DRAWING LIST:
PROJECT CODE: 501-A5501-015
FOR CONSTRUCTION
HVAC REPLACEMENT
STAUNTON, VIRGINIA
VIRGINIA A&E, PLLC
1115 VISTA PARK DRIVE
FOREST, VA 24551
PHONE: (434) 316-6001
VAE PROJECT NO: 13122
PHIL V. MAYS
Lic. No. 014412 Lic. No. 035249
STEVEN M. HOVIS
Lic. No. 034338
Drawing No.:
Job No.:
T1
13122
Lic. No. 015253
DRAWING NO TITLE
T1 TITLE SHEET
D1 DEMOLITION PLAN - BASEMENT REFLECTED CEILING
D2 DEMOLITION PLAN - FIRST FLOOR REFLECTED CEILING
D3 DEMOLITION PLAN - SECOND FLOOR REFLECTED CEILING
D4 DEMOLITION PLAN - BASEMENT HVAC AND ELECTRICAL
D5 DEMOLITION PLAN - BASEMENT PIPING
D6 DEMOLITION PLAN - FIRST FLOOR HVAC AND ELECTRICAL
D7 DEMOLITION PLAN - FIRST FLOOR PIPING
D8 DEMOLITION PLAN - SECOND FLOOR HVAC AND ELECTRICAL
D9 DEMOLITION PLAN - SECOND FLOOR PIPING
D10 DEMOLITION PLAN - ROOF HVAC AND ELECTRICAL
D11 DEMOLITION PLAN - ENLARGED MECHANICAL ROOMS
D12 DEMOLITION PLAN - BASEMENT
D13 DEMOLITION PLAN - FIRST FLOOR
D14 DEMOLITION PLAN - SECOND FLOOR
A1 LEGEND AND SECTIONS
A2 REFLECTED CEILING PLAN - BASEMENT
A3 REFLECTED CEILING PLAN - FIRST FLOOR
A4 REFLECTED CEILING PLAN - SECOND FLOOR
A5 FLOOR PLAN - BASEMENT
A6 FLOOR PLAN - FIRST FLOOR
A7 FLOOR PLAN - SECOND FLOOR
A8 ENLARGED PLANS AND DETAILS
A9 ENLARGED PLANS
A10 ENLARGED PLANS
S1 ROOF PLAN, DETAILS, AND NOTES
FP1 FIRE PROTECTION PLAN - BASEMENT
FP2 FIRE PROTECTION PLAN - FIRST FLOOR
FP3 FIRE PROTECTION PLAN - SECOND FLOOR
M1 LEGEND AND SPECIFICATIONS
M2 HVAC PLAN - BASEMENT
M3 PIPING PLAN - BASEMENT
M4 HVAC PLAN - FIRST FLOOR
M5 PIPING PLAN - FIRST FLOOR
M6 HVAC PLAN - SECOND FLOOR
M7 PIPING PLAN - SECOND FLOOR
M8 HVAC PLAN - ROOF
M9 HVAC PLAN - ENLARGED MECHANICAL ROOMS
M10 HVAC SCHEDULES
M11 HVAC CONTROLS
M12 VRF INSTALLATION DETAILS
M13 VRF PIPING SCHEMATICS
P1 LEGEND AND SPECIFICATIONS
P2 BASEMENT PLUMBING PLAN
P3 FIRST FLOOR PLUMBING PLAN
P4 SECOND FLOOR PLUMBING PLAN
E1 LEGEND AND SPECIFICATIONS
E2 LIGHTING PLAN - BASEMENT
E3 LIGHTING PLAN - FIRST FLOOR
E4 LIGHTING PLAN - SECOND FLOOR
E5 POWER PLAN - BASEMENT
E6 POWER PLAN - FIRST FLOOR
E7 POWER PLAN - SECOND FLOOR
E8 POWER PLAN - ROOF
E9 POWER RISER DIAGRAM
E10 SCHEDULES
E11 DETAILS AND SCHEDULES
E12 SCHEDULES
E13 SCHEDULES
E14 SCHEDULES
E15 SCHEDULES
VDOTSTAUNTON DISTRICT OFFICE BUILDING
VICINITY MAP
S
IT
E
NORTH
PROJECT LOCATION MAP
BUILDING LOCATION
NORTH
I
8
1
I 64
U
S
2
9
S
R
1
1
N
C
O
A
L
T
E
R
S
T
T
A
Y
L
O
R
S
T
E
B
E
V
E
R
L
E
Y
S
T
GENERAL INFORMATION:
PROJECT INFORMATION:
AGENCY: VIRGINIA DEPARTMENT OF TRANSPORTATION
PROJECT TITLE: STAUNTON OFFICE BUILDING HVAC REPLACEMENT
PROJECT CODE: 501-18038-001
ADDRESS: 811 COMMERCE ROAD, STAUNTON, VIRGINIA 24402-2249
BUILDING INFORMATION:
BUILDING NAME/NUMBER: ADMINISTRATION - BUILDING #8000003
WORK PERMITTED: REPLACEMENT OF HVAC, INTERIOR LIGHTING, AND CEILING SYSTEMS
PURPOSE/OCCUPANCY: OFFICE OCCUPANCY
USE GROUP CLASSIFICATION: (B) BUSINESS AND (A3) ASSEMBLY
TYPE OF CONSTRUCTION: IIB
BUILDING HEIGHT (FEET): 36'-6"± ABOVE GRADENUMBER OF STORIES: 3
GROSS AREA (GSF): 24,980 GROSS SQUARE FEET
BUILDING VOLUME: 291,760 CUBIC FEET
CODE MODIFICATIONS ISSUED: N/A
APPLICABLE CODES & STANDARDS:
BUILDING CODES: 2009 VIRGINIA UNIFORM STATEWIDE BUILDING CODE - VUSBC (EFFECTIVE MARCH 1, 2011)
VIRGINIA MECHANICAL CODE - VMC (2009)
VIRGINIA PLUMBING CODE - VPC (2009)
VIRGINIA REHABILITATION CODE - VRC (2009)
VIRGINIA FUEL GAS CODE - VFGC (2009)
VIRGINIA ENERGY CONSERVATION CODE - VECC (2009)
VIRGINIA BUILDING AND FIRE CODE RELATED REGULATIONS - VBFCRR (2009)
NATIONAL ELECTRICAL CODE - NFPA-70 (2008)
OTHER STANDARDS: CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL - CPSM 2013 EDITION, REVISION 0
(OCT 15, 2013)
AN INSPECTION TO IDENTIFY ASBESTOS-CONTAINING MATERIALS HAS BEEN CONDUCTED AND CAN BE FOUND AS PART OF APPENDIX A TO
THE ASBESTOS PROJECT SPECIFICATIONS. ALL ASBESTOS-CONTAINING MATERIALS LISTED IN PART 1, SECTION 1.A. OF THE VDOT
SPECIFICATIONS FOR ASBESTOS REMOVAL IN OCCUPIED BUILDINGS ARE TO BE REMOVED BY A VIRGINIA LICENSED ASBESTOS ABATEMENT
CONTRACTOR USING VIRGINIA LICENSED ASBESTOS ABATEMENT WORKERS PRIOR TO ANY OTHER WORK BEING CONDUCTED IN THESE
AREAS. SHOULD THE CONTRACTOR ACCESS ANY MATERIAL SUSPECTED OF CONTAINING ASBESTOS NOT IDENTIFIED IN THESE REPORTS,
HE SHALL STOP WORK IN THE IMMEDIATE AREA AND NOTIFY THE OWNER.
THE REMOVAL OF ASBESTOS MATERIALS IS NOT TO BE CONDUCTED WITHOUT THE OWNERS ASBESTOS PROJECT MONITOR BEING ON-SITE.
ASBESTOS DISCLOSURE STATEMENT:
LEAD PAINT DISCLOSURE STATEMENT:
AN INSPECTION TO IDENTIFY LEAD COATED BUILDING COMPONENTS HAS BEEN CONDUCTED AND CAN BE FOUND AS PART OF APPENDIX A
TO THE ASBESTOS PROJECT SPECIFICATIONS. THIS REPORT IS PROVIDED FOR THE CONTRACTOR'S USE AND MAY NOT BE ALL INCLUSIVE.
IT IS THE CONTRACTOR'S RESPONSIBILITY TO COMPLY WITH ALL VIRGINIA OCCUPATIONAL SAFETY AND HEALTH (VOSH) REGULATIONS AS
THEY PERTAIN TO EMPLOYEE EXPOSURES TO LEAD.
ALL LEAD AND LEAD COATED BUILDING COMPONENTS ARE TO BE RECYCLED WHENEVER POSSIBLE.
GENERAL NOTES:
1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND ARE NOT INTENDED
FOR USE AS FABRICATION DRAWINGS. THESE DRAWINGS INDICATE THE
GENERAL AND APPROXIMATE SIZE AND LOCATION OF MATERIAL. FIELD
VERIFY ALL DIMENSIONS AND LOCATIONS PRIOR TO BEGINNING WORK.
ALL UTILITIES NOTED ON PLANS ARE APPROXIMATE AND CONTRACTOR
SHALL FIELD VERIFY LOCATION.
2. ALL WORK SHALL BE INSTALLED IN ACCORDANCE WITH APPLICABLE
CODES AND REGULATIONS, INCLUDING, BUT NOT LIMITED TO, THE 2009
VIRGINIA UNIFORM STATEWIDE BUILDING CODE (MARCH 1, 2011) AND
ASSOCIATED CODES OF REFERENCE. REFER TO APPLICABLE CODES LIST
THIS DRAWING.
3. ALL MATERIAL SHALL BE NEW UNLESS OTHERWISE NOTED. MATERIALS
ARE BASED ON THE INDICATED MANUFACTURERS/MODELS AND ARE
INTENDED ONLY TO SHOW THE GENERAL SIZE, CONFIGURATION,
LOCATION, CONNECTIONS, AND SUPPORT FOR INDICATED MATERIAL WITH
RELATION TO OTHER BUILDING SYSTEMS. MATERIAL BY ANY
MANUFACTURER THAT MEETS THE SCHEDULED CRITERIA IS ACCEPTABLE.
CONTRACTOR SHALL BE RESPONSIBLE FOR COORDINATING ACTUAL
INSTALLED MATERIAL AND ASSOCIATED CHANGES.
4. CONTRACTOR SHALL COORDINATE THE WORK WITH EXISTING
CONDITIONS, INCLUDING BEAMS, COLUMNS, SITE FEATURES, AND OTHER
OBSTRUCTIONS, WHETHER OR NOT SUCH IS SHOWN ON DRAWINGS.
5. CONTRACTOR SHALL COORDINATE THE WORK BETWEEN ALL TRADES.
MATERIAL LOCATIONS SHALL BE COORDINATED BETWEEN
ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND DEMOLITION PLANS TO
AVOID CONFLICTS.
6. EXISTING MATERIAL TO BE REMOVED SHALL BE REMOVED CAREFULLY TO
AVOID DAMAGING MATERIAL TO REMAIN. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR DAMAGE THAT OCCURS TO EXISTING MATERIAL TO
REMAIN OR TO BE RELOCATED DURING DEMOLITION AND CONSTRUCTION.
7. CONTRACTOR SHALL ADVISE THE A/E IMMEDIATELY OF DISCREPANCIES
FOUND ON THE DRAWINGS, IN THE SPECIFICATIONS, OR BETWEEN THE
TWO. MINOR DEVIATIONS FROM THE PLANS MAY BE MADE TO AVOID
MINOR CONFLICTS. WHERE MAJOR CONFLICTS ARE ENCOUNTERED, THE
AFFECTED WORK SHALL NOT BE INSTALLED UNTIL THE CONFLICT HAS
BEEN RESOLVED. NEITHER THE A/E NOR THE OWNER SHALL BE
RESPONSIBLE FOR CONSEQUENCES OF PROCEEDING WITH WORK BASED
ON CONTRACTOR INTERPRETATION OR ON DIRECTION FROM OTHER
PARTIES, INCLUDING OWNER'S STAFF AND INSPECTORS.
8. ALL MATERIAL SHALL BE INSTALLED ACCORDING TO MANUFACTURER'S
WRITTEN INSTALLATION INSTRUCTIONS, MAINTAINING ALL REQUIRED
CLEARANCES AND WITH ALL COMPONENTS ACCESSIBLE AND
SERVICEABLE.
9. CONTRACTOR SHALL PROVIDE MATERIAL DATA SUBMITTALS FOR ALL NEW
MATERIAL. REFER TO INDIVIDUAL SHEETS AND SPECIFICATIONS FOR
ADDITIONAL SUBMITTAL REQUIREMENTS.
10. CONTRACTOR SHALL PROVIDE PRE-DEMOLITION PHOTOGRAPHIC OR
VIDEOGRAPHIC DOCUMENTATION TO SHOW EXISTING CONDITIONS OF
FINISHED SURFACES IN WORK AREA AND ADJOINING CONSTRUCTION
INCLUDING SITE STORAGE AND ACCESS AREAS PRIOR TO
PRE-CONSTRUCTION MEETING AND A MINIMUM OF 10 WORKING DAYS
PRIOR TO COMMENCEMENT OF WORK.
11. CONTRACTOR SHALL NOTIFY OWNER OF ANY INTERRUPTION OF UTILITIES
INCLUDING BUT NOT LIMITED TO POWER, WATER, COMMUNICATIONS, ETC
AND COORDINATE OUTAGE WITH OWNER.
12. DEFINITIONS:
FURNISH: SUPPLY AND DELIVER TO PROJECT SITE FOR INSTALLATION BY
OTHERS.
INSTALL: INSTALL ITEMS FURNISHED BY OTHERS, INCLUDING UNLOADING,
TEMPORARILY STORING, UNPACKING, AND ASSEMBLY.
PROVIDE: FURNISH AND INSTALL, COMPLETE AND READY FOR THE
INTENDED USE.
REMOVE: DETACH ITEMS FROM EXISTING CONSTRUCTION AND LEGALLY
DISPOSE OF THEM OFF-SITE UNLESS INDICATED TO BE REMOVED AND
SALVAGED OR REMOVED AND REINSTALLED.
REMOVE AND REINSTALL: DETACH ITEMS FROM EXISTING CONSTRUCTION,
PREPARE FOR REUSE, AND REINSTALL WHERE INDICATED.
REMOVE AND SALVAGE: CAREFULLY DETACH FROM EXISTING
CONSTRUCTION, IN A MANNER TO PREVENT DAMAGE, AND DELIVER TO
OWNER.
DISCLAIMER STATEMENT:
VIRGINIA A&E, PLLC ASSUMES NO RESPONSIBILITY FOR THE ADEQUACY OR ACCURACY OF THE ASBESTOS AND LEAD INSPECTION REPORTS
OR THE SPECIFICATIONS FOR ASBESTOS REMOVAL IN OCCUPIED BUILDINGS CONTAINED IN THE CONTRACT DOCUMENTS AS THIS
INFORMATION WAS PREPARED BY VDOT. THE CONTRACTOR SHALL ADDRESS ANY RELATED QUESTIONS TO THE VDOT REPRESENTATIVE.
APRIL 20, 2015
FIRE SUPPRESSION SYSTEM:
WET
DRY
CHEMICAL
OTHER
NONE
NOT REQUIRED
FIRE ALARM SYSTEM:
AUTOMATIC
MANUAL
NONE
NOT REQUIRED
ROOF STATEMENT:
EXISTING ROOF IS CARLISLE FULLY ADHERED 60 MIL EPDM SINGLE PLY MEMBRANE INSTALLED OVER A POLYISOCYANURATE INSULATION SYSTEM, REPLACED IN 2009
BY DON LARGENT ROOFING, INC. WITH A 20-YEAR WARRANTY. ROOF DECK VARIES BY BUILDING SECTION AND INCLUDES PLYWOOD, METAL, LIGHTWEIGHT CONCRETE,
AND STRUCTURAL CONCRETE. RECORD DRAWINGS FOR THE 2009 ROOF REPLACEMENT ARE AVAILABLE FOR THE CONTRACTOR'S INFORMATION. WORK ON ROOF,
INCLUDING ROOF PENETRATIONS, SHALL NOT NEGATE ANY EXISTING ROOF WARRANTY. CONTRACTOR'S ROOF SUBCONTRACTOR SHALL BE CERTIFIED TO CUT,
PATCH, AND REPAIR EXISTING ROOF TO MAINTAIN WARRANTY IN EFFECT.
PROJECT PHASING STATEMENT:
BUILDING WILL REMAIN OCCUPIED DURING CONSTRUCTION. WORK IN OCCUPIED AREAS SHALL BE PHASED TO TAKE PLACE APPROXIMATELY ONE QUARTER OF A
FLOOR AT A TIME. REFER TO SPECIFICATION SECTION 003115 FOR DETAILED PHASING INFORMATION AND REQUIREMENTS.
04/20/15 04/20/1504/20/15 04/20/15
ADDITIVE BID ITEM 1:
REMOVAL AND DISPOSAL OF ASBESTOS-CONTAINING MATERIAL AND/OR CONTAMINATED MATERIAL, COMPLETE, AND IN ACCORDANCE WITH
THE DRAWINGS AND SPECIFICATIONS. VDOT ADMINISTRATIVE SERVICES DIVISION MUST APPROVE PRE-ABATEMENT ASBESTOS SUBMITTALS
BEFORE THE CONTRACT WILL BE AWARDED.
ADDITIVE
BID ITEM 1
ADDITIVE
BID ITEM 1
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - BASEMENT REFLECTED CEILNG
116
15
14
13
17
18
19
12A
12B
11
10
SERVER ROOM
10
IT ROOM
32
AUDITORIUM
2221
20
RESTROOM
25
RESTROOM
5
MECHANICAL ROOM
26
LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
1
2
ORIGINALADDITION
6
4
5
3
STORAGE
24
CLOSET
CLOSET
STORAGE
KITCHEN
7B
ELEVATOR
VESTIBULE
7A
CLOSET
23
HALL
HALL
HALL
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
GENERAL NOTES:
1. REFER TO ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR
ADDITIONAL DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING:
A. ANY EXISTING CONSTRUCTION THAT IS TO BE REMOVED SHALL BE
REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY EXISTING
CONSTRUCTION THAT IS TO REMAIN. FLOORS, WALLS, AND CEILINGS ARE
TO BE PATCHED (IN A RECTANGULAR PATTERN) TO MATCH EXISTING
CONDITIONS AND MADE READY TO RECEIVE ANY NEW FINISHES WHERE
APPLICABLE.
3. ALL EXISTING FIREPROOFING REMOVED DURING DEMOLITION SHALL BE
PATCHED TO MATCH EXISTING.
4. REMOVE SUSPENDED ACOUSTICAL TILE CEILING AND GRID SYSTEM
COMPLETELY.
5. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
DEMOLITION NOTES:
XX
1. REMOVE LUMINAIRES AS SHOWN. RETAIN WIRE AND CONDUIT FOR RE-USE,
TYPICAL. REMOVED LUMINAIRES SHALL BE TURNED OVER TO VDOT AND STORED
ON SITE WHERE INDICATED.
2. REMOVE WALL SWITCH. RETAIN WIRING AND BACK BOX FOR RE-USE. ANY
SWITCHES NOT INDICATED TO BE REMOVED WILL BE REUSED AS-IS. TYPICAL.
3. SMOKE DETECTOR TO REMAIN. PROTECT DETECTOR DURING CONSTRUCTION BY
SUSPENDING ABOVE CEILING DURING CEILING REMOVAL. TYPICAL.
4. SPEAKER TO REMAIN. PROTECT SPEAKER DURING CONSTRUCTION BY
SUSPENDING ABOVE CEILING DURING CEILING REMOVAL. TYPICAL.
5. REMOVE ALL EXIT SIGNS. RETAIN WIRING FOR RE-USE. TYPICAL OF ALL SIGNS TO
BE REMOVED WITHIN BUILDING. NOT ALL EXIT SIGNS ARE SHOWN HERE.PROVIDE
BLANK COVER PLATES OVER WALL BOXES. REPLACEMENT EXIT SIGNS WILL BE
CEILING MOUNTED. TOTAL NUMBER OF EXIT SIGNS IS LESS THAN 20 OVERALL.
6. REMOVE LIGHT FIXTURES AND EXIT SIGNS ONLY IN AUDITORIUM. CEILING, SMOKE
DETECTORS, AND SPEAKERS TO REMAIN UNDISTURBED.
DEMOLITION SYMBOLS LEGEND:
XX DEMOLITION NOTE
LIMIT OF DEMOLITION
DE
MO
LIT
IO
N P
LA
N
BA
SE
ME
NT
R
EF
LE
CT
ED
C
EIL
IN
G
D1
Lic. No. 034338
04/20/15
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - FIRST FLOOR REFLECTED CEILING
127126
125
123
124
129
130
131C131B131D
HALL
STAIRS
100
102 117
116
101
RESTROOM
103
VESTIBULE
119
HALL
114
113
112
106
107
105
108
STAIRS
2
1
ORIGINALADDITION
4
3
5
LOBBY
115
CLOSET
CLOS
CLOS
CLOS
HALL
CLOSET
HALL
CONFERENCE
110
RESTROOM
104
ELEVATOR
HALL
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
DE
MO
LIT
IO
N P
LA
N
FIR
ST
F
LO
OR
R
EF
LE
CT
ED
C
EIL
IN
G
D2
GENERAL NOTES:
1. REFER TO ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR
ADDITIONAL DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING:
A. ANY EXISTING CONSTRUCTION THAT IS TO BE REMOVED SHALL BE
REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY EXISTING
CONSTRUCTION THAT IS TO REMAIN. FLOORS, WALLS, AND CEILINGS ARE
TO BE PATCHED (IN A RECTANGULAR PATTERN) TO MATCH EXISTING
CONDITIONS AND MADE READY TO RECEIVE ANY NEW FINISHES WHERE
APPLICABLE.
3. ALL EXISTING FIREPROOFING REMOVED DURING DEMOLITION SHALL BE
PATCHED TO MATCH EXISTING.
4. REMOVE SUSPENDED ACOUSTICAL TILE CEILING AND GRID SYSTEM
COMPLETELY.
5. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
DEMOLITION SYMBOLS LEGEND:
XX DEMOLITION NOTE
LIMIT OF DEMOLITION
DEMOLITION NOTES:
XX
1. REMOVE LUMINAIRES AS SHOWN. RETAIN WIRE AND CONDUIT FOR RE-USE,
TYPICAL. REMOVED LUMINAIRES SHALL BE TURNED OVER TO VDOT AND STORED
ON SITE WHERE INDICATED.
2. REMOVE WALL SWITCH. RETAIN WIRING AND BACK BOX FOR RE-USE. ANY
SWITCHES NOT INDICATED TO BE REMOVED WILL BE REUSED AS-IS. TYPICAL
3. SMOKE DETECTOR TO REMAIN. PROTECT DETECTOR DURING CONSTRUCTION BY
SUSPENDING ABOVE CEILING DURING CEILING REMOVAL. TYPICAL.
4. SPEAKER TO REMAIN. PROTECT SPEAKER DURING CONSTRUCTION BY
SUSPENDING ABOVE CEILING DURING CEILING REMOVAL. TYPICAL.
5. REMOVE ALL EXIT SIGNS. RETAIN WIRING FOR RE-USE. TYPICAL OF ALL SIGNS TO
BE REMOVED WITHIN BUILDING. NOT ALL EXIT SIGNS ARE SHOWN HERE.PROVIDE
BLANK COVER PLATES OVER WALL BOXES. REPLACEMENT EXIT SIGNS WILL BE
CEILING MOUNTED. TOTAL NUMBER OF EXIT SIGNS TO BE REMOVED IS LESS
THAN 20 OVERALL.
Lic. No. 034338
04/20/15
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - SECOND FLOOR REFLECTED CEILING
214
215
216
STAIRS
201
200
213
212
211
209
208
207
206
RESTROOM
203
RESTROOM
205
HALL
STAIRS
6
5
4
3
2 1
HALL
HALL
CLOS
CLOS
ELEVATOR
CLOSET
POWER POLE
POWER POLE
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
DE
MO
LIT
IO
N P
LA
N
SE
CO
ND
F
LO
OR
R
EF
LE
CT
ED
C
EIL
IN
G
D3
GENERAL NOTES:
1. REFER TO ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR
ADDITIONAL DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING:
A. ANY EXISTING CONSTRUCTION THAT IS TO BE REMOVED SHALL BE
REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY EXISTING
CONSTRUCTION THAT IS TO REMAIN. FLOORS, WALLS, AND CEILINGS ARE
TO BE PATCHED (IN A RECTANGULAR PATTERN) TO MATCH EXISTING
CONDITIONS AND MADE READY TO RECEIVE ANY NEW FINISHES WHERE
APPLICABLE.
3. ALL EXISTING FIREPROOFING REMOVED DURING DEMOLITION SHALL BE
PATCHED TO MATCH EXISTING.
4. REMOVE SUSPENDED ACOUSTICAL TILE CEILING AND GRID SYSTEM
COMPLETELY.
5. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
DEMOLITION SYMBOLS LEGEND:
XX DEMOLITION NOTE
LIMIT OF DEMOLITION
DEMOLITION NOTES:
XX
1. REMOVE LUMINAIRES AS SHOWN. RETAIN WIRE AND CONDUIT FOR RE-USE,
TYPICAL. REMOVED LUMINAIRES SHALL BE TURNED OVER TO VDOT AND STORED
ON SITE WHERE INDICATED.
2. REMOVE WALL SWITCH. RETAIN WIRING AND BACK BOX FOR RE-USE. ANY
SWITCHES NOT INDICATED TO BE REMOVED WILL BE REUSED AS-IS. TYPICAL.
3. SMOKE DETECTOR TO REMAIN. PROTECT DETECTOR DURING CONSTRUCTION BY
SUSPENDING ABOVE CEILING DURING CEILING REMOVAL. TYPICAL.
4. SPEAKER TO REMAIN. PROTECT SPEAKER DURING CONSTRUCTION BY
SUSPENDING ABOVE CEILING DURING CEILING REMOVAL. TYPICAL.
5. REMOVE ALL EXIT SIGNS. RETAIN WIRING FOR RE-USE. TYPICAL OF ALL SIGNS TO
BE REMOVED WITHIN BUILDING. NOT ALL EXIT SIGNS ARE SHOWN HERE.PROVIDE
BLANK COVER PLATES OVER WALL BOXES. REPLACEMENT EXIT SIGNS WILL BE
CEILING MOUNTED. TOTAL NUMBER OF EXIT SIGNS IS LESS THAN 20 OVERALL.
6. REMOVE ALL LIGHT SWITCHES IN THIS ROOM.
Lic. No. 034338
04/20/15
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - BASEMENT HVAC AND ELECTRICAL
A, B
C
CHILLER
BOILER
AHU
1 1 1 1 1
1
1
UP TO
ROOF
12
8
x18 10 x14 6
7
6
8
6
4
5
1 1
3
2
3
222
5
1
2 2
5
1
12
9
x14 12
9
9 9
10
10
85
12
6
3
Ø14 UP
x12 18
UP
1
CP
12
11
13
10
5
10
UP TO GOOSENECK
1
1
5
1
16
15
1413
17
18
19
12A
12B
11
10
SERVER ROOM
10
IT ROOM
3
2
AUDITORIUM
22
21
20
RESTROOM
25
RESTROOM
5
MECHANICAL ROOM
26
LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
STORAGE
24
CLOSET
CLOSET
STORAGE
KITCHEN
7B
HALL
ELEVATOR
7A
CLOS
CLOS
14
15
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
DEMOLITION NOTES:
XX
1. REMOVE FAN COIL UNIT AND ANY ASSOCIATED PIPING, DUCTWORK (NOT SHOWN),
THERMOSTAT, AND AIR DEVICES. PATCH FLOOR AND WALL TO MATCH ADJACENT
WHERE VERTICAL FAN COILS ARE REMOVED. RETAIN FRESH AIR GRILLE WHERE
APPLICABLE, SEAL WEATHER-TIGHT WITH SHEET METAL AND CAULK, AND PATCH
INTERIOR WALL TO MATCH ADJACENT PER SECTION 1 ON DRAWING A1. REMOVE
ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP AND LABEL ANY
REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE, IF APPLICABLE.
2. REMOVE PTAC. FRESH AIR GRILLE TO REMAIN. SEAL WEATHER-TIGHT WITH
SHEET METAL AND CAULK. PATCH FLOOR AND INTERIOR WALL PER SECTION 1 ON
DRAWING A1. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP
AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE, IF
APPLICABLE.
3. REMOVE FAN AND CAP DUCT. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK
TO SOURCE. CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER
AS SPARE, IF APPLICABLE.
4. REMOVE HEATER. PATCH WALL AND FLOOR TO MATCH ADJACENT. REMOVE ALL
WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP AND LABEL ANY REMAINING
UNUSED CONDUIT. MARK BREAKER AS SPARE, IF APPLICABLE.
5. REMOVE DUCTLESS MINI-SPLIT (INDOOR UNIT ON SECOND FLOOR DRAWING D8).
PATCH AND SEAL WALL AND PENETRATION TO MATCH ADJACENT. REMOVE ALL
WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP AND LABEL ANY REMAINING
UNUSED CONDUIT. MARK BREAKER AS SPARE, IF APPLICABLE.
6. REMOVE CHILLER AND PIPING. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK
TO SOURCE. CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER
AS SPARE, IF APPLICABLE.
7. REMOVE CONDENSING UNIT, AIR HANDLING UNIT, AND PIPING. REMOVE ALL WIRE
AND EXPOSED CONDUIT BACK TO SOURCE. CAP AND LABEL ANY REMAINING
UNUSED CONDUIT. MARK BREAKER AS SPARE, IF APPLICABLE.
8. REMOVE BOILER AND CONDENSATE RECEIVER AND ASSOCIATED PIPING.
REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP AND LABEL
ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE, IF APPLICABLE.
9. REMOVE VAV BOX AND ASSOCIATED PIPING, DUCTWORK, THERMOSTAT, AND AIR
DEVICES. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP AND
LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE, IF
APPLICABLE.
10. REMOVE SPLIT SYSTEM HEAT PUMP AND ASSOCIATED THERMOSTAT,
REFRIGERANT PIPING, AUXILIARY DRAIN PAN, AND CONDENSATE DRAIN PIPING.
REMOVE DUCTWORK (NOT SHOWN) AND AIR DEVICES WHICH SERVE THE IT ROOM
AND ROOMS 10, 11, 12A, 12B. PATCH AND SEAL WALL PENETRATIONS TO MATCH
ADJACENT. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP
AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE, IF
APPLICABLE.
11. REMOVE TRANSFER GRILLES AND PATCH WALL TO MATCH ADJACENT.
12. REMOVE GAS LINE TO DISCHARGE SIDE OF VALVE.
13. REMOVE GRILLE. PATCH WALL TO MATCH ADJACENT.
14. DEMO 60 AMP, (3)CIRCUIT LOAD CENTER ADJACENT TO PANEL 1.
15. REMOVE CEILING GRILLE. DUCT TO REMAIN. REMOVE THE (4) TILES AND GRID
WHICH TOUCH THE GRILLE.
DE
MO
LIT
IO
N P
LA
N
BA
SE
ME
NT
H
VA
C A
ND
E
LE
CT
RIC
AL
D4
Lic. No. 034338
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
2. WHERE PIPING TO BE REMOVED IS CONCEALED WITHIN A METAL CHASE
CONSTRUCTED WITHIN OCCUPIED SPACE, CONTRACTOR SHALL REMOVE CHASE
AND PAINT SURFACES TO MATCH ADJACENT.
04/20/15
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - BASEMENT PIPING
1"D
3/4"CS/R
1 1/2"CS/R&D
1 1/2"HWS/R
2 1/2"DTS
2 1/2"DTR
CONDENSATE DRAIN
BELOW SLAB, TYP
3"DTS/R
2 1/2"DTS/R UP
1 1/4"HWS/R
UP
2
2
2
2
1
4 TYP
567
116
15
14
13
171819
12A
12B
11
10
SERVER ROOM
10
IT ROOM
32
AUDITORIUM
22
21
20
RESTROOM
25
RESTROOM
5
MECHANICAL ROOM
26
LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
STORAGE
24
CLOSET
CLOSET
STORAGE
KITCHEN
7B
ELEVATOR
7A
CLOS
CLOS
3
3
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
DEMOLITION NOTES:
XX
1. REMOVE CONDENSATE PUMP. REMOVE ALL WIRE AND EXPOSED CONDUIT
BACK TO SOURCE. CAP AND LABEL ANY UNUSED CONDUIT. MARK BREAKER AS
SPARE, IF APPLICABLE.
2. ABANDON UNDER-SLAB AND VERTICAL CONDENSATE DRAIN PIPING IN PLACE.
3. CAP 3" CONDENSATE DRAIN OUTLET. DO NOT CAP ROOF CONDUCTOR OUTLET.
CONTRACTOR SHALL DETERMINE WHICH DRAIN IS WHICH BY POURING WATER
DOWN ROOF DRAINS.
4. REMOVE CONDENSATE DRAIN PIPE TO BELOW FINISHED FLOOR AND PLUG OR
CAP. PATCH FLOOR TO MATCH ADJACENT.
5. CONDENSATE DRAIN PIPE ROUTING IS UNKNOWN. REMOVE TO EXTENT
POSSIBLE AND CAP.
6. PATCH AND SEAL PENETRATION PER UL DETAIL W-J-0001 ON DRAWING FP2.
7. SLEEVED WALL PENETRATION TO REMAIN FOR NEW DRAIN PIPE. REFER TO
DRAWING M3.
8. ALL ROOMS ARE OFFICES UNLESS LABELED OTHERWISE.
DE
MO
LIT
IO
N P
LA
N
BA
SE
ME
NT
P
IP
IN
G
D5
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
2. WHERE PIPING TO BE REMOVED IS CONCEALED WITHIN A METAL CHASE
CONSTRUCTED WITHIN OCCUPIED SPACE, CONTRACTOR SHALL REMOVE CHASE
AND PAINT SURFACES TO MATCH ADJACENT.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - FIRST FLOOR HVAC AND ELECTRICAL
1 1 1 1
1
1 1 1 1 1
2 2 2 2 2 2
22
2
2
1
2
2
1
1
1
x10 6
85
95
86
x6 6
x20 16
UP
66
14
6
x20 12
x18 8
Ø12
14
Ø14
UP
2
3
4
4
5 5
5
4
x12 18
DN
6
7
8
8
8 8
127126
125
123
124
129 130
131C131B131D
STAIRS
100
102 117 116
101
RESTROOM
103
VESTIBULE
119
114
113
112
106
107
105
108
LOBBY
115
CLOSET
CLOS
CLOS
CLOS
CLOSET
CONFERENCE
110
RESTROOM
104
ELEVATOR
131A
STAIRS
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
DEMOLITION NOTES:
XX
1. REMOVE FAN COIL UNIT AND ANY ASSOCIATED PIPING, DUCTWORK,
THERMOSTAT, AND AIR DEVICES. PATCH FLOOR AND WALL TO MATCH
ADJACENT WHERE VERTICAL FAN COILS ARE REMOVED. RETAIN FRESH AIR
GRILLE WHERE APPLICABLE, SEAL WEATHER-TIGHT WITH SHEET METAL AND
CAULK, AND PATCH INTERIOR WALL TO MATCH ADJACENT PER SECTION 1 ON
DRAWING A1. REMOVE ALL WIRE AND CONDUIT BACK TO SOURCE. CAP AND
LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE, IF
APPLICABLE.
2. REMOVE PTAC. FRESH AIR GRILLE TO REMAIN. SEAL WEATHER-TIGHT WITH
SHEET METAL AND CAULK. PATCH FLOOR AND INTERIOR WALL PER SECTION 1
ON DRAWING A1. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE.
CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE,
IF APPLICABLE.
3. REMOVE FAN. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE.
CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE,
IF APPLICABLE.
4. REMOVE HEATER. PATCH WALL AND FLOOR OR CEILING TO MATCH ADJACENT.
REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP AND LABEL
ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE, IF APPLICABLE.
5. REMOVE VAV BOX AND ASSOCIATED PIPING, DUCTWORK, THERMOSTAT, AND
AIR DEVICES. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE.
CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE,
IF APPLICABLE.
6. REMOVE GRILLE. PATCH WALL TO MATCH EXISTING.
7. SEAL OPENING IN DUCT AFTER REMOVING BRANCH.
8. REMOVE ENCLOSURE BENEATH PTAC.
9. ALL ROOMS ARE OFFICES UNLESS LABELED OTHERWISE.
DE
MO
LIT
IO
N P
LA
N
FIR
ST
F
LO
OR
H
VA
C A
ND
E
LE
CT
RIC
AL
D6
Lic. No. 034338
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
2. WHERE PIPING TO BE REMOVED IS CONCEALED WITHIN A METAL CHASE
CONSTRUCTED WITHIN OCCUPIED SPACE, CONTRACTOR SHALL REMOVE CHASE
AND PAINT SURFACES TO MATCH ADJACENT.
04/20/15
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - FIRST FLOOR PIPING
1 1/2"CS/R&D
CONDENSATE DRAIN
BELOW FLOOR, TYP
1 1/4"HWS/R UP
1 1/4"
HWS/R
DN
2 1/2"DTS/R DN
CAPCAP
CAP
CWS/R
127126
125
123
124
129
130
131C
131B
131D
STAIRS
100
102 117 116
101
VESTIBULE
119
114
113
112
106
107
105
108
STAIRS
LOBBY
115
CLOSET
CLOS
CLOS
CLOS
CLOSET
CONFERENCE
110
RESTROOM
104
ELEVATOR
131A
RESTROOM
103
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
DE
MO
LIT
IO
N P
LA
N
FIR
ST
F
LO
OR
P
IP
IN
G
D7
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
2. WHERE PIPING TO BE REMOVED IS CONCEALED WITHIN A METAL CHASE
CONSTRUCTED WITHIN OCCUPIED SPACE, CONTRACTOR SHALL REMOVE CHASE
AND PAINT SURFACES TO MATCH ADJACENT.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - SECOND FLOOR HVAC AND ELECTRICAL
1
1
1
1 1 1
1 1 1
1 1 12
2 2
7
3
2
2
2
2
2 2
4
4
x22 10
x22 10
x8 6
10
8
4
5
5
55
Ø10
Ø14
Ø16
Ø12
16
8
8
1
1
5
9
6
1
6
1
6
1
6
1
10 10
214
215
216
STAIRS
201
200 213
212
211
209
208
207
206
RESTROOM
203
RESTROOM
205
CLOSCLOS
ELEVATOR
CLOSET
STAIRS
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
DEMOLITION NOTES:
XX
1. REMOVE FAN COIL UNIT AND ANY ASSOCIATED PIPING, DUCTWORK,
THERMOSTAT, AND AIR DEVICES. PATCH FLOOR AND WALL TO MATCH
ADJACENT WHERE VERTICAL FAN COILS ARE REMOVED. RETAIN FRESH AIR
GRILLE WHERE APPLICABLE, SEAL WEATHER-TIGHT WITH SHEET METAL AND
CAULK, AND PATCH INTERIOR WALL TO MATCH ADJACENT PER SECTION 1 ON
DRAWING A1. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE.
CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE,
IF APPLICABLE.
2. REMOVE PTAC. FRESH AIR GRILLE TO REMAIN. SEAL WEATHER-TIGHT WITH
SHEET METAL AND CAULK. PATCH FLOOR AND INTERIOR WALL PER SECTION 1
ON DRAWING A1. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE.
CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE,
IF APPLICABLE.
3. REMOVE DUCTLESS MINI-SPLIT (OUTDOOR UNIT ON BASEMENT FLOOR,
DRAWING D4). PATCH AND SEAL WALL AND PENETRATION TO MATCH
ADJACENT. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP
AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE, IF
APPLICABLE.
4. REMOVE HEATER. PATCH WALL AND FLOOR OR CEILING TO MATCH ADJACENT.
REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP AND LABEL
ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE, IF APPLICABLE.
5. REMOVE VAV BOX AND ASSOCIATED PIPING, DUCTWORK, THERMOSTAT, AND
AIR DEVICES. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO SOURCE.
CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS SPARE
IF APPLICABLE.
6. REMOVE CONDENSATE PUMP AND PIPING. REMOVE ALL WIRE AND EXPOSED
CONDUIT BACK TO SOURCE. CAP AND LABEL ANY REMAINING UNUSED
CONDUIT. MARK BREAKER AS SPARE, IF APPLICABLE.
7. REMOVE THROUGH-THE-WALL AIR CONDITIONER. FRESH AIR GRILLE TO
REMAIN. SEAL WEATHER-TIGHT WITH SHEET METAL AND CAULK. PATCH
INTERIOR AND EXTERIOR WALL PER SECTION 1 ON DRAWING A1. REMOVE
RECEPTACLE SERVING AIR CONDITIONER AND SURFACE MOUNTED CONDUIT
AND WIRING BETWEEN RECEPTACLES. RETAIN ONE RECEPTACLE AND PLUG
OPEN HOLE IN OUTLET BOX.
