ULDF6000 INSTALLATION Manual...ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018...

61
ULDF6000 INSTALLATION Manual

Transcript of ULDF6000 INSTALLATION Manual...ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018...

  • ULDF6000 INSTALLATION Manual

  • 2 ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITYThe information, recommendations, descriptions and safety notations in this document are based on Eaton Corporation’s (“Eaton”) experience and judgment and may not cover all contingencies. If further information is required, an Eaton sales office should be consulted. Sale of the product shown in this literature is subject to the terms and conditions outlined in appropriate Eaton selling policies or other contractual agreement between Eaton and the purchaser.

    THERE ARE NO UNDERSTANDINGS, AGREEMENTS, WARRANTIES, EXPRESSED OR IMPLIED, INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY, OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES. ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON. THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES.

    In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict liability or other-wise for any special, indirect, incidental or consequential damage or loss whatsoever, including but not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting from the use of the information, recommendations and descriptions contained herein. The information contained in this manual is subject to change without notice.

  • 3

    ULDF6000 INSTALLATION

    Manual

    ULDF6000 INSTALLATION MANUAL

    Contents

    INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .61.1. Fire alarm system limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

    1.2. Installation precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    1.3. Product descriptions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7

    1.4. Product features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    1.5. Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8

    1.6. Controls and indication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    1.6.1. Touch screen user button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    1.6.2. LED Indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12

    1.7. Panel controls and indicators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13

    1.8. Fitting printer paper role . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14

    2 INSTALLATION GUIDELINES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .152.1 essential please read before proceeding! . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    2.2 Agency requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    2.3 Calculating current draw and standby battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    2.4 Calculating maximum current draw and battery backup

    Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    2.4.1 Detector technical characteristics UL approved . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15

    2.4.1.1 calibrated detector sensitivity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

    2.4.2 UL Approved audio visual devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

    2.4.3 Examples of battery calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    2.4.4 Maximum number of devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    2.4.5 Wiring requirement for SLC circuits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

    3 INSTALLATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .20 3.1 Mounting the enclosure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

    3.2 Earth cable on ULDF6000RM (does not apply to ULDF6000) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    3.3 Installing cabling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    3.4 Connecting the AC Power and earth connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

    3.5 Battery Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.6 Output (NAC) Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.6.1 Class B Style Y NAC wiring using main board (Horns only) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22

    3.6.2 Class B Style Y NAC Wiring using wheelock DS 12/24 (Horns & Strobes) . . . . . . . . . . . . . . . . . . . . . . . 22

    3.7 SLC Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    3.8 Supervisory signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    Addressable devices can be programmed for supervisory signals. This input on a latching mode and requires a manual reset to restore their normal state provided the condition is cleared.Panel Relay Outputs . . 23

    Panel relay outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23

    4 NETWORKING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .244.1 Battery maintenance installation cautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

    5 TECHNICAL SPECIFICATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .25

    6 COMMISSIONING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .276.1 Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    6.2 Panel programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

    6.3 PC Commissioning software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

    6.3.1 Device input programming . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29

  • 4 ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    ULDF6000 INSTALLATION Manual

    6.3.2 Isolate Zone / Address . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Error! Bookmark not defined.

    7 PANEL CONTROLS & INDICATORS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .307.1 Touch screen display. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    7.2 Panel operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30

    7.3 Public access level 1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

    7.4 Evacuate (Access level 2) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    7.5 Silence alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32

    7.6 Acknowledge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    7.7 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

    7.8 Pre-alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    7.9 Disabled devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    7.10 Troubles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    7.11 Enable/disable (Others menu) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

    7.12 Print . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    7.13 Lamp test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

    7.14 Weekly test. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

    7.15 Viewing events . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

    7.16 Check auto config . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39

    7.17 Test device (Access level 3) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41

    7.18 Test zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42

    7.19 Sounder level test mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

    7.20 Global flashing LED on/off . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44

    7.21 One man walk test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45

    7.22 Commission: Load CDR from Laptop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46

    7.23 Commission: Download CDR to Laptop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47

    7.24 Commission: Auto learn . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48

    7.25 Erase log . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49

    7.26 Change date/time . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    7.27 Change text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

    7.28 Change zone text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51

    7.29 Change panel text . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52

    7.30 Configure zones . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53

    7.31 Change user code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54

    7.32 Add zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    7.33 Delete zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55

    7.34 Add device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    7.35 Delete device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56

    7.36 Configure heat detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

    7.37 Network . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57

    7.38 Password protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58

    8 BATTERY DISPOSAL INSTRUCTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

    9 COMPATIBILITY TABLE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .59

  • 5

    ULDF6000 INSTALLATION

    Manual

    ULDF6000 INSTALLATION MANUAL

    NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER INVOLVED PARTIES

    This product incorporates field-programmable software. In order for the product to comply with the requirements in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features or options must be limited to specific values or not used at all as indicated below.

    Program feature or option

    Permitted in UL 864? (Y/N)

    Possible settings

    Settings permitted in UL 864

    Enable All / Disable All

    N Enable All / Disable All

    Enable All

    Noee:N For maintenance recommendations refer to the NFPA 72 National Fire Alarm Code, 2007.

    Noee:N Software release: DTS Micro: 3.03.50.xx Loop: 3.2.4.xx

    Noee:N Install in accordance to NFPA 70, 72 (2007). The ULDF6000 is suitable as a Local signaling unit. All circuits inherently power limited except AC wiring and battery cabling.

  • 6

    Introduction

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    Introduction1.1. Fire alarm system limitationsAn automatic fire alarm system – in general is made up of smoke detectors, heat detectors, manual pull stations, Call points, audible warning devices, and fire alarm control panels with remote notification capability, which can supply early warning of a developing fire. Such a system, on the other hand, is unable to assure protection against property damage or loss of life resulting from a fire.

    The Manufacturer recommends that smoke and /or heat detectors must be positioned throughout a protected premise following the recommendations of the current edition of the National Fire Protection Association Standard 72 (NFPA72), manufacturer’s recommendations, State and local codes, and the recommendations contained in the Guide for Proper Use of System Smoke Detectors, which is made available at no charge to all installing dealers. A study by the Federal Emergency Management Agency (an agency of the United States government) indicated that smoke detectors may not go off in as many as 35%of all fires. While fire alarm systems are intended to provide early warning against fire, they cannot promise warning or protection against fire. A fire alarm system may not provide timely or sufficient notice, or might not function, for a diversity of reasons.

    Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in or behind walls, on roofs, or on the other side of closed doors Smoke detectors also may not sense afire on another level or floor of a building. A second-floor detector, for example, may not sense a first-floor or basement fire.

    Particles of combustion or “smoke” from a developing fire may not reach the sensing chambers of smoke detectors because:-

    • Barriers such as closed or partially closed doors, walls,or chimneysmay inhibit particle or smoke flow.

    • Smoke particles may become “cold,” stratify,and not reach the ca lingor upper walls wheredetectors are located.

    • Smoke particles may be blown away from detectorsby air outlets.

    • Smoke particles may be drawn into air returns beforereaching thedetector.

    The amount of “smoke” present may be insufficient to alarm the smoke detectors. Smoke detectors are designed to alarm at various levels of smoke density. If such density levels are not created by a developing fire at the location of detectors, the detectors will not go into alarm.

    Smoke detectors, even when working property, have sensing limitations. Detectors that have photo electronic sensing chambers tend to detect smoldering fires better than flaming fires, which have little visible smoke. Detectors that have ionizing-type sensing chambers tend to detect fast – flaming fires better than smoldering fires. Because fires develop in different ways and are often unpredictable in their growth, both type of detector is necessarily best and a given type of detector may not provide adequate warning of a fire.

    Smoke detectors cannot be expected to provide adequate warning of fires caused by arson, children playing with matches (especially in bedrooms), smoking in bed, and violent explosions (caused by escaping gas, improper storage of flammable materials, etc.).

    Heat detectors do not sense particles of combustion and alarm only when heat on their sensors increases at a preset rate or reaches a predetermined level. Rate-of-rise heat detectors may be subject to reduced sensitivity overtime. For this reason, the rate-of-rise feature of each detector should be tested at least once per year by a qualified fire protection expert. Heat detectors are designed to protect property, not life.

