SETUP MANUAL
Cat. No. V107-E1-04
NB3Q-TWB
NB5Q-TWBNB7W-TWB
NB10W-TW01B
NB-series
Programmable Terminals
-
5/20/2018 V107-E1-04+NB series Setup Manual
2/102
OMRON, 2012
All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or
by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of
OMRON.
No patent liability is assumed with respect to the use of the information contained herein. Moreover, because OMRON is con-stantly striving to improve its high-quality products, the information contained in this manual is subject to change without
notice. Every precaution has been taken in the preparation of this manual. Nevertheless, OMRON assumes no responsibility
for errors or omissions. Neither is any liability assumed for damages resulting from the use of the information contained in
this publication.
-
5/20/2018 V107-E1-04+NB series Setup Manual
3/102
NB-series
NB3Q-TWB
NB5Q-TWBNB7W-TWB
NB10W-TW01B
Programmable Terminals
Setup Manual
Revised August 2012
-
5/20/2018 V107-E1-04+NB series Setup Manual
4/1021NB-series Programmable Terminals Setup Manual(V107)
Introduction
Thank you for purchasing an NB-series Programmable Terminal.
NB-Series Programmable Terminals (PTs) are designed to handle information generated in FA productionsites. Be sure to understand the functions and performances etc thoroughly before using PT correctly.
This manual is intended for the following personnel, who must also have knowledge of electricalsystems (an electrical engineer or the equivalent).
Personnel in charge of introducing FA systems into production facilities.
Personnel in charge of designing FA systems.
Personnel in charge of installing and connecting FA facilities.
Personnel in charge of managing FA systems and facilities
The user must operate the product according to the performance specifications described in theoperation manuals.
Do not use the PT touch switch input functions for applications where danger to human life or seriousproperty damage is possible, or for emergency switch applications.
Before using the product under conditions which are not described in the manual or applying theproduct to nuclear control systems, railroad systems, aviation systems, vehicles, combustionsystems, medical equipment, amusement machines, safety equipment, and other systems,machines and equipment that may have a serious influence on lives and property if used improperly,consult your OMRON representative.
Make sure that the ratings and performance characteristics of the product are sufficient for thesystems, machines, and equipment, and be sure to provide the systems, machines, and equipmentwith double safety mechanisms.
This manual provides information for connecting and setting up an NB-Series PT. Be sure to readthis manual before attempting to use the PT and keep this manual close at hand for reference duringinstallation and operation.
Intended Audience
General Precautions
-
5/20/2018 V107-E1-04+NB series Setup Manual
5/102
2 NB-series Programmable Terminals Setup Manual(V107)
NB-series Manuals
NB-series manuals are organized in the sections listed in the following tables. Refer to the appropriate
section in the manuals as required.
Programmable Terminals Setup Manual (Cat. No. V107)(This Manual)
Section Contents
Section 1 Part Names and Functions This section describes the names and functions of the various parts ofan NB Unit.
Section 2 Installing the NB Unit and
Connecting Peripheral Devices
This section describes the methods used to install the NB Unit andconnect peripheral devices.
Section 3 System Setting Mode This section describes the System Setting Mode.Section 4 Calibrate Mode This section describes the Calibrate Mode.
Appendices The appendices provide information on specifications, dimensions,wirings, and lists of the NB Units, the applicable PLCs and options.
Programmable Terminals NB-Designer Operation Manual(Cat. No. V106)
Section Contents
Section 1 Introduction This section provides an outline of the NB-series PTs, including their
functions, features, connection types and communication methods.Section 2 Installation and Startup of
NB-Designer
This section describes how to install and start the NB-Designer.
Section 3 Functions of NB-Designer This section describes the functions of NB-Designer.
Section 4 Functions of NBManager This section describes the functions of NBManager.
Section 5 Maintenance and
Abnormality Handling
This section describes the maintenance and check to prevent theabnormality occurrence and the handling of the abnormalities occurredin NB Unit.
Section 6 Descriptions of New
Functions Added into NB-
TW01B
This section describes the new functions added into NB-TW01B,the system attributes and the component attributes.
Appendices The appendices provide lists of the NB Units, the Communication Units,the applicable PLCs, and the list of NB-Designer functions.
-
5/20/2018 V107-E1-04+NB series Setup Manual
6/1023NB-series Programmable Terminals Setup Manual(V107)
Programmable Terminals Host Connection Manual (Cat. No. V108)
Section Contents
Section 1 List for All PLCs
Supported by NB series
This section lists all PLCs supported by NB Units.
Section 2 Connecting to SIEMENS
PLCs
This section describes the connection to SIEMENS PLCs.
Section 3 Connecting to Mitsubishi
PLCs
This section describes the connection to Mitsubishi PLCs.
Section 4 Connecting to Schneider
PLCs
This section describes the connection to Schneider PLCs.
Section 5 Modbus Connection This section describes the connection on Modbus protocol.
Section 6 Connecting to Delta PLCs This section describes the connection to Delta PLCs.
Section 7 Connecting to LG PLCs This section describes the connection to LG PLCs.
Section 8 Connecting to PanasonicPLCs This section describes the connection to Panasonic PLCs.
Section 9 Connecting to Allen-
Bradley (Rockwell) PLC
This section describes the connection to Allen-Bradley PLC.
Section 10 Connecting to PLC of GE
Fanuc Automation Inc.
This section describes the connection to PLC of GE Fanuc AutomationInc.
Programmable Terminals Startup Guide Manual (Cat. No. V109)
Section Contents
Section 1 NB Overview This section provide specifications of the NB Unit, describes its namesand functions of the various parts.
Section 2 System Design This section describes the manual structure, takes NB7W as anexample to introduce the operation procedures of the NB system.
Section 3 Installation and Wiring This section describes how to install and wire the NB Unit.
Section 4 Screen Creation This section describes how to create a demonstration project throughNB-Designer.
Section 5 Run This section describes how to start running at the Host side andprepare to send screen data to NB7W.
Section 6 Maintenance and
Troubleshooting
This section describes the maintenance and inspection methods forpreventing errors occurring, and troubleshooting measures when errorsoccur.
WARNING
Failure to read and understand the informationprovided in this manual may result in personal injuryor death, damage to the product, or product failure.Please read each section in its entirety and be sure
you understand the information provided in thesection and related sections before attempting anyof the procedures or operations given.
-
5/20/2018 V107-E1-04+NB series Setup Manual
7/102
4 NB-series Programmable Terminals Setup Manual(V107)
Manual Structure
The following page structure and icons are used in this manual.
Special information in this manual is classified as follows:
Page Structure and Icons
Special Information
2-3
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-1InstallingtheNBUnit
2
2-1-2InstallationontotheOperationPanel
Install the NB Unit by embedding it into the operation panel.
Use the metal kit and tool (a crosshead screwdriver) supplied with the Unit for installation.
Proceed the installation following the procedures below.
1 Panel cutout with dimensions is shown below. Fit the NB Unit into the panel from the front side.
2 As follows, insert panel fixators at the locations indicated by red box around the back of the NB Unit.Insert the hooks of positioners into the square holes on the Unit to hold the fixators properly, andtighten the screws firmly with the screwdriver.
NB5Q/NB7W-TWB
Precautions for Safe Use
When operating on the operation panel, make sure to keep metal particles from entering theUnit.
The mounting panel must be between 1.6 and 4.8 mm thick. The NB Unit must be installedin a control panel.
For the sake of waterproof and dustproof, all the fixators must be evenly tightened to atorque of 0.5~0.6 Nm. If the ti ghtening torque exceeds the specified value, or the tighteningis not even, deformation of the front panel may occur.
Make sure that the operation panel i s clean, unbent, and strong enough for the installationprocess.
2-1-2 Installation onto the Operation Panel
Models Opening Dimension (W H mm)
NB3Q-TW00B/TW01B 119.0(+0.5/-0) 93.0(+0.5/-0)
NB5Q-TW00B/TW01B 172.4(+0.5/-0) 131.0(+0.5/-0)
NB7W-TW00B/TW01B 191.0(+0.5/-0) 137.0(+0.5/-0)
N B1 0W- TW0 1B 2 58. 0( +0. 5/ -0) 2 00 .0 (+0 .5 /- 0)
Opening dimensions
Width
Height
Level 1 headingLevel 2 headingLevel 3 heading
Step in a procedure
Manual name
Special Information
(See below.)
Level 3 heading
Page tab
Gives the currentheadings.
Indicates a step in aprocedure.
Gives the numberof the section.
This illustration is provided only as a sample and may not literally appear in this manual.
Icons are used to indicate
precautions andadditional information.
Precautions for Safe UsePrecautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct UsePrecautions on what to do and what not to do to ensure proper operation and performance.
Additional Information
Additional information to increase understanding or make operation easier.
-
5/20/2018 V107-E1-04+NB series Setup Manual
8/1025NB-series Programmable Terminals Setup Manual(V107)
Terminology
The following terminology is used in this manual.
Terms Descriptions
NB Unit Indicates the main Unit of the products in the OMRON NB Series of ProgrammableTerminal.
NB Series Indicates products in the OMRON NBSeries of Programmable Terminal.In this manual, unless otherwise specified, NBSeries is taken as the subjectconcerned.
PLC Indicates a Programmable Controller.
