Type 8BK20 Switchgear up to 24 kVwith Withdrawable Circuit-Breakers
s
Medium-VoltageSwitchgearCatalog HA 25.211999
1
2
3
4
5
6
A
Supersedes: Catalog HA 25.21 · 1995
Type 8BK20 Switchgear up to 24 kV with WithdrawableCircuit-Breakers
Air-Insulated, Metal-Enclosed, Metal-CladSingle/Duplicate Busbar
© Siemens AG 1999
Medium-Voltage SwitchgearCatalog HA 25.21 · 1999
Application, FeaturesTypical uses 2 Personnel safety,Equipment reliability, operation 2 to 4
Technical DataElectrical data, dimensions 5 and 6Installation details 6 and 7Shipping details 8
Product RangeSingle busbar panels 9 to 11Duplicate busbar panels 12
Electrical DesignBasic panel design 13
Mechanical DesignHigh-voltage section 14 to 18Low-voltage section 19
StandardsStandards, specifications,guidelines 20 to 22
AppendixCatalog index 23
Conditions of sale and delivery, 24export regulations, trademarks, dimensions
Contents
1
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
Application Features
8BK20 switchgear with withdrawable circuit-breakersfor indoor installation is suitable for:
� Rated voltages from 7.2 kV to 24 kV
� Rated short-circuit breaking currents from 31.5 kA to 50 kA
� Rated busbar normal currentsup to 4000 A
� Rated feeder normal currents up to 4000 A
Typical uses
� Power stations, transformer stations and switchingsubstations of public utilities
� Cement industry
� Automotive industry
� Iron and steelworks
� Rolling mills
� Mines
� Food and fiber industry
� Chemical industry
� Mineral oil industry
� Pipelines
� Offshore installations
� Electrochemicals
� Petrochemicals
� Railway power supplies
� Shipbuilding
� Diesel power stations
� Emergency power supplies
Personnel safety
Switching operations withdoor closed
Personnel safety is increasedby:• Opening and closing of the
switching device– In the disconnected or
connected position– Mechanically or electrically– With the door closed• Isolation by moving the
withdrawable part, manuallyor motorized, with the doorclosed
• Verification of safe isolationfrom supply. According toVDE 0105, Part 1, there arethree alternative methods:
– Closing of a make-proofearthing switch with the doorclosed
– Pole-by-pole testing with acapacitive voltage detectorwith the door closed
– Testing with conventionalvoltage testers to VDE 0681,Part 4, but with the dooropen
• Opening and closing of themake-proof earthing switchwith the door closed
– On the feeder and on thebusbar: manually
Interlocking of door/withdrawable part
The door is incorporated in theinterlocking concept as follows:• Opening is possible only
when the withdrawable partis locked in the disconnectedposition.
• The withdrawable part can bemoved from the disconnect-ed to the service positiononly when the door is closed
R-HA
25-2
86 e
ps
2�Siemens HA 25.21 · 1999
1
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�3
Features
Personnel safety
Protection against electricshock and ingress of solidforeign bodies
8BK20 switchgear providesboth external and internalprotection. • External protection is
provided by– Complete enclosure of the
panels in all operating states• Internal protection is
provided by– Internal metal compart-
mentalization with enforced-operation shutters, optionalarc-resistant version of thebusbar compartment
– The inter-cubicle partitions;optional arc-resistant version
• Degree of protectionStandard version IP4X/IP3XD.Higher degrees of protection,such as IP31D, IP50 andIP51, can be obtained byadditional measures.
Arc-tested sheet-steelenclosure or compart-mentalization
8BK20 switchgear has beentested in accordance with the relevant standards forresistance to accidental arcingto ensure:• External protection
(personnel safety)• Optional resistance to
internal arcing (exceeding the scope of the standards),i.e. the effects of an arc arelimited as follows:
– Pressure-proof in relation toneighboring panels
– Pressure-proof from thewithdrawable part or theconnection compartment to the busbar compartment(applicable to rated currentsup to 2500 A only)
– Pressure-proof from thebusbar compartment to thewithdrawable part or connec-tion compartment (applicableto rated currents up to 2500 A only)
• Pressure switch– Limits arc duration to a
maximum of 100 ms– Minimizes the damage and
effects of an arc– Recommended use with
grading times >0.5 s– A function check of the
pressure switch is possiblewithout interruptingoperation
– Triggers the feeder circuit-breaker if the pressureswitch responds
Switchgear interlocking
All interlocks are mechanicalwith preventive, key-operatedaccess shutters, i.e.:• Operating levers can only be
inserted when the inter-locking conditions are fulfilled
• This prevents impermissibleoverstraining of the interlock-ing mechanisms
Electric strength
Adequate electric strength of8BK20 switchgear is assuredby:• Sufficiently large air gaps
between phases and to earth• Suitable electrode formThese design features allow all conductor insulation to bedispensed with entirely.
Highest level ofindependence of climate and environment
This is provided by:• Ribbed insulators in cast
resin, with high resistance to pollution
• Total enclosure under alloperating conditions
Maintenance
Minimum maintenanceeffort is assured by:• Total enclosure under all
operating conditions• Use of proven, mainte-
nance-free vacuumswitching devices
Availability
Easy procurement of partsfor extensions and repairsthrough the use of:• Standard insulators• Standard instrument
transformers• Standard vacuum
switching devices• Standard copper sections• Detachable low-voltage
compartment up to 15 kVwith plug-in connectiontechnology
Equipment reliability
8BK20 switchgear withwithdrawable circuit-breakers
1)Additional interlocks that exceed the scope of VDE 0670 Part 6 or IEC 60 298.
1
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
4�Siemens HA 25.21 · 1999
Operation
Moving a withdrawable partinside a panel
Little effort is required by handor motor to move a with-drawable part inside a panelwith the aid of:• A spindle mechanism• Ball-bearing rollers
Moving a withdrawable partoutside a panel
A withdrawable part is light andeasy to move outside a panel: • With a central service truck
(see also adjacent figures)• By one man• Without tools• Regardless of floor surface
Sequence for moving thewithdrawable part
• Move the withdrawable partinto the disconnectedposition
• Open the door• Unplug the low-voltage
connector• Unlock the withdrawable part
(unintentional removal of thewithdrawable part is prevent-ed by an additional interlock)
• Bring up the central servicetruck and lock it onto thepanel (additional interlock isthen overridden)
• Pull out the withdrawablepart onto the truck as far as it will go (it cannot fall)
• Detach the central servicetruck and the withdrawablepart from the panel
Remote control
Electric remote control, e.g.from a central control room,can be provided for thefollowing functions:• Moving a motorized
withdrawable part into thedisconnected or connectedposition
• Opening and closing of theswitching device
Local manual operation isalways ensured.
