Turbine Part 7

download Turbine Part 7

of 19

Transcript of Turbine Part 7

  • 8/12/2019 Turbine Part 7

    1/19

    Lecture 7

    1

    Excitation System, Auxiliariesand Protections

  • 8/12/2019 Turbine Part 7

    2/19

    Generator Excitation

    The purpose of the generator excitation system is:

    To supply rotor field current to the main generator

    To control generator output voltage

    The excitation may be from a separate DC exciter or through self-excitation

    The present trend is the use of separate DC exciter (static excitator) instead of self-excitation

    2

  • 8/12/2019 Turbine Part 7

    3/19

    Generator Excitation

    Following is the principle deployed for self-excitation:

    Rotating shunt wound DC generator provides DC excitation

    DC generator is coupled to the main generator and is driven by the main TG shaft

    through a reduction gear, to reduce sparking at the commutator brushes

    For startup, voltage is built up by residual magnetism and self-excitation

    Main generator field current is controlled by field rheostat of the exciter

    3

  • 8/12/2019 Turbine Part 7

    4/19

    Generator Excitation

    The following is a description of a static excitation system of a typical NPP:

    The excitation transformer is supplied from the Class IV supply

    The voltage is reduced and supplied to the Silicon Controlled Rectifier (SCR)

    SCR converts the AC voltage to DC

    The output of the SCR is varied by the action of the Automatic Voltage Regulator

    (AVR)

    The DC voltage is then applied to the generator slip rings when the main field

    breaker is closed

    The generator output voltage varies as per the field voltage

    The comparator compares this output voltage, sensed through PT, with the voltage

    as set by the control room operator

    Any change as sensed by the AVR is used to adjust the main field current to

    eliminate the difference in the generator output voltage with

    set value 4

  • 8/12/2019 Turbine Part 7

    5/19

    Simplified Version of Static

    Excitater of a Typical NPP

    5

  • 8/12/2019 Turbine Part 7

    6/19

    Generator Neutral Grounding

    The purpose of the neutral grounding transformer is threefold:

    To limit generator winding stresses to maximum design levels by limiting fault

    currents

    To raise neutral above the ground potential to provide sensitivity to the protective

    relaying

    To block capacitive voltage transients from any relaying operation

    6

  • 8/12/2019 Turbine Part 7

    7/19

    Generator Auxiliaries

    The generator auxiliaries consist of:

    The generator stator water cooling system

    The generator hydrogen seal oil system

    The generator hydrogen cooling systems

    7

  • 8/12/2019 Turbine Part 7

    8/19

    Generator Auxiliaries

    Stator Water Cooling System (For Illustration from a Typical NPP)

    2 x 100% pumps for circulation of water

    Power: 415 V, Class IV, 22 kW

    Flow: 60 m3/hr discharge pr 6.6 kg/cm2

    Standby pump starts when either

    i. Running pump trips or

    ii. Discharge header pr < 5.5 kg/cm2

    2 x 100% shell tube type HXsCooling NAPW

    Water temperature at HX outlet is around 40C

    Expansion tank is pressurized with nitrogen, at 0.1 to 0.15 kg/cm2

    Low flow alarm at 38 m3/hr, TG trip at 25 m3/hr

    Low or high conductivity alarm for operator action

    8

  • 8/12/2019 Turbine Part 7

    9/19

    Simplified Diagram of a Typical

    Stator Water Cooling System

    9

  • 8/12/2019 Turbine Part 7

    10/19

    Seal Oil System

    Hydrogen Seals

    Required to prevent the escape of hydrogen from generator casing at the two ends

    of the rotor shaft

    Shafts seals are fitted at each end with compatible seal oil system

    Oil flow also cools and lubricates the seal surfaces

    Shafts seal of radial ring type uses seal ring that is babbitted on shaft journal side

    Oil is used to seal the gap between the seal and shaft journal

    The seal oil is supplied to the sealing gap from the seal body via radial holes and

    groove

    The seal rings are free and remain in floating condition

    10

  • 8/12/2019 Turbine Part 7

    11/19

    Seal Oil System

    Hydrogen Seals (contd)

