AAON Mini Controller User’s Manual QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Installation and service must be performed by a trained, qualified installer. A copy of this manual should be kept with the unit. WARNING

Transcript of User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER...

Page 1: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

AAON Mini Controller

Userrsquos Manual

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this manual should be kept with the unit

WARNING

3

Table of Contents Safety 5 AAONreg Mini Controller Features and Options 7 General Information 8 Installation 9 Locating and Mounting the Controller 9 AAON Mini Controller Backplate Layout 10 Input Connections 12 Remote Space Temperature Sensor 12 Supply Air Temperature Sensor 12 Output Connections 12 Startup 13 Navigation 13 Home Screen Configuration 13 Main Menu Configuration 14 Advanced Menu Configuration 17 Controller Configuration Steps 23

Constant Volume Air Conditioner Configuration 23 Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat 24 Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat 25 Constant Volume Heat Pump Configuration 27 Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat 28 Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat 30 Modulating Hot Gas Reheat 31 Economizer 32 CO2 Override 32

Operation 34 BACnet Points List 40 Maintenance and Support 43 Replacement Parts 43 Glossary 44 AAON Mini Controller Startup Form 47 Maintenance Log 48 Literature Change History 49

R98200 Rev C 150409

4

Index of Tables and Figures

Tables Table 1 - Control Wiring 11Table 2 - UTC Offset 19Table 3 - Default Access Levels 22Table 4 - Analog Values 40Table 5 - Analog Values Continued 41Table 6 - Relay Values 41Table 7 - Multi-State Values 42Table 8 - Analog Inputs 42Table 9 - Analog Outputs 42Table 10 - Relay Outputs 42

Figures Figure 1 - Dimensions and Connections 9Figure 2 - Backplate Terminal Locations 10Figure 3 - MSTP Network End-of-Line Terminology 11Figure 4 - EOL and Pull-Up Switch Resistor Positions on Reverse Side of Controller 12Figure 5 - Switched Common and Relays 12Figure 6 - AAON Mini Controller 13Figure 7 - Home Screen with Flashing Service Message 15

5

Safety

Attention should be paid to the following statements NOTE - Notes are intended to clarify the unit installation operation and maintenance

CAUTION - Caution statements are given to prevent actions that may result in equipment damage property damage or personal injury

WARNING - Warning statements are given to prevent actions that could result in equipment damage property damage personal injury or death

DANGER - Danger statements are given to prevent actions that will result in equipment damage property damage severe personal injury or death

ELECTRIC SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation serious injury death or property damage Improper servicing of HVAC equipment could result in dangerous operation serious injury death or property damage Before servicing disconnect all

electrical power to the equipment More than one disconnect may be provided

When servicing controls label all wires prior to disconnecting Reconnect wires correctly

Verify proper operation after servicing Secure all doors with key-lock or nut and bolt

WARNING Electric shock hazard Before servicing disconnect all electrical power to the equipment including remote disconnects to avoid shock hazard or injury from rotating parts Follow proper Lockout-Tagout procedures

WARNING

GROUNDING REQUIRED All field installed wiring must be completed by qualified personnel Field installed wiring must comply with NECCEC local and state electrical code requirements Failure to follow code requirements could result in serious injury or death Provide proper unit ground in accordance with these code requirements

WARNING

6

1 The controller is for indoor use only See

General Information section for more information

2 READ THE ENTIRE USERrsquoS

MANUAL OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL

3 Keep this manual and all literature

safeguarded near the equipment

During installation testing servicing and troubleshooting of the equipment it may be necessary to work with live electrical components Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks Standard NFPA-70E an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn should be followed

WARNING

7

AAONreg Mini Controller Features and Options LeadSingle Variable Capacity Scroll Compressor Control Constant Volume Control Single Zone VAV Control Air Conditioner or Heat Pump Weekday Weekend Entire Week or Daily Scheduling 12 Day Holiday Scheduling Alarms and Trend Logging Push Button Override 2 Compressor Stages Sensible Controlled Fully Modulating Economizer BACnet MSTP EIA-485 Network Connection Modulating GasSCR Electric Heat With additional controls components

1 2 or 3 Stages of Gas Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 2 or 3 Stages of Electric Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 and 2 Stages of Emergency Heat Second stage available only with some unit configurations See relay output descriptions

for details Options Available that use the Configurable Controller Input Space Humidity Control R80580 Model of Mini Controller Only

Enthalpy Controlled Fully Modulating Economizer CO2 Economizer Override Remote Averaging Space Temperature Sensor Remote Space Temperature Sensor Control Fan Status

8

General Information The AAON Mini Controller has been designed for simple single zone system control Codes and Ordinances HVAC system should be sized in accordance with the American Society of Heating Refrigeration and Air Conditioning Engineers Handbook Installation of equipment must conform to the ICC standards of the International Mechanical Code the International Building Code Installation of Air Conditioning and Ventilating Systems Standard NFPA 90A and local building plumbing and waste water codes All appliances must be electrically grounded in accordance with local codes or in the absence of local codes the current National Electric Code ANSINFPA 70 or the current Canadian Electrical Code CSA C221 Receiving Unit When received the controller should be checked for damage that might have occurred in transit Controller should also be checked to ensure the correct model has been received to match the job requirements AAON Mini Controller R80570 - Space Temperature Control R80580 - Space Temperature and Humidity Control

Specifications Supply Voltage24 VAC (+15-10) Class-2

13 VA Supply Power

Wire clamp type terminal blocks 14-22 AWG copper 4 pin EIA-485

Connections

OutputsAnalog outputs produce 0-10 VDC 20 mA maximum

Binary outputs (NO SPST Form A) carry 1 A maximum per relay or a total of 15 A per bank of 3 relays (relays 1-3 4-6) 24 VACVDC

10k Type 3 Thermistor Inputs

64 x 128 pixel dot matrix LCD Display

White flame retardant plastic Case Material

5551 x 4192 x 1125 inches (H x W x D) Dimensions

141 x 106 x 286 mm

048 lbs 218 g Weight

UL 916 Energy Management Equipment Approvals

FCC Class B Part 15 Subpart B

10k Type 2 Thermistor (Temperature only model)

TemperatureHumidity Sensors

CMOS (Temperature and Humidity model) Temperature Readings

+-09degF (+-05degC) from 40-104degF Accuracy

+- 01degF (+-02degC) Resolution

36-120degF (22-488degC) Operating Range

5-30 seconds Response Time

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this manual should be kept with the unit

WARNING

9

Humidity Readings

0-100 RH Range

+-2 RH (10-90 RH) Accuracy77degF (25degC)

Less than 4 seconds Response Time

Environmental Limits

34-125degF (11-516degC) Operating

-40-140degF (-40-60degC) Shipping

0-95 RH non-condensing Humidity

Installation Locating and Mounting the Controller For optimum performance controller should be mounted on an interior wall 4-5 feet above the floor away from heat sources sunlight windows air vents and air circulation obstructions 1 Complete rough-in wiring at each

location prior to controller installation 2 Hex screws at the bottom and top of the

controller backplate must be turned clockwise until clear of the controller cover to allow removal of the cover

3 Route wiring through the backplate 4 With the embossed UP toward the

ceiling fasten the 2x4 backplate directly to a vertical 2x4 inch wall handy box A 4x4 inch backplate attachment is also provided for horizontal 2x4 handy box and 4x4 handy box applications

5 Make the appropriate connections to the terminal block

6 Place controller cover over the backplate while being careful not to pinch or dislodge any wiring Turn the hex screws counterclockwise until they engage the cover and hold it in place

Figure 1 - Dimensions and Connections

To prevent mounting screw heads from touching the circuit board in the controller use only the mounting screws provided with the controller Using screws other than the type supplied may damage the controller

CAUTION

10

AAON Mini Controller Backplate Layout

Backplate W

iring Cutout

HPU | Std OAD

Analog Outputs

GND G2 Y1(Analog)

MSTP +B RH

Relay Outputs

-A 24 VAC (SC)

Inputs

OAT E2 | W3 | (Y1) SAT E | W2 GND OB | W1

Relay Outputs

IN2 (L) 24 VAC (SC)

24 VAC - C Y2 ~ R G

Figure 2 - Backplate Terminal Locations

+B = BACnet network terminal BACnet MSTP EIA-485 Network

-A = BACnet network terminal

Space Temp (Internal) = IN1 Space Temperature

Inputs

IN2 = L Configurable Input bull Suction Pressure - 0-10 VDC bull Outside Air Humidity - 0-10 VDC bull CO2 - 0-10 VDC bull Remote Space Temperature - 10k Type 3

Thermistor bull Fan Status - 10k Type 3 Thermistor SAT = IN3 Supply Air Temperature - 10k Type 3 Thermistor OAT = IN4 Outside Air Temperature - 10k Type 3 Thermistor Space RH (Internal) = IN5 Space Relative Humidity GND = Ground

- C = COM E Common 24 VAC

~ R = 24 VAC Phase

OAD = OUT9 EC1 Economizer Output - 0-10 10-0 2-10 or 10-2 VDC (0-100)

Analog Outputs

GND = Ground G2 = OUT8 S1 Variable Speed Supply Fan Output - 0-10 VDC (0-100) Y1 (Analog) = OUT7 Variable Capacity Compressor Output - 1-5 VDC (10-100)

RH = RLY6 Dehumidification Relay Outputs

24 VAC = SC Common E2 | W3 | Y1 (Relay) = RLY5 Emer Heat 2Heat 3Compressor 1 E | W2 = RLY4 Emer Heat 1Heat 2 OB | W1 = RLY3 Reversing ValveHeat 1 24 VAC = SC Common Y2 = RLY2 Compressor 2 G = RLY1 Supply Fan

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE ltFEFF03a703c103b703c303b903bc03bf03c003bf03b903ae03c303c403b5002003b103c503c403ad03c2002003c403b903c2002003c103c503b803bc03af03c303b503b903c2002003b303b903b1002003bd03b1002003b403b703bc03b903bf03c503c103b303ae03c303b503c403b5002003ad03b303b303c103b103c603b1002000410064006f006200650020005000440046002003c003bf03c5002003b503af03bd03b103b9002003ba03b103c42019002003b503be03bf03c703ae03bd002003ba03b103c403ac03bb03bb03b703bb03b1002003b303b903b1002003c003c103bf002d03b503ba03c403c503c003c903c403b903ba03ad03c2002003b503c103b303b103c303af03b503c2002003c503c803b703bb03ae03c2002003c003bf03b903cc03c403b703c403b103c2002e0020002003a403b10020005000440046002003ad03b303b303c103b103c603b1002003c003bf03c5002003ad03c703b503c403b5002003b403b703bc03b903bf03c503c103b303ae03c303b503b9002003bc03c003bf03c103bf03cd03bd002003bd03b1002003b103bd03bf03b903c703c403bf03cd03bd002003bc03b5002003c403bf0020004100630072006f006200610074002c002003c403bf002000410064006f00620065002000520065006100640065007200200035002e0030002003ba03b103b9002003bc03b503c403b103b303b503bd03ad03c303c403b503c103b503c2002003b503ba03b403cc03c303b503b903c2002egt13 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN ltFEFF004b0069007600e1006c00f30020006d0069006e0151007300e9006701710020006e0079006f006d00640061006900200065006c0151006b00e90073007a00ed007401510020006e0079006f006d00740061007400e100730068006f007a0020006c006500670069006e006b00e1006200620020006d0065006700660065006c0065006c0151002000410064006f00620065002000500044004600200064006f006b0075006d0065006e00740075006d006f006b0061007400200065007a0065006b006b0065006c0020006100200062006500e1006c006c00ed007400e10073006f006b006b0061006c0020006b00e90073007a00ed0074006800650074002e0020002000410020006c00e90074007200650068006f007a006f00740074002000500044004600200064006f006b0075006d0065006e00740075006d006f006b00200061007a0020004100630072006f006200610074002000e9007300200061007a002000410064006f00620065002000520065006100640065007200200035002e0030002c0020007600610067007900200061007a002000610074007400f3006c0020006b00e9007301510062006200690020007600650072007a006900f3006b006b0061006c0020006e00790069007400680061007400f3006b0020006d00650067002egt13 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR ltFEFF005900fc006b00730065006b0020006b0061006c006900740065006c0069002000f6006e002000790061007a006401310072006d00610020006200610073006b013100730131006e006100200065006e0020006900790069002000750079006100620069006c006500630065006b002000410064006f006200650020005000440046002000620065006c00670065006c0065007200690020006f006c0075015f007400750072006d0061006b0020006900e70069006e00200062007500200061007900610072006c0061007201310020006b0075006c006c0061006e0131006e002e00200020004f006c0075015f0074007500720075006c0061006e0020005000440046002000620065006c00670065006c0065007200690020004100630072006f006200610074002000760065002000410064006f00620065002000520065006100640065007200200035002e003000200076006500200073006f006e0072006100730131006e00640061006b00690020007300fc007200fc006d006c00650072006c00650020006100e70131006c006100620069006c00690072002egt13 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 2: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

3

Table of Contents Safety 5 AAONreg Mini Controller Features and Options 7 General Information 8 Installation 9 Locating and Mounting the Controller 9 AAON Mini Controller Backplate Layout 10 Input Connections 12 Remote Space Temperature Sensor 12 Supply Air Temperature Sensor 12 Output Connections 12 Startup 13 Navigation 13 Home Screen Configuration 13 Main Menu Configuration 14 Advanced Menu Configuration 17 Controller Configuration Steps 23

Constant Volume Air Conditioner Configuration 23 Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat 24 Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat 25 Constant Volume Heat Pump Configuration 27 Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat 28 Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat 30 Modulating Hot Gas Reheat 31 Economizer 32 CO2 Override 32

Operation 34 BACnet Points List 40 Maintenance and Support 43 Replacement Parts 43 Glossary 44 AAON Mini Controller Startup Form 47 Maintenance Log 48 Literature Change History 49

R98200 Rev C 150409

4

Index of Tables and Figures

Tables Table 1 - Control Wiring 11Table 2 - UTC Offset 19Table 3 - Default Access Levels 22Table 4 - Analog Values 40Table 5 - Analog Values Continued 41Table 6 - Relay Values 41Table 7 - Multi-State Values 42Table 8 - Analog Inputs 42Table 9 - Analog Outputs 42Table 10 - Relay Outputs 42

Figures Figure 1 - Dimensions and Connections 9Figure 2 - Backplate Terminal Locations 10Figure 3 - MSTP Network End-of-Line Terminology 11Figure 4 - EOL and Pull-Up Switch Resistor Positions on Reverse Side of Controller 12Figure 5 - Switched Common and Relays 12Figure 6 - AAON Mini Controller 13Figure 7 - Home Screen with Flashing Service Message 15

5

Safety

Attention should be paid to the following statements NOTE - Notes are intended to clarify the unit installation operation and maintenance

CAUTION - Caution statements are given to prevent actions that may result in equipment damage property damage or personal injury

WARNING - Warning statements are given to prevent actions that could result in equipment damage property damage personal injury or death

DANGER - Danger statements are given to prevent actions that will result in equipment damage property damage severe personal injury or death

ELECTRIC SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation serious injury death or property damage Improper servicing of HVAC equipment could result in dangerous operation serious injury death or property damage Before servicing disconnect all

electrical power to the equipment More than one disconnect may be provided

When servicing controls label all wires prior to disconnecting Reconnect wires correctly

Verify proper operation after servicing Secure all doors with key-lock or nut and bolt

WARNING Electric shock hazard Before servicing disconnect all electrical power to the equipment including remote disconnects to avoid shock hazard or injury from rotating parts Follow proper Lockout-Tagout procedures

WARNING

GROUNDING REQUIRED All field installed wiring must be completed by qualified personnel Field installed wiring must comply with NECCEC local and state electrical code requirements Failure to follow code requirements could result in serious injury or death Provide proper unit ground in accordance with these code requirements

WARNING

6

1 The controller is for indoor use only See

General Information section for more information

2 READ THE ENTIRE USERrsquoS

MANUAL OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL

3 Keep this manual and all literature

safeguarded near the equipment

During installation testing servicing and troubleshooting of the equipment it may be necessary to work with live electrical components Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks Standard NFPA-70E an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn should be followed

WARNING

7

AAONreg Mini Controller Features and Options LeadSingle Variable Capacity Scroll Compressor Control Constant Volume Control Single Zone VAV Control Air Conditioner or Heat Pump Weekday Weekend Entire Week or Daily Scheduling 12 Day Holiday Scheduling Alarms and Trend Logging Push Button Override 2 Compressor Stages Sensible Controlled Fully Modulating Economizer BACnet MSTP EIA-485 Network Connection Modulating GasSCR Electric Heat With additional controls components

1 2 or 3 Stages of Gas Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 2 or 3 Stages of Electric Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 and 2 Stages of Emergency Heat Second stage available only with some unit configurations See relay output descriptions

for details Options Available that use the Configurable Controller Input Space Humidity Control R80580 Model of Mini Controller Only

Enthalpy Controlled Fully Modulating Economizer CO2 Economizer Override Remote Averaging Space Temperature Sensor Remote Space Temperature Sensor Control Fan Status

8

General Information The AAON Mini Controller has been designed for simple single zone system control Codes and Ordinances HVAC system should be sized in accordance with the American Society of Heating Refrigeration and Air Conditioning Engineers Handbook Installation of equipment must conform to the ICC standards of the International Mechanical Code the International Building Code Installation of Air Conditioning and Ventilating Systems Standard NFPA 90A and local building plumbing and waste water codes All appliances must be electrically grounded in accordance with local codes or in the absence of local codes the current National Electric Code ANSINFPA 70 or the current Canadian Electrical Code CSA C221 Receiving Unit When received the controller should be checked for damage that might have occurred in transit Controller should also be checked to ensure the correct model has been received to match the job requirements AAON Mini Controller R80570 - Space Temperature Control R80580 - Space Temperature and Humidity Control

Specifications Supply Voltage24 VAC (+15-10) Class-2

13 VA Supply Power

Wire clamp type terminal blocks 14-22 AWG copper 4 pin EIA-485

Connections

OutputsAnalog outputs produce 0-10 VDC 20 mA maximum

Binary outputs (NO SPST Form A) carry 1 A maximum per relay or a total of 15 A per bank of 3 relays (relays 1-3 4-6) 24 VACVDC

10k Type 3 Thermistor Inputs

64 x 128 pixel dot matrix LCD Display

White flame retardant plastic Case Material

5551 x 4192 x 1125 inches (H x W x D) Dimensions

141 x 106 x 286 mm

048 lbs 218 g Weight

UL 916 Energy Management Equipment Approvals

FCC Class B Part 15 Subpart B

10k Type 2 Thermistor (Temperature only model)

TemperatureHumidity Sensors

CMOS (Temperature and Humidity model) Temperature Readings

+-09degF (+-05degC) from 40-104degF Accuracy

+- 01degF (+-02degC) Resolution

36-120degF (22-488degC) Operating Range

5-30 seconds Response Time

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this manual should be kept with the unit

WARNING

9

Humidity Readings

0-100 RH Range

+-2 RH (10-90 RH) Accuracy77degF (25degC)

Less than 4 seconds Response Time

Environmental Limits

34-125degF (11-516degC) Operating

-40-140degF (-40-60degC) Shipping

0-95 RH non-condensing Humidity

Installation Locating and Mounting the Controller For optimum performance controller should be mounted on an interior wall 4-5 feet above the floor away from heat sources sunlight windows air vents and air circulation obstructions 1 Complete rough-in wiring at each

location prior to controller installation 2 Hex screws at the bottom and top of the

controller backplate must be turned clockwise until clear of the controller cover to allow removal of the cover

3 Route wiring through the backplate 4 With the embossed UP toward the

ceiling fasten the 2x4 backplate directly to a vertical 2x4 inch wall handy box A 4x4 inch backplate attachment is also provided for horizontal 2x4 handy box and 4x4 handy box applications

5 Make the appropriate connections to the terminal block

6 Place controller cover over the backplate while being careful not to pinch or dislodge any wiring Turn the hex screws counterclockwise until they engage the cover and hold it in place

Figure 1 - Dimensions and Connections

To prevent mounting screw heads from touching the circuit board in the controller use only the mounting screws provided with the controller Using screws other than the type supplied may damage the controller

CAUTION

10

AAON Mini Controller Backplate Layout

Backplate W

iring Cutout

HPU | Std OAD

Analog Outputs

GND G2 Y1(Analog)

MSTP +B RH

Relay Outputs

-A 24 VAC (SC)

Inputs

OAT E2 | W3 | (Y1) SAT E | W2 GND OB | W1

Relay Outputs

IN2 (L) 24 VAC (SC)

24 VAC - C Y2 ~ R G

Figure 2 - Backplate Terminal Locations

+B = BACnet network terminal BACnet MSTP EIA-485 Network

-A = BACnet network terminal

Space Temp (Internal) = IN1 Space Temperature

Inputs

IN2 = L Configurable Input bull Suction Pressure - 0-10 VDC bull Outside Air Humidity - 0-10 VDC bull CO2 - 0-10 VDC bull Remote Space Temperature - 10k Type 3

Thermistor bull Fan Status - 10k Type 3 Thermistor SAT = IN3 Supply Air Temperature - 10k Type 3 Thermistor OAT = IN4 Outside Air Temperature - 10k Type 3 Thermistor Space RH (Internal) = IN5 Space Relative Humidity GND = Ground

- C = COM E Common 24 VAC

~ R = 24 VAC Phase

OAD = OUT9 EC1 Economizer Output - 0-10 10-0 2-10 or 10-2 VDC (0-100)

Analog Outputs

GND = Ground G2 = OUT8 S1 Variable Speed Supply Fan Output - 0-10 VDC (0-100) Y1 (Analog) = OUT7 Variable Capacity Compressor Output - 1-5 VDC (10-100)

RH = RLY6 Dehumidification Relay Outputs

24 VAC = SC Common E2 | W3 | Y1 (Relay) = RLY5 Emer Heat 2Heat 3Compressor 1 E | W2 = RLY4 Emer Heat 1Heat 2 OB | W1 = RLY3 Reversing ValveHeat 1 24 VAC = SC Common Y2 = RLY2 Compressor 2 G = RLY1 Supply Fan

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f0075007200200075006e00650020007100750061006c0069007400e90020006400270069006d007000720065007300730069006f006e00200070007200e9007000720065007300730065002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt13 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI ltFEFF0049007a006d0061006e0074006f006a00690065007400200161006f00730020006900650073007400610074012b006a0075006d00750073002c0020006c0061006900200076006500690064006f00740075002000410064006f00620065002000500044004600200064006f006b0075006d0065006e007400750073002c0020006b006100730020006900720020012b00700061016100690020007000690065006d01130072006f00740069002000610075006700730074006100730020006b00760061006c0069007401010074006500730020007000690072006d007300690065007300700069006501610061006e006100730020006400720075006b00610069002e00200049007a0076006500690064006f006a006900650074002000500044004600200064006f006b0075006d0065006e007400750073002c0020006b006f002000760061007200200061007400760113007200740020006100720020004100630072006f00620061007400200075006e002000410064006f00620065002000520065006100640065007200200035002e0030002c0020006b0101002000610072012b00200074006f0020006a00610075006e0101006b0101006d002000760065007200730069006a0101006d002egt13 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM ltFEFF005500740069006c0069007a00610163006900200061006300650073007400650020007300650074010300720069002000700065006e007400720075002000610020006300720065006100200064006f00630075006d0065006e00740065002000410064006f006200650020005000440046002000610064006500630076006100740065002000700065006e0074007200750020007400690070010300720069007200650061002000700072006500700072006500730073002000640065002000630061006c006900740061007400650020007300750070006500720069006f006100720103002e002000200044006f00630075006d0065006e00740065006c00650020005000440046002000630072006500610074006500200070006f00740020006600690020006400650073006300680069007300650020006300750020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e00300020015f00690020007600650072007300690075006e0069006c006500200075006c0074006500720069006f006100720065002egt13 RUS ltFEFF04180441043f043e043b044c04370443043904420435002004340430043d043d044b04350020043d0430044104420440043e0439043a043800200434043b044f00200441043e043704340430043d0438044f00200434043e043a0443043c0435043d0442043e0432002000410064006f006200650020005000440046002c0020043c0430043a04410438043c0430043b044c043d043e0020043f043e04340445043e0434044f04490438044500200434043b044f00200432044b0441043e043a043e043a0430044704350441044204320435043d043d043e0433043e00200434043e043f0435044704300442043d043e0433043e00200432044b0432043e04340430002e002000200421043e043704340430043d043d044b04350020005000440046002d0434043e043a0443043c0435043d0442044b0020043c043e0436043d043e0020043e0442043a0440044b043204300442044c002004410020043f043e043c043e0449044c044e0020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200431043e043b043504350020043f043e04370434043d043804450020043204350440044104380439002egt13 SKY 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 SLV 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 SUO 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 SVE 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 TUR ltFEFF005900fc006b00730065006b0020006b0061006c006900740065006c0069002000f6006e002000790061007a006401310072006d00610020006200610073006b013100730131006e006100200065006e0020006900790069002000750079006100620069006c006500630065006b002000410064006f006200650020005000440046002000620065006c00670065006c0065007200690020006f006c0075015f007400750072006d0061006b0020006900e70069006e00200062007500200061007900610072006c0061007201310020006b0075006c006c0061006e0131006e002e00200020004f006c0075015f0074007500720075006c0061006e0020005000440046002000620065006c00670065006c0065007200690020004100630072006f006200610074002000760065002000410064006f00620065002000520065006100640065007200200035002e003000200076006500200073006f006e0072006100730131006e00640061006b00690020007300fc007200fc006d006c00650072006c00650020006100e70131006c006100620069006c00690072002egt13 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 3: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