Features
Central service truck formoving the withdrawablepart
• Withdrawable part can belowered to the floor
• Collapsible for space-savingstorage
• Withdrawable part locksautomatically onto the trunk
• Lifting arms can be crankedup to maximum heights
– 1200 mm for 7.2/12/15 kVinstallations
– 1430 mm for 17.5/24 kVinstallations
• Large, swiveling wheels • Suitable for all withdrawable
parts
Verification of safe isolationfrom supply
With a voltage detector con-forming to the LRM system(Low Resistance Modified) to E VDE 0682 Part 415:• Pole-by-pole verification of
safe isolation from supply• Detector suitable for
continuous operation • Safe to touch• Routine-tested• Measuring system and
voltage detector can betested
• Voltage detector flasheswhen high voltage is applied
Interlocking conditions
The following operations canbe carried out as soon as thefollowing standard interlockingconditions have been met:• Moving the withdrawable
part from the disconnectedto the connected position:
– Low-voltage connectorplugged in
– High-voltage door closed 1)– Circuit-breaker in the OPEN
position– Make-proof earthing switch
in the OPEN position 1)• Moving the withdrawable
part from the connected tothe disconnected position:
– Circuit-breaker in the OPENposition
• Operating the circuit-breaker:withdrawable part in theinterlocked end position
• Operating the make-proofearthing switch:
– Withdrawable part in theinterlocked disconnectedposition 1)
• Opening the high-voltagedoor:
– Withdrawable part in theinterlocked disconnectedposition 1)
HA25
-249
1a e
ps
-C1
-C2
ULE
-H
L1
L2
L3
R-HA
25-2
84 e
psR-
HA25
-285
eps
Ready to use
Collapsed
Central service truckVerification of safeisolation from supply
Legend
–C1
Capacitor integrated in current transformer or in post insulator
–C2
Capacitor of the connectingcables and of the voltagedetector to earth
–HVoltage detector, plug-in
ULE
Voltage between conductorand earth
2
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�5
Technical Data
Electrical data
Withdrawable vacuumcircuit-breaker panel
Disconnector-link panel
Sectionalizer panel
Busbar connection panel,types I and II
Rated voltage kV 7.2 12 15 1) 17.5 24
Width mm 1800 1800 1800 1000 1000
Rated short-time power-frequency withstand voltage kV 1120 1128 1136 1138 1150
Rated lightning impulse withstand voltage kV 1160 1175 1195 1195 1125
Rated short-circuit breaking current max. kA 1150 1150 1150 1125 1125
Rated short-time withstand current 1 s max. kA 1150 1150 1150 1125 1125
3 s max. kA 1140 1140 1140 1125 1125
Rated short-circuit making current/ max. kA 1125 1125 1125 1163 1163rated peak withstand current
Rated normal current of busbars max. A 4000 4000 4000 2500 2500
Rated normal current of feeders max. A 4000 4000 4000 2000 2000
Rated voltage kV 7.2 12 15 1) 17,5 24
Width mm 1800 1800 1800 1000 1000
Rated short-time power-frequency withstand voltage kV 1120 1128 1136 1138 1150
Rated lightning impulse withstand voltage kV 1160 1175 1195 1195 1125
Rated short-time withstand current 1 s max. kA 50/20 2) 150/20 2) 150/20 2) 25/16 2) 25/16 2)
3 s max. kA 40/20 2) 140/20 2) 140/20 2) 25/16 2) 25/16 2)
Rated short-circuit making current/ max. kA 25/50 2) 125/50 2) 125/50 2) 63/40 2) 63/40 2)rated peak withstand current
Rated normal current of busbars max. A 4000 4000 4000 2500 2500
Rated normal current of feeders max. A 1630 1630 1630 1630 1630
Dimensions of HV HRC fuses mm 1292 1292 1292 1442 1442
Withdrawable vacuumswitch panel
Rated voltage kV 7.2 12 15 1) 17.5 24
Width mm 1800 1800 1800 1000 1000
Rated short-time power-frequency withstand voltage kV 1120 1128 1136 1138 1150
Rated lightning impulse withstand voltage kV 1160 1175 1195 1195 1125
Rated short-time withstand current 1 s max. kA 1150 1150 1150 1125 1125
3 s max. kA 1140 1140 1140 1125 1125
Rated peak withstand current max. kA 1125 1125 1125 1163 1163
Rated normal current of busbars max. A 4000 4000 4000 2500 2500
Metering panel
Rated voltage kV 7.2 12
Width mm 1800 1800
Rated short-time power-frequency withstand voltage kV 1120 1128
Rated lightning impulse withstand voltage kV 1160 1175
Rated short-time withstand current 1 s max. kA 1150 1150
3 s max. kA 1140 1140
Rated short-circuit making current/ max. kA 1125 1125rated peak withstand current
Rated normal current of busbars max. A 4000 4000
Earthing transformer panel
1) Please inquire about 17.5 kV with corresponding insulating capacity. 2) When used without HV HRC fuses.
Room planning
Pay attention to theinformation in theadjacent figures andtables for details ofplanning theswitchgear room.
Legend
1 8BK20 switchgear
2 Panel subdivision
3 Switchgear termination
4 Front operating aisle
5 Distance from wall
6 Building wall2
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
Dimensions Installation details
Technical Data
6�Siemens HA 25.21 · 1999
Panel dimensionsRated voltage kV 7.2 12 15 1) 17.5 24
Width mm 1800 1800 1800 1000 1000
Height Standard mm 2050 2050 2050 2250 2250
With additionally mm 2450 2450 2450 2650 2650mounted low-voltagecompartment
With cable connection mm 2550 2550 2550 2750 2750to the busbars
With de- ≥ 20 kA mm 2050 2050 2050 2530 2530flectingplates fitt- ≥ 25 kA mm 2450 2450 2450 2530 2530ed to complywith criteria1 to 6, for arc fault durationof 1s
Depth Single Connection mm 1650 1650 1650 2025 2025busbar at front,panel wall mounting 2)
Connection mm 1775 1775 1775 2150 2150at front,free-standing 2)
Connection mm 1775 1775 1775 2150 2150at rear,free-standing 2)
Duplicate Back- mm 3560 3) 3560 3) 3560 3) 4310 4310busbar to-panel back
arrangement
Useable internaldimensions of the low-voltage compartment
Rated voltage kV 7.2 12 15 1) 17.5 24
Width mm 800 800 800 1000 1000
Standard Width mm 680 680 680 1880 1880compartment Height mm 680 680 680 1680 1680
Depth mm 450 450 450 1450 1450
Additional Width mm 680 680 680 1880 1880top box Height mm 380 380 380 1380 1380
Depth mm 420 420 420 1420 1420
Useable internal heightfor high-voltage cables
Distance betweencenters of lug hole andcable brackets.
Rated voltage kV 7.2 12 15 1) 17.5 24
Width mm 800 800 800 1000 1000
Standard Connection approx. 425 425 425 1520 1520version at front mm
Connection approx. 600 600 600 1650 1650at rear mm
Standard Connection approx. 625 625 625 1720 1720version at front mmwith deeper Connection approx. 800 800 800 1850 1850bottom plate at rear mm
1) Please inquire about 17.5 kV with correspondinginsulating capacity.
