Valve terminal types03/04-B · 2016-03-05 · Valve terminal types03/04-B. Contents and general...
Transcript of Valve terminal types03/04-B · 2016-03-05 · Valve terminal types03/04-B. Contents and general...
Electronicsmanual
Valve terminal withfield bus connectionFB8 Allen-BradleyRIO networkType IFB08-03
Manual152 768en 0002d
Valve terminal types 03/04-B
Contents and general instructions
IFesto P.BE-VIFB8-03-EN en 0002d
Author H.-J. Drung. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Editors H.-J. Drung, M.Holder. . . . . . . . . . . . . . . . . . . . . . . .
Original de. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Translation transline Deutschland GmbH. . . . . . . . . . . . . . .
Layout Festo AG & Co., Dept. KG-GD. . . . . . . . . . . . . . . . . . .
Typesetting DUCOM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Edition en 0002d. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Title MANUAL-EN. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Designation P.BE-VIFB8-03-EN. . . . . . . . . . . . . . . . . . . . . . .
Order no. 152 768. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
� (Festo AG & Co., D-73726 Esslingen, Federal Republic ofGermany, 2000)Internet: http://www.festo.comE-Mail: [email protected]
The copying, distribution and utilization of this document as well asthe communication of its contents to others without expressedauthorization is prohibited. Offenders will be held liable for the pay-ment of damages. All rights reserved, in particular the right to carryout patent, utility model or ornamental design registration.
Contents and general instructions
II Festo P.BE-VIFB8-03-EN en 0002d
Contents and general instructions
IIIFesto P.BE-VIFB8-03-EN en 0002d
Designated use VI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Target group VII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Service VII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Important user instructions VIII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Abbreviations X. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Manuals on this valve terminal XII. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Summary of components 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Summary of multifunctional Festo valve terminals 1-3. . . . . . . . . . . . . . . . . . . .
1.2 Description of components 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1 Types 03/04-B: electric modules 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 Type 03: MIDI pneumatic modules 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.3 Type 03: MAXI pneumatic modules 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.4 Type 04-B: ISO pneumatic modules 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Method of operation 1-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Fitting 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1 Fitting the modules and components 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.1.1 Earthing the end plates 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Fitting onto a hat rail (type 03) 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Fitting the valve terminal onto a wall 2-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Installation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Summary of installation 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 System structure in the RIO network 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Bus node 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1 Opening and closing the node 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.2 Configuration settings in the node 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.3 Setting the valve terminal address 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.4 Setting the RIO baud rate with the DIL switch elements 3-10. . . . . . . . . . . . . . . .
3.3 Switching on the power supply 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 Calculating the current consumption 3-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2 Connecting the power supply 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Connecting the RIO interface 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents and general instructions
IV Festo P.BE-VIFB8-03-EN en 0002d
3.4.1 Installing the terminating resistor 3-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Commissioning 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Configuring and addressing the valve terminal 4-3. . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Ascertaining the configuration data 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 Address assignment of the valve terminal 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.3 Address assignment after extension/conversion 4-11. . . . . . . . . . . . . . . . . . . . . .
4.2 ALLEN-BRADLEY – Bus configuration and addressing 4-13. . . . . . . . . . . . . . . . . .
4.2.1 General instructions on commissioning 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.2 Switching on the power supply 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.3 Address assignment of the valve terminal 4-14. . . . . . . . . . . . . . . . . . . . . . . . . . .
5. Diagnosis and error treatment 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 On-the-spot diagnosis 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.1 LEDs on the bus node 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.2 LEDs of the valves 5-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.3 LEDs of the input/output modules 5-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.4 Testing the valves 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Status bits 5-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1 Short circuit/overload 5-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Error treatment 5-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1 Reaction to errors in the control system 5-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2 Short circuit/overload at an output module 5-16. . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.3 Reaction to faults in the control system 5-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Type 04-B: Fuses for the pilot solenoids 5-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. Technical appendix A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Technical specifications A-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2 Cable length and cross-sectional area A-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.3 Examples of circuitry A-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.3.1 Power supply type 03 – internal layout A-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.3.2 Power supply type 04-B – internal layout A-14. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents and general instructions
VFesto P.BE-VIFB8-03-EN en 0002d
B. Accessories B-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.1 Connecting the cables to the plugs/sockets B-3. . . . . . . . . . . . . . . . . . . . . . . . .
C. Index C-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Contents and general instructions
VI Festo P.BE-VIFB8-03-EN en 0002d
Designated use
The valve terminal described in this manual is intended ex-clusively for use as follows:
– for controlling pneumatic and electric actuators (valvesand output modules)
– for interrogating electric sensor signals by means of theinput modules.
Use the valve terminal only as follows:
– in accordance with designated use
– in faultless technical condition.
– without any modifications by the user
If additional commercially-available components such as sen-sors and actuators are connected, the specified limits forpressures, temperatures, electrical data, torques, etc. mustnot be exceeded.
Please observe the standards specified in the relevantchapters and comply with technical regulations, as well aswith national and local regulations.
Contents and general instructions
VIIFesto P.BE-VIFB8-03-EN en 0002d
Additional modules for this valve terminal
The multifunctional valve terminal can be extended with thefollowing modules:
I/O modules
Type designation Title
VIGE-03-FB-... Input module with 4 or 8 inputs, PNP or NPN, 4-pin or 5-pin, with/without electronic fuse
VIGA-03-FB-16-SUBD-S Input module with 16 inputs, PNP, 15-pin sub-D connectionsocket, with electronic fuse
VIGA-03-FB-... Output module with 4 outputs, PNP or NPN, 4-pin or 5-pin
VIGV-03-FB-... Additional supply module 24 V/25 A for high-current outputs
VIEA-03-FB-... Multi I/O module with 12 inputs and 8 outputs, PNP
Target group
This manual is intended exclusively for technicians trained incontrol and automation technology, who have experience ininstalling, commissioning, programming and diagnosing pro-grammable logic controllers and field bus systems.
Service
Please consult your local Festo service centre if you have anytechnical problems.
Contents and general instructions
VIII Festo P.BE-VIFB8-03-EN en 0002d
Important user instructions
Danger categories
This manual contains instructions on the dangers which mayoccur if the product is not used correctly. These instructionsare marked with a heading (Warning, Caution, etc.), printedon a shaded background and accompanied by a pictogram. Adistinction is made between the following danger categories:
WarningThis means that there is a danger of serious human injuryand damage to property if these instructions are not ob-served.
CautionThis means that there is a danger of human injury anddamage to property if these instructions are not observed.
Please noteThis means that there is a danger of damage to property ifthese instructions are not observed.
In addition, the following pictogram marks passages in thetext which describe activities involving electrostatically sensi-tive components:
Electrostatically sensitive components: Incorrect handlingmay result in damage to the components.
Contents and general instructions
IXFesto P.BE-VIFB8-03-EN en 0002d
Marking special information
The following pictograms mark passages in the text contain-ing special information.
Pictograms
Information:recommendations, tips and references to other sources ofinformation.
Accessories:Information on necessary or useful accessories for the Festoproduct.
Environment:information on the environmentally-friendly use of Festoproducts.
Text markings
� The bullet denotes activities which can be carried out inany sequence.
1. Figures denote activities which must be carried out in theorder specified.
– Hyphens denote general activities.
Contents and general instructions
X Festo P.BE-VIFB8-03-EN en 0002d
Abbreviations
The following product-specific abbreviations are used in thismanual:
Abbreviation Meaning
Terminal or valve terminal Valve terminal type 03 or type 04-B with or without electric I/Os
Node Field bus node/control unit
Sub-base
Single-solenoid sub-base
Double-solenoid sub-base
Type 03:Pneumatic sub-base for two valvesType 04-BManifold sub-base incl. Solenoid intermediate sub-base MUH for 1, 4, 8or 12 valves
Sub-base for single-solenoid valves
Sub-base for double-solenoid or mid-position valves
EAI/O
InputOutputInput or output
Pneumatic module General pneumatic module
I/O module General module with digital inputs or outputs
PLC Programmable logic controller; in brief: Controller
Fig. 0/1: Abbreviations
Contents and general instructions
XIFesto P.BE-VIFB8-03-EN en 0002d
Please noteA simplified representation of a type 03 valve terminal withfour pneumatic sub-bases and four input/output modules(standard fitting) has been used for most drawings in thismanual.
1 Input/outputmodules
2 Field bus node
3 Valves
1 2 3
Fig. 0/2: Standard fitting for the drawings
Contents and general instructions
XII Festo P.BE-VIFB8-03-EN en 0002d
Manuals on this valve terminal
Depending on what you have ordered and on the further ex-tension of your complete system, the following Festo manualsare necessary for the complete documentation of the modularvalve terminal:
Festo designation Title/product
P.BE-MIDI/MAXI-03-... Pneumatics manaul– Valve terminal type 03, MIDI/MAXI
P.BE-VIISO-04-B-... Pneumatics manual– Valve terminal type 04-B, ISO 5599-2
P.BE-VIISO-03-.. Supplementary description of the I/Omodules (digital I/O modules 4I, 8O, 4O,high-current output modules, multi I/Omodules)
P.BE-VIFB8-03-... Electronics manual� Field bus connection FB8 (this manual)
Fig. 0/3: Manuals on this valve terminal
Summary of components
1-1Festo P.BE-VIFB8-03-EN en 0002d
Chapter 1
1. Summary of components
1-2 Festo P.BE-VIFB8-03-EN en 0002d
Contents
1. Summary of components 1-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1 Summary of multifunctional Festo valve terminals 1-3. . . . . . . . . . . . . . . . . . . .
1.2 Description of components 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.1 Types 03/04-B: electric modules 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.2 Type 03: MIDI pneumatic modules 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.3 Type 03: MAXI pneumatic modules 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.2.4 Type 04-B ISO pneumatic modules 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.3 Method of operation 1-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1. Summary of components
1-3Festo P.BE-VIFB8-03-EN en 0002d
1.1 Summary of multifunctional Festo valve terminals
The multifunctional valve terminal is composed of individualmodules and components.
Valve terminal Description of the modules
Type 03Electric modules
Electric modules suited to types 03/04B (PNP or NPN), fitted with:– digital inputs (modules with 4, 8 or 16 inputs)– digital outputs (modules with 4 outputs) 0.5 A– high-current outputs 2 A– multi-I/Os (module with 12 inputs/8 outputs) 0.5 A
– analogue I/Os, AS-i master (not possible with all nodes)
Type 03Pneumatic modules
Pneumatic modules type 03, fitted with:– sub-bases (MIDI and MAXI) fitted with 5/2-way single-solenoid
valves, 5/2-way double-solenoid valves, 5/3-way mid-positionvalves (with auxiliary pilot air) or cover plates
– special modules for pressure supply, for forming pressure zones
Type 04-BISO pneumatic modules
Pneumatic modules type 04-B, fitted with:– adapter plate for manifold sub-bases as per ISO 5599-2 in sizes
1, 2 and 3– manifold sub-bases for intermediate solenoid plates with hole
pattern as per ISO 5588-2, fitted with pneumatic valves (single-solenoid, double-solenoid, mid-position) or cover plates
– components for high-level sub-bases (pressure regulator inter-mediate plates, restrictor plates etc.)
