ULTRA SONE “TB” SERIES - Air Movement and … · 430 5.5 520 4.7 WATTS 159 185 250 293 309 S.P....
Transcript of ULTRA SONE “TB” SERIES - Air Movement and … · 430 5.5 520 4.7 WATTS 159 185 250 293 309 S.P....
ULTRA SONE “TB” SERIESModels QCF-200, QCF-300, QCF-400, QCF-500
CEILING OR IN-LINE TWIN BLOWER FANS
STANDARD:- White Perforated Steel Grille- Continuous Duty Life Time Lubricated Motor with Thermal Protection - Plug Type Disconnect - Galvanized Metal Forward Curved Blower Wheels- Universal Mounting Brackets- Insulated Cabinet - Neoprene Vibration Isolator- Aluminum Backdraft Damper
OPTIONAL:- White Aluminum Egg Crate Grille- Speed Controller- Inline Adapter Kit - Built In Fire Radiation Damper (see FF series)
(call factory)
FAN DIMENSIONS
MODEL
QCF200
QCF300
QCF400
QCF500
A
18
18
19
24
B
10
10
12
14
D
12
12
12
18
19
19
20
25.5
F G
11
11
13
15.5
C
10
10
12
14
E
4
4
4
5
A
C
B
D
E
F
G
ULTRA SONE “TB” SERIES PERFORMANCE CHART (120V AC , 60 Hz)
MODEL
QCF200
QCF300
QCF400
QCF500
RPM
1350
1200
1080
1050
AMPS
0.76
1.25
1.60
4.20
S.P.
CFM
0.00
230
310
411
594
0.10
204
281
350
535
0.15
192
266
315
495
0.20
181
252
280
455
0.25
166
241
265
375
0.30
152
230
250
292
0.40 SONES
3.0
4.0
4.0
4.0
122
191
215
280
0.50
67
158
180
225
WATTS
91.2
150
192
504
QCF200, QCF300 FAN DATA
S.P
. (S
tatic
Pre
ssu
re -
In
ch W
.G.)
0.00
0.10
0.15
0.20
0.25
0.30
0.40
0 50 100 150 200 250
0.50
Air Flow (CFM - Cubic Feet Per Minute)
QCF200
0.60
300 350
QCF300
400 450 500 550 600
QCF400
QCF500
WALL MOUNTEDHORIZONTAL DISCHARGE
IN-LINE MOUNTED REDUCED INLETHORIZONTAL DISCHARGE
CEILING MOUNTED VERTICAL DISCHARGE
TYPICAL IN-LINE INSTALATION
ULTRA SONE “TB” SERIES
Models QCF-600, QCF-800, QCF-1000, QCF-1300, QCF-1600CEILING OR IN-LINE TWIN BLOWER FANS
STANDARD:- White Perforated Steel Grille- Continuous Duty Life Time Lubricated Motor with Thermal Protection - Plug Type Disconnect - Galvanized Metal Forward Curved Blower Wheels- Universal Mounting Brackets- Insulated Cabinet - Neoprene Vibration Isolator- Aluminum Backdraft Damper
OPTIONAL:- White Aluminum Egg Crate Grille- Speed Controller- Inline Adapter Kit (call factory) - Built In Fire Radiation Damper (see FF series)
FAN DIMENSIONS
MODEL
QCF600
QCF800
QCF1000
QCF1300
QCF1600
A
24
24
32
38
38
B
14
14
14
14
14
D
18
18
24
28.5
28.5
25.5
25.5
33
39
39
F G
15.5
15.5
15
15
15
C
14
14
14
14
14
E
5
5
6.5
6.5
6.5
MODEL RPM AMPS 0.00
CFM SONES4.2
5.2
3.2
3.2
3.2
1050
1050
825
825
825
QCF600
QCF800
QCF1000
QCF1300
QCF1600
6427.17556.69285.3
12658.8
13259.4
0.10
5966.46936.38435.1
11307.5
12006.9
0.15
5706.36686.17705.1
10407.5
11406.6
0.20
5256.26406.07185.09707.5
10806.3
0.25
4856.16105.96604.98905.9
10356.0
0.30
4406.05805.76184.88456.09805.3
0.40
2905.85005.54604.66855.88005.0
0.50
--
3805.2--
4305.55204.7
WATTS
159
185
250
293
309
S.P. SOUND
ULTRA SONE “TB” SERIES PERFORMANCE CHART (120V AC , 60 Hz)
QCF600, QCF800 FAN DATA
S.P
. (S
tatic
Pre
ssure
- I
nch
W.G
.)
0.00
0.10
0.15
0.20
0.25
0.30
0.40
100 200 300 400 500 600
0.50
Air Flow (CFM - Cubic Feet Per Minute)
QCF600
0.60
700 800
QCF800
QCF1000, QCF1300, QCF1600 FAN DATA
S.P
. (S
tatic
Pre
ssure
- I
nch
W.G
.)
0.00
0.10
0.15
0.20
0.25
0.30
0.40
400 600 800 1000 1200 1400
0.50
Air Flow (CFM - Cubic Feet Per Minute)
QCF1000
0.60
1600
QCF1300
QCF1600
A
C
B
D
E
F
G
CFM SONES
CFM SONES
CFM SONES
CFM SONES
Performance certified is for installation type B: free inlet, Ducted outlet. Performance ratings include the effects of an inlet grille and backdraft damper. Speed (rpm) shown is nominal. Performance is based on actual speed test. The sound ratings shown are loudness values in spherical fan sones at 5 ft (1.5m) in a spherical free field calculated per Annex B of AMCA 311. Values shown are for installation type B: free inlet spherical fan sone levels.
Reversomatic Manufacturing Limited certifies that Model QCF 600-1600 shown herein are licensed to bear the AMCA Seal. The ratings shown are based on testes and procedures performed in accordance with AMCA Publication 211 and AMCA Publication 311 and comply with the requirements of the AMCA Certified Ratings Program.
Catalogue QCF, January 2014