2) See also section entitled “Panel connection”, page 19.
3) Depth of 3960 mm for rated short-circuit breakingcurrent of 50 kA.
33≥100
33≥50
1
4
2
5
3
6
ac
d
HA25
-249
2a e
ps
2
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�7
Installation details
Room dimensions (min. room height 2800 mm 1))(see also adjacent tables)
Single-row arrangement (plan view)for single busbar installations
Face-to-face arrangement (plan view)for single and duplicate busbar installations
Back-to-back arrangement (plan view)for duplicate busbar installations
Single-row and face-to-face arrangement
Con- Connec- Rear- Arrange- Dimensionnec- tion com- mounted menttion partment pressure a b c dposi- pressure relief ducttion relief mm mm mm mm
Rated voltage 7.2/12/15 kV
Front Downwards None Wall ≥1100 ≥1300 1650 150To rear None Wall ≥1100 ≥1300 1650 150Upwards With Wall/free ≥1100 ≥1300 1775 ≥50 4)
Rear Upwards With Free ≥1100 ≥1300 1775 ≥500
Back-to-back arrangement
Con- Connec- Rear- Arrange- Dimensionnec- tion com- mounted menttion partment pressure a cposi- pressure relief ducttion relief mm mm
Rated voltage 7.2/12/15 kV
Front Upwards With Free ≥1100 1650
Floor loading
Fixing
The switchgear can be fixed by:• Bolting to the foundation rails• Welding to the foundation rails
Foundation rail position
The position of the foundation railsis fixed by fixing points in the baseframe of the panels. Please inquirefor further details.
Single busbar or duplicate busbar Duplicate busbar panels in back-to-backpanels in face-to-face arrangement, equipped with two circuit-breakersarrangement
Weight of each single panel Weight
Rated voltage 7.2/12/15 kV
700 to 1200 kg 1400 to 2000 kg
Rated voltage 17.5/24 kV
800 to 1000 kg 1600 to 2000 kg
Rated voltage 17.5/24 kV
Front Upwards With Free ≥1400 2025
Technical Data
Rated voltage 17.5/24 kV
Front Downwards None Wall ≥1400 ≥1500 2025 150To rear None Wall ≥1400 ≥1500 2025 150Upwards With Wall/free ≥1400 ≥1500 2150 ≥50
Rear Upwards With Free ≥1400 ≥1500 2150 ≥500
1) Please inquire if rooms are low.2) Please inquire about 8BK20 systems up to 15 kV with
a rated short-circuit breaking current of 50 kA.3) A 1200 mm wide operating aisle is needed to move
the withdrawable part.
4) For switchgear with a rated short-circuit breaking current of 50 kA at 7.2/12/15 kV onlyconnection at front and with rear pressure relief duct is feasible.The rear distance from wall must be at least 500 mm. Termination walls at the sides for this distance from wall must be provided on site.
33
4 bc
d
33≥100
33≥100
≥50
33≥50
cd
HA25
-249
3a e
ps
33 33≥1003)
4 aa4
2602)
cc
≥1003)
HA25
-249
4a e
ps
2
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
8�Siemens HA 25.21 · 1999
Packing
Shipping details
Technical Data
Transport units
The following factors should betaken into account whendeciding on the size oftransport units to be employed:• Transport facilities on site• Transport dimensions and
weights• Size of building doorways
Transport dimensions andweights
Transport unit Rated voltage and width
7.2/12/15 kV 17.5/24 kV800 mm 1000 mm
Single busbar panels or single panels max. 3 panels max. 3 panelsof a duplicate busbar installation forface-to-face arrangement
Duplicate busbar panels for back-to-back max. 2 double panels max. 2 double panelsarrangement
Destination Rated Number of panels Dimensions, volumes and weightsvoltage per transport
Width Depth Height Volume Gross weightunitm m m m3 approx.kg
Connection at front, without rear-mounted pressure relief duct
7.2/12/15 kV 1 panel 1.06 1.90 2.25 14.53 17702 panels 1.90 1.90 2.25 18.12 15403 panels 2.66 1.90 2.25 11.37 2300
17.5/24 kV 1 panel 1.26 2.27 2.45 17.00 11002 panels 2.27 2.27 2.45 12.63 22003 panels 3.26 2.27 2.45 18.13 3250
Connection at front or rear, with rear-mounted pressure relief duct
7.2/12/15 kV 1 panel 1.06 2.08 2.25 14.96 17702 panels 1.90 2.08 2.25 18.90 15303 panels 2.66 2.08 2.25 12.48 2300
17.5/24 kV 1 panel 1.26 2.44 2.45 17.53 11002 panels 2.27 2.44 2.45 13.57 22003 panels 3.26 2.44 2.45 19.50 3250
Back-to-back arrangement 1)
7.2/12/15 kV 1 double panel 1.06 4.00 2.30 19.75 13902 double panels 1.90 4.00 2.30 17.48 2780
17.5/24 kV 1 double panel 1.26 4.70 2.55 15.10 20502 double panels 2.27 4.70 2.55 27.10 4100
Germany and Europe
Connection at front, without rear-mounted pressure relief duct
7.2/12/15 kV 1 panel 1.06 1.90 2.41 14.85 10502 panels 1.90 1.90 2.41 18.65 18803 panels 2.66 1.90 2.41 12.15 2730
17.5/24 kV 1 panel 1.26 2.27 2.61 17.65 14502 panels 2.27 2.27 2.61 13.44 26503 panels 3.26 2.27 2.61 19.31 3860
Connection at front or rear, with rear-mounted pressure relief duct
7.2/12/15 kV 1 panel 1.06 2.08 2.41 15.31 10802 panels 1.90 2.08 2.41 19.47 19303 panels 2.66 2.08 2.41 13.30 2770
17.5/24 kV 1 panel 1.26 2.44 2.61 18.03 15002 panels 2.27 2.44 2.61 14.44 27003 panels 3.26 2.44 2.61 20.74 3900
Back-to-back arrangement 1)
7.2/12/15 kV 1 double panel 1.06 4.00 2.46 10.43 19502 double panels 1.90 4.00 2.46 18.70 3460
17.5/24 kV 1 double panel 1.26 4.70 2.70 16.00 27502 double panels 2.27 4.70 2.70 28.81 5000
Overseas
Destination Transport by Type of packing
Germany/ Road and Panels on pallets and open packing with polyethyleneEurope rail sheets covering the panels
Overseas Ship Panels on pallets in sealed crates with upper and lowerpolyethylene sheets, welded together, with desiccant bagsand sealed wooded floor; max. storage: 6 months
1) The gross weight increases byabout 180 kg when there are 2withdrawable circuit-breakers in apanel. The depth will be increasedby 0.4 m for switchgear with ratedshort-circuit breaking current of 50 kA at 7.2/12/15 kV. The volumewill change accordingly.
