ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is...

51
ULTRASONIC HEAT METER IFX-M4-04 TECHNICAL DESCRIPTION IFX-M4-04 V01

Transcript of ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is...

Page 1: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

ULTRASONIC HEAT METER IFX- M4-04

TECHNICAL DESCRIPTION

IFX-M4-04 V01

Dan Macey
HP
Page 2: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 2

SAFETY REQUIREMENTS Before operating the meter, please read this technical description and user's manual

thoroughly and follow their instructions. When the meter is powered from the battery (3.6 V), risk factors during the meter installation

and service is a heat conveying fluid with inner pressure up to 1,6 MPa and temperature up to 1800C.

If meter is powered from mains power supply, it contains dangerous ~230 V electrical current. It

is necessary to follow general safety requirements during installation and maintenance process. To eliminate this risk, only qualified technical personnel may install and maintain heat meters

(certificates for electrical installation work with equipment up to 1000 V are required). Personnel must be familiar with appropriate technical documentation and general safety instructions.

Device comply with safety class II. and does not require protective grounding. To protect power

circuits from current overrun, 0,1A fuse, marked “F1”, is mounted on the bottom side of power supply module. Remove power supply module to replace the fuse. If relay output current exceeds 2 A, it may damage output circuits. It is recommended to use additional protection circuits to protect relay outputs from damage.

Safety guarantees at installation and service of meter is: - Reliable insulation of electrical circuits, - Hermetic fitting of primary flow and temperature sensors into the pipeline, - Reliable fastening of a sub-assemblies of heat meter at installation. Safety requirements for temperature and pressure sensors are provided in appropriate technical documentation.

Warning! Switch off mains power supply before changing, repairing, connecting or

disconnecting system parts, if meter is powered from mains power supply! Power switch has to be installed close to the calculator.

Mounting of the sub-assemblies of heat meter is permissible only after ensuring of absence of heat conveying fluid in the pipeline.

When the meter is powered from the mains supply 230 V:

- The calculator of meter should be mounted in the cabinet (panel) - The calculator of meter must be connected to line voltage 230 V using 3-wire copper cable

with cross-section of each wire not less than 0,5 mm2 (3x0, 5 mm2 ) with the color marking. External diameter of a cable must be 6 ... 8 mm.

- The meter must be connected to mains power supply only through automatic unipolar AC switch (nominal current 2 A) (Annex B, Figure B3).

- The automatic switch should be a part of the building wiring and it should be marked as disconnecting device of meter. The automatic switch should be installed close to meter and so that it was easily available to service personnel.

It is recommended to establish the calculator in the same cabinet as the switches for cutting off power supply. The switches should be adjusted for the power used by the equipment.

Caution: If this equipment is used in a manner not specified by the manufacturer, the

protection provided by the equipment may be impaired.

Page 3: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 3

Contents

Safety requirements.......................................................................................................................... 1. Application field............................................................................................................................... 2. Technical data................................................................................................................................. 3. Accessories and sub-assemblies.............................................................................................. ......... 4. Operating principle...................................................................................................................... ..... 5. Marking and sealing........................................................................................................................... 6. Installation.......................................................................................................................................... 7. Operation ........................................................................................................................................... 8. Verification........................................................................................................................................ 9. Transportation and storage................................................................................................................ 10. Warranty.......................................................................................................................................... Annex A. Measurement schemes and energy calculation formulas .......................................... Annex B. Electrical wiring diagrams........................................................................................

Annex C. Numbering of terminals............................................................................................. Annex D. Outline and mounting dimensions of calculator........................................................

Annex E. Sizes and mounting dimensions of ultrasonic flow sensors………........................... Annex F. Installation recomendation and sealing of temperature sensors.................................

Pg. 2 4 7 15 15 16 16 24 36 36 36 37 41 44 46 49 51

For EU Customers only - WEEE Marking. Marking of electrical and electronic equipment in accordance with Article 11 (2) of Directive 2002/96/EC

This symbol on the product indicates that it will not be treated as household waste. It must be handed over to the applicable take-back scheme for the recycling of electrical and electronic equipment. For more detailed information about the recycling of this product, please contact your local municipal office.

Page 4: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 4

1. APPLICATION FIELD Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy

in heating/cooling systems, and consumed or supplied heating energy in heating systems, installed in dwelling houses, office buildings or energy plants.

Heat meter IFX-M4-04 consists of the primary flow sensor and the calculator with type approved pair of temperature sensors with Pt500 elements.

The user may select (ordering the meter) one of twelve possible measurement schemes, according to the application type. Application of measurement schemes and conventional designation are presented in the table 1.1.

Available measurement schemes IFX- M4–04 –

Table 1.1 Measurement scheme application Conventional designation

For closed heating system with flow sensor in supply pipe U1 For closed heating system with flow sensor in return pipe U2 For closed heating system with flow sensor in supply pipe. With leakage detection option

U1F

For closed heating system with flow sensor in return pipe With leakage detection option

U2F

For closed system for accounting of heating - cooling energy with flow sensor in flow pipe

U1L

For closed system for accounting of heating - cooling energy with flow sensor in return pipe

U2L

Remark: Heat (cooling) energy calculation formulas for each measurement diagrams are presented in Annex A. Additional flow, temperature T3 and pressure measurement channels that are not used for heat energy measurement can be used to control other parameters. Heat meter corresponds to essential requirements of the Technical Regulation for Measuring

Instruments, dated 30 March 2006 (transposing in the NB’s country law Directive 2004/22/EC of 31 March 2004 on measuring instruments):

- Annex I Essential requirements - Annex MI-004 Heat meter ,

IFX-M4-04 complies with the European standard EN 1434 “Heat meters”. IFX-M4-04 fulfils “C” class environment protection requirements according to EN1434-1:2007 Climatic ambient temperature range: from 5 ° to 55 ° C Humidity: non condensing Location: closed Mechanical environment: class M1 Electromagnetic environment: class E2

Page 5: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 5

Type number combination of the heat meter IFX-M4-04 for order placing:

Remark:* - marked number are used only for order coding (It is not used for meter marking).

The flow sensor installation: Code In flow pipe 1 In return pipe 2

Destination of the heat meter: Code For measuring heating energy A For measuring heating and cooling energy B

Communication module: Code None 1 M-bus module 2 RS232 module 3 Universal module (RS232/M-bus/CL ant Current outputs) 4 Wireless Radio readout module RF 868 MHz 5

Length of sensors connection cable, m : Code 3 m 3

5 m 5 10 m 10 15 m 15 20 m 20 40 m 40 60 m 60 80 m 80 100 m 100

Communication package: Code None 0 Optical interface adapter OG-1 OG1 Software READER SW Optical adapter OG-3 for hanheld terminal DK-3 OG3 Hanheld terminal for data acquisition DK-3 DK3

Type Meter IFX-M4-04 – 1-A-10-A -1*-10*-OG1*

Flow sensor: Permanent flow rate, m3/h Mounthing length, mm Code

3.5 260 25 6 260 32 10 300 40 15 270 50 25 300 65 40 350 80 60 350 100

Supply Power: Code

Internal Lithium battery A External supply power 230 VAC C

Page 6: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 6

2. TECHNICAL DATA

2.1. Energy measurement 2.1.1. Accuracy class - 2 Maximum permissible heat energy measurement error of calculator and flow sensor:

),/02,0/5,2( min qqE p %;

Maximum permissible heat energy measurement error of complete meter (error of temperature sensors pair included):

E = (3+4 min /Θ +0,02qp/ q)

where: min - lower limit of the ntemperature difference, K;

- temperature difference, between the measured flow and return

temperatures of heat-conveying liquid K; pq - permanent flow-rate, m³/h ;

q - measured flow-rate, m³/h . 2.1.2. Thermal energy calculation

Consumed heat energy is calculated according to formulas given in Annex A It is possible to perform calculations in two ways, using programmed or practically measured pressure values ( 1-st pressure channel corresponds to the flow pipe, 2-nd – return pipe); 2.1.3. Maximum power value 64 MW 2.2. Temperature measurement

- Number of sensor inputs (measurement channels) 1, 2 or 3* - Temperature sensors type Pt500 - Absolute temperature measurement error not more than 0,3 oC - Sensor connection method ** 2-wire, 4-wire

- Max. cable length between calculator and each of the temperature sensors: for the 4-wire connection method 3; 5; 10; 15; 20; 40; 60; 80; 100 m, for the 2-wire connection method 3; 5 m, - Temperature measuring range (1... 3) 0…180 oC - Temperature displaying range (3) -40…180 oC

- Temperature difference (Θ1-Θ2) measuring range 2…150 oC (or 3…150 oC)*** - RMS value of sensor current 5,5 mkA

- Resolution of temperatures and temperature difference 0,1 oC

NOTES: * - additional 3rd channel selects the user during on-site installation

** - selected by the customer when ordering the device *** - depending on the value of the lower measurement limit of the temperature

difference of the connected pair of temperature sensors - Recorded errors and their duration Θ >181 oC (or open circuit),

Θ < -41 oC (or short-circuit),

Page 7: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 7

2.3. Flow measurement 2.3.1. Ultrasonic flow measurement channels (sensors) 1 and 2 - Ultrasonic flow measurement sensors (depending on the measurement circuits) 2 or 1

Heat meater flow sensor data are presented in Table 2.1 Table 2.1

Connection

type

Flow-rate, m³/h Overall length, mm

Pressure loss p, at qp, kPa,

not more than iq * pq sq

Thread G 1¼ 0,035 (0,14) 3,5 7,0 260 4 Thread G 1¼ 0,06 (0,25) 6,0 12,0 260 10 Thread G 2 0,1 (0,4) 10,0 20,0 300 10

Flange DN50 0,15 (0,6) 15,0 30,0 270 12 DN65 0,25 (1) 25,0 50,0 300 20 DN80 0,4 (1,6) 40,0 80,0 350 18 DN100 0,6 (2,4) 60,0 120,0 350 18

Remark: 1.*Values of the minimum flow rates for measurement schemes U1L and U2L (accounting of heating-cooling energy ) are presented in brackets.