8. REMOVE GRILLE. VERTICAL DUCT TO REMAIN.
9. REMOVE GRILLE. PATCH WALL TO MATCH ADJACENT.
10. REMOVE DUCT UP TO BENEATH ROOF AND CAP.
11. ALL ROOMS ARE OFFICES UNLESS LABELED OTHERWISE.
DE
MO
LIT
IO
N P
LA
N
SE
CO
ND
F
LO
OR
H
VA
C A
ND
E
LE
CT
RIC
AL
D8
Lic. No. 034338
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
2. WHERE PIPING TO BE REMOVED IS CONCEALED WITHIN A METAL CHASE
CONSTRUCTED WITHIN OCCUPIED SPACE, CONTRACTOR SHALL REMOVE CHASE
AND PAINT SURFACES TO MATCH ADJACENT.
04/20/15
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - SECOND FLOOR PIPING
CONDENSATE DRAIN
BELOW FLOOR, TYP
1 1/4"HWS/R
DN
1 1/2"CS/R&D
CAP
CAP
CAP
CWS/R
214
215
216
STAIRS
201
200
213
212
211
209
208
207
206
RESTROOM
203
STAIRS
HALL
HALL
CLOS
CLOS
ELEVATOR
CLOSET
RESTROOM
205
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
DE
MO
LIT
IO
N P
LA
N
SE
CO
ND
F
LO
OR
P
IP
IN
G
D9
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
2. WHERE PIPING TO BE REMOVED IS CONCEALED WITHIN A METAL CHASE
CONSTRUCTED WITHIN OCCUPIED SPACE, CONTRACTOR SHALL REMOVE CHASE
AND PAINT SURFACES TO MATCH ADJACENT.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - ROOF HVAC AND ELECTRICAL
HATCH
CHIMNEY
CHIMNEY
GOOSENECK
1
1
1
1
1
2
Ø16
4
Ø20
3
5
x28 24
FRESH
AIR
INTAKE
TO
REMAIN
DN
6
7
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
DEMOLITION NOTES:
XX
1. REMOVE EXHAUST FAN. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO
SOURCE. CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS
SPARE, IF APPLICABLE.
2. REMOVE CHILLER CONDENSING UNIT AND PIPING. SUPPORT STRUCTURE TO
REMAIN FOR REUSE. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK TO
SOURCE. CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER AS
SPARE, IF APPLICABLE.
3. REMOVE SPLIT SYSTEM AIR HANDLING UNIT, CONDENSING UNIT, DUCTWORK, AND
PIPING. SUPPORT STRUCTURE TO REMAIN. REMOVE ALL WIRE AND EXPOSED
CONDUIT BACK TO SOURCE. CAP AND LABEL ANY REMAINING UNUSED CONDUIT.
MARK BREAKER AS SPARE, IF APPLICABLE.
4. VERTICAL DUCT ABOVE ROOF TO REMAIN. CAP DUCTS AND SEAL
WEATHER-TIGHT USING SCREWS AND CAULK.
5. VERTICAL DUCT RISER AND ELBOW ON ROOF TO REMAIN FOR REUSE.
6. CAP PIPE ABOVE AND BELOW ROOF.
7. REMOVE GOOSENECK AND ASSOCIATED DUCT.
DE
MO
LIT
IO
N P
LA
N
RO
OF
H
VA
C A
ND
E
LE
CT
RIC
AL
D10
Lic. No. 034338
04/20/15
04/20/15
IFB #152724-TW
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED MECHANICAL ROOM 26 - AIRSIDE SYSTEMA
AHU
(E) x12 8
MECHANICAL ROOM
26
ACCU
1
22
22
10
9
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED MECHANICAL ROOM 6C
MECHANICAL
ROOM
6
1
2
SCALE:
6"0 1' 2' 5'
1/2"=1'-0"
SECTION1
AHU
x22 22
16
45
18
32
SUPPORT STRUCTURE
SPRING ISOLATORS
9
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED MECHANICAL ROOM 26 - DUAL TEMPERATURE SYSTEMB
CHILLER
CP
3
AHU
6
BOILER
4
HW
CONV
6
5
MECHANICAL
ROOM
26
8
7
8
11
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
DEMOLITION NOTES:
XX
1. REMOVE ALL CHILLED WATER PIPING. PATCH AND SEAL EXTERIOR WALL
PENETRATIONS FOR PIPING OUT TO CHILLER.
2. REMOVE EXPANSION TANK. REMOVE 1/2" MAKEUP WATER LINE TO ISOLATION
VALVE DOWNSTREAM OF PRESSURE REGULATOR.
3. REMOVE ALL STEAM AND DUAL TEMPERATURE HYDRONIC EQUIPMENT AND
PIPING, INCLUDING CHILLER, BOILER, HOT WATER CONVERTER, CONDENSATE
PUMP, MAIN AND REHEAT HEATING WATER PUMPS, CHILLED WATER PUMP, AND
ASSOCIATED APPURTENANCES. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK
TO SOURCE. CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER
AS SPARE, IF AVAILABLE.
4. REMOVE 14Ø BOILER BREECHING TO WALL AND CAP WITH SHEET METAL.
5. REMOVE NATURAL GAS PIPING TO OUTLET SIDE OF VALVE. REMOVE BOILER PRV
VENT LINE AND PATCH AND SEAL EXTERIOR WALL PENETRATION
WEATHER-TIGHT.
6. REMOVE ALL PNEUMATIC CONTROLS INCLUDING AIR COMPRESSOR. REMOVE ALL
WIRE AND EXPOSED CONDUIT BACK TO SOURCE. CAP AND LABEL ANY REMAINING
UNUSED CONDUIT. MARK BREAKER AS SPARE, IF APPLICABLE.
7. REMOVE FAN THERMOSTAT.
8. CAP PIPE ABOVE AND BELOW ROOF.
9. REMOVE AIR HANDLING UNIT AND SPRING ISOLATORS. CHANNEL SUPPORT
FRAME TO REMAIN FOR REUSE. REMOVE SUPPLY, RETURN, AND OUTSIDE AIR
DUCT TO POINTS INDICATED. REMOVE ALL WIRE AND EXPOSED CONDUIT BACK
TO SOURCE. CAP AND LABEL ANY REMAINING UNUSED CONDUIT. MARK BREAKER
AS SPARE, IF APPLICABLE.
10. REMOVE DX CONDENSING UNIT. PAD TO REMAIN FOR REUSE. REMOVE ALL WIRE
AND EXPOSED CONDUIT. CAP AND LABEL ANY REMAINING UNUSED CONDUIT.
MARK BREAKER AS SPARE, IF APPLICABLE.
11. REMOVE MAKEUP WATER LINE TO POINT INDICATED AND CAP.
DE
MO
LIT
IO
N P
LA
N
EN
LA
RG
ED
M
EC
HA
NIC
AL
R
OO
MS
D11
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - BASEMENT
1
16
15
14
13
17
18
19
12A
12B
11
10
SERVER ROOM
10
IT ROOM
32
AUDITORIUM
22
21
20
RESTROOM
25
RESTROOM
5
MECHANICAL ROOM
26
LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
STORAGE
24
CLOSET
CLOSET
KITCHEN
7B
ELEVATOR
VESTIBULE
7A
CLOSET
23
HALL
HALL
HALL
3
4
4
55555
5
5
33
3
1
1
1
1
1
1
2 2
6
7
7
7
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
DE
MO
LIT
IO
N P
LA
N
BA
SE
ME
NT
D12
GENERAL NOTES:
1. REFER TO ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR
ADDITIONAL DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING:
A. ANY EXISTING CONSTRUCTION THAT IS TO BE REMOVED SHALL BE
REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY EXISTING
CONSTRUCTION THAT IS TO REMAIN. FLOORS, WALLS, AND CEILINGS ARE
TO BE PATCHED (IN A RECTANGULAR PATTERN) TO MATCH EXISTING
CONDITIONS AND MADE READY TO RECEIVE ANY NEW FINISHES WHERE
APPLICABLE.
3. ALL EXISTING FIREPROOFING REMOVED DURING DEMOLITION SHALL BE
PATCHED TO MATCH EXISTING.
4. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
5. REMOVE VCT FLOORING TO CONCRETE IN ALL ROOMS EXCEPT HALLS, STAIRS,
RESTROOMS, AND AUDITORIUM. REFER TO DEMOLITION NOTES FOR
ADDITIONAL INFORMATION. PREPARE SLAB TO RECEIVE NEW FLOORING.
DEMOLITION SYMBOLS LEGEND:
XX DEMOLITION NOTE
LIMIT OF DEMOLITION
DEMOLITION NOTES:
XX
1. REMOVE STUD PARTITION WALL ASSEMBLY.
2. REMOVE METAL PARTITION WALL ASSEMBLY, INCLUDING DOOR AND FRAME.
3. REMOVE DOOR AND HARDWARE.
4. REMOVE RAISED FLOOR ASSEMBLY.
5. REMOVE MECHANICAL CHASE.
6. REMOVE CARPET TO CONCRETE SLAB SUBSTRATE. PREPARE SLAB TO RECEIVE
NEW FLOORING.
7. REMOVE AND REMEDIATE ASBESTOS-CONTAINING TILE FLOORING PER
ASBESTOS SPECIFICATIONS.
04/20/15
ADDITIVE
BID ITEM 1
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - FIRST FLOOR
1
2
3
3
4
44
444
4
4
55
127126
125
123
124
129
130
131C131B131D
HALL
STAIRS
100
102 117116
101
RESTROOM
103
VESTIBULE
119
HALL
114
113
112
106
107
105
108
STAIRS
LOBBY
115
CLOSETCLOS
CLOS
CLOS
HALL
CLOSET
HALL
CONFERENCE
110
RESTROOM
104
ELEVATOR
HALL
6
5 6 5 6
5
5 6
6
7
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
DE
MO
LIT
IO
N P
LA
N
FIR
ST
F
LO
OR
D13
GENERAL NOTES:
1. REFER TO ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR
ADDITIONAL DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING:
A. ANY EXISTING CONSTRUCTION THAT IS TO BE REMOVED SHALL BE
REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY EXISTING
CONSTRUCTION THAT IS TO REMAIN. FLOORS, WALLS, AND CEILINGS ARE
TO BE PATCHED (IN A RECTANGULAR PATTERN) TO MATCH EXISTING
CONDITIONS AND MADE READY TO RECEIVE ANY NEW FINISHES WHERE
APPLICABLE.
3. ALL EXISTING FIREPROOFING REMOVED DURING DEMOLITION SHALL BE
PATCHED TO MATCH EXISTING.
4. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
5. REMOVE VCT FLOORING TO CONCRETE IN ALL ROOMS EXCEPT HALLS, STAIRS,
RESTROOMS, ROOM 107, AND ROOM 108. REFER TO DEMOLITION NOTES FOR
ADDITIONAL INFORMATION. PREPARE SLAB TO RECEIVE NEW FLOORING.
DEMOLITION SYMBOLS LEGEND:
XX DEMOLITION NOTE
LIMIT OF DEMOLITION
DEMOLITION NOTES:
XX
1. REMOVE STUD PARTITION WALL ASSEMBLY.
2. REMOVE METAL PARTITION WALL ASSEMBLY, INCLUDING DOOR, WINDOWS, AND
FRAMES.
3. REMOVE DOOR AND HARDWARE.
4. REMOVE CARPET TO CONCRETE SLAB SUBSTRATE. PREPARE SLAB TO RECEIVE
NEW FLOORING.
5. REMOVE AND REMEDIATE ASBESTOS-CONTAINING TILE FLOORING PER
ASBESTOS SPECIFICATIONS.
6. REMOVE WALLPAPER. PREPARE WALLS FOR NEW PAINT FINISH.
7. REMOVE PERIMETER VCT FLOORING TO PREPARE FOR 12" ACCENT BORDER.
REMAINDER OF EXISTING VCT FLOORING WILL REMAIN.
04/20/15
ADDITIVE
BID ITEM 1
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
DEMOLITION PLAN - SECOND FLOOR
214
215
216
STAIRS
201
200
213
212
211
209
208
207
206
RESTROOM
203
RESTROOM
205
HALL
STAIRS
HALL
HALL
CLOS
CLOS
ELEVATOR
CLOSET
2
1 11
1
2
PANEL "SP2A" 3
30
30
1
ALARM INDICATORS
(7)SWITCHES
30
OFFICE FURNITURE FEED
4 4 4
4 4 4
4
5
45
5
4
54
5
5
5
5 5
555
5
4
4
4
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
DE
MO
LIT
IO
N P
LA
N
SE
CO
ND
F
LO
OR
D14
GENERAL NOTES:DEMOLITION SYMBOLS LEGEND:
XX DEMOLITION NOTE
LIMIT OF DEMOLITION
DEMOLITION NOTES:
XX
1. REMOVE STUD PARTITION WALL ASSEMBLY.
2. REMOVE DOOR, FRAME, AND HARDWARE.
3. REMOVE PANELBOARD AND FEEDER BACK TO SOURCE. MARK BREAKER AS
SPARE.
4. REMOVE CARPET TO CONCRETE SLAB SUBSTRATE. PREPARE SLAB TO RECEIVE
NEW FLOORING.
5. REMOVE AND REMEDIATE ASBESTOS-CONTAINING TILE FLOORING PER
ASBESTOS SPECIFICATIONS.
1. REFER TO ARCHITECTURAL, ELECTRICAL, AND MECHANICAL DRAWINGS FOR
ADDITIONAL DEMOLITION AND ALTERATION NOTES.
2. CUTTING AND PATCHING:
A. ANY EXISTING CONSTRUCTION THAT IS TO BE REMOVED SHALL BE
REMOVED CAREFULLY SO AS NOT TO DAMAGE ANY EXISTING
CONSTRUCTION THAT IS TO REMAIN. FLOORS, WALLS, AND CEILINGS ARE
TO BE PATCHED (IN A RECTANGULAR PATTERN) TO MATCH EXISTING
CONDITIONS AND MADE READY TO RECEIVE ANY NEW FINISHES WHERE
APPLICABLE.
3. ALL EXISTING FIREPROOFING REMOVED DURING DEMOLITION SHALL BE
PATCHED TO MATCH EXISTING.
4. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
5. REMOVE VCT FLOORING TO CONCRETE IN ALL ROOMS EXCEPT HALLS, STAIRS,
AND RESTROOMS. REFER TO DEMOLITION NOTES FOR ADDITIONAL
INFORMATION. PREPARE SLAB TO RECEIVE NEW FLOORING.
04/20/15
ADDITIVE
BID ITEM 1
IFB #152724-TW
METAL COLLAR
SEALANT - INSTALL
STAINLESS STEEL
CLAMPING RING
CONTINUOUS WELD
(E)ROOF DECK
PIPE OR CONDUIT
SEALANT
1/2" TO 6" DIAMETER COLD
(E)ROOFING SYSTEM
FLASHING
PRE-MOLDED MEMBRANE
BETWEEN PIPE AND
PREMANUFACTURED
PIPE PENETRATION (COLD
PIPE OR CONDUIT)
(E)INSULATION;
SCALE:
0 9"6"3" 1'
3"=1'-0"
SECTION - TYPICAL COLD PIPE PENETRATION1
MEMBRANE FLASHING
SCALE:
0 9"6"3" 1'
3"=1'-0"
SECTION - TYPICAL LOUVER INFILL2
(E)INTERIOR WALL, TYP
1/2" GWB PAINTED TO MATCH
ADJACENT WALL COLOR
1 1/2" METAL FURRING; PROVIDE
PERIMETER FRAME AND VERTICAL
MEMBERS @ 16" OC
RUBBER BASE TO MATCH EXISTING
SEALED TO WALL FROM INTERIOR
FORMED SHEET METAL CAP
(E)BRICK
VENEER
(E)LOUVER
TO REMAIN
CAULK PERIMETER SEPARATION
@ CMU WALLS
PATCH FLOOR WHERE CABINET
BASE WAS REMOVED TO MATCH
ADJACENT FINISH AS DIRECTED
BY OWNER
METAL COLLAR
SEALANT
(E)ROOFING SYSTEM
HIGH TEMPERATURE BOOT
PRE-FORMED PENETRATION
TEMPERATURE
STAINLESS STEEL
CLAMPING RING
CONTINUOUS
(E)ROOF DECKING
APPROPRIATE
ELASTOMERIC
SEALANT
SCALE:
0 9"6"3" 1'
3"=1'-0"
SECTION - TYPICAL COMBUSTION AIR VENT THROUGH ROOF3
RE
FE
R T
O D
RA
WIN
G M
9, S
EC
TIO
N 1
AND STRUCTURE
WELD
COMBUSTION AIR
VENT
COMBUSTION AIR
VENT
8" M
IN
IM
UM
2'-0"
NO
T T
O S
CA
LE
8" M
IN
IM
UM
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
LE
GE
ND
A
ND
S
EC
TIO
NS
A1
LEGEND
MATERIAL
LOC
MATCHLINE
1
1
1
NORTH
A
A
A
1
1
LETTER INDICATES
DETAIL
DRAWING NUMBER WHERE
DETAIL IS DRAWN
DRAWING NUMBER WHERE
DETAIL IS TAKEN
LETTER INDICATES
ENLARGED PLAN
DRAWING NUMBER WHERE
ENLARGED PLAN IS DRAWN
DRAWING NUMBER WHERE
ENLARGED PLAN IS TAKEN
LETTER INDICATES
ELEVATION
DRAWING NUMBER WHERE
ELEVATION IS DRAWN
DRAWING NUMBER WHERE
ELEVATION IS TAKEN
NUMBER INDICATES
SECTION
DRAWING NUMBER WHERE
SECTION IS DRAWN
DRAWING NUMBER WHERE
SECTION IS TAKEN
REVISION TRIANGLE
REVISION CLOUD
AFF ABOVE FINISHED FLOOR
ACT ACOUSTICAL TILE
ALT ALTERNATE
ALUM ALUMINUM
APPROX APPROXIMATE
ARCH ARCHITECTURAL
AVG AVERAGE
BD BOARD
BOT BOTTOM
BLDG BUILDING
CAB CABINET
CS CAST STONE
CF CUBIC FOOT
℄ CENTERLINE
CLG CEILING
CT CERAMIC TILE
CLR CLEAR
COL COLUMN
CONC CONCRETE
CMU CONCRETE MASONRY UNIT
CONT CONTINUOUS
CI CUBIC INCH
CY CUBIC YARD
DTL DETAIL
DIAG DIAGONAL
DIA, Ø DIAMETER
DIM DIMENSION
DS DOWNSPOUT
DEPT DEPARTMENT
DN DOWN
DF DRINKING FOUNTAIN
DWG DRAWING
(E) EXISTING
EA EACH
ELEC ELECTRIC
EWC ELECTRIC WATER COOLER
EL ELEVATION (ABOVE SEA LEVEL)
ELEV ELEVATION (GRAPHIC)
EQ EQUAL
EQUIP EQUIPMENT
EJ EXPANSION JOINT
EXT EXTERIOR
FIN FINISH
FF FINISH FLOOR
FL FLOOR
FD FLOOR DRAIN
FRT FIRE RETARDANT TREATED
FT FOOT, FEET
GA GAGE
GAL GALLONS
GALV GALVANIZED
GL GLASS
GYP GYPSUM
GWB GYPSUM WALL BOARD
HDWD HARDWOOD
HDWR HARDWARE
HGT HEIGHT
H HIGH
HM HOLLOW METAL
HORZ HORIZONTAL
HR HOUR(S)
IN INCHES
INFO INFORMATION
ID INSIDE DIAMETER
INSUL INSULATION
INT INTERIOR
INV INVERT
JT JOINT
LAM LAMINATED
LAV LAVATORY
L LENGTH
LF LINEAR FEET
MATL MATERIAL
MAX MAXIMUM
MECH MECHANICAL
MTL METAL
MEZZ MEZZANINE
MIN MINIMUM
MISC MISCELLANEOUS
MPI MASTER PAINTERS INSTITUTE
MR MOISTURE RESISTANT
MTG MOUNTING HEIGHT
NOM NOMINAL
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OC ON CENTER
OPNG OPENING
OH OPPOSITE HAND
OZ OUNCE
OD OUTSIDE DIAMETER
PTD PAINTED
PNL PANEL
PART PARTITION
PH PHASE
PLCS PLACES
PLAS PLASTER
PL PLATE
LBS POUNDS
PSF POUNDS PER SQUARE FOOT
PSI POUNDS PER SQUARE INCH
R RADIUS
R- THERMAL RESISTANT RATING
REF REFER
REINF REINFORCING
REQD REQUIRED
RD ROOF DRAIN
RM ROOM
SCH SCHEDULE
SECT SECTION
SHT SHEET
SPEC SPECIFICATION
SQ SQUARE
SF SQUARE FOOT, FEET
SS STAINLESS STEEL
STD STANDARD
STL STEEL
STOR STORAGE
TB TACKBOARD
TEMP TEMPERATURE
KIP FT THOUSAND FOOT LBS
KIP THOUSAND POUNDS
THRES THRESHOLD
TLT TOILET
T&G TONGUE AND GROOVE
TYP TYPICAL
UON UNLESS OTHERWISE NOTED
VAR VARIABLE
VERT VERTICAL
VOL VOLUME
WC WATER CLOSET
WGT WEIGHT
WWF WELDED WIRE FABRIC
W WIDTH
W/ WITH
WO WITHOUT
WD WOOD
WP WORK POINT
YD YARD
X
X
X
F1 F1
F2 F2
F3 F3
F4 F4
WALKPADS, LIGHTWEIGHT
CONCRETE, GROUT
CAST-IN-PLACE CONCRETE
CONCRETE MASONRY
BRICK MASONRY, CHEMICALLY
RESISTANT MEMBRANE
STEEL
FINISH WOOD
PLYWOOD
RIGID INSULATION
GYPSUM WALL BOARD
BATT INSULATION
EXTENT OF (E)CONSTRUCTION
TO BE REPLACED
SEALANT
WOOD BLOCKING
CONTINUOUS WOOD, STUD
EXISTING CONSTRUCTION
DEMOLITION
NEW CONSTRUCTION
LIMITS OF CONSTRUCTION
MATCHLINE
CENTERLINE
CONDITION ABOVE/BELOW
ONE HOUR RATED FIRE
BARRIER TYPE 1
LINETYPES SYMBOLS ABBREVIATIONS
LIMIT OF REMOVAL
POINT OF EXISTING TO NEW
INDICATES NUMBER OF
REVISION, CORRESPONDS WITH
REVISION NOTE
DEMOLITION NOTE
CONSTRUCTION NOTE
NORTH SYMBOL
WINDOW TYPES
WALL TYPES
BUILDING/TOILET ACCESSORIES
ONE HOUR RATED FIRE
BARRIER TYPE 2
ONE HOUR RATED FIRE
BARRIER TYPE 3
ONE HOUR RATED FIRE
BARRIER TYPE 4
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
REFLECTED CEILING PLAN - BASEMENT
116
15
14 13
17
18
19
12A
12B
11
10
SERVER ROOM
10
IT ROOM
32
HALL
AUDITORIUM
2221
20
RESTROOM
25
RESTROOM
5
MECHANICAL ROOM
26
AUDITORIUM LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
STORAGE
24
CLOSET
CLOSET
KITCHEN
7B
HALL
HALL
HALL
HALL
HALL
HALL
ELEVATOR
VESTIBULE
7A
CLOSET
CLOS
23
TELECOM
15B
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
GENERAL NOTES:
1. REFER TO DEMOLITION, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITIONAL NOTES.
2. PROVIDE SUSPENDED ACOUSTICAL CEILING TILE AND GRID SYSTEM.
3. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
Lic. No. 015253
RE
FL
EC
TE
D C
EIL
IN
G P
LA
N
BA
SE
ME
NT
A2
LEGEND:
2x4 LIGHTING LUMINAIRE
SUPPLY AIR DIFFUSER
RETURN GRILLE
S
SMOKE DETECTOR
GYPSUM BOARD CEILING
2x4 ACOUSTICAL CEILING SYSTEM
2x2 ACOUSTICAL CEILING SYSTEM
2x4 LIGHTING LUMINAIRE
2x2 LIGHTING LUMINAIRE
2x2 LIGHTING LUMINAIRE
RECESSED LIGHT FIXTURE
CEILING MOUNTED EXIT SIGN
CEILING SPEAKER
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
REFLECTED CEILING PLAN - FIRST FLOOR
127126
125
123
124
129
130
131C131B131D
HALL
STAIRS
100
102 117
116
101
RESTROOM
103
VESTIBULE
119
HALL
114
113112
106
107
105
108
STAIRS
LOBBY
115
CLOSET
CLOS
CLOS
CLOS
CLOSET
HALL
CONFERENCE
110
ELEVATOR
HALL
RESTROOM
104
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
RE
FL
EC
TE
D C
EIL
IN
G P
LA
N
FIR
ST
F
LO
OR
A3
LEGEND:
2x4 LIGHTING LUMINAIRE
SUPPLY AIR DIFFUSER
RETURN GRILLE
S
SMOKE DETECTOR
GYPSUM BOARD CEILING
2x4 ACOUSTICAL CEILING SYSTEM
2x2 ACOUSTICAL CEILING SYSTEM
2x4 LIGHTING LUMINAIRE
2x2 LIGHTING LUMINAIRE
2x2 LIGHTING LUMINAIRE
GENERAL NOTES:
1. REFER TO DEMOLITION, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITION NOTES.
2. PROVIDE SUSPENDED ACOUSTICAL CEILING TILE AND GRID SYSTEM.
3. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
RECESSED LIGHT FIXTURE
CEILING MOUNTED EXIT SIGN
CEILING SPEAKER
OCCUPANCY SENSOR
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
REFLECTED CEILING PLAN - SECOND FLOOR
214
STAIRS
201
200
213
212
211
209
208
207
206
RESTROOM
203
RESTROOM
205
HALL
STAIRS
HALL
HALL
CLOS
CLOS
ELEVATOR
CLOSET
TELECOM
201B
OFFICE
217
WAR ROOM
218
OFFICE
216
OFFICE
215
OFFICE
219
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
RE
FL
EC
TE
D C
EIL
IN
G P
LA
N
SE
CO
ND
F
LO
OR
A4
LEGEND:
2x4 LIGHTING LUMINAIRE
SUPPLY AIR DIFFUSER
RETURN GRILLE
S
SMOKE DETECTOR
GYPSUM BOARD CEILING
2x4 ACOUSTICAL CEILING SYSTEM
2x2 ACOUSTICAL CEILING SYSTEM
2x4 LIGHTING LUMINAIRE
2x2 LIGHTING LUMINAIRE
2x2 LIGHTING LUMINAIRE
GENERAL NOTES:
1. REFER TO DEMOLITION, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITION NOTES.
2. PROVIDE SUSPENDED ACOUSTICAL CEILING TILE AND GRID SYSTEM.
3. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
RECESSED LIGHT FIXTURE
CEILING MOUNTED EXIT SIGN
CEILING SPEAKER
OCCUPANCY SENSOR
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
FLOOR PLAN - BASEMENT
SERVER ROOM
9
HALL
AUDITORIUM
RESTROOM
25
RESTROOM
5
MECHANICAL ROOM
26
AUDITORIUM LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
STORAGE
24
CLOSET
CLOSET
KITCHEN
7B
HALL
HALL
HALL
HALL
HALL
ELEVATOR
VESTIBULE
7A
CLOSET
CLOS
C
B
A
CLOS
HALL
IT
15B
OFFICE
15A
OFFICE
16
OFFICE
1
OFFICE
2
OFFICE
3
OFFICE
10
OFFICE
11
OFFICE
12B
OFFICE
12A
OFFICE
13
OFFICE
14
OFFICE
17
OFFICE
19
OFFICE
18
OFFICE
20
OFFICE
21
OFFICE
22
OFFICE
23
IT ROOM
8
1
2
2
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
FL
OO
R P
LA
N
BA
SE
ME
NT
A5
GENERAL NOTES:
1. REFER TO DEMOLITION, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITION NOTES.
2. PAINT ALL INTERIOR WALLS AND DOOR FRAMES THROUGHOUT BUILDING, UNLESS
NOTED OTHERWISE.
3. PROVIDE MATERIAL AND LABOR TO REMOVE LOOSE PLASTER FROM INSIDE OF
EXTERIOR WALL AND ON WINDOW JAMBS IN MULTIPLE LOCATIONS AND PREPARE
WALL FOR PAINTING. AMOUNT OF DAMAGED AREA DOES NOT APPEAR TO EXCEED
100 SQUARE FEET TOTAL.
4. TYPICAL VCT FLOORING TO MATCH EXISTING VCT FLOORING IN HALL (AZROCK
V-913 LIGHT MOVES).
5. TYPICAL VCT BORDER TILE TO MATCH BASIS-OF-DESIGN AZROCK V-957
FIELDSTONE.
CONSTRUCTION NOTES:
XX
1. INFILL OPENING IN EXISTING BRICK WALL WITH METAL STUDS AND GYPSUM WALL
BOARD PER WALL TYPES ON DRAWING A8.
2. PROVIDE 12" VCT BORDER AS INDICATED.
FINISH SCHEDULE
ROOM
NUMBER
ROOM NAME FLOOR BASE WALLS
CEILING
NOTES
MATERIAL HEIGHT
1 OFFICE VCT RUBBER PAINT ACT 9'-2"
HALL EXISTING EXISTING PAINT ACT 9'-2"
2 OFFICE VCT RUBBER PAINT ACT 9'-2"
3 OFFICE VCT RUBBER PAINT ACT 9'-2" 1
CLOSET VCT RUBBER PAINT ACT 9'-2"
5 RESTROOM EXISTING EXISTING PAINT ACT 9'-2"
6 MECHANICAL ROOM EXISTING EXISTING PAINT EXISTING EXISTING
ELEVATOR EXISTING EXISTING EXISTING EXISTING EXISTING
HALL EXISTING EXISTING PAINT ACT 9'-2"
7A VESTIBULE EXISTING EXISTING PAINT EXISTING EXISTING
CLOSET VCT RUBBER PAINT EXISTING EXISTING
7B KITCHEN VCT RUBBER PAINT ACT 9'-2"
HALL EXISTING EXISTING PAINT ACT 9'-2"
8 IT ROOM VCT RUBBER PAINT ACT 9'-2"
9 SERVER ROOM VCT RUBBER PAINT ACT 9'-2"
STAIRS EXISTING EXISTING PAINT EXISTING EXISTING
HALL EXISTING EXISTING PAINT ACT 9'-2"
CLOSET VCT RUBBER PAINT ACT 9'-2"
10 OFFICE VCT RUBBER PAINT ACT 9'-2"
11 OFFICE VCT RUBBER PAINT ACT 9'-2"
12A OFFICE VCT RUBBER PAINT ACT 9'-2"
12B OFFICE VCT RUBBER PAINT ACT 9'-2"
13 OFFICE VCT RUBBER PAINT ACT 9'-2"
14 OFFICE VCT RUBBER PAINT ACT 9'-2"
15A OFFICE VCT RUBBER PAINT ACT 9'-2" 1
15B IT VCT RUBBER PAINT ACT 9'-2"
16 OFFICE VCT RUBBER PAINT ACT 9'-2"
17 OFFICE VCT RUBBER PAINT ACT 9'-2"
18 OFFICE VCT RUBBER PAINT ACT 9'-2"
19 OFFICE VCT RUBBER PAINT ACT 9'-2"
HALL EXISTING EXISTING PAINT ACT 9'-2"
CLOSET VCT RUBBER PAINT ACT 9'-2"
HALL EXISTING EXISTING PAINT ACT 9'-2"
20 OFFICE VCT RUBBER PAINT ACT 9'-2"
21 OFFICE VCT RUBBER PAINT ACT 9'-2"
22 OFFICE VCT RUBBER PAINT ACT 9'-2"
23 OFFICE VCT RUBBER PAINT ACT 9'-2"
CLOSET VCT RUBBER PAINT ACT 9'-2"
24 STORAGE VCT RUBBER PAINT ACT 9'-2"
25 RESTROOM EXISTING EXISTING PAINT ACT 9'-2"
HALL EXISTING EXISTING PAINT ACT 9'-2"
STAIRS EXISTING EXISTING PAINT EXISTING EXISTING
26 MECHANICAL ROOM EXISTING EXISTING PAINT EXISTING EXISTING
AUDITORIUM LOBBY EXISTING EXISTING PAINT EXISTING EXISTING
AUDITORIUM EXISTING EXISTING PAINT EXISTING EXISTING
NOTES:
1. PROVIDE 12" VCT ACCENT BORDER AROUND ROOM PERIMETER.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
FLOOR PLAN - FIRST FLOOR
HALL
STAIRS
RESTROOM
103
VESTIBULE
119
HALL
STAIRS
LOBBY
115
CLOSET
CLOS
CLOS
CLOS
CLOSET
HALL
CONFERENCE
110
ELEVATOR
HALL
RESTROOM
104
B
A
OFFICE
106
OFFICE
105
OFFICE
107
OFFICE
108
OFFICE
112
OFFICE
113
OFFICE
114
OFFICE
116
OFFICE
117
OFFICE
118
OFFICE
100
OFFICE
101
OFFICE
123
OFFICE
124
OFFICE
125
OFFICE
126
OFFICE
127
OFFICE
129
OFFICE
130
OFFICE
131B
OFFICE
131C
OFFICE
131D
OFFICE
131E
OFFICE
131A
1
1 1
1 1 1
1
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
FL
OO
R P
LA
N
FIR
ST
F
LO
OR
A6
GENERAL NOTES:
1. REFER TO DEMOLITION, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITION NOTES.
2. PAINT ALL INTERIOR WALLS AND DOOR FRAMES THROUGHOUT BUILDING, UNLESS
NOTED OTHERWISE.
3. PROVIDE MATERIAL AND LABOR TO REMOVE LOOSE PLASTER FROM INSIDE OF
EXTERIOR WALL AND ON WINDOW JAMBS IN MULTIPLE LOCATIONS AND PREPARE
WALL FOR PAINTING. AMOUNT OF DAMAGED AREA DOES NOT APPEAR TO EXCEED
100 SQUARE FEET TOTAL.
4. TYPICAL VCT FLOORING TO MATCH EXISTING VCT FLOORING IN HALL (AZROCK
V-913 LIGHT MOVES).
5. TYPICAL VCT BORDER TILE TO MATCH BASIS-OF-DESIGN AZROCK V-957
FIELDSTONE.
CONSTRUCTION NOTES:
XX
1. PROVIDE 12" VCT BORDER AS INDICATED.
FINISH SCHEDULE
ROOM
NUMBER
ROOM NAME FLOOR BASE WALLS
CEILING
NOTES
MATERIAL HEIGHT
100 OFFICE VCT RUBBER PAINT ACT 9'-0"
HALL EXISTING EXISTING PAINT ACT 9'-0"
101 OFFICE VCT RUBBER PAINT ACT 9'-0" 1
CLOSET VCT RUBBER PAINT ACT 9'-0"
103 RESTROOM EXISTING EXISTING PAINT ACT 9'-0"
104 RESTROOM EXISTING EXISTING PAINT ACT 9'-0"
105 OFFICE VCT RUBBER PAINT ACT 9'-0"
106 OFFICE VCT RUBBER PAINT ACT 9'-0"
ELEVATOR EXISTING EXISTING EXISTING EXISTING 9'-0"
107 OFFICE VCT RUBBER PAINT ACT 9'-0"1, 2
108 OFFICE EXISTING EXISTING PAINT ACT 9'-0"
HALL EXISTING EXISTING PAINT ACT 9'-0"
STAIRS EXISTING EXISTING PAINT EXISTING 9'-0"
CLOSET EXISTING EXISTING PAINT EXISTING 9'-0"
110 CONFERENCE VCT RUBBER PAINT ACT 9'-0" 1
HALL EXISTING EXISTING PAINT ACT 9'-0"
112 OFFICE VCT RUBBER PAINT ACT 9'-0"
113 OFFICE VCT RUBBER PAINT ACT 9'-0"
114 OFFICE VCT RUBBER PAINT ACT 9'-0"
115 LOBBY VCT RUBBER PAINT ACT 9'-0"
116 OFFICE VCT RUBBER PAINT ACT 9'-0"
117 OFFICE VCT RUBBER PAINT ACT 9'-0"
118 OFFICE VCT RUBBER PAINT ACT 9'-0"
119 VESTIBULE EXISTING EXISTING PAINT EXISTING 9'-0"
HALL EXISTING EXISTING PAINT ACT 9'-0"
CLOSET VCT RUBBER PAINT ACT 9'-0"
STAIRS EXISTING EXISTING PAINT ACT 9'-0"
123 OFFICE VCT RUBBER PAINT EXIST/VCT 9'-0"
124 OFFICE VCT RUBBER PAINT ACT 9'-0"
125 OFFICE VCT RUBBER PAINT ACT 9'-0" 1
126 OFFICE VCT RUBBER PAINT ACT 9'-0" 1
127 OFFICE VCT RUBBER PAINT ACT 9'-0" 1
CLOSET VCT RUBBER PAINT ACT 9'-0"
129 OFFICE VCT RUBBER PAINT ACT 9'-0" 1
CLOSET VCT RUBBER PAINT ACT 9'-0"
130 OFFICE VCT RUBBER PAINT ACT 9'-0" 1
131A OFFICE VCT RUBBER PAINT ACT 9'-0"
131B OFFICE VCT RUBBER PAINT ACT 9'-0"
131C OFFICE VCT RUBBER PAINT ACT 9'-0"
131D OFFICE VCT RUBBER PAINT ACT 9'-0"
131E OFFICE VCT RUBBER PAINT ACT 9'-0"
CLOSET VCT RUBBER PAINT ACT 9'-0"
NOTES:
1. PROVIDE 12" VCT ACCENT BORDER AROUND ROOM PERIMETER.
2. MAJORITY OF EXISTING FLOORING WILL REMAIN. REMOVE PERIMETER FLOORING TO PREPARE FOR 12"
ACCENT BORDER.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
FLOOR PLAN - SECOND FLOOR
STAIRS
RESTROOM
203
RESTROOM
205
HALL
STAIRS
HALL
HALL
CLOS
CLOS
ELEVATOR
CLOSET
A
C
D
OFFICE
201AIT
201B
OFFICE
206
OFFICE
207
OFFICE
208
OFFICE
209
OFFICE
211
OFFICE
212
OFFICE
213
OFFICE
200
OFFICE
214
OFFICE
219
OFFICE
216
OFFICE
215
OFFICE
217
WAR ROOM
218
1
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
FL
OO
R P
LA
N
SE
CO
ND
F
LO
OR
A7
GENERAL NOTES:
1. REFER TO DEMOLITION, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITION NOTES.
2. PAINT ALL INTERIOR WALLS AND DOOR FRAMES THROUGHOUT BUILDING, UNLESS
NOTED OTHERWISE.
3. PROVIDE MATERIAL AND LABOR TO REMOVE LOOSE PLASTER FROM INSIDE OF
EXTERIOR WALL AND ON WINDOW JAMBS IN MULTIPLE LOCATIONS AND PREPARE
WALL FOR PAINTING. AMOUNT OF DAMAGED AREA DOES NOT APPEAR TO EXCEED
100 SQUARE FEET TOTAL.
4. TYPICAL VCT FLOORING TO MATCH EXISTING VCT FLOORING IN HALL (AZROCK
V-913 LIGHT MOVES).
5. TYPICAL VCT BORDER TILE TO MATCH BASIS-OF-DESIGN AZROCK V-957
FIELDSTONE.
CONSTRUCTION NOTES:
XX
1. PROVIDE 3 5/8" METAL STUD WALL, SIMILAR TO WALL TYPE A, FOR PLUMBING
CHASE. MINIMIZE SIZE OF CHASE AS MUCH AS POSSIBLE.
