Page 1: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Low voltage electrical distribution

User manual

Modbus communication

09/2009

Page 2: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Schneider Electric assumes no responsibility for any errors that may appear in this document. If you have

any suggestions for improvements or amendments or have found errors in this publication, please notify

us.

No part of this document may be reproduced in any form or by any means, electronic or mechanical,

including photocopying, without express written permission of Schneider Electric.

All pertinent state, regional, and local safety regulations must be observed when installing and using this

product. For reasons of safety and to help ensure compliance with documented system data, only the

manufacturer should perform repairs to components.

When devices are used for applications with technical safety requirements, the relevant instructions must

be followed.

Failure to use Schneider Electric software or approved software with our hardware products may result

in injury, harm, or improper operating results.

Failure to observe this information can result in injury or equipment damage.

© 2009 Schneider Electric. All rights reserved.

2 LV434107 09/2009

Page 3: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Table of Contents

Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

Chapter 1 Modbus Communication with Compact NSX. . . . . . . . . . . . . . . . . . . . . . . 9Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10

Modbus Communication Interface Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

Schematics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

Configuration of the Modbus Communication Interface Module . . . . . . . . . . . . . . . . . . . . . . . . 17

Chapter 2 Modbus Protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19Modbus Master-Slave Principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Modbus Functions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

Modbus Exception Codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

Write Protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Password Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

Command Interface. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

Command Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

Date Management. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

History Mechanism . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

Modbus Registers Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

Chapter 3 Micrologic Trip Unit Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 413.1 Micrologic Trip Unit Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

Real-Time Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

Minimum/Maximum Values of Real-Time Measurements. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

Energy Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

Demand Measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

Minimum/Maximum Measurements Reset Time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

Alarm History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

Trip History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

Maintenance Operation History. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59

Pre-Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

User-Defined Alarms. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Protection Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Configuration of the SDx Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Measurement Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72

Time-Stamped Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

Maintenance Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81

Miscellaneous . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84

3.2 Micrologic Trip Unit Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86

Protection Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87

Acknowledge Event Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92

Measurement Configuration Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93

Chapter 4 BSCM Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 994.1 BSCM Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100

Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101

Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102

Maintenance Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103

Event History . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104

4.2 BSCM Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106

Commands and Error Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107

Circuit Breaker Control Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 108

Counters Commands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110

LV434107 09/2009 3

Page 4: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Chapter 5 Modbus Communication Interface Module Data. . . . . . . . . . . . . . . . . . . . 1115.1 Modbus Communication Interface Module Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 112

Identification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113

Modbus Network Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 114

5.2 Modbus Communication Interface Module Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115

List of Modbus Communication Interface Module Commands . . . . . . . . . . . . . . . . . . . . . . . . . 116

Modbus Communication Interface Module Commands. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 117

5.3 Communication Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119

Communication Profile. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120

Modbus Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 121

Communication Profile Common Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 123

Readout Examples. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 131

Communication Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132

Appendices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 133Appendix A Cross references to Modbus Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . 135

Cross References to Modbus Registers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 135

4 LV434107 09/2009

Page 5: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

§

Safety Information

Important Information

NOTICE

Read these instructions carefully, and look at the equipment to become familiar with the device before

trying to install, operate, or maintain it. The following special messages may appear throughout this

documentation or on the equipment to warn of potential hazards or to call attention to information that

clarifies or simplifies a procedure.

PLEASE NOTE

Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.

No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this

material.

A qualified person is one who has skills and knowledge related to the construction and operation of

electrical equipment and the installation, and has received safety training to recognize and avoid the

hazards involved.

LV434107 09/2009 5

Page 6: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

6 LV434107 09/2009

Page 7: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

About the Book

At a Glance

Document Scope

The aim of this manual is to provide users, installers, and maintenance personnel with the technical

information needed to operate the Modbus protocol on Compact NSX 100 to 630 A circuit breakers.

Validity Note

This documentation is valid for Compact NSX 100 to 630 A circuit breakers.

Related Documents

You can download these technical publications and other technical information from our website at

www.schneider-electric.com.

User Comments

We welcome your comments about this document. You can reach us by e-mail at techcomm@schneider-

electric.com.

Title of Documentation Reference Number

Compact NSX circuit breakers - User manual LV434101

Micrologic 5 and 6 trip units - User manual LV434104

ULP system - User manual TRV99101

Compact NSX 100 to 630 A - Catalogue LVPED208001EN

LV434107 09/2009 7

Page 8: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

8 LV434107 09/2009

Page 9: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

LV434107 09/2009

1

Modbus Communication Interface Module

LV434107 09/2009

Modbus Communication with Compact NSX

Introduction

This chapter describes the Modbus communication interface module. This module enables a

Compact NSX circuit breaker to be connected to a Modbus network.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Introduction 10

Modbus Communication Interface Module 11

Schematics 14

Configuration of the Modbus Communication Interface Module 17

9

Page 10: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module

Introduction

General Description

The Modbus communication option enables a Compact NSX circuit breaker to be connected to a

supervisor or to any other device with a master Modbus communication channel.

The Modbus communication option is available for the following Compact NSX configurations:

Compact NSX circuit breaker with the BSCM (Breaker Status and Control Module) and with the

communicating motor mechanism

Compact NSX circuit breaker with Micrologic 5/6 trip unit

A Compact NSX circuit breaker is connected to a Modbus communication network through a Modbus

communication interface module.

Access to Functions

The Modbus communication option provides access to many functions, including:

reading of metering and diagnostic data

reading of status conditions and remote operations

transfer of time-stamped events

displaying protection settings

reading of the Compact NSX circuit breaker identification and configuration data

time-setting and synchronization

The list depends on the application, the Compact NSX circuit breaker with its Micrologic trip unit type, and

on the BSCM.

10 LV434107 09/2009

Page 11: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module

Modbus Communication Interface Module

General Description

The Modbus communication interface module enables a ULP (Universal Logic Plug) module, for example

a Compact NSX circuit breaker, to be connected to a Modbus network. Each circuit breaker has its own

Modbus communication interface module and a corresponding Modbus address.

1 5-pin screw type connector (Modbus connection and power supply)

2 Modbus address switches

3 Modbus traffic LED

4 Modbus locking pad

5 Test LED

6 Test button

7 Mechanical lock

8 2 RJ45 connectors

9 Stacking accessory

Mounting

The Modbus communication interface module is a DIN rail mounting device. The stacking accessory

enables the user to interconnect several Modbus communication interface modules without additional

wiring.

LV434107 09/2009 11

Page 12: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module

Description of the 5-pin connector

The 5-pin screw-type connector enables the Modbus communication interface module to be connected

to the Modbus network (2 wires) and to the 24 V DC power supply.

Each pin has a corresponding marking in order to facilitate the wiring operations.

Wiring of the 5-pin connector

NOTE: It is not allowed to connect more than 2 wires inside the same pin of the Modbus communication

interface module connector.

Modbus Address Switches

The Modbus communication interface module bears the Modbus address of the IMU (Intelligent Modular

Unit) to which it is connected. See the ULP System User manual for more information regarding the

intelligent modular unit.

The user defines the Modbus address using the 2 address switches on the front panel of the Modbus

communication interface module.

The address range is 1 to 99. Value 0 is forbidden because it is reserved for broadcasting commands.

The Modbus communication interface module is initially configured with address 99.

Example of the configuration of the address rotary switches for address 21:

Modbus Traffic LED

The Modbus traffic yellow LED informs the user about the traffic transmitted or received by the

Compact NSX circuit breaker over the Modbus network.

When the Modbus address switches are on value 0, the LED is steady ON.

When the Modbus address switches are on value anywhere between 1 and 99, the LED is ON during

the transmission and reception of messages, OFF otherwise.

Connector Marking Color Description Unshielded

Length

Stripped

Length

D1 Blue Communication pair

D1 : RS 485 B/B’ signal or Rx+/Tx+

D0 : RS 485 A/A’ signal or Rx-/Tx-

5 cm max 7 mm

D0 White

— Shield 2 cm max (1) 7 mm

0 V Black 0 V of the power supply 5 cm max 7 mm

24 V Red 24 V DC power supply

(1) To prevent electromagnetic disturbance, the unshielded length of the Modbus cable shield shall be minimized.

12 LV434107 09/2009

Page 13: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module

Modbus Locking Pad

The Modbus locking pad on the front panel of the Modbus communication interface module enables or

disables remote control commands to be sent over the Modbus network to the Modbus communication

interface module itself, and to the other modules (BSCM or Micrologic trip unit).

If the arrow points to the open padlock, remote control commands are enabled.

If the arrow points to the closed padlock, remote control commands are disabled.

The only remote control commands that are enabled even if the arrow points to the closed padlock are

the set absolute time and get current time commands. See Set Absolute Time, page 117.

For the other cases, the only way to modify parameters like the protection settings is through the

Micrologic trip unit front panel or with the RSU software using the maintenance module connected to the

Micrologic trip unit test plug.

Test Button

The test button tests the connection between all the modules connected to the Modbus communication

interface module: Micrologic trip unit, front display module FDM121, and the maintenance module.

Pressing the test button launches the connection test for 15 seconds.

During the test, all the modules keep working normally.

Test LED

The yellow test LED describes the connection between the modules that are connected to the Modbus

communication interface module.

Remote control commands enabled Remote control commands disabled

Test LED status Signification

ON: 50 ms / OFF: 950 ms Nominal mode (no test running)

ON: 250 ms / OFF: 250 ms ULP module address conflict: 2 identical ULP modules are

detected in the same intelligent modular unit.

ON: 500 ms / OFF: 500 ms Degraded mode (EEPROM is out of service)

ON: 1000 ms / OFF: 1000 ms Test mode

Always ON ULP connection is out of service

Always OFF No power supply

LV434107 09/2009 13

Page 14: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module

Schematics

General Description

Depending on the configuration of the Compact NSX circuit breaker, the user must connect the Modbus

communication interface module to the Compact NSX circuit breaker using one of the following

configurations:

connection of the Modbus communication interface module to the Micrologic trip unit

connection of the Modbus communication interface module to the BSCM (Breaker Status and Control

Module)

connection of the Modbus communication interface module to the BSCM and to the Micrologic trip unit

All connection configurations require the NSX Cord or the insulated NSX Cord for system voltages

greater than 480 V AC.

See the Compact NSX Circuit Breakers User manual for more information regarding the description and

mounting of the Compact NSX circuit breaker compliant products (Micrologic trip unit, BSCM, NSX Cord).

Connection of the Modbus Communication Interface Module to the Micrologic Trip Unit

The user can connect the Modbus communication interface module to the Micrologic trip unit using the

NSX Cord:

OK

Mode

Modbus24 V

14 LV434107 09/2009

Page 15: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module

Connection of the Modbus Communication Interface Module to the BSCM

The user can connect the Modbus communication interface module to the BSCM using the NSX Cord:

Connection of the Modbus Communication Interface Module to the BSCM and to the Micrologic Trip Unit

The user can connect the Modbus communication interface module to the BSCM and to the Micrologic

trip unit using the NSX Cord:

Modbus24 V

Modbus

24 V

LV434107 09/2009 15

Page 16: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module

The following figure presents the same connection schematic but with the insulated NSX Cord:

1 Electronic module with RJ45 female connector

2 1.3 m cable

3 Connector for Compact NSX internal connection

4 ULP cable

1

Modbus

24 V

4

2

3

16 LV434107 09/2009

Page 17: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module

Configuration of the Modbus Communication Interface Module

General Description

2 configurations of the Modbus communication interface module are available:

automatic configuration (Auto-Speed sensing ON): when connected to the Modbus network, the Modbus

communication interface module automatically detects the network parameters (default configuration).

personalized configuration (Auto-Speed sensing OFF): the user can personalize the network

parameters using the RSU (Remote Setting Utility) software.

Automatic Configuration

The user defines the Modbus slave address using the 2 address switches on the front panel of the

Modbus communication interface module. When connected to the Modbus network, the Modbus

communication interface module automatically detects the network speed and parity. The Auto-Speed

sensing algorithm tests the available baudrates and parities and automatically detects the network

parameters. The Modbus master must send at least 15 frames on the Modbus network so that the auto-

speed sensing algorithm works. It is recommended that the master sends the frames to the Modbus

address 248.

The transmission format is binary with 1 start bit, 8 data bits, 1 stop bit in case of even or odd parity, and

2 stop bits in case of no parity.

NOTE: In case of problems with the Auto-Speed sensing algorithm, it is recommended to follow this

procedure:

1. Set-up the Modbus communication interface module to Modbus address 1 (see Modbus Address Switches, page 12),

2. Send a Read Multiple Register (FC03) request to slave 1, at any address and for any number of

registers,

3. Send this request at least 15 times.

If the user decides to change the network speed or parity after the Modbus communication interface

module has automatically detected these settings, the Modbus communication interface module must be

restarted (power off/power on) in order to detect the new communication parameters.

Personalized Configuration

The user defines the Modbus slave address using the 2 address switches on the front panel of the

Modbus communication interface module.

The user personalizes the network parameters with the RSU software.

The following figure shows the Modbus communication interface module configuration tab with RSU:

When the Auto-Speed sensing option is disabled, the user selects the network baud rate and parity:

The supported baud rates are: 4800, 9600, 19200, and 38400 bauds.

The supported parities are: even, odd, and none (it is possible to select 1 stop bit or 2 stop bits in case

of no parity).

NOTE: It is not possible to change the Modbus address or the status of the locking pad with RSU.

The RSU software is available at www.schneider-electric.com.

See the RSU Online Help for more information regarding the Modbus communication interface module

with RSU.

LV434107 09/2009 17

Page 18: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module

18 LV434107 09/2009

Page 19: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

LV434107 09/2009

2

Modbus Protocol

LV434107 09/2009

Modbus Protocol

Introduction

This chapter describes the Modbus master-slave protocol and the principle of the command interface.

What's in this Chapter?

This chapter contains the following topics:

Topic Page

Modbus Master-Slave Principle 20

Modbus Functions 23

Modbus Exception Codes 26

Write Protection 27

Password Management 28

Command Interface 29

Command Examples 33

Date Management 35

History Mechanism 38

Modbus Registers Tables 39

19

Page 20: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Modbus Master-Slave Principle

Overview

The Modbus protocol exchanges information using a request-reply mechanism between a master (client)

and a slave (server). The master-slave principle is a model for a communication protocol in which one

device (the master) controls one or more other devices (the slaves). In a standard Modbus network there

are 1 master and up to 31 slaves.

A detailed description of the Modbus protocol is available at www.modbus.org.

Characteristics of the Master-Slave Principle

The master-slave principle is characterized as follows:

Only 1 master is connected to the network at a time.

Only the master can initiate communication and send requests to the slaves.

The master can address each slave individually using its specific address or all slaves simultaneously

using address 0.

The slaves can only send replies to the master.

The slaves cannot initiate communication, either to the master or to other slaves.

Master-Slave Communication Modes

The Modbus protocol can exchange information using 2 communication modes:

request-reply mode

broadcast mode

Request-Reply Mode

In request-reply mode, the master addresses a slave using the specific address of the slave. The slave

processes the request then replies to the master.

1 Request

2 Process

3 Reply

OK

Mode

OK

Mode

OK

Mode

OK

Mode

Master

Slave 1 Slave 2 Slave 3 Slave n

1

2

3

20 LV434107 09/2009

Page 21: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Broadcast Mode

The master can also address all slaves using address 0. This type of exchange is called broadcasting.

The slaves do not reply to broadcasting messages.

Response time

The response time Tr is the time needed by a slave to respond to a request sent by the master:

Values with the Modbus protocol:

Typical value < 10 ms for 90% of the exchanges

Maximum value ≈ 700ms, so it is recommanded to implement a 1second time-out after receiving a

Modbus request.

Data Exchange

The Modbus protocol uses 2 types of data:

bits

16-bit words called registers

Each register has a register number. Each type of data (bit or register) has a 16-bit address.

The messages exchanged with the Modbus protocol contain the address of the data to be processed.

Registers and Addresses

The address of register number n is n-1. For example, the address of register number 12000 is 11999.

In order to avoid confusion, the tables detailed in the following parts of this manual give both register

numbers and corresponding addresses.

OK

Mode

OK

Mode

OK

Mode

OK

Mode

Slave 1 Slave 2 Slave 3 Slave n

Master

LV434107 09/2009 21

Page 22: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Frames

All the frames exchanged with the Modbus protocol have a maximum size of 256 bytes and are composed

of 4 fields:

Field Definition Size Description

1 Slave number 1 byte Destination of the request

0: broadcasting (all slaves concerned)

1...247: unique destination

2 Function code 1 byte See next paragraph

3 Data or sub-function code n bytes Request or reply data

Sub-function code

4 Check 2 bytes CRC16 (to check transmission errors)

22 LV434107 09/2009

Page 23: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Modbus Functions

General Description

The Modbus protocol offers a number of functions that are used to read or write data over the Modbus

network. The Modbus protocol also offers diagnostic and network-management functions.

Only the Modbus functions handled by the Compact NSX circuit breaker are described here.

Read Functions

The following read functions are available:

Read register example

The following table shows how to read the RMS current on phase 1 (I1) in register 1016. The address of

register 1016 is 1016-1 = 1015 =0x03F7. The Modbus address of the Modbus slave is 47 = 0x2F.

The content of register 1016 (address 1015) is 0x022B = 555. Therefore the RMS current on phase 1 (I1)

is 555 A.

Read device identification example

The Read Device Identification function is used to access in a standardized manner the information

required to clearly identify a device. The description is made up of a set of objects (ASCII character

strings).

A complete description of the Read Device Identification function is available at www.modbus.org.

The coding for the identification of the Modbus communication interface module is the following:

Function code (dec) Sub-function code (dec) Name Description

3 — Read holding registers Read n output or internal words.

4 — Read input registers Read n input words.

43 14 Read device identification Read the identification data of the

slave.

Master request Slave reply

Field name Example Field name Example

Modbus slave address 0x2F Modbus slave address 0x2F

Function code 0x03 Function code 0x03

Address of the word to read (MSB) 0x03 Data length in bytes 0x02

Address of the word to read (LSB) 0xF7 Register value (MSB) 0x02

Number of registers (MSB) 0x00 Register value (LSB) 0x2B

Number of registers (LSB) 0x01 CRC MSB 0xXX

CRC MSB 0xXX CRC LSB 0xXX

CRC LSB 0xXX —

Name Type Description

Vendor name STRING ‘Schneider Electric’ (18 characters)

Product code STRING ‘TRV00210’

Firmware version STRING ‘VX.Y.Z’ (at least 6 characters)

Vendor URL STRING ‘www.schneider-electric.com’ (26 characters)

Product name STRING ‘ULP/Modbus SL communication interface module’

LV434107 09/2009 23

Page 24: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Scattered Holding Register Read Function

The scattered holding register read function is available:

The maximum value for n is 100.

The scattered holding register read function enables the user to:

avoid reading a large block of contiguous words when only few words are needed

avoid multiple use of functions 3 and 4 in order to read non-contiguous words

Example

The following table shows how to read addresses 101 = 0x65 and 103 = 0x67 of a Modbus slave. The

Modbus address of the Modbus slave is 47 = 0x2F.

Write Functions

The following write functions are available:

Function code (dec) Sub-function code (dec) Name Description

100 4 Read scattered holding register Read n non-contiguous words

Master request Slave reply

Field name Example Field name Example

Modbus slave address 0x2F Modbus slave address 0x2F

Function code 0x64 Function code 0x64

Data length in bytes 0x06 Data length in bytes 0x06

Sub-function code 0x04 Sub-function code 0x04

Transmission number (1) 0xXX Transmission number (1) 0xXX

Address of first word to read (MSB) 0x00 First word read (MSB) 0x12

Address of first word to read (LSB) 0x65 First word read (LSB) 0x0A

Address of second word to read (MSB) 0x00 Second word read (MSB) 0x74

Address of second word to read (LSB) 0x67 Second word read (LSB) 0x0C

CRC MSB 0xXX CRC MSB 0xXX

CRC LSB 0xXX CRC LSB 0xXX

(1) The master gives the transmission number in the request. The slave returns the same number in the reply.

Function code (dec) Sub-function code (dec) Name Description

6 — Preset single register Write 1 word

16 — Preset multiple registers Write n words

24 LV434107 09/2009

Page 25: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Diagnostic Functions

The following diagnostic functions are available:

Diagnostic Counters

Modbus uses diagnostic counters to enable performance and error management. The counters are

accessible using the Modbus diagnostic functions (function codes 8 and 11).The Modbus diagnostic

counters and the Modbus event counter are described in the following table:

Counters Reset

The counters are reset to 0

when they reach the maximum value 65535,

when they are reset by a Modbus command (function code 8, sub-function code 10),

when power supply is lost, or

when communication parameters are modified.

Function

code (dec)

Sub-function

code (dec)

Name Description

8 — Diagnostic Manage diagnostic counters

8 10 Clear counters and diagnostic register Reset all diagnostic counters

8 11 Return bus message counter Read the counter of correct bus messages

managed by the slave

8 12 Return bus communication error counter Read the counter of incorrect bus

messages managed by the slave

8 13 Return bus exception error counter Read the counter of exception responses

managed by the slave

8 14 Return slave message counter Read the counter of messages sent to the

slave

8 15 Return slave no response counter Read the counter of broadcast messages

8 16 Return slave negative acknowledge

counter

Read the counter of messages sent to the

slave but not answered because of the

Negative Acknowledge exception code 07

8 17 Return slave busy counter Read the counter of messages sent to the

slave but not answered because of the

Slave Device Busy exception code 06

8 18 Return bus overrun counter Read the counter of incorrect bus

messages due to overrun errors

11 — Get communication event counter Read Modbus event counter

Counter

number

Counter name Description

1 Bus message counter Counter of correct bus messages managed by the slave

2 Bus communication error counter Counter of incorrect bus messages managed by the slave

3 Slave exception error counter Counter of exception responses managed by the slave and

incorrect broadcast messages

4 Slave message counter Counter of messages sent to the slave

5 Slave no response counter Counter of broadcast messages

6 Slave negative acknowledge

counter

Counter of messages sent to the slave but not answered because

of the Negative Acknowledge exception code 07

7 Slave busy count Counter of messages sent to the slave but not answered because

of the Slave Device Busy exception code 06

8 Bus character overrun counter Counter of incorrect bus messages due to overrun errors

9 Comm. event counter Modbus event counter (this counter is read with function code 11)

LV434107 09/2009 25

Page 26: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Modbus Exception Codes

Exception Responses

Exception responses from either the master (client) or a slave (server) can result from data processing

errors. One of the following events can occur after a request from the master (client):

If the slave (server) receives the request from the master (client) without a communication error and

can handle the request correctly, it returns a normal response.

If the slave (server) does not receive the request from the master (client) due to a communication error,

it does not return a response. The master program eventually processes a timeout condition for the

request.

If the slave (server) receives the request from the master (client) but detects a communication error, it

does not return a response. The master program eventually processes a timeout condition for the

request.

If the slave (server) receives the request from the master (client) without a communication error, but

can not handle it (for example, the request is to read a register that does not exist), the server returns

an exception response to inform the master of the nature of the error.

Exception Frame

The slave sends an exception frame to the master to report an exception response. An exception frame

is composed of 4 fields:

Exception Codes

The exception response frame has two fields that differentiate it from a normal response frame:

The exception function code of the exception response is equal to the function code of the original

request plus 128 (0x80).

The exception code depends on the communication error that the slave encounters.

The following table describes the exception codes handled by the Compact NSX circuit breaker:

Field Definition Size Description

1 Slave number 1 byte Destination of the request

0: broadcasting (all slaves concerned)

1...247: unique destination

2 Exception function code 1 byte Request function code + 128 (0x80)

3 Exception code n bytes See next paragraph

4 Check 2 bytes CRC16 (to check transmission errors)

Exception

code (dec)

Name Description

01 Illegal function The function code received in the request is not an authorized action

for the slave. The slave may be in the wrong state to process a specific

request.

02 Illegal data address The data address received by the slave is not an authorized address

for the slave.

03 Illegal data value The value in the request data field is not an authorized value for the

slave.

04 Slave device failure The slave fails to perform a requested action because of an

unrecoverable error.

05 Acknowledge The slave accepts the request but needs a long time to process it.

06 Slave device busy The slave is busy processing another command. The master must

send the request once the slave is free.

07 Negative acknowledgment The slave can not perform the programming request sent by the

master.

08 Memory parity error The slave detects a parity error in the memory when attending to read

extended memory.

10 Gateway path unavailable The gateway is overloaded or not correctly configured.

11 Gateway target device

failed to respond

The slave is not present on the network.

26 LV434107 09/2009

Page 27: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Write Protection

General Description

Remote modifications of Modbus registers can either be dangerous to personnel near the circuit breaker

or can cause equipment damage if the protection settings are altered. Therefore, remote control

commands are hardware and software protected.

Hardware Protection

The Modbus locking pad on the front panel of the Modbus communication interface module enables or

disables remote control commands to be sent over the Modbus network to the Modbus communication

interface module itself, and to the other modules (BSCM or Micrologic trip unit).

If the arrow points to the open padlock, remote control commands are enabled.

If the arrow points to the closed padlock, remote control commands are disabled.

The only remote control commands that are enabled even if the arrow points to the closed padlock are

the set absolute time and get current time commands. See Set Absolute Time, page 117.

For the other cases, the only way to modify parameters like the protection settings is through the

Micrologic trip unit front panel or with the RSU software using the maintenance module connected to the

Micrologic trip unit test plug.

Software Protection

To prevent an inadvertent change to the trip unit configuration, remote modifications of the Modbus

registers is protected by both of the following:

a robust data structure and a set of dedicated Modbus registers

a multi-level password scheme

This combination is called the command interface. Failure to conform to this results in an error code and

the operation is not performed. The hardware protection has always precedence over the software

protection.

Remote control commands enabled Remote control commands disabled

LV434107 09/2009 27

Page 28: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Password Management

General Description

4 passwords are defined, each corresponding to a level.

A level is assigned to a role:

Levels 1, 2, and 3 are used for general purpose roles, like an operator role.

Level 4 is the administrator level. The administrator level is required to write the settings to the

Micrologic trip units using RSU.

