Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD...

74
B30 Presentation Examples Universal Relay Family Universal Relay Family

Transcript of Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD...

Page 1: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

B30 Presentation

Examples

Universal Relay FamilyUniversal Relay Family

Page 2: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: RTDS Testing EnvironmentRTDS Testing Environment

Real Time Digital SimulatorPSCAD graphical user interface

Real Time Digital

Simulator

(RTDS)

Real Time DigitalReal Time Digital

SimulatorSimulator

(RTDS)(RTDS)

•Final product validation

•Customer requested tests

Used for:

Page 3: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: RTDS Testing EnvironmentRTDS Testing Environment

Page 4: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: RTDS Applications and UsersRTDS Applications and Users

RTDS ApplicationsRTDS Applications

GEC Alsthom T&D (UK)

Asea Brown Boveri (Sweden)

Siemens (Germany)

Hitachi Corp. (Japan)

Toshiba Corp. (Japan)

Furnas Centrais Electricas (Brazil)

Ontario Hydro Technologies Inc (Canada)

Chugoku Electric (Japan)

Korea Electric Power Co. (S. Korea)

Nanjing Automation Research Institute (China)

Electric Power Research Institute (China)

Manitoba Hydro (Canada)

University of Manitoba (Canada)

LG Systems (S. Korea)

Nanyang Technical University (Singapore)

Chanwang University (S. Korea)

Kinkei Systems (Japan)

Toshiba Engineering (Japan)

University of Canterbury (New Zealand)

RTDS UsersRTDS Users

• Conventional TNA type studies

• AC System breaker sequences

• Power swings due to disturbance

• DC Transmission systems with various short circuit ratios

• DC System controls studies

• Relay test studies

• AC & DC System interactions

• SVS Applications and controls studies

Page 5: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Contents...Contents...

Case 1: External SLG Fault

Case 2: External SLG Fault

Case 3: External LLG Fault

Case 4: External 3P Fault

Case 5: External 3P Fault

Case 6: External SLG Fault

Case 7: External LLG Fault

Case 8: Internal SLG Fault

Case 9: Internal SLG Fault � next page

Page 6: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Contents...Contents...

Case 10: Internal LLG Fault

Case 11: Internal 3P Fault

Case 12: Internal SLG Fault (weak infeed)

Case 13: Internal SLG Fault (weak infeed)

Case 14: Closing onto Internal SLG Fault

Case 15: Closing onto Internal SLG Fault

Case 16: Closing onto Internal 3P Fault

Case 17: Closing onto External SLG Fault

Case 18: Closing onto External... � next page

Page 7: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Contents...Contents...

Case 19: External SLG Fault (autorecl.)

Case 20: External 3P Fault (autorecl.)

Page 8: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 1 (External Fault)Case 1 (External Fault)

• External AG fault on circuit #4

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #4 CT saturates after about 2 ms

• The B30 remains stable

COMTRADE File: B30_case_01

Page 9: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 1 (External Fault)Case 1 (External Fault)

AG, pow=0o

Page 10: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 1 (External Fault)Case 1 (External Fault)

Page 11: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 2 (External Fault)Case 2 (External Fault)

• External AG fault on circuit #4

• Point on Wave = 90 deg

• All six circuits connected

• Circuit #4 CT saturates after about 1.6 ms

• The B30 remains stable

COMTRADE File: B30_case_02

Page 12: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 2 (External Fault)Case 2 (External Fault)

AG, pow=90o

Page 13: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 2 (External Fault)Case 2 (External Fault)

Page 14: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 3 (External Fault)Case 3 (External Fault)

• External ABG fault on circuit #4

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #4 CT saturates after about 2.6 ms

• The B30 remains stable

COMTRADE File: B30_case_03

Page 15: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 3 (External Fault)Case 3 (External Fault)

ABG, pow=0o

Page 16: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 3 (External Fault)Case 3 (External Fault)

Page 17: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 4 (External Fault)Case 4 (External Fault)

• External ABCG fault on circuit #4

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #4 CT saturates after about 2.6 ms

• The B30 remains stable

COMTRADE File: B30_case_04

Page 18: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 4 (External Fault)Case 4 (External Fault)

ABCG, pow=0o

Page 19: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 4 (External Fault)Case 4 (External Fault)

Page 20: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 5 (External Fault)Case 5 (External Fault)