Fig. 1/1: Summary of modules for the multifunctional Festo valve terminals
1. Summary of components
1-4 Festo P.BE-VIFB8-03-EN en 0002d
1.2 Description of components
1.2.1 Types 03/04-B: electric modules
The following connecting and display elements can be foundon the electric modules:
1
2 3 4 5 6 7
89
1 Input socket for two electric inputs(PNP or NPN)
2 Red LED (error display per input mod-ule with electronic fuse)
3 Two green LEDs (one LED per input)
4 Input socket for one electric input(PNP or NPN)
5 Green LED (per input)
6 Output socket for electric output (PNP)
7 Yellow LED (status display per output)
8 Red LED (error display per output)
9 Further modules (e.g. additional powersupply, high-current outputs PNP/NPN)
Fig. 1/2: Connecting and display elements on the electric modules
1. Summary of components
1-5Festo P.BE-VIFB8-03-EN en 0002d
1.2.2 Type 03: MIDI pneumatic modules
The following display and operating elements can be foundon the pneumatic MIDI modules type 03:
1 2 3
4
1 Yellow LEDs (per valve solenoid coil)
2 Manual override (per valve solenoidcoil), either locking or non-locking
3 Valve location inscription field (desig-nation signs)
4 Unused valve location with cover plate
Fig. 1/3: Display and operating elements on the MIDI modules type 03
1. Summary of components
1-6 Festo P.BE-VIFB8-03-EN en 0002d
1.2.3 Type 03: MAXI pneumatic modules
The following display and operating elements can be found onthe pneumatic MAXI modules type 03:
1 2
3
45
1 Yellow LED (per valve solenoid coil)
2 Manual override (per valve solenoidcoil), either locking or non-locking
3 Unused valve location with cover plate
4 Valve location inscription field (desig-nation signs)
5 Regulator for limiting the pressure ofthe auxiliary pilot air
Fig. 1/4: Display and operating elements on the MAXI modules type 03
1. Summary of components
1-7Festo P.BE-VIFB8-03-EN en 0002d
1.2.4 Type 04-B: ISO pneumatic modules
The following connecting, display and operating elements canbe found on the pneumatic ISO modules type 04-B:
1 2 3 4 5 6 7
4 5
8
1 1
2 2
1 Adapter plate type 04-B
2 Fuses for the valves
3 Power supply connection
4 1 Yellow LEDs(per pilot solenoid 14)
2 Yellow LEDs(per pilot solenoid 12)
5 1 Manual override(per pilot solenoid 14, non-locking)
2 Manual override(per pilot solenoid 12, non-locking)
6 Valve location inscription field
7 0.135 A fuse (per pilot solenoid)
8 Adapter cable for power supply to thenode and the I/O modules
Fig. 1/5: Operating, display and connecting elements on the ISO modules type 04-B
1. Summary of components
1-8 Festo P.BE-VIFB8-03-EN en 0002d
1.3 Method of operation
The node controls the following functions:
– it connects the valve terminal to the appropriate field busand to the power supply.
– it performs the system settings of the valve terminal, anautomatic valve test and further node-dependent func-tions can be set.
– it controls data transfer to/from the field bus module ofyour control system
– it controls the valve terminal internally
1 Incoming fieldbus
2 Continuing fieldbus
3 Node
4 Compressed air
5 Work air (2, 4)
1 2
3
4
5
Fig. 1/6: Summary of the functions of a valve terminal
1. Summary of components
1-9Festo P.BE-VIFB8-03-EN en 0002d
The input modules process input signals (e.g. from sensors)and transmit these signals via the field bus to the controller.
The output modules are universal electric outputs and controllow-current consuming devices with positive logic, e.g.further valves, bulbs, etc.).
Additional I/O modules for special applications are also avail-able.
Further information on the use of all I/O modules can be foundin the ”Supplementary description of the I/Omodules” for yourvalve terminal.
The pneumatic modules perform the following functions:
– they form the common channels for supply and exhaustair
– they supply electric signals from all the valve solenoidcoils
Work connections 2 and 4 are provided for each valve loca-tion on the individual pneumatic modules.
The valves are supplied with compressed air via the commonchannels on the pneumatic end plate or via special supplymodules. The exhaust air and pilot exhaust are also ventedvia these channels/modules. Further modules for pressuresupply are also available, e.g. for working with different pres-sures or for fitting either MIDI/MAXI valves or ISO valves on anode.
Further information on their use can be found in the ”Pneu-matics manual” for your valve terminal.
1. Summary of components
1-10 Festo P.BE-VIFB8-03-EN en 0002d
Fitting
2-1Festo P.BE-VIFB8-03-EN en 0002d
Chapter 2
2. Fitting
2-2 Festo P.BE-VIFB8-03-EN en 0002d
2. Fitting 2-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4 Fitting the modules and components 2-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.4.1 Earthing the end plates 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.5 Fitting onto a hat rail (type 03) 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.6 Fitting the valve terminal onto a wall 2-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Fitting
2-3Festo P.BE-VIFB8-03-EN en 0002d
2.1 Fitting the modules and components
The valve terminal is supplied from the factory ready fitted. Ifyou wish to supplement or replace individual modules orcomponents, please follow the instructions in the followingmanuals:
– “Supplementary description of the I/O modules” for fit-ting the electric I/O modules
– “Pneumatics manual” for fitting the pneumatic modules
– Fitting instructions are supplied with the product in thecase of modules and components ordered at a later date.
Please noteHandle all modules and components of the valve terminalwith the utmost care. Pay particular attention to the follow-ing:
– Make sure that screws are not distorted and not sub-jected to mechanical stress. Make sure that screws arecorrectly aligned (otherwise their threads may be dam-aged).
– Make sure that the specified torques are not exceeded.
– Avoid misalignment between the modules (IP 65).
– Make sure that connecting surfaces are clean (avoidleakage and contact faults).
– The contacts of type 03 valve solenoid coils must not bebent (they are not resistant to bending, i.e. theywillbreak off if bent backwards).
– Electrostatically sensitive componentsDo not touch the contact surfaces of the plug connectorson the sides of the modulesand components.
2. Fitting
2-4 Festo P.BE-VIFB8-03-EN en 0002d
2.1.1 Earthing the end plates
The valve terminal possesses both a left-hand and a right-hand end plate as a mechanical termination of the valve ter-minal. These end plates fulfil the following requirements:
– they comply with protection class IP 65.
– they contain connections/contacts for earthing.
– they contain holes for fitting the valve terminal onto a walland, in the case of type 03, also for the hat-rail clampingunit.
Please noteWhen supplied from the factory, the end plates of the valveterminal are earthed internally. If you wish to extend/con-vert the type 03 valve terminal, earth the end plates of thevalve terminalas described below.
You thereby avoid faults caused by electromagnetic in-fluences.
Earth the end plates after extension/conversion as follows:
1. Right-hand end plate (type 03):In order to earth the right-hand end plate, connect theready-fitted cable on the inside to the appropriate con-tacts on the pneumatic modules or on the node (see dia-gram below).
2. Left-hand end plate:The left-hand end plate is connected conductively to theother components by means of the ready-fitted springcontacts.
Remark:Instructions on earthing the complete valve terminal can befound in the chapter“Installation”.The diagram below shows how the end plates are fitted usingas an example a type 03 valve terminal.
2. Fitting
2-5Festo P.BE-VIFB8-03-EN en 0002d
1 2 3
4
1
1 Seals
2 Contact for the earth cable
3 Ready-fitted earth cable
4 Fastening screws max. 1 Nm
Fig. 2/1: Fitting the end plates (example of type 03 valve terminal)
2. Fitting
2-6 Festo P.BE-VIFB8-03-EN en 0002d
2.2 Fitting onto a hat rail (type 03)
The valve terminal is suitable for fitting onto a hat rail (sup-port rail as per EN 50022). For this purpose there is a guidegroove on the rear of all modules in order that they can behung on a hat rail (see Fig. 2/3).
Caution– Fitting the valve terminal onto a hat rail without a hat-railclamping unit is not permitted.
– If the valve terminal is fitted in a sloping position or if itis subject to vibration, secure the hat-rail clamping unitadditionally:- against sliding down and use the locking screws(item 3) to protect it against unintentional loosening/opening.
Please note– If the valve terminal is fitted in a horizontal position andif the load is at rest, the hat-rail clamping unit can beused without locking screws (item 3).
– If you do not have a hat-rail clamping unit for your valveterminal, you can order this and fit it at a later stage.
– The use of MIDI or MAXI clamping units depends on theend plates available (MIDI/MAXI).
Hat-rail clamping unit (type 03)
In order to fit the valve terminal onto a hat rail, you will re-quire a hat-rail clamping unit. This must be fitted on the rearof the end plates as shown in the diagram below. Pay particu-lar attention to the following:
2. Fitting
2-7Festo P.BE-VIFB8-03-EN en 0002d
Before fitting:
� Make sure that the surfaces for gluing on the rubber feetare clean (cleaned with spirit).
� Make sure that the flat-head screws (item 3) are tight-ened.
After fitting:
� Fasten the lever with a locking screw (item 7).
2
3
4
5
6
1
1
1 Lever*)
2 O-ring
3 Flat-head screw
4 Self-adhesive rubber foot
5 Clamping elements
6 Locking screw
*) Different lever lengths with MIDI and MAXI
Fig. 2/2: Fitting the hat-rail clamping unit
2. Fitting
2-8 Festo P.BE-VIFB8-03-EN en 0002d
Proceed as follows:
1. Ascertain the weight of your valve terminal as describedin chapter 2.3.
2. Make sure that the mounting surface can support thisweight.
3. Fit a hat rail (support rail as per EN 50022 - 35x15; width35 mm, height 15 mm).
4. Fasten the hat rail to the fastening surface at least every100 mm.
5. Hang the valve terminal onto the hat rail. Fasten the valveterminal on both sides with the hat-rail clamping unit toprevent it from tilting or sliding (see Fig. 2/3).
6. If the hat-rail clamping unit is subject to vibration or if it isfitted in a sloping position, fasten it with two lockingscrews (item 3) against unintentional loosening/opening.
1 Hat-rail clampingunit unlocked
2 Hat-rail clampingunit locked
3 Locking screw
1 3 32
Fig. 2/3: Fitting the type 03 valve terminal to a hat rail
2. Fitting
2-9Festo P.BE-VIFB8-03-EN en 0002d
2.3 Fitting the valve terminal onto a wall
CautionIn the case of long valve terminals with several I/O mod-ules, use additional support brackets for the modules (ap-proximately every 200 mm). You can thereby avoid:
– overloading the fastening eyes on the left-hand endplate
– the terminal sagging (I/O side)
– natural resonance
Proceed as follows:
1. Ascertain the weight of your valve terminal (weigh orcalculate). Reference values:
Valve terminal module
type 03 *)
� per pneumatic module (incl. valves)MIDI0.8 kg
MAXI1.2 kg
Type 04-B manifold sub-bases*)
– Adapter plate and right-hand endplate
– per pneumatic module (incl. manifoldsub-base, intermediate solenoidplate and valve)
ISO size 13.0 kg
1.2 kg
ISO size 23.2 kg
1.6 kg
ISO size 34.1 kg
2.4 kg
Node 1 kg 1 kg 1 kg
I/O module 0.4 kg 0.4 kg 0.4 kg
*) Components for high-level linking: Weight see Pneumatics manual
2. Make sure that the mounting surface can support thisweight. Check to see if you require support brackets forthe I/O modules.
