QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for use by a qualified service technician familiar with safety procedures and equipped with the proper tools and test instruments • Installation or repairs made by unqualified persons can result in hazards to you and others. • Failure to carefully read and follow all instructions in this manual can result in equipment malfunction, property damage, personal injury and/or death. • This service is only for service engineer to use.

Transcript of USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31...

Page 1: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

QUANTUMINVERTER MINI SPLIT

USER MANUAL

WIN310C2V31WIN414C2V31WIN520C2V31WIN628C2V31

WARNING

• The information contained in the manual is intended for use by a qualified service technicianfamiliar with safety procedures and equipped with the proper tools and test instruments• Installation or repairs made by unqualified persons can result in hazards to you and others.• Failure to carefully read and follow all instructions in this manual can result in equipmentmalfunction, property damage, personal injury and/or death.• This service is only for service engineer to use.

Page 2: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

Contents

Safety Instructions .............................................................

Safety Precautions .............................................................

Maintenance ........................................................................

Preparation before use ......................................................

Identification of parts .........................................................

Display Introductions .........................................................

Protection ............................................................................

Installation instructions .....................................................

Troubleshooting .................................................................

1

2

3

4

5

6

7

8

16

Remote controller operating instructions. See" remote controllerinstructions".

Page 3: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

Safety Instructions• To guarantee the unit work normally, please read the manual carefully before installation, and try to install strictly according to this manual.• Do not let air enter the refrigeration system or discharge refrigerant when moving the air conditioner.• Properly ground the air conditioner into the earth.• Check the connecting cables and pipes carefully, make sure they are correct and firm before connecting the power of the air conditioner.• There must be an air-break switch.• After installing, the consumer must operate the air conditioner correctly according to this manual, keep a suitable storage for maintenance and moving of the air conditioner in the future.• Fuse of indoor unit: T 3.15A 250VAC.• For 7k-12k models, fuse of outdoor unit: T 15A 250VAC or T 20A 250VAC.• For 14k-18k models, fuse of outdoor unit: T 20A 250VAC.• For 21 k-30k models, fuse of outdoor unit: T 30A 250VAC .• The installation instructions for appliances that are intended to be permanently connected to fixed wiring, and have a leakage current that may exceed 10 mA, shall state that the installation of a residual current device (RCD) having a rated residual operating current not exceeding 30 mA is advisable.• Warning: Risk of electric shock can cause injury or death: Disconnect all remote electric power supplies before servicing .• The maximum length of the connecting pipe between the indoor unit and outdoor unit should be less than 5 meters. It will affect the efficiency of the air conditioner if the distance longer than that length.• This appliance can be used by children aged from 8 years and above and persons with reduced physical, sensory or mental capabilities or lack of experience and knowledge if they have been given supervision or instruction concerning use of the appliance in a safe way and understand the hazards involved. Children shall not play with the appliance. Cleaning and user maintenance shall not be made by children without supervision.• The batteries in remote controller must be recycled or disposed of properly. Disposal of Scrap Batteries --- Please discard the batteries as sorted municipal waste at the accessible collection point.• If the appliance is fixed wiring, the appliance must be fitted with means for disconnection from the supply mains having a contact separation in all poles that provide full disconnection under over voltage category 111 conditions, and these means must be incorporated in the fixed wiring in accordance with the wiring rules.• If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or similarly qualified persons in order to avoid a hazard.• The appliance shall be installed in accordance with national wiring regulations.• The air conditioner must be installed by professional or qualified persons.• The appliance shall not be installed in the laundry.

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

1

Page 4: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m 2

Be sure not to do.

ºPay attention to such a situation.

Safety precautions

Grounding is essential.

Warning: Incorrect handling couldcause a serious hazard,

Symbols in this Use and Care Manual are interpreted as shown below.

Page 5: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

3

• Air �lter maintenance

Cut off the power supply

Front panel maintenance

Turn off the appliancefirst before disconnectingfrom power supply.

Grasp position "a" andpull outward to remove thefront panel.

Wipe with a softand dry cloth.Use soft moisture clothto clean if the front panelis very dirty;

Never sprinkle water onto theindoor unit

Never use volatile substance such as gasoline or polishing powder to clean the appliance.

Reinstall and shut the front panel.Reinstall and shut the front panel bypressing position "b" downward.

