Unique Firestop Products: Threaded Sleeve Fire Stop System

16
Threaded Firestop Sleeve System Installation

Transcript of Unique Firestop Products: Threaded Sleeve Fire Stop System

Page 1: Unique Firestop Products: Threaded Sleeve Fire Stop System

Threaded Firestop Sleeve

System Installation

Page 2: Unique Firestop Products: Threaded Sleeve Fire Stop System

UNIQUE Threaded Firestop Sleeve

System is designed for new cable

installations where the hole through

the firewall or floor is core bored or

precut.

Page 3: Unique Firestop Products: Threaded Sleeve Fire Stop System

The Threaded Firestop Sleeve is

constructed of rigid steel tubing that

is threaded on both ends and made of

(IMC) Intermediate Metal Conduit.

Page 4: Unique Firestop Products: Threaded Sleeve Fire Stop System

The system includes:

1 – 12″ threaded IMC sleeve

2 – large flat washers

2 – threaded couplings

2 – plenum rated bushings

2 – documentation/warning labels

1 – A package of UNIQUE Intumescent Putty

Page 5: Unique Firestop Products: Threaded Sleeve Fire Stop System

Threaded Firestop Sleeves come in

4” inches, 2”, and 1" diameters.

Page 6: Unique Firestop Products: Threaded Sleeve Fire Stop System

INSTALLATION PICTORIAL

Page 7: Unique Firestop Products: Threaded Sleeve Fire Stop System

A 4 inch System will require a 4 & 1/2 inch hole

minimum! Most people should drill a 5 inch

hole for the 4 inch Threaded Sleeve.

Pre-drill the hole in

advance. BE SURE to

drill the hole to the

outside diameter

(O.D.) of the System

you will be using.

Page 8: Unique Firestop Products: Threaded Sleeve Fire Stop System

Remove the documentation warning label.

Page 9: Unique Firestop Products: Threaded Sleeve Fire Stop System

Disassemble one side of the System.

Adjust the

coupling, washer

and bushing so

that the sleeve will

protrude evenly on

both sides when

installed.

Page 10: Unique Firestop Products: Threaded Sleeve Fire Stop System

Feed the System into the hole you have pre-

drilled. Go below and install the other half of

the hardware.

Page 11: Unique Firestop Products: Threaded Sleeve Fire Stop System

The vertical

application of the

Threaded Sleeve

requires the sleeve

to be packed (3 inch

depth) with mineral

wool batt insulation.

This keeps gravity from having any effect on

the intumescent putty.

Page 12: Unique Firestop Products: Threaded Sleeve Fire Stop System

If used horizontally, this system needs

no wool batt.

Page 13: Unique Firestop Products: Threaded Sleeve Fire Stop System

When the cables

reach their

destination, install a

minimum 1/2 inch

thickness of Unique

Putty per the vertical

application.

This System used horizontally, needs a

minimum 1 inch thickness of putty.

Page 14: Unique Firestop Products: Threaded Sleeve Fire Stop System

Fill out and attach the documentation/warning

label.

Page 15: Unique Firestop Products: Threaded Sleeve Fire Stop System

Don’t forget to take a

picture of your completed

installation for future

reference.

Page 16: Unique Firestop Products: Threaded Sleeve Fire Stop System

Visit our website for more firestop products

and complete installation pictorials.

https://www.uniquefirestop.com/