Temperature limits of heat conveying liquid: Θ q = 10....130 ºC (to all measurement schemes, except U1L and U2L);

Θ q = 0....130 ºC (to measurement schemes U1L and U2L, intended for the account of energy for

heating and cooling); Accuracy class - 2 Limits of a permissible error of volume (mass) measurement:

Ef = (2 +0,02qp/q), %

- Difference of measurement errors of the pair flow sensors in flow range from 0.1 qp to qs (for circuits U1F, U2F, A1) no more than 1,0 . Function of flow measurement in two directions is provided

- Connection line length between the calculator and each of the flow sensor 3; 5; 10; 15; 20; 40; 60; 80; 100 m,

- Recorded errors and their duration: - the flow channel is broken, -the pipe is emty, - flow rate exceeds maximum allowed value, - flow rate is under minimum allowed value,

- measurement units m3 or t ; - threshold value 0,001*qp - maximum admissible working pressure PS (PN 16) of flow sensor 1,6 MPa

Page 8: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 8

2.3.2. Flow pulse input ( 3 and 4) - number of pulse inputs 2 - pulse input device class IB (or IC,if the noise filtrer is Off)

- pulse values programmable - type of pulses active, passive - high voltage ranges of active pulses 2,5...3,7V - low voltage ranges of active pulses 0 ...0,7V - input resistance* at the bartery supply 2 MOm - input resistance* at the main supply 10 kOm (*Resistance of internal resistor to 3.6 V circuit) - integrated programmable filter: programmatically

rejected input pulses, where the repetition period 2...999 ms is less than the stated period of the filter (only for IB class pulses) - communication cable length between calculator and each of the sensors 3; 5; 10; 15; 20; 40; 60; 80; 100 m, - recorded errors and error duration(depending on the configuration):

- none recorded - recorded at short circuit on line (or an impulse low level) longer than 2 s - recorded when flow rate exceeds programmed maximum allowed value - recorded when flow rate is under programmed minimum allowed value - recorded when the pulse is not more than 24 hours.

- display units m3 - maximum permissible input pulse frequency and

minimal permissible pulse or pause duration, depending on pulse type and cable length:

Table 2.2

Power supply of meter/ Flow pulse input type

Connection cable length , m

Maximum permissible pulse

frequency, Hz

Minimal permissible pulse or pause duration, ms

Mains supply / Active or passive pulses

(transistor key or mechanical contact)

<100 m 200 (5) 2,5 (100)

Battery supply/ Passive pulses

(transistor key or mechanical contact)

< 10 m 5 100

Note: Values of maximum permissible input pulse frequency and minimal permissible pulse or pause duration for pulse input device class IB are presented in brackets.

- Flow rate value (for information) is calculated: a) when the flow input pulse duration period is T 10 s - each 10 s as multiplication of flow

pulse value and flow pulse average period,

b) when the flow input pulse duration period is T =10...180 s - flow input pulse duration periodicity as multiplication of flow pulse value and flow pulse period,

c) when the flow input pulse duration period is T 180 s - the value zero is indicated.

Page 9: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 9

2.4. Pressure measurement

- Number of pressure inputs 0...2 - Display units kPa

- Fiducial error not more than 0,25 of the upper limit of the measurement range

Pressure measurement ranges: - lower limit , programmable from 0 kPa to 2500 kPa - upper limit, programmable from 100 kPa to 2500 kPa Normalized input dimension current, linearly dependent on the pressure - input current limits, programmable 0-5 mA, 0-20 mA, 4-20 mA - input resistance 110 Om

2.5. Time measurement

Relative time measurement error not more than 0,01 % Heat meter calculator measures: - real time - calendar - time, when device is powered on - normal working hours - failure time of additional flow sensors V3 .. V4 - time, when flow rate exceeds programmed maximum allowed value for channels V3…V4 - time, when flow rate is under programmed minimum allowed value for channels V3…V4 - time, when temperature difference Θ1-Θ2 is under programmed minimum allowed value Display resolution:

the real time display 1 s for operating time display 0,01 h

Time of storage date not less than 12 years 2.6. Display (LCD) The device is equipped with 8-digits LCD (Liquid Crystal Display) with special symbols to display parameters, measurement units and operation modes The following information can be displayed: - integral and instantaneous measured parameters and archive data, listed in the Table 2.4. - device configuration information (see Fig. 8.2.6). - report printing control information (see Fig.8.2.5). Display resolution (directly corresponding with pulse output value), depending on programmed

maximum flow rate value (the highest value of the flow channel, involved in the energy calculation formula), is provided in the Table 2.3

Table 2.3 Maximum

programmed flow rate, m3/h

Displayed fluid volume (mass) lowest digit value

(flow pulse output value), m3

Displayed energy lowest digit value (energy pulse output value),

MWh, Gcal, GJ qs < 5 0,001 0,0001

5 qs <50 0,01 0,001 50 qs <500 0,1 0,01

500 qs 1 -

Page 10: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 10

2.7. Measured and recorded parameters:

Table 2.4

Arbitrary symbol Parameter

Display capacity, measurement units,

measurement ranges

Recorded in archive

Integral parameters

E Total consumed energy (in accordance with Annex A)

8 digits, MWh, Gcal, GJ*

Absolute values every hour, alterations every hour, day and month

E1 1st component of energy (in accordance with Annex A)

E2 2nd component of energy (in accordance with Annex A)

V1(M1) Fluid volume (mass) of 1-st measurement channel

8 digits, m3 (t)

V2 (M2) Fluid volume (mass) of 2-nd measurement

channel Absolute values

every hour, alterations every hour, day and month

M1-M2 (V1-V2)

Fluid volume (mass) difference between 1-st and 2-nd measurement channels

8 digits, m3 (t)

V3 (M3) Fluid volume (mass) of 3-rd measurement channel

8 digits, m3

V4 Fluid volume of 4-th measurement channel Total operation time 8 digits,

0,01 h

A Operation time in normal mode Er 1 Codes of significant faults (errors) 6 digits Amount in hour,

day, month Er 2 Codes of transistory faults (errors) 6 digits Instantaneous parameters

P Total instantaneous thermal power 5 digits, kW ------- q1 Flow rate on 1-st channel 5 digits,

m3 /h a rba t /h 5 digits, m3 /h

------- q2 Flow rate on 2-nd channel q3 Flow rate on 3-rd channel q4 Flow rate on 4-th channel p1 1-st channel fluid pressure 0 ... 2500,0 kPa Average hourly,

daily and monthly data

p2 2-nd channel fluid pressure

1 1-st channel fluid temperature 0...180 oC 2 2-nd channel fluid temperature

1-2 1-st and 2-nd channel temperature difference (2...150) oC 3 3-rd channel fluid temperature - 40...+180 oC 2.8. Data recording and storage Following daily, weekly and monthly parameter values are recorded in heat meter memory: - absolute integral instantaneous parameter values (listed in Table 2.4) - hourly, weekly and monthly alterations of integral parameters - hourly, weekly and monthly average values for all measured temperature and pressure values - error (fault) and information codes (see paragraph. 8.2.2) that occurred during the last hour, day and month Data logger capacity:

up to 110 days (3,5 months) – for hourly records. up to 1024 days (33 last months) -. for daily and monthly records,

Archive data retention time not more than 33 months Retention time of measured integrated parametres even if device is disconnected from power supply not more than 12 years

Page 11: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 11

2.9. External communication modules and interfaces 2.9.1. Optical interface according to EN 62056-21:2003

(integrated into the front panel) Optical interface is designed for:

- read out of values by protocol EN IEC 62056 or M-bus - direct printing reports (by ASCII codes) - read out archive data by protocol M-bus - configuring of the meter by means of the special protocol (parameterization mode is actuated by button “SET”) - adjusting of the meter by means of the special protocol (adjusting mode is actuated by jumper)

Programmable data transfer rate (300 ... 9600) bps with the "Even" parity or not.

2.9.2. Wire communication interfaces (as optional plug in modules) - M-bus (according to EN1434-3); - M-bus / CL / RS232 / two pulses outputs; - M-bus /CL / RS232 / two current outputs; - RS232, - R485. Wire communication interface protocol M-bus (according to EN1434-3) Data transfer rate Programmable (300 ... 9600) bps with the "Even" parity or not.

2.9.2. Pulse -frequency and current outputs The following outputs are available as optional plug-in modules: Two programmable (configurable) pulse outputs or frequency (available only with mains power supply version) outputs Class OD Pulse outputs type (the user can select) Active pulses +18 V

(when mains supply) or passive pulses (Umax 42 V, 20 mA )

Two programmable current outputs (only available with mains power supply version) 0-20 mA or 4-20 mA Four pulse outputs for verification tests Class OD

Active pulses 3.5 V ± 0.3 V I< 0.1 mA The configurable pulse-frequency output in “pulse mode” can be used for thermal energy (E, E1,

E2) or quantity of liquid V1 (M1), V2(M2), V3(M3), V4 pulses Pulse value will correspond to the lowest digit of indicated parameter.