CP Series Indicates the following products in the OMRON CP Series of Programmable Controllers:CP1H, CP1L, CP1E
CS/CJ Series Indicates the following products in the OMRON CS/CJ Series of ProgrammableControllers: CS1G, CS1H, CS1G-H, CS1H-H, CJ1G, CJ1M, CJ2M, CJ2H
C Series Indicates the following products in the OMRON C Series of Programmable Controllers:C200HX(-Z), C200HG(-Z), C200HE(-Z), CQM1, CQM1H, CPM1A, CPM2A, CPM2C
Serial CommunicationUnit
Indicates a Serial Communication Unit for an OMRON SYSMAC CS/CJ-Series PLC.
Serial CommunicationBoard
Indicates a Serial Communication Board for an OMRON SYSMAC CS/CJ-Series PLC.
Communication Board Indicates a Communication Board for an OMRON C200HX/HG/HE(-Z) PLC.
CPU Unit Indicates a CPU Unit in the OMRON CP, CS/CJ or SYSMAC C Series of ProgrammableControllers.
NB-Designer Indicates the OMRON NB-Designer.
Host Indicates the PLC and other units functioning as the control devices for NB-Series
Units.PT Indicates an OMRON Programmable Terminal.
HMI Indicates an OMRON Programmable Terminal.
-
5/20/2018 V107-E1-04+NB series Setup Manual
9/102
6 NB-series Programmable Terminals Setup Manual(V107)
-
5/20/2018 V107-E1-04+NB series Setup Manual
10/1027NB-series Programmable Terminals Setup Manual(V107)
CONTENTS
Introduction............................................................................................................... 1
NB-series Manuals.................................................................................................... 2
Manual Structure ...................................................................................................... 4
Terminology .............................................................................................................. 5
Safety Precautions ................................................................................................. 12
Precautions for Safe Use ....................................................................................... 14
Precautions for Correct Use .................................................................................. 16
Conformance to EC Directives.............................................................................. 17
Related Manuals ..................................................................................................... 18
Sec. 1 Part Names and Functions.................................................... 1-1
1-1 Part Names............................................................................................................................... 1-2
1-2 Part Specifications .................................................................................................................. 1-6
Sec. 2 Installing the NB Unit and Connecting Peripheral Devices 2-12-1 Installing the NB Unit .............................................................................................................. 2-2
2-1-1 Installation environment.............................................................................................................. 2-22-1-2 Installation onto the Operation Panel.......................................................................................... 2-32-1-3 Connecting the Power Supply..................................................................................................... 2-52-1-4 Grounding Wiring........................................................................................................................ 2-6
2-2 Start of NB Series.................................................................................................................... 2-7
2-3 Connecting of NB-series with PC .......................................................................................... 2-82-3-1 Connecting by RS-232C............................................................................................................. 2-82-3-2 Connecting by USB .................................................................................................................... 2-92-3-3 Connecting by Ethernet ............................................................................................................ 2-10
2-4 Serial Communication Connection...................................................................................... 2-112-4-1 Host Link Connection Method................................................................................................... 2-112-4-2 Connecting more than one PLC ............................................................................................... 2-122-4-3 Settings for each Unit ............................................................................................................... 2-13
2-5 FINS/UDP Communication Connection............................................................................... 2-262-5-1 Connecting to Host Via Ethernet .............................................................................................. 2-262-5-2 Parameter Settings for FINS/UDP at NB Side.......................................................................... 2-292-5-3 Host Types and Settings of Ethernet Unit................................................................................. 2-312-5-4 Host Types and Settings of Ethernet/IP Unit ............................................................................ 2-382-5-5 Parameter Settings for FINS/UDP at Host Side........................................................................ 2-42
Sec. 3 System Setting Mode............................................................. 3-13-1 Display Method of System Setting Mode .............................................................................. 3-2
3-2 Functions of System Setting Mode........................................................................................ 3-3
-
5/20/2018 V107-E1-04+NB series Setup Manual
11/102
8 NB-series Programmable Terminals Setup Manual(V107)
Sec. 4 Calibrate Mode ....................................................................... 4-1
4-1 Display Method of Calibrate Mode ......................................................................................... 4-2
4-2 Functions of Calibrate Mode .................................................................................................. 4-2
4-3 On-line Touch-control Calibration Function.......................................................................... 4-2
Sec. A Appendices.............................................................................A-1
A-1 Specifications .........................................................................................................................A-2A-1-1 General Specifications ................................................................................................................A-2A-1-2 Performance Specifications.........................................................................................................A-2A-1-3 Communication Specifications....................................................................................................A-4
A-2 External Dimensions ...............................................................................................................A-5
A-3 RS-422A/485 Connections ......................................................................................................A-7A-3-1 Grounding and Shielding of the Cables ......................................................................................A-7
A-4 Fabrication of the Connection Cable .....................................................................................A-9A-4-1 Cable Processing........................................................................................................................A-9A-4-2 Soldering...................................................................................................................................A-10A-4-3 Shield Assembly........................................................................................................................A-10A-4-4 Method for Fabricating the Cable for Connection to OMRON PLC...........................................A-11A-4-5 Method for fabricating the cable for connection to PC ..............................................................A-13
A-5 List of Models ........................................................................................................................A-14
A-6 List of Options .......................................................................................................................A-19
Revision History ........................................................................................................ 1
-
5/20/2018 V107-E1-04+NB series Setup Manual
12/1029NB-series Programmable Terminals Setup Manual(V107)
Read and Understand this Manual
Please read and understand this manual before using the product. Please consult your OMRON representativeif you have any questions or comments.
Warranty and Limitations of Liability
WARRANTY
OMRONs exclusive warranty is that the products are free from defects in materials and workmanship for aperiod of one year (or other period if specified) from date of sale by OMRON.
OMRON MAKES NO WARRANTY OR REPRESENTATION, EXPRESS OR IMPLIED, REGARDING NON-INFRINGEMENT, MERCHANTABILITY, OR FITNESS FOR PARTICULAR PURPOSE OF THEPRODUCTS. ANY BUYER OR USER ACKNOWLEDGES THAT THE BUYER OR USER ALONE HASDETERMINED THAT THE PRODUCTS WILL SUITABLY MEET THE REQUIREMENTS OF THEIRINTENDED USE. OMRON DISCLAIMS ALL OTHER WARRANTIES, EXPRESS OR IMPLIED.
LIMITATIONS OF LIABILITY
OMRON SHALL NOT BE RESPONSIBLE FOR SPECIAL, INDIRECT, OR CONSEQUENTIAL DAMAGES,LOSS OF PROFITS OR COMMERCIAL LOSS IN ANY WAY CONNECTED WITH THE PRODUCTS,WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICTLIABILITY.
In no event shall the responsibility of OMRON for any act exceed the individual price of the product on whichliability is asserted.
IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMSREGARDING THE PRODUCTS UNLESS OMRONS ANALYSIS CONFIRMS THAT THE PRODUCTSWERE PROPERLY HANDLED, STORED, INSTALLED, AND MAINTAINED AND NOT SUBJECT TOCONTAMINATION, ABUSE, MISUSE, OR INAPPROPRIATE MODIFICATION OR REPAIR.
-
5/20/2018 V107-E1-04+NB series Setup Manual
13/102
10 NB-series Programmable Terminals Setup Manual(V107)
Application Considerations
SUITABILITY FOR USE
OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the
combination of products in the customers application or use of the products.
At the customers request, OMRON will provide applicable third party certification documents identifyingratings and limitations of use that apply to the products. This information by itself is not sufficient for acomplete determination of the suitability of the products in combination with the end product, machine,system, or other application or use.
The following are some examples of applications for which particular attention must be given. This is notintended to be an exhaustive list of all possible uses of the products, nor is it intended to imply that the useslisted may be suitable for the products:
Outdoor use, uses involving potential chemical contamination or electrical interference, or conditions oruses not described in this manual.
Nuclear energy control systems, combustion systems, railroad systems, aviation systems, medicalequipment, amusement machines, vehicles, safety equipment, and installations subject to separateindustry or government regulations.
Systems, machines, and equipment that could present a risk to life or property.
Please know and observe all prohibitions of use applicable to the products.
NEVER USE THE PRODUCTS FOR AN APPLICATION INVOLVING SERIOUS RISK TO LIFE ORPROPERTY WITHOUT ENSURING THAT THE SYSTEM AS A WHOLE HAS BEEN DESIGNED TOADDRESS THE RISKS, AND THAT THE OMRON PRODUCTS ARE PROPERLY RATED AND INSTALLEDFOR THE INTENDED USE WITHIN THE OVERALL EQUIPMENT OR SYSTEM.
PROGRAMMABLE PRODUCTS
OMRON shall not be responsible for the users programming of a programmable product, or anyconsequence thereof.
-
5/20/2018 V107-E1-04+NB series Setup Manual
14/10211NB-series Programmable Terminals Setup Manual(V107)
Disclaimers
CHANGE IN SPECIFICATIONS
Product specifications and accessories may be changed at any time based on improvements and other
reasons.
It is our practice to change model numbers when published ratings or features are changed, or whensignificant construction changes are made. However, some specifications of the products may be changedwithout any notice. When in doubt, special model numbers may be assigned to fix or establish keyspecifications for your application on your request. Please consult with your OMRON representative at anytime to confirm actual specifications of purchased products.
DIMENSIONS AND WEIGHTS
Dimensions and weights are nominal and are not to be used for manufacturing purposes, even whentolerances are shown.
