Utility Pump Station Design Spreadsheet
-
Upload
farhat-khan -
Category
Documents
-
view
447 -
download
19
description
Transcript of Utility Pump Station Design Spreadsheet
General:
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Spreadsheet Instructions
Input the Vertical Datum to which the elevations to be provided correspond.
This spreadsheet is to be used as a tool for design engineers to design pump station and force main systems to connect to the Brunswick County Collection System. The use of this spreadsheet does not relieve the design engineer of the responsibility of verifying the results of the spreadsheet and taking into account conditions which may not be accounted for with the spreadsheet. Should such conditions which are not accounted for in this spreadsheet be present, the designer should contact the Brunswick County Engineering Department prior to submittal. Data should only be entered into shaded cells. User entered data will be linked to calculations in subsequent sheets as required. Warnings and approval messages appear behind Bold & Italicized text.
Begin with the "Tributary Flow Calculations" tab. Insert the number of applicable units corresponding to the description in the Establishment column. Add additional flow generating establishments as required which are not included in the list. The flow generated by these units is subject to Brunswick County approval.
Move to the "Design Pumping Flow Rate" tab. The Minimum Pumping Rate Required is calculated. The designer should enter the desired Design Pumping Rate in the shaded cell. The Design Pumping Rate should not be less than the Minimum Pumping Rate Required. Additional pumping capacity may be beneficial to allow for non-clog pumps, larger force main diameters, etc.
Move to the "Cycle Time & Wet Well Geometry" tab. Input the target cycles per hour in the Target Cycles per Hour box. Pick a Wet Well Diameter and Wet Well Cycle in the "Determine Wet well Diameter" box. The Volume in Cycle value should closely match the Required Volume value. If not, adjust desired Cycles Per Hour, Wet Well Diameter, and Wet Well Cycle values. Note: Wet well diameter to be standard precast wet well inside diameter. Submit manufacturer's cut sheet of proposed wet well.
Input the existing Ground Elevation and the Sanitary Sewer Invert In elevation. Do not enter the Bottom Invert Elevation until the specific pump has been determined in instruction item #11. The vertical distance between Pump Off and Bottom Invert Elev shall provide for complete pump submergance, and not be less than 4'.
Move to the "Force Main & Piping Design" tab. Input the proposed force main diameter. Resultant velocity should be between 2-5 fps. Check for warnings below the velocity line. Enter the length of force main from the downstream connection point to the transition at the valve vault piping.
Enter the Connection Point in the shaded box. Example Values are as follows: Existing 12" FM at Mt. Misery Rd & Cedar Hill Rd, Existing MH at Hwy 17 & Holden Beach Rd., etc.
Select Valve Vault and Wet Well Piping Size. This piping may be slightly smaller than the Off-Site Force Main. Enter the appropriate quantity of fittings and the total length of pipe the flow travels through from one pump until transiting to the larger off-site force main diameter, or leaving the valve vault (if Pump Station Piping and Off-Site Force Main are same diameter). Add additonal fittings and associated L/D values as required.
Spreadsheet Instructions
If Wet Well ballast is required as indicated on the last box on the sheet submit proposed concrete anchor design for approval.
Enter data provided by Brunswick County in the GPM, Pressure Head at Connection Condition "All Pumps On", and Pressure Head at Connection Condition "Only Proposed Pump On" columns. The Engineer shall determine the appropriate value to input into the “Static Head” column from either 1) the “Connection Point Elevation” minus the wetwell “Pump Off” elevation or 2) the Force Main High Point elevation minus the wetwell “Pump Off” elevation. Option #2 is appropriate when the High Point Elevation exceeds the Hydraulic Grade Line elevation at the location of the proposed force main High Point. As a quick check to see if option #2 needs further investigation, sum the “Pressure Head at Connection” and the “Connection Point Elevation” to calculate the Connection Point Hydraulic Grade Line for both the “All On” and “Only Proposed Pump Station On” scenarios. If the Connection Point Hydraulic Grade Line exceeds the High Point Elevation for both conditions then option #1 is the appropriate choice for determining the static head. If static head is determined by option 2 for any condition, the designer shall indicate the flow rate above which static head as defined by option 1 is the approperate value.
Select a pump that can provide the “Minimum Required Pumping Rate” at the head in the column "’All On TDH”. Check to ensure the proposed pump will also provided the Design Flow Rate at the head in column "’All Off TDH”. Use the graph provided on the "System Curve" tab to aid in determining operating points. All pumps should be non-overloading at the impeller diameter chosen. Note: If the proposed force main discharges to a non-pressurized point such as a gravity manhole or to a WWTP outfall, or option 2 above governs static head, the values for both “Pressure Head at Connection” columns will be 0.” Note: Velocity Head is not included in spreadsheet calculation due to neglidgeable value for normal force main operating velocities.