The configurable pulse-frequency output in “frequency mode” or current output can be used for thermal power , flow rate (q1, q2, q3, q4), temperature (1, 2, 3) or pressure (p1, p2) pulses.

Zero value of frequency (or the minimum value of the selected range of a current) corresponds to zero value of an output parameter, and frequency 1000 Hz (or maximum value of the selected range of a current) corresponds to maximum value of parameter:

flow rate – qmax, temperature – 180 oC, pressure – p max, thermal power– qmax*100 [kW], There qmax- the maximum flow rate in the measurement channel [m3/h]).

Page 12: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 12

2.10. Additional functions 2.10.1. Regulation function Available only with mains power supply version. The double relay output (230V) is intended for

controling of current load up to 2A and it is fitted in main supply module. Using electrically-controlled valve gives the possibility:

automatically maintain selected parameter value within defined limits, prevent selected parameter from exceeding maximum allowed value, prevent selected parameter from falling below minimal allowed value control a water temperature on the flow pipeline, to maintain the preset room temperature, depending on outdoor temperature (Θ3).

Following parameters can be selected for regulation: thermal power, any flow (q1…q4), any temperature (Θ1 … Θ3), temperature difference (Θ1- Θ2), any pressure (p1 or p2).

IMPORTANT: Regulation will be efficient only if regulated valve is installed in such way that

it can effect regulated parameter. Regulation speed (time interval from fully opening the valve to fully closing the valve) is

programmable. Following electrically-controlled valves may be used for regulation:

with separate control inputs for opening and closing the valve, where current required to open or close the valve does not exced 2A, where voltage required to open or close the valve does not exceed 230 V

2.11. Alarm function If regulation function is not required, relay output can be used to generate alarm signal. Relay

contacts will close, if: - selected parameter value exceeds measurement limits,

- selected parameter exceeds maximum allowed value, - selected parameter falls below minimum allowed value. Any parameter listed in paragraph 2.10.1 can be used to generate alarm signal. 2.12. Supply voltage Internal baterry* 3,6 VDC, D-cell lithium

Replacement interval not less than 10 years,

Mains supply AC (502) Hz, 230 V 1015 ,

Power supply < 3 VA (only for meter, consumption of energy per year to 26,3 kWh) Power supply < 15 VA (for meter and extra sensors,

consumption of energy per year to 131,5 kWh) The meter readings are not available, if meter power supply is disrupted. Readings will be available again, as soon as the power supply will be restored.

Page 13: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 13

Power supply for extra sensors Voltage for powering pressure or extra flow sensors +18 V 10 (only for meter with mains supply module) total current < 400 mA.

Voltage for powering extra flow sensors +3,6 V 10 , (only for meter with mains supply module) total current < 20 mA.

Voltage for powering extra ultrasonic flow sensors +3,6 V 10 , (for meter with supply from baterry) total current < 70 mkA.

NOTE: *

2.13. Mechanical data Dimensions of calculator 159 mm x 52 mm x 142 mm Dimensions of flow sensors According to Annex H Weight of calculator 0,5 kg. Weight of flow sensors According to table 2.7 Table 2.7

Permanent flow rate in m3/h (connection type) Mass*, not more than, kg 3,5 ( G1 ¼ B) 3,0 6 ( G1 ¼ B) 3,0 10 (G2 B ) 4,0 15 (DN50 ) 10,0 25 (DN65 ) 13,0 40 (DN80 ) 15,0

60 (DN100 ) 18,0 NOTE: The mass of flow sensor is presented without mass of connecting cables. Maximum mass of cables is 8 kg (2x100 m) Envoronmental class Meets EN1434 class C Ambient temperature: Calculator at +5 oC to +55 oC (non-condensing,indoor installation) Flow sensors at -30 oC to 55 oC Relative humidity < 93 Mechanical environment class: M1

Electromagnetic environment class: E2

Protection class of calculator enclosure IP65 Protection class of flow sensor enclosure IP65 (IP67 – by special ordering)

Functional limitations, when the meter is powered from internal batteries: 1. It is impossible to use relay regulator/alarm outputs function 2. It is impossible to use frequency and current outputs function 3. Unavailable pressure sensor power supply from the meter 4. Automatic restriction of operating time of communication interface (wire and optical) till 80 minutes per month

Page 14: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 14

3. ACCESSORIES AND SUB-ASSEMBLIES OF HEAT METER

Required sub-assemblies and accessories may be delivered according to the particular application and flow measurement scheme, as defined by the customer (listed in Table 3.1): Table 3.1 Item Amount, pcs 1. Heat meter calculator IFX-M4-04 1 2. Technical description, user manual for heat meter IFX-M4-04 1 3. Mounting kit for heat meter calculator 1* 4. Ultrasonic flow sensors 1…2* 5. Internal baterry 3,6 V 1* 6. Internal 230 V mains power supply module 1* 7. Communication module SKS43 with M-bus interface 1* 8. Communication module SKU45 with M-bus, CL, RS-232 interfaces and two current outputs

1*

9. Communication module SKU46 with M-bus, CL, RS-232 interfaces and two pulse outputs

1*

10. Communication module SKS48 with special interface, compatible with RS-232 1* 11. Temperature sensors PL-6, Pt500 (two wire connection method) 1…3* 12. User manual for temperature sensors type PL-6 1* 13. Pressure sensors MBS 2* REMARKS: 1. “*” – required options selected by the customer, 2. Heat meter may be equipped with other types of temperature sensors, if they correspond to requirements listed in paragraph 2, requirements of EN1434 standard and have the EC-type examination certificate by Directive 2004/22/EC 3. Heat meter may be equipped with other types of pressure sensors, if they correspond to requirements listed in paragraph 2.

4. OPERATING PRINCIPLE

Ultrasonic heat and water meters IFX-M4-04 is multichannel programmable microprocessor measuring device which consists of electronic unit (calculator) and the initial flow (up to 2), temperature (up to 3) and pressure (up to 2) sensors.

The flow measuring principle is based on ultrasonic measurement method. Fluid volume is calculated according the formula: V KH * KM * (1/t+ - 1/t-) *T ,

where: V - measured fluid volume, m3; T – time of integration, s; t+ - measured downstream time of flight of ultrasonic pulse, s; t- - measured upstream time of flight of ultrasonic pulse, s; KH – hydrodynamic correction factor; KM –coefficient that depends on the flow sensor dimensions. The liquid temperature is measured with standard platinum resistance temperature sensors Pt500 or Pt1000. Pairs of temperature sensors with 2-wire or 4-wire connection method for measurement temperatures on flow and return pipelines are used. Flow and return temperature sensors can be replaced only in pairs. The temperature sensor T3 (if not used for calculation of thermal energy ) the user can activate and use for other technological measurements or for regulation function.

Thermal energy is calculated using formulas provided in Annex A. Additional inputs of flow V3, V4 and pressure sensors, which are not used for thermal energy measurement, can be used (or not), for the control of other parameters.

Values of the measured and calculated patameters are shown on the display.

Page 15: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 15

5. MARKING AND SEALING 5.1.Marking of meter

Marking of calculator: There are following information on the front panel of calculator - manufacturer’s trade mark , identity marking (type designation and type number), serial number, year of manufacture, EC-type examination certificate number, limits of the temperature,limits of the heat conveying temperature, limits of the temperature diferences, type of temperature sensors (Pt500), the limiting values of the flow rate(qi,qp,qs), flow sensor installation site (flow or return pipe), accuracy class, environmental class by LST EN1434-1, electromagnetic and mechanical environmental class, enclosure protection class, the maximum admissible working pressure (PN class), voltage level for external power supply, conventional designation of the applied measurement scheme. Numbers of terminal pins are marked close to the terminal Marking of flow sensor: There are following information on the flow sensor- manufacturer’s trade mark , year of manufacture, serial number, nominal diameter, arrow indicating the direction of the flow. 5.2.Security seals:

Manufacturer’s seals:

- One warranty seal (the adhesive seal-sticker) on the one fixing bolt of electronic module under protective cover (see Fig.8.1) .

- Calibration (verification) seal on the one bolt of protective cover of electronic module inside the calculator (see Fig.8.1).

- Seals on the screws of protective cover of flow sensor ( Sticker or hanging seal according Annex E, Fig. E1..E4).

Mounting seals: - One or two hanged seals on the fixers of junction of the top and botton part of the calculator

(see Annex D) - Seals on the protective cover and mounting bolt of temperature sensors (see Annex F,

Fig.1...2).

6. INSTALLATION

6.1. Basic requirements Before installing the device:

- check if all parts listed in the documentation are available, - check if there are no visible mechanical defects, - check if there are valid labels of manufacturer and certification authority.

Only qualified personnel may install the equipment, following the requirements listed in this document, in technical documentation of other system components and in heat meter installation project

Mechanical mounting Mounting of calculator

Heat meter calculator may be installed in heated premises, on vertical surface. It may not be exposed to direct sunlight. Outline and mounting dimensions are provided in Annex D

Calculator can be mounted in five different ways: - Wall mounting, without possibility sealing of mounting (see Annex D, fig. D2) - Wall mounting, with possibility sealing of mounting (see Annex D, fig. D3) - Mounting on standard DIN-rail(see Annex D, fig. D4)

Page 16: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 16

- Panel mounting (see Annex D, fig. D5) - Direct mounting on ultrasonic flow sensors, when the flow sensors are equipped with special holders (see Annex D, fig. D6).