1 2

1

3

2

3 4

5 6

Stop the appliance, cut off thepower supply and remove the airfilter. Clean and reinstall the air filter.

1. 0pen the front panel.2. Press the handle of the filter gently3. Grasp the handle and slide out the filter.

Close the front panel again.II Clean the air filter every two weeksIf the air conditioner operates In anextremely dusty environment.

It is necessary to clean the air filterafter using it for about 100 hours.

If the dirt is conspicuous,wash it with a solution ofdetergent in lukewarm water.After cleaning, dry well inshade.

Page 6: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m 4

Preparation before use

Note

Preset

Safeguarding the environmentThis applianc e is made of rec y clable or re-usabl e material. Scrapping must be carried out incompliance with local waste disposal regulations. Before scrapping it, make sure to cut off the mainscord so that the appliance cannot be re-us ed.For more d etailed information on handling and recycling this product, contact your local authoritieswho d e al with the separate collection of rubbish or the shop where you bought the appliance.SCRAPPING OF APPLIANCEThis appliance is marked according to the European Directiv e 2012/19/EC, Waste Electrical andElectronic Equipment (WEEE).This marking indicates that this product should not be disposedwith other household wast e s throughout the EU. To prevent possibleharm to the environment or human health from uncontrolled wastedisposal,recycle it responsibly to promote the sustainable reuse ofmaterial resources. To return your used devic e , please use the r eturnand collection systems or contact the retailer where the product waspurchased. They can take this product for environmental safe recycling.

• When charging refrigerant into the system, make sure to charge in liquid state,if therefrigerant of the appliance is R41 QA.Otherwise, chemical composition ofrefrigerant (R41 0A) inside the system may change and thus affect performance ofthe air conditioner.• According to the character of refrigerant (R410A,the value of GWP is 2088), thepressure of the tube is very high, so be sure to be careful when you install and repairthe appliance.• If the supply cord is da maged, it must be replaced by the manufacturer, itsservice agent or si milarly quali fied persons in order to avoid a hazard.• The air conditioner must be installed by a professional engineer.• The temperature of refrigerant circuit will be high, please keep theinterconnection cable away from the copper tube .

Before using the air conditioner, be sure to check and preset the following.• Remote Control presettingEach tim e after the remote control is replaced with new batteries or is energized, re mote control auto presetting heat pump.If the air conditioner you purchased is a Cooling Only one, heat pump remote controller can also be used.• Back-light function of Remote Control(optional)Hold down any button on remote control to activate the back light. It automatically shuts off 10 seconds later.Note: Back-light is an optional function.

• Auto Restart PresettingThe air conditioner has an Auto-Restart function.

Page 7: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

Indoor unit

Outdoor unit

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

5

Page 8: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INV ERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m 6

Display introduction

The symbols may be different from these models, but the functions are similar.

ON/OFF To let the AC run or stop by pressing the button.

Emergency button 11

Temperature indicatorDisplay set temperature.It shows FC after 200 hours of usage as reminder to clean the filter.After filter cleaning press the filter reset button located on the indoor unit behind the front panel in order to reset the display.(optional)

Running indicatorIt lights up when the AC is running.It flashes during defrosting.

Timer indicatorIt lights up during set time.

Sleep indicatorIt lights up in sleep mode.

Signal Receptor

1

2

3

4

5

Page 9: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

7

Protection

• Operating conditionThe protective device maybe trip and stop the appliance in the cases listed below.

Outdoor air temperature is over 24°CHEATING Outdoor air temperature is below -10°C °

COOLING Outdoor air temperature is over *43°C

Room temperature is over 27°C DRY Room temperature is below 18°cRoom temperature is below 21°c

*For Tropical (T3) Climate condition models, the temperature point is 55°Cinstead of 43°C.The temperature of some products is allowed beyond the range. In speci�c situation, please consult the merchant.If the air conditioner runs in COOLING or DRY mode withdoor or window opened for a long time when relativehumidity is above 80%,dew may drip down from the outlet.

Noise pollution

• Install the air conditioner at a place that can bear its weight in order to operate more quietly.• Install the outdoor unit at a place where the air discharged and the operation noise would not annoy your neighbors.• Do not place any obstacles in front of the air outlet of the outdoor unit lest it increases the noise level.