4

Index of Tables and Figures

Tables Table 1 - Control Wiring 11Table 2 - UTC Offset 19Table 3 - Default Access Levels 22Table 4 - Analog Values 40Table 5 - Analog Values Continued 41Table 6 - Relay Values 41Table 7 - Multi-State Values 42Table 8 - Analog Inputs 42Table 9 - Analog Outputs 42Table 10 - Relay Outputs 42

Figures Figure 1 - Dimensions and Connections 9Figure 2 - Backplate Terminal Locations 10Figure 3 - MSTP Network End-of-Line Terminology 11Figure 4 - EOL and Pull-Up Switch Resistor Positions on Reverse Side of Controller 12Figure 5 - Switched Common and Relays 12Figure 6 - AAON Mini Controller 13Figure 7 - Home Screen with Flashing Service Message 15

5

Safety

Attention should be paid to the following statements NOTE - Notes are intended to clarify the unit installation operation and maintenance

CAUTION - Caution statements are given to prevent actions that may result in equipment damage property damage or personal injury

WARNING - Warning statements are given to prevent actions that could result in equipment damage property damage personal injury or death

DANGER - Danger statements are given to prevent actions that will result in equipment damage property damage severe personal injury or death

ELECTRIC SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation serious injury death or property damage Improper servicing of HVAC equipment could result in dangerous operation serious injury death or property damage Before servicing disconnect all

electrical power to the equipment More than one disconnect may be provided

When servicing controls label all wires prior to disconnecting Reconnect wires correctly

Verify proper operation after servicing Secure all doors with key-lock or nut and bolt

WARNING Electric shock hazard Before servicing disconnect all electrical power to the equipment including remote disconnects to avoid shock hazard or injury from rotating parts Follow proper Lockout-Tagout procedures

WARNING

GROUNDING REQUIRED All field installed wiring must be completed by qualified personnel Field installed wiring must comply with NECCEC local and state electrical code requirements Failure to follow code requirements could result in serious injury or death Provide proper unit ground in accordance with these code requirements

WARNING

6

1 The controller is for indoor use only See

General Information section for more information

2 READ THE ENTIRE USERrsquoS

MANUAL OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL

3 Keep this manual and all literature

safeguarded near the equipment

During installation testing servicing and troubleshooting of the equipment it may be necessary to work with live electrical components Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks Standard NFPA-70E an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn should be followed

WARNING

7

AAONreg Mini Controller Features and Options LeadSingle Variable Capacity Scroll Compressor Control Constant Volume Control Single Zone VAV Control Air Conditioner or Heat Pump Weekday Weekend Entire Week or Daily Scheduling 12 Day Holiday Scheduling Alarms and Trend Logging Push Button Override 2 Compressor Stages Sensible Controlled Fully Modulating Economizer BACnet MSTP EIA-485 Network Connection Modulating GasSCR Electric Heat With additional controls components

1 2 or 3 Stages of Gas Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 2 or 3 Stages of Electric Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 and 2 Stages of Emergency Heat Second stage available only with some unit configurations See relay output descriptions

for details Options Available that use the Configurable Controller Input Space Humidity Control R80580 Model of Mini Controller Only

Enthalpy Controlled Fully Modulating Economizer CO2 Economizer Override Remote Averaging Space Temperature Sensor Remote Space Temperature Sensor Control Fan Status

8

General Information The AAON Mini Controller has been designed for simple single zone system control Codes and Ordinances HVAC system should be sized in accordance with the American Society of Heating Refrigeration and Air Conditioning Engineers Handbook Installation of equipment must conform to the ICC standards of the International Mechanical Code the International Building Code Installation of Air Conditioning and Ventilating Systems Standard NFPA 90A and local building plumbing and waste water codes All appliances must be electrically grounded in accordance with local codes or in the absence of local codes the current National Electric Code ANSINFPA 70 or the current Canadian Electrical Code CSA C221 Receiving Unit When received the controller should be checked for damage that might have occurred in transit Controller should also be checked to ensure the correct model has been received to match the job requirements AAON Mini Controller R80570 - Space Temperature Control R80580 - Space Temperature and Humidity Control

Specifications Supply Voltage24 VAC (+15-10) Class-2

13 VA Supply Power

Wire clamp type terminal blocks 14-22 AWG copper 4 pin EIA-485

Connections

OutputsAnalog outputs produce 0-10 VDC 20 mA maximum

Binary outputs (NO SPST Form A) carry 1 A maximum per relay or a total of 15 A per bank of 3 relays (relays 1-3 4-6) 24 VACVDC

10k Type 3 Thermistor Inputs

64 x 128 pixel dot matrix LCD Display

White flame retardant plastic Case Material

5551 x 4192 x 1125 inches (H x W x D) Dimensions

141 x 106 x 286 mm

048 lbs 218 g Weight

UL 916 Energy Management Equipment Approvals

FCC Class B Part 15 Subpart B

10k Type 2 Thermistor (Temperature only model)

TemperatureHumidity Sensors

CMOS (Temperature and Humidity model) Temperature Readings

+-09degF (+-05degC) from 40-104degF Accuracy

+- 01degF (+-02degC) Resolution

36-120degF (22-488degC) Operating Range

5-30 seconds Response Time

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this manual should be kept with the unit

WARNING

9

Humidity Readings

0-100 RH Range

+-2 RH (10-90 RH) Accuracy77degF (25degC)

Less than 4 seconds Response Time

Environmental Limits

34-125degF (11-516degC) Operating

-40-140degF (-40-60degC) Shipping

0-95 RH non-condensing Humidity

Installation Locating and Mounting the Controller For optimum performance controller should be mounted on an interior wall 4-5 feet above the floor away from heat sources sunlight windows air vents and air circulation obstructions 1 Complete rough-in wiring at each

location prior to controller installation 2 Hex screws at the bottom and top of the

controller backplate must be turned clockwise until clear of the controller cover to allow removal of the cover

3 Route wiring through the backplate 4 With the embossed UP toward the

ceiling fasten the 2x4 backplate directly to a vertical 2x4 inch wall handy box A 4x4 inch backplate attachment is also provided for horizontal 2x4 handy box and 4x4 handy box applications

5 Make the appropriate connections to the terminal block

6 Place controller cover over the backplate while being careful not to pinch or dislodge any wiring Turn the hex screws counterclockwise until they engage the cover and hold it in place

Figure 1 - Dimensions and Connections

To prevent mounting screw heads from touching the circuit board in the controller use only the mounting screws provided with the controller Using screws other than the type supplied may damage the controller

CAUTION

10

AAON Mini Controller Backplate Layout

Backplate W

iring Cutout

HPU | Std OAD

Analog Outputs

GND G2 Y1(Analog)

MSTP +B RH

Relay Outputs

-A 24 VAC (SC)

Inputs

OAT E2 | W3 | (Y1) SAT E | W2 GND OB | W1

Relay Outputs

IN2 (L) 24 VAC (SC)

24 VAC - C Y2 ~ R G

Figure 2 - Backplate Terminal Locations

+B = BACnet network terminal BACnet MSTP EIA-485 Network

-A = BACnet network terminal

Space Temp (Internal) = IN1 Space Temperature

Inputs

IN2 = L Configurable Input bull Suction Pressure - 0-10 VDC bull Outside Air Humidity - 0-10 VDC bull CO2 - 0-10 VDC bull Remote Space Temperature - 10k Type 3

Thermistor bull Fan Status - 10k Type 3 Thermistor SAT = IN3 Supply Air Temperature - 10k Type 3 Thermistor OAT = IN4 Outside Air Temperature - 10k Type 3 Thermistor Space RH (Internal) = IN5 Space Relative Humidity GND = Ground

- C = COM E Common 24 VAC

~ R = 24 VAC Phase

OAD = OUT9 EC1 Economizer Output - 0-10 10-0 2-10 or 10-2 VDC (0-100)

Analog Outputs

GND = Ground G2 = OUT8 S1 Variable Speed Supply Fan Output - 0-10 VDC (0-100) Y1 (Analog) = OUT7 Variable Capacity Compressor Output - 1-5 VDC (10-100)

RH = RLY6 Dehumidification Relay Outputs

24 VAC = SC Common E2 | W3 | Y1 (Relay) = RLY5 Emer Heat 2Heat 3Compressor 1 E | W2 = RLY4 Emer Heat 1Heat 2 OB | W1 = RLY3 Reversing ValveHeat 1 24 VAC = SC Common Y2 = RLY2 Compressor 2 G = RLY1 Supply Fan

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f00730020005000440046002000640065002000410064006f0062006500200061006400650063007500610064006f00730020007000610072006100200069006d0070007200650073006900f3006e0020007000720065002d0065006400690074006f007200690061006c00200064006500200061006c00740061002000630061006c0069006400610064002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt13 ETI 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f0075007200200075006e00650020007100750061006c0069007400e90020006400270069006d007000720065007300730069006f006e00200070007200e9007000720065007300730065002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt13 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL ltFEFF0055007300740061007700690065006e0069006100200064006f002000740077006f0072007a0065006e0069006100200064006f006b0075006d0065006e007400f300770020005000440046002000700072007a0065007a006e00610063007a006f006e00790063006800200064006f002000770079006400720075006b00f30077002000770020007700790073006f006b00690065006a0020006a0061006b006f015b00630069002e002000200044006f006b0075006d0065006e0074007900200050004400460020006d006f017c006e00610020006f007400770069006500720061010700200077002000700072006f006700720061006d006900650020004100630072006f00620061007400200069002000410064006f00620065002000520065006100640065007200200035002e0030002000690020006e006f00770073007a0079006d002egt13 PTB 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 RUM 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 RUS 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 SKY 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 SLV ltFEFF005400650020006e006100730074006100760069007400760065002000750070006f0072006100620069007400650020007a00610020007500730074007600610072006a0061006e006a006500200064006f006b0075006d0065006e0074006f0076002000410064006f006200650020005000440046002c0020006b006900200073006f0020006e0061006a007000720069006d00650072006e0065006a016100690020007a00610020006b0061006b006f0076006f00730074006e006f0020007400690073006b0061006e006a00650020007300200070007200690070007200610076006f0020006e00610020007400690073006b002e00200020005500730074007600610072006a0065006e006500200064006f006b0075006d0065006e0074006500200050004400460020006a00650020006d006f0067006f010d00650020006f0064007000720065007400690020007a0020004100630072006f00620061007400200069006e002000410064006f00620065002000520065006100640065007200200035002e003000200069006e0020006e006f00760065006a01610069006d002egt13 SUO 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 SVE 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 TUR ltFEFF005900fc006b00730065006b0020006b0061006c006900740065006c0069002000f6006e002000790061007a006401310072006d00610020006200610073006b013100730131006e006100200065006e0020006900790069002000750079006100620069006c006500630065006b002000410064006f006200650020005000440046002000620065006c00670065006c0065007200690020006f006c0075015f007400750072006d0061006b0020006900e70069006e00200062007500200061007900610072006c0061007201310020006b0075006c006c0061006e0131006e002e00200020004f006c0075015f0074007500720075006c0061006e0020005000440046002000620065006c00670065006c0065007200690020004100630072006f006200610074002000760065002000410064006f00620065002000520065006100640065007200200035002e003000200076006500200073006f006e0072006100730131006e00640061006b00690020007300fc007200fc006d006c00650072006c00650020006100e70131006c006100620069006c00690072002egt13 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 4: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

5

Safety

Attention should be paid to the following statements NOTE - Notes are intended to clarify the unit installation operation and maintenance

CAUTION - Caution statements are given to prevent actions that may result in equipment damage property damage or personal injury

WARNING - Warning statements are given to prevent actions that could result in equipment damage property damage personal injury or death

DANGER - Danger statements are given to prevent actions that will result in equipment damage property damage severe personal injury or death

ELECTRIC SHOCK FIRE OR EXPLOSION HAZARD Failure to follow safety warnings exactly could result in dangerous operation serious injury death or property damage Improper servicing of HVAC equipment could result in dangerous operation serious injury death or property damage Before servicing disconnect all

electrical power to the equipment More than one disconnect may be provided

When servicing controls label all wires prior to disconnecting Reconnect wires correctly

Verify proper operation after servicing Secure all doors with key-lock or nut and bolt

WARNING Electric shock hazard Before servicing disconnect all electrical power to the equipment including remote disconnects to avoid shock hazard or injury from rotating parts Follow proper Lockout-Tagout procedures

WARNING

GROUNDING REQUIRED All field installed wiring must be completed by qualified personnel Field installed wiring must comply with NECCEC local and state electrical code requirements Failure to follow code requirements could result in serious injury or death Provide proper unit ground in accordance with these code requirements

WARNING

6

1 The controller is for indoor use only See

General Information section for more information

2 READ THE ENTIRE USERrsquoS

MANUAL OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL

3 Keep this manual and all literature

safeguarded near the equipment

During installation testing servicing and troubleshooting of the equipment it may be necessary to work with live electrical components Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks Standard NFPA-70E an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn should be followed

WARNING

7

AAONreg Mini Controller Features and Options LeadSingle Variable Capacity Scroll Compressor Control Constant Volume Control Single Zone VAV Control Air Conditioner or Heat Pump Weekday Weekend Entire Week or Daily Scheduling 12 Day Holiday Scheduling Alarms and Trend Logging Push Button Override 2 Compressor Stages Sensible Controlled Fully Modulating Economizer BACnet MSTP EIA-485 Network Connection Modulating GasSCR Electric Heat With additional controls components

1 2 or 3 Stages of Gas Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 2 or 3 Stages of Electric Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 and 2 Stages of Emergency Heat Second stage available only with some unit configurations See relay output descriptions

for details Options Available that use the Configurable Controller Input Space Humidity Control R80580 Model of Mini Controller Only

Enthalpy Controlled Fully Modulating Economizer CO2 Economizer Override Remote Averaging Space Temperature Sensor Remote Space Temperature Sensor Control Fan Status

8

General Information The AAON Mini Controller has been designed for simple single zone system control Codes and Ordinances HVAC system should be sized in accordance with the American Society of Heating Refrigeration and Air Conditioning Engineers Handbook Installation of equipment must conform to the ICC standards of the International Mechanical Code the International Building Code Installation of Air Conditioning and Ventilating Systems Standard NFPA 90A and local building plumbing and waste water codes All appliances must be electrically grounded in accordance with local codes or in the absence of local codes the current National Electric Code ANSINFPA 70 or the current Canadian Electrical Code CSA C221 Receiving Unit When received the controller should be checked for damage that might have occurred in transit Controller should also be checked to ensure the correct model has been received to match the job requirements AAON Mini Controller R80570 - Space Temperature Control R80580 - Space Temperature and Humidity Control

Specifications Supply Voltage24 VAC (+15-10) Class-2

13 VA Supply Power

Wire clamp type terminal blocks 14-22 AWG copper 4 pin EIA-485

Connections

OutputsAnalog outputs produce 0-10 VDC 20 mA maximum

Binary outputs (NO SPST Form A) carry 1 A maximum per relay or a total of 15 A per bank of 3 relays (relays 1-3 4-6) 24 VACVDC

10k Type 3 Thermistor Inputs

64 x 128 pixel dot matrix LCD Display

White flame retardant plastic Case Material

5551 x 4192 x 1125 inches (H x W x D) Dimensions

141 x 106 x 286 mm

048 lbs 218 g Weight

UL 916 Energy Management Equipment Approvals

FCC Class B Part 15 Subpart B

10k Type 2 Thermistor (Temperature only model)

TemperatureHumidity Sensors

CMOS (Temperature and Humidity model) Temperature Readings

+-09degF (+-05degC) from 40-104degF Accuracy

+- 01degF (+-02degC) Resolution

36-120degF (22-488degC) Operating Range

5-30 seconds Response Time

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this manual should be kept with the unit

WARNING

9

Humidity Readings

0-100 RH Range

+-2 RH (10-90 RH) Accuracy77degF (25degC)

Less than 4 seconds Response Time

Environmental Limits

34-125degF (11-516degC) Operating

-40-140degF (-40-60degC) Shipping

0-95 RH non-condensing Humidity

Installation Locating and Mounting the Controller For optimum performance controller should be mounted on an interior wall 4-5 feet above the floor away from heat sources sunlight windows air vents and air circulation obstructions 1 Complete rough-in wiring at each

location prior to controller installation 2 Hex screws at the bottom and top of the

controller backplate must be turned clockwise until clear of the controller cover to allow removal of the cover

3 Route wiring through the backplate 4 With the embossed UP toward the

ceiling fasten the 2x4 backplate directly to a vertical 2x4 inch wall handy box A 4x4 inch backplate attachment is also provided for horizontal 2x4 handy box and 4x4 handy box applications

5 Make the appropriate connections to the terminal block

6 Place controller cover over the backplate while being careful not to pinch or dislodge any wiring Turn the hex screws counterclockwise until they engage the cover and hold it in place

Figure 1 - Dimensions and Connections

To prevent mounting screw heads from touching the circuit board in the controller use only the mounting screws provided with the controller Using screws other than the type supplied may damage the controller

CAUTION

10

AAON Mini Controller Backplate Layout

Backplate W

iring Cutout

HPU | Std OAD

Analog Outputs

GND G2 Y1(Analog)

MSTP +B RH

Relay Outputs

-A 24 VAC (SC)

Inputs

OAT E2 | W3 | (Y1) SAT E | W2 GND OB | W1

Relay Outputs

IN2 (L) 24 VAC (SC)

24 VAC - C Y2 ~ R G

Figure 2 - Backplate Terminal Locations

+B = BACnet network terminal BACnet MSTP EIA-485 Network

-A = BACnet network terminal

Space Temp (Internal) = IN1 Space Temperature

Inputs

IN2 = L Configurable Input bull Suction Pressure - 0-10 VDC bull Outside Air Humidity - 0-10 VDC bull CO2 - 0-10 VDC bull Remote Space Temperature - 10k Type 3

Thermistor bull Fan Status - 10k Type 3 Thermistor SAT = IN3 Supply Air Temperature - 10k Type 3 Thermistor OAT = IN4 Outside Air Temperature - 10k Type 3 Thermistor Space RH (Internal) = IN5 Space Relative Humidity GND = Ground

- C = COM E Common 24 VAC

~ R = 24 VAC Phase

OAD = OUT9 EC1 Economizer Output - 0-10 10-0 2-10 or 10-2 VDC (0-100)

Analog Outputs

GND = Ground G2 = OUT8 S1 Variable Speed Supply Fan Output - 0-10 VDC (0-100) Y1 (Analog) = OUT7 Variable Capacity Compressor Output - 1-5 VDC (10-100)

RH = RLY6 Dehumidification Relay Outputs

24 VAC = SC Common E2 | W3 | Y1 (Relay) = RLY5 Emer Heat 2Heat 3Compressor 1 E | W2 = RLY4 Emer Heat 1Heat 2 OB | W1 = RLY3 Reversing ValveHeat 1 24 VAC = SC Common Y2 = RLY2 Compressor 2 G = RLY1 Supply Fan

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 5: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

6

1 The controller is for indoor use only See

General Information section for more information

2 READ THE ENTIRE USERrsquoS

MANUAL OTHER IMPORTANT SAFETY PRECAUTIONS ARE PROVIDED THROUGHOUT THIS MANUAL

3 Keep this manual and all literature

safeguarded near the equipment

During installation testing servicing and troubleshooting of the equipment it may be necessary to work with live electrical components Only a qualified licensed electrician or individual properly trained in handling live electrical components shall perform these tasks Standard NFPA-70E an OSHA regulation requiring an Arc Flash Boundary to be field established and marked for identification of where appropriate Personal Protective Equipment (PPE) be worn should be followed

WARNING

7

AAONreg Mini Controller Features and Options LeadSingle Variable Capacity Scroll Compressor Control Constant Volume Control Single Zone VAV Control Air Conditioner or Heat Pump Weekday Weekend Entire Week or Daily Scheduling 12 Day Holiday Scheduling Alarms and Trend Logging Push Button Override 2 Compressor Stages Sensible Controlled Fully Modulating Economizer BACnet MSTP EIA-485 Network Connection Modulating GasSCR Electric Heat With additional controls components

1 2 or 3 Stages of Gas Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 2 or 3 Stages of Electric Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 and 2 Stages of Emergency Heat Second stage available only with some unit configurations See relay output descriptions

for details Options Available that use the Configurable Controller Input Space Humidity Control R80580 Model of Mini Controller Only

Enthalpy Controlled Fully Modulating Economizer CO2 Economizer Override Remote Averaging Space Temperature Sensor Remote Space Temperature Sensor Control Fan Status

8

General Information The AAON Mini Controller has been designed for simple single zone system control Codes and Ordinances HVAC system should be sized in accordance with the American Society of Heating Refrigeration and Air Conditioning Engineers Handbook Installation of equipment must conform to the ICC standards of the International Mechanical Code the International Building Code Installation of Air Conditioning and Ventilating Systems Standard NFPA 90A and local building plumbing and waste water codes All appliances must be electrically grounded in accordance with local codes or in the absence of local codes the current National Electric Code ANSINFPA 70 or the current Canadian Electrical Code CSA C221 Receiving Unit When received the controller should be checked for damage that might have occurred in transit Controller should also be checked to ensure the correct model has been received to match the job requirements AAON Mini Controller R80570 - Space Temperature Control R80580 - Space Temperature and Humidity Control

Specifications Supply Voltage24 VAC (+15-10) Class-2

13 VA Supply Power

Wire clamp type terminal blocks 14-22 AWG copper 4 pin EIA-485

Connections

OutputsAnalog outputs produce 0-10 VDC 20 mA maximum

Binary outputs (NO SPST Form A) carry 1 A maximum per relay or a total of 15 A per bank of 3 relays (relays 1-3 4-6) 24 VACVDC

10k Type 3 Thermistor Inputs

64 x 128 pixel dot matrix LCD Display

White flame retardant plastic Case Material

5551 x 4192 x 1125 inches (H x W x D) Dimensions

141 x 106 x 286 mm

048 lbs 218 g Weight

UL 916 Energy Management Equipment Approvals

FCC Class B Part 15 Subpart B

10k Type 2 Thermistor (Temperature only model)

TemperatureHumidity Sensors

CMOS (Temperature and Humidity model) Temperature Readings

+-09degF (+-05degC) from 40-104degF Accuracy

+- 01degF (+-02degC) Resolution

36-120degF (22-488degC) Operating Range

5-30 seconds Response Time

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this manual should be kept with the unit

WARNING

9

Humidity Readings

0-100 RH Range

+-2 RH (10-90 RH) Accuracy77degF (25degC)

Less than 4 seconds Response Time

Environmental Limits

34-125degF (11-516degC) Operating

-40-140degF (-40-60degC) Shipping

0-95 RH non-condensing Humidity

Installation Locating and Mounting the Controller For optimum performance controller should be mounted on an interior wall 4-5 feet above the floor away from heat sources sunlight windows air vents and air circulation obstructions 1 Complete rough-in wiring at each

location prior to controller installation 2 Hex screws at the bottom and top of the

controller backplate must be turned clockwise until clear of the controller cover to allow removal of the cover

3 Route wiring through the backplate 4 With the embossed UP toward the

ceiling fasten the 2x4 backplate directly to a vertical 2x4 inch wall handy box A 4x4 inch backplate attachment is also provided for horizontal 2x4 handy box and 4x4 handy box applications

5 Make the appropriate connections to the terminal block

6 Place controller cover over the backplate while being careful not to pinch or dislodge any wiring Turn the hex screws counterclockwise until they engage the cover and hold it in place

Figure 1 - Dimensions and Connections

To prevent mounting screw heads from touching the circuit board in the controller use only the mounting screws provided with the controller Using screws other than the type supplied may damage the controller

