1 | Building America Program www.buildingamerica.gov
Buildings Technologies Program
Date: November 1, 2011
Ventilation in Multifamily Buildings
Welcome to the Webinar! We will start at 2:00 PM Eastern Time
Be sure that you are also dialed into the telephone conference call:
Dial-in number: 888-324-9601; Pass code: 5551971 Download the presentation at: www.buildingamerica.gov/meetings.html
![Page 2: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/2.jpg)
Building Technologies Program eere.energy.gov
Building America: Introduction November 1, 2011
Cheryn Engebrecht [email protected]
Building Technologies Program
![Page 3: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/3.jpg)
Building Technologies Program eere.energy.gov
• Reduce energy use in new and existing residential buildings • Promote building science and systems engineering /
integration approach • “Do no harm”: Ensure safety, health and durability are
maintained or improved • Accelerate adoption of high performance technologies
www.buildingamerica.gov
Introduction to Building America
![Page 4: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/4.jpg)
Building Technologies Program eere.energy.gov
15 Industry Research Teams
Habitat Cost Effective Energy Retrofit Program
NorthernSTAR Building America Partnership
Building Energy Efficient Homes for America (BeeHa)
Building America Retrofit Alliance (BARA)
Alliance for Residential Building Innovation (ARBI)
![Page 5: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/5.jpg)
Building Technologies Program eere.energy.gov
Today’s Speakers
Maureen Mahle is an engineer with Steven Winter Associates, Inc. where she manages the firm’s work with projects seeking certification under LEED® for Homes, Green Communities, the National Green Building Standard, and ENERGY STAR® for both single family homes and multifamily buildings. Much of her work focuses on balancing objectives for indoor air quality and energy efficiency. Sean Maxwell is a Senior Energy Consultant with Steven Winter Associates, Inc. where he provides energy audits for large and small residential buildings. He has extensive experience in performance testing of ventilation and other building systems. He also participates in research activities on emerging high-performance building strategies.
![Page 6: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/6.jpg)
Maureen Mahle and Sean Maxwell November 1, 2011
Multifamily Ventilation
![Page 7: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/7.jpg)
• Part I: Multifamily Ventilation Design • Part II: Multifamily Ventilation Implementation
Today’s Discussion
![Page 8: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/8.jpg)
• Ventilation Requirements • Air Movement in Multifamily Buildings • Fresh Air Ventilation Strategies • Local Exhaust Strategies • Energy Impacts of Ventilation
Part I: Ventilation Design
![Page 9: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/9.jpg)
Why Ventilate?
• Materials have changed
• Siting has changed
• Tightness has changed
• Codes and standards
Build-tight-ventilate-right saves more energy than building naturally leaky buildings, and air quality is better, too
![Page 10: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/10.jpg)
Two Primary Objectives
1) Providing Fresh Air - Whole-House
2) Removing Pollutants - Local Exhaust Our goal is to find the simplest solution that satisfies both objectives while minimizing cost and energy impacts.
![Page 11: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/11.jpg)
ASHRAE 62.2 Ventilation & IAQ
• Low-Rise Residential • Fresh Air (Section 4) Q = .01*S.F. + 7.5*(#BR+1) • Local exhaust (Section 5) K = 100cfm int /5ACH cont B = 50 cfm int / 20 cfm cont • Windows do not count • Best for Multifamily in-unit spaces
regardless of building height
![Page 12: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/12.jpg)
ASHRAE 62.1 Ventilation for IAQ
• MF 4+ stories • Fresh Air (Table 6-1) 5cfm/person + 0.6cfm/SF • Local exhaust (Table 6-4) K = 100cfm int /50 cfm cont B = 50 cfm int / 25 cfm cont • Kitchen exhaust not req’d for MF • Windows count for 25’ deep units • Best for MF common areas regardless of height
![Page 13: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/13.jpg)
Venting Challenges in Multifamily
• Forces acting on building (wind, stack effect) are much greater in multifamily buildings than other residential buildings
• Control of air movement is crucial! – Defining air barriers (pressure boundaries) – Tightening up mechanical systems to control flow
of air
![Page 14: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/14.jpg)
Fans as System Components
Question: How much air does a one horsepower fan move? Answer: It depends!
