TS110 Self-Powered Controller Operations Guide Rev. 5

download TS110 Self-Powered Controller Operations Guide Rev. 5

of 77

Transcript of TS110 Self-Powered Controller Operations Guide Rev. 5

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    1/77

    Houston, Texas

    TS110 Self-Powered Controller

    October 2009

    TS110 Operations Guide

    Revision 5Document No. 4912-0003A

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    2/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    3/77

    iii

    October 2009 Rev. 5

    Copyright

    Information in this document is subject to change without notice. Companies, names and data used in

    examples herein are fictitious unless otherwise noted. No part of this document may be reproduced ortransmitted in any form or by any means, electronic or mechanical, for any purpose, without the

    express written permission of Tri-Sen Systems Corporation.

    20082009 by Tri-Sen Systems Corporation. All rights reserved.

    Microsoft, Windows, and Windows NT are registered trademarks of Microsoft Corporation.

    Modbus is a registered trademark of Modicon Corporation, a division of Schneider.

    All other brands or product names may be trademarks or registered trademarks of their respective

    owners.

    Printed in the United States of America.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    4/77

    iv TS110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Revision History

    Rev. 0 September 1991 Initial Issue.

    Rev. A November 1991 General technical revisions.

    Rev. B December 1991 General technical revisions.

    Rev. C January 1992 Technical changes to sections 5 and 6 only.

    Rev. D January 1992 Technical changes to section 6; added min/max output

    paragraph.

    Rev. E March 1993 Revised Figures 7-1, 7-2, 7-3, and 7-4 for CSA approval.

    Rev. F July 1993 Revised the following pages:

    i, iv, ix, x, xi, xiii, xiv, 1-1, 2-1, 2-5, 3-1, 3-7, 3-9, 3-10, 5-1, 5-2,

    5-8, 5-9, 5-10, 6-7, 7-3, 7-4, 7-5, 7-6, 7-7, 7-13, 7-14, 7-15, 8-2,

    8-3, and 8-4.

    Drawing 91-1026 was revised and

    Drawing 92-2163 was added to Section 7.

    Rev. 1 July 1998 General editorial revision including format for A4.

    Rev. 2 June 1999 Changes to Figures 5, 6 and 15; and to last paragraph of

    Chapter 5.

    Rev. 3 Oct 2003 Add calibration procedure for DT9. Update address/legal name.

    Update certifications.

    Rev. 4 Dec 2008 Made revisions for Tri-Sen acquiring the product; including

    company name and logo, address, and contact information.

    Rev. 5 Oct 2009 Added Factory Mutual (FM) certification of the TS110.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    5/77

    v

    October 2009 Rev. 5

    Warnings!

    READ THIS ENTIRE MANUAL AND ALL RELATED PUBLICATIONS PERTAINING TO

    THE WORK TO BE PERFORMED BEFORE INSTALLING, OPERATING, OR

    SERVICING THIS EQUIPMENT.

    Practice all plant and safety codes and standards. Failure to follow instructions can resultin personal injury and/or property damage.

    To prevent ignition of hazardous atmosphere, do not remove covers of Class I Division I(explosion-proof) units with power applied.

    All servicing should be performed by qualified technicians. Dangerous voltages may be presenton the circuit boards.

    Use extreme caution when working around power-input cables. These cables may havepotentially lethal voltages on them.

    Be very careful when working on the digital (or discrete) input/output field termination panels.The external devices being controlled can have high, potentially lethal voltages on them. Turn offthe power to the external devices before disconnecting or connecting the cable or a wire between

    the digital (or discrete) input/output field termination panels and the field wiring.

    Replace fuses only with specified parts for continued safe operation.

    Equip the engine, turbine, or other type of prime mover with an overspeed (overtemperature oroverpressure, where applicable) shutdown device that operates totally independently of the prime

    mover control device. This protects against run-away or damage to the engine, turbine, or other

    prime mover, or personal injury or loss of life, should the mechanical-hydraulic or electronic

    governor, actuator, fuel control, driving mechanism, linkage, or controlled device fail.

    Make sure the charging device is turned off before disconnecting the battery from the system toprevent damage to a control system that uses an alternator or battery-charging device.

    Prior to energizing the equipment, have qualified personnel verify all wiring and connectionsagainst vendor drawings. Incorrect wiring and/or connections can result in equipment damage.

    Contact appropriate manufacturer for instructions on operation of engine, turbine, or driven unit.This manual does not contain this information.

    If you have questions or need more information on installing and operating Tri-Sen equipment,

    contact Tri-Sen.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    6/77

    vi TS110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Disclaimer

    Because of the variety of uses for this equipment, the user of and those responsible for applying this

    equipment must satisfy themselves as to the acceptability of each application and the use of the

    equipment.

    The illustrations in this manual are intended solely to illustrate the text of this manual. Because of the

    many variables and requirements associated with any particular installation, Tri-Sen cannot assume

    responsibility or liability for actual use based upon the illustrative uses and applications.

    In no event will Tri-Sen be responsible or liable for indirect or consequential damages resulting from

    the use or application of this equipment.

    TRI-SEN DISCLAIMS ANY IMPLIED WARRANTY OR FITNESS FOR A PARTICULAR

    PURPOSE.

    No patent or copyright liability is assumed by Tri-Sen with respect to use of information, circuits,

    equipment, or software described in this text.

    Reproduction of the content of this manual in whole or part, without written permission from Tri-

    Sen, is prohibited.

    Warranty

    All Tri-Sen products are warranted to be free of defects in materials and workmanship for a period of

    twelve months from the date of shipment. In case of failure, Tri-Sen liability shall be limited to

    furnishing, but not installing, necessary repair parts; or at the option of Tri-Sen, to repairing the

    defective product at its manufacturing location, providing the equipment is returned at purchasers

    expense.

    This warranty does not apply to equipment showing abuse or damage or to equipment which has

    been altered or repaired by others, except as authorized by Tri-Sen. Nor does it extend to products

    that have been subjected to a corrosive and/or abnormal atmosphere, or to product components (such

    as batteries, lamps, etc.) which have provided a normal service life.

    Tri-Sen will determine if warranty applies when material is received at its manufacturing location. A

    purchase order and a Returned Merchandise Authorization (RMA) must accompany all returned

    material. The purchase order number as well as the RMA number should be clearly marked on the

    outside of the shipping container. Tri-Sen Customer Service Department issues RMA numbers.

    In no event will responsibility be assumed or implied for consequential damages arising from

    interrupted operation or any other causes.

    This warranty is in lieu of all other warranties expressed or implied, and no one is authorized to

    assume any liability on behalf of Tri-Sen, or to impose any liability on behalf of Tri-Sen, or to

    impose any obligation on it in connection with the sale of any equipment other than as stated above.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    7/77

    vii

    October 2009 Rev. 5

    Electrostatic Discharge Awareness

    Electrostatic discharge can damage or destroy electronic components, assemblies, or systems.

    1. Keep the following materials away from components and work area:

    Styrofoam (polystyrene): cups, packing material cellophane: cigarette packages or candy wrappers

    vinyl: books or folders

    plastic: cups, bottles, ash trays

    2. Avoid synthetic clothing. Instead, wear cotton or cotton-blend materials. Keep components away

    from elastics, clothing, and hair.

    3. Beforehandling electronic components, discharge static electricity buildup from your body by

    using a properly connected wrist strap.

    4. Do not handle components in the field unless properly grounded via wrist strap. If you are not

    properly grounded:

    Do notpick up components. Do nottouch the printed circuit board.

    Do notremove components from the chassis.

    5. Transport all static-sensitive components only in static-shielding carriers or packages. Place

    static awareness labels on all components to prevent removal from static-shielding container

    during transit.

    6. Handle all static-sensitive components at a static-safe work area including floor mat, wrist strap,

    air ionizer, ground cord, and conductive table mat.

    7. Wear a grounded wrist strap in the field whenever possible. Where wrist straps are impractical,

    wear grounded heel straps or special footwear on properly grounded dissipative flooring.