Enter specific pump information in the shaded areas. Attached manufacturer's cut sheet. Move to "Cycle Time & Wet Well Geometry" tab and enter Wet Well Invert Elevation based on the depth required to provide complete submergence for the specific pump chosen.
Move to the "Operational Check" tab. The operational points entered should be points on the pump curve that intercept the system curves.
Check for Warnings in Red at the bottom of the page. If both read OK, then the pump and force main design can be submitted to Brunswick County for review. If warnings are present adjust previously entered values as required to obtain a cycle time between 2-8 cycles per hour. Values which can affect cycle time include: wet well diameter, wet well cycle, pump selection, etc.
Move to the "Buoyancy Calculations" tab. Input the outside diameter of the wet well, diameter of the extended base, extended base slab thickness, and top slab thickness in appropriate shaded boxes. Provided manufacturer's cut sheet to verify dimensions.
Enter the Saturated unit weight of soil. Use 50 pcf for the submerged unit weigh of soil unless geotechnical investigations justify greater values. Attach supporting geotechnical information if applicable.
Once the design of the pump station and force main is complete, move to the "Cover & Summary" tab. Input the project specific data as required. Note these cells are not shaded.
Brunswick CountyWastewater Pump Station
& Force Main
Design Calculations
Project Name:
Location:
Designed By:
Checked By:
Date:
Project no.:
Brunswick CountyWastewater Pump Station
&Force Main
Project Summary
Project Name:
Average Daily Flow (gpm):
Pump Operational Point No. 1 (gpm@tdh):
Pump Operational Point, No. 2 (gpm@tdh):
Pump Manufacturer:
Model Number:
Impeller Diameter:
Horse Power:
Voltage:
Force Main Diameter (in):
Force Main Length (ft):
Tributary Wastewater Flow Calculations
Establishment Unit Type
Residential (To NEWWTF) 360 Residence
Residential (all other Treatment Facilities) 210 Residence
Barber Shops 50 Chair
Beauty Shops 125 Booth or Bowl
Business - General & Office 25 Employee per shift
Business - Factories Excluding Industrial Waste 25 Employee per shift
Business or Factories w/showers or food preparation 35 Employee per shift
Business - Warehouse 100 Loading bay
Business - Warehouse Self Storage (not including Caretaker Residence) 1 Unit
Churches without kitchens, day care, or camps 3 Seat
Churches with kitchens 5 Seat
Churches providing day care or camp 25 Person (child+employee)
Fire or Rescue without on-site staff 25 Person
Fire or Rescue with on-site staff 50 Person per shift
Food & Drink - Banquet Dining Hall 30 Seat
Food & Drink - Bars, Cocktail Lounges 20 Seat
Food & Drink - Caterers 50 100 sf floor space
Food & Drink - Restaurants, Full Service 40 Seat
Food & Drink - Restaurants, Single Service Articles 20 Seat
Food & Drink - Restaurants, Drive-in 50 car space
Food & Drink - Restaurants, Carry out only 50 100 sf floor space
Food & Drink - Institutions, Dining Halls 5 meal
Food & Drink - Deli 40 100 sf floor space
Food & Drink - Bakery 10 100 sf floor space
Food & Drink - Meat Dept., Butcher, Fish Market 75 100 sf floor space
Food & Drink - Specialty Food Stand or Kiosk 50 100 sf floor space
Hotels/Motels/B&B without in-room cooking facilities 120 Room
Hotels/Motels/B&B with in-room cooking facilities 175 Room
Hotels/Motels- Resort Hotels 200 Room
Hotels/Motels- Cottages, Cabins 200 Unit
Laundries (Self-Service) 500 Machine
Medical or Dental offices 250 Practitioner per shift
Medical - Veterinary offices without boarding 250 Practitioner per shift
Medical - Veterinary, Kennels, with boarding 20 Pen, Cage, Kennel, Stall