![Page 15: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/15.jpg)
Fans as System Components
• Fan performance dependent on rest of system
Graphic courtesy of Trane
• Higher static pressure = lower flow
• Fans = “pressure inducers”
![Page 16: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/16.jpg)
• Other forces at play: – Wind – Stack effect
• Pressure difference due to stack effect can be large >5 Pascals per floor
on cold days 10 story building =
50 Pa total
Forces at Play
![Page 17: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/17.jpg)
• Different fan locations = different flows
• Large fans for whole building must overcome stack effect
• Small fans for individual units must each overcome local pressure differences
Stack Effect
![Page 18: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/18.jpg)
Systems View of Ventilation
• Systems interact with each other: Positive and negative pressure zones produce inter-zonal flows
• Systems interact with air barriers: Good ventilation systems take advantage of good air barriers
![Page 19: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/19.jpg)
Systems View of Ventilation
• Tight construction both requires and allows good ventilation
• Compartmentalization, the construction of airtight individual compartments, breaks big forces (stack, wind) into smaller forces. It’s also important for unitized ventilation.
![Page 20: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/20.jpg)
Fresh Air Strategies
• Exhaust-driven fresh air ventilation, with or without makeup air
• Supply-driven fresh air
• Balanced fresh air and exhaust with heat or energy recovery
![Page 21: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/21.jpg)
Exhaust-Driven Fresh Air Design
• Exhaust slightly depressurizes the units
• Outside air enters through leaks, cracks, or planned inlets (trickle vent, not undercut)
• Widely used in the North
![Page 22: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/22.jpg)
Exhaust-Driven Fresh Air Design
%
LR
K
BR1BR2
CL B2 B1
9 CFM trickle vent-5 Pa
25 CFM25 CFM25 CFM
9 CFM trickle vent-5 Pa
9 CFM trickle vent5 Pa
75 CFM exhaust
9 CFM trickle vent-5 Pa
![Page 23: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/23.jpg)
Designed Inlets for Exhaust-Driven
18
• Intentional openings in building envelope that allow a trickle of air into buildings in response to pressure differential
• Trickle Vents often built into window frames (AL,FG)
• Comfortable and effective when located high
• Good practice for 4+ stories
![Page 24: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/24.jpg)
Trickle Vents
AAMA = American Architectural Manufacturers Association
19
A real-world application of 4 in 2 trickle vents
![Page 25: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/25.jpg)
Energy Impacts from Exhaust-Driven
• Align Local Exhaust with Fresh Air requirements for best efficiency (Ex: 25 Bath + 25 Kitchen)
• Continuous OR timer • Adjustable fans rated for
continuous use are best • Quiet fans <= 1 sone • ENERGY STAR fans
40-60 cfm, 6-10 watts
![Page 26: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/26.jpg)
Supply-Driven Fresh Air Design
• Mechanically supplied fresh air slightly positively pressurizes the units
• Forces stale air out through leaks and cracks
• Typically a 4-6” fresh air duct to return ductwork
• Used in Moderate and Southern climate
+
+
+
+
+
+
+ +
+
+
![Page 27: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/27.jpg)
Supply-Driven Fresh Air Design
LR
Kitchen
Bed 1
Closet
Laundry
HVAC
Bath
Bed 2
Typically 40-50 cfm design fresh air
![Page 28: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/28.jpg)
Energy Impacts from Supply-Driven
• Draws fresh air when air handler runs; add a control with timer + damper to trigger fresh intake periodically
• Air handler fans are large, so need efficient VFD to avoid energy penalty with this strategy
![Page 29: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/29.jpg)
Balanced Fresh Air Ventilation
• Transfer heat between indoor and outdoor air
• Neither pressurizes nor depressurizes
• Potential solutions for many climate zones
![Page 30: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/30.jpg)
Heat Recovery Ventilation
• Warms incoming winter air (or the reverse)
• Good to remove humidity
• Good for favorable humidity levels in & out
Cold Fresh Air from Outdoors
Cooled Stale Air Exhausted
Warmed Fresh Air to Living Space
Warm Stale Air from Living Space
