Doc.no.: M0618691-000/1 - Rev. 251105 U:\Hovedbibliotek\Produkter\Standard\Uniflo 1200\2. Kundemappe UK\10_Ex_applications\Ex-applications.doc Uniflo 1200 Applications for Ex-installations Please look at our homepage www.flonidan.dk there you will find the newest version of the document.

Transcript of Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone:...

Page 1: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Doc.no.: M0618691-000/1 - Rev. 251105

U:\Hovedbibliotek\Produkter\Standard\Uniflo 1200\2. Kundemappe UK\10_Ex_applications\Ex-applications.doc

Uniflo 1200 Applications for Ex-installations

Please look at our homepage www.flonidan.dk

there you will find the newest version of the document.

Page 2: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 2 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

Index

part

title page

1 Index 3 2 Overview

Find the solution that fulfils your requirements, in the “overview” section. 4

3 Details Details for the wiring etc.

8

4 General precautions Some general precautions, to take in a count when designing ex-installations

18

Applications: The possibilities in terms of applications is described by 8 basic samples. By using these samples, or combining them, all needs should be covered.

1: Modem connected to battery powered Uniflo 1200 2: Uniflo 1200 in Ex-area powered by external power supply 3: Uniflo 1200 in Ex-area supplying serial data to Medi Flomote 4: Uniflo 1200 in Ex-area supplying serial data to PC or PLC 5: Uniflo 1200 in Ex-area supplying pulses to PLC etc. 6: Uniflo 1200 in Ex-area supplying 4-20mA signals to PLC etc. 7: Uniflo 1200 in safe area, using 4-20mA transmitters 8: Uniflo 1200 in Ex-area, connected to 4-20mA transmitters

General comments: Ex-box:

Ex-barriers and other modules for installation in safe area may be installed in a Ex-box (part no.: 0618691-000). If one box is too small, more boxes may be used. Standard delivery includes 3 cable glands: 1 M16 for ex connection, one M20 for output to safe area, one M 12 for ground connector. Note that additional cable glands may be required, depending on the application. Refer to part numbers for box and cable glands at page 6. Note that Ex-box must be ordered separately. It is not included in the part numbers for the modules.

Uniflo 1200 option modules:

On the detailed drawings, Uniflo 1200 symbol indicates option boards for Uniflo 1200. Note the following, when used for hazardous area: - Analogue output card is available in two options: - passive output, for use in hazardous or safe area (part no. 0618630-000) - active or passive output, for use in safe area only (part no. 0618631-000)

Modems and 230 V AC power supply modules must be installed in safe area only.

Attention:

Always check that ex-limits for the option boards (refer to customer file, sections for the option modules) matches the limits for the barriers (this has been taken care of on the application samples).

Always follow local regulations for electrical installations, in particular for the hazardous area.

Page 3: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 3 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

Uniflo 1200

Applications for Ex-installations Examples

Examples can be combined. See details for each example. For general precautions at installation, please refer to next section.

1: Modem, battery powered Uniflo 1200:

2: External power for Uniflo 1200:

3: Connection to MediFlomote:

Serial data, Uniwire (unipolar)

Page 4: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 4 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

4: Connection to PC (RS232):

Serial data, Uniwire (bipolar)

5: Pulses to auxillary equipment

pulses

6: Analogue signals to auxillary equipment

4 - 20 mA

Page 5: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 5 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

7: Uniflo 1200 in safe area, using 4-20mA transmitters

8: Uniflo 1200 in Ex-area, connected to 4-20mA transmitters

a: with Uniflo 1200 battery supplied

Page 6: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 6 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

b: with Uniflo 1200 for external power supply

Enclosure for all applications:

Part no.

Ex-box with DIN rail and cable glands, for click-on installation of modules (190 x 180 x 180 mm) (see front page) 0618691-000 Additional cable gland, PG 13, grey 0618895 Additional cable gland, PG 13, blue (Ex) 0618896

Note: - Enclosure is not included in the part numbers under each application. - Additional cable glands may be required, if more applications are fitted in the same ex-box.

Page 7: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 7 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

Applications for Ex-installations

Details

Examples can be combined.

1. Modem, battery powered Uniflo 1200:

Serial data

Details:

Communication card is installed in Uniflo 1200, and powered by battery. The battery lifetime will be reduced (approx. 50 %), because of the additional power consumption of the communication card.

Zener barrier, GSM modem and power supply for GSM modem is installed in a box, to be mounted in safe area.

Max. cable length from Uniflo 1200 to modem box is 100 m.

Attention: Be sure to follow regulations for ex-installations.

Page 8: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 8 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

2. External power for Uniflo 1200:

Details:

This solution is used when Uniflo 1200 is mains supplied, e.g. if equipped with options requiring external power supply, such as HF board.