3. If necessary, use spacers.
2. Fitting
2-10 Festo P.BE-VIFB8-03-EN en 0002d
4. Fasten the valve terminal, depending on the type, asshown in the following table. The valve terminal can befitted in any desired position.
Type of valve terminal Fastening methods
Type 03 – with four M6 screws on the left-hand andright-hand end plate.
In the case of valve terminals with several I/Omodules, use additional support brackets for themodules (approximately every 200 mm).
Type 04-B – with two M6 screws on the left-hand end plate– with three M6 screws (ISO sizes 1 and 2) or
M8 (ISO size 3) on the adapter plate and onthe right-hand end plate.
If required, use the following additional methodsof fastening:– a fastening screw per manifold sub-base– the hole on the bottom of the manifold sub-
base (“blind hole,” see Pneumatics manual)– In the case of valve terminals with several I/O
modules, use additional support brackets forthe modules (approximately every 200 mm).
Fig. 2/4: Possibilities for fitting onto a wall
Installation
3-1Festo P.BE-VIFB8-03-EN en 0002d
Chapter 3
3. Installation
3-2 Festo P.BE-VIFB8-03-EN en 0002d
3. Installation 3-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1 Summary of installation 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1.1 System structure in the RIO network 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Bus node 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.1 Opening and closing the node 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.2 Configuration settings in the node 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.3 Setting the valve terminal address 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.2.4 Setting the RIO baud rate with the DIL switch elements 3-10. . . . . . . . . . . . . . . .
3.3 Switching on the power supply 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.1 Calculating the current consumption 3-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.3.2 Connecting the power supply 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4 Connecting the RIO interface 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.4.1 Installing the terminating resistor 3-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Installation
3-3Festo P.BE-VIFB8-03-EN en 0002d
3.1 Summary of installation
3.1.1 System structure in the RIO network
The multifunctional valve terminal is a slave on the RIO net-work. It is addressed as quarter or half rack like an Allen-Bradley remote I/O block.
3. Installation
3-4 Festo P.BE-VIFB8-03-EN en 0002d
PLC-5
Further RIO slaves
1
2
3
4
1 Allen-Bradley 1771 I/O Chassis
2 Valve terminal type 03:MIDI/MAXI valves and electricmodules
3 Valve terminal type 03:Only MAXI valves
4 Valve terminal type 04-B:ISO valves and electric modules
Fig. 3/1: System structure with valve terminals in the RIO network
3. Installation
3-5Festo P.BE-VIFB8-03-EN en 0002d
3.2 Bus node
Please noteThe following A-B specific functions are not implemented:
– Last chassis
– Retain last status
– Restart locking of the processor
CautionFor applications which require safety measures, usedouble-solenoid valves if you wish to implement the func-tions “Retain last status” or “Restart locking of processor”when using the Festo valve terminals.
3.2.1 Opening and closing the node
WarningBefore carrying out installation and maintenance work,switch off the following:
– the compressed air supply
– the operating voltage for the electronics (pin 1).
– the load voltage supply for the outputs/valves (pin 2).
You will thereby avoid:
– uncontrolled movements of loose tubing.
– uncontrolled movements of the connected actuators
– undefined switching states of the electronics.
3. Installation
3-6 Festo P.BE-VIFB8-03-EN en 0002d
CautionThe node contains electrostatically sensitive components.
� Do not therefore touch any contacts.
� Observe the regulations for handling electrostaticallysensitive components.
You will then prevent the electronics in the node from beingdamaged.
You will find the following connecting and display elementson the cover of the node:
1 Red LED
2 Green LED
3 RIO interface
4 Fuse for the oper-ating voltage ofthe inputs
5 Power supplyconnection
1
2
3
45
Fig. 3/2: Cover of the node
3. Installation
3-7Festo P.BE-VIFB8-03-EN en 0002d
Please note– The cover is linked to the internal printed circuit boardsby means of the cable for the power supply connectionand cannot, therefore, be removed completely.
– If you wish to remove the cover:make sure that you remove not only the 6 Philips screwsin the cover, but also the 4 Philips screws in the busplug.
Opening
1. Unscrew the 4 Philips screws in the bus plug.
2. Unscrew and remove the 6 Philips screws in the cover.Carefully lift up the cover and, if necessary, press downthe bus plug at the same time, in order to prevent theinternal circuit boards from tilting or loosening. Do notdamage the cable as a result of mechanical stress.
Closing
1. Replace the cover. Place the cables for the operating volt-age into the housing so that they are not squashed.Tighten the Philips screws in the cover in diagonally oppo-site sequence.
2. Tighten the bus plug again.
3.2.2 Configuration settings in the node
There are four circuit boards in the node. There is an LED onboard 2; on board 3 there are an LED, switches for setting thevalve terminal address and baud rate and two plugs for thefield bus cables.
3. Installation
3-8 Festo P.BE-VIFB8-03-EN en 0002d
1 Red LED
2 DIL switch
3 Green LED
4 Address selectorswitch
5 RIOinterfaces
6 Flat plug for oper-ating voltage con-nection
12
3
4
5
6
Fig. 3/3: Connections, display and operating elements on the node
3.2.3 Setting the valve terminal address
The valve terminal address is used to determine the RIO ad-dress (rack address and I/O module). The determined RIOaddress depends on the dimension of the respective valveterminal, i. e. quarter or half rack. Tables for the setting of thevalve terminal address in comparison to the RIO address youcan find in chapter 4, “Commissioning”.
The valve terminal address can be set with the address selec-tor switches. The switches are numbered from 0...9. The ar-row on the address selector switches indicates the tens orunits figure of the set valve terminal address.
3. Installation
3-9Festo P.BE-VIFB8-03-EN en 0002d
Proceed as follows:
1. Switch off the power supply.
2. Assign a non-reserved RIO address to the valve terminal(see chap. 4).
3. Use a screwdriver to set the arrow of the relevant addressselector switch to the units or tens figure of the desiredRIO address.
1 Example 1:Valve terminaladdress 05
2 Example 2:Valve terminaladdress 38
3 Units figure
4 Tens figure
1
2
3
4
3
4
Fig. 3/4: Examples of set valve terminal addresses
Please noteRIO addresses may only be assigned once per scannermodule. Only a clear assignment of the RIO addresses willguarantee faultless NOMINAL/ACTUAL comparison in theconfiguration run.
3. Installation
3-10 Festo P.BE-VIFB8-03-EN en 0002d
Recommendation:Assign the RIO addresses in ascending order. Adapt them tothe machine structure of your system.
3.2.4 Setting the RIO baud rate with the DIL switch elements
Please noteSet the RIO baud rate on the valve terminal so that it corre-sponds to the setting of the master of thecontrol system.The following A-B specific functions are not implemented:
– Last chassis
– Retain last status
– Restart locking of the processor
Baud rate in kBaud
57.6 115.2 230.4 230.4
ON{ ON{ ON{ ON{
Fig. 3/5: Setting the RIO baud rate
3. Installation
3-11Festo P.BE-VIFB8-03-EN en 0002d
3.3 Switching on the power supply
WarningUse only power units which guarantee reliable electricalisolation of the voltage supplies in accordance with IEC742/EN 60742/VDE 0551 with at least 4 kV isolation resis-tance (Protected Extra-Low Voltage, PELV). Switch powerpacks are permitted providing they guarantee reliableisolation in accordance with EN 60950/VDE 0805.
Remark:By using PELV power units with Festo valve terminals, you canensure protection against electric shock (protection againstdirect and indirect contact) in accordance with EN60204-1/IEC 204. For supplying power to PELV networks youshould use safety transformers with the symbol shown here.The valve terminal must be earthed in order to guarantee theoperation of certain functions (e.g. EMC).
CautionThe load voltage supply for the outputs/valves must befused externally with maximum 10 A (slow blowing). Withthe external fuse you can avoid functional damage to thevalve terminal in the event of a short circuit.
3. Installation
3-12 Festo P.BE-VIFB8-03-EN en 0002d
Before connecting the power supply, please note the follow-ing:
� Avoid long distances between the power unit and thevalve terminal. If necessary, calculate the maximum per-mitted distance as described in Appendix A.
� The following apply as orientation values for your valveterminal.
Cross-sectional area ofcable
Distance
1.5 mm2
2.5 mm2± 8 m
± 14 m
Current consumption (at VB = 24 V):Operating voltage (pin 1) = 2.2 AOperating voltage (pin 2) = 10 A
� If necessary, calculate the complete current consumptionas shown in the table below and then select a suitablepower unit and suitable cable cross-sectional area.
3.3.1 Calculating the current consumption
The table below shows you how to calculate the completecurrent consumption for the valve terminal. The values speci-fied have been rounded up. If you wish to use other valves ormodules, please refer to the relevant technical specificationsfor their current consumption.
3. Installation
3-13Festo P.BE-VIFB8-03-EN en 0002d
Current consumption for electronics and inputs(Pin 1 on the node, 24 V ± 25 %)
Node 0.200A
Number of simultaneouslyassigned sensor inputs ____ x 0.010 A + � A
Power supply for sensors
(see manufacturer specifications) ____ x _____ A+ � A
Current consumption for electronics andinputs (pin 1 on the node) max. 2.2 A = � A A
Current consumption of valves and outputs (pin 2 am onthe node, 24 V ± 10 %)
Number of valve coils (simultaneously actuated):
Type 03: MIDI: ____ x 0.055 A
MAXI: ____ x 0.100 A
Type 04-B: ISO: ____ x 0.140 ANumber of simultaneously actuatedelectric outputs: ____ x 0.010 ALoad current of simultaneously actuatedelectric outputs ____ x _____ A
� A
+ � A
+ � A
Current consumption of outputs(Pin 2 on the node) 3 max. 10 A = � A A+
Current consumption on the node = � A
Current consumption of high-current outputs*)
(Pin 1 of additional supply*) 24 V/25 A)
Number of high-current output modules fitted ____ x 0.100 A
Load current of simultaneously actuated
high-current output modules ____ x _____ A
� A
+ � A
Current consumption of high-current outputs*)
*) per additional supply module max. 25 A = � A � A
Fig. 3/6: Calculating the complete current consumption
3. Installation
3-14 Festo P.BE-VIFB8-03-EN en 0002d
3.3.2 Connecting the power supply
The following are supplied separately with +24 V DC via thepower supply connection:
– the internal electronics and the inputs of the input mod-ules (pin 1: +24 V DC , tolerance ±25 %, external fuseM3.15 A recommended).