CAUTION

10

AAON Mini Controller Backplate Layout

Backplate W

iring Cutout

HPU | Std OAD

Analog Outputs

GND G2 Y1(Analog)

MSTP +B RH

Relay Outputs

-A 24 VAC (SC)

Inputs

OAT E2 | W3 | (Y1) SAT E | W2 GND OB | W1

Relay Outputs

IN2 (L) 24 VAC (SC)

24 VAC - C Y2 ~ R G

Figure 2 - Backplate Terminal Locations

+B = BACnet network terminal BACnet MSTP EIA-485 Network

-A = BACnet network terminal

Space Temp (Internal) = IN1 Space Temperature

Inputs

IN2 = L Configurable Input bull Suction Pressure - 0-10 VDC bull Outside Air Humidity - 0-10 VDC bull CO2 - 0-10 VDC bull Remote Space Temperature - 10k Type 3

Thermistor bull Fan Status - 10k Type 3 Thermistor SAT = IN3 Supply Air Temperature - 10k Type 3 Thermistor OAT = IN4 Outside Air Temperature - 10k Type 3 Thermistor Space RH (Internal) = IN5 Space Relative Humidity GND = Ground

- C = COM E Common 24 VAC

~ R = 24 VAC Phase

OAD = OUT9 EC1 Economizer Output - 0-10 10-0 2-10 or 10-2 VDC (0-100)

Analog Outputs

GND = Ground G2 = OUT8 S1 Variable Speed Supply Fan Output - 0-10 VDC (0-100) Y1 (Analog) = OUT7 Variable Capacity Compressor Output - 1-5 VDC (10-100)

RH = RLY6 Dehumidification Relay Outputs

24 VAC = SC Common E2 | W3 | Y1 (Relay) = RLY5 Emer Heat 2Heat 3Compressor 1 E | W2 = RLY4 Emer Heat 1Heat 2 OB | W1 = RLY3 Reversing ValveHeat 1 24 VAC = SC Common Y2 = RLY2 Compressor 2 G = RLY1 Supply Fan

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 6: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

7

AAONreg Mini Controller Features and Options LeadSingle Variable Capacity Scroll Compressor Control Constant Volume Control Single Zone VAV Control Air Conditioner or Heat Pump Weekday Weekend Entire Week or Daily Scheduling 12 Day Holiday Scheduling Alarms and Trend Logging Push Button Override 2 Compressor Stages Sensible Controlled Fully Modulating Economizer BACnet MSTP EIA-485 Network Connection Modulating GasSCR Electric Heat With additional controls components

1 2 or 3 Stages of Gas Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 2 or 3 Stages of Electric Heat Third stage available only with some unit configurations See relay output descriptions

for details 1 and 2 Stages of Emergency Heat Second stage available only with some unit configurations See relay output descriptions

for details Options Available that use the Configurable Controller Input Space Humidity Control R80580 Model of Mini Controller Only

Enthalpy Controlled Fully Modulating Economizer CO2 Economizer Override Remote Averaging Space Temperature Sensor Remote Space Temperature Sensor Control Fan Status

8

General Information The AAON Mini Controller has been designed for simple single zone system control Codes and Ordinances HVAC system should be sized in accordance with the American Society of Heating Refrigeration and Air Conditioning Engineers Handbook Installation of equipment must conform to the ICC standards of the International Mechanical Code the International Building Code Installation of Air Conditioning and Ventilating Systems Standard NFPA 90A and local building plumbing and waste water codes All appliances must be electrically grounded in accordance with local codes or in the absence of local codes the current National Electric Code ANSINFPA 70 or the current Canadian Electrical Code CSA C221 Receiving Unit When received the controller should be checked for damage that might have occurred in transit Controller should also be checked to ensure the correct model has been received to match the job requirements AAON Mini Controller R80570 - Space Temperature Control R80580 - Space Temperature and Humidity Control

Specifications Supply Voltage24 VAC (+15-10) Class-2

13 VA Supply Power

Wire clamp type terminal blocks 14-22 AWG copper 4 pin EIA-485

Connections

OutputsAnalog outputs produce 0-10 VDC 20 mA maximum

Binary outputs (NO SPST Form A) carry 1 A maximum per relay or a total of 15 A per bank of 3 relays (relays 1-3 4-6) 24 VACVDC

10k Type 3 Thermistor Inputs

64 x 128 pixel dot matrix LCD Display

White flame retardant plastic Case Material

5551 x 4192 x 1125 inches (H x W x D) Dimensions

141 x 106 x 286 mm

048 lbs 218 g Weight

UL 916 Energy Management Equipment Approvals

FCC Class B Part 15 Subpart B

10k Type 2 Thermistor (Temperature only model)

TemperatureHumidity Sensors

CMOS (Temperature and Humidity model) Temperature Readings

+-09degF (+-05degC) from 40-104degF Accuracy

+- 01degF (+-02degC) Resolution

36-120degF (22-488degC) Operating Range

5-30 seconds Response Time

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this manual should be kept with the unit

WARNING

9

Humidity Readings

0-100 RH Range

+-2 RH (10-90 RH) Accuracy77degF (25degC)

Less than 4 seconds Response Time

Environmental Limits

34-125degF (11-516degC) Operating

-40-140degF (-40-60degC) Shipping

0-95 RH non-condensing Humidity

Installation Locating and Mounting the Controller For optimum performance controller should be mounted on an interior wall 4-5 feet above the floor away from heat sources sunlight windows air vents and air circulation obstructions 1 Complete rough-in wiring at each

location prior to controller installation 2 Hex screws at the bottom and top of the

controller backplate must be turned clockwise until clear of the controller cover to allow removal of the cover

3 Route wiring through the backplate 4 With the embossed UP toward the

ceiling fasten the 2x4 backplate directly to a vertical 2x4 inch wall handy box A 4x4 inch backplate attachment is also provided for horizontal 2x4 handy box and 4x4 handy box applications

5 Make the appropriate connections to the terminal block

6 Place controller cover over the backplate while being careful not to pinch or dislodge any wiring Turn the hex screws counterclockwise until they engage the cover and hold it in place

Figure 1 - Dimensions and Connections

To prevent mounting screw heads from touching the circuit board in the controller use only the mounting screws provided with the controller Using screws other than the type supplied may damage the controller

CAUTION

10

AAON Mini Controller Backplate Layout

Backplate W

iring Cutout

HPU | Std OAD

Analog Outputs

GND G2 Y1(Analog)

MSTP +B RH

Relay Outputs

-A 24 VAC (SC)

Inputs

OAT E2 | W3 | (Y1) SAT E | W2 GND OB | W1

Relay Outputs

IN2 (L) 24 VAC (SC)

24 VAC - C Y2 ~ R G

Figure 2 - Backplate Terminal Locations

+B = BACnet network terminal BACnet MSTP EIA-485 Network

-A = BACnet network terminal

Space Temp (Internal) = IN1 Space Temperature

Inputs

IN2 = L Configurable Input bull Suction Pressure - 0-10 VDC bull Outside Air Humidity - 0-10 VDC bull CO2 - 0-10 VDC bull Remote Space Temperature - 10k Type 3

Thermistor bull Fan Status - 10k Type 3 Thermistor SAT = IN3 Supply Air Temperature - 10k Type 3 Thermistor OAT = IN4 Outside Air Temperature - 10k Type 3 Thermistor Space RH (Internal) = IN5 Space Relative Humidity GND = Ground

- C = COM E Common 24 VAC

~ R = 24 VAC Phase

OAD = OUT9 EC1 Economizer Output - 0-10 10-0 2-10 or 10-2 VDC (0-100)

Analog Outputs

GND = Ground G2 = OUT8 S1 Variable Speed Supply Fan Output - 0-10 VDC (0-100) Y1 (Analog) = OUT7 Variable Capacity Compressor Output - 1-5 VDC (10-100)

RH = RLY6 Dehumidification Relay Outputs

24 VAC = SC Common E2 | W3 | Y1 (Relay) = RLY5 Emer Heat 2Heat 3Compressor 1 E | W2 = RLY4 Emer Heat 1Heat 2 OB | W1 = RLY3 Reversing ValveHeat 1 24 VAC = SC Common Y2 = RLY2 Compressor 2 G = RLY1 Supply Fan

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f0075007200200075006e00650020007100750061006c0069007400e90020006400270069006d007000720065007300730069006f006e00200070007200e9007000720065007300730065002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt13 GRE ltFEFF03a703c103b703c303b903bc03bf03c003bf03b903ae03c303c403b5002003b103c503c403ad03c2002003c403b903c2002003c103c503b803bc03af03c303b503b903c2002003b303b903b1002003bd03b1002003b403b703bc03b903bf03c503c103b303ae03c303b503c403b5002003ad03b303b303c103b103c603b1002000410064006f006200650020005000440046002003c003bf03c5002003b503af03bd03b103b9002003ba03b103c42019002003b503be03bf03c703ae03bd002003ba03b103c403ac03bb03bb03b703bb03b1002003b303b903b1002003c003c103bf002d03b503ba03c403c503c003c903c403b903ba03ad03c2002003b503c103b303b103c303af03b503c2002003c503c803b703bb03ae03c2002003c003bf03b903cc03c403b703c403b103c2002e0020002003a403b10020005000440046002003ad03b303b303c103b103c603b1002003c003bf03c5002003ad03c703b503c403b5002003b403b703bc03b903bf03c503c103b303ae03c303b503b9002003bc03c003bf03c103bf03cd03bd002003bd03b1002003b103bd03bf03b903c703c403bf03cd03bd002003bc03b5002003c403bf0020004100630072006f006200610074002c002003c403bf002000410064006f00620065002000520065006100640065007200200035002e0030002003ba03b103b9002003bc03b503c403b103b303b503bd03ad03c303c403b503c103b503c2002003b503ba03b403cc03c303b503b903c2002egt13 HEB ltFEFF05D405E905EA05DE05E905D5002005D105D405D205D305E805D505EA002005D005DC05D4002005DB05D305D9002005DC05D905E605D505E8002005DE05E105DE05DB05D9002000410064006F006200650020005000440046002005D405DE05D505EA05D005DE05D905DD002005DC05D405D305E405E105EA002005E705D305DD002D05D305E405D505E1002005D005D905DB05D505EA05D905EA002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002E05D005DE05D905DD002005DC002D005000440046002F0058002D0033002C002005E205D905D905E005D5002005D105DE05D305E805D905DA002005DC05DE05E905EA05DE05E9002005E905DC0020004100630072006F006200610074002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002Egt13 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN ltFEFF004b0069007600e1006c00f30020006d0069006e0151007300e9006701710020006e0079006f006d00640061006900200065006c0151006b00e90073007a00ed007401510020006e0079006f006d00740061007400e100730068006f007a0020006c006500670069006e006b00e1006200620020006d0065006700660065006c0065006c0151002000410064006f00620065002000500044004600200064006f006b0075006d0065006e00740075006d006f006b0061007400200065007a0065006b006b0065006c0020006100200062006500e1006c006c00ed007400e10073006f006b006b0061006c0020006b00e90073007a00ed0074006800650074002e0020002000410020006c00e90074007200650068006f007a006f00740074002000500044004600200064006f006b0075006d0065006e00740075006d006f006b00200061007a0020004100630072006f006200610074002000e9007300200061007a002000410064006f00620065002000520065006100640065007200200035002e0030002c0020007600610067007900200061007a002000610074007400f3006c0020006b00e9007301510062006200690020007600650072007a006900f3006b006b0061006c0020006e00790069007400680061007400f3006b0020006d00650067002egt13 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 7: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

8

General Information The AAON Mini Controller has been designed for simple single zone system control Codes and Ordinances HVAC system should be sized in accordance with the American Society of Heating Refrigeration and Air Conditioning Engineers Handbook Installation of equipment must conform to the ICC standards of the International Mechanical Code the International Building Code Installation of Air Conditioning and Ventilating Systems Standard NFPA 90A and local building plumbing and waste water codes All appliances must be electrically grounded in accordance with local codes or in the absence of local codes the current National Electric Code ANSINFPA 70 or the current Canadian Electrical Code CSA C221 Receiving Unit When received the controller should be checked for damage that might have occurred in transit Controller should also be checked to ensure the correct model has been received to match the job requirements AAON Mini Controller R80570 - Space Temperature Control R80580 - Space Temperature and Humidity Control

Specifications Supply Voltage24 VAC (+15-10) Class-2

13 VA Supply Power

Wire clamp type terminal blocks 14-22 AWG copper 4 pin EIA-485

Connections

OutputsAnalog outputs produce 0-10 VDC 20 mA maximum

Binary outputs (NO SPST Form A) carry 1 A maximum per relay or a total of 15 A per bank of 3 relays (relays 1-3 4-6) 24 VACVDC

10k Type 3 Thermistor Inputs

64 x 128 pixel dot matrix LCD Display

White flame retardant plastic Case Material

5551 x 4192 x 1125 inches (H x W x D) Dimensions

141 x 106 x 286 mm

048 lbs 218 g Weight

UL 916 Energy Management Equipment Approvals

FCC Class B Part 15 Subpart B

10k Type 2 Thermistor (Temperature only model)

TemperatureHumidity Sensors

CMOS (Temperature and Humidity model) Temperature Readings

+-09degF (+-05degC) from 40-104degF Accuracy

+- 01degF (+-02degC) Resolution

36-120degF (22-488degC) Operating Range

5-30 seconds Response Time

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this manual should be kept with the unit

WARNING

9

Humidity Readings

0-100 RH Range

+-2 RH (10-90 RH) Accuracy77degF (25degC)

Less than 4 seconds Response Time

Environmental Limits

34-125degF (11-516degC) Operating

-40-140degF (-40-60degC) Shipping

0-95 RH non-condensing Humidity

Installation Locating and Mounting the Controller For optimum performance controller should be mounted on an interior wall 4-5 feet above the floor away from heat sources sunlight windows air vents and air circulation obstructions 1 Complete rough-in wiring at each

location prior to controller installation 2 Hex screws at the bottom and top of the

controller backplate must be turned clockwise until clear of the controller cover to allow removal of the cover

3 Route wiring through the backplate 4 With the embossed UP toward the

ceiling fasten the 2x4 backplate directly to a vertical 2x4 inch wall handy box A 4x4 inch backplate attachment is also provided for horizontal 2x4 handy box and 4x4 handy box applications

5 Make the appropriate connections to the terminal block

6 Place controller cover over the backplate while being careful not to pinch or dislodge any wiring Turn the hex screws counterclockwise until they engage the cover and hold it in place

Figure 1 - Dimensions and Connections

To prevent mounting screw heads from touching the circuit board in the controller use only the mounting screws provided with the controller Using screws other than the type supplied may damage the controller

CAUTION

10

AAON Mini Controller Backplate Layout

Backplate W

iring Cutout

HPU | Std OAD

Analog Outputs

GND G2 Y1(Analog)

MSTP +B RH

Relay Outputs

-A 24 VAC (SC)

Inputs

OAT E2 | W3 | (Y1) SAT E | W2 GND OB | W1

Relay Outputs

IN2 (L) 24 VAC (SC)

24 VAC - C Y2 ~ R G

Figure 2 - Backplate Terminal Locations

+B = BACnet network terminal BACnet MSTP EIA-485 Network

-A = BACnet network terminal

Space Temp (Internal) = IN1 Space Temperature

Inputs

IN2 = L Configurable Input bull Suction Pressure - 0-10 VDC bull Outside Air Humidity - 0-10 VDC bull CO2 - 0-10 VDC bull Remote Space Temperature - 10k Type 3

Thermistor bull Fan Status - 10k Type 3 Thermistor SAT = IN3 Supply Air Temperature - 10k Type 3 Thermistor OAT = IN4 Outside Air Temperature - 10k Type 3 Thermistor Space RH (Internal) = IN5 Space Relative Humidity GND = Ground

- C = COM E Common 24 VAC

~ R = 24 VAC Phase

OAD = OUT9 EC1 Economizer Output - 0-10 10-0 2-10 or 10-2 VDC (0-100)

Analog Outputs

GND = Ground G2 = OUT8 S1 Variable Speed Supply Fan Output - 0-10 VDC (0-100) Y1 (Analog) = OUT7 Variable Capacity Compressor Output - 1-5 VDC (10-100)

RH = RLY6 Dehumidification Relay Outputs

24 VAC = SC Common E2 | W3 | Y1 (Relay) = RLY5 Emer Heat 2Heat 3Compressor 1 E | W2 = RLY4 Emer Heat 1Heat 2 OB | W1 = RLY3 Reversing ValveHeat 1 24 VAC = SC Common Y2 = RLY2 Compressor 2 G = RLY1 Supply Fan

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE ltFEFF03a703c103b703c303b903bc03bf03c003bf03b903ae03c303c403b5002003b103c503c403ad03c2002003c403b903c2002003c103c503b803bc03af03c303b503b903c2002003b303b903b1002003bd03b1002003b403b703bc03b903bf03c503c103b303ae03c303b503c403b5002003ad03b303b303c103b103c603b1002000410064006f006200650020005000440046002003c003bf03c5002003b503af03bd03b103b9002003ba03b103c42019002003b503be03bf03c703ae03bd002003ba03b103c403ac03bb03bb03b703bb03b1002003b303b903b1002003c003c103bf002d03b503ba03c403c503c003c903c403b903ba03ad03c2002003b503c103b303b103c303af03b503c2002003c503c803b703bb03ae03c2002003c003bf03b903cc03c403b703c403b103c2002e0020002003a403b10020005000440046002003ad03b303b303c103b103c603b1002003c003bf03c5002003ad03c703b503c403b5002003b403b703bc03b903bf03c503c103b303ae03c303b503b9002003bc03c003bf03c103bf03cd03bd002003bd03b1002003b103bd03bf03b903c703c403bf03cd03bd002003bc03b5002003c403bf0020004100630072006f006200610074002c002003c403bf002000410064006f00620065002000520065006100640065007200200035002e0030002003ba03b103b9002003bc03b503c403b103b303b503bd03ad03c303c403b503c103b503c2002003b503ba03b403cc03c303b503b903c2002egt13 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL ltFEFF0055007300740061007700690065006e0069006100200064006f002000740077006f0072007a0065006e0069006100200064006f006b0075006d0065006e007400f300770020005000440046002000700072007a0065007a006e00610063007a006f006e00790063006800200064006f002000770079006400720075006b00f30077002000770020007700790073006f006b00690065006a0020006a0061006b006f015b00630069002e002000200044006f006b0075006d0065006e0074007900200050004400460020006d006f017c006e00610020006f007400770069006500720061010700200077002000700072006f006700720061006d006900650020004100630072006f00620061007400200069002000410064006f00620065002000520065006100640065007200200035002e0030002000690020006e006f00770073007a0079006d002egt13 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020006d00610069007300200061006400650071007500610064006f00730020007000610072006100200070007200e9002d0069006d0070007200650073007300f50065007300200064006500200061006c007400610020007100750061006c00690064006100640065002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt13 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 8: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

9

Humidity Readings

0-100 RH Range

+-2 RH (10-90 RH) Accuracy77degF (25degC)

Less than 4 seconds Response Time

Environmental Limits

34-125degF (11-516degC) Operating

-40-140degF (-40-60degC) Shipping

0-95 RH non-condensing Humidity

Installation Locating and Mounting the Controller For optimum performance controller should be mounted on an interior wall 4-5 feet above the floor away from heat sources sunlight windows air vents and air circulation obstructions 1 Complete rough-in wiring at each

location prior to controller installation 2 Hex screws at the bottom and top of the

controller backplate must be turned clockwise until clear of the controller cover to allow removal of the cover

3 Route wiring through the backplate 4 With the embossed UP toward the

ceiling fasten the 2x4 backplate directly to a vertical 2x4 inch wall handy box A 4x4 inch backplate attachment is also provided for horizontal 2x4 handy box and 4x4 handy box applications

5 Make the appropriate connections to the terminal block

6 Place controller cover over the backplate while being careful not to pinch or dislodge any wiring Turn the hex screws counterclockwise until they engage the cover and hold it in place

Figure 1 - Dimensions and Connections

To prevent mounting screw heads from touching the circuit board in the controller use only the mounting screws provided with the controller Using screws other than the type supplied may damage the controller

CAUTION

10

AAON Mini Controller Backplate Layout

Backplate W

iring Cutout

HPU | Std OAD

Analog Outputs

GND G2 Y1(Analog)

MSTP +B RH

Relay Outputs

-A 24 VAC (SC)

Inputs

OAT E2 | W3 | (Y1) SAT E | W2 GND OB | W1

Relay Outputs

IN2 (L) 24 VAC (SC)

24 VAC - C Y2 ~ R G

Figure 2 - Backplate Terminal Locations

+B = BACnet network terminal BACnet MSTP EIA-485 Network

-A = BACnet network terminal

Space Temp (Internal) = IN1 Space Temperature

Inputs

IN2 = L Configurable Input bull Suction Pressure - 0-10 VDC bull Outside Air Humidity - 0-10 VDC bull CO2 - 0-10 VDC bull Remote Space Temperature - 10k Type 3

Thermistor bull Fan Status - 10k Type 3 Thermistor SAT = IN3 Supply Air Temperature - 10k Type 3 Thermistor OAT = IN4 Outside Air Temperature - 10k Type 3 Thermistor Space RH (Internal) = IN5 Space Relative Humidity GND = Ground

- C = COM E Common 24 VAC

~ R = 24 VAC Phase

OAD = OUT9 EC1 Economizer Output - 0-10 10-0 2-10 or 10-2 VDC (0-100)

Analog Outputs

GND = Ground G2 = OUT8 S1 Variable Speed Supply Fan Output - 0-10 VDC (0-100) Y1 (Analog) = OUT7 Variable Capacity Compressor Output - 1-5 VDC (10-100)

RH = RLY6 Dehumidification Relay Outputs

24 VAC = SC Common E2 | W3 | Y1 (Relay) = RLY5 Emer Heat 2Heat 3Compressor 1 E | W2 = RLY4 Emer Heat 1Heat 2 OB | W1 = RLY3 Reversing ValveHeat 1 24 VAC = SC Common Y2 = RLY2 Compressor 2 G = RLY1 Supply Fan

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f006300680077006500720074006900670065002000500072006500700072006500730073002d0044007200750063006b0065002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt13 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS ltFEFF04180441043f043e043b044c04370443043904420435002004340430043d043d044b04350020043d0430044104420440043e0439043a043800200434043b044f00200441043e043704340430043d0438044f00200434043e043a0443043c0435043d0442043e0432002000410064006f006200650020005000440046002c0020043c0430043a04410438043c0430043b044c043d043e0020043f043e04340445043e0434044f04490438044500200434043b044f00200432044b0441043e043a043e043a0430044704350441044204320435043d043d043e0433043e00200434043e043f0435044704300442043d043e0433043e00200432044b0432043e04340430002e002000200421043e043704340430043d043d044b04350020005000440046002d0434043e043a0443043c0435043d0442044b0020043c043e0436043d043e0020043e0442043a0440044b043204300442044c002004410020043f043e043c043e0449044c044e0020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200431043e043b043504350020043f043e04370434043d043804450020043204350440044104380439002egt13 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 9: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

10

AAON Mini Controller Backplate Layout

Backplate W

iring Cutout

HPU | Std OAD

Analog Outputs

GND G2 Y1(Analog)

MSTP +B RH

Relay Outputs

-A 24 VAC (SC)

Inputs

OAT E2 | W3 | (Y1) SAT E | W2 GND OB | W1

Relay Outputs

IN2 (L) 24 VAC (SC)

24 VAC - C Y2 ~ R G

Figure 2 - Backplate Terminal Locations

+B = BACnet network terminal BACnet MSTP EIA-485 Network

-A = BACnet network terminal

Space Temp (Internal) = IN1 Space Temperature

Inputs

IN2 = L Configurable Input bull Suction Pressure - 0-10 VDC bull Outside Air Humidity - 0-10 VDC bull CO2 - 0-10 VDC bull Remote Space Temperature - 10k Type 3

Thermistor bull Fan Status - 10k Type 3 Thermistor SAT = IN3 Supply Air Temperature - 10k Type 3 Thermistor OAT = IN4 Outside Air Temperature - 10k Type 3 Thermistor Space RH (Internal) = IN5 Space Relative Humidity GND = Ground

- C = COM E Common 24 VAC

~ R = 24 VAC Phase

OAD = OUT9 EC1 Economizer Output - 0-10 10-0 2-10 or 10-2 VDC (0-100)

Analog Outputs

GND = Ground G2 = OUT8 S1 Variable Speed Supply Fan Output - 0-10 VDC (0-100) Y1 (Analog) = OUT7 Variable Capacity Compressor Output - 1-5 VDC (10-100)