![Page 31: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/31.jpg)
Energy Recovery Ventilation
• Transfers heat and moisture between indoor and outdoor air
• Moisture moves from more moist air to less
• Latent energy transfer adds 30%+ efficiency
• Good for cold dry AND hot humid conditions
![Page 32: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/32.jpg)
Energy Impacts of Balanced Design
• For best IAQ, avoid using bath exhaust
• Most efficient with small, separate ducts
• Central ERV systems serving multiple units are challenging to isolate
• Costly, so correct design and install is crucial
![Page 33: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/33.jpg)
Local Exhaust
• Remove pollutants and moisture
• Kitchens and bathrooms vented to outdoors
• Continuous exhaust
• Intermittent exhaust
• MF Central Systems
• MF Unitized Approach
![Page 34: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/34.jpg)
Exhaust: Central or Unitized? Central Exhaust Unitized Exhaust
![Page 35: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/35.jpg)
Exhaust System Design Parameters
Central Systems
• Constant Air Regulating (CAR) dampers to balance flows
• Airtight ductwork, including fan and grille connections
• Tightly compartmentalized units
Unitized Systems
• ENERGY STAR fans with variable speed where appropriate
• Short straight duct runs
• Tightly sealed ducts
• Tightly compartmentalized units
![Page 36: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/36.jpg)
Continuous vs. Intermittent Exhaust
Continuous • Bathrooms 20-30 cfm • Kitchens 5 ACH • Match whole-house flow
rates for Exhaust Only • Boost flow for localized
humidity or pollutants • Timed options
acceptable
Intermittent • User demand controlled • Bathrooms 50-80 cfm • Kitchens 100cfm • Vented range hood
removes pollutants closer to source
• Distinct from whole-house
![Page 37: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/37.jpg)
Energy Impacts of Ventilation
Specific heat of air (constant)
Yearly heating degree-days
Seasonal heating system efficiency (%)
Approximate change in infiltration due to exhaust (use 0.7 for central exhaust systems)
Ventilation means additional air must be conditioned.
![Page 38: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/38.jpg)
Sample Calculation
Annual Cost of Ventilation 23,000 CFM = $34,390/yr (heating cost only) + Electricity savings from
reduced fan energy and reduced cooling
![Page 39: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/39.jpg)
Specify & Verify Performance
• Write performance-based specifications for apartment tightness and duct tightness, based on ASHRAE, LEED, ENERGY STAR, etc. – Total duct leakage <6 cfm25 per 100 SF floor area – Total unit infiltration leakage <0.30 cfm50/SF enclosure – Exhaust fan flows within +/- 15% of ASHRAE 62 design
• Measure performance for to identify potential problems and to advance industry knowledge
34
![Page 40: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/40.jpg)
Educate End Users
• Ventilation is often misunderstood!
• Provide manuals and training
• Educate both building maintenance pros and apartment occupants
• Label switches and components
35
![Page 41: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/41.jpg)
Summary: Successful MF Ventilation
• Step 1: Understand ventilation requirements
• Step 2: Select the simplest design that can achieve both air quality and energy objectives
• Step 3: Build a tight building
• Step 4: Pay attention to installation quality
• Step 5: Check to make sure ventilation works
• Step 6: Educate users
![Page 42: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/42.jpg)
Section Break
![Page 43: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/43.jpg)
Doing it right the first time • Design • Construction • Common problems • Retrofit
Part II: Implementation Discussion
![Page 44: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/44.jpg)
MF Ventilation Design Essentials
• Focus on IAQ goals, not technologies • Choose appropriate technologies to fit goals • Design for durability • Do basic duct design, and do it well • Include performance specifications for leakage
and flow
![Page 45: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/45.jpg)
Is this appropriate design? • 2 ERVs
– 27,000 CFM supply to corridors
– 30,600 CFM exhaust from apts
• Code requires: – 900 CFM to
corridors (IMC) – 12,000 CFM
from apts (ASHRAE 90.1)
![Page 46: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/46.jpg)
Is this appropriate design?