PERFORMANCE DATA
Performance data given in this manual is provided as a guide for the user in determining suitability and doesnot constitute a warranty. It may represent the result of OMRONs test conditions, and the users mustcorrelate it to actual application requirements. Actual performance is subject to the OMRON Warranty andLimitations of Liability.
ERRORS AND OMISSIONS
The information in this manual has been carefully checked and is believed to be accurate; however, noresponsibility is assumed for clerical, typographical, or proofreading errors, or omissions.
-
5/20/2018 V107-E1-04+NB series Setup Manual
15/102
12 NB-series Programmable Terminals Setup Manual(V107)
Safety Precautions
The following notation is used in this manual to provide precautions required to ensure safe usage ofthe product. The safety precautions that are provided are extremely important to safety. Always readand heed the information provided in all safety precautions.
Notation Used for Safety Information
Symbols
ProhibitionIndicates a general prohibition.
CautionIndicates general cautionary, warning, or danger levelinformation.
WARNINGIndicates an imminently hazardous situation which,if not avoided, will result in death or serious injury.Additionally, there may be severe property damage.
Precautions for Safe UseIndicates precautions on what to do and what not to do to ensure using the product safely.
Precautions for Correct UseIndicates precautions on what to do and what not to do to ensure proper operationand performance.
Note Indicates suggestive information and precautions on operation of the product.
-
5/20/2018 V107-E1-04+NB series Setup Manual
16/10213NB-series Programmable Terminals Setup Manual(V107)
Do not attempt to take the product apart and do not touch the product inside while thepower is being supplied. Otherwise it may result in electric shock.
Always ensure that the personnel in charge confirm that installation, inspection, andmaintenance were properly performed for the NB Unit.
Personnel in charge refers to individuals qualified and responsible for ensuringsafety during machine design, installation, operation, maintenance, and disposal.
Ensure that installation and post-installation checks are performed by personnel incharge who possess a thorough understanding of the machinery to be installed.
Do not use the input functions of the touch switch, etc. of the NB Unit, in applicationsthat involve human life, in applications that may result in serious injury, or for
emergency stop switches.
Do not attempt to disassemble, repair, or modify the NB Unit. Otherwise it may impairthe safety functions.
Never press more than two points on the touch panel of the NB Unit at a time.Otherwise, it may activate a switch somewhere between the two points.
WARNING
-
5/20/2018 V107-E1-04+NB series Setup Manual
17/102
14 NB-series Programmable Terminals Setup Manual(V107)
Precautions for Safe Use
When unpacking the NB Units and the peripheral devices, check carefully for any external scratches
or other damages. Also, shake the Units gently and check for any abnormal sound. The NB Unit must be installed in a control panel.
The mounting panel must be between 1.6 and 4.8 mm thick. Tighten the Mounting Brackets evenly toa torque of between 0.5 and 0.6 Nm to maintain water and dust resistance. If the tightening torqueexceeds the specified value, or the tightening is not even, deformation of the front panel may occur.What is more, make sure the panel is not dirty or warped and that it is strong enough to hold theUnits.
Do not let metal particles enter the Units when preparing the panel.
Do not connect an AC power supply to the DC power terminals.
Use a DC power with a slight voltage fluctuation and that will provide a stable output even if the inputis momentarily interrupted for 10 ms.
Rated Power Supply Voltage: DC 24 V (Allowable range DC 20.4 ~ 27.6 V) Do not perform a dielectric voltage test.
Making the connection by using terminal screws crimping on a twisted-pair cable with a crimpingrange of 12~26 AWG, and only 6.5 mm of insulation peel of the cable needs to be peeled off. Tightenthe terminal screws at a torque of between 0.3 and 0.5 Nm. Make sure the screws are properlytightened.
To prevent malfunctions caused by noise, ground the Unit correctly.
Do not touch the packaging part of the circuit board with your bare hands. Discharge any staticelectricity from your body before handling the board.
When using the No. 6 pin of the serial communication port COM1 connector for a voltage of DC+5V,make sure the supply equipments current capacity is below 250mA before using it. The DC+5V
voltage output of the NB unit is +5V5%, and the maximum current is 250mA. (The serialcommunication port COM1 of NB3Q-TW00B and NB3Q-TW01B is unable to output the current.)
Turn OFF the power supply before connecting or disconnecting cables.
Always keep the connector screws firmly tightened after the communication cable is connected.
The maximum tensile load for cables is 30 N. Do not apply loads greater than this.
Confirm the safety of the system before turning ON or OFF the power supply, or pressing the resetbutton.
The whole system may stop depending on how the power supply is turned ON or OFF. Turn ON/OFFthe power supply according to the specified procedure.
Reset by pressing the reset button, or restart the power supply, once the DIP switch settings arechanged.
To ensure the systems safety, make sure to incorporate a program that can confirm the normalfunctionality of the NB Unit before running the system.
Start actual system application only after sufficiently checking screen data, macros and the operationof the program at the host side.
Do not press the touch panel with a force greater than 30 N.
Do not use hard or pointed objects to operate or scrub the screen, otherwise, the surface of thescreen may be damaged.
Confirm the safety of the system before pressing the touch panel.
Signals from the touch switches may not be input if the touch switches are pressed consecutively athigh speed. Confirm each input before proceeding to the next one.
Do not accidentally press the touch panel when the backlight is not lit or when the display does not
appear. Make sure of the safety of the system before pressing the touch panel. To use numeric input functions safely, always make maximum and minimum limit settings.
Before initializing screen data, confirm that existing data is backed up at the NB-Designer.
-
5/20/2018 V107-E1-04+NB series Setup Manual
18/10215NB-series Programmable Terminals Setup Manual(V107)
When changing the password with the screen, do not reset or turn OFF the power supply until writingis finished. Failure to save the password may cause the screen to fail to function.
When using an equipment monitor, confirm the safety of the system before carrying out the followingoperations:
Changing monitor data.
Changing operation mode. Forced setup/reset.
Changing the current value or the set value.
Do not connect a USB connector to any device that is not applicable.
When connecting the equipment with the USB HOST connector, make sure the supply equipmentscurrent capacity is below 150mA before using it. The DC+5V voltage output of the NB Unit is+5V5%, and the maximum current is 150mA.
Before connecting a USB connector to a device, make sure that the device is free of damage.
Commercially available and the recommended USB HUBs are different from the generalspecifications of the NB Unit. The unit may not function well in an environment subject to noise, staticelectricity. Therefore, when using a USB HUB, employ sufficient noise and static electricity insulationmeasures, or install it at a site free of noise or static electricity.
While uploading or downloading screen data or system programs, do not perform the followingoperations that may corrupt the screen data or the system program:
Turning OFF the power supply of the NB Unit.
Pressing the PTs reset switch.
Dispose of the Units and batteries according to local ordinances as they apply.
When exporting products with lithium primary batteries containing perchlorate at 6ppb or above to or
delivering them through California, USA, the following precautionary measures have to be publicized.Perchlorate material - applicable through special processing. Refer tohttp://www.dtsc.ca.gov/hazardouswaste/perchlorate.NB-Series products contain lithium primary batteries. When exporting products containing this kind ofbatteries to or delivering them through California, USA, label all the product packages as well as theappropriate delivery packages.
Do not use benzene, paint thinner, or other volatile solvents, and do not use chemically treated cloths.
Do not dispose the Units together with general waste at waste yards. When disposing them, followthe related local ordinances or rules.
Customers may not replace the backlight lamp inside the NB Unit. Please contact OMRONscustomer service center.
Deterioration over time can cause the touch points to move. Calibrate the touch panel periodically. Water and oil resistance will be lost if the front sheet is torn or is peeling off. Do not use the Unit, if the
front sheet is torn or is peeling off.
The rubber packing will deteriorate, shrink, or harden depending on the operating environment.Inspect and replace the rubber packing periodically.
The communication cables of the COM1 and COM2 connectors are not interchangeable. Confirm thepins of the ports before carrying out communications. (NB3Q-TW00B and NB3Q-TW01B only haveCOM1.)
Periodically check the installation conditions in applications where the PT is subject to contact with oilor water.
Do not perform the following operations during the communication of the USB memory:
Turning off the power supply of the NB Unit. Pressing the Reset button on the NB Unit.
Removing the USB memory.
Do not use the USB memory in the environment subject to strong vibration.
-
5/20/2018 V107-E1-04+NB series Setup Manual
19/102
16 NB-series Programmable Terminals Setup Manual(V107)
Precautions for Correct Use
Do not install the unit in any of the following locations:
Locations subject to severe changes in temperatureLocations subject to temperatures or humidity outside the range specified in the specificationsLocations subject to condensation as the result of high humidityLocations subject to corrosive or flammable gasesLocations subject to strong shock or vibrationLocations outdoors subject to direct wind and rainLocations subject to strong ultraviolet lightLocations subject to dustLocations subject to direct sunlightLocations subject to splashing oil or chemicals
Take appropriate and sufficient countermeasures when installing systems in the following locations:
Locations subject to static electricity or other forms of noiseLocations subject to strong electric field or magnetic fieldLocations close to power supply linesLocations subject to possible exposure to radioactivity
Precautions for software:The update, restoration, uninstall and reinstallation of software in running status is prohibited in orderto guarantee the correct use of the product.