FINISH SCHEDULE
ROOM
NUMBER
ROOM NAME FLOOR BASE WALLS
CEILING
NOTES
MATERIAL HEIGHT
200 OFFICE VCT RUBBER PAINT ACT 9'-5"
201A OFFICE VCT RUBBER PAINT ACT 9'-5"
201B IT VCT RUBBER PAINT ACT 9'-5"
HALL EXISTING EXISTING PAINT ACT 9'-5"
203 RESTROOM EXISTING EXISTING PAINT ACT 9'-5"
CLOSET VCT EXISTING PAINT EXISTING 9'-5"
205 RESTROOM EXISTING EXISTING PAINT ACT 9'-5"
206 OFFICE VCT RUBBER PAINT ACT 9'-5"
207 OFFICE VCT RUBBER PAINT ACT 9'-5"
ELEVATOR EXISTING EXISTING EXISTING EXISTING 9'-5"
HALL EXISTING EXISTING PAINT ACT 9'-5"
208 OFFICE VCT RUBBER PAINT ACT 9'-5"
209 OFFICE VCT RUBBER PAINT ACT 9'-5" 1
HALL EXISTING EXISTING PAINT ACT 9'-5"
STAIRS EXISTING EXISTING PAINT EXISTING 9'-5"
211 OFFICE VCT RUBBER PAINT ACT 9'-5"
212 OFFICE VCT RUBBER PAINT ACT 9'-5"
213 OFFICE VCT RUBBER PAINT ACT 9'-5"
214 OFFICE VCT RUBBER PAINT ACT 9'-5"
215 OFFICE VCT RUBBER PAINT ACT 9'-5"
216 OFFICE VCT RUBBER PAINT ACT 9'-5"
217 OFFICE VCT RUBBER PAINT ACT 9'-5"
218 WAR ROOM VCT RUBBER PAINT ACT 9'-5"
CLOSET VCT EXISTING PAINT EXISTING 9'-5"
219 OFFICE VCT RUBBER PAINT ACT 9'-5"
CLOSET VCT EXISTING PAINT EXISTING 9'-5"
STAIRS EXISTING EXISTING PAINT EXISTING 9'-5"
NOTES:
1. PROVIDE 12" VCT ACCENT BORDER AROUND ROOM PERIMETER.
04/20/15
IFB #152724-TW
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED PLANA
11'-6" 47'-10 3/8"
10'-0 1/4"
10'-0 1/4"
10'-2 1/4"
10'-2 1/4"
13'-10 3/4" 13'-10 3/4"
5'-1 1/4"
3'-4"10'-0 1/4"
2'-2 1/2"
4'-4 7/8"
2'-2 1/2"
4'-4 7/8"
HALL
HALL
2'-0 5/8"
20'-4"
OFFICE
17
OFFICE
19
OFFICE
18
OFFICE
23
OFFICE
22
OFFICE
21
OFFICE
20
CLOSET
18
19
17
19A
20
21 22
23
A
A
A
A
A
A A
A
A
A
D D
DD
A A
11
1
1 2
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED PLANB
6'-6"
3'-8 1/2"
IT
15B
OFFICE
15A
15B
C
A
A
4
3
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED PLANC
OFFICE
11
OFFICE
12B
OFFICE
12A
D
D
1
1
SCALE:
1'6"3"0 9"
1 1/2"=1'-0"
WALL TYPES
1 1/2"=1'-0"
4 7/8"
A
5/8" GYPSUM WALL
BOARD; BOTH SIDES
3 5/8", 20 GA METAL
STUDS @ 16" OC;
ATTACH TO
STRUCTURE ABOVE
B/ACT
(+8'- 0") AFF
ACOUSTICAL
CEILING TILE; BOTH
BASE; BOTH SIDES
B/(E)CONC
DECK
(+8'- 8") AFF
SIDES
7 1/4"
B
5/8" GYPSUM WALL
BOARD; BOTH SIDES
6", 20 GA METAL
STUDS @ 16" OC;
ATTACH TO
STRUCTURE ABOVE
B/ACT
(+8'- 0") AFF
ACOUSTICAL
CEILING TILE; BOTH
BASE; BOTH SIDES
B/(E)CONC
DECK
(+8'- 8") AFF
SIDES
6 5/8"
C
5/8" GYPSUM WALL
BOARD
6", 20 GA METAL
STUDS @ 16" OC;
ATTACH TO
STRUCTURE ABOVE
B/ACT
(+8'- 0") AFF
ACOUSTICAL
CEILING TILE
B/(E)CONC
DECK
(+8'- 8") AFF
(E)WALL
VARIES
D
5/8" GYPSUM WALL
BOARD; BOTH SIDES
20 GA METAL
STUDS @ 16" OC;
ATTACH TO
STRUCTURE ABOVE
B/ACT
(+8'- 0") AFF
ACOUSTICAL
CEILING TILE; BOTH
BASE; BOTH SIDES
B/(E)CONC
DECK
(+8'- 8") AFF
SIDES
MATCH
THICKNESS
OF (E)WALL
SCALE: 1/4"=1'-0"
FRAME TYPES
20-MINUTE RATED
HOLLOW METAL;
F1
3'-0"2"
7'-0"
2"
2"
0 1'
3'-0"
7'-0"
MATCH (E)LAMINATE
A
FINISH
12" x 12"
LOUVER
MATCH (E)LAMINATE
B
FINISH
3'-0"
7'-0"
MATCH (E)LAMINATE
C
FINISH
1'-6"
7'-0"
SCALE:
0 1' 5' 10'
1/4"=1'-0"
DOOR TYPES
3'-0"
1'-6"
2"
5 7/8"±
1 15/16" 1 15/16"
1/2" TYP
4 7/8"
J1 (SIM)
H1
DOOR
HM FRAME
SEALANT
5/8" GWB
STUDS
3 5/8" MTL
SCALE:
1'6"3"0 9"
1 1/2"=1'-0"
DOOR HEAD AND JAMBS (SIM)
1 1/2"=1'-0"
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
EN
LA
RG
ED
P
LA
NS
AN
D D
ET
AIL
S
A8
GENERAL NOTES:
1. REFER TO DEMOLITION, MECHANICAL, AND ELECTRICAL
DRAWINGS FOR ADDITION NOTES.
CONSTRUCTION NOTES:
XX
1. PROVIDE WALL INFILL WITHIN EXISTING DOOR FRAME,
TYPICAL.
2. PROVIDE FINISHED CLEAR OPENING TO MATCH
ADJACENT WALL FINISH.
3. PROVIDE BASE AND WALL CABINETS PER
SPECIFICATIONS. PROVIDE SINGLE TOP DRAWER WITH
CABINET DOOR BELOW PER INDIVIDUAL CABINET UNIT.
4. PROVIDE 12" VCT ACCENT BORDER. REFER TO FINISH
SCHEDULE.
DOOR SCHEDULE
DOOR
NUMBER
DOOR
TYPE
SIZE FRAME
NOTES
HARDWARE
SET
WIDTH HEIGHT THICKNESS TYPE DEPTH
JAMB
COND
HEAD
COND
15B B 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 1 A
18 A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
19 EXISTING B
19A C PR 1'-6" 7'-0" 1-3/4" F1 5 7/8" J1 H1 C
20 A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
21 A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
22 A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
23 A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
131A A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 D
131D A 2'-8" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
131E A 2'-8" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
201B EXISTING A
215 A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
216 A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
217 A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
218 A 3'-0" 7'-0" 1-3/4" F1 5 7/8" J1 H1 B
NOTES:
1. PROVIDE 12" x 12" VENTILATION LOUVER SHOP FABRICATED AS PART OF DOOR ASSEMBLY.
04/20/15
IFB #152724-TW
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED PLANA
11'-9 1/2"
11'-3 3/4"
9'-1 5/8"
5'-0 3/8"
4'-6 7/8"
4'-4 7/8"
HALL
CLOSET
131E
131A
131D
OFFICE
131E
OFFICE
131D
OFFICE
131C
OFFICE
131B
OFFICE
131A
D
A
A
A
A
1
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED PLANB
OFFICE
108
OFFICE
107
D
6'-9"
3
2
1
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED PLANC
8'-4 1/4"
4'-4 1/4"
IT
201B
201B
OFFICE
201A
A
A
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED PLAND
41'-5"
29'-4 1/2"
14'-8"26'-9"4'-2 1/2"
14'-7"
3'-10 1/2"
2'-4"
STAIRS
CLOSET
OFFICE
212
OFFICE
211
2
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
EN
LA
RG
ED
P
LA
NS
A9
GENERAL NOTES:
1. REFER TO DEMOLITION, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITION NOTES.
CONSTRUCTION NOTES:
XX
1. PROVIDE WALL INFILL WITHIN EXISTING DOOR FRAME, TYPICAL.
2. PROVIDE BASE AND WALL CABINETS PER SPECIFICATIONS. PROVIDE SINGLE TOP
DRAWER WITH CABINET DOOR BELOW PER INDIVIDUAL CABINET UNIT.
3. PROVIDE 12" VCT ACCENT BORDER. REFER TO FINISH SCHEDULE.
04/20/15
IFB #152724-TW
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED PLANA
OFFICE
219
WAR ROOM
218
OFFICE
217
OFFICE
216
OFFICE
215
STAIRS
CLOSET
CLOSET
11'-7 5/8"
10'-2 5/8"
13'-1 5/8"
11'-7 5/8" 11'-7 5/8"
10'-2 5/8"
10'-0 5/8"
9'-8 5/8"
7'-1 3/4"
11'-3 1/4"
215
216
217
218
OFFICE
214
A
A
A
B
A
A
A
A
A
A
A
A
A
A
8'-5"
7'-0"
1
'
-
0
"
M
I
N
6'-11"
8'-6"
6'-6"
7'-0"
8'-5"
3'-6 1/4"
2'-7 1/4"
4'-10 3/4"
1
'
-
0
"
M
I
N
1
'
-
0
"
M
I
N
1
'
-
0
"
M
I
N
9'-11"
1
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 015253
EN
LA
RG
ED
P
LA
NS
A10
GENERAL NOTES:
1. REFER TO DEMOLITION, MECHANICAL, AND ELECTRICAL DRAWINGS FOR
ADDITION NOTES.
CONSTRUCTION NOTES:
XX
1. PROVIDE BASE AND WALL CABINETS PER SPECIFICATIONS. PROVIDE TOP
DRAWER WITH CABINET DOOR BELOW PER INDIVIDUAL CABINET UNIT.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 20'10' 30'
1/16"=1'-0"
ROOF AND PARTIAL ROOF EQUIPMENT SUPPORT FRAMING PLANS
C
A
D
B
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED FRAMING PLANA
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED FRAMING PLANB
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED FRAMING PLANC
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED FRAMING PLAND
DOAU-1
HP-5
C8
C8
C8
C8
C8
C8
C8
C8
(E)W8
(E)W8
(E
)W
8
(E
)W
8
8"±
6'-4 7/8"±
2'-6 1/8"±
6"±
6"± 4'-3 3/16"±
4 3/16"± 4'-7 1/8"±
3/16
TYP
3/16
L3x3x1/4x0'-6"
E
6"± 2'-6 1/8"±
4'-3 3/16"±
C8
C8
C8
C8
C8
C8
C8
C8
HP-1 HP-3
(E)ANGLE FRAME
BELOW
3/16
TYP
3/16
L3x3x1/4x0'-6"
NOTES:
1. C8 = C8x11.5.
NOTES:
1. C8 = C8x11.5.
NOTES:
1. C8 = C8x11.5.
4'-3 3/16"±EQ EQ
2'-6"±
EQ
EQ
HP-6
(E)SUPPORT
BELOW
C8
C8
C8
C8
C8
C8
L3x3x1/4x0'-6"
3/16
TYP
(E)PARAPET
NOTES:
1. C8 = C8x11.5.
(E
)W
10
BE
LO
W
(E
)W
10
BE
LO
W
(E
)W
10
BE
LO
W
4'-6"± 9'-0"±
4'-3 3/16"± 4'-3 3/16"±
2'-6"±
(E)WALL
(E)WALL BELOW
C8
C8
C8
C8
C8
C8
1
L3x3x1/4x0'-6"
3/16
TYP
3/16
3"Øx1'-4" SCHEDULE
40 PIPE PIPE POST,
TYPICAL OF (4)
3" TYP
HP-2 HP-4
2
5'-1"±
SCALE:
0 3'1'6" 2'
3/4"=1'-0"
DETAILE
(E)BEAM
BELOW
C8
L3x3
C8
SCALE:
0 3'1'6" 2'
3/4"=1'-0"
SECTION1
C8
L3x3x0'-6" BEYOND
3/8"x4"x4" PLATE
3"Ø SCHEDULE 40
PIPE
C8x11.5x2'-6" W/(4)
3
SCALE:
0 3'1'6" 2'
3/4"=1'-0"
SECTION2
4'-6"±
(E)WALL
RUBBER BOOT, INSTALL
PER MANUFACTURER'S
INSTRUCTIONS &
SPECIFICATIONS
C8 BEYOND
3/16
TYP
3/16
3/16
TYP
3/16
1'-4"
1'-4"
RUBBER BOOT, INSTALL
PER MANUFACTURER'S
INSTRUCTIONS &
SPECIFICATIONS
C8
C8
3/8"x4"x4"
3"Ø SCH 40
PIPE
PLATE
3/4"Ø HOLES FOR
(4) 5/8"Ø BOLTS
C8
BEYOND
C8
SCALE:
1'6"3"0 9"
1 1/2"=1'-0"
SECTION3
4 1/2"
4 1/4"
1/2"x6 1/2"x6 1/2" BASE PLATE
W/(4) 3/4"Ø HOLES FOR
(4) 5/8"Ø A36 GALVANIZED
BOLTS THRU C8x11.5 BELOW
3"Ø PIPE POST
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
GENERAL NOTES:
1. EXISTING ROOF IS CARLISLE FULLY ADHERED 60 MIL EPDM SINGLE PLY
MEMBRANE INSTALLED OVER A POLYISOCYANURATE INSULATION SYSTEM,
REPLACED IN 2009 BY DON LARGENT ROOFING, INC. WITH A 20-YEAR WARRANTY.
ROOF DECK VARIES BY BUILDING SECTION AND INCLUDES PLYWOOD, METAL,
LIGHTWEIGHT CONCRETE, AND STRUCTURAL CONCRETE. RECORD DRAWINGS
FOR THE 2009 ROOF REPLACEMENT ARE AVAILABLE FOR THE CONTRACTOR'S
INFORMATION. WORK ON ROOF, INCLUDING ROOF PENETRATIONS, SHALL NOT
NEGATE ANY EXISTING ROOF WARRANTY. CONTRACTOR'S ROOF
SUBCONTRACTOR SHALL BE CERTIFIED TO CUT, PATCH, AND REPAIR EXISTING
ROOF TO MAINTAIN WARRANTY IN EFFECT.
2. SEE DRAWING M9 FOR STRUCTURAL SUPPORT IN MECHANICAL ROOM.
STRUCTURAL STEEL:
1. STEEL MATERIALS SHALL CONFORM TO THE FOLLOWING SPECIFICATIONS:
STRUCTURAL SHAPES AND PLATES ASTM A36, GRADE 36
STRUCTURAL PIPE ASTM A53, GRADE B
MACHINE BOLTS ASTM A307 HOT DIPPED GALVANIZED
2. DESIGN, FABRICATION, ERECTION, AND WORKMANSHIP SHALL CONFORM TO THE
"SPECIFICATION FOR STRUCTURAL STEEL BUILDINGS ALLOWABLE STRESS DESIGN
AND PLASTIC DESIGN," AISC ASD, NINTH EDITION.
3. BOLTED CONNECTIONS SHALL BE SHEAR-BEARING TYPE WITH THREADS
INCLUDED IN THE SHEAR PLANES UNLESS OTHERWISE NOTED. BOLTS SHALL BE
TIGHTENED TO THE "SNUG-TIGHT" CONDITION, UNLESS OTHERWISE NOTED.
4. ALL SHOP AND FIELD WELDING SHALL BE EXECUTED BY WELDERS AND WELDING
OPERATORS WHO HAVE BEEN PREVIOUSLY QUALIFIED BY TEST AS PRESCRIBED IN
THE "CODE FOR WELDING IN BUILDING CONSTRUCTION", AWS D1.1, OF THE
AMERICAN WELDING SOCIETY TO PERFORM THE TYPES OF WELDS REQUIRED ON
THIS PROJECT.
5. ALL WELDING ELECTRODES SHALL BE E70XX SERIES.
6. MINIMUM FILLET WELD SIZE SHALL BE AS FOLLOWS, UNLESS OTHERWISE NOTED:
THICKNESS OF THICKER PART JOINED WELD SIZE
3/16" TO 1/2" 3/16"
OVER 1/2" TO 3/4" 1/4"
7. RETURN ALL WELDS AT CORNERS TWICE THE NOMINAL SIZE OF THE WELD
MINIMUM, UNLESS OTHERWISE NOTED.
8. SHORE OR BRACE EXISTING MEMBERS WHEN REQUIRED TO REDUCE WARPING TO
A MINIMUM WHEN WELDING TO EXISTING MEMBERS CARRYING LOAD.
9. ALL FIELD CUTS SHALL BE GROUND SMOOTH AND PAINTED WITH TWO COATS
MINIMUM.
10. ALL EXPOSED STEEL SHALL BE PAINTED, SHOP PRIMED, WITH FINISH COATS
APPLIED IN THE FIELD.
11. SHOP PAINTING: ALL SURFACES SHALL BE PRIME PAINTED IN THE SHOP WITH AN
APPROVED PRIMER COMPATIBLE WITH THE TOP COAT. PRIMER COAT SHALL HAVE
A MINIMUM OF 2 MILS DRY FILM THICKNESS. SPOT PAINT ALL FIELD WELDS AND
SERIOUS ABRASIONS TO THE SHOP COAT WITH PAINT COMPATIBLE WITH THE
SHOP COAT. DO NOT PAINT STEEL SURFACES THAT ARE TO BE EMBEDDED IN
CONCRETE OR MORTAR OR WHICH ARE TO RECEIVE SPRAYED-ON FIREPROOFING.
12. APPLY PAINTS ONLY WHEN TEMPERATURES OF SURFACES TO BE PAINTED AND
AMBIENT AIR TEMPERATURE ARE BETWEEN 50 AND 95 DEGREES. DO NOT APPLY
PAINT WHEN RELATIVE HUMIDITY EXCEEDS 85 PERCENT, AT TEMPERATURES LESS
THAN 5 DEGREES ABOVE DEW POINT, OR TO DAMP OR WET SURFACES. FOR
EXTERIOR SURFACES, DO NOT APPLY PAINTS IN SNOW, RAIN, FOG, OR MIST.
13. PROVIDE MATERIALS FOR USE WITHIN EACH PAINT SYSTEM THAT ARE
COMPATIBLES WITH ONE ANOTHER AND SUBSTRATES INDICATED, UNDER
CONDITIONS OF SERVICE AND APPLICATION AS DEMONSTRATED BY
MANUFACTURER, BASED ON TESTING AND FIELD EXPERIENCE. FOR EACH COAT IN
A PAINT SYSTEM, PROVIDE PRODUCT RECOMMENDATIONS IN WRITING BY
MANUFACTURERS OF TOPCOAT FOR USE IN PAINT SYSTEM AND ON SUBSTRATE
INDICATED.
14. TO PRIME STEEL SUBSTRATES, REMOVE RUST, LOOSE MILL SCALE, AND SHOP
PRIMER IF ANY. CLEAN USING METHODS RECOMMENDED IN WRITING BY PAINT
MANUFACTURER BUT NOT LESS THAN: SSPC-SP 3 "POWER TOOL CLEANING".
15. TO FIELD PRIME SHOP-PRIMED STEEL SUBSTRATES: CLEAN FIELD WELDS, BOLTED
CONNECTIONS, AND ABRADED AREAS OF SHOP PAINT, AND PAINT EXPOSED
AREAS WITH THE SAME MATERIAL AS USED FOR SHOP PRIMING TO COMPLY WITH
SSPC-PA 1 FOR TOUCHING UP SHOP-PRIMED SURFACES.
16. EXTERIOR PAINT SCHEDULE AS FOLLOWS:
1) ALKYD SYSTEM:
A) PRIME COAT: PRIMER, ALKYD, ANTICORROSIVE FOR METAL , MPI #79.
B) INTERMEDIATE COAT: EXTERIOR ALKYD ENAMEL MATCHING TOPCOAT.
C) TOPCOAT: ALKYD, EXTERIOR, SEMI-GLOSS (GLOSS LEVEL 5) , MPI #94.
RO
OF
P
LA
N,
DE
TA
IL
S, A
ND
N
OT
ES
S1
PHIL V. MAYS
Lic. No. 014412
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
BASEMENT LIFE SAFETY PLAN
F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F1
F1
F1 F1
F1 F1 F1 F1 F1
F1 F1 F1 F1 F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1
F1 F1 F1 F1 F1 F1
F1 F1 F1 F1 F1 F1
F1
F1
F1
F1
ORIGINALADDITION
1
1
1
4
2
3
SERVER ROOM
9
HALL
AUDITORIUM
RESTROOM
25
RESTROOM
5
MECHANICAL ROOM
26
AUDITORIUM LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
STORAGE
24
CLOSET
CLOSET
KITCHEN
7B
HALL
HALL
HALL
HALL
HALL
ELEVATOR
VESTIBULE
7A
CLOSET
CLOS
CLOS
HALL
IT
15B
OFFICE
15A
OFFICE
16
OFFICE
1
OFFICE
2
OFFICE
3
OFFICE
10
OFFICE
11
OFFICE
12B
OFFICE
12A
OFFICE
13
OFFICE
14
OFFICE
17
OFFICE
19
OFFICE
18
OFFICE
20
OFFICE
21
OFFICE
22
OFFICE
23
IT ROOM
8
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
LEGEND:
UNRATED WALL
F1 F1
ONE HOUR RATED FIRE BARRIER TYPE 1
BA
SE
ME
NT
F
IR
E P
RO
TE
CT
IO
N P
LA
N
FP1
Lic. No. 035249
STEVEN M. HOVIS
BUILDING HISTORY AND DESIGN STRATEGY:
ORIGINAL BUILDING
ORIGINAL BUILDING WAS CONSTRUCTED IN 1953 AND WAS SERVED BY A CONSTANT VOLUME AIR
HANDLING UNIT LOCATED IN THE BASEMENT MECHANICAL ROOM. RATED PARTITIONS ARE IMPLIED
AROUND THE STAIRWELL ON THESE DRAWINGS BASED ON FIRE DAMPERS SHOWN AT SUPPLY GRILLES
PENETRATING STAIRWELLS. NO OTHER DUCTS ARE SHOWN WITH DAMPERS ON THESE DRAWINGS.
DOORS IN CORRIDOR WALLS ALL HAVE TRANSFER GRILLES. THE MAIN VERTICAL RETURN DUCT CHASE
WAS NOT CONSTRUCTED AS A RATED PARTITION AS EACH FLOOR HAS A LARGE COMMON SIDEWALL
RETURN GRILLE WITHOUT DAMPER AT THE CHASE. THE CHASE IS OPEN TO SPACE ABOVE THE CEILING
AT EACH FLOOR.
INTERIOR STAIR DOORS IN THE ORIGINAL BUILDING ARE NOT LABELED. THESE DOORS WILL NOT BE
REPLACED AS PART OF THIS HVAC REPLACEMENT PROJECT. IN ORDER FOR THE STAIRS TO BE FULLY
PROTECTED, IT WILL BE NECESSARY FOR VDOT TO REPLACE DOORS IN THE ORIGINAL BUILDING WITH
60-MINUTE RATED HOLLOW METAL DOORS.
THE AIR HANDLING UNITS AND DUCTWORK WERE REMOVED DURING A 1975 HVAC RENOVATION WHICH
CHANGED THE SYSTEM TO PTACS AND CHILLED WATER FAN COIL UNITS. DUCT PENETRATIONS WERE
LEFT OPEN, INCLUDING THOSE IN STAIRWELLS. THE RETURN DUCT CHASE WALLS HAVE BEEN KNOCKED
OUT ABOVE THE CEILING TO ALLOW ROUTING OF CHILLED WATER PIPE BETWEEN FLOORS.
MECHANICAL ROOM 6 IN THE BASEMENT WAS THE ORIGINAL MECHANICAL ROOM FOR THE BUILDING. THE
AIR HANDLING UNITS WERE REMOVED DURING THE 1975 HVAC RENOVATION. DURING THE 1980 ELEVATOR
PROJECT, THE PARTITION WAS ADDED TO CREATE A HALL. THE CHILLER WAS STILL IN THE MECHANICAL
ROOM AND THE ELEVATOR EQUIPMENT WAS ADDED. THE DOOR SHOWN BETWEEN THE NEW HALL AND
THE STAIRWELL IS NOT PRESENT. IT HAS BEEN ABSENT FOR AT LEAST 21 YEARS, IF IT WAS EVER
ACTUALLY INSTALLED. THE CHILLER WAS LATER RELOCATED OUTDOORS, SO MECHANICAL ROOM 6
CURRENTLY HOUSES ONLY ELEVATOR MACHINERY. THE PARTITION BETWEEN THE MACHINERY ROOM
AND HALL, AND THE MACHINERY ROOM DOOR, NEED TO BE RATED. THE WALL IS A STEEL FRAME AND GYP
ASSEMBLY WHICH WOULD BE SUITABLE FOR A 1-HOUR RATING, EXCEPT IT STOPS AT THE BOTTOM OF
JOISTS. WE PROPOSE TO TAKE THE SAME APPROACH AS THE STAIRWELLS. THAT IS, WE WILL EXTEND
THE WALL UP TO THE DECK, PER NOTE 4 ABOVE, WHILE WE HAVE THE HALL CEILING REMOVED IN ORDER
TO AVOID RE-DISTURBING THE NEW CEILING LATER. HOWEVER, THE DOOR CAN BE REPLACED BY THE
FACILITY UNDER SEPARATE PROJECT. THIS APPROACH COMPLIES WITH THE REQUIREMENTS OF THE
VIRGINIA REHABILITATION CODE, AS THE HVAC PROJECT IS NOT DECREASING THE CURRENT LEVEL OF
PROTECTION.
ADDITION
THE ADDITION WAS CONSTRUCTED IN 1966, AND EXCEPT FOR THE AUDITORIUM, IS SERVED BY DUAL
TEMPERATURE FAN COIL UNITS. THE 1966 DRAWINGS DO NOT INDICATE RATED PARTITION INFORMATION.
DOORS ALONG THE CORRIDOR ARE INDICATED ON DRAWING SCHEDULES AS WOOD WITH 5/8" UNDERCUT
AND THIS AGREES WITH OBSERVED CONDITIONS. CORRIDOR WALLS RUN TO DECK.
INTERIOR STAIR DOORS IN THE ADDITION ARE LISTED IN THE ORIGINAL CONSTRUCTION DRAWINGS AS “B”
LABEL MINERAL FILLED HOLLOW METAL AND THIS AGREES WITH OBSERVED CONDITIONS. DOORS AND
FRAMES IN THE ADDITION WILL REMAIN AS EXISTING.
A ROOFTOP UNIT WAS ADDED IN 1995 TO PROVIDE SUPPLEMENTAL COOLING AND FRESH AIR. RATED
PARTITIONS ARE IMPLIED AT CORRIDOR WALLS AND AT FLOOR SLABS ON THESE DRAWINGS BASED ON
FIRE DAMPERS SHOWN IN DUCTS. HOWEVER, BASED ON FIELD OBSERVATIONS, THE ONLY DAMPERS
ACTUALLY INSTALLED ARE IN THE VERTICAL DUCT PENETRATIONS BETWEEN FLOORS AND IN THE
HORIZONTAL DUCT PENETRATIONS AT THE MECHANICAL ROOM WALLS. NO DAMPERS WERE FOUND
ABOVE THE CEILING IN DUCTWORK PENETRATING CORRIDOR WALLS.
GENERAL OBSERVATIONS
BASED ON VISUAL INSPECTION, THE CORRIDORS IN BOTH THE ORIGINAL PORTION OF THE BUILDING AND
THE ADDITION DO NOT APPEAR TO MEET THE CRITERIA FOR RATED PARTITIONS. ASIDE FROM THE
INFORMATION PROVIDED ABOVE, ONGOING UNDOCUMENTED MODIFICATIONS TO THE BUILDING HAVE
RESULTED IN NUMEROUS UNSEALED PIPE, CONDUIT, AND CABLE PENETRATIONS THROUGH THE
CORRIDOR WALLS. THERE ARE NO DOORS IN THE CORRIDOR SEPARATING THE ORIGINAL BUILDING FROM
THE ADDITION. ON APRIL 17, 2014, VIRGINIA A&E MET WITH THE STATE FIRE MARSHAL TO OBSERVE THESE
CONDITIONS THROUGHOUT THE BUILDING.
VERTICAL SEPARATION IN THE ADDITION APPEARS GENERALLY INTACT. VERTICAL SEPARATION WAS
NEVER PROVIDED IN THE ORIGINAL PORTION OF THE BUILDING DUE TO THE NON-RATED AND
NON-CONTINUOUS DUCT CHASE. UNSEALED PIPE AND CONDUIT PENETRATIONS EXIST IN THE CLOSETS
OFF THE MAIN CORRIDORS IN THE ORIGINAL PORTION OF THE BUILDING.
DESIGN STRATEGY
THE STATE FIRE MARSHAL'S OFFICE HAS DETERMINED THAT BCOM IS RESPONSIBLE FOR ISSUING ANY
CORRECTIVE REQUIREMENTS.
BCOM HAS INDICATED THAT THE PROJECT SHOULD COMPLY WITH THE VIRGINIA REHABILITATION CODE.
THE SCOPE OF WORK ON THIS PROJECT IS LIMITED TO REPLACEMENT OF HVAC SYSTEMS, CEILINGS, AND
LIGHTING. THE PROPOSED HVAC SYSTEMS ARE NOT IN-KIND REPLACEMENTS OF EXISTING EQUIPMENT;
HOWEVER, THEY “SERVE THE SAME PURPOSE” OF PROVIDING HEATING, COOLING, AND VENTILATION FOR
THE BUILDING AND OCCUPANTS. THEREFORE, WE PROPOSE THAT THE WORK IS CLASSIFIED AS A LEVEL 1
ALTERATION.
LEVEL 1 ALTERATIONS REQUIRE THAT THE WORK BE DONE IN A MANNER THAT MAINTAINS THE CURRENT
LEVEL OF FIRE PROTECTION PROVIDED. BASED ON THIS, THERE IS NO REQUIREMENT OTHER THAN TO
SEAL ANY NEW PENETRATIONS. HOWEVER, WE BELIEVE THERE IS AN OPPORTUNITY TO MAKE
ADDITIONAL IMPROVEMENTS WHILE THE CEILING IS REMOVED.
WE PROPOSE TO PROVIDE SEPARATION IN THE ORIGINAL PORTION OF THE BUILDING TO THE EXTENT
POSSIBLE BY CREATING A HORIZONTAL SEPARATION IN THE RETURN DUCT CHASE BETWEEN FLOORS
PER DETAILS ON DRAWING FP2. EXISTING PIPE AND CONDUIT PENETRATIONS IN THE CLOSETS OFF THE
MAIN CORRIDOR SHALL BE SEALED WITH A RATED PRODUCT. PENETRATIONS BY CABLES, CONDUITS,
TUBES, OR PIPES SHALL COMPLY WITH VCC 713.4. THE STAIRWELL PENETRATIONS WILL BE SEALED TO
RESTORE THE RATING.
ANY ADDITIONAL FLOOR PENETRATIONS DISCOVERED DURING DEMOLITION AFTER REMOVAL OF THE
CEILINGS SHALL BE SEALED BY AN APPROVED METHOD.
WE PROPOSE THAT THERE IS CURRENTLY NO CORRIDOR SEPARATION AND IT IS NOT FEASIBLE TO
PROVIDE THIS SEPARATION UNDER THIS PROJECT. AS SUCH, WE ARE NOT PROVIDING FIRE DAMPERS
WHERE DUCTS PENETRATE CORRIDOR WALLS.
CONSTRUCTION NOTES:
XX
1. PATCH AND SEAL ALL EXISTING PENETRATIONS TO RESTORE 1-HOUR RATING. EAST STAIRS HAVE AN
8"x6" PENETRATION PER FLOOR IN ADDITION TO VARIOUS OTHER PENETRATIONS. SEAL BLANK
OPENING PER UL DETAIL C-AJ-0015 ON DRAWING FP2.
2. PROVIDE FIRE STOP MATERIAL AT EXISTING RETURN DUCT CHASE OPENING IN FLOOR PER UL DETAIL
C-AJ-4056 ON DRAWING FP2. BUNDLE ALL LOOSE CABLES AND GROUP TOGETHER IN A THROUGH
PENETRATION.
3. CLOSETS ON EACH FLOOR CONTAIN MULTIPLE PIPE AND CONDUIT PENETRATIONS THROUGH THE
CONCRETE FLOOR SLAB. SEAL PER UL DETAIL C-AJ-3321 ON DRAWING FP3.
4. PATCH AND SEAL ALL EXISTING PENETRATIONS IN EXTERIOR WALLS TO RESTORE 1-HOUR RATING.
SEAL PER UL DETAIL W-J-0001 ON DRAWING FP2. THE WALL BETWEEN MECHANICAL ROOM 6 AND THE
HALL IS METAL STUD FRAMING TO THE DECK ABOVE WITH 5/8" GYPSUM BOARD ON BOTH SIDES TO
BOTTOM OF BAR JOISTS. EXTEND GYPSUM BOARD FINISH ON BOTH SIDES OF THE WALL TIGHT TO
THE DECK ABOVE. PROVIDE WALL COMPOUND AT ALL JOINTS TO SEAL TIGHTLY TO DECK ABOVE AND
ALL AROUND BAR JOISTS. PROVIDE FIRE BARRIER RATED FOAM AS REQUIRED TO ENSURE GAPS ARE
TIGHTLY SEALED.
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
FIRST FLOOR LIFE SAFETY PLAN
F1
F1
F1
F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F1
F1
F1 F1 F1 F1 F1
F1
F1
F1 F1 F1 F1 F1
ORIGINALADDITION
1
1
2
3HALL
STAIRS
BATHROOM
103
VESTIBULE
119
HALL
STAIRS
LOBBY
115
CLOSET
CLOS
CLOS
CLOS
CLOSET
HALL
CONFERENCE
110
ELEVATOR
HALL
BATHROOM
104
OFFICE
106
OFFICE
105
OFFICE
107
OFFICE
108
OFFICE
112
OFFICE
113
OFFICE
114
OFFICE
116
OFFICE
117
OFFICE
118
OFFICE
100
OFFICE
101
OFFICE
123
OFFICE
124
OFFICE
125
OFFICE
126
OFFICE
127
OFFICE
129
OFFICE
130
OFFICE
131B
OFFICE
131C
OFFICE
131D
OFFICE
131E
OFFICE
131A
1
SCALE: NONE
PENETRATION DETAIL
2
SYSTEM NO W-J-0001
MARCH 13, 2009
F RATING - 2 HOUR
T RATING - 0 HOUR
WALL ASSEMBLY: MINIMUM 7-5/8 INCH THICK WALL ASSEMBLY
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS* OR
COMMON BRICKS, LAID UP WITH MORTAR. MINIMUM 2 HOUR
FIRE RATED WALL. MAXIMUM AREA OF OPENING IS 256 SQUARE
INCHES WITH MAXIMUM DIMENSION OF 16 INCHES.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE
RESISTANCE DIRECTORY FOR NAMES OF MANUFACTURERS.
FILL, VOID OR CAVITY MATERAIL* - FOAM: MINIMUM 7-5/8 INCH
THICKNESS OF FILL MATERIAL APPLIED WITHIN THE ANNULUS,
FLUSH WITH BOTH SURFACES OF WALL. FOAMED SILICONE
INSTALLED AS DESCRIBED IN THE MANUFACTURER'S
APPLICATION INSTRUCTIONS AT A DENSITY OF 17 PCF MINIMUM
TO 20 PCF MAXIMUM.
DOW CORNING TORAY SILICONE CO LTD - TYPE SE 1900
FORMS (NOT SHOWN): USED AS A FORM TO PREVENT LEAKAGE
OF FILL MATERIAL DURING INSTALLATION. FORMS TO BE RIGID
SHEET MATERIAL, CUT TO FIT THE CONTOUR OF THE
PENETRATING ITEM AND FASTENED TO BOTH SIDES OF WALL.
FORMS TO BE REMOVED AFTER FILL MATERIAL HAS CURED.
*INDICATES SUCH PRODUCTS SHALL BEAR THE UL OR cUL
CERTIFICATION MARK FOR JURISDICTIONS EMPLOYING THE UL
OR cUL CERTIFICATION (SUCH AS CANADA), RESPECTIVELY.
REPRINTED FROM THE ONLINE CERTIFICATIONS DIRECTORY
WITH PERMISSION FROM UL. © 2014 UL LLC.
1
7 5/8"
2
3
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
FIR
ST
F
LO
OR
F
IR
E P
RO
TE
CT
IO
N P
LA
N
FP2
Lic. No. 035249
STEVEN M. HOVIS
LEGEND:
UNRATED WALL
F1 F1
ONE HOUR RATED FIRE BARRIER TYPE 1
SYSTEM NO C-AJ-4056
SEPTEMBER 20, 2011
F RATING - 3 HR
T RATING - 3/4 HR
L RATING AT AMBIENT - 7 AND 22 CFM/SQ FT (SEE ITEM 4)
L RATING AT 400° - 4 AND 21 CFM/SQ FT (SEE ITEM 4)
SCALE: NONE
PENETRATION DETAIL
CONSTRUCTION NOTES:
XX
1. PATCH AND SEAL ALL EXISTING PENETRATIONS TO RESTORE 1-HOUR RATING.
EAST STAIRS HAVE AN 8"x6" PENETRATION PER FLOOR IN ADDITION TO
VARIOUS OTHER PENETRATIONS. SEAL BLANK OPENING PER UL DETAIL
C-AJ-0015 ON THIS DRAWING.
2. PROVIDE FIRE STOP MATERIAL AT EXISTING RETURN DUCT CHASE OPENING IN
FLOOR PER UL DETAIL C-AJ-4056 ON THIS DRAWING. BUNDLE ALL LOOSE
CABLES AND GROUP TOGETHER IN A THROUGH PENETRATION.
3. CLOSETS ON EACH FLOOR CONTAIN MULTIPLE PIPE AND CONDUIT
PENETRATIONS THROUGH THE CONCRETE FLOOR SLAB. SEAL PER UL DETAIL
C-AJ-3321 ON DRAWING FP3.
SCALE: NONE
PENETRATION DETAIL
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
REPRINTED FROM THE ONLINE CERTIFICATIONS
DIRECTORY WITH PERMISSION FROM UL. © 2014 UL LLC.
REPRINTED FROM THE ONLINE CERTIFICATIONS
DIRECTORY WITH PERMISSION FROM UL. © 2014 UL LLC.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
SECOND FLOOR LIFE SAFETY PLAN
F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F1
F1
F1 F1 F1 F1 F1
F1
F1
F1 F1 F1 F1 F1
ORIGINALADDITION
1
1
2
3
STAIRS
RESTROOM
203
RESTROOM
205
HALL
STAIRS
HALL
HALL
CLOS
CLOS
ELEVATOR
CLOSET
OFFICE
201AIT
201B
OFFICE
206
OFFICE
207
OFFICE
208
OFFICE
209
OFFICE
211
OFFICE
212
OFFICE
213
OFFICE
200
OFFICE
214
OFFICE
219
OFFICE
216
OFFICE
215
OFFICE
217
WAR ROOM
218
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
SE
CO
ND
F
LO
OR
FIR
E P
RO
TE
CT
IO
N P
LA
N
FP3
Lic. No. 035249
STEVEN M. HOVIS
LEGEND:
UNRATED WALL
F1 F1
ONE HOUR RATED FIRE BARRIER TYPE 1
SYSTEM NO C-AJ-3321
JULY 29, 2013
SYSTEM TESTED WITH A PRESSURE DIFFERENTIAL OF 2.5 PA BETWEEN THE EXPOSED AND THE UNEXPOSED
SURFACES WITH THE
HIGHER PRESSURE ON THE EXPOSED SIDE.
FLOOR OR WALL ASSEMBLY —
THROUGH PENETRANTS —
METALLIC PIPES —
STEEL PIPE —
CONDUIT —
COPPER TUBING —
COPPER PIPE —
NONMETALLIC PIPES —
POLYVINYL CHLORIDE (PVC) PIPE —
RIGID NONMETALLIC CONDUIT+ —
CABLES —
TUBE INSULATION - PLASTICS++ —
PLASTICS
FILL, VOID OR CAVITY MATERIAL* — FOAM —
3M COMPANY —
©
F RATINGS — 2 HR
T RATING — 1/4 HR
L RATING AT AMBIENT - LESS THAN 1 CFM/SQ FT
L RATING AT 400 F - LESS THAN 1 CFM/SQ FT
SCALE: NONE
PENETRATION DETAIL
CONSTRUCTION NOTES:
XX
1. PATCH AND SEAL ALL EXISTING PENETRATIONS TO RESTORE 1-HOUR RATING.
EAST STAIRS HAVE AN 8"x6" PENETRATION PER FLOOR IN ADDITION TO
VARIOUS OTHER PENETRATIONS. SEAL BLANK OPENING PER UL DETAIL
C-AJ-0015 ON DRAWING FP2.
2. PROVIDE FIRE STOP MATERIAL AT EXISTING RETURN DUCT CHASE OPENING IN
FLOOR PER UL DETAIL C-AJ-4056 ON DRAWING FP2. BUNDLE ALL LOOSE
CABLES AND GROUP TOGETHER IN A THROUGH PENETRATION.
3. CLOSETS ON EACH FLOOR CONTAIN MULTIPLE PIPE AND CONDUIT
PENETRATIONS THROUGH THE CONCRETE FLOOR SLAB. SEAL PER UL DETAIL
C-AJ-3321 ON THIS DRAWING.