    IMPORTANT Smoke detectors must be installed in the same room as the control panel and in rooms used by the system for the connection of alarm transmission wiring, communications, signaling, and/or power. If detectors are not located, a developing fire may damage the alarm system, crippling its ability to report a fire.

    Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors or are located on another floor of a building. Any warning device may fail to alert people with a disability or those who have recently consumed drugs, alcohol or medication.

    Please note that:

    Strobes can, under certain circumstances, cause seizures in people with conditions such as epilepsy.

    Studies have shown that certain people, even when they hear a fire alarm signal, do not respond or comprehend the meaning of the signal. It is the property owner’s responsibility to conduct fire drills and other training exercise to make people aware of fire alarm signals and instruct them on the proper reaction to alarm signals.

    In rare instances, the sounding of a warning device can cause temporary or permanent hearing loss.

    A fire alarm system will not operate without any electrical power If AC power fails, the system will operate from standby batteries only for a specified time and only if the batteries have been properly maintained and replaced regularly.

    Equipment used in the system may not be technically compatible with the control. It is essential to use only equipment listed for service with your control panel Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily disabled. For added protection against telephone line failure, backup radio transmission systems are recommended.

    The most common cause of fire alarm malfunction is insufficient maintenance. To keep the entire fire alarm system in excellent working order, ongoing maintenance is required as the manufacturer’s recommendations, and UL and NFPA standards. At a minimum, the requirements of NFPA 70, 72 shall be followed. Environments with large amounts of dust, dirt or high air velocity require more frequent maintenance. A maintenance agreement should be arranged through the local manufacturer’s representative. Maintenance should be scheduled

  • 7

    Introduction

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    monthly or as required by National and /or local fire codes and should be performed by authorized professional fire alarm installers only. Adequate written records of all inspections should be kept.

    1.2. Installation precautions

    WARNING Several differeno sNurces Nf pNwer can be cNnnecoed oN ohe fire alarm cNnorNl panel . DiscNnneco all sNurces Nf pNwer befNre servicing ohe CNnorNl unio and assNciaoed equipmeno may be damaged by remNving and/Nr inseroing cards, mNdules Nr inoercNnnecoing cables while ohe unio is energized . DN nNo aooempo oN insoall, service, Nr Nperaoe ohis unio unoil ohis manual is read and undersoNNd fully .

    CAUTION System Reacceptance Test after Software Changes. To ensure proper system operation, this product must be tested in accordance with NFPA 70, 72 after any programming operation or change in site -specific software. Re-acceptance testing is required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware or wiring. All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested.

    In addition, to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change, up to a maximum of 50 devices, must also be tested and proper system operation verified.

    This system meets NFPA requirements for indoor dry operation at 0-49° C/32-120° F and at a relative humidity of 93 ±2% RH (non-condensing) at 32 ±2° C/ 90 ±3° F. However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and all peripherals be installed in an environment with a nominal room temperature of 15-27°C/60-80° F.

    Verify that wire sizes are adequate for all initiating and indicating device loops. Refer to manual Specifications section for maximum allowable I.R. drop from the specified device voltage.

    Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning-induced transients. Although no system is completely immune from lightning transients and interferences, proper grounding will reduce susceptibility. Overhead or out-side aerial wiring is not recommended, due to an increased susceptibility to nearby lightning strikes. Consult with the Technical Services Department if any problems are anticipated or encountered.

    Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.

    Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable entries from the sides or rear. Before making modifications, verify that they will

    not interfere with battery, transformer, and printed circuit board location.

    Do not tighten screw terminals more than 9 in-lbs. Over-tightening may damage threads, resulting in reduced terminal contact pressure and difficulty with screw terminal removal.

    This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that static charges are removed from the body. Use static-suppressive packaging to protect electronic assemblies removed from the unit.

    Follow the instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to the control panel and associated equipment. FACP operation and reliability depend upon proper installation by authorized personnel.

    1.3. Product descriptionsThe ULDF6000 provides all of the sophisticated features required of a leading edge analog fire system along with the simple operation and neat installation demanded by both installers and building users.

    The panel can be flush or surface mounted and the generously sized metal back box allows ample facilities for rear or top cable entries.

    A comprehensive range of ancillary devices is available to operate with ULDF6000, including Optical, Ionization, photo-thermal and heat detectors.

    Each of the ULDF6000 system components has been specifically designed to operate as part of a ULDF6000 system, this provides an assurance that the panel, the detectors, the interfaces and the ancillaries are all fully compatible with one another and that the full range of system functionality is supported by each device.

    Fire alarm control panel models:

    ULDF60002G, ULDF60004G, ULDF60002GP, ULDF60004GP, ULDF60002GNC, ULDF60004GNC, ULDF60002GPNC, ULDF60004GPNC, ULDF60002GRM, ULDF60004GRM, ULDF60002GPRM, ULDF60004GPRM, ULDF60002GNCRM, ULDF60004GNCRM, ULDF60002GPNCRM, ULDF60004GPNCRM, ULDFR6000L2, ULDFR6000L4, ULDFR6000L2NC, ULDFR6000L4NC.

    Designation system:

    The prefix “ULDF6000” is for a stand-alone panel. The prefix “ULDF6000” is for rack-mount panels that are networked within the rack. The various control unit models differ in the following manner:

    2G or L2 2-Loop panel

    4G or L4 4-Loop panel

    GP 2-Loop panel c/w integral printer

    4GP 4-Loop panel c/w integral printer

    2GNC or L2NC 2-Loop panel c/w network card

    4GNC or L4NC 4-Loop panel c/w network card

    2GPNC 2-Loop panel c/w integral printer, network card

    4GPNC 4-Loop panel c/w integral printer, network card

    Model numbers followed by suffix “RM” have a Red Metal enclosure backbox and cover.

  • 8

    Introduction

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    1.4. Product features • The Panel has the following features:

    • 120mm x 90mm Touchscreen Display

    • 2 or 4 SLC loops.

    • Real time clock.

    • Event History Buffer (9,999 events) with Date/Timestamp. Events canbe displayed on Touchscreen.

    • 4 Notification appliance circuits (NAC’s) outputs.

    • 3 programmable general purpose relays.

    • Walk Test Facility

    • Switchable 2 amp power supply 120/240 VAC 60 Hz.

    • Dedicated alarm and trouble relays.

    • Housed in a 50cm W x 4 cm H x 20 D metal cabinet.

    • Cabinet supports two 12V, 7Ah backup batteries.

    • Short circuit isolators incorporated into each loop.

    • Spur tolerant soft addressing

    • Large multifunction touch screen

    • Up to 200 addresses per loop

    • Fully monitored network cable up to 126 panels.

    • Optional integral printer

    • Alarm Verification

    • PAS (Positive Alarm Sequence)

    • Pre-Signal per Point (NFPA 70, 72 compliant)

    • Remote Alarm Silence, Reset , Disablement andDrill via addressablemodules

    • User Programmable password

    • Fully programmable from keypad or Local PC

    • Upload and Download facility

    • Facility to download Logo

    • Autolearn Feature

    • Battery Charger with Temperature Compensation

    • Detector sensitivity

    1.5. SpecificationsAC Power

    (see fig.1)

    120 VAC 60 Hz or 240 VAC 60Hz, 2.0 Amps (L hot, N Neutral) Supervised

    Battery (Lead acid only) J5 (see fig.1)

    Maximum Charging Circuit: Normal- 27.6VDC @ 1.0amp The Control panel battery charge capacity is 2 X 12 AH. Wire batteries in series to produce a 24 Volt equivalent. Do not parallel batteries to increase the Amp Hour rating. It is recommended that the batteries are replaced every 5 years

    SLC Circuits (see fig.1)

    Communication Loop TB6, 7, 8, 9 Addressable Loops = Max 4 Maximum Length, see Table 9 Maximum Loop Current is 500ma (Short Circuit) or 200 ma (nominal) Maximum Loop Resistance is 50 Ohms Supervised and power limited Operation: Class A, Style 6 Supervised for: Ground faults impedance value 0Ω

    When Installing SLC wiring in conduit, each loop must be installed in separate conduit.

    The total number of addresses per loop is 200; this includes detectors, call points and all other addressable items and call points. When designing systems it’s recommended that allowances are made for future expansion, Short circuit isolators are incorporated into every Menvier loop device, including Smoke detectors, heat detectors, sounders, manual pulls and interfaces. Therefore, no further fault protection is required, in the event of a single fault; none of the devices connected to the loop will fail to operate as the fault will be isolated by the two adjacent devices. Spur connected devices downstream of a cable fault will cease to function.