-
5/20/2018 V107-E1-04+NB series Setup Manual
20/10217NB-series Programmable Terminals Setup Manual(V107)
Conformance to EC Directives
NB-Series Programmable Terminals are EMC compliant.
OMRON products are electronic devices that are incorporated in machines and manufacturinginstallations. OMRON PTs conform to the related EMC Directives (see note) so that the devices andmachines into which they are built can more easily conform to EMC Directives. The actual productshave been through inspections and are completely in accordance with EMC directives. However, whenthey are built into customers systems, whether the systems also comply with these Directives is up tothe customers for further inspection.
EMC-related performance of OMRON PTs will vary depending on the configuration, wiring, and otherconditions of the OMRON equipment or control panel. The customer must, therefore, perform final
checks to confirm that the overall machine or device conforms to EMC standards.
Note The applicable EMC (Electromagnetic Compatibility) standards are as follows:EMS (Electromagnetic sensitivity): EN61131-2: 2007EMI (Electromagnetic Interference): EN61131-2: 2007
NB-Series Programmable Terminals are EC compliant. Heed the following precautions in order toensure that the customers overall machine and device conform to EC Directives.
1 The PT must be installed in a control panel.
2 You must use reinforced insulation or double insulation for the DC power supply and the DCpower supply must have minimal voltage fluctuations and provide a stable output even if thepower supply input is interrupted for 10 ms.
3 The PTs conform to the standard EN 61131-2, but radiated emission characteristics (10mregulations) may vary depending on the configuration of the control panel used, other devicesconnected to the control panel, wiring, and other conditions. You must therefore confirm that theoverall machine or equipment complies with EC Directives.
4This is a Class A product (Product for industry purpose). It may cause radio interference inresidential areas, in which case the user may be required to take adequate measures to reduceinterference.
Concepts
Conformance to EC Directives
-
5/20/2018 V107-E1-04+NB series Setup Manual
21/102
18 NB-series Programmable Terminals Setup Manual(V107)
Related Manuals
The related manuals are as follows:
Devices and Software Manual Name Manual No.
NB series NB Series NB-Designer Operation Manual V106
NB Series Setup Manual (This manual) V107
NB Series Host Connection Manual V108
NB Series Startup Guide V109
PLC SYSMAC CP Series CP1L CPU Unit Operation Manual W462
SYSMAC CP Series CP1H/L CPU Unit Programming Manual W451
SYSMAC CP Series CP1H CPU Unit Operation Manual W450
SYSMAC CP Series CP1E CPU Unit Hardware USERSManual
W479
SYSMAC CP Series CP1E CPU Unit Software USERSManual
W480
SYSMAC C200HX/HG/HE(-E/-ZE) Installation Guide W302
SYSMAC C200HX/HG/HE Operation Manual W303
SYSMAC C200HX/HG/HE(-ZE) Operation Manual W322
SYSMAC CPM1A Operation Manual W317
SYSMAC CPM2A Operation Manual W352
SYSMAC CPM1/CPM1A/CPM2A/CPM2C/SRM1(-V2)Programming Manual
W353
SYSMAC CPM2C Operation Manual W356
SYSMAC CS1 Series CS1G/H Operation Manual W339SYSMAC CS/CJ Series Serial Communications Boards andSerial Communications Units Operation Manual
W336
SYSMAC CJ Series CJ1G/H(-H) CJ1M CJ1G OperationManual
W393
SYSMAC CS/CJ Series Programming Manual W394
SYSMAC CS/CJ Series INSTRUCTIONS Reference Manual W340
SYSMAC CS/CJ Series Programming Consoles OperationManual
W341
SYSMAC CS/CJ Series Communications CommandsReference Manual
W342
SYSMAC CJ Series CJ2 CPU Unit Hardware USERS Manual W472SYSMAC CJ Series CJ2 CPU Unit Software USERS Manual W473
SYSMAC CS/CJ Series CS1W/CJ1W-ETN21 (100Base-TX)Ethernet Units Operation Manual Construction of Networks
W420
SYSMAC CS/CJ Series CS1W/CJ1W-ETN21 (100Base-TX)Ethernet Units Operation Manual Construction of Applications
W421
SYSMAC CS/CJ Series CS1W/CJ1W-EIP21 (100Base-TX)EtherNet/IP Units Operation Manual
W465
SYSMAC CP Series CP1L-EL/EM CPU Unit Operation Manual W516
External Tool CX-Programmer Ver.9.Operation Manual W446
-
5/20/2018 V107-E1-04+NB series Setup Manual
22/1021-1NB-series Programmable Terminals Setup Manual(V107)
1\
This section describes the names and functions of the various parts of an NB Unit.
1-1 Part Names . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-2
1-2 Part Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-6
Part Names and Functions
-
5/20/2018 V107-E1-04+NB series Setup Manual
23/102
1 Part Names and Functions
1-2 NB-series Programmable Terminals Setup Manual(V107)
1-1 Part Names
NB3Q-TW00B/NB3Q-TW01B model
Front view
Back view
Precautions for Safe Use
Confirm the safety of the system before turning ON or OFF the power supply, or pressing thereset button.
Power Indicator Display
: NB-TW01B only
-
5/20/2018 V107-E1-04+NB series Setup Manual
24/1021-3
1 Part Names and Functions
NB-series Programmable Terminals Setup Manual(V107)
1-1PartNames
1
NB5Q-TW00B/NB5Q-TW01B model
Front view
Back view
Precautions for Safe Use
Confirm the safety of the system before turning ON or OFF the power supply, or pressing thereset button.
Power Indicator Display
: NB-TW01B only
-
5/20/2018 V107-E1-04+NB series Setup Manual
25/102
1 Part Names and Functions
1-4 NB-series Programmable Terminals Setup Manual(V107)
NB7W-TW00B/NB7W-TW01B model
Front view
Back view
Precautions for Safe Use
Confirm the safety of the system before turning ON or OFF the power supply, or pressing thereset button.
Power Indicator Display
: NB-TW01B only
-
5/20/2018 V107-E1-04+NB series Setup Manual
26/1021-5
1 Part Names and Functions
NB-series Programmable Terminals Setup Manual(V107)
1-1PartNames
1
NB10W-TW01B model
Front view
Back view
Precautions for Safe Use
Confirm the safety of the system before turning ON or OFF the power supply, or pressing thereset button.
Power Indicator Display
-
5/20/2018 V107-E1-04+NB series Setup Manual
27/102
1 Part Names and Functions
1-6 NB-series Programmable Terminals Setup Manual(V107)
1-2 Part Specifications
Touch Panel
Input operation can be carried out by means of the touch panel. By pressing the touch panel, thescreens can be switched, and the contact information can be transmitted to the host.
Precautions for Safe Use
Do not press a touch switch with a force greater than 30N.
Do not accidentally press the touch panel when the backlight is not lit or when the display doesnot appear. Make sure of the safety of the system before pressing the touch panel.
Confirm the safety of the system before pressing the touch panel.
Do not use hard or pointed objects to operate or scrub the screen, or the surface of the screenmay be damaged.
Signals from the touch switches may not be input if the switches are pressed consecutively athigh speed. Confirm each input before proceeding to the next one.
Deterioration over time can cause the touch points to move. Calibrate the touch panelperiodically.
Serial Port COM1
NB5Q/NB7W/NB10W-TWB
Serial port COM1 is a 9-pin D-type socket port. This port supports RS-232C communicationfunction, making it connectable to a controller which features RS-232C function, and it can also be
used for downloading programs or debugging for the product.The pins are defined as follows:
Do not use the input functions of the touch switch, etc. of the NB Unit, in applicationsthat involve human life, in applications that may result in serious injury, or foremergency stop switches.
Never press more than two points on the touch panel of the NB Unit at a time.
Otherwise, it may activate a switch somewhere between the two points.
WARNING
* Pins 4 and 5 are not used, thus not compliant with RS or CS functions.
Pins Signals I/O Functions
1 NC - -
2 SD O Sending data
3 RD I Receiving data
4 RS(RTS) O Request to send*
5 CS(CTS) I Clear to send*
6 DC+5V - DC+5V output (Max. current: 250mA)
7 NC - -
8 NC - -
9 SG - Signal ground
-
5/20/2018 V107-E1-04+NB series Setup Manual
28/1021-7
1 Part Names and Functions
NB-series Programmable Terminals Setup Manual(V107)
1-2PartSpecifications
1
Precautions for Safe Use
When using the No. 6 pin of the serial communications port COM1 connector for a voltage ofDC+5V, make sure the supply equipments current capacity is below 250 mA before using it. TheDC+5V voltage output of the NB Unit is +5V5%, and the maximum current is 250 mA.
NB3Q-TWB
NB3Q-TWB has only 1 serial port COM1, and this port supports communication based onRS-232C, RS-422 and RS-485, of which only 1 connection mode can be applied at one time. Bymeans of the RS-232C mode (PIN 2~5), it can be connected to a controller based on RS-232C,and can also be used for downloading programs, as well as debugging for the product (connectedto a PC). While with the RS-422 or the RS-485 mode (PIN 1, PIN 6~8), only a PLC can beconnected.
The pins are defined as follows:
Serial Port COM2
NB5Q/NB7W/NB10W-TWB
Serial port COM2 is a 9-pin D-type socket port. This port supports RS-232C/RS-485/RS-422Acommunication function.
The pins are defined as follows:
* Pins 4 and 5 are not used, thus not compliant with RS or CS functions.