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
04/20/15
IFB #152724-TW
System No. C-AJ-2576
F Rating - 2 Hr
T Rating - 1/4 Hr
L Rating At Ambient - Less Than 1 CFM/sq ft
L Rating At 400 F - Less Than 1 CFM/sq ft
1. Floor or Wall Assembly - Min 4-1/2 in. (114 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete floor or min 7-1/2 in. (191 mm) thick reinforced
lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete wall. Wall may also be constructed of any UL Classified Concrete Blocks*. Max diam of opening is 5 in. (127 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Steel Sleeve - (Optional) - Nom 5 in. (127 mm) diam (or smaller) Schedule 10 (or heavier) steel pipe or nom 5 in. (127 mm) diam (or smaller) No. 26 GA (0.022 in. or 0.56 mm thick) sheet metal
sleeve with square flange spot welded to the sleeve at approx mid-height and sized to be a min of 2 in. larger than the sleeve diam cast or grouted into floor or wall assembly, flush with floor or wall
surfaces.
3. Through Penetrant - One nonmetallic pipe, conduit or tube to be installed eccentrically or concentrically within the firestop system. The annular space between the pipe, conduit or tube and the
periphery of the opening shall be nom 1/2 in. (13 mm) to max 1 in. (25 mm) . Pipe, conduit or tube to be rigidly supported on both sides of the floor or wall assembly. The following types and sizes of
nonmetallic pipes, conduits and tubes may be used:
A. Polyvinyl Chloride (PVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 polyvinyl chloride (PVC) pipe for use in closed (process or supply) or vented (drain, waste or vent) piping
systems.
B. Chlorinated Polyvinyl Chloride (CPVC) Pipe - Nom 3 in. (76 mm) diam (or smaller) SDR13.5 chlorinated polyvinyl chloride (CPVC) pipe for use in closed (process or supply) piping systems.
C. Rigid Nonmetallic Conduit+ - Nom 3 in. (76 mm) diam (or smaller) Schedule 40 PVC conduit installed in accordance with the National Electrical Code (NFPA 70).
D. Electrical Nonmetallic Tubing+ - Nom 3 in. (76 mm) diam (or smaller) PVC tubing installed in accordance with the National Electrical Code (NFPA 70).
4. Firestop System - The firestop system shall consist of the following:
A. Packing Material - (Optional, Not Shown) - Polyethylene backer rod, mineral wool batt insulation or glass fiber batt insulation friction fit into opening as a permanent form to facilitate installation
of fill material (Item 4B).
B. Fill, Void or Cavity Material* - Sealant - For nom 2-1/2 to 3 in. (64 to 76 mm) diam pipes, min 3 in. (76 mm) thickness of fill material installed within annulus such that fill material is recessed 1/2
in. (13 mm) from top surface of floor or both surfaces of wall. For nom 2 in. (51 mm) or smaller pipes, min 2 in. (51 mm) thickness of fill material installed within annulus, flush with floor or wall
surfaces.
SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant
*Bearing the UL Classification Mark
+Bearing the UL Listing Mark
REPRINTED FROM THE ONLINE CERTIFICATIONS DIRECTORY WITH PERMISSION FROM UL. ©2014 UL LLC
A
Section A-A
3
1
4B
2
3
2
4B
A
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
LE
GE
ND
A
ND
S
PE
CIF
IC
AT
IO
NS
M1
CONSTRUCTION NOTE
A AMPERE
AFF ABOVE FINISHED FLOOR
AFUE ANNUAL FUEL UTILIZATION EFFICIENCY
BHP BRAKE HORSEPOWER
BOD BOTTOM OF DUCT
BOP BOTTOM OF PIPE
BTU BRITISH THERMAL UNIT
BTUH BRITISH THERMAL UNIT PER HOUR
CA COMPRESSED AIR
CF CHEMICAL FEED, CUBIC FEET
CFM CUBIC FEET PER MINUTE
CR CONDENSER WATER RETURN
CS CONDENSER WATER SUPPLY
CWR CHILLED WATER RETURN
CWS CHILLED WATER SUPPLY
DIA, Ø DIAMETER
DB DRY BULB
DBA DECIBELS, A WEIGHTED
DEG DEGREE
DTR DUAL TEMPERATURE WATER RETURN
DTS DUAL TEMPERATURE WATER SUPPLY
DX DIRECT EXPANSION
DWG DRAWING
(E) EXISTING
EAT ENTERING AIR TEMPERATURE
EER ENERGY EFFICIENCY RATIO
EFF EFFICIENCY
EL, ELEV ELEVATION
ESP EXTERNAL STATIC PRESSURE
EWT ENTERING WATER TEMPERATURE
°F DEGREES FAHRENHEIT
FD FIRE DAMPER
FOR FUEL OIL RETURN
FOS FUEL OIL SUPPLY
FT FOOT, FEET
G GAS
GA GAGE
GAL GALLONS
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
H HEIGHT
HD HEAD
HP HORSEPOWER
HR HOUR(S)
HWR HEATING WATER RETURN
HWS HEATING WATER SUPPLY
HZ FREQUENCY
ID INSIDE DIAMETER
IN INCHES
INWG INCHES WATER GAUGE
KW KILOWATT
L LENGTH
LAT LEAVING AIR TEMPERATURE
LB POUND(S)
LF LINEAR FEET
LPG LIQUIFIED PETROLEUM GAS (PROPANE)
LWT LEAVING WATER TEMPERATURE
MAX MAXIMUM
MBH THOUSAND BTU PER HOUR
MCA MINIMUM CIRCUIT AMPACITY
MCB MAXIMUM CIRCUIT BREAKER
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT PROTECTION
N/A NOT APPLICABLE
NIC NOT IN CONTRACT
NC NORMALLY CLOSED
NG NATURAL GAS
NO NORMALLY OPEN, NUMBER
NOM NOMINAL
NTS NOT TO SCALE
OA OUTSIDE AIR
OD OUTSIDE DIAMETER
% PERCENT
PD PRESSURE DROP OR DIFFERENTIAL
PH PHASE
PRV PRESSURE REDUCING OR REGULATING
VALVE
PSIG POUNDS PER SQUARE INCH GAGE
PSV PRESSURE SAFETY VALVE
R12, R22 REFRIGERANT (12, 22, ETC.)
RH RELATIVE HUMIDITY
RPM REVOLUTIONS PER MINUTE
SEER SEASONAL ENERGY EFFICIENCY RATIO
SF SQUARE FOOT, FEET
SHR SENSIBLE HEAT RATIO
SP STATIC PRESSURE
SPEC SPECIFICATION
SQ SQUARE
TD TEMPERATURE DIFFERENTIAL
TEMP TEMPERATURE
TOD TOP OF DUCT
TONS TONS OF REFRIGERATION
TSP TOTAL STATIC PRESSURE
T'STAT THERMOSTAT
TYP TYPICAL
V VOLTS
VAV VARIABLE AIR VOLUME
VRF VARIABLE REFRIGERANT FLOW
VTR VENT THRU ROOF
W WATT, WIDTH
WB WET BULB
MANUAL VOLUME DAMPER
FLEXIBLE DUCTWORK
TRANSITION IN DUCT SIZE
45° BRANCH CONNECTION
FIRE DAMPER IN WALL
FIRE DAMPER IN FLOOR,
CEILING OR ROOF
CONNECT TO EXISTING
INDICATES NUMBER OF
REVISIONS, CORRESPONDS
AIRFLOW
M
M
PIPE CAP
PUMP
THERMOMETER
PRESSURE GAUGE
UNION
PIPE TURNING DOWN
WYE STRAINER
PIPE TURNING UP
TEE DOWN
MOTOR OPERATED DAMPER
1
REVISION CLOUD
REVISION TRIANGLE
SYMBOLS
LEGEND
ABBREVIATIONS
TAG NO
CFM
DIFFUSER/GRILL TAG
1
1. DRAWINGS DO NOT INDICATE PIPING SUPPORT LOCATIONS AND DETAILS. CONTRACTOR SHALL BE RESPONSIBLE FOR
PROVIDING ALL NECESSARY PIPE SUPPORTS .
2. REFER TO REFLECTED CEILING PLAN FOR LOCATION OF AIR DEVICES.
3. ROUTE DUCTWORK CONCEALED ABOVE CEILING AS HIGH AS POSSIBLE UNLESS OTHERWISE NOTED. WHERE REQUIRED TO
AVOID OBSTRUCTIONS, DUCTWORK SHALL BE TRANSFORMED, DIVIDED, OR SHIFTED WITH THE ORIGINAL FREE AREA BEING
MAINTAINED.
4. PROVIDE AIR TURNING DEVICES IN DUCTWORK AT ANY CHANGE IN DIRECTION GREATER THAN 30 DEGREES. SQUARE
THROAT OR MITERED ELBOWS WITHOUT TURNING VANES, STRAIGHT RECTANGULAR AND ROUND DUCT TAPS, AND AIR
SCOOPS ARE NOT PERMITTED.
5. PROVIDE OPENINGS IN BUILDING CONSTRUCTION FOR PASSAGE OF DUCTWORK. DO NOT PENETRATE STRUCTURAL
MEMBERS WITHOUT PRIOR APPROVAL OF ENGINEER.
6. INSTALLATION OF FIELD MOUNTED CONTROL COMPONENTS SHALL BE THE RESPONSIBILITY OF THE CONTRACTOR. ALL
CONTROL WIRING SHALL BE IN CONDUIT AND INSTALLED PER NEC.
7. CONDENSATE DRAIN PIPING SHALL BE SCHEDULE 40 PVC, ASTM D 1785, SAME SIZE AS EQUIPMENT CONNECTION. INSULATE
PER DIVISION 23 SECTION "HVAC PIPING INSULATION." SUPPORT EVERY 4 FEET.
8. VARIABLE REFRIGERANT FLOW SYSTEMS SHALL COMPLY WITH ASHRAE 15 "SAFETY STANDARD FOR REFRIGERATION
SYSTEMS."
9. ALL PENETRATIONS THROUGH RATED WALL OR FLOOR ASSEMBLIES SHALL BE PER UL DETAIL THIS SHEET. ALL FLOORS ARE
RATED.
HVAC SPECIFICATIONS
CONCENTRIC REDUCER
PIPE FLANGE
GLOBE VALVE
CHECK VALVE
BALL VALVE
BUTTERFLY VALVE
GATE VALVE
ECCENTRIC REDUCER
MOTORIZED 2-WAY VALVE
PNEUMATIC 2-WAY VALVE
SOLENOID VALVE
MOTORIZED 3-WAY VALVE
PNEUMATIC 3-WAY VALVE
CALIBRATED BALANCING VALVE
BACKFLOW PREVENTER
AIR VENT (AUTO)
PLUG VALVE
SAFETY RELIEF VALVE
PRESSURE REDUCING VALVE
TEMPERATURE SENSOR
FLOW SWITCH
AIR VENT (MANUAL)
EQUIPMENT TAG
PIPE FLOW ARROW
WITH REVISION NOTE
1
ACCESS DOOR
M
M
S
F
T
A
M
SUPPLY/OA DUCT SECTION OR
DIFFUSER/GRILLE
RETURN/EXHAUST DUCT SECTION
OR DIFFUSER/GRILLE
TRANSITION FROM RECTANGULAR
TO ROUND
45° BRANCH TO ROUND
TAKEOFF CONNECTION
FLEXIBLE CONNECTOR
90° ELBOW UP
90° ELBOW DOWN
45° CONICAL TAP
90° CONICAL TAP
WALL MOUNTED HUMIDISTAT OR
DUCT SMOKE DETECTOR
CONICAL SPIN-IN WITH DAMPER
WALL MOUNTED THERMOSTAT
HUMIDITY SENSOR
OR TEMPERATURE SENSOR
H
S
T
90° ELBOW WITH TURNING VANES
(RECTANGULAR DUCT)
90° RADIUS ELBOW
(RECTANGULAR DUCT)
45° RADIUS ELBOW
(RECTANGULAR DUCT)
TEE WITH TURNING VANES
(RECTANGULAR DUCT)
RADIUS TEE
(RECTANGULAR DUCT)
Y FITTING
(ROUND DUCT)
AHU-1
X-1
000
CARBON DIOXIDE SENSORC
FIRE BARRIER
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
HVAC PLAN - BASEMENT
A
FCU-2-1
FCU-2-2
FCU-2-3
FCU-2-4
FCU-2-6
S-1
300
S-1
510
S-1
155
S-1
160
S-1
245
S-1
110
S-2
35
S-1
155
S-1
110
FCU-2-5
S-1
200
TYP OF 2
S-1
310
S-1
80
S-1
325
S-1
260
44
Ø10
x10 6
x12 6
Ø10
x10 8
x8 4
Ø8
Ø10
44
x10 8
Ø10
TYP OF 4
10
10
x20 10
Ø8
84
10
6
x10 8
x16 8
x8 4
64
x10 8
FCU-1-5
66
x18 12 x18 12 x18 12
S-1
175
10
6
S-1
250
Ø10
x10 10
x8 8
S-1
175
x6 6
Ø12
x18 8
FCU-1-6
Ø12
x10 6
Ø6
x8 6
x10 10
x10 8
x8 6
x16 8
10x8 DN
x8 8
x8 8
Ø10
x6 4
x8 8
S-1
100
(E)
200
Ø4
Ø8
x8 6 DN
x4 8
Ø8
44
35 C
FM
50 C
FM
35 CFM
50 C
FM
45 CFM
40 C
FM
Ø8
x8 6
x10 8
Ø6
4x6, 55 CFM 4x4, 30 CFM
4x6, 75 CFM
ACCU-1
Ø8
E-1
100
TYP OF 3
Ø8
x8 6
(E)12x8 UP
1
16
15
14
13
19
12A
12B
11
10
SERVER ROOM
10
IT ROOM
3
2
AUDITORIUM
22
BATHROOM
25
BATHROOM
5
MECHANICAL ROOM
26
AUDITORIUM LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
STORAGE
24
CLOSET
CLOSET
KITCHEN
7B
HALL
HALL
HALL
HALL
ELEVATOR
VESTIBULE
7A
x18 8
1
x8 4
1
18
8
TELECOM
15B
S-1
260
F-6
Ø8
8Ø,
DN
FCU-1-2
FCU-1-3
46
Ø4
15 CFM
Ø4
15 CFM
18
44
17
FCU-1-4
S-1
165
TYP OF 6
Ø10
Ø10
Ø10
Ø10
Ø10
Ø10
x14 8
x18 10
x24 10
x24 10
x10 8
18
10
18
10
66
110 C
FM
FCU1-1A
Ø8
(E)18x12 UP
HALL
x6 10
x12 10
21
x12 8
Ø8
S-1
215
S-1
235
20
x10 8
68
x8 8
x6 6
x6 8
Ø6
Ø8
S-1
110
S-2
50
FCU1-1B
S-1
70
Ø6
x8 8
x10 8
44
30 C
FM
23
HALL
x16 8
R-2
2
HALL
S-1
205
TYP OF 2
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
GENERAL NOTES:
1. ALL RETURN GRILLES ARE TYPE R-1 UNLESS OTHERWISE NOTED.
2. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
HV
AC
P
LA
N
BA
SE
ME
NT
M2
CONSTRUCTION NOTES:
XX
1. PROVIDE PLENUM OF HEIGHT AND WIDTH MATCHING FCU RETURN AIR OPENING
IN ORDER TO AVOID ABRUPT DUCT TRANSITIONS.
2. PROVIDE CEILING GRID AND (3) CEILING TILES. PROVIDE RETURN GRILLE IN
VACANT TILE. TRANSITION EXISTING DUCT TO CONNECT TO GRILLE.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
PIPING PLAN - BASEMENT
FCU-2-1
FCU-2-2
FCU-2-3
FCU-2-4
FCU-2-6
BS-1-1BS-2-1
FCU-1-5
FCU-1-6
UP TO HP-1
UP TO
HP-2
2"D2"D
1 1/2"D UP
2"D 2"D 2"D
2"D
2"D FROM
ABOVE
2"D
23
(E) PANEL "C1"
1 16
15
14 13
17
18
19
12A
12B
11
SERVER ROOM
10
IT ROOM
32
HALL
AUDITORIUM
2221
20
BATHROOM
25
BATHROOM
5
MECHANICAL ROOM
26
AUDITORIUM LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
STORAGE
24
CLOSET
CLOSET
KITCHEN
7B
HALL
HALL
HALL
ELEVATOR
VESTIBULE
7A
CLOSET
CLOS
TELECOM
15B
10
FCU-2-5
FCU-1-2
FCU-1-3
FCU-1-4
HALL
23
FCU-1-1B
FCU-1-1A
TYP1
HALL
HALL
2"D
2"D
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTES:
XX
1. ALL INDIVIDUAL FAN COIL DRAINS SHALL BE SAME SIZE AS EQUIPMENT
CONNECTIONS. BASIS OF DESIGN IS 1 INCH NOMINAL.
2. ROUTE CONDENSATE DRAIN TO FLOOR DRAIN AND TERMINATE 2 1/2" ABOVE
FLOOR.
3. ROUTE THROUGH WALL AT EXISTING PENETRATION USING UL DETAIL C-AJ-2576.
LEGEND:
REFRIGERANT LINE SET, 2 LINES
REFRIGERANT LINE SET, 3 LINES
CONDENSATE DRAIN
PIP
IN
G P
LA
N
BA
SE
ME
NT
M3
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
HVAC PLAN - FIRST FLOOR
FCU-3-9 FCU-3-10
FCU-3-1
FCU-3-5
FCU-3-6
FCU-3-8
FCU-3-4
FCU-4-3
FCU-4-1
FCU-4-2
S-1
320
S-1
320
S-1
170
S-1
210
S-1
70
S-1
225
S-1
355
S-2
105
S-1
320
S-1
210
FCU-4-5
S-1
340
S-1
350
S-1
355
S-1
200
S-1
440
S-2
50
x20 12(E)
F-4
FCU-3-7
FCU-4-4
x4 6
10
6
Ø6
x10 6
86
x20 8
14
6
S-1
335
Ø12
64
x4 4
x24 8
x10 8
x10 6 x10 8
x18 6
16
8
x10 8
x14 8
68
48
x4 4
x6 4
x10 8
10
6
x10 8
x8 8
Ø8
x8 6
x12 6
12
4
x12 8
x12 8
x10 8
x10 8
x6 4 x4 4
Ø12
Ø12
12Ø DN
x14 8
S-1
105
Ø6
66
x4 4
Ø6
Ø4
4
Ø4
x24 8
Ø10
x14 8
Ø10
x14 8
6x4, 45 CFM
25 CFM 30 CFM
25 C
FM
35 CFM
4x4, 50 CFM
4x3, 25 CFM
4Ø,
25 CFM
x10 6
S-1
105
T-1
TYP 2
S-1
105
x6 8
x12 8
4x3,
30 CFM
4x3, 30 C
FM
30 CFM
x4 4
4x3, 30 CFM
E-1
75
TYP OF 2
(E)18x12 DN
Ø10
Ø10
Ø12
FCU-4-6
20 CFM
127
126
125
123
124
129
130
131B
131D
STAIRS
100
117116
BATHROOM
103
VESTIBULE
119
113 112
106
107
105
108
LOBBY
115
CLOS
CLOS
CLOS
CLOSET
CONFERENCE
110
ELEVATOR
BATHROOM
104
STAIRS
Ø8
22x14 UP
TO CHASE
FCU-4-7
Ø8
S-3
120
x12 10
114
x16 8
x10 8
x18 8
1
12Ø, DN
S-1
475
101
FCU-3-3
1
102
Ø10
Ø10
x10 6
64
x4 4 x4 4
4
4
25 CFM 25 CFM
6x6
131A
Ø10
10Ø
FLEX DN
131C
x6 8
Ø8
x8 8
FCU-3-2
x8 6
x6 6
x10 6
S-1
75
S-1
150
x8 6Ø8
Ø8
x10 6
6x4,
40 CFM
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
GENERAL NOTES:
1. ALL RETURN GRILLES ARE TYPE R-1 UNLESS OTHERWISE NOTED.
2. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
HV
AC
P
LA
N
FIR
ST
F
LO
OR
M4
CONSTRUCTION NOTES:
XX
1. PROVIDE PLENUM OF HEIGHT AND WIDTH MATCHING FCU RETURN AIR OPENING
IN ORDER TO AVOID ABRUPT DUCT TRANSITIONS.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
PIPING PLAN - FIRST FLOOR
FCU-3-9
FCU-3-10
FCU-3-5
FCU-3-6
FCU-3-8
FCU-3-3
FCU-4-1
FCU-4-2
FCU-4-7
FCU-4-6
FCU-3-7
FCU-4-3
FCU-4-5
FCU-4-4
BS-4-1
FCU-3-1
TO HP-3
TO HP-4
1 1/2"D 1 1/2"D
1 1/2"D 1 1/2"D
1 1/2"D
1 1/2"D
1 1/2"D
1 1/2"D
DN
1 1/2"D
UP
1 1/2"D
UP&DN
1TYP
1 1/2"D
FCU-3-4
127
126
125
123
124
129
130
131C131B 131D
STAIRS
100
102
117
116
101
VESTIBULE
119
114113 112
106
107
105
108
STAIRS
LOBBY
115
CLOSET
CLOS
CLOS
CLOS
CLOSET
CONFERENCE
110
BATHROOM
104
ELEVATOR
131A
BATHROOM
103
BS-3-1
FCU-3-2
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTES:
XX
1. ALL INDIVIDUAL FAN COIL DRAINS SHALL BE SAME SIZE AS EQUIPMENT
CONNECTIONS. BASIS OF DESIGN IS 1 INCH NOMINAL.
PIP
IN
G P
LA
N
FIR
ST
F
LO
OR
M5
LEGEND:
REFRIGERANT LINE SET, 2 LINES
REFRIGERANT LINE SET, 3 LINES
CONDENSATE DRAIN
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
HVAC PLAN - SECOND FLOOR
FCU-5-3
FCU-5-4
FCU-5-6
FCU-6-1
FCU-6-3
FCU-6-4
FCU-6-7FCU-6-6
FCU-6-2
S-1
570
S-1
345
S-1
190
S-1
330
S-1
225
S-1
390
S-2
65Ø10
64
x6 4
Ø10
86
6
4
10Ø DN
x10 8
S-1
50
S-1
50
S-1
50
48
46
x12 8
12
6
FCU-6-5
x16 6
x8 8
18
8
12
6
Ø12
x8 6
x12 8
x16 10
14Ø DN
x10 8
Ø6
x8 8
x24 8
Ø6
x4 4
x10 8
x10 4
x12 6
x6 4
66
Ø4
Ø4
x10 8
20 CFM
55 CFM
30 CFM
4x4,
50 CFM
E-1
250
FCU-5-2
T-1
TYP 2
Ø6
S-1
45
Ø6
T-1
TYP 2
1
E-1
75
TYP 2
Ø12
Ø12
FCU-5-1
STAIRS
201
200213
212
211
209
208
207
206
BATHROOM
203
BATHROOM
205
CLOS
CLOS
ELEVATOR
CLOSET
STAIRS
S-1
345
15 C
FM
4
15 C
FM
24
22
14
22
FCU-5-5
FCU-5-7
S-1
415
S-1
430
S-1
335
S-1
335
S-1
355
S-1
80
S-1
260
S-1
260
S-1
260
S-1
260
S-1
355
Ø12
Ø12
x8 12
Ø12
Ø12 DN
x12 10
Ø12
x14 10
x26 12
214
x12 10
x6 6
Ø6
x14 12
12
12
Ø12 Ø12
x12 12 x12 8
Ø10
x12 10
x10 6
Ø10
x26 12
18
12
Ø10
(E)28x24 UP
Ø10
x10 6
x10 6
10
6
x16 12
44
x4 4
x8 8
4
44
4
15 C
FM
Ø4
15 C
FM
Ø12
S-1
340
x12 12
Ø16
Ø16
6x6, 120 CFM
6x6, 110 CFM
2
Ø16
2
Ø16
3x3, 25 C
FM
2
x16 8
2
S-3
55
4x6,
55 CFM
6x4
Ø6
S-3
55
x16 8
Ø6
x8 10
S-1
150
T-2
175
x8 10
x16 10
Ø6
Ø8
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTES:
XX
1. RECONNECT TO EXISTING DUCT GOING TO ROOF FAN.
2. PROVIDE PLENUM OF HEIGHT AND WIDTH MATCHING FCU RETURN AIR OPENING
IN ORDER TO AVOID ABRUPT DUCT TRANSITIONS.
GENERAL NOTES:
1. ALL RETURN GRILLES ARE TYPE R-1 UNLESS OTHERWISE NOTED.
2. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
HV
AC
P
LA
N
SE
CO
ND
F
LO
OR
M6
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
PIPING PLAN - SECOND FLOOR
FCU-5-6
FCU-6-1
FCU-6-4
FCU-6-7FCU-6-6
FCU-6-2
BS-5-1
FCU-6-5
UP TO
HP-5
UP TO HP-6
2"D
2"D
DN
1 TYP
1 1/2"D
DN
1 1/2"D
2"D
214
STAIRS
201
200213
212
211
209
208
207
206
BATHROOM
203
STAIRS
CLOS
CLOS
ELEVATOR
CLOSET
BATHROOM
205
FCU-5-1
FCU-5-3
FCU-5-2
FCU-5-4
FCU-5-7
FCU-5-5
FCU-6-3
2"D
BS-6-1
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTES:
XX
1. ALL INDIVIDUAL FAN COIL DRAINS SHALL BE SAME SIZE AS EQUIPMENT
CONNECTIONS. BASIS OF DESIGN IS 1 INCH NOMINAL.
GENERAL NOTES:
REFRIGERANT LINE SET, 2 LINES
REFRIGERANT LINE SET, 3 LINES
CONDENSATE DRAIN
PIP
IN
G P
LA
N
SE
CO
ND
F
LO
OR
M7
GENERAL NOTES:
1. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
HVAC PLAN - ROOF
V-1
F-1
F-3
F-2
HP-5
DOAU-1
F-5
HP-6
HP-2 HP-4
HP-1 HP-3
1 1/4" NG
D-1
ZS-1
3
21
3 3
3
3
2
1
(E) INTAKE
HOOD TO
REMAIN
x28 24
CONCENTRIC
ROOF VENT
FOR FURNACE
PER SECTION
3 ON DWG A1
4
5
(E) GUARDRAIL
6
OUTSIDE
AIR INTAKE
4
4
7
7
7
7
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTES:
XX
1. SUPPORT GAS PIPING ON ROOF USING ROLLER BEARING OR STRUT AND CLAMP
SUPPORT MOUNTED ON POLYCARBONATE BASE WITH BOTTOM OF PIPE MINIMUM
3.5 INCHES ABOVE ROOF, EQUAL TO MIRO INDUSTRIES.
2. PENETRATE THROUGH WALL ABOVE FIRST FLOOR CEILING, CONTINUED ON
DRAWING M5. EXTERIOR WALL PENETRATIONS SHALL BE SLEEVED AND CAULKED
WEATHER-TIGHT.
3. FIELD VERIFY EXISTING CURB DIMENSIONS AND PROVIDE CURB ADAPTER FOR
NEW FAN/VENTILATOR.
4. EQUIPMENT WITHIN 10 FT OF ROOF EDGE IS REPLACED IN KIND ON EXISTING
CURB.
5. ROUTE CONDENSATE LINE TO ROOF DRAIN.
6. PROVIDE OUTSIDE AIR UNIT ON FACTORY INSULATED DISCHARGE PLENUM FOR
SIDE DISCHARGE.
7. PROVIDE FLASHING PER SECTION 1 ON DRAWING A1.
HV
AC
P
LA
N
RO
OF
M8
GENERAL NOTES:
1. REFER TO DRAWING S1 FOR EQUIPMENT SUPPORT DETAILS.
04/20/15
IFB #152724-TW
SCALE:
0 1' 5' 10'
1/4"=1'-0"
ENLARGED MECHANICAL ROOM 26A
MECHANICAL ROOM
26
ACCU-1
AHU-1
1 1/4" NG UP
(E) x12 8
3/4" NG
12
8
(E)22x22
(E)45x16
TT-11
2
3
SCALE:
6"0 1' 2' 5'
1/2"=1'-0"
SECTION1
AHU-1
(E
)18x32
12
8
(E) SUPPORT STRUCTURE
REFER TO EQUIPMENT SUPPORT
FRAMING PLAN THIS DRAWING
D-2, ZS-2
D-3, ZS-31
1" CONDENSATE
DRAIN
(E)16x45
COMBUSTION AIR
AND VENT
USE LONG RADIUS
ELBOWS
(E) INTAKE AIR HOOD
3 F
T M
IN
3/4" NG
CONCENTRIC ROOF VENT KIT.
REFER TO DRAWING A1, SECTION 3.
SCALE:
1'6"3"0 9"
1 1/2"=1'-0"
SECTION2
L2x2x1/4
1/4"x1 3/4"x1 3/4"
PLATE, TYPICAL
(E)L2x2x1/4,
FIELD VERIFY
3/16
TYP
L2x2x1/4
(E)L2x2x1/4,
FIELD VERIFY
L2x2x1/4
SCALE: NONE
AIR HANDLING UNIT DETAIL
SUPPLY AIR DUCT
RETURN AIR DUCT
MAIN DRAINS
FLEX CONNECTOR
VE
NT
I
N
T
A
K
E
FLEX CONNECTOR
CASED DX COIL
NOTES:
1. DETAIL IS SCHEMATIC. COORDINATE AIRFLOW DIRECTION WITH PLANS AND
CONNECTIONS WITH ACTUAL INSTALLED EQUIPMENT.
2. PROVIDE CONCENTRIC ROOF VENT.
DRIP
LEG
TRAPS ARE SHOWN SCHEMATICALLY
FABRICATE PER MANUFACTURER'S
INSTRUCTIONS
REFRIGERANT
PIPING
NG
PIPING
UNION
VALVE
(E)7'-2"±
1'-10"± 2'-9"± 2'-7"±
FIELD VERIFY FIELD VERIFY
FIELD VERIFY
(E)3'-9"±
FIE
LD
V
ER
IF
Y
L2
x2
L2
x2
L2
x2
L2
x2
(E)L2x2x1/4 FRAME,
FIELD VERIFY
2
SCALE:
6"0 1' 2' 5'
1/2"=1'-0"
EQUIPMENT SUPPORT FRAMING PLAN
DRAIN PIPE FULL SIZE
SAME AS PAN CONNECTION
NOTE:
PROVIDE TRAP PER MANUFACTURER'S WRITTEN INSTRUCTIONS. WHEN INSTRUCTIONS ARE
NOT AVAILABLE, PROVIDE TRAP PER DETAIL. MINIMUM SIZE H1 AND H2 (IN INCHES) AS
FOLLOWS:
1. DRAW THRU UNITS
H1 = (FAN SUCTION PRESSURE) X 1.5
H2 = 1/2 H1 + 1/2"
2. BLOW THRU UNIT
H1 = 1/2"
H2 = (FAN DISCHARGE PRESSURE) X 1.5
3. ALL UNITS H1 + H2 AT LEAST 4".
4. DO NOT REDUCE SIZE OF CONDENSATE DRAIN.
5. DISCHARGE CONDENSATE TO GRADE OR FLOOR DRAIN WITH AIR GAP EQUAL TO 2 TIMES
PIPE DIAMETER.
6. VERIFY ADEQUATE HEIGHT ABOVE FLOOR, CONCRETE PAD, ROOF OR CEILING FOR
INSTALLATION AND MAINTENANCE OF TRAP.
H1
H2
NO
TE
6
UNIT OR DRAIN
PAN BOTTOM
SCALE: NONE
CONDENSATE DRAIN DETAIL
CLEANOUT PLUG
SLOPE DOWN
1/8"/FT MIN
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTES:
XX
1. MECHANICALLY OBSTRUCT RETURN AIR DAMPER TO PREVENT IT FROM CLOSING
MORE THAN REQUIRED TO ACHIEVE 400 CFM OUTSIDE AIR.
2. PROVIDE NATURAL GAS REGULATOR SIZED TO PROVIDE 30-400 MBH AT 10 INWG.
3. ROUTE REFRIGERANT LINE SET THROUGH ONE OF THE EXISTING SLEEVED WALL
PENETRATIONS AND SEAL WEATHER TIGHT. PATCH AND SEAL ADJACENT UNUSED
PENETRATION WEATHER-TIGHT.
HV
AC
P
LA
N
EN
LA
RG
ED
M
EC
HA
NIC
AL
R
OO
MS
M9
04/20/15
IFB #152724-TW
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
HV
AC
S
CH
ED
UL
ES
M10
FURNACE WITH SPLIT SYSTEM AC SCHEDULE
GENERAL
ELECTRICAL REFRIGERATION SYSTEM SUPPLY FAN
COOLING HEATING
FILTER EFFICIENCY
OUTDOOR
SOUND
RATING
DB
WEIGHT
LB
BASIS OF DESIGN (OR EQUAL)
MARK SERVING TYPE
NOM
SIZE
TONS
AMBIENT
DEG F DB
EAT DB/WB
DEG F
LAT DB/WB
DEG F
NET
TOTAL
MBH
NET
SENSIBLE
MBH
EAT
DEG F
LAT
DEG F
NO.
BURNER
STAGES
BURNER
INPUT
(MBH)
BURNER
OUTPUT
(MBH)
GAS
SUPPLY
(INWG)
V PH HZ
POWER
REFRIG-
ERANT
NO./TYPE
COMPRESSORS
NO REFRIG
CIRCUITS
TOTAL
CFM
OA
CFM
ESP
INWG
MOTOR
HPMCA MCB SIZE NO. SEER AFUE
AHU-1
AUDITORIUM
HORIZONTAL
4
120 1 60 --- 20
R-410a
---
1
1200 400 0.6 1 --- 82.3 / 68.2 57.7 / 57.0
44.8 32.9
49.7 109.3 2 88 85 4.5-13 20x25x1 1
15.5 98 76
250LENNOX SLP98UH090XV60C + CH33-49C-2F
ACCU-1 --- 208-230 3 60 18.6 30 1/SCROLL --- 95 --- --- ---
260
LENNOX SSB048H4
1. UNIT SHALL BE UL LISTED AND RATED IN ACCORDANCE WITH ARI.
2.PROVIDE REQUIRED LENGTH OF REFRIGERANT PIPING AND REFRIGERANT CHARGE.
3. PROVIDE CONTROL PANEL CAPABLE OF COMMUNICATING WITH BAS VIA BACNET.
4. PROVIDE SINGLE POINT POWER ENTRY AND CONTROLS TRANSFORMER AT AHU AND ACCU.
5.
REFRIGERATION CIRCUIT SHALL INCLUDE FILTER DRIER, EXPANSION VALVE, CHECK VALVES, SERVICE VALVES WITH GAUGE PORTS, AND HIGH AND LOW PRESSURE CUTOUTS.
6.
PROVIDE OUTDOOR THERMOSTAT, CRANKCASE HEATER, EVAPORATOR DEFROST CONTROL, LOW AMBIENT COOLING TO 30 DEG F, AND ANTI-SHORT-CYLE TIMER.
7. PROVIDE VIBRATION ISOLATION PADS FOR ACCU AND VIBRATION ISOLATION HANGERS FOR AHU.
8. PROVIDE CONDENSATE DRAIN PAN AND PVC DRAIN CONNECTION.
9. PROVIDE CONCENTRIC ROOF VENT KIT.
10. PROVIDE VARIABLE SPEED COMBUSTION AIR INDUCER AND VENT PROVING PRESSURE SWITCH.
11. PROVIDE 10-YEAR WARRANTY.
12. DISCONNECT SWITCHES AT AHU AND ACCU BY ELECTRICAL.
VRF FAN COIL UNIT SCHEDULE
MARK
ELECTRICAL
HIGH
FAN
CFM
SET
FAN
CFM
COOLING HEATING
BASIS OF DESIGN
(OR EQUAL)
TOTAL
MBH
SENS
MBH
EAT DEG F
DB/WB MBH
EAT
DEG FTAG STYLE V PH MCA MCB
FCU-D07A FCU-1-1B
DUCTED
CONCEALED
208-230 1 0.6 15 315 230 7 5.9 78/65 8.8 68 DAIKIN FXMQ07PAVJU
FCU-D07B FCU-2-6
DUCTED
CONCEALED
208-230 1 0.6 15 315 265 7 5.9 78/65 8.8 68 DAIKIN FXMQ07PAVJU
FCU-D07C FCU-3-2*
SLIM DUCT
CONCEALED
208-230 1 0.9 15 280 225 6.9 5.8 78/65 8.7 68 DAIKIN FXDQ07MVJU
FCU-D09A FCU-2-2
DUCTED
CONCEALED
208-230 1 0.6 15 315 315 8.8 7.1 78/65 10.9 68 DAIKIN FXMQ09PAVJU
FCU-D09B FCU-3-8*
SLIM DUCT
CONCEALED
208-230 1 0.9 15 280 280 8.8 6.7 78/65 11.1 68 DAIKIN FXDQ09MVJU
FCU-D12A FCU-1-1A
DUCTED
CONCEALED
208-230 1 1.4 15 450 450 11.1 8.8 78/65 14.0 68 DAIKIN FXMQ12PAVJU
FCU-D12BFCU-2-4, -1-5
DUCTED
CONCEALED
208-230 1 1.4 15 450 390 11.1 8.8 78/65 14.0 68 DAIKIN FXMQ12PAVJU
FCU-D18A FCU-2-3
DUCTED
CONCEALED
208-230 1 1.6 15 635 585 16.7 14.8 78/65 20.7 68 DAIKIN FXMQ18PAVJU
FCU-D18B FCU-4-3*
DUCTED
CONCEALED
208-230 1 1.6 15 635 530 16.7 14.8 78/65 20.7 68 DAIKIN FXMQ18PAVJU
FCU-D24AFCU-4-1, -4-2, -4-5, -6-3, -6-5
DUCTED
CONCEALED
208-230 1 1.8 15 690 690 22.2 14.4 78/65 28.0 68 DAIKIN FXMQ24PAVJU
FCU-D24B FCU-6-5
DUCTED
CONCEALED
208-230 1 1.8 15 690 615 22.2 14.4 78/65 28.0 68 DAIKIN FXMQ24PAVJU
FCU-D24CFCU-3-3, -3-4
SLIM DUCT
CONCEALED
208-230 1 1.4 15 580 580 22.2 15.5 78/65 28 68 DAIKIN FXDQ24MVJU
FCU-D30FCU-1-6, -2-5, -3-1, -5-6
DUCTED
CONCEALED
208-230 1 2.8 15 1100 810 27.8 21.6 78/65 35.2 68 DAIKIN FXMQ30PAVJU
FCU-D48 FCU-1-4
DUCTED
CONCEALED
208-230 1 3.4 15 1375 990 44.5 32.6 78/65 56 68 DAIKIN FXMQ48PAVJU
FCU-D72FCU-5-5, -5-7
DUCTED
CONCEALED
208-230 1 9.5 15 2050 2050 66.7 50.7 78/65 84.0 68 DAIKIN FXMQ72MVJU
FCU-C07A FCU-1-2 CEILING MOUNTED 208-230 1 0.8 15 320 250 6.9 5.3 78/65 8.7 68 DAIKIN FXZQ07MVJU9
FCU-C07BFCU-1-3, -5-4
CEILING MOUNTED 208-230 1 0.8 15 320 320 6.9 5.3 78/65 8.7 68 DAIKIN FXZQ07MVJU9
FCU-C09AFCU-3-7, -4-4
CEILING MOUNTED 208-230 1 0.8 15 320 250 8.8 6.3 78/65 11.1 68 DAIKIN FXZQ09MVJU9
FCU-C09BFCU-5-2, -5-3
CEILING MOUNTED 208-230 1 0.8 15 320 320 8.8 6.3 78/65 11.1 68 DAIKIN FXZQ09MVJU9
FCU-C09BFCU-3-6, -4-6
CEILING MOUNTED 208-230 1 0.3 15 440 350 8.8 7.8 78/65 10.9 68 DAIKIN FXFQ09TVJU
FCU-C12FCU-2-1, -3-9, -3-10
CEILING MOUNTED 208-230 1 0.3 15 440 350 11.1 8.6 78/65 14.0 68 DAIKIN FXFQ12TVJU
FCU-C15A FCU-5-1 CEILING MOUNTED 208-230 1 0.8 15 390 390 13.9 10.0 78/65 18.1 68 DAIKIN FXZQ15MVJU9
FCU-C15B FCU-3-5 CEILING MOUNTED 208-230 1 0.4 15 510 390 13.9 10.3 78/65 17.1 68 DAIKIN FXFQ15TVJU
FCU-C18 FCU-6-1 CEILING MOUNTED 208-230 1 0.6 15 740 620 16.7 14.8 78/65 20.7 68 DAIKIN FXFQ18TVJU
FCU-C24FCU-4-7, -6-6, -6-7
CEILING MOUNTED 208-230 1 0.7 15 775 615 22.2 14.1 78/65 28.0 68 DAIKIN FXFQ24TVJU
FCU-C36 FCU-6-2 CEILING MOUNTED 208-230 1 1.5 15 1165 915 33.3 25.8 78/65 41.5 68 DAIKIN FXFQ36TVJU
1. OUTDOOR CONDITIONS ARE 95 DEG F COOLING AND 13 DEG F HEATING.
2.
PROVIDE DC FAN MOTOR FOR DUCTED CONCEALED (FCU-DXX) UNITS.
