TYPE TEST REPORT OF COMPLETE TYPE TEST

132
TUV Rheinland (Shanghai) Co., Ltd. TÜV Rheinland Building, No. 177, Lane 777, West Guangzhong Road, Jing’an District, Shanghai 200072, P.R. China e-mail : [email protected] Internet: http://www.chn.tuv.com GC Hotline:(86) 4008831300 (86) 8009993668 Tel : ( 86/21) 61081188 Fax : (86/21) 61081199 Version 2.0 TYPE TEST REPORT OF COMPLETE TYPE TEST TEST REPORT NO: 50283626 001 ORDER NO: 1244155356 APPARATUS: Intelligent fully insulated metal clad closed switchgear DESIGNATION: GELPAG-MSS-12/1250-31.5 SERIAL No. RD1007/1001/A1 RD1007/1001/A2 Rated voltage: 12 kV Rated normal current : 1250 A Rated short-circuit breaking current: 31.5 kA Rated frequency: 50 Hz Rated short-time w ithstand current: 31.5 kA/ 4 s CLIENT: GELPAG Advanced Technology GmbH Bauhofstraße 20, 68623 Lampertheim, Germany MANUFACTURER: ISEE Electric International Co., Ltd. No.2 The third Xinfeng Road, Torch High-tech Industrial Development Zone, Xiamen 361006,P.R.China ESTING LOCATION: Xi’an High Voltage Apparatus Research Institute Changzhou Co., Ltd. No.159 Qing Yang North Street, Tianning District, Changzhou Jiangsu P.R.China TESTING LABORATORY: TÜV RHEINLAND (SHANGHAI) CO., LTD. TÜV Rheinland Building, No. 177, Lane 777, West Guangzhong Road, Jing’an District, Shanghai 200072, P.R. China DATE(S) OF TESTS: 19 th August until 30 th August 2019 The apparatus, constructed in accordance with the description, drawings and photographs incorporated in this Report, has been subjected to the series of proving tests in accordance with IEC/TS 62271-304:2008 IEC 62271-1:2007 sub-clauses: 6.9.1.2, 6.9.2.3, 6.9.2.4, 6.9.3.2, 6.9.3.3 IEC 62271-200:2011 sub-clauses: 6.2.6.1, 6.2.6.2, 6.2.9, 6.2.10, 6.4-6.6, 6.7.1,.6.101.2, 6.101.3, 6.102 This Type Test Report has been issued by TÜV Rheinland following exclusively the STL Guides. The tests performed in Laboratory were under supervision of TÜV Rheinland engineers. The results are shown in the record of Proving Tests and the oscillograms attached hereto. The values obtained and the general performance are considered to comply with the above Standard and to justify the ratings assigned by the manufacturer as listed on page 6. The Report applies only to the apparatus tested. The responsibility for conformity of any apparatus having the same designations with that tested rests with the Manufacturer. This Report consists of 132 sheets in total. This Report falls under the scope of the accreditation Report CNAS L0223 of China National Accreditation Service for Conformity Assessment. See information sheet (page 3). © Copyright: Only integral reproduction of this Report, or reproductions of this page accompanied by any page(s) on which are stated the endorsed ratings of the apparatus tested are permitted without written permission from TÜV Rheinland. Electronic copies in e.g. PDF-format or scanned version of this Report may be available and have the status “for information only”. The sealed and bound version of the Report is the only valid version. Verified by: Reviewed by: 11/06/2019 Chengjun Wang/PM 16/09/2019 Rui Ma/ Reviewer Date Name/Position signature Date Name/Position signature

Transcript of TYPE TEST REPORT OF COMPLETE TYPE TEST

Page 1: TYPE TEST REPORT OF COMPLETE TYPE TEST

TUV Rheinland (Shanghai) Co., Ltd. TÜV Rheinland Building, No. 177, Lane 777, West Guangzhong Road, Jing’an District, Shanghai 200072, P.R.

China

e-mail : [email protected] Internet: http://www.chn.tuv.com GC Hotline:(86) 4008831300 (86) 8009993668 Tel : (86/21) 61081188 Fax : (86/21) 61081199

Version 2.0

TYPE TEST REPORT OF COMPLETE TYPE TEST

TEST REPORT NO: 50283626 001 ORDER NO: 1244155356

APPARATUS: Intelligent fully insulated metal clad closed switchgear

DESIGNATION: GELPAG-MSS-12/1250-31.5 SERIAL No. RD1007/1001/A1

RD1007/1001/A2

Rated voltage: 12 kV Rated normal current : 1250 A

Rated short-circuit breaking current: 31.5 kA Rated frequency: 50 Hz

Rated short-time w ithstand current: 31.5 kA/ 4 s

CLIENT: GELPAG Advanced Technology GmbH Bauhofstraße 20, 68623 Lampertheim, Germany

MANUFACTURER: ISEE Electric International Co., Ltd. No.2 The third Xinfeng Road, Torch High-tech Industrial Development Zone, Xiamen 361006,P.R.China

ESTING LOCATION: Xi’an High Voltage Apparatus Research Institute Changzhou Co., Ltd. No.159 Qing Yang North Street, Tianning District, Changzhou Jiangsu P.R.China

TESTING LABORATORY: TÜV RHEINLAND (SHANGHAI) CO., LTD. TÜV Rheinland Building, No. 177, Lane 777, West Guangzhong Road, Jing’an District, Shanghai 200072, P.R. China

DATE(S) OF TESTS: 19th August until 30th August 2019

The apparatus, constructed in accordance with the description, drawings and photographs incorporated in this Report, has been subjected to the series of proving tests in accordance with

IEC/TS 62271-304:2008 IEC 62271-1:2007 sub-clauses:

6.9.1.2, 6.9.2.3, 6.9.2.4, 6.9.3.2, 6.9.3.3

IEC 62271-200:2011 sub-clauses:

6.2.6.1, 6.2.6.2, 6.2.9, 6.2.10, 6.4-6.6, 6.7.1,.6.101.2, 6.101.3, 6.102

This Type Test Report has been issued by TÜV Rheinland following exclusively the STL Guides. The tests performed in Laboratory were under supervision of TÜV Rheinland engineers.

The results are shown in the record of Proving Tests and the oscillograms attached hereto. The values obtained and the general performance are considered to comply with the above Standard and to justify the ratings assigned by the manufacturer as listed on page 6.

The Report applies only to the apparatus tested. The responsibility for conformity of any apparatus

having the same designations with that tested rests with the Manufacturer.

This Report consists of 132 sheets in total.

This Report falls under the scope of the accreditation Report CNAS L0223 of China National Accreditation Service for

Conformity Assessment. See information sheet (page 3).

© Copyright: Only integral reproduction of this Report, or reproductions of this

page accompanied by any page(s) on which are stated the endorsed ratings of

the apparatus tested are permitted without written permission from TÜV

Rheinland. Electronic copies in e.g. PDF-format or scanned version of this Report

may be available and have the status “for information only”. The sealed and bound version of the Report is the only valid version.

Verified by: Reviewed by:

11/06/2019 Chengjun Wang/PM 16/09/2019 Rui Ma/ Reviewer

Date Name/Position signature Date Name/Position signature

Page 2: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 INFORMATION SHEET

Page 2 of 132

1 Certificate A Certificate contains a record of a series of type tests carried out strictly in accordance with a recognized standard. The equipment tested has fulfilled the requirements of this standard and the relevant ratings assigned by the manufacturer are endorsed by TÜV Rheinland. The Certificate is applicable only to the equipment tested. TÜV Rheinland is responsible for the validity and the contents of the Certificate. The responsibility for conformity of any apparatus having the same designation as the one tested rests with the manufacturer. The Certificate contains the essential drawings and a description of the equipment tested. Detailed rules are given in TÜV Rheinland’s Certification procedure.

2 Type Test Report A Type Test Report contains a record of a series of type tests carried out strictly in accordance with a standard recognized by TÜV Rheinland. The test object has fulfilled the requirements of this standard and the relevant ratings assigned by the manufacturer are endorsed by TÜV Rheinland. The Type Test Report is applicable only to the test object. TÜV Rheinland is responsible for the validity and the contents of the Type Test Report. The responsibility for conformity of any apparatus having the same designation as the one tested rests with the manufacturer. The Type Test Report contains the essential drawings and a description of the equipment tested. TÜV Rheinland issues six basic Type Test Certificates (Reports) may be issued by STL Guides. STL Procedure They are as follows:

2.1 Type Test Report of Complete Type Test This Report provides the verification of all the rated characteristics of the equipment as assigned by the manufacturer, by means of the performance of all type tests specified by the Standards.

2.2 Type Test Report of Dielectric Performance This Report provides the verification of all dielectric ratings by means of the performance of the appropriate type tests specified by the Standards.

2.3 Type Test Report of Temperature Rise Performance This Report provides the verification of the temperature-rise limits together with measurement of the main circuit resistance, by means of the performance of the appropriate type tests specified by the Standards.

2.4 Type Test Report of Short-Circuit / Making and Breaking Performance This Report provides the verification of the rated characteristics with respect to short-circuit and/or making and breaking performance, by means of the performance of the appropriate type tests specified by the Standards.

2.5 Type Test Report of Switching Performance This Report provides the verification of the switching ratings (e.g. capacitive current) by means of the performance of the appropriate type tests specified by the Standards. 2.6 Type Test Report of Internal Arc Performance This Report provides the verification of the behavior under internal arc conditions of switchgear and controlgear by means of the appropriate tests specified as type tests by the Standards.

3 Performance Test Report A Performance Test Report contains a record of one or more tests which have been carried out according to a recognized standard and/or the client’s instructions. These tests are not necessarily in accordance with a recognized standard. The test results do not verify ratings of the test object. TÜV Rheinland issues three types of Performance Test Report.

3.1 The tests have been carried out strictly in accordance with a recognized standard. The test object has complied with the relevant requirements.

Page 3: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 INFORMATION SHEET

Page 3 of 132

This sentence will display on the front page of Performance Test Report if the tests have been performed in accordance with a recognized standard, but the series of tests does not completely fulfil the requirements for a Certificate of Compliance (for example, if the number of test series is not a complete series of type tests).The Report contains verified drawings and a description of the test object. The condition of the test object after the tests is assessed and recorded in the Report.

3.2 The tests have been carried out in accordance with the client’s instructions. Test procedure and test parameters were based on a recognized standard. This sentence will display on the front page of Performance Test Report if the number of test duties, the test procedure and the test parameters are based on a recognized standard and related to the ratings assigned by the manufacturer. Verification of the drawings (if submitted) and assessment of the condition after the tests is only done on the client’s request.

3.3 The tests have been carried out according to the client’s instructions. This sentence will display on the front page of Performance Test Report if the test shots, test procedure and/or test parameters are not in accordance with a recognized standard.

4 Standards When reference is made to a standard, and the date of issue is not stated, this applies to the latest issue, including amendments which have been officially published prior to the date of the tests.

5 Official and uncontrolled test documents The official test documents of TÜV Rheinland Laboratory are issued in bound form. Uncontrolled copies may be provided as loose sheets or as a digital file for convenience of reproduction by the client. The copyright has to be respected at all times.

6 Accuracy of measurement In the table of test results the measured quantities are given in three digits. This method of presentation does not indicate an accuracy. The guaranteed uncertainty in the figures mentioned, taking into account the total measuring system, is less than 5%, unless mentioned otherwise.

7 Qualified by CNAS (China National Accreditation Service for Conformity Assessment) Xi’an High Voltage Apparatus Research Institute Changzhou Co., Ltd.( )have been entered in the CNAS-register for laboratories under resp. CNAS L0223 for the testing services as defined in the Field of Accreditation. The accreditation is carried out in accordance with ISO/IEC17025

Page 4: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

TABLE OF CONTENTS

Page 4 of 132

TABLE OF CONTENTS:

1 IDENTIFICATION OF THE APPARATUS TESTED .............................................................................6

1.1 Ratings assigned by the manufacturer ..................................................................................................................... 6 1.2 Description of apparatus tested ................................................................................................................................. 6 1.3 List of documents and photographs .......................................................................................................................... 9

2 GENERAL INFORMATION ........................................................................................................... 11

2.1 The tests were witnessed by .................................................................................................................................... 11 2.2 The tests were observed by ...................................................................................................................................... 11 2.3 Summary of tests......................................................................................................................................................... 11 2.4 Applicable standards................................................................................................................................................... 12

3 GROUP1-195388G-HV................................................................................................................. 13

3.1 Symbols and abbreviation used in test report....................................................................................................... 13 3.2 HV test equipment measuring uncertainties ......................................................................................................... 13 3.3 General of dielectric test ............................................................................................................................................ 14 3.4 Power frequency withstand voltage test................................................................................................................. 14 3.5 Lightning impulse withstand voltage test ............................................................................................................... 17 3.6 Dielectric test on auxiliary and control circuit ........................................................................................................ 25 3.7 Partial discharge tests ................................................................................................................................................ 26 3.8 Verification of the IP coding....................................................................................................................................... 28 3.9 Condensation test ....................................................................................................................................................... 29 3.9.1 Arrangement in climatic chamber and test condition inspection. .................................................................. 29 3.9.2 Power frequency withstand voltage test in climatic chamber ........................................................................ 30 3.9.3 Lightning impulse withstand voltage test ............................................................................................................ 33 3.9.4 Dielectric test on auxiliary and control circuit..................................................................................................... 42

4 GROUP1-195388G-HP................................................................................................................. 44

4.1 Symbols abbreviation and uncertainty of measurements used in test report................................................ 44 4.2 No-load test before high power test. ....................................................................................................................... 44 4.3 Short-time and peak withstand current tests......................................................................................................... 49 4.3.1 Short-time and peak withstand current tests for primary circuit .................................................................... 50 4.3.1.1 Test apparatus primary circuit resistance before testing ............................................................................. 50 4.3.1.2 Test apparatus primar circuit photographs before testing ........................................................................... 50 4.3.1.3 Test circuit: ............................................................................................................................................................. 51 4.3.1.4 Test oscillograms .................................................................................................................................................. 51 4.3.1.5 No-load mechanical characteristics for sequence O .................................................................................... 54 4.3.1.6 Test apparatus photographs after testing ....................................................................................................... 55 4.3.1.7 Test apparatus condition/ inspection after testing ......................................................................................... 55 4.3.1.8 Test apparatus primary circuit resistance after testing................................................................................. 55 4.3.2 Short-time and peak withstand current tests for earthing switch .................................................................. 55 4.3.2.1 Test apparatus primar circuit photographs before testing ........................................................................... 56 4.3.2.2 Test circuit: ............................................................................................................................................................. 56 4.3.2.3 Test oscillograms .................................................................................................................................................. 56 4.3.2.4 Test apparatus photographs after testing ....................................................................................................... 59 4.3.2.5 Test apparatus condition/ inspection after testing ......................................................................................... 59 4.3.3 Short-time and peak withstand current tests for earthing connection.......................................................... 59 4.3.3.1 Test apparatus primar circuit photographs before testing ........................................................................... 60 4.3.3.2 Test circuit: ............................................................................................................................................................. 60 4.3.3.3 Test oscillograms .................................................................................................................................................. 61 4.3.3.4 Test apparatus photographs after testing ....................................................................................................... 64 4.3.3.5 Test apparatus condition/ inspection after testing ......................................................................................... 64 4.4 Electrical endurance class E1 test test-duty T100s to T100a (50 Hz) ............................................................ 65 4.4.1 Test-duty: T100s....................................................................................................................................................... 65 4.4.1.1 Test circuit: ............................................................................................................................................................. 65 4.4.1.2 Test photograph of before testing ..................................................................................................................... 66 4.4.1.3 Test oscillogram .................................................................................................................................................... 66 4.4.1.4 Test apparatus condition/ inspection after testing ......................................................................................... 70

Page 5: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

TABLE OF CONTENTS

Page 5 of 132

4.4.1.5 Test apparatus photograph after testing.......................................................................................................... 71 4.4.2 Test-duty: T100a ...................................................................................................................................................... 71 4.4.2.1 Test apparatus photograph before testing ...................................................................................................... 72 4.4.2.2 Test circuit: ............................................................................................................................................................. 72 4.4.2.3 Test oscillogram .................................................................................................................................................... 72 4.4.2.4 Test apparatus condition/ inspection after testing ......................................................................................... 79 4.4.2.5 Test apparatus photograph after testing.......................................................................................................... 79 4.5 Test apparatus inspection after high power........................................................................................................... 79 4.5.1 No-load test inspection ........................................................................................................................................... 79 4.5.2 Dielectric test inspection for the state of vacuum. ............................................................................................ 83 4.5.3 Measurement of contact resistance inspection................................................................................................. 84 4.6 Short-circuit making tests of earthing circuit. ........................................................................................................ 84 4.6.1 Short-circuit making tests for earthing circuit. ................................................................................................... 84 4.6.1.1 Test apparatus photographs before testing .................................................................................................... 85 4.6.1.2 Test circuit: ............................................................................................................................................................. 85 4.6.1.3 Test oscillograms .................................................................................................................................................. 85 4.6.1.4 Test apparatus photographs after testing ....................................................................................................... 91 4.6.1.5 Test apparatus condition/ inspection after testing ......................................................................................... 91 4.6.1.6 Power frequency withstand voltage test inspection...................................................................................... 92 4.6.1.7 Lightning impulse withstand voltage test inspection..................................................................................... 93

5 GROUP2-195388G-MT AND EMC ................................................................................................. 97

5.1 The lab measurement test equipment calibration ................................................................................................ 97 5.2 Symbols and abbreviation used in report .............................................................................................................. 97 5.3 Measurement of resistance of main circuit ............................................................................................................ 97 5.4 Temperature-rise tests................................................................................................................................................ 98 5.5 Temperature rise tests on auxiliary and control equipment ............................................................................... 99 5.6 Mechanical operation test for circuit breaker ......................................................................................................100 5.7.Mechanical operaton test for disconnector.......................................................................................................... 112 5.8.Mechanical operaton test for earthing switch...................................................................................................... 113 5.9.Mechanical operaton test for earthing switch...................................................................................................... 115 5.10 Electromagnetic compatibility tests(EMC tests)............................................................................................... 117 5.10.1 Emission tests from the auxiliary and control circuits.................................................................................. 117 5.10.2 Electrical fast transient/burst test for Class3 .................................................................................................123 5.10.3 Oscillatory wave immunity test for Class2 .....................................................................................................125 5.10.4 Ripple on d.c. input power port immunity test for Class2 ...........................................................................127 5.10.5 Voltage dips, short interruptions and voltage variations on d.c. input power port immunity tests.....129

6 DRAWINGS .............................................................................................................................. 131

Page 6: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

IDENTIFICATION OF THE APPARATUS TESTED

Page 6 of 132

1 IDENTIFICATION OF THE APPARATUS TESTED

1.1 Ratings assigned by the manufacturer

1.2 Description of apparatus tested

1.2.1 General description of apparatus tested: The circuit breaker in an assembly with intelligent fully insulated metal clad closed switchgear independent manual operation and/or dependent motor stored energy operation function.

Manufacturer ISEE Electric International Co., Ltd.