Pins Signals I/OFunctions
RS-232C RS-485 RS-422A
1 SDB+ I/O - - Sending data(+)
2 SD O PLC Sending data - -
3 RD I PLC Receiving data - -
4 RS(RTS) O Request to send* - -
5 CS(CTS) I Clear to send* - -
6 RDB+ I/O - RS485BSend/Receivedata(+)
Receivingdata(+)
7 SDA- I/O - - Sending data(-)
8 RDA- I/O - RS485ASend/Receivedata(-)
Receivingdata(-)
9 SG - Signal ground
Pins Signals I/OFunctions
RS-232C RS-485 RS-422A
1 SDB+ I/O - - Sending data(+)
2 SD O Sending data - -
3 RD I Receiving data - -
4 Terminal R1 - - Terminal resistor 1
5 Terminal R2 - - Terminal resistor 2
6 RDB+ I/O - Send/Receivedata(+)
Receivingdata(+)
7 SDA- I/O - - Sending data(-)8 RDA- I/O - Send/Receive
data(-)Receivingdata(-)
9 SG - Signal ground
-
5/20/2018 V107-E1-04+NB series Setup Manual
29/102
1 Part Names and Functions
1-8 NB-series Programmable Terminals Setup Manual(V107)
USB HOST
NB-TW01B is equipped with USB HOST port, which is USB A-type port. Through this port, USBmemory can be connected to perform uploading, downloading, project operation and storage of relateddata. And its pins are defined as follows:
Precautions for Safe Use
When connecting the equipment with the USB HOST connector, make sure the supply
equipments current capacity is below 150mA before using it. The DC+5V voltage output of theNB Unit is +5V5%, and the maximum current is 150mA.
USB SLAVE
USB SLAVE port is USB B-type port, which can connect the USB port on PC side to perform theuploading, downloading and debugging of the programs for the product. And its pins are defined asfollows:
Ethernet Interface
NB-TW01B is equipped with Ethernet Interface, which is adaptive RJ-45 type interface with thetransmission rate of 10M/100M. It can be connected with PC to perform the uploading and downloadingof the programs and the system refreshing, and can also be used to realize the communication with thecontroller supporting the Ethernet communication. And its pins are defined as follows:
1 2 3 4
Pins Signals Functions
1 Vbus USB +5V power supply output(Max. current: 150mA)
2 D- Data -
3 D+ Data +
4 GND USB power supply ground
3
4 1
2
Pins Signals Functions
1 Vbus USB +5V power supply output
2 D- Data -
3 D+ Data +
4 GND USB power supply ground
1
1
8
8
Pins Signals Functions
1 TD+ Sending data +
2 TD- Sending data -
3 RD+ Receiving data +
4 --- Not used
5 --- Not used
6 RD- Receiving data -
7 --- Not used
8 --- Not used
TOP Bottom
-
5/20/2018 V107-E1-04+NB series Setup Manual
30/1021-9
1 Part Names and Functions
NB-series Programmable Terminals Setup Manual(V107)
1-2PartSpecifications
1
DIP Switch
NB5Q/NB7W only has 2 switches SW1 and SW2, while for the NB3Q and NB10W, there are totally 4DIP switches, and for all models, SW1 and SW2 feature the same functions. The settings andcorresponding operating modes are as follows:
System Setting Mode: The PT will be launched into a built-in system setup screen, and is subject tothe user for brightness, system time and buzzer settings.
Calibrate Mode: When the user touches the panel, a symbol + will pop up on the screen, with whichthe touch control precision level can be calibrated.
Downloader Mode: This is used for basic operations such as updating the firmware, downloading and
uploading the users engineering documents, etc. and this mode is not intended for general users. User Project Mode: This is the User Project Mode of NB-Series PTs. The PT will display the startup
screen of the project already downloaded.
As mentioned above, the settings and corresponding operating modes of the switches SW1 and SW2of NB3Q and NB10W are the same as those of NB5Q/NB7W (see the table above), and the functions ofSW3 and SW4 of NB3Q and NB10W are stated as below:
Reset Switch
When pressing the reset switch located on the back side of the PT, the system will be rebooted.
ON ON
1 2
SW1 SW2 Operating modes
ON ON System Setting Mode
OFF ON Calibrate Mode
ON OFF Downloader Mode
OFF OFF User Project Mode
Switch No.
(corresponding model(s))Status Descriptions of Function
SW3 (NB3Q)ON Terminal resistance ON
OFF Terminal resistance OFF
SW3 (NB10W) ReservedSW4 (NB3Q/NB10W) Reserved
ON
1 2 3 4
-
5/20/2018 V107-E1-04+NB series Setup Manual
31/102
1 Part Names and Functions
1-10 NB-series Programmable Terminals Setup Manual(V107)
-
5/20/2018 V107-E1-04+NB series Setup Manual
32/1022-1NB-series Programmable Terminals Setup Manual(V107)
2
This section describes the methods used to install the NB Unit and connect peripheraldevices.
2-1 Installing the NB Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2-1-1 Installation environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-2
2-1-2 Installation onto the Operation Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-3
2-1-3 Connecting the Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
2-1-4 Grounding Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
2-2 Start of NB Series . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-7
2-3 Connecting of NB-series with PC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
2-3-1 Connecting by RS-232C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-8
2-3-2 Connecting by USB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-92-3-3 Connecting by Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-10
2-4 Serial Communication Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
2-4-1 Host Link Connection Method . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-11
2-4-2 Connecting more than one PLC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-12
2-4-3 Settings for each Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-13
2-5 FINS/UDP Communication Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
2-5-1 Connecting to Host Via Ethernet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-26
2-5-2 Parameter Settings for FINS/UDP at NB Side . . . . . . . . . . . . . . . . . . . . . . . . 2-292-5-3 Host Types and Settings of Ethernet Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-31
2-5-4 Host Types and Settings of Ethernet/IP Unit . . . . . . . . . . . . . . . . . . . . . . . . . 2-38
2-5-5 Parameter Settings for FINS/UDP at Host Side . . . . . . . . . . . . . . . . . . . . . . . 2-42
Installing the NB Unit andConnecting Peripheral Devices
-
5/20/2018 V107-E1-04+NB series Setup Manual
33/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-2 NB-series Programmable Terminals Setup Manual(V107)
2-1 Installing the NB Unit
This section describes the methods used to mount the NB Unit onto an operation panel and connect
the power supply.
When mounting the NB Unit onto the operation panel, pay attention to the following precautions.
Precautions for Correct UsePrecautions for Correct Use
Do not install the product in any of the following locations:
Locations subject to rapid changes in temperatureLocations subject to temperatures or humidity outside the range specified in thespecifications
Locations subject to condensation as the result of high humidity
Locations subject to corrosive or flammable gases
Locations subject to strong shock or vibration
Locations outdoors subject to direct wind and rain
Locations subject to strong ultraviolet light
Locations subject to dust
Locations subject to direct sunlight
Locations subject to splashing oil or chemicals Take appropriate and sufficient countermeasures when the product is used in the following
locations:
Locations subject to static electricity or other forms of noise
Locations subject to strong electric field or magnetic field
Locations close to power supply lines
Locations subject to possible exposure to radioactivity
Precautions for Safe Use
When unpacking the NB Units and the peripheral devices, check carefully for any externalscratches or other damage. Also, shake the Units gently and check for any abnormal sound.
2-1-1 Installation environment
Always ensure that the personnel in charge confirm that installation, inspection, andmaintenance were properly performed for the NB Unit.
Personnel in charge refers to individuals qualified and responsible for ensuringsafety during machine design, installation, operation, maintenance, and disposal.
Ensure that installation and post-installation checks are performed by personnel incharge who possess a thorough understanding of the machinery to be installed.
WARNING
-
5/20/2018 V107-E1-04+NB series Setup Manual
34/1022-3
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-1Insta
llingtheNBUnit
2
2-1-2InstallationontotheOperationPanel
Install the NB Unit by embedding it into the operation panel.
Use the panel mounting brackets and Phillips screwdriver for installation.
Proceed the installation following the procedures below.
1 Panel cutout with dimensions is shown below. Fit the NB Unit into the panel from the front side.
2 As follows, insert the panel mounting brackets at the locations indicated by red box around the
back of the NB Unit. Insert the hooks of positioners into the square holes on the Unit to hold thefixators properly, and tighten the screws firmly with the screwdriver.
NB5Q/NB7W-TW B
2-1-2 Installation onto the Operation Panel
Models Opening Dimension (WH mm)
NB3Q-TW00B/TW01B 119.0(+0.5/-0)93.0(+0.5/-0)
NB5Q-TW00B/TW01B 172.4(+0.5/-0)131.0(+0.5/-0)
NB7W-TW00B/TW01B 191.0(+0.5/-0)137.0(+0.5/-0)
NB10W-TW01B 258.0(+0.5/-0)200.0(+0.5/-0)
Opening dimensions
Width
Height
-
5/20/2018 V107-E1-04+NB series Setup Manual
35/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-4 NB-series Programmable Terminals Setup Manual(V107)
The insert positions on the body of NB3Q-TW B/NB10W-TW01B (samefixing method as above)
Precautions for Safe Use
Do not let metal particles enter the Units when preparing the panel.