– the load voltage for valve outputs and outputs of the out-put modules (pin 2: +24 V DC , tolerance ±10 %, externalfuse max. 10 A (slow blowing) required).
1 Power supply fortype 03
2 Power supply fortype 04B
1
2
Fig. 3/7: Type-specific power supply connection
Please noteCheck within the framework of your EMERGENCY STOPcircuit, to ascertain the measures which are required forputting your machine/system in a safe state in the event ofan EMERGENCY STOP (e.g. switching off the load voltagefor the valves and output modules, switching off the pres-sure).
3. Installation
3-15Festo P.BE-VIFB8-03-EN en 0002d
The pin assignments of the power supply connection on thenode (type 03) and on the adapter block (type 04-B) areidentical.
1 24 V supply forelectronics andinputs
2 24 V load voltagesupply for valvesand outputs
3 0 V
4 Earthconnection
1
2
3
4
Fig. 3/8: Pin assignment of the power supply connection for types 03/04-B
Please noteCommon operating and load voltage supplies for pin 1(electronics and inputs) and pin 2 (outputs/valves):
� In this case, note that the lower tolerance of ±10 % forboth current circuits must be observed.
Check the 24 V load voltage of the outputs while your systemis operating. Make sure that the load voltage of the outputslies within the permitted tolerance even during operation atfull load.
Recommendation:Use a closed-loop power unit.
3. Installation
3-16 Festo P.BE-VIFB8-03-EN en 0002d
Potential equalization
The valve terminal has two earth connections for potentialequalization.
– on the load voltage connection (pin 4 incoming socket).
– on the left-hand end plate (M4 thread).
Please note� Always connect the earth potential to pin 4 of the volt-age connection.
� Connect the earth connection of the left-hand end plateto the earth potential with low impedance (short cablewith large cross-sectional area).
� By means of low-impedance connections, you can besure that the housing of the valve terminal and the earthconnection at pin 4 have the same potential and thatthere are no equalizing currents.
You can thereby avoid interference due to electromagneticinfluences and you can ensure electromagnetic compatibil-ity in accordance with the EMC guidelines.
3. Installation
3-17Festo P.BE-VIFB8-03-EN en 0002d
Example of connection
The diagram below shows as an example the connection of acommon 24 V power supply for pin 1 and pin 2. Please notehere that:
– the load voltage supply for the outputs/valves must beprotected with an external fuse of maximum 10 A (slowblowing) against short circuit/overload.
– the power supply for the electronics and the inputsshould be protected with an external fuse of 3.15 Aagainst short circuit/overload (recommendation).
– the power supply for the sensors is also protected withthe fuse fitted (2 A).
– the common tolerance of 24 V DC ¦ 10 % must be ob-served.
– both connections are connected for potential equalizationand that equalizing currents are avoided.
– the load voltage at pin 2 (valves/electric outputs) can beswitched off separately.
3. Installation
3-18 Festo P.BE-VIFB8-03-EN en 0002d
0 V
3.15 A
10 A
230 V
¦ 10 %
24 V
1
2
34
5
3
24 V
5
3
1 Fuse for sensor inputs (2 A)
2 Earth connection pin 4 designed for12 A
3 Potential equalization
4 Load voltage can be switched off separ-ately.
5 External fuses
Fig. 3/9: Example – connection of a common 24 V power supply and the potential equal-ization(example for type 03)
3. Installation
3-19Festo P.BE-VIFB8-03-EN en 0002d
3.4 Connecting the RIO interface
There are two connections on the node for connection to theRIO network. One of these connections is intended for thesupply cable; the other is for the continuing bus cable. Thesignal cables are connected with each other internally. Thisenables connections to be made in two different ways:
– Looping the RIO cable from terminal to terminal. Bothplugs are required here.
– Connecting the RIO cable with a T-adapter. Only one plugis required.
CautionBranches (e.g. T-adapters) cause signal reflections whenhigh baud rates are used. This can lead to “telegramfaults” with short “failure times” of the valves.
Recommendation:Please observe the maximum permitted distance of 15 cmbetween the T-adapter and the bus plug, in order to avoidsignal reflections.. Use the ready-made Festo T-adapter FB-TAfor this purpose.
1 RIO incoming
2 RIO continuing
1
2
Fig. 3/10: RIO connection variant 1: Looping through
3. Installation
3-20 Festo P.BE-VIFB8-03-EN en 0002d
1 RIO incoming
2 RIO continuing
3 T-adapter, e.g.Festo FB-TA
4 IP65: Seal withprotective cover
5 Branch line max.15 cm
1 2
3
4
5
Fig. 3/11: RIO connection variant 2 with T-adapter
Caution– Make sure of the correct polarity when you connect thebus interface.
– Connect the screening/shield.
The diagram below shows the pin assignment of the bus in-terface. Connect the bus cable to the appropriate pins of thebus cable socket. Note also the connecting instructions infurther diagrams, as well the instructions in the PLC manualfor your controller.
3. Installation
3-21Festo P.BE-VIFB8-03-EN en 0002d
1 S +
2 n. c. (not con-nected)
3 S- (transparent)
4 Screening/shield
5 Node housing
6 Internal RC net-work
1
2
3
4
5
6
1
23
Fig. 3/12: Pin assignment of the RIO interface
Please noteWith several controllers within the PLC family, the maxi-mum number of terminals specified cannot be connectedor not all specified baud rates can be used.
� Please refer to the A-B documentation for further in-formation.
3. Installation
3-22 Festo P.BE-VIFB8-03-EN en 0002d
PLC familyused
Scannermodule
Max. number of racks
Quarter Half
Terminat-ing resis-tor in Ohm
Selectedbaud ratein kBaud
Max. net-worklength inkm
PLC-2 all 16 8 150 57.6 3.3
28 14 82 57.6 3.3
28 14 82 115.2 1.6
PLC-3 1775-S4A1775 S5
16 8 150 57.6 3.31775-S5
32 16 82 57.6 3.3
32 16 82 115.2 1.6
PLC-5 fittedPLC 5/250
16 8 150 57.6 3.3PLC-5/2505150-RS 32 16 82 57.6 3.3
32 16 82 115.2 1.6
32 16 150 230.4 0.8
SLC-5/02 1747-SN 16 8 82 57.6 3.3
115.2 1.6
230.4 0.8
Fig. 3/13: Extension possibilities in the A-B RIO network
The following scanners are only compatible if used with150� terminating resistors:
1771-AF, 1771-AS, 1771-ASB, 1771-DCM, 1771-SN, 1772-SD,1772-SD2, 1775-SR, 1775-S4A, 1775-S4B, 6008-SQ.
3. Installation
3-23Festo P.BE-VIFB8-03-EN en 0002d
3.4.1 Installing the terminating resistor
If the valve terminal to be connected is at the end of a RIOcable, a suitable terminating resistor must be fitted into thesocket of the incoming RIO cable. The unused plug must besealed with a protective cap (protection class IP 65).
Proceed as follows:
1. Clamp the wires of the resistor together with the wires ofthe incoming RIO cable between the cores S+ (pin 1) andS- (pin 3) of the RIO cable socket. In order to ensureproper connection, we recommend that you clamp thewires of the resistorand those of the incoming RIO cablein a common cable end sleeve.
1 Pin 1 S +
2 Terminating resis-tor 150 Ohm
3 Pin 3 S
4 Pin 4Screening/shield
1
2
3
4
Fig. 3/14: Installing the terminating resistor
2. Mount the RIO cable socket on one of the plugs.
3. Seal the unused plug with a protective cap.
3. Installation
3-24 Festo P.BE-VIFB8-03-EN en 0002d
Commissioning
4-1Festo P.BE-VIFB8-03-EN en 0002d
Chapter 4
4. Commissioning
4-2 Festo P.BE-VIFB8-03-EN en 0002d
4. Commissioning 4-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1 Configuring and addressing the valve terminal 4-3. . . . . . . . . . . . . . . . . . . . . . .
4.1.1 Ascertaining the configuration data 4-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.2 Address assignment of the valve terminal 4-6. . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1.3 Address assignment after extension/conversion 4-11. . . . . . . . . . . . . . . . . . . . . .
4.2 ALLEN-BRADLEY – Bus configuration and addressing 4-13. . . . . . . . . . . . . . . . . .
4.2.1 General instructions on commissioning 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.2 Switching on the power supply 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2.3 Address assignment of the valve terminal 4-14. . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Commissioning
4-3Festo P.BE-VIFB8-03-EN en 0002d
4.1 Configuring and addressing the valve terminal
4.1.1 Ascertaining the configuration data
Before configuring, ascertain the exact number of availableinputs/outputs. A multifunctional valve terminal consists of avarying number of I/Os, depending on what you have or-dered.
Please note� The status bits must be treated like inputs and occupyfour additional input addresses.
� The maximum possible extension of the valve terminal islimited by the addressing limits of the relevant field busprotocol and the mechanical limits of the valve terminal.
� Type 04-BWith this valve terminal, the assignment of the valveaddresses can be set fixed by means of a DIL switch inthe adapter block. This manual valve terminal configur-ation (“Address reserving”) is described in the Appendixof the Pneumatics manual for type 04-B.
4. Commissioning
4-4 Festo P.BE-VIFB8-03-EN en 0002d
The table below shows the number of I/Os required per mod-ule for configuration.
Type of module Number of I/Osassigned*)
MIDI/MAXI manifold (type 03)– Single solenoid sub-base– Double solenoid sub-base
ISO manifold (type 04-B)– Single solenoid sub-base– Double solenoid sub-base
4-output module (4 digital outputs)
4-input module (4 digital inputs)
8-input module (8 digital inputs)
16-input module (16 digital inputs)
Multi I/O module
Status bits**)
2O4O
1O2O
4O
4I
8I
16I
12I + 8O
4I
*) The I/Os are assigned automatically within the valve terminal,irrespective of whether an input/output is actually used.
**) The status bits are assigned automatically within the terminal,as soon as there are input modules.
Fig. 4/1: Number of assigned I/Os per module
Copy the following table for further calculations.
4. Commissioning
4-5Festo P.BE-VIFB8-03-EN en 0002d
Calculating the number of inputs/outputs
Inputs
1. Number of 4-input modules ________ x 4
2. Number of 8-input modules ________ x 8
3. Number of 16-input modules ________ x 16
4. Number of other inputs, e. g. multi I/O module
5. The 4 status bits are assigned internally automatically by the valve terminal.
� E
+ � E
� E
+
� E+
+ 4 E
Total number of inputs to be configured= � E
Outputs
6. Number of single-solenoid sub-bases MIDI/MAXI ________ x 2
7. Number of double-solenoid sub-bases MIDI/MAXI ________ x 4
8. Number of type 04-B single-solenoid sub-bases*) ________ x 1
9. Number of type 04-B double-solenoid sub-bases*) ________ x 2
+ � A
+ � A
+ � A
� A
*) Note the possible address reservations with type 04-B
Intermediate sum 6. – 9.10.Check to see if the sum of 6. – 9.
is divisible by four without remainder.This check is necessary because of the 4-bit-orientatedinternal addressing of the terminal.The following distinction is made:a) if divisible by four without remainder: continue with point 11.b) If not: round up to the next half byte (+1...3).