Designation GELPAG-MSS-12/1250-31.5

Serial number/year of manufacture RD1007/1001/A1 for MT and EMC RD1007/1001/A2 for HP and HV

Sampling procedure By the manufacturer

Rated voltage (Ur) 12 kV X

Rated normal current (Ir) 1250 A X

Number of poles 3 X

Rated power-frequency(fr) 50 Hz X

Rated short-circuit breaking current(Isc) 31.5 kA X

Rated short-time withstand current(main circuit Ik) 31.5 kA X

Rated peak withstand current(main circuit Ip) 80 kA X

Rated duration of short-circuit(main circuit tk) 4 s X

Rated short-time withstand current(earthing connection circuit Ik)

27.4 kA X

Rated peak withstand current(earthing connection circuit Ip)

69.6 kA X

Rated duration of short-circuit(earthing connection circuit tk)

2 s X

Rated power frequency withstand voltage(Ud) 42 kV X

Rated lightning impulse withstand voltage(Up) 95 kV X

Rated power frequency withstand voltage (across gap ceramic vacuum interrupter Ud)

48 kV X

Rated lightning impulse withstand voltage (across gap ceramic vacuum interrupter Up)

95 kV X

Test requirements for main switching devices (with VCB)

Test duty: T100s, T100a X

DS, ES mechanical endurance class M1 X

Short-circuit making tests of earthing circuit (CB+ES)

(12 kV, 80 kA_2C – x – 2C – y – 1C) X

Degree of protection IP4X/IP2X X

Emission tests from the auxiliary and control circuits EMC X

Electrical fast transient/burst test EMC/Class 3 X

Oscillatory wave immunity test EMC/Class 3 X

Ripple on d.c. input power port immunity test. EMC/Class 2 X

Voltage dips, short interruptions and voltage variations on input power port immunity tests

EMC X

Rated supply voltage of closing device DC220V X

Rated supply voltage of opening device DC220V X

X = This rating has been proved by the tests of this report. HP: high power, HV: high voltage, MT: mechanical temperature, EMC: electromagnetic compatibility DS:disconnector switch, ES:earthing switch, VCB:vaccum circuit breaker, CB:circuit breaker

Page 7: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

IDENTIFICATION OF THE APPARATUS TESTED

Page 7 of 132

CB Mechanism: Stored energy closing (springs, charged by motor). Stored energy opening (springs, charged at closing). Supply voltage closing coil: DC220 V Supply voltage opening coil: DC220 V Supply voltage motor: DC220 V 1.2.2 The main parts of apparatus tested assigned by manufacturer as follow: 1.2.2.1 Circuit breaker module

Notes:

Manufacturer ISEE Electric International Co.,Ltd.

Designation GELPAG-SIRING-12/1250-31.5

Serial number/year of manufacture RD1007/1501/A1 for MT and EMC RD1007/1501/A2 for HV and HP

Sampling procedure By the manufacturer

Rated voltage (Ur) 12 kV

Rated normal current (Ir) 1250 A

Number of poles 3

Rated power-frequency(fr) 50 Hz

Rated short-circuit breaking current(Isc) 31.5 kA

Rated short-time withstand current(main circuit Ik) 31.5 kA

Rated peak withstand current(main circuit Ip) 80 kA

Rated out-of-phase breaking current 7.9 kA

Rated duration of short-circuit(main circuit tk) 4 s

Rated power frequency withstand voltage(Ud) 42 kV

Rated lightning impulse withstand voltage(Up) 95 kV

Rated power frequency withstand voltage (across gap ceramic vacuum interrupter Ud)

48 kV

Rated lightning impulse withstand voltage (across gap ceramic vacuum interrupter Up)

95 kV

Operating sequence: -Auto-reclosing duty -Non auto-reclosing duty

O-0.3 s-CO-3 min-CO for auto-reclosing duty O-3 min-CO-3 min- CO for non auto-reclosing duty

Rated line-charging current, 10 A

Rated cable-charging current 25 A

Mechanical endurance class M2

First-pole-to-clear factor 1.5

Minimum opening time 20 ms

DC component 57%

Electric endurance class(auto-reclosing duty) E1

Electric endurance class E2

Circuit-breaker class for capacitive-current breaking C2

Emission tests from the auxiliary and control circuits EMC

Electrical fast transient/burst test EMC/Class 3

Oscillatory wave immunity test EMC/Class 3

Ripple on d.c. input power port immunity test. EMC/Class 2

Voltage dips, short interruptions and voltage variations on input power port immunity tests

EMC

Rated supply voltage of closing device DC220V

Rated supply voltage of opening device DC220V

Page 8: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

IDENTIFICATION OF THE APPARATUS TESTED

Page 8 of 132

HP: high power, HV: high voltage, MT: mechanical temperature 1.2.2.2 Vacuum interrupter

Notes: HP: high power, HV: high voltage, MT: mechanical temperature 1.2.2.3 CB Mechanism. Stored energy closing (springs, charged by motor) Stored energy opening (springs, charged at closing)

1.2.2.4 Disconnector (three-position)

1.2.2.5 Busbar

1.2.2.6 Travel recorder Travel recorder attached to main contact shaft. Linear sensor with contact travel.

Type WL-41153

Rated voltage 12 kV

Rated current 1250 A

Rated power-frequency 50 Hz

Rated symmetrical interrupting current 31.5 kA

Year of manufacture 2019-01

Serial number of vacuum interrupter HP and HV MT and EMC A:S024997 B:S001173 C:S000444

A:S001212 B:S000441 C:S001208

Manufacturer Eaton Electrical Co, Ltd.

Type Assembly with circuit breaker

Supply voltage closing coil DC220 V

Rated current of opening coil 1.5 A

Supply voltage opening coil DC220 V

Rated current of closing coil 1.5 A

Supply voltage motor AC/DC 220V

Supply voltage motor power 90 W

Manufacturer ISEE Electric International Co.,Ltd.

Type Special use in three-position(isolator and earthing) assembly with circuit breaker

Rated voltage 12 kV

Rated current 1250 A

Rated power-frequency 50 Hz

Rated symmetrical interrupting current 31.5 kA

Rated peak withstand current 80 kA

Rated duration of short-circuit 4s

Operating device Manual spring operating mechanism

Manufacturer ISEE Electric International Co.,Ltd.

Main busbar Copper rod ᶲ30 mm

Earthing busbar TMY-30X8 mm Manufacturer ISEE Electric International Co., Ltd.

Page 9: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

IDENTIFICATION OF THE APPARATUS TESTED

Page 9 of 132

1.3 List of documents and photographs

1.3.1 The apparatus tested is guaranteed by the manufacturer to comply with the following technical documents:

1.3.2 Drawings submitted by the manufacturer and identified by XIHARI laboratory and TÜV Rheinland has verified that these drawings adequately represent the equipment tested. -The following drawings were attached in the report:

-The following drawings were returned to the manufacturer:

Notes: The laboratory is responsible for checking that the drawings and data schedules submitted adequately represent essential details of the equipment tested, but is not responsible for the accuracy of detailed drawings. 1.3.3 Confirmed date of the apparatus tested: 17-06-2019 1.3.4 Commission apparatus tested photographs:

12G9950200 GELPAG-MSS-12/1250-31.5 intelligent fully insulated metal clad closed siwtchgear technical specification

12G9950300 GELPAG-MSS-12/1250-31.5 intelligent fully insulated metal clad closed siwtchgear test program

12G0005200 General assembly drawing Approved date:05-2019

12G0004700 Circuit breaker assembly Approved date:06-2019

150-41153 Vacuum interrupter Approved date:02-2015

Page 10: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

IDENTIFICATION OF THE APPARATUS TESTED

Page 10 of 132

Page 11: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GENERAL INFORMATION

Page 11 of 132

2 GENERAL INFORMATION

2.1 The tests were witnessed by

2.2 The tests were observed by

2.3 Summary of tests

Name Company

Ms. Liqin Yan ISEE Electric International Co.,Ltd.

Mr. Jingsong Xu TÜV RHEINLAND (SHANGHAI) CO., LTD.

Name Company

Mr. Ting Wang Xi’an High Voltage Apparatus Research Institute Co., Ltd.

Mr. Ruitao Xie Xi’an High Voltage Apparatus Research Institute Co., Ltd.

Mr. Wei Du Xi’an High Voltage Apparatus Research Institute Co., Ltd.

Group Test records No. Type test Subclause Verdict

1 RD1007/1001/A2 195388G-HV

Power frequency voltage withstand tests (Phase to phase & phase to earth: 42 kV/1min Across the isolating distance and vacuum contact(AID): 48 kV/1min

IEC 62271-200 6.2.6.1

Passed

Lightning impulse voltage withstand tests (Phase to phase & phase to earth:

±95 kV/15 times Across the isolating distance and vacuum contact(AID):

±95 kV/15 times

IEC 62271-200 6.2.6.2

Passed

Dielectric tests on auxiliary and control Circuits(Power frequency withstand voltage:2 kV/1min)

IEC 62271-200 6.2.10

Passed

Partial discharge tests (Test voltage: 1.2×12 kV Required partial discharge quantity: ≤10 pC)

IEC62271-200 6.2.9

Passed

Verification of IP code Enclosure:IP4X Front door open and between compartments:IP2X

IEC62271-200 6.7.1

Passed

2 RD1007/1001/A1 195388G-MT

Measurement of resistance of the main current path

IEC 62271-200 6.4

Passed

Temperature-rise tests 1375 A, 50 Hz (1.1xIr required by client)

IEC 62271-200 6.5

Passed

Temperature rise tests on auxiliary and control equipment

IEC 62271-200 6.5.5

Passed

Mechanical operation tests ( DS, ES :M1 class,5000 times)

IEC 62271-200 6.102

Passed

2 RD1007/1001/A1 195388G-EMC

Emission tests from the auxiliary and control circuits

IEC 62271-1 6.9.1.2

Passed

Electrical fast transient/burst test Class 3

IEC 62271-1 6.9.2.3

Passed

Oscillatory wave immunity test Class 3

IEC 62271-1 6.9.2.4

Passed

Page 12: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GENERAL INFORMATION

Page 12 of 132

Notes: HV: high voltage, MT: mechanical temperature, HP: high power, VCB: Vacuum circuit breaker,

AID: Across the isolating distance, ES :earthing switch, EMC: electromagnetic compatibility

2.4 Applicable standards

When reference is made to a standard and the date of issue is not stated, this applies to the latest issue, including amendments, which have been officially published prior to the date of the tests.

Ripple on d.c. input power port immunity test. Class 2

IEC 62271-1 6.9.3.2

Passed

Voltage dips, short interruptions and voltage variations on input power port immunity tests

IEC 62271-1 6.9.3.3

Passed

Group Test records

No. Type test Subclause Verdict

1

RD1007/1001/A2

195388G-HV

Condensation

test

Condensation test Degrees of severity of service conditions under condensation: CH

IEC/TS 62271-304

Passed

Power frequency voltage withstand tests (Phase to phase & phase to earth: 42 kV/1min Across the vacuum contact and isolating distance(AID): 48 kV/1min

IEC 62271-200

6.2.6.1 Passed

Lightning impulse voltage withstand tests

(Phase to phase & phase to earth:

±95 kV/15 times Across open vacuum contacts and isolating distance(AID): ±95 kV/15 times

IEC 62271-200

6.2.6.2 Passed

Dielectric tests on auxiliary and control Circuits(Power frequency withstand voltage:2 kV/1min)

IEC 62271-200

6.2.10 Passed

Group Test records No. Type test Subclause Verdict

1 RD1007/1001/A2

195388G-HP

Measurement of resistance of the main current path

IEC 62271-200 6.4

Passed

Short time withstand current and peak withstand current tests (Main circuit and ES: 50 Hz, 31.5 kA, 4 s, peak 80 kA)

IEC 62271-200 6.6

Passed

Measurement of resistance of the main current path

IEC 62271-200 6.4

Passed

Test requirements for main switching devices(VCB) T100s, T100a (12 kV, 50 Hz, 31.5 kA, peak 80 kA, DC:57%)

IEC 62271-200 6.101.2

Passed

Inspection test -- Passed

Short time withstand current and peak withstand current tests (Earthing connection: 50 Hz, 27.4 kA, 2 s, peak 69.6 kA)

IEC 62271-200 6.6

Passed

Short-circuit making tests for earthing circuit.(CB+ES) (12 kV, 31.5 kA, peak 80 kA, 2C – x – 2C – y – 1C))

IEC62271-200 6.101.3

Passed

Inspection test -- Passed

Page 13: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP1-195388G-HV

Page 13 of 132

3 GROUP1-195388G-HV

3.1 Symbols and abbreviation used in test report

Symbols and abbreviation Description

LI Lightning impulse

SI Switching impulse

LIC Chopped lightning impulse

IG Impulse voltage generator

DCG Direct current voltage generator

HV High voltage

LV Low voltage

PF Power frequency

P-to-P & P-to-E Phase to phase and phase to earth

SN Serial number

NO.A Application number

NO.D Discharge number

T-OSC Typical Oscillogram

kVp Voltage peak value

RMS Root mean square

Uc Expected voltage value

Ut Measured voltage

Kt1 Correction factor for P-to-P and/or P-to-E

Kt2 Correction factor for across open switching device/isolating distance

Kt3 Correction factor for the most unfavorable position of earthing switch

Kt4 Combined voltage correction factor for P-to-P

K1 Air density correction factor

Ka Altitude correction factor

Ku Altitude correction factor for dielectric test on auxiliary and control

Ue Rated withstand voltage

Up Phase voltage

AID Across the isolating distance

DS Disconnector switches

ES Earthing switches

ISPW Inspection window

VCB Vacuum circuit breaker

CB Circuit breaker

CX Measured capacitance in Measurement of dielectric dissipation factor and capacitance

CX0 Required capacitance in Measurement of dielectric dissipation factor and capacitance

3.2 HV test equipment measuring uncertainties

NO Measuring system Expanded uncertainty

1 Voltage measurement system U<2% (k=2)

2 Impulse voltage wave and time measurement system U<5% (k=2)

3 Radio interference voltage voltage measurement system U=2dB (k=2)

Page 14: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP1-195388G-HV

Page 14 of 132

4

Temperature: THP-2000 Temperature and humidity recorder

U<1.0℃ (k=2)

5 Absolute humidity: THP-2000 Temperature and humidity recorder

U<1g/m3(k=2)

6 Air pressure:DYM3 Air pressure meter U<0.2kPa (k=2)

7 tanδ&C measuring system C:U<0.15% (k=2)

tanδ:U<2.5% (k=2)

8 PD measuring system

<20 pC:U=2.3 pC (k=2)

20pC~50pC:U=5.3 pC (k=2)

>50 pC:U=12% (k=2)

3.3 General of dielectric test

3.3.1 Apparatus tested serial No.RD1007/1001/A2 3.3.2 According IEC62271-200:2011 3.3.3 Apparatus tested is a new clean intelligent integrated fully insulated high voltage AC three-phase vacuum circuit-breaker, including vacuum interrupter, operating mechanism, disconnector, bus bar and the other components in an assembly LSC2B switchgear as in service. 3.3.4 Phase: A, B, C are supply incoming unit (moved contacts) and a, b, c are supply outgoing unit (fixed contacts), F: frame connection the earthing. 3.3.5 The tested object was placed on four 35 kV insulators during the condensation test.

3.4 Power frequency withstand voltage test

3.4.1 1min power frequency withstand voltage test.

AT Regulator Rp Protection resistance

CT Current transformer TT PF transformer

TO Tested object A Currentmeter

C1 H.V arm capacitance C2 L.V arm capacitance

V2 Voltmeter Type:PV2-1A SN:071261

150kV Power frequency voltage measuring systems

Parameters of TT system U/S (kV/kVA) fTT(Hz) Rp(kΩ) C1(pF) C2(μF)

150/300 50.0 5.0 500.0 0.50

Page 15: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP1-195388G-HV

Page 15 of 132

Atmospheric conditions:P=100.9 kPa t=25.8 ℃ RH=55.2 %

Correction factor:Kt1=0.977 Kt2=/ K1=/ Ka=/ Performed date:25-06-2019

Testing position Voltage applied to Earthed terminal Uc(kVr.m.s)

Ut(kVr.m.s)

NO.A NO.D T-OSC

P-to-P & P-to-E

Aa BCbcF &ISPW

42.0

42.0 1 0 --

Bb ACacF & ISPW 42.1 1 0 --

Cc ABabF & ISPW 42.0 1 0 --

Circuit breaker

A BCabcF

42.0

42.0 1 0 --

a ABCbcF 42.1 1 0 --

B ACabcF 42.0 1 0 --

b ABCacF 41.9 1 0 --

C ABabcF 42.1 1 0 --

c ABCabF 42.0 1 0 --

Circuit breaker (AID)

A a

48.0

48.0 1 0 --

a A 48.0 1 0 --

B b 48.1 1 0 --

b B 47.9 1 0 --

C c 48.0 1 0 --

c C 48.1 1 0 --

Result: Passed Notes: a)①Uc=Ue×Kt1×Ka, choosing Kt1=1.000 during test

b)SN of vacuum interrupter: A:S024997, B:S001173, C:S000444 Atmospheric conditions:P=100.9 kPa t=25.8℃ RH=55.2 %

Correction factor:Kt1=0.977 Kt2=/ K1=/ Ka=/ Performed date:25-06-2019

Testing position Voltage applied to Earthed terminal Uc(kV r.m.s)

Ut(kV r.m.s)

NO.A NO.D T-OSC

Disconnector (AID)

A BCabcF

42.0

42.0 1 0 --

a ABCbcF 42.0 1 0 --

B ACabcF 42.1 1 0 --

b ABCacF 42.0 1 0 --

C ABabcF 42.1 1 0 --

c ABCabF 41.9 1 0 --

Disconnector (AID)

A a

48.0

48.1 1 0 --

a A 48.0 1 0 --

B b 48.0 1 0 --

b B 47.9 1 0 --

C c 48.0 1 0 --

c C 48.1 1 0 --

Page 16: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP1-195388G-HV

Page 16 of 132

3.4.2 1min power frequency withstand voltage test photographs

Page 17: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP1-195388G-HV

Page 17 of 132

3.5 Lightning impulse withstand voltage test

Lightning impulse withstand voltage test

C IG capacitance Rf Front resistance Rt Tail resistance S Sphere gap R Damping resistance C1 H.V arm capacitance

TO Tested object C2 L.V arm capacitance DIVMS Digital impulse voltage measuring systems

400kV/20 kJ Impulse voltage measuring systems

Parameters of IG system

Type U(kV) C(μF) Rf(Ω) Rt(Ω) C1(pF) C2(μF)

(LI) 400 0.25 465 213 300 0.555

Page 18: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP1-195388G-HV

Page 18 of 132

3.5.1 Lightning impulse withstand voltage test for P-to-P and P-to-E

Atmospheric conditions:P=100.9 kPa t=25.8℃ RH=55.2%

Correction factor:Kt1=0.977 Kt2=-- K1=-- Ka=-- Performed date: 25-06-2019

Testing

position

Voltage

applied to

Earthed

terminal

Uc

(kVp) Ut(kVp)

NO.A

NO.D

T-OSC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

P-to-P

&

P-to-E

Aa BCbcF

ISPW

95.0

+ 95.2 94.8 95.1 95.3 94.9 94.7 95.2 95.4 94.8 95.3 95.0 94.8 95.0 95.2 95.3 15 0 01

- 94.8 95.3 94.9 95.3 95.4 95.2 94.9 95.3 95.2 95.1 94.9 94.7 95.2 94.7 95.0 15 0 02

Bb ACacF

ISPW

+ 95.1 95.3 95.2 94.8 94.6 95.3 94.7 94.8 95.1 95.0 95.2 94.8 95.1 95.3 95.0 15 0 03

- 95.0 95.1 94.9 94.8 95.0 95.2 94.9 95.1 95.2 94.6 95.0 94.9 95.3 95.4 94.9 15 0 04

Cc ABabF

ISPW

+ 94.6 95.1 95.4 95.0 95.2 95.3 94.7 95.2 94.8 95.2 94.9 95.1 95.3 95.0 95.3 15 0 05

- 95.1 94.9 95.2 94.8 94.9 95.2 94.8 95.3 95.0 94.6 95.2 94.7 95.2 95.1 95.3 15 0 06