    The oil pressure in the annular gap is maintained slightly higher than the hydrogen

    gas pressure to prevent hydrogen escape from the generator casing

    The seal oil from the sealing gap drains out from both the side of seal ring

    Seal body collects the drains from both the side in two separate drain chambers

    and they are led by two separate drain lines to seal the oil system

    The oil is supplied by a closed loop system called seal oil system

    At least one seal oil pump must be fed by Class II because seal oil supply is

    required at every instance, irrespective of shaft rotation

    Hydrogen purity must be >96% to avoid an explosive hydrogen/air mixture

    11

  • 8/12/2019 Turbine Part 7

    12/19

    Use of CO2for Purging

    When changing the casing atmosphere from air to hydrogen or hydrogen to air, it

    is necessary to have a CO2interface

    Carbon dioxide is supplied for purging the casing whenever the generator is filled

    or emptied of hydrogen

    The use of this inert intermediary gas for scavenging prevents the formation of an

    explosive mixture of hydrogen and air within the casing

    Intermixing is prevented by the difference in the densities of the gases

    12

  • 8/12/2019 Turbine Part 7

    13/19

    Gen Hydrogen Cooling System

    It removes the heat accumulated by cooling hydrogen for maintaining the

    generator rotor and stator iron within its temperature limits

    The raw service water hydrogen coolers are within this circuit

    Generator casing hydrogen pressure: 4.0 kg/cm2

    2 x 100% refrigerant type dryer units

    Hydrogen dryers location is the turbine building

    Additional 10 m3capacity carbon dioxide tank provided to store CO2at lower

    pressure

    Provision to purge the hydrogen from the control room

    13

  • 8/12/2019 Turbine Part 7

    14/19

    Turbogenerator Protections on

    Electrical FaultsTo safeguard the generator and turbine, the following classes of trips are initiated on

    detection of certain abnormal conditions

    1. Class A trip

    Tripping of generator breaker and simultaneous trip signal to turbine main trip

    solenoid for tripping of turbine due to electrical fault in the generator/grid

    system

    2. Class B trip

    Tripping of turbine and generator breaker trips on low forward power relay

    due to the fault in mechanical parameters of TG and its auxiliary systems

    3. Class C trip

    The generator is isolated from the grid due to the grid low frequency, etc., andruns on station load

    14

  • 8/12/2019 Turbine Part 7

    15/19

    Types of Protections

    1. Differential protection (Differential-87)

    This is a high speed protection against internal phase and phase to ground

    faults of stator windings

    2. Stator ground (64)

    Following ground fault in the stator winding, an unbalanced voltage is sensed

    by the overvoltage relay

    Also, due to internal and phase to ground fault occurs excessive current flow

    in the neutral circuit causing a voltage drop across the loading resistor in the

    secondary of the neutral grounding transformer

    This is monitored by another overvoltage relay

    Nominal time delay of one second are included to prevent spurious trips

    15

  • 8/12/2019 Turbine Part 7

    16/19

    Types of Protections

    3. Underfrequency protection

    The generators are specified to be capable of continuous operation with

    underfrequency up to say 5% or as specified by the manufacturer

    A two stage underfrequency relay operates and trips all line breakers if

    underfrequency limit is about to be crossed with appropriate delays (say 2

    minutes or 0.1 second when very near the limit)

    4. Loss of excitation protection (40)

    This relay operates after a delay of 0.5 seconds, when reactive power flows

    towards the generator beyond the underexcited limit

    5. Phase unbalance protection (46)

    The current in each phase is measured by CTs Based on these inputs, a relay is used to determine whether there is an

    unbalance in the phase currents or phase/to ground faults

    16

  • 8/12/2019 Turbine Part 7

    17/19

    Types of Protections

    6. Out-of-step (78)

    Out-of-step protection is designed to prevent generator instability that could

    lead to pole slipping and turbine overspeed

    It provides some degree of loss of excitation protection as well as protection

    against system related transients that could cause the generator to go out of

    synchronism with the grid

    The out-of-step protection monitors phase currents at the generator neutral

    and phase voltages at the output. These are input relays, both of which must

    be picked up to activate the trip.

    17

  • 8/12/2019 Turbine Part 7

    18/19

    Types of Protections

    7. Overexcitation protection (59R, 64F)

    The overexcitation protection is intended to protect the generator from

    damage due to overfluxing

    The protection is available during startups and shutdowns as well as normal

    operation

    The V/Hz ratio (i.e., generator terminal volts/frequency) is sensed as it is

    proportional to the flux density in the iron circuits of the machines

    Under overfluxed conditions, the core losses (and hence temperature rise)

    becomes excessive, leading to damage and in the extreme case, structural

    steel components of the generator

    The main transformer and service transformers are also covered for theseprotections

    18

  • 8/12/2019 Turbine Part 7

    19/19

    Types of Protections

    8. Low forward power relay (32A & 32B)

    This relay trips the generator breaker when power flowing to the grid reduces

    to 1% FP, e.g., due to reactor trip

    9. Supplementary start

    During startups and shutdowns, the supplementary start protection provides

    two of the more basic protectionsstator ground and phase unbalanceat

    frequencies other than 50 Hz, when all other protection may not be effective

    19