3
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�9
HA25
-251
5a e
ps
M
Single busbar panels
Product Range
Withdrawable panel
1) See also page 19 for details of voltage measure-ment of the panel connection.
2) Details refer to conventional Siemens single-coresealing ends for XLPE cables or other makes withsimilar dimensions.
Voltagetransformeron busbars
Make-proofearthingswitch on busbars
Bus riser
Cableconnection at top
Spurconnection at top
Panelventilation
or
or
or
or
or
Withdrawablevacuumcircuit-breaker
Withdrawablevacuumcircuit-breaker1)
Withdrawablevacuumswitch
Disconnectorlink
or
or
or
Currenttransformer
Voltagetransformer
Make-proofearthingswitch
Cable sealing ends 2)max. 4 x 500 mm2
per phase
and/or
Barsor
and/or
and/or
Busbarfittings
Withdrawable parts
Connectionfittings
HA25
-251
6a e
ps
M
HA25
-251
7a e
ps
M
3
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
Single busbar panels
Product Range
Sectionalizer(Mirror-image arrangementalso possible)
10�Siemens HA 25.21 · 1999
Voltagetransformeron busbars
Make-proofearthingswitch onbusbars
Panelventilation
or
or
Withdrawablevacuumcircuit-breaker
Withdrawablevacuumcircuit-breaker
Withdrawablevacuumswitch
Disconnectorlink
or
or
or or
Currenttransformer
Busbarfittings
Withdrawable parts
Connectionfittings
Withdrawablepanel
Bus riser panel,type I
Currenttransformer
Meteringsection
Voltage transformer on busbars
Make-proof earthing
switch on busbars
Voltagetransformeron busbars
Make-proofearthingswitch onbusbars
Panelventilation
or
or
Withdrawablevacuumcircuit-breaker
Withdrawablevacuumcircuit-breaker
Withdrawablevacuumswitch
Disconnectorlink
1) See also page 19 fordetails of voltagemeasurement of thepanel connection.
or
or
or or or
or
or
Currenttransformer
Busbarfittings
Withdrawable parts
Connectionfittings
Withdrawablepanel
Bus riser panel,type II
Currenttransformer
Voltagetransformer
Currenttransformerand voltagetransformer
Voltagetransformerand currenttransformer
Voltagetransformeron busbars
Make-proofearthing
switchon busbars
Busbar fittings
Connectionfittings
Busbarfittings
Connectionfittings
Withdrawable part
1)
1)
HA25
-252
0a e
psHA
25-2
521a
eps
3
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�11
HA25
-251
8a e
ps
Single busbar panels
Metering panel, withdrawable type
Earthing transformer panel
Busbar connection panels
Type I
Product Range
Voltagetransformeron busbars
Make-proofearthingswitch onbusbars
Bus riser
Cableconnection at top
or
or
or
Meteringsection
Busbarfittings
Withdrawable part
Type II
Voltagetransformeron busbars
Make-proofearthingswitch onbusbars
Cable sealingends,max. 4 x 500 mm2
per phase
Barsor
and/or
or
Currenttransformer
Voltagetransformer
and/or
Meteringsection
Busbarfittings
Connectionfittings
Withdrawable part
Voltagetransformeron busbars
Make-proofearthingswitch onbusbars
Cable sealing ends,max. 12 x 500 mm2
per phase
Barsor
and/or
or
Currenttransformer
Voltagetransformer
and/or
Busbarfittings
Connectionfittings
HA25
-251
9a e
ps
3
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
12�Siemens HA 25.21 · 1999
HA25
-252
3a e
ps
SS1SS2
Duplicate busbar panels
Product Range
8BK20 duplicate busbar switchgear isassembled from therange of single busbarpanels. They can be arrangedeither:• Face-to-face or • Back-to-back
Face-to-face arrangement
• Panels from the singlebusbar product range
• The two rows are linked bycables or bars underneaththe panels
• Bus coupling, comprising– Withdrawable panel– Busbar connection panel
Back-to-back arrangement
• Panels from the singlebusbar product range
• The two rows are linked bybars inside the panels
• Bus coupling, comprising:– Withdrawable panel, but only
with current transformer anda special bus coupling andriser panel
– Fittings on the busbars as forsectionalizing a single busbarinstallation
Withdrawable panel Withdrawable panel
Withdrawable panel Withdrawable panel
SS1 = Busbar system 1SS2 = Busbar system 2
HA25
-252
4a e
ps
SS1SS2
HA25
-252
5a e
ps
8
7
6
5
1
4
3
2
4
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�13
Basic panel design
Electrical Design
Single busbar panel
Single-row arrangement1 Low-voltage compartment2 Withdrawable vacuum
circuit-breaker3 Cable connection4 Voltage transformer5 Make-proof earthing switch6 Current transformer7 Busbars8 Rear-mounted pressure
relief duct (option)
Duplicate busbar panels
Face-to-face arrangement2 to 8: See above9 Cable or busbar connection
between both panels under-neath the installation (in thecable basement)
10 Special connection bracket
Back-to-back arrangement1 to 8: See above
11 Busbars between bothpanels within the enclosures
Single-row arrangement
Face-to-face arrangement
Back-to-back arrangement
10
HA25
-253
7a e
ps
9
HA25
-253
8b e
ps
11
Withdrawable partin disconnectedposition
Withdrawable partin connectedposition
5
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
High-voltage section
Mechanical Design
Design• Bolted steel profiles and
sheets• Rails for accommodating
the withdrawable part• Base cover optionally
available• Surface treatment– Steel profiles and sheets
galvanized– Doors and front frame
powder-coated, color grey (RAL 7032)
– Switchgear side wallspowder-coated, color grey (RAL 7032)
Design• Galvanized sheet steel• With cutout for
continuous busbars• Bushing plate with cast
resin bushings fortransverse isolation ofbusbars optionallyavailable
• Degree of protectionwith respect toneighboring panels:IP4X/IP3XD
• Optionally in an arc-resistant design
Frame
Panel with pressure relief flaps
14�Siemens HA 25.21 · 1999
Partitions
Partitions isolate neigh-boring panels from oneanother
Design• Galvanized sheet steel• Locked to prevent
unintentional openingfrom the outside
• Separate pressure reliefflaps for busbar, with-drawable part andconnection compart-ments
Pressure relief
When the pressure reliefflaps are opened, theexcess pressure in thepanel in the event of an arcoccurring is dissipated.