3. PROVIDE HARD-WIRED WALL-MOUNTED THERMOSTAT WITH TEMERATURE SENSOR FOR EACH INDOOR UNIT OR GROUP OF CEILING MOUNTED (FCU-CXX) UNITS
WITHIN THE SAME ROOM.
4. PROVIDE DRAIN PAN FLOAT SWITCH WIRED TO SHUT UNIT OFF UPON HIGH WATER LEVEL.
5. PROVIDE INTEGRAL CONDENSATE PUMP WITH MINIMUM 18" VERTICAL LIFT.
6.
PROVIDE FRESH AIR KIT FOR CEILING MOUNTED (FCU-CXX) UNITS.
7. DISCONNECT SWITCH BY ELECTRICAL.
GENERAL NOTES:
1. REFER TO SPECIFICATIONS FOR ADDITIONAL REQUIREMENTS.
DEDICATED 100% OUTSIDE AIR UNIT SCHEDULE
TAG
ELECTRICAL REFRIGERATION SYSTEM SUPPLY FAN
COOLING HEATING
FILTER
SEER /
EER
SOUND
RATING
DB
WEIGHT
LB
BASIS OF DESIGN
(OR EQUAL)
EAT
DB/WB
DEG F
LVG COIL
DB/WB
DEG F
LAT
DB/WB
DEG F
NET
TOTAL
MBH
NET
SENSIBLE
MBH
EAT
DEG F
LAT
DEG F
INPUT
MBH
OUTPUT
MBH AFUE
GAS
SUPPLY
INWGV PH HZ
POWER
TYPE
(NO.) & TYPE
COMPRESSORS
NO.
CKTS
TOTAL
CFM
ESP
INWG HPMCA MCB SIZE NO.
DOAU-1
208-
230
3 60 74 90 R-410a
(1) DIGITAL
SCROLL
1 3090 0.75 1 95 / 75 55.5 / 55.3 56.3 / 55.6 188 122 13 84 293 234 0.8 6-10.5 20x25x2 4 11.1 EER 79 1870
AAON
RN-015-8-0-EA09-3
G4
1.
UNIT SHALL BE UL LISTED, RATED IN ACCORDANCE WITH ARI, FACTORY ASSEMBLED, INTERNALLY WIRED, AND RUN TESTED.
2. PROVIDE INSULATED DISCHARGE PLENUM BENEATH UNIT TO ALLOW SIDE DISCHARGE.
3. PROVIDE DOUBLE WALL CONSTRUCTION WITH R13 FOAM INSULATION AND STAINLESS STEEL DRAIN PAN. PROVIDE HINGED ACCESS DOORS WITH LOCKABLE HANDLES.
4. PROVIDE MICROPROCESSOR BASED CONTROLS CAPABLE OF INTERFACING WITH AN ASHRAE 135 / BACNET BAS.
5.
PROVIDE CLOGGED FILTER SWITCH; FAN CYCLING + FREEZE STAT; AND MODULATING HOT GAS REHEAT.
6. PROVIDE ECM MULTIPLE SPEED CONDENSER FAN.
7. PROVIDE DIRECT DRIVE SUPPLY FAN.
8. PROVIDE VARIABLE CAPACITY COMPRESSOR WITH 10-100% CAPACITY CONTROL.
9. PROVIDE 100% OUTSIDE AIR UNIT WITH NO RETURN AIR OPENING. PROVIDE BIRD SCREEN AND 2-POSITION OUTSIDE AIR SHUTOFF DAMPER.
10. PROVIDE 4-STAGE STAINLESS STEEL GAS HEAT EXCHANGER WITH 25 YEAR WARRANTY.
11. PROVIDE 5-YEAR WARRANTY FOR REFRIGERATION SYSTEM COMPONENTS.
12. DISCONNECT SWITCH BY ELECTRICAL.
VRF HEAT RECOVERY HEAT PUMP SCHEDULE
GENERAL ELECTRICAL REFRIGERATION SYSTEM COOLING HEATING
AHRI 1230
EER / IEER
SOUND
RATING
DB
WEIGHT
LB
BASIS OF DESIGN
(OR EQUAL)
TAG TYPE
NOM
SIZE
TONS
V PH HZ
POWER
TYPE
(NO.) & TYPE
COMPRESSORS
AMBIENT
DEG F DB
NET
MBH
AMBIENT
DEG F DB
NET
MBHMCA MCB
HP-1
HEAT
RECOVERY
8 208-230 3 60
38 45
R-410A
(2) INVERTER
SCROLL
95
98 13
89
13.1/ 21.0
60 525DAIKIN REYQ96TTJU
HP-2
HEAT
RECOVERY
6 208-230 3 60
30 35
R-410A
(1) INVERTER
SCROLL
95
73 13
68
13.4 / 20.8
58 507DAIKIN REYQ72TTJU
HP-3
HEAT
RECOVERY
10 208-230 3 60
43 50
R-410A
(2) INVERTER
SCROLL
95
123 13
95
12.6/20.7
62 527DAIKIN REYQ120TTJU
HP-4
HEAT
RECOVERY
10 208-230 3 60
43 50
R-410A
(2) INVERTER
SCROLL
95
121 13
95
12.6/ 20.7
60 527DAIKIN REYQ120TTJU
HP-5
HEAT
RECOVERY
14 208-230 3 60
62 70
R-410A
(2) INVERTER
SCROLL
95
172 13
120
11.3/19.5
65 694DAIKIN REYQ168TTJU
HP-6
HEAT
RECOVERY
12 208-230 3 60
55 70
R-410A
(2) INVERTER
SCROLL
95
147 13
115
11.9 / 20.7
62 694DAIKIN REYQ144TTJU
1. PROVIDE LOW-AMBIENT COOLING DOWN TO -4 DEG F.
2. PROVIDE SPRING ISOLATORS.
3. PROVIDE VARIABLE SPEED DC FAN MOTOR.
4. DISCONNECT SWITCH BY ELECTRICAL.
5. PROVIDE 6-YEAR WARRANTY FOR COMPRESSOR.
VRF BRANCH SELECTOR SCHEDULE
TAG STYLE
ELECTRICALBASIS OF DESIGN
(OR EQUAL)
V PH MCA MCB
BS-3-1, BS-5-1
10-PORT 208-230 1 0.4 15DAIKIN BS10Q54TVJ
BS-1-1, BS-4-1, BS-6-1
8-PORT 208-230 1 0.4 15DAIKIN BS8Q54TVJ
BS-2-1 6-PORT 208-230 1 0.4 15DAIKIN BS6Q54TVJ
1. DISCONNECT SWITCH BY ELECTRICAL.
AIR DEVICE SCHEDULE
MARK SERVICE TYPE MATERIAL FRAME NECK SIZE FINISH ACCESSORIES
BASIS OF DESIGN (OR EQUAL)
S-1 SUPPLY
CEILING DIFFUSER
(SQUARE)
ALUMINUM
24"x24" FULL
FACE LAY-IN
ROUND, SIZE
PER DWG
BAKED-ENAMEL
WHITE
INSULATE BACK SIDE
4-WAY, ADJUSTABLE, 3-CONE FACE, HIGH CAPACITY.
BASED ON PRICE MODEL ASCDA.
S-2 SUPPLY
CEILING DIFFUSER
(SQUARE)
STEEL
24"x24" PNL MNT
LAY-IN
ROUND, SIZE
PER DWG
BAKED-ENAMEL
WHITE
INSULATE BACK SIDE
4-WAY, ADJUSTABLE, 3-CONE FACE, HIGH CAPACITY.
BASED ON PRICE MODEL SCDA.
S-3
OUTSIDE AIR
SUPPLY
CEILING DIFFUSER
(SQUARE)
STEEL
24"x24" PNL MNT
LAY-IN
ROUND, SIZE
PER DWG
BAKED-ENAMEL
WHITE
INSULATE BACK SIDE
4-WAY, ADJUSTABLE, LOUVERED FACE. BASED ON
PRICE MODEL AMDA.
R-1, E-1, T-1
RETURN EXHAUST
TRANSFER
GRILLE ALUMINUM
24"x24" PNL MNT
LAY-IN
RECT, SIZE
PER DWG
BAKED-ENAMEL
WHITE
STEEL PANEL FOR PANEL
MOUNTING
1/2"x1/2"x1/2" EGGCRATE GRID. BASED ON PRICE
MODEL 80.
T-2 TRANSFER GRILLE STEEL
SURFACE
MOUNT
RECT, SIZE
PER DWG
BAKED-ENAMEL
WHITE
N/A
LONG BLADES, 3/4" SPACING, 35 DEG DEFLECTION.
BASED ON PRICE 630.
R-2 RETURN GRILLE ALUMINUM
24"x48" PNL MNT
LAY-IN
RECT, SIZE
PER DWG
BAKED-ENAMEL
WHITE
STEEL PANEL FOR PANEL
MOUNTING
1/2"x1/2"x1/2" EGGCRATE GRID. BASED ON PRICE
MODEL 80.
FAN AND VENTILATOR SCHEDULE
TAG LOCATION
EXISTING CURB
SIZE (IN)
SERVICE TYPE DRIVE
AIRFLOW
CFM
SP
INWG RPM
BRAKE
HP
SOUND
PRESSURE
DBA
MOTOR
NOTES
BASIS OF DESIGN (OR
EQUAL)
V PH HZ FLA HP
F-1 ROOF 26x26 VENTILATION ROOF CENTRIFUGAL FAN DIRECT 700 0.25 1672 0.07 56 115 1 60 3.4 1/6
1,3,4,6
GREENHECK G-090-VG
F-2 ROOF 22x22 TOILET EXHAUST ROOF CENTRIFUGAL FAN DIRECT 300 0.35 1693 0.04 51 115 1 60 3.4 1/6
1,3,4,6
GREENHECK G-075-VG
F-3 ROOF 18x18 TOILET EXHAUST ROOF CENTRIFUGAL FAN DIRECT 500 0.5 1602 0.08 55 115 1 60 3.4 1/6
1,3,4,6
GREENHECK G-090-VG
F-4 ROOM 103 --- TOILET EXHAUST CEILING CABINET FAN DIRECT 250 0.25 1050 --- 39 115 1 60 0.71 -
2,6
GREENHECK CSP-A290
F-5 ROOF 22x22 TOILET EXHAUST ROOF CENTRIFUGAL FAN DIRECT 250 0.25 1493 0.02 46 115 1 60 3.4 1/6
1,3,4,6
GREENHECK G-070-VG
F-6 15B TELECOM HEAT TRANSFER CEILING EXHAST FAN DIRECT 260 0.25 846 - <3 SONES 115 1 60 1.74 -
1, 5,6
GREENHECK SP-A410
V-1 ROOF 56x56 FRESH AIR RELIEF GRAVITY RELIEF VENTILATOR --- 400 0.025 --- --- --- ---
3,4,7
GREENHECK GRSR-36
1. PROVIDE VARIABLE SPEED CONTROL WITH MOTOR-MOUNTED POTENTIOMETER DIAL.
2. PROVIDE NEOPRENE HANGING BRACKETS.
3. PROVIDE CURB ADAPTER TO MOUNT ON EXISTING ROOF CURB. CONTRACTOR SHALL FIELD VERIFY EXISTING CURB SIZES.
4. PROVIDE BIRD SCREEN.
5.
PROVIDE WITH MOTOR THERMAL OVERLOAD, FILTER, DESIGNER GRILL, ROUND DUCT CONNECTOR, HANGING VIBRATION ISOLATORS.
6. DISCONNECT SWITCH BY ELECTRICAL.
7. PROVIDE 24V MOTORIZED DAMPER.
FAN AND VENTILATOR SCHEDULE
TAG LOCATION
EXISTING CURB
SIZE (IN)
SERVICE TYPE DRIVE
AIRFLOW
CFM
SP
INWG RPM
BRAKE
HP
SOUND
PRESSURE
DBA
MOTOR
NOTES
BASIS OF DESIGN (OR
EQUAL)
V PH HZ FLA HP
F-1 ROOF 26x26 VENTILATION ROOF CENTRIFUGAL FAN DIRECT 700 0.25 1672 0.07 56 115 1 60 3.4 1/6
1,3,4,6
GREENHECK G-090-VG
F-2 ROOF 22x22 TOILET EXHAUST ROOF CENTRIFUGAL FAN DIRECT 300 0.35 1693 0.04 51 115 1 60 3.4 1/6
1,3,4,6
GREENHECK G-075-VG
F-3 ROOF 18x18 TOILET EXHAUST ROOF CENTRIFUGAL FAN DIRECT 500 0.5 1602 0.08 55 115 1 60 3.4 1/6
1,3,4,6
GREENHECK G-090-VG
F-4 ROOM 103 --- TOILET EXHAUST CEILING CABINET FAN DIRECT 250 0.25 1050 --- 39 115 1 60 0.71 -
2,6
GREENHECK CSP-A290
F-5 ROOF 22x22 TOILET EXHAUST ROOF CENTRIFUGAL FAN DIRECT 250 0.25 1493 0.02 46 115 1 60 3.4 1/6
1,3,4,6
GREENHECK G-070-VG
F-6 15B TELECOM HEAT TRANSFER CEILING EXHAST FAN DIRECT 260 0.25 846 - <3 SONES 115 1 60 1.74 -
1, 5,6
GREENHECK SP-A410
V-1 ROOF 56x56 FRESH AIR RELIEF GRAVITY RELIEF VENTILATOR --- 400 0.025 --- --- --- ---
3,4,7
GREENHECK GRSR-36
1. PROVIDE VARIABLE SPEED CONTROL WITH MOTOR-MOUNTED POTENTIOMETER DIAL.
2. PROVIDE NEOPRENE HANGING BRACKETS.
3. PROVIDE CURB ADAPTER TO MOUNT ON EXISTING ROOF CURB. CONTRACTOR SHALL FIELD VERIFY EXISTING CURB SIZES.
4. PROVIDE BIRD SCREEN.
5.
PROVIDE WITH MOTOR THERMAL OVERLOAD, FILTER, DESIGNER GRILL, ROUND DUCT CONNECTOR, HANGING VIBRATION ISOLATORS.
6. DISCONNECT SWITCH BY ELECTRICAL.
7. PROVIDE 24V MOTORIZED DAMPER.
04/20/15
IFB #152724-TW
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
HV
AC
C
ON
TR
OL
S
M11
BUILDING AUTOMATION SYSTEM POINTS LIST
INST /
DEVICE
TAG INSTRUMENT TYPE
BAS
POINT
TYPE
LOCAL
AND/OR
REMOTE
VISIBILITY DESCRIPTION
DEDICATED OUTSIDE AIR UNIT (DOAU-1)
LCP
MANUFACTURER'S SENSORS AND I/O VIA UNITARY
CONTROL PANEL
DO UNIT START / STOP
DI R UNIT STATUS
AI OUTDOOR DRYBULB TEMPERATURE
AI OUTDOOR WETBULB TEMPERATURE
AI OUTDOOR RELATIVE HUMIDITY
AI OUTDOOR DEWPOINT
AO
SUPPLY AIR TEMPERATURE SETPOINT (WRITE)
AI R
SUPPLY AIR TEMPERATURE SETPOINT (READ)
AI DIGITAL COMPRESSOR POSITION
AI MODULATING GAS VALVE POSITION
AI R SUPPLY AIR TEMPERATURE
AI RETURN AIR TEMPERATURE
AI HOT GAS REHEAT VALVE POSITION
DI OUTSIDE AIR DAMPER OPEN/CLOSE POSITION
MI R MANUFACTURER ALARM CODE
AUDITORIUM SPLIT SYSTEM WITH FURNACE (AHU-1, ACCU-1)
D-1 DAMPER ACTUATOR DO GRAVITY VENTILATOR DAMPER OPEN/CLOSE
ZS-1 POSITION SWITCH DI R GRAVITY VENTILATOR DAMPER STATUS
D-2 DAMPER ACTUATOR AO OUTSIDE AIR DAMPER ACTUATOR POSITION
ZS-2 POSITION SWITCH DI R OUTSIDE AIR DAMPER STATUS
D-3 DAMPER ACTUATOR DO RETURN AIR DAMPER ACTUATOR POSITION
ZS-3 POSITION SWITCH DI R RETURN AIR DAMPER STATUS
TT-1 TEMPERATURE TRANSMITTER AI SPACE TEMPERATURE
GT-1 CO2 TRANSMITTER AI SPACE CO2 CONCENTRATION
GT-2 HUMIDITY TRANSMITTER AI SPACE HUMIDITY
LCP
MANUFACTURER'S SENSORS AND I/O VIA
UNITARY CONTROL PANEL
AO SPACE TEMPERATURE
AO SPACE HUMIDITY
DO OCCUPIED / UNOCCUPIED
AO
COOLING TEMPERATURE SETPOINT (WRITE)
AI R
COOLING TEMPERATURE SETPOINT (READ)
AO
HEATING TEMPERATURE SETPOINT (WRITE)
AI R
HEATING TEMPERATURE SETPOINT (READ)
DI COMPRESSOR STATUS
MI BURNER STATUS
DI SUPPLY FAN STATUS
DI COMBUSTION AIR FAN STATUS
MI L & R MANUFACTURER ALARM CODE
VRF INDOOR UNIT (EACH)
LCP
MANUFACTURER'S SENSORS AND I/O VIA
CENTRALIZED VRF CONTROL PANEL
DO START / STOP
DI R START / STOP STATUS
MO AIR CONDITIONING MODE
MI AIR CONDITIONING MODE STATUS
AV ROOM TEMPERATURE SETPOINT
AI R ROOM TEMPERATURE
AV THERMOSTAT ADJUSTMENT LOW LIMIT
AV THERMOSTAT ADJUSTMENT HIGH LIMIT
DI THERMOSTAT STATUS
DI COMPRESSOR STATUS
DI INDOOR FAN STATUS
DI L & R FILTER STATUS
DO FILTER RESET
DO REMOTE CONTROL ENABLE/DISABLE
MO AIR FLOW RATE SETPOINT
MI AIR FLOW RATE STATUS
DI L & R MANUFACTURER ALARM
MI L & R MANUFACTURER ALARM CODE
BUILDING FANS
TT-1 TEMPERATURE TRANSMITTER AI MECHANICAL ROOM TEMPERATURE
JS-1 MOTOR STARTER DO FAN F-1 START/STOP
ISL-1 CURRENT SWITCH LOW DI R FAN F-1 FAULT
TT-2 TEMPERATURE TRANSMITTER AI TELECOM ROOM TEMPERATURE
JS-2 MOTOR STARTER DO FAN F-6 START/STOP
ISL-2 CURRENT SWITCH LOW DI R FAN F-6 FAULT
JS-2 MOTOR STARTER DO FAN F-2 START/STOP
ISL-2 CURRENT SWITCH LOW DI R FAN F-2 FAULT
JS-3 MOTOR STARTER DO FAN F-3 START/STOP
ISL-3 CURRENT SWITCH LOW DI R FAN F-3 FAULT
JS-4 MOTOR STARTER DO FAN F-4 START/STOP
ISL-4 CURRENT SWITCH LOW DI R FAN F-4 FAULT
JS-5 MOTOR STARTER DO FAN F-5 START/STOP
ISL-5 CURRENT SWITCH LOW DI R FAN F-5 FAULT
GENERAL
CONTRACTOR SHALL BE SOLELY RESPONSIBLE FOR ACHIEVING THE SEQUENCE OF OPERATIONS AND SHALL PROVIDE ALL HARDWARE, CONDUIT, WIRING, SOFTWARE, AND PROGRAMMING REQUIRED TO DO SO. THE CONTRACTOR SHALL BE
RESPONSIBLE FOR ENSURING COMPATIBILITY AND COMMUNICATION BETWEEN THE BAS AND ALL EQUIPMENT.
CONTRACTOR SHALL SUBMIT CONTROL SYSTEM PRODUCT DATA INCLUDING HARDWARE, SOFTWARE, LOGIC AND WIRING DIAGRAMS, AND SEQUENCES OF OPERATION AS PART OF THE HVAC SUBMITTAL PACKAGE. ANY DISCREPANCIES WITH
OR RECOMMENDED CHANGES FROM WHAT IS INDICATED ON THESE DRAWINGS SHALL BE HIGHLIGHTED.
ALL SETPOINTS INDICATED IN THESE SEQUENCES OF OPERATIONS SHALL BE UNDERSTOOD TO BE USER ADJUSTABLE. CONTRACTOR SHALL COORDINATE WITH A/E AND OWNER AND PERFORM ALL INITIAL PROGRAMMING OF ZONE SENSORS,
THERMOSTATS, HUMIDISTATS, UNIT CONTROLLERS, CENTRAL CONTROLLERS, TIMERS, AND OTHER COMPONENTS AS REQUIRED. ANY HARDWARE OR SOFTWARE REQUIRED TO VIEW OR ADJUST THE I/O POINTS AT ANY PIECE OF EQUIPMENT
SHALL BE PROVIDED TO THE OWNER AT NO ADDITIONAL COST.
CONTROLS SUBCONTRACTOR SHALL BE IN ATTENDANCE DURING COMMISSIONING EFFORTS.
CONTRACTOR SHALL BE RESPONSIBLE FOR OWNER TRAINING OF THE BUILDING AUTOMATION SYSTEM AND ALL CONTROLS COMPONENTS.
BUILDING AUTOMATION SYSTEM (BAS)
ALL HVAC EQUIPMENT SHALL BE CONTROLLED AND MONITORED BY A DIRECT DIGITAL CONTROLS BUILDING AUTOMATION SYSTEM. ALL EQUIPMENT SHALL BE EQUIPPED WITH A UNITARY CONTROLLER CAPABLE OF COMMUNICATING WITH THE
BAS IF NOT CAPABLE OF DOING SO NATIVELY.
THE BAS SHALL HAVE THE ABILITY TO SCHEDULE OCCUPIED AND UNOCCUPIED MODES, NIGHT SETBACK, OPTIMAL START/STOP, MORNING WARM-UP, AND OTHER MODERN ENERGY EFFICIENCY STRATEGIES.
THE BAS SHALL ALLOW FOR THE OPERATOR TO RECEIVE NOTIFICATION OF ANY WARNINGS VIA PAGER AND EMAIL.
OCCUPANCY
BUILDING OCCUPANCY MODE SHALL BE DETERMINED BY THE BAS 7-DAY, 24-HOUR PROGRAM.
OCCUPIED TEMPERATURE SETPOINTS SHALL BE 78°F FOR COOLING AND 68°F FOR HEATING. UNOCCUPIED TEMPERATURE SETPOINTS SHALL BE 85°F FOR COOLING AND 55°F FOR HEATING.
AUDITORIUM SPLIT SYSTEM (AHU-1, ACCU-1)
DURING UNOCCUPIED PERIODS, THE OUTSIDE AIR AND GRAVITY VENTILATOR DAMPERS SHALL BE CLOSED AND THE SUPPLY FAN SHALL OPERATE ONLY UPON A CALL FOR HEATING, COOLING, OR DEHUMIDIFICATION.
DURING OCCUPIED PERIODS, THE GRAVITY VENTILATOR (GV-1) DAMPER SHALL BE OPEN AND THE SUPPLY FAN SHALL OPERATE CONTINUOUSLY. VENTILATION RATE DURING OCCUPIED HOURS SHALL BE DETERMINED BY SPACE CO2
CONCENTRATION. THE OUTSIDE AIR AND RETURN AIR DAMPERS SHALL MODULATE LINEARLY TO PROVIDE 75 CFM AT 400 PPM TO 400 CFM AT 1700 PPM. THE RETURN AIR DAMPER SHALL BE MECHANICALLY OBSTRUCTED TO PREVENT IT FROM
CLOSING MORE THAN IS REQUIRED TO ACHIEVE AN OUTSIDE AIR RATE OF 400 CFM.
THE ZONE TEMPERATURE SENSOR SHALL BE EQUIPPED WITH A HARDWARE OVERRIDE BUTTON TO TRIGGER A 3-HOUR OCCUPIED PERIOD. THE BAS FRONT END SHALL HAVE A SOFTWARE OVERRIDE BUTTON TO TRIGGER AN OCCUPIED
PERIOD OF ANY DURATION BETWEEN 1 HOUR AND 8 HOURS IN 1 HOUR INCREMENTS AS SELECTED BY THE OPERATOR.
UPON A CALL FOR COOLING BY THE SPACE TEMPERATURE SENSOR, THE COMPRESSOR SHALL CYCLE TO MAINTAIN THE SPACE TEMPERATURE AT SETPOINT. THE UNIT SHALL BE PREVENTED FROM SHORT CYCLING BY AN ANTI-SHORT CYCLE
TIMER. THE UNIT SHALL SHUT OFF UPON HIGH OR LOW REFRIGERANT PRESSURE OR DETECTION OF FROST ON THE INDOOR COIL.
UPON A CALL FOR HEATING BY THE SPACE TEMPERATURE SENSOR, THE COMBUSTION BLOWER SHALL PURGE THE HEAT EXCHANGER FOR 20 SECONDS. UPON PROOF OF AIRFLOW, THE BURNER SHALL IGNITE. AFTER THREE UNSUCCESSFUL
IGNITION ATTEMPTS, THE UNIT SHALL BE LOCKED OUT AND REQUIRE A MANUAL RESET. THE SUPPLY FAN SHALL CONTINUE RUNNING FOR A MINIMUM OF ONE MINUTE AFTER THE BURNER SHUTS OFF. THE UNIT AND GAS VALVE SHALL SHUT
OFF UPON LOSS OF AIRFLOW OR FLAME FAILURE.
UPON A CALL FOR DEHUMIDIFICATION BY THE SPACE HUMIDITY SENSOR WHEN THERE IS NO CALL FOR COOLING, THE UNIT SHALL ENTER A DEHUMIDIFICATION MODE. THE COMPRESSOR AND SUPPLY AIR FAN SHALL RUN CONTINUOUSLY
UNTIL EITHER THE HUMIDISTAT IS SATISFIED OR THE SPACE TEMPERATURE FALLS MORE THAN 3°F BELOW SETPOINT. HUMIDITY SETPOINT SHALL BE 50% DURING OCCUPIED AND UNOCCUPIED PERIODS.
DEDICATED OUTSIDE AIR UNIT (DOAU-1)
THE LOGIC FOR THE FOLLOWING SEQUENCE SHALL BE ACHIEVED AT THE MANUFACTURER'S LOCAL CONTROLLER, WITH THE EXCEPTION OF SUPPLY AIR TEMPERATURE RESET AND ALARM.
THE OUTSIDE AIR DAMPER SHALL BE OPEN AND THE UNIT SHALL OPERATE CONTINUOUSLY DURING OCCUPIED HOURS. THE OUTSIDE AIR DAMPER SHALL BE CLOSED AND THE UNIT SHALL BE OFF DURING UNOCCUPIED HOURS. THE UNIT SHALL
OPEN THE DAMPER AND VERIFY POSITION PRIOR TO STARTING THE SUPPLY FAN. THE UNIT SHALL ENTER HEATING, COOLING, VENTILATING, OR DEHUMIDIFICATION MODE BASED ON OUTDOOR TEMPERATURE AND HUMIDITY.
IN COOLING MODE, THE UNIT SHALL MODULATE ITS COOLING CAPACITY TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT SETPOINT, WHICH SHALL RESET FROM 60°F AT 60°F AMBIENT TO 55°F AT 75°F AMBIENT.
IN HEATING MODE, THE UNIT SHALL MODULATE ITS HEATING CAPACITY TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT SETPOINT, WHICH SHALL RESET FROM 55°F AT 55°F AMBIENT TO 65°F AT 40°F AMBIENT.
UPON A CALL FOR HEATING, THE COMBUSTION BLOWER SHALL PURGE THE HEAT EXCHANGER FOR 20 SECONDS. UPON PROOF OF AIRFLOW, THE BURNER SHALL IGNITE. AFTER THREE UNSUCCESSFUL IGNITION ATTEMPTS, THE UNIT SHALL BE
LOCKED OUT AND REQUIRE A MANUAL RESET. THE SUPPLY FAN SHALL CONTINUE RUNNING FOR A MINIMUM OF ONE MINUTE AFTER THE BURNER SHUTS OFF. THE UNIT AND GAS VALVE SHALL SHUT OFF UPON LOSS OF AIRFLOW OR FLAME
FAILURE.
IN DEHUMIDIFICATION MODE, THE UNIT SHALL MODULATE ITS COOLING CAPACITY TO MAINTAIN THE EVAPORATOR COIL SUCTION TEMPERATURE AND SHALL MODULATE THE HOT GAS REHEAT TO MAINTAIN THE SUPPLY AIR TEMPERATURE AT
SETPOINT, WHICH SHALL RESET BASED ON THE ACTIVE MODE AS DESCRIBED ABOVE.
A SOFTWARE ALARM SHALL INDICATE AT THE OPERATOR WORKSTATION IF THE SUPPLY AIR TEMPERATURE READ AND WRITE VALUES DIFFER FOR MORE THAN 1 MINUTE OR IF SUPPLY AIR TEMPERATURE DEVIATES FROM SETPOINT BY MORE
THAN +/- 5°F.
MECHANICAL ROOM VENTILATION FAN (F-1) AND TELECOM ROOM 15B VENTILATION FAN (F-6)
EXHAUST FAN SHALL OPERATE WHEN SPACE TEMPERATURE SENSOR CALLS FOR VENTILATION.
TOILET EXHAUST FANS (F-2,-3,-4,-5)
EXHAUST FANS SHALL OPERATE WHEN BUILDING IS IN OCCUPIED MODE. EXHAUST FANS SHALL BE OFF WHEN BUILDING IS IN UNOCCUPIED MODE.
VRF SYSTEMS
CONTRACTOR SHALL BE RESPONSIBLE FOR INTEGRATING THE VRF CENTRAL CONTROLLERS OF BOTH THE ADMINISTRATION AND SHOP BUILDINGS. THE ADMINISTRATION BUILDING CENTRAL CONTROLLER INSTALLED UNDER THIS PROJECT
HAS 50 INDOOR UNITS AND 6 OUTDOOR UNITS CONNECTED. THE EXISTING SHOP BUILDING CENTRAL CONTROLLER HAS 29 INDOOR UNITS AND 3 OUTDOOR UNITS CONNECTED.
WHERE A SPACE IS SERVED BY MULTIPLE CEILING UNITS, THE UNITS SHALL OPERATE IN TANDEM OFF A SINGLE THERMOSTAT.
INDOOR UNIT FANS SHALL OPERATE CONTINUOUSLY DURING OCCUPIED PERIODS AND SHALL CYCLE DURING UNOCCUPIED PERIODS.
OCCUPANTS SHALL HAVE THE ABILITY TO ADJUST SETPOINT WITHIN A LIMITED RANGE AS SET AT THE BAS.
SEQUENCES OF OPERATION
04/20/15
IFB #152724-TW
MIN. 20"
AFTER ELBOW
MIN. 20"
MIN 40" BETWEEN
MIN. 20"
(TYP) (TYP)
MIN. 20"
E
N
T
R
A
N
C
E
S
I
D
E
BRANCH SELECTOR
UNIT
E
L
E
C
T
R
I
C
B
O
X
S
E
C
T
I
O
N
(
O
N
S
I
D
E
O
F
U
N
I
T
SCALE: NONE
TYPICAL SEPARATION TUBE INSTALLATION FOR BRANCH REFRIGERANT PIPING
SCALE: NONE
PIPE CLEARANCES FOR INDOOR UNITS
SCALE: NONE
PIPING OFFSET BELOW OBJECT
SCALE: NONE
PIPE CLEARANCES FOR BRANCH SELECTOR UNITS
SCALE: NONE
MAXIMUM ROTATION OF HORIZONTAL SEPARATION TUBE
HORIZONTAL
PLANE
NOTE: THIS SAME HORIZONTAL APPLICATION APPLIES TO HEADERS.
SCALE: NONE
TYPICAL BRANCH SELECTOR PIPING
SCALE: NONE
EXPANSION LOOPS
45° MAX
45° MAX
4" M
AX
4" M
AX
GUIDE BRACKET
"L"
LENGTH "L" = INCHES OFFSET & RETURN
SLEEVE
NITROGEN
NITROGEN
SCALE: NONE
NITROGEN PURGING SET UP
REFRIGERANT PIPING
FROM OUTSIDE UNIT
OR INTERIOR BRANCH
SELECTORS
THE SEPARATION TUBE KITS ARE SUPPLIED WITH INSULATION INTENDED
TO FIT OVER THE MAIN BODY OF THE SEPARATION TUBE JOINT AFTER
INSTALLATION OF THE SEPARATION TUBE KIT IS COMPLETE.
BEFORE ELBOW
TO INTERIOR
TERMINAL UNIT
TO INTERIOR
TERMINAL UNIT
TO INTERIOR
TERMINAL UNIT
SEPARATION TUBES
TYPICAL VRF SEPARATION TUBE
REFRIGERANT BRANCH PIPING DEVICE
INSTALLED IN A TRUE AND LEVEL
POSITION PARALLEL TO CEILING BELOW
OR FLOOR STRUCTURE ABOVE
MAX 15° ROTATION DOWN
MAIN LINE SIDE
NOTES:
USE DEDICATED MANIFOLD, GAUGES, AND HOSES TO GUARD
AGAINST CROSS CONTAMINATION
SERVOCE PORT CHANGE DIAMETER 1/4" ENLARGED TO 5/16"
NOTE: IN CASES WHERE PIPING/TUBING NEEDS TO DROP BELOW
OBJECTS (BEAMS, DUCTS, CONDUITS, PIPES, ETC), PIPING SHALL HAVE
LARGE RADIUS TURNS AS INDICATED ABOVE (NO MORE THAN 45° PER
FITTING) TO PREVENT TRAPPING OF REFRIGERANT.
(LP) SUCTION LINE
(FROM INDOOR UNIT)
(HP) LIQUID LINE
(TO OUTDOOR UNIT)
NOTE: CONTRACTOR TO PROVIDE 5/16" THREADED ROD
HANGERS WITH DOUBLE SIDED RUBBER (1/2" THICK)
ISOLATORS AT EACH SUSPENSION BRACKET (4 EACH) ON
BRANCH SELECTOR FOR SUSPENSION OF UNIT
(HP) HOT GAS LINE
(FROM OUTDOOR UNIT)
INSTALL LINE SIZE REFRIGERANT SHUT-OFF
VALVES IN EACH LINE. SHUT-OFF VALVES
SHALL BE ZERO-CLEARANCE TYPE, ALL
BRONZE, BRAZED CONNECTIONS WITH 1/4"
SCHRADER TYPE SERVICE FITTING IN
VALVE. ALL VALVES SHALL INCORPORATE
DUAL STEM SEAL DESIGN WITH TEFLON
PACKING IN INTERNAL BALL TYPE RELIEF
PORT FOR DUAL DIRECTIONAL SHUT-OFF.
PROVIDE FULL FLOW PORTS ON ALL SIZES
1/4" THROUGH 7/8".
BEFORE ELBOWBEFORE ELBOW
HANGERS HANGERS
BRANCH
SELECTOR
UNIT
NOTE: CALCULATION FOR EXPANSION AND CONTRACTION
SHOULD BE BASED ON THE AVERAGE COEFFICIENT OF
EXPANSION OF COPPER WHICH IS 0.0001128 INCH PER FOOT PER
DEGREE F, BETWEEN 70°F AND 212°F.
(EXAMPLE: EXPANSION RESULTING FROM A 100°F RISE FOR EACH
100 FT OF ANY SIZE IS 1.128 INCHES)
EXPANSION DIMENSION "L" FOR OFFSET & RETURN TO BE BASED
ON THE EXPECTED EXPANSION INCHES PER DIMENSION OF PIPE.
LONG SWEEP
ELBOW OF
LONG BEND OF
SOFT COPPER
(TYP)
LONG SWEEP
ELBOW OF LONG
BEND OF SOFT
COPPER (TYP)
OUTSIDE UNIT SIDE
BRANCH SIDE
MAX 15° ROTATION UP
REFRIGERANT PIPING
PART TO BE BRAZED TAPE COPPER PIPE
PACKLESS VALVE
HIGH PRESSURE HOSE
PRESSURE-REDUCING VALVE
1/4"SERVICE FITTING
(TYP) EACH VALVE
(LP) SUCTION LINE (TO
INDOOR UNIT)
(HP) LIQUID LINE (FROM
OUTDOOR UNIT)
INSTALL BRANCH SELECTOR A MINIMUM
OF 12"x15-1/4" CLEAR FOR ELECTRICAL
SERVICE TO ELECTRIC BOX SECTION
RECOMMENDED EQUIPMENT CLEARANCES:
3"ABOVE
12" ENTERING (3 PIPE)
IN SPACE CONDITIONS THAT DO NOT ALLOW 3" ABOVE THE
DEVICE, MAINTAIN A 1" AIR SPACE BELOW UPPER DECK
AND INSTALL 1/2" FOAM INSULATION ON THE TOP OF THE
DEVICE.
SCALE: NONE
REFRIGERANT PIPE UNISTRUT SUPPORT
REFRIGERANT PIPE
UNISTRUT SUPPORT
ALUMINUM JACKET
OVER INSULATION
UNISTRUT PIPE
CLAMP
MIN. 20"
HANGERS
(TYP)
VRF INDOOR UNIT
BEFORE ELBOW
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
VR
F IN
ST
AL
LA
TIO
N D
ET
AIL
S
M12
04/20/15
IFB #152724-TW
HP-1
BS-1-1
55 FT
3/8"x 7/8" x 3/4"
FCU-1-1
45 FT
1/4" x 1/2"
FCU-1-2
60 FT
1/4"x1/2"
FCU-1-3
55 FT
1/4"x1/2"
FCU-1-4
30 FT
3/8" x 5/8"
FCU-1-5
40 FT
1/4" x 1/2"
FCU-1-6
45 FT
1/4" x 1/2"
HP-2
FCU-2-1
30 FT
1/4" x 1/2"
FCU-2-2
10 FT
1/4" x 1/2"
FCU-2-3
20 FT
1/4" x 1/2"
FCU-2-4
25 FT
1/4" x 1/2"
FCU-2-5
30 FT
3/8" x 5/8"
FCU-2-6
60 FT
1/4" x 1/2"
HP-3
FCU-3-1 FCU-3-2 FCU-3-3 FCU-3-4 FCU-3-5
40 FT
1/4" x 1/2"
FCU-3-6
30 FT
1/4" x 1/2"
FCU-3-7
20 FT
1/4" x 1/2"
FCU-3-8
20 FT
1/4" x 1/2"
FCU-3-9
30 FT
1/4" x 1/2"
FCU-3-10
25 FT
1/4" x 1/2"
HP-4
FCU-4-1 FCU-4-2 FCU-4-3 FCU-4-4 FCU-4-5 FCU-4-6 FCU-4-7
HP-5
FCU-6-1 FCU-6-2 FCU-6-3 FCU-6-4 FCU-6-5 FCU-6-6 FCU-6-7
BS-2-1
35 FT
3/8" x 3/4" x 5/8"
HP-1 REFRIGERANT PIPING
SYSTEM REFRIGERANT CHARGE: 40 LBS
HP-3 REFRIGERANT PIPING
SYSTEM REFRIGERANT CHARGE: 43 LBS
HP-4 REFRIGERANT PIPING
SYSTEM REFRIGERANT CHARGE: 40 LBS
HP-2 REFRIGERANT PIPING
SYSTEM REFRIGERANT CHARGE: 36 LBS
HP-5 REFRIGERANT PIPING
SYSTEM REFRIGERANT CHARGE: 43 LBS
HP-6 REFRIGERANT PIPING
SYSTEM REFRIGERANT CHARGE: 44 LBS
30 FT
5/8" x 1 1/8" x 7/8"
BS-5-1
FCU-5-1
25 FT
1/4" x 1/2"
60 FT
1/4" x 1/2"
55 FT
1/4" x 1/2"
FCU-5-2 FCU-5-3 FCU-5-4
35 FT
1/4" x 1/2"
FCU-5-6
35 FT
3/8" x 5/8"
FCU-5-7
20 FT
3/8" x 3/4"
FCU-5-5
20 FT
3/8" x 3/4"
3/8" x 5/8"
40 FT
1/2" x 1 1/8" x 7/8"
BS-3-1
30 FT
3/8" x 5/8"
35 FT
1/4" x 1/2"
50 FT
3/8" x 5/8"
55 FT
3/8" x 5/8"
70 FT
1/2" x 1 1/8" x 3/4"
BS-4-1
35 FT
3/8" x 5/8"
35 FT
3/8" x 5/8"
35 FT
1/4" x 1/2"
25 FT
1/4" x 1/2"
50 FT
3/8" x 5/8"
55 FT
1/4" x 1/2"
50 FT
3/8" x 5/8"
HP-6
45 FT
1/2" x 1 1/8" x 7/8"
BS-6-1
45 FT
1/4" x 1/2"
20 FT
3/8" x 5/8"
35 FT
3/8" x 5/8"
35 FT
3/8" x 5/8"
30 FT
3/8" x 5/8"
35 FT
1/4" x 1/2"
55 FT
1/4" x 1/2
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
VR
F P
IP
IN
G S
CH
EM
AT
IC
S
M13
GENERAL NOTES:
1. PIPING LENGTHS AND SIZES INDICATED ARE APPROXIMATE. CONTRACTOR SHALL
FIELD VERIFY PIPING LENGTHS AND COORDINATE SIZES WITH VENDOR FOR
ACTUAL INSTALLED EQUIPMENT.