The mounting panel must be between 1.6 and 4.8 mm thick. Tighten the Mounting Bracketsevenly to a torque of between 0.5 and 0.6 Nm to maintain water and dust resistance. If thetightening torque exceeds the specified value, or the tightening is not even, deformation ofthe front panel may occur. What is more, make sure the panel is not dirty or warped and thatit is strong enough to hold the Units.
Display Mode of NB Series touch panel
NB Series touch panel has 2 display modes: horizontal and vertical.The display mode can be selected when dragging a HMI from the Graph element window into theConstruct Window.
NB3Q -TWB
NB10W -TWB
Horizontal display Vertical display
Menu Task BarMenu Task Bar
-
5/20/2018 V107-E1-04+NB series Setup Manual
36/1022-5
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-1Insta
llingtheNBUnit
2
2-1-3C
onnectingthePowerSupply
Precautions for Safe Use
Do not connect an AC power supply to the DC power terminals. Use a DC power with a slight voltage fluctuation and that will provide a stable output even if
the input is momentarily interrupted for 10 ms.Rated Power Supply Voltage: DC 24 V (Allowable range DC 20.4 ~ 27.6 V)
Power Supply
The connectable power supply specifications are as follows: figure out a suitable power supplyspecification so as to satisfy the requirement for power supply capacity.
NB5Q/NB7W/NB10W-TW B
NB3Q -TW
B
Precautions for Safe Use
Making the connection by using terminal screws crimping on a twisted-pair cable with acrimping range of 12~26 AWG, and only 6.5 mm of insulation peel of the cable needs to bepeeled off. Tighten the terminal screws at a torque of between 0.3 and 0.5 Nm. Make surethe screws are properly tightened.
2-1-3 Connecting the Power Supply
Models Rated Voltage Allowable Voltage Range Power
NB3Q-TW00B DC24V DC20.4V to 27.6V 5W
NB3Q-TW01B 9WNB5Q-TW00B 6W
NB5Q-TW01B 10W
NB7W-TW00B 7W
NB7W-TW01B 11W
NB10W-TW01B 14W
0V
The reverse side of NB
MCCB
DC24V
24V
0V
The reverse side of NB
MCCB
DC24V
24V
-
5/20/2018 V107-E1-04+NB series Setup Manual
37/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-6 NB-series Programmable Terminals Setup Manual(V107)
The NB Unit has a functional grounding terminal ( ).
Arrange the wiring according to the following conditions.
1 When a potential difference occurs between the NB Unit and the host, arrange the grounding as
illustrated. If the distance is too long to realize a single-point grounding, do not ground the
of the NB Unit.
2 When the NB Unit, and noise source equipment such as motors and inverters, etc. are installed
on the same panel, do not ground the of the NB Unit.
Precautions for Safe Use
To prevent malfunctions caused by noise, ground the Unit correctly.
2-1-4 Grounding Wiring
NB Unit Host
Single-pointgrounding
-
5/20/2018 V107-E1-04+NB series Setup Manual
38/1022-7
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-2S
tartofNBSeries
2
2-1-4G
roundingWiring
2-2 Start of NB Series
Confirm the hardware are all correctly connected, turn on the power supply, and start the NB-Series.
This part describes the operations of the NB Series when it starts.
When starting the NB Unit for the first time
(1) Confirm that the DIP switches SW1 and SW2 on the back side are both ON.
(2) Turn on the power supply of the NB Unit, and with the POWER LED on the front sideturning green, the NB Unit starts, entering into the System Setting Mode.
(3) Through the System Setup screen, the system time, starting window No., screen savingtime, buzzer and the screen brightness can be set. When the setup is finished, turn OFFthe power supply, turn OFF both of the DIP switches, SW1 and SW2, and then switch onthe power supply again.
When starting the NB Unit after downloading the screen data to it.
(1) Confirm that the DIP switches SW1 and SW2 on the back side are both OFF.
(2) Turn on the power supply of the NB Unit, and with the POWER LED on the front sideturning green, the NB Unit starts.
(3) The starting screen of the screen data downloaded to the NB Unit will be shown.
Entering into Calibrate Mode
(1) Confirm that the DIP switches SW1 and SW2 on the back side are respectively OFF andON.
(2) Turn on the power supply of the NB Unit, and with the POWER LED on the front side
turning green, the NB Unit starts.(3) When the user touches the panel, a symbol + will pop up on the screen, with which the
touch control precision level can be calibrated.
Precautions for Safe Use
Confirm the safety of the system before turning ON or OFF the power supply, or pressing thereset button.
-
5/20/2018 V107-E1-04+NB series Setup Manual
39/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-8 NB-series Programmable Terminals Setup Manual(V107)
2-3 Connecting of NB-series with PC
In order to transmit the screen data established by the NB-Designer to the NB Unit, the NB Unit needs
to be connected to a PC with a RS-232C, USB or Ethernet cable.
Take NB5Q/NB7W-TW01B as example:
Connect the RS-232C cable at the PC side to the serial port COM1 of the NB Unit.
Communication conditions
Select the downloader mode through the tool menu of the NB-Designer. For details, refer to 3-15Downloadin the NB-Designer Operation Manual.
Communication cable
Users can make connection cables by themselves. For details, refer to A-4 Fabrication of theConnection Cable in the NB Series Setup Manual.
2-3-1 Connecting by RS-232C
-
5/20/2018 V107-E1-04+NB series Setup Manual
40/1022-9
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-3ConnectingofN
B-serieswithPC
2
2-3-2C
onnectingbyUSB
Use the USB transmission cable to connect the USB A-type port on PC side with the USB SLAVE B-type port on NB Unit. As to the USB connection, there are some preparations and restrictions that needto be done or heeded. Refer to the following content to ensure a correct connection.
Take NB5Q/NB7W-TW01B as example:
Connect the USB port at the PC side and the USB slave connector of the NB Unit.
USB driver for the NB-Designer
A USB driver needs to be installed in the PC for the purpose of transmitting screen data through USB.
The USB driver should be installed at the first time when connecting the NB Unit to a PC.
Please refer to 2-4 Installation of USB-Driver for NBin the NB-Designer Operation Manualfor details onthe USB driver.
Precautions for Safe Use
Commercially available and the recommended USB HUBs are different from the generalspecifications of the NB Unit. The Unit may not function well in an environment subject tonoise, static electricity. Therefore, when using a USB HUB, employ sufficient noise andstatic electricity insulation measures, or install it at a site free of noise or static electricity.
Do not connect a USB connector to any device that is not applicable.
Before connecting a USB connector to a device, make sure that the device is free ofdamage.
2-3-2 Connecting by USB
-
5/20/2018 V107-E1-04+NB series Setup Manual
41/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-10 NB-series Programmable Terminals Setup Manual(V107)
HMI with model number of NB-TW01B (other than NB-TW00B) can perform the uploading &downloading of data (such as user project and recipe etc.) and the refreshing of HMI firmware throughconnecting the Ethernet cable with RJ45 connectors on both ends and the network interface on PCside.
Communication conditions
Select the corresponding download method by clicking the Download Way option in Tools menu of theNB-Designer. For details, refer to 3-15 Downloadin the NB-Designer Operation Manual.
2-3-3 Connecting by Ethernet
Ethernet Cable
-
5/20/2018 V107-E1-04+NB series Setup Manual
42/1022-11
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-4SerialCommunicationConnection
2
2-4-1H
ostLinkConnectionMethod
2-4 Serial Communication Connection
Host Link is a connection method in which one PLC is connected to one NB Unit. There are 2 kinds ofconnection methods: RS-232C and RS-422A.
The RS-232C connection method using serial ports COM1/COM2
This is the simplest and most feasible method.
The following cables are recommended.
XW2Z-200T (Cable length: 2m) by OMRON
XW2Z-500T (Cable length: 5m) by OMRON
The RS-422A connection method using the serial port COM2
With this method, the communication distance can be extended to a maximum of 500m.
The following cables are recommended.
NB-RSEXT-2M (Cable length: 2m) by OMRON
Note please adopt 4-wire RS-422A connection, and Host Link does not support 2-wire RS-485 connection.
Connectable Units at the host side
When using OMRON PLCs, the Units with built-in Host Link function vary depending on models andseries. There is also the CPU Unit connected in a Host Link method through adding the serialcommunication board or communication board.
When connecting, confirm the connected PLCs series, model and the models of the installed circuitboard/Unit.
As to the Units at the host side which can be connected to NB series Unit by RS-232C or RS-422Athrough a Host Link, refer to A-5 List of Models in theNB Series Setup Manual.
2-4-1 Host Link Connection Method
RS-232C cable(maximum length: 15m)
NB UnitHost
RS-422A cable(maximum length: 500m)
NB UnitHost
-
5/20/2018 V107-E1-04+NB series Setup Manual
43/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-12 NB-series Programmable Terminals Setup Manual(V107)
Communication setting
The communication settings need to be set as following values before carrying out communications inthe Use Host link.
At the NB Unit side, these settings are made through the PT menu of the NB-Designer. For details, referto 3-10-8 COM1/COM2 Settingin the NB-Designer Operation Manual.
For communication settings at the host side, refer to the related PLC manuals as needed.
Select the RS-232C method for COM1, and one from RS-232C, RS-422A and RS-485 for COM2(NB3Q-TWB is not equipped with serial port COM2.).