    Notification appliance (see fig.1)

    TB11, TB12, TB13, TB14, (Horns) +Out1, Minus1, +Out2, Minus2 (Strobes/Horns)

    4 NACs Regulated Outputs (750mA each) for Horns only using the main board (PCBA2314) or two (2) NACs for strobes/horns using Wheelock DSM 12/24 (0.5Amp total for either one NAC or shared between both NAC1, NAC2)

    When the product is powered by 240V, the maximum current of 3.0 A is shared between the circuits on the main board. (cont’d)

    When the product is powered by 120V, the maximum current of 2.25 A is shared between the circuits on the main board.

    When determining the Notification signaling scheme, a panel may only provide power for either Horns from the main board, or Horns/Strobes from the Wheelock synch module model DSM 12/24, but not both!

    Supervised for: Ground faults impedance value 0’Ω Regulated

    NAC Specification

    Four programmable outputs are Notification Appliance Circuit (NAC). The NAC provide the following programmable modes:

    Steady – 24 VDC at alarm condition

    Pulsing – 24 VDC at alarm condition

    Synchronization

    Cooper Wheelock DSM-12/24 R is for 11 Exceeder strobes (15cd). This module can also synchronize horns.

    Power limited circuitry and supervised Operation: Style Y (Class B) Nominal Operating Voltage =24 VDC End of line Resistor = 6K8 1/5W 1% (part number

  • 9

    Introduction

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    ULEOR6K8) Refer to device compatible document listed in table 2.

    AC trouble outputs relay TB15

    Contact rating: 1.0 amp @30VDC (resistive) form C relays

    Alarm/Trouble output relay YPCB2294 TB1

    Contact rating: 1.0 amp @30VDC (resistive) form C relays

    Trouble output

    12V NS, 30mA; 0V Trouble Power Limited Limited to same room installation Special Application – Recorded range of compatibility: 13.7Vdc – 1.8Vdc

    Network SLC

    5V dc rated voltage; 100mA maximum current Maximum Line Impedance 50Ω Power Limited

    Table 1 .

    Primary Operating Supply 120/240 V, 60 Hz, 2.0 ASupervised

    Secondary Operating Supply

    24 V dc nominal battery voltage1.0A maximum battery charge current0.1 Battery derating factor12 Ah maximum battery capacitySupervised

    Notification Appliance Circuits,(Class B) - Style YSounder Group 1 sounder 1,Sounder Group 1 sounder 2,Sounder Group 2 sounder 1,Sounder Group 2 sounder 2;

    24 V dc nominal output voltage0.75 A maximum output current50 ohms maximum line impedance

    When the product is powered by 240Vac, the maximum current of 3.0 A is shared between these circuits.

    When the product is powered by 120Vac, the maximum current of 2.25 A is shared between these circuits.

    Supervised, Power limited, Regulated

    Notification Appliance Circuits,(Class B) - Style YSYNC MODULENAC1, NAC2

    24 V dc nominal output voltage0.5 A maximum output current50 ohms maximum line impedance

    The maximum current of 0.5 A is shared between these circuits.

    Supervised, Power limited,Regulated

    Alarm, Trouble Contacts. Relay Expansion, Fig. 7

    30 V dc, 1 A, Unity power factor30 V dc, 1 A, Unity power factorFor connection to Power limited sources only

    Aux Relay (AC Trouble) Contacts

    30 V dc, 1 A, Unity power factorFor connection to Power limited sources only

    Trouble Output (TB2, RL1) 12V NS, 30mA;Trouble: 0VPower LimitedLimited to same room installationSpecial Application: Recorded range of compatibility: 13.7Vdc – 1.8Vdc

    Signaling Line CircuitStyle [6] Class [A]–(Addressable Loop)

    24 V dc rated voltage;500 mA maximum currentMaximum Line Impedance 50Ω[Supervised, Power limited]

    Network SLC 5V dc rated voltage; 100mA maximum currentMaximum Line Impedance 50ΩPower LimitedLimited to Same-enclosure Installations

  • 10

    Introduction

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    Figure 1 . Typical wiring diagram

  • 11

    Introduction

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    Figure 2 . FNr furoher deoails Nn each device, see ohe respecoive InsoallaoiNn InsorucoiNns . Typical wiring diagram

  • 12

    Introduction

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    1.6. Controls and indication1.6.1.Touch screen user button

    Acknowledge

    This function, also abbreviated to “ACK”, is used to acknowledge an abnormal situation such as an alarm or trouble condition. The acknowledge function tells the panel that building personnel or emergency responders are aware of the alarm, trouble, or supervisory condition. Acknowledging the alarm or trouble condition also normally silences the panel’s own sounder.

    Alarm silence

    Also known as “audible silence”. Depending on the configuration of the alarm system, this function will either silence the system’s notification appliances completely, or will silence only the audible alarm, with strobe lights continuing to flash. Audible silence allows for easier communication amongst emergency responders while responding to an alarm. This can also be used during construction as a means of a preliminary test, before the final full test.

    Reset

    This resets the panel after an alarm condition. All initiating devices are reset, and the panel is cleared of any alarm conditions. If an initiating device is still in alarm after the system is reset, such as a smoke detector continuing to sense smoke, or a manual pull station still in an activated position, another alarm will be initiated.

    Evacuate/Drill

    This will operate all the notifications appliances as well as audible alarms as well as Panel’s own sounder.

    1.6.2.LED Indicators

    Power on LED (Green LED)

    Indicator is lit, power is being provided to the system from building’s electrical supply and or from the battery backup. If this indicator is lit without any other indicators also lit, then the system is in a normal condition. If no LED’s are lit, then there is no power source feeding the panel

    General alarm LED (Red LED)

    This indicator is lit when an alarm condition exists in the system, initiated by smoke detectors, heat detectors, sprinkler flow switches, manual pull stations, manual call points, or otherwise. Along with the indicator on the panel, notification appliances, such as horns and strobes, are also activated, signaling a need to evacuate to building occupants. In an alarm condition, the fire alarm panel indicates where the alarm originated. The alarm panel can be reset once the device which initiated the alarm is reset, such as returning the handle of a manual pull station to its normal position.

    General trouble (Yellow LED)

    When held steady or flashing, it means that a trouble condition exists on the panel. Trouble conditions are often activated by a contaminated smoke detector or an electrical problem within the system. Trouble conditions are also activated by a zone being disabled (disconnected from the system), a circuit being disabled, low power

    on the backup battery, the disabling of a notification appliance, the ground faults, or short or open circuits. The alarm panel’s sounder will activate* if a trouble condition exists. In a trouble condition, the panel displays the zone or devices causing the condition. When the situation causing the trouble condition is rectified and the panel is reset, the General trouble indicator goes out and the trouble relay will return to its normal state.

    System trouble LED (Yellow LED)

    Indicator is lit to indicate system malfunction or system has been rebooted

    Power trouble LED (Yellow LED)

    Indicator is lit and the panel internal sounder will activate*, when there is no power being provided to the system from the Building’s electrical system or from the battery backup .The touch screen display will display the cause of the trouble (AC trouble or Battery trouble).

    If the trouble is due to the AC power input, the AC trouble relay will operate after a programmed delay set by the user. The delay can be set at 0, 60, 120 or 180 minutes. If the trouble condition is due to battery malfunction or battery being disconnected from the panel, the trouble relay will also activate. When the trouble recondition has been restored the panel has been manually reset, the LED and trouble relays will return to their normal state.

    NAC trouble LED (Yellow LED)

    Indicator is lit, the internal sounder* and the trouble relay also activates, it means that a trouble condition exists on the panel NAC circuits. This trouble condition is often activated by a short or open of the NAC circuits. The trouble relay also activates during this condition.

    When the situation causing the trouble condition is rectified and the panel is reset, the NAC trouble indicator goes out and the trouble relay will return to its normal state.

    Silenced LED (Yellow LED)

    This signal indicates that the system has been silenced. All notification appliances have been silenced.

    System test LED (Yellow LED)

    When the system is under a test condition such as “walk test”, the system test led will be illuminated. This led is off when the system is restore to its normal condition

    Alarm silenced (Yellow LED)

    Pre signal LED (Yellow LED)

    LED is lit when the pre-signal feature has been implemented.