For the Micrologic trip unit, all the commands are level 4 password protected except "Acknowledge a

latched output", "Reset minimum/maximum", and "Start/Stop synchronization" commands which are level

3 or 4 password protected.

For the BSCM, all the commands are level 4 password protected except "Open circuit breaker", "Close

circuit breaker", and "Reset circuit breaker" commands which are level 3 or 4 password protected.

For the Modbus communication interface module, all the commands are level 4 password protected

except "Get current time" and "Set absolute time" commands which require no password.

Default Passwords

The default password values are:

Password Modification with RSU

Passwords are modified with the RSU (Remote Setting Utility) software. The Commissioning user

profile (default user profile) enables the user to modify passwords.

Passwords are composed of exactly 4 ASCII characters.They are case sensitive and the allowed

characters are:

digits from 0 to 9

letters from a to z

letters from A to Z

Password Reset with RSU

If the default passwords have been changed, 3 cases require to reset the passwords to their default

values with RSU:

A password is forgotten.

A new module is added in the IMU (Intelligent Modular Unit): for example, a BSCM or a front display

module FDM121.

A faulty module is replaced in the IMU (Intelligent Modular Unit).

Resetting passwords with RSU is only available with the Schneider service user profile. See the RSU online help for more information regarding resetting passwords with RSU.

Password Level Default Value

Level 1 ‘1111’ = 0x31313131

Level 2 ‘2222’ = 0x32323232

Level 3 ‘3333’ = 0x33333333

Level 4 (administrator level) ‘0000’ = 0x30303030

28 LV434107 09/2009

Page 29: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Command Interface

General Description

Remote control commands are enabled when the Modbus locking pad is in the open position. Remote

modifications of the Modbus registers are performed through the command interface.

Each command has a specific code. For example, command code 45192 defines the command to setup

the long time protection parameters.

NOTE: In case of multimaster Modbus application, please consult our technical support.

Executing a Command

Follow these steps to execute a command:

Step Action

1 Load a buffer (word #0...19)

2 Write this buffer with a block write (Modbus function16) of 20 words, starting at register 8000.

3 Read the command status register 8021, and wait while its content shows the command is still in progress

(0x0003).If the command status does not change after a timeout (1s), please check the Modbus connection.

4 Read the error identifier in LSB of register 8021:

If LSB <> 0, then the command failed. Check the error identifier to understand the cause (see next

paragraph). For example, if register 8021 returns 5121 (0x1401), then the error identifier is 1, which means

that the password level is not correct (insufficient user rights).

If LSB = 0, then the command was executed with no errors.

LV434107 09/2009 29

Page 30: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Command Diagram

The following diagram shows the steps to follow in order to execute a command:

30 LV434107 09/2009

Page 31: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Command Data Structure

The command data structure is defined as a set of values written in registers from 8000 to 8149.

The 3 main areas are:

Input parameters: registers 8000 to 8015

The command specific parameters are in registers 8006 to 8015.

Command status: register 8021

Returned values: registers 8022 to 8149

Register Address Description Comments

8000 7999 Command Code Writing at this address triggers the command using the

parameters in the following registers.

8001 8000 Parameter length Number of bytes used for the parameters including this one

(from 10 to 30). This value is provided for each command.

8002 8001 Destination A constant value provided for each command. Default

value: 0x0000

8003 8002 Reserved A constant value provided for each command (0 or 1)

8004 8005 8003 8004 Password The password is composed of 4 ASCII bytes.

The password level to use depends on the command.

This information is provided for each command.

8006 8015 8005 8014 Additional Parameters Additional parameters define how the command is performed.

Some commands have no additional parameters.

8016 8015 Reserved Must be set to 0 (default value).

8017 8016 Reserved Must be set to 8019 (default value).

8018 8017 Reserved Must be set to 8020 (default value).

8019 8018 Reserved Must be set to 8021 (default value).

8020 8019 Reserved —

8021 8020 Command Status When the command exits the busy state, it holds the

completion code.

8022 8021 Data Buffer Size Number of bytes returned.

8023... 8149 8022... 8148 Data Buffer Returned values. It is empty if the previous word is 0.

LV434107 09/2009 31

Page 32: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Command Status

When the command terminates, the command status register contains the IMU module’s address (which

is different from the Modbus address) and the error identifier:

The MSB gives the address of the IMU module that generates the error. When the command is sent

to one IMU module, it is usually the same as the address found in the destination register. When it is

sent to all IMU modules, it is the address of the first module returning an error.

The following table lists the addresses of the modules:

The LSB gives the error identifier.

The following table lists the error identifiers:

The error identifiers listed in this table are generic. If a module or a command generates specific errors,

they will be described after the corresponding command.

Module IMU Module Address

Maintenance module 1 (0x01)

Front display module FDM121 2 (0x02)

Modbus communication interface module 3 (0x03)

BSCM (Breaker Status and Control Module) 17 (0x11)

Micrologic trip unit 20 (0x14)

Error Identifier Description

0 Successful command

1 Insufficient user rights (incorrect password)

2 Access violation (Modbus communication interface module locking pad is locked. See Modbus Locking Pad, page 13)

3 Unable to perform a read access

4 Unable to perform a write access

5 Unable to execute the requested service

6 Not enough memory

7 Allocated memory is too small

8 Resource is not available

9 Resource does not exist

10 Resource already exists

11 Resource is out of order

12 Access out of available memory

13 String is too long

14 Buffer is too small

15 Buffer is too big

16 Input argument is out of range

17 Requested security level is not supported

18 Requested component is not supported

19 Command is not supported

20 Input argument has an unsupported value

21 Internal error during command

22 Timeout during command

23 Checksum error during command

32 LV434107 09/2009

Page 33: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Command Examples

Open Circuit Breaker

The following table details the steps to perform in the master remote device to send a remote command

to open the circuit breaker with the BSCM (see Open Circuit Breaker, page 108). The command itself has

no parameters.

Reset Energy Measurements

The following table details the steps to perform to send a command to reset the minimum/maximum

energy measurements (see Reset Minimum/Maximum, page 94). The command itself has one

parameter.

Step Action

1 Load a buffer (word #0...19)

Load into word #0 the value 904, the code corresponding to the open circuit breaker command.

Load into word #1 the value 10, the length of the input parameters. The command itself has no

parameters, 10 is the length of the fixed part.

Load into word #2 the value 4353 (0x1101), the destination. This value is a constant for the command.It is

provided in the command description.

Load into word #3 the value 1.

Load into word #4 and #5 the 4 ASCII bytes for the level 3 or level 4 password. Assuming this password

is ‘ABcd’, load 16706 (0x4142) into word #4 and 25444 (0x6364) into word #5.

Load into word #17 the value 8019, a command setup constant.

Load into word #18 the value 8020, a command setup constant.

Load into word #19 the value 8021, a command setup constant.

2 Write this buffer with a block write (Modbus function 16) of 20 words, starting at register 8000.

3 Read the command status register 8021, and wait while its content shows the command is still in progress

(0x0003). If the command status does not change after a timeout (1s), please check the Modbus connection.

4 Read the error identifier in LSB of register 8021:

If LSB <> 0, then the command failed. Check the error identifier to understand the cause (see next

paragraph). For example, if register 8021 returns 4353 (0x1101), then the error identifier is 1, which

means that the password level is not correct (insufficient user rights).

If LSB = 0, then the command was executed with no errors.

Step Action

1 Load a buffer (word #0...19)

Load into word #0 the value 46728, the code corresponding to the reset minimum/maximum command.

Load into word #1 the value 12, the length of the input parameters. The command itself has one

parameter, add 2 bytes to 10 which is the length of the fixed part.

Load into word #2 the value 5121 (0x1401), the destination. This value is a constant for the command.

It is provided in the command description.

Load into word #3 the value 1.

Load into word #4 and #5 the 4 ASCII bytes for the level 3 or level 4 password. Assuming this password

is ‘PW57’, load 20599 (0x5077) into word #4 and 13623 (0x3537) into word #5.

Load into word #6 the value 512 (bit 0 set to one). This value requests that the energy measurement

minimum/maximum be reset.

Load into word #17 the value 8019, a command setup constant.

Load into word #18 the value 8020, a command setup constant.

Load into word #19 the value 8021, a command setup constant.

2 Write this buffer with a block write (Modbus function 16) of 20 words, starting at register 8000.

3 Read the command status register 8021, and wait while its content shows the command is still in progress

(0x0003). If the command status does not change after a timeout (1 s), please check the Modbus

connection.

4 Read the error identifier in LSB of register 8021:

If LSB <> 0, then the command failed. Check the error identifier to understand the cause (see next

paragraph). For example, if register 8021 returns 5121 (0x1401), then the error identifier is 1, which

means that the password level is not correct (insufficient user rights).

If LSB = 0, then the command was executed with no errors.

LV434107 09/2009 33

Page 34: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Read Date and Time

The following table details the steps to perform to send a command to read the date and time. The

command itself has no parameters.The date and time are returned in a buffer.

Step Action

1 Load a buffer (word #0...19)

Load into word #0 the value 768, the code corresponding to the read date/time command.

Load into word #1 the value 10, the length of the input parameters. The command itself has no

parameters, the length is the length of the fixed part which is 10.

Load into word #2 the value 768 (0x0300), the destination. This value is a constant for the command. It is

provided in the command description.

Load into word #3 the value 0.

Load into word #4 and #5 the value 0x0000 (no password required).

Load into word #17 the value 8019, a command setup constant.

Load into word #18 the value 8020, a command setup constant.

Load into word #19 the value 8021, a command setup constant.

2 Write this buffer with a block write (Modbus function 16) of 20 words, starting at register 8000.

3 Read the command status register 8021, and wait while its content shows the command is still in progress

(0x0003). If the command status does not change after a timeout (1s), please check the Modbus connection.

4 Read the error identifier in LSB of register 8021:

If LSB <> 0, then the command failed. Check the error identifier to understand the cause (see next

paragraph). For example, if register 8021 returns 783 (0x030F), then the error identifier is 1, which means

that the input argument is out of range (too many parameters).

If LSB = 0, then the command was executed with no errors.

5 If there were no errors, read the data buffer length in register 8022. Its value must be 8 for this command.

6 In the data buffer:

register 8023 holds the month in the MSB, the day in the LSB.

register 8024 holds the year offset in the MSB (add 2000 to get the year) and the hour in the LSB.

register 8025 holds the minutes in the MSB, the seconds in the LSB.

register 8026 holds the milliseconds.

34 LV434107 09/2009

Page 35: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Date Management

Introduction

Each module of the IMU (Intelligent Modular Unit) uses its date to time-stamp events and history

registers.

The date of the IMU modules is updated in 2 steps:

1. The Modbus master synchronizes the Modbus communication interface module (external

synchronization).

2. The Modbus communication interface module synchronizes the IMU modules (internal

synchronization).

Date Format

The date information is coded on 3 registers:

Registers 1 and 2 return the date in number of seconds since 01/01/2000:

Register 1 returns the MSB of the date.

Register 2 returns the LSB of the date.

Register 3 returns the complement in ms with the quality of the date.

The following table details the date registers:

External Synchronization

The user has 2 ways to externally synchronize the Modbus communication interface module:

with the RSU (Remote Setting Utility) software

with a Modbus request to the Modbus communication interface module. The Modbus request is

broadcasted to several Modbus communication interface modules to synchronize them or to one

specific Modbus communication interface module.

The Modbus communication interface module is considered as externally synchronized if the last

synchronization has occured within the last 2 hours (bit 12 = 1).

Internal Synchronization

When the Modbus communication interface module recieves the synchronization request, it broadcasts

it to all the modules within the IMU (Micrologic trip unit, BSCM, front display module FDM121,...).

An IMU module is considered as internally synchronized (bit 13 = 1) if the last external synchronization

has occured within the last 2 hours (bit 12 = 1).

Register Type Bit Description

Register 1

Register 2

UDINT — Date in number of seconds since 01/01/2000

Register 3 UINT — Complement in milliseconds with quality of the date

0...9 Encodes the milliseconds

10...11 Not used

12 Modbus communication interface module external synchronization status

0 = The Modbus communication interface module has not been externally

synchronized within the last 2 hours.

1 = The Modbus communication interface module has been externally

synchronized within the last 2 hours.

13 IMU module internal synchronization status

0 = The IMU module has not been internally synchronized.

1 = The IMU module has been internally synchronized.

14 Synchronization since last power on

0 = No

1 = Yes

15 Reserved

LV434107 09/2009 35

Page 36: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Date Counter

The date is counted in number of seconds since 01/01/2000.

In case of a power loss for an IMU module, the time counter is reset and will restart at 01/01/2000.

If an external synchronization occurs after a power loss, the time counter is updated and converts the

synchronization date to the corresponding number of seconds since 01/01/2000.

If a synchronization has never occured since the last power loss, then bit 14 = 0.

If a synchronization has occured since the last power loss, then bit 14 = 1.

Date Conversion Principle

To convert the date from number of seconds since 01/01/2000 to current date, the following rules apply:

1 non-leap year = 365 days

1 leap year = 366 days

Years 2000, 2004, 2008, 2012,...(multiple of 4) are leap years (except year 2100).

1 day = 86400 seconds

1 hour = 3600 seconds

1 minute = 60 seconds

The following table describes the steps to follow to convert the date from number of seconds since

01/01/2000 to current date:

The complement of the date in milliseconds is coded on bits 0...9 of register 3. Bits 10...15 return the

quality of the date (see Date Format, page 35).

To retrieve the complement in milliseconds, the user must use the logical AND operation between the

register value and 0x03FF.

For example, if register 3 returns 0x15B7, the complement in milliseconds is

0x15B7 AND 0x03FF = 0x01B7 = 439 ms.

Step Action

1 S = Number of seconds since 01/01/2000 = (content of register 1 x 65536) + (content of register 2)

2 S = 86400 x D + s

D = number of days since 01/01/2000

s = remaining number of seconds

3 D = (NL x 365) + (L x 366) + d

NL = number of non-leap years since year 2000

L = number of leap years since year 2000

d = remaining number of days for the current year

4 Date = d + 1 = current date. For example, if d = 303, the current date corresponds to the 304th day of the

year, which corresponds to October 31 for the year 2007.

5 s = (3600 x h) + s’

h = number of hours

s’ = remaining number of seconds

6 s’ = (60 x m) + s’’

m = number of minutes

s’’ = remaining number of seconds

7 The current time is h:m:s’’

36 LV434107 09/2009

Page 37: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Date Conversion Example

The following example shows the date conversion of minimum/maximum current reset (see

Minimum/Maximum Measurements Reset Time, page 50). Registers 2900 and 2901 return the date in

number of seconds since 01/01/2000. Register 2902 returns the complement in ms with the quality of the

date.

LV434107 09/2009 37

Page 38: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

History Mechanism

General Description

The Modbus history registers enable the user to track the occurrence of specific events and their

corresponding dates.

4 event history are available:

Alarm history: the alarm history format corresponds to a series of 10 records. Each record is composed

of 5 registers describing one alarm. See Alarm History, page 55.

Trip history: the trip history format corresponds to a series of 17 records. Each record is composed of

7 registers describing one trip. See Trip History, page 57.

Maintenance operation history: the maintenance operation history format corresponds to a series of

10 records. Each record is composed of 5 registers describing one maintenance operation. See

Maintenance Operation History, page 59.

BSCM event history: the BSCM event history format corresponds to a series of 10 records. Each

record is composed of 5 registers describing one BSCM event. See Event History, page 104.

History Mechanism

Each event is time-stamped using the date format described in Date Format, page 35.

When the history is full, the oldest event record is discarded to make room for the most recent event

record, which is pushed to the top of the history.

The records are ordered in decreasing occurrence time, the most recent occurrence is in the first record.

The following tables describe the history mechanism for a 10 records history format:

Before event E

After event E

After event E, event E-10 is lost.

History Reading

A block read request is necessary to read a history record (see Modbus function read n input words,

function code = 4, in Read Functions, page 23). For example, a block read request of 5 registers is

necessary to read the most recent alarm record of the alarm history format (see Alarm History, page 55).

Furthermore, to read the last n records of a history format, a block read request of (m) x (n) registers is

necessary, where m is the number of registers that compose the record. The history reading starts at the

beginning of the block read.

For example, a block read request of 7x3 = 21 registers is necessary to read the most recent 3 trip

records of the trip history format (see Trip History, page 57):

The first 7 registers describe the first record of the trip history format (most recent trip).

The next 7 registers describe the second record of the trip history format.

The last 7 registers describe the third record of the trip history format.

When not used, history registers return 32768 (0x8000).

Record 1 2 3 4 5 6 7 8 9 10

Event E-1 (most recent event) E-2 E-3 E-4 E-5 E-6 E-7 E-8 E-9 E-10 (oldest event)

Record 1 2 3 4 5 6 7 8 9 10

Event E (most recent event) E-1 E-2 E-3 E-4 E-5 E-6 E-7 E-8 E-9 (oldest event)

38 LV434107 09/2009

Page 39: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Modbus Registers Tables

General Description

The following chapters describe the Modbus registers of the Micrologic trip unit and the Modbus registers

of the modules connected to it. These registers provide information that can be read, like electrical

measures, protection configuration, and monitoring information. The command interface enables the user

to modify these registers in a controlled way.

The presentation rules of the Modbus registers are as follows:

The registers are grouped according to the module they relate to:

Micrologic trip unit: see Micrologic Trip Unit Registers, page 42.

BSCM (Breaker Status and Control Module: see BSCM Registers, page 100.

Modbus communication interface module: see Modbus Communication Interface Module Registers, page 112.

For each module, the registers are grouped in tables of logically related information. The tables are

presented in increasing address.

For each module, the commands are described:

Micrologic trip unit: see Micrologic Trip Unit Commands, page 86.

Breaker Status and Control Module (BSCM): see BSCM Commands, page 106.

Modbus communication interface module: see Modbus Communication Interface Module Commands, page 115.

The Cross References to Modbus Registers, page 135 provides an ordered list of the registers with a

cross reference to the page where these registers are described.

Table Format

Register tables have the following columns:

Register: a 16 bit register number in decimal.

Address: a 16 bit register address (one less than the register number).

RW: whether the register is read only (R) or read-write (RW).

X: the scale factor. A scale of 10 means that the register contains the value multiplied by 10. Hence

the real value is the value in the register divided by 10.

Example

Register 1034 contains the active power on phase 1 (see Active Power, page 44). The unit is kW and

the scale factor is 10.

If the register returns 231, this means that the real active power on phase 1 is

231/10 = 23.1 kW = 23100 W.

Unit: the unit the information is expressed in.

Type: the encoding data type.

Range: the permitted values for this variable, usually a subset of what the format allows.

A/E: the metering type of the Micrologic trip unit.

type A (Ammeter): current measurements

type E (Energy): current, voltage, power and energy measurements

Description: provides information about the register and restrictions that apply.

Data Types

The following data types are found in the Modbus registers tables:

Register Address RW X Unit Type Range A/E Description

Label Description Range

UINT 16 bit unsigned integer 0 to 65535

INT 16 bit signed integer -32768 to +32767

UDINT 32 bit unsigned integer 0 to 4 294 967 295

DINT 32 bit signed integer -2 147 483 648 to +2 147 483 647

STRING Text string 1 byte per character

LV434107 09/2009 39

Page 40: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Protocol

Notes

The Type column tells how many registers to read to get the variable. For instance UINT requires

reading one word, whereas DINT requires reading two words.

Some variables must be read as a set, like the long time protection variables. The whole set must be

read as a block. Reading a partial number results in an error (see History Reading, page 38).

Reading from an undocumented address results in a Modbus exception (see Modbus Exception Codes, page 26).

Variables stored in 2 words like energy or dates are stored in big-endian format: the most significant

word is transmitted first, the least significant second.

Numerical values are given in decimal. When it is useful to have the corresponding value in

hexadecimal, it is shown as a C language type constant: 0xdddd. For example, the decimal value 123

is represented in hexadecimal as: 0x007B.

Out of order and not applicable values are represented as 32768 (0x8000 or 0x80000000 for 32 bit

values).

Out of range values are represented as 32767 (0x7FFF, for 16 bit values only).

For measures that depend on the presence of neutral (as identified by register 3314, see System Type, page 72), reading the value will return 32768 (0x8000) if not applicable. For each table where it occurs,

it is explained in a footnote.

40 LV434107 09/2009

Page 41: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

LV434107 09/2009

3

Micrologic Trip Unit Data

LV434107 09/2009

Micrologic Trip Unit Data

Introduction

This chapter describes the Micrologic trip unit data.

What's in this Chapter?

This chapter contains the following sections:

Section Topic Page

3.1 Micrologic Trip Unit Registers 42

3.2 Micrologic Trip Unit Commands 86

41

Page 42: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

3.1 Micrologic Trip Unit Registers

Introduction

This section describes the Micrologic trip unit registers.

What's in this Section?

This section contains the following topics:

Topic Page

Real-Time Measurements 43

Minimum/Maximum Values of Real-Time Measurements 47

Energy Measurements 48

Demand Measurements 49

Minimum/Maximum Measurements Reset Time 50

Identification 51

Status 53

Alarm History 55

Trip History 57

Maintenance Operation History 59

Pre-Alarms 61

User-Defined Alarms 63

Protection Parameters 67

Configuration of the SDx Module 71

Measurement Parameters 72

Time-Stamped Information 74

Maintenance Indicators 81

Miscellaneous 84

42 LV434107 09/2009

Page 43: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Real-Time Measurements

General Description

The metering manager refreshes the real-time measurements every second. Real-time measurements

include:

voltage and voltage unbalance

current and current unbalance

active, reactive, apparent, and distortion power

reactive power with harmonic

power factor and fundamental power factor

frequency

THD (Total Harmonic Distortion)

Voltage

Register = 0 if voltage < 25 V.

Voltage Unbalance

Register Address RW X Unit Type Range A/E Description

1000 999 R 1 V UINT 0...850 E RMS phase-to-phase voltage V12

1001 1000 R 1 V UINT 0...850 E RMS phase-to-phase voltage V23

1002 1001 R 1 V UINT 0...850 E RMS phase-to-phase voltage V31

1003 1002 R 1 V UINT 0...850 E Phase-to-neutral voltage V1N (1)

1004 1003 R 1 V UINT 0...850 E RMS phase-to-neutral voltage V2N (1)

1005 1004 R 1 V UINT 0...850 E RMS phase-to-neutral voltage V3N (1)

1006 1005 R 1 V UINT 0...850 E Arithmetic mean of V12, V23, and V31:

(V12+V23+V31) / 3 = Vavg L-L.

1007 1006 R 1 V UINT 0...850 E Arithmetic mean of V1N, V2N, and V3N:

(V1N+V2N+V3N) / 3 = Vavg L-N (1)

1145 1144 R 1 V UINT 0...850 E Vmax: maximum of V12, V23, and V31

1146 1145 R 1 V UINT 0...850 E Vmin: minimum of V12, V23, and V31

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

1008 1007 R 10 % INT -

1000...+1000

E V12 phase-to-phase voltage unbalance with

respect to the arithmetic mean of phase-to-

phase voltages

1009 1008 R 10 % INT -

1000...+1000

E V23 phase-to-phase voltage unbalance with

respect to the arithmetic mean of phase-to-

phase voltages

1010 1009 R 10 % INT -

1000...+1000

E V31 phase-to-phase voltage unbalance with

respect to the arithmetic mean of phase-to-

phase voltages

1011 1010 R 10 % INT -

1000...+1000

E V1N phase-to-neutral voltage with respect to

the arithmetic mean of phase-to-neutral

voltages (1)

1012 1011 R 10 % INT -

1000...+1000

E V2N phase-to-neutral voltage with respect to

the arithmetic mean of phase-to-neutral

voltages (1)

1013 1012 R 10 % INT -

1000...+1000

E V3N phase-to-neutral voltage with respect to

the arithmetic mean of phase-to-neutral

voltages (1)

1014 1013 R 10 % INT -

1000...+1000

E Maximum phase-to-phase voltage unbalance

value of registers 1008, 1009, and 1010

1015 1014 R 10 % INT -

1000...+1000

E Maximum phase-to-neutral voltage unbalance

value of registers 1011, 1012, and 1013 (1)

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

LV434107 09/2009 43

Page 44: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Current

Current Unbalance

Active Power

The sign of the active power depends on the configuration of register 3316. See Power Flow Sign, page 72.

Reactive Power

The sign of the reactive power depends on the configuration of register 3316. See Power Flow Sign, page 72.

Register Address RW X Unit Type Range A/E Description

1016 1015 R 1 A UINT 0...20xIn A/E RMS current on phase 1: I1

1017 1016 R 1 A UINT 0...20xIn A/E RMS current on phase 2: I2

1018 1017 R 1 A UINT 0...20xIn A/E RMS current on phase 3: I3

1019 1018 R 1 A UINT 0...20xIn A/E RMS current on neutral: IN (1)

1020 1019 R 1 A UINT 0...20xIn A/E Maximum of I1, I2, I3, and IN

1021 1020 R 1 % UINT 0...4000 A/E % of Ig setting

1022 1021 R 1 % UINT 0...4000 A/E % of IΔn setting

1026 1025 R 1 A UINT 0...20xIn A/E Minimum of I1, I2, and I3

1027 1026 R 1 A UINT 0...20xIn A/E Arithmetic mean of I1, I2, and I3: (I1+I2+I3) / 3 = Iavg

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 31 or 40.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

1028 1027 R 10 % INT -1000...+1000 E I1 current unbalance with respect to the

arithmetic mean of the phase currents

1029 1028 R 10 % INT -1000...+1000 E I2 current unbalance with respect to the

arithmetic mean of the phase currents

1030 1029 R 10 % INT -1000...+1000 E I3 current unbalance with respect to the

arithmetic mean of the phase currents

1031 1030 R 10 % INT -1000...+1000 E IN current unbalance with respect to the

arithmetic mean of the phase currents (1)

1032 1031 R 10 % INT -1000...+1000 E Maximum current unbalance value of

registers 1028, 1029, and 1030

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 31 or 40.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

1034 1033 R 10 kW INT -10000...+10000 E Active power on phase 1: P1 (1)

1035 1034 R 10 kW INT -10000...+10000 E Active power on phase 2: P2 (1)

1036 1035 R 10 kW INT -10000...+10000 E Active power on phase 3: P3 (1)

1037 1036 R 10 kW INT -30000...+30000 E Total active power: Ptot

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

1038 1037 R 10 kVAr INT -10000...+10000 E Reactive power on phase 1: Q1 (1)

1039 1038 R 10 kVAr INT -10000...+10000 E Reactive power on phase 2: Q2 (1)

1040 1039 R 10 kVAr INT -10000...+10000 E Reactive power on phase 3: Q3 (1)

1041 1040 R 10 kVAr INT -30000...+30000 E Total reactive power: Qtot

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

44 LV434107 09/2009

Page 45: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Apparent Power

Power Factor

The sign of the power factor depends on the configuration of register 3318. See Power Factor Sign, page 72.

