Use of Hydro test (G-10)

36
1 Use of Hydro Test PRESENTED BY: HARDISH TRIVEDI

Transcript of Use of Hydro test (G-10)

Page 1: Use of Hydro test (G-10)

1

Use of Hydro Test

PRESENTED BY: HARDISH TRIVEDI

Page 2: Use of Hydro test (G-10)

3

Tests Destructive Tests

Tensile, Impact, Bend,etc

Non-destructive Tests

Radiography,

Ultrasonic,

Dye-penetration,

Magnetic Particle

and leak testing like

Hydrotest, Air Test, Helium Test etc.. PRESENTED BY: HARDISH

TRIVEDI

Page 3: Use of Hydro test (G-10)

4

Hydrotest-------why?

Recommended For pressure vessel operatingunder pressure

Ensures the strength of weld joints &materials

Ensures nozzle-flange joint

Test The strength of The pressure vessel at1.5 times the designed pressure

Ensures safe & reliable performance duringthe operational life

To ensure the integrity of the vessel and system operation under pressure.

PRESENTED BY: HARDISH TRIVEDI

Page 4: Use of Hydro test (G-10)

5

Requirements Of Materials , Tools & Equipments

TEST MEDIUM • WATER WITH ‘X’ PPM AS FREELY AVAILABLE• (PARTS PER MILLION---CHLORINE IMPURITIES)

• ‘X’ ---- 25 PPM OR LESS FOR SS VESSEL• ‘X’ ---- 80 PPM OR LESS FOR CS VESSEL

• CHLORINE PARTICLES AFFECT THE ANTICORROSIVE PROPERTIES OF VESSEL

PRESENTED BY: HARDISH TRIVEDI

Page 5: Use of Hydro test (G-10)

6

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

WOODEN SADDLES (SOFT WOOD)• TO SUPPORT THE VESSEL & AVOID ANY

DEFORMATION OR DENT AT CONTACT SURFACES

• CONTACT ANGLE---120 DEGREES

1200

Vessel

Wooden saddle PRESENTED BY: HARDISH

TRIVEDI

Page 6: Use of Hydro test (G-10)

7

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

THERMOCOL SHEETS

• 20--30 MM THICKNESS• USED AS A SOFT PACKING BETWEEN VESSEL &

SADDLE

PRESENTED BY: HARDISH TRIVEDI

Page 7: Use of Hydro test (G-10)

8

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

COVER FLANGES

• NOZZLES WHICH HAVE ORIGINAL BLIND FLANGES TO BE BLANKED BY THOSE FLANGES

• OTHER NOZZLES TO BE BLANKED AS PER SPECIFIED DRAWING

PRESENTED BY: HARDISH TRIVEDI

Page 8: Use of Hydro test (G-10)

9

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

HIGH TENSILE FASTNERS

• TO BE USED AS SPECIFIED IN THE DRAWING

PRESENTED BY: HARDISH TRIVEDI

Page 9: Use of Hydro test (G-10)

10

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

PIPE FITTING

• HIGH PRESSURE (5000 TO 10000 PSI)• REQUIRED SIZES (BSP,NPT) TO BE USED FOR

INLET & OUTLET EQUIPMENT, VALVES, GAUGES CONNECTIONS

PRESENTED BY: HARDISH TRIVEDI

Page 10: Use of Hydro test (G-10)

11

PUMP ACCESSORIES

• SQUARE BAR

• SHUT OFF VALVE

• COUPLER

• FLOW DIRECTION

PRESENTED BY: HARDISH TRIVEDI

Page 11: Use of Hydro test (G-10)

12

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

GASKETS

• TO BE USED JOB GASKET UNLESS OTHERWISE SPECIFIED

PRESENTED BY: HARDISH TRIVEDI

Page 12: Use of Hydro test (G-10)