Features of protector

1 The protective device will work at following cases.• Restarting the unit at once after operation stops or changing mode during operation, you need to wait for 3 minutes .• Connect to power supply and turn on the unit at once, it may start 20 seconds later.

2. If all operation has stopped, press ON/OFF button again to restart, Timer should be set again if it has been canceled.

Features of HEATING mode

PreheatAt the beginning of the HEATING operation, the airflow from the indoor unit is discharged 2-5 minutes later.Defrost

In HEATING operation the appliance will defrost (de-ice) automatically to raise efficiency.This procedure usually lasts 2-10 minutes. During defrosting, fans stop operation.After defrosting completes, it returns to HEATING mode automatically.

Note: Heating is NOT available for cooling only air conditioner models.

Page 10: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

8

Installation instructions

Air intake distance from the wallshould be over 250mm

Distance from the wallshould be over 50mm

Distance from ceilingshould be over 200 mm

Distance from wallshould be over 50mm

Distance from floor should be over 2500mm

Air intake distance fromthe wall should beover 250mm

Above figure is only a simple presentationof the unit, it may not match the externalappearance of the unit you purchased.

Installation must be performed in accordance withthe national wiring standards by authorized personnel only.

INNOVAIR DC INVERRTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m

Page 11: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

9

Installation instructionsLocation for Installing Indoor Unit• Where there is no obstacle near the air outlet and air can beeasily blown to every corner.• Where piping and wall hole can be easily arranged.• Keep the required space from the unit to the ceiling and wallaccording to the installation diagram on previous page.• Where the air filter can be easily removed.• Keep the unit and remote controller 1 m or more apart fromtelevision, radio etc.• keep as far as possible from fluorescent lamps.• Do not put anything near the air inlet to obstruct it from airabsorption.• Install on a wall that is strong enough to bear the weight of the unit.• Install in a place that will not increase operation noise and vibration.• Keep away from direct sunlight and heating sources. Do not placeflammable materials or combustion apparatuses on top of the unit.

Location for Installing Indoor Unit• Where there is no obstacle near the air outlet and air can beeasily blown to every corner.• Where piping and wall hole can be easily arranged.• Keep the required space from the unit to the ceiling and wallaccording to the installation diagram on previous page.• Where the air filter can be easily removed.• Keep the unit and remote controller 1 m or more apart fromtelevision, radio etc.• keep as far as possible from fluorescent lamps.• Do not put anything near the air inlet to obstruct it from airabsorption.• Install on a wall that is strong enough to bear the weight of the unit.• Install in a place that will not increase operation noise and vibration.• Keep away from direct sunlight and heating sources. Do not placeflammable materials or combustion apparatuses on top of the unit.

Model Max. Allowable TubingLength at Shipment (m)

Limit of TubingLength (m)

Limit of ElevationDifference H (m)

Required amount ofadditional refrigerant (g/m)

7K-18K 5 15 5

21K-25K 5 15 5

30K 5 15 5

If the height or pipe length is out of the scope of the table, please consult the dealer.

20

30

40

Page 12: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

10

Installation instructions

After connecting the piping , install the drain hose. Then connect the power cords. After connecting,wrap the piping, cords and drain hose together with thermal insulation materials.

INNOVAIR DC INVVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m

Piping direction

trough

loadin ece

2 Saw the unloading pieceoff along the trough

Note: When installing the pipe at the directions1,2 or 4, saw the corresponding unloading pieceoff the indoor unit base.

• Put the piping (liquid and gas pipe) and cables through the wall hole from outside or put them throughfrom inside after indoor piping and cables connection is complete to connect to the outdoor unit.• Decide whether to saw the unloading piece off in accordance with the piping direction.(as shown below)

Indoor unit installation1. Installing the Mounting Plate

Note: The shape of your mounting plate may be different from the one above, but the installation method is similar.Note: As the above figure shown, the six holes matched with tapping screw on the mounting plate must be used tofix the mounting plate, the others are prepared.

3. Indoor Unit Piping Installation

2. Drill a Hole for Piping• Decide the position of the hole for piping according to thelocation of mounting plate.• Drill a hole in the wall. The hole should tilt a littledownward toward outside.• Install a sleeve through the wall hole to keep the walltidy and clean.