Fundamental Power Factor (cosϕ)

The sign of the fundamental power factor (cosϕ) depends on the configuration of register 3318. See

Power Factor Sign, page 72.

Frequency

When the software cannot calculate the frequency it returns Not Evaluated = 32768 (0x8000).

Fundamental Reactive Power

The sign of the reactive power depends on the configuration of register 3316. See Power Flow Sign, page 72.

Register Address RW X Unit Type Range A/E Description

1042 1041 R 10 kVA UINT 0...10000 E Apparent power on phase 1: S1 (1)

1043 1042 R 10 kVA UINT 0...10000 E Apparent power on phase 2: S2 (1)

1044 1043 R 10 kVA UINT 0...10000 E Apparent power on phase 3: S3 (1)

1045 1044 R 10 kVA UINT 0...30000 E Total apparent power: Stot

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

1046 1045 R 100 — INT -100...+100 E Power factor on phase 1:PF1 (1)

1047 1046 R 100 — INT -100...+100 E Power factor on phase 2: PF2 (1)

1048 1047 R 100 — INT -100...+100 E Power factor on phase 3: PF3 (1)

1049 1048 R 100 — INT -100...+100 E Total power factor: PF

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

1050 1049 R 100 — INT -100...+100 E Fundamental power factor on phase 1: cosϕ1 (1)

1051 1050 R 100 — INT -100...+100 E Fundamental power factor on phase 2: cosϕ2 (1)

1052 1051 R 100 — INT -100...+100 E Fundamental power factor on phase 3: cosϕ3 (1)

1053 1052 R 100 — INT -100...+100 E Total fundamental power factor: cosϕ

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

1054 1053 R 10 Hz UINT 150...4400 E Network frequency: F

Register Address RW X Unit Type Range A/E Description

1080 1079 R 10 kVAr INT -10000

...+10000

E Fundamental reactive power on phase 1: Q1 Fund (1)

1081 1080 R 10 kVAr INT -10000

...+10000

E Fundamental reactive power on phase 2: Q2 Fund (1)

1082 1081 R 10 kVAr INT -10000

...+10000

E Fundamental reactive power on phase 3: Q3 Fund (1)

1083 1082 R 10 kVAr INT -30000

...+30000

E Total fundamental reactive power: Qtot Fund

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

LV434107 09/2009 45

Page 46: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Distortion Power

Total Harmonic Distortion (THD)

Thermal Image of Motor

The thermal image of motor is available for motor application only.

Register Address RW X Unit Type Range A/E Description

1088 1087 R 10 kVAr UINT 0...10000 E Distortion power on phase 1: D1 (1)

1089 1088 R 10 kVAr UINT 0...10000 E Distortion power on phase 2: D2 (1)

1090 1089 R 10 kVAr UINT 0...10000 E Distortion power on phase 3: D3 (1)

1091 1090 R 10 kVAr UINT 0...30000 E Total distortion power: Dtot

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

1092 1091 R 10 % UINT 0...32766 E Total harmonic distortion of V12 compared to the

fundamental

1093 1092 R 10 % UINT 0...32766 E Total harmonic distortion of V23 compared to the

fundamental

1094 1093 R 10 % UINT 0...32766 E Total harmonic distortion of V31 compared to the

fundamental

1095 1094 R 10 % UINT 0...32766 E Total harmonic distortion of V1N compared to the

fundamental (1)

1096 1095 R 10 % UINT 0...32766 E Total harmonic distortion of V2N compared to the

fundamental (1)

1097 1096 R 10 % UINT 0...32766 E Total harmonic distortion of V3N compared to the

fundamental (1)

1098 1097 R 10 % UINT 0...32766 E Total harmonic distortion of I1 compared to the

fundamental

1099 1098 R 10 % UINT 0...32766 E Total harmonic distortion of I2 compared to the

fundamental

1100 1099 R 10 % UINT 0...32766 E Total harmonic distortion of I3 compared to the

fundamental

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 30 or 31.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

1144 1143 R 1 % UINT 0...32766 E Ith image

46 LV434107 09/2009

Page 47: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Minimum/Maximum Values of Real-Time Measurements

Minimum/Maximum Measurements Rule

Minimum and maximum measurements take into account the absolute value of real-time measurements.

Therefore the following rule applies:

0<10<200<-400<600<-3800.

In this case:

the minimeter = 0.

the maximeter = -3800

NOTE: This rule does not apply for the power factor (PF) and for the fundamental power factor (cosϕ):

PF max (or cosϕ max) is obtained for the smallest positive value of PF (or cosϕ).

PF min (or cosϕ min) is obtained for the highest negative value of PF (or cosϕ).

The reset minimum/maximum command (command code = 46728) configures the content of the

minimum/maximum real-time measurements registers.

Minimum of Real-Time Measurements

Registers 1300 to 1599 hold the minimum values of real-time metering parameters:

The address of the minimum value of a real-time metering parameter is equal to the address of the

real-time metering parameter plus 300.

Examples

Register 1300 holds the minimum value of the phase-to-phase voltage V12 (register 1000).

Register 1316 holds the minimum value of the current on phase 1 (register 1016).

The order of the registers is the same as that of the real-time metering variables.

The scale factors of the minimum values are the same as those of the real-time metering parameters.

The minimum values of unbalance current and unbalance voltage are not available.

The minimum values of Imin (register 1026), Vmax (register 1145), and Vmin (register 1146) are not

available.

Maximum of Real-Time Measurements

Registers 1600 to 1899 hold the maximum values of real-time metering parameters:

The addresses of the maximum value of a real-time metering parameter is equal to the addresses of

the real-time metering parameter plus 600.

Examples

Register 1600 holds the maximum value of the phase-to-phase voltage V12 (register 1000).

Register 1616 holds the maximum value of the current on phase 1 (register 1016).

The order of the registers is the same as that of the real-time metering variables.

The scale factors of the maximum values are the same as those of the real-time metering parameters.

The maximum values of Imin (register 1026), Vmax (register 1145), and Vmin (register 1146) are not

available.

LV434107 09/2009 47

Page 48: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Energy Measurements

General Description

The metering manager refreshes energy measurements every 1 second. Energy measurements are

saved every 1 hour in the non volatile memory of the Micrologic trip unit.

Energy measurements include:

active energy Ep

reactive energy Eq

apparent energy Es

active energy counted positively (EpIn) or negatively (EpOut), according to the configuration of register

3316. See Power Flow Sign, page 72.

reactive energy counted positively (EqIn) or negatively (EqOut), according to the configuration of

register 3316. See Power Flow Sign, page 72.

active energy and reactive energy are accumulated according to the configuration of register 3324

(absolute mode by default). See Energy Accumulation Mode, page 73.

Examples

If Ep = 7589 kWh, then:

register 2000 = 0 (0x0000)

register 2001 = 7589 (0x1DA5)

If Ep = 4589625 kWh, then:

register 2000 = 70 (0x0046)

register 2001 = 2105 (0x0839)

4589625 = 70x65536 + 2105

Energies are stored in big-endian format: the most significant word is transmitted first, the least significant

second.

The reset minimum/maximum command (command code = 46728) configures the content of the energy

registers.

Register Address RW X Unit Type Range A/E Description

2000

2001

1999

2000

RW 1 kWh DINT -1 999 999 999

...+1 999 999 999

E Active energy: Ep

2004

2005

2003

2004

RW 1 kVArh DINT -1 999 999 999

...+1 999 999 999

E Reactive energy: Eq

2008

2009

2007

2008

RW 1 kWh UDINT 0...1 999 999 999 E Active energy counted positively: EpIn

2012

2013

2011

2012

RW 1 kWh UDINT 0...1 999 999 999 E Active energy counted negatively: EpOut

2016

2017

2015

2016

RW 1 kVArh UDINT 0...1 999 999 999 E Reactive energy counted positively: EqIn

2020

2021

2019

2020

RW 1 kVArh UDINT 0...1 999 999 999 E Reactive energy counted negatively:

EqOut

2024

2025

2023

2024

RW 1 kVAh UDINT 0...1 999 999 999 E Apparent energy: Es

2028

2029

2027

2028

R 1 kWh UDINT 0...1 999 999 999 E Cumulative active energy counted

positively (not resetable): EpIn

2030

2031

2029

2030

R 1 kWh UDINT 0...1 999 999 999 E Cumulative active energy counted

negatively (not resetable): EpOut

48 LV434107 09/2009

Page 49: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Demand Measurements

General Description

Demand registers include:

current demand

active, reactive, and apparent power demand

The window duration of current demand depends on the configuration of register 3352. See Demand Time, page 73.

The window duration and the window type of power demand depend on the configuration of registers

3354 and 3355. See Demand Time, page 73.

The metering manager refreshes the demand measurements every 1 minute with the sliding window

type.

The metering manager refreshes the demand measurements at the end of the window interval with the

block window type.

Current Demand

Active Power Demand

Reactive Power Demand

Apparent Power Demand

Register Address RW X Unit Type Range A/E Description

2200 2199 R 1 A UINT 0...20xIn E Current demand on phase 1: I1 Dmd

2201 2200 R 1 A UINT 0...20xIn E Current demand on phase 2: I2 Dmd

2202 2201 R 1 A UINT 0...20xIn E Current demand on phase 3: I3 Dmd

2203 2202 R 1 A UINT 0...20xIn E Current demand on the neutral: IN Dmd (1)

2204 2203 R 1 A UINT 0...20xIn E Maximum of current demand on phase 1: I1 Peak Dmd

2205 2204 R 1 A UINT 0...20xIn E Maximum of current demand on phase 2: I2 Peak Dmd

2206 2205 R 1 A UINT 0...20xIn E Maximum of current demand on phase 3: I3 Peak Dmd

2207 2206 R 1 A UINT 0...20xIn E Maximum of current demand on the neutral:

IN Peak Dmd (1)

(1) Value not accessible for motor application and not accessible when the system type in register 3314 is 31 or 40.

See System Type, page 72.

Register Address RW X Unit Type Range A/E Description

2224 2223 R 10 kW INT -30000...+30000 E Total active power demand: P Dmd (1)

2225 2224 R 10 kW INT -30000...+30000 E Maximum of total active power demand:

P Peak Dmd

(1) For the block window type, this value is updated at the end of the window interval. For the sliding window type,

the value is updated every 1 minute.

Register Address RW X Unit Type Range A/E Description

2230 2229 R 10 kVAr INT -30000...+30000 E Total reactive power demand: Q Dmd (1)

2231 2230 R 10 kVAr INT -30000...+30000 E Maximum of total reactive power demand:

Q Peak Dmd

(1) For the block window type, this value is updated at the end of the window interval. For the sliding window type,

the value is updated every 1 minute.

Register Address RW X Unit Type Range A/E Description

2236 2235 R 10 kVA UINT 0...30000 E Total apparent power demand: S Dmd (1)

2237 2236 R 10 kVA UINT 0...30000 E Maximum of total apparent power demand:

S Peak Dmd

(1) For the block window type, this value is updated at the end of the window interval. For the sliding window type,

the value is updated every 1 minute.

LV434107 09/2009 49

Page 50: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Minimum/Maximum Measurements Reset Time

Minimum/Maximum Measurements Reset Time

The minimum/maximum measurements reset time registers enable the user to know all the dates relative

to the last reset minimum/maximum command.

The reset minimum/maximum command (command code 46728) configures the content of the reset

minimum/maximum registers.

A block read request of 30 registers is necessary to read the minimum/maximum measurements reset

time (see History Reading, page 38).

Register Address RW X Unit Type Range A/E Description (1)

2900

2901

2899

2900

RW 1 s UDINT — A/E Date of reset of minimum/maximum current, in

number of seconds since 01/01/2000

2902 2901 RW 1 ms UINT — A/E Complement in ms with quality of the date

2903

2904

2902

2903

RW 1 s UDINT — E Date of reset of minimum/maximum voltage, in

number of seconds since 01/01/2000

2905 2904 RW 1 ms UINT — E Complement in ms with quality of the date

2906

2907

2905

2906

RW 1 s UDINT — E Date of reset of minimum/maximum power (P, Q,

S), in number of seconds since 01/01/2000

2908 2907 RW 1 ms UINT — E Complement in ms with quality of the date

2909

2910

2908

2909

RW 1 s UDINT — E Date of reset of minimum/maximum power factor

and cosϕ, in number of seconds since 01/01/2000

2911 2910 RW 1 ms UINT — E Complement in ms with quality of the date

2912

2913

2911

2912

RW 1 s UDINT — E Date of reset of minimum/maximum total harmonic

distortion, in number of seconds since 01/01/2000

2914 2913 RW 1 ms UINT — E Complement in ms with quality of the date

2915

2916

2914

2915

RW 1 s UDINT — E Date of reset of peak current demand, in number

of seconds since 01/01/2000

2917 2916 RW 1 ms UINT — E Complement in ms with quality of the date

2918

2919

2917

2918

RW 1 s UDINT — E Date of reset of peak active, reactive and apparent

power demand, in number of seconds since

01/01/2000

2920 2919 RW 1 ms UINT — E Complement in ms with quality of the date

2921

2922

2920

2921

RW 1 s UDINT — E Date of reset of minimum/maximum frequency, in

number of seconds since 01/01/2000

2923 2922 RW 1 ms UINT — E Complement in ms with quality of the date

2924

2925

2923

2924

RW 1 s UDINT — E Date of reset of minimum/maximum thermal image

of motor, in number of seconds since 01/01/2000

(motor application only)

2926 2925 RW 1 ms UINT — E Complement in ms with quality of the date

2927

2928

2926

2927

RW 1 s UDINT — E Date of reset of energy (active, reactive, and

apparent), in number of seconds since 01/01/2000

2929 2928 RW 1 ms UINT — E Complement in ms with quality of the date

(1) See Date Format, page 35.

50 LV434107 09/2009

Page 51: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Identification

Serial Number

The Micrologic trip unit serial number is composed of a maximum of 11 alphanumeric characters with the

following format: PPYYWWDnnnn.

PP = plant code

YY = year of fabrication (05...99)

WW = week of fabrication (01...53)

D = day of fabrication (1...7)

nnnn = sequence number (0001...9999)

A block read request of 6 registers is necessary to read the Micrologic trip unit serial number (see History Reading, page 38).

Hardware Version

Square D Identification

Protection Type

Metering Type

Application

Register Address RW X Unit Type Range A/E Description

8700 8699 R — — STRING — A/E ‘PP’

8701 8700 R — — STRING 05...99 A/E ‘YY’

8702 8701 R — — STRING 01...53 A/E ‘WW’

8703 8702 R — — STRING 1...7 A/E ‘Dn’

8704 8703 R — — STRING 00...99 A/E ‘nn’

8705 8704 R — — STRING 01...99 A/E ‘n’ (the NULL character ends the serial number)

Register Address RW X Unit Type Range A/E Description

8709 8708 R 1 — UINT 0...15 A/E Hardware version of the Micrologic trip unit

Register Address RW X Unit Type Range A/E Description

8716 8715 R — — UINT 15143...15145 A/E Square D identification

15143 = distribution application, type A

15144 = distribution application, type E

15145 = motor application, type E

Register Address RW X Unit Type Range A/E Description

8740 8739 R — — STRING 52...73 A/E Micrologic trip unit protection type

For Compact NSX 100/250:

‘52’ = LSI, ‘62’ = LSIG, ‘72’ = LSIV

For Compact NSX 400/630:

‘53’ = LSI, ‘63’ = LSIG, ‘73’ = LSIV

Register Address RW X Unit Type Range A/E Description

8741 8740 R — — STRING A...E A/E Micrologic trip unit metering type: ‘A’ or ‘E’

Register Address RW X Unit Type Range A/E Description

8747 8746 R — — UINT 1...2 A/E Application

1 = distribution

2 = motor

LV434107 09/2009 51

Page 52: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Standard

Nominal Current

Pole

16 Hz 2/3

Firmware Version

A block read request of 5 registers is necessary to read the Micrologic trip unit firmware version (see

History Reading, page 38).

Part Number

The part number starts with LV4 characters and has the following format: LV4XYZTW.

A block read request of 4 registers is necessary to read the Micrologic trip unit part number (see History Reading, page 38).

Register Address RW X Unit Type Range A/E Description

8748 8747 R — — UINT 1...2 A/E Standard

1 = UL

2 = IEC

Register Address RW X Unit Type Range A/E Description

8750 8749 R 1 A UINT 0...8000 A/E Circuit breaker nominal current In

Register Address RW X Unit Type Range A/E Description

8751 8750 R — — UINT 0...1 A/E 0 = 3-pole

1 = 4-pole

Register Address RW X Unit Type Range A/E Description

8752 8751 R — — UINT 0...1 A/E 0 = not a 16 Hz 2/3 Micrologic trip unit application

1 = 16 Hz 2/3 Micrologic trip unit application

Register Address RW X Unit Type Range A/E Description

29994...

29998

29993...

29997

R — — STRING — A/E The Micrologic trip unit firmware version starts with

a V character and has the following format: VX.Y.Z.

X, Y, and Z are STRING type and in the

1...999 range.

Register Address RW X Unit Type Range A/E Description

30000 29999 R — — STRING — A/E Example: ‘LV’

30001 30000 R — — STRING — A/E Example: ‘4X’

30002 30001 R — — STRING — A/E Example: ‘YZ’

30003 30002 R — — STRING — A/E Example: ‘TW’

52 LV434107 09/2009

Page 53: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Status

Alarms Status

The alarms status register tracks the current status of the alarms.

If the alarm bit is set to 0, then the alarm is not active.

If the alarm bit is set to 1, then the alarm is active.

The following table details the physical values for each bit of the alarms status register:

SDx Module Status

The SDx module status register tracks the status and the validity of the SDx outputs (2 outputs

maximum).

If the status bit is set to 0, then the output is open.

If the status bit is set to 1, then the output is closed.

If the validity bit is set to 0, then the output status is unknown.

If the validity bit is set to 1, then the output status is known.

The following table details the physical values for each bit of the SDx module status register:

Register Address RW X Unit Type Range A/E Bit Description

5704 5703 R — — UINT — A/E — Alarms status register

A/E 0 User-defined alarm 201

A/E 1 User-defined alarm 202

A/E 2 User-defined alarm 203

A/E 3 User-defined alarm 204

A/E 4 User-defined alarm 205

A/E 5 User-defined alarm 206

A/E 6 User-defined alarm 207

A/E 7 User-defined alarm 208

A/E 8 User-defined alarm 209

A/E 9 User-defined alarm 210

A/E 10 Long time protection Ir pre-alarm (PAL Ir)

A/E 11 Earth leakage protection IΔn pre-alarm

(PAL IΔn)

A/E 12 Ground fault protection Ig pre-alarm (PAL Ig)

— 13...15 Reserved

Register Address RW X Unit Type Range A/E Bit Description

8857 8856 R — — UINT — A/E — SDx module status register

A/E 0 Status of output 1

A/E 1 Status of output 2

— 2...7 Reserved

A/E 8 Validity of output 1

A/E 9 Validity of output 2

— 10...15 Reserved

LV434107 09/2009 53

Page 54: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Trip Status

The trip status register tracks the current status of the trip.

If the trip bit is set to 0, then the trip is not active.

If the trip bit is set to 1, then the trip is active.

The following table details the physical values for each bit of the trip status register:

Register Address RW X Unit Type Range A/E Bit Description

10000 9999 R — — UINT — A/E — Trip status register

A/E 0 Long time protection Ir

A/E 1 Short time protection Isd

A/E 2 Instantaneous protection Ii

A/E 3 Ground fault protection Ig

A/E 4 Earth leakage (Vigi) protection IΔn

A/E 5 Integrated instantaneous protection

A/E 6 Internal failure (STOP)

A/E 7 Instantaneous with earth leakage (Vigi)

protection

A/E 8 Unbalance motor protection Iunb

A/E 9 Jam motor protection Ijam

A/E 10 Underload motor protection Iund

A/E 11 Longstart motor protection Ilong

A/E 12 Reflex tripping protection

— 13...15 Reserved

54 LV434107 09/2009

Page 55: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Alarm History

General Description

The alarm history registers describe the last 10 encountered alarms. The alarm history format

corresponds to a series of 10 records. Each record is composed of 5 registers describing one alarm.

A block read request of 5x(n) registers is necessary to read the last n trip records, where 5 is the number

of registers for each trip record. The reading starts at the beginning of the block read (see History Reading, page 38).

For example, a block read request of 5x3 = 15 registers is necessary to read the last 3 alarm records of

the alarm history:

The first 5 registers describe the first alarm record (most recent alarm).

The next 5 registers describe the second alarm record.

The last 5 registers describe the third alarm record.

When not used, alarm history registers return 32768 (0x8000).

Alarm Record

A block read request of 5 registers is necessary to read an alarm record.

The order and the description of the alarms records registers are the same as that of alarm record 1:

Register Address Description

5732...5736 5731...5735 Alarm record 1 (most recent alarm)

5737...5741 5736...5740 Alarm record 2

5742...5746 5741...5745 Alarm record 3

5747...5751 5746...5750 Alarm record 4

5752...5756 5751...5755 Alarm record 5

5757...5761 5756...5760 Alarm record 6

5762...5766 5761...5765 Alarm record 7

5767...5771 5766...5770 Alarm record 8

5772...5776 5771...5775 Alarm record 9

5777...5781 5776...5780 Alarm record 10 (oldest alarm)

Alarm record 1 (most recent alarm)

Register Address RW X Unit Type Range A/E Description

5732 5731 R 1 — UINT 0...65535 A/E Alarm number (see next paragraph)

5733

5734

5732

5733

R 1 s UDINT — A/E Date of alarm in number of seconds since

01/01/2000

5735 5734 R 1 — UINT — A/E Complement in ms (always = 0) with quality of

the date. See Date Format, page 35.

5736 5735 R 1 — UINT 1...2 A/E Event type

MSB = 0 (reserved)

Event occurrence: LSB = 1

Event completion: LSB = 2

LV434107 09/2009 55

Page 56: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Alarm Number

The list of the pre-defined alarms from which the user can chose the 10 user-defined alarms is available

at User-Defined Alarms, page 63.

Alarm number Alarm description

201 User-defined alarm 201

202 User-defined alarm 202

203 User-defined alarm 203

204 User-defined alarm 204

205 User-defined alarm 205

206 User-defined alarm 206

207 User-defined alarm 207

208 User-defined alarm 208

209 User-defined alarm 209

210 User-defined alarm 210

1013 Long time protection Ir pre-alarm (PAL Ir)

1014 Ground fault protection Ig pre-alarm (PAL Ig)

1015 Earth leakage protection IΔn pre-alarm (PAL IΔn)

56 LV434107 09/2009

Page 57: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Trip History

General Description

The trip history registers describe the last 17 encountered trip events. The trip history format corresponds

to a series of 17 records. Each record is composed of 7 registers describing one trip.

A block read request of 7x(n) registers is necessary to read the last n trip records, where 7 is the number

of registers for each trip record. The reading starts at the beginning of the block read (see History Reading, page 38).

For example, a block read request of 7x4 = 28 registers is necessary to read the last 4 trip records of the

trip history:

The first 7 registers describe the first trip record (most recent trip).

The next 7 registers describe the second trip record.

The next 7 registers describe the third trip record.

The last 7 registers describe the fourth trip record.

When not used, trip history registers return 32768 (0x8000).

Register Address Description

9100...9106 9099...9105 Trip record 1 (most recent trip)

9107...9113 9106...9112 Trip record 2

9114...9120 9113...9119 Trip record 3

9121...9127 9120...9126 Trip record 4

9128...9134 9127...9133 Trip record 5

9135...9141 9134...9140 Trip record 6

9142...9148 9141...9147 Trip record 7

9149...9155 9148...9154 Trip record 8

9156...9162 9155...9161 Trip record 9

9163...9169 9162...9168 Trip record 10

9170...9176 9169...9175 Trip record 11

9177...9183 9176...9182 Trip record 12

9184...9190 9183...9189 Trip record 13

9191...9197 9190...9196 Trip record 14

9198...9204 9197...9203 Trip record 15

9205...9211 9204...9210 Trip record 16

9212...9218 9211...9217 Trip record 17 (oldest trip)

LV434107 09/2009 57

Page 58: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Trip Record

A block read request of 7 registers is necessary to read a trip record.

The order and the description of the trips records registers are the same as that of trip record 1:

Trip Code

Trip record 1 (most recent trip)

Register Address RW X Unit Type Range A/E Description

9100 9099 R 1 — UINT 0...65535 A/E Trip code (see next paragraph)

9101

9102

9100

9101

R 1 s UDINT — A/E Date of event (trip or acknowledge) in number of

seconds since 01/01/2000

9103 9102 R 1 — UINT — A/E Complement in ms with quality of the date. See

Date Format, page 35.

9104 9103 R 1 — UINT 1...2 A/E Event type

MSB = 0 (reserved)

Event occurrence: LSB = 1

Event completion: LSB = 2

9105 9104 R 1 — UINT 0...5 A/E Faulty phase

0 = failure (no faulty phase)

1 = phase 1

2 = phase 2

3 = phase 3

4 = phase N

5 = phase 123 (motor application, ground fault,

earth leakage)

9106 9105 R 1 A UINT 0...65535 A/E Interrupted current (peak)

Trip code Trip description

1000 (16384) Long time protection Ir

1001 (16385) Short time protection Isd

1002 (16386) Instantaneous protection Ii

1003 (16387) Ground fault protection Ig

1004 (16388) Earth leakage (Vigi) protection IΔn

1010 (16390) Integrated instantaneous protection

1011 (16391) STOP (trip unit internal failure)

1012 (16392) Instantaneous with earth leakage (Vigi) protection

1032 (16640) Unbalance motor protection

1033 (16641) Jam motor protection

1034 (16642) Underload motor protection

1035 (16643) Longstart motor protection

1036 (16393) Reflex tripping protection

58 LV434107 09/2009

Page 59: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Maintenance Operation History

General Description

The maintenance operation history registers describe the last 10 maintenance operations. The

maintenance operation history format corresponds to a series of 10 records. Each record is composed of

5 registers describing one maintenance operation.