    8. Do notsubject components to sliding movements over any surface at any time.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    8/77

    viii TS110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Tri-Sen Office

    Tri-Sen Systems Corporation17625 El Camino Real

    Houston, Texas 77058Phone: +1-281-286-9700

    Fax: +1-281-286-9704

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    9/77

    Contents ix

    October 2009 Rev. 5

    Contents

    COPYRIGHT ................................................................................................................................... IIIREVISION HISTORY ..................................................................................................................... IVWARNINGS! .................................................................................................................................... VDISCLAIMER .................................................................................................................................. VI

    WARRANTY ................................................................................................................................... VIELECTROSTATIC DISCHARGE AWARENESS ........................................................................ VII

    Tri-Sen Office ........................................................................................................ viii Contents .................................................................................................................. ix

    ILLUSTRATIONS ........................................................................................................................... XIChapter 1 - Introduction .......................................................................................... 1

    1.1 ABOUT THIS MANUAL ......................................................................................................... 11.2 DOCUMENTATION CONVENTIONS ................................................................................... 21.3 USER EXPERIENCE PREREQUISITES ................................................................................ 21.4 REFERENCE DOCUMENTS .................................................................................................. 2

    Chapter 2 - Product Overview ................................................................................. 32.1 FEATURES ............................................................................................................................... 42.2 TYPICAL APPLICATION ....................................................................................................... 52.3 COMPONENTS ........................................................................................................................ 6

    Chapter 3 - Component Descriptions ................................................................... 103.1 DIGITAL TACHOMETER..................................................................................................... 103.2 PICKUPS OK LED ................................................................................................................. 103.3 STOP/RUN/START SWITCH ............................................................................................... 103.4 LOCAL SPEED SETPOINT CONTROL ............................................................................... 103.5 M100 CONTROLLER ASSEMBLY ...................................................................................... 11

    3.5.1 M100 Speed Signal........................................................................................................ 133.5.2 M100 Power Supply ...................................................................................................... 133.5.3 M100 Setpoint Circuit ................................................................................................... 133.5.4 M100 Control Section ................................................................................................... 133.5.5 M100 Speed Switches ................................................................................................... 14

    3.6 M100 TERMINAL STRIPS .................................................................................................... 153.7 AUXILIARY TERMINAL STRIP ......................................................................................... 153.8 9-VOLT BATTERY HOLDER .............................................................................................. 163.9 OVERSPEED TEST SWITCH ............................................................................................... 163.10 I/P TRANSDUCER ................................................................................................................. 163.11 INPUT I/P AIR FITTING ....................................................................................................... 163.12 OUTPUT I/P AIR FITTING ................................................................................................... 163.13 FIELD WIRING CONDUIT CONNECTIONS ...................................................................... 163.14 PURGE AIR FITTING ............................................................................................................ 163.15 PNEUMATIC SETPOINT FITTING ..................................................................................... 163.16 ENCLOSURE ......................................................................................................................... 163.17 MAGNETIC SPEED PICKUPS ............................................................................................. 173.18 GEAR ...................................................................................................................................... 173.19 FINAL ACTUATOR .............................................................................................................. 17

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    10/77

    x TS110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Chapter 4 Specifications and Certi fications ..................................................... 194.1 SPECIFICATIONS .................................................................................................................. 194.2 CERTIFICATIONS ................................................................................................................. 21

    Chapter 5 - Configuration ...................................................................................... 235.1 JUMPER DESCRIPTIONS ..................................................................................................... 235.2 CONFIGURATION SPECIFICATION SHEET ..................................................................... 27

    5.2.1 Selection of Frequency Range ....................................................................................... 285.2.2 Jumper Configuration .................................................................................................... 28

    Chapter 6 - Calibration Procedures ...................................................................... 316.1 DIGITAL TACHOMETER ..................................................................................................... 31

    6.1.1 DT6 Digital Tachometer ................................................................................................ 316.1.2 DT9 Digital Tachometer ................................................................................................ 33

    6.2 M100 CALIBRATION PROCEDURE ................................................................................... 35Chapter 7 - Installation........................................................................................... 41

    7.1 LOCATION & MOUNTING .................................................................................................. 417.1.1 Choosing a Location for the TS110Controller .............................................................. 417.1.2 Mounting ........................................................................................................................ 41

    7.2 FIELD WIRING FOR STANDARD INSTALLATION ......................................................... 43M100 Termination Board Wiring Details ............................................................................... 45

    7.3 FIELD WIRING FOR OPTIONAL CONFIGURATIONS ..................................................... 477.3.1 Remote STOP/RUN/START Switch ............................................................................. 477.3.2 Overspeed Trip Relay .................................................................................................... 49

    7.4 PNEUMATIC INSTALLATION ............................................................................................ 507.4.1 Piping ............................................................................................................................. 507.4.2 Optional Pneumatic Speed Setpoint............................................................................... 507.4.3 Final Actuator ................................................................................................................ 50

    7.5 HYDRAULIC ACTUATOR SYSTEMS INSTALLATION .................................................. 537.6 MAGNETIC SPEED PICKUPS INSTALLATION ................................................................ 537.7 GEAR INSTALLATION FOR SPEED SENSING ................................................................. 54

    Chapter 8 - Operation............................................................................................. 558.1 STARTUP ................................................................................................................................ 55

    8.1.1 Battery By-Pass Start ..................................................................................................... 558.1.2 4- 20-mA Start ................................................................................................................ 558.1.3 Remote Start ................................................................................................................... 568.1.4 Manual Loading Station Start (Option) ......................................................................... 56

    8.2 TUNING .................................................................................................................................. 568.2.1

    Gain and Integral ............................................................................................................ 56

    8.2.2 Derivative ....................................................................................................................... 578.2.3 Reduced Gain Band ....................................................................................................... 588.2.4 Droop ............................................................................................................................. 58

    8.3 OVERSPEED TEST (MECHANICAL) .................................................................................. 598.4 ELECTRONIC OVERSPEED ................................................................................................. 608.5 UNDERSPEED SWITCH ....................................................................................................... 60

    Chapter 9 - Maintenance ........................................................................................ 61Chapter 10 - Troubleshooting ............................................................................... 63

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    11/77

    Contents xi

    October 2009 Rev. 5

    Illustrations

    Figure 1. TS110Self-Powered Controller, Front View .......................................................................... 3

    Figure 2. TS110Self-Powered Controller, Inside View ......................................................................... 4Figure 3. TS110Typical Application ..................................................................................................... 5

    Figure 4. TS110Front View, Component Locations ............................................................................. 7

    Figure 5. TS110Front View with Door Open, Component Locations .................................................. 8

    Figure 6. TS110Bottom View, Component Locations .......................................................................... 8

    Figure 7. Special High-Output Magnetic Speed Pickup ........................................................................ 9

    Figure 8. M100 Controller Assembly .................................................................................................. 11

    Figure 9. M100 Block Diagram ........................................................................................................... 12

    Figure 10. Calibration/Configuration Diagram - Jumpers ................................................................... 26

    Figure 11. DT9 Programming Screens ................................................................................................. 33

    Figure 12. Calibration/Configuration Diagram - Potentiometers ......................................................... 36

    Figure 13. Calibration/Configuration Diagram - Test Points ............................................................... 37

    Figure 14. Mounting Dimensions ......................................................................................................... 42Figure 15. Standard Field Wiring ......................................................................................................... 44

    Figure 16. Field Wiring Detail ............................................................................................................. 46

    Figure 17. Field Wiring for Remote Start of a Backup Turbine Using a Second TS110..................... 47

    Figure 18. Field Wiring for Remote Stop Using 4-20 mA Signal with N.O. or N.C. Switch .............. 48

    Figure 19. Field Wiring for Overspeed Trip Relay .............................................................................. 49

    Figure 20. Pneumatic Installation, General Guidelines ....................................................................... 51

    Figure 21. Pneumatic Installation, Diaphragm Actuator with Air Booster .......................................... 52

    Figure 22. Pneumatic Installation, Piston Actuator with Positioner .................................................... 52

    Figure 23. Reduced Gain Band ............................................................................................................ 58

    Figure 24. Overspeed Trip Test ........................................................................................................... 59

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    12/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    13/77

    Chapter 1 - Introduction 1

    October 2009 Rev. 5

    Chapter 1 - Introduction

    The TS110Self-Powered Controller is a low-cost digital electronic controller, designed as a NEMA

    4X compliant, variable speed PID (Proportional, Integral, Derivative) controller with a single control

    output. It replaces mechanical-hydraulic controllers that require frequent maintenance and overhauls.

    1.1 About This Manual

    As its name implies, this manual is a guideto operating the TS110. In-depth user training is available

    from Tri-Sen.

    Since this document is relatively small, an index is not included. Instead, a detailed table of contents

    is provided. This manual contains the following chapters:

    Chapter 1 - IntroductionThis chapter contains information about this document and related reference documents.

    Chapter 2 - Product Overview

    This chapter presents an overview of the product, including a typical application. Chapter 3 - Component Descriptions

    This chapter describes each component of a TS110.

    Chapter 4 - SpecificationsThis chapter provides all TS110specifications.

    Chapter 5 - ConfigurationThis chapter describes how to configure a TS110for most applications.

    Chapter 6 - Calibration ProceduresThis chapter explains how to calibrate the tachometer and the M100.

    Chapter 7 - InstallationThis chapter provides mounting and wiring details.

    Chapter 8 - OperationThis chapter includes discussions of the various TS110operating modes, as well as

    tuning instructions.

    Chapter 9 - MaintenanceThis chapter provides minor maintenance information.

    Chapter 10 - TroubleshootingThis chapter describes how to trouble shoot the TS110for optimum performance.

    By reading this manual, you will be able to:

    Understand the components of the TS110Self-Powered Controller.

    Configure all control, speed, pressure and synchronization parameters.

    Configure all analog inputs, analog outputs, digital inputs, digital outputs and pressureinputs.

    Configure all analog trips and alarms.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    14/77

    2 TS110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    1.2 Documentation Conventions

    This manual uses the following typographic conventions:

    Example DescriptionNOTE Notes contain supplementary information.

    CAUTION!

    This symbol precedes information about potential equipment damage.

    WARNING!