Note: For water heating temperatures above 90 oC, the calculator must be mounted on the wall. Adapter plate according to figure 8 of EN1434-2:2007 for wall mounting of calculator can be used (see Annex D, fig. D1.1) Important: It is forbidden to attach the calculator directly to a wall if there is a risk that on walls can be condensed humidity or temperature of a surface of a wall can fall lower than 5 °. In this case, it is recommended to attach the calculator so that between it and wall surfaces there was an air gap not less than 5 cm. Mounting of ultrasonic flow sensors

Outline and mounting dimensions of ultrasonic flow sensors are provided in Annex E. Requirements for flow sensor installation in pipeline:

- For flow sensors G1 ¼ (with permanent flow rate qp = 3,5 m3/h and 6pq m3/h):

- no requirements for straight pipeline length in upstream and downstream directions. - For flow sensors with permanent flow rate qp 6 m3/h:

- upstream straight pipeline length must be not less 5DN and downstream straight pipeline length must be not less 3DN when flow disturbance is elbow type (1 or 2 elbows);

- upstream straight pipeline length must be not less 10DN and downstream straight pipeline length must be not less 3DN when flow disturbance is valve, pump or similar disturber;

Avoid the flow sensor installation near after the pumps which can cause cavitations. Flow sensor can be mounted both vertically and horizontally in pipelines. Vertically mounting of the

flowmeter is allowed only if flow direction in the pipeline is from down to up. The direction of the sensor installation (is indicated with the arrow on the label of flow sensor) must mach with the flow direction in pipeline.

The flange gaskets must mach with the pipe diameter. During the installation gasket must be exactly centered with the center of the pipe cross-section to avoid sticking out gaskets inside the pipe.

Mounting of temperature sensors Temperature sensors are mounted by head upwards, is perpendicular to the pipe axis or inclined

by 45 ° angle on fluid flow direction so that the sensing element has been inserted in medium at least up to the pipe axis or beyond (as shown in Annex F).

Electrical wiring

Electrical installation of heat meter is performed according to selected measurement scheme (Annex B) and appropriate installation diagrams (Annex B), also according to technical requirements for other system components. Description of connection terminal pins is provided in Annex C.

The signal wires can be connected to the calculator only after full installation of the meter. It is forbidden to change length of a cable. Temperature sensor connection: 2-wire or 4-wire connections could be used. Using 4-wire connection schemes – the connection must be performed with the grounded cables with signal wires with the cross-section not less than 0.12 mm2.

Using 2-wire connection schemes - the connection must be performed with the grounded cables with total resistance of signal wires not more than 0.5 and the cable length difference no more than 2

Page 17: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 17

Before installation check that the temperature sensors are paired with each other (T1 to T2). If cable length between calculation unit and sensors exceeds 5 m, shielded cables have to be used. Cables should be run through rubber seal caps and anchored with clamps. Four-, three- or two-wire cable should be used respectively. Cable shield should be connected to appropriate terminal pins (see diagram in Annex B) or to any free contacts marked with symbol “ “or is clamped with metal clips in an installation time. At connection with the grounded cables it is necessary in addition one of free contacts „ “to connect to a contour of grounding of a building a copper wire with section (0,5... 1,0) мм2. It is forbidden to wire signal cables nearby (less than 5 cm) with power cables or cables of other devices.

6.2. Setting up the configuration The heat meter is universal device for measurement of supplied (consumed) heating energy. The

calculator has to be customized for the particular application, putting into account the type of heating system, also types of flow, temperature and pressure sensors. After placing an order, calculating unit is adapted to one of several possible measurement circuits. Energy calculation formulas and measurement ciecuits are presented in Annex A. Flow, temperature and pressure channels, unused for heat energy measurement, cal be used to control other parameters. It is possible to select measurement units for flow measurement (volume units or mass units – according to measured media temperature).

The heat meter has to be programmed for the specific application using the control buttons , also the configuration button “SET” (under the lid, see Fig. 7.1) or with the PC.

To enter the configuration mode, open the calculator lid and press the button “SET”. Press the “SET” button once more to leave the programming mode.

When configuration (programming) mode is active, label “SET” is displayed in the upper right conner of the display. All parameters have to be programmed. The algorithm for setting up parameters, possible parameter limits and abbreviations are listed in Table 6.1. Table 6.1

Menu description LC Display example Value (Possible limits of change)

Serial number of meter *

Serial flow sensor number of 1st flow measurement channel*

Serial flow sensor number of 2nd flow measurement channel*

Customer number

0…999999

Real time calendar

The date format is <year>.<month>.<day >

Real time clock

The time format is: <hour>-<minute>-<second>

Page 18: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 18

Set day

The yearly set day format is: 12.31 (<month>.<day>), The monthly set day format is: --.30 (<day>) -- . -- - function is deactivated

Serial communication interface address

0…255

Data transfer rate via wired interface

(300…38400, 300E…38400E) bytes/s “E” –parity “Even” None “E” – no parity

Data transfer rate via optical interface

(300…9600, 300E…9600E) bitų/s “E” –parity “Even” None “E” – no parity

Next replacement date of the battery

The date format is <year>.<month>)

List of active temprature sensors (“1 2 3 “) and type of sensors*

Possible types: Pt500, Pt1000, 500П, 1000П

Type of 3-rd flow input (or OFF), minimal pulse period in ms, flow measurement units m3 (or t)

Flow input type: S-standard, E – with error control; L – with the "24 hour" pulse control; OFF – flow input not used

Type of 4-th flow input (or OFF), minimal pulse period in ms, flow measurement units m3 (or t)

Flow input type: S-standard, E – with error control; L – with the "24 hour" pulse control; OFF – flow input not used

Minimum flow rate value of 3-rd flow input, m3/h

Exponential form X.XXE-X For example: 1,00E-2 = 1,00*10-2 = 0,01 m3/h

Maximum flow rate value of 3-rd flow input, m3/h

Exponential form X.XXE X For example: 3,60E2 = 3,60*102 = 360 m3/h

3-rd flow input pulse value, m3/pulse

Exponential form X.XXE-X For example: 1,00E-2 = 1,00*10-2 = 0,01 m3/pulse

Minimum flow rate value of 4-th flow input, m3/h

Exponential form X.XXE-X For example: 1,00E-2 = 1,00*10-2 = 0,01 m3/h

Maximum flow rate value of 4-th flow input, m3/h

Exponential form X.XXE X For example: 3,60E2 = 3,60*102 = 360 m3/h

4-th flow input pulse value, m3/pulse

Exponential form X.XXE-X

For example: 1,00E-2 = 1,00*10-2 = 0,01 m3/pulse

Minimum value of temperature difference 1 - 2

Page 19: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 19

Current limits of pressure sensors (pressure inputs)

pre-programmed pressure value: 0-20C – corresponding 0…20 mA, 4-20C - corresponding 4…20 mA, 0-5C - corresponding 0…5 mA, OFF – pressure sensors not used

Minimum rated value of pressure sensors, kPa

(0,0…25000) kPa

Maximum rated value of pressure sensors, kPa

(0,0…25000) kPa

The pressure value used in calculations of heat *, kPa

(0,0…9999,9) kPa If specify "0.0 kPa" - for calculation is used the measured pressure value (p1 – for flow pipe , p2–for return pire)

Thermal energy units *

MWh (kWh), Gcal ar GJ

Measurement units of quantity of a liquid of 1-th flow measurement channel

For choice: m3 or t

Measurement units of quantity of a liquid of 2-nd flow measurement channel

For choice: m3 or t

Report printing language and communication with the printer interface type

Report language: Prnt-P –Russian, Prnt-L – Lithuanian, Prnt-E –English. Communication with the printer interface type: 1-wire interface, 2-optical interface

Parameter, derivable to 1st pulse frequency output

MWh –thermal energy, m3- flow rate, kW-thermal power, oC –temperature, kPa-pressure, 1...4 -number of measurement channel, 1-2 difference

Parameter, derivable to 2nd pulse frequency output

MWh –thermal energy, m3- flow rate, kW-thermal power, oC –temperature, kPa-pressure, 1...4 -number of measurement channel, 1-2 difference

Regulation function and settings of regulable (controlled) parameter

OFF – regulation function is disabled, On1 or On2 – type of active operating mode, Regulable parameter: kW-power, oC – temperature, m3/h –flow rate, kPa-pressure. 1…3 – number of channel.

Mode On1 -lower limit (the minimum allowed value) for regulated parameter. Mode On2 - preset room temperature

kW –power, m3/h-flow rate, oC –temperature, kPa –pressure. 1...4 - number of measurement channel. 1-2 –difference

Page 20: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 20

Mode On1 - upper limit (the maximum allowed value) for regulated parameter Mode On2 - adaptation coefficient

kW –power, m3/h-flow rate, oC –temperature, kPa –pressure. 1...4 - number of measurement channel. 1-2 –difference

Valve runtime, s

0…999 s

Pause between actuation period (actuation period is equivalent to 1% of the preset valves runtime, s

0…999 s

Keeping the accuracy of preset flow temperature (hysteresis), oC (only for mode On2)

oC

the maximum allowed value of flow temperature (threshold value of protection), oC (only for mode On2)

oC

Software version number*

LCD segment test*

Page 21: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 21

NOTES: 1. The displayed parameters list can be shorter depending on the selected modification, and a

meter configuration (parameters, inappropriate for the given configuration will not be shown). 2. Marked with "*" parameters values can be modified only by the manufacturer (replacement

possibility is protected by calibration seal). These parameters are displayed only for information

3. Parameters 23... 29 will be displayed only if the meter is completed with the mains supply module. It can be modified (changed) in "SET" and "INF" display modes

4. Displayed parameter values, for example. "1.00-2" are given in exponential form:

There: X.XX E XX

For example: value 1,25E-2 = 1,25*10-2 = 0,00125.

