1
June 2010
K I T C H E N
V E N T I L A T I O N
WAARSCHUWING
ALLEEN OPSTARTEN DOOR
BEVOEGD EN GEKWALIFICEERD
PERSONEEL
WAARSCHUWING
UV-C LUIK ALLEEN OPENEN
DOOR BEVOEGD EN
GEKWALIFICEERD PERSONEEL
Vianen Kitchen Ventilation
Edisonweg 15, 3442 AC Woerden, P.O.Box 163, 3440 AD Woerden, Holland
E-mail: [email protected], Internet: www.vianenkvs.nl
Tel: + 31.348.416300, Fax: +31.348.421595,
WARNING
START UP ONLY BY AUTHORIZED AND QUALIFIED PERSONNEL
W A R N I N G
OPEN UV-C DOOR BY
AUTHORIZED AND QUALIFIED
PERSONNEL ONLY
2
June 2010
Important warning:
UV-C is harmful to the eyes. The
UV-C lamps MUST be off when
servicing or when changing filters.
CHECK THE DISPLAY OF THE
CONTROL CABINET.
Manual – Vianen UV-C System
1. Instructions:
This manual contains important security information and operating instructions. It is
important that the operators read the instruction manual carefully before operating
the Vianen UV-C System.
2. In general:
For security purposes ensure all operators are fully instructed and are familiar with the
operating manual before starting up the system as the manual contains important
information for operating and maintenance of the installation.
This manual is provided with the delivery of the equipment.
Ensure all criteria for secure operation is fully complied with before start up.
Only authorized and qualified personnel may perform installation, operation and
maintenance.
No changes are to be performed to the equipment, without prior consultation with
Vianen B.V., as this can affect the safety of the installation. Vianen B.V. will not be
held responsible for damages caused by unauthorized changes to the installation
and incorrect operation and application by the owners and operating personnel.
N.B. This manual should be accessible at all times to operating personnel.
3
June 2010
3. The Vianen UV-C System
The Vianen UV-C System utilises a Photo Light Oxidation-technique, which produces
ozone through UV-C lamps. The ozone reduces organic substances in the air due to
the oxidation process. The lamps are mounted in a stainless steel frame, which is
installed in the hood behind the grease filters. The protein chains in the fat and
grease are broken down by the intense UV-C radiation allowing the ozone to reduce
the organic substances.
Any leftover of non-reacted ozone automatically turns into oxygen (02).
The ozone produced by the UV-C does not turn into nitrogen oxide (NOx)
Ozone is an environmental-friendly gas, existing in the nature and decomposes in the
atmosphere.
4. Installation of the Vianen UV-C System.
During installation the lamps must be protected from dirt and grease and must be
handled with clean gloves at all times.
4.1 Receiving the delivery.
The packaging of the Vianen UV-C System must be controlled for possible transport
damages. Damages are to be immediately reported to Vianen B.V. Check that the
delivery is complete and in accordance with the packaging list.
4.2 Mechanical installation
The UV-C system is to be installed such that the duct allows a reaction time of a
minimum of two seconds whilst passing through the duct. This is necessary for the
oxidation process. Control the calculation of the air velocity with the length of duct.
N.B. As the UV-C system cleans air using ozone-oxidation no other ducts are to be
connected to the UV-C duct.
4.3 Electrical installation
The electrical installations must conform to local directives.
The location of the control cabinet is designed and constructed for indoor
conditions, and must be installed in a ventilated area, with an ambient temperature
not exceeding 30° C. The control cabinet must be placed where it can be controlled
on a daily basis. A switch must be installed between the main electrical supply and
the control cabinet.
4
June 2010
Control panel: Lay out
On/Off switch; - On - Off
:- When pressed once for longer than 10 seconds the display will
indicate if the lamps are in operation
:- When pressed twice the display will indicate the number of hours the
lamps have been on
:-When pressed for the third time a sub-menu will appear – this is the
configuration menu (AUTHORISED PERSONS ONLY)
Reset switch : Resets messages displayed on screen
Arrow Up : - Changes values of the configuration menu
Arrow Down : - Changes values of the configuration menu
Messages : -During normal working conditions the text UV= 2,3Amps REF=0. Will
display indicating the electrical power consumption (in amps) which
is being used by the UV-C lights
Configuration menu : (authorised persons only).
a. To set the maximum and minimum levels of electrical power press the
arrow up and down
b. With the up and down arrows pressed simultaneously resets the hour
counter
5
June 2010
Errors indicated on the display:
a. FAN-OFF : No current Amps on extraction fan
b. Check Door UVC : Service hatch for UV-C lights is open
c. Check-Filters : Grease filters not in place or complete
d. Check lamps : One or more lamps are broken
(fused - lamps have black ends)
After the system has been running for 7500 hours a warning on the display will
appear “Change Lamps” - this message will remain until 8000 hours are
reached. This is the lifetime of the lamps and the system will automatically
stop if not replaced.
Once the lamps have been replaced the hour counter needs to be reset.
Connection to external signals:
The electrical connection to the fan must be such that the lamps can only operate
when the fan is on and air is passing through the system. This is a very important to
prevent overheating.
Pressure guard for monitoring of the static pressure drop of the grease filters.
Connection of Vianen UV-C system-frames.
The cables from the UV-C system are to be connected in the control cabinet.
4.4 Protection of cables
Appropriate protection of the cables must be ensured at all times.
4.5 Protection during mechanical installation
During installation the Vianen UV-C system must be placed on a secure and flat
surface in a horizontal position. The frames are fragile and must not be subjected to
vibrations and must not be dropped.