RH = RLY6 Dehumidification Relay Outputs

24 VAC = SC Common E2 | W3 | Y1 (Relay) = RLY5 Emer Heat 2Heat 3Compressor 1 E | W2 = RLY4 Emer Heat 1Heat 2 OB | W1 = RLY3 Reversing ValveHeat 1 24 VAC = SC Common Y2 = RLY2 Compressor 2 G = RLY1 Supply Fan

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA ltFEFF06270633062A062E062F0645002006470630064700200627064406250639062F0627062F0627062A002006440625064606340627062100200648062B062706260642002000410064006F00620065002000500044004600200645062A064806270641064206290020064406440637062806270639062900200641064A00200627064406450637062706280639002006300627062A0020062F0631062C0627062A002006270644062C0648062F0629002006270644063906270644064A0629061B0020064A06450643064600200641062A062D00200648062B0627062606420020005000440046002006270644064506460634062306290020062806270633062A062E062F062706450020004100630072006F0062006100740020064800410064006F006200650020005200650061006400650072002006250635062F0627063100200035002E0030002006480627064406250635062F062706310627062A0020062706440623062D062F062B002E0635062F0627063100200035002E0030002006480627064406250635062F062706310627062A0020062706440623062D062F062B002Egt13 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f006300680077006500720074006900670065002000500072006500700072006500730073002d0044007200750063006b0065002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt13 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f00730020005000440046002000640065002000410064006f0062006500200061006400650063007500610064006f00730020007000610072006100200069006d0070007200650073006900f3006e0020007000720065002d0065006400690074006f007200690061006c00200064006500200061006c00740061002000630061006c0069006400610064002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt13 ETI 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 FRA 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 GRE ltFEFF03a703c103b703c303b903bc03bf03c003bf03b903ae03c303c403b5002003b103c503c403ad03c2002003c403b903c2002003c103c503b803bc03af03c303b503b903c2002003b303b903b1002003bd03b1002003b403b703bc03b903bf03c503c103b303ae03c303b503c403b5002003ad03b303b303c103b103c603b1002000410064006f006200650020005000440046002003c003bf03c5002003b503af03bd03b103b9002003ba03b103c42019002003b503be03bf03c703ae03bd002003ba03b103c403ac03bb03bb03b703bb03b1002003b303b903b1002003c003c103bf002d03b503ba03c403c503c003c903c403b903ba03ad03c2002003b503c103b303b103c303af03b503c2002003c503c803b703bb03ae03c2002003c003bf03b903cc03c403b703c403b103c2002e0020002003a403b10020005000440046002003ad03b303b303c103b103c603b1002003c003bf03c5002003ad03c703b503c403b5002003b403b703bc03b903bf03c503c103b303ae03c303b503b9002003bc03c003bf03c103bf03cd03bd002003bd03b1002003b103bd03bf03b903c703c403bf03cd03bd002003bc03b5002003c403bf0020004100630072006f006200610074002c002003c403bf002000410064006f00620065002000520065006100640065007200200035002e0030002003ba03b103b9002003bc03b503c403b103b303b503bd03ad03c303c403b503c103b503c2002003b503ba03b403cc03c303b503b903c2002egt13 HEB ltFEFF05D405E905EA05DE05E905D5002005D105D405D205D305E805D505EA002005D005DC05D4002005DB05D305D9002005DC05D905E605D505E8002005DE05E105DE05DB05D9002000410064006F006200650020005000440046002005D405DE05D505EA05D005DE05D905DD002005DC05D405D305E405E105EA002005E705D305DD002D05D305E405D505E1002005D005D905DB05D505EA05D905EA002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002E05D005DE05D905DD002005DC002D005000440046002F0058002D0033002C002005E205D905D905E005D5002005D105DE05D305E805D905DA002005DC05DE05E905EA05DE05E9002005E905DC0020004100630072006F006200610074002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002Egt13 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f00620065002000500044004600200070006900f900200061006400610074007400690020006100200075006e00610020007000720065007300740061006d0070006100200064006900200061006c007400610020007100750061006c0069007400e0002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt13 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 10: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

11

Electrical Connection terminations are made to the main terminal block of the controller and the HVAC equipment A complete set of unit specific wiring diagrams showing factory and field wiring are laminated in plastic and located inside the controls compartment door of the AAON HVAC equipment Control Wiring Control wiring size must be large enough to prevent excess voltage drop and ensure proper operation Control voltage returning from controller circuit must be a minimum of 21 VAC To assure proper wiring use the following table to determine the allowable wiring distances

Table 1 - Control Wiring Wire Size (Stranded) - Copper Conductors Only

Total Wire Distance Allowable

20 AWG 200 ft 18 AWG 350 ft 16 AWG 500 ft 14 AWG 750 ft 12 AWG 1250 ft Total Wire Distance Allowable = (Quantity of Control Wires) x (Control Wire Distance) Take the total wire distance allowable and divide by the quantity of wires to be connected This indicates the distance

allowable for that size wire The wiring to the unit must not exceed the total wire distance allowable If the voltage at the connectors is less than 21 VAC isolation relays must be installed If under external control 21 VAC must be field verified All external devices must be powered via a separate external power supply Example A total of 8 wires must be pulled 75 ft to a control the unit What size wire should be used According to Table 1 16 AWG allows for 63 ft (500 ft8 wires) and 14 AWG allows for 94 ft (750 ft8 wires) Thus 14 AWG should be used BACnet MSTP EIA-485 Wiring Connect the -A terminals in parallel with all other -A terminals on the network and the +B terminals in parallel with all other +B terminals Connect the shields of the cable together at each device using a wire nut Connect the cable shield to a good earth ground at one end only Controllers on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation If a controller is at the physical end of the MSTP network line set both the EOL termination switches to the On position on the back of the circuit board If not on the end ensure that both switches are Off

Figure 3 - MSTP Network End-of-Line

Terminology

Disconnect all electrical power sources before servicing the unit More than one power source may be provided Failure to do so may result in injury or death from electrical shock or entanglement in moving parts

WARNING

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f006300680077006500720074006900670065002000500072006500700072006500730073002d0044007200750063006b0065002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt13 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI ltFEFF0049007a006d0061006e0074006f006a00690065007400200161006f00730020006900650073007400610074012b006a0075006d00750073002c0020006c0061006900200076006500690064006f00740075002000410064006f00620065002000500044004600200064006f006b0075006d0065006e007400750073002c0020006b006100730020006900720020012b00700061016100690020007000690065006d01130072006f00740069002000610075006700730074006100730020006b00760061006c0069007401010074006500730020007000690072006d007300690065007300700069006501610061006e006100730020006400720075006b00610069002e00200049007a0076006500690064006f006a006900650074002000500044004600200064006f006b0075006d0065006e007400750073002c0020006b006f002000760061007200200061007400760113007200740020006100720020004100630072006f00620061007400200075006e002000410064006f00620065002000520065006100640065007200200035002e0030002c0020006b0101002000610072012b00200074006f0020006a00610075006e0101006b0101006d002000760065007200730069006a0101006d002egt13 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV ltFEFF005400650020006e006100730074006100760069007400760065002000750070006f0072006100620069007400650020007a00610020007500730074007600610072006a0061006e006a006500200064006f006b0075006d0065006e0074006f0076002000410064006f006200650020005000440046002c0020006b006900200073006f0020006e0061006a007000720069006d00650072006e0065006a016100690020007a00610020006b0061006b006f0076006f00730074006e006f0020007400690073006b0061006e006a00650020007300200070007200690070007200610076006f0020006e00610020007400690073006b002e00200020005500730074007600610072006a0065006e006500200064006f006b0075006d0065006e0074006500200050004400460020006a00650020006d006f0067006f010d00650020006f0064007000720065007400690020007a0020004100630072006f00620061007400200069006e002000410064006f00620065002000520065006100640065007200200035002e003000200069006e0020006e006f00760065006a01610069006d002egt13 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 11: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

12

Figure 4 - EOL and Pull-Up Switch Resistor

Positions on Reverse Side of Controller See BACnet Points List section for additional information Input Connections Passive input devices require pull-up resistors in the circuit For passive input devices such as 10k Type 3 thermistors on the IN2 through IN4 set the pull-up switches on the back of the circuit board to the 10K position For active voltage devices set the switches to the 0-12 V position The input switch pairs (3-4 5-6 7-8) must not

have both switches set to the left or both set to the right For example if switch 3 is set to the left switch 4 must be set to the right The input pull-up resistor switch pairs must be fully latched in either the 10K or 0-12 V positions - even if a switch pair has no input connected

IN3 and IN4 the outside and supply air temperature sensor inputs should not be changed and must always be set to the 10K position For IN2 with factory provided sensors inputs should be set up as Suction pressure sensor - 0-12 V Outside air humidity sensor - 0-12 V CO2 sensor - 0-12 V Remote space temperature - 10K Fan status - 0-12 V The controller does not support 1k ohm RTDs

Remote Space Temperature Sensor A maximum of 4 remote space temperature sensors may be wired in a series-parallel arrangement to provide an average remote space temperature reading With remote space temperature sensor averaging configured this average remote space temperature is then averaged with the internal space temperature reading Supply Air Temperature Sensor Supply air temperature sensor must be field installed in the supply ductwork 6-8 feet downstream from the unit to get an accurate reading Output Connections Connect the device under control between the desired output terminal and the related SC (Switched Common for relay outputs) or GND (Ground for analog outputs) For a bank of three relays there is one SC connection

Figure 5 - Switched Common and Relays

Do not attach a device that draws current exceeding the controllerrsquos capacity Maximum output current for individual Analog outputs is 20 mA 12 VDC Maximum output current for individual relays is 1 A 24 VACVDC or a total of 15 A per bank of 3 relays (relays 1-3 4-6) Relays 1-6 are NO SPST Form A

Relays are for Class-2 (24 VAC) only Do not connect line voltage to the relays

CAUTION

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB ltFEFF05D405E905EA05DE05E905D5002005D105D405D205D305E805D505EA002005D005DC05D4002005DB05D305D9002005DC05D905E605D505E8002005DE05E105DE05DB05D9002000410064006F006200650020005000440046002005D405DE05D505EA05D005DE05D905DD002005DC05D405D305E405E105EA002005E705D305DD002D05D305E405D505E1002005D005D905DB05D505EA05D905EA002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002E05D005DE05D905DD002005DC002D005000440046002F0058002D0033002C002005E205D905D905E005D5002005D105DE05D305E805D905DA002005DC05DE05E905EA05DE05E9002005E905DC0020004100630072006F006200610074002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002Egt13 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI ltFEFF0049007a006d0061006e0074006f006a00690065007400200161006f00730020006900650073007400610074012b006a0075006d00750073002c0020006c0061006900200076006500690064006f00740075002000410064006f00620065002000500044004600200064006f006b0075006d0065006e007400750073002c0020006b006100730020006900720020012b00700061016100690020007000690065006d01130072006f00740069002000610075006700730074006100730020006b00760061006c0069007401010074006500730020007000690072006d007300690065007300700069006501610061006e006100730020006400720075006b00610069002e00200049007a0076006500690064006f006a006900650074002000500044004600200064006f006b0075006d0065006e007400750073002c0020006b006f002000760061007200200061007400760113007200740020006100720020004100630072006f00620061007400200075006e002000410064006f00620065002000520065006100640065007200200035002e0030002c0020006b0101002000610072012b00200074006f0020006a00610075006e0101006b0101006d002000760065007200730069006a0101006d002egt13 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 12: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

13

Power Connection The controller requires an external 24 VAC power source Use a Class-2 transformer to supply power Connect the transformerrsquos neutral lead to the 24 VAC Common (- C) terminal and the AC phase lead to the 24 VAC Phase (~ R) terminal Power is applied to the controller when the transformer is plugged in AAON recommends powering only one controller from each transformer If installing a system with other controllers powered from a single transformer however phasing must be correct and total power drawn from the transformer must not exceed its rating Startup (See back of the manual for startup form)

Navigation

Enter - Select or exit value editing General

UpDown - Move among entries LeftRight - Move among value fields Left - Back or return to Home Screen

Enter - Turn on backlight Home Screen

UpDown - Space temperature setpoint viewing and override Left - Open Override Menu Right - Open Main Menu

Figure 6 - AAON Mini Controller

Home Screen Configuration

Press UpDown once to view the existing space temperature setpoint

Space Temperature Setpoint Override

For temporary push button override of the current space temperature setpoint press UpDown repeatedly until the desired temperature setpoint is displayed and press Enter The new setpoint will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

The System Mode of Operation options available are Auto Cooling Heating Emergency Heating and Off

System Mode of Operation

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

Do not mistakenly connect 24 VAC to an analog output ground This is not the same as a relayrsquos switched common See the backplatersquos terminal label for the correct terminal

CAUTION

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS ltFEFF04180441043f043e043b044c04370443043904420435002004340430043d043d044b04350020043d0430044104420440043e0439043a043800200434043b044f00200441043e043704340430043d0438044f00200434043e043a0443043c0435043d0442043e0432002000410064006f006200650020005000440046002c0020043c0430043a04410438043c0430043b044c043d043e0020043f043e04340445043e0434044f04490438044500200434043b044f00200432044b0441043e043a043e043a0430044704350441044204320435043d043d043e0433043e00200434043e043f0435044704300442043d043e0433043e00200432044b0432043e04340430002e002000200421043e043704340430043d043d044b04350020005000440046002d0434043e043a0443043c0435043d0442044b0020043c043e0436043d043e0020043e0442043a0440044b043204300442044c002004410020043f043e043c043e0449044c044e0020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200431043e043b043504350020043f043e04370434043d043804450020043204350440044104380439002egt13 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 13: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

14

When System Enable is set to Auto the controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature When System Enable is set to Heating the controller will maintain only the space heating setpoint When System Enable is set to Cooling the controller will maintain only the space cooling setpoint For heat pump units when System Enable is set to Emergency Heating the controller will maintain only the space heating setpoint using only the emergency heating When System Enable is set to Off the controller operation will be turned off When the controller is in the heating mode of operation HEAT and an animated icon will be displayed When the controller is in the cooling mode of operation COOL and an animated icon will be displayed When OFF is displayed the mode of operation display is off

The Occupancy Override options available are On and Off Override is automatically turned on if the space temperature setpoint has been temporarily changed from the home screen The occupancy override will hold for the duration of the occupancy override amount of time (adjustable under Main Menu System) or until the occupancy override has been turned off manually from the Home Screen

Occupancy Override (OCC)

When in the occupied mode of operation a sun icon is displayed When in the unoccupied mode of operation a quarter moon icon is displayed OVR is displayed when the space temperature setpoint has been temporarily changed from the home screen or occupancy override has been turned on manually

The Fan Mode options available for both the unoccupied and occupied modes of operation are Auto and On

Fan Mode (Fan)

Auto activates the fan only during heating and cooling operation On activates the fan for the duration of the occupied or unoccupied mode of operation When the supply fan has been commanded to run an animated fan icon is displayed When the supply fan command stops the fan icon is motionless Main Menu Configuration

About menu displays information about the controller including

About

FW Firmware VERSION Firmware version BUILT Date and time of firmware build ASV Application software version MODEL Controller model number APP Application configuration OPT Heating and cooling staging INSTANCE BACnet instance number MAC ADDRESS BACnet Mac Address SN Serial Number BOARD REV Hardware revision

A flashing SERVICE message on the Home Screen below the space temperature indicates an alarm Within the Alarm menu press Enter while an alarm is highlighted to view details Press Enter on the alarm details to delete the alarm or Left to go back

Alarm

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200073006f006d00200065007200200062006500730074002000650067006e0065007400200066006f00720020006600f80072007400720079006b006b0073007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c0069007400650074002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt13 POL ltFEFF0055007300740061007700690065006e0069006100200064006f002000740077006f0072007a0065006e0069006100200064006f006b0075006d0065006e007400f300770020005000440046002000700072007a0065007a006e00610063007a006f006e00790063006800200064006f002000770079006400720075006b00f30077002000770020007700790073006f006b00690065006a0020006a0061006b006f015b00630069002e002000200044006f006b0075006d0065006e0074007900200050004400460020006d006f017c006e00610020006f007400770069006500720061010700200077002000700072006f006700720061006d006900650020004100630072006f00620061007400200069002000410064006f00620065002000520065006100640065007200200035002e0030002000690020006e006f00770073007a0079006d002egt13 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f00740020006c00e400680069006e006e00e4002000760061006100740069007600610061006e0020007000610069006e006100740075006b00730065006e002000760061006c006d0069007300740065006c00750074007900f6006800f6006e00200073006f00700069007600690061002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a0061002e0020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt13 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 14: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

15

Figure 7 - Home Screen with Flashing

Service Message Space Temperature Alarm Activated when the space temperature is outside the range of 56-86degF for over 300 seconds Alarm is available on all controllers Space Humidity Alarm Activated when the space humidity is above 65 RH for over 300 seconds Alarm is only available on controllers with humidity control Fan Fail Alarm Activated when there is no fan status signal within 5 seconds on a call for fan Alarm is only available on controllers with a fan status sensor connected Low Limit Alarm Activated when the supply air temperature is below the low limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Cooling will be disabled until supply air temperature is 2degF above the low limit setpoint Alarm is only available on controllers with a supply air temperature sensor connected High Limit Alarm Activated when the supply air temperature is above the high limit alarm temperature setpoint for 2 seconds (Main Menu Advanced Limits) Heating will be disabled until supply air temperature is 2degF below the high limit setpoint Alarm is only available

on controllers with a supply air temperature sensor connected Space CO2 Alarm Activated when the space CO2 is above 2000 ppm Alarm is only available on controllers with CO2 sensor connected

DateTime menu is used to configure the date and time Day month year and time are available for configuration

DateTime

Schedule menu is used to configure an entire week schedule a weekdayweekend schedule or an individual day schedule Only one weekly schedule can be setup Up to 6 occupiedunoccupied changes can be made per day Up to 12 individual days of unoccupied holidays can be setup within the menu

Schedule

The schedule mode of operation changes available are On Off and Null On is a change to occupied operation Off is a change to unoccupied operation Null is no change in mode of operation

Setpoints menu is used to configure the controller setpoints

Setpoints

COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70degF COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR ltFEFF04180437043f043e043b043704320430043904420435002004420435043704380020043d0430044104420440043e0439043a0438002c00200437043000200434043000200441044a0437043404300432043004420435002000410064006f00620065002000500044004600200434043e043a0443043c0435043d04420438002c0020043c0430043a04410438043c0430043b043d043e0020043f044004380433043e04340435043d04380020043704300020043204380441043e043a043e043a0430044704350441044204320435043d0020043f04350447043004420020043704300020043f044004350434043f0435044704300442043d04300020043f043e04340433043e0442043e0432043a0430002e002000200421044a04370434043004340435043d043804420435002000500044004600200434043e043a0443043c0435043d044204380020043c043e0433043004420020043404300020044104350020043e0442043204300440044f0442002004410020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200441043b0435043404320430044904380020043204350440044104380438002egt13 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 15: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

16

MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi

System menu is used for additional startup configuration

System

SYSTEM ENABLE System Mode of Operation Default value is Off Auto - Controller will maintain both the space heating and cooling setpoints with operation depending on the space temperature Cooling - Controller will maintain only the space cooling setpoint Heating - Controller will maintain only the space heating setpoint Emergency Heating - Controller will maintain only the space heating setpoint using only emergency heating Off - Turns the controller operation off OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds DISPLAY BLANKING Available options are Yes and No Default value is No With Yes selected display will turn off at the same time the backlight goes off With No selected display will turn stay on when the backlight goes off When any key is pressed the display and backlight will turn on

Trend viewer displays the trend logs that have already been setup Press Enter when the trend is highlighted to view details

Trend Viewer

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS ltFEFF04180441043f043e043b044c04370443043904420435002004340430043d043d044b04350020043d0430044104420440043e0439043a043800200434043b044f00200441043e043704340430043d0438044f00200434043e043a0443043c0435043d0442043e0432002000410064006f006200650020005000440046002c0020043c0430043a04410438043c0430043b044c043d043e0020043f043e04340445043e0434044f04490438044500200434043b044f00200432044b0441043e043a043e043a0430044704350441044204320435043d043d043e0433043e00200434043e043f0435044704300442043d043e0433043e00200432044b0432043e04340430002e002000200421043e043704340430043d043d044b04350020005000440046002d0434043e043a0443043c0435043d0442044b0020043c043e0436043d043e0020043e0442043a0440044b043204300442044c002004410020043f043e043c043e0449044c044e0020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200431043e043b043504350020043f043e04370434043d043804450020043204350440044104380439002egt13 SKY 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 SLV 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f00740020006c00e400680069006e006e00e4002000760061006100740069007600610061006e0020007000610069006e006100740075006b00730065006e002000760061006c006d0069007300740065006c00750074007900f6006800f6006e00200073006f00700069007600690061002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a0061002e0020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt13 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 16: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

17

Advanced Menu Configuration

Application menu is used for application configuration

(Advanced) Application

DEGREE SCALE degF or degC APP Controller application Standard - Air conditioner application Heat Pump - Heat pump application Not Configured - Default value OPT Number of heating and cooling stages Air conditioners are available with 1 or 2 stages of cooling and 1 2 or 3 stages of heating Heat pumps are available with 1 or 2 compressor stages 0 1 or 2 stages of emergency heat SAT CONTROL Available options are No SAT Control SAT Cooling Only Control and SAT Heating amp Cooling Control Use for single zone VAV applications with supply air temperature cooling capacity control or supply air temperature cooling and heating capacity control ADDITIONAL SETUP HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes DAMPER - ECON Available economizer options are None or Modulating DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95

DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - LOW LIMIT Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF FAN - SPEEDS Available options are Constant Spd C amp H Variable Spd Cool Only or Variable Spd Cool and Heat Constant Spd C amp H - Constant volume application Variable Spd Cool Only - Single zone VAV application with single zone VAV cooling and constant volume heating Variable Spd C amp H - Single zone VAV application with single VAV cooling and single zone VAV heating FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE ltFEFF03a703c103b703c303b903bc03bf03c003bf03b903ae03c303c403b5002003b103c503c403ad03c2002003c403b903c2002003c103c503b803bc03af03c303b503b903c2002003b303b903b1002003bd03b1002003b403b703bc03b903bf03c503c103b303ae03c303b503c403b5002003ad03b303b303c103b103c603b1002000410064006f006200650020005000440046002003c003bf03c5002003b503af03bd03b103b9002003ba03b103c42019002003b503be03bf03c703ae03bd002003ba03b103c403ac03bb03bb03b703bb03b1002003b303b903b1002003c003c103bf002d03b503ba03c403c503c003c903c403b903ba03ad03c2002003b503c103b303b103c303af03b503c2002003c503c803b703bb03ae03c2002003c003bf03b903cc03c403b703c403b103c2002e0020002003a403b10020005000440046002003ad03b303b303c103b103c603b1002003c003bf03c5002003ad03c703b503c403b5002003b403b703bc03b903bf03c503c103b303ae03c303b503b9002003bc03c003bf03c103bf03cd03bd002003bd03b1002003b103bd03bf03b903c703c403bf03cd03bd002003bc03b5002003c403bf0020004100630072006f006200610074002c002003c403bf002000410064006f00620065002000520065006100640065007200200035002e0030002003ba03b103b9002003bc03b503c403b103b303b503bd03ad03c303c403b503c103b503c2002003b503ba03b403cc03c303b503b903c2002egt13 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV ltFEFF005400650020006e006100730074006100760069007400760065002000750070006f0072006100620069007400650020007a00610020007500730074007600610072006a0061006e006a006500200064006f006b0075006d0065006e0074006f0076002000410064006f006200650020005000440046002c0020006b006900200073006f0020006e0061006a007000720069006d00650072006e0065006a016100690020007a00610020006b0061006b006f0076006f00730074006e006f0020007400690073006b0061006e006a00650020007300200070007200690070007200610076006f0020006e00610020007400690073006b002e00200020005500730074007600610072006a0065006e006500200064006f006b0075006d0065006e0074006500200050004400460020006a00650020006d006f0067006f010d00650020006f0064007000720065007400690020007a0020004100630072006f00620061007400200069006e002000410064006f00620065002000520065006100640065007200200035002e003000200069006e0020006e006f00760065006a01610069006d002egt13 SUO 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 SVE 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 TUR ltFEFF005900fc006b00730065006b0020006b0061006c006900740065006c0069002000f6006e002000790061007a006401310072006d00610020006200610073006b013100730131006e006100200065006e0020006900790069002000750079006100620069006c006500630065006b002000410064006f006200650020005000440046002000620065006c00670065006c0065007200690020006f006c0075015f007400750072006d0061006b0020006900e70069006e00200062007500200061007900610072006c0061007201310020006b0075006c006c0061006e0131006e002e00200020004f006c0075015f0074007500720075006c0061006e0020005000440046002000620065006c00670065006c0065007200690020004100630072006f006200610074002000760065002000410064006f00620065002000520065006100640065007200200035002e003000200076006500200073006f006e0072006100730131006e00640061006b00690020007300fc007200fc006d006c00650072006c00650020006100e70131006c006100620069006c00690072002egt13 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 17: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