Circuit breaker

A BCabcF

95.0

+ 95.1 95.3 95.0 95.2 95.0 94.9 95.1 94.6 95.3 95.2 94.8 95.3 95.0 94.7 95.3 15 0 07

- 95.0 95.1 94.8 95.3 95.2 94.9 94.7 94.6 95.4 94.8 94.9 95.0 95.3 95.1 95.2 15 0 08

a ABCbcF + 95.2 94.9 95.2 94.9 95.3 94.7 95.3 95.2 95.2 95.0 94.8 95.1 95.4 94.8 94.9 15 0 09

- 94.9 95.1 94.9 95.0 95.1 94.7 95.0 94.6 94.8 95.0 95.1 95.0 95.3 95.2 95.1 15 0 10

B ACabcF + 94.8 94.9 95.0 95.4 95.1 95.0 95.4 95.3 94.9 95.3 94.7 95.0 94.6 95.3 95.2 15 0 11

- 95.3 94.7 95.2 94.9 94.6 95.1 94.7 95.0 94.9 95.3 94.8 94.9 95.0 95.1 95.2 15 0 12

b ABCacF + 95.3 95.2 95.0 94.7 94.9 95.3 94.6 95.2 94.9 94.7 95.2 94.8 95.3 95.2 95.0 15 0 13

- 94.9 95.1 95.2 95.0 94.8 95.2 95.3 95.2 95.3 94.9 95.0 95.4 94.8 95.3 94.9 15 0 14

C ABabcF + 95.1 95.3 94.8 95.1 95.3 95.4 95.0 94.9 95.2 94.9 95.1 95.3 94.7 95.1 95.3 15 0 15

- 95.0 95.3 94.9 95.0 95.2 94.9 95.1 94.9 94.8 94.7 95.2 95.0 94.6 95.3 95.1 15 0 16

c ABCabF + 94.6 95.2 95.2 95.4 95.1 95.1 95.3 94.7 95.2 94.9 95.0 95.1 95.1 95.0 94.8 15 0 17

- 95.0 95.1 94.9 95.2 95.0 94.9 94.8 95.0 94.8 95.1 94.8 95.2 95.3 94.7 95.0 15 0 18

Result:Passed

Notes:

a) Uc=Ue×Kt1×Ka, choosing Kt1=1.000 during test b) 50%, 65%, 80% Uc are applied in sequence to verify parameters) c) SN of vacuum interrupter: A:S024997,B:S001173,C:S000444

Page 19: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP1-195388G-HV

Page 19 of 132

3.5.2 Lightning impulse withstand voltage test for AID of disconnector Lightning impulse withstand voltage test for P-to-P and P-to-E

Atmospheric conditions:P=100.9 kPa t=25.8℃ RH=55.2%

Correction factor:Kt1=-- Kt2=-- K1=-- Ka=-- Performed date: 25-06-2019

Testing

position

Voltage

applied to

Earthed

terminal

Uc

(kVp) Ut(kVp)

NO.A

NO.D

T-OSC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Disconnector (AID)

A BCabcF

95.0

+ 95.3 95.3 94.7 95.2 95.4 95.2 95.3 95.1 95.3 94.6 95.0 94.8 95.1 94.9 95.0 15 0 19

- 94.8 95.4 95.3 94.9 95.1 95.0 95.0 95.3 95.3 95.0 95.1 94.6 94.9 95.2 95.1 15 0 20

a ABCbcF + 94.9 95.0 95.1 94.8 95.2 95.1 95.0 95.3 95.4 94.7 95.0 94.6 95.2 95.3 95.1 15 0 21

- 94.8 95.3 94.9 94.7 95.2 94.8 95.1 94.9 95.4 95.0 94.7 94.9 95.2 95.3 94.8 15 0 22

B ACabcF + 94.9 94.7 95.0 95.2 95.3 94.9 95.3 95.4 94.7 95.2 95.4 95.1 95.1 94.8 95.3 15 0 23

- 94.8 94.9 95.2 94.9 95.3 94.6 95.4 94.8 95.2 95.1 94.9 95.0 94.7 95.1 94.9 15 0 24

b ABCacF + 95.2 95.0 94.8 94.9 95.0 94.9 95.1 95.3 95.4 94.8 94.9 95.3 94.7 95.1 95.2 15 0 25

- 94.9 95.2 95.3 95.2 95.1 95.2 94.8 94.9 95.2 94.8 95.2 94.7 95.3 95.0 95.0 15 0 26

C ABabcF + 94.7 94.9 95.3 95.0 95.1 94.8 95.3 94.6 95.3 95.0 95.0 95.0 95.2 94.8 95.0 15 0 27

- 94.7 95.2 94.6 95.1 95.4 95.0 95.2 94.6 95.2 94.7 95.3 95.1 95.3 94.8 94.6 15 0 28

c ABCabF + 95.3 95.1 94.7 95.2 94.8 95.0 94.8 94.8 95.1 94.8 94.9 95.2 95.1 95.3 95.0 15 0 29

- 94.7 94.8 95.2 95.0 95.3 95.1 94.7 95.2 95.0 95.0 94.9 95.3 95.1 94.7 95.1 15 0 30

Result:Passed

Notes:

a) Uc=Ue×Kt1×Ka, choosing Kt1=1.000 during test b) 50%, 65%, 80% Uc are applied in sequence to verify parameters)

Page 20: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 20 of 132

3.5.3 Lightning impulse withstand voltage test oscillogram

IPVBT195388G--01

IPVBT195388G--02

IPVBT195388G--03

IPVBT195388G--04

IPVBT195388G--05

IPVBT195388G--06

Page 21: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 21 of 132

IPVBT195388G--07

IPVBT195388G--08

IPVBT195388G--09

IPVBT195388G--10

IPVBT195388G--11

IPVBT195388G--12

Page 22: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 22 of 132

IPVBT195388G--13

IPVBT195388G--14

IPVBT195388G-15

IPVBT195388G--16

IPVBT195388G--17

IPVBT195388G--18

Page 23: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 23 of 132

IPVBT195388G--19

IPVBT195388G--20

IPVBT195388G--21

IPVBT195388G--22

IPVBT195388G--23

IPVBT195388G--24

Page 24: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 24 of 132

IPVBT195388G--25

IPVBT195388G--26

IPVBT195388G--27

IPVBT195388G--28

IPVBT195388G--29

IPVBT195388G--30

3.5.4 Lightning impulse withstand voltage test photograph

Page 25: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 25 of 132

3.6 Dielectric test on auxiliary and control circuit

3.6.1 Dielectric test on auxiliary and control circuit

Atmospheric conditions:P=100.9 kPa t=25.8℃ RH=55.2%

Correction factor:Kt1=0.977 Kt2=-- K1=-- Ka=-- Performed date: 25-06-2019 a) Voltage applied between the auxiliary and control circuit connected together as a whole and the frame of the switching device.

Page 26: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 26 of 132

Testing position

Voltage applied to

Earthed terminal

Uc (kVrms)

Ut (kVrms)

NO.A NO.D T-OSC

Auxiliary and control

circuit

Secondary terminals

F 2.0 2.0 1 0 --

b)Voltage applied between each part of the auxiliary and control circuits, which in normal use may be insulated from the other parts , and the other parts connected together to the frame.

Testing position

Voltage applied to

Earthed terminal

Uc

(kVrms)

Ut

(kVrms) NO.A NO.D T-OSC

Auxiliary and control

circuit

Each secondary terminals

Other secondary terminals &F

2.0 2.0 1 0 --

Result:Passed

Notes: a) Duration: 1min b) Uc=Ue×Kt1×Ku, choosing Kt1=1.000 during test c) Uc is the altitude correction factor specified by: IEC 60664-1:2007 3.6.2 Dielectric test on auxiliary and control circuit photograph

3.7 Partial discharge tests

3.7.1 Partial discharge tests circuit

Page 27: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 27 of 132

Partial discharge tests circuit

TT PF transformer Rp Protection resistance

C1 H.V arm capacitance C2 L.V arm capacitance

CD Coupling device Cc Coupling capacitor

TO Tested object

VM Voltmeter Type:PV0501 SN:4104272

G Step voltage generator Type:LDC-5 SN:JG00005-1

MI Partial discharge measuring instrument

Type:LDS-6 SN:212142

Frequency:10kHz-500kHz

150kV Power frequency voltage measuring systems Validity:2020-07-29

Parameters of TT System U/S (kV/kVA) fTT(Hz) Rp(kΩ) C1(pF) C2(μF)

150/150 50.0 5.0 500.0 0.470

Atmospheric conditions:P=100.9 kPa t=25.8℃ RH=55.2% Performed date: 25-06-2019

Testing position

Voltage applied to

Earthed terminal

Pre-stressing voltage (t=10s)

Test voltage (t=60s)

PD value (pC)

Required value (pC) Uc(kVr.m.s) Ut(kVr.m.s) Uc(kVr.m.s) Ut(kVr.m.s)

P-to-P & P-to-E

Aa BCbcF 15.6 15.6 14.4 14.4 7.2

≤10

Bb ACacF 15.6 15.5 14.4 14.4 6.4

Cc ABabF 15.6 15.7 14.4 14.3 5.9

Disconnector (AID)

A BCabcF 15.6 15.6 14.4 14.4 6.3

a ABCbcF 15.6 15.6 14.4 14.4 5.4

B ACabcF 15.6 15.5 14.4 14.3 5.7

b ABCacF 15.6 15.6 14.4 14.3 6.1

C ABabcF 15.6 15.7 14.4 14.5 4.9

c ABCabF 15.6 15.6 14.4 14.4 5.6

Result: Passed Notes:a)Step voltage generator:10 pC, background noise≤2.0 pC. b)SN of vacuum interrupter: A:S024997, B:S001173, C:S000444 3.7.2 Partial discharge test photograph

Page 28: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 28 of 132

3.8 Verification of the IP coding

3.8.1 Verification of the IP4X for metal-enclosure. Atmospheric conditions: P=100.9 kPa t=25.8℃ RH=55.2%

Rigid steel rod Φ1.0 mm, the object probe is pushed against any opening of the enclosure with the force of 1N. The probe can not penetrate any opening. It’s enclosure reached the requirement of IP4X. Result: Passed.

3.8.1.2 Photograph for verification of the IP4X for metal-enclosure.

3.8.1.3 Verification of the IP2X for different compartments and front door open status. The jointed test finger, whose diameter is 12.0 mm and length is 80.0 mm, is pushed against any opening between different compartments and front door open with the force of 10 N. And the jointed test finger cannot penetrate any opening. The different compartments reached the requirement of IP2X.

Page 29: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 29 of 132

Result: Passed. 3.8.1.4 Photograph for verification of different compartments and front door open reached requirement of IP2X.

3.9 Condensation test

Atmospheric conditions:P=100.5 kPa t=27.9℃ RH=56.7% Performed date: 21-08-2019 to 22-08-2019

3.9.1 Arrangement in climatic chamber and test condition inspection.

1.The tested object was placed on 35 kV insulator in climatic test room as figure B.1 requirements according to IEC/TS62271-304:2008 2.Wiped up the external insulation parts of switchgear, the secondary terminals of current transformer were shorten, the secondary terminals of voltage transformer were opened, the heating or dehumidification devices were moved during the test. 3.The tested object were placed in artificial climate chamber for twelve hours before condensation test. The ambient temperature of artificial climate chamber was 3.8℃.

4. Opened the spray device and increased the relative humidity of artificial climate chamber to 95% -100% as soom as possible (measured value:91%). When the surface of external insulation parts formed a stable condensation and carried out dielectric test. 5. Parameters of TT system and water system.

Over current setting of test transformer 1.5 A Water conductivity 150 μS/cm

6 Test object photograph in artificial climate chamber

Page 30: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 30 of 132

3.9.2 Power frequency withstand voltage test in climatic chamber

3.9.2.1 1min power frequency withstand voltage test.

Page 31: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 31 of 132

AT Regulator Rp Protection resistance

CT Current transformer TT PF transformer

TO Tested object A Currentmeter

C1 H.V arm capacitance C2 L.V arm capacitance

V2 Voltmeter Type:PV2-1A SN:071261

OSC Oscilloscope Type:TDS3032B SN:B030680

150kVPower frequency voltage measuring systems Parameters of TT system

U/S (kV/kVA) fTT(Hz) Rp(kΩ) C1(pF) C2(μF) 150/300 50.0 5.0 500.0 0.5

Performed date:22-08-2019 Atmospheric conditions:P=100.6 kPa t=32.2-32.7 ℃ RH=90.7-94.2%

Correction factor:Kt1=/ Kt2=/ K1=/ Ka=/

Testing position

Voltage applied to

Earthed terminal Uc

(kVr.m.s) Ut

(kVr.m.s) NO.A NO.D T-OSC

P-to-P & P-to-E

Aa BCbcF and ISPW 42.0

42.1 1 0 -- Bb ACacF and ISPW 42.0 1 0 -- Cc ABabF and ISPW 41.9 1 0 --

Outer shutter

ABC Shutter 42.0

42.0 1 0 --

abc Shutter 42.0 1 0 --

VCB (AID)

A BCabcF

42.0

42.1 1 0 --

a ABCbcF 42.0 1 0 --

B ACabcF 41.9 1 0 --

b ABCacF 42.0 1 0 --

C ABabcF 41.8 1 0 --

c ABCabF 42.1 1 0 --

VCB (AID)

A a

48.0

48.1 1 0 -- a A 48.0 1 0 -- B b 48.1 1 0 -- b B 47.9 1 0 -- C c 48.0 1 0 -- c C 48.1 1 0 --

Result: Passed Notes:

a)①Uc=Ue×Kt1×Ka, choosing Kt1=1.000 during test b)SN of vacuum interrupter: A:S024997,B:S001173,C:S000444 3.9.2.2 1min power frequency withstand voltage test photograph:.

Page 32: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 32 of 132

Short duration power frequency withstand voltage (Across open vacuum contacts)

P-to-P and P-to-E short duration power frequency withstand voltage test

Page 33: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 33 of 132

3.9.3 Lightning impulse withstand voltage test

Lightning impulse withstand voltage test

C IG capacitance Rf Front resistance Rt Tail resistance S Sphere gap R Damping resistance C1 H.V arm capacitance

TO Tested object C2 L.V arm capacitance DIVMS Digital impulse voltage measuring systems

400kV/20 kJ Impulse voltage measuring systems

Parameters of IG system

Type U(kV) C(μF) Rf(Ω) Rt(Ω) C1(pF) C2(μF)

(LI) 400 0.25 465 213 300 0.555

Page 34: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 34 of 132

3.9.3.1 Lightning impulse withstand voltage test for P-to-P and P-to-E Atmospheric conditions:P=100.6 kPa t=32.7-37.2℃ RH=90.7-94.2%

Correction factor:Kt1=-- Kt2=-- K1=-- Ka=-- Performed date: 22-08-2019

Testing position

Voltage applied to

Earthed terminal

Uc (kVp)

Ut(kVp)

NO.A

NO.D

T-

OSC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

P-to-P &

P-to-E

Aa BCbcF ISPW

95.0

+ 95.1 95.1 95.3 95.3 94.9 95.1 95.2 95.2 95.4 95.0 95.1 95.4 95.0 95.2 95.1 15 0 01 - 94.8 94.7 94.9 95.1 95.4 94.8 95.4 94.8 94.9 94.9 95.1 95.3 95.2 95.0 95.4 15 0 02

Bb ACacF ISPW

+ 94.8 95.0 94.8 94.9 95.4 94.8 95.0 95.4 94.9 95.1 94.8 95.1 94.7 94.7 95.3 15 0 03 - 95.4 95.0 94.9 95.1 95.9 94.7 94.8 94.7 95.0 94.8 95.5 95.0 95.3 94.8 95.4 15 0 04

Cc ABabF ISPW

+ 95.0 94.7 95.0 94.8 95.4 95.2 95.2 94.7 94.7 94.7 95.0 95.3 94.9 95.3 94.7 15 0 05 - 94.8 95.4 95.5 95.4 94.9 95.3 94.9 94.8 95.1 94.8 94.9 95.1 95.3 95.1 94.9 15 0 06

Result:Passed

Notes: a) Uc=Ue×Kt1×Ka, choosing Kt1=1.000 during test b) 50%, 65%, 80% Uc are applied in sequence to verify parameters) c) SN of vacuum interrupter: A:S024997,B:S001173,C:S000444

Page 35: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 35 of 132

3.9.3.2 Lightning impulse withstand voltage test for AID of VCB Atmospheric conditions:P=100.6 kPa t=32.7-37.2℃ RH=90.7-94.2%

Correction factor:Kt1=0.941 Kt2=-- K1=-- Ka=-- Performed date: 22-08-2019

Testing position

Voltage applied to

Earthed terminal

Uc (kVp)

Ut(kVp)

NO.A

NO.D

T-OSC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

AID Of VCB

A BCabcF

95.0

+ 95.2 95.2 95.1 94.8 94.8 95.2 95.0 95.2 96.0 95.4 95.1 95.4 95.2 95.4 94.8 15 0 07

- 94.7 94.9 95.0 94.8 94.8 94.9 95.4 94.9 94.8 95.1 95.4 94.7 94.9 94.8 94.8 15 0 08

a ABCbcF + 94.8 95.3 94.9 95.3 94.9 94.8 94.8 95.2 94.7 95.4 95.7 94.8 94.7 95.3 95.2 15 0 09

- 95.0 94.9 94.9 95.4 95.1 95.3 95.4 95.0 95.4 95.3 95.0 94.9 94.7 94.9 94.8 15 0 10

B ACabcF + 95.3 95.4 95.4 94.7 95.0 95.3 95.0 94.7 95.1 95.6 95.4 95.0 94.9 94.8 95.3 15 0 11

- 94.7 95.2 95.2 94.9 95.2 94.8 95.3 95.2 94.7 94.9 94.9 95.5 95.4 94.8 95.0 15 0 12

b ABCacF + 95.2 94.8 94.9 94.9 95.0 94.9 94.8 94.9 95.3 95.2 95.3 94.8 95.9 94.7 95.1 15 0 13

- 95.3 95.1 94.9 95.4 95.2 95.1 95.3 95.2 94.8 95.2 95.4 96.0 95.2 95.1 95.4 15 0 14

C ABabcF + 95.1 94.7 95.2 95.0 95.4 95.4 95.3 94.9 95.2 94.7 94.8 94.8 94.7 94.9 95.4 15 0 15

- 95.2 95.1 95.0 95.1 95.4 94.8 95.2 95.4 94.7 95.4 94.9 95.0 94.9 94.7 95.0 15 0 16

c ABCabF + 95.4 95.3 94.9 94.7 95.3 94.8 95.4 95.1 94.9 94.7 94.7 94.8 95.2 96.0 94.8 15 0 17

- 94.9 95.2 95.4 94.7 95.1 94.9 95.1 94.9 94.9 95.4 95.4 95.1 95.3 95.2 94.8 15 0 18

Result:Passed

Notes: a) Uc=Ue×Kt1×Ka, choosing Kt1=1.000 during test b) 50%, 65%, 80% Uc are applied in sequence to verify parameters) c) SN of vacuum interrupter: A:S024997,B:S001173,C:S000444

Page 36: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 36 of 132

3.9.3.3 Lightning impulse withstand voltage test for AID of disconnector Atmospheric conditions:P=100.6 kPa t=32.7-37.2℃ RH=90.7-94.2%

Correction factor:Kt1=0.941 Kt2=-- K1=-- Ka=-- Performed date: 22-08-2019

Testing position

Voltage applied to

Earthed terminal

Uc (kVp)

Ut(kVp)

NO.A

NO.D

T-OSC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Disconnector (AID)