Panel with partition removed
R-HA
25-0
96 e
psR-
HA25
-097
eps
R-HA
25-2
27a
eps
Panel with partition
Steel profiles
Rail for with-drawable part
Cutout forcontinuousbusbars
Partition
Pressurerelief flaps
5
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�15
�
HA 2
5-25
39 e
ps
High-voltage section
• Upper and lower matingcontacts fixed in cup-typebushings
• Enforced operated metalshutters for opening orclosing the cup-typebushings when movingthe withdrawable part
• Metal shutters can belocked when the with-drawable part is rackedout
• Upper barrier (access to the busbar) or lower barrier (accessto the cable) can beunscrewed independ-ently of one another
• Optional resistance tointernal arcing of thebusbar compartment
Compartmentalization
Design• Bolted galvanized steel
sheets subdivide thepanel into
– Busbar compartment– Withdrawable part
compartment– Connection compartment• Degree of protection
between the individualcompartments:IP4X/IP3XD
• Thanks to integrated cup-type bushings, completecompartmentalizationeven when thewithdrawable part is inthe connected position
R-HA
25-2
24 e
ps
Mechanical Design
• Door handle– After the lock has been
unlocked, the door isopened by lifting or isclosed by lowering(taking the interlockingconditions into account)
• CLOSED/OPEN push-button of the switchingdevice
– CLOSED/OPEN switch-ing when the withdrawa-ble part is in the connec-ted position:When the door is closed,mechanically with push-button and tiltableextension mechanism forpushbutton actuation
– CLOSED/OPEN switch-ing when the withdrawa-ble part is in the discon-nected position:When the door is closedmechanically by meansof pushbuttons (directactuation)
• Lever for tilting over theextension mechanism(see adjacent figure foroperating principle)
• Openings for with-drawable part actuation
– For the hand crank formoving the withdrawablepart (taking theinterlocking conditionsinto account)
– For the interlocking keyof the withdrawable part(same key as for thehigh-voltage door).
High-voltage door
• Inspection window (1)– Pressure-proof– For checking the
withdrawable partposition
– For reading off theCLOSED/OPEN positionindicator of the switchingdevice, of the operatingcycle counter and of the “closing springcharged” indication
• Lock (2)– For locking or unlocking
the high-voltage door(taking the interlockingconditions into account)with an interlocking key
• Hand crank opening– Hand crank for charging
the operating mechanismsprings of the switchingdevice
– Opening closes auto-matically
R-HA
25-1
12a
eps
R-HA
25-2
25 e
ps
Metal shutters opened (no operation)
Withdrawable partcompartment
High-voltage door(e.g. for panel with 3AH vacuum circuit-breaker)
Tiltable extension mechanismfor pushbutton actuation
Metal shutters closed
High-voltage door
Inspection window (1) for checking the withdrawable part position
Operating mechanism box of the switching device
Pushbutton actuation in the high-voltage door
Extension mechanism
Actuation of the pushbuttons on the switching device
Lock (2)
CLOSED/OPEN pushbuttons
Door handle
Lever for tilting over theextension mechanism
Inspection window (1) forreading off the indicators
Openings for withdrawable partactuation
Opening for hand crank
CLOSED/OPEN
5
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
16�Siemens HA 25.21 · 1999
High-voltage section
Mechanical Design
Busbars(commercially availableflat copper)
Busbar mounting• On commercially
available cast-resininsulators
• Busbars bolted,length according topanel width
Compartmentalization• Metal compartment-
alization to the with-drawable part andconnection compart-ments with degree of protectionIP4X/IP3XD
• Busbar compartmentcontinuous through-out the entire instal-lation, transversecompartmentalizationwith respect toneighboring panelspossible
• Resistance to internalarcing of the busbarcompartmentoptionally possible
Insulation• Busbar insulation not
necessary becausedielectric strength isalso guaranteed with-out insulation
• Busbar insulation upto the upper matingcontacts optionallypossible
Busbar fittings (options)The following fittings on thebusbars – shown in theadjacent figure with referenceto the example of with-drawable vacuum circuit-breaker panels – are optionallyavailable without detrimentallyinfluencing pressure relief:
4MR voltage transformer • Cast-resin insulated• Up to 3 x one-pole or
2 x two-pole
Make-proof earthing switch• Manually operated• Optionally lockable or
electromagnetically locked
Bus riser• Rated normal current in
accordance with the max.rated normal current of thebusbar
• Connecting bars mounted on3 post insulators
• Necessary bar duct can bemodified
Cable connection at top• Max. 2 x 500 mm2 single-
core XLPE cables per phase1)• With cable connection
compartment and cablebrackets
Spur panel connection at top• Max. 2 x 500 mm2 single-
core XLPE cables per phase1)• Cable connection within the
panel, with cable brackets
1) Details refer to conventionalSiemens sealing ends or othermakes with similar dimensions.
Busbarcompartment
R-HA
25-2
94 e
ps
5
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�17
High-voltage section
Panel connection
• Connection of cablesor bars to currenttransformers or postinsulators
• Connection variantsor types of instal-lation are as shownin the illustrations
• Earthing and short-circuiting via earthingswitch directly at thepoint of connection
• Fixed-mountedvoltage transformerswithin the currenttransformer protection zone
HA25
-254
7a e
ps
Mechanical Design
Panel connection fittings(options)The following optional fittingsare available for panel con-nection according to therelevant project planningdocumentation:
Connection• Connection of max.