18

FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - UNOCC Unoccupied fan mode options are Auto or On Auto activates the fan only during unoccupied heating and cooling operation On activates the fan for the duration of the unoccupied mode of operation Default value is Auto FAN - OCC Occupied fan mode options are Auto or On Auto activates the fan only during occupied heating and cooling operation On activates the fan for the duration of the occupied mode of operation Default value is On HUMIDITY - DEHUMIDIFICATION - DEHUM Options available are None or Dehum Enables modulating hot gas reheat humidity control HUMIDITY - DEHUMIDIFICATION - DEHUM PRIORITY Options available are False or True False activates dehumidification only when heating and cooling setpoints are satisfied True activates dehumidification anytime space humidity is outside dehumidification setpoints Default is False

HUMIDITY - DEHUMIDIFICATION - DEHUM SETPT Default setpoint is 50 RH and range is 20-85 RH HUMIDITY - DEHUMIDIFICATION - DEHUM DEADBAND Default value is 5 RH and range is 5-15 RH SENSOR SETUP - OAT SENSOR (AI4) Available outside air temperature sensor options are Yes or No Outside air temperature sensor is required for all air-cooled application and default value is Yes SENSOR - SAT SENSOR (AI3) Available supply air temperature options are Yes or No Supply air temperature sensor is required for single zone VAV modulating hot gas reheat and economizer applications and default value is No SENSOR - AI2 Additional controller input options Default value is Not Used Not Used - No analog input 2 is connected Fan Status - Airflow sensor is connected for fan status option Remote CO2 Sensor - CO2 sensor is connected for CO2 economizer override option Suction Line PSI - Suction pressure sensor is connected for modulating hot gas reheat humidity control option Remote Space Avg - Space temperature sensor is connected for remote averaging space temperature option Remote Space Only - Space temperature sensor is connected for remote space temperature option OA Humidity - Outside air humidity sensor is connected for enthalpy controlled economizer option COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200073006f006d00200065007200200062006500730074002000650067006e0065007400200066006f00720020006600f80072007400720079006b006b0073007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c0069007400650074002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt13 POL 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 PTB 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 RUM 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 RUS ltFEFF04180441043f043e043b044c04370443043904420435002004340430043d043d044b04350020043d0430044104420440043e0439043a043800200434043b044f00200441043e043704340430043d0438044f00200434043e043a0443043c0435043d0442043e0432002000410064006f006200650020005000440046002c0020043c0430043a04410438043c0430043b044c043d043e0020043f043e04340445043e0434044f04490438044500200434043b044f00200432044b0441043e043a043e043a0430044704350441044204320435043d043d043e0433043e00200434043e043f0435044704300442043d043e0433043e00200432044b0432043e04340430002e002000200421043e043704340430043d043d044b04350020005000440046002d0434043e043a0443043c0435043d0442044b0020043c043e0436043d043e0020043e0442043a0440044b043204300442044c002004410020043f043e043c043e0449044c044e0020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200431043e043b043504350020043f043e04370434043d043804450020043204350440044104380439002egt13 SKY 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 SLV 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 SUO 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 SVE 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 TUR ltFEFF005900fc006b00730065006b0020006b0061006c006900740065006c0069002000f6006e002000790061007a006401310072006d00610020006200610073006b013100730131006e006100200065006e0020006900790069002000750079006100620069006c006500630065006b002000410064006f006200650020005000440046002000620065006c00670065006c0065007200690020006f006c0075015f007400750072006d0061006b0020006900e70069006e00200062007500200061007900610072006c0061007201310020006b0075006c006c0061006e0131006e002e00200020004f006c0075015f0074007500720075006c0061006e0020005000440046002000620065006c00670065006c0065007200690020004100630072006f006200610074002000760065002000410064006f00620065002000520065006100640065007200200035002e003000200076006500200073006f006e0072006100730131006e00640061006b00690020007300fc007200fc006d006c00650072006c00650020006100e70131006c006100620069006c00690072002egt13 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 18: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

19

VALVE - REV VALVE Heat pump reversing valve options Active Htg - Reversing valve is active during the heating mode of operation Default value Active Cool - Reversing valve is active during cooling mode of operation Note RQ and RN Series units are wired for activating the reversing valve during the heating mode of operation H3V3 and CBCC Series units are wired for activating the reversing valve during the cooling mode of operation

The CB Programs displays the status of the software on the controller No adjustments can be made within this menu

(Advanced) CB Programs

MAC ADDRESS (Advanced) Communication

Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

The Advanced DateTime menu is used to configure the date time UTC offset (Coordinated Universal Time) and Daylight Saving Time

(Advanced) DateTime

For areas which observe Daylight Saving Time it must be enabled from this menu If the controller is used in a BACnet network with UTC synchronization set the UTC offset value The offset value is in minutes and corresponds to the distance of

the local time zone to the zero degree meridian

Table 2 - UTC Offset Sample Time Zone Offset to Equal UTC

Alaska Standard 540 Pacific Standard 480

Mountain Standard 420 Central Standard 360 Eastern Standard 300

The Device menu allows setting of the BACnet device instance name and location In addition a warm restart a cold restart and a factory restore can be done from this menu Restarting the controller from this menu is recommended rather than removing power to the controller

(Advanced) Device

Warm Restart - The least disruptive restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Warm restart restores present values of objects to their last values before restart Configuration remains intact Cold Restart - Restart option which lasts around 10 seconds Analog outputs go to 0 and relays go to their normally open state Compressor and fan minimum off delay times should be set before a restart as there may be several changes of state for an output Cold restart restores all values of objects to their relinquished default values and then rewrites menu changes Menu changes may take up to about 2 minutes to write to memory If power to the controller is lost during this time changes may be lost Configuration remains intact Factory Restore - Restore option clears all present values restores configuration to the defaults and restarts the controller

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR ltFEFF04180437043f043e043b043704320430043904420435002004420435043704380020043d0430044104420440043e0439043a0438002c00200437043000200434043000200441044a0437043404300432043004420435002000410064006f00620065002000500044004600200434043e043a0443043c0435043d04420438002c0020043c0430043a04410438043c0430043b043d043e0020043f044004380433043e04340435043d04380020043704300020043204380441043e043a043e043a0430044704350441044204320435043d0020043f04350447043004420020043704300020043f044004350434043f0435044704300442043d04300020043f043e04340433043e0442043e0432043a0430002e002000200421044a04370434043004340435043d043804420435002000500044004600200434043e043a0443043c0435043d044204380020043c043e0433043004420020043404300020044104350020043e0442043204300440044f0442002004410020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200441043b0435043404320430044904380020043204350440044104380438002egt13 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f0075007200200075006e00650020007100750061006c0069007400e90020006400270069006d007000720065007300730069006f006e00200070007200e9007000720065007300730065002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt13 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f00620065002000500044004600200070006900f900200061006400610074007400690020006100200075006e00610020007000720065007300740061006d0070006100200064006900200061006c007400610020007100750061006c0069007400e0002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt13 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 19: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

20

The Inputs menu shows all analog inputs their current value and any calibration offset

(Advanced) Inputs

The Limits menu allows setting of minimum and maximum values

(Advanced) Limits

OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF HEAT OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF

OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB ltFEFF05D405E905EA05DE05E905D5002005D105D405D205D305E805D505EA002005D005DC05D4002005DB05D305D9002005DC05D905E605D505E8002005DE05E105DE05DB05D9002000410064006F006200650020005000440046002005D405DE05D505EA05D005DE05D905DD002005DC05D405D305E405E105EA002005E705D305DD002D05D305E405D505E1002005D005D905DB05D505EA05D905EA002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002E05D005DE05D905DD002005DC002D005000440046002F0058002D0033002C002005E205D905D905E005D5002005D105DE05D305E805D905DA002005DC05DE05E905EA05DE05E9002005E905DC0020004100630072006F006200610074002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002Egt13 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f00620065002000500044004600200070006900f900200061006400610074007400690020006100200075006e00610020007000720065007300740061006d0070006100200064006900200061006c007400610020007100750061006c0069007400e0002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt13 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM ltFEFF005500740069006c0069007a00610163006900200061006300650073007400650020007300650074010300720069002000700065006e007400720075002000610020006300720065006100200064006f00630075006d0065006e00740065002000410064006f006200650020005000440046002000610064006500630076006100740065002000700065006e0074007200750020007400690070010300720069007200650061002000700072006500700072006500730073002000640065002000630061006c006900740061007400650020007300750070006500720069006f006100720103002e002000200044006f00630075006d0065006e00740065006c00650020005000440046002000630072006500610074006500200070006f00740020006600690020006400650073006300680069007300650020006300750020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e00300020015f00690020007600650072007300690075006e0069006c006500200075006c0074006500720069006f006100720065002egt13 RUS ltFEFF04180441043f043e043b044c04370443043904420435002004340430043d043d044b04350020043d0430044104420440043e0439043a043800200434043b044f00200441043e043704340430043d0438044f00200434043e043a0443043c0435043d0442043e0432002000410064006f006200650020005000440046002c0020043c0430043a04410438043c0430043b044c043d043e0020043f043e04340445043e0434044f04490438044500200434043b044f00200432044b0441043e043a043e043a0430044704350441044204320435043d043d043e0433043e00200434043e043f0435044704300442043d043e0433043e00200432044b0432043e04340430002e002000200421043e043704340430043d043d044b04350020005000440046002d0434043e043a0443043c0435043d0442044b0020043c043e0436043d043e0020043e0442043a0440044b043204300442044c002004410020043f043e043c043e0449044c044e0020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200431043e043b043504350020043f043e04370434043d043804450020043204350440044104380439002egt13 SKY ltFEFF0054006900650074006f0020006e006100730074006100760065006e0069006100200070006f0075017e0069007400650020006e00610020007600790074007600e100720061006e0069006500200064006f006b0075006d0065006e0074006f0076002000410064006f006200650020005000440046002c0020006b0074006f007200e90020007300610020006e0061006a006c0065007001610069006500200068006f0064006900610020006e00610020006b00760061006c00690074006e00fa00200074006c0061010d00200061002000700072006500700072006500730073002e00200056007900740076006f00720065006e00e900200064006f006b0075006d0065006e007400790020005000440046002000620075006400650020006d006f017e006e00e90020006f00740076006f00720069016500200076002000700072006f006700720061006d006f006300680020004100630072006f00620061007400200061002000410064006f00620065002000520065006100640065007200200035002e0030002000610020006e006f0076016100ed00630068002egt13 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 20: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

21

The Security menu allows setting of User Operator and Administrator access to setpoint adjustment Main Menu system mode occupancy override and fan operation Passwords for the User Operator and Administrator can be changed from this menu

(Advanced) Security

Trend Logs can be set up from this menu including inputoutput to monitor and interval of time to monitor the inputoutput See individual analog and binary inputs outputs and variables for numbers (BI BO AI AO AV)

(Advanced) Trend Logs

Test menu is used for testing of the controller display pixels and buttons

(Advanced) Test

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 21: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

22

Default Configuration Access Default User Password = 0000 Default Operator Password = 1988 Default Administrator Password = 2425 Note Administrator Password is required to set security passwords If changed keep a record of the new administrator password in a trusted location

Table 3 - Default Access Levels

User Operator Administrator

Home Screen Space Temp Setpoint Adjustment Y Y Y Mode of Operation Override Y Y Y Occupancy Override Y Y Y Supply Fan Override Y Y Y Main Menu About Y Y Y Alarm N Y Y DateTime N Y Y Schedule N Y Y Setpoints N Y Y System N Y Y Trend Viewer Y Y Y Advanced Application N N Y CB Programs N Y Y Communication N N Y DateTime N Y Y Device N N Y Inputs N Y Y Limits N Y Y Security N N Y Trend Logs N Y Y Test N Y Y

QUALIFIED INSTALLER Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a trained qualified installer A copy of this IOM should be kept with the unit

WARNING

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f00620065002000500044004600200070006900f900200061006400610074007400690020006100200075006e00610020007000720065007300740061006d0070006100200064006900200061006c007400610020007100750061006c0069007400e0002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt13 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS ltFEFF04180441043f043e043b044c04370443043904420435002004340430043d043d044b04350020043d0430044104420440043e0439043a043800200434043b044f00200441043e043704340430043d0438044f00200434043e043a0443043c0435043d0442043e0432002000410064006f006200650020005000440046002c0020043c0430043a04410438043c0430043b044c043d043e0020043f043e04340445043e0434044f04490438044500200434043b044f00200432044b0441043e043a043e043a0430044704350441044204320435043d043d043e0433043e00200434043e043f0435044704300442043d043e0433043e00200432044b0432043e04340430002e002000200421043e043704340430043d043d044b04350020005000440046002d0434043e043a0443043c0435043d0442044b0020043c043e0436043d043e0020043e0442043a0440044b043204300442044c002004410020043f043e043c043e0449044c044e0020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200431043e043b043504350020043f043e04370434043d043804450020043204350440044104380439002egt13 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 22: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

23

Controller Configuration Steps 1 Unit Application 2 Heating and Cooling Stages 3 Sensors 4 Supply Fan 5 Features 6 Limits 7 Setpoints 8 DateTime 9 ScheduleHolidays 10 Trend Logs 11 Security Access 12 Restart

1 Main Menu Advanced Application

Constant Volume Air Conditioner Configuration

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

4 Main Menu Advanced Application SAT Control = None

5 Main Menu Advanced Limits

Check Limit Values

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN ltFEFF004b0069007600e1006c00f30020006d0069006e0151007300e9006701710020006e0079006f006d00640061006900200065006c0151006b00e90073007a00ed007401510020006e0079006f006d00740061007400e100730068006f007a0020006c006500670069006e006b00e1006200620020006d0065006700660065006c0065006c0151002000410064006f00620065002000500044004600200064006f006b0075006d0065006e00740075006d006f006b0061007400200065007a0065006b006b0065006c0020006100200062006500e1006c006c00ed007400e10073006f006b006b0061006c0020006b00e90073007a00ed0074006800650074002e0020002000410020006c00e90074007200650068006f007a006f00740074002000500044004600200064006f006b0075006d0065006e00740075006d006f006b00200061007a0020004100630072006f006200610074002000e9007300200061007a002000410064006f00620065002000520065006100640065007200200035002e0030002c0020007600610067007900200061007a002000610074007400f3006c0020006b00e9007301510062006200690020007600650072007a006900f3006b006b0061006c0020006e00790069007400680061007400f3006b0020006d00650067002egt13 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f00740020006c00e400680069006e006e00e4002000760061006100740069007600610061006e0020007000610069006e006100740075006b00730065006e002000760061006c006d0069007300740065006c00750074007900f6006800f6006e00200073006f00700069007600690061002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a0061002e0020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt13 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 23: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

24

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN ltFEFF004b0069007600e1006c00f30020006d0069006e0151007300e9006701710020006e0079006f006d00640061006900200065006c0151006b00e90073007a00ed007401510020006e0079006f006d00740061007400e100730068006f007a0020006c006500670069006e006b00e1006200620020006d0065006700660065006c0065006c0151002000410064006f00620065002000500044004600200064006f006b0075006d0065006e00740075006d006f006b0061007400200065007a0065006b006b0065006c0020006100200062006500e1006c006c00ed007400e10073006f006b006b0061006c0020006b00e90073007a00ed0074006800650074002e0020002000410020006c00e90074007200650068006f007a006f00740074002000500044004600200064006f006b0075006d0065006e00740075006d006f006b00200061007a0020004100630072006f006200610074002000e9007300200061007a002000410064006f00620065002000520065006100640065007200200035002e0030002c0020007600610067007900200061007a002000610074007400f3006c0020006b00e9007301510062006200690020007600650072007a006900f3006b006b0061006c0020006e00790069007400680061007400f3006b0020006d00650067002egt13 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL ltFEFF0055007300740061007700690065006e0069006100200064006f002000740077006f0072007a0065006e0069006100200064006f006b0075006d0065006e007400f300770020005000440046002000700072007a0065007a006e00610063007a006f006e00790063006800200064006f002000770079006400720075006b00f30077002000770020007700790073006f006b00690065006a0020006a0061006b006f015b00630069002e002000200044006f006b0075006d0065006e0074007900200050004400460020006d006f017c006e00610020006f007400770069006500720061010700200077002000700072006f006700720061006d006900650020004100630072006f00620061007400200069002000410064006f00620065002000520065006100640065007200200035002e0030002000690020006e006f00770073007a0079006d002egt13 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 24: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

25

4 Main Menu Advanced Application SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat

App = Standard Opt = Heat Stages Cool Stages

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE ltFEFF03a703c103b703c303b903bc03bf03c003bf03b903ae03c303c403b5002003b103c503c403ad03c2002003c403b903c2002003c103c503b803bc03af03c303b503b903c2002003b303b903b1002003bd03b1002003b403b703bc03b903bf03c503c103b303ae03c303b503c403b5002003ad03b303b303c103b103c603b1002000410064006f006200650020005000440046002003c003bf03c5002003b503af03bd03b103b9002003ba03b103c42019002003b503be03bf03c703ae03bd002003ba03b103c403ac03bb03bb03b703bb03b1002003b303b903b1002003c003c103bf002d03b503ba03c403c503c003c903c403b903ba03ad03c2002003b503c103b303b103c303af03b503c2002003c503c803b703bb03ae03c2002003c003bf03b903cc03c403b703c403b103c2002e0020002003a403b10020005000440046002003ad03b303b303c103b103c603b1002003c003bf03c5002003ad03c703b503c403b5002003b403b703bc03b903bf03c503c103b303ae03c303b503b9002003bc03c003bf03c103bf03cd03bd002003bd03b1002003b103bd03bf03b903c703c403bf03cd03bd002003bc03b5002003c403bf0020004100630072006f006200610074002c002003c403bf002000410064006f00620065002000520065006100640065007200200035002e0030002003ba03b103b9002003bc03b503c403b103b303b503bd03ad03c303c403b503c103b503c2002003b503ba03b403cc03c303b503b903c2002egt13 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 25: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

26

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

4 Main Menu Advanced Application

SAT Control = Heating and Cooling

5 Main Menu Advanced Limits Check Limit Values

6 Main Menu Setpoints

Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f00730020005000440046002000640065002000410064006f0062006500200061006400650063007500610064006f00730020007000610072006100200069006d0070007200650073006900f3006e0020007000720065002d0065006400690074006f007200690061006c00200064006500200061006c00740061002000630061006c0069006400610064002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt13 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN ltFEFF004b0069007600e1006c00f30020006d0069006e0151007300e9006701710020006e0079006f006d00640061006900200065006c0151006b00e90073007a00ed007401510020006e0079006f006d00740061007400e100730068006f007a0020006c006500670069006e006b00e1006200620020006d0065006700660065006c0065006c0151002000410064006f00620065002000500044004600200064006f006b0075006d0065006e00740075006d006f006b0061007400200065007a0065006b006b0065006c0020006100200062006500e1006c006c00ed007400e10073006f006b006b0061006c0020006b00e90073007a00ed0074006800650074002e0020002000410020006c00e90074007200650068006f007a006f00740074002000500044004600200064006f006b0075006d0065006e00740075006d006f006b00200061007a0020004100630072006f006200610074002000e9007300200061007a002000410064006f00620065002000520065006100640065007200200035002e0030002c0020007600610067007900200061007a002000610074007400f3006c0020006b00e9007301510062006200690020007600650072007a006900f3006b006b0061006c0020006e00790069007400680061007400f3006b0020006d00650067002egt13 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020006d00610069007300200061006400650071007500610064006f00730020007000610072006100200070007200e9002d0069006d0070007200650073007300f50065007300200064006500200061006c007400610020007100750061006c00690064006100640065002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt13 RUM ltFEFF005500740069006c0069007a00610163006900200061006300650073007400650020007300650074010300720069002000700065006e007400720075002000610020006300720065006100200064006f00630075006d0065006e00740065002000410064006f006200650020005000440046002000610064006500630076006100740065002000700065006e0074007200750020007400690070010300720069007200650061002000700072006500700072006500730073002000640065002000630061006c006900740061007400650020007300750070006500720069006f006100720103002e002000200044006f00630075006d0065006e00740065006c00650020005000440046002000630072006500610074006500200070006f00740020006600690020006400650073006300680069007300650020006300750020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e00300020015f00690020007600650072007300690075006e0069006c006500200075006c0074006500720069006f006100720065002egt13 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 26: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

27

8 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application Constant Volume Heat Pump Configuration

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valve Check Reversing Valve Active Mode

4 Main Menu Advanced Application

Additional Setup Fan Speeds Constant Unocc On or Auto Occ On or Auto

5 Main Menu Advanced Application SAT Control = None

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA ltFEFF06270633062A062E062F0645002006470630064700200627064406250639062F0627062F0627062A002006440625064606340627062100200648062B062706260642002000410064006F00620065002000500044004600200645062A064806270641064206290020064406440637062806270639062900200641064A00200627064406450637062706280639002006300627062A0020062F0631062C0627062A002006270644062C0648062F0629002006270644063906270644064A0629061B0020064A06450643064600200641062A062D00200648062B0627062606420020005000440046002006270644064506460634062306290020062806270633062A062E062F062706450020004100630072006F0062006100740020064800410064006F006200650020005200650061006400650072002006250635062F0627063100200035002E0030002006480627064406250635062F062706310627062A0020062706440623062D062F062B002E0635062F0627063100200035002E0030002006480627064406250635062F062706310627062A0020062706440623062D062F062B002Egt13 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f0075007200200075006e00650020007100750061006c0069007400e90020006400270069006d007000720065007300730069006f006e00200070007200e9007000720065007300730065002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt13 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL ltFEFF0055007300740061007700690065006e0069006100200064006f002000740077006f0072007a0065006e0069006100200064006f006b0075006d0065006e007400f300770020005000440046002000700072007a0065007a006e00610063007a006f006e00790063006800200064006f002000770079006400720075006b00f30077002000770020007700790073006f006b00690065006a0020006a0061006b006f015b00630069002e002000200044006f006b0075006d0065006e0074007900200050004400460020006d006f017c006e00610020006f007400770069006500720061010700200077002000700072006f006700720061006d006900650020004100630072006f00620061007400200069002000410064006f00620065002000520065006100640065007200200035002e0030002000690020006e006f00770073007a0079006d002egt13 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 27: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

28

6 Main Menu Advanced Limits Check Limit Values

7 Main Menu Setpoints

Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule Setup a Schedule and Holidays

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat

App = Standard Opt = Heat Stages Cool Stages

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f00730020005000440046002000640065002000410064006f0062006500200061006400650063007500610064006f00730020007000610072006100200069006d0070007200650073006900f3006e0020007000720065002d0065006400690074006f007200690061006c00200064006500200061006c00740061002000630061006c0069006400610064002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt13 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 28: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

29

3 Main Menu Advanced Application Additional Setup Fan Speeds Variable Cooling Unocc On or Auto Occ On or Auto Check Minimum Speed

