Used for shower Safety Shower

8
INSTRUCTIONS FOR MODELS 92-SE-6XX-01 For additional assistance or service please contact: SPEAKMAN ® Company 400 Anchor Mill Road New Castle, DE 19720 800-537-2107 [email protected] www.speakman.com Used for Safety Shower combination stations: SE-603 SE-616 SE-690 SE-693 SE-695 SE-697 TOOLS AND SUPPLIES IMPORTANT MAINTENANCE The valve and the eye/face wash are the only portion of the unit that may require maintenance. Should you need parts to repair this unit, please contact Speakman. Reference additional technical sheets (supplied) for information on the eye/face wash, bowl assembly, shower head, and shower activation valve. Before any maintenance is done be sure to shut the water supply off. WARNING: Use only genuine Speakman parts when repairing or replacing components. To order parts call 1-800-537-2107. ANSI Z358.1 specifies that the height of the spray heads is to be between 33” - 53” from the floor. Use Thread Locker or Sealant on all threaded connections. Be sure the Unit is level and plum. Pipe Wrench Adjustable Wrench Strap Wrench Hex Key Wrench Not Included Level OPERATION SAFETY TIPS Cover your drain to prevent loss of parts. Be sure to wear eye protection while cutting pipe. WARRANTY Additional warranty information can be found at: www.speakman.com SHOWER OPERATION The shower is activated by pulling the triangle pull handle. Once the valve is activated the head will continue to discharge water until the ring is released. EYE/FACE WASH OPERATION The eye/face wash is activated by pushing the push handle back 90°. The unit will operate until the push handle is manually pulled back up to the off position. TESTING PROGRAM ANSI/ISEA Z358.1 states that all safety emergency equipment shall be activated on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag (91-0635) with each unit. On this tag the date of inspection and the inspector’s initials should be noted. 1 Front of Unit 1/2” Male Threading At desired location, mount Floor Flange (13) on a flat, level surface using suitable anchors, making sure that one of the three ears on the Floor Flange is positioned at what will be the front of the Stanchion. The Unit should be placed so that there is sufficient unobstructed area around the Stanchion. Assemble 1-1/4” x 29-3/8” Pipe (11) to Floor Flange (13). Thread 1-1/4” x 1/2” Drain/Supply Cross (12) onto Pipe (11). Side Outlets should face the front and back of the Unit, and the 1/2” male threaded outlet upward at 45° to the right side of the Unit.

Transcript of Used for shower Safety Shower

Page 1: Used for shower Safety Shower

INSTRUCTIONS FOR MODELS

92-SE-6XX-01

For additional assistance or service please contact:

SPEAKMAN® Company400 Anchor Mill RoadNew Castle, DE 19720

800-537-2107

[email protected]

www.speakman.com

Used forSafety Showercombinationstations:SE-603SE-616SE-690SE-693SE-695SE-697

TOOLS AND SUPPLIES

IMPORTANT

MAINTENANCEThe valve and the eye/face wash are the only portion of the unit that may require maintenance. Shouldyou need parts to repair this unit, please contact Speakman. Reference additional technical sheets (supplied) for information on the eye/face wash, bowl assembly, shower head, and shower activation valve. Before any maintenance is done be sure to shut the water supply off.

WARNING: Use only genuine Speakman parts when repairing or replacing components.To order parts call 1-800-537-2107.

ANSI Z358.1 specifies that the height of the spray heads is to be between 33” - 53” from the floor. Use Thread Locker or Sealant on all threaded connections. Be sure the Unit is level and plum.

PipeWrench

AdjustableWrench

StrapWrench

Hex KeyWrench

NotIncluded

Level

OPERATION

SAFETY TIPS

Cover your drain to prevent loss of parts. Be sure to wear eye protection while cutting pipe.

WARRANTYAdditional warranty information can be found at: www.speakman.com

SHOWER OPERATIONThe shower is activated by pulling the triangle pull handle. Once the valve is activated the head will continue to discharge water until the ring is released.

EYE/FACE WASH OPERATIONThe eye/face wash is activated by pushing the push handle back 90°. The unit will operate until the push handle is manually pulled back up to the off position.