• External ABCG fault on circuit #4

• Point on Wave = 90 deg

• All six circuits connected

• Circuit #4 CT saturates after about 2.3 ms

• The B30 remains stable

COMTRADE File: B30_case_05

Page 21: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 5 (External Fault)Case 5 (External Fault)

ABCG, pow=90o

Page 22: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 5 (External Fault)Case 5 (External Fault)

Page 23: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 6 (External Fault)Case 6 (External Fault)

• External AG fault on circuit #1

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #1 CT saturates after about 6 ms

• The B30 remains stable

COMTRADE File: B30_case_06

Page 24: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 6 (External Fault)Case 6 (External Fault)

AG, pow=0o

Page 25: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 6 (External Fault)Case 6 (External Fault)

Page 26: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 7 (External Fault)Case 7 (External Fault)

• External ABG fault on circuit #1

• Point on Wave = 0 deg

• All six circuits connected

• Circuit #1 CT saturates after about 5.5 ms

• The B30 remains stable

COMTRADE File: B30_case_07

Page 27: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 7 (External Fault)Case 7 (External Fault)

ABG, pow=0o

Page 28: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 7 (External Fault)Case 7 (External Fault)

Page 29: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 8 (Internal Fault)Case 8 (Internal Fault)

• Internal AG fault

• Point on Wave = 0 deg

• All six circuits connected

• The B30 operates in 10.0 msec

(fast form-C)

COMTRADE File: B30_case_08

Page 30: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 8 (Internal Fault)Case 8 (Internal Fault)

AG, pow=0o

Page 31: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 8 (Internal Fault)Case 8 (Internal Fault)

Phase A operates in

10.0 msec

Phase A operates in

10.0 msec

Page 32: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 9 (Internal Fault)Case 9 (Internal Fault)

• Internal AG fault

• Point on Wave = 90 deg

• All six circuits connected

• The B30 operates in 10.7 msec

(fast form-C)

COMTRADE File: B30_case_09

Page 33: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 9 (Internal Fault)Case 9 (Internal Fault)

AG, pow=90o

Page 34: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 9 (Internal Fault)Case 9 (Internal Fault)

Phase A operates in

10.7 msec

Phase A operates in

10.7 msec

Page 35: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)

• Internal ABG fault

• Point on Wave = 0 deg

• All six circuits connected

• The B30 operates in 9.3 msec (fast form-C)

COMTRADE File: B30_case_10a,b

Page 36: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)

ABG, pow=0o

Page 37: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)

Phase A operates in

9.3 msec

Phase A operates in

9.3 msec

Page 38: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 10 (Internal Fault)Case 10 (Internal Fault)

Phase B operates in

10.5 msec

Phase B operates in

10.5 msec

Page 39: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

• Internal ABCG fault

• Point on Wave = 0 deg

• All six circuits connected

• The B30 operates in 8.8 msec (fast form-C)

COMTRADE File: B30_case_11a,b,c

Page 40: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

ABCG, pow=0o

Page 41: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

Phase A operates in

11.4 msec

Phase A operates in

11.4 msec

Page 42: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

Phase B operates in

8.8 msec

Phase B operates in

8.8 msec

Page 43: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 11 (Internal Fault)Case 11 (Internal Fault)

Phase C operates in

13.8 msec

Phase C operates in

13.8 msec

Page 44: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 12 (Internal Fault - Weak Infeed)Case 12 (Internal Fault - Weak Infeed)

• Internal AG fault

• Point on Wave = 0 deg

• Circuits 3 (wye winding of the transformer:

zero-sequence infeed), 4 (weak infeed) and

5 (load) connected

• The B30 operates in 17.7 msec

(fast form-C)

COMTRADE File: B30_case_12

Page 45: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 12 (Internal Fault - Weak Infeed)Case 12 (Internal Fault - Weak Infeed)

AG, pow=0o

Page 46: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 12 (Internal Fault - Weak Infeed)Case 12 (Internal Fault - Weak Infeed)

Phase A operates in

17.7 msec

Phase A operates in

17.7 msec

Page 47: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 13 (Internal Fault - Weak Infeed)Case 13 (Internal Fault - Weak Infeed)

• Internal AG fault

• Point on Wave = 90 deg

• Circuits 3 (wye winding of the transformer:

zero-sequence infeed), 4 (weak infeed) and

5 (load) connected

• The B30 operates in 13.5 msec

(fast form-C)

COMTRADE File: B30_case_13

Page 48: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 13 (Internal Fault - Weak Infeed)Case 13 (Internal Fault - Weak Infeed)