4 Main Menu Advanced Application

SAT Control = Cooling

5 Main Menu Advanced Limits

Check Limit Values

6 Main Menu Setpoints Check Setpoint Values

7 Main Menu Advanced DateTime

Check Date and Time

8 Main Menu Schedule

Setup a Schedule and Holidays

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f00730020005000440046002000640065002000410064006f0062006500200061006400650063007500610064006f00730020007000610072006100200069006d0070007200650073006900f3006e0020007000720065002d0065006400690074006f007200690061006c00200064006500200061006c00740061002000630061006c0069006400610064002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt13 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020006d00610069007300200061006400650071007500610064006f00730020007000610072006100200070007200e9002d0069006d0070007200650073007300f50065007300200064006500200061006c007400610020007100750061006c00690064006100640065002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt13 RUM 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 RUS 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 SKY ltFEFF0054006900650074006f0020006e006100730074006100760065006e0069006100200070006f0075017e0069007400650020006e00610020007600790074007600e100720061006e0069006500200064006f006b0075006d0065006e0074006f0076002000410064006f006200650020005000440046002c0020006b0074006f007200e90020007300610020006e0061006a006c0065007001610069006500200068006f0064006900610020006e00610020006b00760061006c00690074006e00fa00200074006c0061010d00200061002000700072006500700072006500730073002e00200056007900740076006f00720065006e00e900200064006f006b0075006d0065006e007400790020005000440046002000620075006400650020006d006f017e006e00e90020006f00740076006f00720069016500200076002000700072006f006700720061006d006f006300680020004100630072006f00620061007400200061002000410064006f00620065002000520065006100640065007200200035002e0030002000610020006e006f0076016100ed00630068002egt13 SLV 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f00740020006c00e400680069006e006e00e4002000760061006100740069007600610061006e0020007000610069006e006100740075006b00730065006e002000760061006c006d0069007300740065006c00750074007900f6006800f6006e00200073006f00700069007600690061002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a0061002e0020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt13 SVE 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 TUR ltFEFF005900fc006b00730065006b0020006b0061006c006900740065006c0069002000f6006e002000790061007a006401310072006d00610020006200610073006b013100730131006e006100200065006e0020006900790069002000750079006100620069006c006500630065006b002000410064006f006200650020005000440046002000620065006c00670065006c0065007200690020006f006c0075015f007400750072006d0061006b0020006900e70069006e00200062007500200061007900610072006c0061007201310020006b0075006c006c0061006e0131006e002e00200020004f006c0075015f0074007500720075006c0061006e0020005000440046002000620065006c00670065006c0065007200690020004100630072006f006200610074002000760065002000410064006f00620065002000520065006100640065007200200035002e003000200076006500200073006f006e0072006100730131006e00640061006b00690020007300fc007200fc006d006c00650072006c00650020006100e70131006c006100620069006c00690072002egt13 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 29: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

30

1 Main Menu Advanced Application

Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat

App = Heat Pump Opt = Compressor Stages with or without Emergency Heat

2 Main Menu Advanced Application Additional Setup Sensors OAT Sensor = Yes SAT Sensor = Yes

3 Main Menu Advanced Application Additional Setup Valves Check Reversing Valve Active Mode

4 Main Menu Advanced Application Additional Setup Fan Speeds Variable Heating and Cooling Unocc On or Auto Occ On or Auto Check Minimum Speeds

5 Main Menu Advanced Application

SAT Control = Heating and Cooling

6 Main Menu Advanced Limits

Check Limit Values

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH ltFEFF004e006100750064006f006b0069007400650020016100690075006f007300200070006100720061006d006500740072007500730020006e006f0072011700640061006d00690020006b0075007200740069002000410064006f00620065002000500044004600200064006f006b0075006d0065006e007400750073002c0020006b00750072006900650020006c0061006200690061007500730069006100690020007000720069007400610069006b007900740069002000610075006b01610074006f00730020006b006f006b007900620117007300200070006100720065006e006700740069006e00690061006d00200073007000610075007300640069006e0069006d00750069002e0020002000530075006b0075007200740069002000500044004600200064006f006b0075006d0065006e007400610069002000670061006c006900200062016b007400690020006100740069006400610072006f006d00690020004100630072006f006200610074002000690072002000410064006f00620065002000520065006100640065007200200035002e0030002000610072002000760117006c00650073006e0117006d00690073002000760065007200730069006a006f006d00690073002egt13 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR ltFEFF04120438043a043e0440043804410442043e043204430439044204350020044604560020043f043004400430043c043504420440043800200434043b044f0020044104420432043e04400435043d043d044f00200434043e043a0443043c0435043d044204560432002000410064006f006200650020005000440046002c0020044f043a04560020043d04300439043a04400430044904350020043f045604340445043e0434044f0442044c00200434043b044f0020043204380441043e043a043e044f043a04560441043d043e0433043e0020043f0435044004350434043404400443043a043e0432043e0433043e0020043404400443043a0443002e00200020042104420432043e04400435043d045600200434043e043a0443043c0435043d0442043800200050004400460020043c043e0436043d04300020043204560434043a0440043804420438002004430020004100630072006f006200610074002004420430002000410064006f00620065002000520065006100640065007200200035002e0030002004300431043e0020043f04560437043d04560448043e04570020043204350440044104560457002egt13 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 30: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

31

7 Main Menu Setpoints Check Setpoint Values

8 Main Menu Advanced DateTime

Check Date and Time

9 Main Menu Schedule

Setup a Schedule and Holidays

Mini Controller with space humidity sensor (R80580) and WattMaster Modulating Hot Gas Reheat Board are required for humidity control

Modulating Hot Gas Reheat

1 Main Menu Advanced Application

Additional Setup Sensors Configure Suction Pressure Sensor

2 Main Menu Advanced Application

Additional Setup Humidity Dehumidification Setup Dehumidification

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY ltFEFF0054006900650074006f0020006e006100730074006100760065006e0069006100200070006f0075017e0069007400650020006e00610020007600790074007600e100720061006e0069006500200064006f006b0075006d0065006e0074006f0076002000410064006f006200650020005000440046002c0020006b0074006f007200e90020007300610020006e0061006a006c0065007001610069006500200068006f0064006900610020006e00610020006b00760061006c00690074006e00fa00200074006c0061010d00200061002000700072006500700072006500730073002e00200056007900740076006f00720065006e00e900200064006f006b0075006d0065006e007400790020005000440046002000620075006400650020006d006f017e006e00e90020006f00740076006f00720069016500200076002000700072006f006700720061006d006f006300680020004100630072006f00620061007400200061002000410064006f00620065002000520065006100640065007200200035002e0030002000610020006e006f0076016100ed00630068002egt13 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 31: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

32

3 Main Menu Setpoints Check Humidity Control Setpoint Values

4 Setup Supply Air Temperature Setpoint on WattMaster Modulating Hot Gas Reheat Board

1 Main Menu Advanced Application Additional Setup Sensors

Economizer

Configure OA Humidity Sensor if Enthalpy Controlled

2 Main Menu Advanced Application

Additional Setup Damper Setup Modulating Economizer Damper and Check Setpoint Values

3 Main Menu Advanced Application Additional Setup Damper Setup Economizer Damper Control Factory Provided Actuators are 2-10V

4 Main Menu Advanced Application

Additional Setup Damper Enable Enthalpy Economizer if Enthalpy Controlled

1 Main Menu Advanced Application Additional Setup Sensors

CO2 Override

Configure OA Humidity Sensor

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI ltFEFF004b00610073007500740061006700650020006e0065006900640020007300e4007400740065006900640020006b00760061006c006900740065006500740073006500200074007200fc006b006900650065006c007300650020007000720069006e00740069006d0069007300650020006a0061006f006b007300200073006f00620069006c0069006b0065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740069006400650020006c006f006f006d006900730065006b0073002e00200020004c006f006f0064007500640020005000440046002d0064006f006b0075006d0065006e00740065002000730061006100740065002000610076006100640061002000700072006f006700720061006d006d006900640065006700610020004100630072006f0062006100740020006e0069006e0067002000410064006f00620065002000520065006100640065007200200035002e00300020006a00610020007500750065006d006100740065002000760065007200730069006f006f006e00690064006500670061002e000d000agt13 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020006d00610069007300200061006400650071007500610064006f00730020007000610072006100200070007200e9002d0069006d0070007200650073007300f50065007300200064006500200061006c007400610020007100750061006c00690064006100640065002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt13 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR ltFEFF04120438043a043e0440043804410442043e043204430439044204350020044604560020043f043004400430043c043504420440043800200434043b044f0020044104420432043e04400435043d043d044f00200434043e043a0443043c0435043d044204560432002000410064006f006200650020005000440046002c0020044f043a04560020043d04300439043a04400430044904350020043f045604340445043e0434044f0442044c00200434043b044f0020043204380441043e043a043e044f043a04560441043d043e0433043e0020043f0435044004350434043404400443043a043e0432043e0433043e0020043404400443043a0443002e00200020042104420432043e04400435043d045600200434043e043a0443043c0435043d0442043800200050004400460020043c043e0436043d04300020043204560434043a0440043804420438002004430020004100630072006f006200610074002004420430002000410064006f00620065002000520065006100640065007200200035002e0030002004300431043e0020043f04560437043d04560448043e04570020043204350440044104560457002egt13 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 32: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

33

2 Main Menu Setpoints Check CO2 Setpoint Value

1 Main Menu Advanced Application Additional Setup Sensors

Remote Space Temperature

Configure Remote Space Temperature Sensor or Configure Remote Space Temperature Sensor Averaging

1 Main Menu Advanced Application Additional Setup Sensor

Fan Status

Configure Fan Status Sensor

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f00730020005000440046002000640065002000410064006f0062006500200061006400650063007500610064006f00730020007000610072006100200069006d0070007200650073006900f3006e0020007000720065002d0065006400690074006f007200690061006c00200064006500200061006c00740061002000630061006c0069006400610064002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt13 ETI 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 FRA 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 GRE ltFEFF03a703c103b703c303b903bc03bf03c003bf03b903ae03c303c403b5002003b103c503c403ad03c2002003c403b903c2002003c103c503b803bc03af03c303b503b903c2002003b303b903b1002003bd03b1002003b403b703bc03b903bf03c503c103b303ae03c303b503c403b5002003ad03b303b303c103b103c603b1002000410064006f006200650020005000440046002003c003bf03c5002003b503af03bd03b103b9002003ba03b103c42019002003b503be03bf03c703ae03bd002003ba03b103c403ac03bb03bb03b703bb03b1002003b303b903b1002003c003c103bf002d03b503ba03c403c503c003c903c403b903ba03ad03c2002003b503c103b303b103c303af03b503c2002003c503c803b703bb03ae03c2002003c003bf03b903cc03c403b703c403b103c2002e0020002003a403b10020005000440046002003ad03b303b303c103b103c603b1002003c003bf03c5002003ad03c703b503c403b5002003b403b703bc03b903bf03c503c103b303ae03c303b503b9002003bc03c003bf03c103bf03cd03bd002003bd03b1002003b103bd03bf03b903c703c403bf03cd03bd002003bc03b5002003c403bf0020004100630072006f006200610074002c002003c403bf002000410064006f00620065002000520065006100640065007200200035002e0030002003ba03b103b9002003bc03b503c403b103b303b503bd03ad03c303c403b503c103b503c2002003b503ba03b403cc03c303b503b903c2002egt13 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS ltFEFF04180441043f043e043b044c04370443043904420435002004340430043d043d044b04350020043d0430044104420440043e0439043a043800200434043b044f00200441043e043704340430043d0438044f00200434043e043a0443043c0435043d0442043e0432002000410064006f006200650020005000440046002c0020043c0430043a04410438043c0430043b044c043d043e0020043f043e04340445043e0434044f04490438044500200434043b044f00200432044b0441043e043a043e043a0430044704350441044204320435043d043d043e0433043e00200434043e043f0435044704300442043d043e0433043e00200432044b0432043e04340430002e002000200421043e043704340430043d043d044b04350020005000440046002d0434043e043a0443043c0435043d0442044b0020043c043e0436043d043e0020043e0442043a0440044b043204300442044c002004410020043f043e043c043e0449044c044e0020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200431043e043b043504350020043f043e04370434043d043804450020043204350440044104380439002egt13 SKY 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 SLV 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400200073006f006d002000e400720020006c00e4006d0070006c0069006700610020006600f60072002000700072006500700072006500730073002d007500740073006b00720069006600740020006d006500640020006800f600670020006b00760061006c0069007400650074002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt13 TUR 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 UKR ltFEFF04120438043a043e0440043804410442043e043204430439044204350020044604560020043f043004400430043c043504420440043800200434043b044f0020044104420432043e04400435043d043d044f00200434043e043a0443043c0435043d044204560432002000410064006f006200650020005000440046002c0020044f043a04560020043d04300439043a04400430044904350020043f045604340445043e0434044f0442044c00200434043b044f0020043204380441043e043a043e044f043a04560441043d043e0433043e0020043f0435044004350434043404400443043a043e0432043e0433043e0020043404400443043a0443002e00200020042104420432043e04400435043d045600200434043e043a0443043c0435043d0442043800200050004400460020043c043e0436043d04300020043204560434043a0440043804420438002004430020004100630072006f006200610074002004420430002000410064006f00620065002000520065006100640065007200200035002e0030002004300431043e0020043f04560437043d04560448043e04570020043204350440044104560457002egt13 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 33: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

34

Operation Unit operations should be controlled with the controller never at the main power supply except for servicing emergency or complete shutdown of the unit

Single or Two Stage Cooling

Stage 1 - Variable Capacity Scroll Compressor Stage 2 - Single Stage Compressor RNRQ - Unit Size = 3-25 or 30 tons RNRQ - Refrigerant Style = E F RNRQ - Unit Configuration = A B J K 6 7 RNRQ - Model Option A4 - CoolingHeat Pump Staging = 9 A

0 1 2 or 3 Stages or ModulatingSCR Gas or Electric Heat

Heating

RNRQ - Model Option B1 - Heating Type = 0 1 2 3 4 5 6 7 8 9 RNRQ - Model Option B3 - Heating Stages = 0 1 2 3 9

Manual Outside Air Opening Motorized Outside Air Damper Economizer and CO2 Override

Return AirOutside Air Section

RNRQ - Feature 1A - ReturnOutside Air Section = 0 A B C F G H J L N P Q R S T U V W Y Z 1 2 3 5 RNRQ - Feature 2 - Outside Air Control = 0 C D E P R

Standard or Modulating Hot Gas Reheat Refrigeration Options

RNRQ - Feature 8 - Refrigeration Controls = 0 A B C D E F G H J K L M N

Constant Volume Constant Volume Heat Pump Single Zone VAV - VAV Cool + CV Heat Single Zone VAV - VAV Cool + VAV Heat or Single Zone VAV Heat Pump - VAV Cool + VAV Heat

Controls

RNRQ - Feature 13 - Special Controls = E Y Z 2 3 RNRQ - Feature 22 - Control Vendors = E

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint the variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling space temperature setpoint

Constant Volume Cooling Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for a compressor stage delay amount of time and the space temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling space temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the cooling space temperature setpoint

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE ltFEFF005400610074006f0020006e006100730074006100760065006e00ed00200070006f0075017e0069006a007400650020006b0020007600790074007600e101590065006e00ed00200064006f006b0075006d0065006e0074016f002000410064006f006200650020005000440046002c0020006b00740065007200e90020007300650020006e0065006a006c00e90070006500200068006f006400ed002000700072006f0020006b00760061006c00690074006e00ed0020007400690073006b00200061002000700072006500700072006500730073002e002000200056007900740076006f01590065006e00e900200064006f006b0075006d0065006e007400790020005000440046002000620075006400650020006d006f017e006e00e90020006f007400650076015900ed007400200076002000700072006f006700720061006d0065006300680020004100630072006f00620061007400200061002000410064006f00620065002000520065006100640065007200200035002e0030002000610020006e006f0076011b006a016100ed00630068002egt13 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 34: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

35

As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband above the cooling space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor is activated at 100 for one minute The compressor then modulates to maintain the cooling supply air temperature setpoint

Single Zone VAV Cooling Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the cooling mode of operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage cooling if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the supply air temperature is increasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint For units with two stage cooling if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the cooling supply air temperature is decreasing the second compressor is de-activated The variable capacity scroll compressor modulates to maintain the cooling supply air temperature setpoint As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband supply air temperature control is de-activated and

the variable capacity scroll compressor is de-activated

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the first stage of heating is activated

Constant Volume Heating Operation - Space Temperature Control

If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time if available the second stage of heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time if available the third stage of heating is activated When the space temperature reaches the heating space temperature setpoint the third stage of heating if available is de-activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second stages of heating are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI ltFEFF0049007a006d0061006e0074006f006a00690065007400200161006f00730020006900650073007400610074012b006a0075006d00750073002c0020006c0061006900200076006500690064006f00740075002000410064006f00620065002000500044004600200064006f006b0075006d0065006e007400750073002c0020006b006100730020006900720020012b00700061016100690020007000690065006d01130072006f00740069002000610075006700730074006100730020006b00760061006c0069007401010074006500730020007000690072006d007300690065007300700069006501610061006e006100730020006400720075006b00610069002e00200049007a0076006500690064006f006a006900650074002000500044004600200064006f006b0075006d0065006e007400750073002c0020006b006f002000760061007200200061007400760113007200740020006100720020004100630072006f00620061007400200075006e002000410064006f00620065002000520065006100640065007200200035002e0030002c0020006b0101002000610072012b00200074006f0020006a00610075006e0101006b0101006d002000760065007200730069006a0101006d002egt13 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 35: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

36

supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The first stage of heating modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heating Operation - Supply Air Temperature Control

As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband the first and second heating stages are de-activated ModulatingSCR electric heating operates as a single stage of heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint the variable capacity scroll compressor is activated The compressor modulates to maintain the heating space temperature setpoint

Constant Volume Heat Pump Heating Operation - Space Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of

operation all reversing valves are activated along with the variable capacity scroll compressor For units with two stage heat pump heating if the variable capacity scroll compressor operates at a maximum capacity for the compressor stage delay amount of time and the space temperature is still decreasing the second compressor is activated and the variable capacity scroll compressor modulates to maintain the heating space temperature setpoint For units with two stage heat pump heating if the variable capacity scroll compressor operates at a minimum capacity for the compressor stage delay amount of time and the space temperature is increasing the second compressor is de-activated The variable capacity scroll compressor then modulates to maintain the heating space temperature setpoint As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband heat pump heating de-activated If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the space temperature remains frac12 of the space temperature deadband below the heating space temperature setpoint for another heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200073006f006d00200065007200200062006500730074002000650067006e0065007400200066006f00720020006600f80072007400720079006b006b0073007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c0069007400650074002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt13 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400200073006f006d002000e400720020006c00e4006d0070006c0069006700610020006600f60072002000700072006500700072006500730073002d007500740073006b00720069006600740020006d006500640020006800f600670020006b00760061006c0069007400650074002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt13 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 36: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

37

the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

When the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint supply air temperature control is activated The variable capacity scroll compressor modulates to maintain the heating supply air temperature setpoint

Single Zone VAV Heat Pump Heating Operation - Supply Air Temperature Control

For heat pump units with the controller configured for the reversing valve to be activated during the heating mode of operation all reversing valves are activated along with the variable capacity scroll compressor As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband supply air temperature control is de-activated and heat pump heating de-activated

If the space temperature has deviated frac12 of the space temperature deadband below the heating space temperature setpoint and the outside air temperature is below the compressor outside air temperature lockout if available the first stage of emergency heating is activated If the supply air temperature is decreasing below the heating supply air temperature setpoint for the heating stage delay amount of time and the outside air temperature is below the compressor outside air temperature lockout if available the second stage of emergency heating is activated As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature deadband and the outside air temperature remains below the compressor outside air temperature lockout the emergency heating stages are de-activated ModulatingSCR electric heating operates as a single stage of auxiliaryemergency heating Heating elements modulate using a supply air temperature sensor and setpoint potentiometer to meet a specific supply air temperature setpoint Modulating natural gas heating operates as a single stage of auxiliaryemergency heating Supply air temperature setpoint must be set on the MODGAS board See WattMaster MODGAS Controller manual for modulating gas heat operation Equipment with Modulating GasSCR Electric Heat will require an additional supply air temperature sensor be field installed for the modulating heating controls

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is

Constant Volume Supply Fan

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB ltFEFF05D405E905EA05DE05E905D5002005D105D405D205D305E805D505EA002005D005DC05D4002005DB05D305D9002005DC05D905E605D505E8002005DE05E105DE05DB05D9002000410064006F006200650020005000440046002005D405DE05D505EA05D005DE05D905DD002005DC05D405D305E405E105EA002005E705D305DD002D05D305E405D505E1002005D005D905DB05D505EA05D905EA002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002E05D005DE05D905DD002005DC002D005000440046002F0058002D0033002C002005E205D905D905E005D5002005D105DE05D305E805D905DA002005DC05DE05E905EA05DE05E9002005E905DC0020004100630072006F006200610074002E002005DE05E105DE05DB05D90020005000440046002005E905E005D505E605E805D5002005E005D905EA05E005D905DD002005DC05E405EA05D905D705D4002005D105D005DE05E605E205D505EA0020004100630072006F006200610074002005D5002D00410064006F00620065002000520065006100640065007200200035002E0030002005D505D205E805E105D005D505EA002005DE05EA05E705D305DE05D505EA002005D905D505EA05E8002Egt13 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS ltFEFF04180441043f043e043b044c04370443043904420435002004340430043d043d044b04350020043d0430044104420440043e0439043a043800200434043b044f00200441043e043704340430043d0438044f00200434043e043a0443043c0435043d0442043e0432002000410064006f006200650020005000440046002c0020043c0430043a04410438043c0430043b044c043d043e0020043f043e04340445043e0434044f04490438044500200434043b044f00200432044b0441043e043a043e043a0430044704350441044204320435043d043d043e0433043e00200434043e043f0435044704300442043d043e0433043e00200432044b0432043e04340430002e002000200421043e043704340430043d043d044b04350020005000440046002d0434043e043a0443043c0435043d0442044b0020043c043e0436043d043e0020043e0442043a0440044b043204300442044c002004410020043f043e043c043e0449044c044e0020004100630072006f00620061007400200438002000410064006f00620065002000520065006100640065007200200035002e00300020043800200431043e043b043504350020043f043e04370434043d043804450020043204350440044104380439002egt13 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 37: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

38

selectable for both occupied and unoccupied modes of operation The supply fan will be constant speed with any speed controller input (VFD or ECM) wired for constant speedconstant volume operation

Supply fan operation is selectable between ldquoAutordquo and ldquoOnrdquo The supply fan will either cycle with coolingheating operation (Auto) or operate continuously (On) The setting is selectable for both occupied and unoccupied modes of operation

Single Zone VAV Supply Fan

As the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint the supply fan will be activated and operate at the cooling minimum speed As the space temperature increases the supply fan will increase in speed to the cooling maximum speed delivering more cool air As the space temperature decreases toward the cooling space temperature setpoint the supply fan will decrease in speed delivering less cool air As the space temperature reaches the cooling space temperature setpoint the supply fan will operate at cooling minimum speed As the space temperature achieves the cooling space temperature setpoint minus frac12 of the space temperature deadband the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) As the space temperature deviates frac12 of the space temperature deadband below the space heating setpoint the supply fan will be activated and operate at the heating minimum speed As the space temperature decreases the supply fan will increase in speed to the heating maximum speed delivering more hot air As the space temperature increases toward the heating space temperature setpoint the supply fan will decrease in speed delivering less hot air

As the space temperature reaches the heating space temperature setpoint the supply fan will operate at heating minimum speed As the space temperature achieves the heating space temperature setpoint plus frac12 of the space temperature the supply fan is de-activated (Auto) or operates at the cooling minimum speed (On) During the dehumidification mode of operation the supply fan will operate at the constant dehumidification speed

If the space temperature deviates frac12 of the space temperature deadband above the space cooling setpoint and the outside air temperature is below the economizer enable temperature setpoint the unit will use outside air to cool the space

Economizer

If the controller is enabled for enthalpy controlled economizer the outside air enthalpy must be below 25 Btulb before the economizer will be activated For constant volume systems if the outside air temperature is below 50degF the economizer will modulate to maintain 55degF supply air temperature For single zone VAV systems if the outside air temperature is below the cooling supply air temperature setpoint the economizer will modulate to maintain the cooling supply air temperature setpoint Minimum damper position setpoint compressor low limit setpoint and low supply air temperature setpoint are required The economizer control is used only for occupied cooling If the economizer control does not satisfy the space within three concurrent compressor stage delays mechanical cooling will be activated

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP ltFEFF005500740069006c0069006300650020006500730074006100200063006f006e0066006900670075007200610063006900f3006e0020007000610072006100200063007200650061007200200064006f00630075006d0065006e0074006f00730020005000440046002000640065002000410064006f0062006500200061006400650063007500610064006f00730020007000610072006100200069006d0070007200650073006900f3006e0020007000720065002d0065006400690074006f007200690061006c00200064006500200061006c00740061002000630061006c0069006400610064002e002000530065002000700075006500640065006e00200061006200720069007200200064006f00630075006d0065006e0074006f00730020005000440046002000630072006500610064006f007300200063006f006e0020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e003000200079002000760065007200730069006f006e0065007300200070006f00730074006500720069006f007200650073002egt13 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f00620065002000500044004600200070006900f900200061006400610074007400690020006100200075006e00610020007000720065007300740061006d0070006100200064006900200061006c007400610020007100750061006c0069007400e0002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt13 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV ltFEFF005400650020006e006100730074006100760069007400760065002000750070006f0072006100620069007400650020007a00610020007500730074007600610072006a0061006e006a006500200064006f006b0075006d0065006e0074006f0076002000410064006f006200650020005000440046002c0020006b006900200073006f0020006e0061006a007000720069006d00650072006e0065006a016100690020007a00610020006b0061006b006f0076006f00730074006e006f0020007400690073006b0061006e006a00650020007300200070007200690070007200610076006f0020006e00610020007400690073006b002e00200020005500730074007600610072006a0065006e006500200064006f006b0075006d0065006e0074006500200050004400460020006a00650020006d006f0067006f010d00650020006f0064007000720065007400690020007a0020004100630072006f00620061007400200069006e002000410064006f00620065002000520065006100640065007200200035002e003000200069006e0020006e006f00760065006a01610069006d002egt13 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 38: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