A block read request of 5x(n) registers is necessary to read the last n maintenance operation records,

where 5 is the number of registers for each maintenance operation record. The reading starts at the

beginning of the block read (see History Reading, page 38).

For example, a block read request of 5x2 = 10 registers is necessary to read the last 2 maintenance

operation records of the maintenance operation history:

The first 5 registers describe the first maintenance operation record (most recent maintenance

operation).

The last 5 registers describe the second maintenance record.

When not used, maintenance operation history registers return 32768 (0x8000).

Maintenance Operation Record

A block read request of 5 registers is necessary to read a maintenance operation record.

The order and the description of the maintenance operations records registers are the same as that of

maintenance operation record 1:

Register Address Description

29500...29504 29499...29503 Maintenance operation record 1 (most recent maintenance operation)

29505...29509 29504...29508 Maintenance operation record 2

29510...29514 29509...29513 Maintenance operation record 3

29515...29519 29514...29518 Maintenance operation record 4

29520...29524 29519...29523 Maintenance operation record 5

29525...29529 29524...29528 Maintenance operation record 6

29530...29534 29529...29533 Maintenance operation record 7

29535...29539 29534...29538 Maintenance operation record 8

29540...29544 29539...29543 Maintenance operation record9

29545...29549 29544...29548 Maintenance operation record 10 (oldest maintenance operation)

Maintenance operation record 1 (most recent maintenance operation)

Register Address RW X Unit Type Range A/E Description

29500 29499 R 1 — UINT 0...65535 A/E Maintenance operation code (see next

paragraph)

29501

29502

29500

29501

R 1 s UDINT — A/E Date of maintenance operation in number of

seconds since 01/01/2000

29503 29502 R 1 — UINT — A/E Complement in ms (always = 0) with quality of

the date. See Date Format, page 35.

29504 29503 — — — — — — Reserved

LV434107 09/2009 59

Page 60: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Maintenance Operation Code

Maintenance operation code Maintenance operation description

2000 Push to trip test (with maintenance module)

2001 Ground Fault inhibition

2003 Start numerical injection test

2004 End numerical injection test

2005 Ground fault test

2006 Earth leakage (Vigi) test

2007 Start alarm test

2008 End alarm test

2009 Start long time protection

2010 End long time protection

2011 Start short time protection

2012 End short time protection

2013 Start instantaneous protection

2014 Stop instantaneous protection

2015 Start integrated instant protection

2016 Stop integrated instant protection

2017 Start unbalance protection

2018 Stop unbalance protection

2019 Start ground fault protection

2020 Stop ground fault protection

2021 Start earth leakage (Vigi) protection

2022 Stop earth leakage (Vigi) protection

2023 Start thermal memory

2024 Stop thermal memory

2025 Start connection with maintenance module

2026 Stop connection with maintenance module

2027 Turn rotary wheel 1

2028 Turn rotary wheel 2

2029 Locking pad open

2030 Locking pad closed

2031 ZSI test

2033 Reset software

2034 Reset minimum/maximum of current measurements

2035 Reset minimum/maximum of voltage measurements

2036 Reset minimum/maximum of power measurements

2037 Reset minimum/maximum of power factor measurements

2038 Reset minimum/maximum of total harmonic distortion measurements

2039 Reset maximum of current demand measurement

2040 Reset maximum of power demand (active, reactive, and apparent)

2041 Reset minimum/maximum of frequency measurement

2042 Reset minimum/maximum of thermal image measurements

2043 Reset energy measurements

2044 Reset energy counter

60 LV434107 09/2009

Page 61: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Pre-Alarms

General Description

The RSU software enables the configuration of the following 3 pre-alarms:

long time protection pre-alarm (PAL Ir),

ground fault protection pre-alarm (PAL Ig), and

earth leakage (Vigi) protection pre-alarm (PAL IΔn).

See the RSU Online Help for more information regarding the configuration of the pre-alarms.

Each alarm has a corresponding alarm code:

PAL Ir = 1013

PAL Ig = 1014

PAL IΔn = 1015

Each alarm has a priority level that manages the alarm display on the front display module FDM121:

no priority = N/A (not affected)

low priority = 1. No alarm display on the front display module FDM121.

medium priority = 2. The front display module FDM121 LED is steady ON.

high priority = 3. The front display module FDM121 LED blinks and a pop-up screen informs the user

that the alarm is active.

See the Micrologic 5 and 6 Trip Units User manual for more information regarding the relationship

between alarm priority and front display module FDM121.

The pre-alarms registers describe the settings of the pre-alarms:

Long Time Protection Pre-Alarm (PAL Ir)

A block read request of 10 registers is necessary to read the long time protection pre-alarm parameters

(see History Reading, page 38).

Register Address Description

6650...6659 6649...6658 Long time protection pre-alarm (PAL Ir)

6660...6669 6659...6668 Ground fault protection pre-alarm (PAL Ig)

6670...6679 6669...6678 Earth leakage (Vigi) protection pre-alarm (PAL IΔn)

Register Address RW X Unit Type Range A/E Description

6650 6649 R — — UINT — A/E The MSB gives the activity of the alarm:

0 = On, 1 = Off. The default value is 0 (On).

The LSB gives the priority of the alarm: N/A, 1, 2, or 3.

The default value is 2 (medium priority).

6651 6650 — — — — — — Reserved

6652 6651 R 1 % INT (1) A/E % of Ir pick-up value. The default value is 90.

6653 6652 — — — — — — Reserved

6654 6653 R 1 s UINT 1 A/E Pick-up delay value (fixed to 1 s)

6655 6654 R 1 % INT (1) A/E % of Ir drop-out value. The default value is 85.

6656 6655 — — — — — — Reserved

6657 6656 R 1 s UINT 1 A/E Drop-out delay value (fixed to 1 s)

6658 6657 — — — — — — Reserved

6659 6658 — — — — — — Reserved

(1) For distribution application, the range is 40...100. For motor application, the range is 10...95.

LV434107 09/2009 61

Page 62: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Ground Fault Protection Pre-Alarm (PAL Ig)

A block read request of 10 registers is necessary to read the ground fault protection pre-alarm parameters

(see History Reading, page 38).

Earth Leakage (Vigi) Protection Pre-Alarm (PAL IΔn)

A block read request of 10 registers is necessary to read the earth leakage (Vigi) protection pre-alarm

parameters (see History Reading, page 38).

Register Address RW X Unit Type Range A/E Description

6660 6659 R — — UINT — A/E The MSB gives the activity of the alarm:

0 = On, 1 = Off. The default value is 0 (On).

The LSB gives the priority of the alarm: N/A, 1, 2, or 3.

The default value is 2 (medium priority).

6661 6660 — — — — — — Reserved

6662 6661 R 1 % INT 40...100 A/E % of Ig pick-up value. The default value is 90.

6663 6662 — — — — — — Reserved

6664 6663 R 1 s UINT 1 A/E Pick-up delay value (fixed to 1 s)

6665 6654 R 1 % INT 40...100 A/E % of Ig drop-out value. The default value is 85.

6666 6665 — — — — — — Reserved

6667 6666 R 1 s UINT 1 A/E Drop-out delay value (fixed to 1 s)

6668 6667 — — — — — — Reserved

6669 6668 — — — — — — Reserved

Register Address RW X Unit Type Range A/E Description

6670 6669 R — — UINT — A/E The MSB gives the activity of the alarm:

0 = On, 1 = Off. The default value is 0 (On).

The LSB gives the priority of the alarm: N/A, 1, 2, or 3.

The default value is 2 (medium priority).

6671 6670 — — — — — — Reserved

6672 6671 R 1 % INT 40...100 A/E % of IΔn pick-up value. The default value is 90.

6673 6672 — — — — — — Reserved

6674 6673 R 1 s UINT 1 A/E Pick-up delay value (fixed to 1 s)

6675 6674 R 1 % INT 40...100 A/E % of IΔn drop-out value. The default value is 85.

6676 6675 — — — — — — Reserved

6677 6676 R 1 s UINT 1 A/E Drop-out delay value (fixed to 1 s)

6678 6677 — — — — — — Reserved

6679 6678 — — — — — — Reserved

62 LV434107 09/2009

Page 63: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

User-Defined Alarms

General Description

The RSU software enables the configuration of 10 user-defined alarms that can be chosen from a list of

150 pre-defined alarms.

See the RSU Online Help for more information regarding the configuration of the user-defined alarms.

Each user-defined alarm has a corresponding user-defined alarm number (201...210) and a

corresponding alarm code (see next paragraph).

Each alarm has a priority level that manages the alarm display on the front display module FDM121:

no priority = N/A (not affected)

low priority = 1. No alarm display on the front display module FDM121.

medium priority = 2. The front display module FDM121 LED is steady ON.

high priority = 3. The front display module FDM121 LED blinks and a pop-up screen informs the user

the alarm is active.

See the Micrologic 5 and 6 Trip Units User manual for more information regarding the relationship

between alarm priority and front display module FDM121.

The settings of the 10 user-defined alarms are in the user-defined alarms registers:

Register Address Description

6770...6781 6769...6780 User-defined alarm 201

6782...6793 6781...6792 User-defined alarm 202

6794...6805 6793...6804 User-defined alarm 203

6806...6817 6805...6816 User-defined alarm 204

6818...6829 6817...6828 User-defined alarm 205

6830...6841 6829...6840 User-defined alarm 206

6842...6853 6841...6852 User-defined alarm 207

6854...6865 6853...6864 User-defined alarm 208

6866...6877 6865...6876 User-defined alarm 209

6878...6889 6877...6888 User-defined alarm 210

LV434107 09/2009 63

Page 64: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

User-Defined Alarm Record

A block read request of 12 registers is necessary to read a user defined alarm record (see History Reading, page 38).

The order and the description of the user-defined alarms records are the same as that of user-defined

alarm record 1:

User-defined alarm 201

Register Address RW X Unit Type Range A/E Description

6770 6769 R — — UINT — A/E The MSB gives the activity of the alarm:

0 = On, 1 = Off. The default value is 1 (Off).

The LSB gives the priority of the alarm:

N/A, 1, 2, or 3. The default value is N/A (no priority).

6771 6770 R — — UINT — A/E Measurement identifier (1)

6772 6771 — — — — — — Reserved

6773 6772 R 1 (2) INT -32767

...+32767

A/E Threshold pick-up value

The default value is 0.

6774 6773 — — — — — — Reserved

6775 6774 R 1 s UINT 0...3000 A/E Pick-up delay value. The default value is 0.

6776 6775 R 1 (2) INT -32767

...+32767

A/E Threshold drop-out value

The default value is 0.

6777 6776 — — — — — — Reserved

6778 6777 R 1 s INT 0...3000 A/E Drop-out delay value. The default value is 0.

6779 6778 R — — UINT 0...3 A/EOperator:

6780 6779 R — — UINT 1...1919 — Alarm code (see next paragraph)

6781 6780 — — — — — — Reserved

(1) The value of the measurement identifier is the register number of the measurement. For example, the

measurement identifier of current on phase 1 (I1) is 1016.

(2) The unit of the threshold depends on the measurement identifier. For example, if the measurement identifier is

I1, then the unit is A.

64 LV434107 09/2009

Page 65: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Pre-Defined Alarms Codes

The following table describes the list of pre-defined alarms and corresponding codes from which the user

can chose the 10 user-defined alarms and configure them with RSU:

Alarm code Alarm description

1 Over current instantaneous phase 1

2 Over current instantaneous phase 2

3 Over current instantaneous phase 3

4 Over current instantaneous neutral

5 Ground fault protection alarm

6 Under current instantaneous phase 1

7 Under current instantaneous phase 2

8 Under current instantaneous phase 3

9 Over current unbalance phase 1

10 Over current unbalance phase 2

11 Over current unbalance phase 3

12 Over voltage (phase 1 to neutral)

13 Over voltage (phase 2 to neutral)

14 Over voltage (phase 3 to neutral)

15 Under voltage (phase 1 to neutral)

16 Under voltage (phase 2 to neutral)

17 Under voltage (phase 3 to neutral)

18 Over voltage unbalance (phase 1 to neutral)

19 Over voltage unbalance (phase 2 to neutral)

20 Over voltage unbalance (phase 3 to neutral)

21 Over total apparent power

22 Over total active power

23 Over total active reverse power

24 Over total reactive power

25 Over total reactive reverse power

26 Under total apparent power

27 Under total active power

29 Under total reactive power

31 Leading power factor (IEEE)

33 Leading or lagging power factor (IEC)

34 Lagging power factor (IEEE)

35 Over total harmonic distortion current phase 1

36 Over total harmonic distortion current phase 2

37 Over total harmonic distortion current phase 3

38 Over total harmonic distortion voltage (phase 1 to neutral)

39 Over total harmonic distortion voltage (phase 2 to neutral)

40 Over total harmonic distortion voltage (phase 3 to neutral)

41 Over total harmonic distortion voltage (phase 1 to 2)

42 Over total harmonic distortion voltage (phase 2 to 3)

43 Over total harmonic distortion voltage (phase 3 to 1)

54 Earth leakage (Vigi) protection alarm

55 Over current (average)

56 Over maximum current (I1, I2, I3, or neutral)

57 Under current instantaneous neutral

60 Under current (average)

61 Over current demand phase 1

62 Over current demand phase 2

63 Over current demand phase 3

LV434107 09/2009 65

Page 66: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

64 Over current demand neutral

65 Under minimum current (I1, I2, or I3)

66 Under current demand phase 1

67 Under current demand phase 2

68 Under current demand phase 3

69 Under current demand neutral

70 Over maximum current unbalance (I1, I2, or I3)

71 Over voltage (phase 1 to 2)

72 Over voltage (phase 2 to 3)

73 Over voltage (phase 3 to 1)

75 Over voltage (average)

76 Under voltage (phase 1 to 2)

77 Under voltage (phase 2 to 3)

78 Under voltage (phase 3 to 1)

79 Over maximum voltage

80 Under voltage (average)

81 Under minimum voltage

82 Over maximum voltage unbalance (phases to neutral)

86 Over voltage unbalance (phase 1 to 2)

87 Over voltage unbalance (phase 2 to 3)

88 Over voltage unbalance (phase 3 to 1)

89 Over maximum voltage unbalance

90 Phase sequence

92 Under frequency

93 Over frequency

121 Leading cosϕ (IEEE)

123 Leading or lagging cosϕ (IEC)

124 Lagging cosϕ (IEEE)

125 Over current thermal image motor

126 Under current thermal image motor

141 Over current maximum demand phase 1

142 Over current maximum demand phase 2

143 Over current maximum demand phase 3

144 Over current maximum demand neutral

145 Lead

146 Lag

147 Quadrant 1

148 Quadrant 2

149 Quadrant 3

150 Quadrant 4

Alarm code Alarm description

66 LV434107 09/2009

Page 67: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Protection Parameters

Long Time Protection Parameters

A block read request of 10 registers is necessary to read the long time protection parameters (see History Reading, page 38).

The long time protection command (command code = 45192) configures the content of the long time

protection registers.

Short Time Protection Parameters

A block read request of 10 registers is necessary to read the short time protection parameters (see

History Reading, page 38).

The short time protection command (command code = 45193) configures the content of the short time

protection registers.

Register Address RW X Unit Type Range A/E Description

8754 8753 R — — UINT 0...2 A/E Status: 0 = Off, 1 = On, 2 = Inhibit

8755 8754 — — — — — — Reserved

8756 8755 RW 1 A UINT — A/E Ir pick-up value. The Ir range depends on the nominal

current In.

8757 8756 — — — — — — Reserved

8758 8757 RW 1 ms UINT 500

...16000

A/E tr time delay (distribution application)

tr = 500, 1000, 2000, 4000, 8000, 16000 ms

8759 8758 RW 1 ms UINT 5...30 E Motor class (motor application only)

Possible values = 5, 10, 20, 30 ms

8760 8759 R — — — — — Reserved

8761 8760 RW — — UINT 1...2 E Cool fan (motor application only)

1 = auto, 2 = motor

8762 8761 — — — — — — Reserved

8763 8762 — — — — — — Reserved

Register Address RW X Unit Type Range A/E Description

8764 8763 R — — UINT 0...2 A/E Status: 0 = Off, 1 = On, 2 = Inhibit

8765 8764 RW — — UINT 0...1 A/E Type of protection: 0 = I2t On, 1 = I2t Off.

For motor application, tsd = 30 ms and I2t is Off (fixed

values).

8766 8765 RW 10 — UINT (1) A/E Isd coefficient, adjustable in step of 5.

8767 8766 R 1 A UINT — A/E Isd pick-up value = (Ir) x (Isd coefficient) / 10

8768 8767 RW 1 ms UINT 0...400 A/E tsd time delay

tsd = 0, 30, 100, 200, 300, 400 ms

If tsd = 0 ms, then I2t must be Off.

8769

8770

8768

8769

— — — — — — Reserved

8771 8770 — — — — — — Reserved

8772 8771 — — — — — — Reserved

8773 8772 — — — — — — Reserved

(1) For distribution application, the range is 15...100. For motor application, the range is 50...130.

LV434107 09/2009 67

Page 68: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Instantaneous Protection Parameters

A block read request of 10 registers is necessary to read the instantaneous protection parameters (see

History Reading, page 38).

The instantaneous protection command (command code = 45194) configures the content of the

instantaneous protection registers.

Ground Fault Protection Parameters

A block read request of 10 registers is necessary to read the ground fault protection parameters (see

History Reading, page 38).

The ground fault protection command (command code = 45195) configures the content of the ground

fault protection registers.

Register Address RW X Unit Type Range A/E Description

8774 8773 R — — UINT 0...2 A/E Status: 0 = Off, 1 = On, 2 = Inhibit

8775 8774 — — — — — — Reserved

8776 8775 RW 10 — UINT (1) A/E Ii coefficient, adjustable in step of 5.

8777 8766 R 1 A UINT — A/E Ii pick-up value = (In) x (Ii coefficient) / 10

8778 8777 — — — — — — Reserved

8779

8780

8778

8779

— — — — — — Reserved

8781 8780 — — — — — — Reserved

8782 8781 — — — — — — Reserved

8783 8782 — — — — — — Reserved

(1) The Ii coefficient range depends on the circuit breaker size:

For Compact NSX 100/160, the range is 15...150.

For Compact NSX 250/400, the range is 15...120.

For Compact NSX 630, the range is 15...110.

Register Address RW X Unit Type Range A/E Description

8784 8783 R — — UINT 0...1 A/E Status: 0 = Off, 1 = On

8785 8784 RW — — UINT 0...1 A/E Type of protection: 0 = I2t On, 1 = I2t Off

For motor application, tg = 0 ms and I2t is Off (fixed

values).

8786 8785 RW 100 — UINT — A/E Ig coefficient, adjustable in step of 5.

8787 8786 R 1 A UINT — A/E Ig pick-up value = (In) x (Ig coefficient) / 100

If Ground Fault protection is set to Off, Ig pick-up

value = In

8788 8787 RW 1 ms UINT 0...400 A/E tg time delay

tg = 0, 100, 200, 300, 400 ms.

If tg = 0 ms, then I2t must be Off.

8789

8790

8788

8789

— — — — — — Reserved

8791 8790 — — — — — — Reserved

8792 8791 — — — — — — Reserved

8793 8792 — — — — — — Reserved

68 LV434107 09/2009

Page 69: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Earth Leakage (Vigi) Protection Parameters

A block read request of 10 registers is necessary to read the earth leakage (Vigi) protection parameters

(see History Reading, page 38).

The earth leakage (Vigi) protection command (command code = 45196) configures the content of the

earth leakage (Vigi) protection registers.

Jam Protection Parameters

A block read request of 4 registers is necessary to read the jam protection parameters (see History Reading, page 38).

The jam protection is available for motor application only. The jam protection command

(command code = 45448) configures the content of the jam protection registers.

Unbalance Protection Parameters

A block read request of 4 registers is necessary to read the unbalance protection parameters (see History Reading, page 38).

The unbalance protection is available for motor application only. The unbalance protection command

(command code = 45450) configures the content of the unbalance protection registers.

Underload Protection Parameters

A block read request of 4 registers is necessary to read the underload protection parameters (see History Reading, page 38).

The underload protection is available for motor application only. The underload protection command

(command code = 45449) configures the content of the underload protection registers.

Register Address RW X Unit Type Range A/E Description

8794 8793 R — — UINT 0...2 A/E Status: 0 = Off, 1 = On, 2 = Inhibit

8795 8794 — — — — — — Reserved

8796 8795 RW 1 mA UINT — A/E Earth leakage current IΔn. The IΔn range depends

on the nominal current In.

8797 8796 — — — — — — Reserved

8798 8797 RW 1 ms UINT 0...1000 A/E tΔn time delay

tΔn = 0, 60, 150, 500, 1000 ms

If IΔn = 0.03 mA, then tΔn = 0 ms.

8799

8800

8798

8799

— — — — — — Reserved

8801 8800 — — — — — — Reserved

8802 8801 — — — — — — Reserved

8803 8802 — — — — — — Reserved

Register Address RW X Unit Type Range A/E Description

8900 8899 RW — — UINT 0...1 E Status: 0 = Off, 1 = On

8901 8900 RW 10 — UINT 10...80 E Ijam coefficient, adjustable in step of 1.

8902 8901 R 1 A UINT — E Ijam pick-up value = (Ir) x (Ijam coefficient) / 10

8903 8902 RW 1 s UINT 1...30 E tjam time delay

Register Address RW X Unit Type Range A/E Description

8904 8903 R — — UINT 0...2 E Status: 0 = Off, 1 = On, 2 = Inhibit

8905 8904 RW 1 % UINT 10...40 E Iunbal coefficient

8906 8905 RW 1 s UINT 1...10 E tunbal time delay

8907 8906 R — — — — — Reserved

Register Address RW X Unit Type Range A/E Description

8908 8907 RW — — UINT 0...1 E Status: 0 = Off, 1 = On

8909 8908 RW 100 — UINT 30...90 E Iunderload coefficient, adjustable in step of 1.

8910 8909 R 1 A UINT — E Iunderload pick-up value = (Ir) x (Iunderload) / 100

8911 8910 RW 1 s UINT 1...200 E tunderload time delay

LV434107 09/2009 69

Page 70: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Longstart Protection Parameters

A block read request of 4 registers is necessary to read the longstart protection parameters (see History Reading, page 38).

The longstart protection is available for motor application only. The longstart protection command

(command code = 45451) configures the content of the longstart protection registers.

Neutral Protection Parameters

The neutral protection is only available when system type in register 3314 is 30 or 41. See System Type, page 72.

A block read request of 4 registers is necessary to read the neutral protection parameters (see History Reading, page 38).

The neutral protection command (command code = 45197) configures the content of the neutral

protection registers.

Thermal Memory Inhibit Parameter

Register Address RW X Unit Type Range A/E Description

8912 8911 RW — — UINT 0...1 E Status: 0 = Off, 1 = On

8913 8912 RW 10 — UINT 10...80 E Ilongstart coefficient, adjustable in step of 1.

8914 8913 R 1 A UINT — E Ilongstart pick-up value

= (Ir) x (Ilongstart coefficient) / 10

8915 8914 RW 1 s UINT 1...200 E tlongstart time delay

Register Address RW X Unit Type Range A/E Description

8916 8915 R — — UINT 0... 2 A/E Status: 0 = Off, 1 = On, 2 = Inhibit (1)

8917 8916 RW — — UINT 0...3 A/E Neutral coefficient pick-up value

0 = Off

1 = 0.5

2 = 1.0

3 = OSN

8918 8917 R 1 A UINT 0...32766 — Ir pick-up value

8919 8918 R 1 A UINT 0...32766 — Isd pick-up value

(1) For 40 A IEC and 60 A UL circuit breakers, the user cannot setup the neutral coefficient pick-up value to 0.5.

Register Address RW X Unit Type Range A/E Description

8930 8929 R — — UINT 1... 2 A/E Status: 1 = On, 2 = Inhibit

70 LV434107 09/2009

Page 71: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Configuration of the SDx Module

Output 1

A block read request of 3 registers is necessary to read the output 1 parameters (see History Reading, page 38).

The user can check the status and the validity of output 1 at register 8857 (see SDx Module Status, page 53).

Output 2

A block read request of 3 registers is necessary to read the output 2 parameters (see History Reading, page 38).

The user can check the status and the validity of output 2 at register 8857 (see SDx Module Status, page 53).

Register Address RW X Unit Type Range A/E Description

9801 9800 R 1 — UINT 0...4 A/E Output mode

0 = normal mode

1 = latched mode

2 = time delayed mode

3 = closed forced mode

4 = open forced mode

9802 9801 R 1 s UINT 1...360 A/E Delay (if the output mode is set to 2)

The default value is 1 s.

9803 9802 R 1 — UINT 0...65535 A/E Alarm identifier (201...210, 1013, 1014, 1015)

The alarm identifier is set to 0 if there is no alarm.

Register Address RW X Unit Type Range A/E Description

9808 9807 R 1 — UINT 0...4 A/E Output mode

0 = normal mode

1 = latched mode

2 = time delayed mode

3 = closed forced mode

4 = open forced mode

9809 9808 R 1 s UINT 1...360 A/E Delay (if the output mode is set to 2)

The default value is 1 s.

9810 9809 R 1 — UINT 0...65535 A/E Alarm identifier (201...210, 1013, 1014, 1015)

The alarm identifier is set to 0 if there is no alarm.

LV434107 09/2009 71

Page 72: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Measurement Parameters

System Type

The set up ENVT (External Neutral Voltage Tap) presence command (command code = 46472)

configures the content of the system type register.