A BCabcF

95.0

+ 95.0 94.9 94.9 95.2 95.7 94.8 94.9 95.2 94.9 95.2 95.4 95.2 94.9 95.0 95.2 15 0 19

- 95.2 94.7 95.1 95.1 95.3 95.0 95.2 94.7 95.1 94.7 94.7 95.9 94.9 95.5 95.2 15 0 20

a ABCbcF + 95.2 95.2 94.7 95.3 95.2 94.8 95.2 95.1 95.1 95.9 95.4 95.1 95.1 95.4 95.0 15 0 21

- 95.1 94.8 95.2 94.8 95.4 95.6 94.9 95.1 95.1 94.9 94.8 95.3 95.0 94.7 95.2 15 0 22

B ACabcF + 95.4 95.4 95.0 95.1 95.1 95.1 95.1 95.3 95.2 94.8 94.8 94.7 95.0 95.3 95.1 15 0 23

- 95.0 95.2 95.2 94.7 95.0 95.4 94.7 95.1 94.9 95.0 95.3 95.2 95.0 95.1 95.8 15 0 24

b ABCacF + 94.8 94.8 94.9 94.8 94.8 95.4 95.3 95.4 95.2 95.4 94.8 94.7 94.7 95.0 94.7 15 0 25

- 94.9 95.3 95.3 94.9 95.3 95.3 95.2 95.2 95.0 94.8 94.7 95.0 95.6 95.0 95.1 15 0 26

C ABabcF + 94.9 94.8 95.4 94.7 94.9 95.0 95.4 94.7 95.4 95.4 95.4 95.2 94.9 95.4 94.9 15 0 27

- 94.8 94.7 95.2 95.5 95.4 94.8 94.7 94.9 95.2 95.1 94.9 95.4 94.9 95.0 94.8 15 0 28

c ABCabF + 95.2 95.1 95.0 95.3 95.0 94.8 94.7 95.4 95.0 95.4 94.7 95.3 94.8 95.5 95.3 15 0 29

- 95.0 95.0 95.5 94.9 95.1 95.4 95.0 95.4 95.0 95.3 94.8 95.5 95.4 95.5 95.1 15 0 30

Result:Passed

Notes: a) Uc=Ue×Kt1×Ka, choosing Kt1=1.000 during test b) 50%, 65%, 80% Uc are applied in sequence to verify parameters)

Page 37: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 37 of 132

3.9.3.4 Lightning impulse withstand voltage test oscillograms

IPVBT195388G--01

IPVBT195388G--02

IPVBT195388G--03

IPVBT195388G--04

IPVBT195388G--05

IPVBT195388G--06

Page 38: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 38 of 132

IPVBT195388G--07

IPVBT195388G--08

IPVBT195388G--09

IPVBT195388G--10

IPVBT195388G--11

IPVBT195388G--12

Page 39: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 39 of 132

IPVBT195388G--13

IPVBT195388G--14

IPVBT195388G--15

IPVBT195388G--16

IPVBT195388G--17

IPVBT195388G--18

Page 40: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 40 of 132

IPVBT195388G--19

IPVBT195388G--20

IPVBT195388G--21

IPVBT195388G--22

IPVBT195388G--23

IPVBT195388G--24

Page 41: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 41 of 132

IPVBT195388G--25

IPVBT195388G--26

IPVBT195388G--27

IPVBT195388G--28

IPVBT195388G--29

IPVBT195388G--30

Page 42: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 42 of 132

3.9.3.5 Lightning impulse withstand voltage test photograph

3.9.4 Dielectric test on auxiliary and control circuit

3.9.4.1 Dielectric test on auxiliary and control circuit Atmospheric conditions:P=100.6 kPa t=32.7-37.2℃ RH=90.7-94.2%

Correction factor:Kt1=-- Kt2=-- K1=-- Ka=--

Page 43: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HV

Page 43 of 132

Performed date: 22-08-2019 a) Voltage applied between the auxiliary and control circuit connected together as a whole and the frame of the switching device.

Testing position

Voltage applied to

Earthed terminal

Uc (kVrms)

Ut (kVrms)

NO.A NO.D T-OSC

Auxiliary and control

circuit

Secondary terminals

F 2.0 2.0 1 0 --

b)Voltage applied between each part of the auxiliary and control circuits, which in normal use may be insulated from the other parts , and the other parts connected together to the frame.

Testing position

Voltage applied to

Earthed terminal

Uc

(kVrms)

Ut

(kVrms) NO.A NO.D T-OSC

Auxiliary and control

circuit

Each secondary terminals

Other secondary terminals &F

2.0 2.0 1 0 --

Result:Passed

Notes:

a) Duration: 1min 3.9.4.2 Dielectric test on auxiliary and control circuit photograph

Page 44: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 44 of 132

4 GROUP1-195388G-HP

4.1 Symbols abbreviation and uncertainty of measurements used in test report

Symbols and abbreviation Description

I coil Coil current of test apparatus

Ia Phase A current through test apparatus

Ib Phase B current through test apparatus

Ic Phase C current through test apparatus

Uab Voltage across test apparatus line value

Ubc Voltage across test apparatus line value

Uac Voltage across test apparatus line value

HFUab High frequency voltage across test apparatus line value

HFUbc High frequency voltage across test apparatus line value

HFUac High frequency voltage across test apparatus line value

Ts1 Contact separation signal

Ts2 Contact separation signal

Tr Travel signal

Tro Time signal of contact separation

USab Source voltage line value

USbc Source voltage line value

USac Source voltage line value

ULa Load voltage line value

ULb Load voltage line value

ULc Load voltage line value

Ua Voltage across test apparatus phase value

Ub Voltage across test apparatus phase value

Uc Voltage across test apparatus phase value

Ufab Generator voltage line value

Ufbc Generator voltage line value

Ufca Generator voltage line value

-short-circuit current , applied voltage and recovery voltage ≤5%. -evaluated with a coverage probability of 95% corresponding to a coverage factor k=2 under the assumption of a normal distribution.

4.2 No-load test before high power test.

4.2.1Test oscillograms

195388G-01 195388G-02 195388G-03 195388G-04 195388G-05

Page 45: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 45 of 132

No-load test-195388G-01

Operating voltage: d.c C:220V O: 220V Test sequence:C

Test time: 01-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A of insulating rod SN of vacuum interrupter: A:S024997, B:S001173, C:S000444

Opening time:[ms] Phase A:-- Phase B:-- Phase C:-- Opening coil current:[A]--

Closing time: [ms] Phase A:31.3 Phase B: 31.5 Phase C: 31.6

Closing coil current:[A] 0.98

Opening time:[ms] Phase A:-- Phase B:-- Phase C:-- Opening coil current:[A]--

Opening-closing time [ms]:-- Closing-opening time [ms]:--

Page 46: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 46 of 132

No-load test-195388G-02

Operating voltage: d.c C:220V O: 220V Test sequence:O-0.3s-CO

Test time: 01-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A of insulating rod SN of vacuum interrupter: A:S024997, B:S001173, C:S000444

Opening time:[ms] Phase A:23.9 Phase B:23.7 Phase C:23.7 Opening coil current:[A] 0.90

Closing time: [ms] Phase A:-- Phase B: -- Phase C: --

Closing coil current:[A]--

Opening time:[ms] Phase A:-- Phase B:-- Phase C:-- Opening coil current:[A] --

Opening-closing time [ms]:-- Closing-opening time [ms]:--

Page 47: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 47 of 132

No-load test-195388G-03

Operating voltage: d.c C:220V O: 220V Test sequence:O-0.3s-CO

Test time: 01-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A of insulating rod SN of vacuum interrupter: A:S024997, B:S001173, C:S000444

Opening time:[ms] Phase A:24.1 Phase B:23.9 Phase C:23.9

Opening coil current:[A] 0.91

Closing time: [ms] Phase A:31.2 Phase B: 31.4 Phase C: 31.5

Closing coil current:[A]0.98

Opening time:[ms] Phase A:22.3 Phase B:22.1 Phase C:22.1

Opening coil current:[A] 0.90

Opening-closing time [ms]: 299.6 Closing-opening time [ms]: 99.1

Page 48: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 48 of 132

No-load test-195388G-04

Operating voltage: d.c C:242V O: 242V Test sequence:O-0.3s-CO

Test time: 01-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A of insulating rod SN of vacuum interrupter: A:S024997, B:S001173, C:S000444

Opening time:[ms] Phase A:22.4 Phase B:22.2 Phase C:22.2

Opening coil current:[A]1.01

Closing time: [ms] Phase A:30.2 Phase B:30.4 Phase C:30.5

Closing coil current:[A] 1.08

Opening time:[ms] Phase A:22.0 Phase B:21.8 Phase C:21.8

Opening coil current:[A] 1.00

Opening-closing time [ms]: 300.3 Closing-opening time [ms]: 99.8

No-load test-195388G-05

Page 49: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 49 of 132

4.3 Short-time and peak withstand current tests

Apparatus tested circuit breaker serial No. RD1007/1501/A2 cooperated with switchgear serial No.:

Operating voltage: d.c C:187V O: 143 V Test sequence:O-0.3s-CO

Test time: 01-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A of insulating rod SN of vacuum interrupter: A:S024997, B:S001173, C:S000444

Opening time:[ms] Phase A:36.1 Phase B:35.9 Phase C:35.9

Opening coil current:[A]0.56

Closing time: [ms] Phase A:33.5 Phase B: 33.7 Phase C: 33.9

Closing coil current:[A] 0.82

Opening time:[ms] Phase A:34.1 Phase B:34.0 Phase C:34.0

Opening coil current:[A] 5.70

Opening-closing time [ms]: 298.0 Closing-opening time [ms]: 98.6

Page 50: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 50 of 132

RD1007/1001/A2

4.3.1 Short-time and peak withstand current tests for primary circuit

a) Supply on cables compartment of test apparatus, go through CB and disconnector. Top copper busbar compartment side of switchgear were short circuit. The three-position disconnector was in the main position. b) Test circuit phase sequence: A B C against test apparatus phase sequence: A B C.

c) Between the test apparatus and earth was insulation and insulation resistance not less than 60 M, measured with d.c. of 500 V one minute. d) The test apparatus enclosure go through diameter 0.1 mm length 5 cm copper fuse connected the earthing.

4.3.1.1 Test apparatus primary circuit resistance before testing

-Test method: The resistance measurement was performed by measuring the voltage drop at a certain current(DC 100 A). -Test results:

Phase A (L1) B (L2) C (L3) Interrupter serial No. S024997 S001173 S000444

Resistance (µ) 67.1 66.2 66.9

Ambient temperature (℃) 23.6

4.3.1.2 Test apparatus primar circuit photographs before testing

Page 51: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 51 of 132

4.3.1.3 Test circuit:

G = Generator L = Reactor TO = Test Object GB =Generator Breaker MB = Master Breaker U = Voltage Measurement to earth MS = Make Switch T = Power Transformer I = Current Measurement

`

Supply parameter Power (MVA) 136 Frequency (Hz) 50 Phase 3 Voltage (kV) 2.50 Current (kA) 31.5

Impedance () Pending

Power factor <0.15 Neutral No earthed

Pretest parameter Voltage (kV) 0.85 Current (kA) 10.7

Impedance () 45.9x10-3

Load parameter Short-circuit point No earthed

4.3.1.4 Test oscillograms

190903-002 to 190903-003

Page 52: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 52 of 132

Ia

213.0 kA

-1176.0 kA

Ib

420.0 kA

-969.0 kA

Ic

635.0 kA

-754.0 kA

Ua

1500.0 kV

-1000.0 kV

Ub

1850.0 kV

-650.0 kV

Uc

2175.0 kV

-325.0 kV

Unit1

19.0

-1.0

扫描编号: 1 50.00 ms/div088.0 ms 544.5 ms

Ia 138.9 kA pu

Ib 138.9 kA pu

Ic 138.9 kA pu

Ua 250.0 kV pu

Ub 250.0 kV pu

Uc 250.0 kV pu

Test Parameters(试验参数)

Phase/line 相/线 -- A B C

Current, peak 电流峰值 kA -80.5 71.0 49.3

Current value, r.m.s. 电流有效值 kA 27.3 27.4 27.3

Average current value 电流平均有效值 kA 27.4

Current duration 电流持续时间 ms 321 321 321

Rated short-time withstand current 额定短时耐受电流 kA --

Thermal equivalent 等效时间 ms --

Remarks(备注):

Short-time and peak withstand current tests(短时耐受电流和峰值耐受电流试验)

190903-002

Page 53: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 53 of 132

Ia

213.0 kA

-1176.0 kA

Ib

420.0 kA

-969.0 kA

Ic

635.0 kA

-754.0 kA

Ua

1500.0 kV

-1000.0 kV

Ub

1850.0 kV

-650.0 kV

Uc

2175.0 kV

-325.0 kV

Unit1

19.0

-1.0

扫描编号: 1 1.000s/div-0.51 s 4.70 s

Ia 138.9 kA pu

Ib 138.9 kA pu

Ic 138.9 kA pu

Ua 250.0 kV pu

Ub 250.0 kV pu

Uc 250.0 kV pu

Test Parameters(试验参数)

Phase/line 相/线 -- A B C

Current, peak 电流峰值 kA 69.0 52.0 -26.6

Current value, r.m.s. 电流有效值 kA 31.6 31.9 31.7

Average current value 电流平均有效值 kA 31.8

Current duration 电流持续时间 ms 4048 4048 4048

Rated short-time withstand current 额定短时耐受电流 kA 31.5

Thermal equivalent 等效时间 ms 4113

Remarks(备注):

Short-time and peak withstand current tests(短时耐受电流和峰值耐受电流试验)

190903-003

Page 54: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 54 of 132

4.3.1.5 No-load mechanical characteristics for sequence O

Test oscillograms 195388G-1

Test oscillogram:195388G-1

Operation O

Coil current 0.95 A

Phase Phase A Phase B Phase C Opening time ms 25.9 25.9 25.9

Voltage opening coil: 220Vd.c. Gas pressure at 20℃:--Mpa Voltage closing coil: 220Vd.c Operating pressure:-- Mpa Remarks:--

No-load test

Operating voltage: d.c C:220V O: 220V Test sequence: O

Test time: 03-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A of insulating rod SN of vacuum interrupter: A:S024997, B:S001173, C:S000444

Opening time:[ms] Phase A:25.9 Phase B:25.9 Phase C:25.9 Current of coil: 0.95 A

Page 55: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 55 of 132

4.3.1.6 Test apparatus photographs after testing

4.3.1.7 Test apparatus condition/ inspection after testing

a) No arc injecting, no mechanical damage to any part or separation of the contacts. b) After testing the circuit breaker could smoothly open first time by open release operation. c) The disconnector can smoothly open first time by manual operation. d) The test apparatus could indicate the open position status by mechanical indicator. e) The test apparatus was externally no visible change. f) The copper fuse(diameter 0.1 mm length 5 cm) was normal.

4.3.1.8 Test apparatus primary circuit resistance after testing

-Test method: The resistance measurement was performed by measuring the voltage drop at a certain

current(DC 100 A). -Test results:

Phase A (L1) B (L2) C (L3) Interrupter serial No. S024997 S001173 S000444

Resistance (µ) 68.0 67.5 69.3

Ambient temperature (℃) 28.9

The measured resistances after the test was not increased by more than 20% as previously.

4.3.2 Short-time and peak withstand current tests for earthing switch

Performed date:04-07-2019 -Test samples no maintenance after the short-time and peak withstand current of the main circuit. -Supply on cable compartment and go through circuit breaker and disconnector , three phase was short-circuit on earthing switch side. Three-position disconnector was earthed. -Phase A,B,C of test circuit corresponding to phase A,B,C of test object.

Page 56: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 56 of 132

4.3.2.1 Test apparatus primar circuit photographs before testing

4.3.2.2 Test circuit:

G = Generator L = Reactor TO = Test Object GB =Generator Breaker MB = Master Breaker U = Voltage Measurement to earth MS = Make Switch T = Power Transformer I = Current Measurement

`

Supply parameter Power (MVA) 136 Frequency (Hz) 50 Phase 3 Voltage (kV) 2.50 Current (kA) 31.5

Impedance () Pending

Power factor <0.15 Neutral No earthed

Pretest parameter Voltage (kV) 0.85 Current (kA) 10.7

Impedance () 45.9x10-3

Load parameter Short-circuit point Earthed

4.3.2.3 Test oscillograms

190918-002 to 190918-003

Page 57: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 57 of 132

Ia

213.0 kA

-1176.0 kA

Ib

420.0 kA

-969.0 kA

Ic

635.0 kA

-754.0 kA

Ua

1500.0 kV

-1000.0 kV

Ub

1850.0 kV

-650.0 kV

Uc

2175.0 kV

-325.0 kV

Unit1

19.0

-1.0

扫描编号: 1 50.00 ms/div081.1 ms 550.2 ms

Ia 138.9 kA pu

Ib 138.9 kA pu

Ic 138.9 kA pu

Ua 250.0 kV pu

Ub 250.0 kV pu

Uc 250.0 kV pu

Test Parameters(试验参数)

Phase/line 相/线 -- A B C

Current, peak 电流峰值 kA -80.0 69.6 49.7

Current value, r.m.s. 电流有效值 kA 26.7 26.9 26.7

Average current value 电流平均有效值 kA 26.7

Current duration 电流持续时间 ms 321 321 321

Rated short-time withstand current 额定短时耐受电流 kA --

Thermal equivalent 等效时间 ms --

Remarks(备注):

Short-time and peak withstand current tests(短时耐受电流和峰值耐受电流试验)

190918-002

Page 58: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 58 of 132

Ia

213.0 kA

-1176.0 kA

Ib

420.0 kA

-969.0 kA

Ic

635.0 kA

-754.0 kA

Ua

1500.0 kV

-1000.0 kV

Ub

1850.0 kV

-650.0 kV

Uc

2175.0 kV

-325.0 kV

Unit1

19.0

-1.0

扫描编号: 1 1.000s/div-0.52 s 4.68 s

Ia 138.9 kA pu

Ib 138.9 kA pu

Ic 138.9 kA pu

Ua 250.0 kV pu

Ub 250.0 kV pu

Uc 250.0 kV pu

Test Parameters(试验参数)

Phase/line 相/线 -- A B C

Current, peak 电流峰值 kA 66.1 59.4 -30.3

Current value, r.m.s. 电流有效值 kA 31.6 31.9 31.7

Average current value 电流平均有效值 kA 31.7

Current duration 电流持续时间 ms 4048 4048 4048

Rated short-time withstand current 额定短时耐受电流 kA 31.5

Thermal equivalent 等效时间 ms 4112

Remarks(备注):

Short-time and peak withstand current tests(短时耐受电流和峰值耐受电流试验)

190918-003

Page 59: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 59 of 132

4.3.2.4 Test apparatus photographs after testing

4.3.2.5 Test apparatus condition/ inspection after testing

a) No arc injecting, no mechanical damage to any part or separation of the contacts. b) The disconnector can smoothly open first time by manual operation. c) The test apparatus could indicate the open position status by mechanical indicator. d) The test apparatus was externally no visible change. e) The copper fuse(diameter 0.1 mm length 5 cm) was normal.

4.3.3 Short-time and peak withstand current tests for earthing connection

-Test samples no maintenance after the short-time and peak withstand current of the main circuit and ES. -Supply on cable compartment and go through circuit breaker and disconnector, by earrthing bus to phase C Of test circuit. -Phase A under test.