AG, pow=90o

Page 49: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 13 (Internal Fault - Weak Infeed)Case 13 (Internal Fault - Weak Infeed)

Phase A operates in

13.5 msec

Phase A operates in

13.5 msec

Page 50: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 14 (Closing onto Internal Fault)Case 14 (Closing onto Internal Fault)

• Internal AG fault pre-exists on the bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave

= 0 deg

• The B30 operates in 7.6 msec (fast form-C)

COMTRADE File: B30_case_14

Page 51: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 14 (Closing onto Internal Fault)Case 14 (Closing onto Internal Fault)

AG, pow=0o

Page 52: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 14 (Closing onto Internal Fault)Case 14 (Closing onto Internal Fault)

Phase A operates in

7.6 msec

Phase A operates in

7.6 msec

Page 53: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 15 (Closing onto Internal Fault)Case 15 (Closing onto Internal Fault)

• Internal AG fault pre-exists on the bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave

= 90 deg

• The B30 operates in 7.9 msec (fast form-C)

COMTRADE File: B30_case_15

Page 54: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 15 (Closing onto Internal Fault)Case 15 (Closing onto Internal Fault)

AG, pow=90o

Page 55: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 15 (Closing onto Internal Fault)Case 15 (Closing onto Internal Fault)

Phase A operates in

7.9 msec

Phase A operates in

7.9 msec

Page 56: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

• Internal ABCG fault pre-exists on the bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave

= 0 deg

• The B30 operates in 6.4 msec (fast form-C)

COMTRADE File: B30_case_16a,b,c

Page 57: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

ABCG, pow=0o

Page 58: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

Phase A operates in

8.8 msec

Phase A operates in

8.8 msec

Page 59: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

Phase B operates in

6.4 msec

Phase B operates in

6.4 msec

Page 60: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 16 (Closing onto Internal Fault)Case 16 (Closing onto Internal Fault)

Phase C operates in

8.8 msec

Phase C operates in

8.8 msec

Page 61: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 17 (Closing onto External Fault)Case 17 (Closing onto External Fault)

• Internal ABCG fault pre-exists on the

circuit #4

• The circuit #4 is connected to the de-

energized bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave

= 0 deg

• The B30 remains stable

COMTRADE File: B30_case_17

Page 62: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 17 (Closing onto External Fault)Case 17 (Closing onto External Fault)

ABCG, pow=0o

Page 63: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 17 (Closing onto External Fault)Case 17 (Closing onto External Fault)

Page 64: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 18 (Closing onto External Fault)Case 18 (Closing onto External Fault)

• Internal AG fault pre-exists on the circuit #4

• The circuit #4 is connected to the de-

energized bus

• The bus is energized from the circuit #1

• Closing onto the fault at the Point on Wave

= 0 deg

• The B30 remains stable

COMTRADE File: B30_case_18

Page 65: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 18 (Closing onto External Fault)Case 18 (Closing onto External Fault)

AG, pow=0o

Page 66: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 18 (Closing onto External Fault)Case 18 (Closing onto External Fault)

Page 67: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)

• External AG fault on the circuit #4

• The fault is cleared in 100 msec

• Two AR shots are executed with the dead-

time of 0.5 sec

• The AR fails - the breaker opens after 70

msec during each shot

• The B30 remains stable

COMTRADE File: B30_case_19

Page 68: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)

AG, pow=0o

Page 69: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)

Fault InceptionFault Inception 2nd AR shot2nd AR shot

Page 70: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 19 (External Fault – Autoreclosure)Case 19 (External Fault – Autoreclosure)

Page 71: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)

• External ABCG fault on the circuit #4

• The fault is cleared in 100 msec

• Two AR shots are executed with a dead-

time of 0.5 sec

• The AR fails - the breaker opens after 70

msec during each shot

• The B30 remains stable

COMTRADE File: B30_case_20

Page 72: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)

ABCG, pow=0o

Page 73: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)

Fault InceptionFault Inception 2nd AR shot2nd AR shot

Page 74: Universal Relay Family Management The Universal Relay Examples: RTDS Testing Environment PSCAD graphical user interface Real Time Digital Simulator Real Time Digital

Power Management The The Universal RelayUniversal Relay

Examples: Examples: Case 20 (External Fault – Autoreclosure)Case 20 (External Fault – Autoreclosure)