Determining system type:

Quadrant Total

Power Flow Sign

The power flow sign command (command code = 47240) configures the content of the power flow sign

register.

Power Factor Sign

The power factor sign configuration command (command code = 47241) configures the content of the

power factor sign register.

Register Address RW X Unit Type Range A/E Description

3314 3313 RW — — UINT 30...41 A/E System type

If... Then... Result

the system type is 3-pole circuit

breaker with external neutral

current transformer and without

external neutral voltage tap

system type = 30. Measurements of the phase-to-phase voltages are

available.

Measurements of the phase-to-neutral voltages are not

available.

Measurement of the neutral current is available.

3 wattmeters method is not possible.

the system type is 3-pole circuit

breaker without external neutral

current transformer and without

external neutral voltage tap

system type = 31. Measurements of the phase-to-phase voltages are

available.

Measurements of the phase-to-neutral voltages are not

available.

Measurement of the neutral current is not available.

3 wattmeters method is not possible.

the system type is 3-pole circuit

breaker without external neutral

current transformer and with

external neutral voltage tap

system type = 40. Measurements of the phase-to-phase voltages are

available.

Measurements of the phase-to-neutral voltages are

available.

Measurement of the neutral current is not available.

3 wattmeters method is possible.

the system type is 3-pole circuit

breaker with external neutral

current transformer and external

neutral voltage tap, or if the

system type is 4-pole circuit

breaker

system type = 41. Measurements of the phase-to-phase voltages are

available.

Measurements of the phase-to-neutral voltages are

available.

Measurement of the neutral current is available.

3 wattmeters method is possible.

Register Address RW X Unit Type Range A/E Description

2242 2241 R — — UINT 1...4 E Quadrant total

2243 2242 R — — UINT 0...1 E 0 = lead

1 = lag

Register Address RW X Unit Type Range A/E Description

3316 3315 RW — — UINT 0...1 E Power flow sign

0 = the active power flows from upstream (top) to

downstream (bottom) (default).

1 = the active power flows from downstream

(bottom) to upstream (top).

Register Address RW X Unit Type Range A/E Description

3318 3317 RW — — UINT 0...2 E Sign convention for the power factor and the

fundamental power factor (cosϕ)

0 = IEC convention

2 = IEEE convention (default)

72 LV434107 09/2009

Page 73: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Energy Accumulation Mode

The energy accumulation mode configuration command (command code = 47242) configures the

content of the energy accumulation mode register.

Demand Time

The current demand configuration command (command code 47243) configures the content of register

3352.

The power demand configuration command (command code 47244) configures the content of registers

3354 and 3355.

See the Micrologic 5 and 6 Trip Units User manual for more information regarding the demand calculation

method.

Nominal Voltage

The set up nominal voltage Vn display command (command code = 47245) configures the content of the

nominal voltage register.

Register Address RW X Unit Type Range A/E Description

3324 3323 RW — — UINT 0...1 E Energy accumulation mode

0 = absolute accumulation (default)

Ep = EpIn + EpOut

Eq = EqIn + EqOut

1 = signed accumulation

Ep = EpIn - EpOut

Eq = EqIn - EqOut

Register Address RW X Unit Type Range A/E Description

3352 3351 RW — Min UINT 5...60 E Duration of the current demand calculation window,

adjustable in step of 1 minute.

The default value is 15 minutes.

3354 3353 RW — — UINT 0...5 E Power demand calculation method (window type)

0 = sliding

2 = block

5 = synchronized to communication

The default value is 0 (sliding).

3355 3354 RW — Min UINT 5...60 E Duration of the power demand calculation window,

adjustable in step of 1 minute.

The default value is 15 minutes.

Register Address RW X Unit Type Range A/E Description

9616 9615 RW 1 V UINT 0...65535 A/E Nominal voltage Vn (default value = 400 V)

LV434107 09/2009 73

Page 74: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Time-Stamped Information

General Description

The time-stamped information enables the user to know all the dates relative to important information like

previous protection settings and minimum/maximum values of currents, voltages, and network frequency.

The time-stamped information table describes:

the previous protection setup parameters and corresponding dates

the minimum and maximum values of voltage measurements and corresponding dates

the maximum values of current measurements and corresponding dates

the minimum and maximum network frequencies and corresponding dates

the peak demand of current and power and corresponding dates

A block read request of 100 registers is necessary to read the previous protection registers

(29600...29699). The reading starts at the beginning of the block read (see History Reading, page 38).

Previous Long Time Protection Setup

Previous Short Time Protection Setup

Register Address RW X Unit Type Range A/E Description

29600 29599 R 1 A UINT — A/E Previous Ir pick-up value. The Ir range depends on the

nominal current In.

29601

29602

29600

29601

R 1 s UDINT — A/E Date of setup in number of seconds since 01/01/2000

(1)

29603 29602 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

29604 29603 R 1 ms UINT 500...

16000

A/E Previous tr time delay (distribution application)

Tr = 500, 1000, 2000, 4000, 8000, 16000 ms

29605

29606

29604

29605

R 1 s UDINT — A/E Date of setup in number of seconds since 01/01/2000

(1)

29607 29606 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

29608 29607 R 1 — UINT 5...30 A/E Motor class (motor application only)

Possible values = 5, 10, 20, 30

29609

29610

29608

29609

R 1 s UDINT — A/E Date of setup in number of seconds since 01/01/2000

(1)

29611 29610 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

29612 29611 R — — UINT 1...2 A/E Previous cool fan setup (motor application only)

1 = auto, 2 =motor

29613

29614

29612

29613

R 1 s UDINT — A/E Date of setup in number of seconds since 01/01/2000

(1)

29615 29614 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29616 29615 R 10 — UINT 15...100 A/E Previous Isd coefficient pick-up value

29617

29618

29616

29617

R 1 s UDINT — A/E Date of setup in number of seconds since

01/01/2000 (1)

29619 29618 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

29620 29619 R 1 ms UINT 0...400 A/E Previous tsd time delay

tsd = 0, 100, 200, 300, 400 ms

If tsd = 0 ms, then I2t must be Off.

29621

29622

29620

29621

R 1 s UDINT — A/E Date of setup in number of seconds since

01/01/2000 (1)

29623 29622 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

29624 29623 R — — UINT 0...1 A/E Previous type of protection: 0 = I2t On, 1 = I2t Off

29625

29626

29624

29625

R 1 s UDINT — A/E Date of setup in number of seconds since

01/01/2000 (1)

29627 29626 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

74 LV434107 09/2009

Page 75: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Previous Instantaneous Protection Setup

Previous Ground Fault Protection Setup

Previous Earth Leakage (Vigi) Protection Setup

Register Address RW X Unit Type Range A/E Description

29628 29527 R 10 — UINT (1) A/E Previous Ii coefficient pick-up value

29629

29630

29628

29629

R 1 s UDINT — A/E Date of setup in number of seconds since 01/01/2000

29631 29630 R 1 ms UINT — A/E Complement in ms with quality of the date. See Date Format, page 35.

(1) The Ii coefficient range depends on the circuit breaker size:

For Compact NSX 100/160, the range is 15...150.

For Compact NSX 250/400, the range is 15...120.

For Compact NSX 630, the range is 15...110.

Register Address RW X Unit Type Range A/E Description

29632 29631 R 100 ms UINT — A/E Previous Ig coefficient pick-up value. The Ig

coefficient range depends on the nominal current In.

29633

29634

29632

29633

R 1 s UDINT — A/E Date of setup in number of seconds since

01/01/2000 (1)

29635 29634 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

29636 29635 R 1 ms UINT 0...400 A/E Previous tg time delay tg = 0, 100, 200, 300, 400 ms

29637

29638

29636

29637

R 1 s UDINT — A/E Date of setup in number of seconds since

01/01/2000 (1)

29639 29638 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

29640 29639 R — — UINT 0...1 A/E Previous type of protection: 0 = I2t On, 1 = I2t Off

29641

29642

29640

29641

R 1 s UDINT — A/E Date of setup in number of seconds since

01/01/2000 (1)

29643 29642 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29644 29643 R 1 mA UINT — A/E Previous IΔn pick-up value. The IΔn depends on the

nominal current In.

29645

29646

29644

29645

R 1 s UDINT — A/E Date of setup in number of seconds since 01/01/2000

(1)

29647 29646 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

29648 29647 R 1 ms UINT 0...1000 A/E Previous tΔn time delay

tΔn = 0, 60, 150, 500, 1000 ms

If IΔn = 0.03 mA, then TΔn = 0 ms.

29649

29650

29648

29649

R 1 s UDINT — A/E Date of setup in number of seconds since 01/01/2000

(1)

29651 29650 R 1 ms UINT — A/E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

LV434107 09/2009 75

Page 76: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Previous Jam Protection Setup

The jam protection is available for motor application only.

Previous Unbalance Protection Setup

The unbalance protection is available for motor application only.

Previous Underload Protection Setup

The underload protection is available for motor application only.

Register Address RW X Unit Type Range A/E Description

29652 29651 R — — UINT 0...2 E Previous setup status: 0 = Off, 1 = On

29653

29654

29652

29653

R 1 s UDINT — E Date of setup in number of seconds since

01/01/2000 (1)

29655 29654 R 1 ms UINT — E Complement in ms with quality of the date (1)

29656 29655 R 10 — UINT 10...80 E Previous Ijam coefficient pick-up value

29657

29658

29656

29657

R 1 s UDINT — E Date of setup in number of seconds since

01/01/2000 (1)

29659 29658 R 1 ms UINT — E Complement in ms with quality of the date (1)

29660 29659 R — s UINT 1...30 E Previous tjam time delay

29661

29662

29660

29661

R 1 s UDINT — E Date of setup in number of seconds since

01/01/2000 (1)

29663 29662 R 1 ms UINT — E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29664 29663 R 1 % UINT 10...40 E Previous unbalance coefficient pick-up value

29665

29666

29664

29665

R 1 s UDINT — E Date of setup in number of seconds since 01/01/2000

(1)

29667 29666 R 1 ms UINT — E Complement in ms with quality of the date (1)

29668 29667 R 1 s UINT 1...10 E Previous tunbal time delay

29669

29670

29668

29669

R 1 s UDINT — E Date of setup in number of seconds since 01/01/2000

(1)

29671 29670 R 1 ms UINT — E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29672 29671 R — — UINT 0...2 E Previous setup status: 0 = Off, 1 = On

29673

29674

29672

29673

R 1 s UDINT — E Date of setup in number of seconds since

01/01/2000 (1)

29675 29674 R 1 ms UINT — E Complement in ms with quality of the date (1)

29676 29675 R 100 — UINT 30...90 E Previous Iunderload coefficient pick-up value

29677

29678

29676

29677

R 1 s UDINT — E Date of setup in number of seconds since

01/01/2000 (1)

29679 29678 R 1 ms UINT — E Complement in ms with quality of the date (1)

29680 29679 R — s UINT 1...200 E Previous tunderload time delay

29681

29682

29680

29681

R 1 s UDINT — E Date of setup in number of seconds since

01/01/2000 (1)

29683 29682 R 1 ms UINT — E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

76 LV434107 09/2009

Page 77: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Previous Longstart Protection Setup

The longstart protection is available for motor application only.

Previous Neutral Protection Setup

The neutral protection is only available when system type in register 3314 is 30 or 41. See System Type, page 72.

Minimum/Maximum V12 Voltage Measurements

A block read request of 48 registers is necessary to read the minimum/maximum values of voltage,

current, and frequency registers (29780...29827). The reading starts at the beginning of the block read

(see History Reading, page 38).

Register = 0 if voltage < 25 V.

Register Address RW X Unit Type Range A/E Description

29684 29683 R — — UINT 0...2 E Previous setup status: 0 = Off, 1 = On

29685

29686

29684

29685

R 1 s UDINT — E Date of setup in number of seconds since

01/01/2000 (1)

29687 29686 R 1 ms UINT — E Complement in ms with quality of the date (1)

29688 29687 R 100 — UINT 10...80 E Previous Ilongstart coefficient pick-up value

29689

29690

29688

29689

R 1 s UDINT — E Date of setup in number of seconds since

01/01/2000 (1)

29691 29690 R 1 ms UINT — E Complement in ms with quality of the date (1)

29692 29691 R — s UINT 1...200 E Previous tlongstart time delay

29693

29694

29692

29693

R 1 s UDINT — E Date of setup in number of seconds since

01/01/2000 (1)

29695 29694 R 1 ms UINT — E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29696 29695 R — — UINT 0...3 A/E Previous neutral coefficient pick-up value

0 = Off

1 = 0.5

2 = 1.0

3 = OSN

29697

29698

29696

29697

R 1 s UDINT — A/E Date of setup in number of seconds since 01/01/2000

29699 29698 R 1 ms UINT — A/E Complement in ms with quality of the date. See Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29780 29779 R 1 V UINT 0...850 E Minimum of RMS phase-to-phase voltage V12

29781

29782

29780

29781

R 1 s UDINT — E Date in number of seconds since 01/01/2000 (1)

29783 29782 R 1 ms UINT — E Complement in ms with quality of the date (1)

29784 29783 R 1 V UINT 0...850 E Maximum of RMS phase-to-phase voltage V12

29785

29786

29784

29785

R 1 s UDINT — E Date in number of seconds since 01/01/2000 (1)

29787 29786 R 1 ms UINT — E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

LV434107 09/2009 77

Page 78: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Minimum/Maximum V23 Voltage Measurements

Register = 0 if voltage < 25 V.

Minimum/Maximum V31 Voltage Measurements

Register = 0 if voltage < 25 V.

Maximum I1 Current Measurement

Maximum I2 Current Measurement

Maximum I3 Current Measurement

Register Address RW X Unit Type Range A/E Description

29788 29787 R 1 V UINT 0...850 E Minimum of RMS phase-to-phase voltage V23

29789

29790

29788

29789

R 1 s UDINT — E Date in number of seconds since 01/01/2000 (1)

29791 29790 R 1 ms UINT — E Complement in ms with quality of the date (1)

29792 29791 R 1 V UINT 0...850 E Maximum of RMS phase-to-phase voltage V23

29793

29794

29792

29793

R 1 s UDINT — E Date in number of seconds since 01/01/2000 (1)

29795 29794 R 1 ms UINT — E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29796 29795 R 1 V UINT 0...850 E Minimum of RMS phase-to-phase voltage V31

29797

29798

29796

29797

R 1 s UDINT — E Date in number of seconds since 01/01/2000 (1)

29799 29798 R 1 ms UINT — E Complement in ms with quality of the date (1)

29800 29799 R 1 V UINT 0...850 E Maximum of RMS phase-to-phase voltage V31

29801

29802

29800

29801

R 1 s UDINT — E Date in number of seconds since 01/01/2000 (1)

29803 29802 R 1 ms UINT — E Complement in ms with quality of the date (1)

(1) See Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29804 29803 R 1 A UINT 0...20xIn A/E Maximum of RMS current on phase 1: I1

29805

29806

29804

29805

R 1 s UDINT — A/E Date in number of seconds since 01/01/2000

29807 29806 R 1 ms UINT — A/E Complement in ms with quality of the date. See

Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29808 29807 R 1 A UINT 0...20xIn A/E Maximum of RMS current on phase 2: I2

29809

29810

29808

29809

R 1 s UDINT — A/E Date in number of seconds since 01/01/2000

29811 29810 R 1 ms UINT — A/E Complement in ms with quality of the date. See

Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29812 29811 R 1 A UINT 0...20xIn A/E Maximum of RMS current on phase 3: I3

29813

29814

29812

29813

R 1 s UDINT — A/E Date in number of seconds since 01/01/2000

29815 29814 R 1 ms UINT — A/E Complement in ms with quality of the date. See

Date Format, page 35.

78 LV434107 09/2009

Page 79: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Maximum IN Current Measurement

Minimum Network Frequency

When the software cannot calculate the frequency it returns Not Evaluated = 32768 (0x8000).

Maximum Network Frequency

When the software cannot calculate the frequency it returns Not Evaluated = 32768 (0x8000).

I1 Peak Demand Measurement

A block read request of 20 registers is necessary to read the peak demand of current and power

(29828...29847). The reading starts at the beginning of the block read (see History Reading, page 38).

I2 Peak Demand Measurement

I3 Peak Demand Measurement

Register Address RW X Unit Type Range A/E Description

29816 29815 R 1 A UINT 0...20xIn A/E Maximum of current on neutral: IN

29817

29818

29816

29817

R 1 s UDINT — A/E Date in number of seconds since 01/01/2000

29819 29818 R 1 ms UINT — A/E Complement in ms with quality of the date. See

Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29820 29819 R 10 Hz UINT 150...4400 E Minimum of network frequency

29821

29822

29820

29821

R 1 s UDINT — E Date in number of seconds since 01/01/2000

29823 29822 R 1 ms UINT — E Complement in ms with quality of the date. See

Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29824 29823 R 10 Hz UINT 150...4400 E Maximum of network frequency

29825

29826

29824

29825

R 1 s UDINT — E Date in number of seconds since 01/01/2000

29827 29826 R 1 ms UINT — E Complement in ms with quality of the date. See

Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29828 29827 R 1 A UINT 0...20xIn E I1 peak demand

29829

29830

29828

29829

R 1 s UDINT — E Date in number of seconds since 01/01/2000

29831 29830 R 1 ms UINT — E Complement in ms with quality of the date. See

Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29832 29831 R 1 A UINT 0...20xIn E I2 peak demand

29833

29834

29832

29833

R 1 s UDINT — E Date in number of seconds since 01/01/2000

29835 29834 R 1 ms UINT — E Complement in ms with quality of the date. See

Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29836 298355 R 1 A UINT 0...20xIn E I3 peak demand

29837

29838

29836

29837

R 1 s UDINT — E Date in number of seconds since 01/01/2000

29839 29838 R 1 ms UINT — E Complement in ms with quality of the date. See

Date Format, page 35.

LV434107 09/2009 79

Page 80: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

IN Peak Demand Measurement

P Peak Demand Measurement

Register Address RW X Unit Type Range A/E Description

29840 29839 R 1 A UINT 0...20xIn E IN peak demand

29841

29842

29840

29841

R 1 s UDINT — E Date in number of seconds since 01/01/2000

29843 29842 R 1 ms UINT — E Complement in ms with quality of the date. See

Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

29844 29843 R 10 kW INT -

30000...+3

0000

E P peak demand

29845

29846

29844

29845

R 1 s UDINT — E Date in number of seconds since 01/01/2000

29847 29846 R 1 ms UINT — E Complement in ms with quality of the date. See

Date Format, page 35.

80 LV434107 09/2009

Page 81: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Maintenance Indicators

Time of Use Counter

The time of use counter reports the time of use of the circuit breaker. The time of use is written in the

EEPROM every 1 hour. If the time of use counter reaches the maximum value 4 294 967 295 and a new

time of use event occurs, then the counter is reset to 0.

A block read request of 2 registers is necessary to read the time of use counter (see History Reading, page 38).

Rate of Wear Counter

The rate of wear counter reports the percentage of the circuit breaker contact use.

Boot Counter

The boot counter reports the number of cold starts (power-up) and the number of warm starts (software

reset of the Micrologic trip unit).

EEPROM Writing Counter

The EEPROM writing counter reports the number of storage of the energy measurement in the EEPROM.

The energy measurement is written in the EEPROM every 1 hour. If the EEPROM writing counter

reaches the maximum value 4 294 967 295 and a new EEPROM writing event occurs, then the EEPROM

writing counter is reset to 0.

Load Profile Counters

The load profile counters report the number of hours for each range of current in the Micrologic trip unit.

If the load profile counters reach the maximum value 4 294 967 295 and a new load profile event occurs,

then the load profile counters are reset to 0.

A block read request of 8 registers is necessary to read the load profile counters (see History Reading, page 38).

Register Address RW X Unit Type Range A/E Description

29851

29852

29850

29851

R 1 Hour UDINT 0...4 294 967 295 A/E Counter of time of use

Register Address RW X Unit Type Range A/E Description

29853 29852 R 1 % UINT 0...32766 A/E Rate of wear counter

0% = The circuit breaker contact is new

> 100% = The circuit breaker contact must be

changed

Register Address RW X Unit Type Range A/E Description

29854 29853 R 1 — UINT 0...32766 A/E Boot counter

Register Address RW X Unit Type Range A/E Description

29855

29856

29854

29855

R 1 — UDINT 0...4 294 967 295 A/E Counter of EEPROM writing

Register Address RW X Unit Type Range A/E Description

29880

29881

29879

29880

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours for the 0...49 % of the

nominal current In range

29882

29883

29881

29882

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours for the 50...79 % of the

nominal current In range

29884

29885

29883

29884

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours for the 80...89 % of the

nominal current In range

29886

29887

29885

29886

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours for the 90...100 % of the

nominal current In range

LV434107 09/2009 81

Page 82: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Temperature Profile Counters

The temperature profile counters report the number of hours for each range of temperature in the

Micrologic trip unit. If the temperature profile counters reach the maximum value 4 294 967 295 and a

new temperature profile event occurs, then the temperature profile counters are reset to 0.

A block read request of 12 registers is necessary to read the temperature profile counters (see History Reading, page 38).

Protection Trips Counters

The protection trips counters report the number of protection trips for each type of protection: long time,

short time, instantaneous, ground fault, earth leakage (Vigi), jam, unbalance, longstart, and underload

protections. The protection trips counters stop incrementing when they reach the maximum value 10000.

A block read request of 9 registers is necessary to read the protection trips counters (see History Reading, page 38).

Register Address RW X Unit Type Range A/E Description

29890

29891

29889

29890

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours where the temperature is

< -30 °C

29892

29893

29891

29892

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours where the temperature is

in the -30...+59 °C range

29894

29895

29893

29894

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours where the temperature is

in the +60...+74 °C range

29896

29897

29895

29896

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours where the temperature is

in the +75...+89 °C range

29898

29899

29897

29898

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours where the temperature is

in the +90...+99 °C range

29900

29901

29899

29900

R 1 Hour UDINT 0...4 294 967 295 A/E Number of hours where the temperature is

> +100 °C

Register Address RW X Unit Type Range A/E Description

29910 29909 R 1 — UINT 0...10000 A/E Number of long time protection trips

29911 29910 R 1 — UINT 0...10000 A/E Number of short time protection trips

29912 29911 R 1 — UINT 0...10000 A/E Number of instantaneous protection trips

(including integrated instantaneous protection,

instantaneous with earth leakage (Vigi) protection,

and reflex protection)

29913 29912 R 1 — UINT 0...10000 A/E Number of ground fault protection trips

29914 29913 R 1 — UINT 0...10000 A/E Number of earth leakage (Vigi) protection trips

29915 29914 R 1 — UINT 0...10000 A/E Number of jam protection trips

29916 29915 R 1 — UINT 0...10000 A/E Number of unbalance protection trips

29917 29916 R 1 — UINT 0...10000 A/E Number of longstart protection trips

29918 29917 R 1 — UINT 0...10000 A/E Number of underload protection trips

82 LV434107 09/2009

Page 83: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Alarms Counters

The alarms counters report the number of occurrences of the alarms. When an alarm is configured, the

associated counter is set to 0. The alarm counters stop incrementing when they reach the maximum

value 10000.

A block read request of 13 registers is necessary to read the alarms counters (see History Reading, page 38).

Maintenance Operations Counters

The maintenance operations counters report the number of some maintenance operations. The

maintenance operations counters stop incrementing when they reach the maximum value 10000.

A block read request of 7 registers is necessary to read the maintenance operations counters (see History Reading, page 38).

Register Address RW X Unit Type Range A/E Description

29940 29939 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 201

29941 29940 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 202

29942 29941 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 203

29943 29942 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 204

29944 29943 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 205

29945 29944 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 206

29946 29945 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 207

29947 29946 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 208

29948 29947 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 209

29949 29948 R 1 — UINT 0...10000 A/E Counter of user-defined alarm 210

29950 29949 R 1 — UINT 0...10000 A/E Counter of pre-alarm Ir

29951 29950 R 1 — UINT 0...10000 A/E Counter of pre-alarm Ig

29952 29951 R 1 — UINT 0...10000 A/E Counter of pre-alarm IΔn

Register Address RW X Unit Type Range A/E Description

29980 29979 R — — UINT 0...10000 A/E Counter of Micrologic trip unit locking pad

activation

29981 29980 R — — UINT 0...10000 A/E Counter of connections of the maintenance

module

29982 29981 R — — UINT 0...10000 A/E Counter of ground fault test operation (using

Micrologic keypad only)

29983 29982 R — — UINT 0...10000 A/E Counter of earth leakage (Vigi) test operation

29984 29983 R — — UINT 0...10000 A/E Counter of ZSI (Zone Selective Interlocking) test

operation

29985 29984 R — — UINT 0...10000 A/E Counter of numerical injection test operation

LV434107 09/2009 83

Page 84: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Miscellaneous

Current Date

A block read request of 3 registers is necessary to read the current date (see History Reading, page 38).

The set absolute time command (command code 769) configures the content of the current date

registers.

Temperature

Time Remaining Until Long Time Tripping

Time remaining until long time tripping is evaluated every second. If another protection is tripped, then

time remaining until long time tripping continues to be evaluated.

Phase Rotation

Failure Status

NOTE: In the case of a STOP event, it is mandatory to replace the Micrologic trip unit. In the case of an

ERROR event, it is advised to replace the Micrologic trip unit (the core protection functions still work but

it is preferable to replace the Micrologic trip unit).

Register Address RW X Unit Type Range A/E Description

3000

3001

2999

3000

RW 1 s UDINT — A/E Date in number of seconds since 01/01/2000

3002 3001 RW 1 ms UINT — A/E Complement in ms with quality of the date. See Date Format, page 35.

Register Address RW X Unit Type Range A/E Description

8851 8850 R 1 °C INT -

30...+120

A/E Temperature of the Micrologic trip unit

Register Address RW X Unit Type Range A/E Description

8865 8864 R 1 s UINT 1...7200 A/E Time remaining until long time tripping (1)

(1) Time left until long time tripping = 32768 (0x8000) if

long time protection is already tripped,

time remaining until long time tripping is below 1 s, or

no default is detected by long time protection.