Medical - Medical Hospitals 300 Bed
Medical - Mental Hospitals 150 Bed
Medical - Convalescent, Nursing, Rest Homes without Laundry 60 Bed
Medical - Convalescent, Nursing, Rest Homes w/ Laundry 120 Bed
Medical - Residential Care Facilities 60 Person
Parks & Rec. - Campgrounds w/comfort station but without water & sewer hookup 75 Campsite
Parks & Rec. - Campgrounds with water & sewer hookup 100 Campsite
Parks & Rec. - Campground Dump Station facility 50 Space
Parks & Rec. - Construction, Hunting, or Work camps with flush toilets 60 Person
Parks & Rec. - Construction, Hunting, or Work camps with chemical or portable toilets 40 Person
Parks & Rec. - Parks with Restrooms 250 Plumbing Fixture
Parks & Rec. - Summer camps without food prep or laundry facilitates 30 Person
Parks & Rec. - Summer camps with food prep and laundry facilitates 60 Person
Parks & Rec. - Swimming Pools, Bath Houses, Spas 10 Person
Public Access Restrooms 325 Plumbing Fixture
Unit Value (Gal/Day/Unit)
Tributary Wastewater Flow Calculations
Establishment Unit TypeUnit Value
(Gal/Day/Unit)
Schools - Preschools & Daycares 25 Person (child+employee)
Schools with Cafeteria, Gym, & Showers 15 Student
Schools with Cafeteria 12 Student
Schools without Cafeteria, Gym, & Showers 10 Student
Schools, Boarding 60 Person (student+employee)
Service Stations, Gas Stations 250 Plumbing Fixture
Car Wash Facilities (if recycling water, see Rule .0235 of 2T regulations) 1200 Bay
Sports Centers - Bowling 50 Lane
Sports Centers - Fitness, Exercise, Karate, Dance 50 100 sf floor space
Sports Centers - Tennis, Racquet ball 50 court
Sports Centers - Gymnasium 50 100 sf floor space
Sports Centers - Golf Course with only minimal food service 250 Plumbing Fixture
Sports Centers - Country Clubs 60 Member or Patron
Sports Centers - Mini Golf, Putt-Putt 250 Plumbing Fixture
Sports Centers - Go-Kart, Motorcross 250 Plumbing Fixture
Sports Centers - Batting Cages, Driving Ranges 250 Plumbing Fixture
Sports Centers - Marinas without Bathhouse 10 Slip
Sports Centers - Marinas with Bathhouse 30 Slip
Sports Centers - Video Game Arcades, Pool Halls 250 Plumbing Fixture
Stadiums, Auditoriums, Theatres, Community Centers 5 Seat
Stores, Shopping Centers, Malls & Flea Markets:
Auto, Boat, RV dealerships/showrooms with restrooms 125 Plumbing Fixture
Convenience Stores, with Food Preparation 60 100 sf floor space
Convenience Stores, without Food Preparation 250 Plumbing Fixture
Flea Markets 30 Stall
Shopping Centers and Malls with Food Service 130 1000 sf
Stores and Shopping Centers without Food Service 100 1000 sf
Transportation Terminals - Air, Bus, Train, Ferry, Port & Dock 5 Passenger
Other -
Other -
Other -
Other -
From 15A NCAC 02T .0114 Average Daily Flow (gallons per day)
Tributary Wastewater Flow Calculations
# of Units Discharge, GPD
500 180,000
0 0
0 0
5 625
100 2,500
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
100 3,000
0 0
0 0
0 0
0 0
0 0
10 500
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
368 3,680
0 0
Tributary Wastewater Flow Calculations
# of Units Discharge, GPD
0 0
0 0
1000 12,000
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0 0
0
0
0
0
Average Daily Flow (gallons per day) 202,305
Design Pumping Flow Rate
Peaking Factor Calculation
Service Area Population = 100,000
Peak Factor = 18 + √P
4 + √P
Calculated Peak Factor = 2.0
Design Peak Factor = 2.5
Determine Minimum Pump Rate
Average Daily Flow = 202,305 GPD
Peak Flow = 505763 GPD
Minimum Pumping Rate Required = 351 GPM
Design Pumping Rate = 575 GPM
Cycle Time & Wet Well Geometry
Target Cycles Per Hour
ADF = 140 gpm
Pumping Rate = 575 gpm
Time = 15.0 min.