4 x 500 mm2 single-coreXLPE cables per phase withSiemens sealing ends orother makes of similar size
• Or connections for plug-in,shock-proof sealing ends,including floor plate
• Or connection for bars:Flat copper bar withbushings, optionally withfloor plate or fully insulatedbars including floor plate
4MA post-insulator currenttransformers• Cast-resin insulated• Narrow design to DIN 42600• Max. 3 units
4MR voltage transformers• Cast-resin insulated• Max. 3 x one-pole or
2 x two-pole• Fixed-mounted, without
primary fuses• Withdrawable, optionally with
primary fuses, voltage pickoffon the circuit-breaker, auto-matic earthing of primaryterminals or isolation ofsecondary circuits duringaccess to voltage trans-formers
Make-proof earthing switch• Manually operated• Additional to standard locking
of earthing switch/with-drawable part, optionallylockable or electromagnet-ically locked
Surge arresters or limiters• Surge arresters for protecting
the switchgear againstexternal overvoltages
• Limiters for protecting theloads against switching over-voltages
• Max. 3 units
Connectioncompartment
Connection from front
Connection from rear
R-HA
25-2
95 e
psHA
25-2
548a
eps
5
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
High-voltage section
Mechanical Design
• Fitted with a vacuumcircuit-breaker featuring aspring stored-energyoperating mechanism
Withdrawable vacuumcircuit-breaker section(See page 5 for technicaldata)
• Fitted with a vacuumswitch featuring a springstored-energy operatingmechanism
• Also optionally with HVHRC fuses
Withdrawable vacuumswitch section(See page 5 for technicaldata)
• Performs a disconnectorfunction
• Fitted with copper links• Locking preferably with a
padlock
Withdrawabledisconnector-link section(See page 5 for technicaldata)
• Fitted with 4MR voltagetransformers, cast-resininsulated, Max. 3 x one-pole or 2 x two-pole
• Also optionally with 6.3 Aprimary fuses
Withdrawable meteringsection(See page 5 for technicaldata)
18�Siemens HA 25.21 · 1999
R-HA
25-2
28 e
ps
Chassis
Carriagemechanism
R-HA
25-2
29 e
ps
Chassis
Carriagemechanism
R-HA
25-2
31 e
ps
Chassis
Carriagemechanism
R-HA
25-2
32 e
ps
Chassis
Carriagemechanism
5
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�19
Low-voltage section
Mechanical Design
Low-voltage compartment
• For accommodating thedevices for protection,control, measuring andmetering, e.g. bay controllerSIPROTEC 4 type 7SJ62
• Shock-proof partitioning from the high-voltage section
• Pressure-resistantpartitioning from the high-voltage section
• Low-voltage compartmentcan be removed (onlypossible for installations upto 15 kV) thanks to plug-inring and control cables
• Door optionally withinspection window
• Additional built-on low-voltage compartmentpossible
• See page 6 for details ofuseful internal dimensions
Low-voltage cables
• Withdrawable section controlcables via 64-pole plugconnector, flexible cables in ametal conduit
• Control cables of the panelare flexible and have metalliccovers
• Connection from with-drawable part and panelwiring to the low-voltagecompartment by means of10-pole module connectors
• Ring cables with plug-inconnections between panelsfor installations up to 15 kV
Solid-state HMI(human-machine interface)
Bay controller SIPROTEC 4type 7SJ62 for control andprotection
Features1 LCD for process and
equipment data, e.g. for: – Measuring and metering
values– Binary data for status of
switchpanel and device– Protection data– General signals– Alarm2 Keys for navigation in menus
and for entering values3 Seven programmable LEDs
with possible application-related inscriptions, for indi-cating any desired processand equipment data
4 Four programmable functionkeys for frequently per-formed actions
Door of the low-voltagecompartment
Bay controller SIPROTEC 4 type 7SJ62
Low-voltage compartment with fittings (example)
R-HA
25-0
98a
eps
R-HA
25-2
91ep
sR-
HA25
-292
eps
3
4
2
1
6
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
20�Siemens HA 25.21 · 1999
Standards
Standards, specifications, guidelines
Standards
Type 8BK20 switchgear forindoor installation complieswith the following validstandards:
In accordance with theharmonization agreementreached by the countries of theEuropean Community, theirnational standards conform toIEC 60 298.
Service locations
Type 8BK20 switchgear can beused as indoor installation inaccordance with VDE 0101• Outside lockable electrical
service locations at placeswhich are not accessible tothe public. Enclosures ofswitchgear can only beremoved with tools.
• Inside lockable electricalservice locations. A lockableelectrical service location is aplace outdoors or indoorsthat is reserved exclusivelyfor housing electrical equip-ment and which is keptunder lock and key. Access isrestricted to authorized per-sonnel and persons whohave been properlyinstructed in electricalengineering. Untrained orunskilled persons may onlyenter under the supervisionof authorized personnel orproperly instructed persons.
Definition
“Make-proof earthingswitches” are earthingswitches that have a short-circuit making capacity (VDE 0670 Part 2).
Insulating capacity
• The insulating capacity isverified by testing the switch-gear with rated values ofshort-time power-frequencywithstand voltage andimpulse withstand voltageaccording to VDE 0670 Part1000 or IEC 60 694 (seeadjacent table):
• Rated values are referred tosea level and to normalatmospheric conditions (1013 h Pa, 20 °C, 11 g/m3
humidity in accordance withVDE 0111 and IEC 60 071).
• The insulating capacitydecreases with increasingaltitude, but is not taken intoaccount by the standards andspecifications up to a sitealtitude of 1000 m.
Rated Rated short-time power- Rated lightning impulsevoltage frequency withstand voltage withstand voltage(rms) (rms) (peak)
For Between For Betweenisolating phases and isolating phases anddistances to earth distances to earth
kV kV kV kV kVIEC VDEStandard Standard
17.2 23 20 170 160
12,0 32 28 185 175
15,0 39 36 105 195
17.5 45 38 110 195
24,0 60 50 145 125
IEC 60 694 VDE 0670 Part 1000
IEC 60 298 VDE 0670 Part 6
IEC 60 298 VDE 0670 Part 6,Appendix AA Appendix AA
IEC 60 129 VDE 0670 Part 2
IEC 60 265-1 VDE 0670 Part 301
IEC 60 420 VDE 0670 Part 303
IEC 60 056 VDE 0670 Parts 101 to 107
IEC 61243-5 E VDE 0682 Part 415and EN 61243-5 (E)
IEC 60 529 VDE 0470 Part 1
IEC 60 071 VDE 0111
Resistance to internal arcfaults
• Tests for verifying resistanceto internal arc faults shouldestablish proper protectionfor operating personnel.
• Tests for resistance tointernal arc faults can beagreed between the ownerand manufacturer inaccordance with VDE 0670Part 6 or IEC 60 298.
• The tests must be performedin accordance with VDE 0670Part 6, Appendix AA or IEC60 298, Appendix AA.
• Type 8BK20 switchgearconforms to the criteria ofthe above standards andspecifications
– Criteria 1 to 3 and 6 in thestandard version
– Criteria 1 to 6 with additionalmeasures
For site altitudes above 1000 m,the adjacent correction factor ais recommended, depending on the actual site altitude abovesea level.
• Definitions of criteria:– Criterion 1
Correctly secured doors,covers etc. do not open.
– Criterion 2Parts which may cause ahazard do not fly off.
– Criterion 3No holes in the freelyaccessible external parts ofthe enclosure as the result ofburning in or tearing open.
– Criterion 4Vertically arranged indicatorsdo not ignite.
– Criterion 5Horizontally arrangedindicators do not ignite.
– Criterion 6The effectiveness of theearth connection must not bedetrimentally influenced.
• Resistance to internal arcfaults can be provided overand above the requirementsof the standards and specifi-cations mentioned before.
Rated short-time power-frequencywithstand voltage to be selected
Rated short-time power-frequency withstand voltage (VDE 0670 Part 1000/IEC 60 694)
1.1 · a≥
Rated lightning impulse withstandvoltage to be selected
Rated lightning impulse withstand voltage (VDE 0670 Part 1000/IEC 60 694)
1.1 · a
Site altitude above sea level 3000 mRated voltage of switchgear 12 kVRated lightning impulse withstand voltage (VDE 0670 Part 1000/IEC 60 694) 75 kV
Rated lightning impulse withstand voltage to select = 75 kV = 93 kV1.1 · 0.73
Result:According to the above table, 17.5 kV switchgear should be selected.