04/20/15
IFB #152724-TW
TEMPERED WATER
COLD WATER
ANGLE STOP
(ASSE 1070)
THERMOSTATIC
MIXING VALVE
(TMV)
SINK
COLD WATER
ELECTRIC DISCONNECT FOR DHW-1.
VERIFY PHYSICAL SIZE AND
LOCATION WITH EC.
NOTE: DETAIL IS DIAGRAMMATIC TO SHOW WATER HEATER COMPONENTS.
COLD WATER
SOURCE
DWH-1
TUBE TO ICEMAKER
ICE MAKER
STOP VALVE
SCALE: NONE
DETAIL: WATER HEATER, MIXING VALVE, AND ICE-MAKER WATER CONNECTIONA
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
LE
GE
ND
A
ND
S
PE
CIF
IC
AT
IO
NS
P1
WATER HAMMER ARRESTOR
FLOOR DRAIN
WCOWALL CLEANOUT
WASTE OR SOIL
VENT
DOMESTIC HOT WATER
DOMESTIC COLD WATER
VTR (VENT THROUGH ROOF)
FLOOR CLEANOUT
FCO
BALANCING VALVE
DOMESTIC HOT WATER RETURN
1. PIPING SHALL BE CLEAN AND FREE OF DIRT AND SCALE AT TIME OF INSTALLATION.
2. COLD WATER, HOT WATER, S OIL, WASTE, AND VENT PIPING SHALL BE ROUTED CONCEALED IN WALLS , ABOVE CEILING, OR IN CABINETRY.
3. WATER PIPING LOCATED IN EXTERIOR WALLS SHALL BE ROUTED ON ROOM SIDE OF INSULATION.
4. REFER TO ARCHITECTURAL PLANS FOR DETAILS OF WALL PENETRATIONS.
5. ROUTE PIPING TO CLEAR STRUCTURES, DUCTWORK, CONDUIT, ETC. ALLOWING SPACE FOR PIPE HANGERS AND ACCESS TO VALVES. ALL PIPING SHALL BE INSTALLED SQUARE AND PLUMB.
6. PROVIDE 12"x12" ACCESS DOORS FOR ALL VALVES AND FOR CLEAN OUTS LOCATED ABOVE GYPSUM CEILING.
7. SANITARY CLEAN OUTS SHALL BE SET FLUSH WITH EITHER FINISHED FLOOR, FINISHED WALL, OR FINISHED GRADE . PROVIDE CLEAN OUT COVER PLATES.
8. PIPING SHALL BE SLEEVED THROUGH WALL AND FLOOR PENETRATIONS WITH SCHEDULE 40 STEEL SLEEVES. ALL PENETRATIONS THROUGH FIRE BARRIERS SHALL BE SEALED WITH A RATED
FIRE SYSTEM. SEE SYSTEM C-AJ-2576 ON M1.
9. USE TRANSITION FITTINGS TO JOIN DISSIMILAR PIPING MATERIALS.
10. ABOVE-GROUND SOIL, WASTE, AND VENT PIPE SHALL BE CAST NO-HUB CISPI 301, PIPE & FITTINGS WITH NO-HUB CISPI 310 COUPLINGS.
11. CAST IRON SOIL PIPE AND FITTINGS SHALL BE MARKED WITH THE COLLECTIVE TRADEMARK OF THE CAST IRON SOIL INSTITUTE (CISPI) AND BE LISTED BY NSF INTERNATIONAL.
12. SOIL, WASTE, AND VENT PIPE 2" AND SMALLER SHALL SLOPE AT 1/4" PER FOOT IN THE DIRECTION OF FLOW.
13. ABOVE-GROUND DOMESTIC WATER PIPE 1-INCH AND SMALLER SHALL BE PEX, ASTM F 877, SDR 9 TUBING. FITTINGS SHALL BE ASTM F 1807 METAL-INSERT TYPE WITH COPPER OR STAINLESS
STEEL CRIMP RINGS AND MATCHING PEX TUBE DIMENSIONS AND SHALL BE JOINED PER ASTM F 1807. MANIFOLD SHALL BE MULTIPLE OUTLET, PLASTIC OR CORROSION RESISTANT METAL
ASSEMBLY COMPLYING WITH ASTM F 877, WITH PLASTIC OR CORROSION RESISTANT METAL VALVE FOR EACH OUTLET. PROVIDE LOOP IN DISTRIBUTION PIPING AT EACH CHANGE OF DIRECTION
OF MORE THAN 90 DEGREES. PROVIDE VINYL COATED HANGERS AND SUPPORT AT MAXIMUM INTERVALS OF 32 INCHES HORIZONTALLY AND 48 INCHES VERTICALLY.
14. DRAWINGS DO NOT INDICATE PIPING SUPPORT LOCATIONS AND DETAILS. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING ALL NECESSARY PIPE SUPPORTS. SELECTIONS OF PIPE
SUPPORT TYPES, SIZES, LOCATIONS, AND SPACING SHALL CONFORM TO MSS SP-69 OR TABLE BELOW, WHICHEVER IS MORE STRINGENT. PIPE HANGER MATERIAL, DESIGN, AND MANUFACTURE
SHALL COMPLY WITH MSS SP-58.
PIPE SUPPORT (HORIZONTAL HANGER SPACING)
PVC 4'OC
COPPER 1 1/4" AND SMALLER 6'OC
COPPER 1 1/2" AND LARGER 10'OC
STEEL 1" AND SMALLER 6'OC
STEEL 1 1/4" - 2" 9'OC
STEEL 2 1/2" AND LARGER 12'OC
CAST IRON 5'OC
15. ALL ABOVE-GROUND DOMESTIC WATER PIPE SHALL BE INSULATED WITH ASTM C 534, TYPE I, CLOSED-CELL FLEXIBLE ELASTOMETRIC RUBBER, USING MIL-A-24179A, TYPE II CLASS I ADHESIVE: OR
ASTM C 547, TYPE I, GRADE A PRE-FORMED FIBERGLASS WITH FACTORY-APPLIED ASTM C 1136, TYPE I, ASJ-SSL VAPOR RETARDER JACKET, USING MIL-A-3316C, CLASS 2, GRADE A ADHESIVE.
ADHESIVE SHALL HAVE VOC CONTENT < 50 g/L AND SHALL BE APPLIED PER MANUFACTURER'S INSTRUCTIONS TO MAINTAIN VAPOR BARRIER INTEGRITY ACROSS JOINTS AND SEAMS. MINIMUM
INSULATION THICKNESS:
16. ALL DOMESTIC HOT AND COLD WATER PIPING, FITTINGS, AND VALVES SHALL BE NSF-61 LISTED. ALL PLUMBING COMPONENTS CONTACTING DOMESTIC WATER SHALL COMPLY WITH THE
REDUCTION OF LEAD IN DRINKING WATER ACT AND BE NSF-372 LISTED AS APPLICABLE. DOMESTIC WATER PIPE SHALL BE DISINFECTED PER ICP-610 AND VIRGINIA DEPARTMENT OF HEALTH
REGULATIONS.
CONSTRUCTION NOTE
AFF ABOVE FINISHED FLOOR
C DOMESTIC COLD WATER
CA COMPRESSED AIR
DEG DEGREE
DIA, Ø DIAMETER
DN DOWN
DP DRAIN PAN
DWG DRAWING
(E) EXISTING
°F DEGREE FAHRENHEIT
FCO FLOOR CLEANOUT
FD FLOOR DRAIN
FT FEET
GAL GALLON(S)
GPH GALLONS PER HOUR
GPM GALLONS PER MINUTE
H DOMESTIC HOT WATER
R DOMESTIC HOT WATER RETURN
HB HOSE BIBB
HD HEAD
HZ FREQUENCY
IN INCHES
INWG INCHES WATER GAUGE
KW KILOWATT
MAX MAXIMUM
MCA MINIMUM CIRCUIT AMPACITY
MCB MAXIMUM CIRCUIT BREAKER
MIN MINIMUM
MOCP MAXIMUM OVERCURRENT
PROTECTION
N/A NOT APPLICABLE
NC NORMALLY CLOSED
NG NATURAL GAS
NIC NOT IN CONTRACT
NO NORMALLY OPEN, NUMBER
NTS NOT TO SCALE
PSIG POUNDS PER SQUARE INCH GAGE
PSV PRESSURE SAFETY VALVE
PH PHASE
PRV PRESSURE REDUCING VALVE
S SOIL
SPEC SPECIFICATION
TP TRAP PRIMER
TYP TYPICAL
V VENT, VOLTS
VTR VENT THRU ROOF
W WASTE
WCO WALL CLEANOUT
WH FROST PROOF WALL HYDRANT
YCO YARD CLEANOUT
CONNECT TO EXISTING
INDICATES NUMBER OF
REVISIONS, CORRESPONDS
1
REVISION CLOUD
REVISION TRIANGLE
SYMBOLS
LEGEND
ABBREVIATIONS
1
PLUMBING SPECIFICATIONS
CONCENTRIC REDUCER
BUTTERFLY VALVE
ECCENTRIC REDUCER
WITH REVISION NOTE
1
PIPE CAP
PUMP
PRESSURE GAUGE
PIPE TURNING DOWN
PIPE TURNING UP
PIPE DOWN
GATE VALVE
PRESSURE REDUCING VALVE
PIPE FLOW ARROW
CHECK VALVE
BALL VALVE
BACKFLOW PREVENTER
THERMOMETERUNION
WYE STRAINER
SAFETY RELIEF VALVE
XX
PLUMBING FIXTURE SCHEDULE
EQUAL TO SIZE MOUNT CONNECTION SIZES REMARKS AND ACCESSORIES
MARK TYPE BASIS OF DESIGN MATERIAL COLOR WxDxH HEIGHT WASTE VENT CW HW BASIS OF DESIGN NOTES
P-1
ICE MAKER WALL
VALVE BOX
GUY GRAY
MIB 3
POWDER
COAT
WHITE 7"x7" 24" AFF 1/2" QUARTER TURN VALVE WITH 1/2" PEX CONNECTION 7
P-2
DOUBLE BOWL
KITCHEN SINK
ELKAY HARMONY
UNDERMOUNT
ELUH272010R
STAINLESS
STEEL
SATIN
FINISH
26 3/4"x20"x10"
COUNTER
TOP
1 1/2" 1 1/4" 3/8" 3/8"
3-HOLE DESIGN W/ UNDERCOATING, ELKAY SINGLE
LEVER PULL DOWN FAUCET LKAV4032CR WITH LK133
PLATE ESCUTCHEON PLATE
1 ,2, 3,
4, 5
P-3
DOUBLE BOWL
KITCHEN SINK
ELKAY HARMONY
UNDERMOUNT
ELUH272010R
STAINLESS
STEEL
SATIN
FINISH
26 3/4"x20"x10"
COUNTER
TOP
1 1/2" 1 1/4" 3/8" 3/8"
3-HOLE DESIGN W/ UNDERCOATING, ELKAY SINGLE
LEVER PULL DOWN FAUCET LKAV4032CR WITH LK133
PLATE ESCUTCHEON PLATE
2, 3, 4,
5
P-4
ICE MAKER VALVE
AND TUBING KIT
- - VARIES 1/4" KIT 1/2"
VALVE KIT TO INCLUDE ACCESSORIES TO MATE WITH
REFRIGERATOR ICEMAKER. COORDINATE WITH
APPLIANCES
6
1. PROVIDE T FITTING FOR DRAIN PAN TAP PIPING FOR ROOM 15 SINK INSTEAD OF P-TRAP. PROVIDE T FITTING ON THE FIXTURE SIDE OF THE CHECK VALVE. INSTALL PUMP IN ACCORDANCE TO
MANUFACTURERS' INSTRUCTIONS.
2. PROVIDE WITH ADJUSTABLE THERMOSTATIC MIXING VALVE (WATTS USG-B-M1) ADJUSTED TO 110 DEG F.
3. PROVIDE SINGLE LEVER KITCHEN FAUCET , 8" CENTER TO CENTER COVER PLATE, 9"-10" SWING SPOUT, 2.2 GPM @ 80 PSI AERATOR AND CHROME PLATED. WITH OR WITHOUT SPRAY PER SCHEDULE.
4. PROVIDE BRASSCRAFT OR EQUAL 1/2"PEX X 3/8" COMPRESSION CHROME PLATED SOLID BRASS ANGLE STOPS WITH ROUND WHEEL HANDLES AND FLEXIBLE COPPER OR BRAIDED STEEL SUPPLY
RISERS.
5. PROVIDE 1 1/4" PROFLO OR EQUAL 17 GA CHROME PLATED BRASS ADJUSTABLE P-TRAP, BRASS NUTS, WASHERS, BRASS TUBE AND CHROME PLATED BASKET STRAINER.
6. PROVIDE BRASSCRAFT OR EQUAL 1/2" PEX X 1/4" ICE MAKER TUBING KIT WITH FITTINGS TO CONNECT TO REFRIGERATOR ICE MAKER BEHIND REFRIGERATOR.
7. PROVIDE 1/4" ICE MAKER TUBING KIT WITH FITTINGS TO CONNECT VALVE AT VALVE BOX TO REFRIGERATOR ICE MAKER.
EQUIPMENT TAG P-1
CONTINUATION
INSTANTANEOUS DOMESTIC WATER HEATER SCHEDULE
TEMP
HEATER RISE FLOW CAPACITY MCA MOCP
TAG TYPE DEG F GPM KW VOLTS / PH
BASIS OF DESIGN (OR EQUAL)
DWH-1, -2 ELECTRIC INSTANT SINGLE ELEMENT
57 @ 1.0 GPM
1
8.3 40 50 208/1 EEMAX MODEL SP8208
1. PROVIDE 5-YEAR WARRANTY.
2. HIGH TEMPERATURE LIMIT SWITCH.
3. PROVIDE WATTS USG-B-M1 THERMOSTATIC MIXING VALVE. ADJUST OUTPUT TO 110°F.
4. PROVIDE FAUCET AERATOR WITH RESTRICTOR FOR GPM AS LISTED.
PUMP SCHEDULE
SUCTION x FLOW HEAD MOTOR
TAG LOCATION SERVICE TYPE FLUID
DISCHARGE (IN)
GPM FT HP AMPS VOLT/PHBASIS OF DESIGN OR EQUAL.
LP-1 RM 15 BREAK ROOM SINK LIFT PUMP DIRECT - VENTLESS WATER 1-1/2"X 1" 13 12 1/30 2.3 120/1 HARTELL LTA-1
1. APPROXIMATE DIMENSION: 7"WX8"DX14"H. BASIS OF DESIGN PUMP HAS CHECK VALVE INCLUDED. FIELD PROVIDE FOR MODELS WITHOUT INTEGRAL CHECK VALVE.
2. PUMP SHALL BE VENTLESS TYPE WITHOUT RESERVOIR WITH PRESSURE ACTIVATED ON SWITCH.
3. PROVIDE WITH 6 FOOT CORD AND PLUG FOR USE WITH UNDERCOUNTER GFCI RECEPTACLE.
4. PROVIDE SUBMITTALS INCLUDING MANUFACTURER INSTALLATION INSTRUCTIONS.
04/20/15
IFB #152724-TW
16
15 14 13
3
BATHROOM
5
CLOSET
CLOSET
HALL
TELECOM
15B
SCALE:
NORTH
0 1' 5' 10'
1/4"=1'-0"
ENLARGED WASTE PLUMBING PLAN - BASEMENT
STAIRS
HALL
1"W
(P
UM
PE
D A
BO
VE
C
EILIN
G)
2
(E)S
(E)C
1"W
(A
BO
VE
C
EILIN
G)
3
P-2
LP-1 BELOW
SCALE:
NORTH
0 1' 5' 10'
1/4"=1'-0"
ENLARGED DOMESTIC WATER PLAN - BASEMENT
16
15 14 13
3
BATHROOM
5
CLOSET
CLOSET
HALL
TELECOM
15B
STAIRS
HALL
(E)S
(E)C
1/2"C
1/2"C
3
P-4
1
P-2
1/2"C
DWH-1
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTES:
XX
1. PROVIDE VALVE (P-4) AND ASSOCIATED ICE MAKER TUBING AND ACCESSORIES.
CONNECT DOMESTIC COLD WATER STUB AT SINK TO REFRIGERATOR ICE MAKER.
SEE DETAIL A ON DRAWING P1.
2. 1 1/2" SINK WASTE PIPE SHALL DROP DOWN VERTICALLY INTO PUMP LP-1. THE
PUMP SHALL BE LOCATED UNDER THE SINK INSIDE NEW CABINETRY. 1" WASTE
LINE TO CONTINUE FROM PUMP ASSEMBLY AND INTO CEILING TO REACH TIE-IN
POINT AT EXISTING WASTE RISER.
3. PIPE TO SERVICE ROOM 107 ON FIRST FLOOR. REFER TO DRAWING P3 FOR
COMPLETE ROUTING.
GENERAL NOTES:
1. PLUMBING SHALL BE CONCEALED IN WALLS OR ABOVE CEILING UNLESS
OTHERWISE NOTED.
2. CUT WALLS AS REQUIRED TO ACCESS PLUMBING CHASES IF CHASE WALLS
EXTEND ABOVE CEILING. PROVIDE ACCESS PANELS.
3. PROVIDE BALL VALVE AT EACH WATER TAP.
BA
SE
ME
NT
P
LU
MB
IN
G P
LA
N
P2
Lic. No. 035249
STEVEN M. HOVIS
04/20/15
IFB #152724-TW
106 107
105
108
CLOSET
ELEVATOR
STAIRS
BATHROOM
104
BATHROOM
103
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
ENLARGED WASTE PLUMBING PLAN - FIRST FLOOR
(E)S, IN CHASE
BELOW
(E)C
1 1/2"W
(B
ELO
W F
LO
OR
)
1 1/2"W
(E)C
(E)S
3
1 1/2"W
(ABOVE CEILING)
P-3
1 1/4"V
1 1/4"V
(A
BO
VE
C
EILIN
G)
4
106 107
105
108
CLOSET
ELEVATOR
STAIRS
BATHROOM
104
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
ENLARGED DOMESTIC WATER PLUMBING PLAN - FIRST FLOOR
(E)W
(E)C, IN CHASE
BELOW
1/2"C
(B
ELO
W F
LO
OR
)
2
(E)S
(E)C
3
1/2"C
(ABOVE CEILING)
3/4"C
BATHROOM
103
DWH-2
P-3
P-4
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTES:
XX
1. PROVIDE FLOOR PENETRATION BELOW CABINETRY.
2. PROVIDE VALVE AT TAP. PROVIDE TUBING KIT (P-4) WITH NECESSARY FITTINGS
TO REFRIGERATOR ICE-MAKER. SEE DETAIL A ON DRAWING P1.
3. EXTEND PIPING FROM RISERS ABOVE THE CEILING TO PROVIDE PLUMBING ON
SECOND FLOOR. REFER TO DRAWING P4 FOR COMPLETE PLAN.
4. FIELD ROUTE TO NEAREST 1 1/2" OR LARGER VENT LINE ABOVE FIRST FLOOR
CEILING.
GENERAL NOTES:
1. PLUMBING SHALL BE CONCEALED IN WALLS OR ABOVE CEILING UNLESS
OTHERWISE NOTED.
2. CUT WALLS AS REQUIRED TO ACCESS PLUMBING CHASES IF CHASE WALLS
EXTEND ABOVE CEILING. PROVIDE ACCESS PANELS.
3. PROVIDE BALL VALVE AT EACH WATER TAP.
FIR
ST
F
LO
OR
P
LU
MB
IN
G P
LA
N
P3
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 1' 5' 10'
1/4"=1'-0"
ENLARGED DOMESTIC WATER AND VENT PIPING PLAN - SECOND FLOOR
STAIRS
200 213
209
CLOS
CLOSET
BATHROOM
205
214
CLOS
206
STAIRS
201
BATHROOM
203
(E)S
(E)C, IN CHASE
BELOW
1/2"C (BELOW FLOOR) 1/2"C (BELOW FLOOR)
P-1
2
P-4
1
1/2"C
(BELOW
FLOOR)
212
3/4"C (BELOW FLOOR)
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 035249
STEVEN M. HOVIS
CONSTRUCTION NOTES:
XX
1. PROVIDE ICE MAKER VALVE AND TUBING KIT (P-4). PROVIDE FLOOR PENETRATION
AND DOMESTIC COLD WATER SUPPLY FROM BELOW FLOOR. TUBING CONCEALED
BEHIND REFRIGERATOR.
2. PROVIDE WALL VALVE BOX (P-1) AND ASSOCIATED ICE MAKER TUBING. PROVIDE
FLOOR PENETRATION AND DOMESTIC COLD WATER SUPPLY FROM BELOW
FLOOR.
GENERAL NOTES:
1. PLUMBING SHALL BE CONCEALED IN WALLS OR ABOVE CEILING UNLESS
OTHERWISE NOTED.
2. CUT WALLS AS REQUIRED TO ACCESS PLUMBING CHASES IF CHASE WALLS
EXTEND ABOVE CEILING. PROVIDE ACCESS PANELS.
3. PROVIDE BALL VALVE AT EACH WATER TAP.
SE
CO
ND
F
LO
OR
P
LU
MB
IN
G P
LA
N
P4
Lic. No. 035249
STEVEN M. HOVIS
04/20/15
IFB #152724-TW
CONSTRUCTION NOTE
DEMOLITION NOTE
SYMBOLS ABBREVIATIONS
MDP-1
MDP-1
WALL-MOUNTED, SINGLE-GANG, TELECOMMUNICATIONS OUTLET BOX.
MOUNT 18" AFF UON. PROVIDE 1" CONDUIT WITH PULL STRING FROM
OUTLET BOX TO ACCESSIBLE AREA ABOVE CEILING.
FIRE ALARM CONTROL PANEL
FIRE ALARM STROBE. WALL-MOUNTED 80" AFF, UON.
NUMBER INDICATES CANDELA RATING.
FIRE ALARM COMBINATION HORN/STROBE. WALL-MOUNTED 80" AFF,
UON. NUMBER INDICATES CANDELA RATING.
FIRE ALARM MANUAL PULL STATION. MOUNT 48" AFF UON.
SPECIAL SYSTEMS
INDICATES MULTIPLE HOMERUN CIRCUITS FROM SINGLE
PANEL/CIRCUIT.
HOMERUN TO PANEL AND CIRCUIT NUMBER AS INDICATED.
CONDUCTOR AND RACEWAY SIZE AS INDICATED IN
PANELBOARD SCHEDULE, UON.
HOMERUN CIRCUIT TO OTHER CIRCUIT. CONDUCTORS AND
RACEWAY SIZE AS NOTED.
CONDUCTORS AND RACEWAYS
CONDUIT RUN EXPOSED OR ABOVE CEILING
QUAD RECEPTACLE, MOUNT 18" AFF, UON.
DUPLEX RECEPTACLE, WALL MOUNTED 18" AFF, UON.
WP = WEATHERPROOF WHILE-IN-USE WITH GFI
AC = MOUNT 3" ABOVE COUNTER BACKSPLASH
GFI = GROUND FAULT PROTECTION
EQUIPMENT CONNECTION
POWER
WALL MOUNTED, SINGLE-FACED EXIT SIGN. ARROW
INDICATES FACE CONFIGURATION.
CEILING MOUNTED, DOUBLE-FACED EXIT SIGN.
ARROW INDICATES FACE CONFIGURATION.
CEILING MOUNTED, SINGLE-FACED EXIT SIGN.
ARROW INDICATES FACE CONFIGURATION.
3 = 3-WAY SWITCH
SWITCH, SINGLE POLE UON, MOUNT 48" AFF UON.
RECESSED DOWNLIGHT.
2'x4' FLUORESCENT CEILING-MOUNTED FIXTURE. UPPERCASE
LETTER INDICATES FIXTURE TYPE. LOWERCASE LETTER
INDICATES SWITCHING
LIGHTING
WALL-MOUNTED FIXTURE.
SMOKE DETECTOR
SMOKE DETECTOR, DUCT MOUNTED
FACP
F
30
F
30
E
F
EX1
EX2
EX3
A
E
(3)#12
IN 3/4"C
PUSHBUTTON STATION. MOUNT 48" AFF, UON.
CONDUIT RUN CONCEALED UNDER FLOOR
4 = 4-WAY SWITCH
DOUBLE SWITCH, MOUNT 48" AFF, UON.
SPECIAL PURPOSE RECEPTACLE, AS NOTED, WALL MOUNT 18" AFF, UON.
a
f
e
a = LOWER CASE LETTER INDICATES SWITCHING
SPRINKLER FLOW SWITCH
TAMPER SWITCH
CEILING MOUNTED SPEAKERS
SIMPLEX RECEPTACLE, MOUNT 18" AFF, UON.
MOTOR RATED SWITCH. LOCKABLE TYPE.
JB JUNCTION BOX
CONDUIT TURNING DOWN
CONDUIT TURNING UP
A
a
B
b
B
b
1'x4' FLUORESCENT CEILING-MOUNTED FIXTURE.
1'x4' FLUORESCENT EMERGENCY FIXTURE. CONNECT
EMERGENCY BALLAST AHEAD OF SWITCH.
2'x4' FLUORESCENT EMERGENCY FIXTURE. CONNECT
EMERGENCY BALLAST AHEAD OF SWITCH.
2'x2' FLUORESCENT CEILING-MOUNTED FIXTURE.
C
c
C
c
2'x2' FLUORESCENT EMERGENCY FIXTURE. CONNECT
EMERGENCY BALLAST AHEAD OF SWITCH.
D
d
FLUORESCENT STRIP LIGHT FIXTURE.
RECESSED ROUND EMERGENCY DOWNLIGHT. CONNECT
EMERGENCY BALLAST AHEAD OF SWITCH.
F
f
WALL-MOUNTED EMERGENCY FIXTURE. CONNECT
EMERGENCY BALLAST AHEAD OF SWITCH.
F
f
DUAL-HEAD WALL-MOUNTED EMERGENCY LIGHT
S
D
FUSED SWITCH
400A
300A
CIRCUIT BREAKER
400AF
300AT
N E
TRANSFER SWITCH
LP3
120/208
3P/4W
225A
MCB
PANELBOARD PANELBOARD NUMBER
VOLTAGE
POLES, WIRES
AMP RATING
1
POINT OF CONNECTION
NEW-TO-EXISTING
LIMIT OF DEMOLITION
A AMPERE
AC ABOVE COUNTER
A/E ARCHITECT/ENGINEER
AF AMP FRAME
AT AMP TRIP
AFF ABOVE FINISHED FLOOR
APPROX APPROXIMATE
BCSD BARE C OPPER SOFT DRAWN
C CONDUIT
CB CIRCUIT BREAKER
DWG DRAWING
(E) EXISTING
ECB ENCLOSED CIRCUIT BREAKER
EMT ELECTRICAL METALLIC TUBING
FD FUSED DISCONNECT
FMC FLEXIBLE METALLIC CONDUIT
FTL FEED THROUGH LUGS
FVNR FULL VOLTAGE NON REVERSING
G, GND GROUND
GFI GROUND FAULT INTERRUPTING
HOA HAND-OFF-AUTO
HP HORSEPOWER
HVAC HEATING, VENTILATING, AND AIR CONDITIONING
JB JUNCTION BOX
KVA KILOVOLTAMPS
LFMC LIQUID-TIGHT FLEXIBLE METALL CONDUIT
MAX MAXIMUM
MC METAL CLAD CABLE
MCA MIN CIRCUIT AMPACITY
MCB MAIN CIRCUIT BREAKER
MIN MINIMUM
MLO MAIN LUGS ONLY
MOPD MAX OVERCURRENT PROTECTION DEVICE
N NEUTRAL
NF NON FUSED
NIC NOT IN CONTRACT
OCPD OVERCURRENT PROTECTION DEVICE
P PHASES OR POLES
PB PUSHBUTTON
RNC RIGID NONMETALLIC CONDUIT
RSC RIGID STEEL CONDUIT
R+R REMOVE AND REPLACE
SM SURFACE MOUNTED
STP SHIELDED TWISTED PAIR
TVSS TRANSIENT VOLTAGE SURGE SUPPRESSION
TYP TYPICAL
UG UNDERGROUND
UON UNLESS OTHERWISE NOTED
UTP UNSHIELDED TWISTED PAIR
V VOLTS
VFD VARIABLE FREQUENCY DRIVE
W WIRES
W/ WITH
W/O WITHOUT
WP WEATHERPROOF
XFMR TRANSFORMER
S
1
SM
F
FS
TS
GENERAL NOTES
WALL MOUNTED, SINGLE-FACED COMBO EXIT SIGN.
G
LEGEND
SWITCH SIZE
AMP FRAME
39 FCLIGHTING LEVEL IN FOOTCANDLES.
SWITCHBOX OCCUPANCY SENSOR
CEILING MOUNTED OCCUPANCY SENSOR
1. THESE DRAWINGS ARE SCHEMATIC IN NATURE AND INDICATE THE
GENERAL AND APPROXIMATE LOCATION OF EQUIPMENT AND
EXISTING CONSTRUCTION. FIELD-VERIFY ALL DIMENSIONS AND
LOCATIONS.
2. THESE DRAWINGS MAY NOT INDICATE ALL FITTINGS, PARTS AND
ACCESSORIES THAT ARE REQUIRED FOR A COMPLETE AND
FUNCTIONAL SYSTEM. NO EXCLUSION FROM OR LIMITATION IN
THE SYMBOLISM USED ON THE DRAWINGS FOR THE WORK, OR
THE LANGUAGE USED IN THE SPECIFICATIONS FOR THE WORK
SHALL BE INTERPRETED AS A REASON FOR OMITTING THE
APPURTENANCES OR ACCESSORIES NECESSARY TO COMPLETE
AND REQUIRED WORK, SYSTEM, OR ITEM OF EQUIPMENT.
3. ALL ELECTRICAL WORK ON THIS PROJECT SHALL BE INSTALLED IN
ACCORDANCE WITH THE 2009 VIRGINIA UNIFORM STATEWIDE
BUILDING CODE, NFPA 70-2008 (NATIONAL ELECTRICAL CODE),
AND NFPA 72-2007 (NATIONAL FIRE ALARM CODE), SAFETY CODE
FOR ELEVATORS AND ESCALATORS ANSI/ASME A17.1, 2010, AND
CONSTRUCTION AND PROFESSIONAL SERVICES MANUAL: CPSM
2013, REV 0 - 10/15/13 AND AMERICANS WITH DISABILITIES ACT:
ASAD, 9/15/2010.
4. COORDINATE ARRANGEMENT, MOUNTING, AND SUPPORT OF
ELECTRICAL EQUIPMENT TO AVOID INTERFERENCES WITH
ELECTRICAL AND OTHER TRADES. COORDINATE WORK WITH
EXISTING CONDITIONS INCLUDING BEAMS, COLUMNS, SITE
FEATURES, AND OTHER CONSTRUCTION WHETHER OR NOT SUCH
IS SHOWN ON THE DRAWINGS. SET SLEEVES IN CAST-IN-PLACE
CONCRETE AND MASONRY WALLS, AS THEY ARE CONSTRUCTED.
COORDINATE LOCATION OF ACCESS PANELS AND DOORS FOR
ELECTRICAL EQUIPMENT THAT ARE BEHIND FINISHED SURFACES
OR ARE OTHERWISE CONCEALED. COORDINATE AMPACITY,
VOLTAGE, PHASING, OVERCURRENT PROTECTION, AND LOCAL
DISCONNECT REQUIREMENTS WITH ACTUAL EQUIPMENT
PROVIDED.
5. MAINTAIN A SET OF AS-BUILT RED-LINE MARKUPS INDICATING
ACTUAL INSTALLATION. DELIVER TO OWNER AT CONCLUSION OF
PROJECT.
6. PROVIDE PRODUCT DATA SUBMITTALS FOR THE FOLLOWING:
PANELBOARDS, ENCLOSED SWITCHES, LUMINAIRES, DEVICES,
LIGHTING CONTROLS, MOTORS, AND AUTOMATIC TRANSFER
SWITCH COMPONENTS. MATERIALS INSTALLED PRIOR TO
OBTAINING AN APPROVED SUBMITTAL ARE AT CONTRACTOR'S
RISK.
7. CUT EXISTING CONSTRUCTION AS NEEDED FOR DEMOLITION AND
CONSTRUCTION. USE CUTTING METHODS THAT MINIMIZE DAMAGE
TO FINISHED AND ADJACENT SURFACES. PATCH EXISTING AND
NEW CONSTRUCTION AND REPAIR ALL DAMAGED SURFACES TO
MATCH EXISTING. PATCH UNUSED AND ABANDONED
PENETRATIONS.
8. CONTRACTOR SHALL ADVISE A/E IMMEDIATELY OF
DISCREPANCIES WITHIN DRAWINGS. MINOR DEVIATIONS FROM
THE PLANS MAY BE MADE TO AVOID MINOR CONFLICTS. WHERE
MAJOR CONFLICTS ARE ENCOUNTERED, THE AFFECTED WORK
SHALL NOT BE INSTALLED UNTIL THE CONFLICT HAS BEEN
RESOLVED. THE A/E IS NOT RESPONSIBLE FOR THE
CONSEQUENCES OF PROCEEDING WITH WORK BASED ON
CONTRACTOR INTERPRETATION OR ON DIRECTION FROM OTHER
PARTIES.
9. CONTRACTOR SHALL FIELD VERIFY LOADS OF EXISTING
BRANCH CIRCUITS AND SUBMIT SCHEDULE TO ENGINEER FOR
REVIEW PRIOR TO MODICATIONS TO PANELBOARDS
10. PROJECT CONTACT INFORMATION
OWNER'S REPRESENTATIVE: DANNY STEVENS 540-332-2169
UTILITY PROVIDER: DOMINION POWER
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
LE
GE
ND
A
ND
SP
EC
IF
IC
AT
IO
NS
E1
ELECTRICAL SPECIFICATIONS:
RACEWAYS AND BOXES
A.MATERIALS:
EMT - ANSI C80.3, COMPRESSION FITTING, MIN SIZE 3/4-INCH
RSC - ANSI C80.1, MIN SIZE 3/4-INCH
LFMC - MIN SIZE 3/4-INCH
MC - METAL CLAD CABLE
FMC - MIN SIZE 1/2-INCH
WIREWAYS - SHEET METAL WITH SCREW COVERS
B. INDOOR RACEWAY APPLICATIONS:
EXPOSED OR CONCEALED: EMT, UON
CONCEALED FIXTURE WHIPS: UP TO 72 INCHES OF FMC OR MC CABLE
BOXES AND ENCLOSURES: NEMA 250 TYPE 1, UON
C.USE UP TO 72 INCHES OF LFMC FOR CONNECTION TO VIBRATING
EQUIPMENT INCLUDING TRANSFORMERS AND MOTOR-DRIVEN
EQUIPMENT.
D.PROVIDE 65-LB TEST PULL STRING TIED OFF AT EACH END IN ALL EMPTY
CONDUITS.
WIRING METHODS
A. SINGLE CONDUCTORS SHALL BE COPPER, #12 MINIMUM CONDUCTOR
SIZE, SOLID FOR #10 AWG AND SMALLER, STRANDED FOR #8 AWG AND
LARGER. FOR ABOVE-GROUND APPLICATIONS USE THHN-THWN, 600VAC
INSULATION. FOR CIRCUITS WHERE ANY PART OF THE CIRCUIT IS
BELOW GRADE USE CONDUCTORS WITH XHHW-2, 600 VAC RATED
INSULATION.
B. INSTALL RACEWAYS AND CABLES CONCEALED WITHIN FINISHED WALLS,
CEILINGS, AND FLOORS, UON.
C.RACEWAY APPLICATIONS:
SERVICE CONDUCTORS: SINGLE CONDUCTORS IN RACEWAY, UON
FEEDER CONDUCTORS: SINGLE CONDUCTORS IN RACEWAY, UON
BRANCH CIRCUITS: SINGLE CONDUCTORS IN RACEWAY, UON
CLASS 2 CONTROL CIRCUITS: SINGLE CONDUCTORS IN RACEWAY, UON.
D. SINGLE PHASE 15A AND 20A BRANCH CIRCUITS THAT ARE CONCEALED
WITHIN INTERIOR PARTITIONS AND ABOVE CEILINGS MAY BE PLACED IN
MC CABLE.
E. CLASS 2 CONTROL CIRCUITS THAT ARE CONCEALED WITHIN INTERIOR
PARTITIONS AND ABOVE CEILINGS MAY UTILIZE OPEN WIRING METHODS
WITH PLENUM-RATED POWER LIMITED CABLE.
F. MINIMIZE SPLICES AND PLACE ONLY IN ACCESSIBLE JUNCTION BOXES
AND ENCLOSURES THAT ARE SIZED AND RATED FOR SUCH.
ELECTRICAL IDENTIFICATION
A.EQUIPMENT IDENTIFICATION: PROVIDE LABELS FOR PANELBOARDS,
DISCONNECT SWITCHES, AND AS ADDITIONALLY INDICATED. LABELS
SHALL BE LAMINATED ACRYLIC, WITH 1/2-INCH ENGRAVED BLACK
LETTERING ON 1-1/2-INCH WHITE STOCK ATTACHED WITH SCREWS.
B. DEVICE CIRCUIT IDENTIFICATION: PROVIDE SELF-ADHESIVE 1/4-INCH
HEIGHT CLEAR LABELS WITH 1/8-INCH BLACK PRINTED TEXT WITH EACH
RECEPTACLE INDICATING PANELBOARD AND BRANCH CIRCUIT.
C.RACEWAY AND CABLE LABELS: PROVIDE PRE-TENSIONED, PRE-PRINTED,
WRAPAROUND PLASTIC SLEEVES THAT ARE SIZED TO SUIT THE
DIAMETER OF THE ITEM IDENTIFIED.
D.USE VINYL OR VINYL-CLOTH, SELF-ADHESIVE, WRAPAROUND TYPE TAPE
MARKERS FOR WIRE. FOLLOW THESE WIRE COLOR CODING
CONVENTIONS.
CONDUCTOR 120/240V 208/120V 480/277V
PHASE A BLACK BLACK BROWN
PHASE B BLACK RED ORANGE
PHASE C --- BLUE YELLOW
NEUTRAL WHITE WHITE GRAY
GROUND GREEN GREEN GREEN
E. CONTRACTOR SHALL OPEN EVERY SWITCHBOARD, PANELBOARD, LOAD
CENTER, SAFETY SWITCH AND THE LIKE TO REMOVE ALL ORANGE “HIGH
LEG” MARKING TAPE AND ALL NOTES, LABELS ETC. REFERENCING
HIGH LEG, 120/240, THREE PHASE, DELTA SYSTEM. ALL FEEDER
CONDUCTORS SHALL BE RELABELED TO 120/208 VOLT COLOR CODE PER
THIS DRAWING AND EACH SWITCHBOARD, PANELBOARD, LOAD
CENTER, AND SAFETY SWITCH SHALL HAVE A NEW VOLTAGE
NAMEPLATE INSTALLED ON THE COVER/DOOR.
PENETRATIONS AND SLEEVES
A.FIRE-RATED ASSEMBLIES: APPLY FIRESTOPPING TO ELECTRICAL
PENETRATIONS OF FIRE-RATED FLOOR AND WALL ASSEMBLIES TO
RESTORE ORIGINAL FIRE-RESISTANCE RATING.
B. MASONRY WALLS AND FLOORS: IN CONCRETE SLABS AND WALLS,
INSTALL SLEEVES FOR PENETRATIONS UNLESS CORE-DRILLED HOLES
OR FORMED OPENINGS ARE USED. EXTEND SLEEVES INSTALLED IN
FLOORS 2 INCHES ABOVE FINISHED FLOOR LEVEL. SELECT SLEEVE SIZE
TO ALLOW FOR 1/2-INCH ANNULAR CLEAR SPACE BETWEEN RACEWAY
AND SLEEVES.
C. ABOVE-GRADE EXTERIOR WALL PENETRATIONS: SEAL PENETRATIONS
USING SLEEVES AND CAULK, UON.
D.ROOF PENETRATIONS: SEAL PENETRATIONS OF INDIVIDUAL RACEWAYS
AND CABLES WITH FLEXIBLE BOOT-TYPE FLASHING UNITS OR PITCH
POCKETS APPLIED IN COORDINATION WITH ROOFING.
SUPPORT AND ANCHORAGE
A.PROVIDE SUPPORT AND ANCHORAGE THAT ARE ADEQUATE IN TENSION,
SHEAR, AND PULLOUT FORCE TO RESIST MAXIMUM LOADS CALCULATED
OR IMPOSED WITH A MINIMUM STRUCTURAL SAFETY FACTOR OF FIVE.
B. STEEL SLOTTED SUPPORT SYSTEMS: COMPLY WITH MFMA-3 FACTORY
FABRICATED COMPONENTS FOR FIELD ASSEMBLY WITH FINISH
SUITABLE FOR THE ENVIRONMENT.