If time remaining until long time tripping is > 7200 s, then time remaining until long time tripping = 7200 s.

Register Address RW X Unit Type Range A/E Description

8872 8871 R 1 — UINT 0...1 E 0 = 123 phase sequence

1 = 132 phase sequence

Register Address RW X Unit Type Range A/E Bit Description

29390 29389 R — — UINT — A/E — Failure status

A/E 0 Reserved

A/E 1 STOP (internal failure)

0 = No internal failure

1 = Internal failure

A/E 2 ERROR (internal failure)

0 = No internal failure

1 = Internal failure

A/E 3...15 Reserved

84 LV434107 09/2009

Page 85: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Micrologic Trip Unit Rotary Switches

Micrologic Trip Unit Locking Pad Status

Auxiliary 24 V Power Supply

Micrologic Trip Unit LED

Register Address RW X Unit Type Range A/E Description

29990 29989 R 1 — UINT 1...9 A/E Position of Micrologic trip unit rotary switch 1 (Ir)

29991 29990 R 1 — UINT 1...9 A/E Position of Micrologic trip unit rotary switch 2 (Isd,

Ig/IΔn)

Register Address RW X Unit Type Range A/E Description

29992 29991 R 1 — UINT 0...1 A/E 0 = Micrologic trip unit locking pad open

1 = Micrologic trip unit locking pad closed

Register Address RW X Unit Type Range A/E Description

29993 29992 R 1 — UINT 0...1 A/E 0 = auxiliary 24 V power supply is not present

1 = auxiliary 24 V power supply is present

Register Address RW X Unit Type Range A/E Bit Description

30005 30004 R — — UINT — A/E — Micrologic trip unit LED

A/E 0 Ready LED

0 = not ready (LED is not blinking)

1 = ready (LED is blinking)

A/E 1 Pre-alarm LED (distribution application only)

0 = pre-alarm is not active (LED is steady off)

1 = pre-alarm is active (LED is steady on)

A/E 2 Overload LED

0 = overload is not active (LED is steady off)

1 = overload is active (LED is steady on)

A/E 3...15 Reserved

LV434107 09/2009 85

Page 86: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

3.2 Micrologic Trip Unit Commands

Introduction

This section describes the Micrologic trip unit commands.

What's in this Section?

This section contains the following topics:

Topic Page

Protection Commands 87

Acknowledge Event Commands 92

Measurement Configuration Commands 93

86 LV434107 09/2009

Page 87: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Protection Commands

General Description

The Modbus protection commands are described the following way:

location of the registers where the user reads the corresponding parameters of the protection

command

description of the registers where the user sets the parameters of the protection command

List of Protection Commands

The following table lists the available protection commands, their corresponding command codes and

password levels. Refer to Executing a Command, page 29 for the procedure to follow in order to write a

command.

Long Time Protection

The user can read the long time protection parameters from register 8754 to 8763. See Long Time Protection Parameters, page 67.

To set the long time protection parameters, the user must set up the command registers the following

way:

Command Command code Password level

Long time protection 45192 Level 4

Short time protection 45193 Level 4

Instantaneous protection 45194 Level 4

Ground fault protection 45195 Level 4

Earth leakage (Vigi) protection 45196 Level 4

Neutral protection 45197 Level 4

Jam protection 45448 Level 4

Underload protection 45449 Level 4

Unbalance protection 45450 Level 4

Longstart protection 45451 Level 4

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45192 A/E Command code = 45192

8001 8000 — — UINT 18 A/E Number of parameters (bytes) = 18

8002 8001 — — UINT 5121 A/E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 1 A UINT — A/E Ir pick-up value. The Ir range depends on the nominal

current In and on the position of the Micrologic trip unit

rotary switch 1 (Ir).

8007 8006 1 ms UINT 500

...16000

A/E tr time delay (distribution application only)

tr = 500, 1000, 2000, 4000, 8000, 16000 ms

8008 8007 — — UINT 5...30 A/E Motor class (motor application only)

Possible values = 5, 10, 20, 30

8009 8008 — — UINT 1... 2 A/E Cool fan (motor application only)

1 = auto, 2 = motor

LV434107 09/2009 87

Page 88: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Short Time Protection

The user can read the short time protection parameters from register 8764 to 8773. See Short Time Protection Parameters, page 67.

To set the short time protection parameters, the user must set up the command registers the following way:

Instantaneous Protection

The user can read the instantaneous protection parameters from register 8774 to 8783. See

Instantaneous Protection Parameters, page 68.

To set the instantaneous protection parameters, the user must set up the command registers the

following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45193 A/E Command code = 45193

8001 8000 — — UINT 16 A/E Number of parameters (bytes) = 16

8002 8001 — — UINT 5121 A/E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value =

‘0000’ = 0x30303030)

8006 8005 10 — UINT 15...100 A/E Isd coefficient, adjustable in step of 5.

Isd pick-up value = (Ir) x (Isd coefficient) / 10

8007 8006 1 ms UINT 0...400 A/E tsd time delay

tsd= 0, 100, 200, 300, 400 ms

If tsd = 0 ms, then I2t must be Off.

8008 8007 — — UINT 0...1 A/E Type of protection: 0 = I2t On, 1 = I2t Off

For motor application, tsd = 0 ms and I2t is Off (fixed

values).

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45194 A/E Command code = 45194

8001 8000 — — UINT 12 A/E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 A/E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password

(default value = ‘0000’ = 0x30303030)

8006 8005 10 — UINT (1) A/E Ii coefficient, adjustable in step of 5.

Ii pick-up value = (In) x (Ii coefficient) / 10

(1) The Ii coefficient range depends on the circuit breaker size:

For Compact NSX 100/160, the range is 15...150.

For Compact NSX 250/400, the range is 15...120.

For Compact NSX 630, the range is 15...110.

88 LV434107 09/2009

Page 89: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Ground Fault Protection

The user can read the ground fault protection parameters from register 8784 to 8793. See Ground Fault Protection Parameters, page 68.

To set the ground fault protection parameters, the user must set up the command registers the following

way:

Earth leakage (Vigi) Protection

The user can read the earth leakage (Vigi) protection parameters from register 8794 to 8803. See Earth Leakage (Vigi) Protection Parameters, page 69.

To set the earth leakage (Vigi) protection parameters, the user must set up the command registers the

following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45195 A/E Command code = 45195

8001 8000 — — UINT 16 A/E Number of parameters (bytes) = 16

8002 8001 — — UINT 5121 A/E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value =

‘0000’ = 0x30303030)

8006 8005 100 — UINT — A/E Ig coefficient, adjustable in step of 5. The value is

defined by the position of the Micrologic trip unit rotary

switch 2 (Ig).

Value 0 means the ground fault protection is off.

Ig pick-up value = (In) x (Ig coefficient) / 100

8007 8006 1 ms UINT 0...400 A/E tg time delay

tg = 0, 100, 200, 300, 400 ms

If tg = 0 ms, then I2t must be Off.

8008 8007 — — UINT 0...1 A/E Type of protection: 0 = I2t On, 1 = I2t Off

For motor application, tg = 0 ms and I2t is Off (fixed

values).

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45196 A/E Command code = 45196

8001 8000 — — UINT 14 A/E Number of parameters (bytes) = 14

8002 8001 — — UINT 5121 A/E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value =

‘0000’ = 0x30303030)

8006 8005 1 mA UINT — A/E IΔn value. The IΔn depends on the nominal current In.

8007 8006 1 ms UINT 0...1000 A/E tΔn time delay

tΔn = 0, 60, 150, 500, 1000 ms

If IΔn = 0.03 mA, then tΔn = 0 ms

LV434107 09/2009 89

Page 90: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Neutral Protection

The neutral protection is only available when system type in register 3314 is 30 or 41. See System Type, page 72.

The user can read the neutral protection parameters from register 8916 to 8919. See Neutral Protection Parameters, page 70.

To set the neutral protection registers, the user must set up the command registers the following way:

Jam Protection

The jam protection is available for motor application only.

The user can read the jam protection parameters from registers 8900 to 8903. See Jam Protection Parameters, page 69.

To set the jam protection parameters, the user must set up the command registers the following way:

Underload Protection

The underload protection is available for motor application only.

The user can read the underload protection parameters from register 8908 to 8911. See Underload Protection Parameters, page 69.

To set the underload protection parameters, the user must set up the command registers the following

way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45197 A/E Command code = 45197

8001 8000 — — UINT 12 A/E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 A/E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...3 A/E Neutral coefficient pickup value

0 = Off

1 = 0.5

2 = 1.0

3 = OSN

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45448 E Command code = 45448

8001 8000 — — UINT 16 E Number of parameters (bytes) = 16

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...1 E Activation: 0 = Off, 1 = On

8007 8006 10 — UINT 10...80 E Ijam coefficient, adjustable in step of 1.

Ijam pick-up value = (Ir) x (Ijam coefficient) / 10

8008 8007 1 s UINT 1...30 E tjam time delay

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45449 E Command code = 45449

8001 8000 — — UINT 16 E Number of parameters (bytes) = 16

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...1 E Activation: 0 = Off, 1 = On

8007 8006 100 — UINT 30...90 E Iunderload coefficient, adjustable in step of 1.

Iunderload pick-up value = (Ir) x (Iunderload) / 100

8008 8007 1 s UINT 1...200 E tunderload time delay

90 LV434107 09/2009

Page 91: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Unbalance Protection

The unbalance protection is available for motor application only.

The user can read the unbalance protection parameters from register 8904 to 8907. See Unbalance Protection Parameters, page 69.

To set the unbalance protection parameters, the user must set up the command registers the following

way:

Longstart Protection

The longstart protection is available for motor application only.

The user can read the underload protection parameters from register 8912 to 8915. See Longstart Protection Parameters, page 70.

To set the longstart protection parameters, the user must set up the command registers the following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45450 E Command code = 45450

8001 8000 — — UINT 14 E Number of parameters (bytes) = 14

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 1 % UINT 10...40 E Iunbal coefficient

8007 8006 1 s UINT 1...10 E tunbal time delay

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45451 E Command code = 45451

8001 8000 1 — UINT 16 E Number of parameters (bytes) = 16

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...1 E Activation: 0 = Off, 1 = On

8007 8006 10 — UINT 10...80 E Ilongstart coefficient, adjustable in step of 1.

Ilongstart pick-up value = (Ir) x (Ilongstart coefficient) / 10

8008 8007 1 s UINT 1...200 E tlongstart time delay

LV434107 09/2009 91

Page 92: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Acknowledge Event Commands

List of Acknowledge Event Commands

The following table lists the available acknowledge event commands, their command codes and

password levels:

Acknowledge a Latched Output

The user can read the SDx module outputs parameters from register 9801 to 9810. See Configuration of the SDx Module, page 71.

To acknowledge a latched output, the user must set up the command registers the following way:

Acknowledge a Trip

To acknowledge a trip, the user must set up the command registers the following way:

Command Command code Password level

Acknowledge a latched output 45216 Level 3 or 4

Acknowledge a trip 45217 Level 4

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45216 A/E Command code = 45216

8001 8000 — — UINT 12 A/E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 A/E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 3 or 4 password

For level 4, default value = ‘0000’ = 0x30303030

For level 3, default value = ‘3333’ = 0x33333333

8006 8005 — — UINT 1...2 A/E 1 = relay 1, 2 = relay 2

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 45217 A/E Command code = 45217

8001 8000 — — UINT 10 A/E Number of parameters (bytes) = 10

8002 8001 — — UINT 5121 A/E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value = ‘0000’ = 0x30303030)

92 LV434107 09/2009

Page 93: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Measurement Configuration Commands

List of Measurement Configuration Commands

The following table lists the available measurement configuration commands, their corresponding

command codes and password levels:

Set up ENVT presence

The user can read the ENVT (External Neutral Voltage Tap) presence parameters at register 3314. See

System Type, page 72.

To set up ENVT presence, the user must set up the command registers the following way:

Command Command code Password level

Set up ENVT presence 46472 Level 4

Reset minimum/maximum 46728 Level 3 or 4

Start/stop synchronization 46729 Level 3 or 4

Power flow sign configuration 47240 Level 4

Power factor sign configuration 47241 Level 4

Energy accumulation mode configuration 47242 Level 4

Current demand configuration 47243 Level 4

Power demand configuration 47244 Level 4

Set up nominal voltage Vn display 47245 Level 4

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 46472 E Command code = 46472

8001 8000 — — UINT 12 E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...1 E 0 = ENVT is not present

1 = ENVT is present

LV434107 09/2009 93

Page 94: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Reset Minimum/Maximum

The reset minimum/maximum command resets the minimum values of real-time measurements

(registers 1300 to 1599) and the maximum values of real-time measurements (registers 1600 to 1899).

See Minimum/Maximum Values of Real-Time Measurements, page 47.

The reset minimum/maximum command resets the energy measurements (registers 2000 to 2025). See

Energy Measurements, page 48.

The reset minimum/maximum command resets the peak demand measurements (registers 2200 to

2237). See Demand Measurements, page 49.

The user can read the minimum and maximum values of current, voltage, and frequency measurements

and the corresponding dates from register 29780 to 29827. See Minimum/Maximum V12 Voltage Measurements, page 77.

The user can read the dates of the reset minimum/maximum command from register 2900 to 2929. See

Minimum/Maximum Measurements Reset Time, page 50.

To reset minimum/maximum values of measurements, the user must set up the command registers the

following way:

Register Address Type Range A/E Bit Description

8000 7999 UINT 46728 — — Command code = 46728

8001 8000 UINT 12 — — Number of parameters (bytes) = 12

8002 8001 UINT 5121 — — Destination = 5121 (0x1401)

8003 8002 UINT 1 — — 1

8004

8005

8003

8004

STRING — — — Level 3 or 4 password

For level 4, default value = ‘0000’ = 0x30303030

For level 3, default value = ‘3333’ = 0x33333333

8006 8005 UINT — — — Reset minimum/maximum of metering variables

To reset the metering variable, set the bit to 1.

To keep the current values, set the bit to 0.

A/E 0 Reset minimum/maximum current (I1, I2, I3, IN, Imax, Ig,

IΔn, Iavg, and Iunbalance)

E 1 Reset minimum/maximum voltage (V12, V13, V23, V1N,

V2N, V3N, Vavg L-L, Vavg L-N, and Vunbalance)

E 2 Reset minimum/maximum power (active power, reactive

power, apparent power, and distortion power)

E 3 Reset minimum/maximum power factor and cosϕ

E 4 Reset minimum/maximum total harmonic distortion (THD)

E 5 Reset peak of current demand

E 6 Reset peak of active power, reactive power, and apparent

power demand

E 7 Reset minimum/maximum frequency

E 8 Reset minimum/maximum thermal image (motor application

only)

E 9 Reset energy (active, reactive, apparent)

— 10...15 Reserved

94 LV434107 09/2009

Page 95: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Start/Stop Synchronization

The start/stop synchronization command is used to start or stop the calculation of the current or power

demand. The first command starts the calculation, the next command updates the value of current or

power demand and then restarts the calculation. The time period between two commands must be less

than 1 hour.

To start/stop synchronization, the user must set up the command registers the following way:

Power Flow Sign Configuration

The user can read the power flow sign configuration at register 3316. See Power Flow Sign, page 72.

To set the power flow sign parameters, the user must set up the command registers the following way:

Power Factor Sign Configuration

The user can read the power factor sign configuration at register 3318. See Power Factor Sign, page 72.

To set the power factor sign parameters, the user must set up the command registers the following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 46729 E Command code = 46729

8001 8000 — — UINT 12 E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 3 or 4 password

For level 4, default value = ‘0000’ = 0x30303030

For level 3, default value = ‘3333’ = 0x33333333

8006 8005 — — UINT — E Start/stop synchronization = 1

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 47240 E Command code = 47240

8001 8000 — — UINT 12 E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...1 E Power flow sign

0 = the active power flows from upstream (top) to

downstream (bottom) (default)

1 = the active power flows from downstream (bottom) to

upstream (top).

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 47241 E Command code = 47241

8001 8000 — — UINT 12 E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...2 E Sign convention for the power factor and the fundamental

power factor (cosϕ)

0 = IEC convention

2 = IEEE convention (default)

LV434107 09/2009 95

Page 96: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Energy Accumulation Mode Configuration

The user can read the energy accumulation mode configuration at register 3324. See Energy Accumulation Mode, page 73.

To set the energy accumulation mode parameters, the user must set up the command registers the

following way:

Current Demand Configuration

The user can read the duration of the current demand calculation window at register 3352. See Demand Time, page 73.

The user can read the current demand parameters from register 2200 to 2207. See Current Demand, page 49.

To start current demand, the user must set up the command registers the following way:

Power Demand Configuration

The user can read the power demand calculation method from register 3354 to 3355. See Demand Time, page 73.

The user can read the power demand parameters from register 2224 to 2237. See Active Power Demand, page 49.

To start power demand, the user must set up the command registers the following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 47242 E Command code = 47242

8001 8000 — — UINT 12 E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...1 E Energy accumulation mode

0 = absolute accumulation (default)

1 = signed accumulation

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 47243 E Command code = 47243

8001 8000 — — UINT 12 E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — Min UINT 5...60 E Duration of the current demand calculation window,

adjustable in step of 1.

The default value is 15 minutes (sliding).

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 47244 E Command code = 47244

8001 8000 — — UINT 14 E Number of parameters (bytes) = 14

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — Min UINT 0...5 E Power demand calcultation method (window type):

0 = sliding

2 = fixed

5 = synchronized to communication

The default value is 0 (sliding)

8007 8006 — Min UINT 5...60 E Duration of the power demand calculation window,

adjustable in step of 1.

The default value is 15 minutes.

96 LV434107 09/2009

Page 97: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

Set Up Nominal Voltage Vn Display

The user can read the nominal voltage at register 9616. See Nominal Voltage, page 73.

To set the nominal voltage Vn display parameters, the user must set up the command registers the

following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 47245 E Command code = 47245

8001 8000 — — UINT 12 E Number of parameters (bytes) = 12

8002 8001 — — UINT 5121 E Destination = 5121 (0x1401)

8003 8002 — — UINT 1 E 1

8004

8005

8003

8004

— — STRING — E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — V UINT 0...65535 E Nominal voltage Vn (default value = 400 V)

LV434107 09/2009 97

Page 98: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Micrologic Trip Unit Data

98 LV434107 09/2009

Page 99: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

LV434107 09/2009

4

BSCM Data

LV434107 09/2009

BSCM Data

Introduction

This chapter describes the BSCM (Breaker Status and Control Module) data.

What's in this Chapter?

This chapter contains the following sections:

Section Topic Page

4.1 BSCM Registers 100

4.2 BSCM Commands 106

99

Page 100: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

4.1 BSCM Registers

Introduction

This section describes the BSCM registers.

What's in this Section?

This section contains the following topics:

Topic Page

Identification 101

Status 102

Maintenance Indicators 103

Event History 104

100 LV434107 09/2009

Page 101: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

Identification

Square D Identification

Serial Number

The BSCM serial number is composed of a maximum of 11 alphanumeric characters with the following

format: PPYYWWDnnnn.

PP = plant code

YY = year of fabrication (05...99)

WW = week of fabrication (01...53)

D = day of fabrication (1...7)

nnnn = sequence number (0001...9999)

A block read request of 6 registers is necessary to read the BSCM serial number (see History Reading, page 38).

Register Address RW X Unit Type Range A/E Description

551 550 R — — UINT 15149 A/E Square D identification = 15149 for the BSCM

Register Address RW X Unit Type Range A/E Description

552 551 R — — STRING — A/E ‘PP’

553 552 R — — STRING 05...99 A/E ‘YY’

554 553 R — — STRING 01...53 A/E ‘WW’

555 554 R — — STRING 1...7 A/E ‘Dn’

556 555 R — — STRING 00...99 A/E ‘nn’

557 556 R — — STRING 01...99 A/E ‘n’ (the NULL character ends the serial number)

LV434107 09/2009 101

Page 102: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

Status

Circuit Breaker Status

Communicating Motor Mechanism Status

Register Address RW X Unit Type Range A/E Bit Description

563 562 R — — UINT — A/E — Circuit breaker status register

A/E 0 OF input status

0 = circuit breaker is open

1 = circuit breaker is closed

A/E 1 SD input status

0 = circuit breaker is not tripped

1 = circuit breaker is tripped due to electrical

default or shunt trip or push to trip

A/E 2 SDE input status

0 = circuit breaker is not tripped on electrical

default

1 = circuit breaker is tripped due to electrical

default (including Ground fault test and Earth

leakage test)

— 3...15 Reserved (forced to 0)

Register Address RW X Unit Type Range A/E Bit Description

564 563 R — — UINT — A/E — Communicating motor mechanism status

register

A/E 0 Motor mechanism

0 = not available

1 = available

A/E 1 Manu/auto mode

0 = manu

1 = auto

A/E 2 Last command

0 = last command succeeded

1 = last command failed

A/E 3 Enable automatic reset

0 = automatic reset is not enabled

1 = automatic reset is enabled

A/E 4 Enable reset even if SDE

0 = reset is not enable if the circuit breaker is

tripped on electrical default.

1 = reset is enabled even if the circuit breaker is

tripped on electrical default.

A/E 5 Local/Remote mode

This mode is selected in the Front Display

Module (FDM121) menu.

0 = Remote mode (default value)

The communicating motor mechanism is

controlled through a Modbus command only.

1 = Local mode

The communicating motor mechanism is

controlled through the Front Display Module

(FDM121) menu only.

— 6...15 Reserved (forced to 0)

102 LV434107 09/2009

Page 103: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

Maintenance Indicators

General Description

The BSCM has 7 counters that help managing the Compact NSX circuit breaker.

The BSCM counters have the following properties:

All the counters are saved in non-volatile memory to prevent data loss in case of power loss.

The cumulating OF counter is read only. It stops incrementing when it reaches the maximum value

4 294 967 295.

The user can preset all counters (except the cumulating OF counter) to any value between 0 and

65535. The counters stop incrementing when they reach the maximum value 65535.

A threshold is associated to the OF counter and to the close circuit breaker command counter.

The user can set the threshold to any value between 0 and 65534. The default value is 5000. An alarm

is generated when a counter reaches the threshold.

Counters

Register Address RW X Unit Type Range A/E Description

571 572 570 571 R 1 — UDINT 0...4 294 967 295 A/E Cumulating OF counter (non resetable

open to close counter)

573 572 RW 1 — UINT 0...65535 A/E OF counter (resetable open to close

counter)

574 573 RW 1 — UINT 0...65535 A/E SD counter (Close to SD position)

575 574 RW 1 — UINT 0...65535 A/E SDE counter (Close to SDE position)

576 575 RW 1 — UINT 0...65535 A/E Open circuit breaker command counter

577 576 RW 1 — UINT 0...65535 A/E Close circuit breaker command counter

578 577 RW 1 — UINT 0...65535 A/E Reset circuit breaker command counter

579 578 — — — — — — Reserved

580 579 — — — — — — Reserved

581 580 RW 1 — UINT 0...65535 A/E OF counter threshold

The default value is 5000.

582 581 RW 1 — UINT 0...65535 A/E Close circuit breaker command counter

threshold

The default value is 5000.

LV434107 09/2009 103

Page 104: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

Event History

General Description

The BSCM event history registers describe the last 10 encountered events. The BSCM events format

corresponds to a series of 10 records. Each record is composed of 5 registers describing one BSCM

event.

A block read request of 5x(n) registers is necessary to read the last n BSCM event records, where 5 is

the number of registers for each event record. The reading starts at the beginning of the block read (see

History Reading, page 38).

For example, a block read request of 5x3 = 15 registers is necessary to read the last 3 BSCM event

records of the BSCM event history:

The first 5 registers describe the first BSCM event record (most recent event).

The next 5 registers describe the second BSCM event record.

The last 5 registers describe the third BSCM event record.

Event Counter

The event counter is incremented whenever a new event is logged. If the counter reaches the maximum

value 65535 and a new event is logged, then the counter is reset to 0.

Event Record

The order and the description of the events records registers are the same as that of event record 1:

Register Address Description

602 601 Event counter

603...607 602...606 Event record 1(most recent event)

608...612 607...611 Event record 2

613...617 612...616 Event record 3

618...622 617...621 Event record 4

623...627 622...626 Event record 5

628...632 627...631 Event record 6

633...637 632...636 Event record 7

638...642 637...641 Event record 8

643...647 642...646 Event record 9

648...652 647...651 Event record 10 (oldest event)

Register Address RW X Unit Type Range A/E Description

602 601 R 1 — UINT 0...65535 A/E BSCM event counter

Event 1 (most recent event)

Register Address RW X Unit Type Range A/E Description

603 602 R 1 — UINT 0...65535 A/E BSCM event identifier (see next paragraph)

604

605

603

604

R 1 s UDINT 0...4 294 967 295 A/E Date of event in number of seconds since

01/01/2000

606 605 R 1 ms UINT 0...65535 A/E Complement in ms with quality of the date.

See Date Format, page 35.

607 606 R 1 — UINT 1...2 A/E Event status

1 = event occurrence, 2 = event completion

104 LV434107 09/2009

Page 105: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

Event Identifier

NOTE: In the case of a STOP event, it is mandatory to replace the BSCM. In the case of an ERROR

event, it is advised to replace the BSCM (the core protection functions still work but it is preferable to

replace the BSCM).

Event Identifier Event

1024 SD contact change (occurrence = close to SD position)

1025 Threshold of OF counter is reached

1026 Threshold of close command counter is reached

1027 STOP (internal failure)

1028 ERROR (internal failure)

1029 OF contact change (occurrence = open to close position)

1030 SDE contact change (occurrence = close to SDE position)

1031 Manu/auto mode (occurrence = manu to auto position)

1040 Open command

1041 Close command

1042 Reset command

LV434107 09/2009 105

Page 106: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

4.2 BSCM Commands

Introduction

This section describes the BSCM commands.

What's in this Section?

This section contains the following topics:

Topic Page

Commands and Error Codes 107

Circuit Breaker Control Commands 108

Counters Commands 110

106 LV434107 09/2009

Page 107: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

Commands and Error Codes

List of Commands

The following table lists the available BSCM commands, their corresponding command codes and

password levels. Refer to Executing a Command, page 29 for the procedure to follow in order to write a

command.