• Decide an installing location for the mounting plate according to the indoor unit location and piping direction.• Keep the mounting plate horizontal with a horizontal ruler or dropping line.• Drill holes of 32mm in depth on the wall for fixing the plate.• Insert the plastic plugs to the hole, fix the mounting plate with tapping screws.• Inspect if the mounting plate is well fixed. Then drill a hole for piping.

Page 13: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

11

Installation instructions• Piping Joints Thermal Insulation:Wrap the piping joints with thermalinsulation materials and then wrapwith a vinyl tape.

• Piping Thermal Insulation:a. Place the drain hose under the piping.b. Insulation material uses polythene foam over 6mm in thickness. Note: Drain hose is prepared by user.

• Do not arrange the drain pipe in a way that leaves it twisted, stickingout or waving around. Do not immerse the end of it in water.

• If an extension drain hose is connected to the drain pipe, make sureto insulated when passing along the indoor unit.

• When the piping is directed to the right, piping, powerCord and drain pipe should be thermal insulated andfixed onto the back of the unit with a piping fixer.

Piping Connection:

a. Connect indoor unit pipes with two wrenches. Pay special attentionto the allowed torque as shown below to prevent the pipes, connectorsand flare nuts from being deformed and damaged.

b. Pre-tighten them with fingers at first, then use the wrenches.

*The unit of 12K* is bigger than the unit of 12K. The unit of 18K* is bigger than the unit of 18K.

Model Pipe Size Torque Nut width 7,8,9, 10, 12, 14, 18K Liquid Side ( cp 6mm or 1/4 inch) 15- 20N·m 17mm 18K*,21,22,24,25,30K Liquid Side ( cp 9.53mm or 3/8 inch) 30-35N·m 22mm 7,8,9,10,12K Gas Side ( cp 9.53mm or 3/8 inch) 30-35N·m 22mm 12K*,14K,18K Gas Side ( cp 12mm or 1/2 inch) 50- 55N·m 24mm 18K*,21,22,24,25,30K Gas Side ( cp 16mm or 5/8 inch) 60- 65N·m 27mm

Min.thickness 0.5mm 0.6mm 0.6mm 0.6mm 0.6mm

Page 14: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

12

Installation instructions

NOTE: 1.K* means the power supply of this model comes from indoor unit.2.K** indicates indoor power supply unit model with power line and plug.3.For 14K*-18K* models underTropical(T 3) Climate condition, the normal cross-section!area of Power cord and Power connecting cord is 2.5mm2 x4.Attention:The plug must be accessible even after the installation of the appliance in case there is a need todisconnect it. If not possible, connect appliance to a double-pole switching device with contactseparation of at least 3 mm2 placed in an accessible position even after installation.

INNOVAIR DC INVVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m

• Indoor UnitConnect the power cord to the indoor unit by connectingthe wires to the terminals on the control board individuallyin accordance with the outdoor unit connection.Note: For some models, it is necessary to remove the cabinet toconnect to the indoor unit terminal.

• Outdoor Unit1) Remove the access door from the unit by looseningthe screw. Connect the wires to the terminals on thecontrol board individually as follows.2) Secure the power cord onto the controlboard with cable clamp.3) Reinstall the access door to the original positionwith the screw.

4) Use a recognized circuit breaker for 24K model betweenthe power source and the unit. A disconnecting device toadequately disconnect all supply lines must be fitted.

4. Connecting of the Cable

CAUTION1. Never fail to have an individual power circuit specifically for the air conditioner. As for the method ofwiring, refer to the circuit diagram posted on the inside of the access door .2. Comfirm that the cable thickness is as specified in the power source specification.3. Check the wires and make sure that they are all tightly fastened after cable connection.4. Be sure to install an earth leakage circuit breaker in wet or moist areas.