Parameters, listed in Table 6.1 should be set up as

shown in Fig. 6.2: Select the parameter to be modified, then press

hold button until parameter value starts blinking – and alteration mode is entered.

Select required position by pressing button . Shortly pressing button , set the required value (or select from list). Save changes by holding button pressed and return to display mode.

Parameterization (configuration) procedure Recommendations for the configuration change Measurement circuits, energy calculation algorithms, type of the temperature sensors, value of pressure for thermal energy calculation and numbers of flow sensors should be checked according to individual heat meter data (see Paragraph 13). If are required by measurement circuit, other parametres of a configuration should be made active and entered:

Value of exponent

Value of base

Page 22: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 22

The additional flow inputs (V3 and V4) are activated, the inputs parameters values corresponding values of the water meters which will be connected to these inputs are set: pulse value, minimal and maximum flow rate, type of input pulses and the minimal possible pulse frequency period. The additional pressure inputs are activated, the inputs parameters values corresponding values of the pressure sensors, which will be connected to these inputs are set: limits of current, minimal and maximum pressure orresponding to current limits. The additional tempertature input (T3) are activated. If it is used on regulation mode „On2“ – it is obliged to make active the temperature measurement channel T3 for measurement of outdoor temperature. The individual parameters for a pulse / frequency output should be selected from the list The regulation function are activated, operating mode is selected from list, and the parameters values are entered. If necessary a customer number is entered. The communication interfaces settings are entered: M-bus adress, data transfer rate, parity. Report printing language and communication with the printer interface type are selected from list If necessary real time clock and calendar readings are corrected

The suggested next battery replacement date is set: (or current date plus 12 years for mains power supply version). Suggested battery replacement date is calculated by adding estimated battery operation time to the current date. Estimated battery operation time is given in the Table 6.2:

Table 6.2 Number of flow sensors powered from calculator battery Battery operation time, years

- 10 1 (extra current to 35 mkA) 8 2 (extra current to 70 mkA) 6

Configuration of heat meter is possible via optical (or Wire) interface and in conjunction with the specific configuration programme.

6.3. Setting up jumpers For battery supply: If voltage 3,6 V from the pin “19” and “22” is used to power extra flow sensors V3 and V4, the jumper (beside terminal block) should be conjunct. For mains supply: If voltage 3,6 V from the pin “19” and “22” is used to power extra flow sensors V3 and V4, the jumper (beside terminal block) should be compulsory disjunct.

If the device is equipped with universal interface module (including M-bus, CL, RS-232 interfaces and two current or pulses outputs):

- M-bus, CL or RS-232 interface is activated by plugging in the jumpers “CL – M-bus – RS-232” in such way, that required interface type appears beside the terminal pins “46,,,48”. Marking on the jumper board will show the functional description of the pins.

- required current limits of the 1-st and 2-nd current outputs are set by switching the jumpers “I1” and “I2” into one of the following positions: “0-5 mA”, “4-20 mA” or “0-20 mA”.

- required type of pulses output are set by switching the jumpers „+P1 +P2 GND“: Galvanically isolated passive pulses outputs - not jumpers

Galvanically isolated active (+24 V) pulses- „GND“, “+P1” ir “+P2”

Page 23: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 23

6.4. Optional modules. Exchanging of modules Heat meter may be delivered with 230 V, 24 V power supply module or 3,6 V battery power supply and one of the external communication modules. Possible options are listed in the paragraph 3. Communication module types and specific application restrictions are described in the Table 7,2. Table 7.2

Communication module type Purpose, functions Application restrictions SKU45

Universal with two current outputs

User may choose one of three available interfaces (M-bus, CL, RS-232). Two current outputs are available, with user-selectable current limits ( “4-20 mA” or “0-20 mA”).

Only for 230 V power supply

SKU46 Universal with two pulse

outputs

User may choose one of three available interfaces (M-bus, CL, RS-232). Two pulse outputs are available, with user-selectable type - galvanically isolated passive pulses or not galvani-cally isolated active (+24V) pulses

Only for 230 V power supply

SKS43 M-bus

Allows connecting the device to M-bus network (up to 254 devices in parallel) in distance up to 2 km

Suitable for all power supply options

SKS48 Special type, compatible with

RS-232 interface

Distance up to 15 m. Designed to connect equipment with RS-232 interface, where RTS +9...+12 V and DTR -9...-12 V signals are used

Suitable for all power supply options

SKSRS485 RS485

Connecting to RS485

Only for 230 V power supply

Mains supply or battery module is in the bottom part of the calculator, on the right side beside the terminal block, while communication interface module is on the left side. Modules can be exchanged on-site, by opening the lid, unscrewing the appropriate fixing bolt and pulling out the module from the connector.

Disconnect the equipment from mains supply before replacing modules!

6.5. Verification of installation and set-up

After installing the heat meter, let measured fluid flow through the flow sensor, and switch on the power supply. Measured parameter values should be indicated on the display, if the heat meter (calculating unit, flow, pressure and temperature sensors) is installed correctly. If measured parameter values are not displayed correctly, it is necessary to verify the installation.

7. OPERATION 7.1. Control buttons The information can be displayed using two control buttons and which are on the top of

the calculator(see Fig. 7.1). Configuration button “SET” is under the cover and it is protected by mounting seal (see Fig.7.1). Clicking on this button you can activate configuration and fast verification modes.

Page 24: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 24

Fig. 7.1 Front of the calculator, cover closed, without seals and view at an open cover 7.2. Display function The calculator is equipped with 8-digits LCD (Liquid Crystal Display) with special symbols to

display parameters, measurement units and operation modes. The following information can be displayed: - integral and instantaneous measured parameters, - archive data, - device configuration information, - report printing control information. The display constantly shows the total thermal energy. Other data can be displayed sequentially using the control buttons. Display description

INT PAR LOG PRN INF

Key to symbols Description 1. Groups of parameters Group of displaying corresponding parameters (display level) 2. Number and group of indicated parameters 1…5 Number of energy tariff or number of measurement channel (volume,

flow, temperature, pressure) 1-2 Differences (difference of heating medium quantity (M1-M2), (V1-V2)

or temperature difference (1-2)

1. Groups of parameters and

additional information

3. Operation mode

4. Measurenent units

2. Parameter numbers and group numbers

Control buttons and

Configuration button“SET”

Calibration seal

Manufacturer‘swarranty seal

Page 25: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 25

Key to symbols Description 3. Operation mode H Hourly archive data is being printed (displayed) D Daily archive data is being printed (displayed) M monthly archive data is being printed (displayed) TEST Test mode SET Parameterization mode 3. Operation mode H Hourly archive data is being printed (displayed) D Daily archive data is being printed (displayed) M monthly archive data is being printed (displayed) TEST Test mode SET Parameterization (configuration) mode 4. Measurement units m3 (t) Water volume (mass) m3/h Flow rate kPa Pressure o C Temperature, temperature difference GJ, Gcal, MWh, kWh Energy kW Power h Hours 5. Additional information R Relay output is activated R< Parameter value exceeds maximum permissible value (for relay outputs) <R Parameter value is below minimum permissible value (for relay outputs) ^ Relay P1 is closed (increase) v Relay P2 is closed (decrease) MIN The minimum value MAX The maximum value

Menu structure

The display in user level is arranged in five levels (loops): User levels Identification symbols 1st level. Displaying integral parameters values

▼ INT PAR LOG PRN INF

2nd level. Displaying (viewing) instantaneous parameters values

▼ INT PAR LOG PRN INF

3rd level. Displaying (viewing) set day parameters and archive data values

▼ INT PAR LOG PRN INF

4th level. Printing reports by standard printer

▼ INT PAR LOG PRN INF

5th level. Displaying configuration settings and programming relay output parameters

▼ INT PAR LOG PRN INF

Press and hold ( 3 s) button or button to move to the next display level.

Page 26: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 26

To view data in the same display level press shortly ( 3 s) buttons or . The display will switch automatically to the highest level of displaying current values of integral parameters, or – if at least one error has been detected – error code will be displayed after 5 minutes of inactivity.

Fig. 7.2. Selecting the display level

Arbitrary symbols, used in the diagrams:

At Service level it is provided two service modes: Service mode Identification symbols 6th level. Parameterization mode (SET) SET

▼ ▼ ▼ ▼ ▼ INT PAR LOG PRN INF

7th level. Test mode (TEST)

TEST ▼ ▼ ▼ ▼ ▼ INT PAR LOG PRN INF

To enter the parameterization (configuration) mode (6th level), open the lid and press “SET”

button. Label “SET” is displayed in the upper right side of the display. In this mode by means of control buttons or via optical interface, the use of personal computer

with special software, you can change the configuration of the meter (see section 7.2). By short pressing “SET” button you can leave the parameterization mode and enter to test mode

(7th level). Press the “SET” button once to leave the test mode and confirm return to the 1st level.

