VC200-R · Rod Drop Module Signal Conditioner / Transmitter /Monitor Key Features • Displacement...
Transcript of VC200-R · Rod Drop Module Signal Conditioner / Transmitter /Monitor Key Features • Displacement...
1www.precisiontechplus.co.uk
VC200-R Rod Drop Module
Signal Conditioner / Transmitter /Monitor
Key Features• Displacement proximity probe• Keyphasor® signal• 4-20mA output for rod drop value • Measurement in 3 modes Keyphasor® triggered Average Mode Maximum value of rod drop • sensor OK status LED• DIN Rail Mounting• Push-in type connectors• Energized and De-energized relay option• Delay shutdown function• Modbus RTU support• Installation Up/Downward direction• Rotational speed display in RPM
MechanicalInput type 200mv/mils Displacement Sensor Case Material Plastic
(Other sensitivities available) Mounting DIN Rail TS35 (Top Hat)
Rod drop measurement Average, Maximum, Dimensions 134 x 99 x 22.5 mm (H x D x W)
Keyphasor® Triggered Connections Push in connector
Measurement Range 0-2mm Wire Size 0.5 to 4.0 mm
Keyphasor® Input Displacement or photo electric sensor Weight 110 g (nom)
Electrical EnvironmentalPower Input +24 V DC (50 mA) Operating Temperature Range 0 to 55 ºC
Output 4-20 mA= 0-2 mm Installation Category (IEC664) II
(Other ranges available) Equipment Class (IEC536) III
Adjustment Adjustment of zero point EMC EN61326-1:201
Communication Features Relays 1 SPDT, 1A Form C 24Vdc Configuration Software Vibsens-CNFG
Status LED 3 LEDs RPM of Machine, Communication Protocol Modbus RTU
Danger Relay, Sensor Error Communication Port RS-232
PLC
Configuration Software
Recorder
Rod DropTransmitter module
Trip
Dry contact relay
4-20mA
Modbus RTU
Configuration Type of Keypha-sor Sensor Sensitivity Full Scale
Range Drop Danger Installation Location
DelayTrip
RelayType
I = ISO (Standard Order)
F = Factory configured
VC200R is fully configured
via Modbus protocol
D= Displacementsensor
P= Photo electricsensor
200M = 200 mV/mils Displacement008I = 8 V/mm Displacement
XXXm/I = X v/mm
02 = 0-2mmXX =0-XX mm
0100=100 µm0200=200 µm0300=300 µm0400=400 µm
1500=1500 µmxxx=xxx µm
U= Upwarddirection
D= Downwarddirection
01=1s03=3s05=5s06=6s
10=10sXx=xxs
EN =EnergizedDE =De-energized
How To Order Standard order: I-D-200M-02-0800-U-3-EN
DSP Based
Eddy current probe(Rod drop)
Eddy current probe(Phase reference)
potentiometer(on front panel)
DisplacementProximity Probe
Technical Specifications
2www.precisiontechplus.co.uk
Thrust position Conditioner / TransmitterVC200-TThrust Module
Key FeaturesProximity sensor input4-20mA thrust position output Buffered output for dynamic signalTransducer OK status LEDCurrent loop Error status LEDDIN Rail mountingPush-in type connectorsBuffered output for dynamic signalDelay shutdown function
Configuration Sensor type Sensitivity Full Scale Range
NegativeAlert
PositiveAlert
DelayTrip
RelayType
I = ISO (Standard Order)
F = Factory configured
N= - 24v Power Supply
P= + 24v Power Supply
200M = 200 mV/mils sensitivity
008I = 8 V/mm sensitivity
XXXm/I = X v/mm
02 = 0-2mmXX =0-XX mm
100=100 µm200=200 µm300=300 µm400=400 µm500=500 µmxxx=xxx µm
100=100 µm200=200 µm300=300 µm400=400 µm500=500 µmxxx=xxx µm
01=1s03=3s05=5s06=6s
10=10sXx=xxs
EN =EnergizedDE =De-energized
How To Order Standard order: I-N-200M-02-500-500-3-EN
Analog
PLCRecorder
Buffer Output
Trip
Dry contact relay
4-20mA
DisplacementProximity
Probe
Dc-Gap Transmitter
module
Mechanical SpecificationsInput 200mv/mils Displacement transducer Case Material Plastic
(Other sensitivities available) Mounting DIN Rail TS35 (Top Hat)
Transducer Power +/- 24 VDC Dimensions 134 x 99 x 22.5 mm (H x D x W) including BNC
Maximum Current 50mA Connections Push in connector
Measurement Range 0-2mm Conductor Size 0.5 to 4.0 mm
Measurement mode: DC-Gap Value Weight 110 g (nom)
Electrical EnvironmentalInput power +24 V DC (50 mA) Operating Temperature Range 0 to 55 ºC
Output 1 4-20 mA= 0-2mm Installation Category (IEC664) II
(Other ranges available) Equipment Class (IEC536) III
Output 2 (BNC) Buffered dynamic signal output EMC EN61326-1:201
Relays 1 SPDT, 1A Form C 24Vdc
Status LED 4 LEDs Set point negative level, Set point
positive level, Loop and relay
Technical Specifications
3www.precisiontechplus.co.uk
• ICP® /Voltage/Current Transducer • Acceleration/Velocity/ Displacement input signal • 4-20 mA output for dynamic signal / overall value• Buffered output signal • ICP® sensor OK Function• Current loop Error Function• Delay Shutdown Function DIN Rail Mounted• Energized and De-energized relay option• Push-in type connectors