    Ground trouble

    When the panel detects a ground Fault condition which indicates a short between any line extending from the panel and the Earth Ground circuits, the Ground trouble LED will be illuminated and the trouble relay will also activate during a trouble condition.

    When the trouble condition has been restored and the panel has been manually reset, the LED and trouble relay will return to their normal state.

  • 13

    Introduction

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    *Local piezo sounder

    A piezo sounder provides separate and distinct sounds for alarm, trouble andsupervisory conditions as follows:

    • Alarm - on steady

    • Trouble - pulse 1 second on and 1 second off

    • Supervisory - pulse ½ second on and ½ second off

    1.7. Panel controls and indicators

    1. System LED’s

    2. Zonal LED’s

    3. Touch screen display

    4. Printer access door

    5. Slot for optional printer

    Figure 3 .

    LED Name Function Action

    1 Power On Shows Panel is On Check Indicator is Illuminated

    2 General Alarm Indicators Panel has Detected a Fire Implement Fire Action Procedure

    3 General Trouble Monitors Devices for Troubles e.g. Smoke detectors/Sounders Report to System Supervisor

    4 System Trouble Monitors Fire Panel for Troubles Report Fault to Service Dept

    5 Power Trouble Monitor Internal Battery Charger Report Fault to Service Dept

    6 NAC Trouble Monitors NAC Circuits/Indicates Disablement of this Output Report Fault to Service Dept

    7 Supervisory Part of the System has been Disabled Report to System Supervisor

    8 System Test Indicates when System is under test Check with System Supervisor

    9 Alarm Silenced Indicates panel has been silenced Implement Fire Action Procedure

    10 Ground Trouble Display Activation (If Option Fitted) Check with System Supervisor

    11 Pre-Signal Delays on Outputs Active Check with System Supervisor

    U ULLC D

    F F6300 00

    00

    GeneralALARM

    PowerON SUPERVISORY

    GeneralTROUBLE

    PowerTROUBLE

    NACTROUBLE

    SystemTROUBLE

    System TEST

    GroundTROUBLE

    AlarmSILENCED

    PRE-SIGNAL

  • 14

    Introduction

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    Figure 4 . 1. Log book storage

    2. Insert supervisor key here

    3. Printer

    4. Paper roll storage

    1. Optional hinged cover

    2. Scroll up

    3. Acknowledge

    4. Scroll down

    Figure 5 .

    1.8. Fitting printer paper roleOpen the printer access door on the right hand side of the panel using the key provided. Drop the paper roll into the paper holder and feed paper into the printer. The printer will then automatically pull the paper through if the panel is powered up. Tear off the excess paper them close and secure the printer access door.

    Please note for paper feed to operate correctly, paper end must be straight.

  • 15

    2 Installation guidelines

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    2 Installation guidelines2.1 Essential please read before proceeding!

    The equipment described in this manual is listed by UL Underwriters Laboratories, for use in fire alarm signaling systems, only when installed in accordance with this manual and the latest National Fire Protection Association Standards NFPA 72; the National Electrical Code (NFPA 70); the Life Safety Code (NFPA 101); and/or the local authority having jurisdiction (AHJ).

    It is possible to apply system components incorrectly or arrange system components and installation wiring so that required life safety functions are NOT performed. As a result, lives may be lost.

    To minimize this possibility:

    DO NOT deviate from any installation instructions contained in this manual.

    DO NOT assume any installation details not shown in this manual.

    DO NOT alter any mechanical or electrical features of the equipment supplied

    BE FAMILIAR with the building code, fire prevention code, and/or requirements of the Authority Having Jurisdiction (AHJ) in the locale of the installation.

    CAUTION Under normal and fault conditions, AC line voltages may be present on any terminal. Touching any component could be hazardous and result in loss of life. A short circuit can result in arcing that could cause molten metal injuries to testing personal.

    To minimize this possibility, only qualified electrical technicians familiar with electrical hazards should perform these checkout procedures. Safety glasses should be worn by such personnel, and instruments used for voltage measurement should be designed for the purpose and should be in good mechanical and working order.

    If there is application or installation information that is not clear or not covered in this manual, please contact us at: Menvier Technical Support at +44 (0)1302 321541

    2.2 Agency requirements

    The PANEL is listed by UL Underwriters Laboratories to UL 864 9th edition as a FACP control unit for use in NFPA 72 systems.

    Requirements for All Installations

    General requirements are described in this section. When installing an individual device, refer to the specific section of the manual for additional requirements.

    • All field wiring must be installed in accordance withNFPA 70 NationalElectric Code.

    • Use UL listed smoke detectors and notificationappliances compatiblewith the PANEL from thosespecified in the Appendix to this manual.

    • A full system checkout must be performed every timethe panel isprogrammed.

    The ULDF6000 range of conventional fire alarm control panels are designed in accordance UL864 9th Fire Detection and Fire Alarm systems Control and Indicating Equipment.

    2.3 Calculating current draw and standby battery

    This section is to determine the current draw and standby battery needs for your installation.

    Maximum Battery Standby Load

    It is recommended to use the battery Yuasa Battery (www.yuasabatteries.com). The required nominal batteries capacity as versus standby current system is shown in the table bellow (1-1).

    Make sure that for the system configuration the standby is not more than 0.41 A for 12 Ah battery.

    Table 2 .

    2.4 Calculating maximum current draw and battery backup requirements

    This section will assist you in determining the maximum system current draw and standby battery needs for your installation. Follow the steps below to determine the current draw and standby battery requirements.

    Total standby and alarm current is determined by multiplying the quantity of items by its current draw. To quickly determine maximum system current draw, perform the following computations:

    Fill in the quantities of conventional detectors, addressable detectors and devices.

    Fill in the quantities and current draw of the Notification Appliances or auxiliary-powered devices for each output from the manual for each specific device.

    Fill in the total quantities of detectors and modules. The detectors and modules total alarm current is determinate by estimation method, under the hypothesis that 5% LED will be ON.

    The required battery capacity is determined according to equation:

    Cb >= (Isb* Tsb + Ia*Ta)*1.1

    Make sure the total alarm current you calculated (including current for the panel itself) does not exceed 4.0 Amps. This is the maximum alarm current allowable.

    The calculation example is shown in the table 8.

    Battery Model

    Capacity, Ah Size , mm Maximum permissible System Standby current during

    L W H 24 h

    NP12-12 12 151 99 101 0.4100

    Where:

    Cb required battery capacity, Ah

    Isb standby current, A

    Tsb supervisory time, 24hours

    Ia alarm current, A

    Ta alarm time, 5 min (0.0833 hours)

    1.1 safety factor.

  • 16

    2 Installation guidelines

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    2.4.1 Detector technical characteristics UL approved

    2.4.1.1 Calibrated detector sensitivity

    Detector Head ULMAP320 ULMAPT340 UMAH330

    Base WBA or UCAB300 WBA or UCAB300 WBA or UCAB300

    Working Voltage 18-30Vdc 18-30Vdc 18-30Vdc

    Voltage Waveform Filtered dc +/- 1vmax ripple @120Hz

    Filtered dc +/- 1vmax ripple @120Hz

    Filtered dc +/- 1vmax ripple @120Hz

    Standby Current (Average) 220 uA 220 uA 220uA

    Alarm Current (max) 5 mA 5 mA 5 mA

    Relay Current (max) N/A N/A N/A

    Start-up Time 2 seconds 2 seconds 2 seconds

    Sensitivity 2.55+/- 0.33%/ft 2.55+/- 0.33%/ft N/A

    Sensitivity use checker Use No-ClimbTRUTESTUL Listing 77TL

    Use No-ClimbTRUTESTUL Listing 77TL

    Use No-ClimbTRUTESTUL Listing 77TL

    Heat Element rating N/A 135ºF 135ºFROR+Fixed + Fixed*135ºF Fixed

    Reset Time (max) 2 seconds 2 seconds 2 seconds

    Heat Detector N/A 50ft(heat alone operation)

    50ft

    Ambient Temperature 32-100ºF 32-100ºF 32-100ºF32-50ºF (194ºF

    Mounting Position Ceiling in open areas Ceiling in open areas Ceiling in open areas

    Compatibility Identifier W002 W002 W002

    Part Code Type Normal Pre-Alarm Alarm Trouble

    ULMAP320 Optical 10 – 49(Nominal 20)

    50 – 59 60 – 255 0 – 10

    ULMAPT340 Optical Heat 10 – 49(Nominal 20)

    50 – 59 60 – 255 0 – 10

    Table 3 .