Page 60: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 60 of 132

4.3.3.1 Test apparatus primar circuit photographs before testing

4.3.3.2 Test circuit:

G = Generator L = Reactor TO = Test Object GB =Generator Breaker MB = Master Breaker U = Voltage Measurement to earth MS = Make Switch T = Power Transformer I = Current Measurement

Page 61: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 61 of 132

` Supply parameter Power (MVA) 71.0 Frequency (Hz) 50 Phase Single Voltage (kV) 2.59 Current (kA) 27.4

Impedance () Pending

Power factor <0.15 Neutral No earthed

Pretest parameter Voltage (kV) 0.85 Current (kA) 9.00

Impedance () 94.4x10-3

Load parameter Short-circuit point No earthed

4.3.3.3 Test oscillograms

190923-002 to 190923-003

Page 62: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 62 of 132

Ia

251.0 kA

-626.0 kA

Ua

73.0 kV

-30.0 kV

Unit1

19.0

-1.0

100.0 ms/div38.080 s 38.594 s

Ia 87.72 kA pu

Ua 10.34 kV pu

Short-time and peak withstand current tests(短时耐受电流和峰值耐受电流) 190923-002

Test Parameters(试验参数)

Phase/line 相/线 -- A

Current, peak 电流峰值 kA -70.3

Current value, r.m.s. 电流有效值 kA 27.3

Current duration 电流持续时间 ms 328

Rated short-time withstand current 额定短时耐受电流 kA --

Thermal equivalent 额定电流等效时间 ms --

Remarks(备注):

Page 63: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 63 of 132

Ia

251.0 kA

-626.0 kA

Ua

73.0 kV

-30.0 kV

Unit1

19.0

-1.0

500.0 ms/div01:19.91 01:22.65

Ia 87.72 kA pu

Ua 10.34 kV pu

Short-time and peak withstand current tests(短时耐受电流和峰值耐受电流) 190923-003

Test Parameters(试验参数)

Phase/line 相/线 -- A

Current, peak 电流峰值 kA 38.4

Current value, r.m.s. 电流有效值 kA 27.7

Current duration 电流持续时间 ms 2025

Rated short-time withstand current 额定短时耐受电流 kA 27.4

Thermal equivalent 额定电流等效时间 ms 2065

Remarks(备注):

Page 64: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 64 of 132

4.3.3.4 Test apparatus photographs after testing

4.3.3.5 Test apparatus condition/ inspection after testing

a) No arc injecting, no mechanical damage to any part or separation of the contacts. b) The disconnector can smoothly open first time by manual operation. c) The test apparatus could indicate the open position status by mechanical indicator. d) The test apparatus was open status measured by multimeter. e) Externally no visible change and test valid.

Page 65: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 65 of 132

4.4 Electrical endurance class E1 test test-duty T100s to T100a (50 Hz)

- Apparatus tested serial No. RD1002/1001/001 circuit breaker cooperated with switchgear. -Test apparatus no maintenance.

4.4.1 Test-duty: T100s

Performed date:15-07-2019 a) Supply on cable compartment side of test apparatus. Outgoing busbar compartment side of test apparatus were shortened by copper busbar. b) Test circuit phase sequence: A B C against test apparatus phase sequence: A B C. c) Between the test apparatus and earthing was insulation and insulation resistance not less than 10 M, measured with d.c. of 500 V one minute. d) The test apparatus enclosure go through diameter 0.1 mm length 5 cm copper fuse connected the earthing. e) Arcing time sense was installed on rotating axes of test apparatus mechanical actuation.

4.4.1.1 Test circuit:

G = Generator L = Reactor TO = Test Object GB = Generator Breaker MB = Master Breaker U = Voltage Measurement MS = Make Switch I = Current Measurement Rs,Cs= TRV Device Cd=Capacitor(load)

` Supply parameter Power (MVA) 655 Frequency (Hz) 50 Phase 3 Voltage (kV) 12.0 Current (kA) 31.5

Impedance () 0.22

Power factor <0.17 Neutral Earthed

Load parameter Short-circuit point No earthed

TRV control elements added Cs µf 1.05 Rs Ω 2.73 Cd µf 0.17 Neutral Earthed

Prospective TRV Coscillogram 12kV 31.5kA-T100s -TRV Uc kV 20.7 t3 µs 61.0 Td µs 7.2 RRRV kV/µs 0.34

Page 66: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 66 of 132

4.4.1.2 Test photograph of before testing

4.4.1.3 Test oscillogram

190977-001 to 190977-002

Page 67: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 67 of 132

Icoil

4.887 A

-45.11 A

Ia

352.0 kA

-1500.0 kA

Uab

175.0 kV

-396.0 kV

Ib

827.0 kA

-1096.0 kA

Ubc

319.0 kV

-253.0 kV

Ic

1133.0 kA

-533.0 kA

Uca

425.0 kV

-108.0 kV

Tr

837.0 mm

-89.0 mm

Unit1

19.0

-1.0

200.0 ms/div03:29.25 03:30.44

OCO

Icoil 5.000 A pu

Ia 185.2 kA pu

Uab 57.14 kV pu

Ib 192.3 kA pu

Ubc 57.14 kV pu

Ic 166.7 kA pu

Uca 53.33 kV pu

Tr 92.58 mm pu

HFUab

57.0 kV

-237.0 kV

HFUbc

134.0 kV

-160.0 kV

HFUca

213.0 kV

-50.0 kV

Unit2

19.0

-1.0

Unit3

19.0

-1.0

5.000 ms/div03:29.5587 03:29.5841

HFUab 29.41 kV pu

HFUbc 29.41 kV pu

HFUca 26.32 kV pu

T100s 190977-001(O-CO)

HFUab

57.0 kV

-237.0 kV

HFUbc

134.0 kV

-160.0 kV

HFUca

213.0 kV

-50.0 kV

Unit2

19.0

-1.0

Unit3

19.0

-1.0

5.000 ms/div03:29.9735 03:30.0042

HFUab 29.41 kV pu

HFUbc 29.41 kV pu

HFUca 26.32 kV pu

Page 68: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 68 of 132

Voltage opening coil(分闸线圈电压) 143 Vd.c. Voltage closing coil(合闸线圈电压) 187 Vd.c.

Remarks(备注): Breaker cleared (试品开断)。

Test Parameters(试验参数) O

Time interval since previous test 试验间隔 s -- -- --

Operation 操作方式 -- -- O --

Step 步长 ° -- -- --

Phase/line 相/线 -- A/AB B/BC C/CA

Breaking current, phase value 开断电流 kA 31.6 31.9 31.7

Breaking current, DC-component 直流分量 % 1 0 0

Recovery voltage, line value 工频恢复电压 kV 11.8 11.7 11.7

TRV, peak TRV峰值 kV 20.3 -20.3 -24.0

Arc duration 燃弧时间 ms 6.5 1.5 6.5

Opening time 分闸时间 ms 33.6

Break time 全开断时间 ms 40.1 35.1 40.1

T100s 190977-001(O-CO)

Test Parameters(试验参数) CO

Time interval since previous test 试验间隔 s -- 0.3 --

Operation 操作方式 -- -- CO --

Step 步长 ° -- -40.0 --

Phase/line 相/线 -- A/AB B/BC C/CA

Making current, peak 关合电流峰值 kA 81.9 -69.2 -63.7

Breaking current, phase value 开断电流 kA 32.1 32.4 32.0

Breaking current, DC-component 直流分量 % 0 1 1

Applied voltage, line value 试验电压 kV 12.0 12.0 12.0

Recovery voltage, line value 工频恢复电压 kV 11.7 11.8 11.7

TRV, peak TRV峰值 kV 20.1 -20.1 -23.5

Arc duration 燃弧时间 ms 9.6 4.6 9.6

Opening time 分闸时间 ms 33.3

Break time 全开断时间 ms 42.9 37.9 42.9

Make time 关合时间 ms 35.6

Page 69: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 69 of 132

Icoil

4.978 A

-57.52 A

Ia

365.0 kA

-1558.0 kA

Uab

225.0 kV

-544.0 kV

Ib

739.0 kA

-1047.0 kA

Ubc

409.0 kV

-361.0 kV

Ic

1171.0 kA

-615.0 kA

Uca

592.0 kV

-177.0 kV

Tr

757.0 mm

-84.0 mm

Unit1

19.0

-1.0

扫描编号: 1 100.0 ms/div-061.2 ms 727.6 ms

COIcoil 6.250 A pu

Ia 192.3 kA pu

Uab 76.92 kV pu

Ib 178.6 kA pu

Ubc 76.92 kV pu

Ic 178.6 kA pu

Uca 76.92 kV pu

Tr 84.12 mm pu

HFUab

52.0 kV

-252.0 kV

HFUbc

143.0 kV

-143.0 kV

HFUca

244.0 kV

-50.0 kV

Unit2

17.27

-909.1 m

5.000 ms/div02:11.7224 02:11.7489

HFUab 30.30 kV pu

HFUbc 28.57 kV pu

HFUca 29.41 kV pu

T100s 190977-002(CO)

Page 70: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 70 of 132

4.4.1.4 Test apparatus condition/ inspection after testing

a) Externally no visible change and breaker cleared. b) The copper fuse(diameter 0.1 mm length 5 cm) was normal.

Voltage opening coil(分闸线圈电压) 143 Vd.c. Voltage closing coil(合闸线圈电压) 187 Vd.c.

Remarks(备注): Breaker cleared (试品开断)。

Test Parameters(试验参数)

Time interval since previous test 试验间隔 s -- 180 --

Operation 操作方式 -- -- CO --

Step 步长 ° -- -40.0 --

Phase/line 相/线 -- A/AB B/BC C/CA

Making current, peak 关合电流峰值 kA 81.0 -61.5 -67.5

Breaking current, phase value 开断电流 kA 31.7 31.9 31.8

Breaking current, DC-component 直流分量 % 0 0 1

Applied voltage, line value 试验电压 kV 12.0 12.0 12.0

Recovery voltage, line value 工频恢复电压 kV 11.8 11.7 11.7

TRV, peak TRV峰值 kV 20.4 -20.4 -23.8

Arc duration 燃弧时间 ms 9.6 4.5 9.6

Opening time 分闸时间 ms 34.6

Break time 全开断时间 ms 44.2 39.1 44.2

Make time 关合时间 ms 33.2

T100s 190977-002(CO)

Page 71: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 71 of 132

4.4.1.5 Test apparatus photograph after testing

4.4.2 Test-duty: T100a

Performed date:16-07-2019 a) Supply on copper busbar compartment side test apparatus. Outgoing cables compartment side of test apparatus were shortened by copper busbar. b) Test circuit phase sequence: A B C against test apparatus phase sequence: A B C. c) Between the test apparatus and earthing was insulation and insulation resistance not less than 10 M, measured with d.c. of 500 V one minute. d) The test apparatus enclosure go through diameter 0.1 mm length 5 cm copper fuse connected the earthing. e) Arcing time sense was installed on rotating axes of test apparatus mechanical actuation. f) According to IEC 62271-100:2017 table 15: Interruption arc minor loop peak value:59.2 kA Interruption arc duration of minor loop:12.0 ms

Page 72: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 72 of 132

4.4.2.1 Test apparatus photograph before testing

4.4.2.2 Test circuit:

G = Generator L = Reactor TO = Test Object GB = Generator Breaker MB = Master Breaker U = Voltage Measurement MS = Make Switch I = Current Measurement Rs,Cs= TRV Device Cd=Capacitor(load)

Supply parameter Power (MVA) 655 Frequency (Hz) 50 Phase 3 Voltage (kV) 12.0 Current (kA) 31.5

Impedance () 0.22

Power factor <0.15 Neutral Earthed

Load parameter Short-circuit point Not earthed

TRV control elements added Cs µf 1.05 Rs Ω 2.73 Cd µf 0.17 Neutral Earthed

Prospective TRV Coscillogram 12 kV 31.5kA-T00s -TRV Uc kV 20.7 t3 µs 61.0 Td µs 7.2 RRRV kV/µs 0.34

4.4.2.3 Test oscillogram

190989-002 to 190989-004

Page 73: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 73 of 132

Icoil

5.686 A

-41.93 A

Ia

350.0 kA

-1317.0 kA

Uab

234.0 kV

-480.0 kV

Ib

767.0 kA

-900.0 kA

Ubc

379.0 kV

-288.0 kV

Ic

1167.0 kA

-500.0 kA

Uca

572.0 kV

-143.0 kV

Tr

1487.0 mm

-165.0 mm

UnitBar1

19.0

-1.0

扫描编号: 1 100.0 ms/div067.0 ms 760.3 ms

O

Icoil 4.762 A pu

Ia 166.7 kA pu

Uab 71.43 kV pu

Ib 166.7 kA pu

Ubc 66.67 kV pu

Ic 166.7 kA pu

Uca 71.43 kV pu

Tr 165.2 mm pu

HFUab

52.0 kV

-252.0 kV

HFUbc

126.0 kV

-137.0 kV

HFUca

244.0 kV

-50.0 kV

UnitBar2

19.0

-1.0

5.000 ms/div43.8114 s 43.8364 s

HFUab 30.30 kV pu

HFUbc 26.32 kV pu

HFUca 29.41 kV pu

T100a 190989-002(O)

Page 74: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 74 of 132

Voltage opening coil(分闸线圈电压) 242 Vd.c.

Remarks(备注): Breaker cleared (试品开断)。Extended major loop on phase A (A相延长大半波).

Test Parameters(试验参数)

Time interval since previous test 试验间隔 s -- -- --

Operation 操作方式 - -- O --

Step 步长 ° -- -54.0 --

Phase/line 相/线 - A/AB B/BC C/CA

Breaking current, phase value 开断电流 kA 31.6 31.9 31.7

Breaking current,DC-component 直流分量 % 32 16 15

Current last loop,peak 电流最后半波峰值 kA -53.8 49.1 43.5

Duration last loop 最后半波持续时间 ms 13.2 11.0 9.3

TRV. peak TRV峰值 kV 20.5 -20.5 -23.8

Recorvery voltage, line value 工频恢复电压 kV 11.8 11.7 11.7

Arc duration 燃弧时间 ms 8.8 3.7 8.8

Opening time 分闸时间 ms 21.8

Breaking time 全开断时间 ms 30.6 25.5 30.6

T100a 190989-002(O)

Page 75: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 75 of 132

Icoil

5.209 A

-42.41 A

Ia

333.0 kA

-1333.0 kA

Uab

234.0 kV

-480.0 kV

Ib

767.0 kA

-900.0 kA

Ubc

386.0 kV

-281.0 kV

Ic

1167.0 kA

-500.0 kA

Uca

586.0 kV

-128.0 kV

Tr

1487.0 mm

-165.0 mm

UnitBar1

19.0

-1.0

扫描编号: 1 100.0 ms/div075.8 ms 749.4 ms

O

Icoil 4.762 A pu

Ia 166.7 kA pu

Uab 71.43 kV pu

Ib 166.7 kA pu

Ubc 66.67 kV pu

Ic 166.7 kA pu

Uca 71.43 kV pu

Tr 165.2 mm pu

HFUab

52.0 kV

-252.0 kV

HFUbc

126.0 kV

-137.0 kV

HFUca

244.0 kV

-50.0 kV

UnitBar2

19.0

-1.0

5.000 ms/div54.6694 s 54.6949 s

HFUab 30.30 kV pu

HFUbc 26.32 kV pu

HFUca 29.41 kV pu

T100a 190989-003(O)

Page 76: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 76 of 132

Voltage opening coil(分闸线圈电压) 242 Vd.c.

Remarks(备注): Breaker cleared (试品开断)。Extended major loop on phase B (B相延长大半波).

Test Parameters(试验参数)

Time interval since previous test 试验间隔 s -- -- --

Operation 操作方式 - -- O --

Step 步长 ° -- -25.0 --

Phase/line 相/线 - A/AB B/BC C/CA

Breaking current, phase value 开断电流 kA 31.7 31.9 31.6

Breaking current,DC-component 直流分量 % 25 32 6

Current last loop,peak 电流最后半波峰值 kA -45.3 53.5 -45.7

Duration last loop 最后半波持续时间 ms 9.5 13.1 10.7

TRV. peak TRV峰值 kV 24.0 -20.4 20.4

Recorvery voltage, line value 工频恢复电压 kV 11.8 11.7 11.7

Arc duration 燃弧时间 ms 6.9 6.9 1.5

Opening time 分闸时间 ms 21.8

Breaking time 全开断时间 ms 28.7 28.7 23.3

T100a 190989-003(O)

Page 77: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 77 of 132

Icoil

5.209 A

-42.41 A

Ia

367.0 kA

-1300.0 kA

Uab

242.0 kV

-473.0 kV

Ib

767.0 kA

-900.0 kA

Ubc

372.0 kV

-294.0 kV

Ic

1133.0 kA

-533.0 kA

Uca

572.0 kV

-143.0 kV

Tr

1487.0 mm

-165.0 mm

UnitBar1

19.0

-1.0

扫描编号: 1 100.0 ms/div077.2 ms 745.9 ms

O

Icoil 4.762 A pu

Ia 166.7 kA pu

Uab 71.43 kV pu

Ib 166.7 kA pu

Ubc 66.67 kV pu

Ic 166.7 kA pu

Uca 71.43 kV pu

Tr 165.2 mm pu

HFUab

52.0 kV

-252.0 kV

HFUbc

126.0 kV

-137.0 kV

HFUca

244.0 kV

-50.0 kV

UnitBar2

19.0

-1.0

5.000 ms/div01:12.5927 01:12.6187

HFUab 30.30 kV pu

HFUbc 26.32 kV pu

HFUca 29.41 kV pu

T100a 190989-004(O)

Page 78: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 78 of 132

Voltage opening coil(分闸线圈电压) 242 Vd.c.

Remarks(备注): Breaker cleared (试品开断)。First major loop on phase C(C相首开大半波).

Test Parameters(试验参数)

Time interval since previous test 试验间隔 s -- -- --

Operation 操作方式 - -- O --

Step 步长 ° -- -25.0 --

Phase/line 相/线 - A/AB B/BC C/CA

Breaking current, phase value 开断电流 kA 31.5 31.8 31.6

Breaking current,DC-component 直流分量 % 17 15 33

Current last loop,peak 电流最后半波峰值 kA -37.1 48.6 -53.6

Duration last loop 最后半波持续时间 ms 8.2 12.2 11.6

TRV. peak TRV峰值 kV 23.8 -20.3 20.3

Recorvery voltage, line value 工频恢复电压 kV 11.7 11.7 11.8

Arc duration 燃弧时间 ms 8.0 8.0 3.6

Opening time 分闸时间 ms 21.5

Breaking time 全开断时间 ms 29.5 29.5 25.1

T100a 190989-004(O)

Page 79: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 79 of 132

4.4.2.4 Test apparatus condition/ inspection after testing

a) Externally no visible change and breaker cleared. b) The copper fuse(diameter 0.1 mm length 5 cm) was normal.

4.4.2.5 Test apparatus photograph after testing

4.5 Test apparatus inspection after high power

4.5.1 No-load test inspection

Performed date:17-07-2019 -Test object condition:no maintenance. -Spring energy storage operating mechanism, linear sensor was installed in A phase of insulating rod. -SN of vacuum interrupter: A:S024997,B:S001173,C:S000444 - Result: mechanical characteristic measurements indicate that the CB are agreed with the values before high power performance.