    This symbol precedes information about potential personnel hazards.

    1.3 User Experience Prerequisites

    To use the TS110effectively, users should have some experience with the use of digital control

    systems, or have an instrumentation background.

    Extremely advantageous, though not required, is experience with turbine control systems, and normal

    operations experience within a plant environment.

    1.4 Reference Documents

    Documentation provided with other components of a system containing a TS110.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    15/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    16/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    17/77

    Chapter 3 - Component Descriptions 5

    October 2009 Rev. 5

    2.2 Typical Application

    The TS110System utilizes one or two high power magnetic pickup(s) for power and speed signal.

    The tooth of a ferrous gear passing under the magnetic pickup creates an AC pulse. This pulse is

    converted to a DC voltage to power the controller. The pulse rate (or frequency) is also converted

    into a DC voltage that is compared to a setpoint voltage. The difference is sent through a

    Proportional/Integral/Derivative loop and converted to a 1-5 mA output signal.

    The 1-5 mA signal is sent to a current to pressure (I/P) transducer which converts the signal to a 3-15

    psi low consumption air signal.

    The air signal is sent to a pneumatic diaphragm actuator and air booster or a piston type actuator with

    positioner, depending on size and specifications of the turbine. The actuator is coupled directly, or

    through linkage, to the valve stem.

    The magnetic pickups are mounted around the pickup gear. The pickup gear is mounted on the main

    shaft of the turbine or engine.

    Figure 3. TS110Typical Application

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    18/77

    6 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    2.3 Components

    The Tri-Sen TS110consists of the following components:

    1. An adjustable timebase 4-digit digital tachometer

    2. A PICKUPS OK LED

    3. A STOP/RUN/START switch (actuator)

    4. A local SPEED SETPOINT control (potentiometer)

    5. An M100 self-powered electronic controller assembly (The termination board isvisible. It is hinged, and when the two screws are removed, it lifts up to reveal the

    circuit board below.)

    6. M100 terminal strip

    7. An auxiliary terminal block for wiring external remote run or start with 4 spare sets ofterminals for customer use

    8. A 9 V battery holder

    9. An overspeed test switch

    10. An I/P transducer

    11. Input I/P air fitting

    12. Output I/P air fitting

    13. Field wiring conduit connections

    14. Purge air fitting

    15. Pneumatic Setpoint Fitting

    16. A NEMA 4X stainless steel housing, which can be surface mounted near the turbine

    17. Up to 2 special high-output magnetic speed pickups, and standard interconnect cables

    These components are shown, with corresponding numbers, on three figures on the following pages,

    and are described in detail in Chapter 3.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    19/77

    Chapter 3 - Component Descriptions 7

    October 2009 Rev. 5

    TRISEN

    TS110

    RPM

    STOP

    RUN

    START

    SPEEDSETPOINT

    PICKUPSOK

    1

    2

    4

    3

    TS110-5

    Figure 4. TS110Front View, Component Locations

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    20/77

    8 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    6

    16

    5

    8 10

    9

    7

    13 15 14

    M100

    TS110-6

    11 1211 & 12 ARE DIRECTLY

    BEHIND 15 & 14

    Figure 5. TS110Front View wi th Door Open, Component Locations

    13

    11 12

    3 4

    TS110-7

    15 14

    Figure 6. TS110Bottom View, Component Locations

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    21/77

    Chapter 3 - Component Descriptions 9

    October 2009 Rev. 5

    BOTTOM VIEW

    FRONT VIEW

    TOP VIEW

    0.250 0.003

    0.750, +0.025, -0.000

    JAM NUT

    5/8-18 UNF-2A THD 4.000 0.015

    5.093 REF

    1.093 REF

    AB

    TS110-8

    Figure 7. Special High-Output Magnetic Speed Pickup

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    22/77

    10 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Chapter 3 - Component Descriptions

    This chapter contains descriptions of the TS110components, as outlined in Chapter 2. Refer to the

    previous figures for locations of these components.

    3.1 Digital TachometerThe digital tachometer supplied with the TS110is a 4-digit, configurable tachometer. It can be

    configured for any number of gear teeth. Older units were configured using DIP switches on the back

    of the tachometer, while currently shipping units are configured using push buttons.

    NOTE: The gear must have a diametrical pitch of 8 or less for use with the special magnetic speed

    pickups.

    3.2 PICKUPS OK LED

    This LED flashes every three seconds to indicate that both magnetic pickups are working properly. If

    one pickup fails, the LED will no longer flash, thus indicating a pickup failure.

    3.3 STOP/RUN/START Switch

    The START position is used with a battery or a 4 to 20 mA signal to send an output current to the I/P

    transducer to open the control valve. In the RUN position, the output of the controller is allowed to

    pass to the I/P transducer. In the STOP position the output of the controller is set to minimum.

    3.4 Local SPEED SETPOINT Control

    This control is a ten-turn potentiometer with a numbered dial and a locking tab. The fully clockwise

    position yields maximum governor speed. The numbers on the face of the dial (1-10) represent a

    percentage of the governing range, 1.0 being 10% and 10.0 being 100%.EXAMPLE: Min Governor = 3400 RPM = 0.0

    Max Governor = 3600 RPM = 10.0

    5.0 = 3500 RPM

    NOTE: The local speed setpoint can work in conjunction with the remote speed setpoint.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    23/77

    Chapter 3 - Component Descriptions 11

    October 2009 Rev. 5

    3.5 M100 Controller Assembly

    The M100 controller assembly is located inside the TS110, top left side. The termination board,

    which is visible, provides terminal strips for connection of field wiring. This board is hinged, and

    when the two screws are removed, it lifts up to reveal the circuit board below. The circuit board

    contains all of the jumpers, potentiometers, and test points necessary to configure the TS110for a

    particular application.

    Refer to the figures below and on the following page for the general appearance and a block diagram

    of the M100 controller assembly.

    1 +

    2 -

    3 +

    4 -

    5 +

    6 -

    7 +

    8 -

    9 +

    10 -

    11+

    12 +

    13 -

    14 +

    15 CW

    16 W

    17 CCW

    18 +

    19 -

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    11

    + 12

    - 13

    + 14

    - 15

    16

    + 17

    - 18

    19

    GAIN

    DERIV

    INTEGRAL

    O

    V

    E

    R

    SP

    E

    E

    D

    T

    E

    ST

    R

    ST

    O

    V

    ER

    SP

    E

    ED

    R

    E

    M

    OT

    E

    S

    E

    T

    PN

    T

    A

    N

    A

    D

    I

    G

    T

    A

    C

    H

    E

    X

    T

    P

    W

    R

    RE

    M

    ST

    RT

    M

    A

    X

    FU

    E

    L

    U

    N

    D

    ER

    S

    P

    E

    ED

    S

    WI

    T

    C

    H

    S

    P

    E

    ED

    L

    O

    OP

    T

    UN

    I

    N

    G

    REMOTE

    SETPOINT

    3 - 15

    PSIG

    M100

    SELF-POWERED

    GOVERNOR

    TRISEN

    TB2TB1

    CW

    CW

    S

    WI

    T

    C

    H

    R

    U

    N

    PICKUPS

    O

    K

    L

    OC

    A

    L

    SE

    T

    RE

    M

    SE

    T

    I/

    P

    P

    ICKUP

    2

    PICKUP

    1

    TS110-4

    TRI-SEN Systems, Inc.La Marque, TX U.S.A.

    ASSY90-0360

    AW90-0358

    1

    3

    5

    7

    9

    2

    4

    6

    8

    10

    J1

    W11

    W7

    W10

    W81

    3

    2

    W5

    W11 3

    W9 W

    4

    W31 3

    W21 3

    W6

    TS110-200

    R1

    21

    R60

    R59R65

    R64

    R32

    R33

    R44

    R24

    R23

    R82

    R83

    R101 R102

    R117

    R116

    R115

    TP7 TP8

    TP4

    TP9

    TP6

    TP5

    TP3

    TP1

    TP2

    GND

    M100 Termination Board M100 Circuit Board

    Figure 8. M100 Controller Assembly

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    24/77

    12 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    4-20mA

    REMOTE

    SETPOINT

    3-15PSI

    REMOTE

    SETPOINT

    REMOTE

    POTENTIOMETER

    SETPOINT

    FREQUENCY

    TOVOL

    TAGE

    CONVERTER

    I/V

    P/V

    OVERSP

    EED

    TEST

    HI/LOSELECT

    LOGICW5

    SETPOINT

    ACTION

    SETPOINT

    AMP

    MAXGOV

    MINGOV

    SETPOINT

    AMP

    MAXGOV

    MINGOV

    W1

    W2

    W3

    LOCAL

    POTENTIOMETER

    SETPOINT

    W7

    REMOTE

    STARTLOGIC

    W4

    MAGNETIC

    PICKUP#1

    MAGNETIC

    PICKUP#2

    PICKUPSOK

    VOLTAGE

    DOUBLERS&

    FILTERS

    PULSE

    SELECT

    LOGIC

    VOLTAGE

    REGULA

    TION

    W6

    EXTERNAL

    POWER

    OVERSPEED

    COMPARISON

    UNDERSPEED

    COMPARISON

    STARTUP

    PERMIT

    DIG

    ITALTACH

    ANALOGTACH

    ALARM

    ALARM

    +5V

    TP3

    TP2

    REMOTE

    START

    ERROR

    AMP

    TP6

    + -

    -

    -

    DERIVATIV

    E

    R113

    INTEGRAL

    R4115

    REDUCED

    GAINBAND

    R102

    DROOP

    R101

    GAIN

    R117

    OUTPUT

    CO

    NTROL

    ACTION

    W8

    V/I

    OUTPUT

    0-5mA

    MAX/MIN

    OUTPUT

    R82,R83

    +

    -

    MAXSTARTOUTPUT

    +5

    -V

    TP4

    ++

    R44

    POWERSUPPLY

    S

    PEED

    S

    WITCHES

    SPEEDSIGNAL

    SETPOINTCIRCUIT

    REMOTESTART

    P

    IDBLOCK

    CURRENTDRIVER

    TS110-1

    Figure 9. M100 Block Diagram

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    25/77

    Chapter 3 - Component Descriptions 13

    October 2009 Rev. 5

    3.5.1 M100 Speed Signal

    Pulses from the two magnetic pickups are conditioned by the pulse select logic, and the one with the