39

When the space relative humidity rises above the space relativity humidity setpoint the cooling stages will be activated and modulate to maintain the suction pressure setpoint If the space temperature deviates below the space cooling setpoint minus frac12 of the space temperature deadband the reheat relay is activated

Dehumidification

The dehumidification priority determines whether or not Dehumidification Mode takes priority over Heating and Cooling Modes Default is False If set to True Dehumidification Mode will enable any time the space humidity rises above the dehumidification setpoints regardless of the current mode at that time If set to False Dehumidification Mode will enable only when the space heating and cooling setpoints are satisfied (ie vent mode if FAN OCC = ON) and the space humidity has risen above the dehumidification setpoints See WattMaster MHGRV Controller manual for modulating hot gas reheat operation Equipment with Modulating Hot Gas Reheat will require an additional supply air temperature sensor be field installed for the modulating reheat controls

As the CO2 ppm increases above the CO2 setpoint the economizer outside air damper position increases proportionally to increase ventilation to the space As the CO2 ppm decreases toward the CO2 setpoint the economizer outside air damper decreases proportionally toward the minimum outside air damper position Compressor lockout and economizer supply air low limit have priority over CO2 override and CO2 override has priority over the economizer control

CO2 Economizer Override

Note CO2 Override requires a field installed CO2 sensor

Option is used to average the space temperature with the controllerrsquos internal space temperature sensor and a remote space temperature sensor for space temperature control

Remote Averaging Space Temperature

Option is used to disable the controllerrsquos space temperature sensor and only use a remote space temperature sensor for space temperature control

Remote Space Temperature

Option is used to confirm the operation of the supply fans An alarm will be activated if fan operation cannot be confirmed

Fan Status

Note Because of the AAON Mini Controllerrsquos limited number of inputs only one of the following options is available with a single controller Dehumidification Enthalpy Controlled Economizer CO2 Override Remote Averaging Space Temperature Remote Space Temperature or Fan Status

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU ltFEFF00560065007200770065006e00640065006e0020005300690065002000640069006500730065002000450069006e007300740065006c006c0075006e00670065006e0020007a0075006d002000450072007300740065006c006c0065006e00200076006f006e002000410064006f006200650020005000440046002d0044006f006b0075006d0065006e00740065006e002c00200076006f006e002000640065006e0065006e002000530069006500200068006f006300680077006500720074006900670065002000500072006500700072006500730073002d0044007200750063006b0065002000650072007a0065007500670065006e0020006d00f60063006800740065006e002e002000450072007300740065006c006c007400650020005000440046002d0044006f006b0075006d0065006e007400650020006b00f6006e006e0065006e0020006d006900740020004100630072006f00620061007400200075006e0064002000410064006f00620065002000520065006100640065007200200035002e00300020006f0064006500720020006800f600680065007200200067006500f600660066006e00650074002000770065007200640065006e002egt13 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200073006f006d00200065007200200062006500730074002000650067006e0065007400200066006f00720020006600f80072007400720079006b006b0073007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c0069007400650074002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt13 POL 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 PTB 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 RUM ltFEFF005500740069006c0069007a00610163006900200061006300650073007400650020007300650074010300720069002000700065006e007400720075002000610020006300720065006100200064006f00630075006d0065006e00740065002000410064006f006200650020005000440046002000610064006500630076006100740065002000700065006e0074007200750020007400690070010300720069007200650061002000700072006500700072006500730073002000640065002000630061006c006900740061007400650020007300750070006500720069006f006100720103002e002000200044006f00630075006d0065006e00740065006c00650020005000440046002000630072006500610074006500200070006f00740020006600690020006400650073006300680069007300650020006300750020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e00300020015f00690020007600650072007300690075006e0069006c006500200075006c0074006500720069006f006100720065002egt13 RUS 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 SKY ltFEFF0054006900650074006f0020006e006100730074006100760065006e0069006100200070006f0075017e0069007400650020006e00610020007600790074007600e100720061006e0069006500200064006f006b0075006d0065006e0074006f0076002000410064006f006200650020005000440046002c0020006b0074006f007200e90020007300610020006e0061006a006c0065007001610069006500200068006f0064006900610020006e00610020006b00760061006c00690074006e00fa00200074006c0061010d00200061002000700072006500700072006500730073002e00200056007900740076006f00720065006e00e900200064006f006b0075006d0065006e007400790020005000440046002000620075006400650020006d006f017e006e00e90020006f00740076006f00720069016500200076002000700072006f006700720061006d006f006300680020004100630072006f00620061007400200061002000410064006f00620065002000520065006100640065007200200035002e0030002000610020006e006f0076016100ed00630068002egt13 SLV 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f00740020006c00e400680069006e006e00e4002000760061006100740069007600610061006e0020007000610069006e006100740075006b00730065006e002000760061006c006d0069007300740065006c00750074007900f6006800f6006e00200073006f00700069007600690061002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a0061002e0020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt13 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 39: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

40

BACnet Points List Table 4 - Analog Values

Object ReadWrite Description Default Min Max AV1 RW Min Space Temp Setpoint Diff 2degF 1degF 15degF AV2 R Active Cooling Setpoint - - - AV3 R Active Heating Setpoint - - - AV4 RW Unocc Cooling Setpoint 80degF 55degF 90degF AV5 RW Unocc Heating Setpoint 64degF 55degF 90degF AV6 RW Deadband 2degF 1degF 15degF AV7 RW Occ Min Cooling Setpoint 68degF 55degF 90degF AV8 RW Occ Max Heating Setpoint 72degF 55degF 90degF AV9 RW Cooling Supply Air Setpoint 55degF 50degF 70degF AV10 RW Econ Min OA Damper Pos 10 0 95 AV11 RW Econ OA Temp Enable 60degF 50degF 70degF AV12 RW Compressor Stage Delay 3 min 2 min 15 min AV13 RW Fan Shutoff Delay 180 sec 0 sec 600 sec AV14 RW Heat Stage Delay 3 min 3 min 60 min AV15 RW Dehumidification Setpoint 50 20 85 AV16 RW Override Timer 1 hour 0 hour 12 hour AV17 RW Compressor OA Temp Lockout 40degF 0degF 50degF AV18 RW Economizer SA Low Limit 40degF 0degF 100degF AV19 RW CO2 Setpoint 1100 ppm 500 ppm 1800 ppm AV20 RW Occ Cooling Setpoint 74degF 55degF 90degF AV21 RW Occ Heating Setpoint 70degF 55degF 90degF AV22 R Space Humidity - - - AV23 R Outside Air Temp - - - AV24 R Supply Air Temp - - - AV25 R Configurable Input - AI2 - - - AV26 R Current Mode Setpoint - - - AV27 R UI Setpoint - - - AV28 RW Dehumidification Deadband 5 5 15 AV29 RW Cooling Loop P 2 050 1000 AV30 RW Cooling Loop I 01 001 100 AV31 RW Unocc Min Cooling Setpoint 68degF 55degF 90degF AV32 RW Unocc Max Heating Setpoint 72degF 55degF 90degF AV33 RW Minimum Setpoint Differential 2degF 1degF 15degF AV34 RW Minimum Setpoint Limit 2degF 1degF 15degF AV35 RW Heating Loop P 2 050 1000 AV36 RW Heating Loop I 01 001 100 AV37 RW Economizer Loop P 2 050 1000 AV38 RW Economizer Loop I 01 001 100 AV40 R UI Display Space Temerature - - - AV41 RW Min Digital Comp Setpoint 50 20 80 AV42 RW Max Digital Comp Setpoint 100 5gtmin 100

AV43 RW Cool Supply Fan Min Speed

Setpoint 30 30 80 Through version R12210 these are only accessible through BACnet

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA ltFEFF06270633062A062E062F0645002006470630064700200627064406250639062F0627062F0627062A002006440625064606340627062100200648062B062706260642002000410064006F00620065002000500044004600200645062A064806270641064206290020064406440637062806270639062900200641064A00200627064406450637062706280639002006300627062A0020062F0631062C0627062A002006270644062C0648062F0629002006270644063906270644064A0629061B0020064A06450643064600200641062A062D00200648062B0627062606420020005000440046002006270644064506460634062306290020062806270633062A062E062F062706450020004100630072006F0062006100740020064800410064006F006200650020005200650061006400650072002006250635062F0627063100200035002E0030002006480627064406250635062F062706310627062A0020062706440623062D062F062B002E0635062F0627063100200035002E0030002006480627064406250635062F062706310627062A0020062706440623062D062F062B002Egt13 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020006d00610069007300200061006400650071007500610064006f00730020007000610072006100200070007200e9002d0069006d0070007200650073007300f50065007300200064006500200061006c007400610020007100750061006c00690064006100640065002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt13 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 40: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

41

Table 5 - Analog Values Continued

AV44 RW Cool Supply Fan Max Speed

Setpoint 100 50 100 AV45 RW Dehum Suction PSI Setpoint 1194 psi 50 psi 250 psi AV46 RW Dehum Fan Speed Setpoint 50 25 75 AV47 RW Unocc Dehum Setpoint 65 20 85 AV48 RW SAT Low Limit Alarm 40degF 32degF 60degF

AV49 RW Heat Supply Fan Min Speed

Setpoint 5075 50 100

AV50 RW Heat Supply Fan Max Speed

Setpoint 100 gtMin 100 AV51 RW Heating Supply Air Temp Setpoint 120degF 75degF 200degF AV52 RW Heating OAT High Limit 70degF 50degF 150degF AV53 RW SAT High Limit Alarm 200degF 120degF 250degF AV54 - Not Used - - - AV55 RW Occ Min Heating Setpoint 65degF 53degF 90degF AV56 RW Occ Max Cooling Setpoint 78degF 55degF 92degF AV57 RW OAT Low Limit 150degF 110degF 160degF AV58 RW OAT High Limit -40degF -50degF 40degF AV59 - Not Used - - - AV60 - Not Used - - -

Table 6 - Relay Values

Object ReadWrite Description BV1 R Occupancy Mode BV2 R Setpoint Override Mode BV3 R Economizer Mode

BV4 R Economizer SA Temp Low

Limit BV5 R Fan Alarm BV6 R Fan Need BV7 R HeatingCooling Mode BV8 R Compressor Lockout BV12 RW Occ Fan AutoOn BV13 RW Unocc Fan AutoOn BV14 RW degFdegC BV15 RW Reversing Valve Polarity BV16 R Fan Status BV17 R Backlight Control BV18 R UI Fan Icon BV21 R Dehum Mode Active BV24 R Occ Sensor Override Enable BV31 RW Dehum Priority BV36 R Allow Econ Cooling BV37 R Comp 1 OnOff BV38 R OAT Sensor Installed BV39 R SAT Sensor Installed BV40 R Econ with Enthalpy

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200073006f006d00200065007200200062006500730074002000650067006e0065007400200066006f00720020006600f80072007400720079006b006b0073007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c0069007400650074002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt13 POL ltFEFF0055007300740061007700690065006e0069006100200064006f002000740077006f0072007a0065006e0069006100200064006f006b0075006d0065006e007400f300770020005000440046002000700072007a0065007a006e00610063007a006f006e00790063006800200064006f002000770079006400720075006b00f30077002000770020007700790073006f006b00690065006a0020006a0061006b006f015b00630069002e002000200044006f006b0075006d0065006e0074007900200050004400460020006d006f017c006e00610020006f007400770069006500720061010700200077002000700072006f006700720061006d006900650020004100630072006f00620061007400200069002000410064006f00620065002000520065006100640065007200200035002e0030002000690020006e006f00770073007a0079006d002egt13 PTB 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 RUM ltFEFF005500740069006c0069007a00610163006900200061006300650073007400650020007300650074010300720069002000700065006e007400720075002000610020006300720065006100200064006f00630075006d0065006e00740065002000410064006f006200650020005000440046002000610064006500630076006100740065002000700065006e0074007200750020007400690070010300720069007200650061002000700072006500700072006500730073002000640065002000630061006c006900740061007400650020007300750070006500720069006f006100720103002e002000200044006f00630075006d0065006e00740065006c00650020005000440046002000630072006500610074006500200070006f00740020006600690020006400650073006300680069007300650020006300750020004100630072006f006200610074002c002000410064006f00620065002000520065006100640065007200200035002e00300020015f00690020007600650072007300690075006e0069006c006500200075006c0074006500720069006f006100720065002egt13 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR ltFEFF005900fc006b00730065006b0020006b0061006c006900740065006c0069002000f6006e002000790061007a006401310072006d00610020006200610073006b013100730131006e006100200065006e0020006900790069002000750079006100620069006c006500630065006b002000410064006f006200650020005000440046002000620065006c00670065006c0065007200690020006f006c0075015f007400750072006d0061006b0020006900e70069006e00200062007500200061007900610072006c0061007201310020006b0075006c006c0061006e0131006e002e00200020004f006c0075015f0074007500720075006c0061006e0020005000440046002000620065006c00670065006c0065007200690020004100630072006f006200610074002000760065002000410064006f00620065002000520065006100640065007200200035002e003000200076006500200073006f006e0072006100730131006e00640061006b00690020007300fc007200fc006d006c00650072006c00650020006100e70131006c006100620069006c00690072002egt13 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 41: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

42

Table 7 - Multi-State Values Object ReadWrite Description Options MSV1 RW Application Main Standard Heat Pump

MSV2 RW Application Sub

Heat StagesCool Stages or

Comp StagesEmer Heat Stages

MSV3 RW Fan Control

Constant Speed Variable Speed Cool Variable Speed Cool and Heat

MSV4 RW Economizer Damper None Fully Modulating

MSV5 RW Configurable Input -

AI2

None Fan Status CO2 Compressor Suction

Pressure OA Humidity Average Remote Space

Temp Standalone Space Temp

MSV6 RW Supply Air Temp

Control

None Supply Air Temp Cool Supply Air Temp

Heat and Cool

MSV7 RW System Mode Auto Heat Cool Emer

Heat Off

MSV8 RW DehumidificationEner

gy Recovery None DehumidHeat

Wheel MSV13 RW BO5 Option Not Used Comp 1

Table 8 - Analog Inputs

Object ReadWrite Description AI1 R Space Temp AI2 R Configurable Input AI3 R Supply Air Temp AI4 R Outside Air Temp AI5 R Space Humidity

Table 9 - Analog Outputs

Object ReadWrite Description AO7 R Digital Compressor AO8 R Variable Speed Fan AO9 R Economizer Damper

Table 10 - Relay Outputs

Object ReadWrite Description BO1 R Fan BO2 R Compressor 2 BO3 R Heat 1Reversing Valve BO4 R Heat 2Emergency Heat 1 BO5 R Heat 3Emergency Heat 2Y2 BO6 R DehumidificationHeat Wheel

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN ltFEFF004200720075006700200069006e0064007300740069006c006c0069006e006700650072006e0065002000740069006c0020006100740020006f007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400650072002c0020006400650072002000620065006400730074002000650067006e006500720020007300690067002000740069006c002000700072006500700072006500730073002d007500640073006b007200690076006e0069006e00670020006100660020006800f8006a0020006b00760061006c0069007400650074002e0020004400650020006f007000720065007400740065006400650020005000440046002d0064006f006b0075006d0065006e0074006500720020006b0061006e002000e50062006e00650073002000690020004100630072006f00620061007400200065006c006c006500720020004100630072006f006200610074002000520065006100640065007200200035002e00300020006f00670020006e0079006500720065002egt13 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN ltFEFF004b0069007600e1006c00f30020006d0069006e0151007300e9006701710020006e0079006f006d00640061006900200065006c0151006b00e90073007a00ed007401510020006e0079006f006d00740061007400e100730068006f007a0020006c006500670069006e006b00e1006200620020006d0065006700660065006c0065006c0151002000410064006f00620065002000500044004600200064006f006b0075006d0065006e00740075006d006f006b0061007400200065007a0065006b006b0065006c0020006100200062006500e1006c006c00ed007400e10073006f006b006b0061006c0020006b00e90073007a00ed0074006800650074002e0020002000410020006c00e90074007200650068006f007a006f00740074002000500044004600200064006f006b0075006d0065006e00740075006d006f006b00200061007a0020004100630072006f006200610074002000e9007300200061007a002000410064006f00620065002000520065006100640065007200200035002e0030002c0020007600610067007900200061007a002000610074007400f3006c0020006b00e9007301510062006200690020007600650072007a006900f3006b006b0061006c0020006e00790069007400680061007400f3006b0020006d00650067002egt13 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR ltFEFF04120438043a043e0440043804410442043e043204430439044204350020044604560020043f043004400430043c043504420440043800200434043b044f0020044104420432043e04400435043d043d044f00200434043e043a0443043c0435043d044204560432002000410064006f006200650020005000440046002c0020044f043a04560020043d04300439043a04400430044904350020043f045604340445043e0434044f0442044c00200434043b044f0020043204380441043e043a043e044f043a04560441043d043e0433043e0020043f0435044004350434043404400443043a043e0432043e0433043e0020043404400443043a0443002e00200020042104420432043e04400435043d045600200434043e043a0443043c0435043d0442043800200050004400460020043c043e0436043d04300020043204560434043a0440043804420438002004430020004100630072006f006200610074002004420430002000410064006f00620065002000520065006100640065007200200035002e0030002004300431043e0020043f04560437043d04560448043e04570020043204350440044104560457002egt13 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 42: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

43

Maintenance and Support (See back of the manual for maintenance log) At least once each year a qualified service technician should check out the unit Supply fans evaporator coils and air filters should be inspected monthly Periodically during operation it is necessary to perform routine service checks on the performance of the unit This includes checking of the airflow the air filters condenser water flow and refrigerant charge Replacement Parts Parts for AAON equipment may be obtained from your local AAON representative Reference the unit serial number and part number when ordering parts AAON Warranty Service and Parts Department 2424 S Yukon Ave Tulsa OK 74107 Ph 918-583-2266 Fax 918-382-6364 wwwaaoncom Note Before calling technician should have model and serial number of the unit available for the service department to help answer questions regarding the unit and controller

Improper installation adjustment alteration service or maintenance can cause property damage personal injury or loss of life Installation and service must be performed by a qualified installer A copy of this IOM should be kept with the unit

WARNING

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE ltFEFF03a703c103b703c303b903bc03bf03c003bf03b903ae03c303c403b5002003b103c503c403ad03c2002003c403b903c2002003c103c503b803bc03af03c303b503b903c2002003b303b903b1002003bd03b1002003b403b703bc03b903bf03c503c103b303ae03c303b503c403b5002003ad03b303b303c103b103c603b1002000410064006f006200650020005000440046002003c003bf03c5002003b503af03bd03b103b9002003ba03b103c42019002003b503be03bf03c703ae03bd002003ba03b103c403ac03bb03bb03b703bb03b1002003b303b903b1002003c003c103bf002d03b503ba03c403c503c003c903c403b903ba03ad03c2002003b503c103b303b103c303af03b503c2002003c503c803b703bb03ae03c2002003c003bf03b903cc03c403b703c403b103c2002e0020002003a403b10020005000440046002003ad03b303b303c103b103c603b1002003c003bf03c5002003ad03c703b503c403b5002003b403b703bc03b903bf03c503c103b303ae03c303b503b9002003bc03c003bf03c103bf03cd03bd002003bd03b1002003b103bd03bf03b903c703c403bf03cd03bd002003bc03b5002003c403bf0020004100630072006f006200610074002c002003c403bf002000410064006f00620065002000520065006100640065007200200035002e0030002003ba03b103b9002003bc03b503c403b103b303b503bd03ad03c303c403b503c103b503c2002003b503ba03b403cc03c303b503b903c2002egt13 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f00620065002000500044004600200070006900f900200061006400610074007400690020006100200075006e00610020007000720065007300740061006d0070006100200064006900200061006c007400610020007100750061006c0069007400e0002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt13 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 43: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

44

Glossary BAUD RATE Default is 38400 and options available include 9600 19200 38400 and 76800 CO2 SETPT (PPM) Space CO2 override setpoint Default setpoint is 1100 ppm and range is 500-1800 ppm COMP MIN OFF (SECS) Compressor minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP MIN ON (SECS) Compressor minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 and stage 2 compressors COMP OAT LOW Compressor cooling outside air temperature lockout Default is 40degF and range is 0-50degF COMP STG DELAY (MINS) Compressor stage delay Used for cooling and heat pump heating Default is 3 minutes and range 2-15 minutes COOL SETBACK Unoccupied cooling space temperature setpoint Default setpoint is 80degF COOL SETPT Occupied cooling space temperature setpoint Default setpoint is 74degF and range is 55-90degF DAMPER - CNTRL (0-100) Available options are 0-10 VDC 10-0 VDC 2-10 VDC or 10-2 VDC Default value is 0-10 VDC Factory provided actuators on AAON equipment are 2-10 VDC and the control type must be adjusted to match the equipment DAMPER - ECON Available economizer options are None or Modulating DAMPER - ECON ENBLE TEMP Economizer enable outside air temperature setpoint Default setpoint is 60degF and range is 50-70degF DAMPER - ENTHALPY Available economizer options are Enable or Disable DAMPER - LOW LIMIT ALARM Economizer supply air temperature low limit which returns the economizer to the minimum position Default value is 45degF and range is 0-100degF DAMPER - MIN POSITION () Minimum economizer damper position Default value is 10 and range is 0-95 DEADBAND Space temperature setpoint deadband Default setpoint deadband is 2degF and range is 2-15degF DEHUM DEADBAND Space humidity setpoint deadband Default setpoint is 5 RH and range is 5-15 RH DEHUM PRIORITY Available dehumidification priority options are True or False DEHUM SETPT Occupied space relative humidity setpoint Default setpoint is 50 RH and range is 20-85 RH

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE ltFEFF03a703c103b703c303b903bc03bf03c003bf03b903ae03c303c403b5002003b103c503c403ad03c2002003c403b903c2002003c103c503b803bc03af03c303b503b903c2002003b303b903b1002003bd03b1002003b403b703bc03b903bf03c503c103b303ae03c303b503c403b5002003ad03b303b303c103b103c603b1002000410064006f006200650020005000440046002003c003bf03c5002003b503af03bd03b103b9002003ba03b103c42019002003b503be03bf03c703ae03bd002003ba03b103c403ac03bb03bb03b703bb03b1002003b303b903b1002003c003c103bf002d03b503ba03c403c503c003c903c403b903ba03ad03c2002003b503c103b303b103c303af03b503c2002003c503c803b703bb03ae03c2002003c003bf03b903cc03c403b703c403b103c2002e0020002003a403b10020005000440046002003ad03b303b303c103b103c603b1002003c003bf03c5002003ad03c703b503c403b5002003b403b703bc03b903bf03c503c103b303ae03c303b503b9002003bc03c003bf03c103bf03cd03bd002003bd03b1002003b103bd03bf03b903c703c403bf03cd03bd002003bc03b5002003c403bf0020004100630072006f006200610074002c002003c403bf002000410064006f00620065002000520065006100640065007200200035002e0030002003ba03b103b9002003bc03b503c403b103b303b503bd03ad03c303c403b503c103b503c2002003b503ba03b403cc03c303b503b903c2002egt13 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL ltFEFF0055007300740061007700690065006e0069006100200064006f002000740077006f0072007a0065006e0069006100200064006f006b0075006d0065006e007400f300770020005000440046002000700072007a0065007a006e00610063007a006f006e00790063006800200064006f002000770079006400720075006b00f30077002000770020007700790073006f006b00690065006a0020006a0061006b006f015b00630069002e002000200044006f006b0075006d0065006e0074007900200050004400460020006d006f017c006e00610020006f007400770069006500720061010700200077002000700072006f006700720061006d006900650020004100630072006f00620061007400200069002000410064006f00620065002000520065006100640065007200200035002e0030002000690020006e006f00770073007a0079006d002egt13 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 44: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