13

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

PRESSURE GAUGES

• USE MINIMUM TWO CALIBRATED PRESSURE GAUGES

• RANGE--- MIN. 1.5 TIMES THE TEST PRESSURE MAX. 4 TIMES THE TEST PRESSURE

• EXAMPLE: FOR TEST PRESSURE OF 60 KG/CM2 RANGE SHOULD BE 0-100 KG/CM2

(OR) 0-240 KG/CM2

PRESENTED BY: HARDISH TRIVEDI

Page 13: Use of Hydro test (G-10)

14

• SQUARE BAR

• SHUT OFF VALVE

• COUPLER

• PRESSURE GAUGE

PUMP ACCESSORIES

PRESENTED BY: HARDISH TRIVEDI

Page 14: Use of Hydro test (G-10)

15

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

WATERPUMP & HOSE ASSEMBLIES

• SUBMERSSIBLE OR ANY OTHER PUMP IS USED FOR FILLING THE VESSEL

• CONNECTED THROUGH FLEXIBLE HOSE PIPES TO TANK & VESSEL

PRESENTED BY: HARDISH TRIVEDI

Page 15: Use of Hydro test (G-10)

16

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

HYDROTEST PUMP• REQUIRED FOR PRESSURIZING THE VESSEL TO

THE TEST PRESSURE• COMPRISES OF

A HIGH PRESSURE PUMP

B NON-RETURN VALVE

C RELIEF VALVES

D ATTACHMENTS LIKE HOSES, COUPLERS

PRESENTED BY: HARDISH TRIVEDI

Page 16: Use of Hydro test (G-10)

17

PUMP ACCESSORIES

• PRESSURE GAUGE

• SUBMISSILE

PUMP

• OUTLET HOSE

PRESENTED BY: HARDISH TRIVEDI

Page 17: Use of Hydro test (G-10)

18

REQUIREMENTS OF MATERIALS , TOOLS & EQUIPMENTS-(CONTD.)

TORQUE WRENCH, GUN & STUD TENSIONER

• ALL THE OPENINGS MUST BE CLOSED WITH BLIND FLANGES

• TIGHTENING TO BE ENSURED AT DESIRED TORQUE BY TORQUING WRENCH, TORQUING GUN OR STUD TENSIONER

PRESENTED BY: HARDISH TRIVEDI

Page 18: Use of Hydro test (G-10)

19

TYPES OF HYDROTEST PUMP

• HIGH DISCHARGE LOW PRESSURE

PRESSURE RANGE : UP TO 100 KG/SQ.CM(g)

QTY. : 02

• LOW DISCHARGE HIGH PRESSURE

PRESSURE RANGE : UP TO 400 KG/SQ.CM(g)

QTY. : 06

PRESENTED BY: HARDISH TRIVEDI

Page 19: Use of Hydro test (G-10)

20

HYDROTEST PUMP DETAILS(HIGH PRESSURE, LOW DISCHARGE)

• INLET HOSE• TANK

• TROLLEY

• OUTLET HOSE

PRESENTED BY: HARDISH TRIVEDI

Page 20: Use of Hydro test (G-10)

21PRESENTED BY: HARDISH TRIVEDI

Page 21: Use of Hydro test (G-10)

22

SEQUENCE OF OPERATIONS

SADDLE ARRANGEMENT• REQUIRED NO. OF SADDLES AS

MENTIONED ON DRG. TO BE PLACED AT THE DISTANCES

• PUT THERMOCOL SHEETS ON SADDLES BEFORE KEEPING THE VESSEL

PRESENTED BY: HARDISH TRIVEDI

Page 22: Use of Hydro test (G-10)

23

SEQUENCE OF OPERATIONS (CONTD.)

ORIENTATION• LONGSEAM, CIRCSEAM REMAIN

EXPOSED FOR VISUAL INSPECTION & NOT COVERED UNDER SADDLE

• INLET NOZZLE FOR WATER IS AT THE TOP & DRAIN OUT AT THE BOTTOM OF VESSEL

PRESENTED BY: HARDISH TRIVEDI

Page 23: Use of Hydro test (G-10)

24

SEQUENCE OF OPERATIONS (CONTD.)