    higher output is routed to the Frequency-to-Voltage converter (F/V). The pulse select logic allows

    the M100 to continue to function with just one pickup installed or working.

    3.5.2 M100 Power SupplyPulses from the magnetic pickups are also applied to the inputs of two voltage doublers, where the

    signals are rectified and filtered. The DC output is then fed to a voltage regulator where it is held at

    5.0 volts. This voltage can be monitored between TP2 (+) and GND on the M100 circuit board.

    Pulses from the Pulse Select Logic are fed to a charge pump to generate -4.5 V. This can be

    measured at TP3 on the M100 circuit board and can vary between -3.5 V to -4.5 V from unit to unit.

    This value is not critical and is used only to establish negative bias for the op-amps.

    3.5.3 M100 Setpoint Circuit

    The M100 features two sources of setpoint control - one local potentiometer and one of three remote

    inputs. Hi/Lo Select logic allows the local setpoint to: a) override the high remote setting; b) overridethe low remote setting; or c) disable the local setpoint control. The output of the setpoint circuit is a

    DC voltage that can be monitored at TP6 on the M100 circuit board.

    M100 I/V CircuitA remote 4-20 mA current is converted to a 0-3 V DC signal. The output of this circuit

    can be measured at pin 1 of jumper block W1 on the M100 circuit board.

    M100 P/V CircuitThis circuit converts the 3-15 psi setpoint into a DC voltage. The output from the

    pressure transducer mounted on the M100 cover is amplified to produce 0-3 V over the

    pressure range. This level can be measured at pin 3 of jumper block W1.

    3.5.4 M100 Control Section

    The control section consists of the Error Amplifier, PID Gain Block and Voltage-to-Current Driver.

    3.5.4.1 M100 Error Ampl ifier

    The outputs from the setpoint and tachometer circuits are compared in the error amplifier, such that

    any difference between the two inputs will produce an error or correction voltage. The gain of the

    error amplifier is controlled by the reduced gain band control. As the reduced gain band is increased

    (up to 10%) the error amplifier gain is decreased, resulting in less sensitivity to differences between

    the setpoint and measured speed. This is shown by the graph in paragraph 8.2.3. When the controller

    is tuned and operating properly, the output of the error amplifier should be close to zero volts.

    Pushing the overspeed test switch will reduce the voltage, increasing the output of the controller and

    subsequently increasing the controlled speed.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    26/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    27/77

    Chapter 3 - Component Descriptions 15

    October 2009 Rev. 5

    3.5.5.2 M100 Overspeed Switch

    Like the Underspeed Switch, the Overspeed Switch monitors the voltage at TP4. The speed signal is

    compared to the Overspeed Trip setpoint. When the speed signal is greater than the setpoint, the

    Overspeed Switch SCR is triggered which shorts out the externally supplied loop current. The SCR

    will remain ON as long as loop current is present, regardless of the state of the controller.

    The controller also goes into a latch upmode when an overspeed condition exists, removing all drivecurrent to the I/P output. The only way to reset the controller is to set the STOP/RUN/START switch

    to STOP.

    The setpoint voltage to the Overspeed Switch can be monitored at TP8, and ranges from 0.625 V to

    3.125 V.

    Removing the OVERSPEED TEST jumper (from both W7 on the board and TB2:3,4) raises the

    setpoint by 20% allowing testing of the mechanical overspeed trip.

    NOTE: The Overspeed Switch can be used in conjunction with a 120 VAC, 8 A, solid state relay

    (Tri-Sen part no. 7015-0000) to trip the machine by operating the dump solenoid or

    unlatching the trip lever. For more information, refer to the Operations section of this

    manual.

    3.6 M100 Terminal Strips

    Two terminal strips, TB1 and TB2, are positioned vertically on the M100 termination board. Each

    strip contains 19 terminals for connection of field wiring. Each terminal is labeled on the front of the

    M100 termination board. Connections to the terminal strips are discussed in more detail in Chapter 7,

    Installation.

    3.7 Auxiliary Terminal Strip

    This auxiliary terminal block is located at the bottom of the unit for ease of field wiring. The

    following is a description of the Auxiliary Terminal Strip Connections:

    BATT +/-: In the absence of the 9-volt battery an external 9-12-volt supply can beconnected to these terminals to supply the current for start up. The voltage from these

    terminals is routed through the STOP/RUN/START switch.

    RMT START: To be used with RMT RUN to start the governor from a remote location.A momentary N.O. switch placed across this terminal, with the 9-volt battery in place or

    another power source connected to BATT, will apply a start current to the governor.

    RMT RUN: A STOP/RUN/START switch similar to that supplied with the TS110canbe used to start and stop the governor from a remote location. If no switch is placed on

    these terminals the jumper provided must be left in place. This is also a convenient placeto insert a current meter to monitor the I/P current.

    In addition to these signals, four sets of uncommitted terminals are provided as spares for customer

    use.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    28/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    29/77

    Chapter 3 - Component Descriptions 17

    October 2009 Rev. 5

    3.17 Magnetic Speed Pickups

    The speed measurement signal and power for the TS110are generated by special magnetic pickups in

    conjunction with a ferrous metal gear that is mounted on the turbine shaft. These pickups must be

    mounted approximately 0.005 to 0.020 inch from the gear. This gap allows for the lowest possible

    required power-up speed for the controller.

    3.18 Gear

    A ferrous metal gear with a diametrical pitch of 8 or less attached to the main turbine shaft is needed

    in conjunction with the special magnetic pickups to generate the speed measurement signal and the

    power for the TS110. Diametrical pitch is calculated using the following equation:

    Diametrical Pitch = Number of Teeth + 2

    Diameter of Gear

    3.19 Final Actuator

    The final actuator can be a pneumatically-operated valve or assembly which controls the amount ofsteam or fuel entering the machine. For small turbines, the most economical installation is usually a

    standard pneumatic actuator with positioner, mounted on the governor valve. For critical small

    drivers, such as lube and seal oil turbines that support large process machines, the best solution is a

    standard linear characteristic pneumatic control valve with blocks and a by-pass. This allows on-

    stream maintenance of the governor or valve without shutting down the pump. This could prevent

    catastrophic damage to the large machine, if the spare pump fails while the governor is being

    repaired.

    Larger turbines with hydraulically-operated valves or valve racks can be operated by installing a

    pneumatic actuator and positioner on the hydraulic pilot, using mechanical feedback principles.

    Some medium-to-large turbines with mechanical governors utilize a cup-type hydraulic servomotor,

    which is easily converted to pneumatic control. These servomotors provide excellent performanceand reliability.

    Regardless of which actuator type is used, it is essential that the complete actuator system have the

    fastest possible stroking time and an absolute minimum of reduced gain band. This is especially

    important with small drivers that, because of their low rotating mass, have very short time constants.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    30/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    31/77

    Chapter 2 - Product Overview 19

    October 2009 Rev. 5

    Chapter 4 Specifications and Certi fications

    This chapter contains specifications and certifications of the TS110.