Cycles Per Hour = 4.0
Check Cycles Per Hour: OK
Check Cycles Per Hour: OK
Determine Wet well Diameter
Required Volume = 1592 Gallons
Pick Wet Well Diameter = 8.0 Ft
Pick Wet Well Cycle = 4.0 Vert. Ft
Volume in Cycle = 1504 Gallons
Vertical Datum Used: NAVD 88
Determine Wet Well Invert & Float Elevations
Wet well Dia. = 8.0 Ft
Top Elev= 50.50
Gnd Elev= 50.00
SS Invert In= 42.00
Alarm = 37.00
Lag On = 36.00
Lead On = 35.00
Pumps Off = 31.00
Bottom Invert Elev* = 27.00
*As required for complete submergence
OK
Force Main & Piping Design
Off-Site Force Main Data
Design Pump Rate (gpm) = 575
Select Force Main Size (in) = 8
Velocity (fps) = 3.67
Meets Minimum Velocity Requirement? OK
Meets Maximum Velocity Requirement? OK
Required Pump? Use Non-Clog Pump
Line Length (ft) = 10,320
Account for Minor Losses = 5%
Equiv Length (ft) = 10,325
Connection Point: 24" Force Main @ North Brunswick WWTP
Pump Station Piping Data
Design Pump Rate (gpm) = 575
Pick Wet Well & Valve Vault Piping Size (in) = 6
Velocity (fps) = 6.52
Meets Minimum Velocity Requirement? OK > 2 FPS
Meets Maximum Velocity Requirement? OK < 8 FPS
Item Number of Fittings L/D Ratio Equivalent Length
45 bend 0 16 0.0090 bend 2 30 30.0022.5 bend 1 9 4.50Branch Tee Flow 1 60 30.00Check valve 1 135 67.50Plug Valve 1 17 8.50
0.000.00
0.00Equivalent Fitting Length (ft) = 141
Wet Well & Valve Vault Piping Length (ft) = 20Total Equivalent Pump Station Pipe Length (ft) = 161
Equivalent Off-Site Diameter Length (ft) = 651
Total Equivalent Force Main Length (ft) = 10976
Pump Selection
Force Main Diameter (in) =
Equivalent Force Main Length (ft) =
Hazen-Williams C Factor =
Minimum Required Pump Rate (GPM) =
Design Pumping Rate (GPM) =
GPM Static Head "All On" TDH
100 14 0 20 37 23
300 16.6 0.4 20 58 42
600 20.8 1.4 20 119 100
900 25.5 2.9 0 191 169
1200 30.5 5 0 313 287
Pump Manufacturer: Flygt
Model Number: NP 3171 SH 63-275-00-1070
Impeller Diameter: 195 mm
Horsepower: 35
Voltage: 460v 3phase
Pressure Head at Connection "All
On"
Pressure Head at Connection "Only
Proposed Pump Station On"
"Only Proposed
Pump Station On" TDH
Pump Selection
8
10976
130
351
575
Velocity (fps) Pump Head
0.6 245
1.9 197
3.8 135
5.7 74
7.7
Pg. 8
0 200 400 600 800 1000 1200 14000
50
100
150
200
250
300
350
Pump and Force Main System Curve
Pump Head
All On System TDH
All Off System TDH
Flow (GPM)
TD
H (
FT
)
Station Operation Check
Proposed Operational Point No.1
600 GPM @ 135 TDH
Check Wet well Cycle Times
Wet well Wet well Wet well Wet well
Diameter Area Cycle Volume
(feet) (gal / VF) (ft) (gal)
8.0 376 4.0 1503
Fill = Wet well Volume = 10.7 minutes
ADF
Run = Wet well Volume = 3.3 minutes
Pump Rate - ADF
Total = 14.0 minutes
Cycle Time = 4.3 Cycles / Hour
Meets Minimum Cycle Time? OK
Meets Maximum Cycle Time? OK
Station Operation Check
Proposed Operational Point No. 2
640 GPM @ 125 TDH
Check Wet well Cycle Times
Wet well Wet well Wet well Wet well
Diameter Area Cycle Volume
(feet) (gal / VF) (ft) (gal)
8.0 376 4.0 1503
Fill = Wet well Volume = 10.7 minutes
ADF
Run = Wet well Volume = 3.0 minutes
Pump Rate - ADF
Total = 13.7 minutes
Cycle Time = 4.4 Cycles / Hour
Meets Minimum Cycle Time? OK
Meets Maximum Cycle Time? OK
Buoyancy Calculations
Wet well Outside Dimensions 9.00 Feet
Wet well Inside Dimensions 8.00 Feet
Wet well Top Slab Elevation 50.50 Feet
Wet well Invert Elevation 27.00 Feet
Extended Base Slab Diameter 11.00 Feet
Extended Base Slab Thickness 1.00 Feet
Top Slab Thickness 0.50 Feet
Calculate Total Volume of Wet well Structure
Volume of Wet well Riser Sections= 1494 cf
Volume of Wet well Extended Base= 95 cf
Total Volume of Wet well Structure= 1589 cf
Calculate Total Volume of Water Displaced
H20 Displaced = (Volume of Wet well Structure) * (62.4 lbs/cf)
H20 Displaced= 99168 lbs
Calculate Submerged Weight of Wet well Components
Section Total Ht Weight
Top Slab Thickness (ft.) 0.50 2786
Riser - Total Vertical Ft. 23.50 27486
Base Slab Thickness (ft.) 1.00 8325
Totals= 25 38597
Total Weight of Concrete in Wet well= 38597 lbs.
Calculate Weight of Soil Above Extended Base/Footing
Total Area of Extended Base 95 sf
Total Area of Wet well Riser 64 sf
Area of Extended Base less Wet well 31 sf
Height of Soil Above Extended Base 23 ft
Volume of Soil Above Extended Base 723 cf
Weight of Soil Above Extended Base (estimated) 50 lbs/cf
Total Weight of Soil Above Extended Base 36128 lbs/cf
Flotation Protection Required?
Weight of Concrete and Weight of Soil Above Extended Base: 74726
Weight of Water Displaced By Wet Well: 99168
Flotation Protection Required? YES
lbs
lbs