Example
≥
500040003000200010000 m
0.9
0.8
0.7
0.6
0.1
0
1
HA25
-250
3 ep
s
Cor
rect
ion
fact
or a
Site altitude above sea level
6
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�21
Standards
Conditions in switchgear rooms
Room climate 1) Ambient Relative Condensation Special ambient Additionalaffecting the temperature humidity conditions measuresswitchgear needed
Climate class I1 + 15 to 5 to None None –+ 40 °C 85%
Climate class I2 – 25 to 10 to Occasionally None Yes+ 55 °C 100% once a month Blown sand, dust, small animals Yesfor 2 hours
Climate class I3 – 25 to 10 to Frequently None Yes+ 70 °C 100% once a day Blown sand, dust, small animals Yesfor 2 hours
Dripping water due to ceiling Yescondensation (not harmful) to VDE 0470 Part 1 or IEC 60 529
Areas subject Sulfur dioxide (SO2) ≥ 2 ppm Yesto chemical Hydrogen sulfide (H2S) ≥ 1 ppm Yespollution Hydrochloric acid (HCl) ≥ 3 ppm Yes
Ammonia (NH3) ≥ 15 ppm YesNitric oxides (NO2) ≥ 2 ppm YesChloride deposit (Cl–) (saline fog) ≥ 2 mg/dm2 Yes
Standards, specifications, guidelines
Current-carrying capacity
• According to VDE 0670 Part 6or Part 1000, IEC 60 298 orIEC 60 694, current-carryingcapacities are referred to thefollowing ambienttemperatures:
– Maximum of 24-hour mean + 35 °C
– Maximum + 40 °C• The current-carrying capacity
of the panels and busbarsdepends on the ambienttemperature outside theenclosure.
• In the enclosed panels, thecurrent-carrying capacity canbe partly reduced by therestricted ventilation. It canbe increased by:
– Using a circuit-breaker with ahigher rated current
– Through-ventilation, i.e. prod-proof ventilation slits in thehigh-voltage door and in thetop cover plate
– Forced ventilation, i.e. prod-proof ventilation slits in thehigh-voltage door in conjunc-tion with a fan on the topcover plate
Climate and ambientconditions
Type 8BK20 switchgear, ifnecessary with additionalmeasures, can be used in thefollowing climate classes andunder the following ambientconditions:• Ambient conditions– Natural pollutants– Chemically active pollutants– Small animals• Climate classes I1, I2, I3
The climate classes arebased on IEC 60 721-3-3 andIEC 60 721-3-4 and aredefined as follows:
Withdrawable sectionpositions
There are three differentpositions for the withdrawablesections of type 8BK20switchgear as defined in VDE 0670 Part 6 or IEC 60 298:• Service position– In this position, the switching
device establishes a con-nection between the busbarsand the panel connection.
– The low-voltage connector isplugged in.
• Disconnected position– In this position, segregation
is ensured, i.e. arcingpossible only against earth.
– The low-voltage connectorcan be either plugged in ordisconnected.
• Test position– The low-voltage connector is
plugged in.
– Climate class I1Rooms in buildings with goodthermal insulation or highthermal capacity, heated orcooled: normally only thetemperature is monitored,e.g. in normal living rooms,offices, shops, tele-communications exchanges,storage rooms for sensitiveproducts.
– Climate class I2Rooms in buildings with poorthermal insulation or lowthermal capacity, heated orcooled, without temperaturemonitoring; heating orcooling subject to failure overseveral days, e.g. unattendedrelays, booster or trans-former stations, stables,motor vehicle repair shops,manufacturing rooms forunfinished products, hangars.
– Climate class I3Rooms in buildings withoutsignificant thermal insulationand with low thermalcapacity, neither heated norcooled, e.g. telephonebooths, entrances of build-ings, barns, lofts, unheatedstore rooms, sheds, garages.
1) Based on IEC 60 721-3-3 and IEC 60 721-3-4.
Interlocks
• The following interlocks arespecified by VDE 0670 Part 6and IEC 60 298:
– The withdrawal or engage-ment of a circuit-breaker,switch or contactor shall beimpossible unless it is in theopen position.
– The operation of a circuit-breaker, switch or contactorshall be impossible unless itis in the service, disconnect-ed, removed, test or earthingcondition.
– It shall be impossible to closethe circuit-breaker, switch orcontactor in the serviceposition unless it isconnected to the auxiliarycircuit, unless it is designedto open automatically withoutthe use of an auxiliary circuit.
– The provision of additional or alternative interlocks shallbe subject to agreement between the manufacturerand user.
– The manufacturer shall giveall necessary information onthe character and function ofinterlocks.
– It is recommended thatearthing switches having ashort-circuit making capacityless than the rated peakwithstand current of thecircuit should be interlockedwith the associated dis-connectors.
– Apparatus installed in maincircuits, the incorrect positionof which can cause damageor which are used for assur-ing isolating distances duringmaintenance work, shall beprovided with locking facil-ities (for example, provisionfor padlocks).
– Wherever possible, pref-erence should be given tomechanical interlocks.
• Type 8BK20 switchgearfulfils other interlockingconditions over and abovethose mentioned here; see page 4.
Protection against water,electric shock and ingress ofsolid foreign bodies
As detailed in – VDE 0470 Part 1– IEC 60 298 and 60 529– VDE 0670 Part 6type 8BK20 switchgear con-forms to the following degreesof protection:• For panels without ventilation
slits:
Standard Degree of protection Type of protection
� �
6
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
22�Siemens HA 25.21 · 1999
Standards, specifications, guidelines
Standards
�� �
VDE 0670 I P 4 XPart 6 and IEC 60 298
Shock-hazard protectionProtected against approach to live parts and contact with moving parts by wires or strips of thickness greater than 1 mm.
Protection against waterNo specification.
VDE 0470 I P 3 X DPart 1 andIEC 60 529
Foreign-body protectionProtection against ingress of solid foreign bodies,diameter ≥ 2.5 mm.
Protection against waterNo specification.
Shock-hazard protectionProtected against access to hazardous parts with awire (test probe with a diameter of 1 mm, length 100 mm, must have an adequate clearance from hazardous parts).
�� �I P 3 1 D
Foreign-body protectionProtected against ingress of solid foreign bodies,diameter ≥ 2.5 mm.
Protection against waterProtected against ingress of vertically dripping water.
Shock-hazard protectionProtected against access to hazardous parts with awire (test probe with a diameter of 1 mm, length 100 mm, must have an adequate clearance from hazardous parts).
��I P 5 0
Foreign-body protectionProtected against ingress of solid foreign bodies,dust-protected.
Shock-hazard protectionProtected against access to hazardous parts with awire (test probe with a diameter of 1 mm, length 100 mm, must have an adequate clearance from hazardous parts).
Protection against waterNot protected.
��I P 5 1
Foreign-body protectionProtected against ingress of solid foreign bodies,dust-protected.
Shock-hazard protectionProtected against access to hazardous parts with awire (test probe with a diameter of 1 mm, length 100 mm, must have an adequate clearance from hazardous parts).
Protection against waterProtected against ingress of vertically dripping water.