-Test oscillograms 195388G-06 195388G-07 195388G-08

Page 80: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 80 of 132

No-load test-195388G-06

Operating voltage: d.c C:220 V O: 220 V Test sequence:O-0.3s-CO

Test time: 17-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A rotation axle. SN of vacuum interrupter: : A:S024997,B:S001173,C:S000444

Opening time:[ms] Phase A:23.8 Phase B:23.7 Phase C:23.6 Opening coil current:[A] 0.78

Closing time: [ms] Phase A:32.3 Phase B: 32.4 Phase C: 32.6

Closing coil current:[A] 0.97

Opening time:[ms] Phase A:23.5 Phase B:23.4 Phase C:23.3 Opening coil current:[A] 0.78

Opening-closing time [ms]: 301.1 Closing-opening time [ms]: 98.2

Page 81: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 81 of 132

No-load test-195388G-07

Operating voltage: d.c 242V O: 242 V Test sequence:O-0.3s-CO

Test time: 17-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A rotation axle. SN of vacuum interrupter: : A:S024997,B:S001173,C:S000444

Opening time:[ms] Phase A:22.2 Phase B:22.1 Phase C:21.9 Opening coil current:[A] 0.91

Closing time: [ms] Phase A:30.7 Phase B: 30.8 Phase C: 31.1

Closing coil current:[A] 1.07

Opening time:[ms] Phase A:21.9 Phase B:21.8 Phase C:21.7 Opening coil current:[A] 0.89

Opening-closing time [ms]: 301.2 Closing-opening time [ms]: 98.2

Page 82: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 82 of 132

No-load test-195388G-08

Operating voltage: d.c C:187 V O: 143V Test sequence:O-0.3s-CO

Test time: 17-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A rotation axle. SN of vacuum interrupter: : A:S024997,B:S001173,C:S000444

Opening time:[ms] Phase A:35.7 Phase B:35.6 Phase C:35.5

Opening coil current:[A] 0.56

Closing time: [ms] Phase A:34.1 Phase B: 34.2 Phase C: 34.4

Closing coil current:[A] 0.83

Opening time:[ms] Phase A:35.9 Phase B:35.8 Phase C:35.7 Opening coil current:[A] 0.55

Opening-closing time [ms]: 299.9 Closing-opening time [ms]: 100.9

Page 83: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 83 of 132

4.5.2 Dielectric test inspection for the state of vacuum.

Atmospheric conditions: P=100.1 kPa, T=31.9℃, RH=64.4% Phase: A, B, C are supply incoming unit and a, b, c are supply outgoing unit. Performed date:17-07-2019

AT Regulator Rp Protection resistance

CT Current transformer TT PF transformer

TO Tested object A Current meter

C1 H.V arm capacitance C2 L.V arm capacitance

V2 Voltmeter

OSC Oscilloscope

150kV Power frequency voltage measuring systems

Power frequency withstand voltage test circuit

Testing position Voltage applied to Earthed terminal Uc(kVr.m.s) Ut(kVr.m.s) NO.A NO.D T-OSC

AID(VCB)

A a

38.4

38.5 1 0 --

a A 38.4 1 0 --

B b 38.5 1 0 --

b B 38.3 1 0 --

C c 38.4 1 0 --

c C 38.4 1 0 --

Result: Passed Notes: a)①Uc=Ue×Kt1×Ka, choosing Kt1=1.000 during test

b)SN of vacuum interrupter: A:S024997,B:S001173,C:S000444

Page 84: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 84 of 132

4.5.3 Measurement of contact resistance inspection

-Test method: The resistance measurement was performed by measuring the voltage drop at a certain current(DC 100 A). Phase A B C

Interrupter serial No. S024997 S001173 S000444

Measure resistance of main circuit (μΩ) Before short-time and peak withstand current switching performance

67.1 66.2 66.9

Ambient temperature(℃) 29.9

Interrupter serial No. S024997 S001173 S000444

Measure resistance of main circuit (μΩ) after high power

68.0 67.5 69.3

Ambient temperature(℃) 29.9

Max. difference(%) <20%

-The results of the primary resistance measurements indicate that the VCB are capable of carrying the rated normal current after high power. -Test results: Passed.

4.6 Short-circuit making tests of earthing circuit.

Performed date:15-08-2019

4.6.1 Short-circuit making tests for earthing circuit.

a) TO have already performed the short-time and peak withstand current for main primary and ES circuit. b) Supply incoming cable compartment by cable went through ES and shorten the three-phase on earthing switch, for detail see test circuit. c) Between the test apparatus and earth was insulation and insulation resistance not less than 60 M, measured with d.c. of 500 V one minute. d) The test apparatus enclosure go through diameter 0.1 mm length 5 cm copper fuse connected the earthing.

Page 85: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 85 of 132

4.6.1.1 Test apparatus photographs before testing

4.6.1.2 Test circuit:

G = Generator L = Reactor TO = Test Object GB =Generator Breaker MB = Master Breaker U = Voltage Measurement to earth MS = Make Switch T = Power Transformer I = Current Measurement

`

Supply parameter Power (MVA) 655 Frequency (Hz) 50 Phase 3 Voltage (kV) 12.0

Current (kA) 31.5

Impedance () 0.22

Power factor <0.15 Neutral Not earthed

Pretest parameter Voltage (V) Current (kA)

Impedance ()

Load parameter Short-circuit point Not earthed

4.6.1.3 Test oscillograms

191185-001 to 191185-003 performed date:15-08-2019 191191-001 to 191191-002 performed date:16-06-2019

Page 86: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 86 of 132

Icoil

3.623 A

-36.38 A

Ia

200.0 kA

-800.0 kA

Uab

124.0 kV

-276.0 kV

Ib

389.0 kA

-504.0 kA

Ubc

217.0 kV

-167.0 kV

Ic

612.0 kA

-281.0 kA

Uca

337.0 kV

-80.0 kV

Unit1

19.0

-1.0

扫描编号: 1 100.0 ms/div-113.0 ms 648.9 ms

Icoil 4.000 A pu

Ia 100.0 kA pu

Uab 40.00 kV pu

Ib 89.29 kA pu

Ubc 38.46 kV pu

Ic 89.29 kA pu

Uca 41.67 kV pu

Earth making test(接地开关关合) 191185-001(C)

Voltage closing coil(合闸线圈电压) 187 Vd.c.

Remarks(备注): Test object closed (试品关合正常)。

Test Parameters(试验参数)

Time interval since previous test 试验间隔 s -- -- --

Operation 操作方式 -- -- C --

Phase/line 相/线 -- A/AB B/BC C/CA

Making current, peak 关合电流峰值 kA 55.0 -80.3 73.6

Current, phase value 试验电流 kA 31.4 32.0 31.6

Current duration 电流持续时间 s 0.31 0.30 0.31

Make time 关合时间 ms 33.9

Applied voltage, line value 试验电压 kV 12.0 12.0 12.0

Page 87: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 87 of 132

Icoil

3.625 A

-36.38 A

Ia

200.0 kA

-800.0 kA

Uab

124.0 kV

-276.0 kV

Ib

393.0 kA

-500.0 kA

Ubc

217.0 kV

-167.0 kV

Ic

610.0 kA

-283.0 kA

Uca

335.0 kV

-82.0 kV

Unit1

19.0

-1.0

扫描编号: 1 100.0 ms/div-105.3 ms 661.5 ms

Icoil 4.000 A pu

Ia 100.0 kA pu

Uab 40.00 kV pu

Ib 89.29 kA pu

Ubc 38.46 kV pu

Ic 89.29 kA pu

Uca 41.67 kV pu

Earth making test(接地开关关合) 191185-002(C)

Voltage closing coil(合闸线圈电压) 187 Vd.c.

Remarks(备注): Test object closed (试品关合正常)。

Test Parameters(试验参数)

Time interval since previous test 试验间隔 s -- -- --

Operation 操作方式 -- -- C --

Phase/line 相/线 -- A/AB B/BC C/CA

Making current, peak 关合电流峰值 kA 51.2 -77.0 76.1

Current, phase value 试验电流 kA 31.4 32.1 31.5

Current duration 电流持续时间 s 0.30 0.30 0.30

Make time 关合时间 ms 33.4

Applied voltage, line value 试验电压 kV 12.0 12.0 12.0

Page 88: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 88 of 132

Icoil

3.629 A

-36.37 A

Ia

200.0 kA

-800.0 kA

Uab

124.0 kV

-276.0 kV

Ib

393.0 kA

-500.0 kA

Ubc

217.0 kV

-167.0 kV

Ic

610.0 kA

-283.0 kA

Uca

335.0 kV

-82.0 kV

Unit1

19.0

-1.0

扫描编号: 1 100.0 ms/div-083.9 ms 645.2 ms

Icoil 4.000 A pu

Ia 100.0 kA pu

Uab 40.00 kV pu

Ib 89.29 kA pu

Ubc 38.46 kV pu

Ic 89.29 kA pu

Uca 41.67 kV pu

Earth making test(接地开关关合) 191185-003(C)

Voltage closing coil(合闸线圈电压) 187 Vd.c.

Remarks(备注): Test object closed (试品关合正常)。

Test Parameters(试验参数)

Time interval since previous test 试验间隔 s -- -- --

Operation 操作方式 -- -- C --

Phase/line 相/线 -- A/AB B/BC C/CA

Making current, peak 关合电流峰值 kA -50.1 -74.3 78.6

Current, phase value 试验电流 kA 31.6 32.3 31.7

Current duration 电流持续时间 s 0.31 0.31 0.30

Make time 关合时间 ms 33.0

Applied voltage, line value 试验电压 kV 12.1 12.1 12.1

Page 89: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 89 of 132

Icoil

3.646 A

-36.35 A

Ia

200.0 kA

-800.0 kA

Uab

124.0 kV

-276.0 kV

Ib

393.0 kA

-500.0 kA

Ubc

217.0 kV

-167.0 kV

Ic

616.0 kA

-277.0 kA

Uca

335.0 kV

-82.0 kV

Unit1

19.0

-1.0

扫描编号: 1 100.0 ms/div-021.1 ms 718.8 ms

Icoil 4.000 A pu

Ia 100.0 kA pu

Uab 40.00 kV pu

Ib 89.29 kA pu

Ubc 38.46 kV pu

Ic 89.29 kA pu

Uca 41.67 kV pu

Earth making test(接地开关关合) 191191-001(C)

Voltage closing coil(合闸线圈电压) 187 Vd.c.

Remarks(备注): Test object closed (试品关合正常)。

Test Parameters(试验参数)

Time interval since previous test 试验间隔 s -- -- --

Operation 操作方式 -- -- C --

Phase/line 相/线 -- A/AB B/BC C/CA

Making current, peak 关合电流峰值 kA 51.0 -76.9 76.2

Current, phase value 试验电流 kA 31.4 32.2 31.5

Current duration 电流持续时间 s 0.30 0.30 0.30

Make time 关合时间 ms 33.4

Applied voltage, line value 试验电压 kV 12.0 12.0 12.0

Page 90: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 90 of 132

Icoil

3.646 A

-36.35 A

Ia

200.0 kA

-800.0 kA

Uab

130.0 kV

-270.0 kV

Ib

411.0 kA

-482.0 kA

Ubc

229.0 kV

-156.0 kV

Ic

606.0 kA

-228.0 kA

Uca

356.0 kV

-61.0 kV

Unit1

19.0

-1.0

扫描编号: 1 100.0 ms/div-022.2 ms 720.4 ms

Icoil 4.000 A pu

Ia 100.0 kA pu

Uab 40.00 kV pu

Ib 89.29 kA pu

Ubc 38.46 kV pu

Ic 83.33 kA pu

Uca 41.67 kV pu

Earth making test(接地开关关合) 191191-002(C)

Voltage closing coil(合闸线圈电压) 187 Vd.c.

Remarks(备注): Test object closed (试品关合正常)。

Test Parameters(试验参数)

Time interval since previous test 试验间隔 s -- -- --

Operation 操作方式 -- -- C --

Phase/line 相/线 -- A/AB B/BC C/CA

Making current, peak 关合电流峰值 kA -50.3 -73.2 80.2

Current, phase value 试验电流 kA 31.4 32.2 31.6

Current duration 电流持续时间 s 0.31 0.30 0.30

Make time 关合时间 ms 33.3

Applied voltage, line value 试验电压 kV 12.0 12.0 12.0

Page 91: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 91 of 132

4.6.1.4 Test apparatus photographs after testing

4.6.1.5 Test apparatus condition/ inspection after testing

a) No arc injecting, no mechanical damage to any part or separation of the contacts. b) After testing the test apparatus could smoothly open first time by manual operation. c) The test apparatus could indicate the open position status by mechanical indicator.

Page 92: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 92 of 132

d) The earthing connection circuit is normal e)The copper fuse(diameter 0.1 mm length 5 cm) was normal. f)The test apparatus was open status measured by multimeter.

4.6.1.6 Power frequency withstand voltage test inspection

Power frequency withstand voltage test circuit

AT Regulator Rp Protection resistance

CT Current transformer TT PF transformer

TO Tested object A Current meter

C1 H.V arm capacitance C2 L.V arm capacitance

V2 Voltmeter Type:PV0501 SN:0703209

OSC Oscilloscope Type:TDS3032B SN:B030680

150kV Power frequency voltage measuring systems Validity:2014-07-11

Parameters of TT System

U/S (kV/kVA) fTT(Hz) Rp(kΩ) C1(pF) C2(μF)

150/25 50.0 5.0 177.0 0.211

Atmospheric conditions:P=100.7 kPa t=35.2 ℃ RH=25%

Correction factor:Kt1=0.917 Kt2=/ K1=/ Ka=/

Performed date:19-08-2019

Testing position Voltage applied to Earthed terminal Uc(kVr.m.s) Ut(kVr.m.s) NO.A NO.D T-OSC

Circuit breaker (AID)

A a

48.0

48.1 1 0 --

a A 48.0 1 0 --

B b 48.1 1 0 --

b B 47.9 1 0 --

C c 48.0 1 0 --

c C 48.1 1 0 --

Result: Passed Notes: Condition check test after earthing circuit(CB+ES) making test

Page 93: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP3-195388G-HP

Page 93 of 132

4.6.1.7 Lightning impulse withstand voltage test inspection

Lightning impulse withstand voltage test

C IG capacitance Rf Front resistance Rt Tail resistance S Sphere gap R Damping resistance C1 H.V arm capacitance

TO Tested object C2 L.V arm capacitance DIVMS Digital impulse voltage measuring systems

400kV/20 kJ Impulse voltage measuring systems

Parameters of IG system

Type U(kV) C(μF) Rf(Ω) Rt(Ω) C1(pF) C2(μF)

(LI) 400 0.25 465 213 300 0.555

Page 94: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 94 of 132

4.6.1.7.1 Lightning impulse withstand voltage test for P-to-P and P-to-E

Atmospheric conditions:P=100.7 kPa t=35.2℃ RH=64.1%

Correction factor:Kt1=-- Kt2=-- K1=-- Ka=-- Performed date: 19-08-2019

Testing

position

Voltage

applied to

Earthed

terminal

Uc

(kVp) Ut(kVp)

NO.A

NO.D

T-OSC 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Circuit breaker (AID)

A a

95.0

+ 95.1 95.3 95.0 95.2 95.0 94.9 95.1 94.6 95.3 95.2 94.8 95.3 95.0 94.7 95.3 15 0 01

- 95.0 95.1 94.8 95.3 95.2 94.9 94.7 94.6 95.4 94.8 94.9 95.0 95.3 95.1 95.2 15 0 02

a A + 95.2 94.9 95.2 94.9 95.3 94.7 95.3 95.2 95.2 95.0 94.8 95.1 95.4 94.8 94.9 15 0 03

- 94.9 95.1 94.9 95.0 95.1 94.7 95.0 94.6 94.8 95.0 95.1 95.0 95.3 95.2 95.1 15 0 04

B b + 94.8 94.9 95.0 95.4 95.1 95.0 95.4 95.3 94.9 95.3 94.7 95.0 94.6 95.3 95.2 15 0 05

- 95.3 94.7 95.2 94.9 94.6 95.1 94.7 95.0 94.9 95.3 94.8 94.9 95.0 95.1 95.2 15 0 06

b B + 95.3 95.2 95.0 94.7 94.9 95.3 94.6 95.2 94.9 94.7 95.2 94.8 95.3 95.2 95.0 15 0 07

- 94.9 95.1 95.2 95.0 94.8 95.2 95.3 95.2 95.3 94.9 95.0 95.4 94.8 95.3 94.9 15 0 08

C c + 95.1 95.3 94.8 95.1 95.3 95.4 95.0 94.9 95.2 94.9 95.1 95.3 94.7 95.1 95.3 15 0 09

- 95.0 95.3 94.9 95.0 95.2 94.9 95.1 94.9 94.8 94.7 95.2 95.0 94.6 95.3 95.1 15 0 10

c C + 94.6 95.2 95.2 95.4 95.1 95.1 95.3 94.7 95.2 94.9 95.0 95.1 95.1 95.0 94.8 15 0 11

- 95.0 95.1 94.9 95.2 95.0 94.9 94.8 95.0 94.8 95.1 94.8 95.2 95.3 94.7 95.0 15 0 12

Result:Passed

Notes:

a) Uc=Ue×Kt1×Ka, choosing Kt1=1.000 during test b) 50%, 65%, 80% Uc are applied in sequence to verify parameters) c) SN of vacuum interrupter: A:S024997,B:S001173,C:S000444 4.6.1.7.2 Lightning impulse withstand voltage test oscillogram

Page 95: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 95 of 132

Page 96: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 GROUP1-195388G-HP

Page 96 of 132

Page 97: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 97 of 132

5 GROUP2-195388G-MT and EMC

5.1 The lab measurement test equipment calibration

-Measurement uncertainty for resistants: 1.5%(k=2) -Measurement uncertainty for temperature-rise: 2K(k=2)

5.2 Symbols and abbreviation used in report

symbols and terms Description

A.C.E Auxiliary and Control Equipment

R1 Cold coil resistance

R2 Hot coil resistance

T1 Ambient temperature when the coil is cold

T2 Ambient temperature when the coil is hot

Tr. Maximum permissible temperature-rise value

5.3 Measurement of resistance of main circuit

Test apparatus series No.: RD1007/1501/A2 circuit breaker assembly with switchgear. Performed date: 24-06-2019 5.3.1 Measurement of resistance of switchgear and vacuum circuit breaker -Test method: The resistance measurement was performed by measuring the voltage drop at a certain current(DC 100 A).

