Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District...

16
Use of ATP to identify poor-performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN

Transcript of Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District...

Page 1: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Use of ATP to identify poor-performing filters

Al ParrellaWestern Lake Superior Sanitary District

Duluth, MN

Page 2: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.
Page 3: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Add bleach here

Final effluent

Page 4: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Problem statement:

• Bacteria increases across effluent filters– Seems to be a seasonal phenomenon

(worse towards end of season)

Page 5: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.
Page 6: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Fecal coliform, before and after filtersMonthly geometric mean

April May June July August SeptemberOctober0

50

100

150

200

250

300

350

400

450

BeforeAfter

Page 7: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Fecal coliform, before and after filtersMonthly geometric mean

April May June July August SeptemberOctober0

50

100

150

200

250

300

350

400

450

BeforeAfter

Problem Limit

Page 8: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Troubleshooting

• Use of ATP pen• Test ATP at various location including the

effluent of each filter• Results reported as difference between “total”

and “free”

Page 9: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Seco

ndary Effl

uent

Floc T

ank I

nfluent

Filter

Effluen

t 1

Filter

Effluen

t 2

Filter

Effluen

t 3

Filter

Effluen

t 4

Filter

Effluen

t 5

Filter

Effluen

t 6

Filter

Effluen

t 7

Filter

Effluen

t 8

Filter

Effluen

t 9

Filter

Effluen

t 10

Filter

Effluen

t 11

Filter

Effluen

t 12

Final

Effluen

t0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

ATP Assessment October 2, 2013

Page 10: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Results

• Clearly there was a problem with number 11 filter

• Found several mechanical issues related to backwash system

Page 11: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Seco

ndary Effl

uent*

Floc T

ank I

nfluent

Filter

Effluen

t 1

Filter

Effluen

t 2

Filter

Effluen

t 3

Filter

Effluen

t 4

Filter

Effluen

t 5

Filter

Effluen

t 6

Filter

Effluen

t 7

Filter

Effluen

t 8

Filter

Effluen

t 9

Filter

Effluen

t 10

Filter

Effluen

t 11

Filter

Effluen

t 12

Backwash

Wate

r

Final

Effluen

t0

500

1000

1500

2000

2500

3000

3500

4000

4500

ATP AssessmentOctober 15, 2013

Page 12: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Conclusion

• It’s hard to clean 100+ tons of media

Page 13: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.
Page 14: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.
Page 15: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Steps

• Start meter• Obtain sample• Submerge pen• Break ampule• Mix• Obtain reading– Units are in “relative light units”

Page 16: Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Thanks to…

• …Roger Sandstrom, Treatment Plant Operator• Kathy Hamel, PE, Operations and

Maintenance Supervisor, Clean Water Production