Error Codes

In addition to generic error codes, the BSCM commands generate the following error codes returned in

register 8021:

Any other positive error code means an internal error.

Command Command code Password level

Open circuit breaker 904 Level 3 or 4

Close circuit breaker 905 Level 3 or 4

Reset circuit breaker 906 Level 3 or 4

Enable/disable automatic reset 42636 Level 4

Enable/disable reset even if SDE 42637 Level 4

Preset counters 42638 Level 4

Set up thresholds 42639 Level 4

Error code (dec) Description

4363=0x110B BSCM is out of order.

4503=0x1197 Circuit breaker is tripped. It must be reset before the command.

4504=0x1198 Circuit breaker is already closed.

4505=0x1199 Circuit breaker is already open.

4506=0x119A Circuit breaker is already reset.

4507=0x119B Actuator is in manual mode. Remote commands are not allowed.

4508=0x119C Actuator is not present.

4510=0x119E A previous command is still in progress.

4511=0x119F Reset command is forbidden when SDE is set.

LV434107 09/2009 107

Page 108: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

Circuit Breaker Control Commands

Open Circuit Breaker

To open the circuit breaker, the user must set up the command registers the following way:

Close Circuit Breaker

To close the circuit breaker, the user must set up the command registers the following way:

Reset Circuit Breaker

To reset the circuit breaker, the user must set up the command registers the following way:

Enable/Disable Automatic Reset

The user can read the automatic reset parameters at register 564 (bit 3). See Communicating Motor Mechanism Status, page 102.

To enable/disable automatic reset, the user must set up the command registers the following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 904 A/E Command code = 904

8001 8000 — — UINT 10 A/E Number of parameters (bytes) = 10

8002 8001 — — UINT 4353 A/E Destination = 4353 (0x1101)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 3 or 4 password

For level 4, default value = ‘0000’ = 0x30303030

For level 3, default value = ‘3333’ = 0x33333333

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 905 A/E Command code = 905

8001 8000 — — UINT 10 A/E Number of parameters (bytes) = 10

8002 8001 — — UINT 4353 A/E Destination = 4353 (0x1101)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 3 or 4 password

For level 4, default value = ‘0000’ = 0x30303030

For level 3, default value = ‘3333’ = 0x33333333

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 906 A/E Command code = 906

8001 8000 — — UINT 10 A/E Number of parameters (bytes) = 10

8002 8001 — — UINT 4353 A/E Destination = 4353 (0x1101)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 3 or 4 password

For level 4, default value = ‘0000’ = 0x30303030

For level 3, default value = ‘3333’ = 0x33333333

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 42636 A/E Command code = 42636

8001 8000 — — UINT 12 A/E Number of parameters (bytes) = 12

8002 8001 — — UINT 4353 A/E Destination = 4353 (0x1101)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...1 A/E 0 = automatic reset in not enabled

1 = automatic reset is enabled

108 LV434107 09/2009

Page 109: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

Enable/Disable Reset even if SDE

The user can read the reset parameters at register 564 (bit 4). See Communicating Motor Mechanism Status, page 102.

To enable/disable reset even if SDE, the user must set up the command registers the following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 42637 A/E Command code = 42637

8001 8000 — — UINT 12 A/E Number of parameters (bytes) = 12

8002 8001 — — UINT 4353 A/E Destination = 4353 (0x1101)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 — — UINT 0...1 A/E 0 = reset is not enabled if SDE = 1

1 = reset is enabled even if SDE = 1

LV434107 09/2009 109

Page 110: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

BSCM Data

Counters Commands

Preset Counters

The user can read the values of the counters from register 571 to 578. See Counters, page 103.

To preset the counters, the user must set up the command registers the following way:

Set Up Thresholds

The user can read the values of the thresholds from register 581 to 582. See Counters, page 103.

To set up the thresholds, the user must set up the command registers the following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 42638 A/E Command code = 42638

8001 8000 — — UINT 22 A/E Number of parameters (bytes) = 22

8002 8001 — — UINT 4353 A/E Destination = 4353 (0x1101)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 1 — UINT 0...6553

5

A/E 0...65534 = preset value of the OF counter

65535 = do not preset the OF counter

8007 8006 1 — UINT 0...6553

5

A/E 0...65534 = preset value of the SD counter

65535 = do not preset the SD counter

8008 8007 1 — UINT 0...6553

5

A/E 0...65534 = preset value of the SDE counter

65535 = do not preset the SDE counter

8009 8008 1 — UINT 0...6553

5

A/E 0...65534 = preset value of the open circuit breaker

command counter

65535 = do not preset the open circuit breaker

command counter

8010 8009 1 — UINT 0...6553

5

A/E 0...65534 = preset value of the close circuit breaker

command counter

65535 = do not preset the close circuit breaker

command counter

8011 8010 1 — UINT 0...6553

5

A/E 0...65534 = preset value of the reset circuit breaker

command counter

65535 = do not preset the reset circuit breaker

command counter

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 42639 A/E Command code = 42639

8001 8000 — — UINT 22 A/E Number of parameters (bytes) = 22

8002 8001 — — UINT 4353 A/E Destination = 4353 (0x1101)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value = ‘0000’ = 0x30303030)

8006 8005 1 — UINT 0...6553

5

A/E 0...65534 = value of the OF counter threshold

65535 = do not change the OF counter threshold

8007 8006 1 — UINT 65535 A/E 65535 (no threshold is associated to the SD counter)

8008 8007 1 — UINT 65535 A/E 65535 (no threshold is associated to the SDE counter)

8009 8008 1 — UINT 65535 A/E 65535 (no threshold is associated to the open circuit

breaker command counter)

8010 8009 1 — UINT 0...6553

5

A/E 0...65534 = value of the close circuit breaker command

counter threshold

65535 = do not change close circuit breaker command

counter threshold

8011 8010 1 — UINT 65535 A/E 65535 (no threshold is associated to the reset circuit

breaker command counter)

110 LV434107 09/2009

Page 111: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

LV434107 09/2009

5

Modbus Communication Interface Module Data

LV434107 09/2009

Modbus Communication Interface Module Data

Introduction

This chapter describes the Modbus communication interface module data.

What's in this Chapter?

This chapter contains the following sections:

Section Topic Page

5.1 Modbus Communication Interface Module Registers 112

5.2 Modbus Communication Interface Module Commands 115

5.3 Communication Profile 119

111

Page 112: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

5.1 Modbus Communication Interface Module Registers

Introduction

This section describes the Modbus communication interface module registers.

What's in this Section?

This section contains the following topics:

Topic Page

Identification 113

Modbus Network Parameters 114

112 LV434107 09/2009

Page 113: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Identification

Firmware Version

The Modbus communication interface module firmware version starts with a V character and has the

following format: VX.Y.Z ended by the NULL character (0x00). The firmware version starts at register

11776 and has a maximum length of 7 registers.

X, Y, and Z are in the 1...999 range.

A block read request of 7 registers is necessary to read the Modbus communication interface module

firmware version (see History Reading, page 38).

Serial Number

The Modbus communication interface module serial number is composed of a maximum of 11

alphanumeric characters with the following format: PPYYWWDnnnn.

PP = plant code

YY = year of fabrication (05...99)

WW = week of fabrication (01...53)

D = day of fabrication (1...7)

nnnn = sequence number (0001...9999)

A block read request of 6 registers is necessary to read the Modbus communication interface module

serial number (see History Reading, page 38).

Square D Identification

Hardware Version

Register Address RW X Unit Type Range A/E Description

11784 11783 R — — STRING — A/E ‘PP’

11785 11784 R — — STRING 05...99 A/E ‘YY’

11786 11785 R — — STRING 01...53 A/E ‘WW’

11787 11786 R — — STRING 1...7 A/E ‘Dn’

11788 11787 R — — STRING 00...99 A/E ‘nn’

11789 11788 R — — STRING 00...99 A/E ‘n ’ (the NULL character ends the serial number)

Register Address RW X Unit Type Range A/E Description

11901 11900 R — — UINT — A/E Square D identification = 15146 for the Modbus

communication interface module

Register Address RW X Unit Type Range A/E Description

11903

...11906

11902

...11905

R 1 — STRING — A/E Hardware version of the Modbus communication

interface module

LV434107 09/2009 113

Page 114: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Modbus Network Parameters

IMU Identification

The IMU (Intelligent Modular Unit) is the set of modules (Micrologic trip unit, BSCM, front display module

FDM121) connected to one Modbus communication interface module. When not programmed, these

registers return 0 (0x0000). The front display module FDM121 displays the IMU name but it is limited to

the first 12 characters.

Modbus Locking Pad Position

Auto-Speed Sensing State

Modbus Address of Modbus Communication Interface Module

Modbus Parity

Modbus Baudrate

Number of Stop Bits

Register Address RW X Unit Type Range A/E Description

11801

11823

11800

11822

R — — STRING — A/E IMU name = up to 47 ASCII characters ended by the

NULL character 0x00

11846

11868

11845

11867

R — — STRING — A/E IMU location = up to 47 ASCII characters ended by

the NULL character 0x00

Register Address RW X Unit Type Range A/E Description

11891 11890 R — — UINT 1...3 A/E Modbus locking pad position

1 = Modbus locking pad is on the locked position

3 = Modbus locking pad is on the open position

Register Address RW X Unit Type Range A/E Description

12399 12398 R — — UINT 0...1 A/E Auto-Speed sensing state

0 = Auto-Speed sensing is disabled

1 = Auto-Speed sensing is enabled (default)

Register Address RW X Unit Type Range A/E Description

12400 12399 R — — UINT 1...99 A/E Modbus address of Modbus communication interface

module

Register Address RW X Unit Type Range A/E Description

12401 12400 R — — UINT 1...3 A/E Modbus parity

1 = no parity

2 = even parity (default)

3 = odd parity

Register Address RW X Unit Type Range A/E Description

12402 12401 R — — UINT 5...8 A/E Modbus baudrate

5 = 4800 bauds

6 = 9600 bauds

7 = 19200 bauds (default)

8 = 38400 bauds

Register Address RW X Unit Type Range A/E Description

12403 12402 R — — UINT 0...5 A/E Number of stop bits

0 = no change

1 = Standard Modbus

2 = 1/2 stop bit

3 = 1 stop bit

4 = 1 and 1/2 stop bit

5 = 2 stop bits

114 LV434107 09/2009

Page 115: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

5.2 Modbus Communication Interface Module Commands

Introduction

This section describes the Modbus communication interface module commands.

What's in this Section?

This section contains the following topics:

Topic Page

List of Modbus Communication Interface Module Commands 116

Modbus Communication Interface Module Commands 117

LV434107 09/2009 115

Page 116: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

List of Modbus Communication Interface Module Commands

List of Commands

The following table lists the Modbus communication interface module commands, their corresponding

command codes and password levels. Refer to Executing a Command, page 29 for the procedure to

follow in order to write a command.

Command Command code Password level

Get current time 768 no password required

Set absolute time 769 no password required

Read IMU name and location 1024 4

Write IMU name and location 1032 4

116 LV434107 09/2009

Page 117: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Modbus Communication Interface Module Commands

Get Current Time

The get current time command is not hardware protected. When the arrow of the Modbus locking pad

(located on the front panel of the Modbus communication interface module) points to the closed padlock,

the get current time command is still enabled.

To get the current time for all modules, the user must setup the command registers the following way:

The following registers contain the time data:

register 8023 holds the month in the MSB, the day in the LSB.

register 8024 holds the year offset in the MSB (add 2000 to get the year) and the hour in the LSB.

register 8025 holds the minutes in the MSB, the seconds in the LSB.

register 8026 holds the milliseconds.

Set Absolute Time

The set absolute time command is not hardware protected. When the arrow of the Modbus locking pad

(located on the front panel of the Modbus communication interface module) points to the closed padlock,

the set absolute time command is still enabled.

To set the absolute time for all the IMU modules, the user must setup the command registers the following

way:

In case of 24 V DC power loss, date and time counter is reset and will restart at January 1st 2000. It is

therefore mandatory to set absolute time for all the IMU modules after recovering the 24 V DC power

supply. Furthermore, due to the clock drift of each IMU module, it is mandatory to set absolute time for

all the IMU modules periodically. Recommended period is at least every hour.

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 768 A/E Command code = 768

8001 8000 — — UINT 10 A/E Number of parameters (bytes) = 10

8002 8001 — — UINT 768 A/E Destination = 768 (0x0300)

8003 8002 — — UINT 0 A/E 0

8004

8005

8003

8004

— — STRING 0 A/E Password = 0 (load 0x0000 into registers 8004 and

8005)

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 769 A/E Command code = 769

8001 8000 — — UINT 18 A/E Number of parameters (bytes) = 18

8002 8001 — — UINT 768 A/E Destination = 768 (0x0300)

8003 8002 — — UINT 0 A/E 0

8004

8005

8003

8004

— — STRING 0 A/E Password = 0 (load 0x0000 into registers 8004 and

8005)

8006 8005 — — UINT — A/E MSB = month (1...12)

LSB = day in the month (1...31)

8007 8006 — — UINT — A/E MSB = year (0...99, 0 meaning year 2000)

LSB = hour (0...23)

8008 8007 — — UINT — A/E MSB = minute (0...59)

LSB = second (0...59)

8009 8008 — ms UINT 0...999 A/E Milliseconds (0...999)

LV434107 09/2009 117

Page 118: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Read IMU Name and Location

The user can read the IMU name and location from register 11801 to 11861. See IMU Identification, page 114.

The front display module FDM121 displays the IMU name but it is limited to the first 14 characters.

To read the IMU name and location, the user must set up the command registers the following way:

The response to this command will have the following format:

Write IMU Name and Location

The user can read the IMU name and location from register 11801 to 11861. See IMU Identification, page 114.

The front display module FDM121 displays the IMU name but it is limited to the first 14 characters.

To write the IMU name and location, the user must set up the command registers the following way:

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 1024 A/E Command code = 1024

8001 8000 — — UINT 16 A/E Number of parameters (bytes) = 16

8002 8001 — — UINT 768 A/E Destination = 768 (0x0300)

8003 8002 — — UINT 1 A/E 0

8004

8005

8003 8004 — — STRING — A/E Password = 0 (load 0x0000 into registers 8004 and

8005)

8006

8007

8005 8006 — — UDINT — A/E 17039489 = read IMU name (load 0x0104 into

register 8006, 0x0081 into 8007)

17039490 = read IMU location (load 0x0104 into

register 8006, 0x0082 into 8007)

8008 8007 — — UINT 2048 A/E 2048

Register Address X Unit Type Range A/E Description

8021 8020 — — UINT — A/E Command status

0 = command succeeded

Otherwise, command failed

8022 8021 — — UINT — A/E Number of bytes returned (0 if command failed)

8023 8022 — — STRING — A/E If command succeeded

MSB = first character of IMU name or location

LSB = second character of IMU name or location

... ... — — STRING — A/E Depends on the length of the IMU name or location and

is ended by the NULL character 0x00

Register Address X Unit Type Range A/E Description

8000 7999 — — UINT 1032 A/E Command code = 1032

8001 8000 — — UINT 18...32 A/E Number of parameters (bytes) = depends on the

length of the IMU name or location (up to 47 ASCII

characters ended by the NULL character 0x00)

8002 8001 — — UINT 768 A/E Destination = 0 (0x0000)

8003 8002 — — UINT 1 A/E 1

8004

8005

8003

8004

— — STRING — A/E Level 4 password (default value =

‘0000’ = 0x30303030)

8006

8007

8005

8006

— — UDINT — A/E 17039489 = set IMU name (load 0x0104 into register

8006, 0x0081 into 8007)

17039490 = set IMU location (load 0x0104 into

register 8006, 0x0082 into 8007)

8008 8006 — — UINT 2048 A/E 2048

8009 8008 — — STRING — A/E MSB = First character of the IMU name or location

LSB = Second character of the IMU name or location

... ... — — STRING — A/E Depends on the length of the IMU name or location

and is ended by the NULL character 0x00

118 LV434107 09/2009

Page 119: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

5.3 Communication Profile

Introduction

The Modbus communication interface module holds the communication profile registers.

What's in this Section?

This section contains the following topics:

Topic Page

Communication Profile 120

Modbus Registers 121

Communication Profile Common Registers 123

Readout Examples 131

Communication Test 132

LV434107 09/2009 119

Page 120: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Communication Profile

General Description

The communication profile is a global entity that collects the most useful information of each ULP module

in one convenient table.

The benefit is that in one location the user can, with one block read function, get up-to-date information.

Each module pushes the data on a regular basis so that the structure is refreshed with current values.

The communication profile is defined in the 12000-12180 register range.

NOTE: The communication profile is compatible with previous versions of the Micrologic trip unit. For this

reason data read directly in the Modbus registers is organized in a different way than in the

communication profile.

Update period

The measurement update period with Modbus communication is:

1 second for the following measurements:

voltage and voltage unbalance,

current and current unbalance,

active, reactive, apparent, and distortion power,

reactive power with harmonic,

power factor and fundamental power factor,

frequency,

5 seconds for the following measurements:

energy,

minimum and maximum values of real-time measurements.

THD (Total Harmonic Distorsion).

120 LV434107 09/2009

Page 121: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Modbus Registers

Table of Communication Profile Common Registers

The main information needed for remote supervision of a Compact NSX, Compact NS or Masterpact

NT/NW circuit breaker is contained in the table of common registers starting at register 12000.

This compact table of 113 registers can be read with a single Modbus request.

It contains the following information:

Circuit breaker status

Trip unit protection status

Real-time values of main measurements: current, voltage, power, energy, total harmonic distortion

The content of this table of registers is detailed in the List of Common Registers (Communication Profile)

section.

Use of these common registers is highly recommended to optimize response times and simplify use of

data.

NOTE: For Compact NS/Masterpact circuit breakers, the communication profile (table of common

registers) must be activated by writing 1 in register 800.

Maintenance Data Registers

Maintenance data for a Compact NSX, Compact NS or Masterpact NT/NW circuit breaker is not available

in the table of common registers.

This must be read by specific read requests according to the type of circuit breaker.

See registers 29851 onwards for Compact NSX.

See registers 9094 onwards for Compact NS/Masterpact.

Measurement Update Period

The update period for the common registers is:

1 second for the following measurements:

Voltage and voltage unbalance

Current and current unbalance

Active, reactive, apparent, and distortion power

Reactive power with harmonics

Power factor and fundamental power factor

Frequency

5 seconds for the following measurements:

Energy

Minimum and maximum real-time measurement values

Total harmonic distortion (THD)

LV434107 09/2009 121

Page 122: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Register Tables Format

The register tables consist of the following columns:

Register: Number of the 16-bit register in decimal number format.

Address: Address of the 16-bit register (one less than the register number).

R/W: The register is either read-only (R), or read-write (R/W).

X: Scale factor. Scale 10 means that the register contains the value multiplied by 10. The actual value

is therefore the register value divided by 10.

Example

Register 12036 contains the network frequency. The unit is Hz and the scale factor is 10.

If the register contains the value 502, this means that the network frequency is

502/10 = 50.2 Hz.

Unit: Unit in which the information is expressed.

Type: Type of encoding data.

Range: Permitted values for this register, usually a subset of what the format allows.

A/E: Types of Micrologic Compact NSX trip unit for which the register is available.

Type A (ammeter): Current measurements

Type E (energy): Current, voltage, power and energy measurements

A/P/H: Types of Masterpact NT/NW and Compact NS Micrologic trip unit for which the register is

available.

Type A (ammeter): Current measurements

Type P (power): Current, voltage, power and energy measurements

Type H (harmonics): Current, voltage, power, energy and energy quality measurements

Description: Provides information about the register and the restrictions applying to it.

Data Types

The following data types appear in the Modbus register tables:

Notes

The type column indicates the number of registers to be read in order to obtain the variable. For

example, UINT asks for one word to be read whereas DINT requires 2 words to be read.

Reading from an undocumented address results in a Modbus exception.

Variables stored in 2 words (energy, for example) are stored in big-endian format: the most significant

word is transmitted first, the least significant second.

Digital values are given in decimal format. When there is an advantage in having the corresponding

value in hexadecimal format, this is given as a constant in C language: 0xdddd. For example, the

decimal value 123 is represented in hexadecimal format as 0x007B.

Non-functioning and non-applicable values are represented by 32,768 (0x8000 or 0x8000000 for 32-

bit values).

Out-of-limit values are represented by 32,767 (0x7FFF, for 16-bit values only).

For measurements which depend on presence of the neutral, value readout returns 32,768 (0x8000)

if not applicable. For each table where this appears, an explanation is given in a footnote.

Register Address R/W X Unit Type Range A/E A/P/H Description

Label Description Range

UINT Unsigned 16-bit integer 0 to 65,535

INT Signed 16-bit integer -32,768 to +32,767

UDINT Unsigned 32-bit integer 0 to 4,294,967,295

DINT Signed 32-bit integer -2,147,483,648 to +2,147,483,647

STRING Text string 1 byte per character

122 LV434107 09/2009

Page 123: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Communication Profile Common Registers

Data Validity

Circuit Breaker Status Register

Register Address R/W X Unit Type Range A/E A/P/H Description

12000 11999 R 1 - UINT - A/E A/P/H Indicates the validity of each bit in the

circuit breaker status register (12001).

Register Address R/W X Unit Type Range A/E A/P/H Bit Description

12001 12000 R — — UINT — A/E A/P/H — Circuit breaker status register

A/E A/P/H 0 OF status

0 = The circuit breaker is open

1 = The circuit breaker is closed

A/E A/P/H 1 SD trip indication

For Compact NS and NSX:

0 = circuit breaker is not tripped.

1 = circuit breaker is tripped due

to electrical default or shunt trip

or push to trip.

For Masterpact: Always 0

A/E A/P/H 2 SDE fault trip indication

0 = circuit breaker is not tripped on

electrical default.

1 = circuit breaker is tripped due to

electrical default (including Ground

fault test and Earth leakage test).

— A/P/H 3 CH loaded (only with Masterpact

motor mechanism)

0 = Spring discharged

1 = Spring loaded

— — 4 Reserved

— A/P/H 5 PF ready to close

0 = Not ready to close

1 = Ready to close

— A/P/H 6 Distinction between

Compact/Masterpact

0 = Compact

1 = Masterpact

— — 7...14 Reserved

A/E A/P/H 15 Data availability

If this bit is at 1, the circuit breaker

status is not available.

12002

12003

12001

12002

R — — UINT — — - - Reserved

LV434107 09/2009 123

Page 124: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Tripping Cause

The tripping cause register provides information about the cause of the trip for the basic protection

functions. When a bit is at 1 in the register, it indicates that a trip has occurred and has not been

acknowledged.

Register Address R/W X Unit Type Range A/E A/P/H Bit Description

12004 12003 R — — UINT — A/E A/P/H — Tripping cause for the basic protection

functions

A/E A/P/H 0 Long time protection Ir

A/E A/P/H 1 Short time protection Isd

A/E A/P/H 2 Instantaneous protection Ii

A/E A/P/H 3 Ground fault protection Ig

A/E A/P/H 4 Earth leakage protection (Vigi module)

IΔn

A/E A/P/H 5 Integrated instantaneous protection

A/E — 6 Internal failure (STOP)

— A 6 Other protections

— P/H 6 Internal failure (temperature)

— P/H 7 Internal failure (overvoltage)

— P/H 8 Other protection (see register 12005)

A/E — 9 Instantaneous with earth leakage

protection (Vigi module) on the trip unit

E — 10 Unbalance motor protection

E — 11 Jam motor protection

E — 12 Underload motor protection

E — 13 Long start motor protection

A/E — 14 Reflex tripping protection

A/E A/P/H 15 If this bit is at 1, bits 0 to 14 are not

valid.

12005 12004 R — — UINT — — P/H — Tripping causes for the advanced

protection functions

12006

12007

12005

12006

R — — UINT — — — — Reserved

124 LV434107 09/2009

Page 125: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Overrun of the Protection Setpoints

The alarm setpoint registers provide information about overrun of the standard and advanced protection

setpoints. A bit is at 1 once a setpoint overrun has occurred, even if the time-out has not expired.

Register Address R/W X Unit Type Range A/E A/P/H Bit Description

12008 12007 R — — UINT — A/E P/H — Overrun of the standard protection

setpoints

A/E P/H 0 Long time protection pick-up

— — 1...14 Reserved

A/E P/H 15 If this bit is at 1, bits 0 to 14 are not

valid.

12009 12008 R — — UINT — — P/H — Overrun of the advanced protection

setpoints

— P/H 0 Current unbalance

— P/H 1 Maximum current on phase 1

— P/H 2 Maximum current on phase 2

— P/H 3 Maximum current on phase 3

— P/H 4 Maximum current on the neutral

— P/H 5 Minimum voltage

— P/H 6 Maximum voltage

— P/H 7 Voltage unbalance

— P/H 8 Maximum power

— P/H 9 Reverse power

— P/H 10 Minimum frequency

— P/H 11 Maximum frequency

— P/H 12 Phase rotation

— P/H 13 Load shedding based on the current

— P/H 14 Load shedding based on the power

— P/H 15 If this bit is at 1, bits 0 to 14 are not

valid.

12010 12009 R — — UINT — — P/H — Continuation of the previous register

— P/H 0 Ground fault alarm

— P/H 1 Earth leakage alarm (Vigi module)

— — 2...14 Reserved

— P/H 15 If this bit is at 1, bits 0 to 14 are not

valid.

LV434107 09/2009 125

Page 126: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Alarms

The alarm register provides information about the pre-alarms and the user-defined alarms. A bit is set to

1 once an alarm is active.

Currents

Register Address R/W X Unit Type Range A/E A/P/H Bit Description

12011 12010 R — — UINT — A/E — — Pre-alarm register

A/E — 0 Long time protection time pre-

alarm (PAL Ir)

A/E — 1 Earth leakage protection pre-alarm

(Vigi module) (PAL IΔn)

A/E — 2 Ground fault protection pre-alarm

(PAL Ig)

— — 3...14 Reserved

A/E — 15 If this bit is at 1, bits 0 to 14 are not

valid.