The zener barrier used is a unipolar positive type.

Note that Uniflo 1200 Ex power interface is isolated. Therefore equalizing safe ground for Uniflo 1200 is not required.

Page 9: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 9 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

3. Connection to Medi Flomote:

Details:

This application is used when Uniflo 1200 must be connected to a Medi Flomote installed in safe area. The zener barrier used is a unipolar positive type.

Note that Uniflo 1200 serial port is isolated. Therefore equalizing safe ground for Uniflo 1200 is not required.

Page 10: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 10 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

4. Connection to RS 232 :

Details:

This application is used when Uniflo 1200 must be connected to a RS 232 port on equipment installed in safe area (e.g. a PC or a PLC). The zener barrier used is a bipolar type.

Note that Uniflo 1200 serial port is isolated. Therefore equalizing safe ground for Uniflo 1200 is not required.

Page 11: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 11 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

5. Pulse signals to auxiliary equipment :

Pulses

Details:

This application is used when Uniflo 1200 pulse output must be connected to a digital input on equipment installed in safe area (e.g. a PC or a PLC). Zener barrier is used for safety barrier.

Note that Uniflo 1200 serial port is isolated. Therefore equalizing safe ground for Uniflo 1200 is not required.

See optional installation on next page

Page 12: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 12 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

Same application as above, but with isolation amplifier used for safety barrier.

As isolation amplifier is used for safety barrier, no equalizing safe ground for Uniflo 1200 is required.

Page 13: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 13 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

6. Analogue signals to auxiliary equipment :

4 - 20 mA

Details:

0618630-000

This application is used when Uniflo 1200 must be connected to an analogue input on equipment installed in safe area (e.g. a PC or a PLC). Isolating amplifier is used as safety barrier.

As isolation amplifier is used for safety barrier, no equalizing safe ground for Uniflo 1200 is required.

Page 14: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 14 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

7: Uniflo 1200 in safe area, using 4-20mA transmitters

Details:

This application is used when Uniflo 1200 is installed in safe area, and 4-20mA transmitters in hazardous area must be connected to Uniflo (Using analogue input board). Zener barrier is used for safety barrier.

Note that Uniflo 1200 analogue input is not isolated. Therefore equalizing safe ground for Uniflo 1200 is required.

Page 15: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 15 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

8: Uniflo 1200 in Ex-area, connected to 4-20mA transmitters

a: with Uniflo 1200 battery supplied

Details:

Page 16: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 16 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

b: with Uniflo 1200 for external power supply

Details:

Page 17: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 17 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

Applications for Ex-installations

General precautions

General: Installations in hazardous area must be carried out strictly in accordance to local regulations. People carrying out this kind of work must be trained in these regulations, and must follow closely the actual changes in regulations, standards etc. The following is only meant as a guideline, which is not necessarily up to date.

Standard Ex-installation:

A: Switchboard, main or auxiliary B: Measuring equipment (e.g. PLC or flow computer) C: Ex barrier (Zener barrier or. isolation amplifier) D: Process equipment (transmitters etc.) E: Process installation F: Netforsyningskabel, m. jord, el. jord via jordspyd G: Power supply cable, for measuring equipment H: Signal cable for process

Installations in hazardous area must be carried out , so local heating or sparks is prevented. This is obtained by limiting the power sent to the hazardous area. Normally, this is done by installing zener barriers, that when properly grounded, limits the current and the voltage, or by using isolated amplifiers, where the low power side connected to hazardous area, is isolated from the high power side at the safe area.

Page 18: Uniflo 1200 - gAvilar · Page 3 of 19 FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88 • E-mail: mail@flonidan.dk Examples Uniflo

Page 18 of 19

FLONIDAN DC A/S Islandsvej 29 • DK-8700 Horsens • Phone: +45 75 61 88 88 • Fax: +45 75 62 60 88

www.flonidan.dk • E-mail: [email protected]

The limiting component (C) must be ATEX-approved. As mentioned, it may be a zener barrier, or an isolated amplifier. Zener barriers includes components, that will lead any voltage above the specified limitation voltage, to ground. If the voltage becomes above a certain value, a fuse will blow, and the connection to the safe area will be cut. For zener barriers, it is essential that ground at the hazardous area is the same as in the safe area, to ensure that voltage at the zener barrier at safe area, and the process in hazardous area, will stay within the specified limits. In general, all parts of the installation must refer to the same ground. The requirements for the ground connections are depending on weather the device in hazardous area is isolated by e.g. optocoupler or not. Isolation amplifiers never require this equalization ground, as the high voltage at safe area is isolated from the low power circuits at hazardous area, by the amplifier. When the safe ground is established, zener barriers are relatively easy and cheap to install. However, the safety ground may some times be difficult or impossible to establish.