On Each level the list of displayed parameters may be reduced and the parameter listing order can be changed (on SET mode, using the computer with the special software, joining via the optical or wire communication interface) depending on the user requirements. 7.2.2. Displaying integral parameter values (level 1)

Accumulated total energy ( ∑E )

Accumulated Energy component (E1)

Accumulated Energy component (E2)

Accumulated volume V1 or mass M1

PAR LOG PRN INF INT

- left button, - right button, - long press ( 3 s) - short press( 3 s)

Page 27: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 27

Accumulated volume V2 or mass M2

Accumulated volume V3 or mass M3

Accumulated volume V4

Operating hours

Operating hours without energy calculation error

Significant fault (stopping energy calculation) code E1 In the case of the error - it is always displayed on the top

Transistory fault code Er2

Parameter values are displayed in sequence, shortly pressing buttons: - next parameter, - previous parameter

Sequence of displayed parameters may vary depending on selected measurement scheme and number of installed sensors.

Press and hold ( 3 s) button to move to the next display level(PAR), and button to move

to displsy level (INF). The display will switch automatically to the highest level of displaying current values of integral

parameters, or – if at least one error has been detected – error code will be displayed after 5 minutes of inactivity.

Error codes description The meter continuously analyzes operational modes, diagnoses and informs of errors in system

work Significant faults Er1

If significant faults Er1 are detected in work of heating system, energy calculation is stopping and these errors are displayed via 6 character error code:

Status of temperature sensor T1

Status of temperature sensor T2

Status of temperature sensor T3

Status of flow sensor V1

Status of flow sensor V2

Power supply voltage status (only for archive)

Page 28: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 28

Detailed description of significant faults codes Er1 Error display Error description Er1: 000000 No error. Normal mode Er1: 000001 Fault in temperature 1 measuring circuit*: temperature difference 1-2 < dmin

(dmin – the minimum value of temperature difference) Er1: 000002 Fault in temperature 1 measuring circuit: temperature 1< 0 oC (or sensor has

short circuit) Er1: 000004 Fault in temperature 1 measuring circuit: temperature 1 > 180 oC (or sensor has

open circuit) Er1: 000010 Fault in temperature 2 measuring circuit*: temperature difference 1-2 < dmin

(dmin – the minimum value of temperature difference) Er1: 000020 Fault in temperature 2 measuring circuit**: temperature 2 < 0 oC (or sensor has

short circuit) Er1: 000040 Fault in temperature 2 measuring circuit**: temperature 2 > 180 oC (or sensor has

open circuit) Er1: 000200 Fault in temperature 3 measuring circuit**: temperature 3 < 0 oC (or sensor has

short circuit) Er1: 000400 Fault in temperature 3 measuring circuit**: temperature 3 > 180 oC (or sensor has

open circuit) Er1: 002000 Fault in q1 measuring circuit*: flow rate q1< q1i (qi – the minimum allowable value

of flow rate) Er1: 004000 Fault in q1 measuring circuit*: flow rate q1 q1s (qs – the maximum allowable value

of flow rate) Er1: 008000 Fault in q2 measuring circuit: Fault in flow measuring channel Er1: 020000 Fault in q2 measuring circuit *: flow rate q2< q2i (qi – the minimum allowable value

of flow rate) Er1: 040000 Fault in q2 measuring circuit *: flow rate q2 q2s (qs – the maximum allowable value

of flow rate) Er1: 080000 Fault in q2 measuring circuit: Fault in flow measuring channel Er1: 100000 No supply voltage (only for data logger) Note: * - only when non-standard energy calculation algorithm is applied ** - only in cases where the temperature sensors T2, T3 are used to calculate the thermal energy Active error codes are added and simultaneously displayed Transistory fault Er2 If transistory faults Er1 are detected in work of heating system, energy calculation do not stop and these errors are displayed via 5 character error code:

Status of temperature sensor

Status of flow sensor V1

Status of flow sensor V2

Status of flow sensor V3

Status of flow sensor V4

Page 29: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 29

Detailed description of transistory faults codes Er2 Display Description Er2: 00000 No error. Normal mode Er2: 00001 Flow q1 flow in reverse direction Er2: 00002 Flow value q1< q1i (the minimum allowable value of flow rate) Er2: 00004 Flow value q1 q1s (the maximum allowable value of flow rate) Er2: 00008 Flow sensor V1 is not filled by a liquid Er2: 00010 Flow q2 flow in reverse direction Er2: 00020 Flow value q2< q2i (the minimum allowable value of flow rate) Er2: 00040 Flow value q2 q2s (the maximum allowable value of flow rate) Er2: 00080 Flow sensor V2 is not filled by a liquid Er2: 00100 On input V3 more than 24 hours do not arrive pulses * Er2: 00200 Flow value q3< q3i (the minimum allowable value of flow rate) Er2: 00400 Flow value q3 q3s (the maximum allowable value of flow rate) Er2: 00800 Short circuit V3 *** Er2: 01000 On input V4 more than 24 hours do not arrive pulses * Er2: 02000 Flow value q4< q4i (the minimum allowable value of flow rate) Er2: 04000 Flow value q4 q4s (the maximum allowable value of flow rate) Er2: 08000 Short circuit V4** Er2:10000 Temperature difference 1-2 < dmin Er2:20000 Temperature difference 1-2 < 0 oC Er2:40000 Temperature 3 <- 40 oC or sensor has short circuit *** Er2:80000 Temperature 3 > 180 oC or sensor has open circuit *** Er2:50000 At the same time there are two error: “10000” and “40000” Er2:60000 At the same time there are two error: “20000” and “40000” Er2:90000 At the same time there are two error: “10000” and “80000” Er2:A0000 At the same time there are two error: “20000” and “80000” Note: * - only when flow input type “L”is on (“24 hours pulse control”) ** - only when flow input type “E”is on (“short circuit control”) *** - only when temperature measurement chanell T3 is on Active error codes are added and simultaneously displayed

7.2.3. Displaying (viewing) instantaneous (informative) parameters values (level 2) Parameter values are displayed in sequence, shortly pressing buttons: - next parameter, -

previous parameter

Thermal power

Flow rate q1. Negative flow rate is marked with minus (-) in the display (measurement units - m3/h or t/h)

Flow rate q2. Negative flow rate is marked with minus (-) in the display (measurement units - m3/h or t/h)

Flow rate q3

Page 30: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 30

Flow rate q4

Measured fluid temperature 1

Measured fluid temperature 2

Measured fluid temperature 3

Preset temperature 4

Measured temperature difference 1-2

Measured fluid pressure p1

Measured fluid pressure p2

Sequence of displayed parameters may vary depending on selected measurement circuit and

Sequence of displayed parameters may vary depending on selected measurement scheme and number of active sensors.

Press and hold ( 3 s) button to move to the next display level (LOG), and button to move to displsy level (INF).

The display will switch automatically to the highest level of displaying current values of integral parameters, or – if at least one error has been detected – error code will be displayed after 5 minutes of inactivity.

7.2.4. Displaying (viewing) set day parameters values and archive data values (level 3)

7.2.4.1. When set day and archive data viewing mode (“LOG”) is entered (and set day function is active), set day time stamp value (The date format is <day>.<month>.<year>) will be displayed in turn with relevant parameter value (accumulated energy value) :

By shortly pressing button you can select parameter value for viewing. By shortly pressing button you can select for viewing previous set day parameters values

(previous months or previous years data depends on configuration of calculator)

To display archive data (see p.8.2.4.2) press and hold button . If a set day function is inactive - archive data review mode (p.8.2.4.2) will be displayed

immediately when you enter to level „LOG“.

Page 31: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 31

7.2.4.2 When archive data viewing mode is entered, time stamp value will be displayed:

(The date format is <hour> <day>.<month>) in turn with relevant parameter value and parameter group ID (in three seconds interval). For example, alteration of E1 during 19-th of January, 13-th hour:

Press and hold button while time is displayed to select required time interval: date is

displayed, and first character starts blinking (it is possible to select required time interval now). Move cursor (blinking character) in closed circle by shortly pressing button . Alterate selected value by shortly pressing button . Confirm the selection and return to previous display level by holding down button .

Select parameter group by shortly pressing button while parameter is displayed (display zone D):

H – hourly values increase; average hourly pressure and temperature values group with registered error and error occurrence time,

D – daily values increase; average daily pressure and temperature values group with registered error and error occurrence time,

M – monthly values increase; average monthly pressure and temperature values group with registered error and error occurrence time,

[no symbol] – group of absolute parameter values at the real time point.

