Vacuum Controls Status
MACS week December 2010
PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner1
![Page 2: Vacuum Controls Status MACS week December 2010 PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner 1.](https://reader036.fdocuments.us/reader036/viewer/2022082611/56649ee85503460f94bf8fca/html5/thumbnails/2.jpg)
Progress and time schedule
• Agreement with WP Controls about system to be used as interface between PVSS and vacuum equipment
• Attended to PVSS (WinCC OA) course at CERN• Planned to start programming of control system
Feb 2011• Further training on PVSS foreseen to be able to
act as first level support
PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner2
![Page 3: Vacuum Controls Status MACS week December 2010 PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner 1.](https://reader036.fdocuments.us/reader036/viewer/2022082611/56649ee85503460f94bf8fca/html5/thumbnails/3.jpg)
Design of Vac Control System
• Two main parts:• PVSS in combination with OPC Server for data
acquisition and general controling• Sector valve controller cards for interlock handling on
hardware basis
• Each sector has at least 3 pressure sensors (gauges and ion pumps)
• >1 pressure sensor gives a pressure over a certain thresholdInterlock
• Controllers of pumps and gauges can handle 2 or more devicesnever more than one device of a sector handled by one controller
PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner3
![Page 4: Vacuum Controls Status MACS week December 2010 PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner 1.](https://reader036.fdocuments.us/reader036/viewer/2022082611/56649ee85503460f94bf8fca/html5/thumbnails/4.jpg)
Design of Vac Control System
• Thresholds for interlocks are set in the controllers• Controller is directly connected with the valve
controller cards of the sector valves belonging to the sector
• Communication between valve controller cards and PVSS over 3 digital I/Os:• Input: Open/Close• Output: Valve open• Output: Valve closed
PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner4
![Page 5: Vacuum Controls Status MACS week December 2010 PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner 1.](https://reader036.fdocuments.us/reader036/viewer/2022082611/56649ee85503460f94bf8fca/html5/thumbnails/5.jpg)
Design of Vac Control System
PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner5
Racks with controllers for gauges and pumps
PVSS and OPC
Server
Rack with sector valve
controllers
Digital I/Os
RS232RS422RS485
analogue
Global Interlock System
“Pressure threshold
exceeded”
![Page 6: Vacuum Controls Status MACS week December 2010 PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner 1.](https://reader036.fdocuments.us/reader036/viewer/2022082611/56649ee85503460f94bf8fca/html5/thumbnails/6.jpg)
Interlocks
PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner6
Racks with controllers for gauges and pumps
PVSS and OPC
Server
Rack with sector valve
controllers
Digital I/Os
RS232RS422RS485
analogue
Global Interlock SystemP
t
Close!
Interlock!
Nothing happens on the interlocks…
Message to operator/vac responsible
“Pressure threshold
exceeded”
![Page 7: Vacuum Controls Status MACS week December 2010 PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner 1.](https://reader036.fdocuments.us/reader036/viewer/2022082611/56649ee85503460f94bf8fca/html5/thumbnails/7.jpg)
PP-101207-a-JWA-VacControlStatus.ppt Joachim Wallner7
Thank you for your attention