11.Number of 4-output electric modules _ _______ x 4
12.Number of other outputs, e. g. multi I/O module
= � A
+ 2 A
+ � A
+ � A
Total number of outputs to be configured= � A
4. Commissioning
4-6 Festo P.BE-VIFB8-03-EN en 0002d
4.1.2 Address assignment of the valve terminal
The address assignment of the outputs of a multifunctionalvalve terminal depends on the equipment fitted on the valveterminal. A distinction is made between the following equip-ment fitted:
– valves and digital I/O modules.
– only valves.
– only digital I/O modules.
The basic rules described below apply to the address assign-ment of these fitting variants. A detailed example is givenafter each of these basic rules.
Please noteIf two addresses are assigned for one valve location, thefollowing assignment applies:
– lower-value address: pilot solenoid 14
– higher-value address: pilot solenoid 12
Information on reserving addresses of the valves on the type04-B valve terminal can be found in the Pneumatics manualfor type 04-B.
4. Commissioning
4-7Festo P.BE-VIFB8-03-EN en 0002d
Basic rules of addressing
With mixed fitting, the address assignment of the valves, digi-tal I/O modules and status bits is taken into account.
Outputs
1. The address assignment of the outputs does not dependon the inputs.
2. Address assignment of the valves:– Assign the addresses in ascending order without gaps.– Counting begins on the node from left to right.– Maximum 26 valve solenoid coils can be addressed.
Type 03:– Single-solenoid sub-bases always occupy 2 addresses– Double-solenoid sub-bases always occupy
4 addresses
Type 04-B– Single-solenoid sub-bases always occupy 1 address– Double-solenoid sub-bases always occupy
2 addresses
3. Round up to 4 bits: The following distinction is made:a) If the number of valve addresses can be divided by 4
without remainder, continue with point 4.b) If the number of valve addresses cannot be divided by 4
without remainder, you must round up to 4 bits becauseof the 4-bit orientated addressing. The bits thusrounded up in the address range cannot be used.
4. Commissioning
4-8 Festo P.BE-VIFB8-03-EN en 0002d
4. Address assignment of the output modules:After the (4-bit rounded) addresses of the valvesthe digital outputs must be addressed.– Assign the addresses in ascending order without gaps.– Counting begins on the node from right to left.– Counting on the individual modules is made from the
top to the bottom.– Digital output modules occupy 4 or 8 addresses.
Inputs
1. The address assignment of the inputs does not depend onthe outputs.
2. Address assignment of the input modules:– Assign the addresses in ascending order without gaps.– Counting begins on the node from right to left.– On the individual modules from the top to the bottom.– Input modules occupy 4, 8, 12 or 16 addresses.
3. Status bits:The address assignment of the status bits depends on thefitting variants of the inputs and the configuration.
The following always applies:– The status bits are only available if input modules are
connected to the valve terminal and are configured.– Addressing
The status bits are transmitted to the four highest-value positions of the configured address range.
4. Commissioning
4-9Festo P.BE-VIFB8-03-EN en 0002d
When the power supply is switched on, the valve terminalautomatically recognizes all available pneumatic modulesand digital input/output modules and assigns the appropri-ate addresses. If a valve location is not used (cover plate) or ifan input/output is not connected, the relevant address willstill be assigned. The diagram below shows the address as-signment as an example.
1 2 3 4 5 6
1 4-input module
2 8-input module
3 4-output module
4 Single sub-base
5 Double sub-base
6 Round up
Fig. 4/2: Address assignment of a valve terminal with digital I/Os (example type 03)
Remarks on the diagram
– If single-solenoid valves are fitted onto double-solenoidsub-bases of valve terminal type 03 (MIDI/MAXI), fouraddresses will be reserved for valve solenoid coils; thehigher address in each case will then remain unused (seeaddress 3 or Fig. 4/1).
– if unused valve locations are fitted with cover plates, theaddresses will still be assigned (see addresses 12, 13).
4. Commissioning
4-10 Festo P.BE-VIFB8-03-EN en 0002d
– Due to the 4-bit orientated addressing of the modularvalve terminal, rounding up to the full four bits is alwaysmade on the last valve location (if the fitting does not al-ready use the full four bits). This means that two ad-dresses cannot perhaps be used (see addresses 14, 15).
Additional notes on valve terminals without I/O modules
If only valves are used, the address assignment will always beas described in the section“Basic rules for addressing” .
Please note– Maximum 26 valve solenoid coils can be addressed.
– The last two locations on the valve side are not roundedup.
– Valve terminals without input modules do not require aconfiguration for the inputs. The status bits are nottherefore available.
Additional instructions for valve terminals without valves
If only electric I/Os are used, the address assignment willalways be as described in the section“Basic rules for addres-sing” .
Please note– Counting begins immediately to the left of the node.
– The last two locations on the valve side are not roundedup.
– The maximum possible amount of equipment which canbe fitted on the valve terminal is limited by the addres-sing limits of the relevant field bus protocol and themechanical limits of the valve terminal (max. 96 inputsor 48 outputs).
4. Commissioning
4-11Festo P.BE-VIFB8-03-EN en 0002d
4.1.3 Address assignment after extension/conversion
A special feature of the multifunctional valve terminal is itsflexibility. If the demands made to the machine change, theequipment fitted on the valve terminal can also be changed.
CautionIf the valve terminal is extended or converted at a laterstage, the input/output addresses may be shifted. Thisapplies in the following cases:
– when one or several pneumatic sub-bases are added orremoved at a later stage (types 03/04-B).
– Type 03: when a pneumatic sub-base for two single-sole-noid valves is replaced by a sub-base for two double-solenoid valves or vice versa.
– Type 04-B: when a pneumatic sub-base for one single-solenoid valve is replaced by a sub-base for a double-solenoid valve or vice versa.
– when additional input/output modules are added be-tween the node and the existing input/output modules.
– when existing input/output modules are removed orreplaced by input/output modules which occupy feweror more input/output addresses.
If the configuration of the inputs is modified, the addresses ofthe status bits may be shifted.
4. Commissioning
4-12 Festo P.BE-VIFB8-03-EN en 0002d
The diagram below shows, as an example, the modificationswhich occur to the address assignment when more equip-ment is added to the standard fitting of the previous diagram.2 double-solenoid and 2 single-solenoid sub-bases have beenadded to the valve side. An 8-input module and a 4-outputmodule have been removed from the electric I/Os.
1 2 3 4 5 4 3 6
1 4-input module
2 4-output module
3 Single sub-base
4 Double sub-base
5 Power supply
6 No rounding
Fig. 4/3: Address assignment of a valve terminal with digital I/Os after extension(example type 03)
Remarks on the diagramPressure supply modules and intermediate pressure supplymodules do not occupy any addresses.
4. Commissioning
4-13Festo P.BE-VIFB8-03-EN en 0002d
4.2 ALLEN-BRADLEY – Bus configuration and addressing
4.2.1 General instructions on commissioning
Before commissioning or programming, compile a configur-ation list of all connected field bus slaves. On the basis of thislist, you can:
– carry out a comparison between the NOMINAL and theACTUAL configurations, in order to ascertain if there areany connection faults
– accesss these specifications during the syntax check of aprogram, in order to avoid addressing errors.
Configuration of the valve terminal requires a very accurateprocedure, as different configuration specifications are re-quired for each valve terminal, due, amongst other things, tothe modular structure of each system. Please observe herethe instructions in the following sections.
4.2.2 Switching on the power supply
Please notePlease observe also the switching-on instructions in themanual for your A-B controller.
Some A-B controllers automatically carry out a comparisonbetween the NOMINAL and the ACTUAL configurations whenthe power supply is switched on. For this configuration run itis important that:
– the configuration specifications are complete and correct.
– the power supply for the controller and for the RIO slavesconnected to it are switched on either simultaneously orin the order described below.
4. Commissioning
4-14 Festo P.BE-VIFB8-03-EN en 0002d
Common power supply
Switch on the power supply for all the field bus slaves simul-taneously, e.g. by means of a central switch.
Separate power supply
Switch on the power supply in the following sequence:
1. First switch on the power supply for all the field busslaves.
2. Then switch on the power supply for the controller.
If the controller detects a difference between the NOMINALand the ACTUAL configuration, the PLC will react as follows:
– the red LED will light up
Please noteThe Festo valve terminal must have a separate power sup-ply.
4.2.3 Address assignment of the valve terminal
The valve terminal behaves on the RIO network like a remoteI/O block from Allen-Bradley. Please note that the valve ter-minal must be configured differently, depending on thenumber of inputs/outputs.
Valve terminal A-B configuration
up to 28 inputs (+ 4 status bits)and up to 32 outputs
Quarter rack
up to 60 inputs (+ 4 status bits)and up to 64 outputs
Half rack
4. Commissioning
4-15Festo P.BE-VIFB8-03-EN en 0002d
Please noteWith certain A-B controllers it is necessary to enter the RIOslaves in a Scan list. Please read the A-B documentationfor detailed information on addressing and programming.
The inputs/outputs of the valve terminal are addressed likean A-B remote I/O block as quarter or half rack. The addres-sing in an A-B system is carried out as in the followingexample:
Addressingin the A-B system
Explanation
O xxy/zz Addressing scheme
O Output
xx Rack no.
y I/O group (0-7)
zz Bit
Fig. 4/4: Allen-Bradley addressing scheme
4. Commissioning
4-16 Festo P.BE-VIFB8-03-EN en 0002d
Assigning the I/O addresses of the valve terminal toA-B I/O addresses
Input or output addresses
Valve terminalExample: Address 4
A-B assignment
0 ... 7 010/00 ... 010/07
8 ... 15 010/10 ... 010/17
16 ... 23 011/00 ... 011/07
24 ... 31 011/10 ... 011/17
32 ... 39 012/00 ... 012/07
40 ... 47 012/10 ... 012/17
48 ... 55 013/00 ... 013/07
56 ... 63 013/10 ... 013/17
Fig. 4/5: Assignment of I/O addresses with A-B
4. Commissioning
4-17Festo P.BE-VIFB8-03-EN en 0002d
Addressing possibilities with the PLC family
Please note– With a baud rate of 115.2 kBaud, all unused chassismust be set to OFF via SD2. The chassis LED then lightsup red; this means that the SD or SD2 adapter is inac-tive. Data transmission functions correctly.
– With these controllers, maximum 32 modules can bephysically connected to the RIO network via one chan-nel.
– A valve terminal configured like a half rack must alwayslie within a logical rack.
A-B PLC family Possible range of I/O rackno.