-Test results: Switchgear Before temperature-rise

Performed date:24-06-2019 After temperature-rise

Performed date:26-06-2019 Measuring position Refer to measurement position diagram of the resistance of circuits

From A point to A’ point

Requirements(μΩ) ≤90

Ambient temperature(Ta ℃) Ta:27.1 Ta: 27.2 Tc:27.1

A Phase A(μΩ) 62.8 63.2 63.2

B Phase B(μΩ) 59.7 60.0 60.0

C Phase C(μΩ) 61.1 62.0 62.0

Max. difference limit value 20(%) -- 1.5%

Note: Ta: ambient air temperature. Tc: correction ambient air temperature 5.3.2 Measurement position diagram of the resistance of circuits

Page 98: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 98 of 132

5.4 Temperature-rise tests

5.4.1 Test circuit diagram

TOCT

TVR

CT

A

TVR

CT

TVRA

B

C

N

A

A

A

B

C

N

VR Voltage Regular CT Current Transformer

T Transformer TO Test Object

5.4.2 Test arrangement

a) Test current:1375 A(1.1 Ir required by client), 50 Hz, ambient temperature:28.4℃ b) The CB assembly with in GELPAG-MSS-12/1250-31.5 switchgear (LSC2B) performed the temperature-rise test. c) The test was made indoors in an environment substantially free from air and air velocity did not

merchant exceed 0.5 m/s. d) Temperature-rise measurement point refer to measurement position diagram of the temperature-rise test

provided by the manufacture. e) The ambient air temperature was recorded during the tests by means of at least three thermocouples

devices equally distributed around the switchgear and controlgear at about the average height of its current-carrying parts and at a distance of about 1 m from the switchgear and controlgear. The thermocouples was protected against air currents and undue influence of heat. In order to avoid indication errors because of rapid temperature changes, the thermocouples was put into small bottles containing about 0.5 L of oil. Level 1 tolerance T-type thermocouples were adopted.

f) The type and sizes of the temporary connections. Current supply incoming busbar cross-section:80x10 mm2x 2 m (Length) Current supply outgoing busbar cross-section:800x10 mm2x 2 m (Length)

5.4.3 Temperature-rise test result

The ambient air temperature: 28.4 ℃, performed date:25-06-2019

No. Temperature rise(K)

Tr.(K) Measuring position Coatings A B C

1 46.9 46.5 51.8 -- Incoming power copper bar 1m position -- 2 43.9 42.5 50.1 65 External busbar terminal silver-coated 3 41.1 42.5 44.4 75 Bolted connection silver-coated 4 46.4 54.6 54.8 65 Disconnector contact silver-coated 5 50.4 51.3 58.2 65 Disconnector contact silver-coated 6 57.8 44.6 65.4 75 Bolted connection silver-coated 7 64.8 63.5 64.4 75 Bolted connection silver-coated 8 61.2 56.1 59.6 75 Bolted connection silver-coated 9 58.5 57.4 58.8 65 Terminal silver-coated

10 56.1 55.7 56.7 -- The copper busbar 1 meter away from the terminal

--

11 -- 7.6 -- 40 Unaccessible enclosure -- 12 -- 2.8 -- 30 Accessible enclosure -- 13 -- 16.7 -- 40 Unaccessible enclosure --

Page 99: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 99 of 132

5.4.4 Temperature-rise test photograph

5.5 Temperature rise tests on auxiliary and control equipment

-The ambient air temperature: 27.2 ℃, performed date:26-06-2019

Page 100: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 100 of 132

-Test object for circuit s energized only during switching operations. -When the switching device has an automatic breaking device for interruption of the auxiliary circuit at the end of the operation, the circuit shall be energized 10 times, for either 1 s or until the automatic breaking device operates, the interval between the instant of each energizing being 10 s or, if the construction of the switching device does not permit this, the lowest interval possible. -The maximum temperatures of windings are determined by the resistance method by calculating the temperature rise and adding this value to the ambient temperature. -The temperature rise of copper windings is calculated from the formula:

t = (R2 – R1)(234.5 + t1) / R1 – (t2 – t1) where t is the temperature rise; R1 is the resistance at the beginning of the test; R2 is the resistance at the end of the test; t1 is the ambient temperature at the beginning of the test; t2 is the ambient temperature at the end of the test. -Test results:

TO R1(Ω) t1(℃) R2(Ω) t2(℃) t(K) Tr(K)

Opening coil 226.0 27.2 232.6 27.2 7.6 50 Closing coil 223.7 27.2 230.5 27.2 8.0 50

5.6 Mechanical operation test for circuit breaker

5.6.1 Circuit breaker mechanical operation before mechanical endurance test Rated voltage for operating mechanism:DC 220V, Rated voltage for energy motor:DC220 V

No Test items Before mechanical operation test

Performed date: 28-06-2019

1 Under the rated voltage, C-O, 5 times Normal

2 Under the min voltage, C-O, 5 times Normal

3 Under the max voltage, C-O, 5 times Normal

4 Under the rated voltage, C-O, 35 times(installed in switchgear

Normal

5.6.2 Mechanical characteristics test requirements and results of CB for Opening operation before mechanical endurance test.

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value

Before mechanical endurance test

1 Opening time Max. 15-16 ms 21.7~21.8 Rated 15-60 ms 23.0~23.4 Min. 15-60 ms 33.7~35.8

2 Average opening speed After opening 0-6 mm

Max. 1.1-1.9 m/s 1.78~1.82 Rated 1.1-1.9 m/s 1.73~1.78 Min. 1.1-1.9 m/s 1.78~1.85

3 Non-simultaneity of

three-phase opening

Max. ≤2 ms 0.07~0.10 Rated ≤2 ms 0.10~0.10 Min. ≤2 ms 0.07~0.13

4 Opening coil current Max. -- A 0.86~0.87 Rated -- A 0.75~0.76 Min. -- A 0.52~0.54

5 Rebound amplitude Max. ≤2 mm 1.30~1.40

Page 101: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 101 of 132

Rated ≤2 mm 1.22~1.31 Min. ≤2 mm 1.28~1.47

5.6.3 Mechanical characteristics test requirements and results of CB for Closing operation before mechanical endurance test

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value Before mechanical endurance test

1 Closing time Max. 20~70 ms 31.3~31.5 Rated 20~70 ms 32.4~32.5 Min. 20~70 ms 34.6~34.9

2 Average closing speed 10%-90% clearance between total stroke

Max. 0.6~1.2 m/s 0.76~0.76 Rated 0.6~1.2 m/s 0.76~0.77 Min. 0.6~1.2 m/s 0.75~0.76

3 Non-simultaneity of three-phase closing

Max. ≤2 ms 0.23~0.27 Rated ≤2 ms 0.20~0.23 Min. ≤2 ms 0.20~0.27

4 closing coil current Max. -- A 1.05~1.06 Rated -- A 0.96~0.96 Min. -- A 0.81~0.81

5 Bounce time of contact closing

Max. ≤2 ms 1.17~1.80 Rated ≤2 ms 1.17~1.80 Min. ≤2 ms 1.17~1.80

5.6.3 Mechanical characteristics test requirements and results of CB for O-0.3s-CO operation before mechanical endurance test

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value Before mechanical endurance test

1 The first opening time Rated 15-60 ms 23.4~23.6 2 Closing time Rated 20-70 ms 32.4~32.6

The second opening

time Rated 15-60 ms 22.9~23.4

3 Average the first opening speed

After opening 0-6 mm Rated 1.1-1.9 m/s 1.76~1.81

4 Average closing speed

10%-90% clearance between total stroke

Rated 0.6-1.2 m/s 0.76~0.77

5 Average the second

opening speed After opening 0-6 mm

Rated 1.1~1.9 m/s 1.75~1.78

6 Closing-opening time Rated ≤100±5 ms 100.7~101.0 7 Opening-closing time Rated ≤300±5 ms 301.0~301.2

No. Measuring items Technical

requirements SI

Measurement value

mechanical operation test

A B C 1 Contact opening 13±1.0 mm 13.2 13.1 12.9

5.6.4 Mechanical characteristics test oscilogram before mechanical endurance 195389G-101 195389G-106 195389G-111

Page 102: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 102 of 132

195389G-101-No-load test

Operating voltage: d.c C:220V O: 220V Test sequence: C-O

Test time: 28-06-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A insulating rod. SN of vacuum interrupter: phase A:S001212, phase B:S000441, phase C:S001208

Close time:[ms] Phase A: 32.5 Phase B:32.5 Phase C:32.3

Close coil current:[A] 0.96

Open time:[ms] Phase A: 23.3 Phase B: 23.2 Phase C:23.2

Open coil current: [A] 0.76

Non-simultaneity of three-phase closing[ms]:0.20 Bounce time of contact closing[ms]: Phase A:1.17 , Phase B:0.00, Phase C:1.07 Average closing speed before closing 6 mm:[m/s]:0.76 Closing coil current [A]:0.96 Non-simultaneity of three-phase opening[ms]:0.10 Rebound amplitude [mm]:1.22 Average opening speed before opening 6 mm:[m/s]:1.76 Opening coil current [A]:0.76

Page 103: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 103 of 132

195389G-106-No-load test

Operating voltage: d.c C:242 V O: 242 V Test sequence:C-O

Test time: 28-06-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A insulating rod. SN of vacuum interrupter: phase A:S001212, phase B:S000441, phase C:S001208

Open time:[ms] Phase A: 21.8 Phase B: 21.7 Phase C:21.7

Open coil current: [A]0.86

Close time:[ms] Phase A: 31.3 Phase B:31.3 Phase C:31.1

Close coil current:[A] 1.06

Non-simultaneity of three-phase closing[ms]:0.23 Bounce time of contact closing[ms]: Phase A:1.17 , Phase B:0.87, Phase C:1.77 Average closing speed before closing 6 mm:[m/s]:0.76 Closing coil current [A]:1.06

Non-simultaneity of three-phase opening[ms]:0.10 Rebound amplitude [mm]:1.40 Average opening speed before opening 6 mm:[m/s]:1.82 Opening coil current [A]:0.86

Page 104: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 104 of 132

195389G-111-No-load test

Operating voltage: d.c C:187.0 V O: 143.0 V Test sequence:C-O

Test time: 28-06-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A insulating rod. SN of vacuum interrupter: phase A:S001212, phase B:S000441, phase C:S001208

Open time:[ms] Phase A: 35.8 Phase B: 35.7 Phase C:35.8 Open coil current: [A] 0.54

Close time:[ms] Phase A:34.8 Phase B:34.8 Phase C:34.5 Close coil current:[A] 0.81

Non-simultaneity of three-phase closing[ms]:0.27 Bounce time of contact closing[ms]: Phase A:1.17 , Phase B:0.00, Phase C:1.00 Average closing speed before closing 6 mm:[m/s]:0.75 Closing coil current [A]:0.81 Non-simultaneity of three-phase opening[ms]:0.10 Rebound amplitude [mm]:1.28 Average opening speed before opening 6 mm:[m/s]:1.79 Opening coil current [A]:0.54

Page 105: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 105 of 132

5.6.5 Mechanical characteristics test test photograph before mechanical endurance

5.6.6 The vacuum circuit breaker mechanical endurance tests . Performed day: from 28-06-2019 to 09-07-2019 Mechanical operation test for 10000 operations Number of operating sequence arrangement:

Operating sequence

Opening and closing coils voltage

First cycle Second cycle Three cycle Fourth cycle Fifth cycle

C-t1-O-t2 C:187V O:143V

500 500 500 500 500

C-t1-O-t2 C:220V O:220V

500 500 500 500 500

C-t1-O-t2 C:242 V O:242 V

500 500 500 500 500

O-t3-CO-t4-C-t5

C:220V O:220V

250 250 250 250 250

O= opening(AID disconnection position), C= closing( work position); t1=15s, t2=15s, t3=0.3s,t4=30s,t5=30s

Test results: a) During the mechanical duty no maintenance. b) Auxiliary and control equipment switches appear no malfunction. c) All assembly components did not affect the normal operations. d) No abrasion for insulator and no loose for mechanical seal ring. e) Silver-coated continuously distribute in contacts.

f) Dielectric test 48kV power frequency inspection for the state of vacuum. g) After the tests, mechanical operation and mechanical characteristics tests passed.

Page 106: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 106 of 132

h) Withstood the 10000 operations.

5.6.6 Measurement of resistance of switchgear and circuit breaker -Test method: The resistance measurement was performed by measuring the voltage drop at a certain

current(DC 100 A). -Test results: VCB Before 10000 times

mechanical endurance After 10000 times mechanical

endurance Measuring position Refer to measurement position diagram of the resistance of A point to

A’ point

Requirements(μΩ) ≤90

Ambient temperature(℃) Ta:31.2 Ta:29.6 Tc:31.2

A Phase A(μΩ) 63.0 63.0 63.3

B Phase B(μΩ) 60.8 60.9 61.2

C Phase C(μΩ) 62.1 63.0 63.3

Max. difference limit value 20(%) -- 1.9 %

Auxiliary and control circuit switch Before 10000 times

mechanical endurance After 10000 times mechanical

endurance Measuring position Refer to measurement position diagram of the resistance of normal

close switch contact and normal open switch contact NC NO NC NO

Requirements(μΩ) --

Ambient temperature(℃) Ta:30.5 Ta:30.6 Tc:30.5 Ta:30.6 Tc:30.5

Contact resistance(μΩ) 6.3 6.2 6.8 6.8 6.7 6.7

Max. difference limit value 20(%) -- +7.9% +8.1%

Note: Ta: ambient air temperature. The results of the primary resistance measurements indicate that the switchgear and CB are capable of carrying the rated normal current without exceeding the prescribled temperature-rise limits. -Reference the measuring position diagram of the resistance of the circuit.

Page 107: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 107 of 132

5.6.7 Mechanical operation after mechanical endurance test

No Test items Before test

Performed date: 09-07-2019

1 Under the rated voltage, C-O, 5 times Normal

2 Under the min voltage, C-O, 5 times Normal

3 Under the max voltage, C-O, 5 times Normal

4 Under the rated voltage, C-O, 35 times(installed in switchgear

Normal

5.6.7.1 Mechanical characteristics test requirements and results of CB for Opening operation after mechanical endurance test

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value

Before mechanical endurance test

1 Opening time Max. 15-16 ms 21.3~21.9 Rated 15-60 ms 22.8~23.7 Min. 15-60 ms 33.6~35.1

2 Average opening speed After opening 0-6 mm

Max. 1.1-1.9 m/s 1.63~1.71 Rated 1.1-1.9 m/s 1.66~1.74 Min. 1.1-1.9 m/s 1.73~1.79

3 Non-simultaneity of

three-phase opening

Max. ≤2 ms 0.07~0.10 Rated ≤2 ms 0.07~0.10 Min. ≤2 ms 0.10~0.13

4 Opening coil current Max. -- A 0.84~0.87 Rated -- A 0.74~0.76 Min. -- A 0.52~0.53

5 Rebound amplitude Max. ≤2 mm 1.19~1.26 Rated ≤2 mm 1.21~1.24 Min. ≤2 mm 1.28~1.37

5.6.7.2 Mechanical characteristics test requirements and results of CB for closing operation after mechanical endurance test

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value Before mechanical endurance test

1 Closing time Max. 20~70 ms 31.4~31.6 Rated 20~70 ms 32.6~32.9 Min. 20~70 ms 35.0~35.7

2 Average closing speed 10%-90% clearance between total stroke

Max. 0.6~1.2 m/s 0.73~0.74 Rated 0.6~1.2 m/s 0.74~0.75 Min. 0.6~1.2 m/s 0.73~0.74

3 Non-simultaneity of three-phase closing

Max. ≤2 ms 0.20~0.23 Rated ≤2 ms 0.23~0.23 Min. ≤2 ms 0.20~0.23

4 closing coil current Max. -- A 1.04~1.04 Rated -- A 0.94~0.95 Min. -- A 0.80~0.80

5 Bounce time of contact closing

Max. ≤2 ms 1.17~1.77 Rated ≤2 ms 1.17~1.80 Min. ≤2 ms 1.17~1.80

5.6.7.3 Mechanical characteristics test requirements and results of CB for O-0.3s-CO operation after mechanical endurance test

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value Before mechanical endurance test

1 The first opening time Rated 15-60 ms 23.5~23.7

Page 108: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 108 of 132

2 Closing time Rated 20-70 ms 32.6~33.1

The second opening

time Rated 15-60 ms 22.7~23.5

3 Average the first opening speed

After opening 0-6 mm Rated 1.1-1.9 m/s 1.64~1.70

4 Average closing speed 10%-90% clearance between total stroke

Rated 0.6-1.2 m/s 0.74~0.75

5 Average the second

opening speed After opening 0-6 mm

Rated 1.1~1.9 m/s 1.68~1.70

6 Closing-opening time Rated ≤100±5 ms 99.8~101.0 7 Opening-closing time Rated ≤300±5 ms 300.9~301.7

No. Measuring items Technical

requirements SI

Measurement value

mechanical operation test

A B C 1 Contact opening 13±1.0 mm 12.7 12.7 12.4

5.6.7.4 Mechanical characteristics test oscilogram 195389G-601 195389G-606 195389G-611

Page 109: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 109 of 132

195389G-101-No-load test

Operating voltage: d.c C:220V O: 220V Test sequence: C-O

Test time: 09-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A insulating rod. SN of vacuum interrupter: phase A:S001212, phase B:S000441, phase C:S001208

Close time:[ms] Phase A: 32.7 Phase B:32.7 Phase C:32.5

Close coil current:[A] 0.94

Open time:[ms] Phase A: 23.7 Phase B: 23.6 Phase C:23.6

Open coil current: [A] 0.76

Non-simultaneity of three-phase closing[ms]:0.23 Bounce time of contact closing[ms]: Phase A:1.10 , Phase B:0.00, Phase C:1.80 Average closing speed before closing 0-6 mm:[m/s]:0.74 Closing coil current [A]:0.94 Non-simultaneity of three-phase opening[ms]:0.10 Rebound amplitude [mm]:1.24 Average opening speed before opening 6 mm:[m/s]:1.74 Opening coil current [A]:0.76

Page 110: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 110 of 132

195389G-606-No-load test

Operating voltage: d.c C:242 V O: 242 V Test sequence:C-O

Test time: 09-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A insulating rod. SN of vacuum interrupter: phase A:S001212, phase B:S000441, phase C:S001208

Open time:[ms] Phase A: 21.8 Phase B: 21.7 Phase C:21.8

Open coil current: [A] 0.86

Close time:[ms] Phase A: 31.4 Phase B:31.5 Phase C:31.2

Close coil current:[A]1.04

Non-simultaneity of three-phase closing[ms]:0.23 Bounce time of contact closing[ms]: Phase A:1.17 , Phase B:0.00, Phase C:1.03 Average closing speed before closing 6 mm:[m/s]:0.74 Closing coil current [A]:8.63 Non-simultaneity of three-phase opening[ms]:0.07 Rebound amplitude [mm]:1.27 Average opening speed before opening 6 mm:[m/s]:1.69 Opening coil current [A]:0.86

Page 111: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 111 of 132

195389G-611-No-load test

Operating voltage: d.c C:187.0 V O: 143.0 V Test sequence:C-O

Test time: 09-07-2019

TO status: Spring stored energy mechanism. Linear sensor installed in Phase A insulating rod. SN of vacuum interrupter: phase A:S001212, phase B:S000441, phase C:S001208

Open time:[ms] Phase A: 34.0 Phase B: 33.9 Phase C:34.0

Open coil current: [A] 0.52

Close time:[ms] Phase A: 34.9 Phase B:35.0 Phase C:34.7

Close coil current:[A] 0.80

Non-simultaneity of three-phase closing[ms]:0.23 Bounce time of contact closing[ms]: Phase A:1.17 , Phase B:0.87, Phase C:1.03 Average closing speed before closing 6 mm:[m/s]:0.73 Closing coil current [A]:0.80

Non-simultaneity of three-phase opening[ms]:0.10 Rebound amplitude [mm]:1.36 Average opening speed before opening 6 mm:[m/s]:1.77 Opening coil current [A]:0.52

Page 112: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 112 of 132

5.7.Mechanical operaton test for disconnector

Apparatus tested serial No.: RD1007/1501/A1 cooperated with switchgear.

5.7.1 Measurement of resistance of disconnector -Test method: The resistance measurement was performed by measuring the voltage drop at a certain

current(DC 100 A). -Test results: VCB+disconnector Before 5000 times mechanical

endurance After 5000 times mechanical

endurance Measuring position Refer to measurement position diagram of the resistance of A point to

A’ point

Requirements(μΩ) ≤90

Ambient temperature(℃) Ta:31.2 Ta:29.6 Tc:31.2

A Phase A(μΩ) 63.0 63.0 63.3

B Phase B(μΩ) 60.8 60.9 61.2

C Phase C(μΩ) 62.1 63.0 63.3

Max. difference limit value 20(%) -- 1.9 %

Note Ta: Ambient air temperature, Tc:Corrected temperature 5.7.2 Measurement position diagram of the resistance of circuits

5.7.3 Mechanical operation test of disconnector Performed date:09-07-2019

No. Test item Result

1 Use manual operation handle, C-O, 50 times(installed in switchgear) Passed 5.7.3.1 Mechanical characteristics test requirements and results for disconnector -Opening operation before mechanical tests.