AIR LOCK REMOVAL• ADEQUATE ARRANGEMENT TO BE MADE

FOR VENTING THE AIR, TRAPPED INSIDE THE VESSEL

• FOUR DIFFERENT CASES TO BE STUDIED

PRESENTED BY: HARDISH TRIVEDI

Page 24: Use of Hydro test (G-10)

25

AIR LOCK REMOVAL

1 VESSEL IN HORIZONTAL, INCLINED AT 5 DEG.

PRESENTED BY: HARDISH TRIVEDI

Page 25: Use of Hydro test (G-10)

26

AIR LOCK REMOVAL2. WHEN INTERNALS LIKE TSRs PROVIDED INSIDE THE VESSEL

VESSEL

SADDLE NOZZLE

D/E

PRESENTED BY: HARDISH TRIVEDI

Page 26: Use of Hydro test (G-10)

27

AIR LOCK REMOVAL

3 FOR HORIZONTAL NOZZLE INSIDE THE D/E

PRESENTED BY: HARDISH TRIVEDI

Page 27: Use of Hydro test (G-10)

28

AIR LOCK REMOVAL

PRESENTED BY: HARDISH TRIVEDI

Page 28: Use of Hydro test (G-10)

29

TIGHTENING SEQUENCE

Bitmap Image

1

2

34

5

6 7

8

PRESENTED BY: HARDISH TRIVEDI

Page 29: Use of Hydro test (G-10)

30

PRESSURE VALVE SETTING

• VALVE SETTING FOR REQUIRED PRESSURE

PRESENTED BY: HARDISH TRIVEDI

Page 30: Use of Hydro test (G-10)

31

GUIDELINES FOR HYDROTEST• Pump shaft should rotate clock wise looking

from shaft side

• Ensure bypass line is open.

• Ensure that bypass line should not connect to the pump suction line.

(If discharge line is shut off, bypass water is diverted to the pump suction & as a result there is a rapid rise in temperature , which causes damage to piston plunger packing)

PRESENTED BY: HARDISH TRIVEDI

Page 31: Use of Hydro test (G-10)

32

• Connect pump outlet to vessel inlet through

standard hose pipe, with proper valve connections, square bar, couplers, etc.

• Ensure the pressure regulator valve,foot valve,should be in unloading position.

• Ensure the pressure gauge calibration validity

• Ensure water tank or suction line should be free from any foreign material

PRESENTED BY: HARDISH TRIVEDI

Page 32: Use of Hydro test (G-10)

33

• Start hydrotest pump

• Ensure 100% removal of entrapped air

( monitor the tank into which the outlet hose pipe is dipped. As soon as bubbles stop showing up, close outlet valve)

• Monitor pressure gauge provided at outlet.

OPERATING PROCEDURES

PRESENTED BY: HARDISH TRIVEDI

Page 33: Use of Hydro test (G-10)

34

OPERATING PROCEDURES

• As soon as pressure reaches 50% of the test pressure , wait for 10 minutes

• Increase pressure by 10% in stages till the test pressure is achieved

• Observe pressure drop

• ( by marking line on pressure gauges)

PRESENTED BY: HARDISH TRIVEDI

Page 34: Use of Hydro test (G-10)

35

• Hold the hydrotest pressure for specific time as mentioned in drawing

• Carry out thorough visual inspection of all joints & connections

(If any leakage is noticed, mark the point. The vessel is to be depressurized and then necessary repairs are to be carried out. Again the test procedure is to be repeated)

PRESENTED BY: HARDISH TRIVEDI

Page 35: Use of Hydro test (G-10)

37

DOs & DON’Ts

• Ensure pressure gauge readability

• Working, design & test pressure to be displayed near the vessel

• Ensure all gasket surfaces are free from dent & scratches before blanking

• Do not apply paint, oil, grease on weld joints

• Do not weld on job blind flangePRESENTED BY: HARDISH TRIVEDI

Page 36: Use of Hydro test (G-10)

38PRESENTED BY: HARDISH TRIVEDI