PT with the model number of NB-TW01B, which supports Ethernet, can connect single PLC ormultiple PLCs simultaneously through the Ethernet (through the router). When connecting with multiplePLCs, it can connect the Host manufactured by the same manufacture or different manufacturessimultaneously. (Note: At a certain time, only one from RS-232C, RS-422A and RS-485 can bedesignated for COM2 to perform communications.)
The example of NB5Q/NB7W/NB10W-TW01B connecting with 3 PLCs simultaneously is as shownbelow:
Precautions for Safe Use
Always keep the connector screws firmly tightened after the communication cable isconnected.
The maximum tensile load for cables is 30N. Do not apply loads greater than this.
The communication cables of the COM1 and COM2 connectors are not interchangeable.Confirm the pins of the ports before carrying out communications.
Items Settings
Data bit 7bitStop bit 2bit
Parity check Even
Communication speed Any value, but the values for the NB Unit and the host must be the same.
Connected Unit No. 00
2-4-2 Connecting more than one PLC
COM1 RS-232C cable
Ethernet cable
COM2 RS-232C/422A/485 cable
NB Unit NB Unit 1
NB Unit 2
NB Unit 3
-
5/20/2018 V107-E1-04+NB series Setup Manual
44/1022-13
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-4SerialCommunicationConnection
2
2-4-3S
ettingsforeachUnit
When connecting with the serial communication ports, the settings for each Unit are as follows:
CP1L-L14/L20/M30/M40/M60 models
CP1H-X40/XA40/Y20 models
CP1E-N14/N20 models
CP1E-N30/N40/N60/NA20 models
CP1E-EL20/EM30/EM40 models
PLC System Settings Area
Write settings directly into the [PLC System Settings Area] with a peripheral tool (CX-Programmer, etc.)
based on the model and port of the host.
*1 The channel No. of CP1L/H is PLC Setup area.
*2 The communication speed should be set to the same value as that of the NB Unit.
Settings for the front-side DIP Switches
Set the front-side DIP switches so as to validate the settings for [PLC System Settings Area].
Set the SW4 to OFF when serial port 1 is used, set SW5 to OFF when serial port 2 is used. As theCP1L-L has only one serial port, it has no DIP switch SW5.
2-4-3 Settings for each Unit
When connecting to CP-Series Units
Host model and Port No. Channel No. (*1) Write Value Setting
CP1L-M30/M40/M60, serial port 1CP1H-X40/XA40/Y20, serial port 1CP1L-EM30/EM40, serial port 1
144 8000 Use Host Link
145 0000~000A(*2) Communication speed
147 0000~001F Unit number
CP1L-L14/L20, serial port 1CP1L-M30/M40/M60, serial port 2CP1H-X40/XA40/Y20, serial port 2CP1L-EL20, serial port 1CP1L-EM30/EM40, serial port 2
160 8000 Use Host Link
161 0000~000A(*2) Communication speed
163 0000~001F Unit number
Host model and Port No. Channel No. Write Value Setting
CP1E-N14/N20, serial port 1CP1E-N30/N40/N60/NA20,serial port 1
A617.15~12 0 Use Host Link
A617.11~08 0, 3~A(*2) Communication speed
A617.07~00 00 7 data bits, 2 stop bits, Even
CP1E-N30/N40/N60/NA20,serial port 2
A618.15~12 0 Use Host Link
A618.11~08 0, 3~A(*2) Communication speed
A618.07~00 00 7 data bits, 2 stop bits, Even
CP1L-MCP1H
ON1
2
3
4
56 CP1L-L
ON1
2
34
-
5/20/2018 V107-E1-04+NB series Setup Manual
45/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-14 NB-series Programmable Terminals Setup Manual(V107)
C200HX/HG/HE(-Z), CPM1, CPM2, CQM1H type CPU Units
Connection MethodsThe connection methods for the CPU Units of different PLC models.
PLC System Settings Area
Write settings directly into the [PLC System Settings Area] (Data memory) with a peripheral tool (CX-Programmer, etc.) based on the model and port of the host.
For RS-232C
When connecting to C-Series CPU Units
PLC Models RS-232C connection RS-422A connection
C200HX/HG/HE(-Z) Connect to the RS-232C port built in theCPU Unit
Connect to the RS-232C port (Ports A,B) of the serial communication board
Connect to the RS-422A port (port A) ofthe serial communication board
CPM1A Connect to the peripheral port with adedicated RS-232C adaptor(CPM1-CIF01).
Connect to the peripheral port with adedicated RS-422A adaptor(CPM1-CIF11 type).
CPM2A Connect to the RS-232C port built in theCPU Unit
Connect to the peripheral port with adedicated RS-232C adaptor(CPM1-CIF01).
Connect to the peripheral port with adedicated RS-422A adaptor
(CPM1-CIF11 type).
CPM2C Connect to the RS-232C port built in theCPU Unit or the peripheral port with adedicated conversion cable (CPM2C-CN111 type, CS1W-CN118 type andCS1W-CN114 type) (CPM2C-CN111type is a cable that divides the Unit portinto the RS-232C port built in the CPUUnit and the peripheral port. Whenconnecting to the peripheral port, a RS-232C adaptor (CPM1-CIF01 type) is
also needed to be connected.)
Connect to the peripheral port with adedicated conversion cable (CPM2C-CN111 type or CS1W-CN114 type) anda RS-422A adaptor (CPM1-CIF11 type)(CPM2C-CN111 type is a cable thatdivides the Unit port into the RS-232Cport built in the CPU Unit and theperipheral port).
CQM1H Connect to the RS-232C port built in theCPU Unit
Connect to the peripheral port with aconversion cable (CS1W-CN118 type)Connect to the RS-232C port (Port 1) ofthe serial communication board
Connect to the RS-422A port (Port 2) ofthe serial communication board
Host ModelChannel
No.
Write
ValueSetting
The RS-232C port built inC200HX/HG/HE(-Z),CPM2A, CPM2C, CQM1H
DM6645 0001 Use Host Link
DM6646 03(*3) Communication conditions are standard settings. (*4)
DM6648 0000 Unit No. 00
CPM1A DM6650 0001 Use Host Link
DM6651 03(*3) Communication conditions are standard settings. (*4)
DM6653 0000 Unit No. 00
Port A ofC200HX/HG/HE(-Z) (*1)Port 1 of CQM1H (*2)
DM6555 0001 Use Host Link
DM6556 03(*3) Communication conditions are standard settings. (*4)
DM6558 0000 Unit No. 00Port B ofC200HX/HG/HE(-Z) (*1)
DM6550 0001 Use Host Link
DM6551 03(*3) Communication conditions are standard settings. (*4)
DM6553 0000 Unit No. 00
-
5/20/2018 V107-E1-04+NB series Setup Manual
46/1022-15
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-4SerialCommunicationConnection
2
2-4-3S
ettingsforeachUnit
*1 The RS-232C port of the Communication Board.
*2 The RS-232C port of the Serial Communication Board.
*3is the set value of the communication speed. Set the communication speed to the same value as that ofthe NB Unit.
*4 Standard settings of the Communication conditions are as follows:
Start bit: 1 bit, Data bit: 7 bit, Stop bit: 2 bit, parity check: evenFor RS-422A
*1 The RS-422A port of the Communication Board
*2 The RS-422A port of the Serial Communication Board*3is the set value of the communication speed. Set the communication speed to the same value as that of
the NB Unit.
*4 Standard settings of the Communication conditions are as follows:Start bit: 1 bit, Data bit: 7 bit, Stop bit: 2 bit, parity check: even
For operations on [PLC System Settings Area], refer to the manual of the PLC employed.
Connection methods for CPM2C
CPM2C only has a connector with the same shape of the CS-Series peripheral port, but the signalcables inside are classified as used for the RS-232C port built in the CPU Unit and for the peripheralport. Therefore, when using CPM2C, differentiate between the settings for the RS-232C port built in theCPU and for the peripheral port based on the conversion cable and port employed to ensure correctuse. Besides, when using a simple communication device (CPM2C-CIF21 type), connect to the RS-232C port. For details, refer to the CPM2C Operation Manual (W356).
Use a self-made connection cable to connect the NB Unit and CPM2C. Connect to CPM2Cs built-inRS-232C port instead of the peripheral port.
When using a simple communication device (CPM2C-CIF21 type), connect to the RS-232C portdirectly.
Host Model Channel No. Write Value Setting
Port A ofC200HX/HG/HE(-Z) (*1)
DM6555 0001 Use Host Link
DM6556 03(*3) Communication conditions are standard settings. (*4)
DM6558 0000 Unit No. 00
Port 2 ofCQM1H (*2)
DM6550 0001 Use Host Link
DM6551 03(*3) Communication conditions are standard settings. (*4)
DM6553 0000 Unit No. 00
Port connected to the PT PLC System Settings
CS1W-CN118 type port(D-Sub 9-pin) Carry out settings for the built-in RS-232C port
CS1W-CN118 type
RS-232C port(D-Sub 9-pin socket)
CPM2C
RS-232C port
-
5/20/2018 V107-E1-04+NB series Setup Manual
47/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-16 NB-series Programmable Terminals Setup Manual(V107)
Settings for the front-side DIP Switches
To activate the settings of [PLC System Settings Area] (Data memory), set as follows according to thePLC:
For C200HX/HG/HE (-Z) and RS-232C of CQM1H
For CPM2A
For CPM2C (Only the RS-232C port can be connected)
For C200HX/HG/HE(-Z)
Communication condition setting for the RS-232C portSet the DIP switch 5 to OF, and activate the settings in
PLC system settings.