    Table 3

    Table 4 .

    Normalized smoke detector value versus %/Ft:

    Normalised Smoke detector response ULMAP320 & ULMAPT340

    20 0%/Ft

    50 1.91%/Ft

    60 2.55%/Ft

  • 17

    2 Installation guidelines

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    2.4.2 UL Approved audio visual devices

    UL Max Current* at 99 dB(A)

    24 Vdc 12 Vdc

    Mode Regulated Voltage Range Vdc

    15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75

    HS 8.0-33.0 0.082 0.095 0.102 0.148 0.176 0.197 0.242 0.282 0.125 0.159

    HSC 8.0-33.0 0.082 0.102 0.141 0.148 0.176 0.197 0.242 0.282 0.125

    Table 5 . NNoificaoiNn appliances

    Horn strobe ratings per UL 1971 & UL 464 at 24 Vdc

    UL Max Current* at 95 dB(A)

    24 Vdc 12 Vdc

    Mode Regulated Voltage Range Vdc

    15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75

    HS 8.0-33.0 0.073 0.083 0.087 0.139 0.163 0.186 0.230 0.272 0.122 0.153

    HSC 8.0-33.0 0.073 0.087 0.128 0.139 0.163 0.186 0.230 0.272 0.122

    Horn strobe ratings per UL 1971 & UL 464 at 24 Vdc

    UL Max Current* at 90 dB(A)

    24 Vdc 12 Vdc

    Mode Regulated Voltage Range Vdc

    15 15/75 30 60 75 95 110 115 135 150 177 185 15 15/75

    HS 8.0-33.0 0.065 0.075 0.084 0.136 0.157 0.184 0.226 0.267 0.120 0.148

    HSC 8.0-33.0 0.065 0.084 0.120 0.136 0.157 0.184 0.226 0.267 0.120

    Horn strobe ratings per UL 1971 & UL 464 at 24 Vdc

    Table 6 . PrNduco cNdes

    Part Code Description

    HSR Wall mounted horn strobe

    HSWC Ceiling mounted horn strobe

    HNR Wall mounted horn

    HNWC Ceiling mounted horn

    STR Wall mounted sync strobe

    STWC Ceiling mounted sync strobe

    RSSWP-2475-FR Weatherproof wall mounted sync strobe

    RSSWP-2475C-FW Weatherproof ceiling mounted sync strobe

  • 18

    2 Installation guidelines

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    Table 7 . Examples Nf baooery calculaoiNns

    QUANTITY OF DEVICE/ MODULE

    QUANTITY OF DEVICE/ MODULE IN ALARM CONDITION MAXIMUM

    STAND-BY CURRENT (Amps)

    MAXIMUM ALARM CURRENT (Amps)

    TOTAL STAND-BY CURRENT (Amps)

    TOTAL ALARM CURRENT (Amps)

    SYSTEM COMPONENTS

    Main System on Standby (Loop + Mother Board + Display + Network Card)

    1 0.23 0.23

    Panel in Alarm (As above + Synch Module+ Relay Board+ Zonal Led’s)

    0.27 0.27

    Loop 1

    Photoelectric smoke sensor ULMAP320 100 5 0.00022 0.005 0.022 0.025

    Multi-mode heat sensor UMAH330 50 0 0.00022 0.005 0.011 0

    Photo-thermal smoke sensor ULMAPT340 50 0 0.00022 0.005 0.011 0

    Spur isolator unit ULCSI350 0 0 0.00030 0.00030 0 0

    Zone Monitor Unit ULZMU352 0 0 0.0049 0.005 0 0

    3 Channel I/O unit ULCIO351 0 0 0.00114 0.00136 0 0

    Single input module ULMCIM-C & ULMCIM 0 0 0.00032 0.00032 0 0

    Single output module ULMCOM_S&ULMCOM 0 0 0.00032 0.00032 0 0

    Loop-mounted repeater ULDF6000PR 0 0 0.00031 0.00035 0 0

    4 way sounder controller ULCSC354 0 0 0.00041 0.0054 0 0

    Shop unit monitor ULSUM355 0 0 0.00490 0.005 0 0

    120/240 Single Channel IO ULCMIO353 0 0 0.00033 0..00039 0 0

    Low Cost ZMU ULMIU872 0 0 0.00490 0.005 0 0

    Loop 2

    Photoelectric smoke sensor ULMAP320 100 5 0.00022 0.005 0.022 0.025

    Multi-mode heat sensor UMAH330 50 0 0.00022 0.005 0.011 0

    Photo-thermal smoke sensor ULMAPT340 50 0 0.00022 0.005 0.011 0

    Spur isolator unit ULCSI350 0 0 0.00030 0.00030 0 0

    Zone Monitor Unit ULZMU352 0 0 0.0049 0.005 0 0

    3 Channel I/O unit ULCIO351 0 0 0.00114 0.00136 0 0

    Single input module ULMCIM-C & ULMCIM 0 0 0.00032 0.00032 0 0

    Single output module ULMCOM_S&ULMCOM 0 0 0.00032 0.00032 0 0

    Loop-mounted repeater ULDF6000PR 0 0 0.00031 0.00035 0 0

    4 way sounder controller ULCSC354 0 0 0.00041 0.0054 0 0

    Shop unit monitor ULSUM355 0 0 0.00490 0.005 0 0

    120/240 Single Channel IO ULCMIO353 0 0 0.00033 0..00039 0 0

    Low Cost ZMU ULMIU872 0 0 0.00490 0.005 0 0

    Loop 3

    Photoelectric smoke sensor ULMAP320 100 5 0.00022 0.005 0.022 0.025

    Multi-mode heat sensor UMAH330 50 0 0.00022 0.005 0.011 0

    Photo-thermal smoke sensor ULMAPT340 50 0 0.00022 0.005 0.011 0

    Spur isolator unit ULCSI350 0 0 0.00030 0.00030 0 0

    Zone Monitor Unit ULZMU352 0 0 0.0049 0.005 0 0

    3 Channel I/O unit ULCIO351 0 0 0.00114 0.00136 0 0

    Single input module ULMCIM-C & ULMCIM 0 0 0.00032 0.00032 0 0

    Single output module ULMCOM_S&ULMCOM 0 0 0.00032 0.00032 0 0

    Loop-mounted repeater ULDF6000PR 0 0 0.00031 0.00035 0 0

    4 way sounder controller ULCSC354 0 0 0.00041 0.0054 0 0

    Shop unit monitor ULSUM355 0 0 0.00490 0.005 0 0

    120/240 Single Channel IO ULCMIO353 0 0 0.00033 0..00039 0 0

    Low Cost ZMU ULMIU872 0 0 0.00490 0.005 0 0

  • 19

    2 Installation guidelines

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    Loop 4

    Photoelectric smoke sensor ULMAP320 100 5 0.00022 0.005 0.022 0.025

    Multi-mode heat sensor UMAH330 50 0 0.00022 0.005 0.011 0

    Photo-thermal smoke sensor ULMAPT340 50 0 0.00022 0.005 0.011 0

    Spur isolator unit ULCSI350 0 0 0.00030 0.00030 0 0

    Zone Monitor Unit ULZMU352 0 0 0.0049 0.005 0 0

    3 Channel I/O unit ULCIO351 0 0 0.00114 0.00136 0 0

    Single input module ULMCIM-C & ULMCIM 0 0 0.00032 0.00032 0 0

    Single output module ULMCOM_S&ULMCOM 0 0 0.00032 0.00032 0 0

    Loop-mounted repeater ULCF3000PR 0 0 0.00031 0.00035 0 0

    4 way sounder controller ULCSC354 0 0 0.00041 0.0054 0 0

    Shop unit monitor ULSUM355 0 0 0.00490 0.005 0 0

    120/240 Single Channel IO ULCMIO353 0 0 0.00033 0..00039 0 0

    Low Cost ZMU ULMIU872 0 0 0.00490 0.005 0 0

    AC Trouble Relay (0.025 Quiescent) 1 0 0 0 0

    Trouble relay coil current (0.025 Quiescent) 1 0 0 0 0

    0

    Alarm Trouble 1 0 0.025 0 0.025

    LON Card 0 0.035 0.035 0 0

    Network-mounted repeater ULDFTR6000 0 0

    NOTIFICATION APPLIANCES

    NAC # 1 1 0.75 0 0.75

    NAC # 2 1 0.75 0 0.75

    NAC # 3 1 0.75 0 0.75

    NAC # 4 1 0.75 0 0.75

    A)Supervisory (Standby) Current, (A) 0.406 0.28936 3.39 0.406 3.395

    B)Supervisory Time(24 hours) 24

    C)Supervisory requirements(A*B) 9.744

    D)Alarm Current 3.395

    E)Alarm time hours (5min=0.0833,10min=0.167) 0.0833

    F)Alarm Requirement 0.2828035

    G)Battery backup (C+F) 10.026804

    H)10% Safety Factor (=G*.1) 1.0026804

    I)Battery Requirement with 10% safety factor(=G+H) 11.029484

    REQUIRED BATTERY SIZE Ah 12

    Table 8 . Examples Nf baooery calculaoiNns

    2.4.3 Maximum number of devices

    The maximum number of Menvier addressable devices per SLC circuit is 200. The Menvier Panel can support up to 4 SCL circuit, a total of 800 addressable devices.

