15.20 386 1.67 42 1.03 26024 & 030 20.00 508 24.00 610 1.67 42 1.03 26036 & 042 24.00 610 29.00 737 1.67 42 1.03 26048 & 060 27.00 686 37.39 950 1.67 42 1.03 26

All dimensions are approximate. Certified drawings available upon request.

AccessPanel

D E

F

C

A B* B* A

C

DE F

Fan AccessPanel

AccessPanel

Water SupplyWater SupplyWater Return

Water Return

7/8" (22 mm) O.D.Condensate Drain Conn.

Line Voltage:7/8" (22 mm) Hole (007-042)

11/8" (29 mm) Hole (048 & 060)

Low Voltage: 7/8" (22 mm) Hole& 7/8" (22 mm) Knockout

Compressor/ControlBox Access Panel

*Add 1" (25 mm) for filter bracket

Optional return air duct collar/filter racks

1" (25 mm)

2" (51 mm)

D D

C

AA

B B

C

UNIT SIZE A B C Din. mm in. mm in. mm in. mm

007, 009, 012 20.00 508 11.20 284 2.67 68 1.03 26015 & 019 20.00 508 15.20 386 2.67 68 1.03 26024 & 030 20.00 508 24.00 610 2.67 68 1.03 26036 & 042 24.00 610 29.00 737 2.67 68 1.03 26048 & 060 27.00 686 37.39 950 2.67 68 1.03 26

Unit sizes007-042

Unit sizes048 & 060

Page 39: Vertical Water Source Heat Pumps

Catalog 1160 / Page 39

Typical Wiring DiagramsMark IV/AC unit wiring diagram, 007 thru 060

>

>

<<

L1 GndCommon

L2

ComprMotor1

30 OL

C S

R

33

12Fan

Motor

32 31

2

Cap

Cap

BL

44

70

CRVR

V

Cof

LTLT

HP

HP

Fan

L1 Com

p

30

46

BR

42

43

Hi Press CondensateSensor

Lo Temp

BR

S

CC - Compressor ContactorCap - Motor Capacitor

BK60

ReversingValve

Solenoid

BK61

Common

OR 240V

24VAC

BKXFORMER

WH 115VRD 208VBR 265V

CircuitBreaker

(optional)

WHBK 007/012

RD 009BR

YE

Mark IV/ACPC

Board

O W2

G W1

Y1

F E L U A P V R C

Page 40: Vertical Water Source Heat Pumps

Page 40 / Catalog 1160

16

17

SCap

Cap

BK YERD BR

RDRD

10

18

23

BKRD 208VBR 265V

OR 240V

BK

Line

24VAC

52

51

Circ

uit

Bre

aker

YEBL

12

L1Com

1810 19

ComprContr

32

29

38

Lo Temp

19

52

51

J2

J1

1

2

1

2

3

4

5

6

7

YE

WH

RD

GN

BL

RedTapeEnd

OR

BK53

5455

56

FanMotor

2021

4

Aux

iliar

y M

odul

e(O

ptio

nal)