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value

mechanical operation test

1 Max. force for one handle rotation

-- ≤60 N Close operation:34

-- ≤60 N Open operation:35

Note: Operation handle length:400 mm

Page 113: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 113 of 132

5.7.3.2 The disconnector had 5000 times mechanical endurance. Performed day: from 09-07-2019 to 15-07-2019 Mechanical operation test for 5000 operations Number of operating sequence arrangement:

Operating sequence

First cycle Second cycle Third cycle Fourth cycle End cycle

C-t1-O-t2 1000 1000 1000 1000 1000 O= opening(AID disconnection position),C= closing( work position) t 1= 60s, t2=60s

Test results: a)During the mechanical duty no maintenance. b)Auxiliary and control equipment switches appear no malfunction. c) All assembly components did not affect the normal operations. d) No abrasion for insulator and no loose for mechanical seal ring. e) Withstood the 5000 operations. 5.7.3.3 Mechanical characteristics test requirements and results for disconnector -Opening operation after mechanical tests.

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value mechanical operation test

1 Max. force for one handle rotation

-- ≤60 N Close operation:38

-- ≤60 N Open operation:35

Note: Operation handle length:400 mm 5.7.3.4 test apparatus photograph for phase B after testing

Phase B disconnector contact after endurance test

5.8.Mechanical operaton test for earthing switch

Apparatus tested serial No.: RD1007/1501/A1 cooperated with switchgear. 5.8.1 Measurement of resistance of earthing switch -Test method: The resistance measurement was performed by measuring the voltage drop at a certain

Page 114: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 114 of 132

current(DC 100 A). -Test results:

Switchgear Before mechanical operation test After mechanical operation test

Measuring position Refer to measurement position diagram of the resistance of circuits From B point to B’ point

Requirements(μΩ) ≤100

Ambient temperature(℃) Ta:30.2 Ta: 30.1 Tc:30.2

A Phase A(μΩ) 77.3 77.6 77.6

B Phase B(μΩ) 70.4 73.0 73.0

C Phase C(μΩ) 74.1 75.0 75.0

Max. difference limit value 20(%) -- -- 3.7 %

Note Ta: Ambient air temperature, Tc:Corrected temperature 5.8.2 Measurement position diagram of the resistance of circuits

5.8.3 Mechanical operation test of earthing switch Performed date:16-07-2019

No. Test item Result

1 Use manual operation handle, C-O, 50 times(installed in switchgear) Passed 5.8.3.1 Mechanical characteristics test requirements and results for earthing switch -Opening operation before mechanical tests.

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value mechanical operation test

1 Max. force for one handle rotation

-- ≤60 N Close operation:35

-- ≤60 N Open operation:38

Note: Operation handle length:400 mm 5.8.3.2 The earthing switch had 5000 times mechanical endurance. Performed day: from 16-07-2019 to 22-07-2019 Mechanical operation test for 5000 operations Number of operating sequence arrangement:

Operating sequence

First cycle Second cycle Third cycle Fourth cycle End cycle

C-t1-O-t2 1000 1000 1000 1000 1000 O= opening(AID disconnection position),C= closing( work position) t 1= 60s, t2=60s

Test results: a)During the mechanical duty no maintenance. b)Auxiliary and control equipment switches appear no malfunction. c) All assembly components did not affect the normal operations.

Page 115: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 115 of 132

d) No abrasion for insulator and no loose for mechanical seal ring. e) After the tests: all parts in good condition and no undue wear. f) After the tests, silver plated contacts in good condition and no undue wear. g) Withstood the 5000 operations. 5.8.3.3 Mechanical characteristics test requirements and results for earthing switch -Opening operation after mechanical tests.

No. Measuring items Operating

voltage Technical

requirements SI

Measurement value mechanical operation test

1 Max. force for one handle rotation

-- ≤60 N Close operation:38

-- ≤60 N Open operation:38

Note: Operation handle length:400 mm 5.8.3.4 test apparatus photograph for phase B after testing

Phase B disconnector contact after endurance test

5.9.Mechanical operaton test for earthing switch

Performed date:05-09-2019 5.9.1 Interlocks verification.

No. Situation of the test object Operation command Operation times Test

sitiation

1 CB was the closed position

Closing and opening operation of DS

50 Blocked

2 CB was the closed position

Closing and opening operation of ES

50 Blocked

3

CB was at the closed position, ES was at the closed position

Front lower door was opened

25 Action

4 CB was at the opened Front lower door was opened 25 Blocked

Page 116: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-MT Page 116 of 132

position, ES was at the closed position

5

CB was at the closed position, ES was at the opened position

Front lower door was opened

25 Blocked

6 Front middle door was theclosedposition

Closing operation of CB

50 Action

7 Front middle door was theclosedposition

Opening operation of CB

50 Action

Notes: The operating force was almost the same before and after the test. The disconnector and earth switch form a three-position switch. The back door with screw fastening. 5.9.2 Operating sequence. The operating sequence of test object from the repair position to the service position.

①→ ②→ ③→ ④

①Opening operation of circuit breaker

②Opening operation of earthing switch

③Closing operation of disconnector

④Closing operation of circuit breaker.

5.9.3 The operating sequence of object from the service position to the repair position. ①→ ②→ ③→ ④

①Opening operation of circuit breaker

②Opening operation of disconnector

③Closing operation of earth switch

④Closing operation of circuit breaker.

Page 117: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 117 of 132

5.10 Electromagnetic compatibility tests(EMC tests)

Performed date: 03-07-2019

The lab measurement test equipment calibration Item Expanded uncertainty

Conducted emission test U=2.8dB(k =2)

Radiated emission test U=4.6dB(k=2)

Electrical fast transient/burst immunity test U=2.0%(k=2)

Oscillatory waves immunity test U=5.0%(k=2)

Voltage dips, short interruptions and voltage variations immunity test U=3.0%(k=2)

Ripple on d.c input power port immunity test U=5.3%(k=2)

5.10.1 Emission tests from the auxiliary and control circuits

Performed date:19-08-2019 5.10.1.1 Conducted emission tests from the auxiliary and control circuits. Atmospheric conditions:P=96.3 kPa t=24.9 ℃ RH=50.1 %

Clause 6.9.1.2 of IEC 62271-1:2007 was performed. 5.10.1.1.1 Test equipment Equipment name

Model Serial No. Manufacturer Certificate Valid date

Receivers N9038A MY52260136 Agilent 1GA19006904-0004

16-05-2020

AMN NSLK-8127 8127-672 SCHWARZBECK

1GA19006682-0011

16-05-2020

5.10.1.1.2 Test ports. A.C input port d.c input port Signal line port Grounding port Whole machine

port -- 220V -- -- --

5.10.1.1.3 Test parameters Packet classification according to engineering course medical science equipment

Group1, Class A equipment Quasi-peak dB((μV) RMS value dB((μV)

0.15MHz-0.50MHz termination disturbance voltage limitation 97-89 84-76 0.50MHz-5MHz termination disturbance voltage limitation 89 76 5MHz-30MHz termination disturbance voltage limitation 89 76

5.10.1.1.4 Test object status and test circuit Test object

Integrity production; Integrity auxiliary and control circuit. Sub package; Sub-package in cabinet

Load condition Rated load; other type load Test arrangement photo CE01 Test result Normal; other condition and note

Page 118: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 118 of 132

Test arrangement photo-CE01 5.10.1.1.5 Test circuit.

5.10.1.1.6 Test data d.c. positive measurement data Frequency (MHz)

Amplitude dB((μV)

Limitation dB((μV)

Permission limitation dB((μV)

Wave inspection type

Spectrogram

-- -- -- -- QP CE02 -- -- -- -- QP

Page 119: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 119 of 132

-- -- -- -- QP -- -- -- -- QP -- -- -- -- AV -- -- -- -- AV -- -- -- -- AV -- -- -- -- AV d.c negative measurement data Frequency (MHz)

Amplitude dB((μV)

Limitation dB((μV)

Permission limitation dB((μV)

Wave inspection type

Spectrogram

-- -- -- -- QP CE03 -- -- -- -- QP -- -- -- -- QP -- -- -- -- QP -- -- -- -- AV -- -- -- -- AV -- -- -- -- AV -- -- -- -- AV

Notes: 1. Test spectrogram included the peak value and RMS value in sweep frequency curve. The high amplitude

frequency point measurement value displaied in the above table. If no data display in the above table which stated no high amplitude frequency point were measured.

2. QP: quasi-peak value inspection wave method, AV: RMS value inspection wave method, P: peak value inspection wave mentod.

Fig.CE02 Conducted emission test spectrogram of positibve line

Fig.CE03 Conducted emission test spectrogram of negative line

Page 120: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 120 of 132

5.10.1.1.7 Test result

Passed Failed 5.10.1.2 Radiated emission tests from the auxiliary and control circuits. Atmospheric conditions:P=96.3 kPa t=24.9 ℃ RH=50.1 %

Clause 6.9.1.2 of IEC 62271-1:2007 was performed. 5.10.1.2.1 Test equipment Equipment name

Model Serial No. Manufacturer Certificate Valid date

Receiver N9038A MY52260148 Agilent 1GA19006904-0005

12-05-2020

Biconical logarithm antenna

VULB9160 VULB9160-3341

SCHWARZBECK

ETA2019-4-612

21-04-2020

5.10.1.2.2 Test ports.

A.c input port

d.c input port

Signal line port

Earthing port

Equipment port -- -- -- -- ✔

5.10.1.2.3 Test parameters Packet classification according to engineering course medical science equipment

Group1, Class A type equipment 10 m measure distance

3 m Measure distance

30MHz-230MHz radiated emission disturbance voltage limitation(Quasi-peak)

quasi-peak value: 40dB(μV/m)

quasi-peak value: 50dB(μV/m)

230MHz-1000MHz radiated emission disturbance voltage limitation(Quasi-peak)

quasi-peak value: 47dB(μV/m)

quasi-peak value: 57dB(μV/m)

5.10.1.2.4 Test object status. Test object

Integrity production; Integrity auxiliary and control circuit.

Sub package; Sub-package in cabinet Load condition Rated load; other type load Test arrangement photo RE01 and RE02 Test result Normal; other condition and note

Page 121: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 121 of 132

Horizontal test arrangement photo-RE01

Vertical test arrangement photo-RE02 5.10.1.2.5 Test circuit.

Page 122: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 122 of 132

5.10.1.2.6 Test data Horizontal direction measurement data Frequency (MHz)

Amplitude dB((μV)

Limitation dB((μV)

Permission limitation dB((μV)

Antenna height

Antenna angle(。)

Wave inspection type

Spectrogram

-- -- -- -- -- -- QP RE03 -- -- -- -- -- -- QP -- -- -- -- -- -- QP -- -- -- -- -- -- QP -- -- -- -- -- -- QP -- -- -- -- -- -- QP Vertical direction measurement data Frequency (MHz)

Amplitude dB((μV)

Limitation dB((μV)

Permission limitation dB((μV)

Antenna height(cm)

Antenna

angle(。)

Wave inspection type

Spectrogram

-- -- -- -- -- -- QP RE04 -- -- -- -- -- -- QP -- -- -- -- -- -- QP -- -- -- -- -- -- QP -- -- -- -- -- -- QP -- -- -- -- -- -- QP

Notes: 1, The test object performed distance 3 meter from antenna. 2. Test spectrogram included the peak value and RMS value in sweep frequency curve. The high

amplitude frequency point measurement value displaied in the above table. If no data display in the above table whichstated no high amplitude frequency point were measured.

3. Horizontal direction spectrogram RE03, vertical direction spectrogram RE04 4 QP: quasi-peak value inspection wave method, AV: RMS value inspection wave method,

P: peak value inspection wave mentod.

Page 123: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 123 of 132

Fig.RE03 Radiated emission horiaontal test spectrogram

Fig.RE04 Radiated emission vertical test spectrogram

5.10.1.2.7 Test result

Passed Failed

5.10.2 Electrical fast transient/burst test for Class3

Performed date:19-08-2019 Atmospheric conditions:P=96.3 kPa t=24.9 ℃ RH=50.1 %

Clause 6.9.2.3 of IEC 62271-1:2007 was performed. 5.10.1.1 Test equipment Equipment name Model Serial No. Manufacturer Certificate Valid date Burst generator NSG2025 28662 TESEQ JZ118100189 08-10-2019

5.10.1.2 Test ports.

A.c input port

d.c input port

Signal line port

Earthing port

Equipment port -- ✔220 v d.c -- -- --

5.10.1.3 Test parameters Technical requirements Supply port Signal port Test class 3 -- Apply voltage(kV) 2 -- Burst cluster cycle(ms) 300 --

Page 124: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 124 of 132

Oscillation frequency(kHz) 5 -- -- -- Burst cluster duration(ms) 15 -- -- -- Test time (s) 60 -- --- --

5.10.1.4 Test object status. Test object

Integrity production; Integrity auxiliary and control circuit.

Sub package; Sub-package in cabinet Load condition Rated load; other type load Test arrangement photo EFT01 Test result Normal; other condition and note

Test arrangement photo-EFT01

Page 125: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 125 of 132

5.10.1.5 Test circuit.

5.10.1.6 Test inspection A: Normal performance within the technical requirements. Verified B: Temporary loss of function or degradation of performance which ceases after the

disturbance ceases, and from which the EUT recovers its normal performance, without operator intervention.

N/A

C: Temporary loss of function or degradation of performance, the correction of which requires operator intervention.

N/A

D: Loss of function or degradation of performance which is not recoverable, owing to damage to hardware or software, of loss data

N/A

5.10.1.7 Test result

Passed Failed

5.10.3 Oscillatory wave immunity test for Class3 Performed date:19-08-2019

Atmospheric conditions:P=96.3 kPa t=24.9 ℃ RH=50.1 % Clause 6.9.2.4 of IEC 62271-1:2007 was performed. 5.10.3.1 Test equipment Equipment name Model Serial No. Manufacturer Certificate Valid date Oscillatory wave immunity generator

DOWG-6112G EC0981115 3C TEST JZ0190021 01-01-2020

5.10.3.2 Test ports.

A.c input port

d.c input port

Signal line port

Earthing port

Equipment port -- ✔ -- -- --

5.10.3.3 Test parameters Technical requirements Supply circuit

Page 126: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 126 of 132

Common-mode Difference-mode Test class 3 3 Apply voltage(kV) 2.5 1.0

Oscillation frequency(MHz) 0.1 1 0.1 1 Pulse repeated frequency(times/s) 40 400 40 400 Group pulse times (alternate polarity)

10 10 10 10

Group pulse duration(s) 2 2 2 2 Test time(min) 2 2 2 2

5.10.3.4 Test object status. Test object

Integrity production; Integrity auxiliary and control circuit.

Sub package; Sub-package in cabinet Load condition Rated load; other type load Test arrangement photo Osc01 Test result Normal; other condition and note

Test arrangement photo-Osc01 5.10.3.5 Test circuit

Page 127: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 127 of 132

5.10.3.6 Test inspection A: Normal performance within the technical requirements. Verified B: Temporary loss of function or degradation of performance which ceases after the

disturbance ceases, and from which the EUT recovers its normal performance, without operator intervention.

N/A

C: Temporary loss of function or degradation of performance, the correction of which requires operator intervention.

N/A

D: Loss of function or degradation of performance which is not recoverable, owing to damage to hardware or software, of loss data

N/A

5.10.3.6 Test result

Passed Failed

5.10.4 Ripple on d.c. input power port immunity test for Class2

Performed date: 19-08-2019

Atmospheric conditions:P=96.3 kPa t=24.9 ℃ RH=50.1 % Clause 6.9.3.2 of IEC 62271-1:2007 was performed. 5.10.4.1 Test equipment Equipment name Model Serial No. Manufacturer Certificate Valid date Harmonics source MX30-3Pi-413-

CTSHL-LF 1132A00249 AMETEK 1GA19006904-

0006/0007 15-05-2020

5.10.4.2 Test portS. A.c input port d.c input port Signal line port Earthing port Equipment port

-- ✔ -- -- --

5.10.4.3 Test parameters Technical requirements Supply circuit

Test class 2 Apply voltage RMS value (V) 220

Ripple voltage percent (%) 5 Ripple voltage frequency(Hz) 150 Test duration(min) 15

5.10.4.4 Test object status. Test object

Integrity production; Integrity auxiliary and control circuit. Sub package; Sub-package in cabinet

Load condition Rated load; other type load Test arrangement photo Rip01

Page 128: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 128 of 132

Test result Normal; other condition and note

Test arrangement photo-Rip01

5.10.4.5 Test circuit

5.10.4.6 Test inspection A: Normal performance within the technical requirements. Verified B: Temporary loss of function or degradation of performance which ceases after the

disturbance ceases, and from which the EUT recovers its normal performance, without operator intervention.

N/A

C: Temporary loss of function or degradation of performance, the correction of which requires operator intervention.

N/A

D: Loss of function or degradation of performance which is not recoverable, owing to damage to hardware or software, of loss data

N/A

5.10.4.7 Test result

Passed Failed

Page 129: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 129 of 132

5.10.5 Voltage dips, short interruptions and voltage variations on d.c. input power port

immunity tests

Performed date: 19-08-2019

Atmospheric conditions:P=96.3 kPa t=24.9 ℃ RH=50.1 % Clause 6.9.3.3 of IEC 62271-1:2007 was performed. 5.10.5.1 Test equipment Equipment name Model Serial No. Manufacturer Certificate Valid date Harmonics source MX30-3Pi-413-

CTSHL-LF 1132A00249 AMETEK 1GA19006904-

0006/0007 15-05-2020

5.10.5.2 Test port. A.c input port d.c input port Signal line port Earthing port Equipment port

-- ✔ -- -- --

5.10.5.3 Test parameters Technical requirements Supply circuit

Voltage transient Transient interrupt Voltage variation Test grade (%UT) 40 70 0 80 120

Duration(s) 0.1 0.3 0.01 1 Recycle (times) 3 3 3 Test duration(s) 20 20 10

5.10.5.4 Test object status. Test object

Integrity production; Integrity auxiliary and control circuit. Sub package; Sub-package in cabinet

Load condition Rated load; other type load Test arrangement photo Dip01 Test result Normal; other condition and note

Test arrangement photo-Dip01 5.10.5.5 Test circuit

Page 130: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

GROUP2-195388G-EMC Page 130 of 132

5.10.5.6 Test inspection A: Normal performance within the technical requirements. Verified B: Temporary loss of function or degradation of performance which ceases after the

disturbance ceases, and from which the EUT recovers its normal performance, without operator intervention.

N/A

C: Temporary loss of function or degradation of performance, the correction of which requires operator intervention.

N/A

D: Loss of function or degradation of performance which is not recoverable, owing to damage to hardware or software, of loss data

N/A

5.10.5.7 Test result

Passed Faile END OF TEST REPORT

Page 131: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001 Drawings Page 131 of 132

6 Drawings

Page 132: TYPE TEST REPORT OF COMPLETE TYPE TEST

TÜV Rheinland-TRF

Report No.50283626 001

Declaration Page 132 of 132

1. The test report will be invalid without the original signature. 2. The test report will be invalid with alter of any character or data.

3. Any dissension to this test report should be formally submitted to the Laboratory within 25 days once receiving the report. 4. This test report applies only to the tested object. The responsibility for

conformity of any apparatus having the same designations with that tested rests with the manufacturer.

5. Tested object and relevant content in this report may involve patent. The laboratory will not responsible for identifying these patents or any others.

— TÜV Rheinland (Shanghai) Co., Ltd.

Unternehmensgruppe

TÜV Rheinland Group

— TÜV Rheinland Building, No.

177, Lane 777, West

Guangzhong Road, Jing’an

District, Shanghai 200072,

P.R. China

Tel : (86/21) 61081188

Fax : (86/21) 61081199

e-mail : [email protected]

Internet : http://www.chn.tuv.com

GC Hotline:86 4008831300

86 8009993668