    2.4.4 Wiring requirement for SLC circuits

    Must meet the National Electric Code 760-51 requirements for power limited fire protective signaling cables.

    Maximum wiring resistance is 50 ohms and maximum loop length depends on the wire gauge as per below.

    Table 9 .

    Wire Gauge 22AWG 18AWG 16AWG 14AWG

    mm2 .34 1.0 1.5 2.5

    Maximum Distance

    1500 feet 3900 feet 6200 feet 10,000 feet

  • 20 ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    3 Installation

    3 InstallationRead all the installation instructions before commencing with the installation. The installation of this panel must be carried out by a suitably qualified /trained person.

    With the hinge mounting on the left, determine the number of conductors required for the devices to be installed. Sufficient knockouts are provided for wiring convenience.

    Select the appropriate knockout(s) and pull the conductors into the box. All wiring should be in accordance with the National and/or Local codes for fire alarm systems.

    3.1 Mounting the enclosureThe ULDF6000 and ULDF6000RM can be flush mounted or surface mounted.

    Install the Enclosure as follows:

    1. Carefully unpack the system components and inspectfor any damage dueto shipping.

    2. Mount the enclosure in a clean, dry, vibration-free areawhere extremetemperatures are not encountered.The location should be readilyaccessible with sufficientroom for easy installation and maintenance.

    3. Locate the top of the cabinet approximately 5 feet(1.5 m) above the floor.

    4. Mount by using the two mounting holes located inthe upper back of thecabinet. After the panel has beenproperly located using the mountingholes, the panelcan be secured.

    5. Complete all conduit connections to the cabinet.Use the knockoutsprovided in the top and the sides.

    6. 6.Wire must NOT enter the bottom of the cabinet,since this area is intendedfor batteries only.

    The electronic components within the fire panel are Static Sensitive. Do not touch the electronics directly.

    Figure 6 . Panel mNunoing dimensiNns

    400 mm

    227m

    m

    309

    mm

    364

    mm

    132 mm

    472 mm

  • 21

    3 Installation

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    3.2 Earth cable on ULDF6000RM (does not apply to ULDF6000)Care must be taken to ensure that the earth connection between the back box and the front cover of the on ULDF6000RM is connected each time the cover is removed and refitted. Ensure that there is a serrated washer fitted between the earth terminal and the nut on both ends of the cable.

    Figure 7 . Earoh sorap

    3.3 Installing cablingOnce the backbox is mounted the next stage is to install the power and loop cables and fit the glands.

    3.4 Connecting the AC Power and earth connection

    WARNING TN reduce ohe risk Nf elecorical shNck, make sure ohao all pNwer has been ourned Nff Nr discNnnecoed priNr oNaooempoing oN cNnneco pNwer oN ohe PNwer Supply .

    Noee:N Make sure that AC main circuit breaker is off before wiring any connection between mains and control panel

    The primary power needed for the Menvier Fire Alarm Control Panel is 120VAC 60hz or 240VAC 60Hz.

    1. 1.Enter Power Cable into Cabinet knock out hole.

    2. 2.Attach the brown (live) wire from the source toterminal “Line” (USA usecolor black wire).

    3. 3.Attach the blue (neutral) wire from the source to the“Neutral” terminal (USAuse color white wire).

    4. 4.Attach the ground wire from the source to the “GD”terminal block (USA usecolor green wire).

    Cable anchorage

    The mains cable must be fixed securely with a 20mm cable gland. Remove a suitably located knockout feed the cable through the gland and bolt the gland to the ULDF6000 and ULDF6000RM backbox as shown. Secure the cable to the side of the box using the cable clip provided.

    Connect wiring from AC mains to J2 on the PCBA2147 being careful to observe proper connections in the figure below.

    NNoee: Apply the AC Power BEFORE connecting the batteries to the Panel!

    NNoee: Apply AC power to panel after the system is completely installed and visually checked.

    Figure 8 . AC pNwer enory

    Live(Hot) L

    Neutral N

    Earth

  • 22 ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    3 Installation

    3.5 Battery installationThe batteries are placed at the bottom of the enclosure by removing the four nuts holding the battery plate. The ULDF6000 is fully protected if the batteries are connected in the opposite direction the battery fault yellow led will show steady in such a condition. When green battery LED is in a steady condition to shows that the battery connection is normal.

    Figure 9 . Baooery cNnnecoiNn

    WARNING Before connecting the battery to the fire alarm panel. Ensure the interconnecting cable between the batteries is not connected. Do not connect this cable until the system is fully installed.

    3.6 Output (NAC) installationThe Panel is equipped with 4 regulated Class B Style Y NAC (Notification Appliance Circuits). At 240Vac input, use 4 horns 0.75A each for 3A total . At 120Vac input, use 3 horns, 0.75A each for 2.25A total. At either 240Vac or 120Vac, use 2 NACS for strobe synchronisation using Wheelock DS 12/24 with 2 regulated outputs at 0.25A each or 0.5A total.

    Use UL listed notification appliances only (see table 2). These appliances capable of producing the American National Standards Institute’s ANSI S3.41 audible emergency evacuation signal pattern, and are synchronized on a system basis. These devices can be silenced system or globally.

    3.6.1 Class B Style Y NAC wiring using main board (Horns only)

    Figure 10 .

    3.6.2 Class B Style Y NAC Wiring using Wheelock DS 12/24 (Horns & Strobes)

    Figure 11 .

    Black wireRed wire

    12V Battery

    12V Battery

    InterconnectingCable

    Resistor6K8

    +

    +

    +

    +

    +

    +

    +

    +

    Supervised Power Limited

    ResistorULEOR6K8

    +

    +

    +

    +

    MINUS2

    MINUS1

    OUT2

    OUT1

  • 23

    3 Installation

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    3.7 SLC InstallationFour SLC loop Class A Style 6 are provided on the Menvier Fire Alarm Panel main board. These SLC groups provide communication to addressable detectors, monitors, indication devices and control modules.

    Figure 12 . SLC InsoillaoiNn

    Maximum of 200 addressable devices per SLC circuit (see fig. 2)

    3.8 Supervisory signalAddressable devices can be programmed for supervisory signals. This input on a latching mode and requires a manual reset to restore their normal state provided the condition is cleared.

    Panel relay outputs

    The panel has 3 Form C relays 30V 1A (resistive) Alarm, Trouble, and AC Trouble.

    The AC Trouble relay can be programmed as per NFPA 72 requirements.

    These three out puts can be used to connect to a central station using Firewatch 411UD Digital Alarm Communicator Transmitter.

    Technical specifications

    Contact rating

    Figure 13 . Panel relay Nuopuos

    Class Aconnection returns

    LED remote indicator CIR301

    back to loop A- A+

    1A @ 30VDC (PF=1)

    Soun

    der

    Fau

    lt

    AUX

    Rel

    ay

    ACTrouble

    Alarm

    Trouble

  • 24 ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    This can either be connected in a loop of an individual panel or it can be connected to the network.

    The recommended network cable for the network connection between panels is an enhanced Firetuf cable Manufactured by Draka cables (part number 910234.)