Term

inal

Boa

rd #

2

3

2

22

35

BR

3332

3130

29

27

26

2524

CondensateOverflow

37

36

J4 14 13 12 11

Con

den

sate

Lo T

emp

SR

C

Lo T

emp

SIG

Lo P

ress

SIG

Lo P

ress

SR

C

Hi P

ress

SIG

RV

Com

RV

Out

Com

p C

om

Com

p O

ut

Fan

Com

Fan

Out

24VA

C

24V

Gnd

Dis

char

ge A

ir C

om

Dis

char

ge A

ir In

Wat

er O

ut C

om

Rem

ote

DI S

RC

Rem

ote

DI S

IG

Sp

are

Rel

ay N

C

Sp

are

Rel

ay C

om

Sp

are

Rel

ay N

O

RM

Sen

sor

LED

Tena

nt O

verr

ide

RM

Sen

sor

In

RM

Sen

sor

Com

Lon

Talk

Lon

Talk

24VA

C C

omW

ater

Out

In

Aux

Mod

ule

DC

Com

Aux

Mod

ule

DC

+

Aux

Mod

ule

SE

L 2

Aux

Mod

ule

SE

L 1

Aux

Mod

ule

CLK

Aux

Mod

ule

RC

V

Aux

Mod

ule

XM

T

10 9 8 7 6 5 4 3 2 11J5 10 9 8 7 6 5 4 3 2 1 J6

21J1 3 4 5 6 7 8 9 10 11 12

6874

75

76

67

66

65

64

63

62

1 2 3 4 5 6 7

Terminal Board #1

1st Option

3 4

52

1

J2

1

36

69

70

71 (See Note 3)

72 (See Note 3)

E

L

U

P

C73

73

37

34

Fan Relay

DischargeAir

WaterOut

Hi PressRV

Solenoid

BR

C

R

39

Compr

MicroTechController

Optional WiringShielded Cable

Typical MicroTech unit wiring diagram

Page 41: Vertical Water Source Heat Pumps

Catalog 1160 / Page 41

Thermostat Connection Diagrams Mark IV/AC Units – Unit Sizes 007 to 060

Manual changeover thermostat

Standard automatic and manual changeover thermostat

Deluxe automatic changeover thermostat

Non-programmable electronic thermostat

WSHP Mark IV/AC Board Low Voltage Terminal Strip

Thermostat Terminals

P/N 106069001Includes Thermostat and Subbase(Honeywell P/N T834C2416)Fan Switch: Auto / OnSystem Switch: Heat / Off / Cool

WSHP Mark IV/AC Board Low Voltage Terminal Strip

Thermostat Terminals

P/N 105570701Includes Thermostat and Subbase(Honeywell P/N’s T874A1598 andQ674E1460)Fan Switch: Auto / OnSystem Switch: Off / Heat / Auto / Cool

WSHP Mark IV/AC Board Low Voltage Terminal Strip

Thermostat Terminals

P/N 105571003Includes Thermostat and Subbase(Honeywell P/N’s T874C1869 and Q674C1579)Fan Switch: Auto / On / Tenant OverrideSystem Switch: Off / Auto

Note: Thermostat provides a fixed 13°F differential between W1 and W2.

Operation: The units Mark IV/AC boardwill be in the occupied mode, monitoringterminals W1 and Y1 and ignoringterminal W2, when the time clockcontacts are open. The Mark IV/ACboard will be in the unoccupied mode,monitoring terminal W2 and ignoringterminals W1 and Y1, when the timeclock contacts are closed. No cooling isallowed during the unoccupied mode.The tenant override feature of thethermostat allows the occupant to forcea 2-hour override of unoccupied mode.During this override period the W1 andY1 terminals are monitored and the W2terminal is ignored (same as occupied).

WSHP Mark IV/AC Board Low Voltage Terminal Strip

Thermostat Terminals

P/N 105570801Includes Thermostat and Wall Plate(Honeywell P/N T8524D1064)

Page 42: Vertical Water Source Heat Pumps

Page 42 / Catalog 1160

Engineering guide specificationsGeneral — Contractor shall furnish and install water source heat pumps as indicated on plans. Each unit shall be ISO rated andCETL listed. Each unit shall be fully run tested at the factory. Each unit shall be shipped on a wooden skid and covered withcorrugated material.