Capacity (Btu/h) Power cord Power connecting cord

Type Type

7K-12K H07RN-F 1.0/1.5mm 2X3 H07RN-F 1.0/1.5mm 2X5

7K*-12K* H05W-F 1.0/ 1.5mm 2X3 H07RN-F 1.0/ 1.5mm 2X4

14K-18K H07RN-F 1.5mm 2X3 H07RN-F 1.5mm 2X5

14K*-18K* H05W-F 1.5/2.5mm 2X3 H07RN-F 1.5/2.5mm 2X4

H07RN-F 2.5mm 2X3 H07RN-F 0.75mm 2X4 21K-30K

H07RN-F 2.5mm 2X3 H07RN-F 2.5mm 2X5

21K*-30K* H05W-F 2.5mm 2X3 H07RN-F 2.5mm 2X4

21 K**-24K** H05W-F 1.5mm 2X3 H07RN-F 1.5mm 2X4

Normal cross- sectional area

Normal cross- sectional area

Cable Specifications

Page 15: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

13

Installation instructionsWiring diagramWarning: Before obtaining access to terminals, all supply circuits must be disconnected.Make sure that the color of the wires in the outdoor unit and terminal No. are the same asthose of the indoor unit.For K* and K** models, the power supply is connected from the indoor unit with a circuitbreaker. The diagram is reference only, and the actual terminal shall prevail.

• 7K*-12K* Model

Evaporator

Indoor unit control board Indoor unit control board

Power supply

Evaporator

ACN-IN

Power supply

• 14K*-30K* Model I 21 K**-24K** Model

L

Indoor unitTerminal

Outdoor unitTerminalt

Indoor unitTerminal

Outdoor unitTerminalt

Indoor unitTerminal

Outdoor unitTerminalt

Indoor unitTerminal

Outdoor unitTerminalt

Power supply Power supply

Power supply

• 7K-30K Model

Indoor unitTerminal

Outdoor unitTerminalt

Page 16: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

14

Installation instructions

INNOVAIR DC INVVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m

1. Install Drain Port and Drain Hose (for heat-pump model only)The condensate drains from the outdoor unit when the unit operatesin heating mode. In order not to disturb your neighbor and protectthe environment, install a drain port and a drain hose to direct thecondensate water. Just install the drain port and rubber washer tothe chassis of the outdoor unit, then connect a drain hose to theport as the right figure demonstrates.

2. Install and Fix Outdoor UnitFix with bolts and nuts tightly on a flat and strong floor.If installed on the wall or roof, make sure to fix the supporter well to prevent itfrom shaking due to serious vibration or strong wind.

3. Outdoor Unit Piping Connection• Remove the valve caps from the 2-way and 3-way valve.• Connect the pipes to the 2-way and 3-way valves separately according to the required torque.

4.Outdoor Unit Cable Connection (see previous page)

Outdoor unit installation

Page 17: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

15

Installation instructionsAir purgingThe air which contains moisture remaining in the refrigeration cycle may cause a malfunction on thecompressor. After connecting the indoor and outdoor units, release air and moisture from the refrigerantcycle using a vacuum pump, as shown below.

Note: To protect the environment, be sure not to discharge the refrigerant to the air directly.

How to Purge Air Tubes:(1) Unscrew and remove caps from 2 and 3-way valves.(2) Unscrew and remove cap from service valve.(3) Connect vacuum pump flexible hose to the service valve.(4) Start vacuum pump for 10-15 minutes until reaching a vacuum of 10 mm Hg absolutes.(5) With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop the vacuum pump.(6) Open 2-way valve , 1/4 turn, then close it after 10 seconds. Check tightness of all joints using liquid soap or an electronic leak detector.(7) Turn 2 and 3-way valves stem to fully close the valves. Disconnect the flexible vacuum pump hose.(8) Replace and tighten all valve caps.

Page 18: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

16

Installation instructions

INNOVAIR DC INVVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m

1. Unscrew and remove caps from 2 and 3-way valves.2. Unscrew and remove cap from service valve.3. Connect vacuum pump flexible hose to the service valve.4. Start vacuum pump for 10-15 minutes until reaching a vacuum of 10 mm Hg absolutes.5. With vacuum pump still running close the low pressure knob on vacuum pump manifold. Then stop the vacuum pump.6. Open 2-way valve , 1/4 turn, then close it after 10 seconds. Check tightness of all joints using liquid soap or an electronic leak detector.7. Turn 2 and 3-way valves stem to fully close the valves. Disconnect the flexible vacuum pump hose.8. Replace and tighten all valve caps.

Air purging

The air which contains moisture remaining in the refrigeration cycle may cause a malfunction on thecompressor. After connecting the indoor and outdoor units, release air and moisture from the refrigerantcycle using a vacuum pump, as shown below.

Note: To protect the environment, be sure not to discharge the refrigerant to the air directly.