    4.1 Specifications

    Inputs

    Speed Sensor Tri-Sen Part No. 7131-0004, 2 each

    (3 V rms at 15 mA, 200 - 10,000 Hz)

    Gear Diametrical Pitch of 8 or less

    Remote Start 4-20 mA or 5 V at 4 mA

    Remote Power 9 Volts at 10 mA for testing only

    Setpoints Local SPEED SETPOINT potentiometer on front panel

    AND/OR

    User supplied remote potentiometer OR

    Remote 4-20 mA current loop OR

    3-15 psig pneumatic

    Remote max. Output External 200k potentiometer

    Overspeed Test Open: Test; Closed: Normal

    Start Switch Open: Normal; Closed: Start

    Run Switch Open: Stop; Closed: Run

    Reset Switch Open: Normal; Closed: Reset

    Outputs

    Actuator 3 to 15 psig at maximum rate of 2.0 SCFM

    at 20 psig supply

    Overspeed Isolated SCR, 400 V max, 0.3 A max,

    0.15 mA min

    Low Speed 5 V at 4 mA when speed < low-speed

    switch setting

    Analog Tachometer 0-50 A

    Digital Tachometer 5 V pulse

    Adjustments

    Local and Remote

    Speed Setpoint Minimum Controller, Maximum Controller,

    External 100k Setpoint Potentiometer

    Speed Trips & Alarms Overspeed Trip, Low Speed Switch

    PID Control Gain, Derivative, Integral, Droop,

    Reduced Gain Band

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    32/77

    20 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Output Limits Local and Remote Maximum Output,

    Remote Start Maximum Output,

    Minimum Output, Overspeed Test

    Tachometer F/V Calibration, Analog Tachometer Cal

    Selections

    Frequency Range 5 ranges from 200 to 10,000 Hz

    Setpoint Logic Local and Remote; High or Low Select

    Remote Setpoint Potentiometer, 4-20 mA, 3-15 psig;

    Direct/Reverse for current and pneumatic.

    Power Source Speed Pickup or Battery (for test only)

    Remote Start Enable/Disable

    Overspeed Test Open = Enabled / Shorted = Normal Operation

    Control Action Direct or Reverse

    Power Requirements

    Speed Sensor 3 V rms at 15 mA, 200 - 10,000 Hz

    External Battery 9 VDC, 10 mA (for test only)

    Performance

    Control Action 0.1% Steady State

    Droop Control 0 - 10%

    Proportional Band 5 - 200%

    Reset Time 0 - 10 Seconds/RepeatRate Time 0 - 5 Seconds

    Reduced Gain Band 0 - 10%

    Frequency Range 200 - 10,000 Hz

    I/P

    Input 1 to 5 mA

    Output 3 to 15 psig

    Supply Pressure Normal: 20 psig

    Minimum: 18 psigMaximum: 50 psig

    Output Capacity 4.5 scfm (7.6 m3hr ANR) at 25 psig (175 kPa) supply

    Maximum Air Consumption Less than 0.2 SCFM at 20 psig supply

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    33/77

    Chapter 2 - Product Overview 21

    October 2009 Rev. 5

    Environmental

    Temperature Range -20 F to 160 F

    Humidity 0 - 95%, non-condensing

    Electrical Class/Approvals None

    Construction Single PC Board, mounted in die-cast housing

    4.75" X 7.4", 3.2" max. ht.

    Field Terminations Barrier Strip, 6-32 screws

    4.2 Certifications

    Factory Mutual (FM) approved the TS110 to these standards.

    Standard

    NumberTitle Year Issued

    3600 Electrical Equipment for Use In Hazardous (Classified) Locations

    - General Requirements

    1998

    3610 Intrinsically Safe Apparatus and Associated Apparatus for Use in

    Class I, II & III, Division 1, Hazardous (Classified) Locations

    2007

    3810 Electrical and Electronic Test, Measuring and Process Control

    Equipment

    2005

    FM Approved

    IS/I/1/A,B,C,D

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    34/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    35/77

    Chapter 5 - Configuration 23

    October 2009 Rev. 5

    Chapter 5 - Configuration

    Configuring the TS110is accomplished by placing and/or removing jumpers on the M100 circuit

    board. (Refer to the figure on the following page.) The circuit board is accessed by removing the two

    screws from the termination board and lifting it up and to the left to expose the circuit board.

    5.1 Jumper Descr iptions

    The following table identifies the jumpers and the placement required for various configurations. The

    jumper positions shown in the table are the defaults from the factory.

    Jumper Jumper Description Position Position Description

    J1 FREQUENCY RANGE

    from top to bottom

    1 2

    200-500 Hz

    400-1000 Hz

    800-2000 Hz

    2000-5000 Hz

    4000-10,000 Hz

    W1 REMOTE SIGNAL SETPOINT 2 31

    4-20 mA setpoint select

    NOTE: W1 is valid only when

    W3:2,3 is in place.1 2 3

    3-15 psi setpoint select

    W2 REMOTE SETPOINT ACTION.

    W2 is used to choose Reverse or

    Direct action when using either

    the 4 to 20 mA current (terminals

    TB2:7,8) or the 3 to 15 psigPneumatic Remote Setpoints.

    2 31

    Reverse Action: current/pneumatic

    setpoint

    means that an increase in signal

    will cause a decrease in desired

    speed.

    NOTE: W2 is valid only when

    W3:2,3 is in place.1 2 3

    Direct Action: current/pneumatic

    setpoint

    This is most commonly used and

    means that an increase in signal

    causes an increase in desired speed.

    W3 REMOTE SETPOINT. 2 31

    Remote potentiometer setpoint

    select

    NOTE: If W3:2,3 is selected, W1

    and W2 must be used.1 2 3

    Current/pneumatic setpoint select

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    36/77

    24 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Jumper Jumper Description Position Position Description

    W4 REMOTE START. W4 is used in

    conjunction with the 4 to 20 mA

    Remote Setpoint (terminals

    TB2:7,8). When W4 is installed,

    the governor can be started fromthe 4 to 20 MA current loop.

    1 2

    Remote start from 4-20 mA setpoint

    WARNING!If this feature

    is applied to the TS110, care

    should be taken in training all

    personnel. The turbine will start

    with no one at the turbine/engine

    if the current loop is lost and

    regained.Refer to the remote

    stop figure in paragraph 7.3.1.

    NOTE: If W4 is installed, a (reset)

    switch must be installed in

    the Remote Setpoint 4 to 20

    mA loop to momentarily

    interrupt the current loop to

    reset the Remote Start

    Feature for another startup.

    W5SETPOINT SELECT

    HIGH/LOW.2 31

    Local setpoint high selectcauses the local to override the

    remote when the local is set to a

    higher value.

    NOTE: If W5 is not installed the

    Local Setpoint will be

    disabled.

    1 2 3

    Local setpoint low select

    causes the local to override the

    remote when the local is set to a

    lower value.

    1 2 3

    Local setpoint disabled

    W6 1 2

    M100 powered by magnetic pickup

    W7 NOTE: This jumper is not used if

    overspeed test switch is

    installed across TB2:3,4.

    1 2

    Enable overspeed test

    W8 CONTROL ACTION.

    W8 is used to choose reverse or

    direct control action to the final

    actuator.

    2 31

    Direct Control Action

    means that an increase in speed

    causes an increase in output to the

    actuator.

    1 2 3

    Reverse Control Action

    is most commonly used, and means

    that an increase in speed causes a

    decrease in output to the actuator.NOTE: Reverse Control Action is

    more commonly used so

    that, as the speed of the

    machine increases, the

    valve is closed.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    37/77

    Chapter 5 - Configuration 25

    October 2009 Rev. 5

    Jumper Jumper Description Position Position Description

    W9 EXT +5 VOLT ENABLE. 1 2

    +5 Volts are provided at TB2:12,13

    for powering a solid state relay for

    overspeed trip. For more

    information refer to Paragraph 8.4.

    NOTE: If external power is appliedto TB2:12,13, W9 must be

    removed to prevent damage

    to the board.

    W10 PNEUMATIC SETPOINT

    DISABLE.

    1 2

    Disable Pneumatic Setpoint

    NOTE: W10 and W11 must be

    installed if the pneumatic

    setpoint is not used.

    W11 PNEUMATIC SETPOINT

    DISABLE.

    1 2

    Disable Pneumatic Setpoint

    NOTE: W10 and W11 must be

    installed if the pneumatic

    setpoint is not used.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    38/77

    26 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Figure 10. Calibration/Configuration Diagram - Jumpers

    Tri-Sen Systems, Inc.Houston, TX U.S.A.

    ASSY 90-0360

    AW90-0358

    13579

    2468

    10J1

    W11

    W7W1

    W81

    32

    W5

    W11 3

    W9 W4

    W31 3

    W21 3

    W6

    TS110-201

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    39/77

    Chapter 5 - Configuration 27

    October 2009 Rev. 5

    5.2 Configuration Specification Sheet

    COMPLETE THE FOLLOWING FOR YOUR APPLICATION.

    This information will be used to determine the configuration of your TS110.

    Gear SpecificationsDiameter of Gear = _____ inches (determined by individual turbine)

    Number of Gear Teeth = _____ teeth (3" = 20 teeth; 5" = 30 teeth)

    Controller Parameters

    Minimum Governor Speed = _____ RPM

    Maximum Governor Speed = _____ RPM

    Overspeed Trip = _____ RPM

    Underspeed (if used) = _____ RPM

    Setpoint Selection

    Chooseoneof the following: _____

    1. Local potentiometer only

    2. Local potentiometer and remote potentiometer

    3. Local potentiometer and 4 to 20 mA current signal

    4. Local potentiometer and 3 to 15 psig pneumatic signal

    5. 4 to 20 mA current signal only

    6. 3 to 15 psig pneumatic signal only

    7. Remote potentiometer only

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    40/77

    28 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    The information completed on the Configuration Specification Sheet (previous page) will now be

    used to configure the TS110.