Casing and Cabinet — The cabinet shall be fabricated from unpainted, heavy-gauge, G-60 galvanized steel. The interior shall beinsulated with 1⁄2" (13 mm) thick, 11⁄2 lb. (1681 g) density coated glass fiber. A full height access panel at the rear of the unit shallprovide access to the fan and compressor sections. A separate front panel shall provide access to the fan motor. A separate frontpanel shall provide access to the compressor section and control box. A panel below the coil shall provide access to the evaporatorsection. Unit shall have an insulated panel and drain pan separating the fan compartment from the compressor compartment. Unitshall have a factory installed 1" (25 mm) thick filter bracket for side filter removal. Unit shall have a 1" (25 mm) thick throwaway filter.Unit shall have a galvanized steel drain pan with 7/8" (22 mm) O.D. drain connection extending through the unit casing. Cabinet shallhave separate holes and knockouts for entrance of line voltage and low voltage control wiring. Supply and return water connectionsshall be copper FPT fittings and shall protrude through the cabinet for connection to a flexible hose.

Refrigerant Circuit — Each unit shall have a sealed refrigerant circuit including a hermetic compressor, capillary expansion tube(s),finned tube heat exchanger, reversing valve, water-to-refrigerant coaxial heat exchanger, safety controls, and both high and lowrefrigerant service valves.

Compressor shall be hermetic type with external vibration isolator mounts and thermal overload protection. The finned tube coilshall be constructed of aluminum fins bonded to copper tubes. The coaxial heat exchanger shall be constructed of a copper innertube and a steel outer tube and be U.L. listed. The heat exchanger shall be rated for 400 psig (2760 kPa) on the water side and 450psig (3103 kPa) on the refrigerant side.

Safety controls shall include a low suction temperature (freezestat) switch and a high refrigerant pressure switch to lock outcompressor operation. Units four tons and above shall have a low refrigerant pressure switch for loss of charge protection. A lowpressure switch shall not be permitted to replace a low suction temperature switch for freeze protection. Units shall be capable ofbeing reset only by interrupting the power supply to the unit. Unit shall not be able to be reset from the wall thermostat.

Unit shall be capable of starting in an ambient temperature of 40°F (5°C) with entering water at 70°F (21°C) with both air and waterflow rates at the ARI rating conditions.

Electrical — A control box shall be located within the unit and shall contain controls for compressor, reversing valve and fan motoroperation and shall have a 50 VA transformer and a terminal block for low voltage field wiring connections. The control box shall bemovable without access to the side of the unit.

Unit shall be namplated to accept time delay fuses or HACR circuit breaker for branch overcurrent protection of the power source.Unit control system shall provide heating or cooling as required by the setpoints of the wall thermostat. The unit control scheme

shall provide for fan operation simultaneous with compressor operation (fan interlock) regardless of the thermostat type. The unitshall be capable of providing an output signal to an LED on the thermostat or to a central monitoring panel to indicate a “fault”condition from the activation of any one of the safety switches.

Fan and Motor Assembly — Unit shall have a direct drive centrifugal fan. The fan housing shall have a removable orifice ring tofacilitate fan motor and fan wheel removal. The fan housing shall protrude through the cabinet to facilitate field duct connection. Thefan motor shall be a multispeed, PSC type with integral mounting bracket isolated from the fan housing and thermal overloadprotection. Units above one ton shall have a separate fan access panel for fan operation during compressor operation checkout.

Mark IV/AC Control System — Unit shall have a microprocessor-based control system. The unit control logic shall provide heatingand cooling operation as required by the setpoints on the wall thermostat. The control system shall provide the following:1. The use of standard mercury bulb type wall thermostats.2. Fan operation simultaneous with the compressor (fan interlock) regardless of thermostat logic.3. Time delay compressor operation.4. Delayed de-energization of the reversing valve or quiet reversing valve operation.5. Compressor short cycle protection for a minimum of three minutes before restart is possible.6. Random unit start-up after coming off an unoccupied mode.7. Single grounded wire connection for activation of the unoccupied, load shed or emergency shutdown modes.8. Night setback temperature setpoint input signal from the wall thermostat.9. Override signal from wall thermostat to override unoccupied mode for two hours.