Degree of protection
Standard Op-tional
Enclosure IP4X/ IP31D,IP3XD IP50,
IP51
Compart- IP4X/ –mentalization IP3XD
Degree of protection
Standard Op-tional
Enclosure IP4X/ IP31DIP3XD
Compart- IP4X/ –mentalization IP3XD
• For panels with prod-proofventilation slits:
Refer to the adjacent table forexplanations
A
Type 8BK20 Switchgear up to 24 kV
with WithdrawableCircuit-Breakers
Siemens HA 25.21 · 1999�23
Title Designation Order No.
High-Voltage Equipment (Above 52 kV)
Overvoltage Protection HG 21 E50001-K1521-A101-A1-7600Surge Counting Devices for Surge Arresters HG 21.4 E50001-K1521-A401-A1-7600
Medium-Voltage Equipment (High-Voltage Equipment up to 52 kV)
3AH Vacuum Circuit-Breakers HG 11.11 E50001-K1511-A111-A3-7600Components up to 24 kV for 3AH Vacuum Circuit-Breakers HG 11.15 E50001-K1511-A151-A1-76003TL Vacuum Contactors HG 11.21 E50001-K1511-A211-A1-7600Disconnectors and Earthing Switches HG 11.31 E50001-K1511-A311-A1-7600NXACT Vacuum Circuit-Breaker Module HG 11.51 E50001-K1511-A511-A1-7600Vacuum Switches, Switch-Disconnectors, HV HRC Fuse HG 12 E50001-K1512-A101-A4-7600Switchgear Interlock Units, Control Valves,Compressed Air Systems HG 13 E86010-K1513-A101-A1-7600Overvoltage Protection HG 21 E50001-K1521-A101-A1-76003EH2 Surge Arresters HG 21.2.5 E50001-K1521-A251-A3-76003EE2 Special-Purpose Surge Arresters for the Protectionof Motors, Generators and Furnace Transformers HG 21.2.7 E50001-K1521-A271-A3-7600Insulators of Cast Resin (Excerpt) HG 22 E50001-K1522-A111-A1-7600Current and Voltage Transformers HG 24 E50001-K1524-A101-A2-7600Air-Cored Reactors, High-Voltage Capacitors HG 25 E86010-K1525-A101-A4-7600
Medium-Voltage Switchgear (High-Voltage Indoor Distribution Switchgear)
Metal-Enclosed Truck-Type Switchboardsfor Indoor Installation 8BC1, 8BD1 HA 21 E86010-K1421-A101-A3-7600Type 8BK20 Switchgear up to 24 kVwith Withdrawable Circuit-Breakers (Metal-Clad) HA 25.21 E50001-K1425-A311-A6-7600Type 8BK40 Switchgear up to 17.5 kV/63 kA with Withdrawable Circuit-Breakers HA 25.31 E50001-K1425-A411-A2-7600Generator Circuit-Breaker Units up to 17.5 kV/80 kA, Type 8BK41 HA 25.41 E50001-K1425-A511-A1-7600Type 8BJ50 Switchgear up to 24 kV with Withdrawable Circuit-Breakers* HA 25.61 E50001-K1425-A711-A2-7600 NXAIR Withdrawable Circuit-Breaker Module Switchgear up to 12 kV, Air-Insulated HA 25.71 E50001-K1425-A811-A1-760036/38 kV Switchgearwith Withdrawable Vacuum Circuit-Breakers, HA 26.1 Siemens Den Haag, Type 8BK20 Dept.CMS DMSType 8BK30 Switchgear up to 12 kVwith Draw-Out Vacuum Contactors HA 27.11 E50001-K1427-A111-A2-7600Panels up to 36 kV with Fixed-Mounted Circuit-Breakers,SF6 -Insulated, Types 8DA10 and 8DB10Single-Pole, Metal-Enclosed, Metal-CladSingle-Busbar SwitchgearDuplicate-Busbar Switchgear HA 35.11 E50001-K1535-A101-A6-7600Type 8DC11 Panels up to 24 kV, Fixed-Mounted Vacuum Circuit-Breaker Switchgear, SF6-Insulated HA 35.41 E50001-K1435-A401-A3-7600NXPLUS Fixed-Mounted Circuit-Breaker Switchgear up to 36 kV, SF6-Insulated HA 35.51 E50001-K1435-A511-A1-7600Spline-Shaft Drive 8UG for Torque Transmission up to 200 Nm HA 39.1 E86010-K1439-A111-A2-7600Motor Drive 8UH for Torque Requirements up to 250 Nm HA 39.3 E86010-K1439-A131-A1-7600Fixed-Mounted Ring-Main Units up to 24 kV, SF6-Insulated,Type 8DH10 HA 41.11 E50001-K1441-A101-A2-7600 Fixed-Mounted Ring-Main Units up to 24 kV, SF6-Insulated,Type 8DJ10 HA 45.11 E50001-K1445-A111-A6-7600Secondary Distribution Switchgear up to 24 kV, SF6-Insulated,Type 8DJ20 HA 45.31 E50001-K1445-A311-A1-7600Type 8FB1 Compact Transformer Substations up to 24 kV HA 51.1 E50001-K1451-A111-A2-7600Factory-Built Container Stations, Type 8FF1 HA 52.1 E50001-K1452-A111-A1-7600
Catalog Index of the Power Transmission and Distribution Group (Medium-Voltage Division)
High-Voltage and Medium-VoltageEquipment
Medium-VoltageSwitchgear
Catalog IndexPlease contact your Siemens Representative
A
Type 8BK20 Switchgear up to 24 kV with Withdrawable Circuit-Breakers
24�Siemens HA 25.21 · 1999
Appendix
Conditions of Sale and Delivery
Subject to the General Conditions of Supplyand Deliveryfor Products and Services of the Electrical and Electronic Industry and to any other conditions agreed upon withthe recipients of catalogs.
We reserve the right to adjustthe prices and shall charge theprices applying on the date ofdelivery.
A En 1.91a
�The technical data, dimensionsand weights are subject tochange unless otherwise stated on the individual pagesof this catalog.
The illustrations are for reference only.
Export Regulations Trademarks
In accordance with present provisions of the German Export List and the US Commercial Control List, export licences are not required for the products listed in this catalog.
Responsible for
Technical contents:Dieter Jahn,Siemens AG, Dept. EV MS1 VM,Erlangen
General editing:Gabriele Pollok,Siemens AG, Dept. EV BK T,Erlangen
An export licence may however be required due tocountry-specific application andfinal destination of the products.
Relevant are the export criteriastated in the delivery note andthe invoice subject to a possibleexport and reexport licence.
Subject to change without notice.
All product designations usedare trademarks or productnames of Siemens AG or ofother suppliers.
Dimensions
All dimensions in this catalogare given in mm.
This edition corresponds to the 1998 German edition.Printed in GermanyKGK 1.99 16. 24 En 100857 6101/U827