How to Purge Air Tubes:

Page 19: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

17

6. TROUBLE SHOOTING

1. Indication on the outdoor unit: When the unit has the following trouble and the compressor stops running, the LED of outdoor control board will show the error sequence automatically: NOTE: ★:LIGHT O:FLASH ×:OFF Error code

Outdoor Failure Description LED1 LED2 LED3

The cause may be one of the following

Mark description: the lights flash every second for the following faults Normal � × � × � ×

Outdoor coil temperature sensor in trouble

★ ×� ★ a. the outdoor coil sensor connect is loose; b. the outdoor coil temperature sensor fails; c. the outdoor control board fails

Compressor exhaust temperature sensor in trouble

★ × ×

a. the compressor exhaust temperature sensor connect is loose; b. the compressor exhaust temperature sensor fails; c. the outdoor control board fails

Communication failure between the indoor unit and outdoor unit

� × ×�

O�

a. the communication cable connect is loose; b. the communication cable fails; c. the connection between the filter board and the outdoor control board is incorrect or loose; d. the connection between the filter board and the terminal is incorrect or loose; e. the indoor control board fails; f. the PFC board fails; g. the power board fails; h. the outdoor control board fails.

Current overload protection ★ O� ×

a. the fan motor runs abnormally; b. the condenser and evaporator is dirty; c. the air inlet and outlet is abnormal

Maximum current protection ★

O� ★ a. the outdoor control board is short circuit; b. the drive board is short circuit; c. the other components is short circuit

Communication trouble between outdoor unit and driver

× ★ ★ a. the connection wires connect loose b. the outdoor board or drive board fails;

Page 20: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

18

6. TROUBLE SHOOTING

INNOVAIR DC INVVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m

Outdoor EEPROM in trouble ★ ★ ★

a. the EEPROM chip is loose; b. the EEPROM chip is inserted with opposite direction; c. the EEPROM chip fails

Compressor exhaust temperature too high protection

×� O ★ a. the compressor exhaust temperature sensor fails;

b. the refrigerant of the unit is not enough

Outdoor ambient temperature sensor in trouble

★ ★ ×

a. the outdoor ambient temperature sensor connect is loose;

ambient temperature sensor fails; b. the outdoor c. the outdoor control board fails

Compressor shell temperature too high protection

× ★ O a. the compressor exhaust temperature sensor connect is loose b. the refrigerant of the unit is not enough

Anti-freeze protection with cooling or overload protection with heating in indoor unit

� × � O � O

a. the indoor coil temperature sensor connect is loose; b. the indoor coil temperature sensor fails; c. the indoor control board fails d. the refrigerant system is abnormal.

Compressor drive in trouble O � O

a. the outdoor drive board fails; b. the compressor fails

outdoor control board failsc. the

Outdoor fan motor locked rotor protection

O O ★

a. the connection of the outdoor fan motor is loose; b. there is something blocking the outdoor fan; c. the fan motor fails; d. the outdoor control board fails

Outdoor coil anti-overload protection with cooling

× ★ ×

a. the refrigerant is too much;b. the outdoor fan motor fails;c. the outdoor fan is broken; d. the condenser is dirty; e. the air inlet and air outlet of the indoor unitand the outdoor unit is not normal

Page 21: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

19

6. TROUBLE SHOOTING

IPM module protection × O� ×�

a. The IPM board fails; b. The outdoor fan is broken; c. The outdoor fan motor fails; d. The outdoor fan has been blocked ; e. The condenser is dirty; f. The outdoor unit has been installed without standard.

PFC protection O × ×� a. the PFC fails; b. the outdoor drive board fails

Compressor pre heating process O ★ O it is normal mode in cold weather

Chip in outdoor board in trouble ★ × O a. Using the wrong drive board;

b. Using the wrong compressor.