C.FOR ATTACHMENT TO CONCRETE AND SOLID MASONRY, USE
WEDGE-TYPE, ZINC-COATED STEEL EXPANSION ANCHOR FASTENERS.
DRILL HOLES AT LOCATIONS AND DEPTHS THAT AVOID REINFORCING
BARS. FOR CONNECTIONS TO HOLLOW MASONRY USE ALL-STEEL
SPRINGHEAD TYPE TOGGLE BOLTS.
D.FOR CLAMPING TO STEEL STRUCTURAL ELEMENTS USE WELDED STEEL
STUDS, BEAM CLAMPS OR SPRING-TENSION CLAMPS.
E. FOR CONNECTIONS TO WOOD USE LAG SCREWS OR THROUGH BOLTS.
F. HANGER RODS TO BE THREADED STEEL.
G.FOR CONNECTIONS TO LIGHT STEEL USE SHEET METAL SCREWS.
H.FOR ITEMS MOUNTED ON HOLLOW WALLS AND NONSTRUCTURAL
BUILDING SURFACES USE SLOTTED-CHANNEL RACKS ATTACHED TO
SUBSTRATE.
I. FASTEN HANGERS AND SUPPORTS SECURELY IN PLACE WITH
PROVISIONS FOR STRUCTURAL AND THERMAL MOVEMENT.
J. SEPARATE DISSIMILAR METALS AND METAL PRODUCTS FROM CONTACT
WITH WOOD OR CEMENTITIOUS MATERIALS BY PAINTING EACH METAL
SURFACE IN AREA OF CONTACT WITH A BITUMINOUS COATING OR BY
OTHER PERMANENT SEPARATION.
K. EMT AND RSC MAY BE SUPPORTED BY OPENINGS THROUGH
STRUCTURAL MEMBERS AS PERMITTED IN NFPA-70.
L. RACEWAY SUPPORT INTERVALS
M.RACEWAY SUPPORT INTERVALS
MAXIMUM DISTANCE MAXIMUM
RACEWAY DISTANCE FROM SUPPORT MAXIMUM
TYPE BOX TO FIRST SUPPORT INTERVAL LENGTH
MC CABLE 12 INCHES 54 INCHES NONE
FMC, LFMC 12 INCHES 54 INCHES 72 INCHES
RSC, RAC 36 INCHES 120 INCHES NONE
EMT 36 INCHES 120 INCHES NONE
ENCLOSED SWITCHES
A.NEMA KS 1, TYPE HD, WITH LOCKABLE HANDLE, INTERLOCKED WITH
COVER. IF INDICATED, PROVIDE SPECIFIED FUSES AND APPROPRIATE
CLIPS.
DEVICES
A.STRAIGHT BLADE RECEPTACLES: HEAVY-DUTY CONVENIENCE
RECEPTACLES, 125 V, 20 A: COMPLY WITH NEMA WD 1, NEMA WD 6
CONFIGURATION 5-20R, AND UL 498.
B. GFCI RECEPTACLES: STRAIGHT BLADE, FEED-THROUGH TYPE. COMPLY
WITH NEMA WD 1, NEMA WD 6, UL 498, AND UL 943, CLASS A, 125 V, 20 A,
AND INCLUDE INDICATOR LIGHT THAT IS LIGHTED WHEN DEVICE IS
TRIPPED.
C.SNAP SWITCHES: 20A, 600VAC, HEAVY DUTY, SINGLE POLE - SINGLE
THROW OR AS OTHERWISE INDICATED. COMPLY WITH NEMA WD 1 AND
UL 20.
D. WALL OCCUPANCY SENSORS: SEE SPECIFICATION BOOK FOR
REQUIREMENTS.
E. CEILING MOUNTED OCCUPANCY SENSORS: SEE SPECIFICATION BOOK
FOR REQUIREMENTS.
G.WALL COVER PLATES: PROVIDE SINGLE AND COMBINATION TYPES TO
MATCH CORRESPONDING WIRING DEVICES. FOR FINISHED SPACES
PROVIDE STEEL WITH WHITE BAKED ENAMEL. FOR UNFINISHED SPACES
PROVIDE GALVANIZED STEEL. FOR WET OR DAMP LOCATIONS PROVIDE
THERMOPLASTIC "WEATHERPROOF WHILE IN USE" LOCKABLE COVER.
F. DEVICE COLORS: AS INDICATED.
LIGHTING
A. ALL LUMINAIRES SHALL BE PROVIDED WITH LAMPS.
B. EXIT SIGNS SHALL OPERATE FOR 90 MINUTES. EXIT SIGNS SHALL
INCLUDE INTEGRAL BATTERY CHARGER, BATTERY, AND TEST
PUSHBUTTON.
C.SEE SPECIFICATION BOOK FOR ADDITIONAL REQUIREMENTS.
PANELBOARDS
A.NEW PANELBOARDS: PROVIDE AS SCHEDULED. PANELBOARDS SHALL
HAVE COPPER PHASE BUSSES, COPPER GROUND BUS, AND 100
PERCENT RATED COPPER NEUTRAL BUS. ALL CIRCUIT BREAKERS ARE
TO BE BOLT-ON TYPE. ALL ENCLOSURES ARE TO HAVE
DOOR-WITHIN-DOOR OR HINGED FRONT COVER.
B. MODIFIED PANELBOARDS: PROVIDE OR RELOCATE BREAKERS AS
INDICATED. NEW BREAKERS SHALL BE FROM SAME MANUFACTURER AS
PANELBOARD AND SHALL HAVE SUITABLE FAULT CURRENT RATINGS.
C.PROVIDE TYPED PANELBOARD INDEXES FOR ALL NEW AND MODIFIED
PANELBOARDS.
D.PROVIDE A 2” WIDE SAFETY YELLOW PAINTED LINE ON ALL CONCRETE
FLOORS IN FRONT OF NEW AND MODIFIED PANELBOARDS WITHIN
ELECTRICAL AND MECHANICAL ROOMS TO INDICATE THE ELECTRICAL
WORKING SPACE. THE WIDTH OF MARKED SPACE SHALL BE THE WIDTH
OF THE EQUIPMENT OR 30” WHICHEVER IS GREATER. THE DEPTH OF
THE MARKED SPACE SHALL BE 36” FOR 120 AND 208 VOLT SYSTEMS AND
48” FOR 277 AND 480 VOLT SYSTEMS. CENTERED WITHIN THE OUTLINE
OF THE WORKING SPACE STENCIL “NO STORAGE - ELECTRICAL
WORKING SPACE” IN 2” HIGH SAFETY YELLOW LETTERS.
E. ALL NEW SURFACE MOUNTED PANELBOARDS TO HAVE A MAXIMUM
DEPTH OF 4”. WHERE SURFACE-MOUNTED PANELBOARDS ARE
REPLACING FLUSH PANELBOARDS, RETAIN CAN FROM REMOVED
PANELBOARD. ROUTE EXISTING FEEDER AND BRANCH CIRCUIT FROM
EXISTING CAN INTO BACK OF REPLACEMENT PANELBOARD. WHERE
SURFACE PANELBOARDS REPLACE FLUSH PANELBOARDS IN
CORRIDORS AND FINISHED SPACES, PROVIDE SHEET METAL
ENCLOSURE WITH SCREW-ON COVER FROM TOP OF PANELBOARD TO
CEILING TO CONCEAL NEW RACEWAYS. SHEET METAL ENCLOSURE TO
BE SAME WIDTH AND DEPTH AS PANELBOARD AND PAINTED TO MATCH
EXISTING WALL
F. SEE SPECIFICATION BOOK FOR ADDITIONAL REQUIREMENTS.
GROUNDING
A.PROVIDE GROUNDING IN ACCORDANCE WITH NATIONAL ELECTRICAL
CODE AND ADDITIONALLY AS INDICATED.
04/20/15
IFB #152724-TW
A
A
A
A
A
A
A
A
A
A
A
A
D
E E
E E
D D DD
D D
D D
D
D D
E
E
E
E
E
E E E
EEEEEEEEE
D
D
D
D
C
C
DC C
B B
B B
B B
B B
AA
A A
A A
AA
A1
E
E
DD
EX
EX
EX
EX
EX
EX
EX
EX2
EX
EX2
EX
EX
EX
EX
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
BASEMENT LIGHTING PLAN
F F
F F
EX2
E
E
56 FC
29 FC
52 FC
70 FC
52 FC
41 FC
46 FC
59 FC
54 FC
61 FC64 FC
56 FC 52 FC
43 FC
49 FC
64 FC
49 FC
58 FC55 FC
40 FC
60 FC
56 FC
33 FC
28 FC
33 FC
E
C
C
B B
C CC
D
E1
(E)150KW
GENSET
(E)400A, 3P ATS
ORIGINALADDITION
E
E
E
EX
C
C
B
B B
B B
B B
B
B
B
B
B
B
B
B
B
116
15
14
13
17
18
19
12A
12B
11
10
32
22
21
20
C
C
D
AA
A
47 FC
52 FC
52 FC
D
D
D
D
E
23
C
C
C
C
A
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
DRAWING NOTES:
1. EXISTING EGRESS LIGHTING CONSISTS OF UNITARY DUAL-HEAD WALL
MOUNTED FIXTURES. THIS PROJECT DOES NOT TOUCH OR ALTER THE EXISTING
SCHEME. AS SUCH, THEIR LOCATIONS ARE NOT INDICATED ON PLANS.
2. IN SPACES WHERE NO LIGHTING IS SHOWN, THE EXISTING LIGHTING IS
RETAINED AND UNALTERED BY THIS PROJECT.
3. WHERE SWITCHBOX OCCUPANCY SENSORS ARE INDICATED, MOUNT THEM
WITHIN THE EXISTING SWITCHBOXES.
4. WHERE CEILING MOUNTED OCCUPANCY SENSORS ARE SHOWN, PROVIDE A
BLANK COVERPLATE OVER THE ABANDONED SWITCHBOX.
5. CONNECT EXIT SIGNS TO THE UNSWITCHED LEG OF THE NEAREST LIGHTING
CIRCUIT SERVING THE SPACE.
6. INSTALL RETAINED SPEAKERS AND SMOKE DETECTORS BACK INTO THEIR
ORIGINAL LOCATIONS AFTER THE CEILING IS REPLACED.
7. IN SPACES WHERE NO SWITCHING IS SHOWN, RETAIN EXISTING SWITCHING
ARRANGEMENT.
LIG
HT
IN
G P
LA
N - B
AS
EM
EN
T
E2
8. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
04/20/15
IFB #152724-TW
E
E E E E E E E E E
E
E
E
E
C
C
B B
B B
A
A
B B
B B
D
D
EEE
AAAAAA
DD
A
A
A
A
A
A
C
C
C
C
C
C
C
C
C
C
A1
A
A
D
E
E
EE
EE
C
C
C
A
A
A
A
A
A
A
A
A
A
A
A
EX2
EX2
EX
EX
EX
(E) PANEL "L1"
FF
F
F F F
F F F
58 FC
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
LIGHTING PLAN - FIRST FLOOR
61 FC60 FC
49 FC
52 FC
58 FC 58 FC
56 FC
56 FC
56 FC
33 FC
56 FC 60 FC60 FC
53 FC
47 FC
60 FC
60 FC
62 FC
57 FC
63 FC
56 FC
54 FC
61 FC
36 FC
33 FC
40 FC
60 FC
ORIGINALADDITION
C
C
127126
125123
124
129
130
131C
131B
131D
HALL
STAIRS
100 102 117
116
101
BATHROOM
103
HALL
114
113
112
106
107
105
108
STAIRS
LOBBY
115
CLOSET
CLOS
CLOS
CLOS
HALL
CLOSET
HALL
CONFERENCE
110
ELEVATOR
HALL
D
D
D
C
C
59 FC
DD
A
A
C
C
A
A
A
A
BATHROOM
104
VESTIBULE
119
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
LIG
HT
IN
G P
LA
N - F
IR
ST
F
LO
OR
E3
DRAWING NOTES:
1. EXISTING EGRESS LIGHTING CONSISTS OF UNITARY DUAL-HEAD WALL MOUNTED
FIXTURES. THIS PROJECT DOES NOT TOUCH OR ALTER THE EXISTING SCHEME.
AS SUCH, THEIR LOCATIONS ARE NOT INDICATED ON PLANS.
2. IN SPACES WHERE NO LIGHTING IS SHOWN, THE EXISTING LIGHTING IS RETAINED
AND UNALTERED BY THIS PROJECT.
3. WHERE SWITCHBOX OCCUPANCY SENSORS ARE INDICATED, MOUNT THEM
WITHIN THE EXISTING SWITCHBOXES.
4. WHERE CEILING MOUNTED OCCUPANCY SENSORS ARE SHOWN, PROVIDE A
BLANK COVERPLATE OVER THE ABANDONED SWITCHBOX.
5. CONNECT EXIT SIGNS TO THE UNSWITCHED LEG OF THE NEAREST LIGHTING
CIRCUIT SERVING THE SPACE.
6. INSTALL RETAINED SPEAKERS AND SMOKE DETECTORS BACK INTO THEIR
ORIGINAL LOCATIONS AFTER THE CEILING IS REPLACED.
7. IN SPACES WHERE NO SWITCHING IS SHOWN, RETAIN EXISTING SWITCHING
ARRANGEMENT.
8. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
LIGHTING PLAN - SECOND FLOOR
E E E E E
E
E
E
E
D
D
D
D
D
BB
B
B
DD
D
D
DDD
DDD
DDD
DD
D
D
C
D
D
D
D
D
D
DD
D
D
DD
D
B
B
C
C
D
EX2
EX
EX2
EX
EX
EX2
66 FC
59 FC
50 FC
57 FC
58 FC
51 FC
61 FC
59 FC55 FC
55 FC
42 FC
35 FC
52 FC
32 FC
23 FC
C
C
B
B
B
D
D D
DD
D
C
D
D
D
DDD
DD
A A A
C
C
C
C
D
C
D
214
215
STAIRS
201
200
213
212
211
209
208
207
206
BATHROOM
203
HALL
STAIRS
HALL
HALL
CLOS
CLOS
ELEVATOR
CLOSET
BATHROOM
205
B
C
B
52 FC
216
52 FC
217
219
218
52 FC
57 FC
52 FC
B
C
C
D D D
C
C
D D D D
D
DDDD
D
D
D
D
A
D
B
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
LIG
HT
IN
G P
LA
N - S
EC
ON
D F
LO
OR
E4
DRAWING NOTES:
1. EXISTING EGRESS LIGHTING CONSISTS OF UNITARY DUAL-HEAD WALL MOUNTED
FIXTURES. THIS PROJECT DOES NOT TOUCH OR ALTER THE EXISTING SCHEME.
AS SUCH, THEIR LOCATIONS ARE NOT INDICATED ON PLANS.
2. IN SPACES WHERE NO LIGHTING IS SHOWN, THE EXISTING LIGHTING IS RETAINED
AND UNALTERED BY THIS PROJECT.
3. WHERE SWITCHBOX OCCUPANCY SENSORS ARE INDICATED, MOUNT THEM
WITHIN THE EXISTING SWITCHBOXES.
4. WHERE CEILING MOUNTED OCCUPANCY SENSORS ARE SHOWN, PROVIDE A
BLANK COVERPLATE OVER THE ABANDONED SWITCHBOX.
5. CONNECT EXIT SIGNS TO THE UNSWITCHED LEG OF THE NEAREST LIGHTING
CIRCUIT SERVING THE SPACE.
6. INSTALL RETAINED SPEAKERS AND SMOKE DETECTORS BACK INTO THEIR
ORIGINAL LOCATIONS AFTER THE CEILING IS REPLACED.
7. IN SPACES WHERE NO SWITCHING IS SHOWN, RETAIN EXISTING SWITCHING
ARRANGEMENT.
8. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
POWER PLAN - BASEMENT
FCU-1-3
FCU-1-4
FCU-1-6
FCU-2-1
FCU-2-2
FCU-2-3
FCU-2-4
FCU-2-6
FCU-1-5
FCU-1-1B
FCU-2-5
BS-1-1
BS-2-1
(E) PANEL "BR"
R+R
(E) MDP A&B
(E) PANEL "LB"
R+R
(E) PANEL "PA-A"
(E) PANEL "PA-B"
(E) PANEL "D"
(E) PANEL "C1"
ACCU-1
AHU-1
250V, 1P, 20A
NF, NEMA 1
1
250V, 3P, 30A
NF, NEMA 3R
A
B
(E)HALON PANEL "HR"
R+R
(E)150KW
GENSET
(E)400A, 3P ATS
(E)PANEL "B"
(E)PANEL
4
5
(E) PANEL "PC"
8
9
10
(E)OLD RADIO RM PANEL
2
7
250V, 1P, 30A
NF, NEMA 1
0.6A
0.4A
7.4A
3.4A
0.8A
(E)PANEL "MR"
2.8A
0.3A
1.5A
0.6A
5.2A
0.6A
0.4A
1.6A
0.6A
2.8A
6.0A
910
2
MDP1
MDP2
(E)PHASE MONITOR
ABOVE
(E)1200A SWITCHBOARD
(E)CT CABINET
(E)METER
SERVER ROOM
9
HALL
AUDITORIUM
RESTROOM
25
RESTROOM
5
MECHANICAL ROOM
26
AUDITORIUM LOBBY
STAIRS
STAIRS
MECHANICAL
ROOM
6
STORAGE
24
CLOSET
CLOSET
KITCHEN
7B
HALL
HALL
HALL
HALL
HALL
ELEVATOR
VESTIBULE
7A
CLOSET
CLOS
CLOS
HALL
IT
15B
OFFICE
15A
OFFICE
16
OFFICE
1
OFFICE
2
OFFICE
3
OFFICE
10
OFFICE
11
OFFICE
12B
OFFICE
12A
OFFICE
13
OFFICE
14
OFFICE
17
OFFICE
19
OFFICE
18
OFFICE
20
OFFICE
21
OFFICE
22
OFFICE
23
IT ROOM
8
(E)NORMAL POWER FEEDER
(E)EMERGENCY POWER FEEDER
FCU-1-2
0.8A
FCU-1-1A
1.4A
A
(E) PANEL "BR"
R+R
(E) MDP A&B
A
B
2 3
2
250V, 1P, 30A
NF, NEMA 1
250V, 1P, 30A
NF, NEMA 3R
ACCU-2
AHU-1
MECHANICAL ROOM
8
BR-3
MDP1
MDP2
MECHANICAL ROOM
7
910
(E)PANEL "MR"
TANKLESS EWH
AC/GFCI
PUMP BELOW
WITH CORD TO
GFCI RECEPTACLE
UNDER SINK
MDP1-5
LB-33
F-6
+36"
LB-31
BELOW SINK
250V, 2P, 60A
NF, NEMA 1
11
11
11
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
PO
WE
R P
LA
N -
BA
SE
ME
NT
E5
CONSTRUCTION NOTES:
XX
DRAWING NOTES:
1. EVERY SWITCHBOARD, PANELBOARD, SAFETY SWITCH, AND SIMILAR SHALL
HAVE REFERENCES TO 240VOLTS DELTA REMOVED AND A LABEL INDICATING
208/120VOLTS, 3PH, 4W SYSTEM. LABELS SHALL BE PER THE SPECIFICATIONS.
SEE DRAWING E1, SPECIFICATIONS, ELECTRICAL IDENTIFICATION, SECTION E.
2. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
1. TYPICAL DISCONNECT SWITCH REQUIREMENTS FOR ALL FAN COIL UNITS AND
BRANCH SELECTORS. ATTACH DISCONNECT TO FRAMING FOR FLOOR ABOVE.
2. ACCU-1 PROVIDE 30A, 3P BREAKER IN "MDPA" CIRCUIT 14/16/18. EXTEND 3#10,
1#10EGC, 3/4" C FROM "MDPA" TO UNIT.
3. NOT USED.
4. EXISTING OLYMPIAN DIESEL GENERATOR MODEL D150P1, PRESENTLY
CONNECTED AT 240/120VOLTS, 3 PHASE SHALL BE RECONNECTED
208/120VOLTS, 3 PHASE. CONTRACT WITH FACTORY AUTHORIZED TECHNICIANS
TO MAKE THESE CHANGES.
5. THE EXISTING AUTOMATIC TRANSFER SWITCH, ASCO SERIES 300, 400 AMP, 240
VOLTS, 3 PHASE, 3-POLE CATALOG NUMBER A300340061XC SHALL BE
UPGRADED FOR 208/120 VOLT, 3 PHASE, 4 WIRE SYSTEM. PROVIDE ALL
CONTROL WIRING REQUIRED FOR THE CHANGES IN ELECTRONICS FOR THE ATS
TO COMMUNICATE WITH THE EXISTING OLYMPIAN GENERATOR. CONTRACT
WITH FACTORY AUTHORIZED TECHNICIANS TO PERFORM THIS WORK.
6. NOT USED.
7. THE EXISTING ELEVATOR 30HP, 230V, 3PH MOTOR AND ASSOCIATED CONTROLS
SHALL BE UPGRADED AS REQUIRED TO OPERATE ON A 208V, 3PH SYSTEM.
PROVIDE 30HP, 208V, 3PH, MOTOR, 2165 FRAME TYPE K1 AS REQUIRED BY
DOVER ELEVATOR. ELEVATOR MOTOR REPLACEMENT AND ALL OTHER WORK
ON THE ELEVATOR SYSTEM INCLUDING TESTING SHALL BE PERFORMED BY A
FACTORY AUTHORIZED TECHNICIAN.
8. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
PANEL “BR” LOCATED IN MECHANICAL ROOM. PROVIDE 15AMP, SINGLE POLE
CIRCUIT BREAKER TO FEED BRANCH CIRCUIT.
9. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
ROOM PANEL "MR" CKT 39. PROVIDE 15AMP, SINGLE POLE CIRCUIT BREAKER TO
FEED BRANCH CIRCUIT.
10. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
ELEVATOR EQUIPMENT ROOM PANEL "MR" CKT 40. PROVIDE 15AMP, SINGLE
POLE CIRCUIT BREAKER TO FEED BRANCH CIRCUIT.
11. SURFACE MOUNT CONDUIT AND RECEPTACLE.
SCALE:
NORTH
0 1' 5' 10'
1/4"=1'-0"
PARTIAL FLOOR PLAN - POWER
SCALE:
NORTH
0 1' 5' 10'
1/4"=1'-0"
PARTIAL FLOOR PLAN - POWER
SCALE:
0 1' 5' 10'
1/4"=1'-0"
A
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
POWER PLAN - FIRST FLOOR
(E) PANEL "L1"
R+R
(E) PANEL
"PC-E"
R+R
(E) PANEL
"SP-1"
(E) PANEL "EM"
FCU-3-9
FCU-3-10
FCU-3-1
FCU-3-2
FCU-3-5
FCU-3-6
FCU-3-8
FCU-3-3
FCU-3-4
FCU-4-3
FCU-4-1
FCU-4-2
FCU-4-7
FCU-4-6
FCU-4-5
FCU-3-7
BS-3-1
BS-4-1
FCU-4-4
250V, 2P, 20A
NF, NEMA 1
1
2.8A
3
6.0A
2.8A
0.4A
0.7A
6
3.8A
2.8A
0.3A
3.8A
0.8A
1.6A
1.4A
4
1.4A
6.0A
0.9A
0.3A
0.3A
2.8A
0.9A
0.8A
0.3A
0.4A
0.4A
2
2.5A
5
256 34
F1
F1
F1
F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F1
F1
F1 F1 F1 F1 F1
F1
F1
F1 F1 F1 F1 F1
ORIGINALADDITION
127
126
125
123
124
129
130
131C
131B
131D
HALL
STAIRS
100
102
117
116
101
BATHROOM
103
VESTIBULE
119
HALL
114
113
112
106
107
105
108
STAIRS
LOBBY
115
CLOSET
CLOS
CLOS
CLOS
HALL
CLOSET
HALL
CONFERENCE
110
BATHROOM
104
ELEVATOR
HALL
250V, 2P, 60A
NF, NEMA 1
MDP1-9
SP-1-37
EWH BELOW SINK
0.7AF-4
AC/GFCI/SM
+36"
SM
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
PO
WE
R P
LA
N -
FIR
ST
F
LO
OR
E6
CONSTRUCTION NOTES:
XX
DRAWING NOTES:
1. EVERY SWITCHBOARD, PANELBOARD, SAFETY SWITCH, AND SIMILAR SHALL
HAVE REFERENCES TO 240VOLTS DELTA REMOVED AND A LABEL INDICATING
208/120VOLTS, 3PH, 4W SYSTEM. LABELS SHALL BE PER THE SPECIFICATIONS.
SEE DRAWING E1, SPECIFICATIONS, ELECTRICAL IDENTIFICATION, SECTION E.
2. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
1. TYPICAL DISCONNECT SWITCH REQUIREMENTS FOR ALL FAN COIL UNITS AND
BRANCH SELECTORS. ATTACH DISCONNECT TO FRAMING FOR FLOOR ABOVE.
2. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
SQUARE D, LOAD CENTER, PANEL "SP1-27". PROVIDE 15AMP, SINGLE POLE
CIRCUIT BREAKER TO FEED BRANCH CIRCUIT.
3. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
SQUARE D, LOAD CENTER, PANEL "SP1-8". PROVIDE 15AMP, SINGLE POLE
CIRCUIT BREAKER TO FEED BRANCH CIRCUIT.
4. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
SQUARE D, LOAD CENTER, PANEL SP1-39". PROVIDE 15AMP, SINGLE POLE
CIRCUIT BREAKER TO FEED BRANCH CIRCUIT.
5. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
SQUARE D, LOAD CENTER, PANEL "SP1-38". PROVIDE 15AMP, SINGLE POLE
CIRCUIT BREAKER TO FEED BRANCH CIRCUIT.
6. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
SQUARE D, LOAD CENTER, PANEL "SP1-40". PROVIDE 15AMP, SINGLE POLE
CIRCUIT BREAKER TO FEED BRANCH CIRCUIT.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
POWER PLAN - SECOND FLOOR
(E) PANEL "L2" R+R
(E) PANEL "CR"
FCU-5-6
FCU-6-1
FCU-6-3
FCU-6-4
FCU-6-7FCU-6-6
FCU-6-2
FCU-6-5
BS-5-1
BS-6-1
(E)PANEL "SP2"
(N)PANEL "HB"
53.0A
1.3A
1.3A
0.4A
0.4A
4
2.7A
1.3A
0.7A 0.7A
1.5A
0.6A
0.8A
0.8A
1.8A
(N)PANEL
"HA"
3
3.9A
250V, 2P, 20A
NF, NEMA 1
1
6
2345
F1
F1
F1
F1
F1 F1
F1
F1
F1
F1
F1
F1
F1 F1 F1 F1 F1
F1
F1
F1 F1 F1 F1 F1
ORIGINALADDITION
6
(E) PANEL "PC-F"
R+R
214
215
STAIRS
201
200
213
212
211
209
208
207
206
BATHROOM
203
BATHROOM
205
HALL
STAIRS
HALL
HALL
CLOS
CLOS
ELEVATOR
CLOSET
FCU-5-3
FCU-5-4
FCU-5-2
FCU-5-1
FCU-5-5
FCU-5-7
0.8A
9.5A
9.5A
D
D
0.8A
216
217 218
219
HA-35
HA-39
HA-31
0.4A
L2-38
+36"
L2-42
L2-40
L2-35
PC-F-11
HA-39
L2-39
L2-32
L2-29,31
7
L2-37
L2-33
L2-36
L2-41
3.6A
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
PO
WE
R P
LA
N -
SE
CO
ND
F
LO
OR
E7
CONSTRUCTION NOTES:
XX
DRAWING NOTES:
1. EVERY SWITCHBOARD, PANELBOARD, SAFETY SWITCH, AND SIMILAR SHALL
HAVE REFERENCES TO 240VOLTS DELTA REMOVED AND A LABEL INDICATING
208/120VOLTS, 3PH, 4W SYSTEM. LABELS SHALL BE PER THE SPECIFICATIONS.
SEE DRAWING E1, SPECIFICATIONS, ELECTRICAL IDENTIFICATION, SECTION E.
2. ALL SPACES ARE OFFICES UNLESS LABELED OTHERWISE.
1. TYPICAL DISCONNECT SWITCH REQUIREMENTS FOR ALL FAN COIL UNITS AND
BRANCH SELECTORS. ATTACH DISCONNECT TO FRAMING FOR ROOF ABOVE.
2. NOT USED.
3. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
PANEL "SP2-37". PROVIDE 15AMP, SINGLE POLE CIRCUIT BREAKER TO FEED
BRANCH CIRCUIT.
4. PROVIDE 3 #12, 3/4" CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
PANEL "SP2-39 PROVIDE 15AMP, SINGLE POLE CIRCUIT BREAKER TO FEED
BRANCH CIRCUIT.
5. PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT TO EXISTING
PANEL "SP2-38". PROVIDE 15AMP, SINGLE POLE CIRCUIT BREAKER TO FEED
BRANCH CIRCUIT.
6. PROVIDE PANEL AS SCHEDULED.
7. POWER POLE TYPICAL FOR MODULAR FURNITURE. SHARED NEUTRALS NOT
PERMITTED.
04/20/15
IFB #152724-TW
SCALE:
NORTH
0 10'5' 15' 20'
1/8"=1'-0"
POWER PLAN - ROOF
HP-1 HP-3
F-1
HP-5
F-3
HP-2
HP-4
F-2
HP-6
DOAU-1
WP/GFI
WP/GFI
WP/GFI
250V, 3P, 60A
NF, NEMA 3R
250V, 3P, 60A
NF, NEMA 3R
250V, 3P, 100A
NF, NEMA 3R
250V, 3P, 100A
NF, NEMA 3R
250V, 3P, 60A
NF, NEMA 3R
250V, 3P, 60A
NF, NEMA 3R
WP/GFI
2
HA-3 HA-9
HA-4
HA-10
F-5
HB-3
HB-9
HB-4
2
2
2
250V, 3P, 100A
NF, NEMA 3R
SP2-401
HB-19
250V, 1P, 30A
NF, NEMA 3R
250V, 1P, 30A
NF, NEMA 3R
250V, 1P, 30A
NF, NEMA 3R
250V, 1P, 30A
NF, NEMA 3R
SP2-36
3
3.4
3.4
3.4
3.4
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
PO
WE
R P
LA
N -
RO
OF
E8
CONSTRUCTION NOTES:
XX
DRAWING NOTES:
1. EVERY SWITCHBOARD, PANELBOARD, SAFETY SWITCH, AND SIMILAR SHALL
HAVE REFERENCES TO 240VOLTS DELTA REMOVED AND A LABEL INDICATING
208/120VOLTS, 3PH, 4W SYSTEM. LABELS SHALL BE PER THE SPECIFICATIONS.
SEE DRAWING E1, SPECIFICATIONS, ELECTRICAL IDENTIFICATION, SECTION E.
2. PROVIDE SUPPORT STAND FOR DISCONNECT SWITCHES AND MOTOR RATED
SWITCHES PER DETAIL DRAWING E11.
1. FANS F-3 & F-5, PROVIDE 3 #12, 3/4" CONDUIT FOR COMPLETE BRANCH CIRCUIT
TO EXISTING SQUARE D, LOAD CENTER, PANEL "SP2", CKT #40. PROVIDE 20AMP,
SINGLE POLE CIRCUIT BREAKER TO FEED BRANCH CIRCUIT.
2. SECURE RECEPTACLE TO DISCONNECT SWITCH. MAINTAIN NEMA 3R RATING OF
DISCONNECT SWITCH.
3. FANS F-1 & F-2, PROVIDE 3 #12, 3/4” CONDUIT FOR COMPLETE BRANCH CIRCUIT
TO EXISTING SQUARE D, LOAD CENTER, PANEL "SP2", CKT #36. PROVIDE 20AMP,
SINGLE POLE CIRCUIT BREAKER TO FEED BRANCH CIRCUIT.
04/20/15
IFB #152724-TW
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
PO
WE
R R
IS
ER
D
IA
GR
AM
E9
SCALE: NONE
(E) POWER RISER DIAGRAM
PANEL "L2"
225A MLO
1P/3W
REMOVE
AND
REPLACE
RM 214
PANEL "L1"
225A
1P/3W
REMOVE
AND
REPLACE
HALL
"MDP-A"
240/120V
3PH, 4W
1200A MLO
I-LINE
HCW326812N
BOILER RM
UTILITY UGE SERVICE
EXTERIOR SIEMENS
SERVICE ENTRANCE
NEMA 3R, SWITCHBOARD,
240/120V, 3PH, 4W, 1200A,
MLO, WITH THREE MAIN
BREAKERS
(E) PULL BOX
"MDP-B"
240/120V
3PH, 4W
800A MLO
I-LINE
HCW32688
BOILER RM
DATA CENTER FEEDER
VIA ATS AND GENERATOR
2 SETS (4#3/0, 1#6)
"MDP1"
240/120V
1P/3W
800A MLO
I-LINE
RM 6
"MDP2"
240/120V
3P/4W
600A MLO
I-LINE
RM 6
PANEL "BR"
100A
1P/3W
REMOVE
AND
REPLACE
RM 26
PANEL "LB"
225A
1P/3W
REMOVE
AND
REPLACE
HALL
PANEL "PA-A"
200A
3P/4W
CLOSET
PANEL "PA-B"
200A
3P/4W
CLOSET
PANEL "PC-D"
60A
1P/3W
CLOSET
PANEL "D"
125A
1P/3W
HALL
PANEL "C1"
225A
3P/4W
RM 14
PANEL "MR"
200A MCB
1P/3W
RM 6
PANEL "CR"
200A MLO
1P/3W
"OLD CADD
RM"
RM 213
PANEL "PC-F"
50A MLO
1P/3W
REMOVE
AND
REPLACE
HALL
PANEL "SP-1"
200A MLO
1P/3W
ELEVATOR
HALL
PANEL "PC-E"
100A
1P/3W
REMOVE
AND
REPLACE
HALL
PANEL "EM"
100A
1P/3W
CLOSET
FIRST FLOOR
SECOND FLOOR
MECHANICAL/BOILER
ROOM
PANEL "SP2"
200A MLO
1P/3W
ELEVATOR
HALL
OLD RADIO
RM PNL
240/120V
1P/3W
200A MLO
OLD RADIO
RM PNL
240/120V
1P/3W
60A MLO
PANEL "HR"
240/120V
1P/3W
60A MLO
HALON PNL
CLOSET
MECHANICAL/
ELEVATOR ROOM
BASEMENT LEVEL
PANEL "B"
400A
MLO
240/120V
3P/4W
RM 10
RADIO
ROOM PNL 1
200A
RM 10
D150 P1,
DIESEL GENERATOR
W/ WP ENCLOSURE
400A, 3P ATS, NEMA 3R
ASCO 300 CAT#
A300340061XC
400/3P
600/3P
800/2P
3
(N)PANEL "HA"
400A MLO
3P/4W
208/120V
RM 214
(N)PANEL "HB"
225A MLO
3P/4W
208/120V
ELEVATOR
HALL
4#4/0, (1)#4EGC, 2-1/2" C4#500KCMIL, (1)#3EGC, 3-1/2" C
41 2 666 66
5
6
5
5
PANEL "SP2A"
125A MLO
1P/3W
RM 214
6
400A/3P
65KAIC
CONSTRUCTION NOTES:
XX
DRAWING NOTES:
1. EVERY SWITCHBOARD, PANELBOARD, SAFETY SWITCH, AND SIMILAR SHALL
HAVE REFERENCES TO 240VOLTS DELTA REMOVED AND A LABEL INDICATING
208/120VOLTS, 3PH, 4W SYSTEM. LABELS SHALL BE PER THE SPECIFICATIONS.
SEE DRAWING E1, SPECIFICATIONS, ELECTRICAL IDENTIFICATION, SECTION E.
2. PROVIDE NEW PANEL DIRECTORIES FOR ALL PANELS MODIFIED BY THIS
PROJECT.
3. CONTRACTOR SHALL DOCUMENT ALL FEEDER CIRCUIT BREAKERS AND FEEDER
CONDUCTOR SIZES AND INDICATED ON THIS RISER DIAGRAM.
1. REMOVE THE FOLLOWING CIRCUITS/BREAKERS FROM PANEL “MDPA”: 200/3,
100/3, (4) 30/3 AFTER WIRING IS REMOVED PER DEMOLITION DRAWINGS.
2. PROVIDE 400AMP, 3 POLE CIRCUIT BREAKER IN SQUARE D I-LINE PANELBOARD
“MDPA” TO FEED NEW PANEL “HA”.
3. PROVIDE 225 AMP, 3 POLE CIRCUIT BREAKER IN SQUARE D I-LINE PANELBOARD
“MDPA” TO FEED NEW PANEL “HB”.
4. REMOVE THE FOLLOWING CIRCUITS/BREAKERS FROM PANEL “MDP2”: 150/3 &
100/3 AFTER WIRING IS REMOVED PER DEMOLITION DRAWINGS.
5. COORDINATE SCHEDULING OF VOLTAGE CHANGE WITH ELECTRIC UTILITY,
GENERATOR MODIFICATION, ELEVATOR MODIFICATION, AND AUTOMATIC
TRANSFER SWITCH MODIFICATION.
6. RELABEL WITH NEW VOLTAGE.
7. REPLACE BREAKERS PER SCHEDULE.
1
DEMOLITION NOTES:
XX
1. DEMO "OLD RADIO ROOM PANEL" AND FEED CONDUCTORS BACK TO SOURCE.
THE (3)EXISTING BRANCH CIRCUITS SHALL BE RELOCATED TO PANEL "P1" AND
TERMINATE ON (3)NEW 20AMP, 1PH BREAKERS.
77777
7
7
7
BOILER RM STAIRWELL
04/20/15
IFB #152724-TW
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
SC
HE
DU
LE
S
E10
(N)PANEL "HB" SCHEDULE
PHASE TO PHASE VOLTS: 208
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 208/120
PHASES: 3 225 AMP MAIN LUGS ONLY
WIRES: 4
MINIMUM SHORT CIRCUIT RATING: 22,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B C P AT PHASE NEUT. GND SIZE
1 55.03
3 3 HP-6 M 19.8 55.0 3 703 - 8 1-1/2"
5 55.03
7 30.06
9 9 HP-2 M 10.8 30.0 3 356 - 10 1 1/4"
11 30.06
13
15 15 SPARE 3 50
17
19
21 21 SPACE 3
23
2 43.06
4 4 HP-4 M 15.5 43.0 3 506 - 10 1 1/4"
6 43.06
8
10 10 SPARE 3 50
12
14
16 16 SPACE 3
18
20
22 22 SPACE 3
24
TOTALS 46.1 128.0 128.0 128.0
* R & R
VDOT STAUNTON HVAC SYSTEM REPLACEMENT
ELECTRICAL SERVICE LOAD CHANGES
ALL OF THE EXISTING HVAC EQUIPMENT IS BEING REPLACED
HVAC LOADS REMOVED FROM PANEL MDPA 248.00 AMPS
NEW HVAC LOADS ADDED TO PANEL MDPA 236.00 AMPS
HVAC LOADS REMOVED FROM PANEL MDPB 32.00 AMPS
NEW HVAC LOADS ADDED TO PANEL MDPB 0.00 AMPS
HVAC LOADS REMOVED FROM MDP1 64.00 AMPS
NEW HVAC LOADS ADDED TO PANEL MDP1 44.00 AMPS
HVAC LOADS REMOVED FROM PANELS MDP2 241.60 AMPS
NEW HVAC LOADS ADDED TO PANEL MDP2 128.00 AMPS
SUM HVAC DECREASE 192.00 AMPS
MISCELLANEOUS INCREASES ON SMALLER PANELS 50.00 AMPS
NOTES:
1. SEE DRAWING E9 FOR POWER DISTRIBUTION DIAGRAM
LIGHTING FIXTURE SCHEDULE
TYPE MANUFACTURER CATALOG NUMBER VOLTS VOLT- DESCRIPTION AND COMMENTS
AMPS TYPE COMMENTS
LITHONIA 2GTL 4 72L LP835 3500K RECESSED 2x4 WITH A12125 ACRYLIC LENS
A/A1 METALUX 2GR -LD1-85-A125-UNV-L835-CD1 120 77 LED7,040
A1 SIMILAR EXCEPT PROVIDE FLANGE FOR GYP BOARD CEILING
VISIONEERING LRTA-2X4-LED-8-35K-O77L-120-P13 LUMENS
LITHONIA 2GTL 4 48L LP835 3500K RECESSED 2x4 WITH A12125 ACRYLIC LENS
B METALUX 2GR-LD1-48-A125-UNV-L835-CDE 120 51 LED 4835.7
VISIONEERING LRTA-2X4-LED-8-35K-O49L-120-P13 LUMENS
LITHONIA 2GTL 4 60L LP835 3500K RECESSED 2x4 WITH A12125 ACRYLIC LENS
C/C1 METALUX 2GR-LD1-64-A125-UNV-L835-CD1 120 59 LED 5525.5 C1 SIMILAR EXCEPT PROVIDE FLANGE FOR GYP BOARD CEILING
VISIONEERING LRTA-2X4-LED-8-35K-X-120-P13 LUMENS
LITHONIA 2GTL 4 40L LP835 3500K RECESSED 2x4 WITH A12125 ACRYLIC LENS
D METALUX 2GR-LD1-38-A125-UNV-L835-CD1 120 43 LED 4006.7
VISIONEERING LRTA-2X4-LED-8-35K-X-120-P13 LUMENS
LITHONIA 2GTL 2 33L LP835 3500K RECESSED 2x2 WITH A12125 ACRYLIC LENS
E/E1 METALUX 2GR -LD1-32-A125-UNV-L835-CD1 120 37 LED 3229.8 E1 SIMILAR EXCEPT PROVIDE FLANGE FOR GYP BOARD CEILING.