    Screen continuity must be maintained throughout the entire network circuit including at each junction point. The screen should only be earthed at the connection point provided at the first panel and not at any other point. The screen or drain wire of the network cable should not be considered as a safety earth and therefore should not be connected to terminals marked with the earth symbol, except at the panel, and should not be insulated with green and yellow sleeving

    Where the network cable passes between buildings, screen continuity should not be maintained from building to building. A booster device must however be used irrespective of cable length and should be fitted at a suitable point in the link between buildings. The cable screen should be connected to the earth of one panel in each building.

    4 Networking

    4 NetworkingThis operation is only UL approved while connected in the same enclosure (rack) since the Network Card cannot detect Ground Faults.

    Only the Network Repeater while in passive mode and only able to silence it’s own audible device (piezo buzzer) may be networked.

    Up to 126 ULDF6000 and ULDF6000RM panels or passive repeaters can be networked together to operate as a single networked system. To achieve this each panel must be fitted with a network card (supplied at additional cost.)

    When operating as a networked system all fire and fault event information is displayed at every panel, silencing and resetting of alarms can also be carried out from any panel on a networked system if panels are suitably configured.

    Networked panels are connected using a loop topology as illustrated.

    Networked panels can be used as active repeaters; alternatively a low cost passive repeater is available.

    Figure 14 . NeowNrk example

    NET1

    NET1

    NET2

    NET2

  • 25

    5 Technical specification

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    4.1 Battery maintenance installation cautionsInitial preparation before installation:-

    Verify no abnormalities on battery case (like crack or leakage)

    Free air space must be provided between each battery. Recommended minimum space is 5~10mm (0.02~0.04 inches).

    Set the batteries firmly in the equipment. Otherwise, batteries may be damaged, or connection conductivity may be decreased due to shock. When batteries are used in vibration conditions, they shall be mounted in upright position and with proper cushion for protecting vibration.

    Avoid mixed usage of batteries differing in capacity, manufacturer, storage or charge/discharge conditions. Batteries may be damaged after cycles due to difference in electrical characteristics.

    Regular check and replace precautions

    Measure the total voltage of the batteries during float charge to see whether there is any abnormal deviation and investigate the situation.

    TRANSPORTATION PRECAUTIONS

    Handle the batteries carefully to avoid injuries. Avoid moisture or rain on the batteries and cartons. Transport the batteries in the upright position and avoid abnormally strong shock / vibration.

    Do not lift a battery by its terminal. Otherwise, internal construction may be damaged and leakage may occur.

    Other precautions

    Clean battery with wet soft cloth. Never apply oil, polyvinyl chloride or organic solvents (like gasoline and paint thinner) to the battery. Otherwise, battery cover may be cracked / deform and acid leakage will result.

    Do not disassemble the battery. Otherwise, sulphuric acid will flow out.

    If sulphuric acid deposit on to skin or cloth, wash immediately with water. If splashed into eyes, wash with a large amount of water and consult medical physician immediately.

    Avoid dusting by cloth duster or dry cloth (particularly chemical textile), as they will generate static electricity which is dangerous.

    Wash your hands after handling battery.

    Do not short the battery terminals.

    Never dispose battery into fire.

    5 Technical specificationPower Supply (Approved UL 864 9th Edition) Mains

    Nominal VoltageNominal CurrentMaximum CurrentInput Fuse R1

    : 120 Vac: 240 Vac: 75mA: 1.5A: NTC SG39 Imax 4Amp

    Output Voltage including tolerances : 26V = 18.5 to 29.5Volts: 26V RAW = 18.5 to 29.5Volts: 5Volt Output = 4.6V to 5.5V

    Ripple Voltages 26V = 800mV26V RAW = 800mV5Volt Output = 430mV

    Maximum Loadings 26V O/P = 0.98A I max b26V RAW O/P = 1.7A I max b5V = 0.5A

    Standby Current(4 Loops Loaded)

    : 26V = 280mA I max a: 26V RAW = 150mA I max a: 26V = 280mA I max: 26V RAW = 150mA I max: 5V = 43mA

    ULDF6000 and ULDF6000RM is protected by an internal thermal device, this requires no maintenance.

    I max a, I max b & I min = Current as specified in UL 864 9th Edition

    Batteries

    Number of BatteriesManufacturer:CapacityBattery FuseMaximum battery currentStandby current (mA)Maximum Charging Current to the BatteriesFloat VoltageFinal Voltage

    : 2:YUASA NP12-12: 12 Ah: 6.3A Anti-Surge (F4): 3.5 Amps:175 (4 loops), 125 (2 loops)

    : 0.970amp: 27.4 Volts: 20.4Volts

    Charging Characteristics : Constant Voltage with 0.970A limit with temperature Compensation

    Maximum current drawn from the batteries when the mains is not available

    : 3.5Amps

    Deep Discharge ProtectionBattery Internal Impedance Fault

    : 20.6 Volts: >0.5 ohms

    CAUTION Risk of explosion if battery is replaced by an incorrect type. Dispose of the used batteries according to the instructions.

  • 26

    5 Technical specification

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    NAC circuits

    Number of sounder circuits : 4

    Total sounder Load : 0.75 Amp max per sounder or 1.5 Amp max per sounder with Wheelock DSM 12/24 (2 circuits)

    Sounder Circuit Fuses (F1/2/3/4)End of line resistor

    : 1.6 Amp (Quick Blow): ULEOLR6K8

    AC Trouble, alarm trouble, trouble outputs

    The auxiliary relays provide fused volt free change over contacts. These contacts are not monitored.

    Max LoadAC Trouble Relay: Fused (PTC)

    : 30 Volts 1 Amp Resistive: 1.1 Amp

    Printer (Optional)

    Type : High speed thermal

    Number of Characters per Line : 40

    Type of paper : 58mm x 46mm Thermal Roll

    Replacement paper roll order code : ADF6PRINTERPAPER

    Mechanical specification

    Weight including batteriesWeight excluding batteriesDimensions (Standard batteries)Type of Material (backbox)Type of Material (Fascia)Flammability RatingTotal Number of knockoutsDiameter of Knock outAnti-Tamper Cover ( Optional)

    : 18Kg: 9Kg: 495mm(L) x 395mm(H) x 180mm(D): Mild Steel (Power Coated): PC/ABS: UL 94 5VA: 51: 20mm

    Material usedFlammability Rating

    : Poly Carbonate: UL 94 5VA

    Outputs

    Terminal blocks: do not use excessive force when tightening the screws.

  • 27

    6 Commissioning

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    6 CommissioningBefore connecting and powering up the panel please ensure you read and understand the manual.

    The following is a summary of the minimum steps to start the Menvier ULDF6000 Fire Alarm Panel.

    1. Read Manual

    2. Ensure all cables are fault free (no ground, Open orshort circuit faults) and follow the procedure below.

    Figure 15 . CNmmissiNning prNcedure

    Loop checking with a multimeter

    The first quick test that should be done on all the loops is to check the continuity of the loops using a multimeter.

    The resistance should be measured start positive to end positive, start negative to end negative, and positive to negative at the start and end of each loop.

    The resistance along the positive line should be less than 50 ohms. The resistance across the negative line should be 2k5 ohms for each device on the loop, e.g. 20 devices should measure 50k ohms.

    The resistance across the loop positive to negative will be in the Mohm region.

    Ensure the screen is continuous around the loop; this reading should be approx 10 ohms.

    The screen should not be bonded to building earth.

    Test the loops with the multimeter set to AC volts – this is to check that there is no induced voltage which could be caused by the cables being run too closely to a high voltage source.

    This will show if anything drastic is wrong with the loop devices wired in backwards breaks etc. If there is a short at the end or start of the loop this will need to be fixed before powering the panel.

    Auto-learn function (see page 46)

    This is accessed through the engineer level access code. When the panel is auto-learned all the devices address information is set up from address 1 upwards from the start of each loop, previous addressing is lost. Once the panel has finished the auto-learn it will reset itself. After this is done reset the panel using the touch screen.

    Check auto config.

    This function has two purposes, the first is to check that when a database has been downloaded the transmitted data matches the device data on the loop and then it highlights any anomalies as device unknown or device type mismatches.

    The second is to pinpoint any o/c or s/c faults on the loop. The panel achieves this by electronically disconnecting the return legs and interrogates the devices on the loop. If there is a break the panel will go to fault stating the first device it cannot see beyond the break. This same function also pinpoints short circuits in the same way, creating a fault beyond the point where an isolator has opened.