4.6 Commissioning
a. Check all the fans are operating correctly
b. Check that there is sufficient ventilation at normal operation level.
c. Check all wiring to the distribution boxes and that they are correctly
connected to the control cabinet
d. Check that all the grease filters are in place
6
June 2010
e. Check that the UV-C lamps are not damaged
5. Operational start-up
Preparation:
The authorised personnel must read and understand the operational instructions. The
personnel must have knowledge of security and safety regulations, and other
relevant (local) directives.
Operational and maintenance instructions:
Lamp frames
The lamps are assembled in a sturdy frame of stainless steel. The frame contains two
special transformers. Each frame has its own connecting cable, which is to be
disconnected prior to installation. Only authorized and skilled electricians may open
the electrical section of the UV-C frames.
UV-C lamps
The lamps must be clean for maximum effect and production of ozone. If not clean
fat will stick on and burn into the lamps with a reduction in the air cleaning capacity.
If necessary spray the lamps with a mild cleaning detergent with a high pH Value
(>13) then carefully wipe the lamps with a soft and damp cloth using gloves for
personal protection. Ensure personal protective clothing is used at all times during
installation and servicing of the system.
Cleaning frequency depends on the stress on the lamps. For example, when the
production in the kitchen is at a higher level than normal the cleaning frequency
must be increased.
At normal operating levels it is expected that the frequency be every second month
and subsequently higher at greater production levels. The type of cooking involved
will also influence the cleaning frequency. A maintenance schedule must be
implemented and maintained once the system has been commissioned and is in
operation.
7
June 2010
6. Changing the UV-C lamps
WARNING
Close down the UV-C system completely before removing the grease filters or
opening the service hatches. The blue UV-C light is harmful to eyes and health.
Required tooling: Phillips screwdriver, mild detergent, water, brush or soft cloth.
The lamps are mounted in stainless steel frames and are connected by a multi
contact in the service box left or right side of the frame.
6.1 Shut down the power to the control cabinet
6.2 Remove the grease filters
6.3 Open both end panels of the stainless steel UV-C frames
6.4 Disconnect the speed clamps on the lamps
6.5 Disconnect the lamps from their contacts by removing the wiring from
the lamps and slide them out from their silicone protection rings
6.6 N.B.: The lamps are very delicate and break easily.
6.7 N.B.: New silicone protection rings must be inserted at every lamp change
6.8 Clean the lamps if necessary with a mild detergent and water and dry
the lamps
6.9 Carefully insert a new lamp and re-connect the speed clamps
6.10 Re-connect the electric wiring
6.11 Close the end panels of the stainless steel UV-C frames
6.12 Close the service hatch
6.13 Replace the grease filters.
8
June 2010
7. Safety Warnings
UV-C lamps are harmful to human eyes. Do not look directly into the lamps If the
eyes are exposed contact a doctor immediately!
UV-C lamps must automatically switch off when the exhaust fan is switched off.
When removing grease filters the UV-C lamps switch off the lamps and exhaust fan
automatically.
Always use the protective safety clothing and glasses.
The lamps must be cleaned at regular intervals according to the maintenance
schedule.
Check the Operational counter (time) on the control cabinet on a regular basis.
The UV-C lamps have a life span of approximately 8000 hours and must be changed
before this point.
If the cooking equipment beneath the UV-C system is changed, Vianen B.V. must be
informed to reset airflow volume and velocity.
9
June 2010
8. The working of the control panel and display
During normal working conditions the display indicates the electrical power
consumption in Amps used by the UV-C lamps and the preset setting. If the power
drops below this value the following error appears on the display:
8.1 Press On/off switch for short time and “Hour counter”appears in the
display
8.2 Press again and power is back.
8.3 Press again for a little longer and the UV-C system switches off.
10
June 2010
The working of the control panel and display
Problem with UV-C lamps refer to Paragraph 6 of this manual section: Changing of
UV-C lamps.
Press reset button for 10 seconds to remove message from display.
11
June 2010
The working of the control panel and display
Ventilator is not working - no power ventilator - check electrical connection.
12
June 2010
The working of the control panel and display
Last grease filter removed or not installed properly
- If not working the possible cause is that the Pressure Sensor is situated
above the arrow in the gutter under the last placed filter in the filter
bank is not activated.
Check that the filter is firmly in position.
13
June 2010
The working of the control panel and display
Check Filters : grease filter bank not complete which causes a pressure difference or
pressure switch is not adjusted correctly / broken.
- The pressure difference switch is situated behind the filter in the electrical part
of the UV-box. For exact position of the difference switch look directly above
the arrow on the gutter next to the grease tray.
- Check if the fan is functioning properly.
14
June 2010
The working of the control panel and display
CHANGE LAMPS :
After 7500 working hours of the lamps this message will appear on the display
Prepare to change lamps in the next 500 hours.
With the reset button message can be removed press reset for more than 10
seconds.
When 8000 hours are reached lamps must to be changed. See paragraph 6 of this
manual . On display the message “Lamps out” will appear this message can only be
removed by resetting the hour counter.
After changing of lamps the hour counter must be reset to zero. See 4.3 electrical
installation of this manual.
Warning: UV-C System will switch off at 8000 hours.
15
June 2010
RESETTING OF THE HOUR COUNTER:
Press OFF/ON button for more than 10 seconds
Entry configuration menu
Press both arrow buttons
Hour counter disappears on display
Press both arrow buttons longer than 3 seconds. Hour counter returns to 0
16
June 2010
POWER LIMIT ADJUSTMENT
To set the limit of the electrical power in Amps first determine the total power
consumption used by all the lamps
Set the limit at minus 10 percent.
Press OFF/ON button for more than 10 seconds
Entry configuration menu
Arrow up higher A Arrow down lower A
17
June 2010
18
June 2010
19
June 2010
20
June 2010
21
June 2010
22
June 2010