PLC-2 2; ...; 7
PLC-3 1; ...; 30
PLC-5/250 1; ...; 17
PLC-5/15 01; ...; 03
PLC-5/25 01; ...; 07
PLC-5/30 01; 02; ...; 07
PLC-5/40;PLC-5/60
01; ...; 27
SLC-5/02 with 1747-SN 0; ...; 3
Fig. 4/6: Address range
4. Commissioning
4-18 Festo P.BE-VIFB8-03-EN en 0002d
PLC-2
Station no.Quarter rack Half rack
Rack no. I/O group
4567
4
6
2222
0, 12, 34, 56, 7
891011
8
10
3333
0, 12, 34, 56, 7
12131415
12
14
4444
0, 12, 34, 56, 7
16171819
16
18
5555
0, 12, 34, 56, 7
20212223
20
22
6666
0, 12, 34, 56, 7
24252627
24
26
7777
0, 12, 34, 56, 7
Fig. 4/7: Addressing possibilities with the PLC-2
4. Commissioning
4-19Festo P.BE-VIFB8-03-EN en 0002d
PLC-5-15, -25, -30, -40, -60, -250 and PLC-3
Maximum number of addressing possibilities de-pending on the controller type
Assignment of possible valveterminal addresses to A-B ad-dresses with the PLC family
PLC Station no.Quarter Half
Rackno.
I/Ogroup
-5/15 -5/25;-5/30
-5/40 -5/60 -5/250 -3 4567
4
6
1111
0, 12, 34, 56, 7
8...1415
8...14
2...33
0, 1...4, 56, 7
16...3031
16...30
4...77
0, 1...4, 56, 7
3233...6263
32
...62
1010...1717
0, 12, 3...4, 56, 7
6465...9495
64
...94
2020...2727
0, 12, 3...4, 56, 7
969798
99(Test)
96
98(Test)
303030
(Test)
0, 12, 34, 5(Test)
Fig. 4/8: Addressing possibilities with the PLC-5 family and the PLC-3
4. Commissioning
4-20 Festo P.BE-VIFB8-03-EN en 0002d
SLC-5/02
Station no.Quarter rack Half rack
Rack no. I/O group
0123
0
2
0000
0, 12, 34, 56, 7
4567
4
6
2222
0, 12, 34, 56, 7
891011
8
10
3333
0, 12, 34, 56, 7
12131415
12
14
4444
0, 12, 34, 56, 7
Fig. 4/9: Addressing possibilities with the SLC-5/02
4. Commissioning
4-21Festo P.BE-VIFB8-03-EN en 0002d
Configured I/Os Used I/Os Unused I/Os
32 inputs 12 I (0 ... 11)4 status bits (28 ... 31)
16 I (12 ... 27)
32 outputs Valves 12 O (0 ... 11) 4 O (12 ... 15)
Digital outputs 8 O (16 ... 23) 8 O (24 ... 31)
Fig. 4/10: Configuration example with valve terminal as quarter rack
4. Commissioning
4-22 Festo P.BE-VIFB8-03-EN en 0002d
I010/10I010/11I010/12I010/13
I010/00I010/01I010/02I010/03I010/04I010/05I010/06I010/07
O011/04O011/05O011/06O011/07
O011/00O011/01O011/02O011/03
O011/01
O011/00
O011/03
O011/02
O011/05
O011/04
O011/07
O011/06
O011/11
O011/10
O011/13
O011/12
O011/14O011/15
O011/16O011/17
Fig. 4/11: Configuration example with valve terminal as quarter rack
Diagnosis and error treatment
5-1Festo P.BE-VIFB8-03-EN en 0002d
Chapter 5
5. Diagnosis and error treatment
5-2 Festo P.BE-VIFB8-03-EN en 0002d
Contents
5. Diagnosis and error treatment 5-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1 On-the-spot diagnosis 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.1 LEDs on the bus node 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.2 LEDs of the valves 5-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.3 LEDs of the input/output modules 5-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1.4 Testingthe valves 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2 Status bits 5-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.2.1 Short circuit/overload 5-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3 Error treatment 5-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.1 Reaction to errors in the control system 5-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.2 Short circuit/overload at an output module 5-16. . . . . . . . . . . . . . . . . . . . . . . . . .
5.3.3 Reaction to faults in the control system 5-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.4 Type 04-B Fuses for the pilot solenoids 5-18. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5. Diagnosis and error treatment
5-3Festo P.BE-VIFB8-03-EN en 0002d
5.1 On-the-spot diagnosis
5.1.1 LEDs on the bus node
The LEDs on the cover of the node indicate the operatingstatus of the valve terminal.
1 Red LED (operat-ing status)
2 Green LED (errordisplay) 1
2BUS
POWER
Fig. 5/1: LEDs on the field bus node
LED designation Meaning
POWER (red, operating status) lights up if the operating statusis normal
BUS (green, error display) lights up if the operating statusis normal
5. Diagnosis and error treatment
5-4 Festo P.BE-VIFB8-03-EN en 0002d
Possible LED displays for the operating status of the valveterminal are shown in the diagram below.
LEDs Operating status Error treatment
BUS
POWER Operating status normal or operating statusnormal, but valves do not switch.Possible causes– Load voltage of the valves not connected
or outside the tolerance
– Compressed air connection not correct
– Auxiliary pilot air exhaust blocked
None
Check:� the load voltage and/or the
output connections (toler-ance) 21.6 V DC ... 26.4 V
� the compressed air connec-tion
� the auxiliary pilot air exhaust
POWER Operating voltage not connected � Check the operating voltage(pin 1)
BUSNo data communication with the RIO network � Check the operating voltage
� Check and, if necessary, cor-rect the configuration of theRIO slaves
BUS
The controller has issued a RESET commandorthe controller is not in the operating statusRUN
� Check and, if necessary, cor-rect the program
� Set the operating status toRUN
BUS
(very quickly)
Incorrect setting on the address selectorswitch
� Correct the address
BUS
(flashes at longintervals)
Modules not fitted correctly:– more than 12 I/O modules fitted
– more than 13 pneumatic modules fitted
– Number of I/Os is not supported– This type of electric module is not per-
mitted
� Reduce the number of I/Omodules
� Reduce the number of pneu-matic modules
� Use only permitted moduletypes
out flashes green lights up green
Fig. 5/2: LED display of the operating status
5. Diagnosis and error treatment
5-5Festo P.BE-VIFB8-03-EN en 0002d
5.1.2 LEDs of the valves
There is a yellow LED for each valve solenoid coil on the valveterminal. This shows the switching status of the valve sole-noid coil.
Valve terminal type LEDs of the valve solenoid coils
Type 03
Type 04-B
Fig. 5/3: Positions of the valve solenoid coil LEDs
5. Diagnosis and error treatment
5-6 Festo P.BE-VIFB8-03-EN en 0002d
LED Switching position of the valvesolenoid coil
Meaning
yellow out basic position logical 0 (no signal)
yellow alight – switch positionor– basic position
logical 1 (signal present)
logical 1 but– operating voltage of outputs lies
below permitted tolerance range(21.6 V...26.4 V DC)
or– compressed air supply not correct.or– pilot exhaust blocked.or– servicing required
Fig. 5/4: LEDs for the status display of the valve solenoid coils
Short circuit/overload (only type 04-B)
The valve solenoid coils of valve terminal type 04-B are fittedwith special fuses for protection against short circuit or over-load. The method of replacing these fuses is described inchapter 5.4.
5. Diagnosis and error treatment
5-7Festo P.BE-VIFB8-03-EN en 0002d
5.1.3 LEDs of the input/output modules
Specific explanations on further I/O modules can be found inthe “Supplementary description of the I/O modules”.
Next to the relevant connections on the input/output mod-ules there are one or two LEDs (status displays) in the co-lours:
– green (status display of the digital inputs).
– yellow (status display of the digital outputs).
– red (error display of the digital outputs).
The signal currently at the relevant input or output is shownby means of the yellow and green LEDs. The red LEDs of theoutputs display a short circuit/overload at the relevant out-put.
5. Diagnosis and error treatment
5-8 Festo P.BE-VIFB8-03-EN en 0002d
1
2 3
4
Description LED Status
1 Short circuit/overload displayof the sensor power supply(only input modules with elec-tronic fuse)
Red LED out
Red LED alight
Input without short circuit/overload
Short circuit/overload at the relevantinput *)
2 Switching status display of theinputs
green out
green alight
logical 0 (no signal)
logical 1 (signal present)
3 Switching status display of theoutputs
yellow out
yellow alight
Output without short circuit/overload
Short circuit/overload at the relevantoutput or input (only input moduleswith electronic fuse*))
4 Short circuit/overload displayof the outputs
red out
red alight
logical 0 (no signal)
logical 1 (signal present)
*) Treatment of short circuit/overload see“Supplementary description of the I/O modules”
Fig. 5/5: LED displays of the input/output modules
5. Diagnosis and error treatment
5-9Festo P.BE-VIFB8-03-EN en 0002d
5.1.4 Testing the valves
WarningBefore starting the test, switch off the compressed air sup-ply to the valves.
You can then avoid undesired or dangerous movements ofthe actuators.
Caution– This test function runs automatically in the valve ter-minal. All the valves are switched on/off cyclically.
– None of the programmed lockings or further switchingconditions will be taken into account.
The following valve tests can be carried out on the valve ter-minal. The valves will be switched on/off cyclically.
Test routine Meaning
parallel All the valves will be switched onand off at the same time at 1second intervals.
serial All the valves will be switched onand off one after the other.
Fig. 5/6: Test routine for valves
This test routine repeats itself until the power supply to theterminal is switched off.
5. Diagnosis and error treatment
5-10 Festo P.BE-VIFB8-03-EN en 0002d
Starting the test routine
1. Switch off the operating voltage and the load voltage sup-plies (pins 1 and 2).
2. Open the node in accordance with chapter 3.2, “Openingand closing the node”.
3. Note the setting of the address selector switch and theDIL switch elements.
4. Set address 99 and set DIL switch elements 1 and 2 toOFF.
5. Switch on the power supplies (pins 1 and 2).
6. Set the test routine on the address selector switch as de-sired.
Test routine Set the address
parallel 0, 1 or 2
serial 3
Fig. 5/7: Setting the test routine
7. Start: Set DIL switch elements 1 and 2 to ON.
If faults occur when the test routine is started, the green LEDon the node will flash quickly. The procedure must then berepeated.
Stopping the test routine
1. Switch off the operating voltage and the load voltage sup-plies (pins 1 and 2) of the valve terminal.
2. Reset the address selector switch and DIL switch el-ements 1 and 2 to the starting position.
5. Diagnosis and error treatment
5-11Festo P.BE-VIFB8-03-EN en 0002d
5.2 Status bits
The valve terminal provides 4 status bits for diagnosis via theRIO network.
Please noteThe four status bits of the valve terminal are only availableif the valve terminal is fitted with input modules.
The status bits are configured like inputs and always occupythe four highest-value addresses of the available addressrange.
Configuration as
Quarter rack Half rack
Number of configured inputs 32 64
Addresses of the status bits 28, 29, 30, 31 60, 61, 62, 63
Fig. 5/8: Addresses of the status bits
If the inputs of the addresses thereunder are not used, thevalve terminal will set them to “logical zero”.
5. Diagnosis and error treatment
5-12 Festo P.BE-VIFB8-03-EN en 0002d
The four status bits supply coded diagnostic information withthe following meaning:
Status bits*) Diagnostic information
27 26 25 24
0 0 0 0 No error
X 0 1 X Short circuit/overload at the output
X 1 0 X Vvalves � 21.6 V
X 1 1 X Voutputs � 10 V
1 X X X Vsensor � 10 V
X = not relevant*) The status bits can always be addressed with the four highest-value addresses of the configuredaddress range.
