Utilization of return water in district heating networks
description
Transcript of Utilization of return water in district heating networks
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 1
Utilization of return water in district heating networks
Oddgeir GudmundssonApplication Specialist
Marek BrandApplication Specialist
Jan Eric ThorsenDirector
Danfoss District Heating Application CentreDK-Nordborg
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 2
Content
Introduction
Concept
Technology
Cases
Conclusion
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 4
1G 2G 3G 4G
Introduction
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 5
Concept
District heating schemes are operating with various temperature levels depending on the original design of the network and the connected building stock
In many cases existing buildings may require high supply temperatures and consequently have high return temperatures, f.ex. supply of 90-100°C and return of 40-60°C
Sufficient temperature levels vary and depend on the heating installations New energy efficient buildings with floor heating installation only need supply temperatures of 35-40°C to fulfill
their heating requirement
Domestic hot water (DHW) temperature of 45°C is considered sufficient for everyday use. Having DH supply temperature of 50°C is sufficient for preparing DHW at 45°C via instantaneous heat exchanger solution, without risk of Legionella.
This fact gives the opportunity to utilize the return flow from existing areas in new areas and hence utilize the capacity of existing DH networks to a greater extend with minimum investment costs. Utilize further the capacity of the distribution network Increased efficiency at the plant due to lower return temperature Reduced heat losses in the return line
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 6
Conceptual example of cascading energy usage in district heating
All energy classes
Newly constructed / renovated areas
D D
multi-apartment
single-family
C
C
C
C
Recently build and renovated
C
C
C
C
FF
F
FFF
F
Non-renovated older buildings
CHP waste incineration
CHP natural gas
Large scale solar
A
A
Low-energybuildings
High temperature supply, 90°C
High temperature return, 50°C
Low temperature return, 25°C
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 7
Utilization of return water for existing buildings
Renovation of the existing network Low Temperature District Heating
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 8
Low Temperature DH for existing buildings Project supported by the Danish government
75 single-family buildings from 1997
Floor heating
Realisation
New low-temperature DH in-house substation
New DH network Heat loss reduced from 41% -> 14%
80% of heat demand supplied from main DH return line
Before transition average Tsupply = 70-75°C
After transition average Tsupply = 55°C
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 9
Area substation
As the DH return temperature can vary it may become necessary to raise the return temperature before it is supplied to the secondary network
This can be achieved by mixing the return water with hot water from the main DH supply pipeline
Primary network
Tsupply=90°C
Treturn=52°C
Treturn=26°C
Sønderby Area substation
Sønderby low temperature
DH
Tsupply=52°C
Sønderby Last consumer
Substation at the consumer
Thermostatic bypass
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 10
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 11
Micro booster – Reduced temperature levels
Ultra-Low Temperature District Heating
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 12
Objective: Maximum utilization of district heating return flow
Ultra-Low Temperature DH for existing buildings Project supported by the Danish government
4 single-family buildings from before 1960
Radiators, mix of 1 pipe and 2 pipe systems
Realization
Micro heat pump DH substation in each house to boost the supply temperature for instantaneous preparation of Domestic Hot Water
New U-LTDH network Heat loss only 46% of the heat loss that would be
experienced in a traditionally designed network
Area heat exchanger substation connected to the main district heating network regulates the supply temperature
Supply temperature kept as low as possible at all times
Area substation
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 13
For floor heating temperature levels of 30-40°C are sufficient
Domestic hot water of 45°C is sufficient for all normal use With instantaneous preparation of DHW there is no risk of
Legionella
Micro heat pump unit boost the supply temperature to 53-55°C and stores the water in a primary side located storage tank until DHW tapping occurs
Condenser
Evaporator
Instantaneous DHW preparation
No Legionella risk
DH side storage tank
Micro booster concept
Micro booster installed
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 14
Heat exchanger area substation
The aim of the substation is to maintain constant secondary side temperature of 40°C
As the DH return temperature can vary primary side supply is mixed with the return to maintain constant 45°C supply to the heat exchanger by means of a pump control
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 16
How applicable can this be?
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 17
Low-temperature DH for existing buildings Supported by the Danish government
8 single-family houses from 1970
With traditional radiators: 70/40/20°C
How much could Tsupply be reduced without sacrificing comfort?
Numerical simulations Many possibilities
Various refurbishment stages Low-temperature radiators
Real measurements Should follow real conditions
Results are coming soon…
70°C40°C
heat output 100 %
50°C33°C
heat output 55 %
same radiatorsṁ = constant
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 18
Duration of Tsup over/equal certain temperatureHeating curves for radiators
Single-family-house from 1970 – results from simulation
! !Low-temperature substation for DHW
Tsu
pp
ly [
°C]
hou
rs a
bove c
ert
ain
te
mp
era
ture
[%
/a]
>50 >55 >60 >65 >70 50
non-renovated 20°C
21.4246575342466
8.13698630136986
2.86986301369863
1.25342465753425
0.222602739726027
66.0924657534247
new windows 20°C
6.83561643835616
1.78767123287671
0.23972602739726
0 0 91.1369863013699
extensive renovation 20°C
0.445205479452055
0 0 0 0 99.5547945205479
new windows 22°C
16.5034246575342
4.79794520547945
1.5958904109589
0.14041095890411
0 76.9623287671233
new windows 22°C LT rad.
1.82191780821918
0.318493150684932
0 0 0 97.8595890410959
3
8
13
18
23
Tsupply [°C]
*Extensive renovation = low energy windows + roof insulation
=
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 19
Existing buildings can be supplied with LTDH already today if Tsupply is in cold periods increased above 50°C
Required Tsupply to radiators depends on:
desired indoor temperature
state of the building heating system
DH companies should be more strict in reducing Tsupply to:
reduce heat losses from DH network
integrate more renewables
DHW applicatoin should
always be changed to low-temperature one
LTDH for Existing Buildings
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 20
Conclusions
There is a potential to further utilize the capacity of existing district heating network and reduce the network return temperature significantly by cascading the energy use
Studies show that with light renovation of buildings the requirements to the DH supply temperature sinks significantly
As new areas are built or building areas renovated close to existing district heating network it is possible to establish district heating network with low investment costs utilizing the remaining heat in the return pipeline from the existing DH grid
Nordic Show Room on Energy Quality Management, 27-28th August 2014, O. GUDMUNDSSON, DANFOSS A/S
28.08.2014 | 21
Thank you for the attention
Contact information:Oddgeir Gudmundsson
Application Specialist, Application CentreDanfoss District Energy, DK-Nordborg