    Check the loops with a multimeter

    Auto Learn the panel

    Load to a PC (optional)

    Download from a PC

    Check auto Config

    Run Intermittent Fault search

    Test the device

  • 28 ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    6 Commissioning

    6.1 ConfigurationDetector LED flashing

    The ULDF6000 and ULDF6000RM detector flashing function is used to allow a visual inspection and confirmation that the fire panel is in communication with the installed system devices. This facility can be accessed via the engineering menu and can be switched on or off at any time as required.

    Up/downloading using PC software (see page 45)

    The PC Software enables the panel to upload all the address, location text, any comments and programming of inputs and outputs to be downloaded back to panel. This will speed up commissioning.

    purpose of notifying key personnel who then have the option of initiating a general alarm. All NAC’s circuits, and Auxiliary outputs can be pre-programmed with a delay of up to 10 minutes using Menvier Site Installer software by using a double knock global or zone feature.

    During this condition, the Pre-signal will be lit.

    Alarm verification features

    The panel is equipped with the Alarm verification features used to reduce unwanted false alarm wherein a typical smoke detector report alarm condition for minimum period of time in order to accept a valid alarm condition. This period can be programmed to 15s, 30s or 60s.

    During the minimum 60-second alarm confirmation period following the retard-reset-restart period, re-actuation of the same detector that initiated the alarm verification cycle, actuation of another smoke detector on the same circuit (zone), or an alarm from another zone shall result immediately in an alarm signal from the control unit.

    6.2 Panel programmingPositive alarm sequence

    The positive alarm sequence will program a delay to the NAC’s, Alarm relay and Auxiliary for a period of 15 seconds, if the alarm is acknowledge, it will silence the piezo sounder and start a timer which prevents activation of these outputs for an additional time duration which can be user programmed for up three minutes. After the programmed delay, all the outputs will activate if the source of the alarm is not cleared. If the alarm is not acknowledged or reset during the first time delay of 15 seconds, all the appropriate outputs will be activated.

    Note: If a second alarm occurs during either time delays, the alarm will proceed immediately causing activation of the appropriate output zones.

    Pre-signal: An arrangement where the operation of an automatic detector or initial operation of manual station actuates only on selected devices or devices for the

    Figure 16 . Alarm verificaoiNn oiming diagram

    ULD

    F60

    00

    t=0 seconds

    Retard-Reset-Restart Period -Maximum 60 Seconds

    No Alarm at Control Unit No Alarm at Control Unit

    t=n seconds

  • 29

    6 Commissioning

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    6.3 PC Commissioning Software6.3.1 Device input programming

    Normal Standby Default setting

    Alarm Panel reports fire from device.

    Trouble Panel reports fire from device.

    Reset Panel resets.

    NAC Silence Silence all currently active sounders.

    Supervisory Panel reports supervisory from device.

    Drill Panel manually set into alarm.

    NAC Programming

    Pre-Signal

    The output of a device when triggered can be delayed up to 10minutes - based on a user defined value in minutes.

    This programming option is enabled when a value other than zero is entered inside the ‘Delay’ window.

    Every panel must be configured with the pre-programmed delay Double Knock per Zone is required for outputs to operate pre signal.

    Double Knock feature will override:

    • Pre programmed delays

    • Alarm Verification

    • Positive Alarm Sequencing

  • 30

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    7 Panel controls & indicators7.1 Touch screen display

    The Touch Screen is a multi-function display consisting 320x240 dots featuring high intensity backlighting. In normal operation, the display indicates as above with the backlighting off.

    During an event on the system the display shows the FIRST EVENT and LAST EVENT plus other events as space allows.

    The last 2 lines are normally used to display the total number of events, but they are also used for scrolling fire conditions, faults, pre alarms or disabled devices independently or for displaying a reduced menu when in fire condition.

    When an event occurs the Touch Screen backlighting comes on unless there is a mains power supply fault.

    Use the Touch Screen to scroll through all active events on the system by using the SCROLL UP and SCROLL DOWN buttons (available at access level)

    1. You can display the contents of the log and also viewdetails of any Alarms, Troubles, pre-alarms, faults ordisablements. When displaying the system menu onthe Touch Screen, the last 5 lines of the display areshown in reverse text.

    7.2 Panel operationULDF6000 and ULDF6000RM are operated via a backlit touch screen. The default fire screen is shown below. From this screen all the panels’ functions can be operated. The first time you touch the screen the backlight will illuminate the panel.

    Pressing a field will highlight it and forward to the next screen as shown below.

    AccessCode

    AccessCode

    AccessCode

    AccessCode

  • 31

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    7.3 Public access level 1Public access level does not require an access code and allows anybody to review the functions outlined below

    AccessCode

    AccessCode

    AccessCode

    AccessCode

    AccessCode

  • 32

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    7.4 Evacuate (Access level 2)To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter the supervisor mode touch the supervisor button and enter the passcode.

    Enter the Supervisor Mode Passcode and select “Evacuate” on the menu at the top of the screen.

    Select “Yes” to evacuate the building. Select “yes” to silence Alarm.

    7.5 Silence alarmsTo activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter the supervisor mode touch the supervisor button and enter the passcode.

    Enter the Supervisor Mode Passcode and select “Silence Alarms” button as the top of the screen.

  • 33

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    7.6 AcknowledgeTo activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter the supervisor mode touch the supervisor button and enter the passcode.

    Enter the Supervisor Mode and Select “acknowledge” from the Top Menu.

    7.7 ResetEnter the Supervisor Mode and Select “Reset” from the top Menu. Select “Yes” to reset the panel.

  • 34

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    7.8 Pre-alarmsEnter the Supervisor Mode and Select “Pre-Alarms” tab.

    7.10 TroublesEnter Supervisor Mode Passcode and select “Troubles” tab

    7.9 Disabled devicesEnter the Supervisor mode and Select the “Disabled” tab.

    7.11 Enable/disable (Others menu)To activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter the supervisor mode touch the supervisor button and enter the passcode.

    Enter the Supervisor Mode passcode and select the “Others” tab.

    A pre-alarm is shown when a detector appears to register heat or smoke but in a quantity that is insufficient to warrant an alarm.

    Pre-alarm may indicate a buildup of dirt in a smoke detector which can be interpreted by the detector as smoke presence.

    The individual buttons show which devices and the number of devices which have been disabled. Press one of the buttons to display detailed information for a particular category.

  • 35

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    The “Disable All” feature is not permitted in UL864 9th Edition

    The Enable/Disable feature allows the operator to disable part or a whole system by the sub menus shown on the left.

  • 36

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    7.12 PrintTo activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter the supervisor mode touch the supervisor button and enter the passcode.

    Enter the Supervisor Mode and Select the “Others” Tab. Press “Print”

    7.13 Lamp testTo activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter the supervisor mode touch the supervisor button and enter the passcode.

    Enter the Supervisor Mode and Select the “Others” Tab. Press “Lamp Test”

    Select the Information you wish to print from the Buttons Listed

  • 37

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    7.14 Weekly testTo activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter the supervisor mode touch the supervisor button and enter the passcode. Select the others tab as shown below. Press Weekly test.

    Weekly test is now in progress.

    The panel will automatically return to the system healthy screen once the weekly test has been completed.

  • 38

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    7.15 Viewing eventsTo activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter the supervisor mode touch the supervisor button and enter the passcode.

    Enter the Supervisor Mode Passcode. Select the “Others” tab and press View Log.

    Use the scroll bar to view the list of up to 9999 events

    The ULDF6000 and ULDF6000RM event log stores up to 9999 events including, Alarms, Troubles, resets and address changes. Once the maximum 9999 events have been reached ULDF6000 and ULDF6000RM will automatically overwrite the oldest event every time a new event is stored. The event log can only be reset by an approved service engineer.

  • 39

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    7.16 Check auto configTo activate the touch screen, touch the top left corner of the screen until the screen illuminates. To enter the supervisor mode touch the supervisor button and enter the passcode.

    Enter the Supervisor Mode and Select the “Others”

    Tab. Press Check Auto Config. This feature will scan the loop and pinpoint the exact location of any break in the loop wiring and will also identify any changes in the loop configuration (e.g. New devices added or changed device types).

  • 40

    7 Panel controls & indicators

    ULDF6000 INSTALLATION MANUAL PR209-171-508-06 February 2018 www.eaton.com

    Replace device enables an existing device to be replaced with a new device without losing the existing text and sounder programming.

    Replace a single device then use the replace device menu to allocate an existing address to the new device.