Fig. 5/9: Coded diagnostic information of the four status bits
5. Diagnosis and error treatment
5-13Festo P.BE-VIFB8-03-EN en 0002d
Diagnostic information Description Method of operation
Short circuit/overload at theoutput
Output short-circuited or over-loaded.
Monitors the electric outputs ofthe output modules
Vvalves � 21.6 V Load voltage at pin 2 (valvesand outputs) of the operatingvoltage connection � 21.6 V
Monitors the tolerance of theload voltage for valves and elec-tric outputs
Voutputs � 10 V Load voltage at pin 2 (valvesand outputs) of the operatingvoltage connection � 10 V
Monitors the load voltage forvalves and electric outputs (novoltage, e.g. EMERGENCYSTOP)
Vsensor � 10 V Operating voltage at pin1 (elec-tronics and inputs) of operatingvoltage connection � 10 V
Monitors the operating voltagefor inputs (sensors). Showswhether an internal fuse hasbeen triggered (fuse on node orat least an electronic fuse onthe input module1)
VIGE-03-FB-8-S)
1) Electronic fuse for input modules available since February 1999.
Fig. 5/10: Diagnostic information
5. Diagnosis and error treatment
5-14 Festo P.BE-VIFB8-03-EN en 0002d
5.2.1 Short circuit/overload
In the event of a short circuit or overload, “Short circuit/over-load” will be entered in the four status bits of the error codein the node.
Short circuit/overload at an I/O module
Valve terminals types 03 or 04-B can be fitted with the follow-ing I/O modules:
– output modules
– high-current output modules
– multi I/O modules
– input modules
– input modules with fuse
The reaction of these modules to a short circuit/overload isdescribed in the “Supplementary description of the I/O mod-ules”.
5. Diagnosis and error treatment
5-15Festo P.BE-VIFB8-03-EN en 0002d
5.3 Error treatment
5.3.1 Reaction to errors in the control system
The outputs of the valve terminal are switched off in the fol-lowing cases:
– Transmission errors
– The controller is switched from “Run mode” to “Programmode”
– Cable fracture
CautionThe switch-off reaction differs according to the softwareversion in the FB8 terminal node.
Time-delay switch-off of the outputs in the event of an error
up to version V1.42(software status 30.9.96)
as from version V1.5(software status 30.11.98 and later)
Baud rate Time-delay switch offof the outputs In the event of an error, switching off takes place
irrespective of the baud rate set57.6 kBaud 2000 ms
irrespective of the baud rate set.
after 100 ms if the valve terminal does not115.2 kBaud 1000 ms
– after 100 ms, if the valve terminal does notrecognize any telegrams on the RIO networkif f th 255 t l i d
230.4 kBaud 500 ms– if none of the 255 telegrams recognized was
addressed to the valve terminal
Fig. 5/11: Time-delay switch-off of valve terminal outputs depends on software status
5. Diagnosis and error treatment
5-16 Festo P.BE-VIFB8-03-EN en 0002d
5.3.2 Short circuit/overload at an output module
The following happens if there is a short circuit or overload atan output:
– the digital output will be switched off
– the red LED will light up
– the error bit “Short circuit/overload“ in the diagnosticbyte will be set to “logical 1”
– the error code “Short circuit/overload” will be entered inthe status bits.
In order to activate the output again, proceed as follows:
Step Explanation
Eliminate short circuit/overload
Reset output to “logical 0” � Manual (control)� automatically in the PLC pro-
gramThe error bit in the diagnosticword of the valve terminal isreset to “logical 0”.
The output can then be reset to “logical 1”. If the short circuitstill exists, the output will be switched off again.
5. Diagnosis and error treatment
5-17Festo P.BE-VIFB8-03-EN en 0002d
5.3.3 Reaction to faults in the control system
Reaction of the PLC to faults
RIO network in the control system
Depending on the softwarestatus, all outputs (valves andelectric outputs) will beswitched off after a time delay inthe event of a fault.
Please note– Unilaterally-actuated valves
move to the basic position.– Double-solenoid valves re-
main in the current position.– Mid-position valves move to
the mid-position and (depend-ing on valve type) are pressur-ized,exhausted or blocked.
Fig. 5/12: Reaction of the control system to faults
5. Diagnosis and error treatment
5-18 Festo P.BE-VIFB8-03-EN en 0002d
5.4 Type 04-B: Fuses for the pilot solenoids
The pilot solenoid coils of the valve terminals of type 04-B arefused separately with (quick acting) 0.315 A fuses. Thesefuses are situated on the printed circuit board (behind acover) in each manifold sub-base. Each single-solenoid mani-fold sub-base is fitted with one fuse; each double-solenoidmanifold sub-base is fitted with two fuses.
Replacing defective/burnt through 0.315 A fuses
In order to replace burnt through fuses, proceed as follows(note also Fig. 5/8).
1. Switch off the compressed air supply and the power sup-ply (connections 1 and 2).
2. Open the cover of the manifold sub-base.
3. Carefully remove the defective/burnt through fuse fromits base (see diagram).
4. Insert a new (quick-acting) 0.315 A fuse.
5. Close the cover.
5. Diagnosis and error treatment
5-19Festo P.BE-VIFB8-03-EN en 0002d
1
1 2 3
1 Fastening screws of the cover
2 Left-hand fuse for pilot solenoid coil 12
3 Right-hand fuse for pilot solenoid coil 14
Fig. 5/13: Replacing a fuse for a pilot solenoid coil
Further information can be found in the Pneumatics manualfor valve terminal type 04-B.
5. Diagnosis and error treatment
5-20 Festo P.BE-VIFB8-03-EN en 0002d
Technical appendix
A-1Festo P.BE-VIFB8-03-EN en 0002d
Appendix A
A. Technical appendix
A-2 Festo P.BE-VIFB8-03-EN en 0002d
Contents
A. Technical appendix A-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.1 Technical specifications A-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.2 Cable length and cross-sectional area A-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.3 Examples of circuitry A-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.3.1 Power supply type 03 – internal layout A-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
A.3.2 Power supply type 04-B – internal layout A-14. . . . . . . . . . . . . . . . . . . . . . . . . . . .
A. Technical appendix
A-3Festo P.BE-VIFB8-03-EN en 0002d
A.1 Technical specifications
General
Protection class (as perEN 60529)
Temperature during– operation– storage/transport
IP 65
- 5 °C ... +50 °C-20 °C ... +60 °C
Vibration(as per DIN/IEC68/EN 60068part 2-6 and as per IEC721/EN 60068 part 2-3)– transport
– operation
Shock(as per DIN/IEC 68/EN 60068part 2-27 and IEC 721)
3.5 mm path at 2-8 Hz1 g acceleration at 8-25 Hz0.35 mm path at 25-57 Hz5 g acceleration at 57-150 Hz1 g acceleration at 150-200 Hz
30 g at 11 ms duration
Electromagnetic compatibility(EMC)Immunity against interference– tested as per EN 50082-2Interference emitted– tested as per EN 50081-2
Industry
Industry
Protection against electricshock (Protection against di-rect and indirect contact as perEN 60204-1/IEC 204)
With a PELV power unit (ProtectedExtra Low Voltage)
A. Technical appendix
A-4 Festo P.BE-VIFB8-03-EN en 0002d
Operating voltage for electronics and inputs
(pin 1 – operating voltage con-nection)– Rated value (protected
against incorrect polarity)– Tolerance– Residual ripple– Current consumption (at 24 V)– Fuses for supply to inputs/
sensors
Power consumption (P)– Calculation
Bridging time (drop in logicvoltage)
24 V DC
± 25 % (18 V ... 30 V DC)4 Vpp200 mA + suminternal current consumption ofinputs 2 A, slow-blowing
P[W] = (0.2 A + � Iinputs)�24 V
min. 5 ms
Load voltage for outputs/valves
(pin 2 – load voltage connection)
– Rated value (protectedagainst incorrect polarity)
– Tolerance– Residual ripple– Current capacity (at 24 V)
Power consumption (P)– Calculation
External fuse required (typ. 10 A,see circuitry examplechapter 3.3.2)24 V DC
±10 % (21.6 V ... 26.4 V DC)4 Vpp10 mA+ sum of current consumption
of electric outputs+ sum of current consumption
of switched valve solenoidcoils (e. g. per MIDI-valvesolenoid coil 55 mA)
P[W] = 0.01A+�Ielectr. outputs+�Isolenoid coil) � 24 V
Field bus
Design Master-slave
Transmission type serial asynchronous, half-duplex
A. Technical appendix
A-5Festo P.BE-VIFB8-03-EN en 0002d
Field bus
Protocol A-B RIO network
Baud rate 57.6 kBaud115.2 kBaud230.4 kBaud
Cable type– depending on cable length
and field bus baud rate setsee controller manual
Cable length– depending on baud rate and
cable type3.3 km at 57.6 kBaud1.6 km at 115.2 kBaud0.8 km at 230.4 kBaud
Please refer to the pneumatics manual for technical specifica-tions concerning pneumatics and valves.
Please refer to the supplementary description of the I/O mod-ules for technical specifications concerning the I/O modules.
A. Technical appendix
A-6 Festo P.BE-VIFB8-03-EN en 0002d
A.2 Cable length and cross-sectional area
Please noteIt is assumed here that the user is already familiar with theinformation contained in the chapters “Installation” in thismanual. The following information is therefore aimed ex-clusively at personnel trained in electro-technology.
A load-dependent drop in voltage occurs on all three cablesof the power supply to a valve terminal. This can cause thevoltage at pin 1 or pin 2 of the power supply connection to beoutside the permitted tolerance.
Recommendation:
� Avoid long distances between the power unit and thevalve terminal.
� Calculate suitable cable lengths and cross-sectional areaswith the aid of the graphs or formulae below. When doingthis please note the following:– the graphs provide approximate values for cross
sectional areas 1.5 and 2.5 mm2.– the formulae provide exact values for any cross
section.
Please noteIn the following graphs and formulae it is assumed that thecross sections of the power supply cables (pins 1, 2 and 3)are the same.