For CQM1H
Set the communication condition
setting switch to [OFF] (downwards).
When connecting the PT to the built-in RS-232C port (connect thedevice that needs to perform communications other than that withinthe standard setting range)
When connecting the PT to the built-in RS-232C port (connect aprogramming console to the peripheral port)
Set SW1 to OFFSet SW2 to ON
Set SW1 to OFFSet SW2 to ON
Carry out settings according to the using conditions of the peripheralport and built-in RS-232C port.
-
5/20/2018 V107-E1-04+NB series Setup Manual
48/1022-17
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-4SerialCommunicationConnection
2
2-4-3S
ettingsforeachUnit
Setting methods for communication board switches (For RS-422A)
For C200HX/HG/HE (-Z)
Switch 1:Side (4-wire = RS-422A)
Switch 2: ON side (terminal resistance ON = Terminal resistance activated)
For CQM1H
2-wire/4-wire switch (WIRE):side (4 wire = RS-422A)
Terminal resistance ON/OFF switch (TERM): ON side (terminal resistance ON = Terminal resistanceactivated)
Settings for the communication adaptor switch
For RS-232C adaptor (CPM1-CIF01 type)
Set the mode setting switch to [HOST] (Up side).
For RS-422A adaptor (CPM1-CIF11 type)
Set the terminal resistance switch to ON (Up side)
Serial Communication Board(Lining Board Slot 1)
Set the terminal resistanceON/OFF switch to ON(right side)
2-wire/4-wire Selector SwitchRS-422A: [4](4-wire) (right side)RS-485: [z](2-wire) (left side)
-
5/20/2018 V107-E1-04+NB series Setup Manual
49/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-18 NB-series Programmable Terminals Setup Manual(V107)
For CS1G/H-CPU(-V1) types and CS1G/H-CPUH types
Connection MethodsConnect to the RS-232C port built in the CPU Unit or the RS-232C port of the communication board.When connecting to the peripheral port, a connection cable dedicated for the peripheral port is needed(CS1W-CN118 type).
Only RS-232C can be used for connection.
PLC System Settings Area
When connecting to CS-Series CPU Unit, refer to the following table and set the communicationconditions as follows in [PLC System Settings] based on the communication port in use.
*1 The communication speed should be set to the same value as that of the NB Unit.
[PLC System Settings] can be directly set with a peripheral tool (programming console), or it can be setby transmitting the [PLC System Settings] set up by a peripheral tool (CX-Programmer) to the CPUUnit.
For details about the [PLC System Settings], refer to SYSMAC CS Series Operation Manual (W339).
Settings for the front-side Switches
Set the DIP switches 4 or 5 as follows according to the NB-Series port connected.
When connecting to CS-Series CPU Units
Connection Methods Channel No. Write Value Setting
Use the RS-232C port builtin CS1G/H, CS1G/H-H
160 8000 Use Host Link
161 0000~000A(*1) Communication speed
163 0000 Unit No. 00
Use the peripheral port ofCS1G/H, CS1G/H-H
144 8000 Use Host Link
145 0000~000A(*1) Communication speed
147 0000 Unit No. 00
DIP Switch (in the battery jar)
When connecting a NB-Series Unit to a peripheralport, set SW4 to [ON] (communications carried outaccording to the PLC system settings).
When connecting a NB-Series Unit to a RS-232Cport, set SW5 to [OFF] (communications carriedout according to the PLC system settings).
Peripheral PortMainly used for connectingperipheral tools, ect.(also used for connectingRS-232C devices)
RS-232C PortMainly used for connectingRS-232C devices(also used for connecting
CX-Programmer)
-
5/20/2018 V107-E1-04+NB series Setup Manual
50/1022-19
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-4SerialCommunicationConnection
2
2-4-3S
ettingsforeachUnit
For CJ1G-CPUtype, CJ1G/H-CPUH types and CJ1M-CPUtype
Connection MethodsConnect to the RS-232C port built in the CPU Unit or the RS-232C port of the communication board.When connecting to the peripheral port, a connection cable dedicated for the peripheral port is needed(CS1W-CN118 type). Only RS-232C can be used for connection.
PLC System Settings Area (for RS-232C)
When connecting to the CJ-Series CPU Unit, refer to the following table and set the communicationconditions as follows in [PLC System Settings] based on the communication port in use.
*1 The communication speed should be set to the same value as that of the NB Unit.
[PLC System Settings] can be directly set with a peripheral tool (Programming console), or it can be setby transmitting the [PLC System Settings] set up by a peripheral tool (CX-Programmer) to the CPUUnit.
For details about the [PLC System Settings], refer to SYSMAC CJ Series Operation Manual(W393).
Settings for the front-side Switches
Set the DIP switches 4 or 5 as follows according to the NB-Series port connected.
When connecting to CJ1-Series CPU Units
Connection Methods Channel No. Write Value Setting
Use the RS-232C port built inCJ1G-CPUtype,
CJ1G/H-CPUH types,CJ1M-CPUtypes
160 8000 Use Host Link
161 0000~000A(*1) Communication speed
163 0000 Unit No. 00
Use the peripheral port ofCJ1G-CPUtype,CJ1G/H-CPUH types,CJ1M-CPUtype
144 8000 Use Host Link
145 0000~000A(*1) Communication speed
147 0000 Unit No. 00
Peripheral Port Used for connecting programming consoles, ect.
RS-232C Port Used for connecting devices other than programming consoles.
DIP Switch(in the battery jar) When connecting a NB-Series Unit to a peripheral port, set SW4 to [ON] (communications carried out according to the PLC system settings). When connecting a NB-Series Unit to a RS-232C port, set SW5 to [OFF] (communications carried out according to the PLC system settings).
-
5/20/2018 V107-E1-04+NB series Setup Manual
51/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-20 NB-series Programmable Terminals Setup Manual(V107)
For CJ2M-CPU3type, CJ2M-CPU1type and CJ2H-CPU6(-EIP) type
Connection MethodsConnect to the RS-232C port built in the CPU Unit or the RS-232C port of the communication board.
PLC System Settings Area (for RS-232C)
Carry out setting by transmitting the [PLC System Settings] set up by a peripheral tool (CX-Programmer) to the CPU Unit. On the [Serial Port] options page of [PLC System Settings], set theconnection mode to Host Link: 7 Data Bits, 2 Stop Bits, Even. And set the communication speed to thesame as that of the NB Unit.
For details about the [PLC System Settings], refer to SYSMAC CJ2 Series Software Users Manual(W473).
Settings for the front-side SwitchesSet the DIP switch 5 of the CPU Unit as follows according to the NB-Series port connected.
When connecting to CJ2-Series CPU Units
Turn DIP SW5 OFF forserial communications.
-
5/20/2018 V107-E1-04+NB series Setup Manual
52/1022-21
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-4SerialCommunicationConnection
2
2-4-3S
ettingsforeachUnit
Base-mounted type for C200HE(-Z) / C200HG(-Z) / C200HX(-Z) models
C200H-LK201/LK202-V1 model
Settings for the Switches
For C200H-LK201-V1 (RS-232C)
[Front-side switches]
Each switch is a rotary switch. Use a straight screwdriver set the switches as follows to display thenumbers and symbols shown in the table.
[Back-side switches]
When connecting to Host Link Units of C-Series
Set unit number (SW1, SW2)
SW1 and SW2 set to [0]
Communication speed setting (SW3)4,800Bit/s: Set SW3 to [4]9,600Bit/s: Set SW3 to [5]19,200Bit/s: Set SW3 to [6]
Command level, parity check, transmit code setting (SW4)SW4 set to [2]
Link Type switchSet SW3 to [ON] 1 to 1
CTS switch settingDefault set to [OV] (ON)
-
5/20/2018 V107-E1-04+NB series Setup Manual
53/102
2 Installing the NB Unit and Connecting Peripheral Devices
2-22 NB-series Programmable Terminals Setup Manual(V107)
For C200H-LK202-V1(RS-422A)
[Front-side switches]
Each switch is a rotary switch. Use a straight screwdriver set the switches as follows to display thenumbers and symbols shown in the table.
[Back-side switches]
Unit number settings (SW1, SW2)Both of SW1 and SW2 are set to [0].
Settings of insrruction levels, parity check and transmission codes (SW4)SW4 is set to [2]
Settings of communication speed (SW3)4,800Bit/s: SW3 is set to [4]
9,600Bit/s: SW3 is set to [5]19,200Bit/s: SW3 is set to [6]
Selection of Link Type (DIP switch)Set it to [1 for 1 (ON)] upwards.
Settings of the terminal resistance (selector switch)Set it to [ON] upwards.
-
5/20/2018 V107-E1-04+NB series Setup Manual
54/1022-23
2 Installing the NB Unit and Connecting Peripheral Devices
NB-series Programmable Terminals Setup Manual(V107)
2-4SerialCommunicationConnection
2
2-4-3S
ettingsforeachUnit
For CS1W-SCB21 type (Both of port 1 and 2 are RS-232C ports)
For CS1W-SCB41 type (Port 1 is RS-232C port and Port 2 is RS-422A/485 port.)
(Serial Communication Board for CS-Series CPU Units with RS-232C port, RS-422A port.)
Settings for the DM Fixed Allocation Area of the CPU Uni