AC voltage higher or lower protection

★ ★ O

a. the supply voltage is higher or lower than normal; b. the inner supply voltage of the unit is higher or lower than normal

DC compressor start failure O O� × a. the outdoor drive board fails;

b. the compressor fails

Outdoor ambient temperature too low protection

★ O O� a. Outdoor ambient temperature too low

Mark description: the lights flash every two seconds for the following faults:

Protection against overheated outdoor radiator

Ο × × a. Radiator sensors fail b. Detection circuit of the sensor on the control panel fails

Protection of the system against too high pressure

Ο Ο ×

a. The pressure switch fails b. The pressure detection switch on the control panel fails c. The measured value of the system pressure exceeds the limit

When the compressor is in operation:

Mark description: ★:Light Ο:Flash ×:Off; the flash cycle is 1S No. LED1 LED2 LED3 Reasons for the current operating frequency

of the compressor are limited 1 Ο Ο Ο Normal frequency rising and decreasing, no

limitation 2 × × ★ Frequency decreasing or prohibition of

frequency rising caused by over-current

Page 22: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

20

6. TROUBLE SHOOTING

INNOVAIR DC INVVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m

3 × ★ ★ Frequency decreasing or prohibition of frequency rising caused by anti-freezing of refrigeration or anti-overload in heating

4 ★ × ★ Frequency decreasing or prohibition of frequency rising caused by too high compressor discharge temperature

5 Limit to the max operating frequency caused by too low power voltage

6 ★ ★ ★ Operation at fixed frequency (in the case of capability measuring or compulsory operation at fixed frequency)

7 Ο × × Protective frequency decreasing against outdoor overload (overpower, over frequency conversion rate, over torque, detection of DC under-voltage)

8 ★ × × Frequency decreasing caused by indoor and outdoor communication fault

9 × ★ Ο Frequency decreasing or prohibition of frequency rising protection against overload of outdoor coiled pipe

10 × ★ × Frequency decreasing or prohibition of frequency rising for power-saving when it is being used simultaneously with other appliances

2. Indication by the indoor unit: 2.1. The 7-segment tube of the indoor display board will show the error code

automatically when the unit has the following trouble:

Error code

Power Timer Running Sleep Remark:★Light o Flash x OFF

1 2 3 4 Content Remark The root cause is may be one of the following

EA

the error code will display when the communication between display board and control board is in trouble

a. The connection between the display board and control board is loose; b. The indoor control board fails. c. The wiring of the display board fails.

Page 23: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

21

6. TROUBLE SHOOTING2.2. When the unit has the following trouble and the compressor stops running, press the sleep button on

the remote controller 4 times in ten seconds and the 7-segment tube of the display board will show the error code as the following. If two malfunctions happened at the same time, you must press the sleep button 4 times again, and the LED will show the other error code.

Refer to the remote controller where the sleep key can set into 4 different combination ways (new design remote controller), when using to check the error codes only takes effect for pressing the sleep key 10 times in ten seconds instead of 4 times.

NOTE: If the troubleshooting inquiry display by 7-segment tube, then the error code will be displayed, otherwise only the LED of the display board will show.

Error code

Running Timer Sleep Power Remark:★Light o Flash x OFF

1 2 3 4 Content Remark The root cause is may be one of the following

0 Normal

1 x o x x

Failure of temperature sensor of outdoor coil

a. The outdoor temperature sensor is loose; b. The outdoor temperature sensor fails; c. The indoor control board fails

2

× Ο ★ ×

Compressor exhaust temperature sensor in trouble

a. the compressor exhaust temperature sensor connection is loose; b. the compressor exhaust temperature sensor fails; c. the outdoor control board fails

5

★ Ο × ×

IPM module protection

a. The IPM board fails; b. The outdoor fan is broken; c. The outdoor fan motor fails; d. The outdoor fan has been blocked ; e. The condenser is dirty; f. The outdoor unit has been installed without standard.

6

★ Ο × ★

AC voltage higher or lower protection

a. the supply voltage is higher or lower than normal; b. the inner supply voltage of the unit is higher or lower than normal

Page 24: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

22

6. TROUBLE SHOOTING

INNOVAIR DC INVVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m

7

★ Ο ★ ×

Communication failure between the indoor unit and outdoor unit

a. the communication cable connection is loose; b. the communication cable fails; c. the connection between the filter board and the outdoor control board is incorrect or loose; d. the connection between the filter board and the terminal is incorrect or loose; e. the indoor control board fails; f. the PFC board fails; g. the power board fails; h. the outdoor control board fails.