A. Technical appendix
A-7Festo P.BE-VIFB8-03-EN en 0002d
Calculating with the graph
Proceed as follows:
1. Calculate the maximum current consumption of the out-puts/valves (I2).
2. Calculate the lowest voltage to be expected during oper-ation (VBmin) on the power unit. When doing this, pleasenote:– the load dependency of the power unit– the fluctuations in the primary mains voltage
3. Read off the permitted cable length for your cross sectionin the relevant table.Example for 1.5 mm2:VBmin = 22.8 V, I2 = 2 A; Lmax = 25 m
A. Technical appendix
A-8 Festo P.BE-VIFB8-03-EN en 0002d
VBmin
Cable length
Current I2 [A]
[V]
[m]
Fig. A/1: Calculating the maximum cable length for cross sectional area 1.5 mm2
VBmin
Cable length
Current I2 [A]
[m]
[V]
Fig. A/2: Calculating the maximum cable length for cross sectional area 2.5 mm2
A. Technical appendix
A-9Festo P.BE-VIFB8-03-EN en 0002d
Calculating with a formula
Proceed as follows:
1. Calculate the maximum current consumption of the inputsand electronics (I1) as well as of the outputs/valves (I2).
2. Calculate the lowest voltage to be expected during oper-ation (Vmin) on the power unit. When doing this, pleasenote:– – the load dependency of the power unit– – the fluctuations in the primary mains voltage
3. Enter the values in the formula below. The equivalent cir-cuit diagram and the example explain the correlation.
A. Technical appendix
A-10 Festo P.BE-VIFB8-03-EN en 0002d
T 10 A
Pin 1
Pin 2
Pin 3
T 3.15 A
AC
DC
RL1 VL1 RL2 VL2
RI1 RL2
RL0 VL2+VL1
0 V
Vvalve terminal
I1I2
I0
Power supply
Valve terminal
Equivalent circuit diagram
L
VB
1
2
3
1 Line resistance (outgoing) RL1 + RL2
2 Line resistance (incoming) RL0
3 L = distance (cable length)
Fig. A/3: Equivalent circuit diagram for power supply
A. Technical appendix
A-11Festo P.BE-VIFB8-03-EN en 0002d
Formula for cable length:
L ≤
(VBmin - 21.6 V) � A � �CU
2 ¡ I2 + I1
¡
This means:
– 21.6 V VVALVE TERMINAL = 24 V ± 10%, minimum:≥ 21.6 V
– VBmin = minimum supply voltage(at the power unit)
– l1 = current for electronics and inputs
– I2 = current for outputs/valves
– A = cable cross section (uniform e. g. 1.5 mm2)
– � = conductance value of cables
(uniform e. g. �Cu = 56m
mm2 � �
Example:I1 = 1 AI2 = 5 AVBmin = 24 VVVALVE TERMINALmin = 21.6 V
�Cu = 56m
mm2 � � �
Result of example:
L≤ 18 m for A = 1.5 mm2
L≤ 30 m for A = 2.5 mm2
A. Technical appendix
A-12 Festo P.BE-VIFB8-03-EN en 0002d
A.3 Examples of circuitry
1 24 V supply forelectronics andinputs
2 24 V load voltagesupply for valvesand outputs
3 0 V
4 Earth connection
1
2
3
4
Fig. A/4: Pin assignment (node)
A. Technical appendix
A-13Festo P.BE-VIFB8-03-EN en 0002d
A.3.1 Power supply type 03 – internal layout
1 Electric outputs*)
2 Valves*)
3 Power supplyconnection ofnode type 03
4 Potentialequalization
5 Load voltage canbe switched offseparately.
6 Power unit(e. g. centralpower supply)
7 24V electronics(fused internally)
8 Electric inputs/sensors (fused in-ternally)
1 2
8
7
230 V
3.15 A
10 A
2 A
24 V
24 V ± 10 %
0 V
456
3
4
*) (must be fused externally)
Fig. A/5: Example of circuitry and internal layout of type 03
A. Technical appendix
A-14 Festo P.BE-VIFB8-03-EN en 0002d
A.3.2 Power supply type 04-B – internal layout
1 Electric outputs(fused internally)
2 Adapter cable
3 Valves max. 50 %simultaneity(fused internally)
4 Power supplyconnectionadapter plate(type 04-B)
5 Potentialequalization
6 Load voltage canbe switched offseparately
7 Power unit (e. g.central powersupply)
8 24V electronics(fused internally)
9 Electric inputs/sensors (fused in-ternally)
1
2
7
230 V
3.15 A
10 A
2 A
24 V
24 V ± 10%
0 V
3
56
8
4
9
Fig. A/6: Example of circuitry and internal layout of type 04-B
Accessories
B-1Festo P.BE-VIFB8-03-EN en 0002d
Appendix B
B. Accessories
B-2 Festo P.BE-VIFB8-03-EN en 0002d
B. Accessories B-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
B.1 Connecting the cables to the plugs/sockets B-3. . . . . . . . . . . . . . . . . . . . . . . . .
B. Accessories
B-3Festo P.BE-VIFB8-03-EN en 0002d
B.1 Connecting the cables to the plugs/sockets
CautionThe position of the pins on the plug is different from thaton the socket.
– The connections of the input/output modules are in theform of sockets.
– The connections for the power supply are in the form ofplugs.
Please see the following chapters for the pin assignment.
When you have selected suitable cables, connect them to theplugs/sockets in accordance with the steps listed below.
1. Open the Festo plugs/sockets as follows (see diagram):
– Mains power supply socketInsert the power supply socket in the power supplyconnection of the valve terminal. Unscrew the housingof the socket.Then remove the connecting part of the socket which isinserted in the power supply connection.
– Sensor plug (for input/output modules):Loosen the centre knurled nut.
B. Accessories
B-4 Festo P.BE-VIFB8-03-EN en 0002d
2. Open the strain relief on the rear of the housing. Pass thecable through as follows (see diagram).
Outer diameter of cable– PG7: 4.0 ... 6.0 mm– PG9: 6.0 ... 8.0 mm– PG13.5: 10.0 ... 12.0 mm
Plug/socket (straight or angled):– Power supply socket PG7, 9 or 13.5– Sensor plug PG7– Bus cable socket PG7, 9 or 13.5
1 Cables
2 Strain relief
3 Housing
4 Connecting part
5 Plug
6 Socket
1
2
3
4
56
4
Fig. B/1: Individual plug/socket parts and cable routing
B. Accessories
B-5Festo P.BE-VIFB8-03-EN en 0002d
3. Remove 5 mm of insulation from the end of the conduc-tors.
4. Fit end sleeves to the wires.
5. Connect the conductors.
6. Place the connecting part back on the housing of the plugand screw the two items together. Pull the cable back sothat there are no loops inside the housing.
7. Tighten the strain relief.
B. Accessories
B-6 Festo P.BE-VIFB8-03-EN en 0002d
Index
C-1Festo P.BE-VIFB8-03-EN en 0002d
Appendix C
C. Index
C-2 Festo P.BE-VIFB8-03-EN en 0002d
C. Index C-1. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C-3Festo P.BE-VIFB8-03-EN en 0002d
A
A-B specific functionsLast chassis 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Restart locking of the processor 3-5. . . . . . . . . . . . . . . . . . .Retain last status 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Abbreviations V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address assignment, general 4-6. . . . . . . . . . . . . . . . . . . . . .
Address assignment 4-14. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Address range 4-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Addressing example 4-22. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Addressing possibilities 4-17. . . . . . . . . . . . . . . . . . . . . . . . .
Allen-BradleyAddressing example 4-22. . . . . . . . . . . . . . . . . . . . . . . . . .Addressing possibilities 4-17. . . . . . . . . . . . . . . . . . . . . . .Addressing scheme 4-15. . . . . . . . . . . . . . . . . . . . . . . . . . .Configuration 4-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .I/O addresses 4-16. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Allen-Bradley 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Assignment of I/O addresses 4-16. . . . . . . . . . . . . . . . . . . . .
B
Baud rate 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bus configuration 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bus nodeConfiguration settings 3-7. . . . . . . . . . . . . . . . . . . . . . . . . . .Einstellen Setting the DIL switch 3-10. . . . . . . . . . . . . . . .LED displays 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Opening and closing 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Bus node# 3-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C
CablesConnecting B-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C-4 Festo P.BE-VIFB8-03-EN en 0002d
Load voltage 3-11, A-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . .Selection A-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Configuration example 4-21. . . . . . . . . . . . . . . . . . . . . . . . . . .
ConnectingPower supply 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .RIO interface 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connection variantsLooping through 3-19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .T-adapter 3-20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
ConnectionsElectric modules 1-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .ISO modules 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MAXI modules 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MIDI modules 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
CurrentCalculation 3-12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Fuse 3-14. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Selecting the cables A-6. . . . . . . . . . . . . . . . . . . . . . . . . . .
D
Designated use I. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
DiagnosisBus node 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .LEDs 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnosis 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Diagnostic information 5-12, 5-13. . . . . . . . . . . . . . . . . . . . . .
DIL switch, setting 3-8, 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . .
E
EarthingComponents 2-4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Potential equalization 3-16. . . . . . . . . . . . . . . . . . . . . . . . .
EMERGENCY STOP circuit 3-14. . . . . . . . . . . . . . . . . . . . . . . .
End plates 2-4, 2-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C-5Festo P.BE-VIFB8-03-EN en 0002d
Error treatment 5-15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
F
FaultsField bus 5-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .PLC 5-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
FuseExternal 3-14, 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Internal 3-17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
H
Half rack 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Hat rail 2-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
I
Inputs, Calculating 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Installation, Terminating resistor 3-23. . . . . . . . . . . . . . . . . .
INTERBUS, Configuration 4-13. . . . . . . . . . . . . . . . . . . . . . . .
L
LED displayInputs 5-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Node 5-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Outputs 5-8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
LED displays, node 3-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
O
Outputs, Calculating 4-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C-6 Festo P.BE-VIFB8-03-EN en 0002d
P
Pictograms IV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pin assignment, Operating voltage 3-15. . . . . . . . . . . . . . . .
Pin assignment, RIO interface 3-21. . . . . . . . . . . . . . . . . . . . .
Power supplyCable length A-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Switching on 4-13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Power supply connection 3-14. . . . . . . . . . . . . . . . . . . . . . . .
Power unit 3-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Q
Quarter rack 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
R
Remote I/O block 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
RIO interface, Pin assignment 3-21. . . . . . . . . . . . . . . . . . . .
RIO network, Extension possibilities 3-22. . . . . . . . . . . . . . . .
S
Service II. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Set the test routine 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Setting, valve terminal address 3-8. . . . . . . . . . . . . . . . . . . . . .
Setting the baud rate 3-10. . . . . . . . . . . . . . . . . . . . . . . . . . . .
Short circuit/overload 5-14. . . . . . . . . . . . . . . . . . . . . . . . . . .Short circuit/overload at an I/O module 5-14. . . . . . . . . . .Short circuit/overload at an output module 5-16. . . . . . .
Status bits 5-11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Switching statusInputs 5-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Outputs 5-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
C. Index
C-7Festo P.BE-VIFB8-03-EN en 0002d
System structure 3-3. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
T
Target group II. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical specifications A-3. . . . . . . . . . . . . . . . . . . . . . . . . .
Terminating resistor 3-23. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Test routineStarting 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Stopping 5-10. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .Valves 5-9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Text markings IV. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Time-delay switch off 5-15. . . . . . . . . . . . . . . . . . . . . . . . . . . .
U
User instructions III. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
V
Valve terminal address 3-8. . . . . . . . . . . . . . . . . . . . . . . . . . . .
ValvesISO 1-7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MAXI 1-3, 1-6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .MIDI 1-3, 1-5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Voltage, selecting the cables 3-11. . . . . . . . . . . . . . . . . . . . .
C. Index
C-8 Festo P.BE-VIFB8-03-EN en 0002d