    5.2.1 Selection of Frequency Range

    Jumper J1 allows the TS110to be used for a variety of frequency ranges. To determine the frequency

    range for your application convert the overspeed trip (OS) to a frequency using the followingequation:

    Maximum Frequency (Hz) = OS X 1.2 X Number of Gear Teeth / 60

    Now choose a frequency range (J1, see table in paragraph 5.1) whose upper limit is at least the

    maximum frequency calculated above. Install a jumper in the proper position.

    5.2.2 Jumper Configuration

    The following paragraphs use the number entered for the Setpoint Selectionfrom the Configuration

    Specification Sheet.

    W1 Remote Signal Setpoint Define:

    If you selected number 3 or 5, place a jumper on W1:1,2 and connect the remote 4-20 mA current

    loop to TB2:7(+) and TB2:8(-)

    If you selected number 4 or 6, place a jumper on W1:2,3 and connect 1/8" i.d. flexible pneumatic

    tubing to the barbed fitting of the optional 3-15 psig. Remote Signal Transducer.

    If you selected number 1, 2 or 7, place jumper on W1:2,3.

    W2 Setpoint Control Action:

    If you selected number 3, 4, 5, or 6, determine whether you wish to have a Direct or Reverse Setpoint

    Action. Refer to table in paragraph 5.1 for explanations. Place jumper on appropriate position.

    If you selected number 1, 2, or 7, place the jumper on W2:2,3.

    W3 Remote Setpoint Define:

    If you selected number 1, place jumper on W3:1,2.

    If you selected number 2 or 7, place a jumper on W3:1,2 and connect a remote 100k potentiometer to

    TB1:9-11. Connect the wiper to TB1:10, and the clockwise (CW) end of the potentiometer to TB1:9.

    If you selected number 3, 4, 5, or 6, place a jumper on W3:2,3.

    W4 Remote Start:

    If you selected number 3 or 5 and wish to start the TS110using the 4-20 mA current, place a jumper

    on W4.

    If you selected any other number or do not wish to start the TS110from the 4-20 mA current, do not

    install a jumper.

    NOTE: If W4 is installed, a (reset) switch must be installed in the Remote Setpoint 4 to 20 mA loop

    to momentarily interrupt the current loop to reset the Remote Start Feature for another

    startup.

    Refer to paragraph 7.3.1

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    41/77

    Chapter 5 - Configuration 29

    October 2009 Rev. 5

    W5 Local Setpoint Select:

    If you selected number 1, place a jumper on W5:1,2

    If you selected number 5, 6, or 7, do not install a jumper.

    For any other selection, refer to table in paragraph 5.1 and place W5 jumper in appropriate position.

    W6 Power from Pickups:

    Always install W6 when powering the governor from the pickups.

    W7 Overspeed Test Enable:

    No jumper is needed on W7 when the overspeed test switch is installed across TB2:3,4 on the

    Termination Board.

    W8 Control Action:

    Reverse Control Action, which means that an increase in speed will close the control valve, will be

    used in most situations. Place a jumper on W8:2,3.

    W9 External +5 Volts Enable:

    Only install W9 when you will be using a solid state relay for an electronic overspeed trip. See

    paragraph 7.3.2.

    CAUTION!

    Powering the board with W9 installed can cause damage to some electronic

    components.

    W10 and W11 Pneumatic Setpoint Disable:

    If you selected number 1, 2, 3, 5, or 7, place a jumper on both W10 and W11.

    If you selected number 4 or 6, both W10 and W11 must be removed.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    42/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    43/77

    Chapter 6 - Calibration Procedures 31

    October 2009 Rev. 5

    Chapter 6 - Calibration Procedures

    6.1 Digital Tachometer

    The TS110controls from the frequency received from the pickups and gear. This frequency is related

    to the speed of the gear turning on the shaft and the number of teeth on the gear. The digitaltachometer converts this frequency to RPM to allow the user to see the speed from the display

    window.

    The TS110uses one of two digital tachometers, depending on date of manufacture. Units

    manufactured prior to October, 2003 use the Red Lion DT6 digital tachometer. It is identified by a

    removable plastic cover on its back side, with DIP switches present underneath the cover. Newer

    units use the Red Lion DT9 digital tachometer. It is identified by two buttons marked PAR and

    SEL on the tachometer face: There is no removable cover on the back side; instead, there is a

    product label with DT9 marked on it. The calibration procedure is different for each of the two

    tachometers.

    6.1.1 DT6 Digi tal TachometerThe DT6 digital tachometer converts the frequency from the pickups to RPM by use of a

    configurable Timebase. This configuration is entered via the DIP switches on the rear of the

    tachometer.

    The Timebase for a given gear is calculated by using the following equation

    Timebase = 7680

    No. of gear teeth

    Switch Increments Switch Increments

    SWA1 1 SWB1 256

    SWA2 2 SWB2 512

    SWA3 4 SWB3 1024

    SWA4 8 SWB4 2048

    SWA5 16 SWB5 4096

    SWA6 32

    SWA7 64

    SWA8 128

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    44/77

    32 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    EXAMPLE: Find the appropriate DIP switch setting for a desired display reading with a 20-tooth

    gear.

    TB = 7680 = 384

    20

    TB = 384

    DIP SWB1 - 256 Needed = 128

    DIP SWA8 - 128 Needed = 0

    Set SWB1, SWA8 to the ON position.

    Frequency Doubling

    DIP switch SWB6 is thefrequency doubling disableswitch. This switch is set to the OFF position at

    the factory. SWB6 should always remain in the OFF position since this position allows for the fastest

    update time without sacrificing accuracy.

    NOTE: If SWB6 is in the ON position, the RPM on the digital tachometer will read one-half of theactual RPM.

    Decimal Point Selection

    The selection of Decimal Point is accomplished by DIP switches SWB7 and SWB8. The following

    table shows which combination of switches is needed to obtain the desired decimal point location.

    The tachometer always has leading zero blanking.

    SWB7 SWB8 DP Location

    factory test mode

    0 (preset at factory)

    0.0

    0.00

    NOTE: Decimal point will change only at the normal display update times.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    45/77

    Chapter 6 - Calibration Procedures 33

    October 2009 Rev. 5

    6.1.2 DT9 Digi tal Tachometer

    The DT9 has three configuration parameters that must be programmed properly for the unit to

    accurately display speed. The three parameters are Rate Multiplier, Decimal Point, and Timebase. To

    enter the programming mode, place a jumper between the Push Button Enable (P. B. En.) and

    Common screw terminals on the rear of the tachometer.

    Once in programming mode, you scroll to the Rate Multiplier, Decimal Point, and Timebase entry

    screens by pressing the PAR button. (Screens change when the button is released.) Press PAR again

    to reach the fourth screen, which is the main display or run mode. Once programming is complete,

    the unit must be returned to the main display before exiting the programming mode to obtain normal

    operation. You leave the programming mode by removing the P. B. En. jumper after the DT 9 is

    returned to the main display.

    Note: The display changes on PAR or SEL push button release.

    Figure 11. DT9 Programming Screens

    Rate Multiplier

    The DT9 has a Rate Multiplier (RM) selection range from 0.0001 to 1.9999. See the Programming

    Calculations section below to determine the calculated value. After entering the programming mode,

    the least significant digit will be flashing. To increment this digit, press the SEL button. After the

    value 9, the digit will start over at 0. To move to the next digit press PAR and then that digit can be

    changed by pressing SEL. When reaching the most significant digit, pressing PAR will advance the

    meter to the Decimal Point selection.

    Decimal Point Selection

    The selection of the decimal point position for the display (DDP) is accomplished by repeatedly

    pressing SEL. This selection will always default to 0.0000 when advancing to it from the Rate

    Multiplier selection. By pressing PAR, the DT9 accepts the shown decimal point position and

    advances to the Timebase selection screen.

    Timebase Selection

    The DT9 has a Time Base selection range from 1 second to 7 seconds. See Programming

    Calculations to determine the calculated Rounded Time Base (RTB) value. The value is changed by

    pressing SEL. The value is entered by pressing PAR, after which time the Main Display/Run Mode is

    shown.

    Main Display / Run Mode

    The Main Display follows the Timebase Selection. The unit must be in this mode to exit the

    Programming Mode and have the unit display properly. The push button enable jumper can be

    removed after the DT9 is returned to the main display.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    46/77

    34 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Programming Calculations

    The equations presented in this section will allow you to determine the values for entry above in the

    DT9 configuration process. The following variables are referenced in the equations.

    #TEETH Number of Teeth on Pickup Gear

    CTB Calculated Time Base

    RTB Rounded Time Base

    DDP Display Decimal Point

    Use the following corresponding numbers in the equations below

    Decimal Point:

    0 = 1

    0.0 = 10

    0.00 = 100

    0.000 = 1000

    Use the following equations to determine the values for Rate Multiplier, Decimal Point Selection,

    and Rounded Timebase to be entered in the DT9 configuration process.

    TEETH#

    DDPCTB = 60

    RTB = (CTB) rounded to the nearest integer value

    TEETH#RTB

    DDPRM

    =

    60

    EXAMPLE: As an example, say you have a 30-tooth pickup gear and you want to view speed as

    an integer, i.e. DDP = 1. The equations yield the following values: CTB = 2, RTB = 2, and RM = 1.0.