• Single ERV takes exhaust from 2 risers; supplies air to corridors
• Simple HX core, low maintenance
• All other apt exhausts are at code levels – simple design – great construction
quality – Testing for leakage
and flow
![Page 47: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/47.jpg)
Tips for Long-Term Performance • Don’t rely on timers
– Choose constant, adequate ventilation instead
• Don’t rely on belts – Choose direct-drive, variable
speed instead – Ex: Greenheck Vari-Green
• Efficient DC motors (up to 3 HP soon)
• Variable speed for field adjust
![Page 48: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/48.jpg)
Design for Durability All New Buildings become Existing Buildings
• Fire dampers • Balancing dampers • Roof fan belts • Registers
yum
![Page 49: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/49.jpg)
Mechanical Designers’ World View
• Balancing damper transferring responsibility to balancing contractor
• Many grilles, many floors, relatively low flow targets, plus wind and weather on balancing day = balancing is difficult
• Building inspectors are more worried about cranes falling down
• Many TAB contractors don’t have the right gauges
![Page 50: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/50.jpg)
Construction Quality Control
• Duct leakage • Register leakage • Balancing
• Whole-building systems • In-unit ventilation
![Page 51: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/51.jpg)
Duct Leakage Register Flows
117 CFM
Register blocked 0 CFM
75 CFM
29 CFM
13 CFM
Duct Leakage 49 CFM
Useful Ventilation
Total Flow at roof = 166 CFM
Energy Waste?
![Page 52: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/52.jpg)
Where Do Ducts Leak the Most?
Roof curb?
Takeoffs?
Transverse (sectional) joints?
Longitudinal (lengthwise)
joints? Could be any of them, OR…
Register connections
can be the largest set of leaks
![Page 53: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/53.jpg)
Tips for High Performance • Include performance specifications for duct
tightness in construction documents • Call out specific details to be sealed: all joints,
takeoffs, connections, registers, etc., etc. Then test for leakage:
• Good =
10 CFM50/register • Better =
5 CFM50/register
![Page 54: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/54.jpg)
In-Unit Exhaust Systems
Small fans, relatively low flow (50-100 CFM), low power consumption, easier to balance floor to floor
![Page 55: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/55.jpg)
In-Unit Ventilation Quality Control
• Duct sealing • Avoid kinks, long duct
runs; use rigid duct • Test for leakage early • Can also test for flow with
static pressure probes
From Panasonic
![Page 56: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/56.jpg)
Trickle Vents – Quality Control
Trickle Vents - Window Manufacturer Error
Clean holes
Improperly cut orifice Restricts flow
![Page 57: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/57.jpg)
Automatic Balancing Dampers 60 CFM 40 CFM 20 CFM 30 CFM 20 CFM 10 CFM
30 CFM 30 CFM 30 CFM 30 CFM 30 CFM 30 CFM
Balance in two ways: • Provide restriction in size of
opening (increase static pressure)
• Dynamically self-adjust to changes in the system (automatic balancing)
![Page 58: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/58.jpg)
Effects of Balancing on Performance
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 2
4
6
8
10
12
14
16
Floo
r
Negative Static Pressure WRT Trash Room (- Pascals) CFM
-10 0 10 20 30 40 50 60 70 80 90 100 110 120 2
4
6
8
10
12
14
16
Floo
r
Negative Static Pressure WRT Trash Room (- Pascals) CFM
Pre-retrofit Post-retrofit
![Page 59: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/59.jpg)
Takeaways – Construction Quality
• Duct sealing is easy and critical to success
• Test early, test often • Restriction created by CAR
dampers or fixed orifices raises static pressure and helps balance system
97% reduction in free area
54
![Page 60: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/60.jpg)
Retrofit Process – Video Inspection
Blocked ducts
55
Beer in ducts
Dirty ducts
![Page 61: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/61.jpg)
Retrofit Process – Register Inspection
• Large gaps at takeoff are very common
• Often the largest “duct leak” in the system
• Fixing requires entry into every apartment
56
![Page 62: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/62.jpg)
• Balancing damper at every register • Excellent sealing required (can be significant) • Very labor-intensive; tenant education required
Retrofit Process – CAR Insert Install
![Page 63: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/63.jpg)