8

★ Ο ★ ★

Current overload protection

a. the fan motor runs abnormally; b. the condenser and evaporator are dirty; c. the air inlet and outlet is abnormal

9

× × Ο ×

Maximum current protection

a. the outdoor control board has short circuit; b. the drive board has short circuit; c. the other components have short circuit

10

× × Ο ★ Communication trouble between outdoor unit and driver

a. the connection wires connect loose b. the outdoor board or drive board fails;

11

× ★ Ο ×

Outdoor EEPROM in trouble

a. the EEPROM chip is loose; b. the EEPROM chip inserted with opposite direction; c. the EEPROM chip fails

12

× ★ Ο ★ Outdoor ambient temperature too low protection

Outdoor ambient temperature too low

Page 25: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

INNOVAIR DC INVERTER QUANTUM SERVICE MANUAL

23

6. TROUBLE SHOOTING

13

★ × Ο × Compressor exhaust temperature too high protection

a. the compressor exhaust temperature sensor fails; b. the refrigerant of the unit is not enough

14

★ × Ο ★ Outdoor ambient temperature sensor in trouble

a. the outdoor ambient temperature sensor connect is loose; b. the outdoor ambient temperature sensor fails; c. the outdoor control board fails

15

★ ★ Ο × Compressor shell temperature too high protection

a. the compressor exhaust temperature sensor connect ion is loose b. the refrigerant of the unit is not enough

16

Anti-freeze protection with cooling or overload protection with heating in

a. the indoor coil temperature sensor connect is loose; b. the indoor coil temperature sensor fails; c. the indoor control board fails d. the refrigerant system is abnormal.

17 PFC protection a. the PFC fails;

b. the outdoor drive board fails

18 DC compressor start failure

a. the outdoor drive board fails; b. the compressor fails

19 × × × Ο Compressor

drive in trouble

a. the outdoor drive board fails; b. the compressor fails c. the outdoor control board fails

20

★ × × Ο Outdoor fan motor locked rotor protection

a. the connection of the outdoor fan motor is loose; b. there is something blocking the outdoor fan; c. the fan motor fails; d. the outdoor control board fails

21

Outdoor coil anti-overload protection with cooling

a. the refrigerant is too much; b. the outdoor fan motor fails; c. the outdoor fan is broken; d. the condenser is dirty; e. the air inlet and air outlet of the indoor unit and the outdoor unit are not normal

22 Compressor pre heating process

it is normal mode in cold weather

Page 26: USER MANUAL - Innovair · QUANTUM INVERTER MINI SPLIT USER MANUAL WIN310C2V31 WIN414C2V31 WIN520C2V31 WIN628C2V31 WARNING • The information contained in the manual is intended for

24

6. TROUBLE SHOOTING

INNOVAIR DC INVVERTER QUANTUM SERVICE MANUAL

w w w . i n n o v a i r . c o m

39 o x ★ ★ Indoor fan motor run abnormally

a. There are something blocking the indoor fan motor; b. The fan motor cord connection is loose; c. The fan motor fails; d. The indoor control board fails

41 ★ ★ o ★ Detecting failures by zero-crossing

The indoor control board fails

The failure is detected when the room temperature sensor broken or shorted over 5 sec. The failure is detected when the temperature sensor of heater exchange is broken or shorted over 5 sec.The failure is detected when each setting data is not a match after the EEPPOM self-check two times.The failure occurs when the grounding signal is not detected after the appliance is powered ON.

24 Chip in outdoor board in trouble a. Using the wrong drive board;

b. Using the wrong compressor.

26 Overheated outdoor radiator

a. Radiator sensor fails b. Detection circuit of the sensor on the control panel fails

27

Protection against too high system pressure

a. The pressure switch fails b. The pressure detection switch on the control panel fails c. The measured value of system pressure exceeds the limit

33 o x x ★

Failure of temperature sensor of indoor room

a. The indoor room temperature sensor is loose; b. The indoor room temperature sensor fails; c. The indoor control board fails.

34 o x ★ x

Failure of temperature sensor of indoor coil temperature

a. The indoor coil temperature sensor is loose; b. The indoor coil temperature sensor fails; c. The indoor control board fails.

36

Ο ★ × ★

Communication failure between the indoor unit and outdoor unit

a. the communication cable connection is loose; b. the communication cable fails; c. the connection between the filter board and the outdoor control board is incorrect or loose; d. the connection between the filter board and the terminal is incorrect or loose; e. the indoor control board fails; f. the PFC board fails; g. the power board fails; h. the outdoor control board fails.

38 o ★ ★ ★ Indoor EEPROM failure

a. The EEPROM chip is loose; b. The indoor control board fails