    You would then enter these values in the DT9 configuration screens described above.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    47/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    48/77

    36 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    TRI-SEN Systems, Inc.La Marque, TX U.S.A.

    ASSY90-0360

    AW90

    -0358

    1

    3

    5

    7

    9

    2

    4

    6

    8

    10

    J1

    W11

    W7

    W10

    W81

    3

    2

    W5

    W11 3

    W9 W

    4

    W31 3

    W21 3

    W6

    TS110-202

    R121

    R60

    R59R65

    R64

    R32

    R33

    R44

    R24

    R23

    R82

    R83

    R101 R102

    R117

    R116

    R115

    Figure 12. Calibration/Configuration Diagram - Potentiometers

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    49/77

    Chapter 6 - Calibration Procedures 37

    October 2009 Rev. 5

    TRI-SEN Systems, Inc.La Marque, TX U.S.A.

    ASSY90-0360

    AW90

    -0358

    1

    3

    5

    7

    9

    2

    4

    6

    8

    10

    J1

    W11

    W7

    W10

    W81

    3

    2

    W5

    W11 3

    W9 W

    4

    W31 3

    W21 3

    W6

    TS110-203

    R121

    R60

    R59R65

    R64

    R32

    R33

    R44

    R24

    R23

    R82

    R83

    R101 R102

    R117

    R116

    R115

    TP7 TP8

    TP4

    TP9

    TP6

    TP5

    TP3

    TP1

    TP2

    GND

    Figure 13. Calibration/Configuration Diagram - Test Points

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    50/77

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    51/77

    Chapter 6 - Calibration Procedures 39

    October 2009 Rev. 5

    Overspeed Setpoint

    20. Connect DMM negative lead to GND and the positive lead to TP7. This voltage will be

    approximately -3.5 volts. This indicates that the unit is not in overspeed trip.

    21. Set M115 SIM-CALIB to CALIB and adjust calibrate pot to the overspeed setting.

    22. DT should read the overspeed setting.

    23. Turn R60 CCW until DMM reading goes from a negative voltage to approximately

    +5 volts.

    24. Switch to STOP, and turn M115 power OFF.

    25. Move M115 calibrate pot to slightly below the overspeed setting.

    26. Switch to RUN, and turn M115 power ON.

    27. Slowly turn freq pot CW while watching the DT, and confirm that the DMM reading

    goes to +5 volts at a DT reading of the overspeed value.

    28. Switch to STOP and turn M115 power OFF.

    29. Turn M115 freq pot CCW to 0.0.

    Underspeed Switch

    30. Connect the DMM positive lead to TB2:18, and the negative lead to TB2:19.

    31. Switch to RUN and turn M115 power ON.

    32. Set M115 freq pot to the UNDERSPEED TRIP setting and the SIM-CALIB switch to

    CALIB.

    33. DT should read underspeed trip setting.

    34. Turn R65 CW until DMM indicates +5 volts.

    Mechanical Overspeed Test

    35. Switch to STOP and turn M115 power OFF for about 5 seconds.

    36. Set SIM/CAL switch to SIM.

    37. Turn M115 power ON and switch to START momentarily (switch will revert back to

    RUN).

    38. If you have problems starting the TS110, increase the LOAD and LAG on the M115.

    Always turn M115 power OFF for about 5 seconds between starts to allow the residual

    power to dissipate.

    39. Push and hold the OVERSPEED TEST switch.

    40. Adjust R121 to achieve the maximum rpm that you want to reach while testing the

    mechanical trip on the turbine.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    52/77

    40 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Min/Max Output

    41. Switch to STOP and turn the M115 power OFF.

    42. Remove the jumper from the RMT RUN (terminals 9 and 10 on the auxiliary terminal

    strip).

    43. Place DMM positive lead on terminal 9 and the negative lead on terminal 10.

    44. Place the DMM in MA CURRENT mode.

    45. Set the M115 SIM/CAL switch to CAL.

    46. Switch to run and turn the M115 power ON.

    47. Adjust the freq pot to slightly above maximum governor speed. This should make the

    current on the DMM integrate to about 0 mA.

    48. Adjust R83 CW until the DMM reads 1 mA.

    NOTE: If the current stays at 0 mA the governor may be in an overspeed trip condition.

    Make sure that the speed is adjusted below the overspeed trip setpoint. Turn theSTOP/RUN/START switch to STOP and then back to RUN. This should reset the

    controller. Also check the DMM leads to insure that they are firmly attached and

    making a good connection.

    49. Adjust the freq pot to slightly below minimum governor speed. This should make the

    current on the DMM integrate to about 6.5 mA.

    50. Adjust R82 CCW until the DMM reads 5 mA.

    You have now adjusted the controller to operate between 1 and 5 mA.

    NOTE: After adjusting the min and max output, the M115 valve position will show 20% or more,

    unless the controller has tripped or the STOP/RUN/START switch is in the STOP position.Simulation

    51. Switch to STOP and turn M115 power OFF for about 5 seconds.

    52. Set the SIM-CALIB switch to SIM.

    53. Turn speed setpoint pot CCW (0.0).

    54. Turn M115 power ON and switch to START momentarily (switch will revert back to

    RUN).

    55. If you have problems starting the TS110, increase the LOAD and LAG on the M115.

    Always turn M115 power OFF for about 5 seconds between starts to allow the residual

    power to dissipate.

    56. DT should read minimum governor speed.

    57. Increase speed setpoint CW to 5.0. The valve meter on the M115 should deflect upward

    (open). The DT should read approximately mid-range.

    58. Increase the load on the M115 and the valve should deflect further upward.

    You have now tested the TS110functionally, and it is ready to be configured to your application.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    53/77

    Chapter 7 - Installation 41

    October 2009 Rev. 5

    Chapter 7 - Installation

    7.1 Location & Mounting

    Tri-Sen controllers are high performance, high speed controllers designed for industrial applications.

    However, as with all equipment, good mounting and wiring practices must be used duringinstallation. Failure to follow these mounting and wiring guidelines will result in instability of

    control and/or intermittent shutdown of controlled equipment from random electrical noise.

    Of course, compromises may be necessary, but careful attention to these factors will result in a more

    successful installation.

    7.1.1 Choosing a Location for the TS110Controller

    The TS110is designed to be field mounted at the turbine. The location where the TS110is mounted

    in the field is a critical decision. Factors such as

    accessibility,

    lighting, and

    temperature

    affect the success of the installation.

    Other important factors include

    area classification,

    length of wiring and pneumatic tubing, and

    proximity to sources of electrical noise.

    7.1.2 Mounting

    Refer to the figure on the following page.

    Mount the TS110as close to the turbine as possible. Keep the output air line to theactuator short and direct.

    Consider the heat generated by the turbine or auxiliary equipment in the mounting area.The TS110will function in ambient temperatures up to 160F, but every effort should be

    made to place the unit in a reasonably cool area.

    Since the TS110controller usually is operated through the front panel, it should be

    mounted so that the operator can stand in front of the controller comfortably. The displayshould be at eye level; the most common installations are between 5 feet and 5 feet, 6

    inches high.

    The liquid crystal display is difficult to read in low light, so avoid dark areas; but do notmount the TS110controller in direct sunlight.

    The TS110controller should be mounted to rigid structures only that will not sway.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    54/77

    42 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Service access should also be considered. Assure that:

    the door can be fully opened;

    the unit will not be subjected to steam or dripping water or other liquids; and

    that locating the Tri-Sen controller in a given area will not be in violation of area

    classification.

    If any of these items is doubtful, consider another location.

    TS110-206

    Figure 14. Mounting Dimensions

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    55/77

    Chapter 7 - Installation 43

    October 2009 Rev. 5

    7.2 Field Wiring for Standard Installation

    The TS110System is shipped 90% pre-wired. The only field wiring required is for the magnetic

    pickups, and the remote speed setpoint, if used.

    Magnetic pickups and remote speed setpoint use shielded pairs of 16 - 18 AWG wires.

    Pickup #2 terminates on TB1-14 and TB1-15 with the shield on TB1-16.

    Pickup #1 terminates on TB1-17 and TB1-18 with the shield on TB1-19.

    The remote speed setpoint, if used, should be a 4 - 20 mA signal.The positive lead terminates on TB2-7; and

    the negative lead terminates on TB2-8 with

    the shield terminated on TB1-8.

    Connect TB1-8 to a suitable earth gound.

    This wiring configuration is shown in the figure on the following page.

    CONSULT THE FACTORY WHEN IN DOUBT ABOUT ANY INSTALLATION PROCEDURE.

    WARNING!

    Have qualified personnel verify all wiring and connections against

    appropriate drawings prior to energizing the equipment. Incorrect wiring

    and/or connections can result in equipment damage.

    CAUTION!