10. Brownout protection to suspend unit operation if the supply voltage drops below 80% of nominal.11. Condensate overflow protection to suspend cooling operation in an event of a full drain pan.12. Suspended compressor operation upon activation of the refrigerant pressure switch(es).13. Cooling operation for 60 seconds upon activation of the low suction temperature (freezestat) switch - defrost cycle.14. Method of defeating compressor, reversing valve and fan time delays for fast service diagnostics.

Optional MicroTech Control System — Unit shall have a preprogrammed, pretested, microprocessor-based control system.The unit control logic shall provide control of unit heating and cooling functions in response to a wall mounted comfort sensor.The control system shall provide the following:1. Monitoring of safety controls in each heat pump and appropriate responses.2. Monitoring of discharge air temperature and leaving water temperature at each heat pump.3. Fan, reversing valve, and compressor operation.4. Control outputs for boilerless system electric heat, motorized valves, fresh air damper and other auxiliary equipment.5. Operation status of all vital unit functions.6. Optional night setback override for tenant comfort.7. RS-232 interface for direct interface using a portable IBM-compatible computer.

Page 43: Vertical Water Source Heat Pumps

Catalog 1160 / Page 43

Optional Extended Range Unit — Unit shall be capable of heating operation at 40°F (5°C) minimum entering water temperatureand 40°F(5°C) minimum entering air temperature. Unit shall have a suction line accumulator, insulated coaxial heat exchanger,insulated refrigerant tubing, and a compressor crankcase heater.

Field Installed Accessories

Thermostats (choose one of the following wall thermostats):

M Manual changeover wall thermostat for one-stage heating and cooling operation. Subbase shall have system “heat-off-cool” andfan “on-auto” switches.

M Automatic changeover wall thermostat for one-stage heating and one-stage cooling operation. Subbase shall have system “off-auto”and fan “on-auto” switches with LED for “fault.”

M Automatic and manual changeover wall thermostat for one-stage heating and one-stage cooling operation. Subbase shall havesystem “off-auto” and fan “on-auto” switches with LED for “fault.”

M Programmable microelectronic wall thermostat for one- or two-stage heating, one- or two-stage cooling, night setup, nightsetback and day/night time clock operation. The thermostat shall have system “on-off,” temperature “heat-auto-cool” and fan“on-auto” switches.

Flexible Hoses — Two fire-rated flexible hoses with ASTM ratings of Flame Spread 25, Fuel Contribution 25 and Smoke Density 50for connection to unit and field piping. Hose shall be covered with braided steel.

Valves — Two combination balancing and shutoff valves with adjustable memory stop.

Optional Duct Collar/Filter Rack — Return air duct collar/ 2" (51 mm) filter rack to accept a return air duct connection and a 1"(25 mm) or 2" (51 mm) thick filter. The side bracket shall allow for side or bottom filter removal without removing the ductwork.

Field Installed Controls for Mark IV/AC Control Units — Boilerless system kit locks out compressor operation if the entering waterfalls below the adjustable setpoint. In addition, the control shall provide a contact signal to control a field installed electric heaterdownstream of the heat pump unit. An emergency heat switch shall be provided.

Field Installed Controls — Motorized valve relay and control valve. The assembly shall include a relay, valve and wire harness. Thevalve shall open when the compressor is on and close when the compressor is off.

Multiple unit control panel allows a single thermostat to control up to three units in parallel.Auxiliary relay controls optional devices when the fan is operating. The relay shall have SPDT contacts.

0ptional Water ReguIating Valvet — Unit shall have a factory mounted refrigerant connection. The valve requires field installationto the leaving water line. The valve shall open when the compressor is on and shall close when the compressor is off. During theon-cycle, the valve shall modulate the water flow to maintain correct system refrigerant pressures.

Page 44: Vertical Water Source Heat Pumps

AAF-McQuay Incorporated4900 Technology Park Boulevard, Auburn, NY 13201-9030 USA, (315) 253-2771

Printed on recycled paper containing at least 10% post-consumer recycled material. ©2000 AAF-McQuay Incorporated (Rev. 7/00)