TESTING PROGRAMANSI/ISEA Z358.1 states that all safety emergency equipment shall be activated on a weekly basis to flush the line and verify proper operation. Speakman Company furnishes a testing record tag (91-0635) with each unit. On this tag the date of inspection and the inspector’s initials should be noted.

1

Front of Unit1/2” MaleThreading

• At desired location, mount Floor Flange(13) on a flat, level surface using suitable anchors, making sure that one of the three ears on the Floor Flange is positioned at what will be the front of the Stanchion.

• The Unit should be placed so that thereis sufficient unobstructed area aroundthe Stanchion.

• Assemble 1-1/4” x 29-3/8” Pipe (11)to Floor Flange (13).

• Thread 1-1/4” x 1/2” Drain/SupplyCross (12) onto Pipe (11). Side Outletsshould face the front and back of the Unit,and the 1/2” male threaded outlet upwardat 45° to the right side of the Unit.

Page 2: Used for shower Safety Shower

2 • Assemble 1-1/4” x 29-3/8” Pipe (11) to Drain/Supply Cross (12). Assemble

1-1/4” Tee (10) to Pipe (11).

• Assure the Side Outlet portion of Tee (10)is facing the rear of the Unit.

Rear of Unit

Front of Unit

3 • If water supply is coming from above Unit,install Plug (7) into side outlet of Tee (10).

• If water supply is coming from behindUnit, install Plug (7) into top outlet of Tee (10).

Front of Unit

For Back Supply,install Plug(7) here.

For Top Supply,install Plug(7) here.

4 • Assemble 1” x 4-1/2” Pipe (6) into Side Outlet of Tee (8). Review View 4a belowto understand the orientation of BallValve (5).

• Assemble 1” Ball Valve (5) onto Pipe (6). Valve Stops must be aligned correctly in order for the Pull Handle to operate properly.

Detail View 4a

To Showerhead

Valve Stops

To Showerhead

5 • Install Pipe (2) into Ball Valve (5).

• Assemble Elbow (1) to Pipe (2) being sure to orient Elbow (1) so that the outlet is facing down.

• Assemble Showerhead (14) to Elbow (1).

Page 3: Used for shower Safety Shower

6 • Assemble the Lever Handle Assembly (16)to Ball Valve (5) using Nylo-Hex Nut (17),being sure to orient the Handle as shownbelow.

• Insert the slot in the Pull Rod (20) over the Lever Handle Assembly (16) and insert Pin (18).

• Secure Pin (18) with Cotter Pin (19).

7 • Assemble 1-1/4” x 6“ Pipe (21) to Drain/Supply Cross (12).

• Install Street Elbow (22), making surethe male threading is plum.

• Assemble the 1-1/4” Bowl Mounting Spud (23) to Street Elbow (22), making sure the top surface is level.

BOWL GROUP AND EYE/FACE WASH REFERENCE

• SE-603 Series Includes SE-400 Eye/Face Wash Unit with Aerated Sprays and Stainless Steel Bowl

• SE-616 Series Includes SE-505 Eyewash Unit with Aerated Sprays and Stainless Steel Bowl

• SE-690 Series Includes SE-490 Eye/Face Wash Unit with Soft Flow Sprays and Stainless Steel Bowl

• SE-693 Series Includes SE-582 Eyewash Unit with Aerated Sprays and Stainless Steel Bowl

• SE-695 Series Includes SE-495 Eye/Face Wash Unit with Soft Flow Sprays and Plastic Bowl

• SE-697 Series Includes SE-580 Eyewash Unit with Aerated Sprays and Plastic Bowl

8 • Assemble Eyewash Assembly (24) by aligning the Strainer Drain thread on the Eyewash with the Bowl Mounting Spud (23) on Stanchion.

• Secure Eyewash by tightening StrainerDrain with a 7/16” Allen Wrench, makingsure the Eyewash Assembly (24) is level once fully tightened.

Note: Your Bowl and Eyewash appearance may vary depending on model. Image shownis for reference only. Install Bowl group as described. Reference additional technical sheets (supplied) for information on the bowl assembly. Before any maintenance is done be sure to shut the water supply off.

Page 4: Used for shower Safety Shower

9 • Assemble male end of Flex Hose (15) toBall Valve (27) (Detail View 9a).

