Unitrans D&T GroupUnitrans D&T Group
ZXM10 EISU TrainingZXM10 EISU Training
2
OverviewOverview
The ZXM10 EISU is an imbedded microprocessor system.
It can monitor supervision signals of various base station power equipment and environments in real time, generate alarms, and make corresponding control as required.
it is capable of networking downlink base stations, and networking by making effective use of base station communication resources.
3
Description of EISU ModelsDescription of EISU Models
The ZXM10 EISU (V1.0) is a series product.
Null Basic functionsBT Battery capacity analysis function added
ZXM10 EISU ( - - - )
Null Basic configurationsSS Extended configuration
Null Basic mode, network interface (master comm port) and serial port for master communication1E One E1 interface (master comm port) and timeslot back board for master communication 2E Two E1 interfaces (master comm port), 2M ring and timeslot front board for master communication4E Four E1 interfaces (master comm port), 2M ring + chain networking
48 - 48 VDC power24 +24 VDC power
4
Description of Common Models of the EISU Description of Common Models of the EISU No.
Model Description
1 ZXM10 EISU (48)
Serial port and network interface for master communication, basic configuration for supervision factor, -48 V
2 ZXM10 EISU (2E-48)
2M ring and front board for master communication, basic configuration for supervision factor, -48 V
3 ZXM10 EISU (1E-48)
Back board for master communication, basic configuration for supervision factor, -48 V
4 ZXM10 EISU (1E-SS-48)
Back board for master communication, extended configuration for supervision factor, -48 V
5 ZXM10 EISU (1E-SS-BT-48)
Back board for master communication, extended configuration for supervision factor, battery capacity analysis function being integrated, -48 V
5
FunctionsFunctions In the basic configuration, the ZXM10 EISU provides 12 general
AI/DI measurement channels, two general DI measurement channels and four DO channels to implement data collection and control of the unintelligent equipment. If an extended supervision unit is configured, eight general AI/DI measurement channels, two general DI measurement channels and four DO interfaces are added.
The ZXM10 EISU has the dedicated sensor interface, where one digital temperature sensor, two battery channels for total voltage and one smog detector can be connected.
The ZXM10 EISU provides multiple intelligent equipment protocol resolution interfaces to implement data collection and control of the intelligent equipment. (There are four to six interfaces and 20 intelligent devices can be connected.)
The ZXM10 EISU has the picture supervision function. It provides two USB camera interfaces to process, store and forward picture data. The picture resolution is up to 640 480.
6
FunctionsFunctions The ZXM10 EISU provides multiple communication interfaces
and networking modes. These transmission interfaces contain asynchronous serial ports, Ethernet interfaces and E1 interfaces. They provide the following networking modes: order wire channel, network, 2M protection ring, 2M chain, separate 2M and 2M extracted timeslot.
The ZXM10 EISU provides the local storage function. The data within 15 days can be stored locally after the master communication is interrupted.
The ZXM10 EISU provides the function of remotely or locally downloading the running program and intelligent equipment communication protocol program.
The ZXM10 EISU has the functions of equipment self-diagnosis and fault self-location.
The ZXM10 EISU provides the management function of real-time clocks.
7
FunctionsFunctions
The ZXM10 EISU configured with the extended transmission board provides transparent Ethernet interfaces.
The ZXM10 EISU provides the Web browsing function.
The ZXM10 EISU supports the intelligent equipment center resolution function.
The ZXM10 EISU supports energy saving for air conditioners.
8
Panel IndicatorsPanel Indicators
There are nine indicators on the EISU panel,
9
Jumper and DIP Settings of EISUJumper and DIP Settings of EISU
Basic configuration of EISU includes configuration to EISUP board, EISUM board, ETNM board, and EISUL board.
EISUL board
ETNM board
EISUP board
EISUS board
EISUM board
10
Jumper and DIP Settings on EISUP BoardJumper and DIP Settings on EISUP Board
Key components on EISUP board are as follow. In engineering practice,
S1
S2
X4 X7
EISUP
X5
11
Jumper and DIP Settings on EISUP BoardJumper and DIP Settings on EISUP Board
the jumper X7 on EISUP board must be at pin 2 and 3. DIP switch S2 use default setting.
12
Jumper and DIP Settings on EISUM BoardJumper and DIP Settings on EISUM Board
here are two DIP switches on EISUM
S2
S1
EISUM
13
Jumper and DIP Settings on EISUM BoardJumper and DIP Settings on EISUM Board
boardS1.1~S1.8 and S2.1~S2.4 are AI type switches, ON means current type, OFF means voltage type.
14
Description of External Interfaces-EISUMDescription of External Interfaces-EISUM
External interfaces of the EISU can be viewed when the cable cover is removed. The external interfaces are provided by the EISUM, EISUS and ETNM. The interfaces in the lower row are provided by the EISUM, and the interfaces in the upper row by the EISUS and the ETNM. The EISUS can change its location with the ETNM .
Switch
15
Configuration EISUconfig Configuration EISUconfig
Log in EISUconfig
16
Basic Configuration Basic Configuration
EISU network parameters and security console connection parameters.
17
Board ManagementBoard Management
On Channel Configuration subpage, sensor type, channel type, upper and lower limits of alarm, and return difference, and so on,
18
Serial Port/Intelligent Port ManagementSerial Port/Intelligent Port Management
EISU has 7 serial ports in total.
19
Intelligent Analysis SettingsIntelligent Analysis Settings
the red numbers are the order of the steps in setting intelligent analysis function.
20
USB Video ManagementUSB Video Management
If USB device is closed, then all management and operation related to this USB device are unavailable. If USB device is available, relevant operation may be done.
21
Access Control Communication SettingsAccess Control Communication Settings
22
External access control mode External access control mode
Connect external access controller with EISU applied in dynamic IP networking.
For example, connect CHD805AE in wireless dynamic IP networking or dynamic IP networking.
1. Set the serial port connecting the device as soft transparent;
2. Set up serial port parameters: baud rate, receive mode.
23
EISU built-in access control mode EISU built-in access control mode
24
Operation stepsOperation steps
1.Select the serial port that is specified on engineering drawing in Serial Port box, and select Access Control in the Function box;
2.Click Modify button to set serial port parameters.
If Baud Rate is 9600, then the Waiting Time after Sending should be set as 2083;
If Baud Rate is a value other than 9600, then the Waiting Time after Sending will be automatically set to appropriate value. EISU configuration program above V1.10 supports this function.
3.For receive mode, you must select [Header (7E) +Tail (0D)];
4.Set Function Parameters of Access Control Port:
Server IP and Port No. do not need to be set.
5.Door Magnetic Channel must be set as the exact channel that is connected in construction practice.
25
Update of Application Program and DriverUpdate of Application Program and Driver
EISU supports remote downloading application program and driver.
26
Faults and Alarm HandlingFaults and Alarm Handling
27
Faults and Alarm HandlingFaults and Alarm Handling