VISIONEERING LRTA-2X4-LED-8-35K-O35L-120-P13 LUMENS
LITHONIA 6BPM HL LED 3000 6" RECESSED CAN WITH WHITE BAFFLE
F HALO ML 56 900 90 CRI 120 15.26 LED 943.8
LUM-TECH LED-AFR56-12-DOB LUMENS
LITHONIA LHQM LED R EXIT SIGN WITH EMERGENCY EGRESS HEADS
EX SURE-LITES APCH7 UNIVERSAL R 120 5.2 LEDNICKEL-CADMIUM BATTERY, SELF DIAGNOSTICS
EXITRONIX VLED-U-WH-EL90 FIELD CONVERT EX TO DOUBLE FACE EXIT SIGN AS REQUIRED
REPLACEMENT PANEL "BR" SCH PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240
PHASES: 1 100 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 22,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1
FCU 1-1A, 1-1B, 1-2, 1-3, 1-4/BS-1-1
M 0.9 7.4 1 15 12 12 12 3/4"
3 3 AHU-1 M 1.0 8.3 1 20 12 12 12 3/4"
5 5 SPARE 1 20
7 7 A.T.O. COMPRESSOR 1 20
9 9 TOILET EXHAUST 1 20
11 11 STAIRWELL LIGHTS FIRST FLOOR 1 20
13 13 EXISTING LOAD 1 20
15 15 EXISTING LOAD 1 20
17 17 EXISTING LOAD 1 20
19 19 EXISTING LOAD 1 20
2 2 REFRIGERATOR 1 20
4 4 ICE MACHINE 1 20
6 6 EXISTING LOAD 1 20
8 8 EXISTING LOAD 1 20
10 10 DRINK MACHINES 1 20
12 12 EXISTING LOAD 1 20
14 14 BOILER ROOM EXHAUST FAN 1 20
16 16 EXISTING LOAD 1 20
18 18 EXISTING LOAD 2 50
20
TOTALS 1.89 7.4 8.3
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY "TRACE" LOADS OF EXISTING BRANCH
CIRCUITS AND SUBMIT SCHEDULE TO ENGINEER FOR REVIEW PRIOR TO
MODIFICATIONS TO PANELBOARDS,
(N)PANEL "HA" SCHEDULE
PHASE TO PHASE VOLTS: 208
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 208/120
PHASES: 3 400 AMP MAIN LUGS ONLY
WIRES: 4
MINIMUM SHORT CIRCUIT RATING: 22,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR
RECESSED MOUNTED
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B C P AT PHASE NEUT. GND SIZE
1 38.06
3 3 HP-1 M 13.7 38.0 3 456 - 10 1-1/4"
5 38.06
7 43.06
9 9 HP-3 M 15.5 43.0 3 506 - 8 1 1/4"
11 43.06
13 13 FCU 5-5 M 2.0 9.6 2 1512 - 12 3/4"
15 9.612
17 17 SPACE
19 19 FCU 5-7 M 2.0 9.6 2 1512 - 12 3/4"
21 9.612
23 23 SPACE
2 57.53
4 4 HP-5 M 20.7 57.5 3 803 - 8 1 1/2"
6 57.53
8 59.13
10 10 DOAU-1 M 21.3 59.1 3 903 - 8 1 1/2"
12 59.13
14
16 16 SPARE 3 30
18
20 20
FCU 5-1, 5-2, 5-3, 5-4, BS-5-1
M 0.7 3.4 2 1512 - 12 3/4"
22 3.412
24 24 SPACE
TOTALS 75.9 220.2 220.2 197.6
* R & R
04/20/15
IFB #152724-TW
SCALE: NONE
GROUND-MOUNTED DISCONNECT SWITCH PLAN
BUILDING WALL
ATTACH DISCONNECT TO WALL.
PROVIDE 30" WIDE BY 36" DEEP
CLEAR SPACE IN FRONT OF
DISCONNECT SWITCH
CONDENSING UNIT
AND BASE
SCALE: NONE
GROUND-MOUNTED DISCONNECT SWITCH DETAIL
BUILDING WALL
CONDENSING UNIT
AND BASE
CLAMP LFMC TO BASE
UNDER CONDENSING UNIT
72" LFMC MAX
CLAMP RSC TO WALL
CLAMP LFMC TO WALL
CONDENSING
UNIT
STEEL "C"
CHANNEL
DISCONNECT SWITCH
AND GFI RECEPTACLE
LFMC
1"x1-5/8"
GALVANIZED
STRUT
(TYP OF 2)
ANCHOR STRUT TO
"C" CHANNEL WITH
STAINLESS HARDWARE
1"x1-5/8"
GALVANIZED
STRUT
(TYP OF 2)
SCALE: NONE
ROOF-MOUNTED DISCONNECT SWITCH DETAIL
1"x1-5/8"
GALVANIZED
STRUT
(TYP OF 2)
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
DE
TA
IL
S A
ND
S
CH
ED
UL
ES
E11
SYSTEM NO. C-AJ-1004
FEBRUARY 04, 1994
F RATING -- 1 HR
T RATINGS -- 0 OR 3/4 HR (SEE ITEM 3B)
1. FLOOR OR WALL ASSEMBLY -- MIN 4-1/2 IN. THICK REINFORCED LIGHTWEIGHT
OR NORMAL WEIGHT (100-150 PCF) CONCRETE. WALL MAY ALSO BE
CONSTRUCTED OF ANY UL CLASSIFIED CONCRETE BLOCKS*. MAX DIAM OF
OPENING IS 4 IN.
SEE CONCRETE BLOCKS (CAZT) CATEGORY IN THE FIRE RESISTANCE
DIRECTORY FOR NAMES OF MANUFACTURERS.
2. THROUGH PENETRANTS -- ONE METALLIC PIPE, CONDUIT OR TUBING TO BE
CENTERED WITHIN THE FIRESTOP SYSTEM. PIPE, CONDUIT OR TUBING TO BE
RIGIDLY SUPPORTED ON BOTH SIDES OF FLOOR OR WALL ASSEMBLY. A NOM
ANNULAR SPACE OF 13/16 IN. IS REQUIRED WITHIN THE FIRESTOP SYSTEM. THE
FOLLOWING TYPES AND SIZES OF METALLIC PIPES, CONDUITS OR TUBING MAY
BE USED:
A. STEEL PIPE -- NOM 2 IN. DIAM (OR SMALLER) SCHEDULE 5 (OR HEAVIER)
STEEL PIPE.
B. IRON PIPE -- NOM 2 IN. DIAM (OR SMALLER) CAST OR DUCTILE IRON PIPE.
C. CONDUIT -- NOM 2 IN. DIAM (OR SMALLER) STEEL ELECTRICAL METALLIC
TUBING OR STEEL CONDUIT.
3. FIRESTOP SYSTEM -- THE FIRESTOP SYSTEM SHALL CONSIST OF THE
FOLLOWING:
A. PACKING MATERIAL -- MIN 5-1/2 IN. THICKNESS OF MIN 6 PCF MINERAL
WOOL BATT OR LOOSE CERAMIC FIBER INSULATION FIRMLY PACKED INTO
OPENING AS A PERMANENT FORM. PACKING MATERIAL SHALL EXTEND A
MIN OF 2 IN. ABOVE TOP SURFACE OF FLOOR AND RECESSED FROM
BOTTOM SURFACE OF FLOOR AS REQUIRED TO ACCOMMODATE THE
REQUIRED THICKNESS OF FILL MATERIAL. AS AN ALTERNATE, THE PACKING
MATERIAL MAY EXTEND A MIN OF 2 IN. BEYOND THE BOTTOM SURFACE OF
FLOOR AND RECESSED FROM TOP SURFACE OF FLOOR TO ACCOMMODATE
THE REQUIRED THICKNESS OF FILL MATERIAL. IN WALLS, PACKING
MATERIAL SHALL EXTEND A MIN OF 2 IN. BEYOND ONE SURFACE OF WALL
AND RECESSED FROM THE OTHER SURFACE AS REQUIRED TO
ACCOMMODATE THE REQUIRED THICKNESS OF FILL MATERIAL.
B. FILL, VOID OR CAVITY MATERIAL* -- PUTTY -- MIN 1 IN. THICKNESS OF FILL
MATERIAL APPLIED WITHIN THE ANNULUS, FLUSH WITH EITHER THE TOP OR
BOTTOM SURFACE OF FLOOR. IN WALLS, THE FILL MATERIAL CAN BE
INSTALLED FLUSH WITH EITHER SURFACE OF WALL. THE T RATING OF THE
FIRESTOP SYSTEM IS DEPENDENT UPON THE TYPE OF ASSEMBLY AND
LOCATION OF FILL MATERIAL WITHIN OPENING. IN FLOORS, IF THE FILL
MATERIAL IS INSTALLED FLUSH WITH TOP SURFACE OF FLOOR, THE T
RATING IS 3/4 HR. IF THE FILL MATERIAL IS INSTALLED FLUSH WITH BOTTOM
SURFACE OF FLOOR, THE T RATING IS 1/2 HR. IN WALLS THE T RATING IS 1/2
HR.
EGS NELSON FIRESTOP -- TYPE FSP PUTTY
*BEARING THE UL CLASSIFICATION MARK
REPRINTED FROM THE ONLINE CERTIFICATIONS DIRECTORY WITH PERMISSION
FROM UNDERWRITERS LABORATORIES INC. © 2014 UL LLC.
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY "TRACE" LOADS OF EXISTING BRANCH
CIRCUITS AND SUBMIT SCHEDULE TO ENGINEER FOR REVIEW PRIOR TO
MODIFICATIONS TO PANELBOARDS,
SCALE: NONE
PENETRATION DETAIL
(E) LOAD CENTER "SP-1" SCH
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 225 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 22,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, REPLACE ALL SQUARE D QO BREAKERS WITH 22KAIC RATED BREAKERS
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 EXIST BRANCH CIRCUIT 1 20
3 3 RECEPT COPY ROOM 1 30
5 5 RECEPT OFFICE 1 20
7 7 A/C COPIER ROOM 1 20
9 9 COMPUTER 1 20
11 11 COMPUTER 1 20
13 13 EXIST BRANCH CIRCUIT 1 20
15 15 SIDEWALK LIGHTS 1 20
17 17 CUBICLE RECEPT 1 20
19 19 CUBICLE RECEPT 1 20
21 21 CUBICLE RECEPT 1 20
23 23 RECEPT OUTSIDE CONFERENCE ROOM 1 20
25 25 RECEPT 1 20
27 27
FCU 3-5, 3-6, 3-7, 3-8, 3-9, 3-10
M 0.3 2.5 1 15 12 12 12 3/4"
29 29 RECEPT OFFICE 1 20
31 31 WOMENS BATH HEAT 1 15
33 33 MAIN FL BATH ROOM GFI RECEPT 1 20
35 35 COPIER ROOM 1 20
37 37
RECEPTACLE, REFRIGERATOR ROOM 107
E 0.8 7.0 1 20 12 12 12 3/4"
39 39
FCU-3-1, 3-2, 3-3, 3-8
E 0.7 6.0 1 15 12 12 12 3/4"
2 2 RECEPT COFFEE MAKER 1 20
4 4 RECEPT MICROWAVE 1 20GFCI
6 6 RECEPT OFFICE 1 20
8 8
FCU 4-1, 4-2, BS-4-1
M 0.7 6.0 1 15 12 12 12 3/4"
10 10 RECEPT GEN 1 20
12 12 EXIST BRANCH CIRCUIT 1 20
14 14 EXIST BRANCH CIRCUIT 1 20
16 16 FIRE ALARM PANEL 1 20
18 18 ENTRANCE LIGHTS 1 20
20 20 ENTRANCE AND EMERG LIGHTS 1 20
22 22 EXIST BRANCH CIRCUIT 1 15
24 24 HEAT AND AIR IN OFFICE 2 30
26
28 28 RECEPT IN CONFERENCE ROOM 1 20
30 30 LIGHTS IN CONFERENCE ROOM 1 20
32 32 RECEPT 1 20
34 34 COPIER ROOM 1 20
36 36 COPIER ROOM 1
38 38
FCU 3-4, 4-3, 4-4
M 0.5 3.8 1 15 12 12 12 3/4"
40 40
FCU-4-5, 4-6, 4-7
M 0.5 3.8 1 15 12 12 12 3/4"
TOTALS 3.5 10.8 18.3
(E )LOAD CENTER "SP-2" SCH
PHASE TO PHASE VOLTS: 240 RELABEL 208 VOLTS
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 225 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 22,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, REPLACE ALL SQUARE D QO BREAKERS WITH 22KAIC RATED BREAKERS
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 EXIST BRANCH CIRCUIT E 2 100
3
5 5 CKT 7 A-C 1 20
7 7 CKT 8 A-C 1 20
9 9 CKT 9 A-C 1 20
11 11 CKT 10 A-C 1 20
13 13 A/C IN BRIDGE NORTH 1 20
15 15 A/C IN BRIDGE SOUTH 1 20
17 17 A/C IN BRIDGE WEST 1 20
19 19 A/C IN COPY ROOM 1 20
21 21 MENS BATH RECEPT 1 20
23 23 MENS BATH HEAT 1 15
25 25 SPACE 1
27 27 SPACE 1
29 29 SPACE 1
31 31 SPACE 1
33 33 SPACE 1
35 35 SPACE 1
37 37
FCU-5-6, 6-1, 6-2
M 0.5 3.9 1 15 12 12 12 3/4"
39 39
FCU-6-5, 6-6, 6-7
M 0.3 2.7 1 15 12 12 12 3/4"
41 41 SPACE 1
2 2 CKT 1 B 1 20
4 4 CKT 2 B 1 20
6 6 CKT 3 B 1 20
8 8 CKT 4 B 1 20
10 10 CKT 5 B 1 20
12 12 CKT 6 A-C 1 20
14 14 LASER COPIER RECEPT 1 20
16 16 COMPUTER RECEPT 1 20
18 18 MICROWAVE RECEPT 1 20
20 20 WOMENS BATH RECEPT 1 20
22 22 WOMENS BATH HEAT 1 15
24 24 SPACE 1
26 26 SPACE 1
28 28 SPACE 1
30 30 SPACE 1
32 32 SPACE
34 34 SPACE
36 36 SPACE
38 38
FCU-6-3, 6-4, BS-6-1
M 0.4 3.0 1 15 12 12 12 3/4"
40 40 SPACE
42 42 SPACE
TOTALS 1.15 3.9 5.7
04/20/15
IFB #152724-TW
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
SC
HE
DU
LE
S
E12
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY "TRACE" LOADS OF EXISTING BRANCH
CIRCUITS AND SUBMIT SCHEDULE TO ENGINEER FOR REVIEW PRIOR TO
MODIFICATIONS TO PANELBOARDS,
(E )PANEL "PA-A" SCHEDULE
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 208 VOLTS
PHASES: 3 400 AMP MAIN LUGS ONLY
WIRES: 4
MINIMUM SHORT CIRCUIT RATING: 14,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, REPLACE ALL BREAKERS, GENERAL ELECTRIC TYPE "NLAB" PNL WITH 14KAIC BREAKERS
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B C P AT PHASE NEUT. GND SIZE
1 1 HEAT COIL 2 20
3
5 5 UH5-B - BOILER 1 20
7 7 AC8-2 - OFFICE 2 20
9
11 11 SPARE 2 20
13
15 15 SPACE 1
17 17 ER1-2 - OFFICE 2 30
19
21 21 AC6-2 - OFFICE 2 20
23
25 25 AC7-2 - OFFICE 2 20
27
29 29 SPARE 2 20
31
33 33 PUMP CHILL WATER - BOILER ROOM 2 20
35
37 37 CONDENSER - BOILER ROOM 1 20
39 39 SPACE 1
41 41 FC1-1 - MAIL ROOM 1 20
2
4 4 PC3-B - BREAK ROOM 3 30
6
8 8 AC6-1 - OFFICE 2 30
10
12 12 EXISTING LOAD 2 100
14
16 16 AC1-1 - OFFICE 2 30
18
20 20 EXISTING LOAD 2 20
22
24 24 EXISTING LOAD 2 20
26
28 28 UH4-B - CORRIDOR 2 20
30
32 32 EXISTING LOAD 2 20
34
36 36 FC3-1 - VESTIBULE 1 20
38 38 EXISTING LOAD 1 20
40 40 EXISTING LOAD 2 20
42
(E )PANEL "PA-B" SCHEDULE
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 208 VOLTS
PHASES: 3 400 AMP MAIN LUGS ONLY
WIRES: 4
MINIMUM SHORT CIRCUIT RATING: 14,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, REPLACE ALL BREAKERS, GENERAL ELECTRIC TYPE "NLAB" PNL WITH 14 KAIC RATED BREAKERS
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B C P AT PHASE NEUT. GND SIZE
1
3 3 SPARE 3 80
5
7
9 9 SPARE 3 20
11
13 13 EXISTING LOAD 2 30
15
17 17 EXISTING LOAD 2 30
19
21 21 SPARE 2 20
23
25 25 EXISTING LOAD 2 20
27
29 29 EXISTING LOAD 1 20
31 31 SPARE 1 20
33 33 EXISTING LOAD 2 20
35
37 37 SPARE 2 20
39
41 41 SPACE 1 20
2
4 4 SPARE 3 20
6
8
10 10 B4 & HALLWAY FAN COIL - HVAC UNIT 3 20
12
14 14 F10 HVAC 2 30
16
18 18 EXISTING LOAD 2 20
20
22 22 B8 HVAC 2 20
24
26 26 EXISTING LOAD 2 20
28
30 30 EX. FANS 1 20
32 32 SPARE 1 20
34 34 EXISTING LOAD 2 20
36
38 38 EXISTING LOAD 2 20
40
42 42 EXISTING LOAD 1 20
(E )PANEL "C1" MECH RM SCH
PHASE TO PHASE VOLTS: 208
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/208,EXIST PANEL RATING
PHASES: 3 225 AMP MAIN LUGS ONLY
WIRES: 4
SOLID NEUTRAL, GROUND BAR
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B C P AT PHASE NEUT. GND SIZE
1
3 3 UH1-1 3 20
5
7 7 AC4-B 2 30
9
11 11 AC1-1 2 30
13
15 15 AC2-B 2 30
17
19 19 AC3-B 2 20
21
23 23 AC4-1 2 20
25
27 27 AC2-1 2 20
29
31 31 AC1-B 2 20
33
35 35 F-2 1 20
37 37 F-1 1 20
39 39 RECEPT WEST AND SOUTH SIDE 1 20
41 41 SPACE 1 -
2 2 AC5-1 2 30
4
6 6 AC4-2 2 30
8
10 10 AC3-2 2 30
12
14 14 AC2-2 2 30
16
18 18 AC3-1 2 20
20
22 22 ER1-B 2 20
24
26 26 EXISTING LOAD 1 20
28 28 CONDENSATE PUMP RECEPT 1 20
30 30 AC UNIT 1 20
32 32 AC UNIT 1 20
34 34 FC2-1 1 30
36 36 RECEPT STEVE'S OFFICE 1 20
38 38 RECEPT EAST WALL 1 20
40 40 EXISTING LOAD 1 20
42 42 SPACE 1 -
04/20/15
IFB #152724-TW
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
SC
HE
DU
LE
S
E13
DRAWING NOTES:
1. CONTRACTOR SHALL FIELD VERIFY "TRACE" LOADS OF EXISTING BRANCH
CIRCUITS AND SUBMIT SCHEDULE TO ENGINEER FOR REVIEW PRIOR TO
MODIFICATIONS TO PANELBOARDS.
2. DELIVER ALL SALVAGED BREAKERS TO OWNER.
(E )PANEL "MDPA" MECH RM SCH
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 208 VOLTS
PHASES: 3 1200 AMP MAIN LUGS ONLY
WIRES: 4
MINIMUM SHORT CIRCUIT RATING: 35,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, REPLACE ALL BREAKERS, SQUARE D TYPE "HCW" PNL WITH 35KAIC
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B C P AT PHASE NEUT. GND SIZE
1
3 3 ELEVATOR ROOM MDP PANEL MDP2 3 600
5
7 2/0
9 9 SPARE 3 200 2/0 2/0 #6 2-1/2"
11 2/0
13
15 15 AUDITORIUM CONDENSER UNIT 3 100
17
19 220.2 500
21 21 PANEL "HA" 220.2 3 400 500 500 #3 3-1/2"
23 197.6 500
25
27 27 SPACE 3 -
29
2
4 4 EXHAUST FAN 3 30
6
8
10 10 CHILLER 3 30
12
14 16.1 10
16 16 ACCU-1 6.7 16.1 3 30 10 10 3/4"
18 16.1 10
20
22 22 EVAP FAN 3 30
24
26
28 28 PANEL "C1" 3 200
30
32
34 34 SPACE 3 -
36
(E )PANEL "MDPB" MECH RM SCH
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 208 VOLTS
PHASES: 3 800 AMP MAIN LUGS ONLY
WIRES: 4
MINIMUM SHORT CIRCUIT RATING: 35,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, REPLACE ALL BREAKERS, SQUARE D TYPE "HCW" PNL WITH 35KAIC
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B C P AT PHASE NEUT. GND SIZE
1
3 3 PNL L-R/L2 3 150
5
7
9 9 SPARE 3 30
11
13 13 PNL L-A/LB 2 200
15
17 17 PNL L1 2 200
19
21 21 PNL BR 2 100
23
2 2 SPACE 1
4 4 SPACE 1
6 6 SPACE 1
8 8 SPACE 1
10 10 SPACE 1
12 12 SPACE 1
14 14 SPACE 1
16 16 SPACE 1
18 18 SPACE 1
20 20 SPACE 1
22 22 SPACE 1
24 24 SPACE 1
(E )PANEL "MDP1" ELEV RM SCH
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 208 VOLTS
PHASES: 1 800 AMP MAIN LUGS ONLY
WIRES: 4
MINIMUM SHORT CIRCUIT RATING: 35,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, REPLACE ALL BREAKERS, SQUARE D TYPE "HCM" PNL WITH 35KAIC
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B C P AT PHASE NEUT. GND SIZE
1 1 GEN SET 2 20
3
5 5 TANKLESS WATER HEATER M 8.3 34.6 2 50 #8 #10 3/4"
7 34.6 #8
9 9 TANKLESS WATER HEATER M 8.3 34.6 2 50 #8 #10 3/4"
11 34.6 #8
13 13 PNL SP1 2 200
15
17 17 PNL CR 2 200
19
21 21 PNL SP2 2 200
23
25 25 SPACE 2 -
27
29 29 SPACE 1 -
2 2 PNL HALON ROOM 2 20
4
6 6 PANEL PC-E 2 50
8
10 10 OFF SPARE 2 100
12
14 14 PNL PC-F 2 100
16
18 18 MECH RM A 2 200
20
22 22 OFF SPARE 2 50
24
26
28 28 SPACE 3 -
30
TOTALS 34.6 34.6 69.2
(E )PANEL "MDP2" SCH
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 208 VOLTS
PHASES: 3 600 AMP MAIN LUGS ONLY
WIRES: 4
MINIMUM SHORT CIRCUIT RATING: 22,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, REPLACE (E ) PNL SQUARE D, TYPE "HCN" BREAKERS WITH 22KAIC
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B C P AT PHASE NEUT. GND SIZE
1 1 EXTERIOR WALK LIGHTS 1 20
3
5 5 ELEVATOR 3 100
7
9
11 11 SPARE 3 150
13
15 15 SPACE 1
17 17 SPACE 1
2 128.0 4/0
4 4 PANEL "HB" 128.0 3 225 4/0 4/0 #4 2-1/2"
6 128.0 4/0
8
10 10 PANEL "PA-A" 3 200
12
14
16 16 PANEL "PA-B" 3 200
18
TOTALS 128.0 128.0 128.0
REPLACEMENT PNL "PC-E" SCH PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 100 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 10,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR
SURFACE MOUNTED
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 LIGHTS 1 20
3 3 LIGHTS 1 30
5 5 RECEPT 1 20
7 7 RECEPT 1 20
9 9 COMPUTER 1 20
2 2 LIGHTS 1 20
4 4 LIGHTS 1 20
6 6 LIGHTS 1 20
8 8 COMPUTER 1 20
10 10 COMPUTER 1 20
TOTALS
REPLACEMENT PNL "PC-F" SCH PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 225 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 14,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, SURFACE MOUNTED
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 CORRIDOR LIGHTS IN FILE ROOM & OFFICE 1 1 20
3 3 LIGHTS IN FUTURE OFFICE & EXIT LIGHTS 1 20
5 5 LIGHTS IN FUTURE OFFICE 1 15
7 7 LIGHTS IN TOILETS E&D & OFFICES 2&3 1 15
9 9 RECEPT IN CORRIDOR & FUTURE OFFICES 1 20
11 11 REFIGERATOR ROOM 212 1 20 #12 #12 #12 3/4"
13 13 SPARE 1 20
15 15 SPARE 1 20
17 17 SPARE 1 20
19 19 SPARE 1 20
21 21 SPARE 1 20
23 23 SPARE 1 20
25 25 SPARE 1 20
27 27 SPARE 1 20
29 29 SPARE 1 20
2 2 CORRIDOR LIGHTS IN DRAFTING ROOM 1 15
4 4 LIGHTS IN DRAFTING ROOM 1 15
6 6 RECEPT IN OFFICES 2&3 1 20
8 8 RECEPT CAD ROOM 1 20
10 10 RECEPT DRINKING FOUNTAIN & OFFICE 1 1 20
12 12 SPARE 1 20
14 14 SPARE 1 20
16 16 SPARE 1 20
18 18 SPARE 1 20
20 20 SPARE 1 20
22 22 SPARE 1 20
24 24 SPARE 1 20
26 26 SPARE 1 20
28 28 SPARE 1 20
30 30 SPARE 1 20
TOTALS
04/20/15
IFB #152724-TW
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
SC
HE
DU
LE
S
E14
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY "TRACE" LOADS OF EXISTING BRANCH
CIRCUITS AND SUBMIT SCHEDULE TO ENGINEER FOR REVIEW PRIOR TO
MODIFICATIONS TO PANELBOARDS,
(E ) LOAD CENTER "P1" SCH
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 225 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 10,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 RECEPT - IT ANNEX 1 20
3 3 RECEPT - IT ANNEX 1 30
5 5 RECEPT - IT ANNEX 1 20
7 7 AIR HANDLER - STEVE OFFICE 1 20
9 9 RECEPT - STEVE OFFICE 1 20
11 11 EXISTING LOAD 1 20
13 13 HVAC CONTROLS - AIR COMPRESSOR 1 20
15 15 BOILER FEED - FURNACE ROOM 1 20
17 17
COFFEE POT, MICROWAVE
1 20
19 19 SPARE 1 20
21 21 SPARE 1 20
23 23 EXISTING LOAD 1 20
2 2 RECEPT - IT ANNEX 1 20
4 4 RECEPT - IT ANNEX 1 20
6 6 RECEPT - IT ANNEX 1 20
8 8 RECEPT - DON OFFICE 1 20
10 10 RECEPT - DON OFFICE 1 20
12 12 RECEPT - DON OFFICE 1 20
14 14 HOT WATER PUMP - FURNACE ROOM 1 20
16 16 CONDENSATE PUMP - FURNACE ROOM 1 20
18 18 LIGHTS AND RECEPT - IT 1 20
20 20 RECEPT - IT RELOCATED FROM 60A PANEL 1 20
22 22 EXISTING LOAD RELOCATED FROM 60A PANEL 1 20
24 24 SPARE RELOCATED FROM 60A PANEL 1 20
TOTALS
(E ) LOAD CENTER "CR" SCH
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 225 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 14,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, SQUARE D "QO" LOAD CENTER, PROVIDE ALL NEW 14KAIC BREAKERS
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 SPARE 1 20
3 3 XEROX PRINTER 1 30
5 5 COPIER 1 20
7 7 SPACE 20
9 9 EXISTING LOAD 2 20
11
13 13 CAD RM RECEPT 1 20
15 15 LT SW FEED CEILING LTS 1 20
17 17 RECEPT L. WALL 1 20
19 19 RECEPT R. WALL 1 20
21 21 RECEPT 1 20
23 23 HALLWAY 1 20
25 25 SPARE 1 20
27 27 EXISTING LOAD 1 20
29 29 A/C 2 30
31
33 33 A/C 2 30
35
37 37 PRINTER #1 1 20
39 39 PRINTER #2 1 20
41 41 PRINTER #3 1 20
2 2 PRINTER 2 60
4
6 6 EXISTING LOAD 1 20
8 8 RECEPT 1 20
10 10 C CKT FURNITURE 1 20
12 12 A&B CKT FURNITURE 1 20
14 14 B CKT FURNITURE 1 20
16 16 NEW COPIER 1 20
18 18 EXISTING LOAD 1 20
20 20 RECEPT 1 15
22 22 RECEPT 1 20
24 24 LIGHTS 1 20
26 26 RECEPT 1 20
28 28 RECEPT 1 20
30 30 A/C UNIT SINGLE OUTLET 1 20
32 32 C CKT FURNITURE 1 20
34 34 GEN FURNITURE 1 20
36 36 RECEPT 1 20
38 38 240V RECEPT FOR PRINTER 2 20
40
REPLACEMENT LOAD CENTER "L1" PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 225 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 22,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR
SURFACE MOUNTED
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1
LIGHTS RM 100, 101
1 20
3 3
LIGHTS RM 102, 103
1 30
5 5
LIGHTS RM 109, 110
1 20
7 7
LIGHTS RM 107, 108
1 20
9 9 LIGHTS RM 106 1 20
11 11 LIGHTS CORRIDOR 105 1 20
13 13 PRINTER 1 20
15 15 BOX 1 20
17 17 ANITA CUBICLE 1 20
19 19 DEBBIE MITCHEL CUBICLE 1 20
21 21 COLOR LAZER JET PRINTER 1 20
23 23 HP PRINTER 1 20
25 25 HP PRINTER 1 20
2 2
RECEPT RM 108, 109, 110
1 20
4 4
RECEPT RM 108, 109, 110
1 20
6 6
RECEPT RM 106, 107, 108
1 20
8 8
RECEPT RM 106, 107, 108
1 20
10 10
RECEPT RM 101, 102, 105
1 20
12 12
RECEPT RM 101, 102, 105
1 20
14 14
RECEPT RM 102, 103, 104, 105
1 20
16 16
RECEPT RM 102, 103, 104
1 20
18 18 EPPERLY'S OFFICE RECPT 1 20
20 20 HT & COOL NORTH 1 20
22 22 HT & COOL SOUTH 1 20
24 24 BONNIE CUBICLE 1 20
26 26 DOSHA CUBICLE 1 20
TOTALS
REPLACEMENT PNL "HR" SCH PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 60 AMP MAIN CIRCUIT BREAKER
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 10,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR
SURFACE MOUNTED
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 LIGHTS & RECEPT - BREAK ROOM 1 20
3 3 RECEPT 1 20
5 5 SPARE 1 20
7 7 SPARE 1 20
9 9 SPARE 1 20
11 11 SPARE 1 20
2 2 RECEPT - BREAK ROOM 1 20
4 4 RECEPT - BREAK ROOM 1 20
6 6 SPARE 1 20
8 8 SPARE 1 20
10 10 SPARE 1 20
12 12 SPARE 1 20
TOTALS
REPLACEMENT PNL "L2" SCH PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 225 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 14,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR
SURFACE MOUNTED
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 EXISTING LOAD 1 20
3 3 EXISTING LOAD 1 30
5 5 EXISTING LOAD 1 20
7 7 LIGHTS ROOM 201 1 20
9 9 EXISTING LOAD 1 20
11 11 LIGHTS ROOM 201 1 20
13 13 LIGHTS ROOM 201 1 20
15 15 CEILING RECEPT CENTER REAR 1 20
17 17 LIGHTS ROOM 201 1 20
19 19 EXISTING LOAD 1 20
21 21 LIGHTS ROOM 201 1 20
23 23 EXISTING LOAD 1 20
25 25 BRIDGE INSPECTOR'S OFFICE 1 20
27 27 BRIDGE INSPECTOR'S OFFICE 1 20
29 29 POWER POLE 214 0.7 6.0 1 20 12 12 12 3/4"
31 31 POWER POLE 214 0.7 6.0 1 20 12 12 12 3/4"
33 33 POWER POLE 214 0.7 6.0 1 20 12 12 12 3/4"
35 35
OFFICES 215, 216, 217, 218
0.9 7.5 1 20 12 12 12 3/4"
37 37 POWER POLE 214 0.7 6.0 1 20 12 12 12 3/4"
39 39 POWER POLE 214 0.7 6.0 1 20 12 12 12 3/4"
41 41 POWER POLE 214 1.1 9.0 1 20 12 12 12 3/4"
2 2 RECEPT RM 201 - T JACKSON 2 30
4
6 6 RECEPT RM 201 1 20
8 8 RECEPT RM 201 1 20
10 10 FLOOR RECEPT RM 201 1 20
12 12 FLOOR RECEPT RM 201 1 20
14 14 RECEPT RM E200 & E203 - BRIDGE INSPECT 1 20
16 16 COPIER FILE ROOM 1 20
18 18 HT & COOL 1 20
20 20 EXISTING LOAD 1 20
22 22 FANS 1 20
24 24 FANS 1 20
26 26 HT & COOL RM 201 - SOUTH SIDE 1 20
28 28 HT & COOL RM 201 - NORTH SIDE 1 20
30 30 SPARE 1 20 12 12 12 3/4"
32 32 POWER POLE 214 0.7 6.0 1 20 12 12 12 3/4"
34 34 SPARE 1 20 12 12 12 3/4"
36 36 SPARE 1 20 12 12 12 3/4"
38 38 RECEPT REFRIGERATOR 1.0 8.0 1 20 12 12 12 3/4"
40 40 RECEPT TOASTER 1.2 10.0 1 20 12 12 12 3/4"
42 42 RECEPT MICROWAVE 1.4 12.0 1 20 12 12 12 3/4"
TOTALS 9.9 47.0 35.5
04/20/15
IFB #152724-TW
ST
AU
NT
ON
D
IS
TR
IC
T O
FF
IC
E B
UIL
DIN
G
HV
AC
R
EP
LA
CE
ME
NT
PR
OJE
CT
C
OD
E: 501-A
5501-015
ST
AU
NT
ON
, V
IR
GIN
IA
13
12
22
0 A
PR
1
5
DA
TE
:P
RO
JE
CT
N
O:
RE
VIS
IO
NS
DA
TE
BY
NO
.
Drawing No.:
1"
Full Scale Verification
0"
VIR
GIN
IA
A
&E
, P
LLC
1115 V
IS
TA
P
AR
K D
RIV
E
FO
RE
ST
, V
IR
GIN
IA
24551
PH
ON
E: (434) 316-6001
Lic. No. 034338
SC
HE
DU
LE
S
E15
GENERAL NOTES:
1. CONTRACTOR SHALL FIELD VERIFY "TRACE" LOADS OF EXISTING BRANCH
CIRCUITS AND SUBMIT SCHEDULE TO ENGINEER FOR REVIEW PRIOR TO
MODIFICATIONS TO PANELBOARDS,
(E ) LOAD CTR "MR " SCH
PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 200 AMP MAIN CIRCUIT BREAKER
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 14,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR, SQUARE D "QO" LOAD CENTER, PROVIDE ALL NEW 14KAIC BREAKERS
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 LADIES BATHROOM HEATER 2 20
3
5 5 DUSK TIL DAWN 1 20
7 7 EXISTING LOAD 1 20
9 9 EXISTING LOAD 1 20
11 11 EXISTING LOAD 1 20
13 13 EXISTING LOAD 1 20
15 15 EXISTING LOAD 1 20
17 17 TECHNICIANS OFFICE RECEPT 1 20
19 19 TECHNICIANS OFFICE RECEPT 1 20
21 21 TECHNICIANS OFFICE RECEPT 1 20
23 23 TECHNICIANS OFFICE RECEPT 1 20
25 25 GFI RECEPT - WOMENS BATHROOM 1 20
27 27
SEE JCI (OFF)
2 20
29
31 31 HEATER - ELEVATOR RM 1 20
33 33 SPACE 1 20
35 35 SPACE 1 20
37 37 SPACE 1 20
39 39
FCU 1-5, 1-6, 2-1, 2-6
0.6 5.2 1 20 12 12 12 3/4"
2 2 HWH 2 30
4
6 6 ELEVATOR CONTROL LIGHTS 1 20
8 8 EXHAUST FAN 1 20
10 10 EMERG LTS HALL & EXIT LT AT ENTRANCE 1 20
12 12 AUTO DOOR OPENERS 1 20
14 14 EXISTING LOAD 1 20
16 16 RECEPT PM SIDE PANEL 1 20
18 18 SHUNT TRIP FOR ELEVATOR 1 20
20 20 TECHNICIANS OFFICE RECEPT 1 20
22 22 HEAT PUMP - WOMEN'S BATHROOM 2 15
24
26 26 HTR - MEN'S BATHROOM 1 15
28 28 EXISTING LOAD 2 15
30
32 32 SPACE 1 20
34 34 SPACE 1 20
36 36 SPACE 1 20
38 38 SPACE 1 20
40 40
FCU 2-2, 2-3, 2-4, 2-5, BS-2-1
0.7 6.0 1 15 12 12 12 3/4"
TOTALS 1.34 11.2
REPLACEMENT PANEL "LB" SCH PHASE TO PHASE VOLTS: 240
PANELBOARD CHARACTERISTICS: PHASE TO NEUT. VOLTS: 120
VOLTS: 120/240, RELABEL 120/208 VOLTS
PHASES: 1 225 AMP MAIN LUGS ONLY
WIRES: 3
MINIMUM SHORT CIRCUIT RATING: 14,000 RMS SYM AMPS
SOLID NEUTRAL, GROUND BAR
SURFACE MOUNTED
CKT. POLE LOAD CONN. CONN. AMPS BREAKER NO. & WIRE SIZE COND.
NO. NO. DESCRIPTION TYPE KVA A B P AT PHASE NEUT. GND SIZE
1 1 LIGHTS RM 12 1 20
3 3
LIGHTS RM 10, 11
1 30
5 5 LIGHTS RM 9 1 20
7 7 LIGHTS CORR 8 & E-5 1 20
9 9
LIGHTS RM 4, 5, OUTSIDE
1 20
11 11
LIGHTS RM 4, 5
1 20
13 13
LIGHTS RM 6, 7, & E-1
1 20
15 15
LIGHTS RM E2, E3, E4
1 20
17 17 LIGHTS RM 2 &1 1 20
19 19 LIGHTS RM 3 & OUTSIDE 1 20
21 21 LIGHTS AUDITORIUM 1 20
23 23 EXISTING LOAD 1 20
25 25 SCREEN 1 20
27 27 FLOOD LIGHTS AUD. 1 50
29 29 SPARE 1 50
31 31 RECEPTACLE REFRIGERATOR R 0.7 6.0 1 20 #12 #12 #12 3/4"
33 33
RECEPTACLE PUMP, ABOVE COUNTER
R 0.4 3.0 1 20 #12 #12 #12 3/4"
35 35 EXISTING LOAD 1 50
37 37 EXISTING LOAD 1 50
39 39 EXISTING LOAD 1 50
2 2
REC RM 8, 11, 12
1 20
4 4
REC RM 8, 11, 12
1 20
6 6
REC RM 9, 10, 11
1 20
8 8
REC RM 8, 9, 10, 11
1 20
10 10
REC RM 5, 7
1 20
12 12
REC RM 5, 6
1 20
14 14
REC RM 2, 3, & COKE MACHINE
1 20
16 16
REC RM 2, 3
1 20
18 18
REC 1, 2, 3
1 20
20 20
REC 1, 2, 3
1 20
22 22 REC DRINK FOUNTAIN 1 20
24 24
REC RM E1, E2, E3, E4, E5
1 20
26 26
REC RM E1, E2, E3, E4, E5
1 20
28 28 REC RM BOXES 1 20
30 30 REC TO NEW PHONE BOARD 1 20
32 32 EXISTING LOAD 1 20
34 34 EXISTING LOAD 1 20
36 36 EXISTING LOAD 1 20
38 38REC MECH EQUIP RM
1 20
40 40 HT & COOL RM 2 & 5 1 20
TOTALS 1.08 3.0 6.0
04/20/15
IFB #152724-TW