• Assemble female end of Flex Hose (15) to Drain/Supply Cross (12) (Detail View 9b).

• Install Paddle Handle (25) to Ball Valve (27) using Nylo-Hex Nut (26) (Detail View 9c).

Detail View 9a

Detail View 9b

Detail View 9c

10 • Connect an uninterruptible potable water supply with a minimum of 30psi flowing pressure to Water Inlet (8) (10). Failureto use potable water can result in furtherinjury.

• Connect an adequate drain to Drain Outlet (12) that complies with all local plumbing codes.

• Turn on water supply and check connections for leaks.

• To test the Eye/Face Wash, and forsubsequent operation, push the Paddle Handle forward 90°. The unit will operateuntil the Paddle Handle is manually pulledback to the OFF position.

• To test the Shower, and for subsequentoperation, pull the Pull Rod down. Theunit will operate until the Pull Rod is manually pushed back to the OFF position.

StandardWaterInlet

AlternateWaterInlet

Drain Outlet

Page 5: Used for shower Safety Shower

SE-603 / 616 / 690 / 693 / 695 / 697 EXPLODED VIEW AND REPAIR PARTS

REPAIR PARTS

SPEAKMAN®

SE-911 1” BALL VALVE

SE-911-SS 1” STAINLESS STEEL BALL VALVE

SE-810 8” PLASTIC SHOWERHEAD

RPG63-0095 STAINLESS STEEL SUPPLY HOSE

RPG47-0046 PULL ROD

ITEM NO. PART NO. DESCRIPTION

1" X 90° GALV. STREET ELBOW

1" X 17-5/8" GALV. PIPE, TBE

1" CHROME PLATED BRASS BALL VALVE

1" X 4-1/2" GALV. PIPE, TBE

1-1/4" GALV. PLUG

1-1/4" X 1-1/4" X 1" GALV. TEE

1-1/4" X 22-1/4" LG. PIPE, TBE

ITEM NO. DESCRIPTION

1-1/4" GALV. TEE

1-1/4" X 29-3/8" LG. GALV. PIPE, TBE

1-1/4" X 1/2" GALV. DRAIN/SUPPLY CROSS

1-1/4" GALV. FLOOR FLANGE

8" DELUGE SHOWERHEAD

STAINLESS STEEL FLEXIBLE SUPPLY HOSE

LEVER HANDLE ASSEMBLY WITH SPRING PLUNGER

7/16-20 UNF STAINLESS STEEL NYLO-HEX NUT

CLEVIS PIN

COTTER PIN

29" ALUMINUM PULL ROD

1-1/4" X 6" LG. GALV. PIPE, TBE

1-1/4" GALV. STREET ELBOW

1-1/4" GALV. BOWL MOUNTING SPUD

SE-616 STAINLESS STEEL BOWL / SE-505 (AERATED) EYEWASH

SE-603 STAINLESS STEEL BOWL / SE-400 (AERATED) EYE/FACE WASH

BOWL AND EYEWASH UNIT COMBINATIONS

SE-690 STAINLESS STEEL BOWL / SE-490 (SOFT FLOW) EYE/FACE WASH

SE-693 STAINLESS STEEL BOWL / SE-582 (AERATED) EYEWASH

SE-695 PLASTIC BOWL / SE-495 (SOFT FLOW) EYE/FACE WASH

SE-697 PLASTIC BOWL / SE-580 (AERATED) EYEWASH

PADDLE HANDLE

3/8" STAINLESS STEEL NYLO-HEX NUT

1/2" CHROME PLATED BRASS BALL VALVE

Note: Bowl and Eyewash unit combinations. Please refer to the respective IOM for repair part information.

Page 6: Used for shower Safety Shower

SE-603 ROUGH-IN DIAGRAMS SPEAKMAN®

DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE: ALL UNITS MEET EXISTING ANSI/ISEA Z358.1 STANDARDS. PRODUCT IMPROVEMENTS MAY CAUSE SPECIFICATION AND DIMENSIONAL CHANGES WITHOUT NOTICE.