Shortly pressing button while parameter is displayed will allow to select desired time point or interval. List of parameters is presented in the Table 7.1:

Table 7.1 Symbol on the upper

part of display (Zone C)

Measurement unit (parameter symbol)

Zone E

Parameter code Zone A

Parameter value Zone B

Σ MWh (Gcal, GJ) - Total thermal energy E 2 MWh (Gcal, GJ) - Thermal energy component E1 1 t (m3) - Fluid mass (volume) M1 (V1) 2 t (m3) - Fluid mass (volume) M2 (V2)

1-2 t (m3) - Fluid mass (volume) difference M1-M2 (V1-V2) 3 t (m3) - Fluid mass (volume) M3 (V3) 4 t (m3) - Fluid volume V4 1 oC - Average (hourly, daily or monthly) temperature 1 2 oC - Average (hourly, daily or monthly) temperature 2 3 oC - Average (hourly, daily or monthly) temperature 3

Zone C Parameter number

Zone D Parameter group

Zone E Measurement units or parameter type

Zone A Parameter code

Zone B Parameter value

Page 32: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 32

1 kPa - Average (hourly, daily or monthly) pressure p1 2 kPa Average (hourly, daily or monthly) pressure p2

1 Er: Error code Er1 (total sum) 2 Er: Error code Er2 (total sum) h Device run-time h A: Operating hours (without energy calculation error)

1-2 h 1: Time, when temperature difference (1-2)<dmin

1 h 2: Time, when flow rate q1<q1min 2 h 2: Time, when flow rate q2<q2min 3 h 2: Time, when flow rate q3<q3min 4 h 2: Time, when flow rate q4<q4min 1 h 4: Time, when flow rate q1>q1max 2 h 4: Time, when flow rate q2>q2 max 3 h 4: Time, when flow rate ai q3>q3 max 4 h 4: Time, when flow rate q4>q4 max 2 h 8: Failure time of flow measurement channel V2 3 h 8: Failure time of flow sensor V3 4 h 8: Failure time of flow sensor V4

To move to the next level - “PRN” - press and hold button .

7.2.5. Printing reports (level 4) Connect printer to calculator using external communication interface or optical communication

adapter. Printer serial port data transfer rate should be the same as defined in calculator settings. Printer should be set to condensed printing mode.

For printing report via wire interface – in configuration parameter “20” – to set value “1”, for printing via optical interface – to set value “2” (see table 6.1)

Fig. 7.3. Conection of printer via optical interface

Heat energy meter

Printer

Page 33: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 33

To enter report printing mode, press and hold button several times, until label “PRN” is reached. LCD will display the following:

Select blinking LCD zone (report type, time interval or heating system number) by shortly

pressing button . Define the following report options by shortly pressing button :

Key to symbols Description Report type Ac Printing summary report rP Printing monthly set day parameter values In Printing current values of integral parameters CF Printing device parameterization parameters RL Printing current parameter values Time interval H Printing hourly parameter values D Printing daily parameter values M Printing monthly parameter values System number 1 Printing report for heating system 2 Printing report for additional water meters

Holding down button will allow to select report starting date and time. LCD displays (h

mm.dd): Starting date and time should be defined. First character starts blinking. Press button to move

to another character (selected character starts blinking). Required value can be set by shortly pressing button . For hourly report starting hour, day and month should be defined. For daily report – starting day and month, for monthly report – only starting month should be defined.

Holding down button stores the selection, and report ending date selection mode will be activated. LCD displays (h mm.dd ) :

Report ending date and time is defined in the same way as describe above. Printing will start after holding down button one more time. While report is being printed,

blinking label “Print” will be displayed. Printing can be paused and started again (for example, to add paper) by shortly pressing button . If printing is paused, label “Print” will stop blinking.

To move to another menu level press and hold button . Press and hold button to stop printing in any time.

Report type

System number Time interval

Page 34: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 34

7.2.6. Displaying configuration settings and programming relay output parameters (level 5)

Displaying configuration settings Sequence of displayed parameters may vary depending on selected measurement scheme and

number of active sensors. Settings also are shown, how is indicated in the Table 7.1, only are not shown an inscription the

SET. Foe example:

Serial number

Parameter values are displayed in sequence, shortly pressing buttons: - next parameter, -

previous parameter Use configuration data viewing mode “INF” to view device configuration settings (programmed

parameters and operation modes) and – if regulation function is activated – to change relay output parameter values.

7.3. Programming relay output parameters in regulation mode

7.3.1. Configaration parameters with codes “23:” ..”29:” (Table 7.1) are dedicated for

programming relay output parameters. When information data inspection mode “INF” is entered, it is possible to activate or deactivate regulation function, also to choose regulated parameter and control relay output manually by shortly pressing buttons or and selecting the parameter “23:”.

When button is pressed for long time, regulation status symbol “On” or “Off” starts blinking. Shortly pressing button will activate “On1” , “On2”, or deactivate “Off” regulation function.

When the operation mode On1 is entered, shortly pressing button will activate regulated parameter selection mode (parameter will start blinking). Select regulated parameter code (see Table 7.1) by shortly pressing button .

If regulation mode is deactivated (“Off”), it is possible to control the regulated valve manually. Shortly press button - symbol “R” starts blinking. Pressing button will start closing the valve – symbol “vR” will be displayed. Pressing button one more time will start opening the valve – symbol “^R” will be displayed. Pressing button once again will switch off valve control – only symbol “R” will be displayed.

7.3.2. Programming relay output parameters in regulation mode On1 At work in this mode the regulator can maintain temperature in the established limits, forbid value

of temperature to exceed an admissible maximum limit, forbid value of temperature to fall below an admissible minimum limit or to form alarm signal at occurrence of such disturbances.

According to the procedure described in Section 7.1, if necessary, it is possible to change the upper limit of regulation parameter (setting code “25:”) or lower limit of regulation parameter (setting “24:”), full travel time for actuator valves (setting code“26:L”) and the speed of regulation – pause time in seconds between the valve opening (closing) of 1% of the full valve runtime (setting code“27:P”).

If value of parameter “27:P” is established equal to zero - at break of conditions the corresponding relay will be continuously connected (it can be used for alarm signal formation).

To move to menu level (“INT”) press and hold button .

Page 35: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 35

7.3.3. Programming relay output parameters in regulation mode On2 This mode of regulation is designed for automatic control of temperature Т1 for maintenance of

the room temperature (setting "24"), depending on the changing of the outdoor temperature (measured by temperature sensor T3) and of adaptation factor value of building (setting "24").

Recommended value of parameter „25:“ is 15. Settings "26", "27" set as in the mode On1 (see p. 8.3.2

Only for mode On2 is used: - parameter „28:“ - for maintenance of accuracy of flow temperature (hysteresis). Recommended

value of maintenance accuracy is 0,5...1 ºC (Reducing its value, frequency of opening/closing of the valve increases)

- parameter „29:“ - for setting of the maximum admissible limit of flow temperature Recommended value is 10 ... 20 ° C greater than the possible maximum working flow

temperature. This parameter is intended to limit the flow temperature at failure of temperature sensor or

erroneous settings case.

7.4. Activating test mode

In test mode it is possible to achieve precise results within short measuring time. When test mode is activated, calculation process is stopped and the meter readings are saved in

memory. After return to normal mode, the original values from before the test are displayed again. Test mode is activated by short double pressing configuration button „SET“.“TEST” label is

displayed on the upper part of LCD. In test mode by shortly pressing button , you can select required parameter:

Energy ∑E Mass M1 Temperature difference Θ2 Energy E1 Mass M2 (module) Temperature Θ3 Energy E2 M3 Thermal power P Volume V1 Number of pulses N3 Pressure p1 Volume V2 Number of pulses N4 Pressure p2 VolumeV3 Temperature Θ1 VolumeV4 Temperature Θ2

Volume of liquid can be simulated automatically by the calculator, Provides automatic verification mode (For definition of measurement error of energy, without

measurement error of flow), when the meter is simulating water quantity and calculate the quantities of energy, according to the measured temperature (and pressure).

The automatic test mode can be used, when flow sensors are not connected or not filled by water.

Testing time is 100s. Shortly pressing the button will imitate flow pulses: V1 = 100000, V2 = 50000, V3 =

100000, V4 = 100000 (in volume units, displayed on LCD) During the test, blinking label „TEST“will be displayed. After the 100 s label “TEST” will stop blinking. Shortly pressing the button you can read test

results.

Page 36: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 36

7.5. Remote data reading For data transmission from meter it can be used optical interface ( The optical head is placed on

the front panel of the calculator, as shown in fig.8.3 and is connected to RS-232 interface of reading device) or any other wire serial interface, depending on the interface module is completed (see Table 7.2) can be used.

Data collection from meters can be realised via PC, via telephone modem, via GSM modem, via Internet, and so on.

The scheme of meter connection to the computer is presented in Annex B, Fig. F4. Modem or printer connection scheme – in Annex B, Fig.B5.

Restriction of operating time (only for battery supply version): -operating time after forced activation with any control button not more than 5 min. -total time of sending and receiving data per month not more than 80 min (interface is blocked

after declime of time limit. It can be unblocked after forced activation with any control button not more than for 5 min).

8. VERIFICATION

Metrological control of heat meter parameters is performed according to requirements defined in

EN 1434-5. 9. TRANSPORTATION AND STORAGE REQUIREMENTS

Requirements for safe transportation and storage of temperature and pressure sensors are provided in relevant technical documentation.

Packed equipment may be transported in any type of covered vehicle. Equipment should be anchored reliably to avoid shock and possibility to shift inside vehicle. Equipment should be protected against mechanical damage and shock. Equipment should be stored in dry, heated premises, where environment temperature is not lower than +5 oC. No agresive chemical substances should be stored together because of corrosion hazard.

10. WARRANTY

Manufacturer gives the warranty that equipment parameters will meet the technical requirements, listed in the paragraph 2 of this document, if transportation, storage and operation conditions will be followed. Waranty period - 12 months from bringing into operation, but not more than 18 months from manufacturing date.