Retrofit Process – Cleaning Ducts
Cleaning tips using compressed air
Vacuum to ensure dust removal
![Page 64: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/64.jpg)
Retrofit Process – Sealing Ducts
Rotating spray head applies mastic directly to leaks identified by camera
-Simple concept -Very effective on
straight shafts
![Page 65: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/65.jpg)
Sealing Results – Spray Mastic
0
10
20
30
40
50
60
Registers Installed
Cleaned Sealed
CFM
50 L
eaka
ge
Shaft 1
0 20 40 60 80
100 120 140
Registers Installed
Cleaned Sealed
CFM
50 L
eaka
ge
Shaft 2
Cleaning made leakier (by avg. 10 CFM50)
Sealing made tighter (by avg. 17 CFM50)
![Page 66: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/66.jpg)
Retrofit Results – Spray Mastic
0
200
400
600
800
1000
1200
1400
1600
9B 9K 18B 18K
CFM
50 L
eaka
ge
Pre-and Post-Retrofit Duct Leakage
Initial
Sealed
Recommended Maximum Leakage
10 CFM50/ register
84% Reduction
66% Reduction
60% Reduction
63% Reduction
![Page 67: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/67.jpg)
Retrofit Process – Sealing Ducts
Aeroseal® aerosol duct sealant sticks to holes in ductwork and seals
them
AEROSEAL FAN
Sealant Injector Fan unhinged
for Access to Shaft
Laptop for Automated Control & Diagnostics
• Measures leakage as part of process • Can work in more complicated shafts
• Achieves very tight shafts
![Page 68: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/68.jpg)
Roof Fan Replacement After Duct Fix 25 Fans on Rooftop Avg. Existing Fan Power = 300 W per fan (measured) New Fan Power = 140 W per fan (measured) Annual Electric Savings => $280
per fan ($7,000 for 25 fans) Installed cost = $500 per fan (with building staff installing)
![Page 69: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/69.jpg)
Takeaways – Retrofits
• Several sealing technologies exist – Spray mastic, Aeroseal
• Largest improvements can come from gaps at register connections
• Apartment access is critical obstacle in occupied buildings
• Possibility that building is over-ventilated; opportunity for energy savings
![Page 70: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/70.jpg)
Putting the Pieces Together
• In-unit exhausts • CAR dampers to
balance flow between rooms
• Excellent apartment air sealing (2.5 ACH50)
• Appropriate corridor supply Result = 30+ % savings
over ASHRAE 90.1-2004
![Page 71: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/71.jpg)
Airflow patterns in a tight unit with trickle vents
![Page 72: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/72.jpg)
Airflow patterns in a tight unit with trickle vents
![Page 73: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/73.jpg)
Airflow patterns in a tight unit with trickle vents
![Page 74: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/74.jpg)
Airflow patterns in a tight unit with trickle vents
![Page 75: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/75.jpg)
Airflow patterns in a tight unit with trickle vents
70
More airflow from trickle vents, but still not a lot
Taping apartment-corridor doors
![Page 76: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/76.jpg)
Field Assessment – Balance • Tools
– Static pressure box – Balometer – Vane anemometer – Orifice flow box
• What this tells you: – Balance – Performance at registers
• What it doesn’t tell: – Total system flow (duct
leakage?)
71
![Page 77: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/77.jpg)
Field Assessment – Total Flow
• Velocity traverse on straight sections of duct – Hot wire anemometer
or pitot tube • Duct blaster on roof curb
(up to ~700 CFM) – Measure SP with roof
fan on – Replace w/ duct blaster – Match SP; record flow
![Page 78: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/78.jpg)
Summary
• Step 1: Understand ventilation requirements
• Step 2: Select the simplest design that can achieve both air quality and energy objectives
• Step 3: Build a tight building
• Step 4: Pay attention to installation quality
• Step 5: Check to make sure ventilation works
• Step 6: Educate users
![Page 79: Ventilation in Multifamily Buildings - Energyapps1.eere.energy.gov/buildings/publications/pdfs/building_america/... · Ventilation in Multifamily Buildings . ... 10 story building](https://reader038.fdocuments.us/reader038/viewer/2022103107/5a78ac0a7f8b9ae91b8dc234/html5/thumbnails/79.jpg)
1 | Building America Program www.buildingamerica.gov
Buildings Technologies Program
Thank you for attending the webinar If you have any comments or ideas for future Webinars, please email
Visit www.buildingamerica.gov/meetings.html to download today’s presentation and to register for announcements of upcoming
webinars.