22 2132 "± 3

16 "

576mm±5

13 38 "± 3

16 "

339mm±5

44 1116 "± 1

2 "

1135mm±13

91 11/16"±1"2330mm±25

7 78 "

200mm

8 116 "± 3

16 "

205mm±5

232 "

1041mm±13

"± 1 40 31

62 1116 "±1"

1592mm±25

1-1/4" NPTFEMALE INLET

FEMALE OUTLET1-1/4" NPT

1-1/4" NPTFEMALE INLET

16 "± 38

138 "

225mm±10

"83

209mm±10

"±328

"4326"±

660mm±19

7

14 2132 "± 3

8 "

373mm±10

31"± 3

84"±1"2134mm±25

"8565"±

1651mm±16

"± "8814mm±10

3

"32

16

5

55mm

2

787mm±10

"8 32 1

33"± 58 "

838mm±16

FLOOR FLANGEDETAIL

1732 "

13mm(TYP.) 3 PLACED

EQUALLY SPACED120° APART

PRESSURE FLOW RATE

psi bar

30 2.07

90 4.14

SE-603SHOWER FLOW DATA

gpm L/min

20 75

25 94

PRESSURE FLOW RATE

psi bar

30 2.07

SE-603 EYE/FACEWASH FLOW DATA

gpm L/min

9.55 36.6

Page 7: Used for shower Safety Shower

SE-616 ROUGH-IN DIAGRAMS SPEAKMAN®

DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE.

NOTE: ALL UNITS MEET EXISTING ANSI/ISEA Z358.1 STANDARDS. PRODUCT IMPROVEMENTS MAY CAUSE SPECIFICATION AND DIMENSIONAL CHANGES WITHOUT NOTICE.

26"± 34 "

660mm±19

91 11/16"±1"2330mm±25.40

7 78 "

200mm

1-1/4" NPTFEMALE OUTLET

FEMALE INLET1-1/4" NPT

1-1/4" NPTFEMALE INLET

7 "± "88

208.99mm±9.53

332

3"±

224.61mm±9.53816 "138

12 12 "± 3

8 "

317.88mm±9.53

787.04mm±9.53

331"±1

55.12mm

8

1109.52mm±12.7021"±

"±"

32

2134mm±25

814mm±10

3

16

8 "

"

16

8 "65"± 5

1651mm±16

532 " 2

84"±1"

43 11

33"± 58 "

838.07mm±15.88

16"± "3 34

145.87mm±4.76

5

7 316 "± 3

16 "

182.70mm±4.76

62 "±1"1611

1592mm±25

140"±

1016mm±13

"2

13 2532 "± 3

16 "

350.39mm±4.76

FLOOR FLANGEDETAIL

1732 "

13mm(TYP.) 3 PLACES

EQUALLY SPACED120° APART

PRESSURE FLOW RATE

psi bar

30 2.07

60 4.14

SE-616SHOWER FLOW DATA

gpm L/min

20 75

25 94

PRESSURE FLOW RATE

psi bar

30 2.07

SE-616 EYEWASH FLOW DATA

gpm L/min

3 11.0

Page 8: Used for shower Safety Shower

SE-690 / SE-693 / SE-695 / SE-697 ROUGH-IN DIAGRAMS SPEAKMAN®

DIMENSIONS SUBJECT TO CHANGE WITHOUT NOTICE.

1732 "

13mm(TYP. 3 PLACES EQUALLY

SPACED 120º APART)7 7

8 "

200mm

FLOOR FLANGEDETAIL

PRESSURE FLOW RATE

psi bar

30 2.07

60 4.14

SE-690/693/695/697 SHOWER FLOW DATA

gpm L/min

20 75

25 94

PRESSURE FLOW RATE

psi bar

30 2.07

SE-690/695 EYE/FACEWASH FLOW DATA

gpm L/min

4.5 17.0

PRESSURE FLOW RATE

psi bar

30 2.07

SE-693/697 EYEWASH FLOW DATA

gpm L/min

3.2 14.5

NOTE: ALL UNITS MEET EXISTING Z358.1 STANDARDS. PRODUCT IMPROVEMENTS MAY CAUSE SPECIFICATION AND DIMENSIONAL CHANGES WITHOUT NOTICE.

31"± 38 "

787mm±10

84"±1"2133mm±25

91 1116 "±1"

2329mm±25