Page 37: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 37

Annex A

Measurement schemes and energy calculation formulas

Application type Energy calculation formula For closed heating systems

U1 - Meter for heating. Flow sensor in flow pipe

E=V11(hT1-hT2) M1 =V11

U2 - Meter for heating. Flow sensor in return pipe

E=V12(hT1-hT2) M1 =V12

U1F - Meter for heating with leakage detection option The flow sensor in flow pipe

E=V11(hT1-hT2) M1 =V11 M2 =V22

U2F- Meter for heating with liquid leakage detection option. The flow sensor in return pipe

E=V22(hT1-hT2) M1 =V11 M2 =V22

T1

T2

IFX- M4-04-U2F

V2 p2

V3

V4 V1

p1

T1

T2

IFX- M4-04-U1F

V2 p2

V3

V4 V1

p1

T1

T2

IFX-M4- 04-U2

V1 p2

V3

V4 p1

T1

T2

IFX- M4-04-U1

p2

V3

V4 V1

p1

Page 38: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 38

Annex A Application type Energy calculation formula

For closed heating/cooling systems U1L – Meter for heating and cooling. The flow sensor in flow pipe

∑E = E1 + E2 than Θ1 > Θ2: E1=V11(hT1-hT2), E2=0 than Θ1< Θ2: E2=V11(hT2-hT1), E1=0 M1 =V11

U2L - Meter for heating and cooling. The flow sensor in return pipe

∑E = E1 + E2 than Θ1 > Θ2: E1=V12(hT1-hT2), E2=0 than Θ1< Θ2: E2=V12(hT2-hT1), E1=0 M1 =V12

T1

T2

IFX- M4-04-U2L

V1 p2

V3

V4 p1

T1

T2

IFX- M4-04-U1L

p2

V3

V4 V1

p1

Page 39: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 39

Annex B Electrical wiring diagrams

Fig. B1. Electrical wiring diagram Temperature sensors with 4-wire connection

T1 … T3 - temperature sensors V1 … V2 - ultrasonic flow sensors V3... V4 – water meters with pulse output p1 ... p2 -pressure sensors

Remark: 1. Only required for selected measurement scheme sensors should be connected (see Annex A)

IFX- M4-04

Page 40: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 40

Annex B

Fig. B2. Electrical wiring diagram Temperature sensors with 2-wire connection

T1 … T3 - temperature sensors V1 … V2 - ultrasonic flow sensors V3... V4 – water meters with pulse output p1 ... p2 -pressure sensors

Remark: 1. Only required for selected measurement scheme sensors should be connected (see Annex A)

IFX- M4-04

Page 41: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 41

Annex B

Fig. B3. Wiring diagrams for connecting of the meter to the line voltage 230 V and for connecting of the regulating valve.

Valve power supply and meter supply is 230 V

Fig. B4. Direct connection of the meter to the computer interface RS-232

Fig. B5 Direct connection of the meter to the modem or printer via interface RS-232

IFX-M4-04 IFX-M4-04

IFX-M4-04 IFX-M4-04

Page 42: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 42

Annex C Table C1. Numbering of terminals

Terminal number

Marking Signal description

60 V1-1 ( +) Output signal (OUT) from 1st flow sensor V1 (ultrasonic sensor 1) 61 V1-1( -) GND for output (OUT) of 1st flow sensor V1 (ultrasonic sensor 1) 62 V1-2 (+ ) Input signal (IN) from1st flow sensor V1 (ultrasonic sensor 2) 63 V1-2 ( - ) GND for input (IN) of 1st flow sensor V1 (ultrasonic sensor 2) 64 V2-1 (+ ) Output signal (OUT) from 2nd flow sensor V2 (ultrasonic sensor 1) 65 V2-1 (- ) GND for output (OUT) of 2nd flow sensor V2 (ultrasonic sensor 1) 66 V2-2 (+ ) Input signal (IN) from 2nd flow sensor V2 (ultrasonic sensor 2) 67 V2-2 (- ) GND for input (IN) of 2nd flow sensor V2 (ultrasonic sensor 2) 1* T1 Current terminal for 1-st temperature sensor “+I” 5 T1 Voltage terminal for 1-st temperature sensor “+U” 6 T1 Voltage terminal for 1-st temperature sensor “-U” 2* T1 Current terminal for 1-st temperature sensor “-I” 50* ╧ GND for temperature sensors 3* T2 Current terminal for 2-nd temperature sensor “+I” 7 T2 Voltage terminal for 2-nd temperature sensor “+U” 8 T2 Voltage terminal for 2-nd temperature sensor “-U” 4* T2 Current terminal for 2-nd temperature sensor “-I” 9 + +3,6V power supply voltage for flow sensor V3 , V4 53 V3 Pulse input signal from 3-rd flow sensor (IN) 11 ╧ GND for 3-rd and 4-th flow sensors 54 V4 Pulse input signal from 4-th flow sensor (IN) 56* T3 Current terminal for 3-rd temperature sensor “+I” 57 T3 Voltage terminal for 3-rd temperature sensor “+U” 58 T3 Voltage terminal for 3-rd temperature sensor “-U” 59* T3 Current terminal for 3-rd temperature sensor “-I” 82 ╧ GND for pressure sensor р1 68 P1 Input signal from 1-st pressure sensor (IN) 51 + +18 V power supply voltage for pressure sensors p1, p2 83 ╧ GND for pressure sensor р2 69 P2 Input signal from 2-nd pressure sensor (IN)

REMARK: * - only for 4-wire connection method of temperature sensors (K)

Page 43: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 43

Table C2. Numbering of additional module terminals Terminal number

Marking Signal description

Numbering of power supply module terminals 70 ˇ Relay output “decrease” 71 R GND for relay output 72 ˆ Relay output “increase” 26 ╧ Main ground 27 230V Mains power supply (230V AC) 28 230V Mains power supply (230V AC)

Numbering of communication module terminals 76 ┴ GND for currency outputs (module SKS-45) 77 Iout1 1st currency outputs (+) (module SKU45) 78 Iout2 2nd currency outputs (+) (module SKU45) 79 ┴ GND for pulse outputs (module SKS-46) 80 Puls 1 1st pulse outputs (+) (modulie SKU46) 81 Puls 2 2nd pulse outputs (+) (modulie SKU46)

24 (73) BUS M-bus line L1(CL – CL1 or RS-232 – Rx (input)) 25 (74) BUS M-bus line L2(CL – CL2 or RS-232 – Tx (output))

75 BUS GND for communication interface RS-232

Page 44: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 44

Annex D

Fig.D1. Mounting dimensions of calculator

D1.1. Adapter plate according to figure 8 of EN1434-2:2007 for wall mounting of calculator It can be used for wall mounting, if the aperture in the wall is too large for the calculator

1 – calculator IFX-M4-04 2 – adapter plate 3 – screw M4x6 4 - screw M4x12

IFX-

Page 45: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 45

Annex D

Fig. D2. Wall mounting, without possibility sealing of mounting

Fig. D3. Wall mounting, with possibility sealing of mounting

D4. Mounting on standard DIN-rail

Page 46: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 46

Fig.D5. Panel mounting

a) G 1 ¼ (qp = 3,5 m3/h; qp = 6,0 m3/h ) b) G 2 (qp = 10,0 m3/h)

c) DN 50 (qp = 15,0 m3/h)

Fig. D6. Mounting on ultrasonic flow sensor

Flow temperature max. 90 oC

Page 47: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 47

Annex E Sizes and dimensions of ultrasonic flow sensors

Fig. E1. Dimensions of flow sensors, pq = 3,5/6 m³/h.

Fig. E2. Dimensions of flow sensors, pq = 10 m³/h

Fig. E3 Dimensions of flow sensors, pq = 15 m³/h

qp, m3/h L H B Connecting

3,5 260 112 76 G1 1/4 6,0 260 112 76 G1 1/4

qp, m3/h L H B Prijungimas

10 300 120 120 G 2

DN L D1 H B 50 270 125 130 130

qp, m3/h L H B Connecting

10 300 175 120 G 2

Page 48: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 48

Fig. E4 . Dimensions of flow sensors, pq =25/40/60 m³/h

qp, m3/h L D D1 D2 n d

25 300 180 145 68.8 4 18 40 350 195 160 80.5 4 18 80 350 215 180 100 4 18

Page 49: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 49

Annex F Installation recomendation and sealing of temperature sensors

a)Without pocket b) With pocket

Fig.F1. Installation recomendations for temperature sensors with mounting head

a) angled 45o b) perpendicular

Fig.F2. Installation recomendations for temperature sensors with permanently connected signal leads

Seal

Boss

Seal

Pocket

Seal

Boss

Seal

Pocket

Page 50: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 50

Annex F

a) Temperature sensors with permanently connected signal leads L- signal leads length

b) Temperature sensors pocket

F3 pav. Dimensions of temperature sensors type PL-6 and theirs pockets

Nominal daimeter of pipe, mm DN20...DN100 DN125...DN150 Total length of pocketL, mm 100 135

Page 51: ULTRASONIC HEAT METER IFX-M4-04 - Heating and Process · Ultrasonic heat meter IFX-M4-04 is designed for metering of consumed heating or cooling.energy in heating/cooling systems,

IFX-M4-04 V01 51

Indirizzi

Isoil Industria spa Head office 20092 Cinisello Balsamo (MI) Italy 27, via F.lli Gracchi Phone +39-02-66027.233 Fax +39-02-6123202 E-mail: [email protected] oppure [email protected] Web: www.isoil.com

Service Isoil Industria spa 20092 Cinisello Balsamo (MI) Italy 27, via F.lli Gracchi Phone +39-02-66027.219 Fax +39-02-6123202 E-mail: [email protected]

Dan Macey
HP