    For installations in hazardous locations refer to the notes on the figures in this

    chapter.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    56/77

    44 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    2

    3

    1

    5

    6

    4

    8

    9

    7

    11

    12

    10

    14

    15

    13

    16

    18

    19

    17

    2

    3

    1

    5

    6

    4

    8

    9

    7

    11

    12

    10

    14

    15

    13

    16

    18

    19

    17

    TB1 TB2

    REMOTE SPEED SETPOINT4-20 mA (Optional)

    EARTH GROUND

    1

    RED

    BLACK

    RED

    BLACK

    MAGNETIC SPEED PICKUP #1

    MAGNETIC SPEED PICKUP #2

    2

    M100

    1

    2

    USE AN INTRINSIC SAFETY BARRIER APPROVED BY CSA OR FM TO MAINTAINAPPLICABLE SAFETY CERTIFICATIONS.

    DO NOT USE IN HAZARDOUS AREA. TS110-11

    Figure 15. Standard Field Wiring

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    57/77

    Chapter 7 - Installation 45

    October 2009 Rev. 5

    M100 Termination Board Wiring Details

    Refer to the table below and the figure on the following page for details concerning field wiring

    terminations on the M100 terminal strips.

    Terminal Description

    TB1:1,2 RUN SWITCH - Closed to run; open to stop. Opening this switch removes all electricalcurrent to the I/P.

    TB1:3,4 PICKUPS OK - An LED connected across these terminals as shown will flash periodically

    when both magnetic pickups are functioning.

    TB1:5-7 LOCAL SET - A 10-turn, 100k-ohm potentiometer installed across these terminals provides

    the Local Setpoint.

    TB1:8 GROUND - For terminating the shield around the Remote Potentiometer Setpoint wiring.

    TB1:9-11 RMT SET - A 10-turn, 100k-ohm potentiometer installed across these terminals provides the

    Remote Potentiometer Setpoint. A shielded, three-wire cable should be used to connect the

    potentiometer, with the shield connected only to TB1:8. (Do not terminate other end of

    shield.)

    TB1:12,13 I/P - 0-5 mA output signal from the M100 to the Current-to-Pneumatic converter

    TB1:14-19 PICKUP 2 and PICKUP 1 - Connection for the two magnetic pickups. Each set of wires

    should be individually shielded, twisted pair, with the shields connected ONLY to

    TB1:16/TB1:19. (Do not connect shield at other end.)

    TB2:1,2 O/S ALM - Alarm output indicating an over speed condition has occurred. The output is an

    SCR that remains latched on, even after M100 is powered down as long as external loop

    current flows.

    TB2:3,4 OVERSPEED TEST - Open: raises electronic overspeed trip approximately 20% and

    increases governor range an adjustable amount. This is used to check external mechanical

    overspeed trip.

    TB2:5,6 OVERSPEED RST - a normally open switch is placed across these terminals to reset the

    governor after an electronic overspeed.

    TB2:7,8 REMOTE SETPNT - Input from remote 4-20 mA setpoint signal.

    TB2:9-11 TACHOMETER - A 50 A current meter connected across terminals 9 and 10 indicates

    analog speed. A digital tachometer (frequency counter) is connected across terminals 10 and

    11. The digital tachometer signal is sufficient to drive most self-powered tachometers.

    TB2:12,13 EXT PWR - External power input to M100 for test purposes only. Voltage must be 9-12 volts.

    When jumper W9 is in place, 5 V/4 mA is available at these terminals for tripping a solid state

    relay. See paragraph 7.3.2.

    TB2:14,13 RMT STRT - Remote start input; applying 5 V to these terminals on an unpowered TS110will cause a current to flow out of the I/P terminal (TB1:12). Once the unit is powered and

    controlling, the Remote Start signal is disabled internally. The Remote Start signal must be

    interrupted externally to restart a unit that has been powered down. This input is designed towork with the SPEED SWITCH output of another TS110.

    TB2:15-17 MAX OUTPUT - A 200k-ohm potentiometer connected across these terminals allows the

    maximum output limit to be set externally. To use these terminals, R82 on the M100 board

    must be removed.

    TB2:18,19 UNDERSPEED SWITCH - Output goes to 5 V when speed drops below the speed switch

    setpoint. This is a low-current signal designed to start a second TS110(see RMT STRTabove) in the event the first one drops below a specified speed.

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    58/77

    46 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    3

    2

    4

    2

    1 2 2

    1

    2

    3

    4

    USED FOR BENCH TEST ONLY.

    TO MAINTAIN APPLICABLE SAFETY CERTIFICATIONS,USE CSA OR FM APPROVED BARRIER SUCH AS MTLPIN 787S, 28V MAX 300 OHMS.

    DO NOT USE BATTERY IN HAZARDOUS AREAS.

    DO NOT USE EXTERNAL TACH IN HAZARDOUS AREAS.

    TS110-205

    AUXILIARYTERMINAL STRIP

    Figure 16. Field Wiring Detail

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    59/77

    Chapter 7 - Installation 47

    October 2009 Rev. 5

    7.3 Field Wiring for Optional Configurations

    7.3.1 Remote STOP/RUN/START Switch

    A switch (Tri-Sen P/N 91-1482) can be wired to the RMT START and RMT RUN terminals on the

    auxiliary terminal strip to remotely start and stop the turbine.

    Also refer to the figure on the previous page.

    Remote Start using a Second TS110To start a backup turbine, controlled by a TS110, when the primary turbine falls below a

    preset speed, connect the two TS110sand an underspeed switch as shown in the figure

    below.

    M100M100

    19

    18

    17

    16

    1514

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1TB2TB1

    19

    18

    17

    16

    1514

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    19

    18

    17

    16

    1514

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    19

    18

    17

    16

    1514

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    1

    SPARE BAT

    + -

    RMTSTART

    RMTRUN

    THIS TERMINAL STRIP IS

    LOCATED INSIDE THE TS110,

    BELOW THE M100 TERMINAL

    STRIPS.

    11

    2

    2DO NOT USE IN A HAZARDOUS

    AREA.

    3THE 9-VOLT BATTERY OPTION

    CANNOT BE USED WITH THISAPPLICATION.

    TS110 ON PRIMARY TURBINE TS110 ON BACKUP TURBINE

    TS110-12

    TB2TB1

    Figure 17. Field Wiring for Remote Start of a Backup Turbine Using a Second TS110

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    60/77

    48 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    Remote StopUsing remote setpoint, 4-20 mA signal, normally open or normally closed switch.

    1

    6

    8

    9

    7

    19

    1

    6

    8

    9

    7

    19

    TB1 TB2

    N.O. SWITCH

    4-20 mA LOOP

    M100

    1USE AN INTRINSIC SAFETY BARRIER APPROVED BY CSA OR

    FM TO MAINTAIN APPLICABLE SAFETY CERTIFICATIONS.

    1

    1

    6

    8

    9

    7

    19

    1

    6

    8

    9

    7

    19

    TB1 TB2

    N.O. SWITCH

    4-20 mA LOOP

    M100

    1

    - OR -

    TS110-13

    Figure 18. Field Wiring for Remote Stop

    Using 4-20 mA Signal with N.O. or N.C. Switch

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    61/77

    Chapter 7 - Installation 49

    October 2009 Rev. 5

    7.3.2 Overspeed Trip Relay

    An optional Solid State Relay (Tri-Sen P/N 7015-0000) can be used to trip the machine in an

    overspeed condition by operating the dump solenoid, or by unlatching the trip lever. Refer to the

    figure below. For more information, refer to Section 8, Operations, of this manual.

    2

    3

    1

    5

    6

    4

    8

    9

    7

    11

    12

    10

    14

    15

    13

    16

    18

    19

    17

    2

    3

    1

    5

    6

    4

    8

    9

    7

    11

    12

    10

    14

    15

    13

    16

    18

    19

    17

    TB1 TB2

    1

    M100

    1

    2

    USE AN INTRINSIC SAFETYBARRIER APPROVED BY CSA ORFM TO MAINTAIN APPLICABLESAFETY CERTIFICATIONS.

    JUMPER W9 MUST BEINSTALLED.

    SOLID STATE

    RELAY(TRICONEX

    PN 7015-0000)

    + -

    SOLENOID

    AC LINE

    1

    TS110-14

    Figure 19. Field Wiring for Overspeed Trip Relay

  • 8/13/2019 TS110 Self-Powered Controller Operations Guide Rev. 5

    62/77

    50 TRISEN 110Self-Powered Controller Operations Guide

    October 2009 Rev. 5

    7.4 Pneumatic Installation

    7.4.1 Piping

    Recommended supply piping for the I/P supply air is at least 3/8". The recommended piping for the

    connection from the Governor I/P output to the final actuator is 1/4". A 0-30 PSIG gauge should be

    installed on the governor I/P output to aid in troubleshooting and tuning. This connection should bekept as short as possible for the fastest response of the control valve. Though copper tubing is

    adequate, stainless steel is recommended.

    7.4.2 Optional Pneumatic Speed Setpoint

    This is a 3-15 PSIG signal that can be used to remotely set the running speed of the governor when

    the optional Pneumatic Transducer (Tri-Sen P/N 91-1455) is used. This line can be 1/4" tubing.

    7.4.3 Final Actuator

    Two types of pneumatic actuators can be used