Signal Conditioner / TransmitterVC200-AVibration Module
Key Features
Technical Specifications MechanicalInput 100 mV/g constant current accelerometer
(Other sensitivities available) Case Material Plastic
Frequency Range 1 Hz to 10 kHz (-3dB) (Optional) Mounting DIN Rail TS35 (Top Hat)
Signal Conditioner: Butterworth Dimensions 134 x 99 x 22.5 mm (H x D x W) including BNC
force filter order 8-pole Connections Push in connector
Dynamic Range 80 db Conductor Size 0.5 to 4.0 mm
Measurement mode: Amplifier/integrator to obtain Weight 110 g (nom)
velocity or displacement response
Electrical Environmental
Power Input +24 V DC (50 mA)
Output 1 0-20 mm/s rms Velocity Operating temperature range 0 to 55 ºC
(Other ranges available) Installation Category (IEC664) II
Output 2 (BNC) Buffered acceleration signal Equipment Class (IEC536) III
Relays Output 1 SPDT, 1A Form C 24Vdc EMC EN61326-1:2013
LED Statuse 4 LEDs Power, Loop, ICP, and relay
Configuration Input type Input transducer Full Scale Range
Alert Value
Output Units
Low PassFilter
High Pass Filter Output Relay
Type
I = ISO (Standard Order)
S = Factory configured
A=Acceleration
V=Velocity
D= Displacement
500A = 500 mV/g Accelerometer100A = 100 mV/g Accelerometer050A = 50 mV/g Accelerometer010A = 10 mV/g Accelerometer
100V = 100 mV/IPS Velocity Sensor500V = 500 mV/IPS Velocity Sensor
200D = 200 mV/mils Displacement008D = 8 V/mm Displacement
01 = 0-20002 = 0-10005 = 0-4010 = 0-20
01=102=203=304=405=5xx=X
A=m/s2
V= mm/s
U=µm
01K =1KHz02K = 2KHz
xxK=XK
10= 10Hz02= 2Hz
O=4-20mA(Overall value)
D=4-20 mA (Dynamic signal)
EN =EnergizedDE =De-energized
How To Order Standard order: I-A-100A-02-05-V-01K-10-O-EN
Analog
PLC/DCS Trip
Dry contact relay
Vibration Transmitter module
Raw signal to data collector or analyzer
Buffer Output
Recorder4-20mA
Transducers
4www.precisiontechplus.co.uk
Signal Conditioner /Transmitter /MonitorVC210-AVibration module
MechanicalInput type 100 mV/g constant current accelerometer
(Other sensitivities available) Case Material Plastic
Frequency Range 1 Hz to 10 kHz (-3dB) (Optional) Mounting DIN Rail TS35 (Top Hat)
Filter Butterworth Dimensions 134 x 99 x 22.5 mm (H x D x W)
force filter order 8-pole Connections Push in Clamp
Dynamic Range 80 db Conductor Size 0.5 to 4.0 mm
Signal Conditioner: Amplifier/integrator to obtain Weight 110 gms (nom)
Electrical EnvironmentalPower Input +24 V DC (50 mA) Operating Temperature Range 0 to 55 ºC
Output 1 0-20 mm/s rms Velocity Installation Category (IEC664) II
(other ranges available) Equipment Class (IEC536) III
Output 2 (BNC) Buffered dynamic EMC EN61326-1:2013
acceleration signal Communication Features Relays 2 SPDT, 1A Form C 24Vdc Configuration Software Vibsens-CNFG
Statues LED 3 LEDs Run/Error, Trip, Alarm Communication Protocol Modbus RTU
Communication Port RS-232
velocity or displacement response
Microprocessor Based
PLC/DCS
Configuration Software
Recorder
Vibration measurement & transmissionmodule
ICP/Charge Sensor
Trip
Alarm
Dry contact relay
4-20mA
Modbus RTU
Configuration Input type
TransducerSensitivity
Full Scale Range
Alarm Value
TripValue
Output Units
Low PassFilter
High Pass Filter Output Relay
Type
I = ISO (Standard Order)
S = Factory config-
ured
VC200R is fully configured via
Modbus protocol
A= Acceler-ation
V=Velocity
D= Displace-ment
500A = 500 mV/g Accelerometer100A = 100 mV/g Accelerometer050A = 50 mV/g Accelerometer010A = 10 mV/g Accelerometer
100V = 100 mV/IPS Velocity Sensor500V = 500 mV/IPS Velocity Sensor
200D = 200 mV/mils Displacement008D = 8 V/mm Displacement
01 = 0-1002 = 0-2005 = 0-50
xx = X
01=102=203=304=405=5xx=X
01=102=203=304=405=5xx=X
A=m/s2
V= mm/s
U=µm
01K =1KHz02K = 2KHz
xxK=XK
10= 10Hz02= 2Hz
O=4~20mA(Overall data)
D=4~20 mA (Dynamic Data)
EN =EnergizedDE =De-energized
How To Order Standard order: I-A-100A-02-02-04-V-01K-10-O-EN
Key FeaturesICP® /Voltage/Current TransducerAcceleration/Velocity/ Displacement Output 4-20 mA output for dynamic signal / overall value2 output relays fully configurable with software Buffered acceleration output ICP® transducer OK status LEDDIN Rail MountingPush-in type connectorsEnergized and De-energized relay optionDelay shutdown functionSupported Modbus RTU Protocol
Technical Specifications