45

FAN - COOL MAX SPEED Maximum cooling speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum cooling speed FAN - COOL MIN SPEED Minimum cooling speed of a variable speed fan Default is 30 range is 30-80 and value must be less than the maximum cooling speed FAN - DEHUM SPEED Dehumidification speed of a variable speed fan Default is 50 and range is 25-75 FAN - HEAT MAX SPEED Maximum heating speed of a variable speed fan Default is 100 range is 50-100 and value must be greater than the minimum heating speed FAN - HEAT MIN SPEED Minimum heating speed of a variable speed fan Default is 50 for non-heat pump units 75 for heat pump units range is 50-100 and value must be less than the maximum heating speed FAN - OFF DELAY (SECS) Amount of time the fan will continue to run after heating and cooling is deactivated with Auto fan operation Default value is 180 seconds and range is 0-600 seconds HEAT - DELAY (MINS) Stage delay between auxiliary heating stages Default value is 3 minutes and range is 3-60 minutes HEAT MIN OFF (SECS) Heating minimum off time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT MIN ON (SECS) Heating minimum on time Default is 120 seconds and range is 120-600 seconds Configurable for stage 1 stage 2 and stage 3 heating HEAT SETBACK Unoccupied heating space temperature setpoint Default setpoint is 64degF HEAT SETPT Occupied heating space temperature setpoint Default setpoint is 70deg F and range is 55-90degF HTG OAT HIGH Auxiliary heating outside air temperature lockout Heat pump heating will still be available Default is 70degF and range is 50-150degF INACTIVITY (SECS) Amount of time the backlight will stay on and the current password will stay active after the last button push Default value is 60 seconds and range is 5-600 seconds MAC ADDRESS Default is 1 and range is 0-127 Best practice is to assign the MAC ADDRESS in sequence for most efficient communication MAX DGTL COMP Maximum allowable capacity of the variable capacity scroll compressor Default is 100 and range is 25-100 and value must be 5 greater than the minimum variable capacity scroll compressor capacity setpoint MAX MASTER Default is 127 and range is 0-127 Best practice is to set the MAX MASTER to the highest assigned MAC ADDRESS

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f0075007200200075006e00650020007100750061006c0069007400e90020006400270069006d007000720065007300730069006f006e00200070007200e9007000720065007300730065002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt13 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA ltFEFF005500740069006c0069007a007a006100720065002000710075006500730074006500200069006d0070006f007300740061007a0069006f006e00690020007000650072002000630072006500610072006500200064006f00630075006d0065006e00740069002000410064006f00620065002000500044004600200070006900f900200061006400610074007400690020006100200075006e00610020007000720065007300740061006d0070006100200064006900200061006c007400610020007100750061006c0069007400e0002e0020004900200064006f00630075006d0065006e007400690020005000440046002000630072006500610074006900200070006f00730073006f006e006f0020006500730073006500720065002000610070006500720074006900200063006f006e0020004100630072006f00620061007400200065002000410064006f00620065002000520065006100640065007200200035002e003000200065002000760065007200730069006f006e006900200073007500630063006500730073006900760065002egt13 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200073006f006d00200065007200200062006500730074002000650067006e0065007400200066006f00720020006600f80072007400720079006b006b0073007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c0069007400650074002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt13 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 45: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

46

MIN DGTL COMP Minimum allowable capacity of the variable capacity scroll compressor Default is 50 range is 20-80 and value must be 5 less than the maximum variable capacity scroll compressor capacity setpoint MIN SETPT DIFF Minimum setpoint differential between the cooling and heating space temperature setpoints Used for both the occupied and unoccupied modes of operation Default setpoint differential is 2degF and range is 1-15degF OAT HIGH Description Default is 150degF and range is 110-160degF OAT LOW Description Default is -40degF and range is -50-40degF OCC MAX CLG Occupied maximum cooling space temperature setpoint Default is 78degF and range is 55-92degF OCC MIN CLG Occupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF OCC MAX HTG Occupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF OCC MIN HTG Occupied minimum heating space temperature setpoint Default is 65degF and range is 53-90degF OCC OVRIDE (HRS) Amount of time a space temperature setpoint override and occupancy override will last Default value is 1 hour and range is 0-12 hours When set at 0 the override will last until the next schedule change SAT COOL SETPT Cooling supply air temperature setpoint Default setpoint is 55degF and range is 50-70degF SAT HEAT SETPT Heating supply air temperature setpoint Default setpoint is 120degF and range is 75-200degF SAT HIGH Maximum supply air temperature Default is 200degF and range is 120-250degF Disable all outputs SAT LOW Minimum supply air temperature Default is 40degF and range is 32-60degF Disable all outputs SUCTION (PSI) Dehumidification suction pressure setpoint Default setpoint is 1194 psi and range is 50-250 psi UNOCC DEHUM SETPT Unoccupied space humidity setpoint Default setpoint is 65 RH and range is 20-85 RH UNOCC MAX HTG Unoccupied maximum heating space temperature setpoint Default is 72degF and range is 55-90degF UNOCC MIN CLG Unoccupied minimum cooling space temperature setpoint Default is 68degF and range is 55-90degF

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA ltFEFF06270633062A062E062F0645002006470630064700200627064406250639062F0627062F0627062A002006440625064606340627062100200648062B062706260642002000410064006F00620065002000500044004600200645062A064806270641064206290020064406440637062806270639062900200641064A00200627064406450637062706280639002006300627062A0020062F0631062C0627062A002006270644062C0648062F0629002006270644063906270644064A0629061B0020064A06450643064600200641062A062D00200648062B0627062606420020005000440046002006270644064506460634062306290020062806270633062A062E062F062706450020004100630072006F0062006100740020064800410064006F006200650020005200650061006400650072002006250635062F0627063100200035002E0030002006480627064406250635062F062706310627062A0020062706440623062D062F062B002E0635062F0627063100200035002E0030002006480627064406250635062F062706310627062A0020062706440623062D062F062B002Egt13 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 46: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

47

AAON Mini Controller Startup Form

Date_______________ Job Name_____________________________________________________________________ Address______________________________________________________________________ Model Number_________________________________________________________________ ______________________________________________________________________________ Serial Number___________________________________________ Tag_________________ Startup Contractor______________________________________________________________ Address________________________________________________ Phone________________ Pre Startup Checklist

Installing contractor should verify the following items 1 Is there any visible shipping damage ____________________________ Yes No 2 Are the clearances adequate for service and operation ___________ Yes No 3 Have all electrical connections been tested for tightness _____________ Yes No

Unit Configuration Water-Cooled Condenser ________ Air-Cooled Condenser ___________ Water-Source Heat Pump_________ Air-Source Heat Pump___________ Constant Volume Cooling________ Single Zone VAV Cooling________ Constant Volume Heating________ Single Zone VAV Heating________ Supply Fan Control - VFD ECM NA Supply Fan Cooling Max Speed__________ Supply Fan Heating Max Speed___________ Supply Fan Cooling Min Speed__________ Supply Fan Heating Min Speed___________

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f0075007200200075006e00650020007100750061006c0069007400e90020006400270069006d007000720065007300730069006f006e00200070007200e9007000720065007300730065002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt13 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN ltFEFF004b0069007600e1006c00f30020006d0069006e0151007300e9006701710020006e0079006f006d00640061006900200065006c0151006b00e90073007a00ed007401510020006e0079006f006d00740061007400e100730068006f007a0020006c006500670069006e006b00e1006200620020006d0065006700660065006c0065006c0151002000410064006f00620065002000500044004600200064006f006b0075006d0065006e00740075006d006f006b0061007400200065007a0065006b006b0065006c0020006100200062006500e1006c006c00ed007400e10073006f006b006b0061006c0020006b00e90073007a00ed0074006800650074002e0020002000410020006c00e90074007200650068006f007a006f00740074002000500044004600200064006f006b0075006d0065006e00740075006d006f006b00200061007a0020004100630072006f006200610074002000e9007300200061007a002000410064006f00620065002000520065006100640065007200200035002e0030002c0020007600610067007900200061007a002000610074007400f3006c0020006b00e9007301510062006200690020007600650072007a006900f3006b006b0061006c0020006e00790069007400680061007400f3006b0020006d00650067002egt13 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE ltFEFF0041006e007600e4006e00640020006400650020006800e4007200200069006e0073007400e4006c006c006e0069006e006700610072006e00610020006f006d002000640075002000760069006c006c00200073006b006100700061002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e007400200073006f006d002000e400720020006c00e4006d0070006c0069006700610020006600f60072002000700072006500700072006500730073002d007500740073006b00720069006600740020006d006500640020006800f600670020006b00760061006c0069007400650074002e002000200053006b006100700061006400650020005000440046002d0064006f006b0075006d0065006e00740020006b0061006e002000f600700070006e00610073002000690020004100630072006f0062006100740020006f00630068002000410064006f00620065002000520065006100640065007200200035002e00300020006f00630068002000730065006e006100720065002egt13 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 47: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

48

Maintenance Log This log must be kept with the unit It is the responsibility of the owner andor maintenanceservice contractor to document any service repair or adjustments AAON Service and Warranty Departments are available to advise and provide phone help for proper operation and replacement parts The responsibility for proper start-up maintenance and servicing of the equipment falls to the owner and qualified licensed technician Entry Date Action Taken

NameTel

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE ltFEFF005400610074006f0020006e006100730074006100760065006e00ed00200070006f0075017e0069006a007400650020006b0020007600790074007600e101590065006e00ed00200064006f006b0075006d0065006e0074016f002000410064006f006200650020005000440046002c0020006b00740065007200e90020007300650020006e0065006a006c00e90070006500200068006f006400ed002000700072006f0020006b00760061006c00690074006e00ed0020007400690073006b00200061002000700072006500700072006500730073002e002000200056007900740076006f01590065006e00e900200064006f006b0075006d0065006e007400790020005000440046002000620075006400650020006d006f017e006e00e90020006f007400650076015900ed007400200076002000700072006f006700720061006d0065006300680020004100630072006f00620061007400200061002000410064006f00620065002000520065006100640065007200200035002e0030002000610020006e006f0076011b006a016100ed00630068002egt13 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR ltFEFF004200720075006b00200064006900730073006500200069006e006e007300740069006c006c0069006e00670065006e0065002000740069006c002000e50020006f0070007000720065007400740065002000410064006f006200650020005000440046002d0064006f006b0075006d0065006e00740065007200200073006f006d00200065007200200062006500730074002000650067006e0065007400200066006f00720020006600f80072007400720079006b006b0073007500740073006b00720069006600740020006100760020006800f800790020006b00760061006c0069007400650074002e0020005000440046002d0064006f006b0075006d0065006e00740065006e00650020006b0061006e002000e50070006e00650073002000690020004100630072006f00620061007400200065006c006c00650072002000410064006f00620065002000520065006100640065007200200035002e003000200065006c006c00650072002000730065006e006500720065002egt13 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 48: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

49

Literature Change History October 2010 Revision of the manual correcting the sequence of operation for enthalpy controlled economizer December 2013 Added BACnet Points List glossary and how relay output 5 can be used as the Y1 compressor 1 relay output March 2014 Added dehumidification priority April 2015 Clarified available features and options Added note about factory provided economizer actuators being 2-10 VDC controlled

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA 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 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN 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 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB 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 RUM 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 RUS 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 SKY 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 SLV 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 SUO ltFEFF004b00e40079007400e40020006e00e40069007400e4002000610073006500740075006b007300690061002c0020006b0075006e0020006c0075006f00740020006c00e400680069006e006e00e4002000760061006100740069007600610061006e0020007000610069006e006100740075006b00730065006e002000760061006c006d0069007300740065006c00750074007900f6006800f6006e00200073006f00700069007600690061002000410064006f0062006500200050004400460020002d0064006f006b0075006d0065006e007400740065006a0061002e0020004c0075006f0064007500740020005000440046002d0064006f006b0075006d0065006e00740069007400200076006f0069006400610061006e0020006100760061007400610020004100630072006f0062006100740069006c006c00610020006a0061002000410064006f00620065002000520065006100640065007200200035002e0030003a006c006c00610020006a006100200075007500640065006d006d0069006c006c0061002egt13 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13

Page 49: User’s Manual - AAON Heating and Cooling Products€™s Manual WARNING QUALIFIED INSTALLER Improper installation, adjustment, alteration, service or maintenance can cause property

AAON 2425 South Yukon Ave Tulsa OK 74107-2728 Phone 918-583-2266

Fax 918-583-6094 wwwaaoncom

AAON Mini Controller Userrsquos Manual

R98200 Rev C 150409 It is the intent of AAON to provide accurate and current product information However in the interest of product improvement AAON reserves the right to change pricing specifications andor design of its product without notice obligation or liability

Copyright copy AAON all rights reserved throughout the world AAONreg and AAONAIREreg are registered trademarks of AAON Inc Tulsa OK

  • Safety
  • AAONreg Mini Controller Features and Options
  • General Information
  • Installation
  • Locating and Mounting the Controller
  • AAON Mini Controller Backplate Layout
  • Input Connections
  • Remote Space Temperature Sensor
  • Supply Air Temperature Sensor
  • Output Connections
  • Startup
  • Navigation
  • Home Screen Configuration
  • Main Menu Configuration
  • Advanced Menu Configuration
  • Controller Configuration Steps
    • Constant Volume Air Conditioner Configuration
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + CV Heat
    • Single Zone VAV Air Conditioner Configuration - VAV Cool + VAV Heat
    • Constant Volume Heat Pump Configuration
    • Single Zone VAV Heat Pump Configuration- VAV Cool + CV Heat
    • Single Zone VAV Heat Pump Configuration- VAV Cool + VAV Heat
    • Modulating Hot Gas Reheat
    • Economizer
    • CO2 Override
      • Operation
      • BACnet Points List
      • Maintenance and Support
      • Replacement Parts
      • Glossary
      • AAON Mini Controller Startup Form
      • Maintenance Log
      • Literature Change History
        • ltlt13 ASCII85EncodePages false13 AllowTransparency false13 AutoPositionEPSFiles true13 AutoRotatePages None13 Binding Left13 CalGrayProfile (Dot Gain 20)13 CalRGBProfile (sRGB IEC61966-21)13 CalCMYKProfile (US Web Coated 050SWOP051 v2)13 sRGBProfile (sRGB IEC61966-21)13 CannotEmbedFontPolicy Error13 CompatibilityLevel 1413 CompressObjects Tags13 CompressPages true13 ConvertImagesToIndexed true13 PassThroughJPEGImages true13 CreateJobTicket false13 DefaultRenderingIntent Default13 DetectBlends true13 DetectCurves 0000013 ColorConversionStrategy CMYK13 DoThumbnails false13 EmbedAllFonts true13 EmbedOpenType false13 ParseICCProfilesInComments true13 EmbedJobOptions true13 DSCReportingLevel 013 EmitDSCWarnings false13 EndPage -113 ImageMemory 104857613 LockDistillerParams false13 MaxSubsetPct 10013 Optimize true13 OPM 113 ParseDSCComments true13 ParseDSCCommentsForDocInfo true13 PreserveCopyPage true13 PreserveDICMYKValues true13 PreserveEPSInfo true13 PreserveFlatness true13 PreserveHalftoneInfo false13 PreserveOPIComments true13 PreserveOverprintSettings true13 StartPage 113 SubsetFonts true13 TransferFunctionInfo Apply13 UCRandBGInfo Preserve13 UsePrologue false13 ColorSettingsFile ()13 AlwaysEmbed [ true13 ]13 NeverEmbed [ true13 ]13 AntiAliasColorImages false13 CropColorImages true13 ColorImageMinResolution 30013 ColorImageMinResolutionPolicy OK13 DownsampleColorImages true13 ColorImageDownsampleType Bicubic13 ColorImageResolution 30013 ColorImageDepth -113 ColorImageMinDownsampleDepth 113 ColorImageDownsampleThreshold 15000013 EncodeColorImages true13 ColorImageFilter DCTEncode13 AutoFilterColorImages true13 ColorImageAutoFilterStrategy JPEG13 ColorACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 ColorImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000ColorACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000ColorImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasGrayImages false13 CropGrayImages true13 GrayImageMinResolution 30013 GrayImageMinResolutionPolicy OK13 DownsampleGrayImages true13 GrayImageDownsampleType Bicubic13 GrayImageResolution 30013 GrayImageDepth -113 GrayImageMinDownsampleDepth 213 GrayImageDownsampleThreshold 15000013 EncodeGrayImages true13 GrayImageFilter DCTEncode13 AutoFilterGrayImages true13 GrayImageAutoFilterStrategy JPEG13 GrayACSImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 GrayImageDict ltlt13 QFactor 01513 HSamples [1 1 1 1] VSamples [1 1 1 1]13 gtgt13 JPEG2000GrayACSImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 JPEG2000GrayImageDict ltlt13 TileWidth 25613 TileHeight 25613 Quality 3013 gtgt13 AntiAliasMonoImages false13 CropMonoImages true13 MonoImageMinResolution 120013 MonoImageMinResolutionPolicy OK13 DownsampleMonoImages true13 MonoImageDownsampleType Bicubic13 MonoImageResolution 120013 MonoImageDepth -113 MonoImageDownsampleThreshold 15000013 EncodeMonoImages true13 MonoImageFilter CCITTFaxEncode13 MonoImageDict ltlt13 K -113 gtgt13 AllowPSXObjects false13 CheckCompliance [13 None13 ]13 PDFX1aCheck false13 PDFX3Check false13 PDFXCompliantPDFOnly false13 PDFXNoTrimBoxError true13 PDFXTrimBoxToMediaBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXSetBleedBoxToMediaBox true13 PDFXBleedBoxToTrimBoxOffset [13 00000013 00000013 00000013 00000013 ]13 PDFXOutputIntentProfile ()13 PDFXOutputConditionIdentifier ()13 PDFXOutputCondition ()13 PDFXRegistryName ()13 PDFXTrapped False1313 CreateJDFFile false13 Description ltlt13 ARA 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 BGR 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 CHS ltFEFF4f7f75288fd94e9b8bbe5b9a521b5efa7684002000410064006f006200650020005000440046002065876863900275284e8e9ad88d2891cf76845370524d53705237300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c676562535f00521b5efa768400200050004400460020658768633002gt13 CHT ltFEFF4f7f752890194e9b8a2d7f6e5efa7acb7684002000410064006f006200650020005000440046002065874ef69069752865bc9ad854c18cea76845370524d5370523786557406300260a853ef4ee54f7f75280020004100630072006f0062006100740020548c002000410064006f00620065002000520065006100640065007200200035002e003000204ee553ca66f49ad87248672c4f86958b555f5df25efa7acb76840020005000440046002065874ef63002gt13 CZE 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 DAN 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 DEU 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 ESP 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 ETI 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 FRA ltFEFF005500740069006c006900730065007a00200063006500730020006f007000740069006f006e00730020006100660069006e00200064006500200063007200e900650072002000640065007300200064006f00630075006d0065006e00740073002000410064006f00620065002000500044004600200070006f0075007200200075006e00650020007100750061006c0069007400e90020006400270069006d007000720065007300730069006f006e00200070007200e9007000720065007300730065002e0020004c0065007300200064006f00630075006d0065006e00740073002000500044004600200063007200e900e90073002000700065007500760065006e0074002000ea0074007200650020006f007500760065007200740073002000640061006e00730020004100630072006f006200610074002c002000610069006e00730069002000710075002700410064006f00620065002000520065006100640065007200200035002e0030002000650074002000760065007200730069006f006e007300200075006c007400e90072006900650075007200650073002egt13 GRE 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 HEB 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 HRV (Za stvaranje Adobe PDF dokumenata najpogodnijih za visokokvalitetni ispis prije tiskanja koristite ove postavke Stvoreni PDF dokumenti mogu se otvoriti Acrobat i Adobe Reader 50 i kasnijim verzijama)13 HUN ltFEFF004b0069007600e1006c00f30020006d0069006e0151007300e9006701710020006e0079006f006d00640061006900200065006c0151006b00e90073007a00ed007401510020006e0079006f006d00740061007400e100730068006f007a0020006c006500670069006e006b00e1006200620020006d0065006700660065006c0065006c0151002000410064006f00620065002000500044004600200064006f006b0075006d0065006e00740075006d006f006b0061007400200065007a0065006b006b0065006c0020006100200062006500e1006c006c00ed007400e10073006f006b006b0061006c0020006b00e90073007a00ed0074006800650074002e0020002000410020006c00e90074007200650068006f007a006f00740074002000500044004600200064006f006b0075006d0065006e00740075006d006f006b00200061007a0020004100630072006f006200610074002000e9007300200061007a002000410064006f00620065002000520065006100640065007200200035002e0030002c0020007600610067007900200061007a002000610074007400f3006c0020006b00e9007301510062006200690020007600650072007a006900f3006b006b0061006c0020006e00790069007400680061007400f3006b0020006d00650067002egt13 ITA 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 JPN ltFEFF9ad854c18cea306a30d730ea30d730ec30b951fa529b7528002000410064006f0062006500200050004400460020658766f8306e4f5c6210306b4f7f75283057307e305930023053306e8a2d5b9a30674f5c62103055308c305f0020005000440046002030d530a130a430eb306f3001004100630072006f0062006100740020304a30883073002000410064006f00620065002000520065006100640065007200200035002e003000204ee5964d3067958b304f30533068304c3067304d307e305930023053306e8a2d5b9a306b306f30d530a930f330c8306e57cb30818fbc307f304c5fc59808306730593002gt13 KOR ltFEFFc7740020c124c815c7440020c0acc6a9d558c5ec0020ace0d488c9c80020c2dcd5d80020c778c1c4c5d00020ac00c7a50020c801d569d55c002000410064006f0062006500200050004400460020bb38c11cb97c0020c791c131d569b2c8b2e4002e0020c774b807ac8c0020c791c131b41c00200050004400460020bb38c11cb2940020004100630072006f0062006100740020bc0f002000410064006f00620065002000520065006100640065007200200035002e00300020c774c0c1c5d0c11c0020c5f40020c2180020c788c2b5b2c8b2e4002egt13 LTH 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 LVI 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 NLD (Gebruik deze instellingen om Adobe PDF-documenten te maken die zijn geoptimaliseerd voor prepress-afdrukken van hoge kwaliteit De gemaakte PDF-documenten kunnen worden geopend met Acrobat en Adobe Reader 50 en hoger)13 NOR 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 POL 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 PTB ltFEFF005500740069006c0069007a006500200065007300730061007300200063006f006e00660069006700750072006100e700f50065007300200064006500200066006f0072006d00610020006100200063007200690061007200200064006f00630075006d0065006e0074006f0073002000410064006f0062006500200050004400460020006d00610069007300200061006400650071007500610064006f00730020007000610072006100200070007200e9002d0069006d0070007200650073007300f50065007300200064006500200061006c007400610020007100750061006c00690064006100640065002e0020004f007300200064006f00630075006d0065006e0074006f00730020005000440046002000630072006900610064006f007300200070006f00640065006d0020007300650072002000610062006500720074006f007300200063006f006d0020006f0020004100630072006f006200610074002000650020006f002000410064006f00620065002000520065006100640065007200200035002e0030002000650020007600650072007300f50065007300200070006f00730074006500720069006f007200650073002egt13 RUM 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 RUS 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 SKY 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 SLV 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 SUO 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 SVE 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 TUR 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 UKR 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 ENU (Use these settings to create Adobe PDF documents best suited for high-quality prepress printing Created PDF documents can be opened with Acrobat and Adobe Reader 50 and later)13 gtgt13 Namespace [13 (Adobe)13 (Common)13 (10)13 ]13 OtherNamespaces [13 ltlt13 AsReaderSpreads false13 CropImagesToFrames true13 ErrorControl WarnAndContinue13 FlattenerIgnoreSpreadOverrides false13 IncludeGuidesGrids false13 IncludeNonPrinting false13 IncludeSlug false13 Namespace [13 (Adobe)13 (InDesign)13 (40)13 ]13 OmitPlacedBitmaps false13 OmitPlacedEPS false13 OmitPlacedPDF false13 SimulateOverprint Legacy13 gtgt13 ltlt13 AddBleedMarks false13 AddColorBars false13 AddCropMarks false13 AddPageInfo false13 AddRegMarks false13 ConvertColors ConvertToCMYK13 DestinationProfileName ()13 DestinationProfileSelector DocumentCMYK13 Downsample16BitImages true13 FlattenerPreset ltlt13 PresetSelector MediumResolution13 gtgt13 FormElements false13 GenerateStructure false13 IncludeBookmarks false13 IncludeHyperlinks false13 IncludeInteractive false13 IncludeLayers false13 IncludeProfiles false13 MultimediaHandling UseObjectSettings13 Namespace [13 (Adobe)13 (CreativeSuite)13 (20)13 ]13 PDFXOutputIntentProfileSelector DocumentCMYK13 PreserveEditing true13 UntaggedCMYKHandling LeaveUntagged13 UntaggedRGBHandling UseDocumentProfile13 UseDocumentBleed false13 gtgt13 ]13gtgt setdistillerparams13ltlt13 HWResolution [2400 2400]13 PageSize [612000 792000]13gtgt setpagedevice13