12012 12011 R — — UINT — A/E — — Register of user-defined alarms

A/E — 0 User-defined alarm 201

A/E — 1 User-defined alarm 202

A/E — 2 User-defined alarm 203

A/E — 3 User-defined alarm 204

A/E — 4 User-defined alarm 205

A/E — 5 User-defined alarm 206

A/E — 6 User-defined alarm 207

A/E — 7 User-defined alarm 208

A/E — 8 User-defined alarm 209

A/E — 9 User-defined alarm 210

— — 10...14 Reserved

A/E — 15 If this bit is at 1, bits 0 to 14 are not

valid.

12013...

12015

12012...

12014

R — — UINT — — — — Reserved

Register Address R/W X Unit Type Range A/E A/P/H Description

12016 12015 R 1 A UINT 0...20xIn A/E A/P/H Rms current on phase 1: I1

12017 12016 R 1 A UINT 0...20xIn A/E A/P/H Rms current on phase 2: I2

12018 12017 R 1 A UINT 0...20xIn A/E A/P/H Rms current on phase 3: I3

12019 12018 R 1 A UINT 0...20xIn A/E A/P/H Rms current on the neutral: IN (1)

12020 12019 R 1 A UINT 0...20xIn A/E A/P/H Maximum of I1, I2, I3, and IN

12021 12020 R 1 (2) UINT — A/E A/P/H Ground fault current Ig. The range

depends on the nominal current In.

12022 12021 R 1 (3) UINT — A/E A/P/H Ground leakage current IΔn. The

range depends on the nominal current

In.

(1) Value cannot be accessed for motor applications and in cases of 3-pole circuit breakers without external neutral

current transformer (ENCT).

(2) This value is only available:

For Masterpact NT/NW and Compact NS Micrologic 6.0 trip units, expressed in amps

For Compact NSX Micrologic 6.2 and 6.3 trip units, expressed as %Ig

(3) This value is only available:

For Masterpact NT/NW and Compact NS Micrologic 7.0 trip units, expressed in milliamps

For Compact NSX Micrologic 7.2 and 7.3 trip units, expressed as %lΔn

126 LV434107 09/2009

Page 127: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Maximum Current Values

Voltages

Register = 0 if the voltage < 25 V.

Frequency

When the software cannot calculate the frequency, it returns Not available = 32,768 (0x8000).

Register Address R/W X Unit Type Range A/E A/P/H Description

12023 12022 R 1 A UINT 0...20xIn A/E A/P/H Maximum rms current on phase 1: I1

12024 12023 R 1 A UINT 0...20xIn A/E A/P/H Maximum rms current on phase 2: I2

12025 12024 R 1 A UINT 0...20xIn A/E A/P/H Maximum rms current on phase 3: I3

12026 12025 R 1 A UINT 0...20xIn A/E A/P/H Maximum rms current on the neutral: IN

(1)

12027 12026 R 1 A UINT 0...20xIn A/E A/P/H Maximum rms current out of the 4

previous registers

12028 12027 R 1 (2) UINT — A/E A/P/H Maximum ground fault current Ig. The

range depends on the current In.

12029 12028 R 1 (3) UINT — A/E A/P/H Maximum ground leakage current IΔn.

The range depends on the nominal

current In.

(1) Value cannot be accessed for motor applications and in cases of 3-pole circuit breakers without external neutral

current transformer (ENCT).

(2) This value is only available:

For Masterpact NT/NW and Compact NS Micrologic 6.0 trip units, expressed in amps

For Compact NSX Micrologic 6.2 and 6.3 trip units, expressed as %Ig

(3) This value is only available:

For Masterpact NT/NW and Compact NS Micrologic 7.0 trip units, expressed in milliamps

For Compact NSX Micrologic 7.2 and 7.3 trip units, expressed as %lΔn

Register Address R/W X Unit Type Range A/E A/P/H Description

12030 12029 R 1 V UINT 0...850 E P/H Rms phase-to-phase voltage V12

12031 12030 R 1 V UINT 0...850 E P/H Rms phase-to-phase voltage V23

12032 12031 R 1 V UINT 0...850 E P/H Rms phase-to-phase voltage V31

12033 12032 R 1 V UINT 0...850 E P/H Rms phase-to-neutral voltage V1N (1)

12034 12033 R 1 V UINT 0...850 E P/H Rms phase-to-neutral voltage V2N (1)

12035 12034 R 1 V UINT 0...850 E P/H Rms phase-to-neutral voltage V3N (1)

(1) Value cannot be accessed for motor applications and in cases of 3-pole circuit breakers without external neutral

voltage transformer (ENVT).

Register Address R/W X Unit Type Range A/E A/P/H Description

12036 12035 R 10 Hz UINT 150...4400 E P/H Network frequency: F

12037 12036 R 10 Hz UINT 150...4400 E P/H Network frequency maximum

LV434107 09/2009 127

Page 128: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Power

Energy

Energies are stored in big-endian format: the most significant word is transmitted first, the least significant

second.

Register Address R/W X Unit Type Range A/E A/P/H Description

12038 12037 R (3) kW UINT -

10000...+10000

E P/H Active power on phase 1: P1 (1) (2)

12039 12038 R (3) kW UINT -

10000...+10000

E P/H Active power on phase 2: P2 (1) (2)

12040 12039 R (3) kW UINT -

10000...+10000

E P/H Active power on phase 3: P3 (1) (2)

12041 12040 R (3) kW UINT -

30000...+30000

E P/H Total active power: Ptot (2)

12042 12041 R (3) kVAR UINT -

10000...+10000

E P/H Reactive power on phase 1: Q1 (1) (2)

12043 12042 R (3) kVAR UINT -

10000...+10000

E P/H Reactive power on phase 2: Q2(1) (2)

12044 12043 R (3) kVAR UINT -

10000...+10000

E P/H Reactive power on phase 3: Q3(1) (2)

12045 12044 R (3) kVAR UINT -

30000...+30000

E P/H Total reactive power: Qtot (2)

12046 12045 R (3) kVA UINT 0...10000 E P/H Apparent power on phase 1: S1 (1)

12047 12046 R (3) kVA UINT 0...10000 E P/H Apparent power on phase 2: S2 (1)

12048 12047 R (3) kVA UINT 0...10000 E P/H Apparent power on phase 3: S3 (1)

12049 12048 R (3) kVA UINT 0...30000 E P/H Total apparent power: Stot

(1) Value cannot be accessed for motor applications and in cases of 3-pole circuit breakers without external neutral

current transformer (ENCT).

(2) The sign for the active and reactive power depends on the Micrologic configuration.

(3) The scale factor depends on the type of Micrologic trip unit:

The scale factor is 10 for Compact NSX Micrologic 5.2, 5.3, 6.2, 6.3, 7.2 or 7.3 trip units.

The scale factor is 1 for Masterpact NT/NW and Compact NS Micrologic 5.0, 6.0 or 7.0 trip units.

Register Address R/W X Unit Type Range A/E A/P/H Description

12050

12051

12049

12050

R 1 kWh DINT -1 999 999 999

...+1 999 999 999

E P/H Active energy: Ep

12052

12053

12051

12052

R 1 kVARh DINT -1 999 999 999

...+1 999 999 999

E P/H Reactive energy: Eq

12054

12055

12053

12054

R 1 kWh UDINT 0...1 999 999 999 E P/H Active energy counted

positively: EpIn

12056

12057

12055

12056

R 1 kWh UDINT 0...1 999 999 999 E P/H Active energy counted

negatively: EpOut

12058

12059

12057

12058

R 1 kVARh UDINT 0...1 999 999 999 E P/H Reactive energy counted

positively: EqIn

12060

12061

12059

12060

R 1 kVARh UDINT 0...1 999 999 999 E P/H Reactive energy counted

negatively: EqOut

12062

12063

12061

12062

R 1 kVAh UDINT 0...1 999 999 999 E P/H Total apparent energy: Es

12064

12065

12063

12064

R 1 kWh UDINT 0...1 999 999 999 E — Active energy counted

positively (non-resettable):

EpIn

12066

12067

12065

12066

R 1 kWh UINT 0...1 999 999 999 E — Active energy counted

negatively (non-resettable):

EpOut

12068...

12079

12067...

12078

— — — — — — — Reserved

128 LV434107 09/2009

Page 129: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Current Demand Values

Power Demand Values

When the window is fixed type, this value is updated at the end of the window. For the sliding type, the

value is updated every 15 seconds.

Maximum Voltage Values

Register = 0 if the voltage < 25 V.

Register Address R/W X Unit Type Range A/E A/P/H Description

12080 12079 R 1 A UINT 0...20xIn E P/H Current demand value on phase 1: I1 Dmd

12081 12080 R 1 A UINT 0...20xIn E P/H Current demand value on phase 2: I2 Dmd

12082 12081 R 1 A UINT 0...20xIn E P/H Current demand value on phase 3: I3 Dmd

12083 12082 R 1 A UINT 0...20xIn E P/H Current demand value on the neutral:

IN Dmd (1)

(1) Value cannot be accessed for motor applications and in cases of 3-pole circuit breakers without external neutral

current transformer (ENCT).

Register Address R/W X Unit Type Range A/E A/P/H Description

12084 12083 R (1) kW UINT -30000...+30000 E P/H Demand value of the total active

power: Ptot Dmd

12085 12084 R (1) kVAR UINT -30000...+30000 E P/H Demand value of the total

reactive power: Qtot Dmd

12086 12085 R (1) kVA UINT 0...30000 E P/H Demand value of the total

apparent power: Stot Dmd

12087...

12089

12086...

12088

— — — — — — — Reserved

(1) The scale factor depends on the type of Micrologic trip unit:

The scale factor is 10 for Compact NSX Micrologic 5.2, 5.3, 6.2, 6.3, 7.2 or 7.3 trip units.

The scale factor is 1 for Masterpact NT/NW and Compact NS Micrologic 5.0, 6.0 or 7.0 trip units.

Register Address R/W X Unit Type Range A/E A/P/H Description

12090 12089 R 1 V UINT 0...850 E P/H Maximum rms phase-to-phase voltage V12

12091 12090 R 1 V UINT 0...850 E P/H Maximum rms phase-to-phase voltage V23

12092 12091 R 1 V UINT 0...850 E P/H Maximum rms phase-to-phase voltage V31

12093 12092 R 1 V UINT 0...850 E P/H Maximum rms phase-to-neutral voltage V1N (1)

12094 12093 R 1 V UINT 0...850 E P/H Maximum rms phase-to-neutral voltage V2N (1)

12095 12094 R 1 V UINT 0...850 E P/H Maximum rms phase-to-neutral voltage V3N (1)

(1) Value cannot be accessed for motor applications and in cases of 3-pole circuit breakers without external neutral

voltage transformer (ENVT).

LV434107 09/2009 129

Page 130: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Power Factor

The sign for the fundamental power factor (cosϕ) depends on the Micrologic configuration.

Total Harmonic Distortion (THD)

Miscellaneous

Register Address R/W X Unit Type Range A/E A/P/H Description

12096 12095 R (2) - INT (2) E P/H Power factor on phase 1: PF1 (1)

12097 12096 R (2) - INT (2) E P/H Power factor on phase 2: PF2 (1)

12098 12097 R (2) - INT (2) E P/H Power factor on phase 3: PF3 (1)

12099 12098 R (2) - INT (2) E P/H Total power factor: PF

12100 12099 R (2) - INT (2) E H Fundamental power factor on phase 1:

cosϕ1 (1)

12101 12100 R (2) - INT (2) E H Fundamental power factor on phase 2:

cosϕ2 (1)

12102 12101 R (2) - INT (2) E H Fundamental power factor on phase 3:

cosϕ3 (1)

12103 12102 R (2) - INT (2) E H Total fundamental power factor: cosϕ

(1) Value cannot be accessed for motor applications and in cases of 3-pole circuit breakers without external neutral

voltage transformer (ENVT).

(2) The scale factor and range depend on the type of Micrologic trip unit:

The scale factor is 100 and the range is -100...+100 for Compact NSX Micrologic 5.2, 5.3, 6.2, 6.3, 7.2 or 7.3 trip

units.

The scale factor is 1000 and the range is -1000...+1000 for Masterpact NT/NW and Compact NS Micrologic 5.0,

6.0 or 7.0 trip units.

Register Address R/W X Unit Type Range A/E A/P/H Description

12104 12103 R 10 % UINT 0...32766 E H Total harmonic distortion of V12

compared to the fundamental

12105 12104 R 10 % UINT 0...32766 E H Total harmonic distortion of V23

compared to the fundamental

12106 12105 R 10 % UINT 0...32766 E H Total harmonic distortion of V21

compared to the fundamental

12107 12106 R 10 % UINT 0...32766 E H Total harmonic distortion of V1N

compared to the fundamental

12108 12109 R 10 % UINT 0...32766 E H Total harmonic distortion of V2N

compared to the fundamental

12109 12108 R 10 % UINT 0...32766 E H Total harmonic distortion of V3N

compared to the fundamental

12110 12109 R 10 % UINT 0...32766 E H Total harmonic distortion of I1 compared

to the fundamental

12111 12110 R 10 % UINT 0...32766 E H Total harmonic distortion of I2 compared

to the fundamental

12112 12111 R 10 % UINT 0...32766 E H Total harmonic distortion of I3 compared

to the fundamental

(1) Value cannot be accessed for motor applications and in cases of 3-pole circuit breakers without external neutral

voltage transformer (ENVT).

Register Address RW X Unit Type Range A/E Description

12160 12159 R 1 — UINT 0...32766 A/E Trip counter

12161 12160 R 1 — UINT 0...32766 A/E Counter of alarms with priority level = 3 (high)

12162 12161 R 1 — UINT 0...32766 A/E Counter of alarms with priority level = 2 (medium)

12163 12162 R 1 — UINT 0...32766 A/E Counter of alarms with priority level = 1 (low)

130 LV434107 09/2009

Page 131: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Readout Examples

Readout Example of a Modbus Register

The table below shows how to read the rms current on phase 1 (I1) in register 12016.

The address of register 12016 equals 12016 - 1 = 12015 = 0x2EEF.

The Modbus address of the Modbus slave is 47 = 0x2F.

The content of register 12016 (address 12015) is 0x022B = 555.

The rms current on phase 1 (I1) is thus 555 A.

Readout Example of the Table of Common Registers

The table below shows how to read the table of common registers. This table starts at register 12000 and

consists of 113 registers.

The address of register 12000 equals 12000-1 = 11999 = 0x2EDF.

The table length is 113 registers = 0x71.

The number of bytes is 113x2 = 226 bytes = 0xE2.

The Modbus address of the slave is 47 = 0x2F.

Request from the Master Response from the Slave

Field name Example Field name Example

Modbus slave address 0x2F Modbus slave address 0x2F

Function code 0x03 Function code 0x03

Address of word to be read (MSB) 0x2E Data length in bytes 0x02

Address of word to be read (LSB) 0xEF Register value (MSB) 0x02

Number of registers (MSB) 0x00 Register value (LSB) 0x2B

Number of registers (LSB) 0x01 MSB CRC 0xXX

MSB CRC 0xXX LSB CRC 0xXX

LSB CRC 0xXX — —

Request from the Master Response from the Slave

Field name Example Field name Example

Modbus slave address 0x2F Modbus slave address 0x2F

Function code 0x03 Function code 0x03

Address of word to be read (MSB) 0x2E Data length in bytes 0xE2

Address of word to be read (LSB) 0xDF Value of register 12000 (MSB) 0xXX

Number of registers (MSB) 0x00 Value of register 12000 (LSB) 0xXX

Number of registers (LSB) 0x71 Value of register 12001 (MSB) 0xXX

MSB CRC 0xXX Value of register 12001 (LSB) 0xXX

LSB CRC 0xXX — 0xXX

— 0xXX

Value of register 12112 (MSB) 0xXX

Value of register 12112 (LSB) 0xXX

MSB CRC 0xXX

LSB CRC 0xXX

LV434107 09/2009 131

Page 132: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Modbus Communication Interface Module Data

Communication Test

Introduction

We recommend you use the RCU (Remote Control Utility) to test communication on the various circuit

breakers. You can download the RCU software from our website at www.schneider-electric.com.

Presentation of the RCU Software

The RCU (Remote Control Utility) is simple SCADA software designed for:

Compact NSX circuit breakers

Masterpact circuit breakers

Power Meters

The RCU software allows users to monitor and control their equipment and helps installers to check and

validate newly installed equipment.

Depending on which device the RCU software is connected to, it allows the user to:

Display the I, U, E, THD measurements

Display the date and time

Display the device identification and maintenance data

Control the device (for circuit breakers only)

Save the P, FP, E measurements every 5 minutes

132 LV434107 09/2009

Page 133: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

LV434107 09/2009

Appendices

LV434107 09/2009 133

Page 134: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

134 LV434107 09/2009

Page 135: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

LV434107 09/2009

A

Cross References to Modbus Registers

LV434107 09/2009

Cross references to Modbus Registers

Cross References to Modbus Registers

General Description

The following table gives cross references to the Modbus registers used by the communication modules.

The registers are listed in ascending order.

Cross References Table

Register Address Module Variable Page

551 550 BSCM Square D identification 101

552...557 551...556 BSCM Serial number 101

563 562 BSCM Circuit breaker status 102

564 563 BSCM Communicating motor mechanism status 102

571...582 570...581 BSCM BSCM counters 103

602...652 601...651 BSCM BSCM event counter and BSCM events 104

1000...1015 999...1014 Micrologic trip unit Voltage and voltage unbalance (real-time

measurements)

43

1016...1032 1015...1031 Micrologic trip unit Current and current unbalance (real-time

measurements)

44

1034...1045 1033...1044 Micrologic trip unit Power (active power, reactive power with harmonic,

apparent power) (real-time measurements)

44

1046...1053 1045...1052 Micrologic trip unit Power factor and fundamental power factor

(real-time measurements)

45

1054 1053 Micrologic trip unit Frequency (real-time measurement) 45

1080...1091 1079...1090 Micrologic trip unit Fundamental reactive power and distortion power

(real-time measurements)

45

1092...1100 1091...1099 Micrologic trip unit Total harmonic distortion (real-time measurement) 46

1144 1143 Micrologic trip unit Thermal image of motor (real-time measurement) 46

1145 1144 Micrologic trip unit Vmax: maximum of V12, V23, and V3 (real-time

measurement)

43

1146 1145 Micrologic trip unit Vmin: minimum of V12, V23, and V31 (real-time

measurement)

43

1300...1315 1299...1314 Micrologic trip unit Voltage (minimum of real-time measurement) 47

1316...1332 1315...1331 Micrologic trip unit Current (minimum of real-time measurement) 47

1334...1345 1333...1344 Micrologic trip unit Power (active power, reactive power with harmonic,

apparent power) (minimum of real-time

measurement)

47

1346...1353 1345...1352 Micrologic trip unit Power factor (minimum of real-time measurement) 47

1354 1353 Micrologic trip unit Frequency (minimum of real-time measurement) 47

1380...1391 1379...1390 Micrologic trip unit Fundamental reactive power and distortion power

(minimum of real-time measurements)

47

1392...1411 1391...1410 Micrologic trip unit Total harmonic distortion (minimum of real-time

measurement)

47

1444 1443 Micrologic trip unit Thermal image of motor (minimum of real-time

measurement)

47

1600...1615 1599...1614 Micrologic trip unit Voltage (maximum of real-time measurement) 47

1616...1632 1615...1631 Micrologic trip unit Current (maximum of real-time measurement) 47

135

Page 136: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Cross References to Modbus Registers

1634...1645 1633...1644 Micrologic trip unit Power (active power, reactive power with harmonic,

apparent power) (maximum of real-time

measurement)

47

1646...1653 1645...1652 Micrologic trip unit Power factor (maximum of real-time measurement) 47

1654 1653 Micrologic trip unit Frequency (maximum of real-time measurement) 47

1680...1691 1679...1690 Micrologic trip unit Fundamental reactive power and distortion power

(maximum of real-time measurements)

47

1692...1711 1691...1710 Micrologic trip unit Total harmonic distortion (maximum of real-time

measurement)

47

1744 1743 Micrologic trip unit Thermal image of motor (maximum of real-time

measurement)

47

2000...2031 1999...2030 Micrologic trip unit Energy 48

2200...2237 2199...2236 Micrologic trip unit Demand 49

2242...2243 2241...2242 Micrologic trip unit Quadrant total 72

2900...2929 2899...2928 Micrologic trip unit Minimum/maximum measurements reset time 50

3000...3002 2999...3001 Micrologic trip unit Current date 84

3314 3313 Micrologic trip unit System type 72

3316 3315 Micrologic trip unit Power flow sign 72

3318 3317 Micrologic trip unit Power factor sign 72

3324 3323 Micrologic trip unit Energy accumulation mode 73

3352...3355 3351...3354 Micrologic trip unit Demand time 73

5704 5703 Micrologic trip unit Alarm status register 53

5732...5781 5731...5780 Micrologic trip unit Alarm history 55

6650...6679 6649...6678 Micrologic trip unit Pre-alarms 61

6770...6889 6769...6888 Micrologic trip unit User-defined alarms 63

8000...8149 7999...8148 Micrologic trip unit Command interface 29

8700...8705 8699...8704 Micrologic trip unit Serial number 51

8709 8708 Micrologic trip unit Hardware version 51

8716 8715 Micrologic trip unit Square D identification 51

8740 8739 Micrologic trip unit Protection type 51

8741 8740 Micrologic trip unit Metering type (A, E) 51

8747 8746 Micrologic trip unit Application (distribution, motor) 51

8748 8747 Micrologic trip unit Standard (IEC, UL) 52

8750 8749 Micrologic trip unit Nominal current 52

8751 8750 Micrologic trip unit Pole 52

8752 8751 Micrologic trip unit 16 Hz 2/3 52

8754...8763 8753...8762 Micrologic trip unit Long time protection 67

8764...8773 8763...8772 Micrologic trip unit Short time protection 67

8774...8783 8773...8782 Micrologic trip unit Instantaneous protection 68

8784...8793 8783...8792 Micrologic trip unit Ground fault protection 68

8794...8803 8793...8802 Micrologic trip unit Earth leakage (Vigi) protection 69

8851 8850 Micrologic trip unit Temperature 84

8857 8856 Micrologic trip unit SDx module status 53

8865 8864 Micrologic trip unit Time remaining until long time tripping 84

8872 8871 Micrologic trip unit Phase rotation 84

8900...8903 8899...8902 Micrologic trip unit Jam protection 69

8904...8907 8903...8906 Micrologic trip unit Unbalance protection 69

8908...8911 8907...8910 Micrologic trip unit Underload protection 69

8912...8915 8911...8914 Micrologic trip unit Longstart protection 70

8916...8919 8915...8918 Micrologic trip unit Neutral protection 70

8930 8929 Micrologic trip unit Thermal memory inhibit parameter 70

9100...9218 9099...9217 Micrologic trip unit Trip history 57

Register Address Module Variable Page

136 LV434107 09/2009

Page 137: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Cross References to Modbus Registers

9616 9615 Micrologic trip unit Nominal voltage Vn 73

9801...9810 9800...9809 Micrologic trip unit Configuration of the SDx module outputs 71

10000 9999 Micrologic trip unit Trip status register 54

11776...11782 11775...11781 Modbus communi-

cation interface

Firmware version 113

11784...11789 11783...11788 Modbus communi-

cation interface

Serial number 113

11801...11823 11800...11822 Modbus communi-

cation interface

IMU name 114

11846...11868 11845...11867 Modbus communi-

cation interface

IMU location 114

11891 11890 Modbus communi-

cation interface

Modbus locking pad position 114

11901 11900 Modbus communi-

cation interface

Square D identification 113

11903...11906 11902...11905 Modbus communi-

cation interface

Hardware version 113

12000...12163 11999...12162 Modbus communi-

cation interface

Communication profile

12399 12398 Modbus communi-

cation interface

Auto-Speed sensing state 114

12400 12399 Modbus communi-

cation interface

Modbus address 114

12401 12400 Modbus communi-

cation interface

Modbus parity 114

12402 12401 Modbus communi-

cation interface

Modbus baudrate 114

12403 12402 Modbus communi-

cation interface

Number of stop bits 114

29390 29389 Micrologic trip unit Failure status 84

29500...29549 29499...29548 Micrologic trip unit Maintenance operation history 59

29600...29699 29599...29698 Micrologic trip unit Previous protection settings 74

29780...29819 29779...29818 Micrologic trip unit Time-stamped minimum/maximum measurements 77

29820...29827 29819...29826 Micrologic trip unit Time-stamped minimum/maximum network

frequency

79

29851...29852 29850...29851 Micrologic trip unit Time of use counter 81

29853 29852 Micrologic trip unit Rate of wear counter 81

298534 29853 Micrologic trip unit Boot counter 81

29855...29856 29854...29855 Micrologic trip unit EEPROM writing counter 81

29880...29887 29879...29886 Micrologic trip unit Load profile counters 81

29890...29901 29889...29900 Micrologic trip unit Temperature profile counters 82

29910...29918 29909...29907 Micrologic trip unit Protection trips counters 82

29940...29952 29939...29951 Micrologic trip unit Alarms counters 83

29980...29986 29979...29985 Micrologic trip unit Maintenance operations counters 83

29990...29991 29989...29990 Micrologic trip unit Rotary switches positions 85

29992 29991 Micrologic trip unit Locking pad status 85

29993 29992 Micrologic trip unit Auxiliary 24 V power supply 85

29994...29998 29993...29997 Micrologic trip unit Firmware version 52

30000...30003 29999...30002 Micrologic trip unit Part number 52

30005 30004 Micrologic trip unit Micrologic trip unit LED 85

Register Address Module Variable Page

LV434107 09/2009 137

Page 138: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Cross References to Modbus Registers

138 LV434107 09/2009

Page 139: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to
Page 140: User manual 09/2009 - studiecd.dkstudiecd.dk/pdfs/all/lv434107_Modbus_User_Manual.pdf · LV434107 09/2009 7 About the Book At a Glance Document Scope The aim of this manual is to

Schneider Electric Industries SAS35, rue Joseph MonierCS 30323F - 92506 Rueil-Malmaison CedexRCS Nanterre 954 503 439Capital social 896 313 776 €www.schneider-electric.com

As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.